HomeMy WebLinkAboutAS130174; 2271 COSMOS CT------·-------
11/16/23, 2:20 PM AS130174 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS130174
Job Address: 2271 COSMOS CT
Permit Type: SPRINK
Status: PENDING
Applied 9/26/2013
Approved: Parcel No: 2130504100
Lot#: 0
Reference No.:
PC#:
Project Title:
Applicant:
Issued:
Inspector:
BACKFLOW PREVENTER REPLACEMENT EXISTING SYSTEMS
ARE DESIGNATED FOR .33/3000 AND TO REMAIN AS-IS.
CALCULATIONS HAVE BEEN RUN WITH NEW FLOW TEST AND
NEW LOSS FOR RPDA TO PROVE THAT THE EXISTING
SYSTEMS CAN STILL ACHIEVE THE ORIGINALLY DESIGNED
DENSITIES NO OTHER CHANGES ARE PROPOSED FOR THIS
PROJECT.
Owner:
EPIC FIRE PROTECTION, INC.
765 TURTLE POINT WY
KOCH INVESTMENTS L P
SAN MARCOS, CA
760-310-6122
about:blank
Fees($)
297
Add'I Fees ($)
0
12 CHURCHILL LN
RANCHO MIRAGE CA
Total($)
297
Balance($)
0
1 /1
Flow Test Record
Test Hydrnnt
Hydrant ID No. _____ Size Main ____ _
Static ............. _t~_
Residual......... \"2.0
Pressure Drop .. _--1:2.._ __ (PDI 1) ..... K factor for PDI 1 4. O
Flow Hydrant(s)
Hydrant I location ,Z..-Z.:J l C~UllC:s'°> c:r ·
Hydrant 2 location -------------------Hydrant 3 location __________________ _
Hydrant I Pitot __ !>_O ___ PSI
Hydrant 2 Pitot PSI
Hydrant 3 Pitot PSI
GPM: l'Soo
GPM: ----GPM: =---Total: l ~
(QI)
Calculated test and flow data -OxPD2 k =Q2
PDI*k
. Static:.................... \ ~
Desired Residual....... 20 ---
Size of Orifice -Z \z..
Size of Orifice ----Size of Orifice. ----
Pressure Drop (PD 2).. \\'.2 ................................. K factor PD 2: \12.0"2-
l'2X? x \'2.,0'2.. divided by 4,.o
Q l PD2 k PD 1 k
equals 445o:J GPM at 20 psi residual
Q2
Comments: "--------------------------
Test conducted for :
Date: q . ? · l'3 Time: q ·-ro :N'-1
~ ---~
0 ........
~
SPECIFICATION SHEET
Series 826YD
Reduced Pressure
Detector Assemblies
Size: 2½11 • 10" (65mm -250mm)
The FEBCO Series 826YD Reduced Pressure Detector Assemblies
designed for use In used appl1cat1ons with Automatic lire sprinkler systems
contaInIng toxic substances
Features
• -~e Du•aChe::k. features all stamiess steel chec~ assem:ilies tor :orosIon res,stance, reduced '0J1ng and ,anger va ve life
• ).,raCast, ductile Iror body for superior strength, :orrcsIon resIsta11ce and l"'Jh!er weight. By-pass line has water meter in sanes with an
oppr:ved re:iuced pressure assem:ily
• _ccw Head Loss
• A:proved by the Founda:r:r, for Cross--Conrmect1or Contra. 3nd
"'ydraulIc Research at the Ur,1vers1ty of Sout~-em Cal1fomra
• :.nd Detail IS Flanged
O~ration
In a nonfiO\li' cond1t10", check valves O" the by-oass and maInlIne units are
closed with pressure between the checks. called t",e zone, being main-
tained at least 5psi 135 kPa) lower than the 1n~1 pressure and the relief valve Is ma1ntarned closed 11 tne d tleren11al be:ween the zone ano tne
upstream r:ressure drops tc 2ps1 114~Pal. '.he d1fferen11aI relief valve will
open, ..,.amtaI'1mg proper zone d1fferent1al The by-pass reduced pressure
back:flow preventer will operate 1dent1caliy to the mainline assembly
The bvi:Jass opens to detect inrt1al floN and the mainline opens for all
other flows
Models
• _ess Gates • Remo·e Reader
• A.r Gap Dra1" • Me1e· CFM/GPM
• _eft han:i by-pass
~rovals
• Acproved by the Founda:1on for Cross-Connection Con1rol arid
-ydraulIc Research at the University of Sout"em Cal1fom1a •
Q <>;W,t· <9>'. ~ ~ ........
1047
• Valves must ::e s_.pp1ed with res1l1e"'t seated shutoff valves fo-us:
and ;M approvals '.0 De In effec'. UL and ~M L stings only appl ca:ile
w,th approved OS&Y gates
Job Name _____________ _
Job Location--------------
Engineer
Approval
ES-F-826YD
'lFEB&Of.
S_eecifications
Reduced pressure detector assembly-shall consist of a mamhne reduced pressure conf~ured backflow assembly in parallel with a reduced pressure
by-pass assembly.
FIOYII :urvas shall be oocumented by m:Jependent lat:ora:ory testing
Mamlme -.alve bodies and covers shall be manufacturec1 ol ductile iro" ASTMA-536. Grade 65-t.5-12 and shall be 'langed. ANSI B 1E 1. Class 125. 1111emal al'l(I external fusion epoxy coating
The by-pass shall consIs'. orI~ariv of a bronze water meter m se11es with a br::nze re□uceo pressure ::ackflow pre\ltlnter
Al ow flow demands up to a mrIm_.m of 3 gpm 10 189 LJsi are :o pass only thr:ug~ me by-pass meter and meteF-sIze red .. ced pressure asse--
bly and be accurately recorCled All flaws abo\18 Iha: o' 3 ;;;pm w1;I pass
th·ough both the lIne-sIze red1.1Ced pressure assembly an:i by-pass w1'.hout accurate registration by or damage to the meter.
S"utoff va ves and :estc::cks s~all be res1l1ent seated wrth full flaw char-acteristics and are to be considered integral to the assembiy. The mainline
shu'.--offs are also to be OS&'!'. ~ ./FM 'o-firel·"e sef'Vlce
Reduced pressure detector assemblies shall be rated 175ps1 ONWP (32°F
10 740°FI. tacto-y assem::led and tested tc assu·e ::roper ""'aInlme/by-pass balance an:i cross over performance Reduced press.,re de:ector assem-
blies shall be ~ESCO Series 826YD or pror approved equal
Note: The gap drain Is not designed to catdi the maximum discharge pos-
sible 'ram the ·el1ef valve The 1nstalla:1::n of F:BCO air gap with the drain
I1~e termIr,at ng above a floo· dram will ha11dle any no·ma, 01scha'ge or riuI
sa11ce spI1t1ng :hrcug~ the rel el valve However, foor dram s ze may need
to be d€s1gred to orevent water damage caused by a catastrophic failure
cori::11tion Do no! red~ce :he size o' the drain line from the air gap f ttmg
Pressure -Tem_eerature
Max1m.,m \No~kmg Press~re
Hyoros:at1c Tes~ Press
Temper~rure Range
Materials
Main Valve Body
lntema :"eek Assemt:ly
Trim
By-Pass Valve 2ody
By-Pass Meter
Mam Yaiva Shutot's
Eastomers
175ps1 :·2.1 ba~
350ps1 i24 • ba1
32•~ to 140"F I0°c 10 60"Ci
Ductile iron grade 65-45-12 epoxy coa:ed
internal 10-20 mils
Stainless Steel
Bronze
Bronze
Total1z-ng. 1 t:i 20 gpm, size 5/8' x 3/4'
OS&'!'. ULJFM
N1tnle and N1tr1le/ 'ab11c re1rbceo
Re~o'.e ·ead ng tlaw meters available
Contractor ______________ _
Approval ______________ _
Contractor's P.O. No. __________ _
Representative ____________ _
FEBCO product specifications in U.S. customary units arid metric are approximate and are provided for reference only. For precise mea-
surements, please contact FEBCO. FEBCO reserves the right to change or modify product design, construction, apeclficationa, or materials
without prior notice and witl'oout incurring any obligation to make such changes and modifications on FEBCO product9 previously or subse-
quently sold
Installation
The Reduced Pressure De1ec10" Assembly should be mstaled h::rizontaly w,tn
a suggested mIni .... um cleararice of 12' {30Dmml bet.veen the assembly and the
floor or grade -~F!'/ must be msta·led where discharge from the rel el valve will
riot be o:ijectionable and ca" be pos1:1ver-,' :ira1ned i?Ml2f./ They should be installed
where easily accessible for testing and maintenance and must be protected
from treezmg Thermal water expansion an'.l,lor water hammer downstream of tne
bacdlaw preve~ter can cause excessive ::iressure Excessive p·essure s tua!lo"S
should be eliminated to avoid possible damage to the system and assembly
Dimensions -Wei_s,hts
Size: 2¥.t• -10" 165 -250mmJ
SIZE
lDNI DIMENINJNI WEIBIIT
A B C 0 E ,.~
1n. mm 1n mm 1n. mm 1n. mm 1n. mm in. mm lbs. tc"'
2'1, ~ 37¼ "' "' 562 Tl, 191 1~ 418 101/, .. "" 534.8
J 8C 41:Y. 11"1 "" ~1 B'h 21e 2.21/, 565 10¥, ,., "' ,, ..
4 100 50¼ 1281 '" 82J 11 m 23¼ 591 11 m"' 1031.8
' 150 SB¥. 1518 -981 14"' 30¼ 765 12 305 752 1&54.4
B 200 '"" 1757 46\'o 1172 18 467 '"' 959 13 330 1207 2650.4
10 250 '4¼ "40 SS\'o 1476 22 "' 48 1219 14"' 15173557.4
o,me.,.i<>lli ohown ""' "'m,,..t ollnwor,oo mus, be...-b oormal man•tact"r'ng 10-.:U
FEB CO MODEL 82&YD
SlileYiew
311" Max (150mm)
1T Min (JDDmml
~
··············A··························
-----------8 -------------
IHlg&UI ,~ ......
134 294.8
154 338.8
1$4 42fi.8
397 873.4
537 1181.4
!1572105.4
Ca~
(I i 11 iD I I I l ' • -■ -■p ' ■ • --••
1~ ~ 1 rn,
2llO :m .00 !ll»gp,n
' • • a • ••
I~:;, 11 ITI 1111
' • ■ • ■ -~ ' • ----·
tta !Iii li"l1liDIMII
I~] 1111111111
' -• ----' -----· .... ri--.)
I~ ~I I 11111 I I t l
' ------a 2270 M 5110 !llll lMllllplrl
1] 111 rnn II
' -----~ ' ------
/FEacoZ f) ~1;r:
A. Watts Water T..ohnolo111W, Complll!y USA 4381 N. Brawley• Ste 102 • Fresno CA• 93722 • Tel. (559) 441-5300 • Fax: (559) 441-5301 • wwwFEBCOonllne.oom
Canada. 5435 North Service Rd • Burlington. OITT. • L7L 5H7 • Tel. !90:S) 332-4090 • Fax: (BOS) 332-7068 • www.FEBCOonllne.ca
ES-F-826YD 0718 C 2009 FEBCO
•
EPIC FIRE PROTECTION, INC.
765 TURTLE POINT WAY
SAN MARCOS, CA 92069
(760) 310-6122 FAX (760) 798-0556
Hydraulic Design Information Sheet
Name: BACK.FLOW REPLACEMENT (PHILLIPS) Date: 9-5-13
Location: 2271 COSMOS CT. CARLSBAD
Building: EXISTING System No. 2OF2
Contractor: EPIC FIRE PROTECTION, INC. Contract No.
Calculated By: RAB Drawing No. l OF l
Construction: ..,~--C-o_m_b_usti __ b-le--... □---N-o-n-C-om-bus-tib_l_e _____ Ceiling Height _2_8 ___ _
SYSTEM DESIGN
NFP A 13: Light Hazard Ordinary Hazard Group 1 2 3 Extra Hazard
Curve: 0 NFPA231 0 NFPA231C: Figure: 0 Other (Specify) ----------
□Specific Ruling ___________ Made By
Area of Sprinkler Operation
Density
Area Per Sprinkler
Hose Allowance GPM: Inside
Hose Allowance GPM: Outside
Rack S rinkler Allowance
CALCULATION SUMMARY
------
GPM Required _11_6_0._66 ______ PSI Required _4_8_.3_1 _____ _
"C" Factor Used: Overhead 120 Un
WATER SUPPLY
Date
Water Flow Test Pump Data "<, , Tank or Reservoir ·-Date& Time 9-5-13 Rated Capacity ~acity
Static PSI 133 At PSI ... t1r· apon
Residual PSI 120 Elevation '
ft. ,,.
GPM Flowing 1500 --··~ ...... Well
Ft.
Elevation 0 Proof Flow GPM
Location SITE
Source of Information CARLSBAD MWD
COMMODITY STORAGE
Commodity EXISTING DESIGN Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized %Rack
Rack 0 SingleRow 0 Conventional Pallet D Automatic Storage 0 Encapsulated 0 DoubleRow D Slave Pallet 0 Solid Shelving 0 Non-Encapsulated
0 Multiple Row 0 Open
Flue SP!!ciru! In Inches Clearance From Top of Storage to Ceiling
Longitudinal Transverse Ft. In.
Horizontal Barriers Provided
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED) Sigma Dynamic• CorporaUon
7700 Supply / Demand Graph 250
240
230
220
210
200
190
180
170
160
150
{ 140 --1! 130
J 120
110
•
....
100
90
80
70
60
50
40
30
20
10
./
/~
~ .. ~
.),_DJ
.... i,,"""
--0200 400 600 600
System Demand ..
Sprinkler Demand 64.45 PSI
Additional Flows
Hose at Source
Total Demand 64.93 PSI
-1000 ---1200
@ 1060.66 GPH
100.00 GPM
400.00 GPM
@ 1560.66 GPH
t101e1
1400
Water Flow {GPM)
I I
Margin
Pressure 42.18 PSI
Flow
•---<_t,'
~
I
-~ ~ ~ 1600 1600
Water Supply ..
Static 119.70 PSI
Residual 108.00 PSI
Elevation 0.00 PSI
1891.48 GPM
'S' '-=-'
@ 1500.00 GPM
-
-
N1.85
2000
SUBMI'I"I'AL SERIAL NO:2932HY7 09-05-2013 PAGE 1
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
FLOW TEST RESULTS
Water Supply
STATIC 119.70 PSI
RESIDUAL 108.00 PSI @ 1500.00 GPM
CITY PRESSURE AVAILABLE AT 1560. 7 GPM 107.11 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR PRESSURE ----------------
300 32.86 31.68 8.00 16.87
301 32.18 31.68 8.00 16.18
302 31.88 31.68 8.00 15.88
303 31.82 31.68 8.00 15.82
304 31.83 31.68 8.00 15.83
305 32.74 31.68 8.00 16.75
306 32.07 31.68 8.00 16.07
307 31.77 31.68 8.00 15.77
308 31.72 31.68 8.00 15.72
309 31.73 31.68 8.00 15.73
310 32.69 31.68 8.00 16.70
311 32.02 31.68 8.00 16.02
312 31.74 31.68 8.00 15.74
313 31.68 31.68 8.00 15.68
314 31.69 31.68 8.00 15.69
318 35.16 31.68 8.00 19.32
319 34.96 31.68 8.00 19.10
320 32.67 31.68 8.00 16.68
321 32.59 31.68 8.00 16.60
322 32.57 31.68 8.00 16.58
323 34.66 31.68 8.00 18.77
324 32.64 31.68 8.00 16.65
325 32.56 31.68 8.00 16.56
326 32.54 31.68 8.00 16.54
327 34.62 31.68 8.00 18.73
328 32.63 31.68 8.00 16.64
329 32.55 31.68 8.00 16.55
330 32.53 31.68 8.00 16.53
331 34.61 31.68 8.00 18.72
SUBMITTAL SERIAL NO:2932HY7
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR --------
332 37.79 31.68 8.00
333 37.62 31.68 8.00
334 37.53 31.68 8.00
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 3
OUTSIDE HOSE STREAMS AT 0
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 236 TO 286
PRESSURE --------
22.32
22.12
22.01
1060.66 GPM
100.00 GPM
400.00 GPM
1560.66 GPM
64.93 PSI
0.00 PSI
19.00 FPS
09-05-2013 PAGE 2
SUBMI'ITAL SERIAL NO:2932HY7 09-05-2013 PAGE 3
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
327 331 3.314 L 8.00 C::120 PT 18.72 (331)
Q 34.61 F=0 F 0.00 PE 0.00
BN T 8.00 0.0013 PF 0.01
323 327DQ 34.62 3.314 L 8.00 C-=120 PT 18.73 (327)
Q 69.24 F=0 F 0.00 PE 0.00
BN T 8.00 0.0048 PF 0.04
287 323DQ 34.66 3.314 L 4.00 c-120 PT 18.77 (323)
Q 103.90 F=T F 18.90 PE 0.00
BN T 22.90 0.0101 PF 0.23
PT 19.00 (287) ------------------326 330 3.314 L 8.00 C=120 PT 16.53 (330)
Q Q 32.53 0.00 PE 0.00
BN T 8.00 0.0012 PF 0.01
322 326DQ 32.54 3.314 L 8.00 c-120 PT 16.54 (326)
Q 65.07 F=0 F 0.00 PE 0.00
BN T 8.00 0.0043 PF 0.03
286 322DQ 32.57 3.314 L 4.00 C=120 PT 16.57 (322)
Q 97.64 F=T F 18.90 PE 0.00
BN T 22.90 0.0090 PF 0.21
PT 16.78 (286) ------------------325 329 3.314 L 8.00 C=120 PT 16.55 (329)
Q 32.55 F=0 F 0.00 PE 0.00
BN T 8.00 0.0012 PF 0.01
321 325DQ 32.56 3.314 L 8.00 C=l20 PT 16.56 (325)
Q 65.10 F=0 F 0.00 PE 0.00
BN T 8.00 0.0043 PF 0.03
285 321DQ 32.59 3.314 L 4.00 C=120 PT 16.59 (321)
Q 97.69 F=T F 18.90 PE 0.00
BN T 22.90 0.0090 PF 0.21
PT 16.80 (285) ------------------324 328 3.314 L 8.00 C=120 PT 16.64 (328)
Q 32.63 F=0 F 0.00 PE 0.00
BN T 8.00 0.0012 PF 0.01
320 324DQ 32.64 3.314 L 8.00 C=120 PT 16.65 (324)
Q 65.27 F=0 F 0.00 PE 0.00
BN T 8.00 0.0043 PF 0.03
SUBMITTAL SERIAL NO:2932HY7 09-05-2013 PAGE 4
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
284 320DQ 32.67 3.314 L 4.00 C=120 PT 16.68 (320)
Q 97.94 F=T F 18.90 PE 0.00
BN T 22.90 0.0091 PF 0.21
PT 16.89 (284) ------------------319 287 1. 728 L 16.00 C=120 PT 19.00 (287)
Q 11.21 F=0/T F 9.00 PE 0.00
BL T 25.00 0.0039 PF 0.10
318 319DQ 34.96 1.728 L 4.00 C=120 PT 19.10 (319)
Q 46.17 F=0 F 0.00 PE 0.00
BL T 4.00 0.0538 PF 0.22
317 318DQ 35.16 1.728 L 4.00 C=120 PT 19.32 (318)
Q 81.33 F=0 F 0.00 PE 0.00
BL T 4.00 0.1534 PF 0.61
316 317 1.728 L 4.00 C=120 PT 19.93 (317)
Q 81.33 F=0 F 0.00 PE 0.00
BL T 4.00 0.1534 PF 0.61
315 316 l.728 L 4.00 C=120 PT 20.54 (316)
Q 81.33 F=0 F 0.00 PE 0.00
BL T 4.00 0.1534 PF 0.61
277 315 1.728 L 8.00 C=l20 PT 21.15 (315)
Q 81.33 F=T F 9.00 PE 0.00
BL T 17.00 0.1534 PF 2.61
PT 23.76 (277)
------------------314 313 1.728 L 4.00 C=l20 PT 15.68 (313)
Q 9.54 F=0 F 0.00 PE o.oo
BL 4.00 0.0029 PF 0.01
286 3l4DQ 31.69 1.728 L 16.00 C=120 PT 15.69 (314)
Q 41.23 F=0/T F 9.00 PE 0.00
BL T 25.00 0.0436 PF 1.09
236 286DQ 97.64 l.728 L 1.00 C=120 PT 16.78 (286)
Q 138.87 F=T F 9.00 PE 0.43
RN T 10.00 0.4127 PF 4.13
PT 21.34 (236)
------------------312 313 1.728 L 4.00 C=120 PT 15.68 (313)
Q 22.14 F=0 F 0.00 PE 0.00
BL T 4.00 0.0138 PF 0.06
SUBMITI'AL SERIAL NO:2932HY7 09-05-2013 PAGE 5
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
311 312DQ 31.74 1.728 L 4.00 C=l20 PT 15.74 (312)
Q 53.88 F=0 F 0.00 PE 0.00
BL T 4.00 0.0716 PF 0.29
310 311DQ 32.02 1.728 L 4.00 C=l20 PT 16.03 (311)
Q 85.90 F=0 F 0.00 PE 0.00
BL T 4.00 0.1697 PF 0.68
276 310DQ 32.69 1.728 L 8.00 C=l20 PT 16.71 (310)
Q 118.60 F=T F 9.00 PE 0.00
BL T 17.00 0.3082 PF 5.24
PT 21.95 (276) ------------------309 308 1.728 L 4.00 C=l20 PT 15.72 (308)
Q 9.16 F=0 F 0.00 PE 0.00
BL T 4.00 0.0027 PF 0.01
285 309DQ 31.73 1.728 L 16.00 C=l20 PT 15.73 (309)
Q 40.89 F=0/T F 9.00 PE 0.00
BL T 25.00 0.0430 PF 1.08
235 285DQ 97.69 1.728 L 1.00 C=l20 PT 16.81 (285)
Q 138.58 F=T F 9.00 PE 0.43
RN T 10.00 0.4111 PF 4.11
PT 21.35 (235) ------------------307 308 1.728 L 4.00 C=l20 PT 15.72 (308)
Q 22.56 F=0 F 0.00 PE 0.00
BL T 4.00 0.0143 PF 0.06
306 307DQ 31.77 1.728 L 4.00 C=l20 PT 15.78 (307)
Q 54.33 F=0 F 0.00 PE 0.00
BL T 4.00 0.0727 PF 0.29
305 306DQ 32.07 1. 728 L 4.00 C=l20 PT 16.07 (306)
Q 86.40 F=0 F 0.00 PE 0.00
BL T 4.00 0.1715 PF 0.69
275 305DQ 32.74 1.728 L 8.00 C=l20 PT 16.76 (305)
Q 119.14 F=T F 9.00 PE 0.00
BL T 17.00 0.3108 PF 5.28
PT 22.04 (275) ------------------304 303 1.728 L 4.00 C=l20 PT 15.82 (303)
Q 8.73 F=0 F 0.00 PE 0.00
BL T 4.00 0.0025 PF 0.01
SUBMI'ITAL SERIAL NO:2932HY7 09-05-2013 PAGE 6
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
ure
in Siz & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
284 304DQ 31.83 1.728 L 16.00 C:120 PT 15.83 (304)
Q 40.56 F=0/T F 9.00 PE 0.00
BL T 25.00 0.0423 PF 1.06
234 284DQ 97.94 1.728 L 1.00 C=l20 PT 16.89 (284)
Q 138.50 F=T F 9.00 PE 0.43
RN T 10.00 0.4107 PF 4.11
PT 21.43 (234) ------------------302 303 1.728 L 4.00 C:120 PT 15.82 (303)
Q 23.09 F=0 F 0.00 PE 0.00
BL T 4.00 0.0149 PF 0.06
301 302DQ 31.88 1.728 L 4.00 C=120 PT 15.88 (302)
Q 54.97 F=0 F 0.00 PE 0.00
BL T 4.00 0.0743 PF 0.30
300 301DQ 32.18 1.728 L 4.00 C=120 PT 16.18 (301)
Q 87.15 F=0 F 0.00 PE 0.00
BL T 4.00 0.1743 PF 0.70
274 300DQ 32.86 1.728 L 8.00 C=l20 PT 16.88 (300)
Q 120.01 F=T F 9.00 PE 0.00
BL T 17.00 0.3150 PF 5.35
PT 22.23 (274)
------------------335 277 1.728 L 6.00 C=120 PT 23.76 (277)
Q 28.94 F=0/T F 9.00 PE 0.00
BL T 15.00 0.0227 PF 0.34
257 335 1.728 L 38.00 C=120 PT 24.10 (335)
Q 28.94 F=T F 9.00 PE 0.00
BL T 47.00 0.0227 PF 1.07
207 257 1.728 L 1.00 C=120 PT 25.17 (257)
Q 28.94 F=T F 9.00 PE 0.43
RN T 10.00 0.0227 PF 0.23
PT 25.83 (207) ------------------334 276 1.728 L 6.00 C=120 PT 21.94 (276)
Q 12.42 F=0/T F 9.00 PE 0.00
BL T 15.00 0.0047 PF 0.07
256 334DQ 37.53 1.728 L 38.00 C=120 PT 22.01 (334)
Q 49.95 F=T F 9.00 PE 0.00
BL T 47.00 0.0623 PF 2.93
SUBMI'ITAL SERIAL NO:2932HY7 09-05-2013 PAGE 7
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
206 256 1.728 L 1.00 C=120 PT 24.94 (256)
Q 49.95 F=T F 9.00 PE 0.43
RN T 10.00 0.0623 PF 0.62
PT 25.99 (206) ------------------333 275 1.728 L 6.00 C=120 PT 22.04 (275)
Q 13.32 F=0/T F 9.00 PE 0.00
BL T 15.00 0.0054 PF 0.08
255 333DQ 37.62 1.728 L 38.00 C=120 PT 22.12 (333)
Q 50.95 F=T F 9.00 PE 0.00
BL T 47.00 0.0646 PF 3.04
205 255 1.728 L 1.00 C=120 PT 25.16 (255)
Q 50.95 F=T F 9.00 PE 0.43
RN T 10.00 0.0646 PF 0.65
PT 26.24 (205) ------------------332 274 1.728 L 6.00 C=120 PT 22.23 (274)
Q 14.02 F=0/T F 9.00 PE 0.00
BL T 15.00 0.0059 PF 0.09
254 332DQ 37.79 1.728 L 38.00 c .. 120 PT 22.32 (332)
Q 51.81 F=T F 9.00 PE 0.00
BL T 47.00 0.0666 PF 3.13
204 254 1.728 L 1.00 c-120 PT 25.45 (254)
Q 51.81 F=T F 9.00 PE 0.43
RN T 10.00 0.0666 PF 0.67
PT 26.55 (204) ------------------237 236 4.260 L 12.00 C=l20 PT 21.35 (236)
Q 116.32 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0037 PF 0.04
238 237DQ 92.69 4.260 L 12.00 C=l20 PT 21.39 (237)
Q 209.01 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0109 PF 0.13
239 238DQ -36.17 4.260 L 12.00 c-120 PT 21.52 (238)
Q 172.84 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0076 PF 0.09
240 239DQ -35.31 4.260 L 12.00 C=l20 PT 21.61 (239)
Q 137.53 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0050 PF 0.06
SUBMITl'AL SERIAL NO:2932HY7 09-05-2013 PAGE 8
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
241 240DQ -34.73 4.260 L 12.00 c-120 PT 21.67 (240)
Q 102.80 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0029 PF 0.03
242 241DQ -34.39 4.260 L 12.00 C=120 PT 21.70 (241)
Q 68.41 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0014 PF 0.02
243 242DQ -34.23 4.260 L 12.00 C=120 PT 21.72 (242)
Q 34.18 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0004 PF 0.00
293 243 1.728 L 1.00 C=120 PT 21.72 (243)
Q 34.18 F=T F 9.00 PE -0.43
RN T 10.00 0.0309 PF 0.31
263 293 1.728 L 84.00 C=120 PT 21.60 (293)
Q 34.18 F=T/T F 18.00 PE 0.00
BL T 102.00 0.0309 PF 3.15
213 263 1.728 L 1.00 C=120 PT 24.75 (263)
Q 34.18 F=T F 9.00 PE 0.43
RN T 10.00 0.0309 PF 0.31
212 213 4.260 L 12.00 C=120 PT 25.49 (213)
Q 34.18 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0004 PF 0.00
PT 25.49 (212) ------------------292 242 1.728 L 1.00 C=120 PT 21.72 (242)
Q 34.23 F=T F 9.00 PE -0.43
RN T 10.00 0.0309 PF 0.31
262 292 1.728 L 84.00 C=120 PT 21.60 (292)
Q 34.23 F=T/T F 18.00 PE 0.00
BL T 102.00 0.0309 PF 3.15
212 262 1.728 L 1.00 C=l20 PT 24.75 (262)
Q 34.23 F=T F 9.00 PE 0.43
RN T 10.00 0.0309 PF 0.31
211 212DQ 34.18 4.260 L 12.00 C=120 PT 25.49 (212)
Q 68.41 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0014 PF 0.02
PT 25.51 (211) ------------------291 241 1.728 L 1.00 C=120 PT 21.71 (241)
Q 34.39 F=T F 9.00 PE -0.43
RN T 10.00 0.0312 PF 0.31
SUBMITl'AL SERIAL NO:2932HY7 09-05-2013 PAGE 9
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
261 291 1.728 L 84.00 C=l20 PT 21.59 (291)
Q 34.39 F=T/T F 18.00 PE 0.00
BL T 102.00 0.0312 PF 3.18
211 261 1.728 L 1.00 Ca:120 PT 24.77 (261)
Q 34.39 F=T F 9.00 PE 0.43
RN T 10.00 0.0312 PF 0.31
210 211DQ 68.41 4.260 L 12.00 C=120 PT 25.51 (211)
Q 102.80 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0029 PF 0.03
PT 25.54 (210) ------------------290 240 1.728 L 1.00 C=120 PT 21.67 (240)
Q 34.73 F=T F 9.00 PE -0.43
RN T 10.00 0.0318 PF 0.32
260 290 1.728 L 84.00 c-120 PT 21.56 (290)
Q 34.73 F=T/T F 18.00 PE 0.00
BL T 102.00 0.0318 PF 3.24
210 260 1.728 L 1.00 c-120 PT 24.80 (260)
Q 34.73 F=T F 9.00 PE 0.43
RN T 10.00 0.0318 PF 0.32
209 210DQ 102.80 4.260 L 12.00 c-120 PT 25.55 (210)
Q 137.53 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0050 PF 0.06
PT 25.61 (209) ------------------289 239 1. 728· L 1.00 C=l20 PT 21.61 (239)
Q 35.31 F=T F 9.00 PE -0.43
RN T 10.00 0.0328 PF 0.33
259 289 1.728 L 84.00 c-120 PT 21.51 (289)
Q 35.31 F=T/T F 18.00 PE 0.00
BL T 102.00 0.0328 PF 3.35
209 259 1.728 L 1.00 c ... 120 PT 24.86 (259)
Q 35.31 F=T F 9.00 PE 0.43
RN T 10.00 0.0328 PF 0.33
208 209DQ 137.53 4.260 L 12.00 C=l20 PT 25.62 (209)
Q 172.84 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0076 PF 0.09
PT 25.71 (208) ------------------288 238 1.728 L 1.00 C=l20 PT 21.52 (238)
Q 36.17 F=T F 9.00 PE -0.43
RN T 10.00 0.0343 PF 0.34
SUBMITTAL SERIAL NO:2932HY7 09-05-2013 PAGE 10
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
258 288 1.728 L 84.00 C=120 PT 21.43 (288)
Q 36.17 F=T/T F 18.00 PE 0.00
BL T 102.00 0.0343 PF 3.50
208 258 1.728 L 1.00 C=120 PT 24.93 (258)
Q 36.17 F=T F 9.00 PE 0.43
RN T 10.00 0.0343 PF 0.34
207 208DQ 172.84 4.260 L 12.00 C=120 PT 25.70 (208)
Q 209.01 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0109 PF 0.13
206 207DQ 28.94 4.260 L 12.00 C=120 PT 25.83 (207)
Q 237.95 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0138 PF 0.17
205 206DQ 49.95 4.260 L 12.00 C=l20 PT 26.00 (206)
Q 287.91 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0196 PF 0.24
204 205DQ 50.95 4.260 L 12.00 C=120 PT 26.24 (205)
Q 338.85 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0265 PF 0.32
203 204DQ 51.81 4.260 L 12.00 C=l20 PT 26.56 (204)
Q 390.67 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0345 PF 0.41
PT 26.97 (203) ------------------235 236 4.260 L 12.00 C=120 PT 21.35 (236)
Q 22.55 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0002 PF 0.00
234 235DQ 138.58 4.260 L 12.00 C=120 PT 21.35 (235)
Q 161.13 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0067 PF 0.08
233 234DQ 138.50 4.260 L 12.00 C=l20 PT 21.43 (234)
Q 299.63 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0211 PF 0.25
283 233DQ -252.79 1.728 L 1.00 C=120 PT 21.68 (233)
Q 46.83 F=T F 9.00 PE -0.43
RN T 10.00 0.0553 PF 0.55
273 283 1.728 L 40.00 C=120 PT 21.80 (283)
Q 46.83 F=T/T F 18.00 PE 0.00
BL T 58.00 0.0553 PF 3.21
PT 25.01 (273)
SUBMITTAL SERIAL NO:2932HY7 09-05-2013 PAGE 11
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
------------------232 233 4.260 L 12.00 C=120 PT 21.68 (233)
Q 252.79 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0154 PF 0.18
282 232DQ -204.51 1.728 L 1.00 C=120 PT 21.86 (232)
Q 48.28 F=T F 9.00 PE -0.43
RN T 10.00 0.0585 PF 0.58
272 282 1.728 L 40.00 C=120 PT 22.01 (282)
Q 48.28 F=T/T F 18.00 PE 0.00
BL T 58.00 0.0585 PF 3.39
PT 25.40 (272) ------------------231 232 4.260 L 12.00 C=120 PT 21.87 (232)
Q 204.51 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0104 PF 0.12
281 231DQ -154.20 1.728 L 1.00 C=120 PT 21.99 (231)
Q 50.31 F=T F 9.00 PE -0.43
RN T 10.00 0.0631 PF 0.63
271 281 1.728 L 40.00 C=120 PT 22.19 (281)
Q 50.31 F=T/T F 18.00 PE 0.00
BL T 58.00 0.0631 PF 3.66
PT 25.85 (271) ------------------230 231 4.260 L 12.00 C=120 PT 21.99 (231)
Q 154.20 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0062 PF 0.07
280 230DQ -101.38 1.728 L 1.00 C=120 PT 22.06 (230)
Q 52.82 F=T F 9.00 PE -0.43
RN T 10.00 0.0690 PF 0.69
270 280 1.728 L 40.00 C=120 PT 22.32 (280)
Q 52.82 F=T/T F 18.00 PE 0.00
BL T 58.00 0.0690 PF 4.00
PT 26.32 (270)
------------------253 273 1.728 L 44.00 C=120 PT 25.01 (273)
Q 27.89 F=T/T F 18.00 PE 0.00
BL T 62.00 0.0212 PF 1.31
203 253 1.728 L 1.00 C=120 PT 26.32 (253)
Q 27.89 F==T F 9.00 PE 0.43
RN T 10.00 0.0212 PF 0.21
SUBMITI'AL SERIAL NO:2932HY7 09-05-2013 PAGE 12
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
202 203DQ 390.67 4.260 L 12.00 C=120 PT 26.96 (203)
Q 418.56 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0392 PF 0.47
PT 27.43 (202) ------------------252 272 1.728 L 44.00 C=120 PT 25.41 (272)
Q 28.55 F=T/T F 18.00 PE 0.00
BL T 62.00 0.0221 PF 1.37
202 252 1.728 L 1.00 C=120 PT 26.78 (252)
Q 28.55 F=T F 9.00 PE 0.43
RN T 10.00 0.0221 PF 0.22
201 202DQ 418.56 4.260 L 12.00 C=l20 PT 27.43 (202)
Q 447.10 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0443 PF 0.53
PT 27.96 (201)
------------------251 271 1.728 L 44.00 C=120 PT 25.85 (271)
Q 29.44 F::T/T F 18.00 PE 0.00
BL T 62.00 0.0234 PF 1.45
201 251 1.728 L 1.00 C=120 PT 27.30 (251)
Q 29.44 F=T F 9.00 PE 0.43
RN T 10.00 0.0234 PF 0.23
200 201DQ 447.10 4.260 L 12.00 c-120 PT 27.96 (201)
Q 476.54 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0499 PF 0.60
PT 28.56 (200)
------------------250 270 1.728 L 44.00 C=120 PT 26.33 (270)
Q 30.55 F=T/T F 18.00 PE 0.00
BL T 62.00 0.0251 PF 1.56
200 250 1.728 L 1.00 C=l20 PT 27.89 (250)
Q 30.55 F=T F 9.00 PE 0.43
RN T 10.00 0.0251 PF 0.25
150 200DQ 476.54 4.260 L 2.00 C=120 PT 28.57 (200)
Q 507.09 F=T F 21.07 PE 0.00
CM T 23.07 0.0560 PF 1.29
PT 29.86 (150) ------------------246 230 4.260 L 12.00 C=120 PT 22.07 (230)
Q 101.37 F=-0 F 0.00 PE 0.00
CM3 T 12.00 0.0028 PF 0.03
SUBMI'ITAL SERIAL NO:2932HY7 09-05-2013 PAGE 13
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss summary
From To GPM IN Devices Ft PSI/Ft PSI
247 246DQ -50.73 4.260 L 12.00 C=l20 PT 22.10 (246)
Q 50.65 F=0 F 0.00 PE 0.00
CM3 T 12.00 0.0008 PF 0.01
297 247 1.728 L 1.00 C=120 PT 22.11 (247)
Q 50.65 F=T F 9.00 PE -0.43
RN T 10.00 0.0639 PF 0.64
295 297 1.728 L 56.00 C=120 PT 22.32 (297)
Q 50.65 F=T/T F 18.00 PE 0.00
BL T 74.00 0.0639 PF 4.73
245 295 1.728 L 1.00 c-120 PT 27.05 (295)
Q 50.65 F=T F 9.00 PE 0.43
RN T 10.00 0.0639 PF 0.64
244 245 4.260 L 12.00 C=120 PT 28.12 (245)
Q 50.65 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0008 PF 0.01
PT 28.13 (244) ------------------296 246 1.728 L 1.00 C=l20 PT 22.10 (246)
Q 50.73 F=T F 9.00 PE -0.43
RN T 10.00 0.0641 PF 0.64
294 296 1.728 L 56.00 c-120 PT 22.31 (296)
Q 50.73 F=T/T F 18.00 PE 0.00
BL T 74.00 0.0641 PF 4.74
244 294 1.728 L 1.00 Cal20 PT 27.05 (294)
Q 50.73 F=T F 9.00 PE 0.43
RN T 10.00 0.0641 PF 0.64
151 244DQ 50.65 4.260 L 10.00 c-120 PT 28.12 (244)
Q 101.37 F=T F 21.07 PE 0.00
CM T 31.07 0.0028 PF 0.09
PT 28.21 (151)
------------------227 277 1.728 L 1.00 C=120 PT 23.76 (277)
Q 52.39 F=T F 9.00 PE 0 .43
RN T 10.00 0.0680 PF 0.68
226 227 4.260 L 12.00 C=120 PT 24.87 (227)
Q 52.39 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0008 PF 0.01
PT 24.88 (226) ------------------226 276 1.728 L 1.00 C=120 PT 21.94 (276)
Q 106.18 F=T F 9.00 PE 0.43
RN T 10.00 0.2512 PF 2.51
SUBMITI'AL SERIAL NO:2932HY7 09-05-2013 PAGE 14
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
225 226DQ 52.39 4.260 L 12.00 C=120 PT 24.88 (226)
Q 158.57 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0065 PF 0.08
PT 24.96 (225) ------------------225 275 1.728 L 1.00 C=120 PT 22.04 (275)
Q 105.82 F=T F 9.00 PE 0.43
RN T 10.00 0.2496 PF 2.50
224 225DQ 158.57 4.260 L 12.00 c .. 120 PT 24.97 (225)
Q 264.38 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0168 PF 0.20
PT 25.17 (224) ------------------224 274 1.728 L 1.00 C=120 PT 22.23 (274)
Q 105.99 F=T F 9.00 PE 0.43
RN T 10.00 0.2503 PF 2.50
223 224DQ 264.38 4.260 L 12.00 C=l20 PT 25.16 (224)
Q 370.37 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0313 PF 0.38
PT 25.54 (223) ------------------223 273 1.728 L 1.00 C=120 PT 25.01 (273)
Q 18.94 F=T F 9.00 PE 0.43
RN T 10.00 0.0104 PF 0.10
222 223DQ 370.37 4.260 L 12.00 C=120 PT 25.54 (223)
Q 389.32 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0343 PF 0.41
PT 25.95 (222)
------------------222 272 1.728 L 1.00 C=l20 PT 25.41 (272)
Q 19.74 F=T F 9.00 PE 0.43
RN T 10.00 0.0112 PF 0.11
221 222DQ 389.32 4.260 L 12.00 C=120 PT 25.95 (222)
Q 409.05 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0376 PF 0.45
PT 26.40 (221) ------------------221 271 1.728 L 1.00 C=120 PT 25.85 (271)
Q 20.87 F=T F 9.00 PE 0.43
RN T 10.00 0.0124 PF 0.12
220 221DQ 409.05 4.260 L 12.00 Cm:120 PT 26.40 (221)
Q 429.92 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0412 PF 0.49
PT 26.89 (220)
SUBMITTAL SERIAL NO:2932HY7 09-05-2013 PAGE 15
PHILLIPS BACKFLOW UPGRADE SYSTEM #2 .33/3000 (PEAKED)
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
------------------220 270 1.728 L 1.00 C=l20 PT 26.33 (270)
Q 22.28 F=T F 9.00 PE 0.43
RN T 10.00 0.0140 PF 0.14
151 220DQ 429.92 4.260 L 20.00 C=120 PT 26.90 (220)
Q 452.20 F=E F 8.95 PE 0.00
CM T 28.95 0.0453 PF 1.31
150 151DQ 101.38 4.260 L 25.00 C=120 PT 28.21 (151)
Q 553.58 F=0 F 0.00 PE 0.00
CM T 25.00 0.0658 PF 1.65
PT 29.86 (150) ------------------237 287 1.728 L 1.00 C=120 PT 19.00 (287)
Q 92.69 F=T F 9.00 PE 0.43
RN T 10.00 0.1954 PF 1.95
PT 21.38 (237)
------------------6 150 6.357 L 98.00 C=120 PT 29.86 (150)
Q 1060.66 F=2E F 25.14 PE 0.00
FM T 123.14 0.0312 PF 3.84
4 6 6.357 L 26.00 C=120 PT 33.70 6)
Q 1060.66 F=T,GV/T F 66.63 PE 11.27
FR T 92.63 0.0312 PF 2.89
3 4 8.249 L 2.00 C=120 PT 47.86 4)
Q 1060.66 F=E F 21.14 PE 0.00
MA T 23.14 0.0088 PF 0.20
2 3DQ 100.00 8.249 L 3.00 C=120 PT 48.06 ( 3)
Q 1160.66 F=E F 21.14 PE 0.00
MA T 24.14 0.0104 PF 0.25
1 2 8.249 L 10.00 C=l20 PT 48.31 2)
Q 1160.66 F=2E F 42.28 PE 1.30
MA T 52.28 0.01.04 PF 0.54
0 1 7.680 L 25.00 C=lS0. PT 50.15 1)
Q 1160.66 F 161.62 ,PE 0.00
UN T 186.62 0.0097 PF 1.81 \0 8 II FEBCO 826YD 12.97