HomeMy WebLinkAboutFPC2022-0159; 2470 FARADAY AVEPERMIT REPORT
Fire Permit
Print Date: 10/18/2023
Job Address:
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
2470 FARADAY AVE, CARLSBAD, CA 92010-7224
FIRE-Construction Commercial Work Class:
2090412600 Track#:
$0.00 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Fire Alarm
(city of
Carlsbad
Permit No: FPC2022-0159
Status: Closed -Finaled
Applied: 08/30/2022
Issued: 09/27/2022
Finaled Close Out: 05/09/2023
Final Inspection:
INSPECTOR: Cheung, Nathaniel
Description: SCIEX 2 (BECKMAN COULTER) -ADD 1 DUCT SMOKE DETECTOR & 1 SMOKE HEAT DETECTOR -CONNECT TO EXISTING FIRE PAI
Applicant:
SECURITAS TECHNOLOGY STANLEY SECURITY
SCOTT HAIN ES
13034 CREE DR
POWAY, CA 92064-3815
(858) 276-9742
FEE
FIRE Tl Fire Alarm System
Total Fees: $735.00 Total Payments To Date: $735.00
FPContractor:
STANLEY SECURITY
9240 TRADE PL, # STE 300
SAN DIEGO, CA 92126-6314
(858) 752-1775
Balance Due:
AMOUNT
$735.00
$0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2665 I Inspections: 442-339-2660 I www.carlsbadca.gov
(2) F1re·L11e· Alarms
www.firelite.com
GENERAL
The Fire•Lite Alarms 5D355 and SD355T addressable,
low-profile plug-in photoelectric detectors use a state-of-
the-art photoelectric sensing chamber with communica-
tions to provide open area protection and are used exclu-
sively with Fire•Lite's MS-9200, MS-9200UD, and MS-9600
Addressable Fire Alarm Control Panels (FACPs). The
SD355T adds thermal sensors that will alarm at a fixed
temperature of 135°F (57°C)' Since these detectors are
addressable, they will help emergency personnel quickly
locate a fire during its early stages, potentially saving pre-
cious rescue time while also reducing property damage
Two LEDs on each sensor light to provide a local, visible
sensor indication. Remote LED annunciator capability is
available as an optional accessory (P/N RA400Z)
FEATURES
SLC/oop:
• Two-wire loop connection.
• Unit uses base for wiring. detector head plugs-in.
Addressing:
Addressable by device.
• D,rect Decade 01 -99 (MS-9200, MS-9200UD) and 01
-159 (MS-9600) entry of address.
Architecture:
Unique single-source, dual-chamber design to respond
quickly and dependably to a broad range of fires
Sleek, low-profile design.
Integral communications and built-in type identification.
Built-in tamper-resistant feature
Removable cover and insect-resistant screen for simple
field cleaning.
Operation:
Withstands air velocities up to 1,500 feet-per-minute (7 6
m/sec.) without triggering a false alarm.
Factory preset at 1.5% nominal sensitivity for panel alarm
threshold level.
Visible LED "blinks" when the unit is addressed (com-
municating with the fire panel) and latches on in alarm.
Mechanicals:
Sealed against back pressure
Direct surface mounting or electrical box mounting.
Mounts to: single-gang box, 35" (8.89 cm) or 4.0" (10.16
cm) octagonal box, or 4.0" (10.16 cm) square electrical
box (using a plaster ring -included).
Fire•Lite® Alarms is a Honeywell company
July 14, 2004 DF-52384 • E-160
SD355(A)/ SD355T(A)
Addressable Photoelectrlc Smoke
Detectors
Section: Addressable Devices
®~
LISTED
S1059 MEA
5D355 with
srn,,o,~
SD355T with •
B350LP base '""
Other system features:
California
State Fire
Marshal
7272-0075 194
<8>
APPROVED
Fully coated circuit boards and superior RF/transient pro-
tection.
94-V0 plastic flammability rating
Low standby current
Options:
• Remote LED output connection (PIN RA400Z)
APPLICATIONS
Use photoelectric detectors in life-safety applications to pro-
vide a broad range of fire-sensing capability, especially
where smoldering fires are anticipated. Ionization detec-
tors are often better than photoelectric detectors at sens-
ing fast, flaming fires.
This document is not intended to be used tor installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticipate all
requirements. All specifications are subject to change without notice.
ISO 9001
CERTIFIED
ENIINIIIING I MANUIIICTIIIING QUALITY SYSTEMS For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472.
Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105
OF-52384 • 07/14104 -Page 1 of 2
CONSTRUCTION
These detectors are constructed of off-white LEXAN®.
SD355(T) plug-in, low-profile smoke detectors are designed
to commercial standards and offer an attractive appear-
ance
LEXAN® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
INSTALLATION
SD350(T) plug-in detectors use a detachable mounting base
to simplify installation, service and maintenance. Mount
base on box which is at least 1.5 inches (3.81 cm) deep.
Suitable boxes include:
4.0" (10 16 cm) square box with plaster ring.
4.0" (10 16 cm) octagonal box
3.5" (8 89 cm) octagonal box
Single-gang box.
NOTE: Because of the inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring "T-taps" or
branches are permitted for Style 4 (Class BJ wiring only
OPERATION
Each SD355(T) uses one of 99 possible addresses on the
MS-9200 and MS-9200UD Signaling Line Circuit (SLC), or
up to 318 (159 on each loop) on the MS-9600 SLC. It re-
sponds to regular polls from the system and reports its type
and status.
The SD355(T) addressable photoelectric sensor's unique
unipolar chamber responds quickly and uniformly to a broad
range of smoke conditions and can withstand wind gusts
up to 1,500 feet-per-minute (7.6 m/sec.) without sending
an alarm level signal. Because of its unipolar chamber, the
SD355(T) is approximately two times more responsive than
most photoelectric sensors. This makes it a more stable
detector.
DETECTOR SENSITIVITY TEST
Each detector can have their sensitivity tested (required
per NFPA 72, Chapter 7 on Inspection, Tes/mg and Main-
tenance) when installed/connected to an MS-9200, MS-
9200UD, or MS-9600 addressable fire alarm control panel
The results of the sensitivity test can be printed off the MS-
9200, MS-9200UD, or MS-9600 for record keeping.
SPECIFICATIONS
Voltage range: 15 -32 voe (peak).
Standby current: 300 µA@ 24 voe.
LED current: 6.5 mA@ 24 VDC (latched "ON")
Air velocity: 1,500 ft/min. (7.6 m/sec.) maximum.
Diameter: 6.1" (15.5 cm) installed in B350LP base
Height: 2.1" (5.33 cm) installed in B350LP base.
Weight: 3.6 oz. (102 g).
Operating temperature range: for SD355: O'C to 49'C
(32°F to 120'F) SD350; for SD355T: O'C to 38'C (32'F to
1 OO'F).
Temperature: O'C -49'C (32'F -120'F)
Relative humidity: 10% -93%, non-condensing
Page 2 of 2 ~ DF-52384 • 07/14/04
PRODUCT LINE INFORMATION
NOTE: "A" suffix indicates ULC-Listed model.
S0355 Addressable photoelectric detector (8350LP
base included)
S0355A Same as S0355 with ULC Listing (8350LPA
base included).
SD355T Same as S0355 but with thermal element
(8350LP base included).
S0355TA Same as SD355T with ULC Listing (8350LPA
base included).
RA400Z(A) Remote LED Mounts to a single-gang box.
B350LP(A) Plug-in detector base (included). Dimen-
sions: 6.1" (15.5 cm). Mounting:4.0" (10.16
cm) square box with or without plastic ring,
4.0" (10.16 cm) octagonal box, 3.5" (8 89 cm)
octagonal box, or single-gang box. All mount-
ing boxes have a minimum depth of 1.5" (3 81
cm)
B224RB(A) Plug-in System Sensor relay detector base.
Diameter: 6.2" (15.75 cm). Mounting: 4.0"
(10.16 cm) square box with or without plastic
ring, 4.0" (10 16 cm) octagonal box, or 3.5"
(8 89 cm) octagonal box. All mounting boxes
have a minimum depth of 1.5" (3 81 cm)
B224BI(A) Intelligent isolator base, isolator SLC from
shorts on the loop
B501BH(A) Plug-in System Sensor sounder detector
base. Diameter: 6.0" (15.24 cm). Mounting:
4.0" (10.16 cm) square box with or without
plastic ring. Mounting box has a minimum
depth of 1.5" (3 81 cm).
B501BHT(A) Same as B501BBH(A), but includes tempo-
ral sounder.
Accessories:
RA400Z(A) Remote LED annunciator. 3 -32 VDC. Fits
U.S. single-gang electrical box. For use with
8501 (A) and 8350LP(A) bases only.
SMK400 Surface mounting kit provides for entry of
surface wiring conduit For use with 8501(A)
base only.
RMK400 Recessed mounting kit For use with 8501 (A)
base only.
M02-04-01 Test magnet
XR-2 Detector removal tool. Allows installation and/
or removal of detector heads from bases in
high ceiling applications.
XP-4 Extension pole for XR-2. Comes in three 5-ft.
(1 524 m) sections.
~SYSTEM
'--~ SENSOR.
Duct Smoke
Detector Accessories
Expand the versatility of the lnnovairFlex" line of duct
smoke detectors with System Sensor notification and test
accessories.
Available Accessories
APA151
MHR
MHW
RA 100Z/RA 100ZA
RTS151
RTS151KEY
RTS2
ADS
RTS2-AOS
Piezo Annunciator
Mini-Horn, Red
Mini-Horn. White
Remote Annunciator
Remote Test Station
Remote Test Station with Key
Mult1-S1gnal1ng Accessory
Add-On Strobe
Mult1-S1gnal1ng Accessory
Agency Listings
@
LISTED <8> APJ'ROVED
Duct smoke detector accessories add functionality to the duct
smoke detection system by allowing quick, convenient inspections
at eye level and effective audible and v1s1ble notification options. All
System Sensor duct smoke detectors and accessories are UL listed
The APA151 pIezo annunciator. which replaces the APA451 with a
new. improved look, provides an audible alarm signal. a red LED to
indicate alarm status. and a green LED to indicate power status It Is
intended for use with System Sensor 4-wire conventional duct smoke
detector applications without a system control panel to comply with
NFPA 90A
The MHR and MHW SpectrAlerr·, Advance mini-horns feature
temporal or continuous tones at high and low volume settings
n1eir small footprint allows mounting to single-gang back boxes for
applications wl1ere a small device is desired
The RA100Z and RA100ZA remote annunciators are designed
for both conventional and intelligent applications Their red LED
provides visual indication oi an alarm condition
The RTS151 and RTS151KEY remote test stations are automatic
fire detector accessories designed to test duct smoke detectors
from a convenient location. For 4-wire detectors, the RTS151 KEY test
station features a multi-colored LED that alternates between steady
green and red For 2-wire detectors, the LED illuminates red for
alarm
The RTS2 and RTS2-AOS multi-signaling accessories are
designed to work with lnnova1rFlex 4-wire conventional duct smoke
detectors These accessories include a key switch that can be used
to select one ot two connected sensors to be tested. reset. or both
by a push button switch They also enable sensitivity measurements
using the SENS-RDR sensitivity reader (sold separately). The AOS
(Add-On Strobe) is an optional accessory included with the RTS2-
AOS model
Specifications, Duct Smoke Detector Accessories
APA151 Piezo Annunciator
Voltage Regulated 24 voe
Operating Voltage 16 to 33 voe
Maximum Alarm Current 30mA
Temperature Range O"C to 49°e (32'F to 120"F)
Relative Humidity 1 Oto 93°/c, non-condensing
Wire Gauge 12 to 18 AWG
Dimensions 4 6"H x 2.9"W x .45"0
MHR/MHW SpectrAlerf2' Advance Mini-Horns
Voltage
Sounder Current Draw
Temperature Range
Humidity Range
Nominal Sounder
Frequency
Wire Gauge
Dimensions
Regulated 12 DC or FWR (Full Wave
Rect1f1ed) or Regulated 24 voe or FWR
22 mA RMS max. at 8 to 17 .5 Volts DC
29 mA RMS max. at 16 to 33 Volts DC
O"e to 49 •e (32' F to 120"F)
10 to 93% non-condensing
3 kHz
12 to 18 AWG
46"Hx29"'Wx045 D
RA100Z/RA100ZA Remote Annunciator
Voltage Range
Maximum Alarm Current
Dimensions
RTS151 UL S4011
RA 1002 UL S2522
Conventional System. 3 1 to 32 VDC
Intelligent System rn to 32 voe
10mA
46 "Hx28"Wx 1.3"0
RTS151KEY UL S2522
MHW UL S4011
RTS151 Remote Test Station
Power Requirements
Test Switch
Reset Switch
Alarm Response Time
Temperature Range
Relative Humidity
Wire Gauge
Dimensions
Alarm LED: 2.8 to 32 VDC, 12 mA max
Total Current: 105 mA max
10 VA@32 voe
10VA@32VOe
40 seconds max
-10'e to 60°e (WF to 140"F)
95% non-condensing
14 to 18 AWG
48Hx2.90'Wx14'0
RTS151KEY Remote Test Station with Key
Power Requirements
Alarm Response Time
Temperature Range
Relative Humidity
Wire Gauge
Dimensions
Power LED (Green): 14 to 35 voe,
12 mA max.
Alarm LED (Red) 2 8 to 32 VDC
12 mA max
Total Current: I 05 mA max
40 seconds max
95% non-condensing
14 to 18 AWG
4.6Hx2.75'Wx1.8'0
RTS2 and RTS2-AOS Multi-signaling Accessory
Voltage
Power Requirements
Sounder
Temperature Range
Relative Humidity
Wire Gauge
20 to 29 voe
Standby: 3 O mA max
Trouble. 16 O mA max
Alarm without strobe: 30 mA max
Alarm with strobe: 55 mA max
85 dBA at ten feet
-100 to so•c (14"F to 140'FI
95% non-condensing
14 to 22 AWG
Dimensions 4.S'"W x 5.3"H x 1 6"'0
For the very latest product specifications and listing information.
please visit the System Sensor Web site at www.systemsensor.com
--__; --~ .....-·-.-
APA151 UL S4011 RTS2-AOS UL S2522
MHR UL S4011 AOS
~~SYSTEM C~ SENSOR
3825 Ohio Avenue• St Charles. IL 60174
Phone 800-SENSOR2 • Fax 630-377-6495
www systemsensor.com
,., j, • ,,,I •' 11 ,r " l,W
MMF-300(A) Series,
MDF-300
Addressable Monitor Modules
General
Four different monitor modules are available for Fire•Lite's
intelligent control panels to suit a variety of applications. Moni-
tor modules are used to supervise a circuit of dry-contact input
devices, such as conventional heat detectors and pull stations,
or monitor and power a circuit of two-wire smoke detectors
(MMF-302(A)).
MMF-300(A) is a standard-sized module (typically mounts to a
4" [10.16 cm] square box) that supervises either a Style D
(Class A) or Style B (Class B) circuit of dry-contact input
devices.
MMF-301(A) is a miniature monitor module a mere 1.3" (3.302
cm) H x 2. 75" (6.985 cm) W x 0.65" (1.651 cm) D that super-
vises a Style B (Class B) circuit of dry-contact input devices. Its
compact design allows the MMF-301(A) to be mounted in a
single-gang box behind the device it monitors.
MMF-302(A) is a standard-sized module used to monitor and
supervise compatible two-wire, 24 volt, smoke detectors on a
Style D (Class A) or Style B (Class B) circuit
MDF-300(A) is a standard-sized dual monitor module used to
monitor and supervise two independent two-wire Style B
(Class B) dry-contact initiating device circuits (IDCs) at two
separate, consecutive addresses in intelligent, two-wire sys-
tems.
LiteSpeed™ ls a communication protocol developed by
Fire•Lite Engineering that greatly increases the speed of com-
munication between analog intelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other communication protocols.
MMF-300(A) Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the control panel.
Powered directly by two-wire SLC loop. No additional
power required.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 -159 on MS-9600 series
panels, 01 -99 on other compatible systems.
LEO flashes during normal operation and latches on steady
to indicate alarm.
The MMF-300(A) Monitor Module is intended for use in intelli-
gent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It pro-
vides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for nonmally-open-contact fire alanm and
supervisory devices. The module has a panel-controlled LED
indicator. The MMF-300(A) can be used to replace M300(A)
modules in existing systems.
MMF-300(A) APPLJCATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
DF-52121:E • E-325
@) Flre·LITe'ALarms
by Honeywell
Addressable Devices
MMF-300(A) (Type H)
supervisory indication at the control panel. Monitored circuit
may ba wired as an NFPA Style B (Class B) or Style D (Class
A) Initiating Device Circurt. A 47K Ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is required
for supervision of the Style D circuit.
MMF-300(A) OPERATION
Each MMF-300(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC). A flashing LED
indicates that the module is in communication with the control
panel. The LED latches steady on alanm (subject to current
limitations on the loop).
MMF-300(A) SPECIRCATIONS
Nominal operating voltage: 15 to 32 voe.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 375 µA (LED flashing), 1 com-
munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
EOL resistance: 47K Ohms.
Temperature range: 32'F to 120"F (0'C to 49'C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
MMF-301(A) Mini Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the panel.
Powered directly by two-wire SLC loop. No additional
power required.
High noise (EMF/RFI) immunity.
DF-52121:E•07/30/2015-Page 1 of4
Tinned, stripped leads for ease of wiring.
Direct-dial entry of address: 01 -159 on MS-9600 series
panels, 01 -99 on other compatible systems
1~1@4
150
12
ADDRESS
~: ~~ @ ; LOOP
10 5 D 9 8 7 6 9 8 7 6
TENS ONES
~ ~
~ ~ ~
The MMF-301 (A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The MMF-301 (A) is intended for use in intelligent,
two-wire systems where the individual address of each module
is selected using rotary switches. It provides a two-wire initiat-
ing device circuit for normally-open-contact fire alarm devices.
The MMF-301(A) can be used to replace M301(A) modules in
existing systems.
MMF-301(A) APPLJCAn0NS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterflow devices,
or other normally-open dry-contact devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit/
device is wired as an NFPA Style B (Class B) Initiating Device
Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates
the circuit.
MMF-301(A) OPERAn0N
Each MMF-301(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initialing Device Circuit (IDC).
MMF-301(A) SPECIRCATIONS
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 µA, 1 communication every
5 seconds, 47k EOL; 600 µA Max. (Communicating, IDC
Shorted).
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 450 µA.
EOL resistance: 47K Ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
MMF-302(A) Interface Module
• Supports compatible two-wire smoke detectors.
Page 2 of 4 -DF-52121 :E • 07/30/2015
Supervises IDC wiring and connection of external power
source.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry entry of address: 01 -159 on MS-9600
series panels, 01 -99 on other compatible systems.
LED flashes during normal operation.
LED latches steady to indicate alarm on command from
control panel.
The MMF-302(A) Interface Module is intended for use in intelli-
gent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor two-
wire conventional smoke detectors. It transmits the status
(normal, open, or alarm) of one full zone of conventional
detectors back to the control panel. All two-wire detectors
being monitored must be UL compatible with the module. The
MMF-302(A) can be used to replace M302(A) modules in
existing systems.
MMF-302 (A) APPLICAnONS
Use the MMF-302(A) to monitor a zone of two-wire smoke
detectors. The monitored circuit may be wired as an NFPA
Style B (Class B) or Style D (Class A) Initiating Device Circuit.
A 3.9 K Ohm End-of-Line Resistor (provided) terminates the
end of the Style B or D (class B or A) circuit (maximum IDC
loop resistance is 25 Ohms). Install ELR across terminals 8
and 9 for Style D application.
MMF-302(A) OPERAn0N
Each MMF-302(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC). A flashing LED
indicates that the module is in communication with the control
panel. The LED latches steady on alamn (subject to current
limitations on the loop).
MMF-302(A) SPECIRCAnONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 Ohms.
Average operating current: 270 µA, 1 communication and 1
LED flash every 5 seconds, 3.9k eel.
EOL resistance: 3.9K Ohms.
External supply voltage (between Terminals T10 and T11):
DC voltage: 24 volts power limited.
• Ripple voltage: 0.1 Vmns maximum.
• Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
MDF-300(A) Dual Monitor Module
The MDF-300(A) Dual Monitor Module is intended for use in
intelligent, two-wire systems. It provides two independent two-
wire initiating device circuits (IOCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices. The module has a single panel-
controlled LED.
NOTE: The MDF-300(A) provides two Style B (Class BJ /DC cir-
cuits ONLY. Style D (Class A) /DC circuits are NOT supported in
any application.
MDF-300(A) SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 µA (LED flashing).
Maximum JDC wiring resistance: 1,500 Ohms.
Maximum JDC Voltage: 11 Volts.
Maximum JDC Current: 240 µA
EOL resistance: 47K Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
MDF-300(A) AUTOMATIC ADDRESSING
The MDF-300(A) automatically assigns itself to two address-
able points, starting with the original address. For example, if
the MDF-300(A) is set to address "26", then it will automati-
cally assign itself to addresses "26" and "27".
NOTE: "Ones" addresses on the MDF-300(A) are 0, 2, 4, 6, or 8
only. Terminals 6 and 7 use the first address, and terminals 8 and
9 use the second address.
CAUTION:
Avoid duplicating addresses on the system.
Installation
MMF-300(A), MMF-302(A), and MDF-300(A) modules mount
directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm)
deep, electrical box. They may also be mounted to the
SMB500 surface-mount box. Mounting hardware and installa-
tion instructions are provided with each module. All wiring
must conform to applicable local codes, ordinances, and regu-
lations. These modules are intended for power-limited wiring
only.
The MMF-301 (A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances,
and regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL: S2424.
ULC: S2424.
FM Approved,
CSFM: 7300-0075:0185.
MEA: 72-01-E.
Product Line Information
NOTE: "A" suffix indicates ULC-/isted model.
MMF-300(A): Monitor module.
MMF-301(A): Monitor module, miniature.
MMF-302(A): Monitor module, two-wire detectors.
MDF-300(A): Monitor module, dual, two independent Class B
circuits.
SMBS00: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51309.
Architects'/Englneers' Specifications
Specifications of these devices and all Firelite products are
available from Firelite.
OF-52121 :E • 07/30/2015 -Page 3 of 4
•
ISO 9001 19ii-S ◄IWl¥i-■
1111111111!1 1 IIIIIRIIUNG
IIAIITY SYSTl ■s
Fire-Lite® is a registered trademark and LiteSpeed™ and FireWatch™ are
trademarks of Honeywell International Inc.
C2015 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
we try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Fire•Lite Alarms. Phone: (600) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Page 4 of 4-DF-52121:E • 07/30/2015