HomeMy WebLinkAbout6269 EL FUERTE ST; ; FPC2020-0049; PermitC7city of
Carlsbad
I O1
Print Date: 12/03/2020 Permit No: FPC2020-0049
Job Address: 6269 EL FUERTE ST, CARLSBAD, CA 92009-3094 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Underground Fire
Parcel #: 2131221800 Track #: Applied: 03/19/2020
Valuation: $1,984,662.45 Lot #: Issued: 04/20/2020
Occupancy Group: Project #: DEV06040 Finaled Close Out: 12/03/2020
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check#: Final Inspection:
Project Title: PACIFIC RIDGE SCHOOL
Description: PACIFIC RIDGE SCHOOL - REVISED PLANS FOR UNDERGROUND PLANS FOR NEW BLDG
Applicant:
SWS ENGINEERING INC
261 AUTUMN DR, #115
SAN MARCOS, CA 92069-2878
(760) 744-0011
FEE AMOUNT
FIRE Plan Review Per Hour - Office Hours $204.00
FIRE Underground Piping with up to 4 Hyds/Risers $756.00
Total Fees: $960.00 Total Payments To Date: $960.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 760-602-4665 760-602-8561 f I www.carlsbadca.gov
p,L CA
4'IFO
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION k TO BE COMPLETED BY CUSTOMER
PROJECT NAME: Pacific Ridge Multi Discipline SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: 6269 El Fuerte Dr CITY: Carlsbad
PHONE: (760) 310-6122 FAX NUMBER: (760) 798-0556
Largest Building (ft.2): 15.555 sf Sprinkled? yes Construction Type: Il-B
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): El Fuerte St between Palomar Airport Rd and Poinsettia Lane
Flow Test Results
Static pressure: 132 PSI Hydrant Number (if applicable): H62104
Elevation of test: 244 Feet Main Size: 8 INCH
Pressure Zone: 550 Feet pate/Timeof Test:1
Pitot Tube Reading: Corresponding Flow: GP
Total Flow: 2,800 GPM Residual Pressure114PSI
At peak demand , this water system is capable of providing a fire flow discharge at 20 psi of 7,625 gpm. However, this
exceeds the City's velocity criteria of 10 fps. Therefore, the maximum available fire flow that satisfies both the
pressure and velocity criteria is 2,800 gpm. Based on the maximum square footage and construction type, the
required fire flow is 2,750 gpm.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here:
Name: JenniferR.Mael.P.E. Eng. Lic. No. (if applicable): C69606
Signature: _ la -
Title/Org:pp6I ' Mana 1 Date: 01/24/2020
RD
Project Site
Fire Flow Test
Location H62104
Legend
wHydrent
Pipe
ZONE
-375 N
-550
- 700
#127c Pacific Ridge Multi-Discipline (6269 El Fuerte Dr) - Fire Flow Analysis
12
INDICATOR POST STYLE 2945 A
KENNEDY VALVE TELESCOPING BARREL ASSEMBLY
UL AND FM APPROVED
KENNEDY VALVE
Available in Sizes B C D E
See Page 6 for Dimensions
p-I
p-a
P-7
P-13 zz
/
P-I9 T
F-20 H _ P-21 3 EB
Updated 05/02/2012 rwuiieuy vauveiiiiuiiaiur ros it - i
max. = 10"
mm. = 7"
ENT
top of the
rows and
of 9U
jets for the
op of the
//-
1 1/4" Sq.
All -
11-4 ruIIIUy VaIVIIIIUIL.ØLUI JDL
INDICATOR POST STYLE 2945
FIXED LENGTH ASSEMBLY
UL AND FM APPROVED
KENNEDY VALVE
Available in Sizes F G H
See Page 6 for Dimensions
P-2 P-I
P3
a
/
0
SI-U
00
NT
00
P-23 oo
00
P-I2
-::3 P-22 P-I4
P-18
P-19
IF
upaaiea ubtuzlzulz Kennedy Valve/Indicator Posts 17-3
1 1/4" Sq.
Top Section
- Standpipe
(painted red)
Ground Line
- Standpipe
(painted black)
max. = 10"
mm. = 7"
FIELD ADJUSTMENT
INSTRUCTIONS
Trench
Depth
Remove the top section from the top of the
Indicator Post assembly.
Cut the required length off the bottom of the
Standpipe for the Ground Line to match up
with Standpipe Ground Line mark.
Cut the 1 Sq. Stem at a distance of 9"
above the top of the Standpipe.
Set the "OPEN" and "SHUT" targets for the
appropriate valve size.
Reattach the Top Section to the top of the
Indicator Post assembly.
I riuiiuy VdIVIIIIUJLdLUt FUbLb
DET QTY. PART NO. DESCRIPTION MATERIAL
P-i 1 3361270 Locking Wrench Cast Iron ASTM A-126 CIB
P-2 1 3024872 (4-14) Operating Nut Bronze ASTM B584 Alloy 864
P-3 1 442639P Retainer 0-Ring #226 Buna N
P-4 1 3020913 Top Section Cast Iron ASTM A-126 CI.B
P-5 2 441980P Window Glass Lexan - UV Stabilized
P-6 2 443370P Open Target Cast Aluminum
P-7 2 443371P Shut Target Cast Aluminum
P-8 1 - Target Carrier Assem.
1 3005802 (4-14) Target Carrier Nut Bronze ASTM B584 Alloy 844
2 443347P Target Carrier Plate 1/16" Sheet Metal
4 440736P Clamp Target Retainer 16 Ga. 302 S.S.
8 444171P #10-24X1/2 " Pan Head Stainless Steel
4 442411P #10-24 Hex Nut Zinc Plated steel
P-9 1 443476P 'I? NPT Pipe Plug Mall. Iron
P-i 0 1 440254P 3/i" Eyebolt #23 Forged Steel
P-11A 1 444303P /e-i 6x1" Hex Capscrew (Adj. Post) Zinc Plated Steel
P-11F 2 444306P /8-16x1'/2" Hex Capscrew (Fixed Post) Zinc Plated Steel
P-12 1 ** Stem 1" Sq. AISl M1020 HAS
P-13 1 318035& Crane Coupling Cast Iron ASTM A-126 CI.B
P-14 1 442190P Cotter Pin Brass
P-15 2 444342P 3/4" Hex Hd. Screw Zinc Plated Steel
P-16 1 3004774 Telescoping Barrel Cast Iron ASTM A-126 CI.B
P-17 1 ** Lower Standpipe (Adjustable Post) 40 D.I. Cl 52 ANSI A21.51
P-18 1 3180402 (3-12) Base Flange Cast Iron ASTM A-126 CI.B
P-19 3 444355P 5/e"xl' Hex Hd. Screw Zinc Plated Steel
P-20 4 444357P -5/aux2l/40 Hex Capscrew Zinc Plated steel
P-21 4 442484P /e" Hex Nut Zinc Plated Steel
P-22 1 ** Standpipe Section (Fixed Post) 4" D.I. Cl 52 ANSI A21.51
P-23 1 3004762 Spacer Sleeve (Fixed Post) 5" D.I. Cl 52 ANSI A21.51
"Part numbers change based on post furnished.
ruIlIUy VdIVeIIIIUR.dLVt rUI 11-0
INDICATOR POST STYLE 2945A & 2945
TRENCH DEPTHS FOR GATE VALVES
UL & FM APPROVED
KENNEDY VALVE
RSGV (3" - 12") --- Maximum turns to open = 45
Note: For valves requiring more than 45 turns to open, contact Kennedy Valve
- - - , • - ,, -- - - - - -. Updated 05/02/2012
I I U ruuuIuy VaIVIIIIUII..LUI rUL
TELESCOPING BARREL 2945A
TRENCH DEPTH LIMITS
B Size C Size D Size E Size
Valve
Size Mm. Max. Mm. Max. Min. Max. Mm. Max.
4° 31' 51' 49" 69' 67' 87' 88' 111'
6° 35' 55' 53 73- 71' 91' 92' 115'
8" 42' 62' 60" 80° 780 98' 99' 122'
10" 45' 65' 63" 83" 81' 101" 102" 125'
12" 49' 69 67" 87" 85' 105" 106° 129'
14'/16' 58' 78' 76" 96° 94' 114" 115° 138'
FIXED LENGTH POSTS 2945
MAXIMUM TRENCH DEPTH
Valve
Size
F Size G Size H Size
4' 45V2" 631/2' 871/2"
6' 491/2° 671/2' 911/2"
8' 541/2° 721/2' 961/2"
10" 59" 77' 101'
12° 64" 82' 106'
14° 69" 87' 111°
Installation - The valve should be opened to the fully open position before proceeding with the
Indicator Post installation.
1. Disassembly of the Indicator Post Unit
Telescoping Barrel Units
Remove the Top Section from the end of the barrel.
Loosen the two screws on the barrel and slide off the top of the standpipe.
Fixed Length Units
Remove the Top Section from the end of the standpipe.
2. Base Flange Installation:
Attach the base flange along with the standpipe to the valve plate using the four 5/8 bolts
and nuts provided.
3. Grade Line Adjustments:
Telescoping Barrel Units
Lower the barrel over the standpipe until the grade line mark on the barrel is at ground line
height and then tighten the two screws securely.
Fixed Length Units
Cut the required length off the bottom of the standpipe so that the indicated grade line of
the standpipe is at the ground line height and then secure to the base flange by tightening
the two screws.
Extension Rod Adjustments:
Lower the stem into the barrel/standpipe, placing the crane coupling over the valve operating nut.
It is necessary that the stem engage the operating nut a minimum of 2 inches, but not more than
5 inches.
To check for correct engagement, the end of the stem should be from 7 inches to 10 inches above
the top of the standpipe (Fixed Length Units) or the top of the telescoping barrel.
Target (Open and Shut) Adjustments
Remove the target assembly from inside the body by rotating the operating nut counterclockwise.
Loosen the target retainer screws, but do not remove them.
rwuiieuy vaiveiinuuiawr r05t5 1 (-I
INDICATOR POST
MODEL 2945A AND 2945 UL/FM
INSTALLATION INSTRUCTIONS
KENNEDY VALVE
5. Cont'd
Open Left Valves
Move the OPEN target to the top of the plate.
Note: Position of the SHUT target can be determined by the following chart:
Valve
Size 4" 6" 8" ion 120 14"
Gate
Valve "A" 1" 13/811 113/16" 23/1en 2/e 3"
RW
Valve "A" 7k" 1/1e" 1"/1e" 21/s" 21/2" See Note (1)
Position the SHUT target as indicated below and tighten the retainer screws until snug. Avoid over tightening.
Repeat the procedure for the other side.
Note (1): Resilient Seat Gate Valves 14' and larger, require special target
mechanism threads. Contact Kennedy Valve Engineering
Valve size target location markings
OPEN
Adjustment of target:
Grasp target at midpoint & pull
out slightly. SHUT
Slide up or down to desired
-- - location & then release grip.
Open Right Valves
The procedure is similar as for open left, but with two differences:
The open target is placed below the shut target.
The open target is placed at the very bottom of the plate.
The position of the shut target above the open target is then determined and set as described above.
Maintenance
Lubrication
Lubricate upper bearing area at least once per year, by applying several drops of light machine oil or food grade
grease to the areas where the Operating Nut (P-2) contacts the Top Section (P-4).
Access to this area is gained by removing the Locking Wrench (P-i) and lifting upward on the Operating Nut (P-2).
Operation
The target mechanism will travel off the threads of the operating nut in both directions should the targets or
target mechanism be positioned incorrectly. Should this happen, readjust targets. If the target mechanism falls
from the operating nut, it will be stopped a short distance below the window.
Updated 05/02/2012 17-8 Kennedy Valve/Indicator Posts
2945 (A) Vertical Indicator Post - Changing the Lower Standpipe
Loosen (2) 3/4" - UNC Bolts (Items P-15) that retain the Telescoping Barrel (Item P-16)
to the lower Standpipe (Item P-17)
Working in a safe manner lift off the entire top assembly (Items P-i through P-16)
from the Telescoping Barrel and Base Flange
Remove the Stem (Item P-12) and Crane Coupling (Item P-13) sub-assembly
Loosen the 3/4" -UNC Bolts 19) that retain the Lower Standpipe to the Base Flange
Remove the existing Lower Standpipe and set the new one into the socket in the Base Flange.
Securely tighten the bolts that were loosened in Step 4 (50 to 100 ft.-lb)
Working safely, slide the entire top assembly over the new Lower Standpipe
Tighten the (2) 3/4" - UNC Bolts that retain the Telescoping Barrel to the Lower Standpipe
(Item P-15) - Tighten them securely enough to safely maneuver the Post in the field
Remove the Wrench (Item P- 1), the 3/8" - UNC Bolt (Item hA) and the Eyebolt (Item P- 10)
Lift the assembly of the Top Section (Item P4), Operating Nut (Item P-2), Target Carrier Assembly
Items P-6 through P-8), etc. from the Telescoping Barrel.
If a longer Lower Standpipe has been installed it will be necessary to procure a longer Stem.
Slip the Crane Coupling (Item P-13) over one end of the new Stem and cross drill a new,
cotter pin hole through the new Stem
If the Lower Standpipe just installed is shorter than the one it replaced the Stem will have to be cut
Bolt the Base Flange of the sub-assembly that includes the Base Flange, Lower Standpipe and
Telescoping Barrel to the flange of the valve, using the 3/4" - UNC Bolts & Nuts provided
by Kennedy Valve
Place the square socket in the Crane Coupling on the Stem & Coupling sub-assembly over the
2" Square Nut at the top of the stem of the valve
See page 17-4 of the Kennedy Valve Product Catalog and follow the directions.
NOTE: Kennedy Valve does offer for sale Couplings to extend Stems
Updated 05/02)2012 Kennedy Valve/Indicator Posts 17-9
INSTRUCTIONS FOR EXTENDING A 2945A POST
Loosen the two 3/4" screws on top pipe section (near grade line at bottom of pipe). Pull
apart the upper section from the lower pipe section. Place new extension coupling with new
extension pipe over the existing lower pipe section. Tighten screws provided on the exten-
sion pipe and lower pipe (3/4" X 1" square head screw). Take existing stem and place the
new extension stem with coupling on top of original stem. Drill through stem and coupling
(pilot holes provided on one side) then pin together with pins provided (1/4" X 3" br. cotter
keys). Place stem down the inside of new extension and lower pipe assembly aligning it on
the 2" square nut on valve. At this time, remove top section (with operating nut assembly)
from off the top of indicator post standpipe (two bolts). Place complete upper section over
top of stem and align with the new extension pipe. Push together, adjust to desired height,
and retighten the two 3/4" screws in top pipe section. Stem should be cut 7" - 10" above
the pipe. Adjust open/shut plates per instructions and replace top section with stem nut (can
also be extended at bottom end).
NO DESCRIPTION
1 Ductile Pipe (as reqd)
2E Ktender Coupling
3 Set Screw 3/4 UNCX1 "Ig
4 L wer
5E Ktension Stem
6 Ext. Stem Coupling
7 E Kisting Stem
8 Cotter Pin
Updated 0510212012 17-10 Kennedy Valve/Indicator Posts
641 Wall Post
huE. 6 10 39 TURNS * Standard over-all stem length = 34.63
- NO. ITEM OTY MATL SPEC REMARKS PART NO.
WP-1 Eye Bolt 1/2-UNC 2' LG 1_ Sti ½-UNC 440253P
WP-2 Nut 1I2-UNC Plated 1_ Sti Eye Bolt 477495P
WP-3 Washer 5/ 0 Plated 1_ StI 445834P
WP-4 Handwheel-14' Dia. 1 Cl 3360152
WP-5 Cover 1 Cl A126-B 3180283
WP-6 Ret. Ring #5100-225 _1 - Stl Zinc Plate 443599P
WP-7 Oper. Stem Nut 1 BR AWWA 'A' 3180165
WP-8 Nuts 1/2-UNC Plated _2_ RP Stl Heavy Hex 442482P
WP-9 Bolt 1h-UNC x 2' 1 RP Sti A304 Hex Drilled-1 End 444419P
WP-10 Bolt l/2-LJNCxi.75' 1 RPStl A304 Hex 444348P
WP-11 Top Sect. 1 Cl A126-B 3180204
WP-12 Target Nut 1 Br AWWA 'A' 3180172
WP-13 Windows - Flat 2 Plastic 441982P
WP-14 Screws I40I4 Self Tap 4 444435P
WP-15 Ferrule 2 StI 441587P
WP-17A Target Plate (Open) 2 Alum 443348P
WP-178 Target Plate (Shut) 2 Alum 443350P
WP-18 Clamps - Plated 4 Sti 440734P
WP-19 Nuts 1/4-20 UNC 8 StI Sq. Hd. 442576P
WP-20 Mach Screw 1/4-20 x 7/8L6 8 Br Rd. Hd. 444432P
WP-21 Pipe Plug-1/2 NPT I Iron Socket Hd. 443476P
X WP-22123/24 S/A Stem lEa. 2180912
WP-22 Stem - (Std. Lg -32.5') 1_ StI 1' Square 445312L
WP-23 Cotter Pin 1/4 x 3 Lg 1 Br 442190P
WP-24 Crane Coupling 1_ Cl 318035&
WP-25 Adjustment Card I - Not Shown 440443P
WP-26 Marking Tag 1 Mylar UL Rated Mati
Fig. 551-angle Wall Post Kit, use with 641-13 wall post (Style "a" includes 2 — '18" stems)
(Style "B" includes 2 - 24 stems)
Fig. 551
angle
Post Kit
Wall
0
I CAST TOLERISCU J J I KENNEDY VALVE I 0' to 3' *A' I I __________________________________ aftmallftfaft— ..y. 14001
I 3to6•*.O4• I I I r to o.05' I I I WALL TYPE INDICATOR POST
TOP VIEW I 91012•*•tS I I ILLUSTRATION
I o.10
I 'rtoir.or
18'to24
I 24 to 3U * .1V I __________________ _______ I 0U.
i 30' to
36, * .12 II i.iwif mo. DO*VIO COMM o..o I, 005 XXXXX , I ANGLES 0.50 DES. NO I 5*151 005 0050500 00.0: US
D:E 10tAu
®. .....
--'7'
( i
t---------... -1•
'•-- .
1 '-----.-------' YEAH
IL
I Ir
2&.71 Wi T
-®-
I -----'
F
T"
4' 7HC1.
FIGURE 641-14 NON-RISING
STEM APPLICATION
FLANGED BASE POST INDICATOR
KENNEDY VALVE I
The Kennedy Flanged Base Indicator Post, Figure 641-14, is specially designed to be mounted on a valV
pit cover. This non-adjustable post can be supplied with couplings for non-rising stem valves.
PARTS LIST
NO. ITEM MATL ASTM
*1 WELDLESS EYE BOLT STL
*3 WASHER-PLATED STL Al 08 *4 HANDWHEEL-14' DIA CI A126B
5 COVER CI A126B
6 SNAP RINGS #5100-225
7 STEM NUT BR B-62
8 NUTS 1/2-UNC PLATED AP STL
9 BOLT 1/2-UNC X 2' AP STL A304B
10 BOLT 1/2-UNC X 1.75' AP STL A304B
11 TOP SECTION CI A126B
12 TARGET NUT BR B-62
13 WINDOWS PLAST
14 SCREWS-SELF TAP STL
15 FERRULE STL
16a TARGET PLATE (OPEN) ALUM
16b TARGET PLATE (SHUT) ALUM -
17 CLAMPS-PLATED STL
18 NUTS-SQUARE STL
19 MACH SCREW-AD HEAD BR
20 PIPE PLUG-1/2 NPT CI
21 4 in. D.I. PIPE DI
22 4 In. FLOOR FLANGE CI A126B
23 STEM 87' STANDARD STL
WRENCH MI A47
25 E26
24
CRANE COUPLING CI A126B
COTTER PIN BR B-16
*DENOTES OPTIONAL HANDWHEEL PARTS.
It-1A reflhiuy VdIVeIII1UII.dVF F'0515
Kennedy Valve
A DIVISION OF McWANE, INC.
www.kennedyvalve.com
2009
1021 E. Water Street • Elmira, New York 14901
P.O. Box 981
PHONE: (607) 734-2211 • FAX: 1-800-952-4771
Updated 05/02/2012 PUB_1<81V_909