HomeMy WebLinkAboutCDP 2017-0074; STAINBACK RESIDENCE; PRELIMINARY GEOTECHNICAL INVESTIGATION; 2017-09-284w4~-11 Geotechnical Exploration, Inc.
SOIL AND FOUNDATION ENGINEERING • GROUNDWATER • ENGINEERING GEOLOGY
28 September 2017
Darcy Eaton
5360 Los Robles Drive
Carlsbad, CA 92008
Subject: Preliminary Geotechnical Investigation
Eaton-Stainback Residence
5360 Los Robles Drive
Carlsbad, California
Dear Ms. Eaton :
Job No. 17-11606
In accordance with your request, a representative of Geotechnical Exploration,
Inc. has visited the subject site and performed an evaluation of the soil conditions
in the area of the proposed new residence. It is our understanding that the existing
structure will be removed and the site is being developed to receive a new single-
story, single-family residence and associated improvements which will utilize
continuous footings and slab on grade. As part of our investigation, we observed
and evaluated the shallow soil conditions at two locations within the proposed new
building area.
In addition, we reviewed the building plans by Claire Costello, in accordance with
the requirements of the City of Carlsb~~ Development Services. It is our opinion
that the plans were prepared in accordance with the recommendations included in
this report.
-~c ~ .. v __
MAK O 4 2C19
LAND OF.VELOPMENT
f.:NGINEERING
7420 TRADE STREET• SAN DIEGO, CA. 92121 • (858) 549-7222 • FAX: (858) 549-1604 • EMAIL: geotech@gei-sd.com
Eaton-Stainback Residence
Carlsbad, California
Job No. 17-11606
Page 2
The field work, conducted on September 1, 2017, consisted of logging three hand-
excavated test pits in the location of the proposed new residence. The excavations
revealed that the building site is underlain by approximately 1 to 7 feet of loose to
medium dense, silty sand fill soil over medium dense to dense, silty sand
formational materials. The on-site soils are considered to have a very low
expansion potential with an Expansion Index of less than 20. Currently, the
building pad slopes gently toward the street. The rear yard has a descending slope
to the east.
Based upon our observation, probing of the on-site soils, it is our opinion that the
new foundations for the residence can be founded in properly compacted fill or the
existing formational materials. The loose to medium dense fill soils in the proposed
building pad area should be removed and properly compacted as part of site
preparation for the new foundation and slab areas. All fill should be compacted to
at least 90 percent of Maximum Dry Density. The Maximum Dry Density of the soil
has been determined per ASTM D1557-12.
1. It is our opinion that properly compacted fill or the medium dense to dense
formational materials will provide adequate bearing strength for the proposed
new foundations. New footings placed in properly compacted fill or the
existing medium dense to dense formational soils can be designed for an
allowable soil bearing capacity of 2,500 pounds per square foot (psf). We do
recommend that the proposed footings and slabs contain at least a nominal
amount of reinforcing steel to reduce the separation of cracks should they
occur. The allowable soil bearing capacity may be increased one-third for
structural design including seismic or wind loads. Footings built close to
slopes shall be provided with a setback of at least 7 feet to the slope face.
Eaton-Stainback Residence
Ca rlsbad, California
Job No. 17-11606
Page 3
2. The proposed footings should have a minimum depth of 18 inches and a
width of at least 12 inches, founded in properly compacted fill or the medium
dense to dense formational material. A minimum of steel for continuous
footings should include at least two No. 4 bars continuous, with two bars 3
inches from the bottom of the footing.
3. Site-specific seismic design criteria to calculate the base shear needed for the
design of the residential addition are presented in the following table. The
design criteria was obtained from the California Building Code (CBC) 2016
edition, and is based on the distance to the closest active fault and soil
profile classification.
4. The proposed structure should be designed in accordance with Section 1613
of the 2016 CBC, which incorporates by reference the ASCE 7-10 for seismic
design and the following parameters should be utilized. We have determined
the mapped spectral acceleration values for the site based on a latitude of
33.1298 degrees and longitude of 117.3321 degrees, utilizing a program
titled "Design Maps and Tools," provided by the USGS, which provides a
solution for ASCE 7-10 (Section 1613 of the 2016 CBC) utilizing digitized files
for the Spectral Acceleration maps.
In addition, we have assigned a Site Classification of D. The response
parameters for design are presented in the following table. The design
spectrum acceleration vs. Period T is attached.
Eaton-Stainback Residence
Carlsbad, California
TABLE I
Job No. 17-11606
Page 4
Mapped Spectral Acceleration Values and Design Parameters
1.171 1.032 1.550 1.208 0.805
5. The liquefaction of saturated sands during earthquakes can be a major cause
of damage to buildings. Liquefaction is the process by which soils are
transformed into a viscous fluid that will flow as a liquid when unconfined. It
occurs primarily in loose, saturated sands and silts when they are sufficiently
shaken by an earthquake.
On this site, the risk of liquefaction of foundation materials due to seismic
shaking is considered to be remote due to the relatively shallow, medium
dense to dense nature of the natural-ground material and the lack of a
shallow static groundwater surface under the site. No soil liquefaction or soil
strength loss is anticipated to occur due to a seismic event.
6. Any new concrete slabs on-grade (on properly compacted fill or dense
formational soils) should be a minimum of 4 inches actual thickness and be
reinforced with at least No. 3 steel bars on 18-inch centers, in both
directions, placed at mid-height in the slab. The interior slab should be
underlain by a 15-mil vapor barrier (15-mil StegoWrap) placed directly on
properly compacted subgrade. The sand or gravel base may be waived.
We recommend that isolation joints and sawcuts be incorporated to at least
one-fourth the thickness of the slab in any slab designs. The joints and cuts,
if properly placed, should reduce the potential for and help control floor slab
cracking. In no case, however, should control joints be spaced farther than
20 feet apart, or the width of the slab. Control joints should be placed within
Eaton-Stainback Residence
Carlsbad, California
Job No. 17-11606
Page 5
12 hours after concrete placement as soon as concrete sets and no raveling
of aggregate occurs. Slabs spanning any existing loose soils and supported
by perimeter deepened foundations should be designed by the structural
engineer as structural slabs.
7. If any retaining walls are planned, the active earth pressure (to be utilized in
the design of cantilever, non-restrained walls) should be based on an
Equivalent Fluid Weight of 38 pounds per cubic foot (for level backfill only) if
on-site soils are used. Additional loads applied within the potential failure
block should be added to the active soil earth pressure by multiplying the
vertical surcharge load by a 0.31 lateral earth pressure coefficient.
For restrained wall conditions, we recommend an equivalent fluid weight of
56 pcf. Surcharge loads or restrained walls may be converted to lateral
pressures by multiplying by a factor of 0.47. Should seismic soil increment
be required, the unrestrained walls with level backfill should be designed for
an additional pressure of 14 pcf, in addition to the regular static loading, with
zero pressure at the top and the maximum pressure at the bottom of the
wall.
8. The passive earth pressure of the encountered formational soils to be used
for design of shallow foundations and footings to resist the lateral forces,
should be based on an Equivalent Fluid Weight of 275 pcf. This passive earth
pressure is valid for design only if the ground adjacent to the foundation
structure is essentially level for a distance of at least three times the total
depth of the foundation and is properly compacted or dense natural soil. An
allowable Coefficient of Friction of 0.40 times the dead load may be used
between the bearing soils and concrete foundations, walls or floor slabs.
Eaton-Stainback Residence
Carlsbad, California
Job No. 17-11606
Page 6
9. Adequate measures should be taken to properly finish-grade the site after
the new structure and other improvements are in place. Drainage waters
from this site and adjacent properties should be directed away from
perimeter foundations, floor slabs, footings and slope tops, and onto the
natural drainage direction for this area or into properly designed and
approved drainage facilities. Proper subsurface and surface drainage will
help minimize the potential for waters to seek the level of the bearing soils
under the foundations, footings, and floor slabs. Failure to observe this
recommendation could result in undermining, differential settlement of the
building foundation or other improvements on the site, or moisture-related
problems.
It is not within the scope of our services to provide quality control oversight
for surface or subsurface drainage construction or retaining wall sealing and
base of wall drain construction. It is the responsibility of the contractor
and/or their retained construction inspection service provider to provide
proper surface and subsurface drainage. Finish grading shall provide positive
drainage away from the residence and improvements and be directed toward
storm drain inlets or other approved drainage facilities.
10. Due to the possible build-up of groundwater (derived primarily from rainfall
and irrigation), excess moisture is a common problem in below-grade
structures or behind retaining walls that may be planned. These problems
are generally in the form of water seepage through walls, mineral staining,
mildew growth and high humidity. In order to minimize the potential for
moisture-related problems to develop, proper cross ventilation and water-
proofing must be provided for below-ground areas, in crawl spaces, and the
Eaton-Stainback Residence
Carlsbad, California
Job No. 17-11606
Page 7
backfill side of all structure retaining walls must be adequately waterproofed
and drained.
Proper subdrains and free-draining backwall material (such as gravel or
geocomposite drains such as Miradrain 6000 or equivalent) should be
installed behind all retaining walls on the subject project in addition to wall
waterproofing. Geotechnical Exploration, Inc. will assume no liability for
damage to structures that is attributable to poor drainage.
11. Planter areas and planter boxes should be sloped to drain away from the
foundations, footings, and floor slabs. Planter boxes should be constructed
with a closed bottom and a subsurface drain, installed in gravel, with the
direction of subsurface and surface flow away from the foundations, footings,
and floor slabs, to an adequate drainage facility. The finish grade around the
structure should drain away from the perimeter walls to help reduce or
prevent water accumulation.
Exterior slabs or rigid improvements should also be built on properly
compacted soils and be provided with concrete shrinkage reinforcement and
adequately spaced joints.
Geotechnical Exploration, Inc. recommends that we be asked to verify the
actual soil conditions revealed in footing excavations prior to form and steel
reinforcement placement. In addition, any new fills or loose soils should be
properly compacted under the observations and testing of our firm.
Eaton-Stainback Residence
Carlsbad, California
Job No. 17-11606
Page 8
Should you have any questions regarding this matter, please contact our office.
Reference to our Job No. 17-11606 will help to expedite a response to your
inquiries.
Respectfully submitted,
ECHNICAL EXPLORATION, INC .
. Heiser
Senior Project Geologist
Jaime A. Cerros, P.E.
R.C.E. 34422/G.E. 2007
Senior Geotechnical Engineer
.. _...,._
VICINITY MAP
"-
'
·•~-~ .....
•. ~~ •. l'ff8l/1JII
.\ #-
~-. 'ti!,._ ...
Thomas Bros Guide San Diego County pg 1126-G2
Eaton/Stainback Residence
5360 Los Robles Drive
Carlsbad, CA.
Figure No. I
Job No. 17-11606
17-1160&-p.ai
Retaining
Wall
Wood
Fenc e
• • ♦ • • • • .. • • • • • • • • • ...................... . ... . . .. . . . .. . . ... -. . . .
• • • • • • • • .. • • • • ♦ • • •
. ~~J\B ~TB1',~K'....._ • ....._: . ..:..., ·_._· .•.•.• . . . . . . . . . . . . . -,. . . . • • • • • • • Hl'.li -> • ~ • . . .. . . . r-.,;,. . ..
.,... ___ l+\J)::
_i;f~I~~-~:r
0
I
_ _J
0
Los Robles Drive
REFERENCE: This PLOT PLAN was prepared from an
existing PROPOSED NEW PLAN provided by the client
PROPOSED NEW PLAN
AOORESS -
5360 LOS ROBLES DRIVE,
CARLSBAD CA 92008
Scale: l" = 20'
(approximate)
ASSESSORS PARCEL# •
210-112-04
LEGEND
~
HP..1
Approximate Location
of Exploratory Handpit
NOTE: Thill Plot Plan i8 not lo be used for legal
purp0886. Locations and dimensions -approximale.
Actual property dimanaions and locdor18 of ulillties
may be oblained from the App«Mld Bullding Plans
or the "As-Bult" Grading Plans.
PLOT PLAN
Eaton/Stainbs.ck Residence
5360 Los Robles Drive
Carlsbad, CA.
Figure No. II
Job No. 17-11606
and from on-site field reconnaissance performed by GEi.
G1;1 Geotechnlcal .--, Explo~atio!', Inc.
~ ~ October 2017
,-..
~ ii
5 (!)
Ir 1:i
,-EQUIPMENT DIMENSION & TYPE OF EXCAVATION
Hand Tools 2' X 2' X 3' Handpit
SURFACE ELEVATION GROUNDWATER/ SEEPAGE DEPTH
± 63' Mean Sea Level Not Encountered
-
-
-
2-
-
-
-
3-
-
-
4 -
---
-
5 --
--
---
FIELD DESCRIPTION
AND
CLASSIFICATION
OESCRJPTIOO AND REMARKS
(Grain size, Density, Mlistlxe, Color)
~•LI Y SAND , fine-to medium-grained, with
some asphalt fragments and roots. Medium
dense. Dry to damp. Red-brown.
FILL (Qaf)
SIL TY SAND , fine-to medium-grained, well
cemented. Dense. Damp. Red-brown.
OLD PARAUC DEPOSITS (Qop ,)
Bottom @3'
(I) u (I) ;:;
SM
SM
DATE LOGGED -...,
9-1-17
LOGGED BY
JKH
l ~E l ~I l
ci ~ ci w ::::!dl1! + d d Wet: ~i;; ~ i;; 1;;ci wen :St; j~ ~ en I-zrW :s (I) ;;ii en en:::::E 3:z -en zo :::::i;Q ~; ~z &~ i~ w~ ~~ oa ~~ _!!:! C-WO a!o
@'---..L---......... __________________ .....__..___..__ _ __._ _ __,_ __ ..____,_ __ ...___..____,
(!)
2 (!) z
§
~
g
z 0 I w \..
_y_
~
IT]
■
0
~
PERCHED WATER TABLE
BULK BAG SAMPLE
IN-PLACE SAMPLE
MODIFIED CALIFORNIA SAMPLE
NUCLEAR FIELD DENSITY TEST
STANDARD PENETRATION TEST
JOB NAME
Eaton Residence
SITE LOCATION
5360 Los Robles Drive, Carlsbad, CA
JOB NUMBER REVIEWED BY LDR/JAC LOGNo.
17-11606 fw4.~-· HP-1 FIGURE NUMBER Exploradon, Inc.
Illa $-~
.... ai
"EQUIPMENT DIMENSION & TYPE OF EXCAVATION
Hand Tools 2' X 2' X 3' Handpit
SURFACE ELEVATION GROUNDWATER/ SEEPAGE DEPTH
± 63' Mean Sea Level Not Encountered
<P" ! ?5 w :x: _,
Ii: CD ! UJ ~ 0
1
2
3
4
5
6
7
8
FIELD DESCRIPTION
AND
CLASSIFICATION
DESCRIPTION AND REMARKS
{Grain size, Density, M:>lsture, Color)
LTYSANO, ne-to medium-graine , with
roots. Loose to medium dense. Damp.
Red-brown.
FIU (Qaf)
--18% passing #200 sieve.
SILTY SAND, fine-to medium-grained, with
some roots. Loose to medium dense. Damp. Dark
brown.
FILL (Qaf)
SIL TY SANO , fine-to medium-grained, well
cemented. Dense. Damp. Red-brown.
OLD PARAUC DEPOSITS (Qop ,)
c.ri
c.:i c.ri ::i
SM
SM
SM
ai 9
t:i
e> Bottom @ 8' ~
DATE LOGGED ~
9-1 -17
LOGGED BY
JKH
~ l ~I l ~'R: ci ~ ci UJ :::E ~ ;:;;-+ ' 0-UJ 0::
UJ~ =>~ ~q -d w (I) :s~ :5 j ~ ;: !z a:UJ :::E --:::E z (I) -en -(I) ~o < ~ :::e rs ~; ~z §; i ~ ~~ ~<.)
oa c}j ~ -~ al<.)
12.6 116.0
4.5 101 .1 87
53.....__....._ ___ ........, __________________ __.__.......__...._ _ __.__ ........ __ ....____., __ .....__.......____,
C)
~ C) z §
~ ~
y JOB NAME PERCHED WATER TABLE Eaton Rnidence
i;gi BULK BAG SAMPLE SITE LOCATION
[D IN-PLACE SAMPLE 5360 Los Robles Drive, Carlsbad, CA
■ MODIFIED CALIFORNIA SAMPLE JOB NUMBER REVIEWED BY LDR/JAC LOGNo.
0 NUCLEAR FIELD DENSITY TEST 17-11606 ~~ Cieotechnlcal HP-2 FIGURE NUMBER l!xploratton, Inc. ~ STANDARD PENETRATION TEST lllb ~ '-~
/ EQUIPMENT DIMENSION & TYPE OF EXCAVATION
Hand Tools 2' X 2' X 3' Handpit
SURFACE ELEVATION GROUNDWATER/ SEEPAGE DEPTH
± 60' Mean Sea Level Not Encountered
--
-
3 -
-
-
-
4-
-
-
5-
--
-
-
FIELD DESCRIPTION
AND
CLASSIFICATION g ~ DESCRIPTION AND REMARKS ~ ! (Grain size, Density, Moisture, Color)
SIL TY SAND . fine-to medium-grained, with
some roots and rock fragments. Loose to medium
dense. Dry to damp. Gray-brown.
FILL (Qaf)
u:i (.)
(I)
=i
SM
SIL TY SAND , fine-to medium-grained, well SM
cemented. Dense. Damp. Red-brown.
OLD PARALIC DEPOSITS (Qop 6)
Bottom@ 3'
DATE LOGGED ....
9-1-17
LOGGED BY
JKH
~ ~E ~ &<ff l
ci ~ c:i w :::E ~ 0 Q. ' ci wa: ~~ ::.~ ~q + -~ wen ~~ j~ j~ I-...JW :SU) Cf)::. z en 3:z 0.. ::i: -en -en ~~ ~o t~ ~~ i~ zli oa :::EL>
-:::E ~~ WO mo i}j$
@L-.-..1.........1......&..-------------------'--..l....-"---------...1....-.....1.-...1....-.....1.-.....&..--I
(!)
~ 0 ~
I
§
2 0 I '"
y
~
[TI
■
0
~
PERCHED WATER TABLE
BULK BAG SAMPLE
IN-PLACE SAMPLE
MODIFIED CALIFORNIA SAMPLE
NUCLEAR FIELD DENSITY TEST
STANDARD PENETRATION TEST
JOB NAME
Eaton Residence
SITE LOCATION
5360 Los Robles Drive, Cartsbad, CA
JOB NUMBER REVIEWED BY LDR/JAC LOG No.
17-11606 w=~ HP-3 FIGURE NUIIBER
Ille -@:@;
-'
@
(!)
~
135
130
125
120
115
110
't3 0..
~ ci5 m 105
0 >-0:: 0
100
95
90
85
80
75
0
\
\
,
t
5
I\ '
\
\ 1
\
' \ \ '
\ \
\ ' \ \
\ \
\
\ \
\
\
' ;\ r,
:\ \
' I\ \
\ \ -~.,. r1II \ ..... \ \
,l" \ \
r I\
\ \
I
\ •
10 15
Source of Material HP-2@2.0'
Description of Material SIL TY SAND {SM}1 Red-brown
Test Method ASTM D1557 Method A
I\
\ TEST RESULTS \ 1
\ Maximum Dry Density 116.0 PCF
\ Optimum Water Content 12.6 % \ I\
I\
\ I\ I\
I\ \ A TTERBERG LIMITS \ I\ \
I\ \
I\ \ LL PL Pl
\ ' " ----
I\ \ '
' I\ I\
I\ \ II,, Curves of 100% Saturation ' l'\ ' \ I\. for Specific Gravity Equal to:
I\
I\ ' "' 2.80
II\ ' \ " I\, 2.70
II\ \ II,,
I\ II\ ' 2.60
\ I\. '\
l'I\ \.
I\. \
I'\ I'\ ' I\. 1 '-
\, I\. I'-
' I\..
I'\. ' ri...
l's, ' II,,
I'-. " ' ~ I", ~ ...
" I'> '-..
" "' 'I...
I',, " "'" I'-' I'\. ' I'\.
20 25 30 35 40 45 ~ w WATER CONTENT,%
!r----=,.--=t ----:-i•I_G_e_o_t-ec_h_n_l_ca-l--~~M.:..:...:.-=.:O..:..:..IS:....:.:T:__U_R_E ___ D_E_N_S_ITY_R_E_LA_T_I_ON_S_H_IP--1
~ 1111 Exploratlon, Inc. Figure Number: IV
;t Job Name: Eaton Residence 8 Site Location: 5360 Los Robles Drive, Carlsbad, CA
3.._ __ ;;,_ _______________ _,1.,:,Jo:,:b;,.:.;N,:;um=be:,:r~: ..:1~7--1:..:1:.;;:6;,:;:;0,:;:,6 __________ ....J
ElJSGS Design Maps Summary Report
User-Specified Input
Report Title 5360 Los Robles Drive, Carlsbad, CA
Thu September 21, 2017 16:52:29 UTC
Building Code Reference Document ASCE 7-10 Standard
(which utilizes USGS hazard data available in 2008)
Site Coordinates 33.1298°N, 117.3321°W
Site Soil Classification Site Class D -"Stiff Soil"
Risk Category I/II/III
~
C.rfsb ~'~-> ~ \.",
USGS-Provided Output
S5 = 1.171 g
S1 = 0.450 g
SMS = 1.208 g
SM1 = 0.698 g
" ~)o . .c, .. ..,
• ._ .1.1,J•OU,L t' -.,,. -X-1 lf'Q)n r,1
S0 5 = 0.805 g
S 01 = 0.465 g
For information on how the SS and S1 values above have been calculated from probabilistic (risk-targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application and
select the "2009 NEHRP" building code reference document.
I j(i
.\ .,
,u :: '
For PGAw TL, CRS, and CR, values, please view the detailed report.,.
Although this information is a product of the U.S. Geological Survey, we provide no warranty, expressed or implied, as to the
accuracy of the data contained therein. This tool is not a substitute for technical subject-matter knowledge.