Description: B&D NUTRITIONAL: (PHASE 11) STORAGE RACKS
Applicant: Property Owner:
Tenant Improvement
RACK SUBMITTAL SERVICES
CARRIE SHARIFI
1815 WRIGHT AVE
APG CARLSBAD I LLC RAF PACIFICA GROUP
1010 S COAST HIGHWAY 101, # 103
ENCINITAS, CA 92024-5002
LA VERNE, CA 91750-5817
(626) 384-0481
FEE
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
FIRES Occupancies< 50,000sq. ft. Tl
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $1,689.87 Total Payments To Date: $1,689.87
Permit No:
Status:
(City of
Carlsbad
CBC2021-0008
Closed -Finaled
Applied: 01/08/2021
Issued: 05/11/2021
Finaled Close Out: 12/15/2023
Fina I Inspection: 12/14/2023
INSPECTOR: Kersch, Tim
Balance Due:
AMOUNT
$668.60
$468.02
$89.00
$373.00
$5500
$5.00
$31.25
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
(City of
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Plan Check~= {)IJO!f
Est. Value ~~ _-
PC De posit ----r----+----
Date _l'+-/..-f/,_,_,~::...__,;_J __
Job Address JJ' '7d luA<:f'_-hul. i~p.pE . Suite:. ___ / __ (;_z~APN: _______ _
Tenant Name: /J f j) N, tln·hrnr1J //J l@,,t fl) Lot#:
Year Built: ____ Occupancy: ___ _ C t ct• T f" s • kl RJ□'A/C DD ons ru 10n ype:;..." ----Ire prin ers: yes no : yes no
BRIEF DESCRIPTION OF WORK:
J; 11 slc-1/::,f,,-Yl tr/1s+vY.J f<'-r Lal.$
D Addition/New: _________ New SF and Use,. __________ New SF and Use,
___ Deck SF, Patio Cover SF (not including flatwork)
Jirenant Improvement: &, '-/00 SF,
____ SF,
Existing Use. _____ Proposed Use tVanfit;JI.Jl.,
Existing Use Proposed Use _____ _
D Pool/Spa: ____ SF Additional Gas or Electrical Features? __________ _
□ □□ □□ □□ Solar:. ___ KW, __ Modules,, ___ Mounted, Tilt: Yes/ No, RMA: Yes/ No, Panel Upgrade: Yes/ No
D Plumbing/Mechanical/Electrical Only: -----------------------
~ Othe~:
.Shn~ ,___, __ tlu
This permit is to be issued in the name of the Property Owner as Owner~Builder, licensed contractor or Authorized Agent of the
owner or contractor. The person fisted as the Applicant below will be the main point of contact throughout the permit process.
1635 Faraday Ave Carlsbad, CA 92008
B-2
Ph: 760-602-2719 Fax: 760-602-8558
Page 1 of2
Email: BuHding@carlsbadca.gov ~
Rev. 08/20 ~ ~
ID!:'NTlFV WHO WJU PUffORM nff WOW( B\' (OfV!PLI TlNr, (Ol'rnlN A) Oil TlOI\I ii) 111 /0\i\/
(OPTJON A): IJ(i:r-J'.>ED C:ONT~f\{E?f? D[CU\H/\llfJN:
with Section I hereby flJjfrm under µermlty of perjury that I am JiCPnsed under provmons of Clwpter 9
7000) of Dwision 3 of the Business and Professions Code1 ond my license ism full forr.e and
penalty of petjury one of the following declaration,;
I ulsD a/firm vodcr
[] I hav,i and will maintai!l ,.nen,f,rnte oi coose11t u,;;elf-lm,u« Im wm>ers' wmpensallon provltle'1 h, \,:•ct""' .1, :x, nf the lalmr C"de, fa,r i I"' ,,,.ff,.,rn,,:1, nl
th!? wo,k whirh lhu, parnm ,; '"ued. l'oU,v No.---······ ------· ..... . . ,_. __ ... .,_, __ ,,_, _____ ...
[J l have a1Hi w\ll maintain work,•r', rornp~n~~tkm, ~s r,~qt11red l,y ',en1on :JJOO of the Lahor Code. fm (r,e fl(l /(11n,,i,;r" ()/ u,~ worl< for wrw.l, n.1:. 1.,, rrr•,1 i:, ,1.,u.-rl
My worker\' compensation insurance ,Mrier MIO policym,mber ~re: lnsuram:eComp;iny Name:~-----,--·•~·~···'-·"'···••·-------
Pollcy No. ___ .. -•-·" .... ____ ,,, ___ ····--. _ .... ,,...... . . ···--· ... _____ Expl ration Oate· , __ ..... ··-·-·----,,. " , . . ..... ···-· ........... ,,.·--·
1(lcertifirate ol fNemptlon: I cerllfy that i11 \he p~rfotnld!l{C of lh!> work for which (hi~ permit is is$,1l'd, I .,ha!! not employ ~nv per,m, In ,rnv n,ilnne, i,o "' to
bewme suhJed to the workers' compe11sation laws of CaJifomi~. WARNING; falfure to secure workers compensation mvor ag<'. 1, unlawrot ;,nd ~hall subject an
cmplover to crlmfnal penalties and dvll lines up to $100,000.00, in addition the to the cost of wmpen~11tlon, <1,,111<1ge< ;;s I,rnvlded io, in Se.lion 37()6 or !11;,
labor Code, Interest ;md aHorney's re!!s.
CONSTRUCTION LENDING AGENC'1':1Jr: /\f,l'(:
I hereby affirm that there is a cMstm,:tion lending illJl!IICY for the (}e/lorm,mce of the work this permit" i"""d iSer: 3097 /i) (ivil Cntlel.
Lender's Name: _______ ,,--_____ ,.,,.. ____ ~_tenrler's Address: -----· --···----·
CONTRACTOR PRINT: (:;Jovj/;;J ftl~rf) siGN]> ~ _OATE: '!flfifl'_;>~ _
(OPTION 8): OWNER-BUH.DER DECLARATION: --:;;,)
I hereby affirm that I am exempt from Conttllctor', Uc;me·Law for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the wucture i, not ,ntended or offered for sale !Set
7044, Business and Professions Code: The Contractor's License Law does not apply to an ownl'f of property who build; or impruve, ther€on, and who does such
work hlmself or through his own employees, provided thill such Improvements are not Intended or offered !or $ale. If, however, the buildin~ rn •mprnv.:mert is
sold within one yeilrof completion, the owner-bullderw!U have the burden of proving that he did not build or irnprcwe for the purpose of ;,;,1,,1
0 I, as owner crthe property, am el!'duslve!y contracting wlth licensed contractors to construct the project (Ser. 7044, Business and ProliissiDns Cude 'iii('
ContnctOr's License law does not apply to an owner of property who builds or ,mprnvH thereon, and contr.icts tor suth projects with umHM.to, 1,1
lieensed pursuant lo the Contractor's License Law),
0 I arn el!'empt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
0 "OWner Builder acknowledgement and verification form~ has been filled out, signed and alta(hed to this <lpplitatlon. Proof of ldentilkation attadrnd.
0 owner.s "Atithorl.red ~•mt Form" has been filled out, signed and attached to this application giving th£' H/Jert! 1,111(/;ority to obtain tlae µermil '-'" 11,e nvncr· h•l1alf.
Proof of Identification attached.
By my signature below I acknowledge that, e~cepl for my personal resldence in which I must have resided for ;,t tea,t ('ne year prior to t()Jnpte!lc>11 ul l ,,,,
iml)fovements covered by this permit, I cannot legally sell a stwcture 1hat I have buUt as an owner,builder if 11 h~~ not been construc,te<i In ,,,, ,•nt.!,ctv bv Ii, ,•n•,cd
contractors. I understand that a copy of tM app{lcable law, Stction 7044 of the Business lllld Profe5slons Code, is available upon reque,t whell t l!i:s npplirnr1M 11
subrnltt11d or at the fellowing Web site: http://wwW.leglnfo.co.gov/calaw.html.
OWNER PRINT: __________ _ SIGN: ________ DATE: _____ _
APPLICANT CERTIFICATION: SIGNATURE REQUIRED AT THF. T~!YJE OF SUBMITTAL
By my signature below, I r:ertffy thut: I am the property owner or State of California licensed Contractor or authorized to uct on the property
owner or contractor's behalf. I certify that I have read the application and state that the above Information is correct and that the
Information on the plans Is accurate. I agree to comply with all City ordinances and State lows relating to building tonstruwon.
I hem,y authorize R!presentative of the Oty of Cmlsbad to enter upon the obovt! mentioned property for inspl!!dlon purposes I ALSO AGREE TO SAVt:
INDEMNIFY AND KEEP HARMLESS THE CTTY OF CARLSBAOAGAINSr ALL LIABILJT/ES, JUOGMENTS, 00S~ ANO EXP£NSf.S WHICH MAY IN ANY WAY
A«JIVE AGAINSTSAIO ar'I IN OONSEQUENCE OF THE GRANTING OF THIS PERMIT. OSHA: An OSHA permit Is required for excovot1ons over 5'0'
deep and dsnolltfon or construction of .structures over 3 stories In helgShfGr. N:c~-~ 'O·,.A\.TE:
APPLICANT PRINT: {hccK, ftwa,fi ~ ~-------
'-....,,,c ... x::::::=:~--_.,....,,..•
1635 Faraday Ave Carlsbad, CA 92008
B-2
Ph: 760-602·2719 Fax: 760-602~8558
Page2 of 2
Email: Bulldlng@carfsbadca,sov
Re-v. 08/20
Building Permit Inspection History Finaled
(city of
Carlsbad
PERMIT INSPECTION HISTORY for (CBC2021-0008)
Permit Type; BLDG-Commercial
Work Class: Tenant Improvement
Status: Closed -Finaled
Scheduled Actual Inspection Type
Date Start Date
03/30/2022 03/30/2022 BLDG-14
Frame/Steel/Bolting/We
lding (Decks)
Checklist Item
Application Date: 01/08/2021 Owner; APG CARLSBAD I LLC RAF PACIFICA
GROUP
Issue Date: 05/11/2021 Subdivision: CARLSBAD TCT#97-13-02
Expiration Date: 09/26/2022
IVR Number: 30915
Inspection No. Inspection
Status
179343-2022 Passed
COMMENTS
Address: 2870 WHlPTAIL LOOP, # 107
CARLSBAD, CA 92010-6710
Primary Inspector Reinspection Inspection
Tim Kersch Complete
Passed
BLDG-Building Deficiency Yes
12/14/2023 12/14/2023 BLDG-Final Inspection 233854-2023 Passed Tim Kersch Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
Friday, December 15, 2023 Page 1 of 1
✓. EsG1I
DATE: 1-27-2021
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2021-0008
PROJECT ADDRESS: 2870 Whiptail Loop East
SETI
PROJECT NAME: B & D Nutritional-Phase II Storage Racks
□ APPLICANT
□ JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: _ l/1) Telephone#:
Date contacted: (~) Email:
Mail Telephone Fax In Person
0 REMARKS:
By: Erich A. Kuchar, P.E. Enclosures:
EsGil
1-12-2021
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Structural
Engineering
0
DJ
0
N
0
N
~ N 0 I <D 0 ..........
0 aiN _o
O N-->
00
00 NO -->O
tt Design, Inc
CITY
1815 Wright Ave
La Verne, Ca. 91750
Tel 909-596--1351 Fax 909-596-7186
Prqject Name : B/tD NUiRITIONAL INGREDIENiS, INC.
Prqject Number : SED-120220-14
Date : 12/10/20
Street Address: 2870 WHIPi AIL LOOP, SUliE 107
City/State : CARLSBAD, CA 92010
Scope of Work: SiORAGE RL\CKS
DEC 3 0 2020>
Structural
Engineering & Design Inc.
1815 Wright Aye La Verne CA 91750 Jet 909,596.1351 fax· 909 596,7186
By: Bob S Project: B&D Nutritional Ingredients Inc
TABLE OF CONTENTS
Title Page ............................................................................................................ . 1
Table of Contents................................................................................................... 2
Design Data and Definition of Components.......................................................... 3
Critical Configuration ............................................................................................. 4
Seismic Loads ....................................................................................................... 5 to 6
Column ................................................................................................................ . 7
Beam and Connector .... .. ...... ... .. . .. ...... ....... ... .. .... .. .. ........ .... ........... ..... .. .. .... ... ... .... 8 to 9
Bracing ................................................................................................................ .
Anchors ............................................................................................................... .
10
11
Base Plate ............................................................................................................. 12
Slab on Grade ....................................................................................................... 13
Type C Select-B*-D.xls Paqe 2. of l 3
Project#: 120220-14
I 2/8/2020
Structural
Engineering & Design Inc.
1815 Wright Ave La Verne CA 91750 Tel: 909 5961351 Fax: 909 596 7186
By: Bob S Project: B&D Nutritional Ingredients Inc Project#: 120220-14
Design Data
1) Toe analyses herein conforms to the requirements of the:
2018 /BC Section 2209
2019 CBC Section 2209
ANSI MH 16.1-2012 Specifications for the Design of lndustn'al Steel Storage Racks "2012 RMI Rack Design Manual"
ASCE 7-16, section 15.5.3
2) Transverse braced frame steel conforms to ASTM A570, Gr.55, with minimum strength, Fy=55 ksi
Longitudinal frame beam and connector steel conforms to ASTM A570, Gr.55, with minimum yield, Fy=55 ksi
All other steel conforms to ASTM A36, Gr. 36 with minimum yield, Fy= 36 ksi
3) Anchor bolts shall be provided by installer per ICC reference on plans and calculations herein.
4) All welds shall conform to AWS procedures, utilizing E70xx electrodes or similar. All such welds shall be performed
in shop, with no field welding allowed other than those supervised by a licensed deputy inspector.
5) Toe existing slab on grade is 6" thick with minimum 3000 psi compressive strength. Allowable Soil bearing capacity is 750 psf.
The design of the existing slab is by others.
6) Load combinations for rack components correspond to 2012 RMI Section 2.1 for ASD level load criteria
Definition of Components
Frame
Height
A
ri Beam
~=::tl:=/== ·===fl=t======ti=~
Beam
length
Beam
~
Front View: Down Ai;~
(Lonqitudm-a1) Frame
Type C Select-BtD.xls
Cbunn
Beam to Oibm
Cbnnectll<
Base J:bte and
Anchor.;
Section A: Ooss Aisle
(TranS>Jer5e ) Frame
Paqe S of I~
fbizontal
e-aoe
Clagonal
9-aoe
12/8/2020
Structural
Engineering & Design Inc.
1815 Wright Aye La Verne, CA 91750 Tel· 909.5961351 Fax· 909 596.71 86
By: Bob S Project: B&D Nutritional Ingredients Inc Project #: 120220-14
Configuration & Summary: Type C Selective Rack
T
78"
t
50" 228" t-228"
50"
+
50"
I
T
48"
+·l-----i
48" + 48" + 36" + 36" +
**RACK COLUMN REAC71ONS
ASDLOADS
AXIAL DL == 100 lb
AXIAL LL== 8,200 lb
SEISMIC AXIAL Ps==+/-5,227 lb
BASE MOMENT== 8,000 in-lb
✓-r --108" -------t
Seismic Criteria
Ss=0.923, Fa=l
Component
Column
Column & Backer
Beam
Beam Connector
Brace-Horizontal
Brace-Diagonal
Base Plate
Anchor
Slab & Soil
Level I Load**
1
2
3
4
Per Level
4,100 lb
4,100 lb
4,100 lb
4,100 lb
# Bm Lvls
4
Fy=55 ksi
None
Fy=55 ksi
Fy=55 ksi
Fy=55 ksi
Fy=55 ksi
Fy=36 ksi
2 per Base
Beam Spcg
50 .0 in
50.0 in
50.0 in
78.0 in
** Load defined as product weight per pair of beams
Notes !Sgl & Dbl Row Units ok.
Type C Seiect-B.t-D.xls
Frame Depth Frame Height # Diagonals Beam Length Frame Type
42 in 228.0 in 5 108 in Single Row
Description
Hannibal IF3013-3x3xl3ga P=8300 lb, M=17827 in-lb
None None
HMH 44160/4.5" Face x 0.057" thk Lu=108 in I Capacity: 5103 lb/pr
Lvl 1: 3 pin OK I Mconn= 13363 in-lb I Mcap=15230 in-lb
Hannibal 1-1/2x 1-1/2x16ga
Hannibal 1-1/2x1 -1/2x16ga
8x5x3/8 I Fixity= 8000 in-lb
0.5" x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=2196 lb)
6" thk x 3000 psi slab on grade. 750 psf Soil Bearing Pressure
Brace
36.0 in
36.0 in
48.0 in
48.0 in
48.0 in
Total:
I Story Force I Story Force
Transv Lon git.
163 lb
3261b
489 lb
743 lb
1,721 lb
104 lb
208 lb
312 lb
475 lb
1,099 lb
Page ~ of \ !>
Column
Axial
8,300 lb
6,225 lb
4,150 lb
2,075 lb
I Column I
Moment
17,827 "#
12,436 "#
9,835 "#
9,255 "#
Conn.
Moment
13,363 "#
10,566 "#
9,452 "#
6,010 "#
STRESS
0.75-OK
N/A
0.8-OK
0.88-OK
0.23-OK
0.36-OK
0.85-OK
0.517-OK
0.79-OK
Beam
Connector
3 pin OK
3 pin OK
3 pin OK
3 pin OK
12/8/2020
Structural
Engineering & Design Inc.
1815 Wright Aye La Verne CA 91750 Tel: 909.596.1351 Fax· 909 596.7186
By: Bob S Project: B&D Nutritional Ingredients Inc
Seismic Forces Configuration: Type C Selective Rack
Lateral analysis is performed with reoard to the requirements of the 2012 RMI ANSI MH 16.1-2012 Sec 2.6 & ASCE 7•16 sec 15.5.3
Transverse (Cross Aisle) Seismic Load I
V= Cs*Ip*Ws=Cs*Ip*(0,67*P*Prf+D) • Vt
Csl: ~~:~~8 Cs-max* Ip= 0.1538 • :~'
Cs2= 0.044*Sds Vm1n= 0.015
= 0.0271 Eff Base Shear=Cs= 0.1538 Transvme Elevation
Cs3= O.S*S1/R Ws= (0.67*P'-RF1 * PL)+DL (RMI 2.6.2)
= 0.0425 ____ =_1_1.:...,1_8_8_1b ________ ~
Cs-max= 0.1538
Base Shear Coeff=Cs= 0,1538
Level PRODUCT LOAD P P*0.67*PRF1
1 4,100 lb 2,747 lb
2 4,100 lb 2,747 lb
3 4,100 lb 2,747 lb
4 4,100 lb 2,747 lb
sum: P=16400 lb 10,988 lb
Longitudinal (Downaisle) Seismic Load
Vtransv=Vt= 0.1538 * (200 lb+ 10988 lb)
Etransverse= 1,721 lb
Limit States Level Transverse seismic shear per upright
DL hi wi*hi
SO lb SO in 139,850
50 lb lOOin 279,700
50 lb 150 in 419,550
50 lb 228 In 637,716
2001b W=11188 lb 1,476,816
Project#: 120220-14
Ss= 0.923
S1 = 0.340
Fa= 1.000
Fv= 1.950
Sds=2/3*Ss*Fa= 0.615
Sd1=2/3*51 *Fv= 0.442
ca =0.4*2/3*Ss*Fa= 0.2461
(Transverse, Braced Frame Dir.) R; 4.0
Ip= -~-0 .· ... PRFI= :J:O•',:, • '.: ·-
Pallet Helght=hp= 48.0 in
DL per Beam Lvl= 50 lb
Fi Fi* hi+hp/2)
163.0 lb 12,062-#
325.9 lb 40,412-#
488.9 lb 85,069-#
743.2 lb 187,286-#
1,721 lb 1=324,829
Similarly for longitudinal seismic loads, using R;6,0 Ws= (0.67 * P'-RF2 * P) + DL PRF2= 1.0
Csl=Sdl/(T*R)= 0.0982
Cs2= 0.0271
Cs3= 0.0283
Cs-max= 0.0982
Level PRODUC LOAD P
1 4,100 lb
2 4,100 lb
3 4,100 lb
4 4,100 lb
= 11,188 lb (Longitudinal, Unbraced Dir.) R; 6.0
... es_=_Cs_-m_a_x_*I..,_p_=_0_.0_9_8_2 ______________ T;-,Q.75 sec
Vlong= 0.0982 * (200 lb+ 10988 lb)
Elongitudinal= 1,099 lb
P*0.67*PRF2 DL
2,747 lb 50 lb
2,747 lb 50 lb
2,747 lb 50 lb
2,747 lb 50 lb
Limit States Le-.,e/ Longlt. seismic; shear per upright
hi
SO in
100 In
l SOin
228 in
wi*hi
139,850
279,700
419,550
637,716
Fi
104.1 lb
208.1 lb
312.2 lb
474.6 lb
Ftont View
sum: =======1=0=9=8=8=1b=====2=0=0==1b======W===l=l=l=88::::::::lb====l :::47==6::t:8=1=6========1 =0=99:::::::lb========
Type C 5elect-Bt0 .xls Page ✓S-of \ ~ 12/8/2020
Structural
Engineering & Design Inc.
1815 Wright Aye La Verne CA 91750 Tei· 909 5961351 Fax· 909,596.7186
By: Bob S Project: B&D Nutritional Ingredients Inc
Downaisle Seismic Loads Configuration: Type C Selective Rack
Determine the story moments by applying portal analysis. The base plate is assumed to provide partial fixity.
Seismic Story Forces
Vlong= 1,099 lb
Vcol=Vlong/2= 550 lb
Fl= 104 lb
F2= 208 lb
F3= 312 lb
Seismic Story Moments
Typical fume made
Tnbutiry ,tea o( two columns
oF ,,ck Ii.me '--,.,., ___ _
... ~ ~ t;;;~~~1 : ~~~~~:':' +===-==+==:...,,_:==-l-==~==-l-
~
Conceptual System
Project#: 120220-14
Typical F,ame made
~ of two column,:
~
Mbase-max= 8,000 in-lb
Mbase-v= (Vcol*hleff)/2
< = = = Default capacity hl-eff= hl -beam clip height/2
= 47 in
= 12,913 in-lb <=== Moment going to base
Mbase-eff= Minimum of Mbase-max and Mbase-v
= 8,000 in-lb
M 1-1 = [Vcol * hleff]-Mbase-eff
= (550 lb * 47 in)-8000 in-lb
= 17,827 in-lb
Mseis= (Mupper+Mlower)/2
Mseis(l-1)= (17827 in-lb+ 12436 in-lb)/2
= 15,131 in-lb
LEVEL hi Axial Load
1 50 in 8,300 lb
2 50 in 6,225 lb
3 SO in 4,150 lb
4 78 in 2,075 lb
M 2-2= [Vcol-(Fl)/2] * h2
= [550 lb -104.1 lb]*SO in/2
= 12,436 in-lb
Mseis(2-2)= (12436 in-lb+ 9835 in-lb)/2
= 11,136 in-lb
Summary of Forces
Column Moment** Mselsmic** Mend-fixity
17,827 in-lb 15,131 in-lb 3,958 in-lb
12,436 in-lb 11,136 In-lb 3,958 in-lb
9,835 in-lb 9,545 in-lb 3,958 in-lb
9,255 in-lb 4,627 in-lb 3,958 in-lb
Mconn = (Mseismic + Mend-fixity)*0.70*rho
Mconn-allow(3 Pin)= 15,230 in-lb
**all moments based on limit states level loading
Type C Select-BtD.xls
h2
h1
Beam to Column
Elevation
rho= 1.0000
Mconn** Beam Connector
13,363 in-lb 3 pin OK
10,566 In-lb 3 pin OK
9,452 in-lb 3 pin OK
6,010 in-lb 3 pin OK
12/8/2020
COL
Structural
Engineering & Design Inc.
1815 Wright Ave La Verne CA 91750 Jel· 909 5961351 Fax: 909.596 7186
By: Bob S Project: B&D Nutritional Ingredients Inc Project #: 120220-14
Column (Longitudinal Loads) Configuration: Type C Selective Rack
Section Properties
Section: Hannibal IF3013-3x3x13ga
Kx = 1.7
r3,00:in7
'
Aeff = 0.757 in"2
Ix = 1.320 in"4
Sx = 0.879 in"3
rx = 1.320 in
Qf= 1.67
Iy = 0.871 in"4
Sy = 0.574 ln"3
ry = 1.080 in
Fy= 55 ksi
Lx = 47.8 in
Ky = 1.0
Ly = 36.0 in
Cb= 1.0
y-. -. r . -. --y 3.000 in
Cmx= 0.85
E= 29,500 ksi
Loads Considers loads at level 1
COLUMN DL= 100 lb Critical load cases are: RMI Sec 2.1
10,090 in
JI:
~0.75in
_j_
COLUMN PL= 8,200 lb Load Case 5:: (1+0.105*Sds)D + 0.75*{1.4+0.14Sds)*B*P + 0.75*{0.7*rho*E)<= 1.0, ASD Method
Meal= 17,826 in-lb axial load coeff: 0.78022455 * P seismic moment coeff: 0.5625 * Meo!
Sds= 0.6153 Load Case 6:: (1 +0.14*Sds)D + (0.85+0.14Sds)*B*P + (0.7*rho*E)<= 1.0, ASD Method
1+0.105*Sds= 1.0646 axialload coeff: 0.65530 seismic moment coeff: 0.7 * Meo/
l.4+0.14Sds= 1.4861 By analysis, Load case 6 governs utilizing loads as such
1+0.14Sds= 1.0861
Moment=Mx= 0.7*rho*Mcol 0.85+0.14*Sds= 0.9361
B= 0.7000
Axial Load=Pax= 1.086142*100 lb+ o.936142*0.1•8200 lb
= 5,482 lb = 0.7 * 17826 in-lb
rho= 1.0000
Axial Analysis
Kxlx/rx = 1.7*47.75"/1.3196"
= 61.5
Fe= n" 2E/(KL/r)max" 2
= 76.9ksi
Pn= Aeff*Fn
= 34,195 lb
P/Pa = 0.31 > 0.15
Bending Analysis
KyLy/ry = 1 *36"/1.08"
= 33.3
Fy/2= 27.5 ksi
Qc= 1.92
Check: Pax/Pa + (Cmx*Mx)/(Max*µx) ::S 1.0
P/Pao + Mx/Max ::S 1.0
Pno= Ae*Fy
= 0.757 in"2 *55000 psi
= 41,635 lb
Pao= Pno/Qc
= 416351b/1.92
= 21,685 lb
= 12,478 in-lb
Fe > Fy/2
Fn = Fy(Hy/4Fe)
= 55 ksi*[l-55 ksi/(4*76.9 ksi)]
= 45.2 ksi
Pa= Pn/Qc
= 34195 lb/1.92
= 17,810 lb
Myield=My= Sx*Fy
= 0.879 in"3 * 55000 psi
= 48,345 in-lb
Max= My/Qf Per= n" 2EI/(KL)max" 2
= 48345 in-lb/1.67
= 28,949 in-lb
µx= {1/[1-(Qc*P/Pcr)]}"-1
= {1/[1-(1.92*5482 lb/58325 lb)]}"-1
= 0.82
Combined Stresses
= n"2*29500 ksi/(l.7*47.75 in)"2
= 58,325 lb
(5482 lb/17810 lb)+ (0.85*12478 in-lb)/(28949 in-lb*0.82) =
(5482 lb/21685 lb) + (12478 in-lb/28949 in-lb) =
0.75
0.68
< 1.0, OK
< 1.0, OK
(EQ C5-1)
(EQ CS-2)
** For comparison total column stress computed for load case 5 is: 71. 0% nq loads 6504.30196 lb Axial and M= 9358 1i1-/b
Type C Select-BtD.xls Page ( of \) 12/8/2020
Structural
Engineering & Design Inc.
1815 Wcigbt Ave La Verne CA 91750 Tel· 909 596 1351 fax· 909 596.7186
By: Bob S Project: B&D Nutritional Ingredients Inc
BEAM Contiguratlon: Type C Selective Rack
DETERMINE ALLOWABLE MOMENT CAPACITY
Al Check compression flange for local buckling (82.1}
w= c -2*t -2*r
= 1.75 in -2*0.057 in -2*0.057 in
= 1.522 in
w/t= 26.7
l=lambda= (1.052/(k)"0.5] * (w/t) * (Fy/E)"0.5
= [1.052/(4)"0.5] * 26.7 * (55/29500)"0.5
= 0.606 < 0.673, Flange is fully effective
Bl check web for local buckling per section b2.3
fl(comp)= Fy*(y3/y2)= 50.90 ksi
f2(tension)= Fy*(yl/y2)= 102.67 ksi
Y= f2/fl
= -2.0 17
k= 4 + 2*(1-Y)"3 + 2*(1-Y)
= 64.96
flat depth=w= yl+y3
Eq. 82.3-5
Eq. 82.3-4
Eq. B2.1-4
Eq. 82.1-1
= 4.272 in w/t= 74.94736842 OK
l=lambda= [l.052/(k)"0.5] * (w/t) * (fl/E)"0.5
= (1.052/(64.96)"0.5] * 4.272 * (50.9/29500)/\0.5
= 0.406 < 0.673
be=w= 4.272 in
bl= be(3-Y)
= 0.852
b2= be/2
= 2.14 in
bl +b2= 2.992 in > 1.416 in, Web is fully effective
Determine effect of cold working on steel yield point {Fya) per section A7.2
Fya= C*Fyc + (1-C)*Fy (EQ A7.2-1)
Lcomer=Lc= (p/2) * (r + t/2)
0.134 in
Lflange-top=Lf= 1.522 in
m= 0.192*(Fu/Fy) -0.068
= 0.1590
C= 2*Lc/(Lf+2*Lc)
= 0.150 in
(EQ A7.2-4)
Be= 3.69*(Fu/Fy) -0.819*(Fu/Fy)/\2 -1.79
= 1.427
since fu/Fv= 1.18 < 1.2
and r/t= 1 < 7 OK
then Fye= Be* Fy/(R/t)"m
= 78.485 ksi
(EQ A7.2-2)
Thus, Fya-top= 58.52 ksi (tension stress at top)
Fya-bottom = Fya*Ycg/(depth -Ycg)
= 113.59 ksl (tension stress at bottom)
Check allowable tension stress for bottom flange
Lflange-bot=Lfb= Lbottom -2*r*-2*t
= 2.522 in
Cbottom=Cb= 2*Lc/(Lfb+2*Lc)
= 0.096
Fy-bottom=Fyb= Cb*Fyc + (1-Cb)*Fyf
= 57.26 ksl
Fya= (Fya-top)*(Fyb/Fya-bottom)
= 29.50 ksi
Eq 82.3-2
(EQ A7.2-3)
if F= 0.95 Then F*Mn=F*Fya*Sx= I 23.79 in-k
Project#: 120220-14
2.75 In
t5in 4
T
4.500 in
1.625 In
_J_
1~ 0.057 In
----------
Beam= HMH 44160/4 5" Face x O 057" thk
y1
Ix= 2.009 in"4
Sx= 0.849 in"3
Ycg= 2.970 in
t= 0.057 in
Bend Radius=r= 0.057 in
Fy=Fyv= 55.00 ksi
Fu=Fuv= 65.00 ksi
E= 29500 ksi
top flange=b= 1.750 in
bottom flange= 2.750 in
Web depth= 4 c:nn ;~
__:; Fy -
yl= Ycg-t-r= 2.856 in
y2= depth-Ycg= 1.530 in
y3= y2-t-r= 1.416 in
'Structural
Engineering & Design Inc.
1815 Wright Ave La Verne. CA 91750 Tel· 909 596 1351 Fax· 909 596 7186
By: Bob S Project: B&D Nutritional Ingredients Inc
BEAM Contiguration: Type c Selective Rael<
RMI Section 5.2, PT II
Section
Beam= HMH 44160/4.5" Face x 0.057" thk
Ix=Ib= 2.009 in"-4
Sx= 0.849 in "-3
t= 0.057 in
Fy=Fyv= 55 ksi
Fu=Fuv= 65 ksi
Fya= 58.5 ksi
E= 29500 ksi
F= 300.0
L= 108 in
Beam Level = 1
P=Product Load= 4,100 lb/pair
D=Dead Load= SO lb/pair
1. Check Bending Stress Allowable Loads
Mcenter=F*Mn= W*L *W*Rm/8
W=LRFD Load Factor= 1.2*D + 1.4*P+1.4*(0.125)*P
FOR DL=2% of PL,
W= 1.599
Rm = 1 -[(2*F*L)/(6*E*lb + 3*F*L)]
RMI 2.2, item 8
1 -(2*300*108 in)/[(6*29500 ksi *2.009 in"-3)+(3*300*108 in)]
= 0.857
if F= 0.95
Then F*Mn=F*Fya*Sx= 47.20 in-k
Thus, allowable load
per beam pair=W= F*Mn*8*(# of beams)/(L *Rm*W)
= 47.2 in·k * 8 * 2/(108in * 0.857 * 1.599)
= 5,103 lb/pair allowable load based on bending stress
Mend= W*L *(l-Rm)/8
= (5103 lb/2) * 108 in * (1-0.857)/8
= 4,926 in-lb @ 5103 lb max allowable load
= 3,958 in-lb @ 4100 lb imposed product load
2. Check Deflection Stress Allowable Loads
Dmax= Dss*Rd
Rd = 1 -(4*F*L)/(S*F*L + l O*E*Ib)
= 1 -(4*300*108 in)/[(5*300*108 in)+(10*29SOO ksi *2.009 in"-4)]
= 0.828 in
if Dmax= L/180 Based on l/180 Deflection Criteria
and Dss= 5*W*L "'3/{384*E*Ib)
L/180= 5*W*L"'3*Rd/(384*E*Ib*# of beams)
solving for W yields.
W= 384*E*I*2/(180*5*L "2*Rd)
= 384*2.009 in"4*2/[180*5*(108 in)"2*0.828)
= 5,237 lb/pair allowable load based on deflection limits
Project#: 120220-14
2.75 In
tSin +
1 T 1.625 in
4,500 In
_j_
1~ 0.057 in
111111111111II1111111111111111111111 1111111111 t =-=tle==========;ti:::
"' ..
Beam
Length
Allowable Deflection= L/180
= 0.600 in
Deflection at imposed Load= 0.482 in
....
Thus, based on the least capacity of item 1 and 2 above: Allowable load= 5,103 lb/pair
Imposed Product Load= 4,100 lb/pair
Beam Stress= 0.8 Beam at Level 1
Structural
Engineering & Design Inc.
1815 Weight Ave I a Verne CA 91750 Te!· 909 596 1351 fax· 909 596 Z186
By: Bob S Project: B&D Nutritional Ingredients Inc Project#: 120220-14
3 Pin Beam to Column Connection Type C Selective Rack
I he beam end moments shown herein show the result of the maximum induced hxed end monents form seIsmIc + stabc loads and the code
mandated minimum value ot l.5%(DL+PL)
Mconn max= (Mseismic + Mend-fixity)"'0.70"'Rho
= 13,363 in-lb Load at level 1
Connector Type= 3 Pin
Shear Capacity of Pin
Pin Diam= 0.44 in
Ashear= (0.438 in)"2 * Pi/4
= 0.1507 in"2
Pshear= 0.4 * Fy * Ashear
= 0.4 * 55000 psi* 0.1507in"2
= 3,315 lb
Bearing Capacity of Pin
tcol= 0.090 in
Omega= 2.22
Fy= 55,000 psi
Fu= 65,000 psi
a= 2.22
Pbearing= alpha * Fu "' diam " teal/Omega
= 2.22 "' 65000 psi "' 0.438 in * 0.09 in/2.U
= 2,562 lb < 3315 lb
Moment Capacity of Bracket
Edge Distance=E= 1.00 in Pin Spacing= 2.0 in
C= Pl+P2+P3 tclip= 0.18 in
= Pl +Pl *(2.5"/4.S")+Pl *(0.5"/4.5")
= 1.667 * Pl
Mcap= Sclip * Fbending
= 0.127 in"3 * 0.66 * Fy
= 4,610 in-lb
Pclip= Mcap/(1.667 * d)
C*d= Mcap = 1.667
= 4610.1 in-lb/(1.667 * 0.5 in)
= 5,531 lb
Thus, Pl= 2,562 lb
Mconn-allow= [Pl *4.S"+Pl *(2.5"/4.5")*2.5"+Pl *(0.5"/4.5")*0.S"]
= 2562 LB*[4.5"+(2.5"/4.5")*2.5"+ (0.5"/4.5")*0.5"]
= 15,230 in-lb > Mconn max, OK
Type C Select-B-iD .xis Page C\ of \ ?,
----,.--
1··
I
2"
Fy= 55,000 psi
Sclip= 0.127 in"3
d= E/2
= a.so in
rho= :PQOO:
12/8/2020
Structural
Engineering & Design Inc.
1815 Wright Ave La Verne. CA 91750 Tel· 909.596.1351 fax· 909 596 7186
By: Bob S Project: B&D Nutritional Ingredients Inc Project #: 120220-14
Transverse Brace Configuration: Type C Selective Rack
Section Properties
Diagonal Member= Hannibal 1-l/2xl-1/2x16ga
Area= 0.273 in"2
r min= 0.496 in
Fy= 55,000 psi
K= 1.0
.Qc= 1.92
Frame Dimensions
Diagonal Member
Bottom Panel Height=H= 48.0 in
Frame Depth=D= 42.0 in
Column Width=B= 3.0 in
Horizontal Member= Hannibal 1-1/2xl-1/2x16ga
Area= 0.273 in"2
r min= 0.496 in
Fy= 55,000 psi
K= 1.0
Clear Depth=D-8*2= 36.0 in
X Brace= NO
rho = 1.00
_.a I Load Case 6:: (1J:.:l.,Q'..ilUi0!44*:t:!S.,t"Jd.fs.s)tt.tJr-:+'FTil(1vOG5.Bis'5++0.0.114:4So;d:;'S)J*l*B*P + [0.7*rho*E]<= 1.0, ASD Method
Vtransverse= 1,721 lb
Vb=Vtransv*0,7*rho= 1721 lb * 0.7 * 1
= 1,205 lb
Ldiag= [(D-8*2)"2 + (H-6")"2]"1/2
= 55.3 in
Pmax= V*{Ldiag/D) * 0.75
= 1,190 lb
Vb
(kl/r)= (k * Ldiag)/r min
= (1 x 55.3 in /0.496 in )
= 111.5 in
Fe= pi" 2*E/(kl/r)" 2
= 23,419 psi
axial load on diagonal brace member Since Fe<Fy/2,
Fn= Fe Pn= AREA*Fn
= 0.273 in"2 * 23419 psi
= 6,393 lb
Pallow= Pn/Q
= 6393 lb /1.92
= 3,330 lb
Pn/Pallow= 0.36
Horizontal brace
Vb=Vtransv*0.7*rho= 1,205 lb
(kl/r)= (k * Lhoriz)/r min
= (1 x 42 in) /0.496 in
= 84.7 in
Since Fe>Fy/2, Fn=Fy*(l-fy/4fe)
= 36,366 psi
Pn/Pallow= 0.23
<= 1.0 OK
<= 1.0 OK
Fe= pi"2*E/(kl/r)"2
= 40,584 psi
Pn= AREA*Fn
= 0.273in"2*36366 psi
= 9,928 lb
= 23,419 psi B #
Typical Panel
Confulurawn
Check End Weld
Lweld= 3.0 in
Fu= 65 ksi
tmin= 0.060 in
Weld Capacity= 0.75 * tmin * L * Fu/2.5
= 3,510 lb OK
Fy/2= 27,500 psi
Pallow= Pn/Qc
= 9928 lb /1.92
= 5,171 lb
T
l
Type C Select-BitD .xis Page \ C) of \ ~ 12/8/2020
Structural
Engineering & Design Inc.
1815 Wright Aye La Verne CA 91750 Tel: 909.596.1351 f ax· 909.596.7186
By: Bob S Project: B&D Nutritional Ingredients Inc
Single Row Frame Overturning Configuration: Type C Selective Rack
Loads
Critical Load case(s):
1) RMI Sec 2.2, item 7: (0.9-0.2Sds)D + (0.9-0.20Sds)*B*Papp -E*rho
Sds= 0.6153
(0.9-0.2Sds)= 0.7769
(0.9-0.2Sds)= 0.7769
Project #: 120220-14
Vtrans=V=E=Qe= 1,721 lb
DEAD LOAD PER UPRIGHT=D= 200 lb
PRODUCT LOAD PER UPRIGHT=P= 16,400 lb
Papp=P*0.67= 10,988 lb
Wst LCl=Wstl={0.77694*O + 0.77694*Papp*l}= 8,692 lb
B= "'1'.'""p"'"pa"":""',: • .....,.._,..,,..,,
Product Load Top Level, Ptop= 4,100 lb
DL/Lvl= 50 lb
Seismic Ovt based on E, r (Fi*hi)= 219,559 in-lb
heiqht/deoth ratio= 5 4 in
A) Fully Loaded Rack
Load case 1:
Movt= L(Fi*hi)*E*rho
= 219,559 in-lb
rho= 1.0000
Frame Depth=Df= 42.0 in
Htop-lvl=H= 228.0 in
# Levels= 4
# Anchors/Base= 2
ho= 48 o in
h=H+ho/2= 252.0 in
Mst= Wstl * Df/2
= 8692 lb * 42 in/2
= 182,532 in-lb
SIDE ELEVATION
T= (Movt-Mst)/Df
= (219559 in-lb -182532 in-lb)/42 in
= 882 lb Net Uplift per Column
I Net Seismic Uotift= 882 lb
B) Too Level Loaded Onlv
Load case 1:
0 Vl=Vtop= Cs * Ip* Ptop >= 350 lb for H/D >6.0 Movt= [Vl *h + V2 * H/2]*rho
= 0.1538 * 4100 lb = 162,413 in-lb
= 631 lb T= (Movt-Mst)/Df
Vleff= 631 lb Critical Level= 4 = (162413 in-lb -70158 in-lb)/42 in
V2=VDl.. = Cs*Ip*D Cs*Ip= 0.1538 = 2,197 lb Net Uplift per Column
= 31 lb
Mst= (0.77694*D + 0.77694*Ptop*l) * 42 in/2
= 70,158 in-lb
I Net Seismic Uolift= 2.197 lb
Anchor
Check (2) 0.5" x 3.25" Embed HILTI KWIKBOLT TZ anchor(s) per base plate.
Special inspection is required per ESR 1917.
Fully Loaded:
Top Level Loaded:
Pullout Capacity=Tcap= 1,961 lb L.A. City Jurisdiction? NO
Shear Capacity=Vcap= 2,517 lb Phi= 1
(441 lb/1961 lb)"l + (430 lb/2517 lb)"l =
(1098 lb/1961 lb)"l + (157 lb/2517 lb)"l =
Type C Select-BtD .xis Page \\ of \ }
0.40
0.62
Tcap*Phi= 1,961 lb
Vcap*Phi= 2,517 lb
<= 1.2 OK
<= 1.2 OK
12/8/2020
Structural
Engineering & Design Inc.
1815 Wright Aye La Verne, CA 91750 Tel: 909,596 1351 fax· 909 596 7186
By: Bob S Project: B&D Nutritional Ingredients Inc
Base Plate Configuration: Type C Selective Rack
Section
Baseplate= 8x5x3/8
Eff Width=W = 7.00 in
Eff Depth =D = 5.00 in
Column Width =b = 3.00 in
Column Depth=dc = 3.00 in
L = 2.00 in
a= 2.50 in
Anchor c.c. =2*a=d = 5.00 in
N= # Anchor/Base= 2
Fy = 36,000 psi
Project#: 120220-14
Plate Thickness=!= 0.375 in Downaisle Elevation
Down Aisle Loads Load Case 5:: (1+O.105*Sds)D + O.75*[(1.4+O.14Sds)*B*P + O.75*{O.7*rho*El<= 1.0, ASD Method
COLUMN DL= 100 lb Axial=P= 1.0646065 * 100 lb+ 0.75 * (1,486142 * 0.7 * 8200 lb)
COLUMN PL= 8,200 lb = 6,504 lb
Base Moment= 8,000 in-lb
1+0.105*Sds= 1.0646
Mb= Base Moment*0.75*0.7*rho
= 8000 in-lb * 0.75*0.7*rho
= 4,200 in-lb
Axial Load P = 6,504 lb Mbase=Mb = 4,200 in-lb
Axial stress=fa = P/A = P/(D*W)
= 186 psi
Moment Stress=fb = M/S = 6*Mb/[(D*B"2]
= 102.9 psi
Moment Stress=fbl = fb-fb2
= 44.1 psi
M3 = (1/2)*fb2*L *(2/3)*L = (1/3)*fb2*L"2
= 78 in-lb
5-plate = ( 1 )(t" 2)/6
= 0.023 in"3/in
fb/Fb = Mtotal/[(S-plate)(Fb)]
0.85 OK
Tanchor = (Mb-(PLapp*0.75*0.46)(a))/[(d)*N/2]
= -3,506 lb No Tension
Ml= wl"2/2= fa*L"2/2
= 372 in-lb
Moment Stress=fb2 = 2 * fb * LJW
= 58.8 psi
M2= fbl *L" 2)/2
= 88 in-lb
Mtotal = M1+M2+M3
= 538 in-lb/in
Fb = 0.75*Fy
= 27,000 psi
F'p= 0.7*F'c
= 2,100 psi
Tallow= 1,961 lb
OK
OK
Cross Aisle Loads Cr111GJt /oddc.= RMr Sec 2.1, 11em 4: r1+0.11Sc1sJa, r1,o.usosJPL •o.?s+EL •01s <• 1.0, Aso 11e1hod Check uplift load on Baseplate
EffE
Effe
Pstatic= 6,504 lb
Movt*0.75*0.7*rho= 115,268 in-lb
Frame Depth= 42.0 in
Check upli~ forces on baseplate with 2 or more anchors per RMI 7.2.2.
'When the base plate connguration consists or two anchor bolts located on either side
P=Pstatic+Pseismic= 9,249 lb
b =Column Depth= 3.00 in
L =Base Plate Depth-Col Depth= 2.00 in
fa = P/A = P/(D*W)
= 264 psi
Sbase/in = (l)(t"2)/6
= 0.023 in"3/in
fb/Fb = M/[(S-plate)(Fb)]
Pseismic= Movt/Frame Depth
= 2,744 lb
M= wl"2/2= fa*L"2/2
= 529 in-lb/in
Fbase = 0.75*Fy
= 27,000 psi
f the column and a net uplift force exists, the minimum base plate thickness
hall be determined based on a design bending moment in the plate equal
to the uplift force on one anchor times 1/2 the distance from
he centerline of the anchor to the nearest edge of the rack column"
f!rnt!Qn.
Uplift per Column= 2,196 lb
Qty Anchor per BP= 2
Net Tension per anchor=Ta= 1,098 lb
c= 2.00 in
Mu=Moment on Baseplate due to uplift= Ta*c/2
= 0.84 OK = 1,098 in-lb
Splate= 0.117 in"3
fb Fb *0.75= 0.26 OK
Type C Select-Bil-D.xls Page 12 of \.?, I 2/8/2020
Structural
Engineering & Design Inc.
1815 Wrjght Aye La Verne CA 91750 Tel · 909.596 1351 Fax· 909.596.7186
By: Bob S Project: B&D Nutritional Ingredients Inc Project #: 120220-14
Slab on Grade Configuration: Type C Selective Rack
a
t X ➔1_1-/-~-=--=--I -
SLAB ELEVATION
Baseplate Plan View
Concrete
re= 3,000 psi
tslab=t= 6.0 in
teff= 6.0 in
Soil
fsoil= 750 psf
Movt= 219,559 in-lb
Frame depth= 42.0 in
Sds= 0.615
0.2*Sds= 0.123 Base Plate
Effec. Baseplate width=B= 7 .00 in
Effec. Baseplate Depth=D= 5.00 in
width=a= 3.00 in
depth=b= 3.00 in P=B/D= 1.400
F'c/\0.5= 54.80 psi
Column Loads
DEAD LOAD=D= 100 lb per column
unfactored ASD load
PRODUCT LOAD=P= 8,200 lb per column
unfactored ASD load
Papp= 5,494 lb per column
P-seismic=E= (Movt/Frame depth)
= 5,227 lb per column
unfactored Um,t State load
B= 9;~QOO-._:.: :<~;; ·.·.-. :::C'
rho= !!Q990,:_,.\/·::; .·
Sds= 0.6153
1.2 + 0.2*Sds= 1.3231
0. 9 -0.20Sds= 0.7769
Puncture
Apunct= [(c+t)+(e+t)]*2*t
= 252.0 in /\2
Fpunctl= [(4/3 + 8/(3*p)] *,.. *(F'c/\0.5)
= 106.5 psi
Fpunct2= 2.66 * ,.. * (F'c/\0.5)
= 87.5 psi
Fpunct eff= 87.5 psi
Slab Bending
Pse=OL+PL+E= 13,547 lb
Asoil= (Pse*144)/(fsoil)
= 2,601 in/\2
x= (L-y)/2
= 17.3 in
Fb= S*(phi)*(fc)/\0.5
= 164.32 psi
Type C 5elect-B.$D.xls
midway dist face of column to edge of plate=c= 5.00 in
midway dist face of column to edge of plate=e= 4.00 in
Load Case 1) (1.2+0.2Sds)D + (l.2+0.2Sds)*B*P+ rho*E RMI SEC 2.2 EQTN s
= 1.32306 * 100 lb+ 1.32306 * 0.7 * 8200 lb + 1 * 5227 lb
= 12,954 lb
Load case 2) (0.9-0.2Sds)D + (0.9-0.2Sds)*B*Papp + rho*E RMI SEC 2.2 EQTN 1
= 0.77694 * 100 lb+ 0.77694 * 0.7 * 5494 lb+ 1 * 5227 lb
= 8,293 lb
Load Case 3) 1.2*0 + l.4*P
= 1.2*100 lb + 1.4*8200 lb
= 11,600 lb
Load Case 4) 1.2*0 + 1.0*P + 1.0E
= 13,547 lb
Effective Column Load=Pu= 13,547 lb per column
L= (Asoil)"0.5
= 51.0 in
M= w*x/\2/2
= (fsoil*x/\ 2)/( 144*2)
= 776.2 in-lb
fv/Fv= Pu/(Apunct*Fpunct)
= 0.615 < 1 OK
y= (c*e)/\0.5 + 2*t
= 16.5 in
S-slab= 1 *teff/\ 2/6
= 6.0 in"3
fb/Fb= M/(S-slab*Fb)
= 0.787 < 1, OK
RMI SEC 2.2 EQTN 1,2
AC! 318-14 Sec 5.3.1
Eqtn 5.3.le
12/8/2020