HomeMy WebLinkAboutPD 2022-0022; CANTOR GARAGE ADDITION; GEOTECHNICAL INVESTIGATION FOR PROPOSED GARAGE AND RETAINING WALLS; 2021-06-28Josh Cantor
4215 Hillside Drive
Carlsbad, California 92008
EAST COUNTY SOIL CONSULTATION
AND ENGINEERING, INC.
10925 HARTLEY ROAD, SUITE "I"
SANTEE, CALIFORNIA 92071
TEL. 619-258-7901
June 28, 2021
Project No. 21-1106G7
Subject: Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
Dear Mr. Cantor:
In accordance with your request, we have performed a geotechnical investigation at the subject site
to evaluate the geotechnical site conditions and provide recommendations for design and
construction of the proposed garage and retaining walls.
SCOPE OF SERVICES
The following scope of work was performed for this investigation:
0 Site reconnaissance and review of published geologic and geotechnical reports and maps
pertinent to the project area.
0 Subsurface exploration consisting of drilling two test borings within the area of the proposed
garage. The test borings were logged by our project supervisor.
0 Collection of representative soil samples at selected depths. The obtained samples were stored
in moisture-resistant containers and transported to our soil testing laboratory for subsequent
analysis.
0 Laboratory testing of soil samples obtained during the subsurface exploration.
0 Geotechnical analysis of the field and laboratory data, which provided the basis for our
conclusions and recommendations.
0 Preparation of this report, which summarizes the results of our analysis and presents our
findings and recommendations for the proposed construction.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
SITE DESCRIPTION AND PROPOSED CONSTRUCTION
Page2
June 28 2021
Project No. 21-1106G7
The site location is shown on the attached Vicinity Map, Figure 1. The site consists of an irregular-
shaped residential lot in Carlsbad, California (see Figure 2). The lot is bordered by Hillside Drive
to the northeast and residential parcels to the north, west and south.
The proposed garage is located in a mostly cut portion of the lot. The lot slopes generally down to
the east. Site vegetation is relatively minor.
The proposed garage will be a one-story, wood framed structure supported on continuous and/or
individual spread footings with a slab-on-grade floor. Retaining walls will be constructed along
the west and north sides of the proposed garage.
SUBSURFACE EXPLORATION AND LABORATORY TESTING
Two test borings were drilled on April 21 , 2021 to a maximum depth of 7 feet with a hand auger.
The approximate locations of the test borings are shown on Figure 2. Logs of the test borings are
shown on Figure 3.
Following the subsurface exploration, laboratory testing was performed on representative soil
samples to evaluate the pertinent engineering properties of the foundation materials. The
laboratory tests included moisture content, dry density and expansion index tests. The tests were
performed in accordance with ASTM standards. The test results are shown on the Logs of the Test
Borings, Figure 3 and on Figure 4, Results of Laboratory Tests.
SUBSURFACE SOIL CONDIDONS
The subsurface soil descriptions were interpreted from conditions encountered during the subsurface
exploration and/or inferred from the geologic literature. Detailed descriptions of the subsurface soils
are presented on the logs of the test borings presented on Figure 3. The following is a generalized
description of the soils.
Fill: Fill soils were encountered in Boring B-2 to a depth of approximately 0.5 foot. The fill consisted
of dark grayish brown, dry, loose, silty sand.
Natural Soil: Natural soil was encountered below the fill in Boring B-2 and below the ground surface
in Boring B-1 to the maximum depth explored of 7 feet. The natural soil consisted of dark to
reddish brown, moist, loose to medium dense, silty sand to a depth of 2 feet, underlain by moist,
medium dense, silty sand to the depth explored of 7 feet.
GROUNDWATER
No groundwater was encountered in the test borings.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
GeotechnicaJ Investigation for Proposed Garage and Retaining WaJls
4269 Hillside Drive
Carlsbad, CA 92008
SOIL PROPERTIES
a. Compressible Soils
Page 3
June 28 2021
Project No. 21-1106G7
Our field observations and testing indicate the upper fill and natural soil are loose and
compressible to a depth of about 2 feet.
b. Expansive Soils
An expansion index test was performed on a representative sample of the natural soil. The
results of the test are shown on Figure 4. An expansion index of O was obtained, which
indicates the soils are non-expansive.
GEOLOGY
From published geologic maps, the site is underlain at depth by sedimentary terrace deposits.
There are no known geologic hazards such as landslides, liquefaction-prone areas, or earthquake
faults at the site. However, the proposed buildings are subject to ground shaking and possible
damage from earthquakes on nearby, or more distant, active faults.
SEISMIC DESIGN VALUES
Seismic design values are presented on Figure 5.
CONCLUSIONS
Construction of the proposed one-story garage and retaining walls is feasible from a geotechnical
standpoint, provided the recommendations presented in this report are properly implemented during
construction.
RECOMMENDATIONS
SITE GRADING
a. Site Clearing
The area of the proposed construction should be cleared of vegetation, surface obstructions and
other deleterious materials. Vegetation and debris from the clearing operation should be properly
disposed of off-site.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
b. Temporary Slopes and Excavations
Page4
June 28 2021
Project No. 21-1106G7
Temporary, vertical slopes and excavations should not exceed 5 feet in height. Temporary slopes and
excavations greater than 5 feet in height should be shored or laid back at a maximum inclination of 1 : 1
(horizontal to vertical). Recommendations for shoring design can be provided by our office if desired.
c. Soil Removals
Within the area of the proposed garage and retaining walls and to a distance of at least 5 feet
outside building limits, the loose fill and natural soils should be removed down to medium dense
natural soil, an estimated depth of about 2 feet, and replaced with fill soils compacted to at least 90
percent relative compaction.
d. Compaction and Method of Filling
Prior to fill placement, the exposed subgrade soils should be scarified to a depth of 6 to 8 inches,
moisture conditioned to slightly above optimum moisture content and compacted to at least 90
percent relative compaction.
The on-site soils may be reused as compacted fill, provided they are free of organic materials and
debris, and rocks or cobbles over 6 inches in dimension. Any imported fill soils should be
predominantly granular and approved by our field representative.
All fill should be compacted to a minimum relative compaction of 90 percent as determined by
ASTM Dl557. Fill should be placed at a moisture content slightly above optimum moisture
content, in lifts 6 to 8 inches thick, with each lift compacted by mechanical means.
Utility trench backfill and retaining wall backfill should also be compacted to at least 90 percent
relative compaction.
All grading, fill placement, and compaction should be performed in accordance with the grading
requirements of the City of Carlsbad. Fill placement and compaction should be observed and
tested as necessary by our field representative.
EROSION CONTROL
Due to the predominantly sandy nature of the on-site soils, areas of recent grading or exposed ground
may be subject to erosion. During construction, surface water should be controlled via berms, gravel/
sandbags, silt fences, straw wattles, siltation or bioretention basins, positive surface grades or other
method to avoid damage to the finish work or adjoining properties. All site entrances and exits must
have coarse gravel or steel shaker plates to minimize offsite sediment tracking. Best Management
Practices (BMPs) must be used to protect storm drains and minimize pollution. The contractor
should take measures to prevent erosion of graded areas until such time as permanent drainage and
erosion control measures have been installed. After completion of grading, all excavated surfaces
should exhibit positive drainage and eliminate areas where water might pond.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotecbnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
FOUNDATIONS AND FLOOR SLABS
Pages
June 28 2021
Project No. 21-1106G7
• Continuous and/or individual footings should be founded in properly compacted fill at a
minimum depth of 18 inches below building pad grade or lowest adjacent, finished grade,
whichever is deeper.
• Continuous footings should be at least 12 inches wide and reinforced with a minimum of four
#4 steel bars; with two bars placed near the top of the footings and the other two bars placed
near the bottom of the footings. Individual footings should be at least 18 inches square and
reinforced with a grid of #4 bars spaced 12 inches on centers ( each way) and placed on concrete
blocks at the bottom of the footing. Retaining wall footings should be designed by the project
structural engineer.
• An allowable soil bearing value of 2,000 pounds per square foot may be used for the design of
continuous and/ or individual spread footings and retaining wall footings bearing in properly
compacted fill or medium dense natural soil. This value may be increased by one-third for
short term wind or seismic loads.
• For design purposes, total and differential settlements of½ inch may be assumed.
• Lateral loads may be resisted by an equivalent fluid passive soil pressure of 300 pounds per
cubic foot. A coefficient of friction of 0.3 may also be used. If passive and friction values are
used together, the friction value should be reduced by one-third.
• All footing excavations should be inspected and approved by our field representative. Footing
excavations should be properly cleaned prior to inspection.
• Floor slabs should be at least 5 inches thick and reinforced with #4 bars placed at 18 inches on
centers in two directions in the middle of the slab. The reinforcing steel should be supported on
steel chairs or concrete blocks. Floor slabs should be underlain by 2 inches of clean sand over a
10-mil visqueen moisture barrier over 2 inches of clean sand. To minimize the potential for
shrinkage cracks, concrete should have a minimum compressive strength of 3,000 psi and
maximum water-cement ratio of 0.5. No special inspection of concrete is required. Some
shrinkage cracks are still possible.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
RETAINING WALLS
a. Soil Pressures
Page6
June 28 2021
Project No. 21-1106G7
Cantilever retaining walls may be designed for an active equivalent fluid soil pressure of 3 5 pcf for
a level backfill and 55 pcf for a 2: 1 H:V sloping backfill assuming predominantly sandy, very low
expansive backfill soils (El less than 20). Should the walls be subject to a uniform surcharge load
behind the walls, they should be designed for an additional, uniform lateral pressure equal to one-
third the anticipated surcharge pressure.
Basement and restrained retaining walls may be designed for an at-rest equivalent fluid soil
pressure of 55 pcf for a level backfill and 75 pcf for a 2: 1 sloping backfill assuming predominantly
sandy, very low expansive backfill soils (El less than 20). Should the walls be subject to a uniform
surcharge load behind the walls, they should be designed for an additional, uniform lateral pressure
equal to one-half the anticipated surcharge pressure.
For cantilever or restrained retaining walls over 6 feet in height, an additional earthquake force should
be applied. A horizontal seismic coefficient Kh = Sos/2.5 should be assumed . The earthquake force F
= 3/8*Kh*Soil density*Wall height (H)"'2 and may be assumed to have an inverted triangular
distribution with the resultant force located at a distance of 0.6*H from the base of the wall. Seismic
design values are presented on the attached Figure 5. A soil density of 130 pcf may be assumed.
b. Retaining Wall Foundations
Retaining wall footings should be designed m accordance with the recommendations presented
previously under Foundations.
c. Retaining Wall Drainage and Backfill
Retaining walls should be provided with appropriate waterproofing and wall drainage. Retaining wall
waterproofing should be designed by the project architect or building designer. Recommended wall
drainage is shown on the attached Figure 6. A 2-feet wide prism of Caltrans Class 2 Permeable
Material (graded drain rock) should be placed behind the wall.
Alternatively, retaining wall drainage should consist of Miradrain 6000 or J-Drain SWD-6
prefabricated drain panels placed directly against the wall. The drain panels should connect to a
collector pipe at the bottom of the wall constructed in accordance with drain manufacturer's
requirements. The drain pipe should flow at a 1 percent minimum gradient to an approved outlet.
Retaining walls may be backfilled with imported, predominately sandy, very low expansive soils
(EI less than 20) compacted to at least 90 percent relative compaction in accordance with the
recommendations presented previously under Site Grading.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
SURFACE DRAINAGE
Page 7
June 28 2021
Project No. 21-1106G7
Surface water should not be allowed to pond next to buildings. Finished grades should slope a
minimum of 2 percent away from buildings and along drainage swales. Drainage gradients should
be maintained . Roof gutters and downspouts connecting to solid, outlet pipes are recommended.
Outlet pipes should be discharged to an approved outlet.
LIMITATIONS OF INVESTIGATION
Our investigation was performed using the skill and degree of care ordinarily exercised under similar
circumstances by reputable soil engineers and geologists practicing in this or similar localities. No
other warranty, expressed or implied, is made as to the conclusions and professional advice included in
this report. This report provides no warranty, either expressed or implied, concerning future building
performance. Future damage from geotechnical or other causes is a possibility.
This report is prepared for the sole use of our client and may not be assigned to others without the
written consent of the client and ECSC&E, Inc.
The samples collected and used for testing, and the observations made, are believed representative of
site conditions; however, soil and geologic conditions can vary significantly between exploration
trenches, test borings and surface exposures. As in most major projects, conditions revealed by
construction excavations may vary with preliminary findings. If this occurs, the changed conditions
must be evaluated by a representative of ECSC&E and designs adjusted as required or alternate
designs recommended.
This report is issued with the understanding that it is the responsibility of the owner, or of his/her
representative to ensure that the information and recommendations contained herein are brought to the
attention of the project architect and engineer. Appropriate recommendations should be incorporated
into the structural plans. The necessary steps should be taken to see that the contractor and
subcontractors carry out such recommendations in the field .
The findings of this report are valid as of this present date. However, changes in the conditions of a
property can occur with the passage of time, whether they are due to natural processes or the works of
man on this or adjacent properties. In addition, changes in applicable or appropriate standards may
occur from legislation or the broadening of knowledge. Accordingly, the findings of this report may
be invalidated wholly or partially by changes outside of our control. Therefore, this report is subject to
review and should be updated after a period of two years.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotecbnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
ADDITIONAL SERVICES
Page 8
June 28 2021
Project No. 21-1106G7
A review of plans and specifications, field observations and testing under our direction are integral
parts of the recommendations made in this report. If East County Soil Consultation and Engineering,
Inc. is not retained for these services, the client agrees to assume our responsibility for any potential
claims that may arise during construction. Observation and testing are additional services, which are
provided by our firm, and should be budgeted within the cost of development.
This opportunity to be of service is appreciated. If you have any questions, or we can be of further
service, please do not hesitate to call or contact us.
This opportunity to be of service is appreciated . If you have any questions, or we can be of further
service, please do not hesitate to call or contact us.
Respectfully Submitted,
Martin R. Owen, PE, GE
Geotechnical Engineer
Attachments: Figures 1 through 6
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
~ -..cace: r ... S.
s Ccr~
rs r,-. o, \! ..,..c""a""I'\
: ... rst:=c
Sa rt -!-,
•'3tr1d.:
-, Eleme'lta,y
~ Schoo
Lei.JC lid a p: =
K°tcher ,,, --
V ,,.,.-
l! -
r "·
FIGURE 1
VICINITY MAP
9
Page9
June 28 2021
Project No. 21-1106G7
...
4269 Hillside Dr.
Carlsbad. CA 92008
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
FIGURE2
LOCATIONS OF TEST BORINGS
LEGEND
Page 10
June 28 2021
Project No. 21-1106G7
B-2 • APPROXIMATE LOCATION OF TEST BORING
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
DEPTH
Surface
1.0'
2.0'
3.5'
6.0'
DEPTH
Surface
0.5'
2.0'
6.0'
7.0'
FIGURE3
LOGS OF TEST BORINGS
TEST BORING B-1
SOIL DESCRIPTION
NATURAL SOIL
reddish brown, moist, loose to medium dense, silty sand
It ti II
dark brown, moist, medium dense, silty sand
reddish brown, moist, medium dense, silty sand
bottom of test boring, no caving, no groundwater
test boring backfilled 4/21/2021
TEST BORING B-2
SOIL DESCRIPTION
FILL
dark grayish brown, dry, loose, silty sand
NATURAL SOIL
reddish brown, moist, loose to medium dense, silty sand
dark to reddish brown, moist, medium dense, silty sand
reddish brown, moist, medium dense, silty sand
bottom of test boring, no caving, no groundwater
test boring backfilled 8/11/2020
Page 11
June 28 2021
Project No. 21-1106G7
y M
109.2 8.4
y M
118.8 9.8
----------------------------------------------------------------------------------------------------------------------------------
Y = DRY DENSITY IN PCF
M = MOISTURE CONTENT IN %
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
FIGURE 4
RESULTS OF LABORATORY TESTS
EXPANSION INDEX TEST
(ASTM D 4829)
TEST INITIAL SATURATED INITIAL EXPANSION
LOCATION MOISTURE MOISTURE DRY INDEX
CONTENT CONTENT(%) DENSITY
(%) (PCF)
B-1 @ 2.0' 9.3 18.2 110.8 0
Page 12
June 28 2021
Project No. 21-1106G7
EXPANSION
POTENTIAL
NON-
EXPANSIVE
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive Page 13
June 28 2021
Project No. 21-1106G7 Carlsbad, CA 92008
FIGURES
SEISMIC DESIGN V ALOES
4269 Hillside Dr, Carlsbad, CA 92008, USA
Date
Design Code Reference Document
Risk Category
Site Class
Type Value
Ss 1.045
51 0.379
s ... s 1.13
s-.(: null -See Section 11.4.8
Sos 0.754
5:::. null -See Section 11.4.8
Type Value
soc null -See Section 11.4.8
F, 1.082
Fv null -See Section 11.4.8
Description
Description
6/23/2021, 8:08:24 AM
ASCE7-16
n
D -Stiff Soil
MCER ground motion. {for 0.2 second period)
MCER ground motion. (for l.0s period)
Site-modified spectral acceleration value
Site-modified spectral acceleration value
Numeric seismic design value at 0.2 second SA
Numeric seismic design value at 1.0 second SA
Seismic design category
s·te amplification factor at 0.2 second
Site amplification factor at 1.0 second
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Geotechnical Investigation for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, CA 92008
FIGURE6
RETAINING WALL DRAINAGE
CANTILEVER
RETAINING WALL
WATERPROOFING
I 2' MIN. < >I
..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . . . . . . ..... . . . . .
..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . . . . . . ..... . . . . . . . . . . . . . . . ..... . . . . . . . . . . . . . . . . . . . .
2-FEET WIDE PRISM
OF CALTRANS CLASS
2PERMEABLE
MATERIAL PLACED
TO WlTIIlN 1 FOOT OF
TOP OF WALL
4-INCH DIAMETER,
PERFORATED,
SCHEDULE 35 OR
BETTER PVC PIPE
WRAPPED IN MlRAFl
FILTER SOCK. DRAIN
AT 1%MIN. TO
APPROVED OUTLET
Page 14
June 28 2021
Project No. 21-1106G7
SPECIFICATIONS FOR CALTRANS CLASS 2 PERMEABLE MATERIAL
GRADATION BY SIEVE SIZE
Sieve Percentage
Size Passing
l" 100
3/4" 90-100
3/8" 40-100
No. 4 25-40
No. 8 18-33
No. 30 5-15
No. 50 0-7
No. 200 0-3
Class 2 Permeable Material shall also have a sand equivalent value of at least 75 .
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Josh Cantor
EAST COUNTY SOIL CONSULTATION
AND ENGINEERING, INC.
10925 HARTLEY ROAD, SUITE "I"
SANTEE, CALIFORNIA 92071
TEL. 619-258-7901
4215 Hillside Drive
Carlsbad, California 92008
December 20, 2022
Project No. 21-1106G7
Subject:
Reference:
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
Project No. PD2022-0022, Grading Permit No. GR2022-0031
"Geotechnical Investigation for Proposed garage and Retaining Walls, 4269
Hillside Drive, Carlsbad, California 92008", Project No. 21-1106G7, Prepared by
East County Soil Consultation and Engineering, Inc., Dated June 28, 2021 .
Dear Mr. Cantor:
In accordance with your request, we have prepared this letter in response to the subject
geotechnical review for the Cantor Garage Addition, 4269 Hillside Drive, (1st Review).
Comment No. 1
We have reviewed the grading plan prepared by Bha, Inc., Land Planning, Civil Engineering and
Surveying for the proposed Cantor garage addition at the subject site. The grading plan was
found to be in accordance with the recommendations presented in the referenced geotechnical
report.
Comment No. 2
Based on site geotechnical conditions and a review of the grading plan, it is our opinion that the
proposed project will have no impact on adjacent off-site properties.
Comment No. 3
The proposed construction will consist of a one-story, detached garage to be located east of the
existing residence. In addition, a maximum 4-foot high retaining wall is planned near the bottom
of the existing cut slope adjacent to the east and north property lines. The proposed grading will
include an approximately 4-foot high vertical cut to accommodate the proposed retaining wall.
For the proposed retaining wall and garage, we recommend the upper 2-foot of subgrade be
removed to a distance of 5 feet outside perimeter footings (where feasible). The bottom of the
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
Page2
December 20, 2022
Project No. 21-1106G7
excavation should be moisture-conditioned and compacted. The scarified soils along with the 2
feet of overexcavated soil should be compacted to a minimum of 90 percent relative compaction.
Comment No. 4
The natural soils encountered during our site investigation revealed approximately 2 feet of loose
to medium dense slopewash over medium dense terrace deposits.
Comments No. 5 and 6
Please see attached Figure 1 showing a new "Locations of Test Borings" map using the most
current grading plan, and a geologic cross-section.
Comment No. 7
In the areas of the proposed garage and retammg wall, the subgrade soils consisted of
approximately 2 feet of loose to medium dense slopewash, which we have recommended
overexcavation and recompaction. The soils underlying the slopewash consisted of medium dense
terrace deposits which are considered suitable for support of compacted fill soils and the proposed
structure.
Comment No. 8 and 9
Regional Seisrnicity
Generally, Seismicity within California can be attributed to the regional tectonic movement taking
place along the San Andreas Fault Zone, which includes the San Andreas Fault and most parallel
and subparallel faults within the state. The portion of southern California where the subject site is
located is considered seismically active. Seismic hazards are attributed to groundshaking from
earthquake events along nearby or more distant Quaternary faults . The primary factors in
evaluating the effect an earthquake has on a site are the magnitude of the event, the distance from
the epicenter to the site and the near surface soil profile.
According to the Fault-Rupture Hazard Zones Act of 1994 (revised Alquist-Priolo Special Studies
Zones Act), quaternary faults have been classified as "active" faults, which show apparent surface
rupture during the last 11 ,000 years (i.e., Holocene time). "Potentially-active" faults are those faults
with evidence of displacing Quaternary sediments between 11,000 to 1. 6 millions years old.
Seismic Analysis
Based on our evaluation, the closest known "active" fault is the Rose Canyon Fault located
approximately 8.5 kilometers to the west. The Rose Canyon Fault is the design fault of the
project due to the predicted credible fault magnitude and ground acceleration.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
Page3
December 20, 2022
Project No. 21-1106G7
The Seismicity of the site was evaluated utilizing the 2008 Hazard Maps and Data from the USGS
website, and Seed and Idriss methods for active Quaternary faults within the regional vicinity.
The site may be subjected to a Maximum Probable Earthquake of 6.9 Magnitude along the Rose
Canyon fault, with a corresponding Peak Ground Acceleration of 0.35g. The maximum Probable
Earthquake is defined as the maximum earthquake that is considered likely to occur within a 100-
year time period.
The effective ground acceleration at the site is associated with the part of significant ground
motion, which contains repetitive strong-energy shaking, and which may produce structural
deformation. As such, the effective or "free field" ground acceleration is referred to as the
Repeatable High Ground Acceleration (RHGA). It has been determined by Ploessel and Slosson
(1974) that the RHGA is approximately equal to 65 percent of the Peak Ground Acceleration for
earthquakes occurring within 20 miles of a site. Based on the above, the calculated Credible
RHGA at the site is 0.23g.
Geologic Hazard Assessment
Ground Rupture
Ground rupture due to active faulting is not considered likely due to the absence of known fault traces
within the vicinity of the project; however, this possibility cannot be completely ruled out. The unlikely
hazard of ground rupture should not preclude consideration of"flexible" design for on-site utility lines
and connections.
Liquefaction
Liquefaction involves the substantial loss of shear strength in saturated soils, usually sandy soils with a
loose consistency when subjected to earthquake shaking. Based on the absence of shallow
groundwater and consistency of the underlying terrace deposits, it is our opinion that the potential for
liquefaction is very low.
Landsliding
There is no indication that landslides or unstable slope conditions exist on or adjacent to the
project site. There are no obvious geologic hazards related to landsliding to the proposed
development or adjacent properties.
Tsunamis and Seiches
The site is not subject to inundation by tsunamis due to its elevation. The site is also not subject
to seiches (waves in confined bodies of water).
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
Comment No. 10 and 11
Page4
December 20, 2022
Project No. 21-1106G7
The existing cut slope adjacent to the east and north property lines appears to be weathered,
unstable and steeper than required in the City of Carlsbad. A review of the grading plan indicates
a retaining wall will be constructed which will stabilize the existing slope. The temporary slope
should be excavated in accordance with OSHA guidelines, i.e. a maximum 5-foot high vertical cut
with a maximum lH: 1 V slope above that. If property line constraints do not allow an approved
temporary slope, temporary or permanent shoring may be used. Recommendations for shoring
design can be provided by our office if desired.
Comment No. 12 and 16
Driveways and other exterior slabs may be supported on the subgrade soils provided they are
scarified to a depth of 12 inches, moisture-conditioned around the optimum moisture content and
compacted to at least 90 percent relative compaction. Driveways and other exterior concrete
slabs should be at least 5 inches thick and reinforced with No. 4 rebars spaced at 18 inches on
centers in two directions and placed at mid-height in the slabs. Driveways and other exterior slabs
should be provided with construction joints spaced no more than 10 feet apart to minimize
shrinkage cracking. Slab concrete should have a minimum compressive strength of 3,000 psi and
maximum water-cement ratio of 0.5 to minimize shrinkage cracking. No special testing of
concrete is necessary. Some shrinkage cracking is still possible.
Comments No. 13 and 14
Based on the attached sieve analysis results (Figure 2) and the expansion index test results
provided in the referenced geotechnical report, a soil classification of silty sand (SM) was
obtained which substantiates the soil bearing capacity, passive pressure, coefficient of friction and
active pressure (3 5 pct) provided in the referenced geotechnical report and in accordance with
Tables 1806.2 and 1610.1 of the 2019 California Building Code.
Comment No. 15
Corrosivity tests were performed on a representative sample of the onsite soils. The attached test
results (Figure 3) indicate a low degree of corrosivity.
Accordingly, we recommend Type I/II Portland Cement for foundation construction.
Comment No. 17
Please see attached a list of references.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Res nse to Geotecbnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carl bad, California 92008
Co,imcnt N?. 18
I
Pages
December 20, 2022
Project No. 21-l106G7
The project ~eotechnical engineer or engineer's representative should receive advance notice to
pro ide the necessary intermittent field observations and compaction testing during site
dev lopment-: including overexcavation and recompaction of the building pad and during the
bac ill of t~e retaining wall. In addition. we should observe that the footings have been
exc vated to the proper depth and width into competent compacted fill soils prior to the
pla ment of steel.
Thi~ opportl$ity to be of service is appreciated. If you have any questions, or we can be of
furtper service. please do not hesitate to call or contact us.
Retectfully Submitte~
Ma
RC 54071. GE 2704
Attjichments: Figures 1 thru 3 and References
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
FIGURE 1
Page 6
December 20, 2022
Project No. 21-1106G7
LOCATION OF TEST BORINGS/ GEOLOGIC CROSS-SECTION
.l>-Z. JZ:5r/3ClfN6(Pl';(v~
q>SVtl ~ 5~/ISH
~t
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
\
\
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
U.S. Standard
Sieve Size
2"
l"
1/2"
3/8"
#4
#8
#16
#30
#50
#100
#200
uses
FIGURE2
PARTICLE SIZE ANALYSIS
(ASTMD422)
Percent Passing
B-2@2.0'
Slopewash
-
-
-
-
-
100
99
91
47
25
18
SM
Page 7
December 20, 2022
Project No. 21-1106G7
Percent Passing
B-1 @1.5'
Terr ace Deposits
-
-
-
-
-
100
99
85
38
18
13
SM
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
FIGURE3
CORROSIVITY TEST RESULTS
L A B O R A T O R Y REPORT
Page8
December 20, 2022
Project No. 21-1106G7
Telephone (619) 425-1993 Fax 425-7917 Established 1928
CLARKSON LABORATORY AND SUPPL. Y INC.
350 Trousdale Dr. Chula Vista , Ca. 91910 www.clarksonlab.com
A N A L Y T I C A L A N D C O N S U L T I N G C H E M I S T S
Date : October 18, 2022
Purchase Order Number: NONE
Sales Order Number : 57331
Account Number: EASCS
To: *-------------------------------------------------* East County Soil Consultation and Engineering Inc.
10925 Hartley Road Suite I
Santee, Ca 92071
Attention: Michael Duncan
Laboratory Number: SO9173 Customers Phone : 258-7901
Fax: 258-7902
Sample Designation: *-------------------------------------------------* One soil sample received on 10/11/22 at 12 :30pm,
marked as Highland -Cantor.
Analysis By California Test 643, 1999 , Department of Transportation
Division of Construction, Method for Estimating the Service Life of
Steel Culverts.
pH 6.5
Water Added (ml)
26
34
47
60
73
10
5
5
5
5
5
5
5
years
years
years
years
years
to perforation
to perforation
to perforation
to perforation
to perforation
for a 16 gauge
for a 14 gauge
for a 12 gauge
for a 10 gauge
for a 8 gauge
Water Soluble Sulfate Calif. Test 417
Water Soluble Chloride Calif. Test 422
~
RMB/js
metal
metal
metal
metal
metal
Resistivity (ohm-cm)
8200
culvert.
culvert.
culvert.
culvert.
culvert.
7800
6200
4800
4500
4500
4600
4800
0.004%
0.002%
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
REFERENCES
Page9
December 20, 2022
Project No. 21-1106G7
1. ''2019 California Building Code, California Code of Regulations, Title 24, Part 2, Volume 2 of 2",
Published by International Code Council.
2. "Geologic Map of the San Diego 30' x 60' Quadrangle, California", by Michael P. Kennedy and Siang
S. Tan, 2008.
3. "Geotechnical and Foundation Engineering: Design and Construction", by Robert W. Day, 1999.
4. "Maps of Known Active Fault Near-Source Zones in California and Adjacent Portions of Nevada to be
used with 1997 Uniform Building Code", Published by International Conference of Building Officials.
5. "Geologic Maps of the Northwestern Part of San Diego County, California", Department of
Conservation, Division of Mines and Geology, by Siang S. Tan and Michael P . Kennedy, 1996.
6. "Bearing Capacity of Soils, Technical Engineering and Design Guides as Adapted from the US Army
Corps of Engineers, No. 7", Published by ASCE Press, 1994.
7. "Foundations and Earth Structures, Design Manual 7.2", by Department of Navy Naval Facilities
Engineering Command, May 1982, Revalidated by Change 1 September 1986.
8. "Ground Motions and Soil Liquefaction during Earthquakes", by H.B. Seed and I.M. Idriss, 1982.
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Josh Cantor
EAST COUNTY SOIL CONSULTATION
AND ENGINEERING, INC.
10925 HARTLEY ROAD, SUITE "I"
SANTEE, CALIFORNIA 92071
TEL. 619-258-7901
4215 Hillside Drive
Carlsbad, California 92008
March 30, 2023
Project No. 21-1106G7
Subject: 2nd Response to Geotechnical Review for Proposed Garage
and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
Project No. PD2022-0022, Grading Permit No. GR2022-0031
References: 1. "Response to Geotechnical Review for Proposed Garage and Retaining Walls,
4269 Hillside Drive, Carlsbad, California 92008", Project No. 21-1106G7,
Prepared by East County Soil Consultation and Engineering, Inc., Dated
December 20, 2022.
2. "Geotechnical Investigation for Proposed garage and Retaining Walls, 4269
Hillside Drive, Carlsbad, California 92008", Project No. 21-1106G7, Prepared by
East County Soil Consultation and Engineering, Inc., Dated June 28, 2021 .
Dear Mr. Cantor:
In accordance with your request, we have prepared this second response letter to the geotechnical
review for the proposed garage addition on 4269 Hillside Drive, in Carlsbad, California.
Comments No. 1 and 2
The attached shear test results substantiate the values used for soil bearing capacity, passive
pressure, coefficient of friction and active pressure provided in the referenced geotechnical report
(Reference No. 2), including an active equivalent fluid pressure of 35 pcf for the design and
construction of the proposed retaining walls.
Comment No. 3
In addition to the necessary intermittent field observations and compaction testing recommended
in the referenced response report (Reference No. 1), requfred during site development, the
geotechnical engineer or engineer's representative should observe the excavations of temporary
slopes during grading and retaining wall construction, so additional recommendations may be
provided, if required.
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
Page2
March 30, 2023
ProjedNo. 21-1106G7
This opportunity to be of service is appreciated. If you have any questions, or we can be of
further service, please do not hesitate to call or contact us.
Respectfully Submitted,
Mamadou Saliou Diallo, P.E.
RCE 54071, GE 2704
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.
Response to Geotechnical Review for Proposed Garage and Retaining Walls
4269 Hillside Drive
Carlsbad, California 92008
6000
sooo
"'2000 5. 1000
0
C
7000
5,000
2000
1000
0
0 1000
Norm.I
.......,......._ 5tre.ss (;>sf!
........ .;.r'!
-312'
-4. e •• e ••• e e e e e • • -i091
" fi
Shur Strain f J
2000 3000 4000
~or.mi 5ne.s tpsf'
10
5000 6000 7000
~
SAMPLE ID. C tor H1lslde Dnve -Carlsbad 4> 34.
11 C 659~f
Brown Silty S.lnd Initial
NOTES Renolded
Sz~I
lOfi!.. pd
11
II~..._
S1i'nplEW115 i1nd dni.Md -4,S,.
East County Soils
A-.-I A f:!! ----,-, I .. ,,..., --ORB 0.Jte.
""5e Fpe·
Page 3
March 30, 3023
Project No. 21-1106G7
34•
524 psf
Flllal
100 pcf
177
_., .....
M.lroh.2023
EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC.