HomeMy WebLinkAbout1719 BUENA VISTA WAY; ; FPR2018-0158PERMIT REPORT
(?ity of
Carlsbad
Print Date: 09/07/2023
Job Address: 1719 BUENA VISTA WAY, CARLSBAD, CA
Permit Type: FIRE-Construction Residential Work Class:
Parcel #: Track #:
Valuation: $0.00 Lot #:
Occupancy Group: Project U:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U:
Plan Check U:
Permit No: FPR2018-0158
Status: Closed - Finaled
Single Family Fire Sprinklu
Applied: 09/27/2018
Issued: 12/10/2018
Finaled Close Out: 09/12/2019
Final Inspection:
INSPECTOR: Salcedo, Felix
Project Title:
Description: PLAN 1- YADA FARM LOT 9- 13D NEW RESIDENTAL SYSTEM
FPContractor:
NP MECHANICAL INC
P0 BOX 309
CORONA, CA 92878-0309
(951) 667-4220
FEE AMOUNT
FIRE NFPA 13D Single Family System (lnsp/Bldg) $125.00
FIRE NFPA 13D Single Family System (Plan Review)' $246.00
Total Fees: $371.00 Total Payments To Date: $371.00 • Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
FPR20I8-0158
1719 BUENA VISTA WAY
PLAN 1- YADA FARM LOT 9- 13D NEW RESI DENTAL
SYSTEM
FPR20I8-0158
FPR20I8-0159
1710 YADA PL
PLAN 2-YADA FARM LOT 8- 13D NEW SPRINKLER
SYSTEM
9/27/2018
FPR20I8-0159
FPR20I8-0160
1730 YADA PL
PLAN 3- YADA FARM LOT 7- 13D NEW SPRINKLER
SYSTEM
9/2712018
FPR20I8-0160
fr-oL8 -o('g
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : 12 PACIFIC
Building : PLAN 1
Location : CALC AREA 1
System
Contract
Data File : PLAN1 CAl 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC
Location - CALC AREA 1
Building - PLAN 1
Contractor - NP MECHANICAL
Calculated By - JC
Construction: (X) Combustible
OCCUPANCY - LIGHT HAZARD
Date - 7/30/18
System No. -
Contract No. -
Drawing No. - 1
Non-Combustible Ceiling Height
Listed Flow at Start Point - 13
Listed Pres. at Start Point - 7
MAXIMUM LISTED SPACING 16 x 16
Domestic Flow Added - 5
Additional Flow Added -
Elevation at Highest Outlet -
Note:
Gpm System Type
Psi (X) Wet ( ) Dry
Deluge ( ) PreAction
Gpm Sprinkler or Nozzle
Gpm Make RELIABLE Model RFC49
Feet Size 7/16 K-Factor 4.9
Temperature Rating 165
S
Y
S
T
E
M
D
E
S
I
G
N
Type of Calculation: ( )NFPA 13 Residential ( .)NFPA 13R (X)NFPA 13D
Number of Sprinklers Flowing: ( )1 (X)2 ( )4
)Other
)Specific Ruling Made by Date
Calculation Gpm Required 27.331 Psi Required 32.321 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data:
A Date of Test - Rated Cap.
T Time of Test - @ Psi
E Static (Psi) - 75 Elev.
R Residual (Psi) - 43 Other
Flow (Gpm) - 3050
S Elevation -
P Location:
P
L Source of Information:
Y
Tank or Reservoir:
Cap.
Elev.
Well
Proof Flow Gpm
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical
12 PACIFIC
Page 2
Date 9/11/18
City Water Sup p!y: Demand: Cl - Static Pressure : 67.5 Dl - Elevation : 12.993
C2 - Residual Pressure: 38.7 D2 - System Flow : 27.331
C2 - Residual Flow : 3050 D2 - System Pressure : 62.331
Hose ( Demand) : 5
D3 - System Demand : 32.331
Safety Margin : 5.162
150
140
130
p120
R°
E10°
S90
s 80
U 70
[-Em-
30
400
R6°
40
E___________________________________________
20
10
800 1200 1600 2000 2400 2800 3200 3600
FLOW ( N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N* CPVC90EllHarvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVCCouplingTee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 13 90 Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
Hi 10.0 4.9 7.04 na 13.0
H2 10.0 4.9 8.55 na 14.33
H3 10.0 11.88 na
Dl 11.0 7.36 na
D2 11.0 9.02 na
1 11.0 9.24 na
D3 11.0 11.44 na
2 11.0 11.44 na
3 11.0 12.04 na
4 11.0 13.04 na
5 11.0 19.8 na
6 11.0 18.57 na
7 11.0 17.26 na
8 11.0 14.41 na
9 11.0 12.07 na
TA 11.0 21.28 na
GA 5.0 24.73 na
BR 2.0 32.32 na
EL -3.0 34.82 na
X -3.0 38.48 na 5.0
Ml -3.0 39.66 na
M2 -3.0 43.9 na
CM -3.0 54.96 na
100 -3.0 54.97 na
101 -3.0 54.97 na
SRC -20.0 62.33 na
0.05 256 7.039
0.05 256 7.0
The maximum velocity is 13.34 and it occurs in the DiDe between nodes M2 and CM
Final Calculations - Hazen-Williams
NP Mechanical Page
q
5
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pt Pn
Hi 13.00 0.874 N 7.0 1.000 7.039 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
Di 13.0 0.0944 0.0 8.000 0.755 Vel = 6.95
0.0
13.00 7.361 K Factor = 4.79
H2 14.33 0.874 N 7.0 1.000 8.553 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D2 14.33 0.1131 0.0 8.000 0.905 Vel = 7.66
0.0
14.33 9.025 K Factor = 4.77
H3 0.0 0.874 N 7.0 1.000 11.875
to 150.0 0.0 7.000 -0.433
D3 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 11.442 K Factor =0
Dl 13.00 0.874 N 7.0 9.917 7.361
to 150.0 0 3.0 10.000 0.0
1 13.0 0.0944 0.0 19.917 1.881 Vel = 6.95
0.0
13.00 9.242 K Factor = 4.28
D2 14.33 0.874 R 1.0 0.917 9.025
to 150.0 0.0 1.000 0.0
1 14.33 0.1132 0.0 1.917 0.217 Vel = 7.66
1 -4.24 0.874 3R 3.0 34.250 9.242
to 150.0 0.0 3.000 0.0
2 10.09 0.0591 0.0 37.250 2.200 Vel = 5.40
0.0
10.09 11.442 K Factor = 2.98
D3 0.0 0.874 0 3.0 4.583 11.442
to 150.0 0.0 3.000 0.0
2 0.0 0.0 0.0 7.583 0.0 Vel = 0
2 10.09 0.874 N 7.0 3.167 11.442
to 150.0 0.0 7.000 0.0
3 10.09 0.0591 0.0 10.167 0.601 Vel = 5.40
3 0.0 0.874 2R 2.0 14.833 12.043
to 150.0 0.0 2.000 0.0
4 10.09 0.0591 0.0 16.833 0.995 Vel = 5.40
4 -16.06 0.874 3R 3.0 37.333 13.038
to 150.0 0 3.0 6.000 0.0
9 -5.97 -0.0224 0.0 43.333 -0.971 Vel = 3.19
0.0
-5.97 12.067 K Factor = -1.72
4 16.06 0.874 4R 4.0 41.417 13.038
to 150.0 0 3.0 7.000 0.0
5 16.06 0.1397 0.0 48.417 6.762 Vel = 8.59
5 -27.33 0.874 N 7.0 10.000 19.800
to 150.0 0.0 7.000 0.0
6 -11.27 -0.0725 0.0 17.000 -1.232 Vel = 6.03
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point at Pt/Ft Eqv. Ln. Total Pf Pn
6 0.0 0.874 R 1.0 14.083 18.568
to 150.0 0 3.0 4.000 0.0
7 -11.27 -0.0724 0.0 18.083 -1.310 Vet = 6.03
7 0.0 0.874 5R 5.0 27.333 17.258
to 150.0 N 7.0 12.000 0.0
8 -11.27 -0.0724 0.0 39.333 -2.849 Vet = 6.03
8 0.0 0.874 5R 5.0 27.333 14.409
to 150.0 0.0 5.000 0.0
9 -11.27 -0.0724 0.0 32.333 -2.342 Vet = 6.03
9 -5.97 0.874 0 3.0 14.750 12.067
to 150.0 0.0 3.000 0.0
1 -17.24 -0.1592 0.0 17.750 -2.825 Vet = 9.22
0.0
-17.24 9.242 K Factor = -5.67
5 27.33 1.101 N 7.0 5.250 19.800
to 150.0 0.0 7.000 0.0
TR 27.33 0.1212 0.0 12.250 1.485 Vet = 9.21
0.0
27.33 21.285 K Factor = 5.92
TR 27.33 1.101 R 1.0 6.000 21.285
to 150.0 0.0 1.000 2.599
GA 27.33 0.1211 0.0 7.000 0.848 VeI= 9.21
GA 0.0 1.101 Fsp 0.0 3.000 24.732
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 27.33 0.1213 0 5.0 27.126 3.290 Vet = 9.21
BR 0.0 1.245 0.0 5.000 32.321
to 150.0 0.0 0.0 2.166
EL 27.33 0.0664 0.0 5.000 0.332 Vet = 7.20
EL 0.0 1.245 0.0 55.000 34.819
to 150.0 0.0 0.0 0.0
X 27.33 0.0666 0.0 55.000 3.665 Vet = 7.20
X 5.00 1.025 Ball 3.037 2.000 38.484 Qa = 5
to 150.0 0.0 3.038 0.0
Ml 32.33 0.2344 0.0 5.038 1.181 Vet = 12.57
Ml 0.0 1.025 0.0 1.000 39.665
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 32.33 0.2340 0.0 1.000 0.234 Vet = 12.57
M2 0.0 0.995 1 5.841 35.000 43.899
to 150.0 0.0 5.841 0.0
CM 32.33 0.2709 0.0 40.841 11.063 Vet = 13.34
CM 0.0 7.98 F 13.591 331.000 54.962
to 150.0 1 52.855 66.447 0.0
100 32.33 0.0 0.0 397.447 0.004 Vet = 0.21
100 0.0 9.79 F 14.844 137.000 54.966
to 150.0 1 67.474 82.319 0.0
101 32.33 0.0 0.0 219.319 0.001 Vet = 0.14
101 0.0 6.16 E 22.818 10.000 54.967
to 150.0 0.0 22.818 7.363
SRC 32.33 0.0 0.0 32.818 0.001 Vet = 0.35
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical
12 PACIFIC
Page 7
Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pt/Ft Eqv. Ln. Total Pf Pn
0.0
32.33 62.331 K Factor = 4.09
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name :12 PACIFIC
Building : PLAN 1
Location : CALC AREA 2
System
Contract
Data File : PLAN 1 CA2 20X20.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
09
NP Mechanical Page 1
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC Date - 7/30/18
Location - CALC AREA 2
Building - PLAN 1 System No. -
Contractor - NP MECHANICAL Contract No. -
Calculated By - JC Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA
Y Number of Sprinklers Flowing:
S ( )Other
T ( )Specific Ruling
E
13 Residential
(X)1 ( )2
Made by
( )NFPA 13R (X)NFPA 13D
( )4
Date
M Listed Flow at Start Point - 20 Gpm System Type
Listed Pres. at Start Point - 16.7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 20 x 20 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 20.024 Psi Required 35.783 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - @ Psi Elev.
E Static (Psi) - 75 Elev.
R Residual (Psi) - 43 Other Well
Flow (Gpm) - 3050 Proof Flow Gpm
S Elevation -
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
12 PACIFIC Date 9/11/18
City Water Supply: Demand: Cl - Static Pressure : 67.5 Dl - Elevation : 12.993
C2 - Residual Pressure: 38.7 D2 - System Flow : 20.024
C2 - Residual Flow : 3050 D2 - System Pressure : 59.332
Hose ( Demand) : 5
D3 - System Demand : 25.024
Safety Margin : 8.165
150
140
130
p
12
R 11
E10°
S 90
80
u 70 :
-
DZ-
R6° -
- E 50D3 - -
40
30
20
10
.I -
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW ( N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrv. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC 100 2.25 2 2.5 2.25 10
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 1390 Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Hi 10.0 21.44 na
H2 10.0 21.44 na
H3 10.0 4.9 16.7 na
Di 11.0 21.01 na
D2 11.0 21.01 na
1 11.0 21.01 na
D3 11.0 17.95 na
2 11.0 19.54 na
3 11.0 20.36 na
4 11.0 21.71 na
5 11.0 25.72 na
6 11.0 25.08 na
7 11.0 24.4 na
8 11.0 22.92 na
9 11.0 21.71 na
TR 11.0 26.56 na
GA 5.0 29.63 na
BR 2.0 35.78 na
EL -3.0 38.14 na
X -3.0 40.2 na
Mi -3.0 40.93 na
M2 -3.0 45.08 na
CM -3.0 51.96 na
100 -3.0 51.97 na
101 -3.0 51.97 na
SRC -20.0 59.33 na
20.02 0.05 400 16.7
5.0
Pessure / Flow Summary - STANDARD
NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
The maximum velocity is 10.71 and it occurs in the pipe between nodes H3 and D3
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point at Pt/Ft Eqv. Ln. Total Pt Pn
Hi 0.0 0.874 N 7.0 1.000 21.440
to 150.0 0.0 7.000 -0.433
Di 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 21.007 K Factor = 0
H2 0.0 0.874 N 7.0 1.000 21.440
to 150.0 0.0 7.000 -0.433
D2 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 21.007 K Factor = 0
H3 20.02 0.874 N 7.0 1.000 16.700 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D3 20.02 0.2099 0.0 8.000 1.679 Vel = 10.71
0.0
20.02 17.946 K Factor = 4.73
Dl 0.0 0.874 N 7.0 9.917 21.007
to 150.0 0 3.0 10.000 0.0
1 0.0 0.0 0.0 19.917 0.0 Vel = 0
0.0
0.0 21.007 K Factor = 0
D2 0.0 0.874 R 1.0 0.917 21.007
to 150.0 0.0 1.000 0.0
1 0.0 0.0 0.0 1.917 0.0 Vel =0
1 -8.11 0.874 3R 3.0 34.250 21.007
to 150.0 0.0 3.000 0.0
2 -8.11 -0.0394 0.0 37.250 -1.469 Vel = 4.34
0.0
-8.11 19.538 K Factor = -1.83
D3 20.02 0.874 0 3.0 4.583 17.946
to 150.0 0.0 3.000 0.0
2 20.02 0.2099 0.0 7.583 1.592 Vel = 10.71
2 -8.10 0.874 N 7.0 3.167 19.538
to 150.0 0.0 7.000 0.0
3 11.92 0.0804 0.0 10.167 0.817 Vel = 6.37
3 0.0 0.874 2R 2.0 14.833 20.355
to 150.0 0.0 2.000 0.0
4 11.92 0.0804 0.0 16.833 1.353 Vel = 6.37
4 -12.12 0.874 3R 3.0 37.333 21.708
to 150.0 0 3.0 6.000 0.0
9 -0.2 0.0 0.0 43.333 -0.002 Vel = 0.11
0.0
-0.20 21.706 K Factor = -0.04
4 12.12 0.874 4R 4.0 41.417 21.708
to 150.0 0 3.0 7.000 0.0
5 12.12 0.0829 0.0 48.417 4.014 Vel = 6.48
5 -20.03 0.874 N 7.0 10.000 25.722
to 150.0 0.0 7.000 0.0
6 -7.91 -0.0376 0.0 17.000 -0.639 Vel = 4.23
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pt/Ft Eqv. Ln. Total Pt Pn
6
to
7
0.0
-7.91
0.874
150.0
-0.0377
R
0
1.0
3.0
0.0
14.083
4.000
18.083
25.083
0.0
-0.681 Vel = 4.23
7 0.0 0.874 511 5.0 27.333 24.402
to 150.0 N 7.0 12.000 0.0
8 -7.91 -0.0376 0.0 39.333 -1.479 Vel = 4.23
8 0.0 0.874 5R 5.0 27.333 22.923
to 150.0 0.0 5.000 0.0
9 -7.91 -0.0376 0.0 32.333 -1.217 Vel = 4.23
9 -0.20 0.874 0 3.0 14.750 21.706
to 150.0 0.0 3.000 0.0
1 -8.11 -0.0394 0.0 17.750 -0.699 Vel = 4.34
0.0
-8.11 21.007 K Factor = -1.77
5 20.02 1.101 N 7.0 5.250 25.722
to 150.0 0.0 7.000 0.0
TR 20.02 0.0682 0.0 12.250 0.836 Vel = 6.75
0.0
20.02 26.558 K Factor = 3.88
TR 20.02 1.101 R 1.0 6.000 26.558
to 150.0 0.0 1.000 2.599
GA 20.02 0.0681 0.0 7.000 0.477 Vel = 6.75
GA 0.0 1.101 Fsp 0.0 3.000 29.634
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 20.02 0.0682 0 5.0 27.126 1.850 Vel = 6.75
BR 0.0 1.245 0.0 5.000 35.783
to 150.0 0.0 0.0 2.166
EL 20.02 0.0374 0.0 5.000 0.187 Vel = 5.28
EL 0.0 1.245 0.0 55.000 38.136
to 150.0 0.0 0.0 0.0
X 20.02 0.0375 0.0 55.000 2.061 Vel = 5.28
X 5.00 1.025 Ball 3.037 2.000 40.197 Qa = 5
to 150.0 0.0 3.038 0.0
Ml 25.02 0.1459 0.0 5.038 0.735 Vel = 9.73
Ml 0.0 1.025 0.0 1.000 40.932
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4 M2 25.02 0.1460 0.0 1.000 0.146 Vel = 9.73
M2 0.0 0.995 T 5.841 35.000 45.078
to 150.0 0.0 5.841 0.0
CM 25.02 0.1686 0.0 40.841 6.887 Vel = 10.32
CM 0.0 7.98 F 13.591 331.000 51.965
to 150.0 T 52.855 66.447 0.0
100 25.02 0.0 0.0 397.447 0.003 Vel = 0.16
100 0.0 9.79 F 14.844 137.000 51.968
to 150.0 T 67.474 82.319 0.0
101 25.02 0.0 0.0 219.319 0.0 VeI= 0.11
101 0.0 6.16 E 22.818 10.000 51.968
to 150.0 0.0 22.818 7.363
SRC 25.02 0.0 0.0 32.818 0.001 Vel = 0.27
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical
12 PACIFIC
Page 7
Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C's or Ftng's Pe Pv Notes
Point Qt Pt/Ft Eqv. Ln. Total Pt Pn
0.0
25.02 59.332 K Factor = 3.25
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
PPs2cI S (95
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name :12 PACIFIC
Building : PLAN 1
Location : ALT. CALC AREA 1
System
Contract
Data File : ALT. PLAN1 CAl 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page 1
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC Date - 9/11/18
Location - ALT. CALC AREA 1
Building - PLAN 1 System No. -
Contractor - NP MECHANICAL Contract No. -
Calculated By - JC Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 27.331 Psi Required 32.920 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - @ Psi Elev.
E Static (Psi) - 75 Elev.
R Residual (Psi) - 43 Other Well
Flow (Gpm) - 3050 Proof Flow Gpm
S Elevation -
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical
12 PACIFIC
Page 2
Date 9/11/18
City Water Supply:
Cl - Static Pressure : 67.5
02 - Residual Pressure: 38.7
C2 - Residual Flow : 3050
Demand:
Dl - Elevation : 12.993
D2 - System Flow : 27.331
D2 - System Pressure : 62.931
Hose ( Demand) : 5
D3 - System Demand : 32.331
Safety Margin : 4.563
150
140
130
P 120
A 110
E 100
90
80
U 70
R 60
E 50 D3
40
30
20
10
C2
400 800 1200 1600 2000 2400 2800 3200 C.,,
FLOW ( N " 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC 100
E NFPA 13 90' Standard Elbow
F NFPA 13 45' Elbow
Fsp Flow Switch Potter VSR
N * CPVC 90'Ell Harvel-Spears 0. CPVC Tee - Branch
R * CPVC Coupling Tee - Run
S NFPA 13 Swing Check
T NFPA 1390, Flow thru Tee
2.25 2 2.5 2.25 10
1 2 2 3 4 5 6
1 1 1 1 2 2 3
Fitting generates a Fixed Loss Based on Flow
7 7 8 9 11 12
3 3 5 6 8 10 12
1 1 1 1 1 1 2
0 0 5 7 9 11 14
3 4 5 6 8 10 12
7 8 10 12 14 18 22 27 35 40 45 50 61
3 3 4 5 7 9 11 13 17 19 21 24 28
13 0 0 0 0 0 0 0 0 0 0 0 0
15 0 0 0 0 0 0 0 0 0 0 0 0
2 0 0 0 0 0 0 0 0 0 0 0 0
16 19 22 27 32 45 55 65
15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units
Length Units
Flow Units
Pressure Units
Inches
Feet
US Gallons per Minute
Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *• The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node
No.
Elevation K-Fact Pt
Actual
Pn Flow Density
Actual
Area Press
Req.
Hi 10.0 4.9 7.04 na 13.0 0.05 256 7.039
H2 10.0 4.9 8.55 na 14.33 0.05 256' 7.0
H3 10.0 11.74 na
Di 11.0 7.36 na
D2 11.0 9.02 na
11.0 9.24 na
D3 11.0 11.31 na
2 11.0 11.31 na
3 11.0 11.87 na
4 11.0 12.81 na
5 11.0 18.89 na
6 11.0 20.4 na
7 11.0 18.74 na
8 11.0 15.13 na
9 11.0 12.17 na
TRA 11.0 21.88 na
GA 5.0 25.33 na
BR 2.0 32.92 na
EL -3.0 35.42 na
X -3.0 39.08 na 5.0
Mi -3.0 40.26 na
M2 -3.0 44.5 na
CM -3.0 55.56 na
100 -3.0 55.57 na
101 -3.0 55.57 na
SRC -20.0 62.93 na
The maximum velocity is 13.34 and it occurs in the pipe between nodes M2 and CM
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pt/Ft Eqv. Ln. Total Pf Pn
Hi 13.00 0.874 N 7.0 1.000 7.039 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
Dl 13.0 0.0944 0.0 8.000 0.755 Vel = 6.95
0.0
13.00 7.361 K Factor = 4.79
H2 14.33 0.874 N 7.0 1.000 8.553 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D2 14.33 0.1131 0.0 8.000 0.905 Vel = 7.66
0.0
14.33 9.025 K Factor = 4.77
H3 0.0 0.874 N 7.0 1.000 11.743
to 150.0 0.0 7.000 -0.433
D3 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 11.310 K Factor =0
Di 13.00 0.874 N 7.0 9.917 7.361
to 150.0 0 3.0 10.000 0.0
1 13.0 0.0944 0.0 19.917 1.881 Vel = 6.95
0.0
13.00 9.242 K Factor = 4.28
02 14.33 0.874 R 1.0 0.917 9.025
to 150.0 0.0 1.000 0.0
1 14.33 0.1132 0.0 1.917 0.217 VeI= 7.66
1 -4.57 0.874 3R 3.0 34.250 9.242
to 150.0 0.0 3.000 0.0
2 9.76 0.0555 0.0 37.250 2.068 Vel = 5.22
0.0
9.76 11.310 K Factor = 2.90
D3 0.0 0.874 0 3.0 4.583 11.310
to 150.0 0.0 3.000 0.0
2 0.0 0.0 0.0 7.583 0.0 Vel = 0
2 9.76 0.874 N 7.0 3.167 11.310
to 150.0 0.0 7.000 0.0
3 9.76 0.0556 0.0 10.167 0.565 Vel = 5.22
3 0.0 0.874 2R 2.0 14.833 11.875
to 150.0 0.0 2.000 0.0
4 9.76 0.0555 0.0 16.833 0.934 Vel = 5.22
4 -14.53 0.874 3R 3.0 37.333 12.809
to 150.0 0 3.0 6.000 0.0
9 -4.77 -0.0148 0.0 43.333 -0.641 Vel = 2.55
0.0
-4.77 12.168 K Factor= -1.37
4 14.53 0.874 411 4.0 41.417 12.809
to 150.0 N 7.0 11.000 0.0
5 14.53 0.1160 0.0 52.417 6.082 Vel = 7.77
5 0.0 0.874 0 3.0 10.000 18.891
to 150.0 0.0 3.000 0.0
6 14.53 0.1160 0.0 13.000 1.508 VeI= 7.77
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fi'nal Calculations - Hazen-Williams
NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pt/Ft Eqv. Ln. Total Pf Pn
6 -27.33 0.874 R 1.0 14.083 20.399
to 150.0 0 3.0 4.000 0.0
7 -12.8 -0.0917 0.0 18.083 -1.658 Vel = 6.85
7 0.0 0.874 5R 5.0 27.333 18.741
to 150.0 N 7.0 12.000 0.0
8 -12.8 -0.0917 0.0 39.333 -3.607 Vel = 6.85
8 0.0 0.874 511 5.0 27.333 15.134
to 150.0 0.0 5.000 0.0
9 -12.8 -0.0917 0.0 32.333 -2.966 Vel = 6.85
9 -4.77 0.874 0 3.0 14.750 12.168
to 150.0 0.0 3.000 0.0
1 -17.57 -0.1648 0.0 17.750 -2.926 Vel = 9.40
0.0
-17.57 9.242 K Factor = -5.78
6 27.33 1.101 N 7.0 5.250 20.399
to 150.0 0.0 7.000 0.0
TRA 27.33 0.1213 0.0 12.250 1.486 Vel = 9.21
0.0
27.33 21.885 K Factor = 5.84
TRA 27.33 1.101 R 1.0 6.000 21.885
to 150.0 0.0 1.000 2.599
GA 27.33 0.1211 0.0 7.000 0.848 VeI= 9.21
GA 0.0 1.101 Fsp 0.0 3.000 25.332
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 27.33 0.1212 0 5.0 27.126 3.289 Vel = 9.21
BR 0.0 1.245 0.0 5.000 32.920
to 150.0 0.0 0.0 2.166
EL 27.33 0.0666 0.0 5.000 0.333 Vel = 7.20
EL 0.0 1.245 0.0 55.000 35.419
to 150.0 0.0 0.0 0.0
X 27.33 0.0666 0.0 55.000 3.665 Vel = 7.20
X 5.00 1.025 Ball 3.037 2.000 39.084 Qa = 5
to 150.0 0.0 3.038 0.0
Ml 32.33 0.2344 0.0 5.038 1.181 Vel = 12.57
Ml 0.0 1.025 0.0 1.000 40.265
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 32.33 0.2340 0.0 1.000 0.234 Vel = 12.57
M2 0.0 0.995 1 5.841 35.000 44.499
to 150.0 0.0 5.841 0.0
CM 32.33 0.2709 0.0 40.841 11.063 Vel = 13.34
CM 0.0 7.98 F 13.591 331.000 55.562
to 150.0 1 52.855 66.447 0.0
100 32.33 0.0 0.0 397.447 0.004 Vel = 0.21
100 0.0 9.79 F 14.844 137.000 55.566
to 150.0 1 67.474 82.319 0.0
101 32.33 0.0 0.0 219.319 0.001 Vel = 0.14
101 0.0 6.16 E 22.818 10.000 55.567
to 150.0 0.0 22.818 7.363
SRC 32.33 0.0 0.0 32.818 0.001 Vel = 0.35
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 7
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. 'IC" or Ftng's Pe Pv Notes
Point Qt Pt/Ft Eqv. Ln. Total Pf Pn
0.0
32.33 62.931 K Factor = 4.08
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : 12 PACIFIC
Building : PLAN 1
Location : ALT. CALC AREA 2
System
Contract
Data File : ALT. PLAN1 CA2 20X20.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page 1 ¼
12 PACIFIC Date 9/11/18
HYDRAULIC DESIGN INFORMATION SHEET
Name - 12 PACIFIC Date - 9/11/18
Location - ALT. CALC AREA 2
Building - PLAN 1 System No. -
Contractor - NP MECHANICAL Contract No. -
Calculated By - JC Drawing No. - 1
Construction: (X) Combustible C ) Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: (X)1 C )2 ( )4
S ( )Other
T ( )Specific Ruling Made by Date
H
M Listed Flow at Start Point - 20 Gpm System Type
Listed Pres. at Start Point - 16.7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 20 x 20 ( ) Deluge C ) PreAction
H Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 20.024 Psi Required 36.202 AT BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - @ Psi Elev.
E Static (Psi) - 75 Elev.
R Residual (Psi) - 43 Other Well
Flow (Gpm) - 3050 Proof Flow Gpm
S Elevation -
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
12 PACIFIC Date 9/11/18
City Water Suppjy: Demand: Cl - Static Pressure : 67.5 Dl - Elevation : 12.993
C2 - Residual Pressure: 38.7 D2 - System Flow : 20.024
C2 - Residual Flow : 3050 D2 - System Pressure : 59.751
Hose ( Demand) : 5
D3 - System Demand : 25.024
Safety Margin : 7.745
150
140
130
p120
R°
E10°
S90
S 80
Ci u 70
A6°
E 50 DI
40
30
20
10
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW ( N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
12 PACIFIC Date 9/11/18
Fitting Legend
Abbrev. Name ½ 34 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10
E NFPA 139O'StandardElbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 13 45' Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90'EII Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 1390' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
F4essure / Flow Summary - STANDARD
NP Mechanical Page 4
12 PACIFIC Date 9/11/18
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
Hi 10.0 21.45 na
H2 10.0 21.45 na
H3 10.0 4.9 16.7 na 20.02 0.05 400 16.7
Dl 11.0 21.02 na
D2 11.0 21.02 na
11.0 21.02 na
D3 11.0 17.95 na
2 11.0 19.54 na
3 11.0 20.35 na
4 11.0 21.69 na
5 11.0 25.26 na
6 11.0 26.14 na
7 11.0 25.25 na
8 11.0 23.32 na
9 11.0 21.73 na
TRA 11.0 26.98 na
GA 5.0 30.05 na
BR 2.0 36.2 na
EL -3.0 38.55 na
X -3.0 40.62 na 5.0
Ml -3.0 41.35 na
M2 -3.0 45.5 na
CM -3.0 52.38 na
100 -3.0 52.39 na
101 -3.0 52.39 na
SRC -20.0 59.75 na
The maximum velocity is 10.71 and it occurs in the pipe between nodes H3 and D3
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pt/Ft Eqv. Ln. Total Pt Pn
Hi 0.0 0.874 N 7.0 1.000 21.454
to 150.0 0.0 7.000 -0.433
Di 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 21.021 K Factor =0
H2 0.0 0.874 N 7.0 1.000 21.454
to 150.0 0.0 7.000 -0.433
D2 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 21.021 K Factor =O
H3 20.02 0.874 N 7.0 1.000 16.700 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D3 20.02 0.2099 0.0 8.000 1.679 Vel= 10.71
0.0
20.02 17.946 K Factor = 4.73
Di 0.0 0.874 N 7.0 9.917 21.021
to 150.0 0 3.0 10.000 0.0
1 0.0 0.0 0.0 19.917 0.0 Vel = 0
0.0
0.0 21.021 K Factor =0
D2 0.0 0.874 R 1.0 0.917 21.021
to 150.0 0.0 1.000 0.0
1 0.0 0.0 0.0 1.917 0.0 Vel = 0
1 -8.15 0.874 3R 3.0 34.250 21.021
to 150.0 0.0 3.000 0.0
2 -8.15 -0.0398 0.0 37.250 -1.483 Vel = 4.36
0.0
-8.15 19.538 K Factor= -1.84
D3 20.02 0.874 0 3.0 4.583 17.946
to 150.0 0.0 3.000 0.0
2 20.02 0.2099 0.0 7.583 1.592 Vel = 10.71
2 -8.15 0.874 N 7.0 3.167 19.538
to 150.0 0.0 7.000 0.0
3 11.87 0.0799 0.0 10.167 0.812 Vel= 6.35
3 0.0 0.874 2R 2.0 14.833 20.350
to 150.0 0.0 2.000 0.0
4 11.87 0.0798 0.0 16.833 1.343 Vel = 6.35
4 -10.88 0.874 311 3.0 37.333 21.693
to 150.0 0 3.0 6.000 0.0
9 0.99 0.0008 0.0 43.333 0.035 Vel = 0.53
0.0
0.99 21.728 K Factor = 0.21
4 10.89 0.874 413 4.0 41.417 21.693
to 150.0 N 7.0 11.000 0.0
5 10.89 0.0680 0.0 52.417 3.564 Vel = 5.82
5 0.0 0.874 0 3.0 10.000 25.257
to 150.0 0.0 3.000 0.0
6 10.89 0.0680 0.0 13.000 0.884 Vel = 5.82
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Ai
NP Mechanical Page 6
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. AC" or Ftng's Pe Pv Notes
Point Qt Pt/Ft Eqv. Ln, Total Pt Pn
6 -20.03 0.874 R 1.0 14.083 26.141
to 150.0 0 3.0 4.000 0.0
7 -9.14 -0.0492 0.0 18.083 -0.889 Vel = 4.89
7 0.0 0.874 511 5.0 27.333 25.252
to 150.0 N 7.0 12.000 0.0
8 -9.14 -0.0492 0.0 39.333 -1.934 Vel = 4.89
8 0.0 0.874 511 5.0 27.333 23.318
to 150.0 0.0 5.000 0.0
9 -9.14 -0.0492 0.0 32.333 -1.590 Vel = 4.89
9 0.99 0.874 0 3.0 14.750 21.728
to 150.0 0.0 3.000 0.0
1 -8.15 -0.0398 0.0 17.750 -0.707 Vel = 4.36
0.0
-8.15 21.021 KFactor= -1.78
6 20.02 1.101 N 7.0 5.250 26.141
to 150.0 0.0 7.000 0.0
TRA 20.02 0.0682 0.0 12.250 0.836 Vel = 6.75
0.0
20.02 26.977 K Factor = 3.85
TRA 20.02 1.101 R 1.0 6.000 26.977
to 150.0 0.0 1.000 2.599
GA 20.02 0.0681 0.0 7.000 0.477 Vel = 6.75
GA 0.0 1.101 Fsp 0.0 3.000 30.053
to 150.0 2S 19.125 24.126 4.299 * * Fixed Loss = 3
BR 20.02 0.0682 0 5.0 27.126 1.850 Vel = 6.75
BR 0.0 1.245 0.0 5.000 36.202
to 150.0 0.0 0.0 2.166
EL 20.02 0.0374 0.0 5.000 0.187 Vel = 5.28
EL 0.0 1.245 0.0 55.000 38.555
to 150.0 0.0 0.0 0.0
X 20.02 0.0375 0.0 55.000 2.061 Vel = 5.28
X 5.00 1.025 Ball 3.037 2.000 40.616 Qa=5
to 150.0 0.0 3.038 0.0
Ml 25.02 0.1459 0.0 5.038 0.735 Vel = 9.73
Ml 0.0 1.025 0.0 1.000 41.351
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 25.02 0.1460 0.0 1.000 0.146 VeI= 9.73
M2 0.0 0.995 T 5.841 35.000 45.497
to 150.0 0.0 5.841 0.0
CM 25.02 0.1686 0.0 40.841 6.887 Vel = 10.32
CM 0.0 7.98 F 13.591 331.000 52.384
to 150.0 T 52.855 66.447 0.0
100 25.02 0.0 0.0 397.447 0.003 Vel = 0.16
100 0.0 9.79 F 14.844 137.000 52.387
to 150.0 T 67.474 82.319 0.0
101 25.02 0.0 0.0 219.319 0.0 VeI= 0.11
101 0.0 6.16 E 22.818 10.000 52.387
to 150.0 0.0 22.818 7.363
SRC 25.02 0.0 0.0 32.818 0.001 Vel = 0.27
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams 'I.
NP Mechanical Page 7
12 PACIFIC Date 9/11/18
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv ******* Notes
Point at Pt/Ft Eqv. Ln. Total Pt Pn
0.0
25.02 59.751 K Factor = 3.24
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
t*OIc5
Bulletin 006 Rev. I
Model RFC30 (SIN RA0611)
® Model RFC43 (SIN RA061 2) Reli a b U e Model RFC49 (SIN RA061 6)
Residential Flat Concealed
Sprinklers
C
CD
:
0 0 C,
CD
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft2 with
low GPM requirements.
Features
Very low water flow requirements.
Cover plate attachment (Plain or Perforated)
with ½" (13mm) Total adjustment.
Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
Smooth aesthetic ceiling profile.
Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ
from standard sprinklers primarily in their response time
and water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has
demonstrated, in fire testing, an ability for controlling
residential fires, and thereby providing significant evacu-
ation time for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and 1/2" (13mm) of cover adjustment for ease
of installation. The small diameter cover plate is easily
main uover i-late
Perforated Cover Plate
and positively attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an
automatic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residen-
tial Sprinklers to be installed in the residential portions
of any occupancy in accordance with NFPA 13, 13R, &
13D.
The RFC30, RFC43 and RFC49 can reduce the need
for precise cutting of drop nipples. The threaded cover
plate assembly can be adjusted without tools to fit ac-
curately against the ceiling. The fire protection system
need not be shut down to adjust or remove the cover
plate assembly.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application and Installation
The RFC30, RFC43 and RFC49, for residential instal-
lations, use a 165°F (74°C) fusible solder link in a tun-
ing fork style sprinkler frame with a drop-down deflector.
This assembly is recessed into the ceiling and concealed
by a flat cover plate. The cover plate is attached to the
skirt, using 135°F (57°C) ordinary temperature classifica-
tion solder. When the ceiling temperature rises, the solder
holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
inside to ceiling temperature. The subsequent operation
of the solder link opens the waterway and causes the de-
flector to drop into position to distribute the discharging
water in a hemispherical pattern below the sprinkler de-
flector. Any adjustment of thread engagement between
the cover plate and cup will assure that the drop-down
deflector is properly located below the ceiling. The resi-
dential distribution pattern contains a finer droplet size
than a standard sprinkler, and the pattern produces sig-
nificantly higher wall wetting.
After a 21/8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler/cup assembly and around the hexago-
nal body of the sprinkler frame. The Wrench must bottom
out against the cup in order to ensure proper, safe instal-
lation. The sprinkler is then tightened into the pipe fitting.
When inserting or removing the wrench from the sprin-
kler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL
RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 135°F RATED COV-
ERS.
Note: A leak tight 1/2" NPT (131/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1/2" (13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option,
the cover assembly is pushed onto the cup and final ad-
justment is made by turning the cover clockwise until the
skirt flange makes full contact with the ceiling. Cover re-
moval requires turning in the counter-clockwise direction.
In ceilings that have a plenum space above the
sprinkler, the plenum space may have neutral or neg-
ative pressurization but must not be positively pres-
surized. Inspect all sprinklers after installation to en-
sure that the gap between the cover plate and ceiling
and the 4 slots in the cup are all open and free from
any air flow impediment.
Model Thread Nominal Sprinkler CCP Assembly Max.
Ambient K Max.
(SIN) Size Orifice Temp Rating Temp. Rating Temp. Factor Pressure
Inch (mm) Inch (mm) psi (bar) OF °C OF °C OF °C
RFC 30
(RA0611) 1/2" (15) 21/& (8,2) 165 74 135 57 100 38 3.0 (43.2) 175 (12)
RFC43 ½"(15) 3h(10) 165 74 (RA0612)
135 57 100 38 4.3(62) 175 (12)
RFC 49
(RA0616) 1/2"(15) '/16(11) 165 74 135 57 100 38 4.9 (70.6) 175 (12)
Note: 1 bar = 100 Kpa
RFC 30
Ordinary Temp. Rating Max. Coverage Max. Spacing (165°F1740C) Top of Deflector Installation Minimum
area
FtxFt(mxm) Ft (m) to Ceiling
Inch (mm) Type Spacing
Ft (m) Flow Fl Pressure
GPM (L/min) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 9(34,1) 9.0(0,62) Smooth Ceilings ½ to 1(13 to 25.4)
Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2.4)
14 x 14 (4,3 x 4,3) 14(4.3) 10(37,8) 11.0 (0,76) 13 installed in beams 1/2 to 1(13 to 25.4)
For Ceiling types refer to NEPA 13, 13R or 13D
2.
RFC 43
Ordinary Temp. Rating Max. Coverage Max. Spacing (165°F174°C) Top of Deflector Installation Minimum
area
FtxFt(mxm) Ft (m) to Ceiling
Inch (mm) Type Spacing
Ft (m) Flow Pressure
GPM (L/min) PSI (bar)
12x 12(3,6x3,6) 12(3,6) 12(4,5) 7.8 (0,54)
Smooth Ceilings Y2 to 1(13 to 25.4)
14 x 14(4,3 x 4,3) 14(4,3) 13(49) 9.1 (0,63)
16 x 16(4,9 x 4,9) 16(4.9) 13(49) 9.1 (0,63) Beamed Ceilings per NFPA 1313, 13R or
13 installed in beams ½ to 1(13 to 25.4)
Concealed 8(2.4)
18x 18(5,5x5,5) 18(5,5) 18(68) 17.5 (1,21)
20x20(6,1 x6,1) 20(6,1) 21(79) 23.8(1,64)
For Ceiling types refer to NFPA 13, 13R or 13D
RFC49
Max. Coverage Ordinary Temp. Rating Top of Deflector Minimum
area Max. Spacing (165- 40c)
to Ceiling Installation Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) T ype Ft (m) GPM (L/min) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0 (0,48)
Smooth Ceilings ½ to 1(13 to 25.4)
14 x 14 (4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48)
16 x 16 (4,9 x 4,9) 16(4,9) 13(49) 7.0 (0,48) Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams ½ to 1(13 to 25.4)
Concealed 8(2.4)
18 x 18(5,5 x 5,5) 18(5,5) 17(64,3) 12.0 (0,83)
20x20(6,1 x6,1) 20(6,1) 20(75,73) 16.7(1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprin-
klers should be inspected and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler cover plate as-
sembly which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used to minimize the potential for
damage to sprinklers that would cause improper opera-
tion or non-operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft2. Sprinkler frame and deflector
shall be of bronze frame construction having a ½" NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon-coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler K-
factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6)
having a 3/8" and /16" orifice. Temperature rating
shall be Ordinary 165°F (74°C); cover plate temperature
rating to be 135°F (570C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a ½" cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop-down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty - specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA061 1
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
3.
Ordering Information
Specify:
Sprinkler Model
Cover Plate Finish
Thread-On or
Push-On Feature
Cover Plate Finishes'
Standard Finishes
Chrome
White Paint
Special Application
Finishes(')
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
x 1/2 REDXINO lEroRaaowfl
(66mmJ
4 [58.42mm] DL4 HOLE IN CEIUNO
CUP
- 2 (50.8mm) MAX
FACE OF F1TI7NO
' (12 70mm1 M4) \ s. TO FACE OF CEiLiNG
COADJUS7MUff "\\ " DIMes,
I/2Ø2.7Omm] MIN. 7V j110i/
_______ . 1 Ma.
DROPPED DEFLECTOR FRMF
CEiLING TO cEJu ! (4.96mm)
21mml DA ASSEMBLY
SPRINKLER
COVER PLATE: 1/2" (12.7mm] ADJUSTMEN
to
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the united States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
(800) 431-1588 Sales Offices Paper Reliabk (800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 11/14 P/N 9999970261
D
F1 Res 3O,49,58&76 F1 Res 30,49,58 & 76
Recessed Pendent/ Fl Recessed Pendent/ P
Fl Res 44SWC Fl Res 40 Recessed
HSW/F2
Fl Res 44&58
Recessed HSW/F2
The low flow Fl Res sprinklers are specially
engineered for fast thermal response to meet the
sensitive fire protection application needs of the latest
residential market standards (UL 1626 Standard). Upon
fire conditions, rising heat causes a sprinkler's
heat-sensitive glass-bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly
distributing the discharged water to control a fire.
Technical Data:
Thermal Sensor: Nominal 3mm glass-bulb
Sprinkler Frame: Brass Casting
Sprinklers' Pressure Rating: 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size: ½" NPT (R1/2)
K-Factor: 3.0 (Actual) - Fl Res 30 Pendent Sprinkler
4.9 (Actual) - Fl Res 49 Pendent Sprinkler
5.8 (Actual) - Fl Res 58 Pendent & HSW Sprinkler
7.6 (Actual) - Fl Res 76 Pendent Sprinkler
4.4 (Actual) - Fl Res 44 HSW Spnkler
4.0 (Actual) - Fl Res 40 HSW Spnkler
Density: Minimum 0.05 gpm/ft2
Application
Model Fl Res Sprinklers are used for Residential Fire
Protection according to UL 1626 Standard*. Be sure that orifice size, temperature rating, deflector style and
sprinkler type are in accordance with the latest
published standards of The National Fire Protection
Association or the approving authority having
jurisdiction.
103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 135 Rev.G ____ CO
® Model Fl
Residential Sprinklers for - I,a Designe Density of .05 gpm/ft2 ()
(71
CD
0
Model Fl Res Sprinklers engineered for the lowest flows
to meet the minimum design density of .05 gpm1ft2
Types:
F1 Res 30Pendent
Fl Res 30 Recessed Pendent/F2
Fl Res 30 Recessed Pendent/FP
Fl Res 49 Pendent
Fl Res 49 Recessed Pendent/F1
Fl Res 49 Recessed Pendent/FP
Fl Res 58 Pendent
Fl Res 58 Recessed Pendent/F1
Fl Res 58 Recessed Pendent/FP
Fl Res 76 Pendent
Fl Res 76 Recessed Pendent/F1
Fl Res 76 Recessed Pendent/FP
Fl Res 30 CCP Pendent
Fl Res 49 CCP Pendent
Fl Res 58 CCP Pendent
Fl Res 76 CCP Pendent
Fl Res 44 HSW
Fl Res 44 Recessed HSW/F2
Fl Res 58 HSW
Fl Res 58 HSW Recessed HSW/F2
F1 Res 44SWC
Fl Res 40 HSW
Fl Res 40 Recessed HSW/F2
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus) I 2. NYC MEA 258-93-E
Slope Ceiling Approvals: Refer to Bulletin 035
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the
Model Fl Res 49 & 58 Pendent Sprinklers
Product Description
Model Fl Res Pendent sprinklers (Figs. 1, 2,3, &4) are fast response sprinklers combining excellent durability
high sensitivity glass-bulb and low profile decorative
design. The Fl Res Horizontal Sidewall sprinklers (Figs
5,6 & 7) are equally attractive when above ceiling piping
cannot be used.
The 3mm glass-bulb pendent sprinklers permit the
efficient use of residential water supplies for sprinkle i
coverage in residential fire protection design.
The Reliable Automatic Sprinkler Co., Inc.,
2 I/4 Z OL
_____•_ .- ts,.2_
(4&tnm,J II I
N
AM cam Lm 80DOW am
#vnm 10
cw
r 1z7
I±L t ARWTMW
vrj
L35F2
F5.v'Li
Installation
Models Fl Res sprinklers are to be installed as
shown. Model Fl, F2 and FP Escutcheons, illustrated
herewith, are the only recessed escutcheons to be used
with Model Fl Res sprinklers. Use of any other
recessed escutcheon will void all approvals and
warranties. For installing Model Fl Res Pendent
sprinklers use only the Model D sprinkler Wrench; for
installing Models Fl Res Recessed Pendent, CCP &
Model Fl Res 30,49,58 & 76 Pendent
SWC sprinklers use only the Model GFR2 sprinkler
wrench; for installing Model Fl Res Recessed HSW
sprinklers use only the Model GFR2 Sprinkler Wrench.
Use of wrenches other than those specified may
damage these sprinklers. Install Fl Res 44 and 40 HSW
with a ceiling to deflector distance of 411 - 12". Flow arrow
on deflector must point away from near wall and "Top"
marking must face ceiling.
Model Fl Res 30 Recessed
Pendent/F2
Model Fl Res 49,58 & 76
Recessed Pendent I Fl
1 escutcheon, 3/411 (19mm) adjustmer
Fig. 1 Fig. 2
Escutcheon*, Fl or F2, Data:
Type Adjustment "A" Face of fitting to
ceiling Inch (mm) Inch (mm) th (mm)
Fl 3/4(19.0) Min.= %" (19.1) Max.=1%" (38.1)
Y. - 15/6 (4.7-24.0)
F2 X (12.7) Min.= 15/6 (23.8)
Max. =1Y" (38. 1) /6 - % (4.7- 17.4)
* Note: Escutcheons Fl or F2 may be used with
Model Fl Res 49, 58 & 76 Recessed Pendent
2.
Technical Data: Fl Res 30 Pendent and Recessed Pendent
Nominal Sprinkler Max Max; Actual Sprinkler Thread Orifice Temp. An K Length
Size Inch Rating psi Temp. Factor Inch
OF I oc °F I (mm) (bar) (mm)
/2(R,)
11 NPT 2164' (8.2) 155
175
I I 68
79 175 (12) 100 38 3.0 2.25(57)
Deflector - to - ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sprinkler Flow Pressure Sprinkler
Spacing m (L gppm) psi (bar) Identification
ft (m) Number (SIN)
12 x 12 (3.6x3.6) 8(30.3) 7.0 (0.48) R3511 11(0.76) 14 x 14 (4.3x4.3) 10(37.8)
Technical Data: Fl Res 49 Pendent and Recessed Pendent
Nominal Sprinkler MwL Max. Actual r
SLength Thread Orifice Temp. Pressure Ambient K She Inch Rating psi Temp. i:acto. Inch
°F I °c °F IOc (mm) (bar)
Y 2R 'IjI (11) 155
1751
68 175(12) 100
1501
38 66 4.9 2.25(57)
Deflector - to - ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sprinkler
Spacing
ft (m) _
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 13(49) 7.0(0.48)
R3516
16.7(1.14)
14 x 14 (4.3x4.3) 13 (49) 7.0(0.48)
16 x 16 (4.9x4.9) 13(49) 7.0(0.48)
18 x 18 (5.5x5.5) 17(64.3) 12.0(0.83)
20 x 20(6.1x6.1) 20 (75.7)
*Deflector - to - ceiling
Maximum 4" (100mm) to 8" (203mm)
Max. Sprinkler
Spacing
ft (m) _
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65)
R3516
20.2(l.4)
14 x 14 (4.3x4.3) 16(60.5) 10.6(0.73)
16 x 16 (4.9x4.9) 17(64.3) 12.0(0.83)
18 x 18 (5.5x5.5) 19 (72) 15.0 (1.0)
20 x 20(6. 1x6. 1) 22(83.2)
*Note: The Fl Res 49 pendent and recessed pendent
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria:
Maximum beam depth = 7" (178mm)
Beam spacing at or greater than 7.5 ft. (2.3m) on center.
Technical Data: Fl Res 58 Pendent and Recessed Pendent
Nominal Sprinkler MaL Max Sprinkler Thread Orifice Temp. Pressure Ambient K Length Size Inch Rating psi Temp. Factor Inch
OF I ° OF I _______ (mm) (bar) (mm)
½" NPT
(R½) 4' (13) 155
175
68
I 79 175 (12) 100
150
38
I 66 1 5.8 2.25 (57)
Max. Sprinkler
Spacing
ft (m)
Row
gpm (Lpm)
Pressure
psi (bar)
Ceiling -to-
Deftector
Inch (mm)
Sprinkler
Identification
Number (SIN)
12x 12(3.6x3.6) 16(61) 7.6 (0.53)
1-4
(25-100) R3513
14 x 14 (4.3x4.3) 16(61) 7.6(0.53)
16 x 16 (4.9x4.9) 16(61) 7.6(0.53)
18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75)
20 x 20 (6.1x6.1) 22(83.3) 14.4(1.0)
3.
Technical Data: Fl Res 76 Pendent and Recessed Pendent
Norninal Slliftr Max Max S*Jder
Thread Orifice Temp Pessue AL1 K Length
Size Inch Fkiq psi Ten Facr kth
°F I °c (mm) (bar) (mm)
3/4" NPT
(R%)
1%2'
(13.5)
155 1751 68
79
_______
175(12) 100
150
I 38
I 66 T6 2.25(57)
Max. Sprinkler Spacing
ft (m)
flow gpm (Lpm) Pressure psi (bar)
Sprinkler
Identification Number (SIN)
12 x 12 (3.6x3.6) 21 7.6(0.53)
R7618
9.2(0.63)
14 x 14 (4.3x4.3) 21 7.6 (0.53)
16 x 16 (4.9x4.9) 21 7.6 (0.53)
18 x 18 (5.54.5) 21 7.6 (0.53)
20 x 20 (6. 1 x6. 1) 23
Model Fl Res 30,49,58 & 76
ienaent
Model Fl Res 30,49,58 & 76
Recessed Pendent I FP
FP push-on/thread-off
escutcheon
2 5/8" (66.7mm] 0/A.
2 5/76" DLA. - HOLE IN CEILING
[58.7mm]
CUP
I
7'xl/2" REDUCER
CUP
CEILING
7 7/4" [37.5mm]
1 11A -. MAX. PACE OP FliT/NC
TO PACE OP CEILING F--.—.. DIMENSION
A ____
COVER ADJUSTMENT i "8"
L 3 5/16" 0/A.
135FG040 [84.1mm]
Fl RES 30, 49. 58 & 76 CCP PEND.
Fig.3
NOTE: The Fl Res 76 will use a 1" x 3/4" reducer.
r2 2 5/I6 t
Cw
fimxcm
cwNc :. , 4lDFUENSION
'A FP ADAWMW
Fig. 4
4.
Technical Data: Fl Res 30 CCP Pendent and Recessed Pendent I FP
Nominal Sp.iilder CCP
Max MOX_
__
__
Thread Orifice Taix Tetyi Pressure AL,i K Length
Size Inch ii,g Flailing psi Ga) Ten Faor Inch
(mm) ( °F ° C T IOC
NPT 2j/°(82) 155168
I 1351 I
57 175 (12) 1001
I
38 3.0
(R½)
Max. Sprinkler I
I Flow
I
Pressure Sprinkler
Spacing
ft (m) gpm (Lpm) I psi (bar) Identification
Number (SIN)
12 x 12 (3.6x3.6) I 8(30.3) I 7.0 (0.48) R3511 I_13.4_(0.92) 14 x_14 (4.3x4.3)_I_11(41.6)
Technical Data: Fl Res 49 CCP Pendent and Recessed Pendent I FP
Nominal Spñlde cc Max. Spñlde
Thread Orifice Ten!1 Ti Anti1 K Length
Size Inch Ffrrg ps Temp. Farcr Inch
(mm) ,I°c
NPT X6 (11) T15568
¶1CC
½"
1351 49
(R1/2)
I
57 175(12) iool 38
I 2.25
I I
Max. Sprinkler
Spacing
ft (m)
How
gpm (Lpm)
________
Pressure
psi (bar)
________
Sprinkler
Identification
Nibei (SIN) ____
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)
R3516
1
14 x 14 (4.3x4.3) 13 (49) 7.0(0.48)
16 x 16 (4.9x4.9) 14(53) 8.2(0.56)
18 x 18 (5.5x5.5) 1 18(68.1) 1 13.5(0.93)
20x20(6.1x6.1) 1 20(75.7) 1 16.7(1.14)
CCP Options Data:
Cover Adjustment CCP Height Inch (mm) Inch (mm)
)4(12.7) 15/(24)
'X6(7.9) /4 (19)
FP Data "A":
FP Position Inch (mm)
Max. Recessed X6(11)
Mm. Recessed 15/ (24) 1
Note: Sprinklers shown in Hg. 3 and Hg. 4 are not
suitable for installation in ceilings which have
positive pressure in the space above.
Technical Data: Fl Res 58 CCP Pendent and Recessed PendentlFP
No minal rfrder cc Max Max. __
Thread
Size Orifice Tenç Assently Aessue Mtkd K Length
Inch ROM PAUM
Ten psi Teni Far Inch
(mm) (bar) () °F I 'C 'F I'c
2) 1 1/2" NPT (gy (13) 15568 1351 57 175(12) 10038 5 2.25(57)
Max. Sprinkler
Spacing
ft (m)
How
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Nunter (SIN) ____ 12x12(3.6x3.6) 16(61) 7.6(0.53)
R3513
1. 14.4(1.0)
14 x 14 (4.3x4.3)- 16(61) 7.6(0.53)
16 x 16(4.9x4.9) 16(61) 7.6(0.53)
18 x 18 (5.5x5.5)1 19(72) 1 10.8 (0.75)
20x20(6.1x6.1) 1 22(83.3)
Technical Data: Fl Res 76 CCP Pendent and Recessed Pendent/FP
Nominal spnlder CCP Max. Max.
Thread
Size
Orifice
Inch
Ten!i
R*rg
Assenty
Tenhi
_plalirm _____
Pvessue
psi
Antierl
Teihi
_____
K
Far
Wder
Length
hch(nin) (mm) (bar) 'F I c °F 'C
3/4" NPT
(R3/4)
l%2
(13.5)
155
175
68
79 _____
175(12) 100138 150166 76 2.25(57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN) ____ 12 x 12 (3.6x3.6) 21 7.6(0.53)
R7618
14 x 14 (4.3x4.3) 21 7.6 (0.53)
16 x 16 (4.9x4.9) 21 7.6(0.53)
18 x 18 (5.5x5.5) 22 8,4(0-5 8)
20 x 20 (6.1x6.1) 25 10.8(0.74)
5.
Escutcheon, F2, Data:
Type I Adjustment Face of Fitting I to wall I Inch (mm) Inch (mm) I
F2 I X(13) X6-1Y1,(47-174)I
Model Fl Res 44 & 58 HSW Model Fl Res 44&58
Recessed HSW/F2
F2 escutcheon, )" (13
adjustment
Technical Data: Fl Res 44 HSW & HSW/F2
Nomin IiIder Max Iy nder
Ttnad Orifice TØYi Pssue Mt11 K Length
She Inch FIIg psi TOMFacr Inch
¶ icC TI cc (mm) (bar) (mm)
W'NPT 3/0 (10) 155
1751
___ I 68
79 175(12) 100 1501 38
66 4.4 2.45 (62)
MaSpnnlder
ft
awy
Ceiling
Inch (mm)
Spiinkter Temp.
Rating
OF (°C)
IdentificationpDeflector
Row
gpm
(1-131111)
Pressure
psi QW)
Sprinkler
Number (SI
12 x 12 (3.6x3.6)
4-6
(101-152)
155(68) 175(79) 12(45.4) 7.5(0.52)
R3531
127.4(1.89)
14 x 14 (4.3x4.3) 155(68) 175(79) 14(53.0) 10.2(0.71)
16 x 16 (4.9x4.9) 155(68) 175(79) 16(60.6) 13.3(0.92)
16 x 18 (4.9x5.5) 155(68) 175(79) 18(68.1) 16.8(1.16)
18x 18(5.5x5.5) 155(68) 175(79) 19(72.0) 18.7(1.29)
16 x 20 (4.9x6.1) 155 (68) 175(79) 23 (87.1) 27.4(1.89)
12 x 12 (3.6x3.6)
6-12
(152-305)
155(68) 175(79) 14(53.0) 10.2(0.71)
14 x 14 (4.3x4.3) 155(68) 175(79) 16(60.6) 13.3(0.92)
16 x 16 (4.9x4.9) 155(68) 175 (79) 17(64.4) 15.0 (1 .04)
16 x 18 (4.9x5.5) 155(68) 175 (79) 20 (75.7) 20.7
16 x 20(4.9x6.1) 155(68) 175(79) 23(87.1)
Escutcheon. F2. Data:
T Adjustment I Face of Fitting I
I towall I Inch (mm) Inch (mm) I
F2 (13) I3X6-%(4.7-17.4)I
Technical Data: Fl Res 58 HSW & HSWIF2
Nominal *Wder Max. Max. SpñiId
meri Orifice Teni Psssue Aii1 K Lengiji
Size Inch R pa Tenp.Pactor Inch
OF I cc OF I cc (mm) (bar) (mm)
Y2"(13) 1551
1751
68
79 175(12) 100
150
I 38
I 66 5.8 2.45 (62)
Max. Sprinkler
Spacing
ft (m)
Awl
ceiling
Deflector
Inch (mm)
Sprin
R
kl
li
er Temp.
Rating
F ) ° (°C
Flow
gpm
(1pm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
155(68) 175 (79) 16(60.6) 7.6(0.53)
R3533
14 x 14 (4.3x4.3) 155(68) 175(79) 18(68.2) 9.7(0.67)
16 x 16 (4.9x4.9) 155(68) 175(79) 21(79.5) 13.2(0.91)
16 x 18(4.9x5.5) 155(68) 175(79) 25(94.7) 18.6 (1 .28)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 29(109.8) 25(1.73)
12x 12(3.6x3.6)
6-12
(152-305)
155(68) 175(79) 22(83.3) 14.4(l.0)
28.6(l.97)
14 x 14(4.3x4.3) 155(68) 175 79) 22(83.3) 14.4 (1.0)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 26(98.4) 20.1 (1.39)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 31(117.4)
Model Fl Res 44 SWC
Recommended I
I WolIMob 25/76
2 5/8" (5&74mm1 __.. 3 5/7 • (66.68mm) 010
Dft
. (84.umm)
ah
WN COLLAR TIGHT AGAINST SPRINKLER I - I 21/32" WRENCH 8O55 (42.07mm)
UNW?_ø. .._ 1/2"[12.7omm]
Adjustment
Fl RES 44 SWC
4 to 72"
(I01.60mn, To
___________ l 7/4" (31.75mm) Mozimum -. - 304.80mm)
Pace Of Rtd.
Wall Dtmenson PUSH ON COlRl7 -.E.To / IVAN TO ADJUST UNTIL J now AGAINST WALL.
I" X 7/2" Reducer
Fig. 5
Technical Data: Fl Res 44 SWC
Thesd
Nominal
Orifice
ri1der CouerTeni Terrill K
Nhx Max. SIAAW
Langlh
She Inch _____ ____ psi Factr Inch
CF I cc OF I CF
_____
cc (mm) (bar) (mm)
½"NPT
(R1/2) /8 "(10) 155 68 135 57 175(12) 100 38 4.4 2.45(62)
MaL Sprinkler
Spacing
ft (m)
Ceiling -to-
Deflector
Inch (mm)
R Flow
gpm
(Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
13(49.2) 8.7(0.60)
R3531
20.7(l. )
14x 14(4.3x4.3) 14 (53.0) 10.2 (0.71)
16x 16 (4.9x4.9) 17(64.3) 15.0(1.1)
16x 18(4.9x5.5) 19 (71.8) 18.7(l.13)
16 x 20 (4.9x6.1) 23(87.1) 27.4(l.89)
12 x 12 (3.6x3.6)
6-12
(152305)
14(52.9) 10.2 (0.71)
14 x 14 (4.3x4.3) 15(56.7) 11.7(0.81)
16 x 16 (4.9x4.9) 18(68.1) 16.8(l.16)
16 x 18 (4.9x5.5) 20(75.6)
2. Model Fl Res 40 Recessed
HSW/F2
Escutcheon. F2. Data:
Type Adjustment I Face of Fitting
I to wall I Inch (mm) Inch (mm) I
F2 %(13) l/6-%(4.7 -17.4)
F2 escutcheon, " (13m
adjustment
WALL DIMENSION
(31.8mm) I
FACE OF F7T?NG TO
I 1/4 MIN.
2 1/4 HOLE 014. I/8 CEILING TO [57.2--](3.2mm) DEFLECTOR
1 X I/2 DIMENSION REDUCER -p
2 27/32 ON
(72.2mm)
135FG05
TURN COLLAR UNTIL -
TIGHT AGAINST SPRINKLER
WRENCH BOSS. 9 L.... 7/2 (73mm)
ADJUSTMENT
Fl RES 58. 44 & 40 HSW/F2
Fig. 6 Fig. 7
Technical Data: Fl Res 40 HSW & HSW/F2
Nominal iIder Nlax _
lhsad Orifice Teni Plesmre Ambient K Lngih
She Inch Fiig psi Tom Faor Inch
OF I cc OF I cc (mm) (bar) (mm)
'/2"NPT /°(10) 155
175
68
I 79 175(12) 100
150 38
I 66 4.0 2.45 (62)
Max. Sprinkler "A"
ceiling -to- Sprinkler Temp. Flow Pressure Sprinkler
Spacing Deflector Rating gpm psi 0 Identification
ft (m) Inch (mm) OF (°C) (Lpm) Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
155(68) 175 (79) 13(49.0) 10.6(0.73)
14 x 14 (4.3x4.3) 155(68) 175(79). 16 (60.5) 16.0 (1.10)
16 x 16 (4.9x4.9)- 155 (68) ______ 17(64.3) 18.1(1.24)
16 x 16 (4.9x4.9)- 175(79) 18(68.1) 20.2(1.39)
16 x 18(4.9x5.5) 155(68) 175 (79) 20 (75.7) 25.0 (1.72) R3538
25.0(1.72)
18 x 18 (5.5x5.5) 155(68) 1 175(79) 22(83.3) 30.2(2.08)
16 x 20 (4.9x6.1) 155(68) 175 (79) 23(87.0) 33.1 (2.28)
12 x 12 (3.6x3.6)
6-12
(152-305)
155(68) 175(79) 13 (49.0) 10.6(0.73)
14 x 14(4.3x4.3) 155(68) 175 (79) 17 (64.3) 18.1 (1.24)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 20(75.7)
Finishes"
Standard Finishes
Sprinkler Fl, F2, FP
Escutcheons
Cover Plates
Bronze Brass White Painted
Chrome Plated Bright Chrome Plated Chrome
White Polyester White Painted Coated I
Special Application Finishes
Sprinkler Fl, F2,
Escutcheons
Cover Plates
Bright Brass Bright Brass Bright Brass
Black Plated Black Plated Black Plated
Black Paint Black Paint Black Paint
Off White Off White Off White
Satin Chrome Satin Chrome Satin Chrome
Other finishes and colors are available on special order.
Consult factory for details.
Note: Paint or any other coating applied over the factory finish will
void all approvals and warranties.
Maintenance
Model Fl Res 30, 49, Fl Res 58, Fl Res 76, Fl Res 44
and Fl Res 40 Sprinklers should be inspected quarterly,
and the sprinkler system maintained in accordance with
NFPA 25, 13, 13D, and 13R. Do not Clean sprinkler with
soap and water, Ammonia or any other Cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming.
Remove any sprinkler which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers should remain in the original Cartons
and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper
operation or non-operation.
Model Fl Res 30,49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent
sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch from [4/12] to
[8/12], the sprinklers shall be listed for such use.
Deflector-to-ceiling distance listing shall be l"to 8"
maximum. Sprinkler frame and deflector shall be of bronze
frame construction having a ½" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville spring
washer with top-loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of [155°F (68°C)] [175°F (79°C)].
Sprinklers shall have a nominal K-factor of 3.0,4.9 and 5.8.
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish- specify]. Residential pendent
sprinklers shall be Reliable Model Fl Res 30,49 & 58, SIN
R3511, R3516 & R3513 (Bulletin 135).
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Temperature Rating
Sprinkler Finish
Escutcheon Finish
Cover Plate Finish
Model Fl Res 49 & 58 Recessed Pendent/F1,
Model Fl Res 30,49 & 58 Recessed Pendent/F2,
Model Fl Res 30,49 & 58 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/ff over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's installation
guidelines and the applicable installation standard. Where
pendent residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance
listing shall be 1" to 8" maximum. Sprinkler frame and
deflector shall be of bronze frame construction having a ½"
NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer with top-loaded
extruded or cold head cup with 3 mm glass bulb containing
no plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (790C)]. Sprinklers shall have a nominal
K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish- specify].
Recessed escutcheon assembly shall be a steel, two-piece
escutcheon [with 1/2" adjustment (Model F2)] [with 3/4"
adjustment (Model Fl)] [of push-on and thread off design
with ½" adjustment (Model FP)]. Standard finish shall be
[brass][bright chrome] [white painted]. Residential
recessed pendent sprinklers shall be Reliable [Model Fl
Res 3.0, 49 & 58 Recessed Pendent/F1] [Model Fl Res 30,
49 & 58 Recessed Pendent/F2] [Model Fl Res 30,49 & 58
Recessed Pendent/FP] SIN R3511, R3516 & R3513
(Bulletin 135).
10.
Model Fl Res 30,49 & 58 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch from [4/12]
to [8/12], the sprinklers shall be listed for such use.
Sprinkler frame and deflector shall be of bronze frame
construction having a ½" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville
spring washer with top-loaded extruded or cold head
cup with 3 m glass bulb containing no plastic parts, and
having a temperature rating of 155°F (680C). Cover plate
assembly shall consist of a brass cover plate and copper
alloy retainer flange. Method of attaching the cover plate
to the sprinkler cup shall be a push-on and thread-off
design allowing a ½" cover plate adjustment. Cover
plate temperature rating shall be 135°F (570C). A plastic
protective cap shall be provided and factory installed
inside the sprinkler cup to protect the sprinkler from
damage, which could occur during construction before
the cover plate is installed. Standard cover plate finish:
[White] [Custom Color- specify]. ]. Concealed pendent
sprinklers shall be Reliable Model Fl Res 30, 49 & 58
CCP, SIN R3511, R3516 & R3513 (Bulletin 135).
Model Fl RES 40 and Fl Res 44 Horizontal Sidewall
Residential Sprinkler Specifications
Model Fl Res 40 Horizontal Sidewall Sprinkler
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential horizontal
sidewall sprinklers engineere1 to provide a minimum
design density of 0.05 gpm/ft over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Where horizontal sidewall
residential sprinklers are installed under sloped ceilings
having a pitch from [4/12] to [8/12], the sprinklers shall be
listed for such use. Sprinkler frame and deflector shall be
of bronze frame construction having a ½" NPT thread.
Water seal assembly shall consist of a Teflon-coated
Belleville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (680C)] [175°F (790C)]. Sprinklers shall have a nominal K-factor of
4.0 (57.1). Standard finish: [Bronze] [Chrome-plated]
[White Polyester] [Special finish- specify]. Residential
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 40, SIN R3538 (Bulletin 135).
Model Fl Res 40 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model Fl Res 40 horizontal
sidewall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½" adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish- specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 40/F2, SIN R3538 (Bulletin 135).
Model Fl Res 44 Horizontal Sidewall Sprinkler
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the
applicable installation standard. Where horizontal
sidewall residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the
sprinklers shall be listed for such use. Sprinkler frame
and deflector shall be of bronze frame construction
having a ½" NPT thread. Water seal assembly shall
consist of a Teflon-coated Belleville spring washer with
top-loaded extruded or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a
temperature rating of [155°F (680C)] [175°F (790C)]. Sprinklers shall have a nominal K-factor of 4.4 (62.8).
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish- specify]. Residential
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 44, SIN R3531 (Bulletin 135).
Model Fl Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model Fl Res 44 horizontal
sidewall sprinkler with the following modifications:
Replace "horizontal sidewall sprinkler" with "recessed
horizontal sprinkler." Add: Recessed escutcheon
assembly shall be a steel, two-piece escutcheon with ½"
adjustment (Model 172). Standard finish shall be
[brass][bright chrome] [white painted] [Special finish-
specify]. Residential recessed horizontal sidewall
sprinklers shall be Reliable Model Fl Res 44/F2, SIN
R3531 (Bulletin 135).
11.
Model Fl Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall be
of bronze frame construction having a 3/4" NPT thread.
Water seal assembly shall consist of a Teflon-coated
Belleville spring washer with machined or cold head cup
with 3 mm glass bulb containing no plastic parts, and
having a temperature rating of [155°F (680C)] [175°F
(791C)]. Sprinklers shall have a nominal K-factor of 7.6.
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish- specify]. Residential pendent
sprinklers shall be Reliable Model Fl Res 76, SIN R7618
(Bulletin 135).
Model Fl Res 76 Recessed Pendent/Fi,
Model Fl Res 76 Recessed Pendent/F2,
Model Fl Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpm/e over the listed
coverage area. Listed flows as specified by the
manufacturer's technical data sheets are to be used.
Residential sprinklers shall be installed in conformance
with the manufacturer's installation guidelines and the
applicable installation standard. Sprinkler frame and
deflector shall be of bronze frame construction having a
3%" NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer with machined or
cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (790C)]. Sprinklers shall have a nominal
K-factor of 7.6. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish-
specify]. Recessed escutcheon assembly shall be a
steel, two-piece escutcheon [with ½" adjustment (Model
172)] [with 3%" adjustment (Model Fl)] [of push-on and
thread off design with ½" adjustment (Model FP)].
Standard finish shall be [brass][bright chrome] [white
painted]. Residential recessed pendent sprinklers shall
be Reliable [Model Fl Res 76 Recessed Pendent/Fl]
[Model Fl Res 76 Recessed Pendent/F2] [Model Fl Res
76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model Fl Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gprn/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprinklers
shall be installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Sprinkler frame and deflector shall be of bronze
frame construction having a 3/4" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville spring
washer with machined or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a temperature
rating of 155°F (680C). Cover plate assembly shall consist
of a brass cover plate and copper alloy retainer flange.
Method of attaching the cover plate to the sprinkler cup
shall be a push-on and thread-off design allowing a ½"
cover plate adjustment. Cover plate temperature rating
shall be 135°F (570C). A plastic protective cap shall be
provided and factory installed inside the sprinkler cup to
protect the sprinkler from damage, which could occur
during construction before the cover plate is installed.
Standard cover plate finish: [White] [Custom Color-
specify]. ]. Concealed pendent sprinklers shall be Reliable
Model Fl Res 76 CCP, SIN R7618 (Bulletin 135).
The equipment presented in this bulletin is lobe installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances, whenever applicable.
Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable
sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices Recycled
(800) 848-6051 Sales Fax '41 Paper
(914) 829-2042 corporate Offices Revision lines indicate updated or new data.
www.reliabtesprinkler.com Internet Address EG. Printed in U.S.A. 06/08 P/N 9999970235
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
510
CPVC - STEEL - COPPER
HANGER
SIZE - 3/4" thru 3" pipe.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTING/APPROVAL -
,®an 203 - EX 4231, EX 2551
FUNCTION - To support horizontal piping - CPVC, Copper or Steel.
Hanger in listed mounting positions - Top, Bottom or Side.
Also, provides stability on vertical piping.
INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers
instructions on top, bottom or side of building element. Space by pipe type.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC pipe - #905 screw - no pre-drill.
3/4" - 3" Copper pipe - #905 screw - no pre-drill.
3/4" - 3" Steel pipe - 1/4"x1112" lag screw - no pre-drill.
in STEEL - mm. 18 GA.
3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 3" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 3" Steel pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
*C4 ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or banger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
2/08
Side View - For
Drawings Below
Hanger - Wood Stud Hanger - Metal Stud
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
511
SIDE MOUNT
CPVC - COPPER
HANGER
SIZE - 3/4" thni 2" pipe.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
203 - EX 4231, EX 2551
FUNCTION - Hanger on CPVC and Copper pipe.
INSTALLATION - Per NFPA 13,13R, 13D and CPVC
manufacturers instructions on top or bottom of beam.
Space by pipe type
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre-drill.
3/4" - 2" Copper pipe - #905 screw - no pre-drill.
in STEEL - mm. 18 GA.
3/4" - 2" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against she failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
2/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
513
CPVC — STEEL — COPPER
HANGER
SIZE - 3/4" thru 2" pipe.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
203 - EX 4231, EX 2551
FUNCTION - To support horizontal piping - CPVC, Copper or Steel.
Tab up = Hanger.
INSTALLATION - Per NFPA 13,13R and 13D on
side or top of beam. Space by pipe type.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre-drill.
3/4" - 2" Copper pipe - #905 screw - no pre-drill.
3/4" - 2" Steel pipe - 1/4"x1 1/2" lag screw - no pre-drill.
FEATURES
* Offset edge eliminates abrasion.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwill NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or told by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to Iota of business or profit, when non-AFCON products have been, or are used.
2/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
OFFSET CPVC HANGER
SIZE - 3/4" thru 3"pipe. -
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized..
LISTING/APPROVAL -
203 - EX 4231, EX 2551 e
PATENT - No. 6,648,278.
FUNCTION - 314"-2" Hanger/restrainer for horizontal CPVC, Copper or Steel pipe.
Listed hanger/restrainer in all 3 mounting positions, i.e. vertical surface and both top and
bottom of horizontal surface. Provides listed vertical/lateral restraint and prevents upward
movement of pipe that supplies a pendent sprinkler below a ceiling.
Size 2 'h" Hanger for horizontal CPVC pipe. Listed hanger in all 3 mounting positions.
i.e. vertical surface and both top and bottom of horizontal surface.
Size 3" Hanger for horizontal CPVC pipe in two mounting positions, side and bottom.
i.e. vertical surface and bottom of horizontal surface.
Stabilizes vertical piping by providing horizontal restraint.
INSTALLATION - Per NFPA 13,13R and 13D.
Space by pipe type. Install on wood, concrete or steel - See Drawings.
Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed
When #905 threads are exposed in wood, install #906 backing nut. 3/4'
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13
WOOD - 3/4" - 3" CPVC pipe - #905 screw- no pre-drill.
3/4" - 2" Copper pipe - #905 screw- no pre-drill.
3/4" - 2" Steel pipe - 1/4"x1 1/2" lag screw - no pre-drill.
Thru 5/8" gypsum board - 1/4" x 2" lag screw.
STEEL- mm. 18 GA. - 3/4" -3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Steel pipe - 1/4" or #14 Tek Screw.
CONCRETE: Required minimum load each fastener = 5(wt)+2501bs.
2
FEATURES
* 1 1/2" Offset - loose fit allows pipe to slide.
* 3/4" and 1" pipe size made with common center-line.
* Patented design for superior strength.
* Offset edge eliminates abrasion.
* AFCON#905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold separately.
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
6/08
'1W Part NUmber I Box Qty.
06-5tin"Ne
V5011-020 2
2-1/2" V5011-025 1
V5011-030 1
Tee
4%
Reducing Tee
Pipe
Manufactured for Viking SupplyNet by Viking Plastics, LLC (Huntsville, Alabama USA.)
'1W
3/4"
Part NUmber
34P1PE
Bag Qty.
240 It
1 1PIPE 150 ft
1-1/4" 114PIPE 105 ft
1-112" 112P1PE 75 ft
2P1PE 60 ft
2-1/2" 212PIPE 30 ft
3PIPE 15 ft
BlazeMaster® CPVC fittings are manufactured/supplied for Viking SupplyNet by NIBCO, Inc.
Standard Fittings
Size
3/4"x3/4"xl"
lIfl1UT
V5011 R-102
Box Qty
10
1"x3/4"x3/4" V5011 R-125 100
1"x3/4x1" V5011 R-126 10
1"x1"x3/4" V5011 R-131 100
1-1/4"x1"x3/4" V5011 R-157 5
1-1/4"xl"xl" V5011 R-158 25
1-1/4"xl"xl-1/4" V5011 R-159 5
1-1/4"x1-1/4"x3/4" V5011 R-167 25
1-1/4"xl-114"xl" V5011 R-168 25
1-1/4"xl-1/4"xl-1/2" V5011 R-169 5
1-112"x1-1/4"x3/4" V5011 R-201 5
1-1/2"x1-1/4"xl" V5011 R-202 5
1-1/2"xl-1/2"x314" V5011 R-210 25
1-1/2"x1-1/2"x1" V5011 R-211 25
'1W
R?Te'iii)
Part NUmber I Box Qty.
1-1/2x1-1/2"xl-1/4" V5011 R-212 5
1-1/2"xl-1/2"x2 V5011 R-213 5
2"x2"x3/4" V5011 R-248 2
2"x2"xl" V5011 R-249 10
2"x2"x1-114" V5011 R-250 2
2"x2"xl-1/2" V5011 R-251 2
2-1/2x2-112"xl" V5011 R-289 1
2-1/2"x2-1/2"xl-1/4" V5011 R-290 1
2-1/2"x2-1/2"xl-1/2" V5011 R-291 1
2-112"x2-1/2"x2" V5011 R-292 1
3"x3"xl-112" V5011 R-337 1
3x3"x2" V5011 R-338 1
3"x3"x2-1/2" V5011 R-339 1
wwwvikinggroupinc.com Refer to manufacturer's DESIGN AND INSTALLATION GUIDE for technical specifications and installation instructions.
Standard Fittings continued from Page 1
90° Elbow Size
3/4"
ThIittT
V5007-007
Box Qty.
250
V5007-010 100
1-1/4" V5007-012 25
1-112" V5007-015 25
V5007-020 10
Size Part NUmber I
9OEIb'6iiël)
Box Qty.
2-1/2" V5007-025 1
V5007-030 1
1" x 3/4" V500711-131 100
450 Elbow Size Pail NumberBox Qty.
3/4" V5006-007 250
1" V5006-010 100
1-1/4" V5006-012 5
1-1/2" V5006-015 5
'IN' Part Number I Box Qty.
45,lbiiIiiiTh1)
V5006-020 2
2-1/2" V5006-025 1
V5006-030 1
Cross
84
Size
3/4"
ImuT
V5035-007
.e.n'j
10
1" V5035-010 100
1-1/4" V5035-012 5
1-1/2" V5035-015 6
2" V5035-020 4
Size I •rt NUmber Iz,.iJJ € continueal
2-1/2" V5035-025 4
3" V5035-030 1
1 "xl "x3/4"x3/4" V503511-131 10
Tg1ImuT Box Qty. Coupling Size
3/4" V5001-007 250
1" V5001-010 100
1-1/4" V5001-012 25
1-1/2" V5001-015 25
IN' IBox i11 Reducing Coupling y.
1"x314" V5001 R-131 10
1-1/4" x 1" V5001 R-168 5 I • ] 1-112"x3/4" V5001 R-210 5
1-1/2"xl" V5001 R-211 5
IN' I Part Number I Box Qty.
ouglingl(continu
2" V5001-020 10
2-1/2" V5001-025 1
3" V5001-030 1
Size Part NUrriber I Box Qty.
I 1-1/2'x 1-1/4" ' V5001 R-212 ' 5
2"x I" V5001 R-249 2
2" x 1-1/2" V5001 R-251 2
Bushing I.] 'iN'
1"x3/4"
Part Writer
V5018-131
I!Xi111
100
1-114" x 3/4" V5018-167 25
1-1/4" x 1" V5018-168 25
1-1/2" x 3/4" V5018-210 5
1-1/2"x 1" V5018-211 25
1-1/2'x 1-1/4" V5018-212 25
2" x 3/4" V5018-248 2
2"x 1" V5018-249 2
'IN' Part NUmber I Box Qty.
x 1-1/4" V5018-250 2
2 x 1-112" V5018-251 2
2-1/2"x 1-114" V5018-290 1
2-1/2'x 1-1/2" V5018-291
2-112" x 2" V5018-292 1
3" x 2" V5018-338 1
x 2-1/2" V5018-339
'IN' Part Number I Box Qty.
V5017-020 2
2-1/2" V5017-025 1
V5017-030 1
www.vikinggroupinc.com
Sprinkler Head Adapters
BRASTIC'TM Sprinkler Size Pail ry Box Qty.
Head Adapter 3/4" x 112" V5003SBT-101 100
1"x1/2" V5003SBT-130 50
Brass starter thread molded into plastic, virtually eliminating cross-threading.
Female Sprinkler Head 'IM' Part fl r Box Qty.
Adapter with Metal
Thread Insert 3/4" X 1/2" V5003SBI-101 100
1" x 1/2" V5003SBI-130 50
1"x314" V5003SBI-131 10
Spigot Female Sprinkler i," Part Nuniber Box Qty.
Head Adapter with Metal
Thread Insert 3/4" x 1/2" V50032SB1-101 100
1" x 1/2" V500325B1-130 1 50
Metal Thread Insert
Sprinkler Head 90 with Size
3/4" x 1/2"
Pail NUmber
V500735B1-101
Box Qty.
100
1" x 1/2" V500735B1-130 50
1" x 3/4" V500735B1-131 10
1-1/4" x 1/2" V50073SB1-166 5
Sprinkler Head Tee with
Metal Thread Insert
1r4'
1"xl"xl"
IPail IBWTB1IT
V5012SBI-010
I Box Qty.
50
3/4"0/4"xl/2" V50125B1-101 10
1"xl"xl/2" V50125B1-130 50
1-1/4"x1-114"x112" V50125B1-166 5
1-1/2"x1-112"x1/2" V5012SB1-209 5
2"x2"x1/2" V50125B1-247 2
I
1"x3/4"xl/2" I V5012R5B1-124 • 10
1-114"xl"xl/2" V5012RSBl-156 5
1-1/2"x1-114"x112" V5012RSB1-199 5
2"xl-1/2"x112" V5012RSBl-237 2
1 "x112"xl " V5014RSBl122* 10
Socket x Fl Pr x Socket
Sprinkler Head Back to _______ M _ I' •t NUniber Box Qty.
Back Cross with Metal
Thread Insert 1x1l"x1/2'x1/2" 1-1/8" V503535B1S-130 1
0 1x1"x112"x1/2" 1-15/16" V503535B1L-130 1
Back to Back Tee with 'IN' I Part NUmber Box Qty.
Metal Threads Insert 112"x112"x1l" 1-1/8" V5011335B1S-075 48
1/2"x1/2"x1" 1-15/16" V501133SB1L-075 48
'IN' Part NUmber I Box Qty. Test Plug
1/2" V450005 50
www.vikinggroupinc.com
Size Part Number I Box Qty.
SjUi[i)
V5033E-020 1
2-112" V5033E-025 1
V5033E-030 1
Standard Union
fo
1W Part NUmber Box Qty.
3/4" V5003B1-007 10
1" V5003B1-010 50
1-1/4" V5003B1-012 5
Transition Fittings
Female Adapter with
Metal Thread Insert
1W Part Number Box Qty, I
1-1/2" V5003B1-015 5
2" V5003131-020 2
Spigot Female Adapter Size ;EIrIIuT_ ItêXS11I
with Metal Thread Insert 3/4" V50032131-007 10
1" V50032B1-010 10
Male Adapter with
Metal Thread Insert
1W Part Number I Box Qty.
314" V5004BI-007 10
1" V5004B1-010 10
1-1/4" V5004B1-012 5
1W NUmber Box Qty.
(ffhijij(Z tinue
1-1/2" V5004B1-015 5
2" V5004B1-020 2
Grooved Coupling Size •II!tTh1 ITh11
Adapter 1-1/4" V5001 G-012 30 . 1-1/2" V5001 G-015 25 2-1/2" V5001G-025 10
2" V5001 G-020 15 3" V5001 G-030 8
Accessories
Solvent Cement Size Part NUmber I Box Qty
Quart V5097QF12
Pint V5097P
Roller Size Part NUmber Box Qty
N/A V5097
Dauber Size _Box Qty _____
Small V5093-1 100
Large V5093-L 100
Size Part Number Box Qty 777 M~~M
Refer to manufacturers DESIGN AND INSTALLATION GUIDE for technical specifications and installation instructions.
c®us ? @ www,vikinggroupinc.com
September 2010
0 (tag
No.162
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: 12 Pacific SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: 1835 Buena Vista Way CITY: Carlsbad
PHONE: ( 951 ) 667-4220 x348 FAX NUMBER:
Largest Building (ft.2): 3,809 Sprinkled? YES Construction Type: new
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): Loker Ave E east of El Fuerte Street
TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED
Flow Test Results
Static pressure: 75 PSI Hydrant Number (if applicable):new
Elevation of test: 157 Feet Main Size: 10 INCH
Pressure Zone: 330 Feet Date/Time of Test:
Pitot Tube Reading: - PSI Corresponding Flow: GPM
Total Flow: 3,050 GPM Residual Pressure 43 PSI
At peak demand , this water system is capable of providing a fire flow discharge at 20 psi of 4,585 gpm. However, this
flow exceeds the District's maximum pipeline velocity of 10 fps. The maximum fire flow that meets both the velocity
and pressure criteria is 3,050 gpm. There was no specific requestforfireflowfrom the Client or Fire Department.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here: x
Name:jJe:n'fer.Mael,P.E. Eng. Lic. No. (if applicable): C69606
Signat
Title/O Manager Date: 08/17/2018
'.\
52 1835 Buena Vista Way - Fire Flow Analysis