HomeMy WebLinkAboutPD 2020-0007; FUKUDA RESIDENCE; GEOTECHNICAL UPDATE REPORT AND GRADING PLAN REVIEW; 2020-08-03£9AST GEOTECHNICAL
GENGINEERING GEOLOGISTS
August 3, 2020 W.O. 707419
Lane Fukuda
2726 Morning Glory Lane
Carlsbad, California 92008
Subject: GEOTECHNICAL UPDATE REPORT AND GRADING PLAN REVIEW
Proposed Second Story Addition and Basement
2726 Morning Glory Lane
Carlsbad, California
References: THIRD PARTY GEOTECHNICAL REVIEW (FIRST) J]CijyJfl) Proposed Second Story Addition and Basement
2726 Morning Glory Lane
Carlsbad, California LAND DEVELOPMENT Project ID: PD2020-0007
Prepared by Hetherington Engineering, Inc. ENGINEERING
Dated June 19, 2020
GRADING PLAN
Fukuda Addition
2726 Morning Glory Lane
Prepared by Rancho Coastal Engineering & Surveying, Inc.
Dated May 20, 2020 and July 17, 2020
Scale: 1 "=5', Sheets 1, 3 and 4
PRELIMINARY GEOTECHNICAL INVESTIGATION
Proposed Second Story Addition and Basement
2726 Morning Glory Lane
Carlsbad, California
Prepared by Coast Geotechnical
Dated June 18, 2019
Dear Mr. Fukuda:
At the time of our Preliminary Geotechnical Investigation Report, site plans, topographic surveys
and grading plans were unavailable for review. This report presents an Update to our Preliminary
Geotechnical Investigation Report, a Grading Plan Review and our response to the referenced third
party review comments.
P.O. BOX 230163 • ENCINITAS, CALIFORNIA 92023
(858) 755-8622
Coast Geotechnical August 3, 2020
W.O. P-707419
Page 2 of 8
GEOTECHNICAL UPDATE
A review of the current grading plans prepared by Rancho Coastal Engineering and Surveying
suggests that the development of the site is in substantial conformance with the design concepts
anticipated in the Preliminary Geotechnical Investigation Report.
Proposed Grading
The grading recommendations including temporary slopes and alternate slot cuts remain applicable
and should be implemented during the grading and construction phases. Temporary slopes and slot
cuts should be observed by an Engineering Geologist. Additional recommendations may be
necessary based on actual conditions revealed during grading.
Foundations
The foundation recommendations presented in the Preliminary Geotechnical Investigation Report
remain applicable and should be implemented during the design and construction phases.
Retaining Walls
Retaining wall design parameters remain applicable and should be implemented in the design phase.
Special consideration should be given to waterproofing, as indicated in the Preliminary Geotechnical
Investigation Report.
Dynamic (Seismic) Lateral Earth Pressures
Potential seismic loading has been revised based on California Building Code (2019) and ASCE
7-16.
For proposed restrained walls (non-yielding), potential seismic loading should be considered. For
smooth rigid walls, Wood (1973) expressed the dynamic thrust in the following form:
APe = khYH2 (nonyielding)
P.O. BOX 230163 • ENCINITAS, CALIFORNIA 92023
(858) 755-8622
Coast Geotechnical August 3, 2020
W.O. P-707419
Page 3 of 8
where kh is /2 peak ground acceleration equal to 50 percent of the design spectral response
acceleration coefficient (Sds) divided by 2.5 per C.B.C. (2007), Y is equal to the unit weight of
backfill, and H is equal to the height of the wall.
The pressure diagram for this dynamic component can be approximated as an inverted trapezoid with
stress decreasing with depth. The point of application of the dynamic thrust is at a height of 0.6
above the base of the wall. The magnitude of the resultant is:
iPe = 18.8 H2 (nonyielding)
This dynamic component should be added to the at-rest static pressure for seismic loading
conditions.
For cantilever walls (yielding), Seed and Whitman (1970) developed the dynamic thrust as:
iPe = 3/8 khYH2 (yielding)
The pressure diagram for this dynamic component can be approximated as an inverted trapezoid with
stress decreasing with depth and the resultant at a height of 0.6 above the base of the wall. The
magnitude of the resultant is:
APe = 7.1 H2 (yielding)
This dynamic component should be added to the static pressure for seismic loading conditions.
P.O. BOX 230163. ENCITAS, CALIFORNIA 92023
(858) 755-8622
Coast Geotechnical August 3, 2020
W.O. P-707419
Page 4 of 8
Seismic Considerations
Although the likelihood of ground rupture on the site is remote, the property will be exposed to
moderate to high levels of ground motion resulting from the release of energy should an earthquake
occur along the numerous known and unknown faults in the region. The Newport/Inglewood Fault
Zone located approximately 5.2 miles west of the property is the nearest known active fault, and is
considered the design fault for the site. In addition to the Newport-Inglewood Fault, several other
active faults may affect the subject site.
Seismic design parameters were evaluated as part of this investigation in accordance with the 2019
California Building Code (CBC) and ASCE 7-16 Standard using the web-based United States
Geological Survey (USGS) Seismic Design Tool. The generated results for the parameters are
presented on Table 2.
Table 2: Seismic Design Parameters
Factors Values
Site Class D
Seismic Design Category 1111/Ill
Site Coefficient, Fa 1.084
Site Coefficient, Fv N/A
Mapped Short Period Spectral Acceleration, S 1.041
Mapped One-Period Spectral Acceleration, S1 0.378
Short Period Spectral Acceleration Adjusted for Site Class, 5MS 1.128
One-Second Period Spectral Acceleration Adjusted for Site, 5M1 N/A
Design Short Period Spectral Acceleration, SDS 0.752
Design One-Second Period Spectral Acceleration, SDI N/A
P.O. BOX 230163 • ENCIT4ITAS, CALIFORNIA 92023
(858) 755-8622
Coast Geotechnical August 3, 2020
W.O. P-707419
Page 5 of 8
Site Classification For Seismic Design
Site soils are classified based on the upper 100 feet maximum of site subsoil profile. In the absence
of sufficient or specific site data, appropriate soil properties are permitted to be estimated by the
project geotechnical consultant based on known geotechnical conditions, and Site Class D is
typically used as a "default", unless otherwise noted. Site Classes A and B shall not be assigned to
a site, if there is more than 10 feet of soil (or fill) between the top of the underlying rock surface and
bottom of the foundation.
Site Classes A and B are most commonly supported by shear wave velocity determination (Us, ft/s).
Site Class F, which may require a site response analysis, consists of liquefiable or collapsible soils
and highly sensitive clayey soil profile. Site Classes C, D, and E soils may be classified using an
average field Standard Penetration Resistance (R) method for soil layers based on Section 20.4.2 of
ASCE 7-16. Where refusal is met for a rock layer (blow counts of 50 or greater for 6 inches or less
penetration), Ni is taken as 100 blows per foot. Site Classification is then established based on Table
20.3-1 of ASCE 7-16.
Requirements provided below are also applicable and should be incorporated in the project designs
where appropriate:
1. Site specific hazard analysis is required (see Section 11.4.8) in accordance with Chapter 21.2 of
ASCE 7-16 for structures on Site Class E sites with values of Ss greater than or equal to 1.0g,
and structures on Site Class D and E sites with values of Si greater than or equal to 0.2g.
However, the following 3 exceptions are permitted for Equivalent Lateral Force design (ELF)
using conservative values of seismic design parameters in lieu of performing a site specific
ground motion analysis:
P.O. BOX 230163 • ENCINITAS, CALIFORNIA 92023
(858) 755-8622
Coast Geotechnical August 3, 2020
W.O. P-707419
Page 6 of 8
* Structures on Site Class E sites with Ss greater than or equal to 1.0, provided the site
coefficient Fa is taken as equal to that of Site Class C.
* For structures on Site Class D sites with Si greater than or equal to 0.2, a long period
coefficient (Fv) of 1.7 may be utilized for calculation of Ts, provided that the value of
Seismic Response Coefficient (Cs) is determined by Equation (12.8-2) for values of the
fundamental period of the building (T) less than or equal to 1 .5Ts, and taken as 1.5 times the
value computed in accordance with either Equation 12.8-3 for T greater than 1.5 Ts and less
than or equal to TL or Equation 12.8-4 for T greater than IL.
* Structures on Site Class E sites with S 1 greater than or equal to 0.2, provided that I is less
than or equal to Ts and the equivalent static force procedure is used for the design.
Where Site Class B is recommended, and a site specific measurement is not provided, the site
coefficients Fa, Fv, and FPGA shall be taken as unity (1.0) in accordance to Section 11.4.3 of
ASCE 7-16.
Where Site Class D is selected as the "default" site class per Section 11.4.3 of ASCE 7-16, the
value of Fa shall not be less than 1.2. Where the simplified procedure of Section 12.4 is used,
the value of Fa shall be determined in accordance with Section 12.14.8.1, and the values of Fv,
SMS and SM1 need not to be determined.
At the project property massive dense and competent Pleistocene Very Old Paralic Deposits occur
at very shallow depths on the order of 1.0 foot maximum below the existing ground surface (BGS),
and based on our past experience with similar deposits, Site Class D (Stiff Soil), can be
conservatively considered for the project site subsoil profile, unless otherwise noted.
P.O. BOX 230163 • ENCINITAS, CALIFORNIA 92023
(858) 755-8622
Coast Geotechnical August 3, 2020
W.O. P-707419
Page 7 of 8
RESPONSE TO THIRD PARTY REVIEW
Plans, grading, foundations and other pertinent data are addressed in this Updated Geotechnical
Report and are consistent with the 2019 C.B.C.
The current grading plans have been reviewed and are in general conformance with the
recommendations of the Preliminary Geotechnical Investigation Report and this Updated
Geotechnical Report.
Geotechnical conditions, boring/test pit locations and other pertinent data are plotted on the
enclosed Geotechnical Map which is based on the current grading plan. Revised Cross Sections
A-A' and B-B', based on the current grading plan, depicting general subsurface conditions and
slot cuts are included in this report. Our previous ABC Slot Cuts Excavation Detail, Figure 7,
remains applicable and is included in this report.
Seismic design parameters and seismic loading for retaining wails have been updated, based on
ASCE 7-16.
The following list of geotechnical observations/testing is recommended during the grading and
construction phases.
Observation of temporary cut slopes and slot cuts
Observation of basement excavation
Observation of wall backdrainage
Density testing and observation during placement of wall backfill
Laboratory testing for Maximum Dry Density and Optimum Moisture Content for each soil
type used as fill
Observation of footing excavations prior to placement of steel
Utility trench observation and testing
P.O. BOX 230163 • ENCINITAS, CALIFORNIA 92023
(858) 755-8622
Coast Geotechnical August 3, 2020
W.O. P-707419
Page 8 of 8
6) The site location map is included on Page 6 of the Preliminary Geotechnical Investigation Report
and is designated as Figure 1.
LIMITATIONS
All of the recommendations in the Preliminary Geotechnical Investigation Report which are not
superceded by this report remain applicable and should be implemented during the design and
construction phases.
If you have any questions, please do not hesitate to contact us at (858) 755-8622. This opportunity
to be of service is appreciated.
Respectfully submitted,
COAST GEOTECHNICAL
h M. 4W
Kevin McFarland
Project Geologist
,jIS441' 2
Mark Burwell, C.E.G. c Li.i
Engineering Geologist
,XC 31ST
FIGURES
VithaA Singhanet, P.E.
Geotechnical Engineer
Figure 2: Geotechnical Map
Figure 3: Geological Cross Section A-A'
Figure 4: Geological Cross Section B-B'
Figure 7: ABC Slot Cuts Excavation Detail
P.O. BOX 230163 • ENC1NITAS, CALIFORNIA 92023
(858) 755-8622
FIGURES
7/0
Li
' ( 0 I
\\
'B
.5 '
0
4 °0 4
0
44 6
o Qs over - 4
4 4 Qvop 4
4
0
4 4
C
Project Number: 107419
Figure Number: 2
GEOTECHNICAL MAP
2726 MORNING GLORY LANE, CARLSBAD, CA
SCALE: I= 10' I 0' 10' N
00
0
.5
.5
Legend
Geologic Cross Sections
121.47
Proposed Addition
Boring Location
Approximated no.2, .,
-1% • Icat Pit Location '
Approximated I is
-- Qs over Topsoil over Very "- SC
r
Qvop Old Patalic Dcpuaits '\ , 155500 WALLS
iTp 20
: ETGSWAEWAY
L ftII
..io.3i4IP. No ?A*
--
COAST GOTECHN1CAL
5931 Sxa UmMore. Scile 109
Ca,Ob.d. CA 9.2010
£55500 NoM
CROSS - SECTION A-A'
2726 MORNING GLORY LANE, CARLSBAD, CA
SCALE: V'= 10' 0' 10' 20'
170
I I Proposed Addition II Boring Location Ii Approximated
Existing Residence Laf Qs Fill /Topsoil J
Existing Grade _________
Very Old
Test Pit Location Paralic Deposits
Approximated
I 165 - ------.
160— Existing Garage : : Proposed Addition
I Existing 2.5
155 - Existing Driveway I I Retaining Wall
af/ Qs (Fill / Topsoil)
150-----------
-IL- 1'2 Proposed
\4asement I -
-
140 Qvop (Very Old Paralic Deposits)
B-i 135 T.D. 13 ft
130
@ COAST GEOTECHNICAL
5931 Sea Lion Place, Suite 109
Carlsbad. CA 92010
Project Number: 707419
Figure Number: 3
CROSS - SECTION B-B'
2726 MORNING GLORY LANE, CARLSBAD, CA
SCALE: 1,1= 10'
0' 10' 20'
B B6
Legend
Proposed Addition
Existing Residence
.1
Existing Grade
Test Pit Location
Approximated
Boring Location U Approximated
af/Qs j Fill /Topsoil
Qvop Very Old
Paralic Deposits
PL
Existing Covered Patio : Proposed Addition Exi sting 2.5'
Existing Lawn Rel aining Wall
I--1t .. Proposed all Qs (Fill / Topsoil) si\ld Basement .
Cuts
140 H Qvop (Very Old Paalic Deposits) LI
I B-i
135 4 T.D.13ft
170
165
160
155
150
145
COAST GEOTECHNICAL
5931 Sea Lion Place, Suite 109
Carlsbad, CA 92010
Project Number: 707419
Figure Number: 4
PLAN VIEW
Existing Covered Patio
Column Pad IN
CROSS SECTION
Existing Covered Patio
Existing Column Pad 1 \ Temporary 1:1 Slope
Slot Cut B\
- ---I:1
NO SCALE
Excavate Slot Cuts A and C, 5 feet wide not to exceed 6 feet. Consthict wall in Slot Cuts A and C prior to
Excavating Slot Cut B.
ABC SLOT CUTS EXCAVATION DETAIL
COAST GEOTECBNJCAL
Project Number: 707419 5931 Sea Lion Place, Suite 109 Carlsbad, Figure Number: 7 CA