HomeMy WebLinkAbout2456 TOWN GARDEN RD; ; CBC2018-0507; Permit{City of
Carlsbad
Print Date: 10/03/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
II Dwelling Units:
Bedrooms:
Project Title:
2456 Town Garden Rd
BLDG-Commercial
2132601100
$150,000.00
Commercial Permit
Work Class: Cogen
Lot II:
Reference II:
Construction Type:
Bathrooms:
Orig. Plan Check II:
Plan Check II:
Description: VIASAT: INSTALL 19 ELECTRIC VEHICLE CHARGERS IN PARKING GARAGE
Applicant: Owner:
ARATI RANGASWAMY VIASAT INC A DELAWARE CORPORATION
858-793-4777
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
6155 El Camino Real
CARLSBAD, CA 92009
760-476--2200
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
FIRE Special Equipment (Ovens, Dust, Battery)
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $1,919.95 Total Payments To Date: $1,919.95
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/e)(actions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Permit No: CBC2018-0507
Closed -Finaled
09/05/2018
06/25/2019
10/3/2019 2:11:12PM
$0.00
$803.50
S562.45
$89.00
$417.00
S6.00
$42.00
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: □PLANNING □ENGINEERING □BUILDING OARE □HEALTH 0HAZIIATIAPCD
{ City of Blllldlng Permit Appllcatlon Plan Check No.(x(...201£;-D:YJ-1
1635 Faraday Ave., Car1sbad, CA 92008 Est. Value \~1 1 QCfJ -.
CarlsbadP--1. Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Deposit email: building@car1sbadca.gov
www.carlsbadca.gov Date %--~'"\--· \"r\ ISWPPP
JOB ADDRESS IUIIDJU'ACE•JUNffll
rPN 213 2456 Town Garden Road, Carlsbad CA 92009 -260 -02 -
CT/PROJECT# rOT# r~·· I# OF UNITS I# BEDIVNMS #BATHROOMS ,lEIWff-llAME I
CONSTR. ,_ I ooc. GROUP
1-B 5-2
DESCRIPTION OF WORK: lnclade Squa,e Feet or M'IKCw AIN{a)
INCLUDES ELECTRICAL WORK ONLY FOR PROPOSED EV CHARGERS: TOTAL OF (17) DUAL PORT ANO (2) SINGLE
PORT CHARGERS.
EXIS11N8 UIE !PROPOSED USE !GARAGE (SF) PATIOS (SF) I DECKS (SF) RREPI.ACE
I
AIR CONDITIONING IRRE SPRINKLERS
Parking Garage N/A 209,524 YESD Ne@ YESONO[Z) YES@N<O
APPLICANT NAME Arati Rangaswamy PIIOPERIY OWNER NAME ViaSat Inc. 3 'JIJ.:\"'t·APEIMD
ADDRESS ADDRESS
vening Creek Dr. Suite 12513280 Evening Creek Dr.I!!! 6155 El Camino Real
CllY STATE ZIP cnv STATE ZIP
San Diego CA 92128 Carlsbad CA 92009
PHONE !FAX PHONE rAX 858.793.4777 760.476.2200
EMAIL EMAIL
aratir@sca-sd.com bob.rota@viasat.com
DDIGN PROFESSIONAL SCA Architecture CONTRACl'OR BUS. NAME RE QJ,>ffft_ E~crl2t<:.-, /-U~_
ADDRESS ADDRESS J>o 13280 Evening Creek Dr. Suite 125 ~x 1'-t(
CllY STATE ZIP Cl1Y STATE ZIP
San Diego CA 92128 $.P'_KI:-VC .. ~cl,€--,/ CA-q, 1-J(
PHONE IFAX PHONE , IFAX 858.793.4777 6/"i•L/5-3/-63-5.S-,,-V/_.d
EMAIL EMAIL
re A. /s:tereled,,/c/:-' v~,/~, c.,......-,
1STATEUC.c 11101 STATELIC.# -f~n, r I cnv BUS. UC.#
g~ >>C'i l?u.:>5 l:?~061/0
[Sec. 7031.5 Busmess and Professions Code: Any Cl!)' or~ which requires a ~It ta construct. alter, Improve, demolish or repair any structure, Dlfor to its issuance-'-l!!so rt,qulres the applicant for such permit to file a slaned statement tnat he is licensed pursuant to the provisions of the Contrai::tDr's Lice,-Lew IChar>ter 9, commendlnl with Section 7uuu of DMsion 3 of the Business and Professions Code} or that he is mcem_P.t therefrom, and the basis for the alleged exemption. Any violation of Section 1031.5 II'/ any appllcanflor a permit subjects the appllcant to a civil penalty of not more than five hundred dollars {$500}).
WCll'kn' Companullon Declll'lllan: / helllly atlfnn !Rider penally of pe{jutyfllll of 1118 fdloVling dedelllionB: . Q I have ■nd will malnt■ln a catlllcate of canalllt lD Hlf.lnaunt forWDlktn' eompenll8lion 18 pnr,idad by Section 3700 of the Labor Code, far Iha parfonnanc:e ol lhe work for whic:h this plllfflil ii iaued.
):d_.1 hlVII and wll maintain WOiken' COIIIPIIIUllon, as IIQllired bv Section 3700 of the \abor Code. for the perfomlan~ of the work for which lhis pennil.is iuued. Mywork1111' compallllltion ilalnnca c:anter and policy
oomber818:lnauranceCo. 5EC1.-"lf'rq /f/,a.,no,r./AL :Tv,s-. La, PolicyNo. S.WG I~ 3t/S:: ElipqlionDate 7·-3/ -, c;
lblf. seclion need not be completed if the perml is for one hundred dollara ($100) or less. LI Clrllfleate of Enmpllon: I certify that In Iha petformanc:a of the work for whk:ll this permit Is Issued, I lhall not .,....iloy any pnan In any ll'IIINr ao •• to blcame subjecuo the WOlkn' COrrfle111811Dn t... of
Calllomla. WARNING: Fallun to IIICllfl ---· campanlllkln co.,. It untawful, 111d .., .. IUbJect III llllploym' to cdmlnal pllllllel ■nd clvll hi up to one hundr.i ...... d dGllus (&108,DIO), In
addition lD 1h11 -t of CCllllplllAllon, dlffllllllS ~ for n Section ,!' of lhl Labar eode, 111W and llllarMJ'• flll.
_.s CONJRACTOR SIGNATURE ,f" E, /4~:c...···---
I hMby llfflml Illa! I am mmp! tiolll Canlractor's L.icensl Law for Ille h'lowlllg 181101!: 0 I, as owner of the property or my employHS wilh wages as !heir sole compensation, \\111 do Iha work and the etnll:Wre Is not ln1ended or ollenld for sale (sec. 7044, BIIHHl88 and P!ofeeslons COde: The Conhctol's
License Law does not apply to an C7Mler ol property Who builds or Improves tllenlan, and who does 8Udl work himself or through Iii awn employaes. pnwided that IUCh impnwementa are not intended or afferad far
sale. If, however, the building or Improvement i8 BOid within 0!1B year ol completion, the owner-builder will have Iha burden of pnl'ling that he did not Ill.id or improve far IHI IJIIP088 ol sale).
□ I, as owner of Iha property, am exclu&iWly cantradlrv wilh Mcensad cantracloll to construct Iha projed (Sec. 7044, BuainlSS and Profassions Code: The Conlractor's License Law don nat apply ID III DW1111r of
property who huilds or Improves lllanlon, and COn1rads far auch projects with conlrador(s) licensed pursuant ID Iha Conlractor's License law). D I am exempt under Sadian ____ Bllllness and Profession& Code for this niaBOO:
I. I personally plan to provide Iha major labor and ma1erials for c:onslnK:lion of the PfDP08'-'d property improwment. CJves O,o
2. I (have I h8Ve not) sjgnad an application for II blllding permit for Iha praposed work.
3. I have tontracted with Iha lolloWing person (!inn) to p!D'lide Iha proposed construdion Onc:lude name addrass / phone/ conbaelar8' license oomber):
4.1 plan ID provide pol1ions of the work, but I have hired the fllllowlng person to coafdinata, aupeM88 and provide Iha mejor 'Mll1c (ild!Jde name/ addn111 /phone/ ml\raclOrS' lic.en8a numbar):
5. I will provide SOl11II of Iha work, but I have conlrBded (hired) lhe fol\cMhg pan1011s to provide !he work indlcaled Ondude name/ address/ phone/ !)'pa of 'Mll1c):
,6 PRDPER1Y OWNER SIGNATURE DATE
<OMPLET£ THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or ~U(8 bullding oc:cupant required ID submtt a busin-plan, acute\' hazardous materials regstration form or risk management and prewnllon program under sedions 25505, 25533 or 25534 of the
Presley•ll'rmer Hazardous Subslance AccllUnt Adi Yes ., No
Is \he aPi/icant or future building DCCUpanl 1eqllm!d ID obtain a permit from the mr pollulion con1rol district or aif quality management cisttict? Yes ., ltJ
Is \he IBCilily to be oonstructed within 1,000 feet of \he outer boundary of a school site? Yes ., No
IF ANY Of THE ANSWERS ARE Y£S. A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE issum UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES ANO THE AIR POLLUTION CONTROL DISTRICT.
I~:
l-· ._ ,;; • STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE .
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email building@carlsbadca.gov or MaU the completed form to City or carlsbad, ~ Division 1635 Faraday Avenue, carlsbad, ca1ifumia 92008.
COi': (Olfkle u.. Only)
CONTACT NAME OCCUPAHJ NAME
ADDRESS BUIWING ADDRESS
CITY STATE ZIP CRY STATE
car1sbad CA
P1lONE FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Ustect above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
MAIL 10: CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
MAIL/ FAX 10 OTHER:
OCCUPANT (Listed abova)
-----·----
.Jt5 APPLICANT'S SIGNATURE
ASSOCIATEDCB•-----------
NO CHANGE IN USE/ NO CONSTRUCTION
CHANG£ OF USE/ NO CONSTRUCTION
DATE
ZIP
' , PERMIT INSPECTION HISTORY REPORT (C8C2018-0507}
Permit Type:
Work Class:
Status:
Scheduled
Date
BLDG-Commercial
Cogen
Closed -Finaled
Actual
Start Date Inspection Type
Application Date: 09105/2018 Owner:
Issue Date: 06/25/2019 Subdivision:
Expiration Date: 03/31/2020 Address:
IVR Number: 13668
Inspection No. Inspection Status Primary Inspector
10/03/2019 10/03/2019 BLDG-34 Rough
Electrical
106314-2019 Passed Chris Renfro
October 03, 2019
BLDG.final
Inspection
Checklist Item
BLDG-Building Deflciency
106315-2019
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
Passed Chris Renfro
COMMENTS
VIASAT INC A DELAWARE
CORPORATION
2456 Town Garden Rd
Carlsbad, CA 92009-1742
Reinspection
Passed
Yes
Passed
Yes
Yes
Yes
Yes
'(es
Complete
Complete
Complete
Page 1 of1
Carlsbad CBC2018-0507
11/13/2018
DATE: 11/13/2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0507
✓. EsG1I
SET: II
PROJECT ADDRESS: 2456 Town Garden Road
PROJECT NAME: Install 17 Electric Vehicle Chargers for ViaSat
D APPLICANT
D JURIS.
C8J The plans transmitted herewith have been corrected where necessary and substantially
comply with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed
check list and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at
EsGil until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the
applicant contact person.
D The applicant's copy of the check list has been sent to:
C8] EsGil staff did not advise the applicant that the plan check has been completed.
□ EsGil staff did advise the
Person contacted:
Date contacted:
pplicant that the plan check has been completed.
_ff'L Telephone#:
(b~) Email:
Mail Teleph ne Fax In Person
0 REMARKS:
By: Morteza Beheshti
EsGil
Enclosures:
11/6
✓. EsG1I
DATE: 9/17/2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0507
PROJECT ADDRESS: 2456 Town Garden Road
SETI
PROJECT NAME: Install 17 Electric Vehicle Chargers for ViaSat
□ APPLICANT f JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Arati Telephone#: 858.793.4777
,,--.Qa~=tac:~e1!_d:: '1/ll?/IK' (b~) Email: aratir@sca-sd.com
Mail Telephone Fax In Person
0 REMARKS: ---\JN~Ail..A15 Lb
By: Morteza Beheshti
EsGil
9/7
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBC2018-0507
9/17/2018
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK#.: CBC2018-0507
OCCUPANCY: U
TYPE OF CONSTRUCTION: NA
ALLOWABLE FLOOR AREA:
SPRINKLERS?:
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 11/6/17
DATE INITIAL PLAN REVIEW
COMPLETED: 9/17/2018
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: Parking Garage
ACTUAL AREA: 209,524
STORIES: 1
HEIGHT:
OCCUPANT LOAD:
DA TE PLANS RECEIVED BY
ESGIL CORPORATION: 9/7
PLAN REVIEWER: Morteza Bebeshti
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2016 CBC, which adopts the 2015 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list {or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBC2018-0507
• 9/17/2018
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Morteza Beheshtl
PLAN CHECK#.: CBC2018-0507
DATE: 9/17/2018
BUILDING ADDRESS: 2456 Town Garden Road
BUILDING OCCUPANCY: B
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
17 EV CharQer install
TOTAL VALUE
Jurisdiction Code CB By Ordinance
1997 use Building Permit Fee • ··--····-·
1997 USC Plan Check Fee •
Type of Review: 0 Complete Review
D Repetitive Fee -----~, Repeats
Comments:
□ Other
0 Hourly
EsGil Fee
Reg.
Mod.
VALUE ($)
150,000
150,000
$803.561
$522.31 I
O Structural Only
$458.031
Sheet 1 of 1
Carlsbad CBC2018-0507
9/17/2018
Please make all corrections on the original tracings, as requested in the
correction list. Submit two sets of plans to the City of Carlsbad Building
Department Or EsGil Corporation.
ELECTRICAL, and ENERGY COMMENTS
PLAN REVIEWER: Morteza Beheshti
ELECTRICAL (CALIFORNIA ELECTRICAL CODE)
1. Provide a single line diagram for the new service. Include the following
information:
• Indicate the ground electrode type for the 225 KVA transformer.
• Specify whether the system design is fully-rated, series rated, or
engineered (fault current levels shown throughout the system).
2. Out swinging door(s) equipped with panic hardware is required for doors
accessing rooms containing electrical equipment rated BOO amperes or more.
CEC110.26(C)(3).
3. Emergency illumination is required to be installed in electrical equipment rooms.
Please provide. CBC 1008.3.3
4. Please include brochure cuts of the chargers.
5. Please include installation method for the EV1 chargers. Demonstrate physical
protection is provided from vehicles.
6. At least (1) convenience receptacle outlet shall be installed within 50' of the
electrical service (Does not apply to one and two family residential occupancies).
CEC 210.64
7. Electric Vehicle Charging for the ADA parking van accessible must comply with
CBC Table 11 B-228.3.2.1
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
Carlsbad CBC2018-0507
9/17/2018
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Morteza Beheshti
at Esgil Corporation. Thank you.
SAN DIEGO
858-638-0600
858-638-0640 FAX
4115 Sorrento Valley Blvd.
San Diego, CA 92121
IRVINE
949---864-0600
949-864-0640 FAX
5251 California
Suite 110
Irvine, CA 92617
www.mwalleng.com
MICHAEL WALL ENGINEERING
NOV O 5 2018
-\: Sep. 18, 2018
Morteza Beheshti
EsGil Corporation
9320 Chesapeake Drive, Suite 208
San Diego, CA 92123
Re: Install 17 Electric Vehicle Chargers for Viasat
Plan Check#: CBC2018-0507
MWE Job No. 16-190
We have received the comments from your plan review for the above referenced project.
We have responded to each Issue (in italics), and have included the original Issues (in
boldface} for your reference.
Electrical:
D 1. Provide a single line diagram for new service. Include the following
information:
• Indicate the ground electrode type for 225KVA transformer.
• Specify whether the system design is fully-rated, series rated, or
engineered (fault current levels shown throughout the system)
Response: See sheet E2. 1 for singleline diagram indicating wat is new and what
is existing. Also see singleline diagram for grounding conductor for
new transformer T-EV1. The system is and engineered system. See
fault current values for new equipment on singleline diagram.
D 2. Out swinging door(s) equipped with panic hardware is required for doors
accessing rooms containing electrical equipment rated 800 amperes or
more. CEC110.26(C)(3).
Response: See architectural plans for panic hardware. See attached sheet A4.03
□ 3. Emergency illumination is required to be installed in electrical equipment
rooms. Please provide. CBC 1008.3.3.
Response: Lighting in the main electrical room is existing and connected to the
existing emergency lighting inverter.
□ 4. Please include brochure cuts of the chargers.
Response: For brochure for EV chargers, refer to separate pdf cut sheet model
CT4023 with highlighted options.
MICHAEL WALL ENGINEERING
□ 5. Please include installation method for the EV1 chargers. Demonstrate
physical protection is provided from vehicles.
Response: Refer to architectural drawings for physical protection from vehicles.
See details 5 and 12 on attached sheet A4.03
□ 6. At least 11) convenience receptacle outlet shall installed within 50' of the
electrical service (Does not apply to one and two family residential
occupancies).
Response: For existing convenience receptacle located in the Electrical room,
refer to sheet E4. 1 Enlarged Plans & Details
□ 7. At Electric Vehicle Charging for ADA parking van accessible must comply
with CBC Table 118-228.3.2.1.
Response: Two EV locations are shown on sheet E1.3B for ADA parking van
accessible compliance.
We trust that these responses, along with the corrections to the plans, meet with your
approval. Should you have any questions or comments, please feel free to contact me at
858-638-0600.
Sincerely,
Ray Thompson
Sr. Project Engineer
Michael Wall Engineering, Inc.
\.,
-charge poin+
CT4000 Level 2 Commercial Charging Stations
Specifications and Ordering Information
Ordering Information
Specify model number followed by the applicable code(s).
The order code sequence is: Model-Options. Software. Services
and Misc are ordered as separate line items.
Hardware
Description Order Code
Model 1830 mm (6') Single Port Bollard Mount CT4011
1830 mm (6') Dual Port Bollard Mount CT4021
1830 mm (§') Single Port Wall Mount CT4013
1830 mm (6') Dual Port Wall Mount CT4023
2440 mm (8') Dual Port Bollard Mount CT4025
2440 mm (8') Dual Port Wall Mount CT4027
Options Integral Gateway Modem -USA -GWl
Integral Gateway Modem -Canada -GW2
Misc Power Management Kit CT 4000-PMGMT
Bollard Concrete Mounting Kit CT4001-CCM
Software & Services
Description Order Code
ChargePoint Commercial Service Plan
ChargePoint Service Provider Plan
ChargePoint Assure
Station Activation and Configuration
ChargePoint Station Installation and Validation
CTSW-SAS-COMM-n1
CTSW-SAS-SP-n'
CT 4000-ASSUREd
CPSUPPORT-ACTIVE
CT 4000-INSTALLVALID
Note: All CT 4000 stations come with 1 year of ChargePoint Assure coverage at no
charge for qualified installations. Other conditions apply. All CT 4000 stations require
a network service plan.
1 Substitute n for desired years of service (1, 2. 3. 4, or 5 years).
• Substitute n for the duration of the additional coverage (1. 2, 3, or 4 years).
Order Code Examples
If ordering this the order code is
1830 mm (6') Dual Port Bollard USA Gateway Station CT4021-GW1
with Concrete Mounting Kit CT 4001-CCM
ChargePoint Commercial Service Plan, CTSW-SAS-COMM-3
3 Year Subscription
ChargePoint Station Installation and Validation CT4000-INSTALLVAUD
2 Additional Years of Assure Coverage CT4000-ASSURE2
1830 mm (6') Single Port Wall Mount Station CT4013
ChargePoint Commercial Service Plan.
S Year Subscription
4 Additional Years of Assure Coverage
Station Activation and Configuration
CTSW-SAS-COMM-5
CT 4000-ASSURE4
CPSUPPORT-ACTIVE
CT4021
,. Ch~Point CT 4000 Family
CT 4021 1830 mm (6')
CT 4025 2440 mm (8')
Bollard
347mm ~ (13.7") +-
CT4025
2426 mm
(95.5")
CT4021
1811 mm
(71.3")
2 chargepoint.com
233mm
(9.2")
1186 mm
(46.7")
J
i
470mm
(18.5")
CT 4023 1830 mm (6')
CT 4027 2440 mm (8')
Wall Mount
CT4027
2426 mm
(95.5")
347mm ---+ (13.7")
CT4023
1811 mm
(71.3")
l
302mm
(11.9")
~ 233mm
(9.2")
1184 mm
(46.6")
_l
i
483mm
(19.0")