MEMORANDUM 629-029
TO: Jesse Kleist, KB Home Coastal
FROM: Steven Henderso4txter Wilson Engineering, Inc.
DATE: November 12, 2021
SUBJECT: Marja Acres Residential Master Water Meters and Private
Domestic Water System Sizing
Background
The Marja Acres project is located in the north-central portion of the City of Carlsbad. It is
situated along El Camino Real to the southeast of Kelly Drive. The majority of the proposed
24 acre development will consist of 248 townhome residential units spread amongst several
clusters where a master water meter is proposed for each cluster. The 17 different clusters
vary from containing six units up to 34 units.
The current site plan for the Marja Acres project is attached to the back of the memorandum.
2234 FARADAY AVENUE 0 CARLSBAD, CA 92008 • (760) 438-4422 • FAX (760) 438-0173
Jesse Kleist
November 12, 2021
Page 2
Master Water Meter Sizing bvTownhome C.lusteE
To size the master water meters an estimate of Water Fixture Units (WFUs) was done for
each townhome residential cluster. This was achieved by calculating the typical number of
WFUs for the townhome residential units. Using Chart A- 103.1(1) in the 2019 California
Plumbing Code, a flow rate in gpm can be calculated from the WFUs. Using the City of
Carlsbad's meter capacity ranges, a meter size and type can be determined from the flow
rates in gpm. The WFU tabulation, Chart A-103.1(1) in the 2019 California Plumbing Code,
and the City of Carlsbad meter flow rate range are all attached to this memorandum. The
breakdown for each townhome cluster is summarized in Table 1 below.
TABLE 1
WFU, MAXIMUM FLOW, AND WATER METER SIZE BY TOWNHOME CLUSTER
Townhome
Cluster
Quantity
of Units
Estimated
WFUs'
Maximum
Flow2, gpm
Water Meter
Size8
Cluster
Supply Size
1 29 971.5 228
2" (Turbo) 6-Inch 2 32 1,072 242
21 703.5 189 1.5" (Turbo) 4-Inch
4 34 1,139 250 2" (Turbo) 6-Inch
5 22 737 197
1.5" (Turbo) 6 13 435.5 145
7 19 636.5 179
6 201 97 1.5" (PD)
9
8 268 112 1.5" (PD)
4-Inch
10
11
12
13
14
15
16
17
Total 248 8,808
1 Attached WFU Breakdown - -
2 From Chart A-103.1(1) in the 2019 California Plumbing Code (attached) plus a 26-gpm fire sprinkler allowance
Per City meter flow rate range (attached e-mail)
Jesse Kleist
November 12, 2021
Page 3
The master water meters have been sized according to City of Carlsbad standards. The City
primarily follows the AWWA standards for Cold Water Meters. As mentioned earlier, an e-
mail correspondence stating this requirement from the City of Carlsbad is attached to this
memorandum.
The size for the master meters for the Marja Acres townhome clusters shall be either 1.5-
inch positive displacement, 1.5-inch turbo, or 2-inch turbo depending on demand and unit
quantities. Typical available pressures at the public water meter connections are expected
to range between 60 psi and 70 psi.
These 1.5-inch or 2-inch meter sizes are required based on a single meter supplying a
respective townhome cluster. If a townhome cluster's private water system consists of a
"looped" system with two meter connections then two smaller size meters could be utilized in
lieu of the single larger meter. This two meter setup for a townhome cluster is not analyzed
within this memorandum.
Private Domestic Water System giziri
Using the WFUs and flow rates for each townhome cluster as shown in Table 1, a worst case
scenario was analyzed for the 2-inch meter and 1.5-inch meter clusters in regard to domestic
demand onsite. The highest calculated domestic water demand for a 2-inch meter and 1.5-
inch meter cluster respectively were inputted at the furthest distance from the public
connection. This was done along the townhome cluster's main water distribution line and, to
be conservative in the analysis, the entire flow was calculated across the entire piping length.
Hydraulic calculations are attached to this memorandum confirming that a 6-inch diameter
main cluster distribution water line can provide adequate service to the 2-inch meter clusters
and 4-inch diameter main cluster distribution water line can provide adequate service to the
1.5-inch meter clusters. Residual pressure under maximum domestic demands is greater
than 45 psi at the furthest unit's connection.
Jesse Kleist
November 12, 2021
Page 4
It is recommended to oversize the individual unit's supply laterals due to the low expected
working pressures (45 to 50 psi) within the private water systems throughout the Marja
Acres site.
SH:
cc: Mel Landy, P.E., HWL Planning & Engineering
Attachment(s)
Marja Acres Site Plan and Proposed Townhome Cluster Layout
Marja Acres Water Fixture Unit Breakdown
California Plumbing Code Appendix A Excerpt
4 - City of Carlsbad Water Meter Capacity Ranges
5 - Hydraulic Calculations for Marja Acres Private Water Systems
I
1/
II .
it
/7,
/ IlL CLUSTER I
WFU Calculations Townhome
Maria Acres
Typical Townhome Unit
Job Number 736-013
Date 11/12/2021
Water Fixture Units:
DESCRIPTION
CLOTHES WASHER
TUB/SHOWER
SHOWER
KITCHEN SINK
BAR SINK
DISHWASHER
LAUNDRY SINK
MOP BASIN
LAVATORY
WATER CLOSET (1.6 GPF, private)
DRINKING FOUNTAIN
HOSE BIBB
EACH ADDTL HB
TOTAL
Typ. Townhome Unit
FIXTURE TOTAL
QUANTITY UNITS FIXTURE
EACH UNITS
1 4 4
2 4 8
1 2 2
1 1.5 1.5
0 1 0
1 1.5 1.5
0 1.5 0
0 3 0
5 1 5
3 2.5 7.5
1 0.5 0.5
1 2.5 2.5
1 1
33.5
Cluster Quantity WFU Total
1 29 33.5 971.5
2 32 33.5 1072
3 21 33.5 703.5
4 34 33.5 1139
5 22 33.5 737
6 13 33.5 435.5
7 19 33.5 636.5
8 6 33.5 201
9 8 33.5 268
10 8 33.5 268
11 8 33.5 268
12 8 33.5 268
13 8 33.5 268
14 8 33.5 268
15 8 33.5 268
16 8 33.5 268
17 8 33.5 268
248 8308
Page 1
1)
APPENDIX A
TABLE A 103.1
WATER SUPPLY FIXTURE UNITS (WSFU) AND MINIMUM FIXTURE BRANCH PIPE SIZES3
APPLIANCES, APPURTENANCES, OR FIXTURES2
MINIMUM
FIXTURE
BRANCH PIPE
SIZE'4
(Inches)
PRIVATE PUBLIC ASSEMBLY5
Bathtub or Combination Bath/Shower (fill) Y2 4.0 4.0 -
3/4 inch Bathtub Fill Valve 3/4 10.0 10.0 -
Bidet 1/2 1.0 - -
Clothes Washer 1/2 4.0 4.0 -
Dental Unit, cuspidor /2 - 1.0
Dishwasher, domestic 1/2 1.5 1.5 -
Drinking Fountain or Water Cooler '/2 0.5 0.5 0.75
Hose Bibb. 1/2 25 25 -
Hose Bibb, each additional7 1/2 1.0 1.0 -
Lavatory 1/2 1.0 1.0 1.0
Lawn Sprinkler, each head' - 1.0 1.0 -
Mobile Home, each (minimum) - 12.0 - -
Sinks - - - - -
Bar '/2 1.0 2.0 -
Clinical Faucet '/2 - 3.0 -
Clinical Flushometer Valve wib or without faucet 1 - 8.0 -
Kitchen, domestic - '/2 1.5 1.5 -
Laundry /2 1.5 1.5 -
Service or Mop Basin '/z 15 3.0 -
Washup, each set of faucets /2 - 2.0 -
Shower per head '/2 2.0 20 -
Urinal, 1.0 GPF Flushorneter Valve 3/4 3.0 4.0 5.0
Urinal, greater than 1.0 GPF Flushometer Valve 4.0 5.0 6.0
Urinal, flush tank /2 2.0 2.0 3.0
Wash Fountain, circular spray - 4.0
Water Closet 1.6 GPF Gravity Tank Vs 2.5 2.5 3.5
Water Closet,, 1.6 GPF Flushometer Tank 1/2 2.5 2.5 3.5
Water Closet, 1.6 GPF Flushometer Valve 1 5.0 5.0 8.0
Water Closet, greater than 1.6 GPF Gravity Tank 1/2 3.0 5.5 7.0
Water Closet, greater than 1.6 GPF Flushometer Valve 1 7.0 8.0 10.0
For SI units: 1 inch = 25 mm
Notes:
Size of the cold branch pipe, or both the hot and cold branch pipes.
2 Appliances, appurtenances, or fixtures rot included in this table shall be permitted to be sized by reference to fixtures having a similar flow rate and frequency
of use.
The listed fixture unit values represent their total load on the cold water building supply. The separate cold water and hot water fixture unit value for fixtures
having both cold and hot water connections shall be permitted to be three-quarters of the listed total value of the fixture.
The listed minimum supply branch pipe sizes for individual fixtures are the nominal (ID.) pipe size.
For fixtures or supply connections likely to impose continuous flow demands, determine the required flow in gallons per minute (gpm) (Us) and add it sep-
arately to the demand in gpm (L/s) for the distribution system or portions thereof. 6 Assembly [Public Use (see Table 422.1)].
Reduced fixture unit loading for additional hose bibbs is to be used where sizing total building demand and for pipe sizing where more than one hose bibb
is supplied by a segment of water distribution pipe. The fixture branch to each hose bibb shall be sized by 2.5 fixture units,
2019 CALIFORNIA PLUMBING COLE 359
APPENDIX A
CHART A 103.1 (1)
ESTIMATE CURVES FOR DEMAND LOAD
500
400
E
200
z 4
No. 1 for system predominantly for Ilushometer valves
No. 2 for system predominantly for flush tanks
iaT. IiI•ls I1iI• sJ.Is 2!sII c!,Ii
FIXTURE UNITS
For SI units: 1 gallon per minute = 0.06 Us
CHART A 103.1(2)
ENLARGED SCALE DEMAND LOAD
100
80
. 60
cc
: 40 (a a)
20
z 4
I., 6 0 20 40 60 80 100 120 140 160 180 200 220 24(
FIXTURE UNITS
For SI units: 1 gallon per minute = 0.06 Us
360 2019 CALIFORNIA PLUMBING CODE
100
-II )0
VaiRay Nelson
From: Mario Remillard
Sent: Wednesday, July 13, 2016 8:49 AM
To: VaiRay Nelson
Subject: Meter GPMs
Hi ValRay,
Below are the GPM's for the various meter sizes.
5/8 = 0.5 —20 gpm
3/4= .75-35gpm
1" = 1-55gpm
11/2 PD=2.5—l2ogpm
11/2 Turbo = 4 — 200 gpm
2PD = 2.5 — 170 gpm
2 Turbo = 4-310 gpm
Mario Remillard
Meter & Customer Services Supervisor/Conservation Coordinator
Carlsbad Municipal Water District
5950 El Camino Real
Carlsbad, Ca 92008
760-438-2722 Ext. 7153
(Carlsbad
Municipal Water District
1
Project: Marja Acres r v. Water for Townhome Clusters
Job: 629-029
Date: 11/11/2021
CLUSTER 4 POINT OF CONNECTION TO FURTHEST UNIT
FRICTION LOSSES IN PIPING -11(f)
Hazen-Williams Formula (~~
) 1.852
I-If
- D 48655
H(f) = friction losses in ft
Q = 250.0 gpm
C = 120 for design
L= 500.00 ft
D = 6 i
Therefore, 11(0 = 3.33 ft
MINOR LOSSES IN LATERAL PIPING- Hm
H 7 =K-
2g
H) = minor losses, ft
sum of minor loss coefficients
g = gravitational constant
= 32.17 fps'
Diameter = 6 in v, fps = 2.8
Minor loss coefficients
Description Quantity K-value K-value, total
90 degree bend 6 0.3 1.8
45 degree bend 0 0.2 0.0
Tee-thru, flanged 0 0.3 0.0
Isolation Valve 2 1.0 2.0
Tee-branch, flanged 0 0.8 0.0
Wye 0 0.5 0.0
Check valve 1 2.5 2.5
Meter 1 1.5 1.5
Entrance/Exit Loss 2 1.0 2.0
JK = 9.8
11m 1.23 ft
RESIDUAL PRESSURE AT CLUSTER 4 FURTHEST UNIT
Total Fricion Losses 4.6 ft Summation of all headlosses
Flow Meter and Backflow Preventer Loss = 15.0 psi
34.6 ft
Total Loss = 39.2 ft
17.0 psi
Available pressure at P.O.C. = 65 psi per water study, max day demand
Residual Pressure at Further Unit = 48 psi
\\ARTIC\Docs\629-029\2021-11-11 Hydraulic Calculations Marja Acres Pvt Water.xlsx Pg. 1
Project: Marja Acre. v t. Water for Townhome Clusters
Job: 629-029
Date: 11/11/2021
CLUSTER 5 POINT OF CONNECTION TO FURTHEST UNIT
FRICTION LOSSES IN PIPING - H(f)
f \1.852
Hazen-Williams Formula l0.44* *L
H1
- D48655
H(f) = friction losses in ft
Q = 197.0 gpm
C = 120 for design
L= 400.00 ft
D= 4 i
Therefore, 11(0 = 12.31 ft
MINOR LOSSES IN LATERAL PIPING- Hm
H =JK
v2
,,,
2g
H) = minor losses, ft
sum of minor loss coefficients
g = gravitational constant
= 32.17
Diameter = 4 in
Minor loss coefficients
Description Quantity K-value
90 degree bend 2 0.3
45 degree bend 0 0.2
Tee-thru, flanged 0 0.3
Isolation Valve 2 1.0
Tee-branch, flanged 0 0.8
Wye 0 0.5
Check valve 1 2.5
Meter 1 1.5
Entrance/Exit Loss 2 1.0
JK
Hm
RESIDUAL PRESSURE AT CLUSTER 5 FURTHEST UNIT
Total Fricion Losses = 15.7 ft Summation of all headlosses
Flow Meter and Backflow Preventer Loss = 15.0 psi
34.6 ft
Total Loss = 50.3 ft
21.8 psi
Available pressure at P.O.C. = 67 psi per water study, max day demand
Residual Pressure at Further Unit = 45 psi
\\ARTIC\Docs\629-029\202 1-11-11 Hydraulic Calculations Marja Acres Pvt Water.xlsx
V, fps = 5.0
K-value, total
0.6
0.0
0.0
2.0
0.0
0.0
2.5
1.5
2.0
8.6
3.38 ft
Pg. 2