HomeMy WebLinkAbout2141 PALOMAR AIRPORT RD; 160; AS130209; Permit12/28/2020 AS1 30209 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS130209
2141 PALOMAR
Job Address: Status: ISSUED
AIRPORT RD
Permit Type: SPRINK Applied 11/26/2013
Parcel No: 2130701600 Approved: 12/10/2013
Lot #: 0
Reference No.: Issued: 12/10/2013
PC #: Inspector:
Project Title: SPEC STE 160 TI: REMOVE EXISTING 1" LINES AND REPLACE
WITH NEW 1" LINES TO CENTER UPRIGHT PROTECTION W/IN
STRUCTURAL BAYS. SEE FLOOR PLAN FOR NEW SPRINKLER
LAYOUT.
Applicant: Owner:
REALTY ASSOCIATES FUND VII L P
C/O TA ASSOCIATES REALTY
1301 DOVE ST #860
NEWPORT BEACH CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
268 0 268 0
1/1
TE'DrZiecinc.
MATERIAL DATA SUBMITTAL
Spec Suite * 160
2141 Palomar Airport Road
Carlsbad, CA 92011
Page Product Description
1-2 Sprinkler Piping
3-10 Sprinkler Piping
11-12 Sprinkler Piping
13-19 Sprinkler
20 Pipe Hangers & Supports
21 Pipe Hangers & Supports
22 Pipe Hangers & Supports
23 Pipe Hangers & Supports
24-26 Pipe Hangers & Supports
ALLIED Dyna Thread Pipe
TYCO Ductile Iron Fittings
TYCO Mechanical Tee
TYCO TY-FRB Q.R. SSP & SSU
AFCON Fig 100 Beam Clamp
AFCON Fig 162 Retaining Strap
AFCON Fig 300 Ring
AFCON Fig 655 All Thread Rod
HILTI HDI Drop in Anchor
Total Fire Protection, Inc.
1611 A S. Melrose Dr. *244
Vista, Ca 92081
(760)525-4329 fax (877) 724-4329
C16-955387
tfpjohncgmail.com
A5130209
DynamThreade
S Full Line Sch-40 Replacement
Dyna-Thread offers the life expectancy of Sch40 with superior hydraulics and greater value.
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
S
Dyna-Thread's inside diameter is up
to 3.6% larger than Sch-40 giving it
superior hydraulics. And, when used
in combination with Dyna-Flow pipe,
down sizing often occurs.
Dyna-Thread is fully listed and
approved by UL, ULC, and FM for
fire sprinkler applications.
The life expectancy of Dyna-Thread
and Sch-40 are equal based on the
calculated wall thicknesses per UL.
The consistent quality of steel used to
make Dyna-Thread facilitates smooth
threading and lower maintenance
costs.
The exterior of Dyna-Thread is
protected by a clean, durable mill
coating for extended shelf life and
easy paint application.
(9 <S> 9
Listed Approved Listed
With its increased strength and lighter
weight, Dyna-Thread reduces
installation fatigue and is ideal for
retro-fit applications.
Corrosion Resistance Ratio (CRR) is a
UL (Underwriters Laboratory) term for
the estimated life expectancy of a pipe
joint. This is based on the calculated
wall thickness at the base of the first
exposed thread, assumed to be the
weakest point of the pipe length. Dyna-
Thread and Sch-40 have the same
calculated wall thicknesses at this point
and are both assigned the same CRR of
1.00.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF". In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of
Microbiologically Influenced corrosion
(MIC) when the First Sprinkler System
is first installed.
More wall thickness at the thread
(CRR 1.00) gives Dyna-Thread
better life expectancy than lightwall
threadable pipe joints.
Unlike lightwall threadable pipe,
Dyna-Thread has no thread gauge
warning.
Dyna-Thread is approved for
standard hanger spacing (15 ft.
O.C.), can be used as earthquake
sway bracing, and is safe to use as
drops.
Dyna-Thread is safer to weld on.
Dyna-Thread is more widely
accepted than lightwall threadable
where Sch-40 is specified.
Super 40fDyna-Thread pipe is
manufactured to meet: ASTM A-135,
Grade A and is in compliance with
NFPA- 13. All sizes of Super 40/Dyna-
Thread are rated at 300 psi working
pressure. Super 40/Dyna-Thread is UL
and ULC Listed for wet, dry deluge and
pre-action sprinkler systems and FM
Approved for use in wet systems. Super
40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all
roll-grooved, and plain-end fittings.
(See listing information).
Speci fications
NPS Nominal I.D. WI. WI. (1120 Filled) Pcs/ Wt/Lift (21') WVLifI (24') Wt/Lift (25')
In; mm In; mm Lbs/Ff;Kg/m Lbs/Ft;Kglm Lift Lbs;Kg Lbs;Kg Lbs;Kg
1" 1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 105
1W 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
1'!? 1.639 2.290 3.22 44 2115 2418 2519
40 41.6 3.4 4.79 44 959 1097 114
2 2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
16100 S. Lathrop • Harvey, IL 60426 tqca '/Flow Control died 11350 Norcom Rd. • Philadelphia, PA 19154
TUBE& CONDUIT 2525 N. 27th Ave. Phoenix, AZ 85009
Customer Service:
(800) 882-5543
Fax 708-339-1806
S3-3
Submittal Data Sheet
Dyna-Thread*
Full Line Sch-40 Replacement
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler
pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with
quality and superior hydraulic advantages.
Comparison to Schedule 40 Dyna-Threads inside diameter is up to 3.6% larger than
Sch-40 giving it superior hydraulics. Also, when used in combination with Dyna-Flow
pipe, down sizing often occurs. Dyna-Thread is fully listed and approved UL, ULC,
and FM for fire sprinkler applications. The life expectancy of Dyna-Thread and Sch-40
are equal based on the calculated wall thicknesses per UL. The consistent quality of
steel used to make Dyna-Thread facilitates smooth threading and lower maintenance
costs. The exterior of Dyna-Thread is protected by a clean, durable mill coating for
extended shelf life and easy paint application. With its increased strength and lighter
weight, Dyna-Thread reduces installation fatigue and is ideal for retro-fit applications.
Corrosion Resistance Ratio (CRR) is a UL (Underwriters Laboratory) term for the
estimated life expectancy of a pipe joint. This is based on the calculated wall thickness
at the base of the first exposed thread, assumed to be the weakest point of the pipe
length. Dyna-Thread and Sch-40 have the same calculated wall thicknesses at this
point and are both assigned the same CRR of 1.00.
Comparison to L.W.T. Pipe More wall thickness at the thread (CRR= 1.00) gives
Dyna-Thread better life expectancy than lightwall threadable pipe joints. Unlike
lightwall threadable pipe Dyna-Thread has no thread gauge warning. Dyna-Thread is
approved for standard hanger spacing (15 ft. O.C.), can be used as earthquake sway
bracing, and is safe to use as drops. Dyna-Thread is safer to weld on than many zinc-
coated lightwall threadable pipe products. Dyna-Thread is more widely accepted than
lightwall threadable where Sch-40 is specified.
Stamp Here
is Specifications & Approvals Super 40/
Dyna-Thread pipe is manufactured to
meet: ASTM A 135, Grade A and is in
compliance with NFPA-13. All sizes of
Super 40fDyna-Thread are rated at 300
psi working pressure. Super 40/ Dyna-
Thread is UL and ULC Listed for wet,
dry and pre-action sprinkler systems and
FM Approved for use in wet systems.
Super 40fDyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all roll-
grooved, and plain-end fittings. (See
listing information).
The internal surface of all black Fire
Sprinkler pipe up to 4.5000" in diameter
shall be coated with Allied Tube &
Conduit Antibacterial Formula "ABF".
Specifications
NPS Nominal I.D. WI. WI. (1120 Filled) Pcs/ WI/LIlt (21') WI/Lift (241 WI/tilt (25'
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs: Kg Lbs; Kg Lbs; Kg
1 1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 105
1W 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
11/2' 1.639 2.290 3.22 44 2115 2418 2519
40 41.6 3.4 4.79 44 959 1097 114
2' 2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
American Tube and Pipe was acquired by Allied Tube and Conduit on February 1,
1997. The engineered lightwall and standard wall family of products although they
have different names are the same in all respects with regard to strength, weight,
bundle count, listings and approvals. For example,
Dyna-Flow and Super Fin are the same product as (j) .> @are Dyna Thread and Super 40. XL is manufactured
with Exterior galvanized coating. BIT is
manufactured with Black lacquer coating. Listed Approved Listed
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments: 2
S3-4
S tqC0 Fire & Building
I)Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Pipe Fittings
NPT Threaded,
Ductile Iron
General
Description
The Tycoe Series 800 Threaded Pipe
Fittings and California Tees & Elbows
are manufactured from ductile iron.
They are stronger and more corrosion
resistant than cast iron fittings. The
additional strength is provided by the
ductile properties and by adding mag-
nesium while the iron is being poured
into the final cast shape. Although
lighter than standard cast iron, the fit-
tings have an added advantage of be-
ing less susceptible to cracking due to
their added strength.
The Series 800, California, and Figure
719 Threaded Pipe Fittings are a re-
designation for the Central Series 800,
California, and Figure 719 Threaded
Pipe Fittings.
WARNINGS
The Threaded Pipe Fittings described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Approvals:
UL Listed and FM Approved
Maximum Working Pressure:
Series 800 and California Fittings: 250 psi (17.2 bar)
Figure 719 Plug:
250 psi (17,2 bar)
Page 1 of 10
Material:
Series 800 and California Fittings:
Ductile Iron
Figure 719 Plug:
Cast Iron
Pipe Thread:
NPT per ANSI B1.20.1
Installation
Apply Teflont tape or high quality pipe
joint compound on male pipe threads
and tighten two to three turns beyond
hand tight.
NOTE
Installers who have not used ductile
iron threaded fittings should be in-
structed that the fittings are stron-
ger than the pipe and overtightening
the fitting can create leaks and cause
damage to pipe threads. In general,
there is about one-half turn difference
between cast iron and ductile iron fit-
tings. Apply Teflon tape or high qual-
ity pipe joint compound on the male
pipe threads and tighten two to three
turns beyond hand tight. If an auto-
matic make-on machine is being used,
please exercise caution in setting the
machine to the proper parameters pri-
or to tightening fittings onto the male
pipe threads.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
JANUARY, 2008
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP's sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties. ex-
oress or implied, including warranties
of merchantability and fitness for a
oarticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Please specify the
quantity, figure number, wall thickness,
and size.
registered trademark of E. I. du Pont de ('Tj"\ Nemours and Company or its affiliates.
TFP171"'1
Page 2of1O TFP1710
fl
Nominal Pipe Figure 813 Size
ANSI A Approx.
Inches Inches Weight Part
ON (mm) Lbs. Number
(kg)
1/2 1.13 0.22 86780 DN15 (28,7) (0,09)
3/4 1.31 0.33 86781 DN20 (33,3) (0,15)
1 1.50 0,48 86280 0N25 (38,1) (0,21)
1-1/4 1.75 0.73 88281 0N32 (44,5) (0,33)
1-1/2 1.94 0.93 86282 DN40 (49,3) (0,42)
2 2.25 1.55 86283 DN50 (57,1) (0,70) _______
2-1/2 2.69 2.70 T 86782 DN65 (68,3) (1,22)
0
L~.B
BT
A
FIGURE 811 FIGURE 813
900 ELBOW 450 ELBOW
TABLE 1
NOMINAL DIMENSIONS FIGURES 811 & 813
Figure 811
B Approx. A B
Inches Weight Part inches inches
(mm) Lbs. Number (mm) (mm) (kg)
0.56 0.24 86206 0.88 0.38
(14,2) (0,11) (22,4) (9,7)
0.75 0.40 86205 1.00 0.44
(19,0) (0,18) (25,4) (11,2)
0.81 0.64 86200 1.13 0.81
(20,6) (0,29) (28,7) (20,6)
1.06 0.95 86201 1.31 0.63 (26,9) (0,43) (33,3) (16,0)
1.19 1.24 86202 1.44 0.69 (302) (0,56) (36,6) (17,5)
1.50 1.74 86203 1.68 0.94
(38,1) (0,79) (42,7) (23,9)
1.56 3.28 86204 1.94 1.00
(39,6) (1,49) (49,3) (25,4)
TFPI7IO Page 3 of 10
62
FIGURE 812
90 REDUCING ELBOW
Nominal Pipe Figure 812 Size
ANSI A B C D Approx.
Weight Part Inches Inches Inches Inches Inches Lbs. ON (mm) (mm) (mm) (mm) Number
(kg)
3/4 x 1/2 1.19 1.19 0.63 0.63 0.33 86342 DN20x15 (30,2) (302) (16,0) (16,0) (0,15)
1 x112 1.25 1.38 0.56 0.81 0.44 86210 DN25 x 15 (31,8) (35,1) (14,2) (20,6) (0,20)
1 x3/4 1.38 1.44 0.69 0.88 0.53 86211 DN25 x 20 (35,1) (36,6) (17,5) (22,4) (0,24)
1-114x 1/2 1.31 1.50 0.63 0.94 0.64 86212 DN32 x 15 (33,3) (38,1) (16,0) (23,9) (0,29)
1-1/4x3/4 1.44 1.63 0.75 1.06 0.75 86213 DN32 x 20 (36,6) (41,4) (19,0) (26,9) (0,34)
1-1/4x1 1.56 1.68 0.88 1.00 0.77 86214 DN32 x 25 (39,6) (42,7) (22,4 (25,4) (0,35)
1-1/2x3/4 1.50 1.75 0.75 1.19 0.95 86221 0N40 x 20 (38,1) (44,4) (19,0) (30,2) (0,43)
1-1/2 x 1 1.63 1.81 0.88 1.13 0.99 86215 DN40x25 (41,4) (46,0) (22,4) (28,7) (0,45)
1-112x1-114 1.81 1.88 1.13 1.19 1.14 86216 DN40 x 32 (46,0) (47,8) (26,7) (30,2) (0,52)
2x314 1.63 1.94 0.88 1.38 1.39 86217 DN50x20 (41,4) (49,3) (22,4) (35,1) (0,63)
2x1 1.75 2.06 2.00 1.31 1.58 86218 DN50x25 (44,4) (523) (50,8) (33,3) (0,72)
2 x 1-1/2 2.00 2.19 1.25 1.44 1.67 86220 DN50x40 (50,8) (55,6) (31,8) (36,6) (0,76)
2-112x2 2.38 2.63 1.25 1.88 3.01 86262 DN65 x 50 (60,5) (66,8) (31,8) (47,8) (1,36)
TABLE 2
NOMINAL DIMENSIONS FIGURE 812
S
TFPI7I0 Page 5of 10
S
N"N t
FIGURE 814 FIGURE 818
IRON TEE STRAIGHT COUPLING
TABLE 4
NOMINAL DIMENSIONS FIGURES 814 & 818
Figure 814 Figure 818
B Approx. A B
Inches Weight
Lbs.
Part
Number Inches Inches
(mm) (kg)
(mm) (mm)
0.56 0.33 86340 1.38 0.31
(14,2) (0,15) (35,1) (7,9)
0.75 0.50 86341 1.63 0.56
(19,0) (0,23) (41,4) (14,0)
0.81 0.85 86230 1.75 0.38
(20,6) (0,38) (44,4) (9,7)
1.06 1.30 86231 2.00 0.56
(26,9) (0,59)(50,8) (14,0)
1.19 1.63 86232 2.19 0.75
(30,2) (0,74) (5516) (19,0)
1.50 2.63 86233 2.63 1.13
(38,1) (1,19) (66,8) (28,7)
1.56 4.55 86234 3.00 0.75
(39,6) (206) (76,2) (19,0)
Nominal Pipe
Size
A Approx.
ANSI Inches
ON Inches Weight
Lbs.
Part
Number (mm) (kg)
1/2 1.13 0.18 72779 DN15 (28,7) (0,08)
3/4 1.31 0.26 72778 DN20 (33,3) (0,11)
1 1.50 0.44 72755 DN25 (38,1) (0,20)
1-1/4 1.75 0.54 72754 DN32 (44,4) (0,24)
1-1/2 1.94 0.71 72753 DN40 (49,3) (0,32)
2 2.25 1.15 72752 DN50 (57,1) (0,52)
2-1/2 2.69 2.29 72758 DN65 (68,3) (1,04)
0
TFPI7I0 Page 6of 10
0
Page 7 of 10 TFPI7IO
FIGURE 815
REDUCING TEE
Nominal Pipe Size Figure 815
A B C D E F Approx.
ANSI Inches Inches Inches Inches Inches Inches Inches Weight Part
DN (mm) (mm) (mm) (mm) (mm) (mm) Lbs. Number
(kg)
1-1/2x1-1/4x112 1.44 1.31 1.69 0.69 0.63 1.13 1.03
DN40x32x15 (36,6) (33,3) (42,9) (17,5) (16,0) (28,7) (0,47) 86257
1-1/2x1-1/4x3/4 1.50 1.44 1.75 0.75 0.75 1.19 1.10
DN40x32x20 (38,1) (36.6) (44,5) (190) (19,0) (30,1) (050)
86258
1-1/2x 1-114x 1 1.63 1.56 1.81 0.88 0.88 1.13 1.31
DN40x32x25 (41.4) (39,7) (46,0) (22,4) (22,4) (28.7) (0,59) 86259
1-112x1-114x2 2.19 2.13 2.00 1.44 1.44 1.25 1.94
DN40x32x50 (55,6) (54,1) (50,8) (36,6) (36,6) (57,1) (0,88) 86260
1-112x1-1/2x1/2 1.44 1.44 1.69 0.69 0.69 1.13 1.14
DN40x40x15 (36.6) (36,6) (42,9) (17.5) (17,5) (28.7) (0,52) 86261
1-112 x 1-1/2 x 3/4 1.50 1.50 1.75 0.75 0.75 1.19 1.23
DN40x40x20 (38,1) (38,1) (44,4) (19,0) (19.0) (30,1) (0,56) 86262
1-1/2x1-1/2x1 1.63 1.63 1.81 0.88 0.88 1.13 1.38
DN40x40x25 (41,2) (41,2) (46.0) (22,4) (22,4) (28,7) (0,62) 86263
1-112x1-1/2x1-114 1.81 1.81 1.88 1.06 1.06 1.19 1.50
DN40x40x32 (46,0) (46,0) (47,6) (27,0) (27,0) (30,1) (0,68) 86264
1-112x1-1/2x2 2.19 2.19 2.00 1.44 1.44 1.25 2.00
DN40 x 40 x 50 (55,5) (55,5) (50,8) (36,6) (36,6) (31,7) (0,91)
86265
2 x 1 x 2 2.25 2.00 2.25 1.50 1.31 1.50 2.18
0N50 x 25 x 50 (57,2) (50,8) (57,2) (38,1) (33,3) (38,1) (0,99) 86266
2x1-1/4x2 2.25 2.13 2.25 1.50 1.44 1.50 2.31
DN50x32x50 (57,2) (54,1) (57,2) (38,1) (36,6) (38,1) (1,05) 86267
2x1-1/2x1/2 1.50 1.44 1.88 0.75 0.69 1.31 1.50
DN50x40x15 (38,1) (36,6) (47,8) (19.0) (17,5) (33,3) (0,68) 86268
2x1-1/2x314 1.63 1.50 1.94 0.88 0.75 1.38 1.61
DN50x40x20 (41,4) (38,1) (49,3) (22.4) (19,0) (35,0) (0,73)
86269
2x1-1/2x1 1.75 1.63 2.00 1.00 0.88 1.31 1.65
DN50x40x25 (44,5) (41,4) (50,8) (25.4) (22,4) (33,3) (0,75) 86270
2x1-1/2x1-1/2 2.06 1.94 2.19 1.31 1.19 1.44 2.03
DN50 x 40 x 40 (52.4) (49,2) (55,5) (33,3) (30,2) (36,6) (0,92) 86272
2x1-1/2x2 2.25 2.19 2.50 1.50 1.44 1.50 2.37
DN50 x 40 x 50 (57,1) (55,5) (63.5) (38,1) (36,6) (38,1) (1.07) 86273
2x2x1/2 1.50 1.50 1.88 0.75 0.75 1.31 1.50
DN50x50x15 (38,1) (38,1) (47,8) (19,0) (19,0) (33,3) (0,68) 86222
2x2x3/4 1.63 1.63 1.94 0.88 0.88 1.38 1.67
DN50x50x20 (41,4) (41,4) 1 (49.3) (22,4) (22,4) (35,0) (0,76) 86223
2x2x1 1.75 1.75 2.00 1.00 1.00 1.31 1.91
DNSO x 50 x 25 (44,5) (44,5) (50.8) (25,4) (25,4) (33,3) (0,86) 86224
2x2x1-114 1,88 1.88 2.13 1.13 1.13 1.44 2.05
DNSO x 50 x 32 (47,8) (47,8) (54.1) (28.7) (28.7) (36,6) (0,93)
86225
2x2x1-1/2 2.00 2.00 2.19 1.25 1.25 1.50 2.11
DN50x50x40 (50.8) (50,8) (55,6) (31,8) (31,8) (38,1) (0,95)
86226
2x2x2-112 2.63 2.38 1.Th 1.88 1.44 3.67
DN50 x 50 x 65 (66,8) (60,5) (44,5) (47,8) (36,6) (1,66) 86227
2-1/2x2x314
E44
1.63 2.31 0.63 0.88 1.75 2.22
DN65 x 50 x 20 (41,4) (58,7) (15.9) (22,4) (44,5) (1,01)
86274
TABLE 5(2 0F2)
NOMINAL DIMENSIONS FIGURE 815
S
Page 8 of 10 TFPI7IO
I!A!I1
ii a I irniui
FIGURE 820 FIGURE 830 FIGURE 719
CAP BRASS SEAT UNION PLUG
Nominal Pipe Figure 820 Figure 830 Figure 719 Size
ANSI A Approx. A B Approx. A Approx.
Inches Inches Weight Part Inches Inches Weight Part Inches Weight Part
DN (mm)
Lbs. Number (mm) (mm) Lbs. Number (mm) Lbs. Number
(kg) (kg) (kg)
1/2 088 0.15 72776 1.88 0.81 0.47 86207 0.94 0.10 86292 DN15 (22,4) (0,06) (47,8) (20,6) (0,21) (23,9) (0,04)
3/4 1.00 0.22 72777 2.00 0.94 0.66 86275 1.13 0.18 86293 0N20 (25,4) (0,10) (50,8) (23,9) (0,30) (28,7) (0,08)
1 1.18 0.33 72824 2.19 0.81 1.08 86276 1.25 0.28 86294 0N25 (30,0) (0,15) (55,6) (20,6) (0,49) (31,7) (0,13)
1-1/4 1.31 0.54 72756 2.50 1.06 1.54 86277 1.38 0.50 86295 lN32 (33,3) (0,24) (63,5) (26,9) (0,70) (35,1) (0,23)
1-1/2 1.38 0.68 72822 2.63 1.19 2.03 86278 1.44 0.70 86296 DN40 (35,1) (0,31) (66,8) (30,2) (0,92) (36,6) (0,32)
2 1.50 0.96 72823 3.13 1.63 3.15 86279 1.50 0.90 86297 0N50 (38,1) (0,43) (79,5) (41,4) (1,43) (38,1) (0141)
2-1/2 1.75 1.80 72825 - - - - - - - 0N65 (44,5) (0,82)
TABLE 6
NOMINAL DIMENSIONS FIGURES 820,830 & 719
9
TFPI7IO Page 9 of 10
r-----'_ii
FIGURE 825 FIGURE 827 FIGURE 816
EXTENSION PIECE HEX BUSHING REDUCING COUPLING
Nominal Pipe Figure 825 Figure 827 Figure 816
Size Extension Piece Hex Bushing Reducing Coupling
A Approx. A Approx. A B Approx.
ANSI Inches Inches Weight Part Inches Weight Part Inches Inches Weight Part
DN
(mm)
Lbs. Number (mm) Lbs. Number (mm) (mm) Lbs. Number
(kg) (kg) (kg)
1/2x1/2 1.50 0.20
72751 - - - - - - - 0N15 x 15 (38,1) (0,09)
1/2 x 1/2 2.00 0.27 72980 - - - - - - - DN15 x 15 (50,8) (0,12)
3/4 x 3/4 1.50 0.22 72981 - - - - - - - DN20 x 20 (38,1) (0,10)
3/4 x 3/4 2.00 0.31 73982 - - - - - - - DN20 x 20 (50,8) (0,14)
3/4 x 1/2 1.75 0.69 0.38 86772 DN20 x 15 - - - - (43,2) (17,5) (0,17)
1 x 1/2 1.06 0.22 72726 1.69 0.50 0.38 86228 0N25 x 15 - - - (26,9) (0,10) (42,9) (12,7) (0,17)
1 x3/4 1.06 0.18 72762 1.75 0.50 0.53 86229 0N25 x 20 - (26,9) (0,08) (43.2) (12,7) (0,24)
1-1/4x1 1.19 0.31
DN32x25 - - - (30,2) (0,14)
1-1/2x1 1.25 0.53 72757 - - - - DN40 x 25 - - (31,7) (0,24)
1-1/2x1-1/4 1.25 0.35 72764 - - - DN40 x 32 - - - (31,7) (0,10)
2x1 1.38 0.75 72759 - - - - DN50x25 - - - (35,1) (0,34)
2x1-1/4 1.38 0.69 72761 - - - - DN50 x 32 - - - (35,1) (0,31)
2 x 1-1/2 1.38 0.62 72775 - - - - 0N50 x 40 - - (35,1) (0,28)
TABLE 7
NOMINAL DIMENSIONS FIGURE 825, 827 & 816
0
tqZa Fire & Building
IlProducts
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
www.tyco-fire.com
Grinnell Grooved Fire Protection Products
Figure 40-5
Strap
[I:
General
Description
& UL b See Fire Protection
Submittal Sheet for FM Pressure Rating and
Listing/Approval Information
The Figure40-5 Strap is an economical alternative
to welded pipe outlets on steel pipe.
The Figure 40-5 Strap may be used with full
lengths of pipe and eliminates threading and
welding, decreasing waste and installation time.
The 40-5 Strap may be used in wet, dry pipe and
deluge systems.
WARifiNG
The Figure 40-5 Strap described herein must be
installed and maintained in compliance with this
document as well as with theapplicablestandards
of the National Fire Protection Association, in
addition to the standards otanyotherauthorities
ha ving jurisdiction. Failure to do so mayimpair
the performance of this device.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contractor or
sprinkler manufacturer should be contacted with
any questions.
Technical fFft Data
Figure: 40-5
Outlet: Threaded
Approvals: UL, FM, ULC, and VdS;
See Fire Protection Submittal Sheet for exact
Listing / Approval information.
Page 1 of 2
Housing: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Protective Coatings:
Clear rust inhibitive coating
Zinc electroplated conforming to
ASTM 8-633, Type Ill Service 2 (optional)
U-Bolt: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Nuts: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Gasket: (specify when ordering)
Grade 'E" EPOM green color code.
(See Data Sheet 1FP1895 for aid in selecting
proper gasket)
When placing an order, indicate the full product
name. Please specifythe quantity, figure number,
type of gasket, Grade "E" EPDM, and size.
Grinnell Grooved Piping Products, valves,
accessories and other products are available
throughoutthe U.S., Canada, and internationally,
through a network of distribution centers. You
may write directly or call 215-362-0700 for the
distributor nearest you.
Care and
Maintenance
The owner is responsible for the inspection,
testing, and maintenance of their lire protection
system and devices in accordance with the
applicable standards of the National Fire Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractor or product manufacturer
should be contacted relative to any questions.
Any impairment must be immediately corrected.
It is recommended that automatic sprinkler
systems be Inspected, tested, and maintained by
a qualified Inspection Service.
September 2004
Limited
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10)
years against defects in material and workmanship
when paid for and property installed and maintained
under normal use and service. This warranty will
expire ten (10) years from date of shipment byTyco
Fire Products. No warranty is given for products or
components manufactured by companies not
affiliated by ownershipwith Tyco Fire Products orfor
products and components which have been subject
to misuse, improperinstallation, corrosion, orwhich
have not been installed, maintained, modified or
repaired in accordance with applicable Standards of
the National Fire Protection Association (NFPA),
and/or the standards of any ottierAuthorities Having
Jurisdiction. Materials found byTyco Fire Products
to be defective shall be either repaired or replaced, at
Tyco Fire Products' sole option. Tyco Fire Products
neither assumes, nor authorizes any person to
assumeforit,anyotherobligationinconnectionwith
the sale of products or parts of products. Tyco Fire
Productsshallnotberesponsibleforsprinklersystem
designerrorsorinaccurateorincompleteinformation
supplied by Buyer or Buyers representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL THEORY, FOR
INCIDENTAL, INDIRECT, SPECIAL OR
CONSEQUENTtALDAMAGES, INCLUDING BUTNOT
LIMITED TO LABOR CHARGES, REGARDLESS OF
WHETHERTYCO FIREPRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENTSHALLIYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT EQUAL TO THE
SALES PRICE.
(B
TFPI72O
Pipe Nominal Dimensions Hole Net
Size Size Wt. A B C D
Run x Inches Inches Inches Inches Inches Lbs.
Branch mm mm mm mm mm Kg.
2.00 1.50 3.50 1.20 134e 0.84
50.8 38.1 88.9 30.5 30.2 0.4
11/40 x 3/0 2.00 1.50 3.50 1.20 1/16 0.88
50.8 38.1 88.9 30.5 30.2 0.4
11/40 i 2.31 1.66 3.50 1.20 1/16 1.13
58.7 42.7 88.9 30.5 30.2 1 0.5
11/20 X 1/20 2.12 1.62 3.50 1.32 1/is 0.84
53.8 41.1 88.9 1 33.5 30.2 0.4
11/2 X3/4° 2.12 1.62 3.50 1.32 i/16 0.88
53.8 41.1 88.9 33.5 30.2 0.4
11/20 X i 2.43 1.80 3.50 1.32 i/I6 1.13
61.7 45.7 88.9 33.5 30.2 1 0.5
2X 1I2 2.36 1.86 3.74 1.55 13'i 0.88
59.9 47.2 95.0 39.4 30.2 0.4
2' x 3/4k 2.36 1.86 3.74 1.55 0.95
59.9 47.2 95.0 39.4 30.2 0.4
2"x 1' 2.67 2.04 3.74 1.55 1/18 1.16
67.8 51.8 95.0 39.4 30.2 0.5
21/20 X 1/20 2.61 2.11 4.25 1.80 l/i 0.90
66.3 53.6 1 108.0 45.7 30.2 0.4
21/20 X3140 2.61 2.11 4.25 1.80 1/16 0.99
________ 66.3 53.6 108.0 45.7 30.2 0.4
21/2' x 2.92 2.29 4.25 1.80 1/i 1.21
74.2 58.2 108.0 45.7 1 30.2 1 0.5
Item Description
1 Housing
2 Gasket
3 Flanged Nut
4 U-Bolt
Fitting
Size
Equivalent Length
(1 inch pipe)
11/4"X 1' 8
11/2'X 1" 6
2"x 1 6
21/2"x 1' 4
The friction loss for these outlets is specified in
equivalent length of 1 inch Schedule 40 (C=120) pipe.
Ii
Page 2 of 2 TFP1 720
Figure 40-5 Strap
The 1 inch outlets can be used with a nipple leading Note: Outlet threads conforming to ISO 7-1 are available, contact
directly to a sprinkler. These fittings should be used Tyco Fire Products.
for hydraulically calculated systems only.
12
General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure 1311" 0 that pressure ratings and performance data is not exceeded. Always read and understand the installation 9001 instructions (I1-1.1000). Never remove any piping component or corrector modify any piping deficiencies without
first depressurizing and draining the system. Material and gasket selection should be verified to be compatible
for the specific application. . Certified Company
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
tYCJJ Fire & Building
IlProducts
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series TYIFRB - 2.8,4.2,56, and 80 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Tyco° Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
1FP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
AUGUST, 2007
Model/Sprinkler
Identification
Numbers
TVII3I - Upright 2.8K, 1/2"NPT
1Y1231 - Pendent 2.81K, 1/2"NPT
TY2131 - Upright 4.21K, 1/2"NPT
1Y2231 - Pendent 4.21K. 1I2"NPT
TY3131 - Upright 5.61K, 1/2"NPT
1Y3231 - Pendent 5.61K. 112"NPT
1Y4131 - Upright 8.01K, 3/4"NPT
1Y4231 - Pendent 8.0K, 314"NPT
TY4831- Upright 8.01K, 1/2"NPT
TY4931- Pendent 8.0K, 1/2"NPT
(B TFPI 71
TFPI7I Page 3 of 10
7/16(1l.1 mm) STYLE 100r2(
RECESSED
ESCUTCHEON
2-7/8" (73,0 mm) DIA. -I
PENDENT RECESSED PENDENT
- Frame 3- Sealing 4 - Bulb 6 - Deflector
2 - Button Assembly 5: Compression
Screw
DEFLECTOR
;rN(OMINAL
"
6
mm)2-3/16"
(55,6mm) 3
-IN
1/2° NPT
UPRIGHT CROSS SECTION
* Temperature rating is Indicated on deflector or adjacent t
orifice seat on frame.
ESCUTCHEON
PLATE SEATING
SURFACE NPT
2-3/16" -
(55,6 mm)
1-1/2
(38,11 mm)
SSP DEFLECTOR *
FIGURE 3
QUICK RESPONSE SERIES TV-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2' (12,7 mm)
PLATE SEATING NOMINAL
SURFACE MAKE-IN NPT
2-5/16"
_
(58, mm)
I 1-9/16"
(39,7 mm)
SSP DEFLECTOR * 2-7/8"
PENDENT RECE
STYLE 30 0r40
RECESSED SSU* ESCUTCHEON DEFLECTOR
112" 5
PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembl..-' 5 - Compression orifice seat on frame. Screw
FIGURE 4
..-QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4 131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
Page 4oflO TFP171
7/16"(11,1 mm)
NOMINAL SSU 1/2 MAKE-IN DEFLECTOR N PT
2-1/4" 2-3/16"
(57,2 mm) ________ (55,6 4
\ /
1-9/16" _________ 2
(39,7 mm) FLATS
WRENCH
3
SP*
EFLECTOR CROSS
PE NT UPRIGHT SECTION
- Frame 3 - Sealing 4 ulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
Assembly 6 Compression orifice seat on frame. Screw
iII°fl FIGURE 5
UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psi112 (40,3 LPM/bar112)
K = 4.2 GPM/psi1/2 (60,5 LPM/barl'2)
K = 5.6 GPM/psil'2 (80,6 LPM/bar112)
K = 8.0 GPM/psi112 (115,2 LPM/barl'2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Page 6 of 10 TFPI7I
SPRINKLER FINISH (See Note 8)
K I TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED I WHITE"'
1POLYESTER
LEAD
COATED
5.6
1/2*
PENDENT
(TY3231)
and
135°F/57°C
155°F/68°C
Orange
Red
1,2,3,4,5,6,7 12, 3,5 175°F/79°C Yellow
(TY3131)
UPRIGHT I 200°F/93°C Green
286°F/141°C Blue
NPT
PENDENT
(TY3231)*
Figure 10
135°F/57°C Orange
1,2,4,5 N/A
RECESSED155°F/68°C Red I
175°F/79°C Yellow
200°F/93°C Green
RECESSED
PENDENT
(1Y3231)**
Figure 11
135°F/57°C Orange
1,2,3,4,5 N/A
155°F168°C Red
175°F179°C Yellow
200°F/93°C Green
-
8.0
3,4,,
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135"F/57°C Orange
1, 2, 3,4,5, 6, 7
1, 2, 5
155"F/68°C Red
175°F179°C Yellow
200"F/93°C Green
286°F/141°C Blue
NPT
RECESSED
PENDENT
(TY4231)°
Figure 12
135°F/57°C Green
1,2,4,5 N/A
155°F/68°C Orange
175°F/79°C Red
200°F193°C Yellow
RECESSED
PENDENT
(TY4231)
Figure 13
135°F/57°C Orange
1,2, 3, 4,5 N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
-
8.0
1/2"
NPT
PENDENT
(1Y4931)
and
UPRIGHT
(TY4831)
135°F/57°C Orange
1,2,4,5,6
1, 2,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use In Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City or New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4° Total Adjustment Recessed Escutcheon, as applicable.
** installed with Style 20 (1/2" NPT) or Style 30 (3/4° NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND &O K-FACTOR SPRINKLERS
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME I WHITE LEAD
BRASS PLATED POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
112" RECESSED PENDENT NPT (1Y323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 OR I UPRIGHT (TY3131)
1/2k 175 PSI (12,1 BAR) L RECESSED PENDENT NPT (TY3231) (SEE NOTE 1) N/A
PENDENT (1Y4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
RECESSED PENDENT NPT (fl'4231) N/A
8.0 PENDENT(TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories,lnc. for use in Canada (C-UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
10
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135F/57C to 3/32
inch (2,4 mm) for the 286F/141C
temperature ratings.
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
S
S
TFPI7I
2-718" DIA. -
5/8±1/4" (73,0 mm) I 3/4"(19,1 mm
(15,9±6,4 mm) 2-1/4" DIA. 1/4~(6
~
A
FACE OF ,
'•
MTING
SPRINKLER PLTE
FITTING
I
(3,2 mm)
I. MOUNTING
SURFACE
SERIES 1-1/4"(31,8 mm) I CLOSURE TY-FRB 3/4"(19,1 mm)
FIGURE 10
RIES TY-FRB RECESSED PENDENT
WIT TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
(15,91-6,4 mm) 2-1/4"IDIA. •___.- 114"(6,4 m
(57,2 mm) FACE OF MOU INC
SPRINKLER ATE
FITTING
/ 1/8"
I (3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33.3J.M)
TY-FRB 13/16'(20.6 mm)
FIGURE 12
S IES TY.FRB RECESSED PENDENT
WIT 0-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 9 of 10
- 2-7/8' DIA.
(73,0 mm) 1/2±1/8" 1/2"(12,7 m
(1 2,7±3,2 mm) - 2-1/4" OIA 1/4" (6,4 m)
FACE OF (57.2 mm) 71 MO TING
SPRINKLER PLATE
)5.6
Iz
(3,2 mm)
SERIES 1-114"(31,8 mm)
TY.FRB 1" (25,4 mm)
FIGURE 11
-FRB RECESSED PENDENT
E 1/2 INCH TOTAL ADJUSTMENT
RECESSED ESCUTCHEON
-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
1/2±1/8" (73.0 mm) 1/2"(12,7 mm)
(12,7±3.2 mm) 2-1/4" OIA. 1/4" (6,4
(57,2 mm) FACE OF MO TING
SPRINKLER LATE
FITTING
/ 1/8" I - (3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1.5/16" (33,3 mm)
TYFR8 1-1116'(27.0 mm)
FIGURE 13
RIES TY.FRB RECESSED PENDENT
WIT TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes.
8
Page 10 of 10 TFPI 71
P/N 57- XXX
MODEL/SIN
330 2.8K UPRIGHT (1/2"NPT) TYII31
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2'NPT) 1Y2131
341 4.2K PENDENT (1/2"NPT) 1Y2231
1370 5.6K UPRIGHT (112NPT) TY3131
LEL
5.6K PENDENT (1/2"NPT) TY3231
390 8.0K UPRIGHT (314"NPT) TY4131
391 8.0K PENDENT (3/4"NPT) TY4231
360 8.0K UPRIGHT (112'NPT) TY4831*
361 8.0K PENDENT (1/2'NPT) TY4931*
I I I SPRINKLER
1 NATURAL BRASS
4 WHITE POLYESTER
3 WHITE (RAL90IO)*
9 CHROME PLATED
7 LEAD COATED
I
135
155
175
200
286
RATING
TEMPERATUI
135*F/57*C
155°F/68°C
175°FI79C
2000F/93*C
286°F/141°C
* Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
S Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shalt TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
cress or imoilea. inciva;na warranties
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table 0).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
PIN 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
PIN 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
100
BEAM CLAMP SMALL MOUTH
<9> C®US
SIZE - 3/8 and 1/2" rod.
MATERIAL - Ductile iron with hardened cup point set screw and jam nut.
FINISH - Plain, Electro-Galvanized and H.D.G. and Stainless Steel.
LISTING - UL in US and CANADA.
APPROVAL- Factory Mutual Research.
CONFORMS WITH: Federal Specification WW-H-1 71 E Type 19 and 23 and
Manufactures Standardization Society ANSI/MSS-SP-58 Type 19 and 23.
FUNCTION -To hang from steel beam with flange thickness ofi ess than 3/4'.
INSTALLATION - Per NFPA#13 - 3/8 rod will support 1/2' thru 4' pipe
and 1/2' rod 5" thru 8' pipe. Install in accordance with ANSI/MSS-SP-69.
Torque - 3/8=60 inch pounds. Torque - 1/2= 125 inch pounds. In the absence
of a torque wrench, the set screw should be finger tightened and then an
additional 1/3 turn applied to the set screw.
FEATURES
* Maintains CONSTANT HANGER CENTER-LINE, with set screw
up or down.
* Flat throat back prevents twisting during installation.
ORDERING - Part #, rod size and finish.
Index
5/01
162
UNIVERSAL - RETAINING STRAP
Nut optional, if
insufficient rod dimension
SIZE- One size fits both 3/8" and 1/2" rod or set screw.
Available lengths 4" and longer.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING - UL in US and CANADA.
PATENT - No. 5,897,088
FUNCTION - To offer more secure fastening of Beam Clamp to beam
when danger of movement might be expected.
INSTALLATION - Install tight to structure and component parts
Minimum return on strap: 1"
FEATURES * Fast installation for new construction or retrofit. * Requires no hanger disassembly to install.
IMPORTANT NOTE "No Nut Is Required"
When installed tight to structure and component parts per good
installation practice (See drawings provided)
ORDERING - Part # and overall length.
Index
12/00
IMPERIAL MAX REC.
LOAD LBS.
METRIC
PIPE PIPE ROD
1/2 3/8 400 10
—;:;-- 3/8 400 20 10
1 3/8 0° 25 10
1 1/4 3/8 400 32 10
11/2 3/8 400 40 10
2 3/8 400 so 10
21/2 3/8 600 65 10
3 600 80 io
3 1/2 600 10
4 1000 100 10
1250 125 12
6
18
5
1250 150 12
1250
Order Part #300m
Note: 1/2' Ring Hanger not <FM> approved
( D
300
RING HANGER
1 thru 4 inch pipe 1/2 and 3/4 Inch pipe
5 thru 8 inch pipe
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mil. Galvanized to G-90 specification.
FINISH - Mil. Galvanized and Stainless Steel.
LISTING - UL in US and CANADA.
APPROVAL - Factory Mutual Research.
CONFORMS WITH: Federal Specification WW-H-1 71 (Type 10),
Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10); install
in accordance with ANSI/MSS- SP-69.
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - For fire sprinkler and general piping purposes.
Swivel nut permits hanger adjustment after installation.
FEATURES -
1 thru 4 inch:
*Offset edge for EASY pipe insertion.
1 thru 8 inch:
* Full length knurl on swivel nut for better grip.
UNIQUE FEATURES
1 thru 3 inch:
* UL listed to accept AFCON #310 Surge Restrainer.
* Swivel nut
Retained in ring to keep the assembly intact prior to installation.
Removed easily if needed.
* UL listed for use on CPVC pipe.
ORDERING - Part # and pipe size.
Index
02/01
[I C SD
655
ALL THREADED ROD CUT TO LENGTH
ROD
SIZE
MAX. REC. LOAD LBS.
FOR SERVICE TEMP.
650°F 750°F
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
NOTE; maximum Temperature: 750°F
SIZE - 3/8 thru 7/8 inch rod in linch
increments.
MATERIAL - Carbon Steel.
FINISH - Plain, Electro-Galvanized and
Stainless Steel.
ORDERING - Part #, rod diameter, rod
length and finish.
2/00 ( D
Listinas/Aoorovals
City of Los Angeles
Research Report No. 23709 (HDI Only)_
FM (Factory Mutual)
Pipe Hanger Components for Automatic
Sprinkler Systems (3/8 - 3/4')
(HDI and HDI-L)
UL (Underwriters Laboratories)
UL 203 Pipe Hanger Equipment for Fire
Protection Services (3/8 - 3/4)
A:IHDI & HD Drop Anchor TT
4.3.8.1 Product Description
The Hilti HDI/HDl-L Drop-In anchor is an • Intelligent expansion section
internally threaded, flush mounted adapts to the base material and
expansion anchor for use in concrete. reduces number of hammer blows
up to 50% (HDI-L)
Product Features Guide Specifications
4,3.8.1 Product Description
is 4.3.8.2 Material Specifications
4.3.8.3 Technical Data
4.3.8.4 Installation Instructions
4.3.8.5 Ordering Information
Anchor, setting tool and Hilti drill bit
form a matched tolerance system
to provide reliable fastenings
Allows shallow embedment without
sacrificing performance
Lip provides flush installation,
consistent anchor depth, and easy
rod alignment (HDI-L)
Lip allows accurate flush
surface setting, independent
of hole depth (HDI-L)
Ideal for repetitive fastenings with
threaded rods of equal length
Expansion Anchor Expansion anchors
shall be flush or shell type and zinc
plated in accordance with ASTM B 633,
SC 1, Type III. Anchors shall be Hilti
HDI/HDI-L anchors as supplied by Hilti.
Installation Install shell or flush type
anchors in holes drilled with Hilti carbide
tipped drill bits. Install anchors as per
manufacturer's recommendations.
4.3.8.2 Material Specifications
HDI/HDI-L, 1/4', 3/8", 1/2', and HDI 5/8" and 3/4" are manufactured from mild
carbon steel which is plated with a zinc finish for corrosion protection in
accordance with ASTM B 633, SC 1, Type III
HDI Stainless Steel material meets the requirements of AlSI 303
4.3.8.3 Technical Data
HDI/HDI-L Specification Table
Anchor HDl/HDI-L HDI
1/4 318 1/2 5/8 3/4 Size in.
Details (mm) (6.4) (9.5) (12.7) (15.9) (19.1)
dbit Nominal Bit diameter In. 3/8 1/2 5/8 27/32 1
h 0 Std. depth of embed. in. 1 1-9/16 2 2-9/16 3-3/16
Anchor length (mm) (25) (40) (51) (65) (81)
h1 Hole depth
Useable thread in. 7/16 5/8 11/16 7/8 1-3/8
length (mm) (11) (15) (17) (22) (34)
Threads per inch 20 16 13 11 10
h mm. base material in. 3 3-1/8 4 5-1/8 6-3/8
thickness (mm) (76) (79) (102) (130) (162)
Tmax max tightening ft-lb 4 11 22 37 80
torque (Nm) (5.4) (14.9) (29.8) (50.2) (108.5)
Combined Shear and Tension Loading . IN, \5/3 fVd \513
7j + , 1.0 (Ref. Section 4.1.2.7)
362 HHLI, Inc. (US) 1-800-879-8000 1 www.us.hUtl.com I an espafiol 1-800-879-5000 1 Hilti (Canada) Corp. 1-800-363-4458 1 www.hilti.ca I Product Technical Guide 2008
fl
HDI & HDI-L Drop-In Anchor 4.3.8
Carbon Steel HDI Allowable Loads in Concrete
Anchor size 2000 psi (13,8 MPa) 4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
in.(mni) Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN)
HDI FlDl-1. HDI HDl-L HDI I HDI-L HDI Hal-I HDI HDI-L HDI HDI-L
1/4 (6.4) 500) 2.2) 500(2.2) 450) 8.0) 450(8.0) 570) 2.5) 570(2.5) 625) 2.8) 625(2.8) 790) 3.5) 790 3.5) 700 3.1) 700( 3.1)
3/8 1 9.5) 890) 4.0) 890(4.0) 965) 4.3) 965(4.3) 1115) 5.0) 1115(5.0) 1250) 5.6) 1250(5.6) 1 1360) 6.0) 1360) 6,0) 1500) 6.7) 1500) 6.7)
1120 ( 5.0) 1120 (5.0) 1500) 6.7) 1500(6.7) 1785(7.9) 1785(7.9) 2125) 9.5) 1940(8.6) 2345 (10.4) 2345(10.4) 2500(11.1) 2500(11.1)
5/8 115.9) 1875) 8.3) - 2500(11.1) - 2920(13.0) - 3250(14.5) - 3715(16.5) - 3750(16.7) -
2500)11.1) - 3875(17.2) - 4065(18.1) - 5000(22.2) - 5565(24.8) - 5500(24.5) -
Note: The ultimate shear and allowable shear values are based on the use or SAE Grade 5 bolts, 0r = 85 ksi, F = 120 ksi) with the exception of the 114 HDlIHDI-Linf' = 6000 psi
concrete which is based upon the use of a SAE Grade 8 bolt (l - 120 ksi, F, - 150 ksi).
Carbon Steel HDI Ultimate Loads in Concrete
Anchor size 2000 psi (13.8 MPa) 4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
In. 011m) Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN)
HDI HDl-L HDI HDI-I HDI HDI-L HDI HDl-L HDI HDI-L HDI HDI-L
1/4 (6.4) 1995) 8.9) 1995) 8.9) 1800) 8.0) 1800) 8.0) 2270)10.1) 2270(10.1) 2500(11.1) 2500(11,1) 3150(14.0) 3150)14.0) 2800(12.5) 2800(12.5)
3/8 ( 9.5) 3555(15.8) 3555(15.8) 3850(17.1) 3850(17.1) 4480(19.8) 4480(19.8) 5000(22.2) 5000(22.2) 5430(24.2) 5430(24.2) 6000(26.7) 6000(26.7)
4470 (19.9) 4470(19.9) 6000(26.7) 6000(26.7) 7140 (31.8) 7140(31.8) 8500(37.8) 7750(34.4) 9375(41.7) 9375 (41.7) 10000(44.5) 10000(44.5)
7500(33.4) - 0000(44.5) - 11685(52.0) - 13000(57.8) - 14865(66.1) - 15000(66.7) -
10000(4.4.5) - 5500 (69.0) - 16260(72.3) - 20000(89,0) - 2250(99,0) - 22000(97.9) -
Carbon Steel HDI Allowable Loads in Lightweight Concrete and
Lightweight Concrete over Metal Deck12
Anchor
Size
Anchor Installed in 3000 psi (20.7 MPa)
It Wt. Concrete3
Anchor Installed Through Steel Deck Upper Flute
Into 3000 psi (20.7 MPa) It. Wt. Concrete4
Anchor Installed Through Steel Deck Lower Flute
Into 3000 psi (20.7 MPa) U. Wt. Concrete4
in. (mm) Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN)
1/4(6.4) 465 (2.1) 340 (1.5) 530 (2.4) 335(l.5) 375(l.7) 250(1.1)
3/8(9.5) 755 (3.4) 940 (4.2) 880(3.9) 1010 (4.5) 500 (2.2) 500 (2.2)
1/2(12.7) 1135 (5.0) 1700 (7.6) 1105 (4.9) 1755 (7.8) 625 (2.8) 750 (3.3)
5/8(15.9) 1465 (6.5) 2835 (12.6) - - 875 (3.9) 875 (3.9)
3/4(19.1) 2075 (9.2) 3680(16.4) - - 1250(5.5) 1000 (4.4)
S Li
1 The allowable values are based on the use 01 SAE Grade 2 bolts installed in the
anchors.
2 Based on using a safety Factor of 4.0.
Stainless Steel HDI Allowable Loads in Concrete
The tabulated shear and tensile values are for anchors installed in structural light-
weight concrete having the designated ultimate compressive strength at the time of
installation. The concrete must comply with ASTM C 330-71.
The tabulated shear and tensile values are For anchors installed through 20 gauge
intermediate decking into structural lightweight concrete having the designated
ultimate strength at the time 01 installation. The concrete must comply with ASTM
C 330-77.
Anchor size
in. (mm)
4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN)
SS HDI -1/4 (6.4) 480 (2.1) 600 (2.7) 740 (3.3) 600 (2.7)
SS HDI -3/8 (9.5) 1040 (4.6) 1230 (5.5) 1460 (6.5) 1230 (5.5)
SS HDI -1/2 (12.7) 1840 (8.2) 2760 (12.4) 2410 (10.7) 2760 (12.3)
SS HDI -5/8 (15.9) 2630(11.7) 4510 (20.1) 3770 (16.8) 4510 (20.1)
SS HDI -3/4 (19.1) 3830 (17.0) 5580 (24.8) 5030 (22.4) 5580 (24.8)
Note The ultimate and allowable shear values are based on the use of Type 18-8 bolts.
Stainless Steel HDI Ultimate Loads in Concrete
Anchor size
in. (mm)
4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN)
SS HUI - 1/4 (6.4) 1930 (8.6) 2400 (10.7) 2950 (13.1) 2400 (10.7)
SS HDI -3/8 (9.5) 4170 (18.5) 4920 (21.9) 5850 (26.0) 4920 (21.9)
SS HDI -1/2 (12.7) 7350 (32.7) 11040 (49.1) 9630 (42.8) 11040 (49.1)
SSHDI-5/8 (15.9) 10540 (46.9) 18040 (80.2) 15100 (67.2) 18040 (80.2)
SS HDI - 3/4 (19.1) 15340 (68.2) 22320 (99.3) 20130 (89.5) 22320 (99.3) 25
Hilti, Inc. (US) 1.800-879-8000 1 www.us.hllti.com I en espahol 1-800-879-5000 1 Hf ti (Canada) Corp. 1.800-363-4458 1 www.hilti.ca I Product Technical Guide 2008 363
: i j ti :1.] Drop-inrvrAnchorr
Anchor Spacing and Edge Distance Guidelines (See Anchoring Technology Section 4.1.3)
Anchor Spacing Adjustment Factors
S = Actual Spacing
Smin = 2.0 hnom
= 3.5 hnom
Sr
3.0' Shear& " 111
2.0
Smin
S I
1.0
0 I
0 .2 .4 .6 .8 1.0
Anchor Spacing Adjustment Factor
(1A)
Edge Distance Adjustment Factors
c = Actual edge distance
Cmtn = 2.0 hnom
Ccr = 3.0 hnom
Ccr
3.0
Shear
: __ __ . rIi!! 2.0 -- __
1.0-
0 1 11111 I
0 .2 .4 .6 .8 1.0
Edge Distance Adjustment Factor
(f RV 1Rn)
Influence of Anchor Spacing &
Edge Distance 'IA, R
Anchor Size
in. (mm)
hnom
In. (mm)
1/4(6.4) 1(25)
3/8(9,5) 1-9/16(40)
1/2(12.7) 2(51)
5/8(15.8) 2-9/16(65)
3/4(19.1) 3-3/16(81)
h,., = standard embedment depth
Load Adjustment Factors (Anchor Spacing) fA Load Adjustment Factors (Edge Distance) f
Tension/Shear Loads Tension, f,, Shear,
Spacing
S
in. (mm)
Anchor Diameter Edge Distance
C
in. (mm)
Anchor Diameter Anchor Diameter
1/4 3/8 1/2 5/8 314 1/4 3/8 1/2 5/8 3/4 1/4 3/8 1/2 5/8 3/4
2 (51) .50 - - - 2 (i) .80 - - .65
-1I2 () .67 - - 2-1/2 LL .90 - - .83
( - 83 0 - - 3 tO O - 1.0 .65
-1/2( 1.0 8 - - - 3-1/2 (89) - 85 1 - .73 1 -
4 (102) - 9 0 - 4 (102) -.91 0 85 5 -
4-1/2(114 - 79 8 - 4-1/2(114) - .98 85 1 .96 .74
5(127) O.67.50 5(127) 1.0.90.80 t083 .65 -
5-1/2(140) - 1.0 75 .55 - 5-1/2 (140) - .95 83 .91 10
6(152) 3 .61 50 6(152) tO .87 tO 17
7(178) 1 1 1.0 .74 L 6-1/2 (165) 1 .91 .80 1 - - .84 .65
8(203) 7.67 7(178) 584 J2
9(229) - - - tO 17 8(203) - - to o - - 1.0 .83
10 (254) - - - - .88 9 (229) - - - - .96 - - .94
11 (279) - - - - .98 10 (254) - - 1.0 - 1.0
12 (305) 1.0
S 2.0 hnom, S0 = 3.5 h o
fA = 0.33 s- 0.17
h,yj,,,
for Scr> S> Smin
cmin = 2.0 hnom, C0 = 3.0 h,
fRN = 0.2 ci- 0.4
hnom
for C > Cmin
cmin = 2.0 hnom, Ccr = 3.0 hnom
ffiv = 0.35 c- 0.05
hnom
for cc, > C> cmin
364 Huh, Inc. (US) 1-800-879-8000 1 www.us.hihtl.com I en espahol 1-800-879-5000 1 Huh (Canada) Corp. 1-800-363.4458 1 www.hiltl.ca I Product Technical Guide 2008