HomeMy WebLinkAbout7100 AVIARA RESORT DR; ; FPC2018-0137PERMIT REPORT
(ity of
Carlsbad
Print Date: 09/07/2023
Job Address: 7100 AVIARA RESORT OR, CARLSBAD, CA 92011-4908
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2157500100 Track #:
Valuation: $85,717.93 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:
Permit No: FPC2018-0137
Status: Closed - Finaled
Applied: 05/07/2018
Issued: 05/24/2018
Finaled Close Out: 03/19/2021
Final Inspection:
INSPECTOR: Fieri, Dominic
Project Title:
Description: TRAVEL TRADERS AT PARK HYATT AVIARA -SPRINKLER TI (28 HEADS)
Applicant:
RED HAWK FIRE AND SECURITY CA LLC
ROBERT HASTINGS
920S ANDREASEN DR, # 102
ESCONDIDO, CA 92029-1936
(760) 233-9787
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $536.00
Total Fees: $536.00 Total Payments To Date: $536.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 I Inspections: 442-339-2660 1 www.carlsbadca.gov
frcd2OtS- Ov1-
FIRE SPRINKLER
TENANT IMPROVEMENT SUBMITTAL
For
TRAVEL TRADERS T.I.
7100 AVIARA RESORT DRIVE,
CARLSBAD, CA 92011
Submitted By:
Red Hawk Fire & Security
920 South Andreasen Drive, Suite 102,
Escondido, California 92029
(760) 233-9787
Bulletin 034 Rev. F April 2017
Reliable
Model G5 Series Sprinklers Standard Coverage, Concealed Pendent
Available with Solid, Perforated, or Gasket Cover Plate K2.8,4.2, 5.6, & 8.0 (40,60, 80, & 115 metric)
Product Features
Flat concealed cover plate available solid or perfo-
rated in a variety of finishes.
NEW: Stainless Steel Clad cover plate (see Table H).
3/4-inch (19 mm) cover plate adjustment.
Cover plate available with optional gasket
Product Description
Model G5 series sprinklers are standard coverage, flat plate
concealed sprinklers designed for installation in accord-
ance with NFPA 13. The sprinklers are offered with a stand-
ard Model G4/G5 cover plate (solid or perforated), a Model
G4/G5 cover plate with a Quick-response (QR) gasket, or a
Model G4/G5 cover plate with a Standard-response (SR)
gasket. Model G5 sprinklers must only be used with the
Model G4/G5 cover plate listed or approved with the sprin-
kler. All Model G5 series sprinklers use a fusible-link operat-
ing element. Table A provides a summary of available Model
G5 series sprinklers, along with Listing and Approval infor-
mation for each sprinkler and cover plate combination.
Model G5 Series Sprinkler Cover Plates
Model G4/G5 Cover
Model G4/G5 Cover Plate Plate
(Solid) (Perforated)
LL
Model G4165 QR Gasket
Cover Plate
I- t=1100-m-t.
Mode! G4/G5 SR
Gasket
Model G5 Series Snrinkler Summary
Sprinkler K-Factor Cover Plate Listings Max. Working Sprinkler
Model gpm/psi112 Model and Sensitivity Pressure Identification
(L/min/bar') Approvals psi (bar) Number (SIN)
cULus OR
2.8
G4/G5 FM SR G5-28 (40) 175(12) RA3411 G4/G5 OR Gasket cULus OR
G4/G5 SR Gasket cULus, FM SR
4.2
G4/G5 cULus QR G4/G5 OR Gasket
-
G5-42 (60) 175(12) RA3413
G4/G5 SR Gasket cULus SR
cULus OR 250 (17) G4/G5
______________ FM, LPCB, VdS, CE SR 175(12) G5-56 5.6
(80) RA3415 G4/G5 QR Gasket cULus OR 250 (17)
cULus SR 250 (17) G4/G5 SR Gasket FM SR 175(12)
G4/G5
G5-56 5.6 cULus 300(21) RA4014 G4/G5 OR Gasket
300 (80) SR G4/G5 SR Gasket cULus
G5-80 8.0 G4/G5 cULus OR G4/G5 OR Gasket (115) 175 (12) RA3412
G4/G5 SR Gasket cULus SR
www.reliablesprinkler.com
Technical Specifications Sprinkler Temperature Ratings
Style: Flat Concealed Pendent 165:F (74 C)
Threads: 1/2" NPT or ISO 7-1 R1/2 212 F(100 C)
Nominal K-Factor: 2.8(40 metric) Sensitivity Max. Working Pressure: 175 psi (12 bar) (See Table B)
Material Specifications cover Plates Fusible Link: Beryllium Nickel Model G4/G5 (Solid or Perforated) Sprinkler Body: Brass Alloy Model G4/G5 OR Gasket (cULus only) Levers: Bronze Alloy Model G4/G5 SR Gasket Yoke: Brass Alloy
Sealing washer: Nickel with PTFE Cover Plate Finishes
Load Screw: Bronze Alloy (See Table 0)
Towers: Copper Alloy Sprinkler Wrench Pins: Stainless Steel Model FC Deflector: Bronze Alloy
Listings and Approvals Cup. Steel
cULus Listed (Light Hazard only)
FM Approved
Model G5-28 Sprinkler Components and Dimensions siui
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended)
Ceiling
3/4(19 mm) Max.
Cover Plate Adjustment 3/16(5 mm)
Model G4 Cover Plate 3-5/16(84 mm) Dia. Ceiling
Model G5-28 Sprinkler Sensitivity
Cover Plate Model
Listing or Approval Agency
cULus FM
G4/G5 OR SR
G4/G5 OR Gasket OR --
G4/G5 SR Gasket SR SR
OR: Quick-response
SR: Standard-response
Bulletin 034 Rev. F Page 2 of 8
April 2017 OR www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 1`11/2
Nominal K-Factor: 4.2 (60 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Fusible Link: Beryllium Nickel
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing washer: Nickel with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Sprinkler Temperature Ratings
165°F (74°C)
212°F (100°C)
Sensitivity
(See Table C)
Cover Plates
Model G4/G5 (Solid or Perforated)
Model G4/G5 OR Gasket
Model G4/G5 SR Gasket
Cover Plate Finishes
(See Table G)
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed (Light Hazard only)
Model G5-42 Sprinkler Components and Dimensions L!IUI(P
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended)
Ceiling
3/4(19 mm) Max.
Cover Plate Adjustment 3/16(5 mm)
Model G4 Cover Plate 3-5/1611 (84 mm) Dia. Ceiling
Model 1135-42 Sensitivity
Cover Plate Model
Listing or Approval Agency
cULus
G4/G5 OR
G4/G5 OR Gasket OR
G4/G5 SR Gasket SR
OR: Quick-response
SR: Standard-response
Bulletin 034 Rev. F Page 3 of 8
April 2017 Weumbld www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2 NPT or ISO 7-1 R1/2
Nominal K-Factor: 5.6 (80 metric)
Max. Working Pressure:
175 psi (12 bar)
250 psi (17 bar) (cULus only)
Material Specifications
Fusible Link: Beryllium Nickel
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing washer: Nickel with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Sprinkler Temperature Ratings
165°F (74°C)
212°F (100°C) (cULus, FM, LPCB, CE only)
Sensitivity
(See Table D)
Cover Plates
T7
Model G4/G5 (Solid or Perforated)
Model G4/G5 OR Gasket (cULus only)
Model G4/G5 SR Gasket (cULus and FM only)
Cover Plate Finishes
(See Table D)
Sprinkler Wrench
Model FC
Listings and Approvals ( cULus Listed (Light & Ordinary Hazard Only)
FM Approved
LPCB Approved
VdS Approved [165°F (74°C) only]
CE Listed
Model G5-56 Sprinkler Components and Dimensions LsIuIlC
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended)
Ceiling
3/4(19 mm) Max.
Cover Plate Adjustment 3/16(5 mm)
Model G4 Cover Plate 3-5/16(84 mm) Dia. Ceiling
Model G5-56 Sensitivity
Cover Plate Model
Listing or Approval Agency
cULus FM LPCB, VdS, CE
G4/G5 OR SR SR
G4/G5 OR Gasket OR -- --
G4/G5 SR Gasket SR SR --
OR: Quick-response
SR: Standard-response
Bulletin 034 Rev. F neffablid Page 4 of 8
April 2017 www.reliablesprinkler.com
Technical Specifications
Style: Fiat Concealed Pendent
Threads: 1/2 NPT or iso 7-1 R1/2
Nominal K-Factor: 5.6 (80 metric)
Max. Working Pressure: 300 psi (21 bar)
Material Specifications
Fusible Link: Beryllium Nickel
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Ahoy
Sealing washer: Nickel with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Sprinkler Temperature Ratings
165°F (74°C)
212°F (100°C)
Sensitivity
(See Table E)
Cover Plates
Model G4/G5 (Solid or Perforated)
Model G4/G5 OR Gasket
Model G4/G5 SR Gasket
Cover Plate Finishes
(See Table G)
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed (Light & Ordinary Hazard only)
Model G5-56 300 Sprinkler Components and Dimensions
2-5/16"
(58 mm)
Dia.
Threads
Body
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended)
Ceiling
3/4(19mm) Max.
Cover Plate Adjustment 3/16(5 mm)
Model G4 Cover Plate 3-5/16" (84 mm) Dia. Ceiling
Model G5-56 300 Sensitivity
Cover Plate Model
Listing or Approval Agency
cULus
G4/G5 OR
G4/G5 OR Gasket OR
G4/G5 SR Gasket SR
QR: Quick-response
SR: Standard-response
Bulletin 034 Rev. F Page 5 of 8
April 2017 www.reiiabiesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 3/4 NPT or ISO 7-1 R3/4
Nominal K-Factor: 8.0 (115 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Fusible Link: Beryllium Nickel
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing washer: Nickel with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Sprinkler Temperature Ratings
165°F (74°C)
212-F (100-C)
Sensitivity
(See Table F)
Cover Plates
Model G4/G5 (Solid or Perforated)
Model G4/G5 OR Gasket
Model G4/G5 SR Gasket
Cover Plate Finishes
(See Table G) ...
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed (Light & Ordinary Hazard Only)
Model 11315-80 Sprinkler Components and Dimensions
2-5/16" h (5
Threads
Body
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended)
Ceiling
3/4(19mm) Max.
Cover Plate Adjustment 3/16(5 mm)
Model G4 Cover Plate 3-5/16(84 mm) Dia. Ceiling
Model 1135-80 Sensitivity
Cover Plate Model
Listing or Approval Agency
cULus
G4/G5 OR
G4/G5 OR Gasket OR
G4/G5 SR Gasket SR
UK: QUICK-response
SR: Standard-response
Bulletin 034 Rev. F Page 6 of 8
April 2017 www.reliablesprinkler.com
Installation Dimensions and Cover Plate Information
Mm. to Max. Mm. to Max.
Cover Recommended Cover Plate Face of Fitting Dropped Cover Plate
Cover Plate Plate Hole Diameter Adjustment to Deflector Temperature
Model Diameter in Ceiling Inch Ceiling(l)Distance Rating
Inch Inch (mm) Inch below Ceiling OF
(mm) (mm) (mm) Inch (°C)
(mm)
G4/G5 (2) 3-5/16
(84) 135°P
G4/G5 OR Gasket(3)3-11/16
(94) 2-5/8
(67)
3/4
(19)
1-1/2t02-1/4
(38 to 57)
1/4to1
(6 to 25) or
G4/G5 SR Gasket(3) 165°F5 (101 mm) (74°C)
Notes:
Face of fitting to ceiling dimensions are based on nominal thread make up. Verify dimensions based on fitting and thread sealing
method prior to installation. A 1/2" x 1/2' brass nipple extension (Reliable P/N 6999991900) is available to assist with replacement of
Reliable Model G4A sprinklers.
Model G4/G5 cover plates are available either solid or perforated.
Model G4/G5 OR Gasket and Model G4/05 SR Gasket cover plates are sold as assembled units including both the cover plate and
gasket. Model G4/G5 OR Gasket and Model G4/G5 SR Gasket cover plates and gaskets are not interchangeable.
For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (380C).
For use with 212°F(100°C)temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F (660C).
Cover Plate Finishes1t
Standard Finishes
White Paint
Chrome
pecial Application Finishes
Off White Paint
Black Paint
Custom Color Paint - Specify(2)
Raw Brass (Lacquered)
Bright Brass
Finished Bronze
Black Plated
Satin Chrome
Stainless Steel Clad (3)
Notes:
Paint or any other coating applied over the factory finish will void all approvals and warranties. Gaskets for Model G4/G5 OR Gasket
and Model G4/G5 SR Gasket cover plates are only available in white.
Custom color paint is semi-gloss unless specified otherwise.
Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Alloy on the back side. Cover
plates are not listed or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated.
Application
Model G5 series sprinklers are standard coverage, flat plate
concealed pendent sprinklers. The sprinklers are intended
for use in accordance with NFPA 13, as well as the require-
ments of the applicable approval agencies.
Model G5 series sprinklers are available as either Quick-re-
sponse (QR) or Standard-response (SR) depending on the
approval agency and cover plate selected.
Model G5 series sprinklers use Model G4/G5 flat cover
plates. Model G4/G5 QR Gasket and G4/G5 SR Gasket
cover plates are available to limit air and dust movement
through the ceiling.
Listing & Approval Agencies
Individual Model G5 series sprinkler may be listed or ap-
proved by the following agencies:
Underwriters Laboratories, Inc. and UL Canada (cULus)
Listing Category: Sprinklers, Automatic and Open
Guide Number: VNIV
FM Approvals (FM)
Loss Prevention Certification Board (LPCB)
VdS Schadenverhutung GmbH (VdS)
EC-Certificate of Conformity 0832-CPD-2062 (CE)
See Table A and the individual sprinkler data sheets in this
Bulletin for listings and approvals applicable to each sprin-
kler.
Bulletin 034 Rev. F Page 7 of 8
April 2017 www.reliablesprinkler.com
Installation
Model G5 series sprinklers are intended to be installed in
accordance with NFPA 13 and the requirements of other ap-
plicable authorities having jurisdiction. Model G5 series
sprinklers must not be installed in ceilings with positive
pressure in the space above.
Model G5 series sprinklers are shipped with a protective
cap that should remain on the sprinkler until installed. The
protective cap should be replaced following installation of
the sprinkler and permanently removed only when the cover
plate is installed and the sprinkler system is placed in ser-
vice following construction.
Model G5 series sprinkler are installed with the Model FC
wrench. The use of any other wrench to installed Model G5
series sprinklers is not permitted and may damage the
sprinkler. Temporarily remove the protective cap during in-
stallation of the sprinkler. Insert the Model FC wrench over
the sprinkler until the wrench engages the body. Do not
wrench any other part of the sprinkler/cup assembly. The
Model FC wrench is designed to be turned with a standard
1/2" square drive. Tighten the sprinkler into the fitting after
applying a PTFE based thread sealant to the sprinkler's
threads. Recommended installation torque is specified in
Table I.
Installation Torque
Recommended
Sprinkler Threads Installation Torque
(mm. - max.)
ft-lb I N-rn
1/2"NPTorlS07-1R1/2 8-18 11-24
W NPTor 1S07-1R3/4 14-20 19-27
Do not exceed the maximum recommended torque. Ex-
ceeding the maximum recommended torque may cause
leakage or impairment of the sprinkler. Use care when in-
serting or removing the wrench from the sprinkler to avoid
damage to the sprinkler.
a:J
Maintenance
Reliable Model G5 series sprinkler should be inspected and
the sprinkler system maintained in accordance with NFPA
25, as well as the requirements of any Authorities Having
Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the po-
tential for damage to sprinklers that could cause improper
operation or non-operation.
Do not clean sprinklers with soap and water, ammonia liquid
or any other cleaning fluids. Remove dust by gentle vacu-
uming without touching the sprinkler.
Replace any sprinkler or cover plate which has been
painted (other than factory applied). Properly installed
Model G4/G5 cover plates will have an air gap that is re-
quired for proper operation, do not seal the gap or paint the
cover plates. Model G5 series sprinklers have holes in the
cup that must remain unobstructed.
Replace any sprinkler which has been damaged. A stock of
spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvert-
ent operation or non-operation during a fire event.
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee,
terms, and conditions, visit www.reliablesprinkler.com.
Patents
Model G5 series sprinklers may be covered by one or more
of the following patents:
U.S. Patent 6,554,077, U.S. Patent 7,275,603, U.S. Patent
8,776,903, U.S. Patent 9,248,327
Ordering Information
Specify the following when ordering.
Sprinkler
Model (G5-28, G5-42, G5-56, G5-56 300, G5-80)
Temperature Rating [165°F (74°C) or 212°F
(100°C)]
Threads (NPT or ISO 7-1)
Cover Plate
Model (G4/G5 [Solid], G4/G5 Perforated, G4/G5
OR Gasket, G4/G5 SR Gasket)
Finish (See Table G)
Install the cover plate by hand, turning the cover in the
clockwise direction until it is tight against the ceiling. For
Model G4/G5 OR Gasket and Model G4/G5 SR Gasket
cover plates, the gasket should be attached to the flange of
the cover plate skirt only. Do not glue the gasket in place or
allow the gasket to overlap both the cover plate and the
flange of the skirt.
Sprinkler Wrench
Model FC c'J
C N- a) 0) 0) 0) 0) Z a-
Bulletin 034 Rev. F Page 8 of 8
April 2017 www.reliablesprinkler.com