Loading...
HomeMy WebLinkAbout1915 CALLE BARCELONA; ; FS1500089/12/23, 9:58 AM FS 150008 Permit Data City of Carlsbad Fixed Systems Permit Permit No: FS150008 1915 CALLE Job Address: Status: ISSUED BARCELONA Permit Type: FIXSYS Applied 4/6/2015 Parcel No: 2550120400 Approved: 5/4/2015 Lot #: 0 Reference No.: Issued: 5/4/2015 PC #: Inspector: Project Title: SUR LA TABLE NEW INSTALL OF TWO ANSUL, R102 WET CHEMICAL FIRE SUPPRESSION SYSTEMS., EACH SYSTEM IS A FIXED FIRE EXTINGUISHING SYSTEM INSTALLED TO PROVIDE FIRE PROTECTION FOR THE KITCHEN HOOD, DUCT, AND GREASE-LADEN APPLIANCES. THE WET CHEMICAL SYSTEM IS PROVIDED WITH AUTOMATIC AND MANUAL ACTIVATION DEVICES, THE SYSTEM IS UL-300 COMPLIANT Applicant: SIMPLEX GRINNELL 3568 RUFFIN ROAD SOUTH SAN DIEGO CA 858-583-0426 Owner: 1-C FORUM AT CARLSBAD L L C C/O TIAA-CREF 4675 MACARTHUR CT #1100 NEWPORT BEACH CA Fees ($) Add'l Fees ($) Total ($) Balance ($) 232 0 232 0 about:blank 1/1 0- 0 -C) L Li A I" R-102 RESTAURANT FIRE SUPPRESSION SYSTEM Design, Installation, Recharge and Maintenance Manual This manual is intended for use with ANSUL® R.102TM Restaurant Fire Suppression Systems. Those who install, operate, recharge, or maintain these fire sup- pression systems should read this entire manual. Specific sec- tions will be of particular interest depending upon one's responsibilities. Design, installation, recharge, and maintenance of the system must conform to the limitations detailed in this manual and per- formed by an individual who attended an ANSUL training pro- gram and became trained to install, recharge, design, and main- tain the ANSUL system. Fire suppression systems are mechanical devices. They need periodic care. Maintenance is a vital step in the performance of your fire suppression system. As such it must be performed in accordance with NFPA 96 (Standard for the Installation of Equipment for the Removal of Smoke and Grease-Laden Vapors from Commercial Cooking Equipment) and NFPA 17A (Standard on Wet Chemical Extinguishing Systems) by an authorized ANSUL distributor. To provide maximum assurance that the fire suppression system will operate effectively and safely, mainte- nance must be conducted at six-month intervals, or earlier if the situation dictates. Twelve-year maintenance must include agent tank hydrostatic testing. ANSUL PART NO. 418087-11 ANSUL ANSUL AUTOMAN and ANSULEX are trademarks of Tyco International Ltd. or its affiliates. REVISION INDEX UL EX3470 ULC EX3470 Pagel 7-1-09 REV. 12 DATE PAGE REV. NO. DATE PAGE REV. NO. 8-1-01 5-27 Deleted 7-1-09 1-3 New 10-1-02 4-7 3 7-1-09 1-4 New 10-1-02 6-4 2 7-1-09 2-1 4 10-1-02 9-2 5 7-1-09 2-2 5 10-1-02 9-3 5 7-1-09 3-1 6 10-1-02 9-4 7 7-1-09 3-2 6 10-1-02 9-8 3 7-1-09 3-5 8 10-1-02 9-10 3 7-1-09 3-6 7 10-1-02 9-11 5 7-1-09 3-7 6 10-1-02 9-15 Deleted 7-1-09 3-8 8 10-1-02 9-16 Deleted 7-1-09 3-9 5 4-1-06 3-3 8 7-1-09 3-10 4 4-1-06 3-4 7 7-1-09 3-11 1 4-1-06 4-2 4 7-1-09 3-12 1 4-1-06 4-8 6 7-1-09 4-1 8 4-1-06 4-9 8 7-1-09 4-3 5 4-1-06 4-11 8 7-1-09 4-4 7 4-1-06 5-2.1 5 7-1-09 4-5 5 4-1-06 9-9 4 7-1-09 4-6 7 4-1-06 9-10.2 2 7-1-09 4-10 7 7-1-09 In addition to the revised technical information, the ULC Listing file number at page has been updated. 7-1-09 4-12 6 the top of each manual 7-1-09 4-13 8 7-1-09 4-14 6 7-1-09 T.O.C. - Page 1 10 7-1-09 4-15 5 7-1-09 T.O.C. - Page 2 8 7-1-09 4-16 7 7-1-09 1-1 6 7-1-09 4-17 6 7-1-09 1-2 6 7-1-09 4-18 7 Indicates revised information. Indicates change in page sequence. REVISION INDEX UL EX3470 ULC EX3470 Page 2 REV. 6 7-1-09 DATE PAGE REV. NO. - - DATE PAGE REV. NO. 7-1-09 4-19 4 7-1-09 4-42 7 7-1-09 4-20 5 7-1-09 4-43 6 7-1-09 4-21 4 7-1-09 4-43.1 New 7-1-09 4-22 5 7-1-09 4-43.2 New 7-1-09 4-23 8 7-1-09 4-43.3 New 7-1-09 4-24 7 7-1-09 4-43.4 New 7-1-09 4-25 7 7-1-09 4-44 6 7-1-09 4-26 6 7-1-09 4-45 4 7-1-09 4-27 5 7-1-09 4-46 6 7-1-09 4-28 6 7-1-09 4-47 5 7-1-09 4-29 6 7-1-09 4-48 6 7-1-09 4-30 4 7-1-09 4-49 5 7-1-09 4-31 7 7-1-09 4-50 5 7-1-09 4-32 7 7-1-09 4-51 5 7-1-09 4-33 6 7-1-09 4-52 4 7-1-09 4-34 8 7-1-09 4-53 4 7-1-09 4-34.1 1 7-1-09 4-54 5 7-1-09 4-34.2 1 7-1-09 4-55 4 7-1-09 4-34.3 New 7-1-09 4-56 4 7-1-09 4-34.4 New 7-1-09 4-57 2 7-1-09 4-35 6 7-1-09 4-58 2 7-1-09 4-36 5 7-1-09 4-59 2 7-1-09 4-37 5 7-1-09 4-60 2 7-1-09 4-38 8 7-1-09 4-61 New 7-1-09 4-39 7 7-1-09 4-62 New 7-1-09 4-40 6 7-1-09 5-1 7 7-1-09 4-41 6 7-1-09 5-2 5 Indicates revised information. Indicates change in page sequence. REVISION INDEX UL EX3470 ULC EX3470 Page 3 7-1-09 REV. 4 DATE PAGE REV. NO. DATE PAGE REV. NO. 7-1-09 5-3 3 7-1-09 5-17.9 New 7-1-09 5-4 5 7-1-09 5-17.10 New 7-1-09 5-5 5 7-1-09 5-17.11 New 7-1-09 5-6 4 7-1-09 5-17.12 New 7-1-09 5-7 6 7-1-09 5-18 6 7-1-09 5-7.1 New 7-1-09 5-19 5 7-1-09 5-7.2 New 7-1-09 5-20 3 7-1-09 5-7.3 New 7-1-09 5-20.1 New 7-1-09 5-7.4 New 7-1-09 5-20.2 New 7-1-09 5-8 3 7-1-09 5-20.3 New 7-1-09 5-9 2 7-1-09 5-20.4 New 7-1-09 5-10 3 7-1-09 5-21 4 7-1-09 5-11 3 7-1-09 5-22 4 7-1-09 5-12 4 7-1-09 5-23 Deleted 7-1-09 5-13 3 7-1-09 5-24 Deleted 7-1-09 5-14 3 7-1-09 5-25 Deleted 7-1-09 5-15 4 7-1-09 5-26 Deleted 7-1-09 5-16 3 7-1-09 6-1 3 7-1-09 5-17 4 7-1-09 6-2 3 7-1-09 5-17.1 New 7-1-09 6-3 4 7-1-09 5-17.2 New 7-1-09 7-2 6 7-1-09 5-17.3 New 7-1-09 7-3 5 7-1-09 5-17.4 New 7-1-09 7-4 3 7-1-09 5-17.5 New 7-1-09 8-1 8 7-1-09 5-17.6 New 7-1-09 8-2 4 7-1-09 5-17.7 New 7-1-09 8-3 5 7-1-09 5-17.8 New 7-1-09 8-4 6 Indicates revised information. U Indicates change in page sequence. REVISION INDEX UL EX3470 ULC EX3470 Page 4 REV.O 7-1-09 TABLE OF CONTENTS UL EX3470 ULC EX3470 Pagel 7-1-09 REV. 10 SECTION PAGES GENERAL INFORMATION 1-1-1-4 DESIGN AND APPLICATION 1-1 UL LISTING 1-1 SYSTEM APPROVALS 1-1 DEFINITION OF TERMS 1-1 -1-3 SYSTEM DESCRIPTION 2-1-2-2 TOTAL SYSTEM 2-1 Single-Tank 2-1 Double-Tank 2-1 Three-Tank 2-2 Multiple-Tank 2-2 SYSTEM COMPONENTS 3-1-3-12 EXTINGUISHING AGENT 3-1 "ANSUL AUTOMAN" REGULATED 3-1 RELEASE ASSEMBLY (MECHANICAL) "ANSUL AUTOMAN" REGULATED 3-1 RELEASE ASSEMBLY (ELECTRICAL) REMOTE MECHANICAL RELEASE 3-2 SINGLE TANK ENCLOSURE 3-2 ASSEMBLY RED PAINTED BRACKET ASSEMBLY 3-2 REGULATED ACTUATOR 3-2 ASSEMBLY AGENT TANK ASSEMBLY 3-3 OEM RELEASE/BRACKET 3-3 ASSEMBLY (FOR OEM IN-CABINET USE ONLY) OEM REGULATED ACTUATOR 3-3 ASSEMBLY TWO TANK ENCLOSURE ASSEMBLY 3-3 24 VDC REGULATED RELEASE 3-4 ASSEMBLY ADDITIONAL SHIPPING ASSEMBLY 3-4 GAS CARTRIDGES 3-5 NOZZLES 3-5 SILICONE LUBRICANT 3-5 SWIVEL ADAPTOR 3-6 RUBBER BLOW-OFF CAP 3-6 CB METAL BLOW-OFF CAP 3-6 CONDUIT OFFSET ASSEMBLY 3-6 "QUlK-SEAL" ADAPTOR 3-6 "COMPRESSION-SEAL" ADAPTOR 3-7 "HOOD SEAL' ADAPTOR 3-7 ASSEMBLY REDUCING COUPLING 3-7 COCKING LEVER/LOCK BAR 3-7 DETECTORS 3-8 PULLEY ELBOWS 3-8 SECTION PAGES III. SYSTEM COMPONENTS 3-1-3-12 (Continued) PULLEY TEE 3-8 STAINLESS STEEL CABLE 3-8 REMOTE MANUAL PULL STATION 3-9 FLEXIBLE CONDUIT 3-9 MECHANICAL GAS VALVES 3-9 ELECTRICAL GAS VALVES 3-10 MANUAL RESET RELAY 3-10 ELECTRICAL SWITCHES 3-10 ALARM INITIATING SWITCH 3-11 REGULATOR TEST KIT 3-11 FUSIBLE LINK 3-11 MAXIMUM REGISTERING 3-11 THERMOMETER HOSE/GROMMET PACKAGE 3-11 IN-LINE BURST DISC ASSEMBLY 3-12 (MANIFOLDED SYSTEMS ONLY) 1/4 IN. CHECK VALVE 3-12 NOZZLE AIMING DEVICE 3-12 STAINLESS STEEL ACTUATOR HOSE 3-12 AGENT DISTRIBUTION HOSE AND 3-12 RESTRAINING CABLE KIT SYSTEM DESIGN 4-1-4-62 NOZZLE PLACEMENT 4-1 -4-31 REQUIREMENTS Duct Protection 4-1-4-3 Transition Protection 4-4 Electrostatic Precipitator 4-4 Protection Plenum Protection 4-5 -4-6 Appliance Protection Fryer - Single Nozzle Protection 4-7 -4-9 Multiple Nozzle Fryer Protection - 4-10-4-12 Tilt Skillet/Braising Pan 4-12 Range Protection 4-13-4-17 Griddle Protection 4-18 -4-21 Chain Broiler Protection 4-22 Horizontal Chain Broiler Protection 4-22 Overhead Chain Broiler Protection 4-22 -4-23 Upright/Salamander Broiler 4-23 Protection Gas-Radiant/Electric Char-Broiler 4-24 Protection Lava-Rock (Ceramic) Char-Broiler 4-25 Protection Natural Charcoal Broiler Protection 4-25 Alternate Ceramic/Natural 4-26 Charcoal Char-Broiler Protection Wood Fueled Char-Broiler Protection 4-26 Wok Protection 4-27 Nozzle Application Chart 4-28 -4-31 Specific Application by Model 4-32 -4-42 Overlapping Nozzle Coverage 4-43 -4-46 TABLE OF CONTENTS UL EX3470 ULC EX3470 Page 2 REV.8 7-1-09 SECTION PAGES SECTION PAGES IV. SYSTEM DESIGN (Continued) 4-1 -4-62 INSTALLATION INSTRUCTIONS 5-1-5-22 TANK AND CARTRIDGE 447 (Continued) REQUIREMENTS INSTALLING ELECTRICAL 5-18 ACTUATION AND EXPELLANT 4-47 -4-49 GAS VALVE GAS LINE REQUIREMENTS INSTALLING ELECTRICAL 5-19-5-20 DISTRIBUTION PIPING 4-49 -4-56 SWITCHES REQUIREMENTS INSTALLING ALARM 5-20 General Piping Requirements 4-49 INITIATING SWITCH Supply and Branch Line 4-50 -4-51 ELECTRICAL SWITCH 5-20.1 - 5-20.3 Identification REQUIREMENTS 1.5 Gallon System 4-52 3.0 Gallon System 4.53 WIRING 24 VDC REGULATED 5-21 6.0 Gallon Manifolded System 4-54 -4-55 RELEASE ASSEMBLY 9.0 Gallon System 4-56 DETECTION SYSTEM 4-57 -4-58 TESTING AND PLACING IN SERVICE 6-1-6-4 REQUIREMENTS TESTING MANUAL PULL STATION 6-1 Detector Identification 4-57 TESTING MECHANICAL GAS 6-1 Detector/Pulley Elbow Quantity 4-57 VALVES Detector Placement Requirements 4-57 -4-58 TESTING ELECTRICAL GAS 6-2 Detection Line Requirements 4-58 VALVES Fusible Link Selection 4-58 MANUAL PULL STATION 4-59 TESTING ELECTRIC SWITCH 6-2 REQUIREMENTS TESTING DETECTION SYSTEM 6-3 MECHANICAL GAS VALVE 4-59 -4-60 RECHARGE AND RESETTING 7-1-7-4 REQUIREMENTS PROCEDURES ELECTRICAL GAS VALVE 4-60 CLEANUP PROCEDURES 7-1 REQUIREMENTS Approvals 4-60 RECHARGE 7-1-7-3 ALARM INITIATING SWITCH 4-60 RESETTING 7-3-7-4 REQUIREMENTS REPLACEMENT CARTRIDGE 7-4 ELECTRICAL SWITCH 4-60 -4-61 REQUIREMENTS MAINTENANCE EXAMINATION 8-1-8-10 SEMI-ANNUAL MAINTENANCE 8-1 -8-4 V. INSTALLATION INSTRUCTIONS 5-1-5-22 EXAMINATION MOUNTING THE COMPONENTS 5-1 -5-2.1 ANNUAL MAINTENANCE 8-5 INSTALLING THE ACTUATION 5-3-5-6 EXAMINATION AND EXPELLANT GAS LINES 12-YEAR MAINTENANCE 8-5 -8-9 INSTALLING THE DISTRIBUTION 57 EXAMINATION PIPING INSTALLING THE AGENT 5-7.1 - 5-7.3 IX. APPENDIX 9-1-9-14 DISTRIBUTION HOSE (FOR SYSTEM SELECTION GUIDE 9-1 -9-4 CASTERED/MOVEABLE EQUIPMENT) SYSTEM COMPONENT INDEX 9-5 -9-6.2 INSTALLING THE DETECTION 5-8-5-11 PARTS LISTS 9-7 -9-10.2 SYSTEM "Scissors" Style Linkage Installation 5-8 -5-11 MULTIPLE NOZZLE FRYER 9-11 PROTECTION CALCULATION INSTALLING REMOTE MANUAL 5-12-5-13 EXAMPLES PULL STATION General Installation Requirements 5-12 WIRING DIAGRAM 9-12-9-13 Installation for Remote Manual Pull 5-12-5-13 Station Utilizing EMT Conduit Only INSTALLING MECHANICAL 5-13 -5-17 GAS VALVE INSTALLATION REMOTE MANUAL 5-17 - 5-17.11 PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT SECTION I - GENERAL INFORMATION UL EX3470 ULC EX3470 Page 1-1 7-1-09 REV. 6 DESIGN AND APPLICATION The ANSUL R-102 Restaurant Fire Suppression System is designed to provide fire protection for restaurant cooking appli- ances, hoods, and ducts. It is a pre-engineered group of mechan- ical and electrical components for installation by an authorized ANSUL distributor. The basic system consists of an ANSUL AUTOMAN regulated release assembly which includes a regulat- ed release mechanism and a liquid agent storage tank housed within a single enclosure. Nozzles, detectors, cartridges, liquid agent, fusible links, pulley tees, and pulley elbows are supplied in separate packages in the quantities needed for each fire suppres- sion system arrangement. The system provides automatic actuation; or it can be actuated manually through a remote manual pull station. The system is also capable of shutting down appliances at system actuation. For appliance shutdown requirements, refer to the current version of NFPA 17A, 'Standard For Wet Chemical Extinguishing Systems," and NFPA 96, "Standard For Ventilation Control and Fire Protection of Commercial Cooking Operations." Additional equipment includes: remote manual pull station, mechanical and electrical gas valves, and electrical switches for automatic equipment and gas line shut-off. Accessories can be added, such as alarms, warning lights, etc., to installations where required. The R-102 system suppresses fire by spraying the plenum area, the filters, cooking surfaces, and the exhaust duct system with a predetermined flow rate of ANSULEX Low pH Liquid Fire Suppressant. When the liquid agent is discharged onto a cooking appliance fire, it cools the grease surface, and reacts with the hot grease (saponification) forming a layer of soap-like foam on the surface of the fat. This layer acts as insulation between the hot grease and the atmosphere, thus helping to prevent the escape of combustible vapors. Exhaust fans in the ventilating system should be left on. The forced draft of these fans assists the movement of the liquid agent through the ventilating system, thus aiding in the fire suppression process. These fans also provide a cooling effect in the plenum and duct after the fire suppression system has been discharged. The system is UL listed with or without fan operation. Make up or supply air fans, integral to the exhaust hood(s) being protected, shall be shut down upon system actuation. Along with the fire suppression system, the total system design must include hand portable fire extinguisher(s) located within the cooking/restaurant area that can be used to manually suppress a fire that may be burning in an unprotected area. Class K extin- guisher(s) must be provided for hazards where there is a potential for fires involving combustible cooking media (vegetable or animal oils and fats). Refer to NFPA 10, "Standard For Portable Fire Extinguisher," for additional information. UL LISTING The R-102 Restaurant Fire Suppression System has been tested and is listed by Underwriters Laboratories, Inc. as a pre-engi- neered system. The system is in compliance with UL Test Standard 300. These tests require extinguishment of fires which are initiated in deep fat fryers, ranges, griddles, char-broilers, woks, upright broilers, chain-broilers, filters, plenum chambers, hoods, and ducts after pre-loading each appliance with a pre- scribed amount of cooking grease. Each fire is allowed to progress to maximum intensity before the fire suppression system is actuated. 'SYSTEM APPROVALS UL EX3470 ULC EX3470 MEA 59-95E DEFINITION OF TERMS 'Actuation Gas Line: Piping and/or stainless steel braided hose assemblies from the ANSUL AUTOMAN Regulated Release Assembly which supplies high pressure nitrogen or carbon dioxide to the Regulated Actuator Assembly for multiple-tank system actu- ation. Agent Tank: A pressure vessel containing the liquid agent. ANSUL AUTOMAN Regulated Release Assembly (Electrical): An assembly which contains the regulated release mechanism, agent tank (ordered separately), expellant gas hose, solenoid, and electric switch within a metal enclosure. The enclosure contains knockouts to facilitate component hookups. ANSUL AUTOMAN Regulated Release Assembly (Mechani- cal): An assembly which contains the regulated release mecha- nism, agent tank (ordered separately), and expellant gas hose within a metal enclosure. The enclosure contains knockouts to facilitate component hookups. Authority Having Jurisdiction: The "authority having jurisdiction" is the organization, office, or individual responsible for "approving" equipment, an installation, or a procedure. The phrase "Authority Having Jurisdiction" is used in a broad manner since jurisdictions and "approval" agencies vary as do their responsibilities. Where public safety is primary, the "authority having jurisdiction" may be a federal, state, local, or other regional department or individual such as a fire chief, fire marshal, chief of a fire prevention bureau, labor department, health department, building official, electrical inspector, or others having statutory authority. For insurance pur- poses, an insurance company representative may be the "author- ity having jurisdiction." In many circumstances the property owner or his designated agent assumes the role of the "authority having jurisdiction;" at government installations, the commanding officer or departmental official may be the "authority having jurisdiction." 'Blow-Off Cap: A siliconized rubber or metal cap which covers the end of the nozzle to protect the nozzle tip and minimize cooking 'grease migration into the nozzle orifice. Branch Line: The agent distribution piping which extends from the supply line to the nozzle(s). 'Bursting Disc: A disc installed in the tank adaptor which mini- mizes the remote chance of siphoning of the agent into the dis- charge piping during extreme temperature variations. Cartridge: A hermetically sealed, steel pressure vessel containing nitrogen or carbon dioxide gas used to pressurize the agent tank. Cooking Appliance: Includes fryers, griddles, ranges, upright broilers, chain broilers, natural charcoal broilers, or char-broilers (electric, lava rock, gas-radiant, or mesquite). Cooking Area: Cooking area is defined as the maximum surface that requires protection. Each type of appliance has a defined cooking area with parameters that vary for each appliance. For example, the cooking area for a griddle is the entire flat cooking surface, while a fryer may have two areas that need consideration, 'depending on whether the fryer has a dripboard or not. Conduit Offset Assembly: A pre-formed piece of conduit which can be installed between the ANSUL regulated release and the conduit to allow the wire rope for the detection, gas valve and remote manual pull station to be installed in a more convenient manner. SECTION I - GENERAL INFORMATION UL EX3470 ULC EX3470 Page 1-2 REV. 6 7-1-09 DEFINITION OF TERMS (Continued) Depth: When referring to depth as a linear dimension, it is the horizontal dimension measured from front to back of the appliance or plenum. Detector: A device which includes the detector bracket, detector linkage, and fusible link used for automatic operation of the fire suppression system. Detector Linkage: A device used to support the fusible link. Discharge Hose Assembly: An agent distribution hose to be used with castered cooking appliances with castered supports to allow the movement of the appliance for service or cleaning pur- poses. Distribution Piping: Piping which delivers the extinguishing agent from the tank to each discharge nozzle. See also Supply or Branch lines. Ducts (or Duct System): A continuous passageway for the trans- mission of air and vapors which, in addition to the containment components themselves, may include duct fittings, dampers, duct filters, duct transitions, in-line or end-duct pollution control units (PCUs), and/or other items or air handling equipment. Electrostatic Precipitator: A device used to aid in the cleaning of the exhaust air. This device is normally installed at or near the base of the ventilation duct or may be included as an integral part of a pollution control unit (PCU). Expellant Gas Line: Piping and/or hose which supplies the nitro- gen or carbon dioxide gas from the regulated release assembly/ regulated actuator assembly to each agent tank. Flexible Conduit: A flexible means to route stainless steel cable from the ANSUL AUTOMAN Regulated Release to a manual pull station or mechanical gas valve. Flow Number: Term used in system design to describe the flow capacity of each nozzle used to determine the quantity of tanks needed to cover a certain group of hazards. Fusible Links: A fixed temperature heat detecting device employed to restrain the operation of a mechanical control until its designed temperature is reached, allowing separation of the link and system operation. Gas Valve: An electrically or mechanically operated device used to shut off the gas supply to the cooking equipment when the sys- tem is actuated. Gas Valve Air Cylinder: An air cylinder, located in the release mechanism, which operates pneumatically to mechanically unlatch a mechanical gas valve actuator, causing the gas valve to close upon system actuation. High Proximity: Indicates a distance (vertically) between the noz- zle tip and the surface of the appliance being protected. Hood: A device provided for cooking appliances to direct and cap- ture grease-laden vapors and exhaust gases from cooking appli- ances. It shall be constructed in a manner which meets the requirements of NFPA 96. Liquid Agent: A potassium-based solution used for the knock- down and suppression of fire. Low Proximity: Indicates a distance (vertically) between the noz- zle tip and the surface of the appliance being protected. Maximum Length of Cooking Appliance: The maximum dimen- sion, on any side, which may be protected by one nozzle. Maximum Piping: Specified length of piping and number of fit- tings which must not be exceeded for each system. Medium Proximity: Indicates a distance (vertically) between the nozzle tip and the surface of the appliance being protected. Minimum Piping: Minimum length of distribution piping required between the agent tank outlet and any nozzle protecting a griddle, range, or fryer. Nozzle: A device designed to deliver the liquid agent with a spe- cific flow rate and stream pattern. Overlapping Protection: When discharge nozzles are spaced equally apart over one or more appliances requiring protection. Nozzles used in this manner provide area protection of eligible appliances within the protected area. Two types of overlapping pro- tection is available: full hood continuous protection and group pro- tection. Overlapping protection is in addition to appliance specific coverages. Plenum: The space enclosed by the filters and the portion of the hood above the filters. Pre-engineered System: NFPA 17A defines a pre-engineered system as one which has "...predetermined flow rates, nozzle pressures, and quantities of liquid agent." The R-102 system, as prescribed by UL (Underwriter's Laboratories), has specific pipe sizes, maximum and minimum pipe lengths and numbers of fit- tings, and number and types of nozzles. The hazards protected by this system are also specifically limited as to type and size by UL based upon actual fire tests. All limitations on hazards that can be protected and piping and nozzle configurations are contained in the R-102 installation and maintenance manual which is part of the UL listing. Pulley Elbow: A device used to change the direction of the wire rope which runs between: the regulated release mechanism and the detectors, the regulated release mechanism and the mechan- ical gas valve, and/or the regulated release mechanism and the remote manual pull station. Pulley Tee: A device used to change the direction of two wire ropes which run from a regulated release or a regulated actuator to two remote manual pull stations, or from two regulated releases or regulated actuators to a single mechanical gas valve or from one regulated release or regulated actuator to two gas valves. Regulated Actuator Assembly: An assembly which contains the regulator, pneumatic actuator, agent tank, and expellant gas hose within a metal enclosure. This assembly is used to pressurize addi- tional agent tanks in a multiple tank system. Regulated Release Mechanism: An enclosed device within the ANSUL AUTOMAN regulated release assembly which releases the expellant gas, activates alarms, and/or shuts off other devices when signaled automatically by a detector or manually with a remote pull station. Regulator: A device used to regulate the pressure from the nitro- gen cartridge into the agent tank(s) when the system is actuated. Remote Manual Pull Station: A device which provides manual actuation of the system from a remote location. Salamander Broiler: A broiler very similar in design to the upright broiler. A salamander broiler is used for general broiling of meats and fish, toasting, and holding/warming foods. Most contain a removable grease drip tray. Series Detector: Any detector located in-line between the regu- lated release assembly and the terminal detector. Silicone Lubricant: A heat-resistant organic compound used to lubricate 0-rings, rubber and mechanical components. Supply Line: The agent distribution piping which extends from the agent tank outlet and serves as a manifold for the branch lines. SECTION I - GENERAL INFORMATION UL EX3470 ULC EX3470 Page 1-3 7-1-09 REV. 0 DEFINITION OF TERMS (Continued) Terminal Detector: The last in a series of detectors, or the only detector used in a single-detector system. This detector is thus named because it is at the point at which the wire rope ends, or "terminates." There is only one terminal detector per detection system. Transition: An extension of the hood or canopy which allows for the smooth transmission of gases, air, and vapors between the hood opening and the base of the ventilation duct. Vent Plug: A device used to prevent pressure build-up within the agent tank or agent distribution lines due to temperature fluctuations. SECTION I - GENERAL INFORMATION UL EX3470 ULC EX3470 Page 1-4 REV.O 7-1-09 NOTES: SECTION II— SYSTEM DESCRIPTION UL EX3470 ULC EX3470 Page 2-1 7-1-09 REV. 4 I. TOTAL SYSTEM There are four types of R-102 Restaurant Fire Suppression Systems: Single-tank System Double-tank System Three-tank System (1 Cartridge) Multiple Tank System (Three Tanks or More - Multiple Cartridges) The type of system required for the particular installation will be determined through the guidelines covered in "System Design:' Additional equipment which may be required to complete the sys- tem design is explained in the "System Components" section. Additional devices covered are: remote manual pull stations, mechanical and electrical gas shut-off valves, electrical switches, and pressure switches. Single-Tank System The R-102 single-tank system is available with a stainless steel enclosure and consists of: ANSUL AUTOMAN Regulated Release Assembly (Electrical or Mechanical) Nitrogen Cartridge and/or Carbon Dioxide Cartridge ANSULEX Low pH Liquid Fire Suppressant Discharge Nozzles Detection Components Additional Devices (As Required) The regulated release assembly contains the regulated release mechanism, agent tank, expellant gas hose for agent tank hookup, and enclosure knockouts to facilitate installing detection system and additional equipment. Refer to 'System Components" section for individual component descriptions. FIGURE 1 000133 Double-Tank System The R-102 double-tank system is available with stainless steel enclosures and consists of: ANSUL AUTOMAN Regulated Release Assembly (Electrical or Mechanical) Nitrogen Cartridge and/or Carbon Dioxide Cartridge ANSULEX Low pH Liquid Fire Suppressant Enclosure or Bracket Assembly Discharge Nozzles Detection Components Additional Devices (As Required) The regulated release assembly contains the regulated release. mechanism, agent tank, expellant gas hose for agent tank hookup, and enclosure knockouts to facilitate installing expellant piping, detection system, and additional equipment. The enclosure or bracket assembly is mounted separately but within the guidelines of the regulated release assembly expellant gas piping requirements to ensure simultaneous actuation of the system. Refer to "System Components" section for individual com- ponent descriptions. FIGURE 2 008321 SECTION II— SYSTEM DESCRIPTION UL EX3470 ULC EX3470 Page 2-2 REV.5 7-1-09 TOTAL SYSTEM (Continued) Three-Tank System (1 Cartridge with Three (3) 3.0 Gal Tanks ONLY) The R-102 three-tank system is available with stainless steel enclosures and consists of: ANSUL AUTOMAN Regulated Release Assembly (Electrical or Mechanical) Double Tank Enclosure Assembly Nitrogen Cartridge ANSULEX Low pH Liquid Fire Suppressant Discharge Nozzles Detection Components Additional Devices (As Required) The regulated release assembly contains the regulated release mechanism, agent tank, expellant gas hose for agent tank hookup, and enclosure knockouts to facilitate installing expellant piping, detection system, and additional equipment. The double tank enclosure assembly is mounted separately but within the guidelines of the regulated release assembly expellant gas piping requirements to ensure simultaneous actuation of the system. Refer to 'System Components" section for individual com- ponent descriptions. FIGURE 3 3n Multiple Tank System (Three (3) Tanks or More - Multiple Cartridges) The R-102 multiple-tank system is available with stainless steel enclosures and Consists of: ANSUL AUTOMAN Regulated Release Assembly (Electrical or Mechanical) or ANSUL AUTOMAN Remote Release Assembly(ies) Nitrogen Cartridge(s) and/or Carbon Dioxide Cartridge(s) Regulated Actuator Assembly(ies) ANSULEX Low pH Liquid Fire Suppressant Enclosure or Bracket Assembly(ies) Discharge Nozzles Detection Components Additional Devices (As Required) The regulated release assembly contains the regulated release mechanism, agent tank, expellant gas hose for agent tank hookup, and enclosure knockouts to facilitate installing actuation piping, expellant piping, detection system, and additional equipment. The remote release assembly(ies) is used in large systems or multi-hood systems to actuate regulated actuator assembly(ies) ONLY. The remote release assembly contains a release mecha- nism (unregulated), with enclosure knockouts to facilitate installing the actuation piping, expellant piping, detection system, and addi- tional equipment. Each regulated actuator assembly is mounted separately but with- in the guidelines of the regulated release assembly actuation/ expellant gas piping requirements to ensure simultaneous actua- tion of the system. The assembly contains the pneumatic actuator, regulator, agent tank, expellant gas hose for agent tank hookup, and enclosure plugs to facilitate installing expellant piping. Each enclosure or bracket assembly is mounted separately but within the guidelines of the regulated release assembly or regulat- ed actuator assembly expellant gas piping requirements to ensure simultaneous actuation of the system. Refer to 'System Components" section for individual component descriptions. FIGURE 4 oa NOTE: AGENT TANK MUST BE ORDERED SEPARATELY OR SEE PAGE 3-4 SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-1 7-1-09 REV.6 EXTINGUISHING AGENT ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon - Part No. 79694 or 3.0 gallon - Part No. 79372) is a potassium-based solu- tion designed for fast knock-down and suppression of grease- related fires. The agent is shipped in plastic containers which pro- vide one complete tank charge. (Refer to Section V, Page 5-2.1,for maximum agent fill capacity.) Agent storage life expectancy is twelve years and can be stored at a temperature of —40 OF to 130 OF (-40°C to 54°C). Note: When installing agent in R-102 sys- tem, temperature range is 32 OF (0 °C) to 130 OF (54 °C). The distributor must record the batch numbers and date of shipment receipt to be filed with each installation record. "ANSULE)r LOW pH LIQUID FIRE SUPPRESSANT 3.0 GALLON 1.5 GALLON SHIPPING WE 35 LB (16 kg) SHIPPING WE 19 LB (9 kg) O136 OD0137 FIGURE 1 REGULATED RELEASE ASSEMBLY (MECHANICAL) The ANSUL AUTOMAN Regulated Mechanical Release Assembly (Part No. 429853) contains the regulated release mechanism, expellant gas hose for agent tank hookup, and enclosure knock- outs to facilitate installing actuation piping; expellant piping; detec- tion system; and additional equipment. This regulated release assembly is used in single, double, and multiple-tank systems and must be mounted to a rigid surface. The release mechanism can be used to interconnect both the actuation and expellant gas lines as required per system design. The regulator is designed to allow a constant flow of gas into the tank at 110 psi (7.6 bar) when the system is actuated. The agent tank must be ordered separately. In single, double, and multiple-tank systems, the provided expel- lant gas hose connects the agent tank to the bottom outlet of the regulator. In double and multiple-tank system configurations, the back outlet of the regulator is used as an expellant gas feed for one additional tank-enclosure or tank-bracket hookup. The enclo- sure contains the required knockouts to facilitate this connection. If a pressure switch is to be attached to the regulator, additional fit- tings are required. The tank is mounted within the enclosure. The tank contains an adaptor/tube assembly with a burst disc union. The burst disc helps prevent siphoning of the agent up the pipe due to significant temperature fluctuations in the area where the tank is located. The tank is stainless steel and, under normal conditions, requires hydrostatic testing every twelve years. The detection and additional equipment required per system design are connected to the release mechanism. The enclosure contains knockouts to facilitate detection and additional hookups. The system can be actuated automatically or manually. Automatic actuation occurs when a fusible link within the detection system separates in a fire condition. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. "ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY (MECHANICAL) FIGURE 2 OWI3B REGULATED RELEASE ASSEMBLY (ELECTRICAL) The ANSUL AUTOMAN Regulated Electrical Release Assembly (Part No. 429856) is identical to the mechanical version except it also contains a factory installed 120 VAC solenoid and electrical switch. The solenoid is used to provide electrical actuation of the release mechanism. The electric switch is used to protect the solenoid by opening the circuit to the solenoid once the system is fired. Additional electrical switches can be added as required for auto- matic equipment and gas shut-off accessories, as well as initiating audible and visual alarms. "ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY (ELECTRICAL)* NOTE: AGENT TANK MUST ORDERED SEPARATELY OR SEE PAGE 3.4 REGULATOR Ell ff SWITCH SOLENOID SHIPPING WE 34 LB (15 kg) FIGURE 3 000139 * NOTE: ANSUL AUTOMAN Regulated Electrical Release, Part No. 429856, is not intended to be used with electric detection. MOUNTING BRACKET SHIPPING WE 7 LB (3 kg) RELEASE - MECHANISM SHIPPING WEIGHT: 20 LB (9.1 kg) FIGURE 4 007498 FIGURE 6 000141 REGULATED ACTUATOR ASSEMBLY The Regulated Actuator Assembly (Part No. 429850) contains the regulator, pneumatic actuator, expellant gas hose for agent tank hookup, and enclosure knockouts to facilitate installing expellant pip- ing. This assembly is used in multiple-tank systems and must be mounted to a rigid surface. The regulator contains two outlets 1350 apart. One outlet is used to interconnect the expellant gas hose to the enclosed agent tank. The other outlet connects an expellant gas line to an additional enclosure or bracket assembly. The regulator is designed to allow a constant flow of nitrogen into each agent tank connected (two tanks maximum) at 110 psi (7.6 bar). The pneumatic actuator is designed to puncture the expellant gas cartridge seal upon receiving pressure from the regulated release assembly actuation piping. The enclosure contains a knockout to facilitate distribution piping hookup. REGULATED ACTUATOR ASSEMBLY NOTE: AGENT TANK MUST BE ORDERED SEPARATELY OR SEE PAGE 3-4 PNEUMATIC ACTUATOR ASSEMBLY REGULATOR ING WT. (9 kg) FIGURE 7 000143 SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-2 REV.6 7-1-09 REMOTE MECHANICAL RELEASE The Remote Mechanical Release, Part No. 433485, is used to actuate up to five (5) R-102 regulated actuators. The remote mechanical release utilizes a 101-10 carbon dioxide cartridge as the actuation pressure to operate the regulated actuators. The release is housed in a stainless steel enclosure. The tank bracket is constructed of mild steel and painted red. It is designed for mounting the tank in a minimum amount of space. The Bracket Assembly can only be utilized with 3.0 gallon tanks (Part No. 429862). BRACKET ASSEMBLY SINGLE TANK ENCLOSURE ASSEMBLY The Single Tank Enclosure Assembly (Part No. 429870) is used in double and multiple-tank systems and must be mounted to a rigid surface near the regulated release or regulated actuator assembly its expellent gas line will be connected to. The enclosure is designed for mounting either a 1.5 gallon (Part No. 429864) or a 3.0 gallon tank (Part No. 429862) in a minimum amount of space. ENCLOSURE ASSEMBLY NOTE: AGENT TANK MUST BE ORDERED SEPARATELY OR SEE PAGE 3-4 MOUNTING ENCLOSURE SHIPPING Wt E 13 LB (6 kg) FIGURE 5 000142 RED PAINTED BRACKET ASSEMBLY The Bracket Assembly (Part No. 429878) is used in double and multiple-tank systems and must be mounted to a rigid surface near the regulated release assembly or regulated actuator assembly that its expellant gas line will be connected to. SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-3 4-1-06 REV.8 AGENT TANK ASSEMBLY The agent tank shipping assembly (3-Gallon, Part No. 429862, and 1.5 Gallon, Part No. 429864) consists of a stainless steel tank and an adaptor/tube assembly. The adaptor/tube assembly con- tains a burst disc. The burst disc prevents agent leakage due to significant temperature fluctuations in the area where the tank is located. Under normal conditions, the tank requires hydrostatic testing every twelve years. The date of manufacture is stamped on the tank nameplate. The tank is shipped uncharged and must be filled with only ANSULEX Low pH Liquid Fire Suppressant during installation. (ADAPTOR! S ASSEMBLY 3 GALLON SHIPPING WT. 7 LB (3 kg) 1.5 GALLON SHIPPING Wt 5 LB (2 kg) AGENT TANK FIGURE 8 000140 OEM RELEASE/BRACKET ASSEMBLY (FOR OEM IN-CABINET USE ONLY) The OEM Regulated Mechanical Release/Bracket Assembly, Part No. 79493, contains the same regulated release mechanism as the standard ANSUL AUTOMAN Regulated Release Assembly. The OEM Regulated Electrical Release/Bracket Assembly, Part No. 418054*, is identical to the mechanical version except it con- tains a factory installed 120 VAC solenoid and electrical switch. These release/bracket assemblies must be installed in a suitable equipment enclosure either horizontally or vertically. They contain all the necessary mounting and conduit holes needed to fully install the assembly. The agent tank is installed separately and need not be bracketed once it is piped and filled. Note: OEM Release/Bracket Assembly must be installed high enough in cabi- net so that there is sufficient room to install and remove cartridge. 'Note: OEM Regulated Electrical Release/Bracket Assembly, Part No. 418054, is not intended to be used with electric detection. I MOUNTING RELEASE BRACKET MECHANISM /T 0 REGULATOR OEM REGULATED ACTUATOR ASSEMBLY The OEM Regulated Actuator Assembly, Part No. 418691, includes the regulator, pneumatic actuator, expellant gas hose and OEM bracket. Also available is an OEM Regulated Actuator Assembly with all the above mentioned components except for the bracket. This assembly is Part No. 418522. rm 3 SHIPPING WE 4 LB (2 kg) FIGURE 10 000000 TWO TANK ENCLOSURE ASSEMBLY The Two Tank Enclosure Assembly, Part No. 429872, consists of two expellant gas hoses, two grommets, and the mounting enclo- sure. The assembly is used in 9 gallon systems. It can be coupled with a 3-gallon regulated release assembly or a 3-gallon regulated actuator assembly to give a total of 9 gallons of agent. Agent tanks must be ordered separately. The tank enclosure is designed to mount in a minimum amount of space. SHIPPING wt 26 LBS (12 kg) FIGURE 11 002277 SHIPPING Wt 10 LB (5 kg) FIGURE 9 002144 SECTION III SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-4 REV. 7 4-1-06 24 VDC REGULATED RELEASE ASSEMBLY (ULC APPROVED ONLY) The 24 VDC Regulated Release Assembly, Part No. 429859, is used where electric, thermostat detection is required via the use of a releasing control unit. This assembly consists of a 24 VDC ANSUL AUTOMAN Il-C regulated release mechanism, expellant gas hose, and enclosure knockouts to facilitate installing actuation piping, expellant piping, detection system, and additional equip- ment. Agent tank must be ordered separately. The system can be actuated automatically or manually. Automatic actuation occurs when the control panel receives a signal from the detection circuit. The panel then sends an electrical signal to the 24 VDC regulated release, causing it to actuate. When actuation occurs, the gas cartridge is punctured, pressurizing the agent tank and discharging the agent through the distribution piping. Manual actuation of the system occurs when personnel pull on the remote manual pull station pull ring. ADDITIONAL SHIPPING ASSEMBLIES Several complete shipping assemblies are available containing both the release or actuator mechanism and the agent tank. When ordering a complete shipping assembly, order the following part numbers: Shipping Wt. Part No. Description lb (kg) 430299 3.0 Gallon Mechanical Release 33 (15) Shipping Assembly including: 429853 Mechanical Regulated Release Assembly 429862 3.0 Gallon Tank Assembly 430300 1.5 Gallon Mechanical Release 30 (14) Shipping Assembly including: 429853 Mechanical Regulated Release Assembly 429864 1.5 Gallon Tank Assembly 430324 6.0 Gallon Stainless Steel Enclosure 40 (18) Shipping Assembly including: 429872 Two Tank Mounting Box Assembly 429862 3.0 Gallon Tank Assembly (2) 430332 3.0 Gallon Mounting Bracket Shipping 20 (9) Assembly including: 429878 3.0 Gallon Mounting Bracket Assembly 429862 3.0 Gallon Tank Assembly NOTE: AGENT TANK MUST BE ORDERED SEPARATELY 430309 3.0 Gallon Regulated Actuator 36 (16) Shipping Assembly including: SHIPPING WE 429850 Regulated Actuator Assembly 34 LB (15 kg) 429862 3.0 Gallon Tank Assembly 430316 1.5 Gallon Stainless Steel Enclosure 18 (8) Shipping Assembly including: 429870 Single Tank Mounting Box Assembly 429864 1.5 Gallon Tank Assembly 418511 Hose Assembly 430317 3.0 Gallon Stainless Steel Enclosure 20 (9) Shipping Assembly including: omm FIGURE 12 429870 Single Tank Mounting Box Assembly 429862 3.0 Gallon Tank Assembly 418511 Hose Assembly SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-5 7-1-09 REV. 8 GAS CARTRIDGES The R-102 system uses gas cartridges to store nitrogen or carbon dioxide expellant gases under pressure until the system is actuat- ed, at which time the cartridge seal is punctured and the released gas expels liquid agent from one or more tanks through the dis- charge piping and out the discharge nozzles. Four nitrogen gas cartridges and three carbon dioxide gas car- tridges are available as shown in Figure 13. Cartridges noted as TC/DOT are both Transport Canada (IC) and Department of Transportation (DOT) approved. Cartridges noted as DOT are Department of Transportation approved only. Cartridge selection options are provided in Section IV under Tank and Cartridge Requirements. NITROGEN GAS CARTRIDGES tg 21/2 IN. 21/2 IN. 431161N. 39/16IN. (6.4 cm) (6.4 cm) (10.6 cm) (9 cm) LT-20-R LT-30R DOUBLE-TANK LT-A-101-30 CARTRIDGE CARTRIDGE CARTRIDGE CARTRIDGE 000145 000148 000147 000148 CARBON DIOXIDE CARTRIDGES 11 5/8 IN. gIN. 77/8 IN. (29.5 cm) (22.9 cm) (20 cm) - 2IN. 21/2IN. 21/2 IN. (5.1 cm) (6.4 cm) (6.4 cm) 101-10 CARTRIDGE 101-20 CARTRIDGE 101-30 CARTRIDGE 000149 005150 005151 FIGURE 13 Additional cartridge shipping assemblies are available for European and Australian requirements. Cartridge European Australian TC/DOT Description Part No. Part No. Part No. LT-20-R 428440 428948 423429 LT-30-R 428441 426553 423435 Double Tank 428446 426563 423493 LT-A-101-30 428442 426555 423491 101-10—0O2 428443 N/A 423439 101 -20— CO2 428445 N/A 423441 101-30 - CO2 428444 N/A 423443 i-Note: For 101-10 cartridge, Part No. 15850 is DOT only. NOZZLES There are 11 types of discharge nozzles each designed to distrib- ute the liquid agent in a uniform pattern throughout the hazard area: 1W Nozzle 7. 245 Nozzle IN Nozzle 8. 260 Nozzle 112N Nozzle 9. 290 Nozzle 3N Nozzle 10. 2120 Nozzle 2W Nozzle 11. 1 F Nozzle 230 Nozzle Although these nozzles are similar in appearance and have certain common parts, the tip of each nozzle is designed for a specific application and must only be used in those areas. See Nozzle Application Chart in Section IV - System Design, for individual nozzle usage. 3/8-18 NPT FEMALE THREAD INTERNAL CUP STRAINER INSIDE RECESS FOR VENDOR CAP LOOP BLOW OFF :~W (IF PRESENT) CODE NOZZLE STAMPING FIGURE 14 Nozzle Identification Chart Note: See Component Index for nozzle package shipping assem- bly part numbers. Nozzle Nozzle Nozzle Nozzle* Flow Part No. Stamping Na. Nozzle Material 1W Nozzle 419336 1 W** 1 Chrome-Plated Body 1 N Nozzle 419335 1 N** 1 Chrome-Plated Body 1/2N Nozzle 419334 1/2N 1/2 Chrome-Plated Body 3N Nozzle 419338 3N 3 Chrome-Plated Body 2W Nozzle 419337 2W 2 Chrome-Plated Body 230 Nozzle 419339 230 2 Chrome-Plated Body 245 Nozzle 419340 245 2 Chrome-Plated Body 260 Nozzle 419341 260 2 Chrome-Plated Body 290 Nozzle 419342 290 2 Chrome-Plated Body 2120 Nozzle 419343 2120 2 Chrome-Plated Body 1 F Nozzle 419333 1 F 1 Chrome-Plated Body * Nozzle stamping may contain an additional letter indicating a vendor's code. **sISS steel versions are available in the 1W nozzle (Part No. 432527) and the 1 N nozzle (Part No. 435672). SILICONE LUBRICANT Dow Corning Compound 111, Part No. 78112, is available in a 5.3-ounce tube. Compound has excellent qualities for sealing and lubricating system components. SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-6 REV. 7 7-1-09 SWIVEL ADAPTOR . The Swivel Adaptor Assembly consists of a swivel nut, swivel body and swivel ball. All are chrome-plated. The swivel adaptor allows any nozzle to be rotated approximately 30° in all directions. Swivel Adaptors must be ordered as a Swivel Adaptor Shipping l. Assembly, Part No. 423572, which contains 25 Swivel Adaptors or o. Part No. 419385, which contains 9 Swivel Adaptors. 3/8-18 NPT FEMALE THREAD IPT READ 30 AC FIGURE 15 oo RUBBER BLOW-OFF CAPS P. The Rubber Blow-Off Cap helps keep the orifice of the nozzle free of grease or other substances that could interfere with agent dis- tribution. A retaining strap attaches the blow-off cap to the nozzle. Rubber Blow-Off Caps must be ordered as a Shipping Assembly, ' Part No. 77695, which contains 50 blow-off caps, or Part No. 77411, which contains 12 blow-off caps. FIGURE 16 OQoQ CB METAL BLOW-OFF CAP The CB Metal Blow-off Cap Package, Part No. 433208, is used for all high temperature environments. The metal blow-oft cap con- tains a special 0-ring placed inside the cap which integrates with the nozzle to create a seal and to help hold the blow-off cap in position. The CB Metal Blow-Off Cap Package, Part No. 433208, contains 10 blow-oft caps. Also available is a 10 pack of CB Stainless Steel Blow-Oft Caps, Part No. 434707. A 10 pack of Metal Blow-Oft Cap 0-rings, Part No. 551530, is also available. STAINLESS STEEL WIRE METAL CAP FIGURE 17 007633 CONDUIT OFFSET ASSEMBLY The conduit offset assembly, Part No. 435961, is used to change direction of the wire rope on detection, mechanical gas valve, and remote pull station lines. The conduit offset assembly can only be used in the area where the conduit attaches to the regulated release assembly. When using the conduit offset assembly, the maximum number of pulley elbows is still allowed. The Conduit Offset Shipping Assembly, Part No. 436063, consists of 6 conduit offsets. CONDUIT COUPLING CONDUIT OFFSET FIGURE 18 000153 "QUIK-SEAL" ADAPTOR The "Quik-Seal" adaptor is a listed mechanical bulkhead fitting that produces a liquid-tight seal around both distribution piping and detection conduit which runs through restaurant hoods and ducts. The "Quik-Seal" adaptor accepts threaded pipe or conduit. The adaptor is available for 1/4 in. (Part No. 78196), 3/8 in. (Part No. 77285), 1/2 in. (Part No. 77287), or 3/4 in. (Part No. 77289) pipe or conduit sizes. When using with EMT conduit, a conduit connector must be installed in each end of the adaptor. The "Quik-Seal" Adaptor Shipping Assembly must be ordered as stated below: Shipping Assembly Hole Size Size Part No. Qty. Required 1/4 in. 78196 24 3/4 in. 3/8 in. 77285 24 11/8 in. 1/2 in. 77287 24 11/8 in. 3/4 in. 77289 24 13/8 in. ADAPTOR BODY GASKET LOCK WASHER NUT FIGURE 19 000154 SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-7 7-1-09 REV. 6 "COMPRESSION-SEAL" ADAPTOR This adaptor is a mechanical bulkhead fitting that produces a liquid-tight seal around pipe and conduit when installing distribu- tion piping and detection conduit through restaurant hoods and ducts. The "Compression-Seal" adaptor is a straight-through design requiring no cutting or threading of conduit or pipe. The o. adaptor is available for pipe sizes of 1/4 in. (Part No. 79149), 3/8 in. (Part No. 79151), 1/2 in. (Part No. 79147), and EMT conduit size of 1/2 in. (Part No. 79153). Each "Compression-Seal" Adaptor Shipping Assembly must be ordered as stated below: Shipping Assembly Hole Size Size Part No. Qty. Required 1/4 in. Pipe / 1/2 in. tube 79149 24 3/4 in. 3/8 in. Pipe / 5/8 in. tube 79151 24 11/8 in. 1/2 in. Pipe 79147 24 11/8 in. 1/2 in. EMT Conduit 79153 24 11/8 in. =D- COMPRESSION NUT ____________________ ADAPTOR BODY GASKET -----o -I LOCK WASHER NUT L3 FIGURE 20 Ol55 "HOOD SEAL" ADAPTOR ASSEMBLY This adaptor is a mechanical bulkhead fitting that produces a liq- uid-tight seal around 1/2 in. EMT conduit when installing the detec- tion line through restaurant hoods and duct. The adaptor accepts a high temperature pulley elbow and, when used, correctly posi- tions the elbow or conduit in line with the conduit adaptor hole in the detector bracket. The "Hood Seal" eliminates the need for mul- tiple elbows when penetrating the top of a hood when installing the detection line. "Hood Seal" Adaptors are available in quantities of 6 as Shipping Assembly Part No. 423253. COCKING LEVER/LOCK BAR The cocking lever is a component required to cock (arm) both the mechanical/electrical ANSUL AUTOMAN release and the mech- anical gas valve. After the ANSUL AUTOMAN is cocked (armed), the lock bar must be inserted to eliminate the accidental firing of the release mechanism. These components are available as either an individual shipping assembly or a shipping assembly containing both. Listed below are the various shipping assembly part num- bers. Part No. Description 435603 Short Handle Cocking Lever only (Mechanical/Electrical ANSUL AUTOMAN) 435790 Short Handle Cocking Lever with Lock Bar (Mechanical/Electrical ANSUL AUTOMAN) 14995 Long Handle Cocking Lever only (Mechanical/Electrical ANSUL AUTOMAN) 15618 Long Handle Cocking Lever with Lock Bar (Mechanical/Electrical ANSUL AUTOMAN) 26310 Cocking Lever only (ANSUL AUTOMAN Il-C) 416018 Cocking Lever only (Mechanical Gas Valve) 14985 Lock Bar Short Handle Cocking Lever "Requires a crescent wrench or open end/box wrench Long Handle Cocking Lever SEAL ADAPTOR BODY - = (NOT PART \•__, OF ASSEMBLY) SEAL NUT Lock Bar USE ONLY PULLEY ELBOW, PART NO. 423250 FIGURE 21 000156 REDUCING COUPLING The reducing coupling, Part No. 436228, is made of stainless steel material with 3/8 in. x 1/2 in. NPT inlet threads. If necessary, the reducing coupling can be utilized when installing the Agent Distribution Hose Line Kit, Part No. 435982. Two couplings are required per Agent Distribution Hose. 1/4 IN. (3.3 cm) Crr . 1 3/16 IN. (3.0 cm) FIGURE 22 O324 FIGURE 23 Dom SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-8 REV.8 7-1-09 DETECTORS The detector consists of three basic components: the bracket, link- age, and fusible link. (Fusible links are not included and must be ordered separately.) The bracket holds the entire assembly to the mounting surface. The linkage is used to support the fusible link. The fusible link is designed to separate at a specific temperature and release the wire rope, thereby actuating the regulated release mechanism. The scissor style detector allows the wire rope to be strung com- pletely through the detection system conduit and brackets first and the detector linkage assemblies are then clipped on later. . The detector consists of two types of assemblies: The Terminal Detector (Part No. 435546) includes a test link and is placed last in a series of detectors. This detector is sometimes referred to as the end-of-line detector and is thus named because it is at the point at which the wire rope "terminates," or is anchored at the detector bracket. Only one terminal detector is required per detection system. The Series Detector (Part No. 435547) is any detector located in- line between the regulated release assembly and the terminal detector. When using Part No. 435546 and 435547 detectors, a total of 15 detectors can be in one detection system: 14 series detectors, Part No. 435547 and 1 terminal detector, Part No. 435546. Note: Series Detector, Part No. 435547, is also available as Part No. 435548, 25/Pkg. SCISSOR STYLE - PART NO. 435546 AND 435547 PULLEY TEE The Pulley Tee (Part No. 427929) is used to change the direction of two wire ropes by 900. It must be used in areas where the tem- peratures are within the range of 32 OF to 130 OF (0 °C to 54 °C). Pulley tees can be used in mechanical gas valve actuation lines and remote manual pull station lines. Pulley tees cannot be used within a detection line. FIGURE 26 0cc447 STAINLESS STEEL CABLE The 1/16 in. stainless steel cable is run from the terminal detector, through conduit, all series detectors and pulley elbows, and into the regulated release mechanism trip lever. When any fusible link separates, the tension on the cable is relaxed, and the trip lever actuates the regulated release mechanism. The cable can also be used for mechanical gas valves and remote manual pull stations. The cable is available in 50 ft (15 m) (Part No. 15821) and 500 ft (152.4 m) (Part No. 79653) lengths. BRACKET / FIGURE 24 O159 PULLEY ELBOWS There are two types of pulley elbows used to change the direction of the wire rope by 900. ANSUL recommends for temperatures not in excess of 700 OF (371 "C). Part No. 415670 has socket ends with set screws for 1/2 in. conduit, and Part No. 423250 has com- pression ring ends also for 1/2 in. conduit. Pulley elbows must be ordered in quantities of 50 as Shipping Assembly Part No. 415671 (socket end type) and Part No. 423251 (compression end type). PART NO. 415670 PART NO. 423250 000160 000161 FIGURE 25 SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-9 7-1-09 REV. 5 REMOTE MANUAL PULL STATION The remote manual pull station (Part No. 434618 or 435960) is made out of a molded red composite material. The red color makes the pull station more readily identifiable as the manual means for fire suppression system operation. The pull station is compatible with the ANSUL Flexible Conduit. The molded manual pull station should be mounted at a point of egress and positioned at a height determined by the authority having jurisdiction. Trim Rings, Part No. 427074 (pack of 10), are available. Part No. 434618 (Without Wire Rope) Part No. 435960 (With 50 ft (15.2 m) of Wire Rope) FIGURE 27 omm FLEXIBLE CONDUIT Flexible conduit allows for quicker installations and the conve- nience of being able to route the cable over, under and around obstacles. Flexible conduit can be used as a substitute for stan- dard EMT conduit or can be used with EMT conduit. Flexible con- duit can be used only with the Molded Manual Pull Station, Part No. 434618, and mechanical gas valve installations. The Flexible Conduit comes in a 500 It (152.4 m) length, Part No. 434525, or together with 500 ft (152.4 m) of wire rope, Part No. 435959. Also available is a Flexible Conduit Strain Relief (50-pack), Part No. 435979. A 50-pack of Flexible Conduit Inserts, Part No. 434347, is also available. Note: Flexible conduit cannot be used in detection systems. MECHANICAL GAS VALVES The mechanical gas valves are designed to shut off the flow of gas to the appliances upon actuation of the regulated release assem- bly. The valves are available in sizes of 3/4 in., 1 in., 1 1/4 in., 1 1/2 in., and 2 in. ANSUL style; and 2 1/2 in. and 3 in. ASCO style. The valves are rated for natural and LP gas. Both styles are UL Listed and includes the air cylinder, tubing, and fittings, Part No. 15733, for connection to the release mechanism. Maximum Part Operating No. Description Pressure 55598 3/4 in. Gas Valve (ANSUL) 10 psi (0.69 bar) 55601 1 in. Gas Valve (ANSUL) 10 psi (0.69 bar) 55604 1 1/4 in. Gas Valve (ANSUL) 10 psi (0.69 bar) 55607 1 1/2 in. Gas Valve (ANSUL) 10 psi (0.69 bar) 55610 2 in. Gas Valve (ANSUL) 10 psi (0.69 bar) 25937 2 1/2 in. Gas Valve (ASCO) 5 psi (0.35 bar) 25938 3 in. Gas Valve (ASCO) 5 psi (0.35 bar) Flow Capacity BTU/HR, at 1 in. P.D. (CFH) 0.64 SP GR Pipe Size P.D. 1 in. WC 1000 BTU/ft3 (inches) 0.64 SP GR Natural Gas 3/4 751 751,000 1 1288 1,288,000 11/4 1718 1,718,000 1 1/2 2630 2,630,000 2 4616 4,616,000 21/2 5700 5,800,000 3 7100 7,300,000 To calculate gas flow for other than 1 inch p.d.: New cfh = (cfh at 1 inch) x / new p.d. To calculate gas flow for other than 0.64 SP GA: New cfh = (cfh at 0.64) x J 0.64 New SP GA A B C Valve Size in. (mm) in. (mm) in. (mm) 3/4 in. 33/4 (95.3) 63/8 (161.9) 51/2 (139.7) 1 in. 33/4 (95.3) 63/8 (161.9) 51/2 (139.7) 11/4 in. 47/8 (123.8) 73/8 (187.3) 63/8 (161.9) 11/2 in. 47/8 (123.8) 73/8 (187.3) 63/8 (161.9) 2in. 57/8 (149.2) 77/8 (200.0) 611/16 (169.9) 2 1/2 in. 713/16 (198.4) 91/16 (230.2) 3 in. 725/32 (197.6) 91/16 (230.2) 3/4 IN. THRU 2 IN. 42O8 2 1/2 IN. THRU 3 IN. 42O9 FIGURE 28 N.O. COM Valve A B Size in. (mm) in. (mm) 3/4 in. 35/16 (81.0) 35/8 (92.1) 1 in. 5 (127.0) 627/32 (173.8) 11/4 in. 713/16 (198.4) 729/32 (200.8) 11/2 in. 5 (127.0) 519/32 (142.1) 2in. 63/32 (78.6) 515/16 (150.8) 2 1/2 in. 713/16 (198.4) 729/32 (200.8) 3 in. 713/16 (198.4) 729/32 (200.8) SECTION III -SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-10 REV.4 7-1-09 ELECTRICAL GAS VALVES The electrical gas valves are designed to shut off the flow of either natural or LP gas to the appliances upon actuation of the regulat- ed release assembly. The valves are available in sizes of 3/4 in., 1 in., 1 1/4 in., 1 1/2 in., 2 in., 2 1/2 in., and 3 in. The valve is held open by an energized solenoid and upon system actuation, the switch contacts in the regulated release assembly open, thus de- energizing the circuit to the gas valve solenoid, causing the valve to close. Valves are available in 120 VAC and are UL Listed. Part Max. Operating No. Description Pressure 13707 3/4 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 13708 1 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 550360 1 1/4 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 13709 1 1/2 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 13710 2 in. Solenoid Gas Valve (ASCO) 25 psi (1.7 bar) 550363 2 1/2 in. Solenoid Gas Valve (ASCO) 5 psi (0.35 bar) 17643 3 in. Solenoid Gas Valve (ASCO) 5 psi (0.35 bar) Flow Capacity BTU/HR, at 1 in. P.D. (CFH) 0.64 SP GR Pipe Size P.D. 1 in. WC 1000 BTU/ft3 (inches) 0.64 SP GR Natural Gas 3/4 264.96 247,500 1 1091.01 1,119,000 1 1/4 1662.49 1,730,000 1 1/2 1818.35 1,900,000 2 3117.18 3,251,000 2112 6078.49 5,821,000 3 7169.51 7,430,000 To calculate gas flow for other than 1 inch p.d.: New cfh = (cfh at 1 inch) x .1 new p.d. To calculate gas flow for other than 0.64 SP GR: New cfh = (cfh at 0.64) x J 0.64 New SP GA MANUAL RESET RELAY The Manual Reset Relay, Part No. 426151, is required when using an electrical gas valve shut-off system. After the electric gas valve has closed, either due to system actuation or power failure, the valve cannot be re-opened, allowing gas to flow, until the reset relay button is manually pressed, re-energizing the circuit. The reset relay is available 120 VAC. The manual reset relay is also recommended for electrical shut down. FIGURE 30 =0081 ELECTRICAL SWITCHES The electrical switches are intended for use with electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-oft devices and other electrical devices that are designed to shut off or turn on when the system is actuated. Switches are available in kits: One Switch Kit, Part No. 423878, Two Switch Kit, Part No. 423879, Three Switch Kit, Part No. 423880, and Four Switch Kit, Part No. 423881. Mounting hardware and 12 in. (305 mm) long wire leads are provided with each kit. Each switch has a set of single-pole, double-throw contacts rated at: UL/cUL/CSA Rating ENEC Rating 250 VAC, 21 A Resistive lE4T10511 Approved 250 VAC, 2 HP 250V, 21A Resistive 125 VAC, 1 HP 8A Motor Load FIGURE 31 001612 FIGURE 29 004210 SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-11 7-1-09 REV. 1 ALARM INITIATING SWITCH The Alarm Initiating Switch Kit, Part No. 428311, can be field mounted within the ANSUL AUTOMAN release. This switch must be used to close a supervised alarm circuit to the building main fire alarm panel when the ANSUL AUTOMAN release actuates. This action will signal the fire alarm panel that there was a system actu- ation in the kitchen area. The switch kit contains all necessary mounting components along with a mounting instruction sheet. The switch is rated 50 mA, 28 VDC. SPACER TOWARD ANSUL WHEN SPACER AND AUTOMAN SWITCH ARE PROPERLY MOUNTED, THIS DIVIDER MUST BE BETWEEN THE N.C. AND NC. TERMINALS COM N.C. N.C. ALARM INITIATING SWITCH FIGURE 32 000890 REGULATOR TEST KIT The Test Kit Assembly (Shipping Part No. 56972) is required to test the regulator setting and nitrogen flow during 12-year maintenance examinations. This will ensure that the regulator is functioning properly. - ..___g•w••• ..i_ FIGURE 33 000189 FUSIBLE LINK Select correct UL Listed fusible link(s) for installation in detector(s) according to the temperature condition chart below: K STYLE Fusible Link To Be Used Fusible Shipping Where Link Assembly Temperature Temperature Part No. Part No. Rating Does Not Exceed 415739(1) 415739(1) 165°F (74°C) 100°F (38°C) 415740(1) 415740(1) 212°F(100°C) 150°F (66°C) 415741(l) 415744(25) 280°F(138°C) 225 °F(107°C) 415742(1) 415745 (25) 360°F (182 °C) 290°F (143 °C) 415743(1) 415746 (25) 450°F (232 °C) 360 °F (182 °C) ML STYLE Fusible Link To Be Used Fusible Shipping Where Link Part No. Assembly Part No. Temperature Rating Temperature Does Not Exceed 550368(1) 551522(10) 165°F (74°C) 100°F (38°C) 550365(1) 551523 (10) 212°F (100 °C) 150°F (66 °C) 550366(1) 551524(10) 280°F (138 °C) 225°F (107 °C) 550009(l) 551525 (10) 360°F (182 °C) 290°F (143 °C) 550367(1) 551526(10) 450°F (232 °C) 360°F (182 °C) 56816(l) 551527(10) 500 °F (260 °C) 400°F (204 °C) 56816(l) 73867 (25) 500 °F (260 °C) 400 °F (204 °C) 901909.. TEMPERATURE RATING STAMPED ON FUSIBLE LINK BODY o K STYLE ML STYLE 000170 000171 FIGURE 34 MAXIMUM REGISTERING THERMOMETER The Maximum Registering Thermometer, Part No. 15240, may be used to indicate the highest normal temperature for the protected area. Once this is established, the correct rated fusible link can be chosen. Other methods for determining maximum temperatures may be used. HOSE/GROMMET PACKAGE The Hose/Grommet Package, Part No. 418511, consists of a 24 in. rubber hose and 2 (two) grommets. This package is required when expellant gas hose is routed outside the ANSUL AUTOMAN Regulated Release, Regulated Actuator, and/or tank enclosure assemblies. FIGURE 35 008399 RED SIDE OF B DISC TOBE M ADAPTOR, PART NO. 417707 FIGURE 38 MUM SECTION III - SYSTEM COMPONENTS UL EX3470 ULC EX3470 Page 3-12 REV. 1 7-1-09 IN-LINE BURST DISC ASSEMBLY (MANIFOLDED SYSTEMS I ONLY) The in-line burst disc assembly is required to eliminate the siphon- ing of the agent up the pipe during extreme temperature variations. In addition to eliminating the siphoning effect, the common in-line burst disc assembly eliminates the possibility of one or more indi- vidual discs located in the tank adaptor from failing to burst. The assembly consists of a stainless steel body which houses the burst disc. When utilizing this assembly in a manifolded system, it is necessary to modify (remove) the burst disc located in all of the R-1 02 tank adaptors in the system. The in-line burst disc assem- bly is to be mounted as close to the tank outlet as possible. After system discharge, the assembly must be disassembled and a new burst disc installed. Part No. Description 416970 In-Line Burst Disc Assembly 417911 Burst Disc (Pack of 10) NOZZLE AIMING DEVICE The Nozzle Aiming Device, Part No. 431992, is available to prop- erly aim each nozzle to the correct aiming point. The device clamps to the nozzle and emits a small laser light that reflects on the surface that it is aiming at. The nozzle can then be rotated to point at a predetermined aiming point and then tightened to hold that angle. The aiming device adaptor attaches to the nozzle. The shipping assembly consists of the aiming device and the adaptor. C'l ADAPTOR NOZZLE AIMING DEVICE FIGURE 37 008520 STAINLESS STEEL BRAIDED ACTUATION HOSE The Stainless Steel Actuation Hose is used to connect the actua- tion line compression tees between each pneumatic actuator. The hose has the same thread, 7/16-20, as the fittings. The actuation hose allows flexibility between the AUTOMAN and each regulated actuator. Hose Part No. Length Couplings 31809 16 in. (41 cm) 7/16-20 x 7/16-20 Females 32335 20 in. (51 cm) 7/16-20 x 7/16-20 Females 32336 24 in. (61 cm) 7/16-20 x 7/16-20 Females 430815 42 in. (107 cm) 7/16-20 Female x 1/4 in. NPT Fitting Part No. Description 31810 Male Elbow (7/16-20 x 1/4 in. NPT) 31811 Male Tee (7/16-20 x 7/16-20 x 1/4 in. NPT) 415371 Tee (7/16-20 x 1/8 in. Male NPTx 1/8 in. Female NPT) 32338 Male Straight Connector (7/16-20 x 1/4 in. NPT) 25627 1/4 in. Check Valve 1/4 IN. CHECK VALVE The 1/4 in. check valve, Part No. 25627, blocks the flow of actua- tion gas from the actuator that was actuated to the actuator(s) that was not actuated. This prevents actuation gas from escaping from an open actuator which may have had the cartridge removed. CHECK VALVE PART NO. 25627 !' AGENT DISTRIBUTION HOSE AND RESTRAINING CABLE KIT The Agent Distribution Hose and Restraining Cable Kit, Part No. 435982, consists of a 5 It (1.5 m) long Agent Distribution Hose, a 3 It (0.9 m) long Restraining Cable, and a Restraining Cable Hardware Package. The Agent Distribution Hose can be utilized with castered cooking appliances with castered supports found in commercial kitchens. The hose allows for movement of the appli- ance for cleaning without having to disconnect any fire suppres- sion system discharge piping. Note: The Agent Distribution Hose is authorized for use with only UL Listed ANSUL Wet Chemical Restaurant Fire Suppression Systems. /NN 1/4 IN. NPT (0.6 cm) 2 IN. (5.1 cm) FIGURE 36 000899 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-1 7-1-09 REV. 8 SYSTEM DESIGN The ANSUL R-102 Restaurant Fire Suppression System may be used on a number of different types of restaurant cooking appli- ances and hood and duct configurations. The design information listed in this section deals with the limitations and parameters of this pre-engineered system. Those individuals responsible for the design of the R-102 system must be trained and hold a current ANSUL certificate in an R-102 training program. The R-1 02 and the PIRANHA systems use compatible agents and components, therefore, they may be used together for cooking appliance, hood, and duct protection. The primary ANSUL AUTOMAN Release can be either an R-102 or a PIRANHA ANSUL AUTOMAN Release and can actuate up to two additional R-102 or PIRANHA Regulated Actuators. In systems utilizing a 101 remote release, any combination of the maximum number of regulated actuators can be used. Both systems must actuate simultaneously. Each system must be designed and installed per its appropri- ate manual. Adjacent appliances requiring protection must be protected with the same type of system, either R-102 or PIRANHA, unless the center-to-center spacing between the adjacent R-102 and PIRANHA nozzles is no less than 36 in. (91.4 cm). When appliances are protected with R-102 nozzles, the hood and connecting duct above those appliances cannot be pro- tected with PIRANHA nozzles. Mixing systems in a common plenum is not allowed. One of the key elements for restaurant fire protection is a correct system design. This section is divided into ten sub-sections: Noz- zle Placement Requirements, Tank Quantity Requirements, Actu- ation and Expellant Gas Line Requirements, Distribution Piping Requirements, Detection System Requirements, Manual Pull Sta- tion Requirements, Mechanical Gas Valve Requirements, Electri- cal Gas Valve Requirements, Electrical Switch Requirements, and Pressure Switch Requirements. Each of these sections must be completed before attempting any installation. System design sketches should be made of all aspects of design for reference during installation. NOZZLE PLACEMENT REQUIREMENTS This section gives guidelines for nozzle type, positioning, and quantity for duct, plenum, and individual appliance protection. This section must be completed before determining tank quantity and piping requirements. Duct Protection - Single Nozzle All duct protection is UL listed without limitation of maximum duct length (unlimited length). This includes all varieties of ductworks both horizontal and vertical including ducts that run at angles to the horizontal and ducts with directional bends. The R-102 system uses different duct nozzles depending on the size of duct being protected. GENERAL INFORMATION 1. Nozzles must be located 2-8 in. (5-20 cm) into the center of the duct opening, discharging up. See Figure 1. 2-8 IN. (5-20 cm) FIGURE 1 0m173 In installations where a UL listed damper assembly is employed, the duct nozzle can be installed beyond the 8 in. (20 cm) maximum, to a point just beyond the damper assem- bly that will not interfere with the damper. Exceeding the maxi- mum of 8 in. (20 cm) in this way will not void the UL listing of the system. Previously listed 3 flow number and 5 flow number duct pro- tection detailed in earlier published manual, Part No. 418087- 06, can also still by utilized. DUCT SIZES UP TO 50 IN. (127 cm) PERIMETER! 16 IN. (41 cm) DIAMETER One 1W nozzle (Part No. 419336) = one flow number 50 in. (127 cm) perimeter maximum 16 in. (41 cm) diameter maximum DUCT SIZES UP TO 100 IN. (254 cm) PERIMETER! 32 IN. (81.3 cm) DIAMETER One 2W Nozzle (Part No. 419337) = two flow numbers 100 in. (254 cm) perimeter maximum 32 in. (81.3 cm) diameter maximum The chart below shows the maximum protection available from each duct nozzle. Part 3.0 Gallon 1.5 Gallon Description No. System System 2W Nozzle 419337 Maximum Maximum 100 in. (254 cm) 100 in. (254 cm) Perimeter Perimeter 1W Nozzle 419336 Maximum Maximum 50 in. (127 cm) 50 in. (127 cm) Perimeter Perimeter SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-2 REV.4 4-1-06 Duct Protection - Multiple Nozzle DUCT SIZES UP TO 135 IN. (343 cm) PERIMETER -3 FLOW OPTION One 1W Nozzle (Part No. 419336) and one 2W Nozzle (Part No. 419337) = three flow numbers 135 in. (343 cm) perimeter maximum No round duct option available Follow design table in Figure 2 to determine maximum module size for each nozzle 1W Module 2W Module Side A Side B Side B Side B Maximum Maximum Maximum Maximum 4 (10) 60.0 (152) 23.0 (58) 37.0 (94) 5 (13) 60.0 (152) 23.0 (58) 37.0 (94) 6 (15) 59.5 (151) 22.5 (57) 37.0 (94) 7 (18) 59.0 (150) 22.0 (56) 37.0 (94) 8 (20) 58.5 (149) 22.0 (56) 36.5 (93) 9 (23) 58.0 (147) 21.5 (55) 36.5 (93) 10 (25) 57.0 (145) 21.0 (53) 36.0 (91) 11 (28) 56.0 (142) 20.5 (52) 35.5 (90) 12 (31) 55.5 (141) 20.0 (51) 35.5 (90) 13 (33) 54.5 (138) 19.5 (50) 35.0 (89) 14 (36) 53.5 (136) 18.5 (47) 35.0 (89) 15 (38) 52.0 (132) 18.0 (46) 34.0 (86) 16 (41) 51.0 (130) 17.0 (43) 34.0 (86) 17 (43) 49.5 (126) 16.0 (41) 33.5 (85) 18 (46) 47.5 (121) 14.5 (37) 33.0 (84) 19 (48) 46.0 (117) 13.5 (34) 32.5 (83) 20 (51) 43.5 (111) 12.0 (31) 31.7 (81) 21 (53) 41.0 (104) 10.0 (25) 31.0 (79) 22 (56) 38.0 (97) 7.5 (19) 30.5 (78) 23 (58) 33.5 (85) 4.0 (10) 29.5 (75) 4 ISideB I ISideA I iwl I2WI FIGURE 2 O52l Example: Protection is required for a duct that has an "A" dimen- sion of 8.0 in. (20 cm) wide and a "B" dimension of 55 in. (140 cm) long. Referring to the table in Figure 2, if the "A" dimension is 8.0 in. (20 cm), the "B" dimension must not exceed 58.5 in. (149 cm). In this example, the "B" dimension is 55 in. (140 cm), therefore, this duct can be protected with a three flow application. Read over from the 8.0 in. (20 cm) line on the table to the 1W Module column. At that point, the chart shows that the "B" module length for the 1W nozzle can be 22.0 in. (56 cm). Center the 1W nozzle in that module. The 2W module can now be centered with- in the remaining module. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-3 7-1-09 REV.5 Duct Protection - Multiple Nozzle (Continued) DUCT SIZES GREATER THAN 100 IN. (254 cm) PERIMETER Ducts over 100 in. (254 cm) perimeter may be modularized using 2W nozzles (Part No. 419337) No round duct option available Follow the design chart to determine maximum module size for each 2W nozzle When determining number of nozzles required, it is sometimes an advantage to check the chart using the shortest side as Side "A" and then recheck it using the longest side as Side "A". This comparison may reveal a need for a lesser quantity of nozzles one way versus the other way. When working with Chart 1, the quantity of nozzles determined must be equally divided within the duct area. When working with Chart 2, one half of the quantity of nozzles determined must be equally positioned in the top half of the area of the duct and the remaining half of the nozzles must be posi- tioned in the bottom half of the duct area. Example: The duct to be protected has a Side "A" of 40 in. (101.6 cm) and a Side "B" of 60 in. (152.4 cm). Referring to the design chart, this duct requires 4 nozzles. One half of 4 = 2. Therefore, 2 nozzles must be equally positioned in each of the two duct areas. See Figure 3. SIDE "B" 30 IN. (76 cm) 30 IN. (76 cm) 20 IN. . (51 CM) I SIDE "A" 20 IN. I (51 cm) 40 IN. (102 cm) CHART NO.1 Al.. . In. SIDE "B" cm 60 IN. (152 cm) FIGURE 3 I 0D0 0 Ell Ell F3 Ell Ea 0 Ell MEII Mm ••u•••uuuuu•••••uuiEEI u 13 CHART NO.2 B NOTE: NOZZLE QUANTITIES LISTED IN CHART 2 MUST BE EQUALLY DIVIDED INTO EACH OF ThE TWO DUCT MODULES. uuunu••uuu•u••auui•m•• 13 0 SIDE "A" In. SIDE "A" CM 006522 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-4 REV.7 7-1-09 Transition Protection Transitions are protected at a point in the transition where the perimeter or the diameter is equal to or less than the maximum size duct that can be protected. The nozzle(s) must be located in the center of the area at that point, or center of the module pro- tected when more than one duct nozzle is required. Note: Nozzles to protect ducts with a transition that is more than 4 ft (1.2 m) in height, will be required to be positioned in the opening of the transition from the hood 2 to 8 in. (5.1 to 20.3 cm) into the opening using standard duct nozzle design parameters. See Figure 4. FIGURE 4 000174 Electrostatic Precipitator Protection Some restaurant ventilating ducts have an electrostatic precipita- tor installed at or near the base. These precipitators are generally small and are used to aid in the cleaning of exhaust air. Ducts with precipitators located at or near the base can be pro- tected using duct nozzle(s) above the precipitator and 1/2N noz- zle(s) (Part No. 419334) for the precipitator. One 1/2N nozzle must be used for each cell being protected. This nozzle tip is stamped with 1/2N, indicating that it is a 1/2-flow nozzle and must be count- ed as 1/2 flow number. When protecting ducts equipped with precipitators, the duct noz- zle(s) must be installed above the precipitator and aimed to dis- charge downstream. If the area above the precipitator is a duct, the nozzle(s) must be positioned according to duct protection guide- lines. If the area above the precipitator is a transition, the transition guidelines must be followed. The 1/2N nozzle (Part No. 419334) must be centered 10 to 26 in. (25 to 66 cm) below the precipitator and aimed to discharge at the center of each precipitator cell. However, if it is physically impossi- ble to mount the nozzle at 10 to 26 in. (25 to 66 cm) due to pre- cipitator placement, the nozzle may be mounted closer than 10 in. (25 cm). See Figure 5. DUCT II I II SEE DUCT FOR II i II TRANSITION I NOZZLE I I II PROTECTION PRECIPITATOR - 10.261N. (25.66 cm) I NOZZLE FOR PRECIPITATOR PROTECTION IF PHYSICALLY IMPOSSIBLE AT 10 TO 26 IN. (25 TO 66 cm), NOZZLE MAY BE MOUNTED CLOSER THAN 10 IN. (25 cm). FIGURE 5 I96 Note: For protection of Pollution Control Units (PCUs) or air scrub- bers with or without ESPs, contact Ansul Technical Services for non-UL listed recommended application. 20 IN. (51 cm) MAXIMUM 1 IN. (2.5 cm) MINIMUM SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-5 7-1-09 REV. 5 Plenum Protection The R-102 system uses the 1W Nozzle (Part No. 419336) or the 1 N Nozzle (Part No. 419335) for plenum protection. The 1W noz- zle tip is stamped with 1W and the 1 N nozzle tip is stamped with 1 N, indicating they are one-flow nozzles and must be counted as one flow number each. When protecting a plenum chamber, the entire chamber must be protected regardless of filter length. VERTICAL PROTECTION - GENERAL 1W NOZZLE - PART NO. 419336 - SINGLE AND "V" BANK ' PROTECTION One 1W nozzle will protect 4 linear feet (1.2 m) of plenum. The maximum distance from the end of the hood to the first and last nozzle must be no more than 2 ft (0.6 m). After the first nozzle, any additional nozzles must be positioned at a maximum of 4 ft (1.2 m) apart down the entire length of the plenum. The plenum width must not exceed 4 It (1.2 m). (The 1W nozzle can be used on single or V-bank filter arrangements.) See Figure 6. 2FT(0.6m) MAXIMUM 4FT(1.2m) 4FT(1.2m) MAXIMUMl..— ..- "....4FT(1.2m) 2 FT (0.6 m) MAXUvIUM MAXIMUM FIGURE 6 omigi When protecting plenums with the 1W nozzle, two options of cov- erage are available: Option 1: The 1W nozzle must be on the center line of the single or "V" bank filter and positioned within 1-20 in. (2.5-51 cm) above the top edge of the filter. See Figure 7. (51 cm) IUM FIGURE 7 000199 Option 2: The 1W nozzle must be placed perpendicular, 8-12 in. (20-30 cm) from the face of the filter and angled to the center of the filter. The nozzle tip must be within 2 in. (5 cm) from the perpendicular center line of the filter. See Figure 8. 12 IN. (30 cm) MAXIMUM BIN. (20 cm) MINIMUM NOZZLE TIP - MUST BE WITHIN THIS AREA FIGURE 8 000 HORIZONTAL PROTECTION - OPTION 1 1 NOZZLE - PART NO. 419335— SINGLE BANK PROTECTION One 1 N nozzle will protect 10 linear feet (3.1 m) of single filter bank plenum. The nozzle(s) must be mounted in the plenum, 2 to 4 in. (5 to 10 cm) from the face of the filter, centered between the filter height dimension, and aimed down the length. The nozzle must be positioned 0-6 in. (0-15 cm) from the end of the hood to the tip of the nozzle. See Figure 9. FIGURE 9 FIGURE 13 000207 FIGURE 14 000206 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-6 REV. 7 7-1-09 Plenum Protection (Continued) HORIZONTAL PROTECTION - OPTION 2 1W NOZZLE - PART NO. 419336 - 'V" BANK PROTECTION One 1W nozzle will protect 6 linear feet (1.8 m) of "V" bank plenum. The nozzle must be mounted horizontally, positioned 1/3 the filter height down from the top of the filter. Nozzles can be located at 6 ft (1.8 m) spacings on longer plenums. The nozzle must be positioned 0-6 in. (0-15 cm) from the end of the hood to the tip of the nozzle. See Figure 10. 1W NOZZLE FIGURE 10 006524 TWO (2) 1 NOZZLES - PART NO. 419335 - "V" BANK PRO- TECTION Two 1 nozzles will protect 10 linear feet (3.1 m) by 4 ft (1.2 m) wide of "V" bank plenum. The nozzles must be mounted in the plenum, 2 to 4 in. (5 to 10 cm) from the face of the filter, centered between the filter height dimension, and aimed down the length. The nozzle must be positioned 0-6 in. (0-15 cm) from the end of the hood to the tip of the nozzle. See Figure ii. For a plenum, either single or "V" bank, with a linear extension longer than 10 ft (3.1 m), each bank may be protected using one 1 nozzle every 10 ft (3.1 m) or less depending on the overall length of the plenum. See Figure 12. The nozzles may point in the opposite directions as long as the entire plenum area is protected, and the 10 It (3.1 m) limitation is not exceeded. See Figure 13. The nozzle positioning shown in Figure 14 is not an acceptable method of protection because the plenum area directly under the tee is not within the discharge pattern of either nozzle. 10FT(3.1 m) MAXIMUM I0FT(3.1 m) MAXIMUM 10FT(3.1 m) MAXIMUM Fr (9.1 m) FIGURE 12 000206 10PT(3.1 m) MAXIMUM 10FT(3.1 m) MAXIMUM 10 PT (3.1 m) MAXIMUM Fr (9.1 m) 2 FIGURE 11 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-7 10-1-02 REV.3 Appliance Protection The following pages detail types of appliance protection. Each design requires several factors: correct nozzle choice, correct noz- zle height above hazard, correct nozzle location and correct aim- ing point. Fryer - Single Nozzle Protection 1. Design requirements for flyers are broken down into two types. FRYERS WITHOUT DRIPBOARDS If the fryer does not include a dripboard, measure the internal depth (horizontal dimension from front to back) and length of the frypot. FRYERS WITH DRIPBOARDS If the fryer includes any dripboard areas, measure both the internal depth (horizontal dimension from front to back) and length of the frypot portion, and then measure the internal depth and length of the overall hazard area including any dripboard areas. 2. Using Table, "Maximum Cooking Area Dimension - Single Nozzle Fryer Protection:' determine which nozzle is needed to protect the flyer based on the maximum dimensions listed. If the fryer does not include a dripboard, use the maxi- mum dimensions listed in the first column of the table to select the correct nozzle. If the fryer includes any dripboard areas, use both the maximum frypot dimensions in the first column of the table, and the maximum overall dimensions in the second column of the table to select the correct nozzle. None of the maximum dimensions in either column may be exceeded. 3. If either the maximum frypot or the overall sizes are exceed- ed, an additional nozzle(s) will be required. Refer to the mul- tiple nozzle requirements. Example: A fryer with a dripboard. The inside of the frypot without the dripboard measures 18 in. in depth x 18 in. in length (46 cm x 46 cm) and the inside of the overall area including the dripboard measures 18 in. in depth x 24 in. in length (46 cm 61 cm). From the Table "Maximum Cooking Area Dimension - Single Nozzle Fryer Protection," either the 3N or the 290 nozzle should be select- ed to protect the fryer, depending on the maximum nozzle height above the fryer and the positioning requirements allowed. Refer to appropriate Figures. Liz TOP OF FRYER SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-8 REV. 6 4-1-06 Fryer - Single Nozzle Protection (Continued) Maximum Area Dimensions - Single Nozzle Fryer Protection Max. Size Max. Size Overall Type of Nozzle Height Frypot Only With Dripboard Nozzle Above Top of Fryer Full or Split Vat Full or Split Vat 230 27 in. to 47 in. l4 in. xl5in. l4 in. x2lin. (69cmtoll9cm) (36cmx38cm) (36cmx53cm) Full or Split Vat Full or Split Vat 245 20 in. to 27 in. 14 in. x 15 in. 14 in. x 21 in. (51 cm to 69 cm) (36cmx38cm) (36cmx53cm) Full or Split Vat Full or Split Vat 290 13 in. to 16 in. l4 in. xl5in. 14 in. x2lin. (33cmt041cm) (36cmx38cm) (36cmx53cm) Full or Split Vat Full or Split Vat 290 16 in. to 27 in. 14 1/2 in. x14 in. 14 1/2 in. x26 1/2 in. (41 cm to 69 cm) .(37cmx38cm) (37cmx67cm) Nozzle Location See Figure 15 and 16 See Figure 15 and 16 See Figure 17 See Figure 17 FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOKING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA. FIGURE 15 O2 FRYER WITHOUT DRIPBOARD -- II I I I I )F FRYER Ift \t FRYER WITH DRIPBOARD SPLIT VAT NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOKING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA. FIGURE 16 O2 TOP OF FRYER SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-9 4-1-06 REV. 8 Fryer - Single Nozzle Protection (Continued) Maximum Area Dimensions - Single Nozzle Fryer Protection (Continued) - Max. Size Max. Size Overall Type of Nozzle Height Frypot Only With Dripboard Nozzle Above Top of Fryer 19.5 in. xl9in. 19.5 in. x 25 3/8 in. 290 l3 in. tol6in. (50 cm x 48 cm) (50 cm x 65 cm) (33 to 41 cm) 19.5 in. x 19 in. 19.5 in. x 253/8 in. 3N See Figure (50cmx48cm) (50cmx65cm) 18 'l8 in. xl8in. l8 in. x273/4in. 3N 25 in. t035in. (46 cm x 46 cm) (46 cm x 70.5 cm) (64 cm to 89 cm) Nozzle Location See Figure 17 See Figure 18 See Figure 19 FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD 290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE HAZARD AREA* 3 IN. (7.6 cm) FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE HAZARD AND* I IN. (2.5 cm) FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE HAZARD AND AIMED AT THE MIDPOINT OF THE COOKING AREA. FIGURE 17 oonm 34 IN. (86 cm) MAXIMUM DIAGONAL DISTANCE BETWEEN NOZZLE AND CENTER OF HAZARD AREA FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD 3N NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOKING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA. FIGURE 18 002287 000010 RIGHT4O.LEFT CENTERLINE FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD NOTE: 3N NOZZLE TIP MUST BE LOCATED WITHIN THE PERIMETER OF THE SURFACE AREA WITHIN THE FRONT HALF OF THE FRY POT AND AIMED AT THE CENTER. FIGURE 19 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-10 REV. 7 7-1-09 Fryer - Multiple Nozzle Protection Design Requirements: Fryers exceeding the coverage of a single nozzle can be divided into modules. Each module must not exceed the maximum area allowed for a single nozzle. However, when utilizing multiple nozzle protection, the longest side allowed for a fryer with dripboard can be used, regardless of whether the fryer has a dripboard or not. The maximum size fryer that can be modularized is 864 in.2 (5574 cm2) or in terms of it, 6 ft2 (0.6 m2). 1. Design requirements for multiple nozzle fryers are broken down into two types: FRYERS WITHOUT DRIPBOARD(S) If the fryer does not include a dripboard, measure the inter- nal depth (horizontal dimension from front to back) and length of the frypot. Then, multiply the depth and length to obtain the area of the frypot in square inches. FRYERS WITH DRIPBOARD(S) If the fryer includes any dripboard areas, measure both the internal depth and length of the frypot portion, and then measure the internal depth and length of the overall hazard area including any dripboard areas. Determine the area of both the frypot and the area of the overall vat by multiplying corresponding depth and length dimensions. 2. Divide the frypot or overall vat into modules, each of which can be protected by a single nozzle, based on the maximum dimension and area coverage of the nozzle as specified in Table, 'Maximum Cooking Area Dimension - Multiple Nozzle Protection." If the module considered does not include any portion of the dripboard, use only the maximum frypot area and max- imum dimension listed in the first column of the table to select the correct nozzle. If the module considered includes any dripboard areas, use both the maximum frypot area and dimension listed in the first column of the table, and the maximum overall area and dimensions listed in the second column of the table to select the correct nozzle. 3. None of the maximum dimensions in either column may be exceeded. If either the maximum frypot or the overall sizes are exceeded, the area divided into modules will need to be rede- fined with the possibility of an additional nozzle. Options For Modularizing Fryers The following Figure 20 shows approved methods of dividing (mod- ularizing) fryers so that each section can be properly protected. Example: A fryer with a dripboard. The inside vat without The drip- board measures 18 in. in depth x 30 in. in length (46 cm. x 76 cm) and The inside of the overall vat including The dripboard measures 24 in. in depth x 30 in. in length (61 cm 76 cm). Because The fryer is 30 in. (76 cm) in length, it exceeds the coverage of a single nozzle. Dividing The length in half each module now has an overall vat dimension of 24 in. in depth x 15 in. in length (61 x 38 cm). From the Table, 'Maximum Cooking Area Dimension - Multiple Nozzle Fryer Protection," either the 3N or the 290 nozzle should be select- ed to protect each fryer module, depending on the maximum noz- zle height above the fryer and The positioning requirements allowed. Refer to appropriate Figures, 15 through 19. See additional examples in Appendix Section. AREA OF EACH FRY POT MODULE CANNOT EXCEED 324 IN.2 (2090 cm2) EACH MODULAR AREA, INCLUDING DRIPBOARD, MUST NOT EXCEED 497 IN.2 (3207 cm2) MIDPOINT + MIDPOINT + DRIP BOARD DRIP BOARD 0m214 EXAMPLE ONLY FRYER WITH DRIPBOARD AREA OF EACH FRY POT MODULE 77-CANNOT EXCEED 324 IN.2 (2090cm2) AREA OF THIS I MODULE (FRY I POT PLUS DRIP BOARD) CANNOT EXCEED 497 IN.2 13206 cm2 000215 EXAMPLE ONLY FRYER WITHOUT DRIPBOARD DRIP BOARD EXAMPLE ONLY FRYER WITH DRIPBOARD FIGURE 20 FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD POSITION NOZZLE TIP ANYWHERE ALONG OR WITHIN THE PERIMETER OF THE MODULE IT IS PROTECTING AND AIM AT THE MIDPOINT OF THAT MODULAR AREA. FIGURE 21 FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD 3N NOZZLE TIP MUST BE POSITIONED ANYWHERE ALONG OR WITHIN THE PERIMETER OF THE MODULAR IT IS PROTECTING AND AIMED AT THE MIDPOINT OF THAT RESPECTIVE MODULE AREA. FIGURE 23 34 IN. (86 cm) MAXIMUM DIAGONAL BETWEEN NOZZLE CENTER I RD AREA 21 in. (53 MINIMUM VERTICAL NOZZLE HEIGHT AIM POINT (DIAGONAL CENTER OF MODULE COOKING AREA) RIGHT-TO- LEFT CENTER- LINE FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD I AIM POINT (DIAGONAL I CENTER OF MODULE COOKING AREA) 0-LEFT ILINE SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-11 4-1-06 REV.8 Fryer - Multiple Nozzle Protection (Continued) Maximum Area Dimension - Multiple Nozzle Fryer Protection Max. Size Module Max. Size Module Overall Type of Nozzle Height Nozzle Frypot Only With Dripboard Nozzle Above Top of Fryer Location Full or Split Vat Full or Split Vat 21 in. x 210 in.2 21 in. x 294 in.2 230 27 in. to 47 in. See Figure 21 (53 cm 0.14 m2) (53 cm 0.19 m2) (69 cm to 119 cm) Full or Split Vat Full or Split Vat 21 in. x 210 in.2 21 in. x 294 in.2 245 20 in. to 27 in. See Figure 21 (53 cm 0.14 m2) (53 cm 0.19 m2) (51 to 69 cm) Full or Split Vat Full or Split Vat 21 in. x 210 in.2 21 in. x 294 in.2 290 13 in. to 16 in. See Figure 22 (53 cm x 0.14 m2) (53 cm x 0.19 m2) (33t041 cm) 253/8 x 370.5 in2 253/8 x 495 in2 290 13 in. to 16 in. See Figure 22 (65 cm x 0.24 m2) (65 cm x 0.32 m2) (33 to 41 cm) Full or Split Vat Full or Split Vat 26 1/2 in. x 203 in.2 26 1/2 in. x 384 1/4 in.2 290 16 in. to 27 in. See Figure 22 (67 cm x 0.13 m2) (67 cm x 0.25 m2) (41 t069cm) 253/8 x 370.5 in2 25 3/8 x 495 in2 3N See Figure 23 See Figure 23 (65 cm x 0.24 m2) (65 cm x 0.32 m2) 27 3/4 x 324 in.2 273/4 x 497 in2 3N 25 in. to 35 in. See Figure 24 (70.5 cm x 0.21 m2) (70.5 cm x 0.32 m2) (64 cm to 89 cm) FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD 290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE RESPECTIVE MODULAR AREA ± 3 IN. (7.6 cm) FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE MODULE AND * I IN. (2.5 cm) FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE MODULE AND AIMED AT THE MIDPOINT OF THE MODULE. THE 3N NOZZLE TIP MUST BE POSITIONED ANYWHERE ALONG OR WITHIN THE PERIMETER AND FORWARD OF THE RIGHT-TO-LEFT CENTERLINE OF THE COOKING AREA. THE AIMING POINT OF THE NOZZLE MUST BE AT THE DIAGONAL CENTER OF THE MODULAR COOKING AREA. FIGURE 22 FIGURE 24 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-12 REV. 6 7-1-09 Multiple Nozzle Fryer Protection —Tilt Skillet! Braising Pan Protection for tilt skillets or braising pans is to be based upon the coverage limitations provided for deep fat fryer protection. Refer to Section IV, DESIGN, starting on Page 4-10, for maximum fryer nozzle coverages and maximum fryer nozzle height limitations. Although the maximum 6 ft2 (0.6 m2) total surface cooking area requirement applies to fryer protection, it does not apply to tilt skil- lets or braising pans. Each tilt skillet/braising pan protected module must not exceed the fryer limitations for 'MAXIMUM SIZE MODULE OVERALL WITH DRIPBOARD" coverage per nozzle as described in Table on Page 4-11. Tilt skillets and braising pans generally utilize a hinged cover. Fryer protection nozzles are to be placed toward the front of the appli- ance to minimize the potential for the tilt skillet or braising pan cover to interfere with the nozzle discharge. See Figures 25 and 26. THE NOZZLE IS TO BE PLACED TOWARD THE FRONT OF THE APPLIANCE TO MINIMIZE THE POTENTIAL FOR THE SKILLET OR BRAISING PAN COVER TO INTERFERE WITH THE NOZZLE DISCHARGE. FIGURE 25 COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN FOR MINIMUM AND MAXIMUM NOZZLE HEIGHTS, REFER 10 FRYER NOZZLE PARAMETERS FRYER NOZZLE USED FOR TILT SKILLET OR BRAISING PAN PROTECTION MUST BE POSITIONED NEAR THE FRONT EDGE OF THE PAN AND AIMED AT THE FRONT TO BACK CENTERLINE OF THE PAN. THE DISCHARGE FROM THE NOZZLE(S) MUST COMPLETELY CLEAR THE PAN COVER WITH AN UNOBSTRUCTED VIEW TO THE BACK OF THE PAN. FIGURE 26 / / SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-13 7-1-09 REV. 8 'Range Protection The R-102 system uses five different nozzles for the protection of ranges. Two of the design options require a one-flow nozzle and three of the design options require two-flow nozzles. NOTICE A 13 in. (33 cm) diameter wok pan is the largest wok size that can be protected on ranges. When protecting hot top ranges, the entire cooking surface must be protected. 'Range Protection iN (1-Flow) Nozzle - High Proximity Application No Obstructions Single and multiple burner ranges can be protected using a 1N nozzle, Part No. 419335. The nozzle tip is stamped with 1 N, indi- cating that this is a one-flow nozzle and must be counted as one flow number. When using this nozzle for range protection, the maximum length of the burner grates being protected with a single nozzle must not exceed 32 in. (81 cm) and the maximum area of the burner grates 'must not exceed 384 j2 (2477 cm2) per nozzle. When protecting a range, the 1N nozzle must be located a maxi- mum of 10 in. (25.4 cm) from each burner grate centerline and must be aimed at the center of the cooking surface. See Figures 27 and 28. 1/ IN Ak f4\ T/ 006539 FIGURE 27 10 IN. (25 cm) MAXIMUM 32 I IN. (81 cm) MAXIMUM NOZZLE I AIMING POINT 10 IN. 006540 FIGURE 28 245 NOZZLE TIP LOCATION CENTER 0 COOKING SURFACE OR 113/8 IN. (29 cm) MAXIMUM FROM CENTERLINE OF NOZ TO CENTER OF ANY BURNER GRATE 3NG FIGURE 30 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-14 REV.6 7-1-09 Range Protection 245 (2-Flow) Nozzle - High Proximity Application No Obstructions 40 in. to 50 in. (102 cm to 127 cm) above the cooking surface. This high proximity application uses the 245 nozzle, Part No. 419340. The nozzle tip is stamped with 245 indicating this is a two-flow nozzle and must be counted as two flow numbers. One 245 nozzle will protect a maximum cooking area of 672 in.2 (4335 cm2) with a maximum longest dimension of 28 in. (71 cm). When using this nozzle for range protection, the nozzle must be pointed vertically down and positioned as shown in Figures 29 and 30. 245 NOZZLE TIP LOCATION CENTER 0 COOKING SURFACE OR 113/8 IN. (29 cm) MAXIMUM FROM CENTERLINE OF NOZ TO CENTER OF ANY BURNER GRATE ING 245 NOZZLE TIP LOCATION CENTERLINE OF COOKING SURFACE 5011. (127 cm) MAXIMUM HEIGHT OF 245 NOZZLE TIP 40 IN. (102 cm) MINIMUM HEIGHT OF 245 'NOZZLE I TIP DOOMS FIGURE 29 NOTICE Four burner grates shown in Figure 30. For sin- gle or double burner grates, locate nozzle at center of cooking surface or 11 3/8 in. (29 cm) maximum from nozzle centerline to center of any burner grate. 260 NOZZLE TIP LOCATION CENTER OF COOKING SURFACE OR 10 IN. (25.4 cm) MAXIMUM FROM CENTERLINE OF NOZZLE TO CENTER OF ANY BURNER GRATE 260 NOZZLE TIP LOCATION CENTE OF COOKING SURFACE OR 10 IN. (25.4 cm) MAXIMUM FROM CENTERLINE OF NOZZLE TO CENTER OF ANY BURNER GRATE ING ONG FIGURE 32 00UM NOTICE Four burner grates shown in Figure 32. For sin- gle or double burner grates, locate nozzle at center of cooking surface. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-15 7-1-09 REV. 5 Range Protection 260 (2-Flow) Nozzle - Medium Proximity Application No Obstructions 30 in. to 40 in. (76 cm to 102 cm) above the cooking surface. The medium proximity application uses the 260 nozzle, Part No. 419341. The nozzle tip is stamped with 260 indicating this is a two-flow nozzle and must be counted as two flow numbers. One 260 nozzle will protect a cooking area of 768 in.2 (4955 cm2) with a maximum dimension of 32 in. (81 cm). When using this nozzle for range protection, the nozzle must be pointed vertically down and positioned as shown in Figures 31 and 32. 260 NOZZLE TIP LOCATION CENTERLINE OF COOKING SURFACE I 40111. (102 cm) MAXIMUM HEIGHT OF 260 NOZZLE TIP 30 IN. (76 cm) MINIMUM HEIGHT OF 260 'NOZZLE I TIP FIGURE 31 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-16 REV.7 7-1-09 Range Protection 1 N (1-Flow) Nozzle - Low Proximity Range Protection Two (2) 290 (2-Flow) Nozzles - Low Application Proximity Application 15 in. to 20 in. (38.1 cm to 50.8 cm) above the cooking surface. 15 in. to 20 in. (38 cm to 51 cm) above the cooking surface. The low proximity 1-flow nozzle application for the protection of The low proximity 24low application requires the use of two (2) 290 ranges requires the 1 N nozzle, Part No. 419335. nozzles, Part No. 419342. The nozzle tip is stamped with iN indicating that it is a one-flow nozzle and must be counted as one (1) flow number, When using the 1 N nozzle for low proximity range protection with or without obstruction, the maximum length of the burner grates being protected must not be exceed 24 in. (61.0 cm) length, aimed along a centerline to a point 20 in. (50.8 cm) from the end of the length, protecting a maximum width of 18 in. (45.7 cm). When protecting a range, the iN nozzle must be located a maxi- mum of 9 in. (22.9 cm) from each burner grate centerline and must be positioned above the edge of the hazard area to be protected. The 1 N nozzle tip must be positioned at or below the obstruction, if present. The protected area begins at the point straight down from the nozzle tip. The nozzle can be placed at the side of the range aimed either left or right, or can be placed in the front or back of the range. See Figures 33 and 34 for nozzle location details. Ii Ij"I F \ 15-201N. I I AIM (38-51 an) POINT 201N. 51 cm) FIGURE 33 PROTECTED AREA IT I 2 M93 i 7CM Both nozzle tips are stamped with 290 indicating they are two flow nozzles and must be counted together for a total of four (4) flow numbers. Two (2) 290 nozzles will protect a cooking area of 1008 in.2 P. (6503 cm2) with a maximum dimension of 36 in. (91 cm). When using two of these nozzles for low proximity range protec- tion, the nozzles must be positioned along the cooking surface perimeter to 1.5 in. (3.8 cm) inside the perimeter, and aimed at a 450 angle along the longitudinal centerline of the range. See m. Figures 35 and 36. 290 NOZZLE TIP ' LOCATION o-1.5IN. (0-3.8 cm) ØP\ IN FROM EDGE OF 45* COOKING SURFACE t II 15 INTO 20 IN. II 15 INTO 20 IN. (38 to 51 cm) I (38 to 51 cm) MAXIMUM MAXIMUMI [_00000 . 1 FIGURE 35 002278 COOKING LONGITUDINAL. AREA CENTERLINE COOKING AREA I 290 NOZZLE TIP 14- LOCATION CENTER OF COOKING SURFACE ±2 IN. (5 cm) 290 NOZZLE TIP LOCATION 0— 1.5 IN. (3.8 cm) IN FROM EDGE 000239 OF COOKING SURFACE 20 IN. (51 CM) — 24 IN. (6l an) FIGURE 34 COOKING AREA AREA I 290 NOZZLE TIP LOCATION CENTER OF COOKING SURFACE ±2 IN. (5 cm) 290 NOZZLE TIP LOCATION 0— 1.5 IN. (3.8 cm) IN FROM EDGE OF COOKING SURFACE FIGURE 36 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-17 7-1-09 REV. 6 Range Protection (With or Without Back Shelf/Obstruction b. When this type of hazard is equipped with a back shelf or other similarly sized obstruction located above the range top, two pro- tection options are available: One requires a 1 F nozzle, Part No. 419333, and the other option requires a 260 nozzle, Part No. 419341. P. Range Protection 1 F (1-Flow) Nozzle (With or Without Back Shelf/Obstruction) Single and multiple burner ranges can be protected using a IF nozzle, Part No. 419333. The nozzle tip is stamped with 1 F indi- cating that it is a one-flow nozzle and must be counted as one flow number. When using the 1 F nozzle for range protection with or without back shelf or other similarly sized obstruction, the maximum length of the burner grates being protected must not exceed 28 in. (71 cm) and the maximum area of the burner grates must not exceed D. 336 in.2 (2168 cm2). See Figure 37 for nozzle location details. 1 F NOZZLE SHELF OR OTHER SIMILARLY SIZED OBSTRUCTION CAN OVERHANG BURNER(S) BY A MAXIMUM OF 11 IN. (28 Cm) 20 It. 40. AIM (51 cm) 1 IN. MINIMUM (10 14 IN. 12 IN. FRONT TO REAR (35.6 cm) MAXIMUM (30.5 cm) MAXIMUM CENTERLINE MAXIMUM IF NOZZLE LOCATED OVER FRONT EDGE OF BURNER GRATE AND ORIENTED SO NOZZLE TIP FLATS ARE PARALLEL WITH BURNER GRATE FRONT TO REAR CENTERLINE AND SHALL BE AIMED AT THE CENTER OF THE COOKING SURFACE. FIGURE 37 000 Range Protection 260 (2-Flow) Nozzle (With or Without Back Shelf/Obstruction) Single and multiple burner ranges can be protected using a 260 nozzle, Part No. 419341. The nozzle tip is stamped with 260 indi- cating that it is a two-flow nozzle and must be counted as two flow numbers. When using the 260 nozzle for range protection with or without 'back shelf or other similarly sized obstruction, the maximum length of burner grates being protected must not exceed 32 in. (81 cm) and the maximum area of the burner grates must not exceed 384 in.2 (2477 cm2). Nozzle must be located on the front edge of the burner grates and aimed at a point 10 in. (25 cm) from the back edge of the burner grates. Nozzle must be mounted 30 to 40 in. '(76 to 102 cm) above the hazard surface. See Figure 38. 260 NOZZLE SHELF OR OTHER SIMILARLY SIZED OBSTRUCTION CAN OVERHANG BURNER(S) BY A MAXIMUM OF 11 IN. (28 cm) 18 IN. (45.7 cm) (76- 102 cm) MINIM 30-40 IN. (25 cm) FROM BACK OF BURNER GRATES FIGURE 38 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-18 REV.7 7-1-09 b. Griddle Protection 1 N (1-Flow) Nozzle - High Proximity Application The R-102 system uses four different nozzles for the protection of griddles. One of the applications requires a 1-flow nozzle and three of the applications require a 2-flow nozzle. High Proximity Application: 35 in. to 40 in. (89 to 102 cm) above the cooking surface. This high proximity application uses the 1 N nozzle, Part No. 419335. The nozzle tip is stamped with 1 N indicating this is a one-flow noz- zle and must be counted as one flow number. 'Griddle Protection 290 (2-Flow) Nozzle - High Proximity 'Application Option 1 - Nozzle Center Located 30 in. to 50 in. (76 cm to 127 cm) above the cooking surface. This high proximity application uses the 290 nozzle, Part No. 419342. The nozzle tip is stamped with 290 indicating this is a 2-flow noz- zle and must be counted as two flow numbers. One 290 nozzle will protect a maximum cooking area of 720 in.2 (4645 cm2) with a maximum dimension of 30 in. (76 cm). When using this nozzle for high proximity applications, the nozzle One 1 N nozzle will protect a maximum cooking area of 1080 j2 must be positioned within 1 in. (2.5 cm) of the center of the cook- (6968 cm2) with the maximum longest side of 36 in. (91 cm). 'ing surface and pointed vertically down. See Figure 41 and 42. When using this nozzle for griddle protection, the nozzle must be positioned along the cooking surface perimeter to a maximum of 2 in. (5 cm) inside the perimeter, and aimed to the midpoint of the cooking surface. See Figure 39 and 40. CENTER LINE OF GRIDDLE SURFACE * 1 IN. (2 Cm) IN ANY DIRECTION NOTICE When using this type of griddle protection, only 5 flow numbers are allowed on a 1.5 gal (5.7 L) system and only 11 flow numbers are allowed on a 3 gal (11.4 L) system. r t MIDPOINT OF l COOKING SURFACE + I I h I I J IN NOZZLE LOCATED ALONG COOKING SURFACE EDGE ANY SIDE OF GRIDDLE SURFACE WITHIN 0-2 IN. (0-5 cm) OF COOKING SURFACE EDGE. NOZZLE MUST BE AIMED AT MIDPOINT OF COOKING SURFACE. FIGURE 39 241 I NOZZLE LOCATION I I 0-2 IN. (0-5CM) 1)1 I I INSIDE PERIMETER 40 IN. ...,J L._ OF COOKING SURFACE I I (102 Cm) MAXIMUM HEIGHT I OF 1N I NOZZLE TIP / I 35 IN. (89cm) I / / I MINIMUM I I I HEIGHT I EDGE I OF 1N I OF —0-' I/ i NOZZLE TIP COOKING I I SURFACE L I FIGURE 40 243 I 501N. (127 cm) MAXIMUM II, HEIGHT I 0F290 1 f NOZZLE TIP 30 IN. (76 cm) MINIMUM HEIGHT OF 290 I NOZZLE I TIP FIGURE 41 244 COOKING AREA LOCATION - MAXIMUM + CLING AREA 1 IN. (2 cm) MAXIMUM CENTER OF GRIDDLE SURFACE OR A MAXIMUM DIMENSION OF 20.6 IN. (52 cm) FROM NOZZLE CENTERLINE TO FURTHEST CORNER OF GRIDDLE FIGURE 42 000773 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-19 7-1-09 REV. 4 Griddle Protection 260 (2-Flow) Nozzle - High Proximity Application Option 2— Nozzle Perimeter Located 30 in. to 50 in. (76 cm to 127 cm) above the cooking surface. This high proximity application uses the 260 nozzle, Part No. 419341. The nozzle tip is stamped with 260 indicatiAg this is a two-flow nozzle and must be counted as two flow numbers. One 260 nozzle will protect a maximum cooking area of 1440 in.2 (9290 cm2) with a maximum dimension of 48 in. (122 cm). When using this nozzle for griddle protection, the nozzle must be positioned along the cooking surface perimeter to 2 in. (5.1 cm) inside perimeter, and aimed at the center of the cooking surface. See Figure 43 and 44. I NOZZLE LOCATION II 0 — 2 IN. (0 — 5 cm) I I INSIDE PERIMETER L— OF COOKING SURFACE 50 IN. I I (127 cm) I MAXIMUM HEIGHT O F 260 NOZZLE TIP / MINIMU HEIGHT EDGE OF 260 OF NOZZLE COOKING SURFACE _____ I 3OIN.(7jcm) .9- I000243 FIGURE 43 000243 COOKING AREA r- T MIDPOINT OF COOKING SURFACE COOKING I I I AIM POINT L_ AREA j 260 NOZZLE LOCATED ALONG COOKING SURFACE EDGE ANY SIDE OF GRIDDLE SURFACE WITHIN 0-2 IN. (0-5CM) OF COOKING SURFACE EDGE. NOZZLE MUST BE AIMED AT MIDPOINT OF COOKING SURFACE. FIGURE 44 000241 ° Griddle Protection 290 (2-Flow) Nozzle - Medium Proximity Application Option 2a - Nozzle Perimeter Located (Continued) 20 in. to 30 in. (51 cm to 76 cm) above the cooking surface. The medium proximity application uses the 290 nozzle, Part No. 419342. The nozzle tip is stamped with 290 indicating this is a two-flow nozzle and must be counted as two flow numbers. One 290 nozzle will protect a maximum cooking area of 1440 in.2 (9290 cm2) with a maximum dimension of 48 in. (122 cm). When using this nozzle for griddle protection, the nozzle must be positioned along the perimeter to 2 in. (5.1 cm) inside perimeter, and aimed at the center of the cooking surface. See Figure 45 and 46. U COOKING AREA T T CENTER OF COOKING SURFACE COOKING AREA - AIM POINT J 290 NOZZLE LOCATED ALONG COOKING SURFACE EDGE ANY SIDE OF GRIDDLE SURFACE WITHIN 0-2 IN. (0-5cm) OF COOKING SURFACE EDGE. NOZZLE MUST BE AIMED AT CENTER OF COOKING SURFACE. FIGURE 45 000241 NOZZLE LOCATION I 0 — 2 IN. (0 — 5 cm) I I INSIDE PERIMETER 30 IN. --I *- OF COOKING SURFACE I (76 cm) MAXIMUM II I e__t 0F290 HEIGHT NOZZLE TIP / I 20 IN. (51 cm) I / / I MINIMUM I - IEIGHT I )F290 IOZZLE TIP I EDGE OF COOKING SURFACE FIGURE 46 1243 NOZZLE LOCATION 1 0-2 IN. (0-5cm) t INSIDE PERIMETER 20 IN. OF COOKING SURFACE I (51 cm) MAXIMUM HEIGHT OF 2120 /410IN( NOZZLE TIP mm) MINIMUM I HEIGHT I I / 0F2120 I I I, NOZZLETIP I 000243 EDGE OF COOKING SURFACE OVERHEAD VIEW 36 IN. (91.4 CM) MAX. 2W NOZZLE AIM POINT 0-3 IN. (0-7.6 cm) 10 REAR OF COOKING SURFACE CENTER NE WHEN 2W NOZZLE IS SmONED AT OR TO THE REAR OF CENTER LINE NOZZLE AIM POINT IN. (0-7.6 cm) FORWARD tCOOKING SURFACE CEN- TER LINE WHEN 2W NOZZLE IS POSITIONED AT OR FOR- WARD OF COOKING SURFACE CENTER LINE 0- 10 IN. (0-25.4 an) FROM CENTERUNE MAX 0-101N. (0- 25.4 an) FROM CENTER LINE MAX 30 IN. -( (76.2 cm) MAX 089149 COOKING SURFACE EDGE FRONT VIEW 20 IN. (50.8 cm) MAX 10 IN. (25.4cm) MIN. r__ r CENTEROF COOKING SURFACE COOKING I I I I I AREA I I -4-- AIM POINT 2120 NOZZLE LOCATED ALONG ANY SIDE OF GRIDDLE SURFACE WITHIN 0-2 IN. (0-5 cm) OF COOKING SURFACE EDGE. NOZZLE MUST BE AIMED AT CENTER OF COOKING SURFACE. 0-3 IN. (76.2 cm) NOTE: A 2W NOZZLE CAN PROTECT A GRIDDLE WITH A MAXIMUM COOKING SURFACE OF 30 IN X 36 IN. (762 cm 91.4 cm), AT A HEIGHT OF 10-20 IN. (25.4-50.6 cm). THE 2W NOZZLE CAN BE POSITIONED A MAXIMUM OF ±10 IN. (25.4 cm) FOR- WARD OR BEHIND COOKING SURFACE CENTER LINE AND A MAXIMUM OF 3 IN. (7.6 CM) AWAY FROM EITHER SIDE OF THE COOKING SURFACE, AIMED IN 9 IN. (22.9 cm) TO A POINT 0-3 IN. (0-22.0 CM). FORWARD ORTOTHE REAR OF THE COOKING SURFACE CENTER LINE SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-20 REV. 5 7-1-09 Griddle Protection 2120 (2-Flow) Nozzle - Low Proximity Application Option 2b - Nozzle Perimeter Located (Continued) 10 in. to 20 in. (25 cm to 51 cm) above the cooking surface. The low proximity application uses the 2120 nozzle, Part No. 419343. The nozzle tip is stamped with 2120 indicating this is a two-flow nozzle and must be counted as two flow numbers. '- One 2120 nozzle will protect a maximum cooking area of 1440 in.2 (9290 cm2) with a maximum dimension of 48 in. (122 cm). When using this nozzle for griddle protection, the nozzle must be positioned along the perimeter to 2 in. (5.1 cm) inside perime- ter, and aimed at the center, of the cooking surface. See Figure 47 and 48. - Griddle Protection 2W (2-Flow) Nozzle - Low Proximity I Application Option 2c - Nozzle Perimeter Located (Continued) 10 in. to 20 in. (25 cm to 51 cm) above the cooking surface. The low proximity application uses the 2W nozzle, Part No. 419337. The nozzle tip is stamped with 2W indicating this is a two-flow noz- zle and must be counted as two flow numbers. One 2W nozzle will protect a maximum cooking area of 1080 in.2 (6967.7 cm2) with a maximum dimension of 36 in. (91.4 cm). When using this nozzle for griddle protection, the nozzle must be positioned along the perimeter to 9 in. (22.9 cm) inside perimeter, and aimed at the center of the cooking surface. See Figure 49 and 50. FIGURE 47 I -. 000243 AIM POINT 9 IN. (22.9 cm) FROM EITHER SIDE OF COOKING AREA COOKING SURFACE FIGURE 49 FIGURE 48 000241 AIM POINT 9 IN. (22.9 cm) FROM EITHER SIDE OF COOKING SURFACE 008150 FIGURE 50 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-21 7-1-09 REV. 4 Griddle Protection 1W (1-Flow) Nozzle - Low Proximity I Application 115 in. to 20 in. (38.1 cm to 50.8 cm) above the cooking surface. The low proximity 14low nozzle application for the protection of griddles requires the 1W nozzle, Part No. 419336. The nozzle tip is stamped with 1W indicating that this is a one-flow nozzle and must be counted as one flow number. When using the 1W nozzle for low proximity griddle protection with our without obstruction, the maximum length of the cooking sur- face to be protected must not exceed 26 in. (66.0 cm). The nozzle must be centered at one end of the maximum 26 in. (66.0 cm) length, aimed along a centerline to a point 20 in. (50.8 cm) from the end of the length, protecting a maximum width of 20.5 in. (52.1 cm). The 1W nozzle tip must be positioned at or below the obstruction, if present. The protected area begins at the point straight down from the nozzle tip. The nozzle can be positioned above the edge of the hazard area to be protected. See Figures 51 and 52. Note: If the hazard area exceeds the single nozzle coverage list- ed above, additional nozzles will be required. The additional noz- zle can be positioned in front at high proximity or at the side at low proximity. 15-20 IN. (38-51 cm) I 201N. r (51 an) FIGURE 51 PROTECTED AREA 20 IN. (51 CM) — 26 IN. -(66-) FIGURE 52 12 IN. (30.5 cm) MINIMUM MAXIMUM INTERNAL BROILER SIZE 32 x 34 IN. (81 x86CM) MAXIMUM INTEF BROILER SIZE 4: (109 179 cm) TOP VIEW TOP VIEW FIGURE 56 000249 Note: The CB Metal Blow-off Cap must be used when using chain broiler protection. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-22 REV. 5 7-1-09 Chain Broiler Protection The following listed protection guidelines can be applied to any manufacturer's chain broilers, if the chain broiler meets the speci- fied parameters. Chain broilers utilizing catalytic converters can be protected from overhead using model specific protection iden- tified in the "Specific Application by Model" section in System Design. Or, they can be protected with standard 1 N nozzle hori- zontal chain broiler protection with the nozzles positioned at either end of the chain broiler openings. Refer to the Horizontal Chain Broiler Protection section for specific design information. Horizontal Chain Broiler Protection The R-102 system can use two 1 Nozzles (Part No. 419335) for horizontal chain broiler protection. The nozzle tip is stamped 1 N, indicating that this is a one-flow nozzle and must be counted as one flow number (total of two flow numbers for each chain broiler being protected). Two 1 N nozzles are always needed for chain broiler protection when the hazard area to be protected does not meet the "Overhead Broiler Protection" requirements. The maximum inter- nal size of the broiler is 43 x 31 in. (109 cm x 79 cm). The nozzles must be positioned at each end of the enclosed cooking chamber 1 t 3 in. (2.5 to 7.5 cm) above the surface of the chain and a max- imum distance of 4 in. (10 cm) away from the broiler opening. The nozzles may be mounted at either corner as long as they are at opposite ends of the chain broiler and positioned to discharge v. diagonally across the top of the chain. See Figures 53 and 54. 000245 FIGURE 53 Overhead Chain Broiler Protection P. The R-102 system can use two 1W Nozzles (Part No. 419336) for overhead chain broiler protection. The nozzle tip is stamped with 1W, indicating that this is a one-flow nozzle and must be counted as one flow number. Overhead protection is only available for chain broilers with exhaust opening dimensions that are not less than 60% of the internal broiler length and not less than 60% of the internal broiler width, to a minimum size of 12 in. x 12 in. (30.5 x 30.5 cm). Internal broiler size can not be larger than 32 in. x 34 in. (81 x 86 cm). When overhead protection is used, the nozzles must be centered above the exhaust opening within 4 to 8 in. (10 to 20 cm) of each• other and they must be located 10 to 26 in. (25 to 66 cm) above the top of the broiler surface. See Figure 55. FIGURE 55 000248 The nozzles may vary in position as long as they are evenly spaced from the exhaust center and are always 1800 opposite of each other. If the opening is not square, the nozzles must be posi- tioned along the centerline, parallel to the longest side of the open- o. See Figure 56. FIGURE 54 000247 iN NOZZLE (PART NO. 419335) NOZZLE - LOCATION ZONE 12 IN. (30 cm) 6 IN. (15 cm) 6IN (15cm) ATCENTER V ........................ OF BROILER OPENING FIGURE 57a com AIM AT CENTER OF BROILER OPENING SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-23 7-1-09 REV. 8 Overhead Chain Broiler Protection (Continued) Example No. 1 - Internal broiler size is 24 in. long x 20 in. wide (61 x 51 cm), with an opening of 16 in. x 16 in. (40.6 x 40.6 cm). To determine minimum opening size, multiply the internal length and the internal width by 0.6: Length of opening -24 in. x 0.6 = 14.4 in. (61 cm x 0.6 = 36.6 cm) Width of opening -20 in. x 0.6 = 12.0 in. (51 cm x 0.6 = 30.5 cm) The minimum allowable opening for overhead protec- tion would be 14.4 in. x 12.0 in. (36.6 x 30.5 cm). This example would be acceptable for overhead pro- tection. Example No. 2 - Internal broiler size is 30 in. long x 24 in. wide (76 x 61 cm) with an opening of 22 in. x 12 in. (56 x 30 cm). To determine minimum opening size, multiply internal length and internal width by 0.6: Length of opening -30 in. x 0.6 = 18.0 in. (76 cm x 0.6 = 45.7 cm) Width of opening -24 in. x 0.6 = 14.4 in. (61 cm x 0.6 = 36.6 cm) Minimum allowable opening for overhead protection would be 18 in. x 14.4 in. (45.7 x 36.6 cm). Because this broiler has an opening of 22 in. x 12 in., the 12 in. width is below the minimum allowable cal- culated dimension of 14.4 in. (36.6 cm) and therefore would not be acceptable for overhead protection. Salamander Broiler Protection The R-102 system uses three different nozzle locations for sala- mander broiler protection. All of the design options require a one- low nozzle. Salamander Broiler Protection -1 N (1-Flow) Nozzle Overhead A salamander broiler with a maximum hazard area (internal broil- er chamber) of 16 in. (41 cm) deep x 29 in. (74 cm) wide can be protected using a IN nozzle, Part No. 419335. The nozzle tip is stamped with 1 N, indicating that this is a one-flow nozzle. The single 1 N nozzle must be located directly in line with either vertical edge of the broiler opening, 6 in. (15 cm) to 12 in. (30 cm) in front of the broiler, and 0 in. to 12 in. (30 cm) above the top of the broiler. The nozzle must be aimed at the center of the broiler opening. See Figure 57a. VERTICAL EDGE OF BROILER OPENING Salamander Broiler Protection -1 F (1-Flow) Nozzle Overhead A salamander broiler with a maximum hazard area (internal broil- er chamber) of 15 in. (38 cm) deep x 31 in. (79 cm) wide can be protected using a IF nozzle, Part No. 419333. The nozzle tip is stamped with 1 F, indicating that this is a one-flow nozzle. The single 1 F nozzle must be located directly in line with the cen- ter of the broiler opening, 8 in. (20 cm) to 12 in. (30 cm) in front of the broiler and 12 in. (30 cm) to 18 in. (46 cm) above the top of the broiler. The nozzle must be aimed at the center of the top broiler opening when the grate is located in the middle position. The noz- zle must be orientated so the nozzle tip flats are parallel with the grate left to right centerline. See Figure 57b. I NOZZLE -4 NOZZLE (PART NO. 6 IN. LOCATION ZONE 419333) (l5 CM) [ B IN. (20cm) IN. IN 41N. (10CM) AIM AT CENTER OF THE AIM AT CENTER OF THE TOP TOP BROILER OPENING BROILER OPENING WHEN THE WHEN THE GRATE IS GRATE IS LOCATED IN THE LOCATED IN THE MIDDLE POSITIONAIM AT CENTER MIDDLE POSITION OF BROILER OPENING FIGURE 57b 426 Salamander Broiler Protection -1 N (1-Flow) Nozzle Local A salamander broiler with a maximum hazard area (internal broil- er chamber) of 15 in. (38 cm) deep x 31 in. (79 cm) wide can be protected using a IN nozzle, Part No. 419335. The nozzle tip is stamped with 1 N, indicating that this is a one-flow nozzle. The single 1 N nozzle must be located above the grate on either vertical edge of the broiler opening. The nozzle must be aimed at the center of the grates. See Figure 57c. FIGURE 57c OO84 IN NO AT CENTER OF GRATES SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-24 REV.7 7-1-09 Upright Broiler Protection The R-1 02 system uses two 112N Nozzles (Part No. 419334) for all upright broiler protection. The nozzle tip is stamped 1/2N, indicat- ing that this is a half-flow nozzle. A pair of these nozzles will equal one flow number. Two 1/2N nozzles will protect a maximum hazard area (internal broiler chamber) of 30 in. x 32.5 in. (76 cm x 82.5 cm). These noz- zles must always be used in pairs on an upright broiler. One noz- zle must be positioned above the grate and pointed at the back opposite corner of the broiler chamber. The second nozzle must be pointed down into the center of the drip pan through the open slot. See Figure 58. UPRIGHT BROILER BROILER CHAMBER Gas-Radiant/Electric Char-Broiler Protection The R-1 02 system uses the 1 N nozzle, (Part No. 419335) for gas- radiant/electric char-broiler protection. The nozzle tip on the 1 N nozzle is stamped with a 1 N, indicating that this is a one-flow nozzle and must be counted as one flow number. One IN nozzle will protect a hazard with a maximum length of 36 in. (91 cm) and a total cooking area which does not exceed 864 in.2 (5574 cm2). The nozzle tip must be located 15 to 40 in. (38 to 102 cm) above the hazard surface. When using this nozzle for gas-radiant/electric char-broiler protection, the nozzle must be positioned anywhere along or within the perimeter of the maximum cooking area and shall be aimed at the center of the cooking surface. See Figure 59. L_ VIEW SIDE VIEW 40 IN. (102 cm) I MAXIMUM 1001 115511N- * 5IN. f(38 cm) I J MINIMUM i 0mm2 FIGURE 58 O257 FIGURE 59 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-25 7-1-09 REV. 7 Lava Rock (Ceramic) Char-Broiler Protection The R-102 system uses the 1 Nozzle (Part No. 419335) for all lava rock char-broiler protection. The nozzle tip is stamped with 1 N, indicating that this is a one-flow nozzle and must be counted as one flow number. One IN nozzle will protect a hazard which has a maximum length of 24 in. (61 cm) and a total cooking area which does not exceed 312 in.2 (2013cm2). The nozzle tip must be located 18 to 35 in. (46 to 89 cm) above the hazard surface. When using this nozzle for lava rock (ceramic) char-broiler protection, the nozzle must be positioned anywhere along or within the perimeter of the maximum cooking area and angled to the center. See Figure 60. COOKING AREA COOKING I AREA AREA - 1-. -- IT IT 35 IN. \\ (89cm) MAXIMUM I I I (46cm) I MINIMUM Natural Charcoal Broiler Protection The R-102 system uses the 1 Nozzle (Part No. 419335) for all natural charcoal broiler protection. The nozzle tip is stamped with 1 N indicating that this is a one-flow nozzle and must be counted as one flow number. One IN nozzle will protect a hazard area which has a maximum length of 24 in. (61 cm) and a total cooking area which does not exceed 288 in.2 (1858 cm2). The nozzle tip must be located 18 to 40 in. (46 to 102 cm) above the hazard surface. When using this nozzle for natural charcoal broiler protection, the nozzle must be positioned anywhere along or within the perimeter of the maximum cooking area and aimed at the Center of the cooking surface. See Figure 61. The coverage of such appliances only applies when the depth of the charcoal does not exceed 4 in. (10 cm). COOKING I_COOKING AREA AREA I - I Nr I I I Ij I I / 4OIN. i \ I (102cm) \ MAXIMUM I I 4 IN. (locml"\'\ 18IN. I / I (46 c' I MAXIMUM DEPTH i J MINIMUM I ii NI FIGURE 60 FIGURE 61 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-26 REV.6 7-1-09 Alternate Ceramic/Natural Charcoal Char-broiler Protection The R-102 system may also use the 3N nozzle (Part No. 419338) for all ceramic (lava rock) and natural charcoal char-broiler protec- tion. The nozzle tip is stamped with 3N, indicating that this is a three-flow nozzle and must be counted as three flow numbers. One 3N nozzle will protect a hazard which has a maximum length of 30 in. (76 cm) and a total cooking area which does not exceed 720 j2 (4645 cm2). The nozzle tip must be located 14 to 40 in. (36 to 102 cm) above the hazard surface. The nozzle must be positioned anywhere along or within the perimeter of the max- imum cooking area and angled to the center. See Figure 62. For natural charcoal char-boiler protection, this coverage only applies when the depth of the charcoal does not exceed 4 in. (10 cm). COOKING I....COOKING AREA AREA - I - I Nr I II I II I Wood Fueled Char-Broiler Protection The R-102 system uses the 3N Nozzle (Part No. 419338) for mesquite char-broiler protection. The nozzle tip is stamped with 3N indicating that this is a three-flow nozzle and must be counted as three flow numbers. One 3N nozzle will protect a hazard which has a maximum length of 30 in. (76 cm) and a total cooking area which does not exceed 720 in.2 (4645 cm2). The nozzle tip must be located 14 to 40 in. (36 to 102 cm) above the hazard surface. The nozzle must be positioned anywhere along or within the perimeter of the max- imum cooking area and aimed at the center of the cooking surface. See Figure 63. Mesquite logs and pieces, no larger than 4 in. (10 cm) in diameter, may be protected with a maximum allowable wood depth of 6 in. (15 cm). COOKING I'COOKING AREA AREA I — I I I l I I I I II I 11 I S' 40 IN. 40 IN. / (102 cm) I \ / (102cm) MAXIMUM MAXIMUM 4 IN. (lOcm) \ I / I (36 cm) 6 IN. (15 cm \ i /h 14 IN. MAXIMUM IN. DEPTH MINIMUM MAXIMUM / (36 cm) I DEPTH MINIMUM \\V mm; FIGURE 62 IL I. FIGURE 63 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-27 7-1-09 REV. 5 Wok Protection The R-1 02 system uses two different nozzles for the protection of woks. 1. A 260 nozzle, Part No. 419341, will protect a wok 14 in. (36 cm) minimum diameter up to 30 in. (76 cm) maximum diameter. The wok depth must be no less than 3.75 in. (9.5 cm) and no greater than 8 in. (20 cm). The nozzle tip is stamped with 260 indicating that this is a two- low nozzle and must be counted as two flow numbers. When using this nozzle, the nozzle must be positioned as shown in Figure 64. NOZZLE MUST BE POSITIONED WITHIN 1 IN. (2 Cm) RADIUS OF THE CENTER OF THE WOK, POINTED VERTICALLY DOWN 260 NOZZLE ii 35-45 IN. MINIMUM DEPTH 3.75 IN. (9.6 Cm) (89— 114 cm) MAXIMUM DEPTH 8 IN. (20 cm) I t 'I 14 IN. (35.6 Cm) MINIMUM DIAMETER 30 IN. (76.2 Cm) MAXIMUM DIAMETER FIGURE 64 2. A 1 N Nozzle, Part No. 419335, will protect a wok 11 in. (28 cm) minimum diameter up to 24 in. (61 cm) maximum diameter. The wok depth must be no less than 3 in. (8 cm) and no greater than 6 in. (15 cm). The nozzle tip is stamped with 1 N indicating that this a one-flow nozzle and must be counted as one flow number. When using this nozzle, the nozzle must be positioned anywhere along or within the perimeter of the wok, aimed at the center, 30 in. to 40 in. (76 to 102 cm) above the hazard surface, as shown in Figure 65. NOTICE When using this type of wok protection, only 5 flow numbers are allowed on a 1 1/2 gal (5.7 L) system, and only 11 flow numbers are allowed on a 3 gal (11.4 L) system. "I 40 IN. 1\\J/7T / 30 IN. MINIMUM DEPTH (76 cm) .4 3.0 IN. (7.6 cm) MAXIMUM DEPTH 6.O IN. (l5cm)be f 4 11 IN. (28 cm) MINIMUM DIAMETER 24 IN. (61 cm) MAXIMUM DIAMETER FIGURE 65 ommi SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-28 REV. 6 7-1-09 Nozzle Application Chart The following chart has been developed to assist in calculating the quantity and type of nozzle required to protect each duct, plenum, or appliance. NOTICE This chart is for general reference only. See complete details for each type of hazard. Minimum Hazard Maximum Hazard Dimensions Nozzle Quantity Duct or Transition Length - Unlimited 1 (Single Nozzle) Perimeter —50 in. (127 cm) Diameter - 16 in. (40.6 cm) Duct or Transition Length - Unlimited 1 (Single Nozzle) Perimeter - 100 in. (254 cm) Diameter —31 7/8 in. (81 cm) Duct or Transition Length - Unlimited 2 (Dual Nozzle) Perimeter - 150 in. (381 cm) Diameter —48 in. (122 cm) Electrostatic Precipitator Individual Cell 1 (At Base of Duct) Plenum Length - lOft (3.1 m) 1 (Horizontal Protection) Plenum Length —6 It (1.8 m) 1 (Horizontal Protection) Width —4 It (1.2 m) 1 Plenum Length —4 It (1.2 m) 1 (Vertical Protection) Width —4 It (1.2 m) Fryer (Split or Maximum Size Non-Split Vat) (without drip board) 14 in. (36 cm) x l5 in. (38cm) 1 Low Proximity Fryer (Split or Maximum Size Non-Split Vat) (without drip board) 14 1/2 in. (37 cm) x l4 in. (36cm) 1 Medium Proximity Fryer (Split or Maximum Size Non-Split Vat)* (without drip board) 15 in. (38 cm) x 14 in. (36 cm) High Proximity 1 Medium Proximity 1 Fryer (Non-Split Vat Only) Maximum Size (without drip board) 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity 1 Low Proximity 1 Maximum Size (without drip board) 18 in. (45.7 cm) x 18 in. (45.7 cm) High Proximity 1 For multiple nozzle protection of single fryers, see detailed information on Pages 4-10 and 4-11. Nozzle Tip Nozzle Nozzle Heights Part No. Stamping - Flow No. - 430912 1W - 419337 2W - 419337 2W - 419334 1/2N - 419335 1 - 430192 1W - 419336 1W - 419336 1W 13—l6in. 419342 290 (33-41 cm) 16-27 in. 419342 290 (41 —69 cm) 27-47 in. 419339 230 20-27 in. 419340 245 21-34in. 419338 3N 13-161n. 419342 290 25-35 in. 419338 3N (64-89 cm) SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-29 7-1-09 REV.6 Nozzle Application Chart (Continued) Minimum Nozzle Tip Hazard Maximum Hazard Dimensions Nozzle Quantity Nozzle Heights Nozzle Part No. Stamping - Flow No. Fryer (Non-Split Maximum Size Vat Only)* (with drip board) 21 in. (53 cm) x 14 in. (36 cm) (Fry Pot must not exceed 15 in. x 14 in. (38 cm x 36 cm)) High Proximity 1 27-47 in. 419339 230 Medium Proximity 1 20-27 in. 419340 245 Maximum Size (with drip board) 25 3/8 in. (64.4 cm) x 19 1/2 in. (49.5 cm) (Fry pot side must not exceed 19 1/2 in. (49.5 cm) x 19 in. (48.2 cm) High Proximity 1 21 —34 in. 419338 3N Low Proximity 1 13-16 in. 419342 290 Maximum Size (with drip board) 18 in. (45.7 cm) x 27 3/4 in. (70.5 cm) High Proximity 1 25-35 in. 419338 3N (64-89 cm) Fryer (Split or Maximum Size Non-Split Vat) (with drip board) 14 in. (36 cm) x 21 in. (53 cm) 1 13-16 in. 419342 290 Low Proximity (33-41 cm) Fryer (Split or Maximum Size Non-Split Vat) (with drip board) 14 1/2 in. (37 cm) x 26 1/2 in. (67 cm) 1 16-27 in. 419342 290 Medium Proximity (41 —69 cm) P. Range Longest Side (High Proximity) 1 30-40 in. 419335 1 N 32 in. (81 cm) (76 - 102 cm) Area - 384 sq. in. (2477 sq cm) Longest Side (Low Proximity) 1 15-20 in. 419335 1 24 in. (61 cm) (38-51 cm) Area - 432 in.2 (2787 cm2) Longest Side 40-48 in. 419333 1 F 28 in. (71 cm) (102-122 cm) Area —336 sq in. (With Backshelf) (2168 sq cm) Longest Side (High Proximity) 1 40— 50 in. 419340 245 28 in. (71 cm) (102-127 cm) Area - 672 sq in. (4335 sq cm) Longest Side (Medium Proximity) 1 30-40 in. 419341 260 32 in. (81 cm) (76 - 102 cm) Area - 768 sq in. (4955 sq cm) * For multiple nozzle protection 01 single fryers, see detailed information on Pages 4.10 and 4-11. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-30 REV. 4 7-1-09 Nozzle Application Chart (Continued) Minimum Nozzle Tip Hazard Maximum Hazard Dimensions Nozzle Quantity Nozzle Heights Nozzle Part No. Stamping - Flow No. Range (Continued) Longest Side (Low Proximity) 2 15-20 in. 419342 290 36 in. (91 cm) (38-51 cm) Area - 1008 sq in. (6503 sq cm) Griddle Longest Side (High Proximity) 1 30-50 in. 419341 260 48 in. (122cm) (76-127cm) Area - 1440 sq in. (perimeter (9290 sq cm) located) Longest Side (High Proximity) 1 30— 50 in. 419342 290 30 in. (76 cm) (76— 127 cm) Area - 720 sq in. (center located) (4645 sq cm) Longest Side (High Proximity) 1 35 - 40 in. 419335/435672 iN/i NSS 36 in. (91 cm) (89— 102 cm) Area - 1080 sq in. (perimeter located) (6968 sq cm) Longest Side 1 20-30 in. 419342 290 (Medium Proximity) (51 —76 cm) 48 in. (122 cm) (perimeter Area - 1440 sq in. located) (9290 sq cm) Longest Side (Low Proximity) 1 15-20 in. 4193336 1W 26 in. (66 cm) (38-51 cm) Area - 533 in.2 (center located) (3439 cm2) Longest Side (Low Proximity) 1 10 —20 in. 419337 2W 36 in. (91 cm) (25-51 cm) Area - 1080 in.2 (perimeter located) (6968 cm2) Longest Side (Low Proximity) 1 10-20 in. 419343 2120 48 in. (122 cm) (25 - 51 cm) Area - 1440 sq in. (perimeter (9290 sq cm) located) Chain Broiler* Longest Side —34 in. (86 cm) 2 10-26 in. 419336/432527 1W/1 WSS (Overhead Protection) Area - 1088 sq in. (25 —66 cm) (7019 sq cm) Chain Broiler Length —43 in. (109 cm) 2 1 —3 in. 419335/435672 iN/i NSS (Horizontal Protection) Width —31 in. (79 cm) (3-8 cm) Gas-Radiant Char-Broiler Longest Side —36 in. (91 cm) 1 15-40 in. 419335/435672 1 N/l NSS Area —864 sq in. (38 - 102 cm) (5574 sq cm) Electric Char-Broiler Longest Side —34 in. (86 cm) 1 20-50 in. 419335/435672 1 N/i NSS Area-680 sq in. (51 —127cm) (4388 sq cm) Lava-Rock Broiler Longest Side —24 in. (61 cm) 1 18 —35 in. 419335/435672 1 N/i NSS Area — 312 sq in. (46-89cm) (2013 sq cm) Natural Charcoal Broiler Longest Side —24 in. (61 cm) 1 18 —40 in. 419335/435672 1 N/i NSS Area —288 sq in. (46— 102 cm) (1858 sq cm) SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-31 7-1-09 REV. 7 Nozzle Application Chart (Continued) Minimum Nozzle Tip Hazard Maximum Hazard Dimensions Nozzle Quantity Nozzle Heights Nozzle Part No. Stamping - Flow No. Lava-Rock or Natural Longest Side —30 in. (76 cm) 1 14-40 in. 419338 3N Charcoal Char-Broiler Area - 720 sq in. (36 - 102 cm) (4645 sq cm) Wood Fueled Char-Broiler Longest Side —30 in. (76 cm) 1 14-40 in. 419338 3N Area —720 sq in. (36— 102 cm) (4645 sq cm) Upright Broiler Length —32.5 in. (82.5 cm) 2 - 419334 1/2N Width —30 in. (76 cm) Salamander Length —29 in. (74 cm) 1 - 419335 1 Broiler Width - 16 in. (41 cm) Length —31 in. (79 cm) 1 - 419333 1 Width - 15 in. (38 cm) Length —31 in. (79 cm) 1 - 419335 1 N Width - 15 in. (38 cm) Wok l4 in. —30 in. (36-76cm) 1 35-45in. 419341 260 Diameter (89 - 114 cm) 3.75 —8.0 in. (9.5-20 cm) Deep 11 in. —24 in. (28 —61 cm) 30-40 in. 419335/435672 1 N/l NSS Diameter (76 - 102 cm) 3.0-6.0 in. (8-15.2 cm) Deep Minimum chain broiler exhaust opening —12 in. a 12 in. (31 cm 31 cm), and not less than 60% of internal broiler size. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-32 REV.7 7-1-09 SPECIFIC APPLICATION BY MODEL Due to the configuration, application, and/or additional features that pose protection problems using conventional protection, noted in the guidelines previously addressed, the following appliances/applications are considered hazard specific. The following hazard specific applications have been individually tested and listed by make and model number of the equipment designated. Dean Industries Gas Fryer, Model 2424 GIl, 120,000 BTU/hr. Rating This specialized gas fryer can be protected with a combination of a 290 nozzle, Part No. 419342, and a 1W nozzle, Part No. 419336, for low proximity (7 3/4-8 in. nozzle height only) and two (2) 230 nozzles, Part No. 419339, for high proximity (45 in. nozzle height only). The maximum dimension of the fry pot is 24 in. x 24 in. (61 x 61 cm). Nozzles must be positioned and aimed as shown in Figure 66 Note: For low proximity protection, see Special Piping Layout in Figure 67. Dean Industries Model Gil Gas Fryer Special Piping Layout Section A (Tank to Hood Penetration) Piping Limitations Maximum Length: 30 ft (9.1 m) Maximum Rise: 6 It (1.8 m) Maximum Number of 900 Elbows: 7 Maximum Number of Tees: 0 FRY POT CENTERLINE 8 IN. 11/8 IN. (20 cm) 1 1/8 IN - I I (2.9 cm) 6 IN. .._.jE°j (2.9 cm)R ,__ W NOZZLE 290 NOZZLE—i (15 cm) I I 73/4-8 IN. ONLY I AIM POINT L-------j I (19.7 — 20.3 cm) OODM LOW PROXIMITY (73/4-8 IN. NOZZLE HEIGHT) 21/4 IN. 21/4 IN. I (5.7 cm) (5.7 cm) 230 NOZZLE FRONT EDGE OF FRY POT A 230 NOZZLE 11 IN. (53 cm) / 45 IN. ONLY (114 3) I4) TOP OF FRYER AIMPOINT L I I H-- HIGH PROXIMITY (45 IN. NOZZLE HEIGHT ONLY) 000283 FIGURE 66 Section B (Hood Penetration to Nozzles) Piping Limitations Piping configuration shall be as shown with ±1/4 in. tolerance on dimensions. All nozzles shall be at the same elevation. Each pair of appliance nozzles shall be equally spaced from left-to-right centerline of fryer. : -? I Ir"o I:4 k, 290 2 1/4 IN. 21 IN. (53.3 cm) or (5.7 cm) 24 IN. (60.9 cm) TO 3 GAL (11.4 L)TANK SECTION A A HOOD PENETRATION 81/4 IN. $/ t (20.9 cm] 295/BIN. 1W 211/16 IN. (75.2 cm) (6.9cm) ) 290 21/8 IN. (5.4 Cm) 23/4 IN. (69 cm) 24 IN. (60.9 Cm) 290 21/4 IN. 21 IN (53.3Cm) or 24 IN: (60.9 cm) (5.7 cm) 21/4 IN. (5.7 cm) 2114 IN. (5.7 Cm) SPECIFIC DISCHARGE PIPING FOR LOW PROXIMITY PROTECTION OF (4) FOUR DEAN INDUSTRIES MODEL GTI GAS FRYERS FIGURE 67 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-33 7-1-09 REV. 6 SPECIFIC APPLICATION BY MODEL (Continued) Far West Hospitality Products Gas Fryer, Model PAR-1-20, 63000 BTU/hr Rating This specialized gas fryer can be protected with a single, 290 nozzle, Part No. 419342. The maximum dimension of the fry pot is 21 in. x 21 in. (53 x 53 cm). The 290 nozzle must be located on the front-to-rear centerline and aimed at the center of the cooking surface. See Figure 68. 41/2 IN. (11.5CM) Frymaster 14 KW - 208V Electric Fryer, Model MACH 14 Series This specialized single vat electric fryer can be protected either with a Single 230 nozzle, Part No. 419339, located 27 in. to 47 in. (69 cm to 120 cm) above the top surface of the fryer or with a sin- gle 245 nozzle, Part No. 419340, located 20 in. to 27 in. (51 cm to 69 cm) above the top surface of the fryer. Either nozzle must be located anywhere along or within the perimeter of the cooking surface and aimed at the midpoint. See Figure 69. The maximum size of the fry pot (without drip board) is 133/4 in. x 16 3/4 in. (35 cm x 42.6 cm) and the maximum size of the cooking surface (with drip board) is 13 3/4 in. x 20 7/8 in. (35 cm x 53 cm). The vat may be divided in half to make two split vats. 230 NOZZLE TIP OR 245 NOZZLE TIP ANYWHERE ALONG OR WITHIN THE PERIMETER OF THE COOKING SURFACE AND AIMED AT THE MIDPOINT. 207/8 IN. 230 NOZZLE (53 cm) MAXIMUM 230 NOZZLE 712 27 IN.-47 IN. ZZLE (69cm—l2ocm) 133/4 IN SURFACE (35cm) MAXIMUM OF FRYER NL ABOVETOP LE .-27 IN. m-69cm) VETOP FACE OF ER I 163/4 IN. (42.6 cm) MAXIMUM FIGURE 69 1 (3' BACK OF FRYER SIDE VIEW OF FRYER 000285 290 NOZZLE LOCATED ON FRONT-TO-REAR CENTERLINE* 4.5 IN. (11.4 cm) FROM SIDE TO SIDE CENTERLINE AND AIMED AT CENTER OF COOKING AREA. FIGURE 68 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-34 REV. 8 7-1-09 SPECIFIC APPLICATION BY MODEL (Continued) McDonald Fryer (Nozzle Heights of Less Than 20 In.) When the 245 nozzle is used to protect McDonald's fryers at heights less than 20 in. (51 cm) above the top of the fryer, the fol- lowing appliance and distribution piping rules shall apply: 1. Each McDonald's gas or electric fryer shall be protected by one 245 nozzle, Part No. 419340. The fryer vat dimensions for one full vat or two split vats shall not exceed 14 in. x 15 in. (36 cm x 38 cm) without the dripboard and 14 in. x 21 in. (36 cm x 53 cm) with the dripboard. The heat input rating of the fryer shall not exceed 122,000 BTU/HR. The 245 nozzle shall be located 18 in. to 20 in. (46 cm to 51 cm) above the top of the fryer vat, 2 in. to 2 1/4 in. (5 cm to 5.7 cm) to the right or left of the front-to-rear vat centerline, and 0 to 3 1/4 in. (0 cm to 8 cm) forward of the right-to-left vat centerline, and aimed at the vat center point. See Figure 70. REAR FRONT-TO-REAR VAT CENTERLINE RIGHT-TO- LEFT VAT AIM CENTERLINE POINT I NOZZLE I I4 t3114 LOCATION I • ZONES 2 IN.1 21N. 2114 IN. 4 P 4 ' 21141N. FRONT FIGURE 70 297 The distance between the start of the first branch line and the start of the last branch line shall not exceed 79 in. (201 cm). The total length of all branch lines shall not exceed 162 in. (412 cm). The 3 gallon agent tank shall be elevated above the connec- tions between the supply and branch lines. The requirements of the following table shall not be exceeded: Duct Plenum Appliance Supply Branch Branch Branch Requirement Line Line Line Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 318 in. Maximum Length 140 in. 67 in. 6 in. 42 in. (356 cm) (170 cm) (15 cm) (107 cm) Minimum Length 81 in. 4 in. 4 in. 17 in. (206 cm) (10 cm) (10 cm) (43 cm) Maximum 5 3 1 6 90° Elbows Maximum Tees 0 1 1 1 Maximum Flow 11 2 1 2 Numbers Minimum Flow 5 0 0 1/2 Numbers FRONT VIEW (TEE BLOCK LOCATION) SIDE VIEW NOTE 1: IT IS RECOMMENDED THAT THE AGENT DISTRIBUTION HOSE Kfl FART NO. 435982, BE UTILIZED DURING SYSTEM INSTALLATION. NOTE 2: VAT DIMENSIONS - 16 IN. (40.6 cm) WIDE 20 1/4 IN. (51.4 cm) LENGTH 281/2 IN. (724 an) DEPTH MAXIMUM LID HEIGHT ABOVE VAT 15 IN. (38.1 cm) TEE BLOCK TOP VIEW 51N. (12.7 cm) 7 9/16 IN. IN. 3cm) I IN. 6cm) SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-34.1 7-1-09 REV. 1 'SPECIFIC APPLICATION BY MODEL (Continued) Note: In this application, R-102 agent storage tanks must be pres- I surized from a dedicated R-102 double-tank nitrogen cartridge. Henny Penny Mono Rail Center Lift System - Models 690, 691,692 I The cartridge utilized for this hazard-specific Henny Penny fryer Nozzle Type: (1) One IN nozzle, Part No. 419335 (Upper posi- protection cannot be shared with tanks intended for standard I R-1 02 protection. Standard protection will require an expellant gas tion) cartridge installed in another actuation device such as an ANSUL (1) One 1 F nozzle, Part No. 419333 (Lower posi- AUTOMAN regulated release or regulated actuator assembly. tion) Nozzle Location: 1 Nozzle (Upper position): From the Tee Block, part No. 434424, position nozzle tip 16 in. (40.6 cm) up from base of fryer surface and 5 in. (12.7 cm) in from right side of appliance back shroud 1 Nozzle (Lower Position): Running down from the Tee Block, Part No. 434424, to the base of the fryer, position the nozzle tip 2 in. (5.1 cm) from back side of fry vat, and 8 in. (20.3 cm) in from the right side of appliance back shroud Nozzle Aiming Point: 1 N Nozzle: At center point of fry vat 1 F Nozzle: The 1 F nozzle is a flat spray nozzle and the spray must be horizontal to that of the edge of the back lip of the fry vat System Coverage: Each fryer requires a minimum of 3 gal (11.4 L) of ANSULEX® Low pH agent discharging through the two one-flow nozzles (1 N and 1 F) FIGURE 71 AIMING PflIPT 5 IN. SIDE VIEW FIGURE 72 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-34.2 REV. 1 7-1-09 r SPECIFIC APPLICATION BY MODEL (Continued) Hen fly Penny Dual Lift System - Models 580,581,582, 590, 591,592,680,682 Nozzle Type: IN Nozzle (Upper position): From the Tee Block, part No. 434424, position nozzle tip 16 in. (40.6 cm) up from base of fryer surface and 5 in. (12.7 cm) in from left side of appliance back shroud IF Nozzle (Lower position): Running down from the Tee Block, Part No. 434424, to the base of the fryer, position the nozzle tip 2 in. (5.1 cm) from back side of fry vat, and 8 in. (20.3 cm) in from the left side of appliance back shroud Nozzle Aiming Point: 1 N Nozzle: At center point.of fry vat 1 F Nozzle: The 1 F nozzle is a flat spray nozzle and the spray must be horizontal to that of the edge of the back lip of the fry vat System Coverage: Each fryer requires a minimum of 3 gal (11.4 L) of ANSULEX Low pH agent discharging through the two one-flow nozzles (1 N and 1 F) NOTE 1: IT IS RECOMMENDED THAT THE AGENT DISTRIBUTION HOSE KIT, PART NO. 435982, BE UTILIZED DURING SYSTEM INSTALLATION. NOTE 2 VAT DIMENSIONS - 16 IN. (40.6 cm) WIDE 201/4 IN. (51.4 cm) LENGTH 281/2 IN. (72.4 cm) DEPTH MAXIMUM LID HEIGHT ABOVE VAT 15 IN. (38.1 cm) 79/16 IN. jEE 16 131 (42. FRONT VIEW (TEE BLOCK LOCATION) Note: In this application, R-102 agent storage tanks must be pres- surized from a dedicated R-102 double-tank nitrogen cartridge. The cartridge utilized for this hazard-specific Henny Penny fryer protection cannot be shared with tanks intended for standard R-102 protection. Standard protection will require an expellant gas cartridge installed in another actuation device such as an ANSUL AUTOMAN regulated release or regulated actuator assembly. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-34.3 7-1-09 REV. 0 Dunkin Donuts Fryer Model DD400CGF Nozzle Type: 3N Nozzle (Part No. 419338) Nozzle Spacing: 11.5 in. (292 mm) maximum from end of fryer and 25.5 in. (647 mm) maximum on centers Nozzle Height: 35 in. (889 mm) above top of appliance Nozzle Position: 2 in. (51 mm) in from inside edge of fry vat Nozzle Aim Point: Along the centerline of fry vat 25.5 IN. (647 mm) 25.5 IN. (254 mm) 25.5 IN. 10 IN. (254 mm) 25.5 IN. \ (647 mm) Krispy Kreme Fryers - Models 150 0/H, 270 D/H, 600 D/H, and 1000 D/H Nozzle Type: 3N Nozzle (Part No. 419338) Nozzle Spacing: 11.5 in. (29.2 cm) maximum from end of fryer and on maximum 25.5 in. (64.8 cm) centers Nozzle Height: 35 in. (88.9 cm) above top of appliance Nozzle Position: 2 in. (5.1 cm) from inside edge of fry vat Nozzle Aiming Point:Along centerline of fry vat Note: Figure 89 shows maximum size fryer (Model 1000 D/H). Smaller size fryers (Models 150 D/H, 270 D/H, and 600 D/H) can be protected with less nozzles but nozzle spacings, height require- ments, and positions, must be maintained as shown in Figure 89. 11.5 IN. 25.5 IN. .1.r (292 mm) 11.5 IN. (292 mm) 35 IN. (889 mm) Fryer Specifications: Vat Size: Length: 122 in. (310 cm Width: 31.3 in. (79.5 cm Depth: 11 in. (28 cm) BTU Rating: 360k Vat Oil Capacity: 1250 lb (567 kg) P. 7SO5a FIGURE 73 FIGURE 74 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-34.4 REV. 0 7-1-09 2W Nozzle 20 in. (508 mm) 007414 Front View (Feed Side) FIGURE 75 Nozzle W SIDE PLATE 6 1/2 in. (165 mm) Side View SECTION IV - SYSTEM DESIGN 0 UL EX3470 ULC EX3470 Page 4-35 7-1-09 REV. 6 ' SPECIFIC APPLICATION BY MODEL (Continued) DUKE Chain Broiler - Model FBB-High Proximity DUKE Chain Broiler With or Without Catalyst View: Nozzle Quantity/Type: (1) One 2W nozzle, Part No. 419337 Nozzle Height: 20 in. (508 mm) above top of appliance Nozzle Location: Centered 6 1/2 in. (165 mm) back from front feed edge of appliance. Nozzle must be oriented to spray onto impedance plate. Nozzle Aiming Point: Aimed at center of impedance plate DUKE Chain Broiler - Model FBB - Low Proximity Nozzle Location: 6.5 in. (16.5 cm) from front or back edge of hazard First nozzle positioned 17.25 in. (43.8 cm) from right side of broiler (facing broiler) Second nozzle positioned 15 in. (38.1 cm) from first nozzle Nozzle must be oriented to spray onto impedance plate. Nozzle Aiming Point: Aimed at at center of impedance plate Note: If the deflector or flue gas diverter is rotated 180 degrees, the nozzles must also rotate to discharge into the opening. I,...15 IN. 4j71I4 IN. I 6112 IN. (165 mm) 1 1(381 mm) 11438.15mm FLUE GAS FROM EDGE OF APPLIANCE THAT DEFLECTOR PLATE IS ANGLED TOWARD (SEE SIDE VIEW) T O OUTPUT I.. c$000$ GRILL 8 INiEmm) 10 - PERFORATED 245 NOZZLE DIVERTER 6112 IN. (165mm) '15 IN.381 mm) FROM EDGE OF APPLIANCE THAT \ NOZZLE HEIGHT PRODUCT —CENTER DEFLECTOR PLATE I DUCT IS ANGLED I TOWARD I PRODUCT OUTPUT JLJLAJL.1 PRODUCT INPUT BACK FRONT I comm TOP VIEW SIDE VIEW FIGURE 76 DUKE Chain Broiler With or Without Catalyst View Exhaust Deflector Size - 6.25 in. (15.9 cm) x 26.75 in. (67.9 cm): Nozzle Quantity/Type: (2) Two 245 nozzles, Part No. 419340. Nozzle Height: 8 in. to 15 in. (20.3 cm to 38.1 cm) above top of appliance. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-36 REV. 5 7-1-09 SPECIFIC APPLICATION BY MODEL (Continued) DUKE Electric Broiler - Model FBB - High Proximity DUKE Electric Broiler with or without Catalyst View Nozzle Quantity/Type: (2) Two 1 N nozzles Nozzle Height: 18 in. (45.7 cm) Nozzle Location: 6.5 in. (16.5 cm) from edge of appliance that deflector plate is angled toward First nozzle positioned 5 in. (12.7 cm) to left of opening centerline Second nozzle positioned 5 in. (12.7 cm) to right of opening centerline See Figure 77 Nozzle Aiming Point: Aimed at center of opening (2)- IN NOZZLE -F 18 IN. (457 mm) 6 1/2 IN. (165 mm) NOZZLE HEIGHT FROM EDGE OF--b- APPLIANCE THAT I DEFLECTOR I PLATE IS ANGLED I TOWARD I PRODUCT I - PRODUCT INPUT OUTPUT I BACK I I FRONT SIDE VIEW 008365 10 IN. (254 miii)254 mm) CENTERED 61/2 IN. (165 mm) FROM L ON OPENINGj EDGE OF APPLIANCE THAT DEFLECTOR PLATE PERFORATED IS ANGLED TOWARD - 00 000 ]' GRILL (SEE SIDE VIEW) f PRODUCT -,1 0I I 4-1-- o I xl I I CENTER OUTPUT DUCT 00000001 000 000 I I L.....PRODUCT INPUT 008366 _____________ TOP VIEW FIGURE 77 . DUKE Electric Broiler - Model FBB - High Proximity DUKE Electric Broiler without Catalyst View Nozzle Quantity/Type: (1) One 2W nozzle Nozzle Height: 20 in. (50.8 cm) Nozzle Location: 6.5 in. (16.5 cm) from edge of appliance that deflector plate is angled toward See Figure 78 Nozzle Aiming Point: Aimed at center of opening (1)- 2W NOZZLE -F 20 IN. (508 mm) 6 1/2 IN. (165 mm) NOZZLE HEIGHT FROM EDGE OF APPLIANCE THAT I 1 DEFLECTOR I PLATE IS ANGLED I TOWARD I PRODUCT _________ PRODUCT INPUT I OUTPUT BACK I I FRONT SIDE VIEW 006365 61/2 IN. (165 mm) FROM EDGE OF APPLIANCE THAT DEFLECTOR PLATE I PERFORATED IS ANGLED TOWARD I 000 000 000 g 000 I' GRILL (SEE SIDE VIEW) PRODUCT -4. 0' I I I I I CENTER OUTPUT 00000001 DUCT 0000000 I INPUT 008366 TOP VIEW FIGURE 78 PRODUCT - OUTPUT BACK 61/2 IN. (165 mm) FROM EDGE OF APPLIANCE - THAT DEFLECTOR PLATE IS ANGLED TOWARD - (SEE SIDE VIEW) PRODUCT OUTPUT SIDE VIEW 008365 15 IN. 171/2 IN. (381 mm (444.5 mm p -a p-1 0000 00 0000cSoo I oI Q. L 0X 1' 0 0000000 0000000 30 FRONT (2)1 N NOZZLES PART NO. 56930 II I] 1 14.25±11W. (36 cm) PERFORATED GRILL 12 INTO 13 IN. I CENTER (31 cm TO 33 cm) DUCT L. I (j..------ L - — - — - SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-37 7-1-09 REV. 5 SPECIFIC APPLICATION BY MODEL (Continued) DUKE Electric Broiler - Model FBB - Low Proximity DUKE Electric Broiler with or without Catalyst View Nozzle QuantityIrype: (2) Two 245 nozzles Nozzle Height: 8 in. (20.3 cm) to 15 in. (38.1 cm) Nozzle Location: 6.5 in. (16.5 cm) from edge of appliance that deflector plate is angled toward First nozzle positioned 17.5 in. (44.5 cm) from right side of broiler (facing broiler) Second nozzle positioned 15 in. (38.1 cm) from first nozzle See Figure 79 Nozzle Aiming Point: Aimed at center of opening (2)- 245 NOZZLE- 6 1/2 IN. (165 mm) FROM EDGE OF~ APPLIANCE THAT DEFLECTOR PLATE IS ANGLED TOWARD SPECIFIC APPLICATION BY MODEL (Continued) Nieco Broiler Model 940,962 or 960 With Catalytic Converter Protection Note: Nieco broilers without catalytic converters use standard chain broiler protection options. Certain models of the Nieco broiler (Models 940, 962, and 960) are equipped with a catalytic converter to comply with new clean air laws. Because of the converter, it is necessary to protect these broilers in a special way. The guidelines for protecting these broil- ers are as follows: - The maximum internal broiling area is 29 in. x 23.5 in. (74 cm x60cm). - An R-102 3-gallon system with a maximum of 6 flow numbers, must be used for protection of each broiler, including plenum and duct. - Each individual broiler must be protected with a minimum of (2) two, 1 N nozzles, Part No. 419335. The nozzles must be locat- P. as shown in Figure 80. - The broiler must be fitted with two 1 in. (2.5 cm) high agent bar- riers on the angled surface of the broiler. If these have not been completed by the equipment supplier, they must be added in the field. + 8 IN. (203 mm) 10 151N.(381 mm) NOZZLE HEIGHT PRODUCT INPUT TOP VIEW PRODUCT INPUT I LOCATE NOZZLES 2 13/16 IN. (7.1 cm) ON FIGURE 79 I EACH SIDE OF BROILER CENTER LINE 14.25±11W. (36 cm) r — — 000774 FIGURE 80 (2) 2W NOZZLES (305 mm) f 20 IN. I (508 MM) CENTERLINE OF LARGE OPENING FRONT VIEW FIGURE 82 007010 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-38 REV.8 7-1-09 SPECIFIC APPLICATION BY MODEL (Continued) Nieco Broiler - Model 950, 960,980, 1424 Nozzle Quantity/Type: (1) One 2W nozzle, Part No. 419337. Nozzle Height: 20 in. (508 mm). above top of appliance. See Figure 81a. Nozzle Location: 6 1/2 in. (165 mm) back from front edge of appliance. See Figure 81 a. Nozzle Aiming Point: Aimed at center of opening. See Figure 81a. Nieco Broiler - Model 950, 960,980, 1424 (with Catalytic Converter) Nozzle Quantity/Type: (2) Two 2W nozzles, Part No. 419337. Nozzle Height: 20 in. (508 mm) above top of appliance. See Figure 81b. Nozzle Location: 6 1/2 in. (165 mm) back from front edge of appliance. See Figure 81 b. Nozzle Aiming Point: Aimed at center of opening. See Figure ' 81b—Side View. Nozzle Aiming Point: Aimed at point 3 in. (76 mm) each side of center. See Figure 81 b - Front View. CATALYTIC J I I CONVERTER) /1 / 6 1/2 IN. 61/2 IN. Lr (165 mm) I Ii (165 mm) SIDE VIEW I SIDE VIEW 2W NOZZLE 2W NOZZLE 3IN. 31N. (76 mm) (76 mm) 20 t N. 20 IN. (508 mm) 1 (508 mm) CENTERLINE OF CENTERLINE OF LARGE OPENING LARGE OPENING FRONT VIEW FRONT VIEW FIGURE 81a FIGURE 81b 00648 007034 Niece Broiler - Model 9015 (With or Without Catalytic Converter) Nozzle Quantity/Type: (2) Two 2W nozzles, Part No. 419337. Nozzle Height: 20 in. (508 mm) above top of appliance. See Figure 82. Nozzle Location for Large Chamber: 6 1/2 in. (165 mm) back from front edge of appliance. See Figure 82. Nozzle Location for Small Chamber: Nozzle to be located 6 1/2 in. (165 mm) back from front edge of appliance and 12 in. (305 mm) over from large chamber nozzle. Nozzle Aiming Point for Large Chamber: Aimed at center of opening. See Figure 82. Nozzle Aiming Point for Small Chamber: Nozzle to be aimed 12 in. (305 mm) over from large chamber nozzle aiming point. Li L_61/2IN. (165 mm) SIDE VIEW SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-39 7-1-09 REV. 7 SPECIFIC APPLICATION BY MODEL (Continued) Nieco Broiler - Model 9025 (With or Without Catalytic Converter) Nozzle Quantity/Type: (2) Two 2W nozzles, Part No. 419337. Nozzle Height: 20 1/2 in. (521 mm) above top of appliance. See Figure 83. Nozzle Location: 6 1/2 in. (165 mm) back from front edge of appliance. See Figure 83. Nozzle Aiming Point: Aimed at center of each opening. See Figure 83. ---- =) SIDE VIEW (2)2W NOZZLES Nieco Broiler - Model MPB94 and MPB84 - High Proximity b. (With/Without Catalytic Converters) Nozzle Quantity/Type: (1) One 2W nozzle, Part No. 419337. Nozzle Height: 20 in. (508 mm) above top of converter. See Figure 84. Nozzle Location: Centered 6 1/2 in. (165 mm) back from any edge of the appliance. See Figure 84. Nozzle Aiming Point: Aimed at center of opening. See Figure 84. TOP VIEW 6112 IN. (165 mm)TYP. I I 1322 SIDE VIEWS I I I I 18-201121N. 61 (457.521 mm) (16I Tyf SIC I I --f--- I----.1----I CENTERLINE CENTERLINE OF OPENING OF OPENING FRONT VIEW FIGURE 83 004355 M) 007323 FIGURE 84 008487 BACK IL TOP VIEW TOP VIEW 245 NOZZLE 61/2 IN. (165mm) l 245 NOZZLE - SIDE VIEW SIDE VIEW OO88 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-40 REV. 6 7-1-09 SPECIFIC APPLICATION BY MODEL (Continued) Nieco Broiler - Model MPB94 - Low Proximity (With or Without Catalytic Converter) Nozzle Quantity/Type: (2) Two 245 nozzles, Part No. 419340. Nozzle Height: 8 in. to 15 in. (20.3 to 38.1 cm) measured from top of converter Nozzle Location: 6.5 in. (16.5 cm) from front or back edge of hazard. First nozzle positioned 7.5 in. (19.1 cm) to the right from center of hazard. Second nozzle positioned 7.5 in. (19.1 cm) to the left from center of hazard. See Figure 85. Nozzle Aiming Point: Aimed at opening on respective center lines AIM POINT 245 NOZZLE -f 245 NOZZLE AIM POINT Nieco Broiler - Model MPB84 - Low Proximity (With Catalytic Converter) Nozzle Quantity/Type: (2) Two 245 nozzles, Part No. 419340. Nozzle Height: 8 in. to 15 in. (20.3 to 38.1 cm) measured from top of converter Nozzle Location: 6.5 in. (16.5 cm) from front or back edge of hazard. First nozzle positioned 7.5 in. (19.1 cm) to the right from center of hazard. Second nozzle positioned 7.5 in. (19.1 cm) to the left from center of hazard. See Figure 86. Nozzle Aiming Point: Aimed at opening on respective center lines AIM POINT 245 NOZZLE : 245 NOZZLE AIM POINT BACK FRONT -r 71/2 IN. (191 mm) 7 1/2 IN. (191 mm) 6 1/2 IN. ( mm)' 165 _c FRONT b. FIGURE 85 1b. FIGURE 86 (2)— IN NOZZLE AIM Lo& fDINT 51N.(127 MT) I AP °cP 0000 _( 5 IN (127 • oo Pool I110, 61/2IN.(165m0) FROM FRONT OR —0. - —O 001 AIM I•'Oc90 BACK EDGE -t 0 0 IPOINT L0 O%j BACK FRONT 008370 c. TOP VIEW 71/2IN.(191 mm] 7 1/2 IN. (19± 6 1/2 IN. (165 mm) FROM FRONT OR -. BACK EDGE BACK 'c 00 AIM 1p INT 0000 'i 0d od p00 F1 t o 00 POINT 0 AIM c. TOP VIEW =1 FRONT 008370 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-41 7-1-09 REV.6 SPECIFIC APPLICATION BY MODEL (Continued) Nieco Broiler - Model MPB84 and MPB94 - High Proximity (With Perforated Cap OR with Catalytic Converter and Chimney) Nozzle Quantity/Type: (2) Two 1 N nozzles Nozzle Height: 18 in. (45.7 cm) to 20 in. (50.8 cm) Nozzle Location: 6.5 in. (16.5 cm) from front or back edge of haz- ard First nozzle positioned 5 in. (12.7 cm) to left of opening centerline Second nozzle positioned 5 in. (12.7 cm) to right of opening centerline See Figure 87 Nozzle Aiming Point: Aimed at center of opening (2)— IN NOZZLE WITH OR WITHOUT CHIMNEY 6112 IN. (165mm) 18 IN. (457 mm) TO FROM FRONT _ 20 IN. (508 mm) OR BACK EDGE ...-.... - - NOZZLE HEIGHT PRODUCT PRODUCT OUTPUT.. INPUT Nieco Broiler - Model MPB84 and MPB94 - Low Proximity (With Perforated Cap OR with Catalytic Converter and Chimney) Nozzle Quantity/Type: (2) Two 245 nozzles Nozzle Height: 8 in. (20.3 cm) to 15 in. (38.1 cm) Nozzle Location: 6.5 (16.5 cm) from front or back edge of hazard First nozzle positioned 7.5 in. (19.1 cm) to the right of hazard centerline Second nozzle positioned 7.5 in. (19.1 cm) to the left of hazard centerline See Figure 88 Nozzle Aiming Point: Aimed at center of opening (2) -245 NOZZLE - \ WITH OR WITHOUT ' CHIMNEY 8 IN. (203 mm) TO FROM FRONT —s- L1— 15 IN. (381 mm) OR BACK EDGE •—I-. --. - NOZZLE HEIGHT PRODUCT PRODUCT OUTPUT. INPUT BACK I FRONT BACK I I FRONT SIDE VIEW 008369 SIDE VIEW 008369 (2)— 245 NOZZLE FIGURE 87 FIGURE 88 CENTERED ON CONVERTER Cc FRONT VIEW SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-42 REV.7 7-1-09 SPECIFIC APPLICATION BY MODEL (Continued) Marshall Air - Model 2001 BK Multi-Chamber Broiler Nozzle Quantity/Type: (2) Two 1W nozzles, Part No. 419347. Nozzle Location: Front nozzle tip must be located 14 in. direct- ly above the appliance, aligned with the front face and centerline of the catalytic converter. The aim point is 4 in. forward of the front edge of the converter on the centerline. The rear nozzle tip is a mirror image of the front. The rear noz- zle is located 14 in. vertically above the appliance, aligned with the "rear" face and centerline of the catalytic converter. The aim point is 4 in. behind the "rear" edge of the converter on the cen- terline. See Figure 89. System Limitation: Maximum of 5 flows for a 3.0 gallon sys- tem: Remaining flow points available may be used to protect other hazards. ZLES Marshall Air Electric Broiler - Model FR14B AutoBroil Nozzle Quantity/Type: One 260 Nozzle (Part No. 419341) Nozzle Height: 15 —20 in. (38.1 - 50.8 cm) above the top of the broiler Nozzle Location: The nozzle must be centered above the front edge of the broiler Nozzle Aiming Point: Aimed at the center of the exhaust opening of the broiler. See Figure 90. 24.25 IN. 14.50 IN. (61.6 cm) (36.8 cm) 15-20 IN. (38.1— 50.8 cm) 24 IN. 34.69 IN. I (61.0cm) (88.1cm) • 48 IN. (121.9 cm) NOZZLE ALIGNED WITH FRONT OF CONVERTER NOZZLE ALIGNED WITH NOZZLE ALIGNED WITH BACK FRONT OF CONVERTER, OF CONVERTER, AIMED AIMED 4 IN. (102 mm) BACK 4 IN. (102 mm) FORWARD liW 1W NOZZLE NOZZLE $ - 14 IN. 14 IN. (356mm) (102mm) (356mm) FIGURE 90 006737 Grease Grabber-80m' Two Stage Filtration System The Grease Grabber-80 Two Stage Filtration System consists of two components: The primary filter (The Grease-X Tractor) and the secondary filter (The Grease Grabber-80). The protection required for this application is the same as the stan- dard plenum/filter protection: One (1)1 N Nozzle, Part No. 419335, protecting 10(3.1 m) linear feet of plenum length by 4 ft (1.2 m) of plenum chamber depth (width), positioned 2-4 in. (5-10 cm) from m. peak of secondary filter. See Figure 91. 4 FT. (1.2 m) MAXIMUM 0034168 SIDE VIEW FILTER FIGURE 89 NOZZLE / FILTER ' I 241N. (6-10 CM) NOTE: TWO NOZZLES MUST BE UTILIZED FOR V-BANK FILTER ARRANGEMENT. FIGURE 91 006526 For appliance hazard surfaces with listed protection exceed- ing the standard hazard zone of 28 in. (71.1 cm) in depth, the hazard surface(s) must be aligned with the back edge of the hazard zone, with the front edge overhanging the front edge of the zone. See Appliance Chart, Table 1. For appliance hazard surfaces that exceed the listed protec- tion sizes, multiple zones must be utilized. Align entire hazard surface area within the multiple zones. All hood, duct, individual appliance, and piping limitations are as specified in the R-102 Design, Installation, Recharge and Maintenance Manual, Part No. 418087. All appliance protection currently listed in the R-102 Design Manual, Part No. 418087, is also approved protection. Zone pro- tection can be considered optional protection. TABLE 1 Overlapping Nozzle Coverage (Zone Protection) Appliance Type Maximum Cooking Hazard Fryer 34 in. (86.4 cm) Deep x 5.8 ft2 (0.5 m2) Griddle 30 in. (76.2 cm) Deep x Unlimited Length Range 28 in. (71.1 cm) Deep x Unlimited Length Wok, Maximum 30 in. (76.2 cm) Diameter x 8 in. (20.3 cm) Deep Wok, Minimum 11 in. (27.9 cm) Diameter x 3 in. (7.6 cm) Deep Braising Pan/Tilt 34 in. (86.4 cm) Deep x Unlimited Skillet* Length Lava Rock 32 in. (81.3 cm) Deep x Unlimited Char-Broiler Length Charcoal Broiler 32 in. (81.3 cm) Deep x Unlimited Length (4 in. (10.2 cm) Maximum Fuel Depth) Mesquite Wood 32 in. (81.3 cm) Deep x Unlimited Length Broiler (12 in. (30.5 cm) Maximum Fuel Depth) Gas Radiant 36 in. (91.4 cm) Deep x Unlimited Char-Broiler Length Electric Char-Broiler 34 in. (86.4 cm) Deep x 20 in. (50.8 cm) * See Figure 91 a for nozzle location COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN Ill j -t' 0-6 IN. (0.15 cm) I j 40-45 IN. (1-1.1 m) Ii I ZONE SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43 7-1-09 REV. 6 OVERLAPPING NOZZLE COVERAGE Overlapping Coverage - Option 1 For each group of protected appliances under a common hood(s), the overlapping nozzles must be located from right to left so that each end nozzle is located a maximum of 6 in. (15.2 cm) inside the outside edge of the cooking hazard of each end appliance, and the inside overlapping nozzles must be located between the two end nozzles at a maximum spacing of 12 in. (30.5 cm). Hazard Zone The hazard zone is defined as a theoretical, flat and level, rectan- gular surface, that includes all of the cooking hazards of the pro- tected appliances under a common hood(s). The purpose of the hazard zone is to provide a means of locating the appliances and the overlapping nozzles, as well as aiming the overlapping noz- zles. The hazard zone measures 28 in. (71.1 cm) deep by the length of the cooking hazard(s). The centerline of the hazard zone must bisect the 28 in. (71.1 cm) depth (from front to back) and run from right-to-left for the full width of the hazard zone. Overlapping Nozzle Appliance Protection Overlapping Nozzle Appliance Protection is defined as protection of cooking appliances by nozzles spaced uniformly at uniform ele- vations under a common hood(s). Overlapping protection of appli- ances is continuous for the full length of the hood or divided when group(s) of protected appliances are separated by counters or appliances not requiring protection. Full hood continuous protection is defined as overlapping noz- zle appliance protection that covers the appliance line-up located under the total hood length. All appliances requiring protection are the appliances under the hood that can be an ignition source of grease in the hood, grease removal device or the duct Group protection is defined as overlapping nozzle appliance pro- tection that protects individual hazard zones located under a com- mon. hood. These "groups" of appliances may be separated by appliances not requiring protection, such as steam equipment or work tables, or by dedicated appliance protection, such as sala- mander broilers. See Figure 91d (full hood continuous protection) and Figure 91e (multiple group protection). Dedicated Nozzle Appliance Protection Appliance protection using dedicated nozzle coverage is defined as protection of cooking appliances with enclosed cooking haz- ards, such as upright broilers, which cannot be protected with overlapping nozzles and therefore must be protected with nozzles dedicated to the appliance. General Design Limitations Maximum depth of zone is 28 in. (71.1 cm). The 245 nozzle, Part No. 419340, is the only approved nozzle for overlapping (zone) protection. Nozzle must be located 0 in. to 6 in. (0 cm to 15.2 cm) forward of zone centerline, aimed back at the zone centerline. Nozzles must be spaced a maximum of 6 in. (15.2 cm) from each end of hazard and then a maximum of 12 in. (30.5 cm) on center for the remaining overlapping nozzles until the complete hazard is covered. ZONE CENTER LINE FIGURE 91a 0m927 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43.1 REV.0 7-1-09 OVERLAPPING NOZZLE COVERAGE (Continued) Overlapping Appliance Nozzle and Hazard Zone Locations All overlapping appliance nozzles must be the "245" nozzle, Part No. 419340, and must be located under a common hood at the same height above the hazard zone, in a straight line from right to left and aimed at the centerline of the hazard zone. The overlapping nozzle is used for both continuous over- lapping and multiple group overlapping protection. The hazard zone must be positioned (located) so that all appli- ance hazard surfaces are within the zone. For appliance haz- ard surfaces with listed protection exceeding the standard hazard zone size of 28 in. (71 cm) in depth (see Table 1), the hazard surface(s) must be aligned with the back edge of the hazard zone, with the front edge overhanging the front of the zone. The overlapping appliance nozzles must be located 40 in. to 45 in. (1 m to 1.1 m) above the top surface of the protected appliances. See Figure 91c. Exception No. 1: Nozzle dimensions for wok protection are measured to bottom of wok. Exception No. 2: When using overlapping appliance nozzles in areas where there is a back shelf, the nozzle cannot be positioned in the shaded area as shown in Figure 91b. Also, back shelf must not extend more than 11 in. (27.9 cm) over the hazard zone and cannot be less than 20 in. (50.8 cm) above the hazard zone. See Figure 91 b. /- OVERLAPPING NOZZLE(S) 45 CANNOT BE POSITIONED 44 IN THIS SHADED AREA 43 42 40 ..__ CENTER LINE OF HAZARD ZONE BACK SHELF 11 IN. (27.9 cm) MAXIMUM 20 IN. (50.8 cm) MINIMUM I 4_ 28 IN. (71.1 cm) FIGURE 91b 006914 The overlapping appliance nozzles must be located 0 in. to 6 in. (0 cm to 15.2 cm) forward of the centerline or aimline of the selected hazard zone. See Figure 91c. 245 NOZZLE - NOZZLE MUST BE AIMED STRAIGHT - DOWN OR BACK AT CENTERLINE OF HAZARD ZONE - 61N (15.2 CM) 45 IN. (1.1 m) 40 IN. (I M) FRONT BACK OF ZONE OF ZONE L 28 IN. CENTERLINE OF HAZARD ZONE 71.1 ZONE FIGURE 91c 006915 6 IN. -* (15.2 cm) MAXIMUM FROM EDGE OF I COOKING / HAZARD / .- 6IN. (15.2 Cm) MAXIMUM FROM EDGE OF COOKING HAZARD SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43.2 7-1-09 REV.0 OVERLAPPING NOZZLE COVERAGE (Continued) Overlapping Appliance Nozzle and Hazard Zone Locations - Group Protection 1. For each group of protected appliances under a common hood(s), the overlapping nozzles must be located from right to left so that each end nozzle is located a maximum of 6 in. (15.2 cm) inside the outside edge of the cooking hazard of each end appliance, and the inside overlapping nozzles must be located between the two end nozzles at a maximum spac- ing of 12 in. (30.5 cm). See Figures 91d and 91e. 12 IN. (30.5 cm) MAXIMUM SPACING(S) BETWEEN OVERLAPPING NOZZLES FULL HOOD CONTINUOUS APPLIANCE PROTECTION FIGURE 91d miiio 2. When obstructions are located adjacent to appliance(s) pro- tected by overlapping nozzles, the overlapping appliance noz- zle spacing must start with the appliance(s) adjacent to the obstruction. See Figure 91f. 12 IN. 12 IN. 12 IN. 12 IN 6 IN. 1(30.5 CM) 1(30.5 cm) 1(30.5 cm) 1(30.5 cm) L_.. (15.2 cm) ..... MAX. 6 IN. (15.2 cm) MAX. 4MAX. MAX.- MAX. 4 MAX. OUTSIDE I EDGE OF I I COOKING HAZARD • HAZARD AREA Ii OBSTRUCTION FIGURE 91f 001713 3. When an appliance requires dedicated protection with a pro- tected area intended for overlapping appliance nozzle protec- tion, the group protection option will be required for appliances on either side of the appliances using dedicated protection. Group protection using overlapping appliance nozzles must begin with the protected appliance(s) adjacent to the dedicat- ed appliance protected. An overlapping appliance nozzle(s) must be positioned within 6 in. (15.2 cm) of the edge(s) of the appliance hazard surface area(s) adjacent to the dedicated nozzle protection. See Figure 91g. 12 IN. (30.5 cm) 6 IN. (15.2 cm) I I MAXIMUM MAXIMUM ___ L EDGE OF COOKING HAZARD 61N. I •L I I I L 61N. 12 IN. (15.2 cm) + 12 IN. + $ 12IN. $ 12 IN. $ (15.2 cm) MAXIMUM I (30.5 cm) I MAXIMUM (15.2 cm) 1(30.5cm)l 1(30.5 cm)I(30.5 cm)I 6 IN. FROM ____________________ ______________ F' (15.2 CM) MAXIMUM I FROM MAX. I MAX. I EDGE OF ___________________ - EDGE OF _____________________ _______________ MAX. I MAX. I MAX. I COOKINGCOOKING I I COOKING HAZARD HAZARD 61N.(15.2cm) EDGE HAZARD EDGEOF I I HAZARD EDGE- 6lN.(l5.2cri) _______ OF MAXIMUM MAXIMUM OF I I I COOKING ' COOKING I I HAZARD GROUP APPLIANCE PROTECTION FIGURE 91e 001720 DEDICATED NOZZLE APPLIANCE FIGURE 91g 001756 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43.3 REV. 0 7-1-09 OVERLAPPING NOZZLE COVERAGE (Continued) Overlapping Appliance Nozzle and Hazard Zone Locations - Group Protection (Continued) 4. On protected appliances, all hazard surfaces located in a group must be within 40-45 in. (102-114 cm) from the noz- zle(s). Once that dimension is exceeded, a new group must be started. See Figure 91h. Note: The supply pipe feeding nozzle groups is to be at the same elevation. Adjust height for each group only by varying lengths of nozzle drops. 6 IN. (15.2 cm) __ 6 IN. (15.2 cm) MAXIMUM MAXIMUM I I I I I I NOZZLES + t t I 401N. NOZZLES 45 IN. (102 cm) I 114 FIGURE 91h 006917 Detection Requirements For Overlapping Appliance Protection When utilizing overlapping appliance protection, fusible link detec- tors must be installed on a maximum of 2 ft (0.61 m) centers, starting with detectors located in (under) the duct opening(s). Starting from the detector under the duct opening, add detectors on 2 It (0.61 m) maximum spacing until the complete length of the plenum area is covered, from one end to the other. The location of the last detector on each end of the plenum must not exceed 2 ft (0.61 m) from end of plenum. Note: Standard detector coverage, as specified in "Design Section," is acceptable when utilizing dedicated nozzle cov- erages. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-43.4 7-1-09 REV. 0 OVERLAPPING NOZZLE COVERAGE (Continued) r Overlapping Coverage - Option 2 For each group of protected appliances under a common hood(s), the overlapping nozzles must be located from right to left so that each end nozzle is located a maximum of 11.5 in. (29.2 cm) inside the outside edge of the cooking hazard of each end appliance, and the inside overlapping nozzles must be located between the two end nozzles at a maximum spacing of 25.5 in. (64.8 cm). Hazard Zone The hazard zone is defined as a theoretical, flat and level, rectan- gular surface, that includes all of the cooking hazards of the pro- tected appliances under a common hood(s). The purpose of the hazard zone is to provide a means of locating the appliances and the overlapping nozzles, as well as aiming the overlapping noz- zles. The hazard zone measures 28 in. (711 mm) deep by the length of the cooking hazard(s). The centerline of the hazard zone must bisect the 28 in. (711 mm) depth (from front to back) and run from right-to-left for the full width of the hazard zone. Overlapping Nozzle Appliance Protection Overlapping Nozzle Appliance Protection is defined as protection of cooking appliances by nozzles spaced uniformly at uniform ele- vations under a common hood(s). Overlapping protection of appli- ances is continuous for the full length of the hood or divided when group(s) of protected appliances are separated by counters or appliances not requiring protection. Full hood continuous protection is defined as overlapping noz- zle appliance protection that covers the appliance line-up located under the total hood length. All appliances requiring protection are the appliances under the hood that can be an ignition source of grease in the hood, grease removal device or the duct. Group protection is defined as overlapping nozzle appliance pro- tection that protects individual hazard zones located under a com- mon hood. These "groups" of appliances may be separated by appliances not requiring protection, such as steam equipment or work tables, or by dedicated appliance protection, such as sala- mander broilers. See Figure 95 (full hood continuous protection) and Figure 96 (multiple group protection). Dedicated Nozzle Appliance Protection Appliance protection using dedicated nozzle coverage is defined as protection of cooking appliances with enclosed cooking haz- ards, such as upright broilers, which cannot be protected with overlapping nozzles and therefore must be protected with nozzles dedicated to the appliance. General Design Limitations If overlapping appliance protection is mixed with dedicated appli- ance protection on the same pipe system, THE OVERLAPPING APPLIANCE PROTECTION PIPING REQUIREMENTS MUST BE FOLLOWED. Overlapping protection requires the use of 3.0 gal (11.4 L) tank(s) and a maximum of six (6) flows per tank. In installations using tanks only intended for overlapping protec- tion, a single Double Tank nitrogen expellant gas cartridge can be utilized with up to three (3) 3.0 gal (11.4 L) tanks. In installations using both overlapping protection and conven- tional non-overlapping protection (ex. hood/duct or dedicated appliance protection), a single Double Tank nitrogen expellant gas cartridge can be utilized with up to three (3) 3.0 gal (11.4 L) tanks, as long as none of the 3.0 gal (11.4 L) tanks exceed a total flow output of more than six (6) flows. If more than six (6) flows will be used in a conventional non- overlapping tank, it cannot share the same cartridge as tanks intended for overlapping protection. In this case, an additional Regulated Actuator Assembly with another expellant gas car- tridge will be required. The 245 nozzle, Part No. 419340, must be used for "end of zone' protection. The 260 nozzle, Part No. 419341, must be used for zone pro- tection. Maximum depth of zone is 28 in. (71.1 cm). Refer to overlapping system piping requirements listed in Table 2. Nozzle must be located 0 in. to 12 in. (0 cm to 30.5 cm) forward of zone centerline, aimed back at the zone centerline. Nozzles must be spaced a maximum of 11.5 in. (29.2 cm) from each end of hazard and then a maximum of 25.5 in. (64.8 cm) on center for the remaining overlapping nozzles until the com- plete hazard is covered. For appliance hazard surfaces with listed protection exceed- ing the standard hazard zone of 28 in. (71 cm) in depth, the haz- ard surface(s) must be aligned with the back edge of the hazard zone, with the front edge overhanging the front edge of the zone. See Appliance Chart, Table 1. For appliance hazard surfaces that exceed the listed protec- tion sizes, multiple zones must be utilized. Align entire hazard surface area within the multiple zones. All hood, duct, and individual appliance protection are as speci- fied in the R-102 Design, Installation, Recharge and Mainten- ance Manual, Part No. 418087. All appliance protection currently listed in the R-102 Design Manual, Part No. 418087, is also approved protection. Zone pro- tection can be considered optional protection. Lava Rock 26 in. (66.0 cm) Deep x Unlimited Char-Broiler (see Note 1) Length Charcoal Broiler 30 in. (76.2 cm) Deep x Unlimited Length 3. (4 in. (10.2 cm) Maximum Fuel Depth) Mesquite Wood 30 in. (76.2 cm) Deep x Unlimited Length Broiler (6 in. (15.2 cm) Maximum Fuel Depth) Gas Radiant 36 in. (91.4 cm) Deep x Unlimited Char-Broiler Length Electric Char-Broiler 34 in. (86.4 cm) Deep x Unlimited Length * See Figure 92 for nozzle location Note 1: Always try to place Lava Rock Char-Broiler(s) near the center of the zone. When the Lava Rock Char-Broiler is the first or last appliance in the zone, the outside edge of the broiler must not be more than 6 in. (15 cm) outside the end nozzle. COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN II 0-12 IN. I (0-30.5 cm) 40-45 IN. I (1-1.1 M) I I I? I ZONE SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-44 REV.6 7-1-09 OVERLAPPING NOZZLE COVERAGE (Continued) TABLE 1 Overlapping Nozzle Coverage (Zone Protection) Appliance Type Maximum Cooking Hazard Fryer 34 in. (86.4 cm) Deep x 5.8 ft2 (0.5 m2) Griddle 30 in. (76.2 cm) Deep x Unlimited Length Range 30 in. (76.2 cm) Deep x Unlimited Length Wok, Maximum 30 in. (76.2 cm) Diameter x 8 in. (20.3 cm) Deep Wok, Minimum 11 in. (27.9 cm) Diameter x 3 in. (7.6 cm) Deep Braising Panrnit 34 in. (86.4 cm) Deep x Unlimited Skillet* Length Overlapping Appliance Nozzle and Hazard Zone Locations All overlapping appliance nozzles must be the 245 nozzle, Part No. 419340, for "end of zone" protection and the 260 noz- zle, Part No. 419341, for zone protection, and must be located under a common hood at the same height above the hazard zone, in a straight line from right to left and aimed at the cen- terline of the hazard zone. The overlapping nozzle is used for both continuous overlapping and multiple group overlapping protection. The hazard zone must be positioned (located) so that all appli- ance hazard surfaces are within the zone. For appliance haz- ard surfaces smaller than the standard hazard zone size, the hazard surface can be located anywhere within the standard hazard zone. For appliance hazard surfaces with listed pro- tection exceeding the standard hazard zone size of 28 in. (71 cm) in depth (see Table 1), the hazard surface(s) must be aligned with the back edge of the hazard zone, with the front edge overhanging the front of the zone. The overlapping appliance nozzles must be located 40 in. to 45 in. (1 m to 1.1 m) above the top surface of the protected appliances. See Figure 94. Exception No. 1: Nozzle dimensions for wok protection are measured to bottom of wok. Exception No. 2: When using overlapping appliance nozzles in areas where there is a back shelf, the nozzle cannot be positioned in the shaded area as shown in Figure 93. Also, back shelf must not extend more than 11 in. (27.9 cm) over the hazard zone and cannot be less than 18 in. (45.7 cm) above the hazard zone. See Figure 93. /- OVERLAPPING NOZZLE(S) 45 CANNOT BE POSITIONED I IN THIS SHADED AREA 43 42 41 40 1210 ..__ CENTER LINE OF HAZARD ZONE BACK SHELF 11 IN. (27.9 cm) MAXIMUM 18 IN. (45.7 cm) MINIMUM ZONE CENTER LINE FIGURE 92 006927 ~__ 28 IN.(71.1 cm) FIGURE 93 005914 11.5 IN. (29.2 cm) MAXIMUM FROM EDGE OF COOKING HAZARD / 4- 11.5 IN. (29.2 cm) MAXIMUM FROM EDGE OF COOKING HAZARD SECTION IV - SYSTEM DESIGN a UL EX3470 ULC EX3470 Page 4-45 7-1-09 REV. 4 OVERLAPPING NOZZLE COVERAGE (Continued) 4. The overlapping appliance nozzles must be located 0 in. to 12 in. (0 cm to 30.5 cm) forward of the centerline or aimline of the selected hazard zone. See Figure 94. 245 OR 260 NOZZLE MUST BE AIMED STRAIGHT DOWN OR BACK AT CENTERLINE OF HAZARD ZONE 12 IN. 446- (305 m) 45 IN 40 IN. (I m) FRONT • "" BACK OF ZONE OF ZONE L CENTERLINE OF _______ HAZARD ZONE (71.1cm ZONE FIGURE 94 001537 Table 2 Overlapping System Piping Limitations Overlapping Appliance Nozzle and Hazard Zone Locations - Group Protection 1. For each group of protected appliances under a common hood(s), the overlapping nozzles must be located from right to left so that each end nozzle is located a maximum of 11.5 in. 11. (29.2 cm) inside the outside edge of the cooking hazard of each end appliance, and the inside overlapping nozzles must be located between the two end nozzles at a maximum spac- ing of 25.5 in. (64.8 cm). See Figures 95 and 96. 25.5 IN. (64.8 cm) MAXIMUM 1 SPACING(S) BETWEEN OVERLAPPING NOZZLES I I I I I I FULL HOOD CONTINUOUS APPLIANCE PROTECTION FIGURE 95 007538 Total Max. 3/8 in. Max. Maximum System Flow Pipe No. of Elevation Cartridge I T Size Numbers Length Elbows Rise Size 3 Gallon 6 75 ft 25 lOft LT-30-R e I 25.5 IN. (64.8cm) 11.5 IN. (29.2 cm) (11.4 L) (22.9 m) (3.1 m) MAXIMUM MAXIMUM 6 Gallon 12 75 ft 25 loft Double (22.7 L) (22.9 m) (3.1 m) Tank/ 11.5 IN. I 1245 245' Manifolded LT-A-101- (29.2 cm) 245 260 245 25.5 IN. _.j . L I 30* 01 MAXIMUM I (64.8 cm) FROM I MAXIMUM 9 Gallon 18 75 it 25 loft Double EDGE OF COOKING I (34.1 L) (22.9 m) (3.1 m) Tank/ HAZARD I I JEDGE OF I I LT-A-101- I I OKING 30* I II I - 11.5 IN. (29.2 cm) MAXIMUM FROM EDGE OF COOKING HAZARD 50 ft (15.2 m) maximum pipe from first to last nozzle. 50 ft (15.2 m) maximum pipe after the split on a split system. *Use with regulated actuator only- GROUP APPLIANCE PROTECTION NOTE: On group appliance protection, Start and end of EACH zone group must be protected with a 245 nozzle. 0. FIGURE 96 001720 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-46 REV.6 7-1-09 OVERLAPPING NOZZLE COVERAGE (Continued) Overlapping Appliance Nozzle and Hazard Zone Locations - Group Protection (Continued) When obstructions are located adjacent to appliance(s) pro- tected by overlapping nozzles, the overlapping appliance noz- zle spacing must start with the appliance(s) adjacent to the obstruction. See Figure 97. 25.5 IN. 25.5 IN. 25.5 IN. 25.5 IN. I 11.5 IN. I 1(64.8cm) j(64.8 cm) (64.8 cm) (29.2 cm) ........ ,._ 1 1.5 IN. 4 MAX. 41MAx. -MAX.- + MAX. 4 245 260 260 260 245 MAX. (29.2 cm) MAX. 1 J - OUTSIDE II EDGE OF COOKING HAZARD I-I HAZARD AREA OBSTRUCTION NOTE: On continuous appliance protection, start and end with 245 nozzles and 260 nozzle(s) in the middle. FIGURE 97 001713 When an appliance requires dedicated protection with a pro- tected area intended for overlapping appliance nozzle protec- tion, the group protection option will be required for appliances on either side of the appliances using dedicated protection. Group protection using overlapping appliance nozzles must begin with the protected appliance(s) adjacent to the dedicat- ed appliance protected. An overlapping appliance nozzle(s) must be positioned within 11.5 in. (29.2 cm) of the edge(s) of the appliance hazard surface area(s) adjacent to the dedicat- ed nozzle protection. See Figure 98. EDGE OF COOKING HAZARD 11.5 IN. I Y 25.5 IN.? J I 25.5 IN. 25.5 IN. y (29.2 cm)-,,.I l(64.Bcm)l I I I(6 (29.2c m4.8cm)l(64.8cm)I 115 IN. L ) MAX. - ' IMAX. I MAX. I MAX. EDGE ---- ...I 11.5 IN. I11.5 IN. (262cm) I....EDGE p. OF I (29.2 cm) MAX. I I MAXIMUM ___ I OF = COOKING COOKING_- HAZARD I 1 HAZARD -I, L_1____ DEDICATED NOZZLE APPLIANCE NOTE: On group appliance protection, start and end of EACH zone group must be protected with a 245 nozzle. FIGURE 98 001756 On protected appliances, all hazard surfaces located in a group must be within 40-45 in. (1-1.1 m) from the nozzle(s). Once that dimension is exceeded, a new group must be start- ed. See Figure 99. Note: The supply pipe feeding nozzle groups is to be at the same elevation. Adjust height for each group only by varying lengths of nozzle drops. 11.5 IN. (29.2 cm) MAXIMUM AI--i- I I I I 4 $ I I I I I END OF i I NOZZLES ZONE I 401N. NOZZLES 451N. (1.0m) 401N. I . I I (1.1w) I END OF (1.0 m) 45 IN. ZONE I (1.1 m) i I NOTE: On group appliance prolection, start and end of EACH zone group must be protected with a 245 nozzle. FIGURE 99 007539 Detection Requirements For Overlapping Appliance Protection When utilizing overlapping appliance protection, fusible link detec- tors must be installed on a maximum of 2 ft (0.61 m) centers, starting with detectors located in (under) the duct opening(s). Starting from the detector under the duct opening, add detectors on 2 ft (0.61 m) maximum spacing until the complete length of the plenum area is covered, from one end to the other. The location of the last detector on each end of the plenum must not exceed 2 It (0.61 m) from end of plenum. Note: Standard detector placement can also be utilized when using overlapping protection. However, the overlapping detector option cannot be used when utilizing standard R-102 protection. Refer to Pages 4-57 and 4-58 for detector placement. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-47 7-1-09 REV. 5 TANK AND CARTRIDGE REQUIREMENTS Once the hazard analysis is completed and the total nozzle flow numbers are established, the quantity and size of agent tanks and cartridges needed to supply the nozzles with the proper volumes of agent at the proper flow rates can be determined. For cartridges used in the regulated release mechanism, flow capacities, tank quantities and sizes, and regulated release cartridge options are given in the table below. Total Quantity and Regulated Release Flow Numbers* Size of Tank(s) Cartridge Options Nitrogen Carbon Dioxide 1— 5 (1) 1.5 Gallon LT-20-R 101-10 6-11 (1) 3.0 Gallon LT-30-R 101-20 11-16 (1) 1.5 Gallon Double 101-30 3.0 Gallon 16-22 3.0 Gallon Double 101 16-22 (2) 3.0 Gallon Double - (Manifold) 22-33 (3) 3.0 Gallon Double - When one or more regulated actuators are used, the following tank and cartridge combinations apply for each regulated actuator: Regulated Actuator Regulated Actuator Tank(s) Cartridge (1) 1.5 Gallon LT-20-R or 101-10 (1) 3.0 Gallon LT-30-R or 101-20 (1) 1.5 Gallon and LT-A-101-30 or 10130** or 3.0 Gallon double tank 3.0 Gallon LT-A-101-30 or 101-30** or double tank P. (2) 3.0 Gallon (Manifold) LT-A-101-30 or Double s. (3) 3.0 Gallon LT-A-101-30 or Double For exceptions to maximum flow numbers, see Distribution Piping Requirements for 1.5 gallon and 3.0 gallon systems in this Section. The 101-30 cartridge can not be used when (2) two 3.0 gallon tanks are manilotded together. For higher total flow numbers (23 to 110), multiple cartridges and regulated actuators are required as shown in the System Selection Guide in Section IX - Appendix. ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS This section contains the guidelines for installing the actuation and expellant gas lines between the regulated release mechanism reg- ulator, each regulated actuator regulator, and each agent tank. These limitations should be considered when selecting the com- ponent mounting locations. The actuation gas line is the length of pipe and/or hose that is run from either the AUTOMAN Regulated Release Assembly or the Remote Release Assembly that directs high pressure from the cartridge in the release to actuate one or more additional Regulated Actuator Assemblies. The actuation gas line can consist of 1/4 in. Schedule 40 black iron, chrome-plated, stainless steel, or galvanized steel pipe and fittings, and/or factory supplied stainless steel braided actuation hose. The expellant gas line is the length of pipe that is run from the regulator in either the AUTOMAN Regulated Release Assembly or a Regulated Actuator Assembly that directs regulated pressure to the agent storage tanks to pressurize the tank and discharge the agent. The expellant gas line shall consist of 1/4 in. Schedule 40 black iron, chrome-plated, stainless steel, or galvanized steel pipe and fittings. ' Actuation Gas Line _6108* Tanks Maximum 8 Tank maximum reflects the utilization of 3 tank regulated actuators. Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- nized, chrome-plated, or stainless steel pipe and fittings. The actuation gas line piping is installed from the regulated release mechanism to each regulated actuator connected within the system. The total length of the actuation gas line from the regulated release assembly to the regulated actuator assembly(ies) must not exceed 20 ft (6 m) when using an LT-20-R, an LT-30-R nitrogen cartridge, or a 101-10 or a 101-20 carbon dioxide cartridge. See Figure 100. REGULATED ACTUATOR ASSEMBLY EXPELLANT GAS LINES NOT INCLUDED IN ACTUATION GAS LINE LENGTH TOTALS REGULATED ACTUATOR ACTUATION GAS LINE WITH AN LT-20-R, LT-30-R, 101-10 OR 101.20 CARTRIDGE MAXIMUM LENGTH OF 20 Ft (6 m), MAXIMUM NO. OF FITTINGS 9 ANSUL AUTOMAN REGULATED RELEASE ASSEMBLY FIGURE 100 wons SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-48 REV.6 7-1-09 ACTUATION AND EXPELLENT GAS LINE REQUIREMENTS (Continued) Actuation Gas Line —6 to 8* Tanks Maximum (Continued) If an expellant gas line is connected to the regulated release assembly along with an actuation gas line, the total combined length of the actuation and expellant gas line must not exceed 30 ft (9 m) when using a "double-tank" nitrogen car- tridge or a LT-A-101-30 nitrogen cartridge or a 101-30 carbon dioxide cartridge. See Figure 101. A combined total of nine fittings may be used in these lines, eight 900 elbows and one tee. Two 450 elbows equal one 900 elbow. Actuation Gas Line - 10 to 15* Tanks Maximum * 15 Tank maximum reflects the utilization of 3 tank regulated actuators. 1. Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- nized, chrome-plated, or stainless steel pipe and fittings. Note: Stainless steel hose and fittings can also be used. See Component Section for detailed information. ACTUATOR AND EXPELLANT GAS LINES WITH A DOUBLE TANK CARTRIDGE OR A 101-30 CARTRIDGE OR A LT-A-101-30 CARTRIDGE MAXIMUM COMBINED LENGTH -30 FT (9 m) MAXIMUM COMBINED FITTINGS -9 The actuation gas line piping is installed from the 101 remote mechanical release to each R-102 regulated actuator assem- bly. The total length of the actuation gas line from the remote mechanical release to the regulated actuator assemblies must not exceed 100 ft (30.5 m). A combined total of 20 elbows and 9 tees may be used in these lines. Two 450 elbows equal one 900 elbow. See 101 Figure 102. Use only a 101 -10 carbon dioxide cartridge in the 101 remote mechanical release. A safety vent relief valve (Part No. 15677) is required in the actuation gas line to relieve residual pressure after actuation. v. Actuation Gas Line - Using 1/4 in. Stainless Steel Hose 15 Tank maximum reflects the utilization of 3 tank regulated actuators. Maximum total length of hose cannot exceed 17.5 ft (5.3 m). Note: A combination of 1/4 in. stainless steel braided hose and 1/4 in. NPT pipe can be used as long as the total com- bined actuation gas line length does not exceed 17.5 ft (5.3 m). Stainless steel braided hose cannot be used for expellant gas lines. See Figure 102 for additional details. Maximum of 5 regulated actuators allowed Actuated with remote release (Part No. 433485) or Regulated Release Assembly (Part No. 429853) REGULATED ACTUATOR ASSEMBLY ACTUATOR u>ASSEMBLY [JJJ REGULATED ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY REGULATED ACTUATOR ASSEMBLY EXPELLANT GAS LINES NOT INCLUDED IN COMBINED TOTALS FIGURE 101 SAFETY EXPELLANT RELIEF VALVE GAS LINE 20 ELBOWS 1/4 IN. ACTUATION LINE - 9 TEES MAXIMUM MAXIMUM 100 FT (30.5 m) MAXIMUM I i I. Holimliuhl' .ir'__ REGULATED ACTUATOR WITH TANK 1/4 IN. STAINLESS STEEL HOSE OPTIONS SAFETY 42 IN. (to 7S c SE m) RELIEF VALVE MAX. HO LENGTH (TYP.) ** I t..z I I I II I II I I I j II III I Ill I II I I I I I I I I I I I II I Ii I - REGULATED ACTUATOR WITH TANK NOTE: WHEN MULTIPLE RELEASE ASSEMBLIES ARE UTILIZED, A 1/4 IN. CHECK VALVE, PART NO. 25627, WILL BE REQUIRED AFTER EACH REGULATED RELEASE. IIt]II I=Ipo._ IurTI qrP iiii 11114 i Iii ( I l4II 11:1 I ±r-f--1 I 11 I LJIIH Li AGENT TANK MAXIMUM OF 5 REMOTE RELEASE MECHANISMS REGULATED (PART NO. 433485)5 MAXIMUM ACTUATORS 1/4 IN. STAINLESS STEEL HOSE / CHECK VALVE MAXIMUM OF .... 5 REMOTE RELEASE MECHANISMS (PART NO. 433485) OR ONE (1) REGULATED k RELEASE (PART NO. 429853) MAXIMUM OF 5 REGULATED ACTUATORS FIGURE 102 ocmm SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-49 7-1-09 REV.5 ACTUATION AND EXPELLENT GAS LINE REQUIREMENTS (Continued) Expellant Gas Line 1. The expellant gas line is installed from the regulated release mechanism in double, three, and multiple-tank systems, and from the regulated actuator assembly in multiple-tank sys- tems. The expellant gas line is the piping and/or hose between the regulator and the tank-enclosure/tank-bracket assembly. The total length of the expellant gas line from the regulated release mechanism or each regulated actuator assembly must not exceed 30 ft (9 m) when using a "double-tank" car- tridge, an LT-A-101-30 Cartridge, or a 101-30 Cartridge. See Figures 103 and 104. EXPELLANT GAS LINE MAXIMUM LENGTH —30 FT (9 m), MAXIMUM NO. OF FITTINGS —9 ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY FIGURE 103 n6 EXPELLANT GAS LINE MAXIMUM LENGTH —30 FT (9 m), MAXIMUM NO. OF FITTINGS —9 4. If three 3.0 gallon tanks are connected to the regulator in either a regulated release or regulated actuator assembly, only factory supplied expellant gas hose assemblies will be utilized. Refer to Distribution Piping Requirements - 9.0 Gallon System, page 4-55 for additional design requirements. DISTRIBUTION PIPING REQUIREMENTS Once the nozzle placement and quantity of tanks has been deter- mined, it is then necessary to determine the piping configurations between the tank adaptor and each discharge nozzle. This section contains the guidelines and limitations for designing the distribu- tion piping so that the liquid agent will discharge from the nozzles at a proper flow rate. These limitations should also be referred to when selecting the mounting location for the regulated release mechanism and agent tank. General Piping Requirements All R-102 system piping is straight line. Therefore, the need for critical lengths and balancing is minimized. Two 450 elbows count as one 900 elbow. Each branch line includes the tee or elbow leading to it, and all fittings within the branch line itself. The minimum piping length of Schedule 40, 3/8 in. pipe from the tank outlet to any nozzle protecting a range, fryer, or wok must be 6ft(1.8 m). Pipe lengths are measured from center of fitting to center of fitting. See Figure 105. CENTER TO CENTER FIGURE 105 Ofl8 REGULATED ACTUATOR ASSEMBLY FIGURE 104 ocj7ii All distribution piping must be 3/8 in. Schedule 40 black iron, chrome-plated, or stainless steel. Do not use hot dipped gal- vanized pipe on the distribution piping. All threaded connections located in and above the protected area must be sealed with pipe tape. Tape should be applied to male threads only. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distribution. Before installing blow-off caps on nozzles, apply a small amount of Dow Corning No. 111 silicone grease across the opening in the nozzle tip and also a small amount coating the exterior of the blow-off cap. This will help keep cooking grease from building up on the cap. Tees used in the distribution piping can be used as thru tees, side outlet tees, or bull tees. A combined total of nine fittings may be used in these lines, eight 900 elbows and one tee. Two 450 elbows equal one 900 elbow. If two tanks are connected to the regulated release assembly in a multiple-tank system arrangement, the total combined length of the actuation and expellant gas lines must not exceed 30 ft (9 m) when using a "double-tank" nitrogen car- tridge, an LT-A-101-30 nitrogen cartridge, or a 101-30 carbon dioxide cartridge. See Figure 101. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-50 REV. 5 7-1-09 DISTRIBUTION PIPING REQUIREMENTS (Continued) Supply and Branch Line Identification The R-102 distribution piping network is broken down into four specific pipe runs: the Supply Line, the Duct Branch Line, the Plenum Branch Line, and the Appliance Branch Line. See Figure 106. DUCT BRANCH LINE i SUPPLY LINE The Supply Line is defined as the length of pipe which runs from the agent tank outlet to the last branch line (whether a duct, appli- ance, or plenum branch line). This includes all supply line fittings except for the tees or elbows leading to the branch lines. See Figures 106 and 107. SUPPLY LINE PLENUM APPLIANCE BRANCH LINE BRANCH LINE NOTE: THIS IS A CONCEPTUAL DRAWING ONLY. THIS IS NOT AN ACTUAL INSTALLATION. P. FIGURE 106 NOTE: THESE ARE EXAMI END OF SUPPLY LINE D OF PPLY LINE 1~ (NOZZLES FOR PLENUM PROTECTION) END OF SUPPLY LINE BRANCH LINE CANNOT START AHEAD OF A SUPPLY LINE TEE (NOZZLES FOR PLENUM PROTECTION) BRANCH LINE CANNOT START AHEAD OF A SUPPLY LINE TEE FIGURE 107 000780 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-51 7-1-09 REV. 5 DISTRIBUTION PIPING REQUIREMENTS (Continued) Supply and Branch Line Identification (Continued) NOTICE Branch lines cannot start ahead of a supply line tee. DUCT BRANCH LINE The Duct Branch Line is defined as the length of pipe which runs from the supply line to the duct nozzle(s). This includes all branch line fittings as well as the tee or elbow used to start the branch line. See Figures 107 and 108. DUCT BRANCH LINE (ELBOW INCLUDED) $ DUCT BRANCH LINE (TEE INCLUDED) 10 DUCT BRANCH LINE (TEES INCLUDED) \ PLENUM BRANCH LINE The Plenum Branch Line is defined as the length of pipe which runs from the supply line to the plenum nozzle(s). This includes all branch line fittings as well as the tee or elbow used to start the branch line. See Figures 106 and 109. --.4 Ear PLENUM BRANCH LINE (TEE INCLUDED) PLENUM BRANCH LINE (TEE INCLUDED) FIGURE 109 owm APPLIANCE BRANCH LINE The Appliance Branch Line is defined as the length of pipe which runs from the supply line to the appliance nozzle(s). This includes all branch line fittings as well as the tee or elbow used to start the branch line. See Figures 107 and 110. i_____• ICZ1 APPLIANCE BRANCH LINES (TEES INCLUDED) FIGURE 108 000781 FIGURE 110 000707 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-52 REV. 4 7-1-09 DISTRIBUTION PIPING REQUIREMENTS (Continued) Distribution Piping Requirements - 1.5 Gallon System DUCT, PLENUM, AND APPLIANCE PROTECTION This option allows for duct protection, plenum protection, appliance protection, or any combination. However, only one (1) duct nozzle may be used, either a 1W or a 2W, nozzle. All distribution piping, supply and branch, must be 3/8 in. Schedule 40 black iron, chrome-plated, or stainless steel. Each 1.5 gallon tank allows a maximum of five flow numbers.* The pipe length between the start of the first branch line and the start of the last branch line must not exceed 8 ft (2.4 m). When the supply line is split, the combined length of both legs of the supply line (start of first branch line to start of last branch line) must not exceed 8 ft (2.4 m). See Figure 111. The combined length of all branch lines must not exceed 22 It (6.7 m). See Figure 112. The requirements of the following table must not be exceeded: START OF LAST BRANCH LINE START OF FIRST BRANCH LINE SUPPLY LINE TEE TOTAL LENGTH MUST NOT EXCEED 8 FT (2.4 m) START OF LAST BRANCH LINE START OF FIRST BRANCH LINE FIGURE 111 O784 1W NOZZLE (BRANCH LINES IN BOLD) COMBINED LENGTH MUST NOT EXCEED 22 Ft (6.7 m) FIGURE 112 O785 Duct Plenum Appliance Requirements Supply Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 6 It 4 ft loft (12.2 m) (1.8 m) (1.2 m) (3m) Maximum Rise 6 ft 4 It 2 It 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 900 Elbow 9 4 4 6 Maximum Tees 1 1 2 3 Maximum Flow Numbers 5* 2 2 3 * Exceptions: Six (6) flow numbers are allowed when a duct branch line is the last branch line on the piping network and no IN nozzles are used to protect woks or griddles. Six (6) flow numbers are allowed when six (6)1 N nozzles are used and none of the nozzles are used to protect woks, griddles, ranges, and salamanders. NOTE: Only five (5) flow numbers are allowed if a IN nozzle is used for wok, griddle, range, or salamander protection. Six (6) flow numbers are allowed when only two (2) 3N nozzles are used. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-53 7-1-09 REV. 4 DISTRIBUTION PIPING REQUIREMENTS (Continued) Distribution Piping Requirements —3.0 Gallon System The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 It (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). See Figure 113. The total length of all branch lines must not exceed 36 It (10.9 m). See Figure 113. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. supply line. A maximum of two nozzles are allowed per duct branch line. The requirements of the following table must not be exceeded: SUPPLY TEE 000266 COMBINED LENGTH OF BOTH LEGS OF SUPPLY ~v LINE MUST NOT 3 BRANCH LINES EXCEED 24 FT (7.3 m) 1 NOZZLE 2W NOZZLE - IN NOZZLE n1 COMBINED LENGTH MUST LL9 230 NOZZLE j4 245 NOZZLE 1/2N NOZZLE (BRANCH LINE IN BOLD) 000502 NOT EXCEED 36 FT (10.9 m) FIGURE 113 Requirements Supply Line Duct Branch Line Plenum Branch Line Appliance Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 It 8 ft 4 ft 12 It (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 It 4 ft 2 It 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11* 4 2 4 Numbers Exceptions: Twelve (12) flow numbers are allowed in any one tank for duct and plenum protection only. Twelve (12) flow numbers are allowed with any one tank using Only two-flow appliance nozzles. Twelve (12) flow numbers are allowed with any one tank using only three-flow appliance nozzles. Special Instructions: I. Twelve (12) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 66 on Page 4-32. The discharge piping must be as shown in Figure 67 on Page 4-32. 2. For certain McDonald's applications. 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 112N electrostatic precipitator nozzle, one (1) IN plenum nozzle, and four (4) two-flow appliance nozzles. Contact ANSUL Applications Engineering Department for additional information. 2W ZZLE 2 FLOW APPLIANCE NOZZLE SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-54 REV.5 7-1-09 DISTRIBUTION PIPING REQUIREMENTS (Continued) Distribution Piping Requirements - 6.0 Gallon Manifolded System As an option to piping two (2) 3.0 gallon tanks separately, two (2) 3.0 gallon tanks can be manifolded together to share a common agent distribution line. Only (2) 3.0 gallon tanks connected to the same regulator can be manifolded. The following requirements must be met when manifolding: All piping must be 3/8 in. Schedule 40. See Figure 115 for tank connections. The length of supply line piping between the start of the first branch line and the start of the last branch line must not exceed 24 ft (7.3 m). See Figure 94. When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft (7.3 m). The combined length of all branch lines must not exceed 36 It (10.9 m). See Figure 114. A maximum of 22 flow numbers are allowed. The requirements of the following table must not be exceeded. LENGTH OF PIPING MUST NOT EXCEED 24 FT. (7.3 m) FROM START OF FIRST BRANCH LINE TO START OF LAST BRANCH LINE START OF LAST BRANCH LINE - (BRANCH LINES IN BOLD) COMBINED LENGTH MUST NOT EXCEED 36 FT (10.9 m) Requirements Supply Line Duct Branch Line Plenum Branch Line Appliance Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 32 ft 8 ft 4 It 12 ft (9.7 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 It 4 ft 2 It 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 900 8 4 4 6 Elbows Maximum Tees 2 2 2 4 Maximum Flow 22 4 2 4 Numbers FIGURE 114 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-55 7-1-09 REV. 4 DISTRIBUTION PIPING REQUIREMENTS (Continued) Distribution Piping Requirements —6.0 Gallon Manifolded System (Continued) This configuration consists of two 3 gallon tanks. Both tanks are connected to a common manifold tee and are pressurized from a single double tank (Part No. 73022) nitrogen cartridge in the regu- P. release assembly. See Figure 115. Note: A tank mounting bracket can be utilized instead of the tank/enclosure assembly. ',See Figure 117. 3/8 IN. 3/8 IN. 3/8 IN. BRANCH SUPPLY SUPPLY USE HOSE! SEE GROMMET NOTE PACKAGE (PART NO. 3/8 IN BRANCH 418511) INBURST DISC ASSEMBLY - SEE NOTE NO.4 REMOVE BURST DISC- SEE NOTE NO.3 3.0 ii 3.0 I GALLON GALLON DOUBLE TANK TANK f TANK NITROGEN CARTRIDGE OR I CARTRIDGE- (LT-A-101.30 008127 REGULATED 3.0 GALLON REGULATED RELEASE ACTUATOR ONLY) ASSEMBLY OR 3.0 GALLON REGULATED ACTUATOR ASSEMBLY TANK/ENCLOSURE ASSEMBLY NOTE 1: THE PIPE CONNECTION FROM TANK CENTER TO TANK CENTER CANNOT EXCEED 8-1/2 IN. (21.5 cm). ALSO, OEM RELEASEIBRACKET ASSEMBLY CAN BE UTILIZED WHEN MANIFOLDING 3.0 GALLON TANK. NOTE 2: ONLY 3 GALLON TANKS CAN BE MANIFOLDED. NOTE 3: THE BURST DISC THAT IS PART OF THE TANK ADAPTOR/BURST DISC ASSEMBLY MUST BE REMOVED AND MODIFIED. SEPARATE THE ALUMINUM DISC MATERIAL FROM THE PLASTIC GASKET. DISCARD THE ALUMINUM DISC MATERIAL AND REINSTALL THE PLASTIC GASKET BACK INTO THE TANK ADAPTOR/BURST Disc ASSEMBLY. NOTE 4: THE IN-LINE BURST DISC ASSEMBLY, PART NO. 416790, IS TO BE MOUNTED AS CLOSE TO THE TANK OUTLET AS POSSIBLE. AFTER SYSTEM DISCHARGE, THE ASSEMBLY MUST BE DISASSEMBLED AND A NEW BURST DISC INSTALLED. FIGURE 115 Distribution Piping Requirements -With Independent Pipe Runs Independent pipe runs can also be used with the regulated release assembly and the tank/enclosure assembly or tank mount- ing brackets. See Figure 116. When manifolding is not used, each of the two (2) 3 gallon tanks utilize the piping limitations of a single tank system. HOSE! GROMMET PACKAGE (PART NO. Ni] 418511) HYGALLON3.0 GALLON TANK OR FIGURE 116 78G Note: If an expellant gas hose is to be used for a second tank in an adjacent tank enclosure or tank bracket assembly, the second tank will need to be installed on the left side of the ANSUL AUTOMAN Regulated Release, with the outlets a maximum of 8 1/2 in. (21.6 cm) from center to center, similar to the manifolded system in Figure 115. Otherwise, the second tank will require 1/4 in. NPT pipe instead of expellant gas hose. -DOUBLE TANK 1.5 GALLON TANK NITROGEN CARTRIDGE OR 101 -30 CO2 CARTRIDGE (LT-A-101-30 REGULATED RELEASE ASSEMBLY OR CARTRIDGE - REGULATED ACTUATOR ASSEMBLY REGULATED TANK/ENCLOSURE ACTUATOR ONLY) ASSEMBLY SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-56 REV.4 7-1-09 DISTRIBUTION PIPING REQUIREMENTS (Continued) Distribution Piping Requirements - 9.0 Gallon System This optional configuration consists only of three 3-gallon tanks, all pressurized from a single double-tank nitrogen cartridge with e expellant gas hoses connected as shown in Figure 117. Tanks No. 1 and No. 2 must be connected directly to the regulator with sepa- rate expellant gas hoses and Tank No. 3 must be connected to Tank No.2 with a third expellant gas hose as shown in Figure 117. Each tank must be connected to an independent distribution pip- ing network as shown in Figure 117. Distribution piping require- ments for each network must be as follows: The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 It (7.3 m). When the supply line is split, the combined total of both legs of the supply line (from the start of the first branch line to the start of the last branch line) must not exceed 24 It (7.3 m). See Figure 113. The total length of all branch lines must not exceed 36 It (10.9 m). See Figure 113. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. supply line. A maximum of two nozzles are allowed per duct branch line. When using this 9.0 gallon system configuration, no man!- folding of distribution piping is allowed. When an ANSUL AUTOMAN Regulated Release is utilized in this configuration, additional regulator actuators cannot be used. Only 3 gallon tanks can be utilized in this configuration. The requirements of the following table must not be exceeded for each 3 gallon tank: 3.0 3.0 3.0 GALLON GALLON GALLON TANK TANK I: TANK NO.3 NO.2 H NO.1 TWO TANK ENCLOSURE 3 GALLON REGULATED DOUBLE TANK NITROGEN ASSEMBLY PART NO. RELEASE ASSEMBLY, CARTRIDGE OR 430324 (INCLUDES (2) OR 3 GALLON LT-A-101-30 CARTRIDGE HOSES AND (2) REGULATED ACTUATOR (REGULATED ACTUATOR GROMMETS) ASSEMBLY ONLY) NOTE: WHEN THREE (3) 3.0 GALLON TANKS ARE CONNECTED TO ONE (1) AUTOMAN REGULATED RELEASE ASSEMBLY, NO ADDITIONAL REGULATED ACTUATOR(S) ASSEMBLIES CAN BE USED. FIGURE 117 008126 Requirements Supply Line Duct Branch Line Plenum Branch Line Appliance Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft 8 ft 4 It 12 ft (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 It 4 ft 2 It 2 It (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 900 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11* 4 2 4 Numbers 'Exceptions: Twelve (12) flow numbers are allowed in any one tank for duct and plenum protection ONLY. Twelve (12) flow numbers are allowed with any one tank using only two-flow appliance nozzles. Twelve (12) flow numbers are allowed with any one tank using Only three-flow appliance nozzles. Special Instructions: When four (4) Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 66 on Page 432, the discharge piping must be as shown in Figure 67 on Page 4-32. For certain McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N electrostatic precipitator nozzle, one (1) 1 N plenum nozzle, and four (4) two-flow appliance nozzles. Contact Ansul Applications Engineering Department for additional information. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-57 7-1-09 REV. 2 DETECTION SYSTEM REQUIREMENTS Once the fire suppression system design has been determined, a detection system design must be completed. This section contains guidelines and limitations for detection system installation. Detector Identification The two types of detectors are distinguished from each other by their location in the detection system. The Terminal Detector (Part No. 417368) is the last in a series of detectors, or the only detector used in a single-detector sys- tem. This detector is thus named because it is at the point at which the wire rope ends, or terminates" A Series Detector (Part No. 417369) is any detector located in- line between the regulated release mechanism and the termi- nal detector. Detector/Pulley Elbow/Conduit Off-Set Design Limitations Conduit runs, pulley elbows, and number of detectors per sys- tem must be within the approved system guidelines. The fol- lowing requirements must not be exceeded: Maximum Maximum Maximum Number of Number of Length of 1/2 Detectors Elbows in. Conduit per System per System per System Scissors Style 15 20 150 ft (45.7 m) Detector (Without Off-Set Conduit Scissors Style 15 16 150 It (45.7 m) Detector (With Off-Set Conduit If the hazard requires more than 15 detectors, up to five 101 Remote Releases (Part No. 433485) can be used for system actuation. Each 101 remote release allows the use of a maxi- mum of 15 scissor" style detectors (14 series and 1 terminal) for a total of 75 detectors if needed. If an electrostatic precipitator is located at or near the base of the exhaust duct, it is necessary to locate a detector below the pre- cipitator, at the base of the duct, and also locate one in the duct, just above the precipitator. See Figure 119. When installing the detector bracket and system conduit, make certain they do not interfere with the operation of the precipitator. Note: On secondary filtration units utilizing multiple filter stages/media, contact Ansul Technical Services for instructions. Detector Placement Requirements EXHAUST DUCTS Each exhaust duct must have at least one detector installed in the duct entrance, located in the airstream of the cooking vapors, or at a maximum of 20 ft (6.1 m) into the duct opening. See Figure 118. - 20 FT. (6 m) MAXIMUM FIGURE 118 onI NOTICE When gas appliances are used and the flue gases from the burner are exhausted into the duct, the detector must be kept out of the air stream of these exhaust gases. These gases can be very hot and could actuate the system unnecessarily. Duct openings that are long and narrow or large enough to require multiple duct nozzles may require additional detectors. ELECTROSTATIC PRECIPITATOR FIGURE 119 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-58 REV. 2 7-1-09 Detector Replacement Requirements (Continued) COOKING APPLIANCES If the cooking appliance is located under an exhaust duct where a detector has been mounted, it is normally not necessary to utilize another detector for that cooking appliance, provided the detector is not more than 12 in. (30 cm) into the duct and the appliance has no larger cooking surface than 48 in. x 48 in. (121.9 cm x 129.1 cm). See Figure 120. Note: If two (2) appliances are located under a duct opening where a detector has been mounted and both appliances togeth- er do not exceed a cooking surface of 48 in. x 48 in. (121.9 cm 121.9 cm) and the detector is located above both the protected appliances, it is not necessary to utilize an additional detector pro- vided the duct detector is not more than 12 in. (30.5 cm) into the 1 duct opening. I APPLIANCE REQUIRES SEPARATE DETECTOR APPLIANCE COVERED BY DETECTOR UNDER DUCT APPLIANCE REQUIRES SEPARATE DETECTOR FIGURE 120 O2 Each cooking appliance with a continuous cooking surface not exceeding 48 in. x 48 in. (122 x 122 cm) can be protected by a min- imum of one detector. Cooking appliances with a continuous cook- ing surface exceeding 48 in. x 48 in. must be protected by at least one detector per 48 in. x 48 in. cooking area. Detectors used for cooking appliances must be located above the protected appli- ance toward the exhaust duct side of the appliance. The detector should be located in the air stream of the appliance to enhance system response time. Note: For overlapping detector coverage, see Page 4-45 for design requirements. Detection Line Requirements CONDUIT Rigid conduit or 1/2 inch EMT thin-wall conduit may be used. Standard steel conduit fittings (compression type are recommend- ed) must be employed to properly install the detection system. All conduit or pipe must be firmly supported. When using pipe, make certain that all ends are carefully reamed, deburred and blown clear of chips and scale before assembly. NOTICE The conduit offset can be used at the top or bot- tom of the regulated release to change direction of the conduit. The conduit offset cannot be used with pulley tees. All other changes in direc- tion must be made by using ANSUL approved pulley elbows, Part No. 423254 or 415670. See Figure 121. FIGURE 121 O27O Fusible Link Selection When possible, temperature readings should be taken at each detector location to determine correct fusible link temperature rat- ing. Temperature can be recorded using either a maximum regis- tering thermometer, Part No. 15240, temperature tape or any other accurate thermometer. @F:2D ANSULa am TEMPERATURE RATING I STAMPED ON FUSIBLE E:J ® LINK BODY Ig __ oI7o K STYLE ML STYLE 000171 FIGURE 122 Select correct UL Listed fusible link(s) for installation in detector(s) according to the temperature condition. Two styles are available. See Figure 122. See Component Section for detailed temperature ratings. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-59 7-1-09 REV. 2 MANUAL PULL STATION REQUIREMENTS A remote manual pull station allows the R-102 system to be man- ually operated at some point distant from the regulated release assembly. The pull station should be installed at a height of 42-48 in. (107-122 cm), in accordance with the requirements of the American Disabilities Act (ADA) and the Authority having Jurisdic- tion, and located in the path of egress. The pull station is the only source of manual actuation of the regulated release assembly. The total length of the cable used for each manual pull station with- in a system must not exceed 150 ft (46 m). The maximum number of pulley elbows that may be used per pull station is 20. One pulley tee, Part No. 427929, is allowed per cable system. The maximum length of cable from the AUTOMAN to a pull station is 150 ft (45.7 m) with a maximum of 20 pulley elbows used per side of the tee. As the tee is located farther from the AUTOMAN, the 150 It (45.7 m) maximum must be observed but as pulley elbows are placed between the AUTOMAN and the tee, they must be deducted from the available pulley elbows (20) allowed on each side. Example: If 10 pulley elbows are placed between the AUTOMAN and the pulley tee, the maximum available pulley elbows left for use on each side of the tee is 10 per side. See Figure 123 for three different examples. (Note: Both must be gas valves or both must be pull stations. Mixing is not allowed.) TEE CLOSE TO AUTOMAN (EXAMPLE) PULLEY TEE 12 IN. (3105 mm) AUTOMAN GAS VALVE OR GAS VALVE OR MANUAL PULL MANUAL PULL 149 FT (45.4 m) AND 20 PULLEY ELBOWS MAXIMUM PER EACH SIDE OF TEE TEE CLOSE TO GAS VALVES OR MANUAL PULL (EXAMPLE) 1 gPULLEY 12 IN. I (305 mm) 3omm) LII E GAS VALVE OR GAS VALVE OR MANUAL PULL MANUAL PULL AUTOMAN 149 FT (45.4 m) AND 20 PULLEY ELBOWS BETWEEN AUTOMAN AND TEE TEE HALFWAY BETWEEN AUTOMAN AND GAS VALVES OR MANUAL PULL (EXAMPLE) 75 FT (22.9 m) AND 10 PULLEY ELBOWS 75 FT (22.9 m) AND 75 FT (22.9 m) AND 10 PULLEY ELBOWS 1 10 PULLEY ELBOWS 6 PULLEY TEE AUTOMAN GAS VALVE OR GAS VALVE OR MANUAL PULL MANUAL PULL FIGURE 123 004907 Metal Stamped Style - Part No. 4835 or 54011 Parts that may be used for installation of a metal stamped remote manual pull station are: Description Remote Manual Pull Station Assembly* Part No. 54011 Remote Manual Pull Station Assembly 4835 Pulley Elbow 423250 Pulley Elbow 415670 Pulley Tee 427929 *Assembly includes parts listed below: 1/16 in. Stainless Steel Cable 50 ft. (15 m) 15821 Oval Press-To-Crimp Sleeves 4596 Glass Break Rod (1) 4834 MECHANICAL GAS VALVE REQUIREMENTS An ANSUL or ANSUL approved mechanical gas shut-off valve system can be attached to the R-102 system. The system works both mechanically and pneumatically by use of an air cylinder located inside the regulated release assembly. Upon actuation of the fire suppression system, a pneumatically-operated air cylinder assembly will mechanically close the gas shut-off valve. The total length of the cable for each mechanical gas valve must not exceed 150 ft (46 m). The maximum number of pulley elbows that may be used is 20 for each valve. One pulley tee (Part No. 427929) is allowed per cable system. The maximum length of cable from the AUTOMAN to a gas valve is 150 ft (45.7 m) with a maximum of 20 pulley elbows used per side of the tee. As the tee is located farther from the AUTOMAN, the 150 ft (45.7 m) maximum must be observed but as pulley elbows are placed between the AUTOMAN and the tee, they must be deducted from the available pulley elbows (20) allowed on each side. Example: If 10 pulley elbows are placed between the AUTOMAN and the pulley tee, the maximum available pulley elbows left for use on each side of the tee is 10 per side. See Figure 123 for three different examples. Parts that may be used for installation of a Mechanical Gas Shut- off Valve are: Description Part No. Gas Valve/Actuator 3/4 in. Assembly (ANSUL) 55598 Gas Valve/Actuator 1 in. Assembly (ANSUL)* 55601 Gas Valve/Actuator 1 1/4 in. Assembly (ANSUL)* 55604 Gas Valve/Actuator 1 1/2 in. Assembly (ANSUL)* 55607 Gas Valve/Actuator 2 in. Assembly (ANSUL)* 55610 Gas Valve/Actuator 2 1/2 in. Assembly (ASCO)* 25937 Gas Valve/Actuator 3 in. Assembly (ASCO)* 25938 Pulley Elbow 423250 Pulley Elbow 415670 Pulley Tee 427929 1/16 in. Stainless Steel Cable 15821 or 50 ft (15 m) or 500 ft (152 m) roll 79653 Oval Press-To-Crimp Sleeve 4596 Stop Sleeve (2) 26317 Assembly includes parts listed below: Air Cylinder Assembly 15733 Air Cylinder 15521 Tubing Assembly 15529 Copper Tubing, 1/8 in. 15525 Male Elbow 15523 Male Connector 15522 Machine Screw (2) 15421 Hex Nut (2) 15527 Lockwasher (2) 4141 Visual Inspection Seal (2) 197 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-60 REV. 2 7-1-09 MECHANICAL GAS VALVE REQUIREMENTS (Continued) All valves above are UL listed and approved. They may be mount- ed in any position. Pipe threads are type NPT. Ambient operating temperature range of all valves is 32 OF to 120 OF (0 °C to 49 °C). The valves are not weatherproof and must be located indoors in areas approved by the "authority having jurisdiction." ELECTRICAL GAS VALVE REQUIREMENTS A UL Listed electrically-operated gas shut-off valve can be attached to the R-102 system to provide an electrical means of shutting off the gas line at a predetermined point. If an electric gas shut-off valve is used in the system it must be attached with both an electric (snap-action) switch and a manual reset relay. For more information on the types of electric (snap-action) switches, refer to the Electrical Switch, Field Installation section. The manual reset relay is reviewed in this section. All electrical connections should be performed by a QUALIFIED ELECTRICIAN and in accordance with authority having jurisdiction. The following is a brief explanation of how the R-102 system oper- ates with an Electric Gas Shut-off Valve attached: With the regulated release cocked in the ready condition, the nor- mally closed contacts in the snap-action switch allow current to flow to the manual reset relay. With the relay coil energized, nor- mally open contacts in the reset relay close, allowing the solenoid in the gas valve to be energized. Once the R-102 system is activated, the normally closed contacts in the snap-action switch will open, de-energizing the reset relay. This will, in turn, open the contacts in the relay which will cause the gas valve to become de-energized and close. The system must be re-armed and the "push to reset" button on the reset relay must be operated to reopen the gas valve. It is important to note that a power failure or an electrical power interruption will cause the gas valve to close even though the sys- tem was not fired. In either case, whether in a fired condition or when a power failure has occurred, the manual reset relay and electric gas shut-off valve must be reset to resume a normal operating condition. For resetting, refer to the "Recharge and Resetting Procedures" section in this manual. Approvals ANSUL gas valves listed in this section are UL listed and approved for 110 VAC. If more information is required, refer to the Gas and Oil Equipment List of Underwriters Laboratories, Inc. under "Electrically Operated Valves Guide No. 440 A5" or consult Ansul Incorporated, Marinette, Wisconsin 54143-2542. If other gas valves are used, they shall be "UL listed electrically- operated safety valves for natural or LP gas as required, of appro- priate pressure and temperature rating, 110 VAC/60 Hz."The infor- mation on temperature and type of gas that the valves are suitable for may be found in the Gas and Oil Equipment List of Underwriters Laboratories, Inc. under "Electrically Operated Valves Guide No. 440 A5." The electrically operated gas valve must be of the type that needs to be energized to remain open. Note: For electrical wiring diagrams, see Installation Section, Pages 5-19.1 through 5-19.3. Parts that may be used for installation of a 110 VAC Gas Shut-off Valve are: Description Part No. Electric Solenoid Valve, 3/4 in. NPT" 13707 Electric Solenoid Valve, 1 in. NPT" 13708 Electric Solenoid Valve, 1 1/2 in. NPT* 13709 Electric Solenoid Valve, 2 in. NPT* 13710 Electric Solenoid Valve, 3 in. NPT" 17643 Manual Reset Relay (110 VAC) 14702 Valves are normally dosed when de-energized. ALARM INITIATING SWITCH REQUIREMENTS The Alarm Initiating Switch can be field mounted within the ANSUL AUTOMAN release. The switch must be used to close a supervised alarm circuit to the building main fire alarm panel when the ANSUL AUTOMAN release actuates. This action will signal the fire alarm panel that there was a system actuation in the kitchen area. The switch kit contains all necessary mounting components along with a mounting instruction sheet. See Page 5-19 for wiring information. The switch is rated 50 mA, 28VDC. Part No. Description 428311 Alarm Initiating Switch Kit ELECTRICAL SWITCH REQUIREMENTS Note: Electrical connections shall not be made in the ANSUL ' AUTOMAN. The electric (snap-action) switches for the R-1 02 system are spe- cially designed to fit the regulated release assembly. The switches are intended for use with electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-oft devices, and other electrical devices that are designed to shut off or turn on when the fire suppression system is actuated. (See Figures 110 through 112 in Installation Section for reference). Contractors shall supply "UL listed, enclosed industrial control equipment or magnetic switch having a rating matching that of the cooking appliance, coil 110 VAC/60 Hz or 24 VAC/60 Hz." All electrical connections should be performed by a QUALIFIED ELECTRICIAN and in accordance with authority having jurisdiction. Electric (Snap-Action) Switches that may be field installed are: Part No. Description 423878 One Switch Kit 423879 Two Switch Kit 423880 Three Switch Kit 423881 Four Switch Kit Each switch has a set of single-pole, double throw contacts rated at 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC. Note: A relay must be supplied by others if the equipment load exceeds the rated capacity of the switch. Electrical wiring and equipment shall be installed in accordance with NFPA 70 (National Electrical Code) or the requirements of the authority having jurisdiction. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-61 7-1-09 REV.0 ELECTRICAL SWITCH REQUIREMENTS (Continued) If a fire alarm system is provided, the fire extinguishing system shall be connected to the alarm system in accordance with the requirements of NFPA 72, National Fire Alarm Code, so that the actuation of the extinguishing system will sound the fire alarm as well as provide the extinguishing function of the system. If supervision of the electrical detection, electrical actuation or electrical power supply circuit is provided, it shall give prompt audi- ble or visual indication of trouble and shall be distinctive from alarms or indicators indicating operation or hazardous conditions as specified in NFPA 17A. SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-62 REV. 0 7-1-09 NOTES: SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-1 7-1-09 REV. 7 INSTALLATION INSTRUCTIONS The installation information listed in this section deals with the limi- If not already done, mount both boxes to a rigid surface tations and parameters of this pre-engineered system. Those mdi- using appropriate fasteners. viduals responsible for the installation of the R-102 system must Fill tanks per instructions listed in Steps 3 and 4 on be trained and hold a current ANSUL certificate in an R-102 train- Page 5-2-1. ing program. Next, route hose through grommets and wrench tighten into Before attempting any installation, the entire system design must 1/4 in. inlet of the adaptor on the tank in the tank/enclosure have been determined including: Nozzle Placement, Tank assembly. Also install hose to tank adaptor in regulated Quantity, Actuation and Expellant Gas Piping, Distribution Piping, release and wrench tighten. See Figure 116 in "Design and Detection System Requirements and an installation sketch Section" for details of hose routing. should be completed. MOUNTING THE COMPONENTS For successful system performance, the regulated release assem- bly, regulated actuator assembly(ies), and tank-enclosure(s) or tank-bracket assembly(ies) used must be located in areas where the air temperature will not fall below 32 OF (0 "C) or exceed 130 OF (54 "C). The R-1 02 system is limited to interior applications only. Also, the components must be arranged to conform to the actuation and expellant gas line, and the distribution piping guide- lines noted in "System Design." REGULATED RELEASE ASSEMBLY/REGULATED ACTUATOR ASSEMBLY/DOUBLE TANK ENCLOSURE -...16 1/2 IN. (42 Cm) 13 13/16 IN. - — (35 an) 13/8 IN. (3.5 cm) 23 1/2 IN. 0 I (59.7cm) I I 19 7/16 IN. (49.3 cm) Use only an ANSUL AUTOMAN Regulated Release assembly or OEM Release/Bracket Assembly. The regu- lator in this assembly is specifically designed to allow a regulated flow of expellant gas into the agent tank(s). Absence of this regulator could cause the tank(s) to rupture or create an improper system discharge. Mount the regulated release assembly, OEM Release Assembly, and each regulated actuator assembly required by completing the following steps: See Figures 1, 2, and 3. Select a rigid surface for mounting the enclosure. The mounting locations must allow the regulated release assembly and the regulated actuator assembly(ies) to be within the limitation of the actuation and expellant gas line lengths and must be able to support the weight of the assembly(ies). When the OEM Release Assembly is mounted inside a cabinet, clearances shall be provided for unrestricted movement of the release assembly compo- nents within the closed cabinet. Detach cover from the enclosure. Remove agent tank from enclosure and the expellant gas line hose from the tank/adaptor assembly. Secure enclosure box to selected mounting location using the four mounting holes. Use appropriate type of fasteners depending on the mounting surface. When mounting a 6-gallon manifolded system (or a 6- gallon individual piped system) it is critical that each mount- ing box is located as shown in Figure 3. There must be a 5/16 in. space between each box. Less than 5/16 in. will cause interference with the covers, and more than a 5/16 in. will cause a gap between the two hose grommets which will expose the hose to possible tampering or damage. Remove the 7/8 in. knockout in the left side of the ANSUL AUTOMAN release box and remove the 1 in. knockout in the right side of the tank-enclosure box. Install grommets in each (use ANSUL hose/grommet package, Part No. 418511). Remove 1/4 in. plug from back side of R-102 regular and install fixed end of secondary expellant gas hose (included in hose/grommet package, Part No. 418511) in 1/4 in. regulator outlet and wrench tighten. 1/2 IN. (19 0M) FIGURE 1 000287 9 3/4 IN (25 cm) 713/16 IN (20 cm) S. SINGLE TANK ENCLOSURE/REMOTE RELEASE L.1... 91N. (22.9 cm) FIGURE 2 787 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-2 REV. 5 7-1-09 MOUNTING THE COMPONENTS (Continued) OEM RELEASE/BRACKET ASSEMBLY 6 IN 7 IN. (18 CM) I 3.0 GALLON TANK BRACKET 31/2 IN. 1.0 L'- 38 18.5 IN. -jj:381N. S (47cm (la7cm) 115! (38 cm) •• S. .62(1.5cm) .62 (1.5 cm) 5.75 IN. (14.6 cm) MOUNTING HOLE DIMENSIONS 65/16 IN. (16 cm) LOCATION OF GROMMETS .-4 —'-I - 1313116 IN. 01 I ci I 1 (59.7 cm) 0 I 231/2 IN. 197116 IN. (49cm) 19 7/16 IN. (49 cm) ;ii 4 - 71121N. - (19.1 cm) O29O FIGURE 4 115/16 IN. .28 IN. (.7 cm) HOLE (TYP) (.8 CM) S. FIGURE 3 000788 CAUTION Do not install cartridge at this time or system may be actuated. 2. Mount each tank-enclosure or tank-bracket assembly by completing the following steps: Select a rigid, vertical surface for mounting the enclosure or bracket. (Keep in mind that the 3 gallon tank is taller than the bracket. Allow sufficient space for convenient piping and removal). Remove tank from enclosure or bracket, and secure enclo- sure or bracket to the mounting location using the four mounting holes. Use appropriate type of fasteners depend- ing on the mounting surface. STAINLESS STEEL TANKS 21/4 IN.* 1/8 IN. (57 mm ±3 mm) FROM THE TOP OF THE COLLAR FOR THE 3.0 GALLON TANK OR 1 314 IN. ±1/8 IN. (45mm* 3mm) FROM THE TOP OF THE COLLAR FOR THE 1.5 GALLON TANK RED PAINTED STEEL TANK I 1 IN. TO 11/8 IN. (25.29 mm) FROM THE BOTTOM OF THE FILL OPENING FOR BOTH 3.0 GALLON AND 1.5 GALLON TANKS FIGURE 6 292 c. Reinstall adaptor/tube assembly to tank by tightening until metal to metal contact is achieved between bottom of adaptor and tank collar. 4. Place each tank into its enclosure or bracket. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-2.1 4-1-06 REV. 5 MOUNTING THE COMPONENTS (Continued) 3. Fill each agent tank by completing the following steps: a. Remove tank adaptor/tube assembly from tank fill opening. Visually inspect tank adaptor to determine bursting disc is in place and that silver side is away from tank. See Figure 5. FIGURE 5 O29I b. Safety glasses should be worn during transfer opera- tions of ANSULEX Low pH Liquid Fire Suppressant. Avoid contact with skin or eyes. In case of contact, flush immediately with water for 15 minutes. If irritation persists, contact a physician. Do not take internally. If taken internally do not induce vomiting. Dilute with water or milk and contact a physician immediately. Place plastic funnel in fill opening and fill tank with 1.5 (5.8 L) or 3.0 (11.6 L) gallons of only ANSULEX Low pH Liquid Fire Suppressant. See Figure 6 for detailed filling tolerances. Note: Use a funnel with a screen to stop any foreign material from entering the tank. See Figure 6. During filling, the agent temperature should be 60 OF to 80 OF (16 °C to 27 °C). DO NOT FILL WITH COLD AGENT. DO NOT OVERFILL. Overfilling may result in agent entering gas hoses and regulator potentially causing system malfunction. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-2.2 REV. 1 7-1-98 NOTES: SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-3 7-1-09 REV.3 INSTALLING THE ACTUATION AND EXPELLANT GAS LINE . Before installing any actuation or expellant gas line, the design must be determined; and the regulated release assembly, each regulated actuator assembly and each tank-bracket assembly should be securely mounted. General Piping Requirements Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- nized, chrome-plated, or stainless steel pipe and fittings. Before assembling the pipe and fittings, make certain all ends are carefully reamed and blown clear of chips and scale. Inside of pipe and fittings must be free of oil and dirt. The piping and fitting connections must be sealed with pipe tape. When applying pipe tape, start at the second male thread and wrap the tape (two turns maximum) clockwise around the threads, away from the pipe opening. NOTICE Do not allow tape to overlap the pipe opening, as this could cause possible block- age of the gas pressure. Thread sealant or compound must not be used. When connecting actuation or expellant gas line piping, install a 1/4 in. union near the tank inlet for easy disassembly later. Note: Expellant gas line cannot use stainless steel braided hose. Actuation Gas Line Note: See Appendix for complete list and specifications when using rubber hose for actuation gas line. Install actuation gas line from the regulated release mechanism high pressure side outlet (side opposite regulated outlet) through the appropriate knockout in the enclosure by completing the following steps: 1. Remove the 1/8 in. plug from high pressure side outlet. Install the appropriate fitting for additional equipment attachment as required. A 1/4 x 1/8 in. reducing fitting is required to connect the 1/4 in. actuation line. See Figure 7. Typical Arrangements For A One Device Connection To Cartridge Receiver Typical Arrangements ii.i1For 1 &"71Device r1 Cartridge T1Receiver TypicaliArrangementsiFor i Three Device Conne -rnmTo Cartridge Receiver omm TypicaliArrangementsi tiRegulator Connections TO TANK IN TO REGULATED ACTUATOR BRACKET OR ASSEMBLY(IES) ENCLOSURE (PIPE OR HOSE) KINREGUD T TA OK IN REGULMEO RELEASE ASSEMBLY RELEASE ASSEMBLY SINGLE TANK DOUBLE AND MULTIPLE TANKS NOTE: WHEN PIPE IS USED, ALL PIPE AND FITTINGS SHALL BE SCHEDULE 40 (STANDARD WEIGHT) BLACK FIGURE 7 IRON, HOT-TIPPED GALVANIZED, CHROME-PLATED, OR STAINLESS STEEL SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-4 REV. 5 7-1-09 INSTALLING THE ACTUATION AND EXPELLANT GAS LINE (Continued) Actuation Gas Line (Continued) Run piping or hose up through the regulated release assem- bly enclosure knockout to the inlet on top of each regulated actuator assembly used within the system. The total combined length of the actuation gas line from the regulated release assembly to all regulated actuator assem- blies must not exceed 20 ft (6 m) when using an LT-20-R nitro- gen cartridge, an LT-30-R nitrogen cartridge, a 101-10 CO2 cartridge, or a 101-20 CO2 cartridge. See Figure 8. o. Note: When using stainless steel actuation line, a maximum ' of 17.5 It (5.3 m) of hose may be used. ACTUATION GAS LINE WITH AN LT-20-R, LT-30-R, 101-20 OR 101-30 CARTRIDGE MAXIMUM LENGTH -20 FT (6 m), - MAXIMUM NO. OF FITTINGS -9 If an expellant gas line is connected to the regulated release assembly along with an actuation gas line, the total combined length of the actuation and expellant gas line must not exceed 30 ft (9.1 m). See Figure 9. S. A combined total of nine fittings may be used in these lines, eight 900 elbows and one tee. Two 450 elbows equal one 900 elbow. REGULATED ACTUATOR ASSEMBLY EXPELLANT GAS LINES NOT INCLUDED IN ACTUATION GAS LINE LENGTH TOTALS REGULATED ACTUATOR ASSEMBLY REGULATED ACTUATOR ASSEMBLY FIGURE 8 ANSULAUTOMAN 000775 REGULATED RELEASE ASSEMBLY ACTUATION AND EXPELLANT GAS LINES WITH A DOUBLE-TANIc OR 101-30 CARTRIDGE MAXIMUM COMBINED LENGTH -30 FT (9 m), MAXIMUM COMBINED FITTINGS -9 ASSEMBLY EXPELLANT REGULATED ACTUATOR GAS LINES NOT INCLUDED IN COMBINED TOTALS REGULATED ACTUATOR ASSEMBLY REGULATED ACTUATOR ASSEMBLY REGULATED RELEASE ASSEMBLY FIGURE 9 ANSUL AUTOMAN REGULATED 000298 RELEASE ASSEMBLY SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-5 7-1-09 REV. 5 INSTALLING THE ACTUATION AND EXPELLENT GAS LINE (Continued) Expellant Gas Line From The Regulated Release Assembly Install expellant gas line from the regulated release assembly regulator in the enclosure by completing the following steps: The regulated release assembly is shipped with a factory- installed regulator. The regulator has two 1/4 in. outlets, one at the back and one at the bottom. The bottom outlet connects the expellant gas hose to the agent tank which is mounted inside the enclosure. The back outlet is sealed with a 1/4 in. plug. Connect expellant gas hose to the agent tank mounted inside the enclosure. TWO TANK, THREE TANK, AND MULTIPLE TANK SYSTEMS: If the expellant gas piping is required because an additional tank-enclosure or tank-bracket assembly is being installed, the plug installed in the back outlet must be removed. (See Figure 6 for proper connections to the regulator.) Pipe the 1/4 in. expellant gas line from the regulator back outlet through one of the knockouts provided in the enclosure. The total length of the expellant gas line from the regulated release assembly must not exceed 30 It (9 m) when using a "double-tank" nitrogen cartridge or a 101-30 CO2 cartridge. See Figure 10. EXPELLANT GAS LINE MAXIMUM LENGTH -30 FT (9 m), MAXIMUM NO. OF FITTINGS -9 If an actuation gas line is connected to the regulated release assembly along with an expellant gas line, the total combined length of the gas lines must not exceed 30 It (9 m) when using a "double-tank" nitrogen cartridge or a 101-30 CO2 cartridge. See Figure 9. A combined total of nine fittings may be used in these lines, eight 900 elbows and one tee. Two 450 elbows equal one 900 elbow. Expellant Gas Line From The Regulated Actuator Assembly Install expellant gas piping from the regulated actuator assembly regulator through the appropriate knockout in the enclosure by completing the following steps: The regulated actuator is shipped with a factory-installed regulator. The regulator has two 1/4 in. outlets 1350 from each other. One outlet is sealed by a 1/4 in. plug and the other contains the expellant gas hose for the agent tank which will be mounted within the enclosure. Connect expellant gas hose to the agent tank that is mounted inside the enclosure. Remove the 1/4 in. pipe plug from the regulator side outlet and pipe the 1/4 in. expellant gas line from the regulator through the knockout provided in the enclosure to a tank-enclosure or tank-bracket assembly. A maximum of one tank-enclosure or tank-bracket assembly is allowed per regulated actuator assembly. The maximum length of the expellant gas line from the regu- lated actuator to the tank-bracket assembly must not exceed 30 ft (9 m). See Figure 11. A total of nine fittings may be used in these lines, eight 900 elbows and one tee. Two 450 elbows equal one 900 elbow. EXPELLANT GAS LINE MAXIMUM LENGTH-3D FT (9 m), MAXIMUM NO. OF FITTINGS -9 REGULATED RELEASE ASSEMBLY FIGURE 10 000776 REGULATED ACTUATOR ASSEMBLY FIGURE 11 CHECK VALVE t r'l t MAXIMUM OF I ._ REMOTE I RELEASE MECHANISMS II I 1 (PART NO. I 433485)OR I c' ONE (1) REGULATED RELEASE (PART NO. 429853) 1/4 IN. STAINLESS STEEL HOSE III I II MAXIMUM OF 5 REGULATED ACTUATORS SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-6 REV. 4 7-1-09 INSTALLING THE ACTUATION AND EXPELLENT GAS LINE (Continued) Actuation Gas Line From Remote Release(s) to Regulated Actuators Install actuation gas piping from the remote release(s) to the regu- lated actuators by completing the following: Pipe the 1/4 in. actuation gas line from the 1/4 in. outlet in the remote release receiver, through the knockout provided in the top of the release enclosure, to each regulated actuator assembly. The maximum length of the actuation gas line from the remote release to all regulated actuators must not exceed 100 ft. (30.5). See Figure 12. Note: Stainless steel hose and fittings can be used. See Component Section for detailed information. A maximum of nine tees and twenty elbows are allowed in the actuation piping. Two 450 elbows equal one 900 elbow. See Figure 12. A safety relief valve (Part No. 15677) must be installed in the actuation piping. See Figure 12. P. Actuation Gas Line - 15* Tanks Maximum - Using 1/4 in. Stainless Steel Hose Note: Not for use with expellent gas line. Maximum hose length cannot exceed 17.5 ft (5.3 m). See Figure 13. Maximum of 5 regulated actuators allowed. Actuated with Remote Release (Part No. 433485) or Regulated Release Assembly (Part No. 429853). SAFETY RELIEF 9 TEES 20 ELBOWS VALVE MAXIMUM CK ACTUATOR AGENT TANK AND BRACKET OR WITH TANK (TYP.) AGENT TANK IN ENCLOSURE (TYR) I1(5ULATU RELEASES (5 MAXIMUM) P. FIGURE 12 000301 1/4 IN. STAINLESS STEEL HOSE OPTIONS SAFETY 42 IN. (107 cm) RELIEF VALVE MAX. HOSE LENGTH (TYR) I II I I' i n i i ii ii i I I I F I s.l II I I I II I I Li I I II I Li II I I Ii I REGULATED ACTUATOR WITH TANK NOTE: WHEN MULTIPLE RELEASE ASSEMBLIES ARE UTILIZED, A 1/4 IN. CHECK VALVE, PART NO. 25627, FIGURE 13 WILL BE REQUIRED AFTER EACH REGULATED RELEASE. 000301 NOTE: '15 TANKS MAXIMUM REFLECTS THE UTILIZATION OF THREE (3) TANK REGULATED ACTUATORS. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-7 7-1-09 REV. 6 INSTALLING THE DISTRIBUTION PIPING Before the following procedures can be completed, the piping design must already be determined; and the actuation and expel- lant gas lines from the regulated release, each regulated actuator, and each tank-enclosure or tank-bracket assembly should already be installed. These installation instructions are identical for single, double, and multiple-tank systems except for the quantity of tanks and hazard areas to be covered. General Piping Requirements Use Schedule 40 black iron, chrome-plated, or stainless steel pipe and fittings. NOTICE Do not use hot-dipped galvanized iron pipe or fittings in the agent distribution piping. Before assembling the pipe and fittings, make certain all ends are carefully reamed and blown clear of chips and scale. Inside of pipe and fittings must be free of oil and dirt. The distribution piping and fitting connections, located in or above the hood or the protected area, must be sealed with pipe tape. When applying pipe tape, start at the second male thread and wrap the tape (two turns maximum) clockwise around the threads, away from the pipe opening. NOTICE Do not allow tape to overlap the pipe opening as the pipe and nozzles could become plugged. Thread sealant or compound must not be used as it could plug the nozzles. Distribution piping may be run independently or two agent tanks may be manifolded together and run to the predeter- mined hazard area. Only agent tanks expelled from the same cartridge may be manifolded. NOTICE Closely follow the piping requirements for each size system, as detailed in the 'System Design" section, when installing distribution piping. Branchline tees can be used to create more than one branch and can be installed as a thru tee, side outlet tee or bull tee. Pipe Hanger Recommended Guidelines Space hangers as follows: Maximum Recommended Pipe Size Distance Between Hangers 3/8 in. 5ft(1.5m) Hangers should be placed between elbows when the distance is greater than 2 ft (0.6 m). Piping Installation Starting at the tank, pipe directly from the union located on the tank adaptor. A reducing fitting may be necessary to conform to the distribution piping. Based on the piping sketch developed in the 'System Design" section of this manual, install the supply line and position the tees at points where branch lines must be installed. See Figure 14. Run all branch lines to the hazard area and connect each nozzle. (Make certain all piping is securely bracketed.) 1 • —r JL ----------- -------- - N FIGURE 14 Make certain all threaded connections are properly tightened. Threaded connections located in the protected area(s) and above the hood must be sealed with Teflon pipe tape, as a minimum. Apply pipe tape to male threads only. Make certain tape does not extend over the end of the thread, as this could cause possible blockage of the agent distribution. Pipe tape minimizes friction between bearing surfaces of the threads when threading pipe to fittings. The resulting heat may expand the pipe threads before the joint is properly made. When the pipe threads cool and contract in the fitting, the joint may become loosened causing cooking grease to migrate into the distribution piping, and/or leakage at the fitting during a pressure test or agent discharge. Note: When required to provide pressure testing of pipe or a system discharge test, it is recommended that all pipe connec- tions utilize Teflon pipe tape. Install the correct nozzle(s) for each hazard area as previously designed. Some nozzles are required to be properly oriented before they are positioned for aiming. Aim the nozzles to a pro-determined aim point in accordance with the instructions in the "System Design" section. Using the Nozzle Aiming Device (Part No. 431992) will aid in the aiming process. The device clamps to the nozzle and emits a small laser light that reflects on the surface where it is aiming. If the nozzle is used with Swivel Adapter (Part No. 418569), the nozzle with Aiming Device can be rotated to the exact aiming point and then tightened to hold that angle. Before installing blow-off caps on nozzles, apply a small amount of Dow Corning No. 111 silicone grease across the opening in the nozzle tip and also a small amount coating the exterior of the blow-off cap. DO NOT FORCE SILICONE GREASE INTO NOZZLE TIP OPENING OR FILL CAP WITH GREASE. NOTICE When using old style metal blow-off cap, make certain the spring clip rotates freely on the metal cap and coat the outside of the cap, including the clip, with Dow Corning No. 111 silicone grease. Make certain a blow-off cap is in place over each nozzle tip. These blow-oft caps are designed to keep grease from build- ing-up on the nozzle orifice and inhibiting the agent flow. See Figure 15. , liii 11*1 a. FIGURE 15 6. 7 8. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-7.1 REV.0 7-1-09 INSTALLING THE AGENT DISTRIBUTION HOSE (FOR CASTERED/MOVEABLE EQUIPMENT) Agent Distribution Hose can be used in the supply line or appliance branch line to allow a castered cooking appliance with castered supports with nozzles attached directly to the appliance, to be moved out of its normal operating position for service or cleaning. The following instructions must be followed in their entirety. Failure to do so may result in the R-102 Fire Suppression System not functioning properly due to incorrect installation. CRITICAL INSTALLATION REQUIREMENTS 1; Design and installation must be performed by qualified personnel. The Agent Distribution Hose shall not be concealed within or run through any wall, floor, or partition, and shall not have any direct exposure to excessive heat or radiant flame from the cooking appliances. Strong cleaning solutions or chemical substances must not come in contact with the Agent Distribution Hose. These may include acids, solvents, fluxes with zinc chloride, or other chlo- rinated chemicals. In case of contact, rinse down the Agent Distribution Hose with water and dry thoroughly. Contact with foreign objects, sharp edges, wiring, or substances must be avoided. Bending and flexing of Agent Distribution Hose on moveable appliances (i.e. those factory equipped with casters) should be limited to pulling and pushing the appliances in or out for cleaning or maintenance. The hose shall never be installed or bent tighter than a 3 in. (7.6 cm) radius (6 in. (15.2 cm) diam- eter) loop. The Agent Distribution Hose must not be kinked, twisted, or have sharp bends when installed or when equipment is pulled away from the wall. Make sure that all fittings are tightened properly. Adequate means must be provided to limit the movement of castered appliances. A 36 in. (91.4 cm) long Restraining Cable supplied with the agent distribution hose is required to be used for all castered appliances using the Agent Distribution Hose. (Refer to Restraining Cable Installation Instructions.) The Restraining Cable requires periodic maintenance to ensure proper operation. The Restraining Cable must be attached to the wall and appli- ance anytime the distribution hose is connected to the appli- ance. Do not over-extend the Agent Distribution Hose when moving equipment (for cleaning, maintenance, etc.). AGENT DISTRIBUTION HOSE INSTALLATION INSTRUCTIONS Before proceeding, CAREFULLY read all instructions, including all CRITICAL INSTALLATION REQUIREMENTS. General Requirements 1. The Agent Distribution Hose, Part No. 434462 (which is part of Discharge Hose and Restraining Cable Kit, Part No. 435982), is 1/2 in. (12.7 mm) diameter x 60 in. (152.4 cm) long and is provided with two (2) male NPT swivels for ease of installation. Maximum of six (6) Agent Distribution Hoses can be used in each agent distribution piping network. Agent Distribution Hose can only be used for castered appli- ances or appliances setting on castered supports. Maximum of two (2) Agent Distribution Hoses are allowed in the supply line. However, the Agent Distribution Hose can only be used at the castered appliance. Maximum of two (2) Agent Distribution Hoses are allowed in the branch line. An acceptable installation scenario would be providing separate protection of two (2) (side-by-side) appli- ances, each with its own Agent Distribution Hose and tether, supplied from the same appliance branch. The Agent Distribution Hose is to only be used in the distrib- ution piping of a single 1 1/2 or 3 gal (5.7 or 11.4 L) tank or two (2) manifolded 3 gal (11.4 L) R-102 extinguishing systems or larger systems using combinations thereof. However, the Agent Distribution Hose is never to be used to manifold two (2)3 gal (11.4 L) tanks. Installation Requirements Agent Distribution Hose must be connected to 3/8 in. NPT black iron, chrome-plated, or stainless steel fittings. The connection from hose to fitting requires a 1/2 in. x 3/8 in. reducing coupling, Ansul Part No. 436228. All Agent Distribution Hose connections must be sealed with pipe tape. When applying pipe tape, start at the second male thread on the swivel ends of the hose. Wrap the tape (two turns maximum) clockwise around the threads, away from the hose end fitting opening. All connections of distribution piping to Agent Distribution Hose for castered appliances, with distribution nozzles installed/affixed to the appliance, must be located behind the cooking equipment in an area protected from obstructions and possible wear or damage. 3/8 in. schedule 40 pipe will need to be run from the hose connection to the distribution nozzle(s) installed/affixed to the appliance. Pipe must be installed and adequately secured at a height at or below the cooking surface of the appliance. (See Figure 21.) All existing distribution pipe and fitting limitations must be observed and followed. Each flex distribution hose used is to be considered as an equivalent length of 3/8 in. pipe when calculating the acceptable length (ft (m)) of allowable distribu- tion pipe. All hose-to-pipe connection fittings are to be oriented in a vertical down position. The hose connections must be positioned below an elevation where the hose could be exposed to the radiant or convected heat generated by normal cooking operations (such as the horizontal plane of appliance's cooking surface), or to heat from appliance exhaust. As a minimum height, the hose connection shall be no lower than 30 in. (76.2 cm) from the floor. The distribution piping shall be supported and secured per local plumbing practices. Hose ends are to be offset 6 to 8 in. (15.2 to 20.3 cm) center to center of fittings (See Figure 16) to maximize hose life expectancy and facilitate appliance movement. With the appli- ance in its normal operating position, check the hose bend to make certain the bend is not less than a 3 in. (7.6 cm) bend radius (6 in. (15.2 cm) diameter). SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-7.2 7-1-09 REV. 0 AGENT DISTRIBUTION HOSE INSTALLATION INSTRUCTIONS (Continued) Installation Requirements (Continued) OVERHEAD VIEW W APPLIANCE A L L PIPE (NOT SUPPLIED IN Ku) - HOSE 6-8 IN (15.2-20.3 cm) OFFSET PIPE (SUPPLIED ONLY WITH CENTER TO CENTER HENNY PENNY FRYER NOZZLE KIT, PART NO. 434455) FIGURE 16 Restraining Cable Installation Important: A Restraining Cable shall always be permanently attached to the appliance and wall directly behind the appliance when the Agent Distribution Hose is installed. Removal of this cable shall only occur when the Agent Distribution Hose is not installed to the appliance. See Figure 17 for mounting the Restraining Cable to the wall. See Figure 18 for mounting the Restraining Cable to the back of an appliance. RESTRAINING CABLE —WALL-MOUNTED OPTION SHEET METAL WALL -0. COVERED WALLS STUD WALL MOUNT / BRACKET SCREW EYE BOLT (4) SELF TAPPING SHEET METAL SCREWS FIGURE 17 omom RESTRAINING CABLE - APPLIANCE-MOUNTED OPTION BACK OF APPLIANCE NUT EYE NYLON LOCK NUT BOLT-09 _1~~ WASHER WASHER FIGURE 18 RESTRAINING CABLE - HENNY PENNY-MOUNTED OPTION BACK OF— APPLIANCE PHILIPS SCREW NUT WASHER FIGURE 19 ONIMI The Restraining Cable must be connected from the appliance to the wall or some other structurally sound object capable of restraining the castered appliance from being able to be pulled or pushed out to a point that will result in strain or stress to the Agent Distribution Hose. The Restraining Cable should be installed in line with the Agent Distribution Hose. For sheet metal covered walls, the Restraining Cable Assembly includes four (4) 3/4 in. x #8 self tapping sheet metal screws, and a Restraining Cable Bracket. Securely attach the Restraining Cable Bracket to the sheet metal covered wall using the 3/4 in. x #8 self tapping metal screws provided. For mounting to wall studs, the Restraining Cable Assembly includes one (1) screw eye lag bolt, 5/16 in. x 2.5 in. (6.4 cm) long. Locate a structural area (frame) on the rear side of the equip- ment that is in line with the wall attachment. Note: It may be necessary to contact the appliance manufacturer for a suit- able location. Drill a 5/16 in. (8 mm) diameter hole. Use caution when drilling hole, so that internal components are not damaged. The Restraining Cable Assembly also includes a 5/16 in. threaded eye-bolt, 5/16 in. hex head nut, 5/16 in nylon lock nut, and two (2) 5/16 in. flat washers. Thread the included hex nut onto the eye-bolt. Slide one washer onto the eye-bolt threads next to the nut. Then, slide the eye-bolt through the drilled hole and place a washer and nylon locknut onto the eye-bolt on the inside frame of the equipment. Tighten securely. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-7.3 REV.0 7-1-09 AGENT DISTRIBUTION HOSE INSTALLATION INSTRUCTIONS (Continued) Restraining Cable Installation (Continued) 7. Attach one of the snap hooks (included in the Restraining Cable package) on the end of the Restraining Cable to the wall bracket and the other snap hook to the eye-bolt (See Figure 20). After snap-hooking the assembly, seal the Restraining Cable Loops to the wall bracketry and appliance connection hardware with ANSUL Lead Wire Seal, Part No. 197. Note: For the Kenny Penny Pressure Fryers that utilize the ANSUL Kenny Penny Fryer Nozzle Kit, Part No. 434455, the 5/16 in. philips screw supplied in the Kenny Penny Fryer Nozzle Kit, the 5/16 in. eye nut, and 5/16 in. washer included in the Restraining Cable Assembly Kit, must be used. (See Figure 19). RESTRAINING CABLE INSTALLATION PACKAGE A - RESTRAINING CABLE B-STAPLE ri F-5/I6INNYLON • '' BRACKET LOCK NUT II', G-51161N XSII6IN C-3/41N.X#8 WASHERS SCREWS (4) (2) 4,, H-SCREW EYE BOLT D - EYE BOLT %. I-SNAP HOOK E- 5/16 IN HEX NUT A - RESTRAINING CABLE I - SNAP HOOK D - EYE BOLT EYE BOLT FASTENING-* - HARDWARE FIGURE 20 OUM Final Installation Guidelines and Checkout Procedures After the Agent Distribution Hose and the Restraining Cable is properly installed, carefully push the appliance back to its normal operating position. Check that the hose does not have sharp bends, and is not kinked, twisted, or caught on anything behind the appliance. Verify the Restraining Cable limits the travel of the appliance and prevents the application of any pull force or bending stress on the Agent Distribution Hose or hose-to-pipe connec- tions. Make certain there are no sharp bends and kinks in the hose when pulling out the cooking equipment. The Agent Distribution Hose should always be in a vertical natural loop, never having any bends greater than a 3 in. (7.6 cm) radius (6 in. (15.2 cm) diameter), hose twists, or sharp bends. (See Figure 21.) If any of these conditions exist, the hose and/or hose connections will require installation modifications. SIDE VIEW ACCEPTABLE HOSE ORIENTATION AGENT DISTRIBUTION 3/8 IN - PIPING HEIGHT OF HOSE CONNECTION IS MIN. TO BE BELOW 30 IN THE APPLIANCE (76.2 COOKING Cm) SURFACE UNACCEPTABLE HOSE ORIENTATION SHARP BENDS TWISTING FATIGUE 1 6 1 V 6 FIGURE 21 Return the appliance to its normal operating position in accor- dance with NFPA 96. Means shall be provided to verify that the appliance returns to its original designed positioning. Failure to do so may result in undue stress and fatigue of the hose and hose connections. B - STAPLE BRACKET I- SNAP HOOK SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-8 REV.3 7-1-09 INSTALLING THE DETECTION SYSTEM Before the following procedures can be completed, the detection design must already be completed. These installation instructions are identical for single, double, and multiple-tank systems except for the number of hazard areas to be covered. NOTICE Inform customer that fusible links should not be exposed to ammonia-based chemical cleaners or steam. Based on the requirements listed in the "System Design" section, mount the detectors in their predetermined locations. Run 1/2 in. conduit from the regulated release mechanism trip hammer assembly knockout hole to locations selected for mounting the detectors. Note: Before assembling the conduit and fittings, make certain all ends are carefully reamed and blown clear of chips and scale. Inside of pipe and fittings must be free of oil and dirt. When changing the direction of conduit, use only ANSUL pulley elbows, except, at the top of the regulated release, it is acceptable to use the "Conduit Offset Assembly" (Part No. 436063). Note: If stainless steel scissor linkage is used in the system while using conduit off-set assembly, the following limitations must be observed: Maximum number of elbows - 16 Maximum number of detectors - 15 Maximum length of 1/2 in. EMT Conduit - 150 ft (45.7 m) Part No. 435546 and 435547 are the "scissor" style series and terminal detector assemblies. These detector assemblies use a detector linkage assembly which does not require the wire rope to be threaded through the linkage assembly while it is being fed through the detection system. "Scissor" Style Linkage Installation 1. Secure the conduit to the detector bracket using the two 1/2 in. steel compression fittings on the series detector bracket or the single 1/2 in. steel compression fitting on the terminal detector bracket. See Figure 22. COMPRESSION FITTING NUT 1/2 IN. STEEL I COMPRESSION FITTING FIGURE 22 000306 NOTICE Do not use zinc die cast compression connec- tors on the detection conduit lines as these will not withstand the normally high temperatures experienced in the plenum area. 2. For a terminal detector located in a duct or header opening, secure both sides of the detector bracket with conduit, as shown in Figure 23. 2463 002464 FIGURE 23 FIGURE 28 000003 ANSUL AUTOMAN OR REMOTE RELEASE ASSEMBLY SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-9 7-1-09 REV.2 INSTALLING THE DETECTION SYSTEM (Continued) 2-3 IN. "Scissor" Style Linkage Installation (Continued) (58 cm) 3. Starting at the release assembly, feed the wire rope through the hole in the release mechanism locking clamp, allowing the excess wire rope to hang down. (Do not tighten set screws in locking clamp at this time.) See Figure 24. FIGURE 27 000312 6. To give a constant tension on the wire rope during installation of the detector linkage, hang a vice grip or other weighted device on the excess stainless steel wire rope, leaving an LOCKING adequate length of spare wire rope between the locking clamp CLAMP and the weighted device. NOTICE When attaching the weighted device to the excess wire rope, allow approximately 3 in. (8 cm) of wire rope for each detector linkage for proper installation. FIGURE 24 000300 From the release assembly, run the stainless steel wire rope through the conduit, pulley elbows and detector brackets to the terminal detector. NOTICE If wire rope requires splicing, make certain splice is at least 12 in. (30.5 cm) away from any pulley elbow or conduit adaptor to avoid interfer- ence. Feed the wire rope through the terminal detector bracket as shown in Figure 25 or as shown in Figure 26 if the terminal detector is mounted within a duct or header opening, and install the stop sleeve approximately 2 to 3 in. (5 to 8 cm) from the end of the wire rope. See Figure 27. Use the National Telephone Supply Company Nicopress Sleeve Tool (Stock No. 51-C-887) or equal to properly crimp the stop sleeve. FIGURE 25 310 Example: If the system has six detectors, there should be approximately 18 in. (46 cm) of excess wire rope between the locking clamp and the weighted device, which will be utilized when the linkage is put in place. Install detector scissor assembly as shown in Figure 28. Note that the ANSUL AUTOMAN or remote release assembly is located on the left side of the detector bracket. Slightly crimp the two assembly boot-hooks" over the cable with pliers so the cable is captured under each hook but the whole assem- bly can move from side to side. Center the assembly in the detector bracket. FIGURE 26 000311 FIGURE 32 000100 9. Install the linkage and the correct ANSUL approved fusible link in the remainder of the detector brackets. Make certain all detector linkages are positioned against either the front or back upper lip of the formed detector bracket. See Figure 30a. FIGURE 30 000324 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-10 REV.3 7-1-09 INSTALLING THE DETECTION SYSTEM (Continued) "Scissor" Style Linkage Installation (Continued) 8. Hook the fusible link on the ANSUL AUTOMAN or remote release assembly side of the hook assembly, then pull the fusible link to the opposite side and complete the hookup as shown in Figures 29 and 30. The top of the hook assembly must be inside the bracket stiffeners. The hook assembly with the ANSUL fusible link in place must be located toward the terminal detector side of the bracket. FIGURE 29 00004 Insert cocking lever (Part No. 14995 or Part No. 435603) on left side of the release mechanism, with the movable flange resting securely against the corner of the cartridge receiver and spring housing, and with the notched lever portion engag- ing the cocking pin on both sides of the release mechanism. See Figure 31. KING PIN COCK FIGURE 31 000319 Using long handle cocking lever, Part No. 14995, or wrench on short handle cocking lever nut, Part No. 435603, pull down to raise cocking pin until the trip lever indented surface moves underneath the pin and locks the pin in the up position. See Figure 32. FIGURE 30a :( BAR PERLY INSTALLED FIGURE 33 0m321 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-11 7-1-09 REV. 3 INSTALLING THE DETECTION SYSTEM (Continued) "Scissor" Style Linkage Installation (Continued) 12. Remove cocking lever and insert lock bar (Part No. 14985) on left side of the cable lever, over the two shouldered projecting stud extensions, and slide bar forward into locking position. (The release mechanism cannot be actuated, nor can enclo- sure cover be replaced until the lock bar is removed.) See Figure 33. 16. Lower tension lever to 'DOWN" position and inspect the base of the wire rope locking clamp to make certain that there is a minimum of 1/4 in. (6.4 mm) and a maximum of 3/8 in. (9.5 mm) clearance between the base of the trip hammer locking clamp assembly and the cable lever assembly. See Figure 35. (If clearance is not between 1/4 in. (6.4 mm) or 3/8 in. (9.5 mm), raise tension lever, loosen set screws on locking clamp and repeat Steps 15 and 16.) Make certain the hook assembly with the ANSUL fusible link in place is located toward the terminal detector side of each bracket. Failure to do so may restrict travel of detec- tion line, causing system to malfunction. TRIP HAMMER LOCKING ASSEMBLY / CLAMP 1/4 IN. MINIMUM (6.4 mm) 3/Sin. MAXIMUM (9.5 mm) 13. Make certain tension lever is in the 'UP" position. See Figure 34. FIGURE 34 000322 Verify each detector linkage assembly, with correct fusible link, is in the detector bracket, located fully toward the terminal detector side. NOTICE Due to the close adjustment between the trip hammer and cable lever assemblies, use only the particular fusible link(s) selected for installa- tion in each detector, including terminal detec- tor, to ensure correct adjustment when performing Steps 15 and 16. Raise trip hammer 3/8 in. to 1/2 in. (9.5 to 12.7 mm), pull all slack out of wire rope, and tighten set screws on locking clamp. CABLE LEVER ASSEMBLY FIGURE 35 323 A CAUTION Do not install cartridge at this time as an accidental actu- ation could cause system discharge. Test detection system in accordance with the Testing and Placing in Service Section, Page 7-1 - 7-3, of this manual. When testing has been completed, cut off excess wire rope in the regulated release assembly, leaving approximately 2 in. (5.1 cm) of wire rope below the locking clamp. TENSION LEVER IN UP POSITION SECTION V — INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-12 REV. 4 7-1-09 INSTALLING REMOTE MANUAL PULL STATION GENERAL INSTALLATION REQUIREMENTS To install a remote manual pull station complete the following steps: Make certain that regulated release assembly enclosure cover is detached and lock bar is properly inserted within the regu- lated release mechanism. NOTICE Failure to follow these instructions may lead to system actuation. Verify that cartridge has been removed from regulated release assembly and that the regulated release assembly is in the cocked position. If regulated release assembly does not have lock bar inserted or cartridge removed, refer to the "Semi-Annual Maintenance:' Page 8-1, in "Maintenance Examination" section, and complete Steps 2 and 3 before completing the following installation steps. Select a convenient location in the path of egress for mount- ing the pull station(s) to the wall. The pull station should be installed at a height of 42 in. to 48 in. (107 cm to 122 cm) in accordance with the authority having jurisdiction and the American Disabilities Act (ADA) requirements. A maximum of two (2) manual pull stations can be connected to each AUTOMAN Release. INSTALLATION FOR REMOTE MANUAL PULL STATION UTILIZING EMT CONDUIT ONLY The total length of the wire rope used for each manual pull station within a system must not exceed 150 It (46 m). The maximum number of pulley elbows that may be used per each manual pull station is 20 of Part No. 423250 or 415670. If junction box(es) is used, fasten a 4 in. (10 cm) junction box to wall or in wall where pull station is to be mounted, with mounting screws positioned so that when pull station cover is positioned in place, the printing will appear right side up and readable. Install and secure 1/2 in. conduit, pulley tee (if required), and pulley elbows from each pull station junction box to regulated release assembly as necessary. See Figure 36. See Figures 36a, 36b, and 36c for optional methods of installing wire rope when utilizing a pulley tee, Part No. 427929. REMOTE MANUAL PULL STATION SINGLE APPLICATION PULLEY ELBOW WIRE ROPE OVAL SLEEVE CABLE LEVER MECHANISM REMOTE 's. MANUAL PULL STATION BREAK ROD LOCK BAR SIDE STUD JUNCTION BOX (NOT •- RING HANDLE FIGURE 36 SUPPLIED BY ANSUL) 001090 REMOTE MANUAL PULL STATION DUAL APPLICATION - OPTION 1 (ONE (1) WIRE ROPE CONNECTED TO CABLE LEVER ASSEMBLY) 6 IN. (152 mm) MINIMUM FROM CRIMP SLEEVE TO PULLEY TEE 2 IN. (51 mm) MINIMUM FROM CRIMP SLEEVE 10 COMPRESSION FITTING JUNCTION BOX (NOT SUPPLIED BY ANSUL) REMOTE MANUAL PULL STATION DUAL APPLICATION - OPTION 2 (TWO (2) WIRE ROPES CONNECTED TO CABLE LEVER ASSEMBLY) 8 PULLEY TEE PULLEY ELBOW OVAL SLEEVE RELEASE MECHANISM t f CABLE LEVER I _—.. LOCK r9LN BAR u 000335 JUNCTION BOX (NOT REMOTE/ SUPPLIED BY ANSUL) MANUAL PULL STATION FIGURE 36b REMOTE MANUAL PULL STATION APPLICATION - OPTION 3 RELEASE MECHANISM FIGURE 36c PULLEY 'PULLEY TEE ELBOW NO PULLEY ELBOWS ALLOWED WHERE TWO WIRE .ROPES ARE PRESENT USE (2) TWO OVAL SLEEVES, PART NO. 4596 RELEASE - MECHANISM — j- 008391 REMOTE / MANUAL PULL STATION FIGURE 36a CAI LE SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-13 7-1-09 REV. 3 5. Fasten pull station assembly to each junction box (if junction box is used). m. 6. Slide oval crimp sleeve onto wire rope. Loop wire rope through cable lever guide holes and back through the oval crimp sleeve. See Figure 36. 7. Pull slack out of each wire rope and crimp sleeve. (Use the National Telephone Supply Company Nicopress Sleeve Tool 4. Stock No. 51-C-887 or equal to properly crimp stop sleeve.) See Figure 36. Note: When utilizing flexible conduit for remote manual pull station or mechanical gas valve installation, refer to "Installation of Remote Manual Pull Station or Mechanical Gas Valve Utilizing Flexible Conduit" instructions on pages 5-17 through 5-17.11. INSTALLING REMOTE MANUAL PULL STATION (Continued) INSTALLATION FOR REMOTE MANUAL PULL STATION UTILIZING EMT CONDUIT ONLY (Continued) MINIMUM OF 6 IN. (152 mm)_j__ (2) OVAL SLEEVES, PART NO. 4596 TO AIR CYLINDER NO ELBOWS ALLOWED FOR GAS WHERE TWO WIRE VALVES OR ROPES ARE PRESENT RELEASE CABLE CONTINUOUS WIRE LEVER FOR ROPE PULL STATIONS PULLEY TEE, PART NO. 427929 ONLY 10 EIThER GAS VALVES OR PULL STATIONS. MIXING IS NOT ALLOWED. m83m TWO (2) WIRE ROPES CONNECTED BETWEEN A PULLEY ELBOW AND A PULLEY TEE FIGURE 36d 4. Feed wire rope from the ANSUL AUTOMAN release through conduit and pulley elbows and pulley tee, if provided, to the pull station junction box. Follow the instructions for assem- bling the pull station and block assembly and attaching the wire rope to the pull station pull knob (see Figures 64 through 79). NOTICE Make certain that wire rope rides on top and in center of pulley sheave. If the 50 it (15 m) wire rope has been spliced to accommodate a longer run, do not allow the spliced ends to be within 6 in. (152 cm) of any pulley elbow or conduit adaptor. INSTALLING MECHANICAL GAS VALVE NOTICE Mechanical gas valves are designed for indoor installation only. To install each Mechanical Gas Shut-off Valve complete the follow- ing steps. (All gas valve installation and testing shall be made in accordance with the authority having jurisdiction.) Note: Mechanical gas valve air cylinder(s) can be installed in regulated release assemblies and also regulated actuator assem- blies. Installation in either is the same. Make certain that regulated release assembly enclosure cover is detached and lock bar is properly inserted in the regulated release mechanism. NOTICE Failure to follow these instructions may lead to system actuation. Verify that cartridge has been removed from regulated release assembly and that the regulated release mechanism is in the cocked position. If regulated release mechanism does not have lock bar inserted or cartridge removed, refer to the 'Semi-Annual Main- tenance:' Page 8-1, in 'Maintenance Examination" section, and complete Steps 2 and 3 before completing the following installation steps. Remove plug from cartridge receiver. See Figure 37. CARTRIDGE RECEIVER PLUG FIGURE 37 000339 Locate air cylinder and bracket assembly over the two 7/32 in. (0.6 cm) holes on right side of the enclosure. Assemble with screws, Iockwashers, and nuts. Wrench tighten. See Figure 38. Air cylinder(s) can also be mounted in the inverted posi- tion, allowing for direct exit out the knockout(s) in the bottom of the enclosure. See Figure 39. FOR MOUNTING ONE MECHANICAL GAS VALVE WIRE ROPE -01 ,, STOP SLEEVE ROD ~~l MOUNTING BRACKET AIR CYLINDER H 1-4 1/8 IN. COPPER TUBING AND FITTINGS FIGURE 38 0003 MINIMUM OF 6 IN. (152 mm) SPLICED WIRE ROPE SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-14 REV. 3 7-1-09 INSTALLING MECHANICAL GAS VALVE (Continued) TOP KNO 6011DM KNOCKOUTS MECHANICAL GAS VALVE AIR CYLINDER -102 REGULATED ELEASE FIGURE 39 Note: Two air cylinders are necessary only if the old style pulley tee, Part No. 15342, is utilized. If new style pulley tee, Part No. 427929, is utilized, only one air cylinder is required. Individual wire ropes can be run from each gas valve to a single air cylinder. See Figure 40. 5. To install second mechanical gas valve shut-off system, locate second air cylinder and bracket assembly adjacent to first assembly and over the two remaining 7/32 in. (.6 cm) holes provided on right side of the enclosure. Assemble second cylinder with screws, lockwashers, and nuts as required. Wrench tighten. See Figure 40. WIRE ROPE STOP SLEEVES (SYSTEMS USING AIR CYLINDER RODS PART NO. 15342) J PULLEY TEE, MOUNTING BRACKETS - W0342 118 IN. COPPER TUBING AND FITTINGS - / / (SYSTEMS USING I PULLEY TEE, PART NO. STOP SLEEVES 4V9) . (2) SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-15 7-1-09 REV.4 INSTALLING MECHANICAL GAS VALVE (Continued) 6. Install the necessary 1/8 in. copper tubing and fittings for each air cylinder to the accessories piping arrangement on the regulated release mechanism. See Figures 38 and 40. NOTICE Do not kink 1/8 in. copper tubing or form a bend too close to a fitting. Secure each fitting without over tightening. Over tightening could result in pressure leakage or line separation at actuation. To reduce the risk of explosion due to leaking gas, make certain that the gas line is turned off before connecting the gas valve. Gas valve installation shall be performed by qualified individuals in accordance with local jurisdiction requirements. Install mechanical gas valve to its selected location in gas line so that it ensures safe shut-off to all predetermined appliances being protected upon actuation of the system. Mechanical gas valves may be mounted in any convenient horizontal or verti- cal position. See Figure 41. Use new pipe, properly reamed and cleaned of metal chips. Make certain gas flow is in the same direction as arrow shown on gas valve. To avoid cracking the gas valve casting, do not overtighten pipe connections. If pipe tape, paste, spray, or similar lubricant is used, extra care should be taken to avoid overtightening. Apply lubricant to male threads only. Wrench tighten pipe to gas valve. DO NOT USE GAS VALVE AS A LEVER WHEN INSTALLING OR VALVE DAMAGE MAY OCCUR. See Figure 41. If strainer is utilized, attach strainer ahead of gas valve. If necessary, install drip leg in gas line in accordance with the authority having jurisdiction. The total length of wire rope allowed for each valve must not exceed 150 ft (46 m). The maximum number of pulley elbows allowed for each gas valve is 20. ANSUL MECHANICAL GAS VALVES CORRECT WAY: VISE GRIP ENDS NEXT TO PIPE BEING INSERTED. PREVENTS EXCESS STRAIN ON VALVE BODY. CORRECT WAY: WRENCH APPLIED NEXT TO PIPE BEING INSERTED PREVENTS WRONG WAY: WRENCH APPLIED EXCESS STRAIN ON VALVE BODY AT THIS POINT STRAINS VALVE BODY. ASCO MECHANICAL GAS VALVES WAY: 'APPLIED NEXT IEING INSERTED S EXCESS N VALVE BODY. CORRECT WAY: WRENCH APPLIED NEXT TO PIPE BEING INSERTED. PREVENTS EXCESS STRAIN ON VALVE BODY. WRONG WAY: WRENCH APPLIED AT THIS POINT STRAINS VALVE BODY. FIGURE 41 6 IN. (152 mm) MINIMUM FROM CRIMP SLEEVE 10 PULLEY TEE NO PULLEY ELBOWS ALLOWED WHERE TWO WIRE ROPES ARE PRESENT 2 IN. (51 mm) MINIM FROM CRIMP SLEE TO COMPRESSION FITTING S, FIGURE 44 001091 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-16 REV. 3 7-1-09 INSTALLING MECHANICAL GAS VALVE (Continued) Install 1/2 in. conduit, and pulley elbow(s) from the mechanical gas valve to regulated release assembly enclosure as neces- sary. Beginning at the regulated release assembly, thread the end of the wire rope through hole provided in air cylinder rod. See Figure 38. Feed end of wire rope through conduit and each pulley elbow. Make certain that wire rope rides on top and in center of pulley sheave. If the 50 ft (15 m) wire rope has been spliced to accom- modate a longer run, do not allow the spliced ends to be within 12 in. (30 cm) of any pulley elbow or conduit adaptor. Remove side cover on gas valve and thread end of wire rope through hole in cocking lever. Slide stop sleeve (Part No. 26317) on to wire rope and crimp. (Use the National Telephone Supply Company Nicopress Sleeve Tool Stock No. 51-C-887 or equal to properly crimp stop sleeve.) Make certain crimp is on top of trigger, with wire rope curled under lever. See Figure 42. TRIGGER FIGURE 42 000341 With the end of wire rope already threaded through hole in air cylinder rod, slide stop sleeve (Part No. 26317) onto wire rope and leave loose. Do not crimp stop sleeve at this time. See 0. Figure 38. Cock mechanical gas valve as shown in Figure 43. Note: A valve cocking tool is available. Order Part No. 416018. ANSUL MECHANICAL GAS VALVE COCKED OPEN POSITION FIRED CLOSED POSITION ASCO MECHANICAL GAS VALVE COCKED OPEN POSITION FIRED CLOSED POSITION FIGURE 43 Raise air cylinder rod "UP" to its maximum extended position. See Figure 38. Manually pull wire rope to remove excess slack. Slide stop sleeve against air cylinder rod, make certain all slack is removed from wire, and crimp stop sleeve. See Figure 38. Cut off any excess wire rope approximately 3/4 in. (2 cm) from end of stop sleeve. Note: If utilizing a pulley tee to operate either a single mechanical gas valve from two (2) ANSUL AUTOMAN releases or two (2) mechanical gas valves from one (1) air cylinder in an ANSUL AUTOMAN release, see Figures 44 and 45 for installation instructions. Maximum length of wire rope to each ANSUL AUTOMAN release must not exceed 150 ft (45.7 m) and maximum number of elbows must not exceed 20. r TWO (2) AIR CYLINDERS - ONE (1) MECHANICAL GAS VALVE 10 AIR CYLINDER IN TO AIR CYLINDER IN "ANSUL AUTOMAN ANSUL AUTOMAN" RELEASE NO. 1 RELEASE NO. 2 NOTICE IE ROPE DO NOT ACTUATE THE MECHANICAL GAS VALVE. Each Mechanical Gas Valve System must have gas valve cocked and air cylinder rod extended "UP" to its maximum extension before completing next step. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17 7-1-09 REV. 4 INSTALLING MECHANICAL GAS VALVE (Continued) r ONE (1) AIR CYLINDER —TWO (2) MECHANICAL GAS VALVES 7 TO AIR CYLINDER IN tfi- MINIMUM OF 6 IN. ANSUL AUTOMAN" (152 mm) RELEASE TWO OVAL SLEEVES, RT NO. 4596 MINIMUM OF 6 IN.j_ .__ NO ELBOWS ALLOWED (152 mm) WHERE TWO WIRE ROPES ARE PRESENT SPLICED WIRE ROPE _______ IN B-? tf62?\ WIRE CONTUOUS ROPE PULLEY TEE, PART NO. 427929 ONLY NOTE: EITHER BOTH MUST BE GAS VALVES OR BOTH MUST BE PULL STATIONS. MIXING IS NOT ALLOWED. FIGURE 45 008394 NOTICE When connecting two (2) mechanical gas valves to one (1) air cylinder, make certain both gas valves properly operate (close) when the air cylinder rod is in the down (operated) position. INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT Flexible conduit allows for quicker installations and the conve- nience of being able to route the cable over, under and around obstacles. Flexible conduit can be used as a substitute for standard EMT conduit or can be used with EMT conduit. NOTICE Flexible conduit can be used only with NEW remote pull station, Part No. 434618, and mechanical gas valve installations. Flexible conduit CAN NOT be used in detection systems. These instructions address the components and installation of both the pull station, Part No. 434618, and the flexible conduit. Design Requirements Flexible conduit cannot be utilized in detection systems. Flexible conduit inserts, Part No. 434347, can ONLY be used with the flexible conduit system. The maximum distance from an ANSUL AUTOMANe Release to a Pull Station, Part No. 434618, is 140 ft (42.7 m) with a maximum of 3600 (for example, 3-90° and 2-450 bends, 2-900 and 4-450 bends, etc.) bends in the flexible conduit, one pulley tee (refer to pages 5-17.9 through 5-17.11 for detailed splicing instructions), two splices, and 15 pulley elbows. Note: When installing flexible conduit, make sure to feed wire rope through conduit directly from the spool. DO NOT pre-cut wire rope. Feeding pre-cut rope through flexible conduit will cause excessive kinks in the rope, making it difficult to install. The maximum distance from an ANSUL AUTOMAN Release to a mechanical gas valve is 75 ft (22.9 m) with a maximum of 4- 900 bends in the flexible conduit and 4 pulley elbows. Any portion of the flexible conduit system can be substituted with EMT conduit provided the proper connections are used to join the two types of conduit. All bends in the flexible conduit system must have a minimum bend diameter of 6 in. (15 cm). When the flexible conduit is used to make 900 bends between an ANSUL AUTOMAN release and a mechanical gas valve, the bends must start at the gas valve. No pulley elbows can be used between the bends. If more than 3600 of bends are needed, then pulley elbows can be used. When the flexible conduit is used to make 900 bends between an ANSUL AUTOMAN release and a pull station, the bends must start at the ANSUL AUTOMAN release. No pulley elbows can be used between the bends. If more than 3600 of bends are needed, then pulley elbows can be used. When not utilizing a conduit offset, Part No. 79825, 2-450 bends in the flexible conduit are allowed between the strain relief fitting on top of the ANSUL AUTOMAN release, and the location where the flexible conduit is supported. When installing flexible conduit, conduit should be secured at intervals not to exceed 5 ft (1.5 m) and before and after each bend. Flexible conduit CANNOT slide in the clamp(s) used for mounting. Make certain mounting clamp(s) do not pinch the conduit. The following style clamp ('P' clip), Part No. 436150, is a suitable type for use on flexible conduit. E1101711ric 008141 TABLE 1 Mechanical Manual Pull Gas Valve Detection 90° Cable Bends 4 4 N/A Bend Diameter - in. (cm) 6(15.2) 6(15.2) N/A Mechanical Corner Pulley 15 4 N/A Conduit Secured Max. ft (m) 5(1.5) 5(1.5) N/A Conduit Max. Length it (m) 140 (42.7) 75 (22.9) N/A Conduit Offset or 2-450 Bends 1 0 N/A (Only between the strain relief fitting and support location Pulley Tees 1 0 N/A Splices 2 0 N/A SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.1 REV.0 7-1-09 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Installation Instructions Note: Do not add any type of lubricants inside or on the flexible conduit. Make certain stainless steel wire rope is clean and debris- free. The flexible conduit should be routed along the same path that EMT conduit would normally be run. Stainless steel wire rope should be routed through the flexible conduit as it is in EMT conduit. Flexible conduit must not be located within 6 in. (15 cm) of the hood or in areas exceeding 130 °F (54 °C). Also, do not route flexible conduit in areas where conduit can be crushed, pinched, or broken. Flexible conduit can be used to connect an ANSUL AUTOMAN Release to a remote pull station, Part No. 434618, or mechanical gas valves. Before starting the system installation, take a few minutes to plan the layout of the system. This will minimize the amount of compo- nents needed to complete the installation. Once the path of the flexible conduit has been determined, verify that the layout does not exceed the design requirements. Connecting the Flexible Conduit to the ANSUL AUTOMAN Release, Electrical Junction Box, or MECHANICAL Gas Valve 1. Layout the flexible conduit and secure it in place. Note: If inner liner is crimped, turn a drywall screw into the end to open it. See Figure 46. FIGURE 46 Qo195 Starting at the ANSUL AUTOMAN Release, connect the conduit connector using the supplied nut. Use only ANSUL conduit fittings, Part No. 55813. See Figure 47. FIGURE 47 007988 Unscrew the nut from the EMT conduit connector and remove the compression ring. Discard ring. See Figure 48. FIGURE 48 007987 Thread the stainless steel wire rope through the EMT conduit connector and flexible conduit insert. Make certain thread in flexible conduit insert is facing out toward end of connector. See Figure 49. FIGURE 49 offim FIGURE 55 001994 FIGURE 52 007991 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.2 7-1-09 REV. 0 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Connecting the Flexible Conduit to the ANSUL AUTOMAN Release, Electrical Junction Box, or Mechanical Gas Valve (Continued) Tighten the nut to the connector body, locking the flexible conduit insert in place. See Figure 50. FIGURE 50 OO79 Loosen the nut on the strain relief and thread the wire rope through a strain relief. See Figure 51. FIGURE 51 197990 Tighten the body of the strain relief to the conduit connector. Thread the wire rope through the flexible conduit. See Figure 53. (If a splice is required in the flexible conduit, proceed to "Splicing Installation Instructions." FIGURE 53 OO72 Slide the flexible conduit into the strain relief until it is approx- imately 1/16 in. (2 mm) from the bottom of the flexible conduit insert. See Figure 54. FIGURE 54 197999 Tighten the strain relief nut onto the strain relief. See Figure 55. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.3 REV. 0 7-1-09 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Connecting Flexible Conduit to Pulley Elbows, Pulley Tees, or Union Fittings Unscrew the nut from pulley elbow, pulley tee, or EMT conduit connector and remove the compression ring. Discard ring. See Figure 56. FIGURE 56 CUM Thread the stainless steel wire rope through the EMT conduit connector and flexible conduit insert. Make certain thread in flexible conduit insert is facing out toward end of connector. See Figure 57. FIGURE 57 Tighten the nut to the connector conduit body, locking the flex- ible conduit insert in place. See Figure 58. FLEXIBLE CONDUrr INSERt LOCKED 4 PLACE FIGURE 58 007997 Loosen the nut on the strain relief and thread the wire rope through the strain relief. See Figure 59. FIGURE 59 7998 Tighten the body of the strain relief to the conduit connector. See Figure 60. FIGURE 60 Push the wire race into the flexible conduit. See Finure Al FIGURE 61 OOco SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.4 7-1-09 REV. 0 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Connecting Flexible Conduit to Pulley Elbows, Pulley Tees, or Union Fittings (Continued) Slide the flexible conduit into the strain relief until it is approx- imately 1/16 in. (2 mm) from the bottom of the flexible conduit insert. See Figure 62. FIGURE 62 Oo81 Tighten the strain relief nut onto the strain relief. See Figure 63. FIGURE 63 82 Complete the same procedures on the other end of the conduit fitting as described in Steps 1 through Step 8 above. Assembling the Block Note: For installations that do not require the tee block, refer to page 5-17.12 for instructions. 1. The flexible conduit and wire rope should be connected to the electrical box as described in "Connecting the Flexible Conduit to the ANSUL AUTOMAN Release, Electrical Box, or Mechanical Gas Valve." See Figure 64. Note: For 1 1/2 in. (3.8 cm) deep electrical box, the bearing should be installed in the block's shallow box location. For 2 1/8 in. (5.4 cm) deep electrical box, the bearing should be installed in the block's deep box location. FIGURE 64 Thread the wire rope through the small end of the block into the bearing area to be used. See Figure 65. FIGURE 65 Pull slack, make a loop and insert the rope through the larger opening in the bearing area. See Figure 66. PUSH WIRE THROUGH ROPE LARGE CPENING FIGURE 66 omm FIGURE 69 own FIGURE 72 olI SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.5 REV.0 7-1-09 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Assembling the Block (Continued) 4. Pull wire rope out of the large end of the block. See Figure 67. FIGURE 67 omm Place the bearing against the wire rope. Make certain wire rope is in the bearing groove. See Figure 68. rpnnkip BEARING FIGURE 68 Align the bearing against the wire rope so that the bearing center and the hole in the block line up. See Figure 69. Insert the supplied bolt into the bearing and tighten securely. Take care not to strip the thread. See Figure 70. FIGURE 70 Oo6O Connecting the Block and the Faceplate The block can be inserted into the faceplate at 900 intervals. See Figure 71. FIGURE 71 oIo Thread the wire rope through the faceplate. Insert the block by depressing the tabs and pushing the block into the faceplate until it snaps in place. See Figure 72. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.6 7-1-09 REV. 0 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Connecting the Block and the Faceplate (Continued) 3. Place the faceplate over the top of the electrical box and insert the two screws to secure the faceplate. See Figure 73. FIGURE 73 008012 Insert the break rod into the two holes toward the top of the pull knob. See Figure 76. FIGURE 76 OI5 Pull the excess slack back to the ANSUL AUTOMAN Release. This will pull the pull knob assembly in place. See Figure 77. 5. Thread the wire rope through stop sleeve and leave approxi- mately 1/4-3/8 in. extended past sleeve. Crimp the stop sleeve twice using Crimping tool, National Telephone Supply Co. Nicopress Sleeve Tool (Stock No. 51-C-887). Verify the stop sleeve is secure on the wire rope. See Figure 75. Hold the pull knob assembly against the faceplate. Rotate the pull knob assembly counterclockwise until the break rod and pull knob snap in place. See Figure 78. Note: Take care in snapping in the ends of the break rod into the pull station side shields while rotating the entire assembly. 4. Thread the wire rope through the pull knob. See Figure 74. FIGURE 74 OOOI3 FIGURE 75 008014 FIGURE 78 017 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.7 REV. 0 7-1-09 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Connecting the Block and the Faceplate (Continued) 9. Snap the pull tab onto the pull knob so it is legible. See Figure 79. FIGURE 79 OI8 Refer to R-102 or PIRANHA installation manual to complete system installation. Test Remote Manual Pull Station and Mechanical Gas Valves in accordance with the "Testing and Placing in Service" Testing Manual Pull Station and Testing Mechanical Gas Valves section of this manual. Installing Flexible Conduit Through a Conduit Offset Starting at the ANSULAUTOMAN Release, connect the conduit connector using the supplied nut. Use only ANSUL conduit fittings, Part No. 55813. See Figure 80. FIGURE 80 007986 Install Conduit Offset, Part No. 79825, into conduit connector and tighten nut. See Figure 81. FIGURE 81 086009 Install compression union to opposite end of conduit offset. Tighten securely. See Figure 82. FIGURE 82 000098 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.8 7-1-09 REV. 0 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Installing Flexible Conduit Through a Conduit Offset (Continued) Install the conduit required to get above the ceiling. See Figure 83. FIGURE 83 008041 Install compression union to top of conduit riser. See Figure 84. FIGURE 84 O42 Remove union nut and ring. Discard ring. Do not reinstall nut at this time. See Figure 85. Remove strain relief nut and install strain relief body into compression union. See Figure 86. FIGURE 86 Install union nut over strain relief body and tighten nut. See Figure 87. -._ FIGURE 87 o45 Install strain relief nut onto strain relief body. Do not tighten nut at this time. See Figure 88. FIGURE 88 FIGURE 85 omw FIGURE 89 008047 Tighten nut on strain relief on top of conduit riser. See Figure 90. FIGURE 90 Complete the remainder of the flexible conduit and wire rope installation to the pull station or the gas valve. FIGURE 91 008061 Install strain relief nut, strain relief, compression union nut, flexible conduit insert and compression union over the flexible conduit with wire rope installed. See Figure 92. FIGURE 92 008049 Tighten compression union nut onto union body, locking flexi- ble conduit insert in place. See Figure 93. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.9 REV. 0 7-1-09 INSTALLATION OF REMOTE MANUAL PULL STATION OR Flexible Conduit Splicing (Allowed on Pull Station MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT Installations Only) (Continued) Note: Wire rope cannot be spliced together, only the flexible Installing Flexible Conduit Through a Conduit Offset conduit. (Continued) Flexible conduit can be spliced together using EMT compression 10. Push flexible conduit completely through conduit offset, fitting union, Part No. 79827. Flexible conduit should stop flush or i-I-- 1/2 in. (1.3 cm) from 1. Remove rings from both ends of compression union. See bottom conduit fitting in ANSUL AUTOMAN Release. See Figure 91. Figure 89 .... .... FIGURE 93 050 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.10 7-1-09 REV. 0 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Flexible Conduit Splicing (Allowed on Pull Station Installations Only) (Continued) Install strain relief body into compression union and tighten. See Figure 94. FIGURE 94 006051 Push flexible conduit into strain relief until it is approximately 1/16 in. (2 mm) from the bottom of the flexible conduit insert, then tighten strain relief nut onto strain relief body. See Figure 95. Install strain relief nut, strain relief, and compression union nut on remaining section of flexible conduit and install flexible conduit insert on wire rope. See Figure 97. r ------ --- _ '°!mb f . FIGURE 97 XSOM Push wire rope completely through remaining section of flexi- ble conduit. See Figure 98. _ .................... 1 FIGURE 98 55 lighten compression union nut onto union body, securing flex- ible conduit insert in place. See Figure 99. _ : FIGURE 99 006056 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.11 REV. 0 7-1-09 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Flexible Conduit Splicing (Allowed on Pull Station Installations Only) (Continued) Tighten strain relief into compression union. See Figure 100. FIGURE 100 057 Push flexible conduit into strain relief until it is approximately 1/16 in. (2 mm) from the bottom of the flexible conduit insert, then tighten strain relief nut onto strain relief body. See Figure 101. FIGURE 101 000058 Complete the remainder of the flexible conduit and wire rope installation to the pull station or the gas valve. Component Removal Instructions Removal of Block Using thumbs on the clips on each side of the block, press firmly in the direction of the center of the block, at the same time press- ing in a slightly downward direction. As the clips on the side of the block release from the pull station cover, the block will release and be free to be removed from the backside of the cover. See Figure 102. FIGURE 102 007884 Removal of Pull Knob Insert a small screwdriver into slot at bottom of pull knob. Push slightly on the screwdriver and turn pull knob clockwise, then pull knob can be removed without breaking the glass rod. See Figure 103. FIGURE 103 008059 Removal of Pull Cap Using a small screwdriver or other blunt object, push on the back- side of the pull cap. This will free the cap from the pull knob. See Figure 104. FIGURE 104 000088 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-17.12 7-1-09 REV. 0 INSTALLATION OF REMOTE MANUAL PULL STATION OR MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT (Continued) Pull Station Installation without Pulley Block Assembly Note 1: When using this installation option, the distance from the back of the faceplate and the connection to the 1/2 in. EMT conduit compression fitting must not exceed 6 in. (15.2 cm). Note 2: To provide for a straight run of wire rope from the pull station, an octagonal junction box with a center knockout in the back of the junction box will be needed. See Figure 104a. If a pre- fabricated box or enclosure is to be used, it must allow the pull station face plate to be firmly attached to the box or enclosure, with a hole or knockout suitable for a 1/2 in. EMT threaded conduit compression connector to be installed directly in line with the center of the pull station pull knob. FIGURE 104a 008415 Attach a 1/2 in. EMT conduit compression fitting (Part No. 55813) to the back center knock out of the junction box. If something other than a junction box is to be utilized, a method of securing the flexible conduit or EMT conduit directly in line with the center of the pull station pull knob must be used. This will ensure that in the event of manual operation the wire rope, exiting the back of the pull station faceplate, will be pulled straight out without binding or resulting in undue additional pull force due to friction loss. Remove the block assembly from the pull station face plate. Thread the wire rope from either flexible conduit or 1/2 in. EMT conduit attached to the back of the junction box or fabricated enclosure through the back side of the pull station faceplate and through the pull knob. Thread the wire rope through the stop sleeve (Part No. 26317) and leave approximately 1/4 in. to 3/8 in. (6 mm to 10 mm) extending past the sleeve. Crimp the stop sleeve twice using the crimping tool National Telephone Supply Co. Nicopress Sleeve Toll (Stock No, 51-C- 887). Verify the sleeve is secure on the wire rope. 001092 CORRECT WA WRENCH APP BEING INSERl EXCESS STR AY: PPLIED AT T STRAINS N. FIGURE 105 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-18 REV. 6 7-1-09 INSTALLING ELECTRICAL GAS VALVES NOTICE Electric gas valves are designed for indoor installation only. The following instructions and schematics illustrate methods of procedures for installing 110 VAC Electric Gas Shut-off Valves. 1. Make certain that regulated release assembly enclosure cover is detached and lock bar is properly inserted within the regu- lated release mechanism. CORRECT WAY: VISE GRIP ENDS NEXT TO PIPE BEING INSERTED. PREVENTS EXCESS STRAIN ON VALVE BODY. NOTICE Failure to follow these instructions may lead to system actuation. Verify that cartridge has been removed from regulated release assembly and that the regulated release mechanism is in the cocked position. If regulated release mechanism does not have lock bar inserted or cartridge removed, refer to the "Semi-Annual Maintenance," Page 8-1, in "Maintenance Examination" section and complete Steps 2 and 3 before completing the following installation steps. To rduce the risk of explosion due to leaking gas, make certain that the gas line is turned off before connecting the gas valve. Gas valve installation shall be performed by qualified individuals in accordance with local jurisdiction requirements. Install each electric gas valve to its selected location in gas line so that it ensures safe shut-off to all predetermined appli- ances being protected upon actuation of the system. Refer to manufacturer's instructions (if provided). See Figure 105. Use 'new pipe properly reamed and clean of metal chips. Instill valve so that the actuator is above the horizontal pipe line with no more than a five degree (50) lean either way. Make certain gas flow is in the same direction as arrow shoin on gas valve. If strainer is utilized, attach strainer ahead of gas valve. If ncessary, install drip leg in gas line in accordance with authority having jurisdiction. Install and secure 1/2 in. conduit from each electric gas valve to manual reset relay enclosure. Tag and connect electrical wiring to each electric gas valve. Then, feed wire through conduit to manual reset relay. Tape or place a wire nut on any unused wire leads in accordance with authority having jurisdiction. Refer to Figures at the end of this section for typical wiring diagrams. _I1-1IIIN [.] Before working on any electrical wiring, make certain main power has been disconnected. Failure to disconnect main power could cause personal injury or death if contact is made with energized wires. I1JiIl[s] All electrical wiring/connections shall be performed by qualified individuals in accordance with local jurisdiction requirements. Connect electrical wiring to manual reset relay along with any contactor, or contractor supplied devices needed. Refer to manufacturer's instructions and proper figure listed for assis- tance. Tape or place a wire nut on any unused wire leads in accor- dance with authority having jurisdiction. Install and secure 1/2 in. conduit from the regulated release assembly enclosure to manual reset relay enclosure. If snap-action switches have not been attached, go to "Electric Switch" section and install them at this time by completing Steps 3 through 8. Tag and connect electrical wiring to each electric (snap-action) switch. Then, feed wire through conduit to manual reset relay. Connect wiring from each electric (snap-action) switch to manual reset relay terminals. Refer to manufacturer's instruc- tions (if provided) and proper figure for assistance. Tape or place a wire nut on any unused wire leads in accor- dance with authority having jurisdiction. Properly return electrical power to the system. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-19 7-1-09 REV. 5 INSTALLING ELECTRICAL SWITCHES The procedure for field installing an electric (snap-action) switch is as follows: Unused wire leads will become "hot" when the system is oper- ated. Failure to adequately cover exposed wire end(s) will cause electric shock if touched. I1UIl[I] Before working on any electrical wiring, make certain main power has been disconnected. Failure to disconnect main power could cause personal injury or death if contact is made with energized wires. NOTICE Except for the Alarm Initiating Switch, all electri- cal wiring connections are to be made outside the ANSUL AUTOMAN Release enclosure in suitable enclosures in accordance with local jurisdiction requirements. 1. Make certain that regulated release assembly enclosure cover is detached with lock bar properly inserted within the regu- lated release mechanism. NOTICE Failure to follow these instructions may lead to system actuation. 2. Verify that cartridge has been removed from regulated release assembly and that the regulated release mechanism is in the cocked position. If regulated release mechanism does not have lock bar inserted or cartridge removed, refer to the "Semi-Annual Maintenance," Page 8-1, in "Maintenance Examination" section, and complete Steps 2 and 3 before completing the following installation steps. If regulated release mechanism has a factory installed sole- noid, it will also have a factory installed switch. 3. Press each wire assembly onto the 3-terminals located on the switch(s). Be sure that the connector is pressed tight against the switch. See Figure 106. BLACK SNAP-ACTION SWITCH COMMON RED f- J BLACK BROWN 10 N.O. - N.C.: PRESS CONNECTOR TIGHTLY AGAINST SWITCH NOTE: SWITCH SHOWN IN NORMAL POSITION ACTUATING ARM FIGURE 106 001621 4. Install switch(es) to the mounting bracket using provided fasteners and tighten securely. 5. If more than one switch is being installed, it is necessary to attach the trip lever extension stud to the trip lever. See Figure 107. Using the provided fasteners, securely install the exten- sion stud. 6. Raise switch actuating arm squarely over the cam surface of the trip lever. This will allow the trip lever, when actuated, to force the actuating arm "UP," thus reversing the normal condi- tion of the switch. See Figure 107. For multiple switch installations, make certain switch actuating arms are positioned on trip lever extension stud. Before proceeding with Step 7, test electric (snap-action) switches: Remove lock bar. With the ANSUL AUTOMAN in the cocked or ready position, press the lever of each switch up. If the switch is working properly there should be an audible click. With the ANSUL AUTOMAN in the fired position, press the lever of each switch up, there should be no audible click. When installing multiple switches, make certain all switches transfer when the release operates. If they do not, readjust their position. If an audible click is heard in the fired position several adjustments can be made. The trip lever extension pin can be rotated so the peak of one of the hex points is pointed up against the switch levers. Tighten it in that position. If this doesn't resolve the problem, loosen the screws holding the switches, apply a small counterclockwise torque on the switches and retighten the screws. If necessary, a final adjustment can be made by removing the snap action switch and bending the lever slightly. After adjustments repeat steps a and b. Then, recock ANSUL AUTOMAN and install lock bar. ACTUATING ARM Go G! 1Li rMOUNTINGR TRIP LEVER EXTENSION 001624 FIGURE 107 Z~! CAUTION All electrical wiring/connections shall be performed by qualified individuals in accordance with local jurisdiction requirements. 7. The switch may now be connected to compatible components that are predetermined to shut off or turn on. Refer to compo- nent manufacturer's instructions for proper wiring connections to compatible components. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-20 REV. 3 7-1-09 INSTALLING ELECTRICAL SWITCHES (Continued) NOTICE Except for the Alarm Initiating Switch, all electri- cal wiring connections are to be made outside the ANSUL AUTOMAN Release enclosure in suitable enclosures in accordance with local jurisdiction requirements. 8. Tape or place a wire nut on any unused wire leads in accor- dance with authority having jurisdiction. FIRE ALARM CONTROL PANEL ALARM CIRCUIT END-OF-LINE RESISTOR OR NEXT DEVICE NOTICE Do not connect power source to any relay, contactor, or contractor supplied devices until all other electrical connections are made. Refer to proper section or manufacturer supplied instruc- tions for recommended installation procedures for these devices. 9. Turn off power source and connect power line to any relay, contactor, or contractor supplied devices where used. INSTALLING ALARM INITIATING SWITCH The Alarm Initiating Switch Kit, Part No. 428311, consists of: Alarm Initiating Switch Assembly - Rated 50 mA 28VDC Spacer Mounting Screw with Nut (2) Extension Pin Extension Pin Nut Instruction Sheet The Alarm Initiating Switch is mounted in the ANSUL AUTOMAN Release on the same mounting plate where the current snap- action switches are mounted. If the alarm initiating switch is used alone, the enclosed extension pin and pin nut are not needed. When mounting the switch, the spacer must be installed first, between the ANSUL AUTOMAN mounting plate (or existing switches) and the alarm initiating switch. See NFPA 72, 'National Fire Alarm Code," Initiating Devices section, for the correct method of wiring connection to the fire alarm panel. After the switch is properly mounted, follow the steps listed in the installation section of the Design, Installation, Recharge, and Maintenance Manual for correct positioning of the switch lever on the ANSUL AUTOMAN cam surface. TOWARD SPACER WHEN SPACER AND AUTOMAN / SWITCH ARE PROPERLY / MOUNTED, This DIVIDER ----1 MUST BE BETWEEN THE , N.O. AND N.C. TERMINALS GOM N.O. N.C. 0 ALARM INITIATING SWITCH FIGURE 108 004990 009001 ALARM INITIATING SWITCH (i INCORRECT ,3 llL-4I liii LIII IN OUT IN OUT CORRECT - SEPARATE INCOMING AND OUTGOING CONDUCTORS FIGURE 109 Note: With the exception of the Alarm Initiating Switch, all electri- cal connections must be made in an approved electrical box which also meets NEC article 314.40 (0) Grounding Provisions. SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-20.1 7-1-09 REV. 0 ELECTRICAL SWITCH REQUIREMENTS Electric (110 VAC/60 Hz) Gas Shut-off Valve INSTALLATION OVERVIEW POWER SOURCE 0 0 MANUAL RESET RELAY ELECTRIC SNAP-ACTION SWITCH ELECTRIC GAS VALVE \ JUNCTION BOXES (NOT SUPPLIED BY ANSUL) WIRING SCHEMATIC WIRING SCHEMATIC - RELAY PART NO. 426151 ANSUL SNAP-ACTION SWITCH (SWITCH CONTACTS SHOWN WITH ANSUL AUTOMAN IN THE COCKED POSITION) I-------------------I I RESET POWER I INDICATOR GNO IA M B SCREW: Li RELAY COIL MANUAL RESET RELAY I (PART NO. 426151) ELECTRIC RATING 1/3 HP, 10 Amp, 120 VAC 1/2 HP, 10 Amp, 240 VAC BLACK RED BROWN L2NEUTRAL Li HOT 110 VAC/6OHZ FIGURE 110 GAS VALVE SEE NOTE 3 NOTE: 13 Amp, 28 VDC DENOTES FIELD INSTALLATION. -----DENOTES FACTORY INSTALLATION. CONTRACTORS: UL LISTED ENCLOSED INDUSTRIAL CONTROL EQUIPMENT OR MAGNETIC SWITCH HAVING A RATING MATCHING THAT OF THE COOKING APPLIANCE COIL, 110V/60HZ. DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. BLACK WIRE TO BE USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC. SECTION V. - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-20.2 REV.0 7-1-09 ELECTRICAL SWITCH REQUIREMENTS (Continued) Electric (110 VAC/60 Hz) Application with Customer Supplied Contactor and Heating Element Load INSTALLATION OVERVIEW POWER SOURCE -- ELECTRIC ;:~SNAP I ITCH -ACTION JUNCTION BOX I (NOT SUPPLIED BY ANSUL) 0 0 POWER ON-OFF SWITCH (CUSTOMER SUPPLIED) MANUAL RESET RELAY CONTACTOR (CUSTOMER SUPPLIED) 060276 WIRING SCHEMATIC WIRING SCHEMATIC - RELAY PART NO. 426151 ANSUL SNAP-ACTION SWITCH (SWITCH CONTACTS SHOWN WITH ANSUL AUTOMAN IN THE COCKED POSITION) - BLACK REC BROWN RESET POWER I rRED] INDICATOR GND B SCREWI Af1 J :rLi RELAY COIL 6 I 9 I 3— C, I 7 I 1 va I I I I L2 NEUTRAL 110 VAC/6OHZ Li HOT jCONTACTOR (CUSTOMER SUPPLIED) I (PART NO. 4151) I (CUSTOMER SUPPLIED) L_ I MANUAL RESET RELAY i L r -, POWER ON-OFF SWITCH _1 ELECTRIC RATING 1/2 HP, 10 Amp. 240 VAC EMENT LOAD ____ TO POWER SUPPLY 1/3 HP, 10 Amp, 120 VAC TO HEATING ____ i3Amp,28VDC 220V/440V 002400 NOTE: ____________ DENOTES FIELD INSTALLATION. -----DENOTES FACTORY INSTALLATION. GAS VALVES: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND TEMPERATURE RATING, I 10V160 Hr OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710, AND 17643. DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. BLACK WIRE TO BE USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC. FIGURE 111 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-20.3 7-1-09 REV. 0 ELECTRICAL SWITCH REQUIREMENTS (Continued) Electric (110 VAC/60 Hz) Application with Customer Supplied Contactor and Heating Element Load, and Power Supply Switch INSTALLATION OVERVIEW POWER SOURCE ELECTRIC SNAP-ACTION SWITCH 01 o MANUAL RESET RELAY SWITCH OR THERMOSTAT (CUSTOMER SUPPLIED) JUNCTION BOX (NOT SUPPLIED BY ANSUL) CONTACTOR (CUSTOMER SUPPLIED) WIRING SCHEMATIC WIRING SCHEMATIC - RELAY PART NO. 426151 BLACK RED ANSUL SNAP-ACTION SWITCH BROWN (SWITCH CONTACTS SHOWN WITH ANSUL AUTOMAN IN THE COCKED POSITION) - - RESET POWER INDICATOR Ii REDJ GND I AM B Li RELAY COIL 001 7 701 MANUAL RESET RELAY I (PART NO. 426151) ELECTRIC RATING 1/3 HP, 10 Amp, 120 VAC 1/2 HP, 10 Amp, 240 VAC 13 Amp, 28 VDC 12 NEUTRAL 110 VACiSOHZ Li HOT CONTACTOR SWITCH OR THERMOSTAT (CUSTOMER SUPPLIED) (CUSTOMER SUPPLIED) _______ TO POWER SUPPLY TO HEATING _______ ELEMENT LOAD ________ i_ 220 V/440V 002461 NOTE: -DENOTES FIELD INSTALLATION. -----DENOTES FACTORY INSTALLATION. CONTRACTORS: UL LISTED ENCLOSED INDUSTRIAL CONTROL EQUIPMENT OR MAGNETIC SWITCH HAVING A RATING MATCHING THAT OF THE COOKING APPLIANCE COIL, 11OV/60HZ' DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. BLACK WIRE TO BE USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC. FIGURE 112 SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-20.4 REV. 0 7-1-09 NOTES: SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-21 7-1-09 REV. 4 WIRING 24 VDC REGULATED RELEASE ASSEMBLY (ULC APPROVED ONLY) Refer to the following notes and wiring diagram for instruction on wiring the 24 VDC regulated release assembly. Notes: To be connected to a nominal 12 VDC or 24 VDC releasing circuit. Input power: 450 mA at 12 VDC or 750 mA at 24 VDC. Solenoid on time: Approximately 50 milliseconds. Polarization: Observe polarity when connected to a release circuit; Terminal 4 positive, Terminal 8 negative. All interconnecting wiring must be 18 AWG minimum. S1 contact rating: 15A, 1/3 HP, 125 or 250 VAC resistive; 1/2A, 125 VDC; 1/4A, 250 VDC; 5A, 120 VAC inductive. SOL coil resistance: 28 OHMS +1- 10% at 77 °F (25 °C). Install the in-line supervisory device SD across terminals No. 4 and No. 5. Refer to the releasing panel installation instruc- tions for supervisory device requirements. If an in-line super- visory device is not required, install jumper J2 across terminals No.4 and No. 5. THESE SWITCH CONTACTS TRANSFER UPON ACTUATION OF RELEASE HIGH ACCESSORY POWER SOURCE ** LOW (+) (+) aOR UL LISTED qSDX SUPERVISED RELEASING CONTROL UNIT IN-LINE SUPERVISORY DEVICE (—) VOLTAGE TRANSIENT I SUPPRESSOR AUXILIARY ALARMING DEVICES, SEE S RATINGS FUEL SHUT-OFF VALVE, BLOWER MOTOR, DOOR CLOSER, ETC., SEE S RATINGS. FIGURE 113 OO2OO SECTION V - INSTALLATION INSTRUCTIONS UL EX3470 ULC EX3470 Page 5-22 REV.4 7-1-09 NOTES: SECTION VI - TESTING AND PLACING IN SERVICE UL EX3470 ULC EX3470 Page 6-1 7-1-09 REV. 3 After the system has been completely installed, and BEFORE INSTALLING THE CARTRIDGE, the system must be tested at the regulated release assembly. The testing information listed in this section deals with the limitations and parameters of this pre-engi- neered system. Those individuals responsible for the testing of the R-102 system must be trained and hold a current ANSUL certifi- cate in an R-102 training program. Note: ANSUL AUTOMAN Release must be in the cocked position before testing manual pull station. Make certain to remove lock bar before performing pull station testing. TESTING MANUAL PULL STATION To test each remote manual pull station, complete the following steps: With the expellant gas cartridge removed, remove lock bar from regulated release assembly cable lever. On pull station, remove break rod from the pull station by inserting a small screwdriver into slot at bottom of pull knob to facilitate turning the pull knob. Push slightly on the screwdriver and turn pull knob clockwise, then the pull knob can be removed without breaking the glass rod. NOTICE Take care in removing the break rod from the pull station side shields while rotating the break rod/pull knob assembly. Pull ring handle on pull station. If the regulated release assembly is tripped easily, the remote manual pull station is properly installed. If the regulated release assembly does not trip, remove pulley tee (if provided) and each pulley elbow cover to make certain wire rope is resting on the pulley sheave. If this does not correct the problem, there is too much slack in the line and it must be retightened. Recock regulated release assembly using cocking lever (Part No. 14995 or 435603) and reinstall lock bar (Part No. 14985). On pull station, insert the break rod into the two holes toward the top of the pull knob. Rotate the pull knob counterclockwise. NOTICE Take care in snapping in the ends of the break rod into the pull station side shields while rotat- ing the entire assembly. NOTICE If no other devices are being attached, proceed to Page 6-3, Step No. 1, and test the detection system. TESTING MECHANICAL GAS VALVES To test each mechanical gas shut-off valve complete the following steps: To reduce the risk of explosion due to leaking gas, before the gas line is turned on, make certain to extinguish any open flames and turn off all burners and any electrical or mechanical devices that are capable of igniting gas. Turn gas line on. Manually push each air cylinder rod to full "DOWN" position. The gas valve should close. If mechanical gas valve does not trip, remove each pulley elbow cover to make certain wire rope is resting on each pulley elbow sheave. If this does not correct the problem there may be too much slack in the line and it should be retightened. Test for gas leaks by painting connections with a soap solu- tion. Bubbles indicate a gas leak. Tighten connections where leaks appear and repeat test again to make certain no other gas leaks exist. If no gas leak is found, pull air cylinder rod to full "UP" position. Recock mechanical gas valve. Check burners for gaseous odor. IF GASEOUS ODOR EXISTS, MANUALLY PUSH THE AIR CYLINDER ROD TO THE FULL "DOWN" POSITION IMMEDIATELY. This will cause the mechanical gas valve to shut the gas line off. Open any doors and/or windows to clear the area of gaseous fumes, then correct the gas leak before proceeding any further. If no gaseous odor exists, pilot light may be ignited at this time. Reinstall side covers to gas valve housing. Make certain roll pin is positioned within both sides of the valve housing slot. Connect visual inspection seals (Part No. 197) on ANSUL type valves. See Figure 1. 'ECTION NO. 197) FIGURE 1 DOM Make certain the regulated release mechanism is cocked with lock bar in place. NOTICE If no other devices are being attached, proceed to Page 6-3, Step No. 1, and test the detection system. SECTION VI - TESTING AND PLACING IN SERVICE UL EX3470 ULC EX3470 Page 6-2 REV.3 7-1-09 TESTING ELECTRICAL GAS VALVES To test each Electric Gas Shut-off Valve complete the following steps: To reduce the risk of explosion due to leaking gas, before the gas line is turned on, make certain to extinguish any open flames and turn off all burners and any electrical or mechanical devices that are capable of igniting gas. Turn gas line on. Make certain electric (snap-action) switch is properly wired. Make certain all other devices connected to the manual reset relay are properly wired. Refer to typical wiring diagrams in Figures 110, 111, 112, and 113 in "Installation" section. Test for gas leaks by painting connections with a soap solu- tion. Bubbles indicate a gas leak. Tighten connections where leaks appear. Repeat test again to make certain no other gas leaks exist. If no gas leaks are found, turn power source on and depress the reset button on the manual reset relay (RED LIGHT ON) to energize (OPEN) electric gas valve. Remove lock bar from regulated release mechanism. Manually actuate the system by operating the remote pull station. (It may be necessary to remove the glass break rod prior to operating pull station.) Manual reset relay (RED LIGHT OUT) will de-energize (CLOSE) the electric gas valve, thus shutting off the gas line. If this does not happen, turn power source oft. Then re-examine all wiring connections for proper hookup. Refer to Figures 110, 111, 112, and 113 in "Installation" section for typical wiring diagrams. If test is successful, recock regulated release mechanism using cocking lever (Part No. 14995 or 435603) and reinstall lock bar (Part No. 14985). Depress reset button on manual reset relay (RED LIGHT ON). Check burners for gaseous odor. IF GASEOUS ODOR EXISTS, TURN OFF POWER SOURCE IMMEDIATELY. This will cause the electric gas valve to shut the gas line off. Open any doors and/or windows to clear the area of gaseous fumes, then correct the gas leak before proceeding any further. If no gaseous odor exists, pilot light may be ignited at this time NOTICE If no other devices are being attached, proceed to Page 6-3, Step No. 1, and test the detection system. TESTING ELECTRIC SWITCH The procedure for testing a field installed Electric (Snap-Action) Switch is as follows: NOTICE If an electrical gas shut-off valve is attached to system, perform proper test procedure for the gas valve first, before completing the following steps. Turn power source on and if installed, depress reset button on manual reset relay (RED LIGHT ON). All electrical devices should be operating at this time. Remove lock bar. I S Do not install cartridge at this time or system may be actuated. Manually actuate the system by operating the remote pull station. It may be necessary to remove the glass break rod prior to operating pull station. (If installed, the manual reset relay will de-energize the electric gas valve, thus shutting off the gas line.) All electrically-operated devices predetermined to shut off or turn on should do so. If this does not occur, turn power source off and make sure all wiring is properly connected and retest. Refer to Figures 110, 111, 112, and 113 in "Installation" section for typical wiring diagrams. If test is successful, recock regulated release mechanism using cocking lever (Part No. 14995 or 435603) and reinstall lock bar (Part No. 14985). If a manual reset relay is installed, depress the reset button (RED LIGHT ON). It will also be necessary to re-light any pilot lights on the cooking appli- ances. NOTICE If no other devices are being attached, proceed to Page 6-3, Step No. 1, and test the detection system. Do not install cartridge at this time or system may be actuated. SECTION VI - TESTING AND PLACING IN SERVICE UL EX3470 ULC EX3470 Page 6-3 7-1-09 REV. 4 TESTING DETECTION SYSTEM 1. Test detection system by completing the following steps: Raise the regulated release mechanism tension lever to the "UP" position. Remove the fusible link from the terminal detector and install a test link (Part No. 15751). See Figure 2. 0 0 TEST LINK FIGURE 2 OO Locate detector linkage and center in each bracket. For "clip on" style linkage, locate linkage in bracket slightly toward termination end of detection run. For 'scissor" style linkage, locate linkage in bracket all the way toward termination end of detection run. Lower regulated release mechanism tension lever to "DOWN" position and remove lock bar. Using a wire cutter, cut the test link at the terminal detector to simulate automatic actuation. If system actuates successfully, go to Step 4. 2. If the regulated release mechanism does not actuate, check the following components and remedy any disorder as follows: Check the detector linkage for correct positioning. Check the wire rope for knotting or jamming. Check pulley elbows to see that wire rope is free and centered in pulley sheaves. If any evidence of pulley elbow deformation is found, replace the pulley elbow. Make certain that lock bar is removed. Make certain that regulated release mechanism is cocked. Make certain that tension lever is in 'DOWN" position. 3. Re-test the system by completing the following steps: Make certain regulated release is cocked and lock bar is inserted. Raise the regulated release mechanism tension lever to the "UP" position. Install a new test link (Part No. 15751) on the terminal detector. Lower the regulated release mechanism tension lever to the 'DOWN" position. Check for 1/4 in. (6.4 mm) minimum 3/8 in. (9.5 mm) maximum clearance between the trip hammer assembly and the cable lever assembly. Remove the lock bar. Using a wire cutter, cut the test link at the terminal detector to simulate automatic actuation. 4. Upon successful actuation of the system, complete the follow- ing steps: Raise tension lever to 'UP" position and install a properly- rated fusible link in the terminal detector. Cock regulated release mechanism using cocking lever (Part No. 14995 or 435603) and insert lock bar (Part No. 14985). Lower tension lever to 'DOWN" position. For 'scissor" style linkage, locate linkage in bracket all the way toward termination end of detection run. Make certain the 1/4 in. (6.4 mm) minimum to 3/8 in. (9.5 mm) maximum clearance was maintained between the base of the trip hammer assembly and the cable lever assembly. NOTICE Reset any electrical equipment that may have been affected by the system actuation. Remove shipping cap and weigh each cartridge. Replace if weight is 1/2 ounce (14.2 g), or more, below weight stamped on cartridge. Install cartridge into the regulated release mechanism receiver and each regulated actuator receiver. Hand tighten firmly. Remove the lock bar. Install cover on regulated release assembly and each regu- lated actuator assembly and secure with appropriate fasteners or visual inspection seal. Insert seal (Part No. 197) in each upper and lower cover hole, if applicable. If system is install in an OEM enclosure, attach enclosure cover and secure with appropriate hardware or procedure. UflIe] Before installing cover, make certain detection tension lever is secured in the "DOWN" position to enable auto- matic detection and operation of the ANSUL AUTOMAN Regulated Release. Record installation date on tag attached to unit and/or in a permanent file. SECTION VI - TESTING AND PLACING IN SERVICE UL EX3470 ULC EX3470 Page 6-4 REV.2 10-1-02 r NOTES: SECTION VII - RECHARGE AND RESETTING PROCEDURES UL EX3470 ULC EX3470 Page 7-1 7-1-98 REV. 1 The recharge information listed in this section deals with the limi- RECHARGE I tations and parameters of this pre-engineered system. Those mdi- NOTICE viduals responsible for the recharge of the R-102 system must be Determine the cause of system discharge and i trained and hold a current ANSUL certificate in an R-102 training correct immediately before performing system program. recharge. For continued fire protection, the R-102 restaurant fire sup- 1. Remove the enclosure cover from the ANSUL AUTOMAN pression system must be recharged immediately after use. regulated release assembly and each regulated actuator Recharge procedures for single, double, and multiple-tank sys- assembly. tems are as follows. CLEANUP PROCEDURES Although there is no unusual cleanup procedure of ANSULEX or ANSULEX Low pH agents, due to the alkaline nature of these agents, they should be cleaned from kitchen surfaces within 24 hours after system discharge. The reaction from the wet chemical agent on cooking grease or oil produces a foamy bi-product that can be wiped up with a cloth or sponge. The following procedures should be followed: Before attempting any cleanup, make certain that all fuel sources to the equipment to be cleaned have been shut off. Make certain that the exhaust hood and all appliance electrical controls have been de-energized to avoid any chance of elec- trical shock resulting from the cleaning process or from electri- cally conductive alkaline liquid agent and/or its residue. Make certain all surfaces to be cleaned have cooled down to room temperature. Do not use water to clean any appliances that contain hot grease or cooking oils. Doing so may result in violent steaming and/or spattering. From tank in regulated release enclosure: Disconnect the expellant gas hose from each tank adaptor assembly. From tank in mounting bracket or mounting enclosure: Disconnect expellant gas piping union at each tank adaptor inlet line(s). Disconnect distribution piping union at each tank adaptor out- let line(s). From tank in enclosure: Remove tank. From tank in bracket assembly: Loosen wingnut, disengage bracket band, and remove each tank. Remove each tank adaptor/tube assembly and complete the following: Remove 0-ring and inspect for damage. Clean and coat 0-ring with a good grade of extreme tem- perature grease and reinstall into adaptor groove. See Figure 1. Remove 1/4 in. vent plug. Clean and inspect for free movement and corrosion. Replace if necessary. Reinstall vent plug into adaptor body. The agent is non-toxic; however, food product and cooking grease/oil that has come in contact with the agent will no longer be suitable for human consumption and should be dis- carded. Sponge up as much of the agent as possible using sponges or clean rags. Dispose of these sponges or rags in a local san- itary land fill site in accordance to local authorities. Note: Wear rubber gloves during cleanup as sensitive skin may become irritated. If the ANSULEX agent or its residue comes in contact with skin or eyes, flush thoroughly with clean water. Using hot, soapy water and either a clean cloth or sponge, wipe away all foamy residue and thoroughly scrub all surfaces 6 that have come in contact with the agent. Note: Wear rubber gloves during cleanup as sensitive skin may become irritated. If the ANSULEX agent or its residue comes in contact with skin or eyes, flush thoroughly with clean water. After thoroughly cleaning all affected surfaces, adequately rinse and allow to completely dry before re-energizing the equipment. FIGURE i o3 CAUTION Do not flush pipe with only water or other non-approved material, as this could cause internal corrosion, leading to possible improper discharge. Piping system must be flushed to remove any wet chemical residue. To prepare the system for flushing: Pour the complete contents of one 32-oz. bottle of ANSUL Flushing Concentrate (Part No. 79656) into an empty R-102 agent tank. One complete bottle is used for either size tank, the 1.5 gallon or the 3.0 gallon. Fill the tank approximately half full with warm, clean water. Agitate the tank for a few seconds and then add more warm water to bring the fill level to within approximately 1 in. (2.5 cm) from the bottom of the fill opening. SECTION VII - RECHARGE AND RESETTING PROCEDURES UL EX3470 ULC EX3470 Page 7-2 REV.6 7-1-09 RECHARGE (Continued) c. Install adaptor/tube assembly and tighten. 7. To perform the flushing procedure, either secure heavy-duty plastic bags to each nozzle (See Figure 2) or remove each nozzle tip and strainer and attach plastic tubing. See Figure 3. If using plastic bags, secure bags and proceed to Step 9. If using plastic tubing, proceed to Step 8. VENT HOLES NOZZI FIrrIr HEAVY GAUGE PLASTIC BAG Using a 1 N nozzle tip and retainer, (Part No. 56930), slide a length of 1/2 in. (1.3 cm) plastic tubing over the rib on the nozzle tip and secure with a 1/2 in. (1.3 cm) adjustable hose clamp. See Figure 4. This nozzle tip will be connected to the nozzle body left installed in the distribution piping. In the pail cover, drill the number of holes required, large enough to insert 1/2 in. NPT fittings, with one additional hole that can be used for venting. Secure 1/2 in. compression fitting/threaded adaptors to the pail cover, using 1/2 in. conduit nuts. See Figure 4. IN NOZZLE TIP AND RETAINER RIB ON NOZZLE (PAIF RT NO. 56930) 1/2 IN. TUBING -... 1/2 IN. ADJUSTABLE HOSE CLAMP NOZZLE TIP AND RETAINER FIGURE 2 001739 '. 1/2 IN. COMPRESSION TUBING FITTING/THREADED INSERT-. /' ADAPTOR \ NOZZLE BODY HIGH i— PRESSURE PLASTIC TUBING 1/2 IN. NPT COMPRESSION FITTING/THREADED ADAPTOR FIGURE 3 001740 8. If using the plastic tubing option, utilize 1/2 in. (1.3 cm) 00 plastic tubing with wall thickness not to exceed 0.062 in. (1.6 mm), and make certain it can withstand the pressures of at least 90 psi (6.2 bar) expelled during the flushing and blow- down procedures. Also required is a container with some means of securing tub- ing to it such as a five-gallon plastic pail and cover that snaps onto the pail. To prepare the plastic tubing: a. Cut as many tubing lengths as required, making them long enough to reach the container from each nozzle outlet 1/2 IN. CONDUIT PAIL NUTS COVER FIGURE 4 000300 e. Attach the tubing ends to the compression fittings. Tubing inserts will be required. See Figure 4. I. Install nozzle/tubing ends to nozzle bodies in discharge piping. g. Make certain each length of tubing is fastened to the pail cover with the cover snapped securely to the pail. 9. Complete the following steps in the flushing procedure: Connect discharge piping and expellant gas line to agent tank adaptor. Cock ANSUL AUTOMAN Release Mechanism and insert lock bar. Refer to Components Section of this manual for detailed part numbers. Install LT-30-R Cartridge; hand tighten. Remove lock bar. If regulated actuators are included in the system, also install LT-30-R cartridges in them. Actuate system via pull station. Wash out all system nozzles and strainers in warm soapy water, rinse and return all nozzles and strainers to their appropriate locations in the discharge piping. Verify that all nozzle types are correct. Utilizing the Nozzle Aiming Device, Part No. 431992, ensure that all nozzles are correctly aimed at the appropriate location on the appli- ance. I. Remove empty tank. SECTION VII - RECHARGE AND RESETTING PROCEDURES UL EX3470 ULC EX3470 Page 7-3 7-1-09 REV. 5 RECHARGE (Continued) Fill each tank with 1.5 (5.8 L) or 3.0 (11.6 L) gallons of only ANSULEX Low pH Liquid Fire Suppressant. Note: Use a fun- nel with a screen to stop any foreign material from entering the tank. See Page 5-2.1, Figure 6, for detailed filling instructions. During filling, the agent temperature should be 60 OF to 80 OF (16 "C to 27 "C). DO NOT FILL WITH COLD AGENT. DO NOT OVERFILL Overfilling may result in agent entering gas hose and regulator potentially causing system malfunction. Replace bursting disc, Part No. 416974, in adaptor assembly. Make certain silver side of disc is away from tank. Replace adaptor/tube assembly and tighten into place. Return and secure each tank in regulated release assembly and mounting bracket/enclosure. Reconnect expellant gas and dis- tribution piping and/or as required. Raise tension lever to "UP" position. Cock regulated release mechanism using cocking lever (Part No. 14995 or 435603) and install lock bar (Part No. 14985). Remove empty cartridge from regulated release assembly and each regulated actuator assembly as required. AuilLs] Do not install replacement cartridge at this time or system may be actuated. Install properly-rated fusible links in all detectors except the terminal detector. NOTICE If actuation was caused by a fire situation, all fusible links must be replaced. Install test link (Part No. 15751) in terminal detector. Lower tension lever to "DOWN" position. Remove the lock bar. Using wire cutter, cut the test link at the terminal detector to simulate automatic actuation. NOTICE If regulated release mechanism does not actu- ate, refer to Steps 2 and 3 of the "Testing Detection System" portion of the 'Testing and Placing In Service" section, Page 6-3, of this manual. After successful actuation, raise the tension lever to "UP" position. Install properly-rated, ANSUL approved, fusible link in terminal detector. Cock the regulated release mechanism and install lock bar (Part No. 14985). Locate detector linkage and correctly position in each bracket. Lower tension lever to "DOWN" position. Inspect the base of the wire rope clamping device to make certain there is a minimum of 1/4 in. (6.4 mm) to a maximum of 3/8 in. (9.5 mm) clearance between the base of the trip hammer assembly and the cable lever assembly. NOTICE If clearance is not 1/4 in. (6.4 mm) minimum to a maximum of 3/8 in. (9.5 mm), raise tension lever to "UP" position, raise trip hammer 3/8- 1/2 in. (9.5-12.7 mm), tighten set screws, and repeat Steps 25 and 26. Remove lock bar. Manually test the regulated release mechanism by operating the remote manual pull station. Recock the regulated release mechanism and insert the lock bar. Reset all devices which were affected by the system actua- tion. Refer to "Resetting" section, Page 7-3 and 7-4. RESETTING Resetting Remote Manual Pull Station Metal Stamped Style (Part No. 4835 and 54011) Reset each remote manual pull station by completing the following steps: If necessary, remove set screw that is retaining the break glass rod. If necessary, carefully remove any remaining broken glass from station. Press and position ring handle in proper location against cover and slide the replacement glass break rod (Part No. 4834) through stud and handle. Tighten set screw into stud. If no other resetting is required, refer to "Cartridge Replacement," Page 7-4, and complete steps 1 through 5. ' Molded Composite Style (Part No. 415255) Position pull ring in vertical groove of pull station cover. Insert break-away seal, Part No. 79029, through holes in cover and snap in place. Molded Composite Style with Side Shields (Part No. 434618 and 435960) If necessary, carefully remove any remaining broken glass from station. Insert the break rod into the two holes toward the top of the pull knob. Pull the excess slack back into the ANSUL AUTOMAN Release. This will pull the pull knob assembly in place. NOTICE Take care in snapping in the ends of the break rod into the pull station side shields while rotat- ing the entire assembly. Hold the pull knob assembly against the faceplate. Rotate the pull knob assembly counterclockwise until the break rod and pull knob snap in place. Snap the PULL tab onto the pull knob so it is legible. If no other resetting is required, refer to "Cartridge Replacement," Page 7-4, and complete steps 1 through 5. SECTION VII - RECHARGE AND RESETTING PROCEDURES UL EX3470 ULC EX3470 Page 7-4 REV. 3 7-1-09 RESETTING (Continued) Resetting Mechanical Gas Shut-Off Valve Resetting Electrical Gas Shut-Off Valve Reset each mechanical gas shut-off valve by completing the fol- Reset each electric gas shut-off valve by completing the following lowing steps: steps: To reduce the risk of explosion due to leaking gas, before the gas line is turned on, make certain to extinguish any open flames and turn off all burners and any electrical or mechani- cal devices that are capable of igniting gas. Remove side cover from gas valve housing. Extend air cylinder rod to full "UP" position. Air cylinder is located inside the regulated release assembly enclosure. Recock gas valve by pulling valve stem up so pin in stem engages in cocking lever. Check burners for gaseous odor. IF GASEOUS ODOR EXISTS, MANUALLY PUSH THE AIR CYLINDER ROD TO THE FULL "DOWN" POSITION IMMEDIATELY. This will cause the mechanical gas valve to shut the gas line off. Open any doors and/or windows to clear the area of gaseous fumes, then correct the gas leak before proceeding any fur- ther. If no gaseous odor exists, pilot light may be ignited at this time. Reinstall side cover to gas valve housing. On ANSUL type valve, make certain roll pin is positioned within both sides of the valve housing slot and secure visual inspection seal (Part No. 197). If no other resetting is required, refer to "Cartridge Replacement" and complete steps 1 through 5. Resetting Electrical Switch (Snap-Action) Reset the electric (snap-action) switch by completing the following steps: Make certain the power source is on. Electric (snap-action) switch is reset automatically when the regulated release mechanism is recocked. If no other resetting is required, refer to "Cartridge Replace- ment" and complete steps 1 through 5. To reduce the risk of explosion due to leaking gas, before the gas line is turned on, make certain to extinguish any open flames and turn off all burners and any electrical or mechani- cal devices that are capable of igniting gas. Make certain the power source is on. Depress reset button on manual reset relay (red light on). Gas valve will resume its normal operating (open) position. Check burners for gaseous odor. IF GASEOUS ODOR EXISTS, TURN OFF POWER SOURCE IMMEDIATELY. This will cause the electric gas valve to shut the gas line off. Open any doors and/or windows to clear the area of gaseous fumes, then correct the gas leak before proceeding any further. If no gaseous odor exists, pilot light may be ignited at this time. If no other resetting is required, refer to "Cartridge Replace- ment" and complete steps 1 through 5. Resetting Pressure Switch Reset the pressure switch by completing the following: Depress the reset button(s) on the pressure switch cover. The pressure switch assembly(ies) is located on the right side of the regulated release enclosure. An audible click will be heard to verity the pressure switch has resumed its normal (non- actuated) condition. If no other resetting is required, refer to "Cartridge Replace- ment" and complete steps 1 through 5. REPLACEMENT CARTRIDGE To complete the recharge and resetting procedures: Remove shipping cap and weigh replacement cartridge. Replace if weight is 1/2 ounce (14.2 g), or more, below weight stamped on cartridge. Make certain regulated release mechanism is cocked and lock bar is installed. Then, install replacement cartridge into the regulated release assembly and each regulated actuator receiver and hand tighten. Remove lock bar. Snap cover on regulated release and each regulated actuator assembly, insert visual seal (Part No. 197) in upper and lower cover hole and secure. CAUTION Before installing cover, make certain detection tension lever is secured in the "DOWN" position to enable auto- matic detection and operation of the ANSUL AUTOMAN Regulated Release. Record recharge date on tag attached to unit and/or in a per- manent file. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-1 7-1-09 REV. 8 The maintenance information listed in this section deals with the limitations and parameters of this pre-engineered system. Those individuals responsible for the maintenance of the R-102 system must be trained and hold a current ANSUL certificate in an R-102 training program. Maintenance is required semi-annually. At the 12 year interval, along with the normal maintenance exam, the tank(s) must be hydro-tested and the regulator(s) must be flow tested. Prior to performing the required maintenance steps, verify that the R-102 system protection is designed and installed correctly for the existing appliance and ventilation system configuration. If not, make corrections as required. SEMI-ANNUAL MAINTENANCE EXAMINATION Semi-annual maintenance procedures for single, double, and multiple-tank systems are as follows. NOTICE Under certain circumstances hood and duct cleaning operations may render the fire suppression system ineffective due to a coating of cleaning chemical left on the detection equip- ment or mishandling of the system by cleaning service personnel. Therefore, it is strongly recommended that the R-102 system be completely inspected and serviced by an authorized ANSUL distributor immediately following any such cleaning operations. Remove the enclosure cover from the ANSUL AUTOMAN regulated release assembly and each regulated actuator assembly. Insert the lock bar (Part No. 14985) on the cocked regulated release mechanism. See Figure 1. FIGURE 1 Q32I Remove cartridge from regulated release assembly and each regulated actuator assembly, install safety shipping cap, and set aside in a safe location. Check to make certain the actuation line used to connect the regulated actuator assembly(s) to the ANSUL AUTOMAN regulated release assembly is connected to the high pressure side (right side) of the cartridge receiver in the ANSUL AUTOMAN and that it is intact, with all fittings securely tight- ened. This includes any 1/8 in. copper tubing and fittings used to connect to the air cylinder for the ANSUL mechanical gas valve. ZL CAUTION If the actuation line leaks pressure, the regulated actuator assembly(s) may not operate. A severe leak can render the entire system inoperable. To check for leaks in the actuation line, a hand held or electric vacuum pump may be used: Disconnect the actuation line from the ANSUL AUTOMAN regulated release cartridge receiver and connect the pump to the line. The pump should pull a vacuum to 20 inches of mercury, as shown on the gauge. Leaks should not exceed 5 inches of mercury loss within a 30 second time frame. If the gauge indicates a leak in the line, examine for loose connections or damage. Repair or replace as needed. If leakage is not due to piping, disassemble the pneumatic actuator assembly(s) in the regulated actuator(s) and inspect the actuator and the 0-ring in the actuator. Repair or replace as needed. Note: Vacuum pumps can be obtained from automotive parts/supply stores. Alternate Test Method: The actuation line can also be pressurized with either CO2 or N2 from a cartridge or with dry air, CO2, or N2 from a larger cylinder. Cock the ANSUL AUTOMAN regulated release assembly and carefully insert Lock Bar, Part No. 14985. See Figure 8. Make certain expellant gas line hose and/or pipe from the regulator in the ANSUL AUTOMAN regulated release is disconnected from agent storage tanks. Connect Regulator Test Kit, Part No. 56972, to one of the expellant gas line hoses and securely cap the remaining hose or pipe. See Figure 10. Verify that no cartridges are installed in the ANSUL AUTOMAN or the regulated actuator assembly(s). To verify operation of the regulated actuator assembly(s), Pressure Adaptor, Part No. 427560, can be used to connect to a pressurized CO2 or N2 cylinder, instead of using a CO2 or N2 cartridge. Note: The pressure adaptor assembly comes with a 1/4 in. NPT pipe plug that is required to be installed in the side of the adaptor. Install a suitable 1/4 inch air pressure quick connect fitting (supplied by others) to the bottom of the adaptor. Install and hand tighten the adaptor to the cartridge receiver and securely attach the corresponding connector from the gas cylinder hose assembly. With the valve on the regulator test kit closed, remove the lock bar and operate the remote cable operated pull station to operate the regulated release. Open the pressure cylinder valve to verify that the regu- lated actuator assembly(s) has operated properly and the air cylinder has unlatched the ANSUL mechanical gas valve, if used. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-2 REV. 4 7-1-09 SEMI-ANNUAL MAINTENANCE EXAMINATION (Continued) Once regulated actuator and gas valve operation is veri- fied, close the valve on the pressurized cylinder, if used, and open the valve on the regulator test kit to relieve any residual pressure. Note: Although only required at 12 year intervals, the regula- tor in the ANSUL AUTOMAN regulated release can also be verified. See Maintenance steps on page 8-6. Re-cock the ANSUL AUTOMAN regulated release and remove the spent cartridge or pressure adaptor from the cartridge receiver. I. If there were leaks in the actuation line or in the 1/8 inch copper gas tubing for the air cylinder(s), re-tighten the fittings or replace damaged components. m. If the cartridge puncture pin in the regulated actuator(s) did not fully extend, dismantle the actuator and inspect compo- nents of the actuator assembly. - Once the pneumatic actuator is disassembled, remove the actuator piston assembly and check the interior walls of the actuator body for signs of damage or corrosion. Check the 0-ring for elasticity or cuts. Replace, if neces- sary. Clean and coat 0-ring with a good grade of extreme temperature silicone grease and reinstall. . 11. Make certain that each tank is filled with 1.5 (5.8 L) or 3.0 (11.6 L) gallons of only ANSULEX Low pH Liquid Fire Suppressant. Fill level to be ONLY to the level indicated in the "Installation" section. See Page 5-2.1, Figure 6, for detailed filling tolerances. 12. Examine threads on each tank adaptor and tank collar for nicks, burrs, or cross-threading. Clean and coat 0-ring with a good grade of extreme temperature grease. See Figure 3. Remove 1/4 in. vent plug and clean and inspect for free move- ment and corrosion (replace if necessary). Reinstall vent plug. Make certain bursting disc is in place and silver side is away from tank. Clean seating surface and return adaptor/tube assembly to each tank. Tighten securely. SILVER SIDE OF DISC AWAY FROM TANK O-RINI;G FIGURE 3 Re-assemble the actuator assembly(s), and reconnect all 1, 13. Place fully charged tanks in enclosures and/or brackets and actuation and all expellant piping or hose. secure. Remove gasket from cartridge receiver in regulated release mechanism and each regulated actuator. Check gasket for elasticity or cuts and replace if necessary. Clean and coat gasket lightly with a good grade of extreme temperature grease. Reinstall gasket into cartridge receiver(s). From tank in regulated release assembly: Disconnect the expellant gas hose from each tank adaptor assembly. From tank in bracket/enclosure assembly: Disconnect the expellant gas piping union at each tank adaptor inlet line. Disconnect distribution piping union at each tank adaptor outlet line. From tank in enclosure: Remove tank. Keep in upright position to avoid spilling the agent. From tank in bracket assembly: Loosen wingnut, disengage bracket band, and remove each tank. Keep tank in upright position to avoid spilling the agent. Remove tank adaptor/tube assembly from each tank. See Figure 2. FIGURE 2 OI Carefully assemble and wrench tighten all expellant gas and agent distribution piping. Remove blow-off caps from nozzles. Inspect each blow-off cap and replace if deteriorated. On older style metal blow-off caps, make certain spring clip rotates freely on cap. On newer metal blow-off caps, make certain integral 0-ring is intact and undamaged. Replace cap(s) if necessary. NOTICE Rubber blow-off caps that have been installed in the system for one year or more must be replaced. Verify that all nozzle types are correct. Check all nozzles to ensure that they are free of cooking grease build-up and have a thin coating of clean silicone grease across the orifice. Note: Do not allow silicone grease to enter nozzle orifice. Note: If there is any evidence of cooking grease or other residue in the nozzles or distribution piping or agent or agent residue in the distribution piping, the entire piping network must be inspected and thoroughly cleaned. Portions of piping that cannot be thoroughly cleaned must be replaced. Utilizing the Nozzle Aiming Device, Part No. 431992, ensure that all nozzles are correctly aimed at the appropriate location on the appliance. Reinstall blow-off caps. 117. Remove the lock bar and manually test the regulated release assembly by operating the remote manual pull station. Check pull station cover for damage or wear. Replace cover if cable has worn a groove in the cover as deep as the diameter of the cable. If flexible conduit is used in installation, check conduit for damage, cuts and sharp bends. Install test link (Part No. 15751) in terminal detector. Lower tension lever to "DOWN" position. See Figure 6. TENSION LEVER IN DOWN POSITION SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-3 7-1-09 REV. 5 SEMI-ANNUAL MAINTENANCE EXAMINATION (Continued) 18. Cock the regulated release mechanism using cocking lever (Part No. 14995 or 435603). See Figure 4. Before proceeding with Step 18, test electric (snap-action) switches: With the ANSUL AUTOMAN in the cocked or ready posi- tion, press the lever of each switch up. If the switch is working properly, there should be an audible click. With the ANSUL AUTOMAN in the fired position, press the lever of each switch up, there should be no audible click. If an audible click is heard in the fired position several adjustments can be made. The trip lever extension pin can be rotated so the peak of one of the hex points is pointed up against the switch levers. Tighten it in that position. If this doesn't resolve the problem, loosen the screws holding the switches, apply a small counterclockwise torque on the switches and retighten the screws. If necessary, a final adjustment can be made by removing the snap action switch and bending the lever slightly. After adjustments, repeat Steps a. and b. Then, recock ANSUL AUTOMAN and insert lock bar. 19. Raise tension lever to "UP" position. See Figure 5. TENSION LEVER IN UP" POSITION FIGURE 5 FIGURE 4 FIGURE 6 00M 001096 Using wire cutter, cut test link at terminal detector to simulate automatic actuation. NOTICE If regulated release mechanism does not actuate, refer to Steps 2 and 3 of "Testing Detection System" in 'Testing and Placing in Service," Section 6, Page 6-3. After successful actuation, raise the tension lever to "UP" position. Remove and destroy all existing fusible links from the terminal and series detector brackets and replace with properly-rated ANSUL approved, fusible links in accordance with NFPA 17A. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-4 REV. 6 7-1-09 SEMI-ANNUAL MAINTENANCE EXAMINATION (Continued) Inspect wire rope at all detector locations, pulley elbows, pulley tee and at ANSUL AUTOMAN release. If wire rope shows signs of wear or fraying, replace entire length. Lower the tension lever to "DOWN" position. Recock the regulated release mechanism and insert the lock bar. Inspect the base of the wire rope locking clamp to make certain that there is a minimum of 1/4 in. (6.4 mm) and a maximum of 3/8 in. (9.5 mm) clearance between the base of the trip hammer locking clamp assembly and the cable lever assembly. See Figure 7. TRIP HAMMER i- ASSEMBLY LOCKIN F I G S CLAMP Test electric switches and electric gas valves by completing steps on Page 6-2 in Section 6, 'Testing and Placing In Service." Before reinstalling cartridge, reset all additional equipment by referring to appropriate section of "Recharge and Resetting Procedures," Section 7. Remove shipping cap and weigh each cartridge. Replace if weight is 1/2 ounce (14.2 g), or more, below weight stamped on cartridge. Make certain regulated release mechanism is cocked and lock bar is installed, then screw replacement cartridge into regu- lated release mechanism and each regulated actuator receiver(s) and hand tighten. Remove lock bar. 1/4 IN. (6.4 mm) I Make certain tension lever is in the "DOWN" position after MINIMUM I completing all tests. Failure to put the tension lever in the -r- 3/8 IN. (9.5 mm) I MAXIMUM I "DOWN" position will cause the system to not operate N. I I I automatically. CABLE LEVER ASSEMBLY FIGURE 7 0003m NOTICE If clearance is not between 1/4 in. (6.4 mm) or 3/8 in. (9.5 mm), raise tension lever to "UP" posi- tion, raise trip hammer 3/8-1/2 in. (9.5- 12.7 mm), tighten set screws, and repeat Steps 24 and 26. '29. For "scissor" style linkage, locate linkage and properly position I in each bracket all the way toward termination end of detection 1,30. If a mechanical gas valve is installed, begin the test procedure by removing both side covers. 0,31. At the regulated release, push the air cylinder rod fully down. The gas valve should operate. Pull the air cylinder rod to its fully extended position. p"34. Re-cock the gas valve by pulling the valve stem up until the pin in the stem engages the cocking lever. 1,35. Reinstall side covers on the gas valve and connect the visual indication seal. 41. Snap cover on regulated release and each regulated actuator, insert visual seal (Part No. 197) through holes in cover and box, and secure. 42. If system contains an Agent Distribution Hose and Restraining Cable Assembly, also perform the following steps: Carefully pull or push out the appliance and verify that the Restraining Cable limits the travel of the appliance and prevents the application of any pull force or bending stress on the Agent Distribution Hose or hose-to-pipe connec- tions. Check the Restraining Cable to verify it is not frayed and is securely fastened to the appliance and the wall or restrain- ing location. Check the hose and hose fittings and verify that the hose remains in a vertical natural loop with no noticeable fatigue at hose end couplings, no hose twists, no hose kinking or sharp bends. Check the outer hose covering for signs of damage, check- ing, tears, or wear. If any of these signs are observed, replace the hose. Return the appliance to its normal operating position. Again, check the hose and hose fittings to verify that the hose does not have sharp bends, and is not kinked, twisted, or caught on anything behind the appliance. If any of these conditions exist, the hose and/or hose connections will require installation modifications. With the appliance in its normal operating position, check the hose bend to make certain the bend is not less than a 3 in. (7.6 cm) bend radius (6 in. (15.2 cm) diameter). If less, replace hose. Verify that the appliance is returned to its original desired location. Failure to do so may result in undue stress and fatigue of the hose and hose connections. 43. Record semi-annual maintenance date on tag attached to unit and/or in a permanent file. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-5 7-1-09 REV. 5 ANNUAL MAINTENANCE EXAMINATION In addition to prforming all the steps necessary for Semi-Annual Maintenance, disconnect the agent discharge piping from the storage tank outlet(s) and verify that the agent distribution piping is not obstructed. At least annually, use dry air or nitrogen and blow through the agent distribution piping with the nozzle blow-off caps removed, verifying that dry air or nitrogen is discharging at each nozzle location. If nozzles show signs of cooking grease migration into the orifice of the nozzle, or if there is evidence of agent residue in the nozzle(s) or the inlet to the agent distribu- tion piping, some or all of the piping may require disman- tling to verify that the piping is not obstructed. At least annually, all rubber nozzle blow-off caps must be replaced. 12-YEAR MAINTENANCE EXAMINATION In addition to performing all of the steps necessary for semi-annual and annual maintenance, the following twelve-year maintenance procedures for single, double, and multiple-tank systems must be performed. NOTICE Under certain circumstances hood and duct clean- ing operations may render your fire suppression system ineffective due to a coating of cleaning chemical left on the detection equipment or mishandling of the system by cleaning service personnel. Therefore, it is strongly recommended that the R-102 system be completely inspected and serviced by an authorized ANSUL distributor immediately following any such cleaning oper- ations. At twelve-year intervals, the liquid agent tank(s) must be hydrostatically tested and refilled with a fresh charge of ANSULEX Low pH Liquid Fire Suppressant. The date of manufacture is stamped on the bottom of the agent tank or on the tank label. Remove the enclosure cover from the ANSUL AUTOMAN regulated release assembly and each regulated actuator assembly. Insert the lock bar (Part No. 14985) on the cocked regulated release mechanism. See Figure 8. LOCK BAR PROPERLY INSTALLED FIGURE 8 000321 Remove cartridge from regulated release assembly and each regulated actuator assembly, install safety shipping cap, and set aside in a safe location. lUfl[e] Do not reinstall cartridge at this time or system may be actuated. Remove gasket from cartridge receiver in regulated release mechanism and each regulated actuator. Check gasket for elasticity or cuts and replace if necessary. Clean and coat gasket lightly with a good grade of extreme temperature grease. Reinstall gasket into cartridge receiver(s). From tank in enclosure: Disconnect the expellant gas piping or hose from each tank adaptor assembly. From tank in bracket assembly: Disconnect expellant gas piping union at each tank adaptor inlet line. Disconnect distribution piping union at each tank adaptor outlet line. From tank in enclosure: Remove tank. From tank in bracket assembly: Loosen wingnut, disengage bracket band, and remove each tank. Keep tank in upright position to avoid spilling the agent. Loosen tank adaptor/tube assembly and remove. Safety glasses should be worn during transfer operations of ANSULEX Low pH Liquid Fire Suppressant. Avoid contact with skin or eyes. In case of contact, flush imme- diately with water for 15 minutes. If irritation persists, contact a physician. Do not take internally. If taken inter- nally do not induce vomiting. Dilute with water or milk and contact a physician. Pour the liquid agent from the tank into a clean, plastic container, and flush tank with clear water. At this point, each liquid agent tank, including the 1/4 in. gas hose assembly, must be HYDROSTATICALLY TESTED to 330 psi (26.6 bar). Refer to Hydrostatic Test Instructions," F-7602, for test adaptors and instructions. NOTICE DO NOT hydrostatically test a red painted mild steel agent storage tank. Instead, replace the tank with a new stainless steel tank shipping assembly (3-Gallon, Part No. 429862, or 1.5 Gallon, Part No. 429864). Verify date stamped on cartridge. The cartridge must also be hydrotested at intervals not greater than 12 years. (European cartridges are not refillable, therefore cannot be hydrotested and refilled. They must be discarded). If cartridge date indicates the need for hydrotesting, the cartridge must be bled down through normal ANSUL AUTOMAN release operation, returned to ANSUL for credit (or hydrotested by properly trained and ANSUL Authorized cartridge refilling stations), and replaced with a charged, replacement cartridge. FIGURE 9 For Second Tank: Disconnect expellant gas piping at union. Remove union from expellant gas piping and install pipe cap to prevent cartridge pressure from escaping during test. See Figure 10. FIGURE 10 000370 Pressure Switch: If an ANSUL supplied pressure switch is still in good operating condition, it should remain connected as part of system maintenance test. NOTICE For multiple-tank systems, one test kit (Part No. 56972) is required for each regulator in the system. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-6 REV. 5 7-1-09 12-YEAR MAINTENANCE EXAMINATION (Continued) NOTICE Cartridge bleed down can be used to verify pneumatic accessories operation. If system contains an Agent Distribution Hose and Restraining Cable Assembly, a hydrostatic test is required at 220 psi (15.2 bar) for hose assembly. The regulator must be flow tested at 12 year intervals. Check the date code stamped on the regulator body to determine if the regulator(s) requires the 12 year testing (see data code table). If regulator does not require testing, proceed to step 12. Flow test the regulator(s) per the following: Date Code Table Code Code Month Code Year UL 541L UL 74FF January A 1981 K February B 1982 L March C 1983 M April D 1984 N May E 1985 P June F 1986 R July G 1987 S August H 1988 T September J 1989 U October K 1990 V November L 1991 W December M 1992 Y 1993 Z 1994 A 1995 B 1996 C 1997 D 1998 E 1999 F 2000 G 2001 H 2002 J 2003 K 2004 L 2005 M E 2006 F 2007 G 2008 H 2009 2010 J 2011 K 2012 L 2013 M 2014 N 2015 0 a. Regulated Release Mechanism For First Tank: Disconnect expellant gas pipe or hose from tank. Connect regulator test kit (Part No. 56972) to hose. See Figure 9. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-7 7-1-09 REV. 5 12-YEAR MAINTENANCE EXAMINATION (Continued) b. Regulated Actuator For First Tank: Disconnect expellant gas hose from tank. Connect regulator test kit (Part No. 56972) to hose. See Figure 11. FIGURE 11 07l For Second Tank: Disconnect expellant gas piping at union. Remove union from expellant gas piping and install pipe cap to prevent cartridge pressure from escaping during test See Figure 12. FIGURE 12 000372 NOTICE Make certain valve is closed on regulator test kit or pressure will escape before test can be performed. Install either a nitrogen or CO2 cartridge into release mech- anism and each regulated actuator provided with the system. (Cartridge should be conditioned to approximately 70 °F (21 °C) before test.) NOTICE Before continuing with Step d, make certain valve on test kit is closed. Remove lock bar and operate remote manual pull station to actuate the regulated release and supply pressure to each test kit. Two styles of regulators are used with the R-102 release mechanisms. The diaphragm style (see Figure 13) was used in R-102 systems up to approximately 1988. The piston style (see Figure 13) has been used since 1988. Each style requires a slightly different flow test procedure. Use the appropriate flow test procedure as stated in Step DIAPHRAGM STYLE PISTON STYLE (USED UNTIL 1988) (USED AFTER 1988) FIGURE 13 002301 Flow test each regulator by completing the following steps: Diaphragm Style - The correct pressure should read 90 to 110 psi (6.2 to 7.6 bar) with the valve on the test kit closed and 80 psi (5.5 bar) with the valve on the test kit opened. Keep the valve opened to completely empty the pressure cartridge after pressure test has been verified. Piston Style - Open the valve on the regulator test kit. The correct pressure should read between 95 to 125 psi (6.6 to 8.6 bar). Keep the valve open to completely empty the pres- sure cartridge. If necessary, continue to flow test at each additional regu- lated actuator. Test each regulated actuator by repeating Step e. Cock release mechanism using cocking lever (Part No. 14995) and insert lock bar (Part No. 14985). Remove empty nitrogen cartridge(s) from release mecha- nism and each regulated actuator. Remove test kit(s) from release mechanism and each regu- lated actuator. L If regulator test was not successful, replace regulator. Reconnect all expellant gas lines. Reset all additional equipment that was operated by release mechanism. 15. Examine threads on each adaptor and tank collar for nicks, burrs, or cross-threading. Clean and coat 0-ring with a good grade of extreme temperature grease. Make certain bursting disc is in place and silver side is away from tank. See Figure 14. 0 0-RING FIGURE 14 SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-8 REV.2 7-1-09 12-YEAR MAINTENANCE EXAMINATION (Continued) '23. Raise the tension lever to "UP" position. See Figure 16. '16. Examine pick-up tube for signs of damage or corrosion. Replace assembly if needed. 17. Refill each tank with 1.5 (5.8 L) or 3.0 (11.6 L) gallons of only new ANSULEX Low pH Liquid Fire Suppressant. Note: Use a funnel with a screen to stop any foreign material from entering the tank. During filling, the agent temperature should be 60 OF to 80 OF (16 'C to 27 'C). DO NOT FILL WITH COLD AGENT. Refer to the "Installation" section, Page 5-2.1 for maximum fill heights for ANSULEX Low pH agent storage tanks. DO NOT OVERFILL. Overfilling may result in agent entering gas hose and regulator, potentially causing system malfunction. ' 18. Clean seating surface and return each adaptor/tube assembly to tank. Firmly tighten. NOTICE Do not reinstall any tank at this time. 19. Remove blow-off caps from nozzles. Inspect each blow-oft cap and replace if deteriorated. On metal blow-off caps, make certain spring clip rotates freely on cap. TENSION LEVER IN UP POSITION FIGURE 16 O3 Install test link (Part No.15751) in terminal detector. Lower tension lever to "DOWN" position. See Figure 17. NOTICE Rubber blow-off caps that have been installed in the system for one year or more must be replaced. Check all nozzles to ensure that they are free of cooking grease build-up and have a covering of clean silicone grease on the orifice. Reinstall blow-off caps. Remove lock bar and manually test the regulated release assembly by operating the remote manual pull station. 22. Cock the regulated release mechanism using cocking lever (Part No. 14995 or 4.35603). See Figure 15. TENSION LEVER IN DOWN POSITION 2 FIGURE 17 OOl8 26. Using wire cutter, cut test link at terminal detector to simulate automatic actuation. NOTICE If regulated release mechanism does not actuate, refer to Steps 2 and 3 of "Testing Detection System" in 'Testing and Placing in Service:' Section 6. FIGURE 15 s. 27. After successful actuation, raise the tension lever to "UP' position. 28. Remove and destroy all existing fusible links from the terminal and series detector brackets and replace with properly-rated , ANSUL approved, fusible links in accordance with NFPA 17A. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-9 7-1-09 REV. 0 12-YEAR MAINTENANCE EXAMINATION (Continued) Lower tension lever to "DOWN" position. Recock the regulated release mechanism and insert lock bar. Inspect the base of the wire rope locking clamp to make certain that there is a minimum of 1/4 in. (6.4 mm) and a maximum of 3/8 in. (9.5 mm) clearance between the base of the trip hammer locking clamp assembly and the cable lever assembly. See Figure 18. TRIP HAMMER ASSEMBLY i-i LOCKING %CLAMP 1/4 IN. (6.4 mm) MINIMUM 3/8 IN. (9.5 mm) MAXIMUM TRIP HAMMER BASE FIGURE 18 O003 NO110E If clearance is not between 1/4 in. (6.4 mm) or 3/8 in. (9.5 mm), raise tension lever to "UP" position, raise trip hammer 3/8-1/2 in. (9.5- 12.7 mm), tighten set screws, and repeat Steps 29 and 31. Locate detector linkage and properly position in each bracket. Make certain additional devices have operated as intended. Before reinstalling cartridge, reset all additional equipment by referring to appropriate section of "Recharge and Resetting Procedures," Section 7. Place each fully charged tank in enclosure and/or bracket and secure. Reconnect all distribution piping and expellant gas piping unions as required. Wrench tighten. Check each gas cartridge by removing shipping cap and weighing cartridge. Replace if weight is 1/2 ounce (14.2 g), or more, below weight stamped on cartridge. Make certain regulated release mechanism is cocked and lock bar is installed, then screw replacement cartridge into regu- lated release mechanism and each regulated actuator receiver(s) and hand tighten. Remove lock bar. Install cover on regulated release assembly and each regu- lated actuator assembly and secure with appropriate fasteners or visual inspection seal. Insert seal (Part No. 197) in each upper and lower cover hole, it applicable. If system is installed in an OEM enclosure, attach enclosure cover and secure with appropriate hardware or procedure. jUfl[S1 Before installing cover, make certain tension lever is in the "DOWN" position after completing all tests. Failure to put the tension lever in the "DOWN" position will cause the system to not operate automatically. Record date of 12 year maintenance examination on tag attached to enclosure and/or in a permanent file. SECTION VIII - MAINTENANCE EXAMINATION UL EX3470 ULC EX3470 Page 8-10 REV. 0 7-1-09 NOTES: SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-1 7-1-09 REV. 6 SYSTEM SELECTION GUIDE o. Note: System options do not cover all conceivable/acceptable variations. They are listed here as a general guideline to show the most common type arrangement for multiple systems, Based on certain system designs utilizing manifolding, non-manifolding, 3-tank sys- tems, etc., other tank/cartridge combinations can be designed. The combinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizing 12 flow and 6 flow systems when appropriate. Total Tank Flow No. Quantity Type of System Type of Hardware Carbon Dioxide Cartridge Required Nitrogen Cartridge Required 1-5 1 Single 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423429) 6-11 1 Single 3.0 Gal. Reg. Release 101-20(423441) LT-30-R (423435) 12-16 2 Double 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) 3.0 Gal. Additional Tank 16-22 2 Manifold 3.0 Gal. Reg. Release - Double (423493) L 3.0 Gal. Additional Tank 17-22 2 Double 3.0 Gal. Reg. Release 101-30 (423443)** Double (423493) 3.0 Gal. Additional Tank 22-33 3 Multiple 3.0 Gal. Reg. Release - Double (423493) 3.0 Gal. Reg. Actuator 3.0 Gal. Additional Tank 23-33 3 Multiple 3.0 Gal. Reg. Release 101-20 (423441) LT-30-R (423435) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 23-27 3 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423429) (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 28-33 3 Multiple 3.0 Gal. Reg. Release N/A Double (423493) (Optional) (2) 3.0 Gal. Additional Tanks 34-38 4 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423435) 3.0 Gal. Reg. Actuator N/A LT-A-101-30 (423491) Double 3.0 Gal. Tank Box 34-38 4 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) (Optional) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 39-44 4 Multiple 3.0 Gal. Reg. Release 101-20 (423441) LT-30-R (423435) 3.0 gal. Reg. Actuator N/A LT-A-1 01-30 (423491) Double 3.0 Gal. Tank Box 39-44 4 Multiple 3.0 Gal. Reg. Release 101-30 (423443)** Double (423493) (Optional) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (4234.43)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 45-49 5 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator N/A LT-A-101-30 (423491) Double 3.0 Gal. Tank Box 45-49 5 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423429) (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank Based on 5 flow numbers for a is gal system and 11 flow numbers for a 3.0 gal. system. ; flank are manifolded, only a "double tank nitrogen cartridge (Part No. 423493) can be used. If tanks are manifolded, either an LT-A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part No. 423493) can be used. SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-2 REV.5 10-1-02 SYSTEM SELECTION GUIDE (Continued) Total Tank Type of Carbon Dioxide Nitrogen Flow No.* Quantity System Type of Hardware Cartridge Required Cartridge Required 50-55 5 Multiple 3.0 Gal. Reg. Release 101-30 (423443) Double (423493) 3.0 Gal. Additional Tank 3.0 Reg. Actuator N/A LT-A-1 01-30 (423491) Double 3.0 Gal. Tank Box 50-55 5 Multiple 3.0 Gal. Reg. Release 101-20 (423441) LT-30-R (423435) (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 56-60 6 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 61-66 6 Multiple 3.0 Gal. Reg. Release 101-30 (423443)** Double (423493) 3.0 Gal. Additional lank 3.0 Gal. Reg. Actuator 101-30 (4234.4.3)*** LT-A-101-30 (423491) 3.0 Gal. Additional lank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 67-71 7 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423429) (2) 3.0 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491) (2) Double 3.0 Gal. Tank Box 67-71 7 Multiple Remote Mechanical Release 101-10 (423439) - - (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443) LT-A-101-30 (423491) 1.5 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-20 (423441) ... LT-30-R (423435) 72-77 7 Multiple 3.0 Gal. Reg. Release 101-20 (423441) LT-30-R (423435) (2) 3.0 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491) (2) Double 3.0 Gal. Tank Box 72-77 7 Multiple Remote Mechanical Release 101-10 (423439) - - (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-20 (423441) LT-30-R (423435) * Based on 5 flow numbers for a 1.5 gal. system and ii flow numbers for a 3.0 gal. system. If tanks are manifolded, only a 'double tank" nitrogen cartridge (Part No. 423493) can be used. If tanks are manifolded, either an LT-A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part No. 423493) can be used. SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-3 10-1-02 REV.5 SYSTEM SELECTION GUIDE (Continued) Total Tank Type of Carbon Dioxide Nitrogen Flow No.* Quantity System Type of Hardware Cartridge Required Cartridge Required 78-82 8 Multiple 1.5 Gal. Reg. Release 101-30 (423443) LT-30-R (423435) 3.0 Gal. Additional Tank (2) 3.0 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491) (2) Double 3.0 Gal. Tank Box 78-82 8 Multiple Remote Mechanical Release 101-10 (423439) - - (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443) LT-A-1 01-30 (423491) 1.5 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (4234.43)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 83-88 8 Multiple 3.0 Gal. Reg. Release 101-30 (423443) LT-30-R (423435) 3.0 Gal. Additional Tank (2) 3.0 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491) Double 3.0 Gal. Tank Box 83-88 8 Multiple Remote Mechanical Release 101-10 (423439) - (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 89-99 9 Multiple Remote Mech. Release 101-10 (423439) N/A 3.0 Gal. Reg. Actuator N/A (3) LT-A-101-30 (423491) (3) Double 3.0 Gal. Tank Box 89-93 9 Multiple Remote Mechanical Release 101-10 (423439) - - (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 1.5 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-20 (423441) LT-30-R (423435) 94-99 9 Multiple Remote Mechanical Release 101-10 (423439) -- (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-20 (423441) LT-30-R (423435) Based on 5 flow numbers for a 1.5 gal, system and 11 flow numbers for a 3.0 gal. system. If tanks are manifolded, Only a"double tank' nitrogen cartridge (Part No. 423493) can be used. flanks are manifolded, either an LT-A-1 01 30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part No. 423493) can be used. SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-4 REV. 7 10-1-02 SYSTEM SELECTION GUIDE (Continued) Total Tank Type of Carbon Dioxide Nitrogen Flow No.* Quantity System Type of Hardware Cartridge Required Cartridge Required 100-110 10 Multiple Remote Mech. Release 101-10 (423439) N/A (3) 3.0 Gal. Reg. Actuator N/A (3) LT-A-101-30 (423491) (3) Double 3.0 Gal. Tank Box 3.0 Gal. Reg. Actuator 101-20 (423441) LT-30-R (423435) 100-104 10 Multiple Remote Mechanical Release 101-10 (423439) - - (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443) LT-A-101-30 (423491) 1.5 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 100-104 10 Multiple Remote Mech. Release 101-10 (423439) N/A (Optional) (2) 3.0 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491) (2) Double 3.0 Gal. Tank Box (2) 3.0 Gal. Reg. Actuator (2)101-30 (423443) (2) LT-A-101-30 (423491) 3.0 Gal. Additional Tank 1.5 Gal. Additional Tank 105-110 10 Multiple Remote Mechanical Release 101-10(423439) -- (Optional) 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank 3.0 Gal. Reg. Actuator 101-30 (423443)*** LT-A-1 01-30 (423491) 3.0 Gal. Additional Tank Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3.0 gal. system. -- If tanks are manifolded, only a"double tank' nitrogen cartridge (Part No. 423493) can be used. If tanks are manifolded, either an LT-A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part No. 423493) can be used. Options are available up to a maximum of 15 tanks. Contact ANSUL Technical Services Department for detailed information. SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-5 7-1-09 REV. 6 SYSTEM COMPONENT INDEX Part No. Description 429853 Mechanical ANSUL AUTOMAN (ULC Regulated Release Shipping Assembly Also) Includes: Regulated Release Mechanism in Stainless Steel Mounting Enclosure 429856 Electric ANSUL AUTOMAN Regulated Release Shipping Assembly Includes: Regulated Release Mechanism with Solenoid and Switch in Stainless Steel Mounting Enclosure 429850 Regulated Actuator Shipping Assembly (ULC Includes: Actuator and Regulator in Also) Stainless Steel Mounting Enclosure 429870 Stainless Steel Mounting Box Shipping Assembly (ULC Includes: Stainless Steel Mounting Box Also) 429872 Two Tank Enclosure Shipping Assembly (ULC Includes: Two (2) Expellant Gas Hoses Also) Two (2) Grommets Stainless Steel Mounting Box 429859 24 VDC Regulated Release Shipping Assembly (ULC) Includes: 24 VDC ANSUL AUTOMAN Il-C Release Mechanism in Stainless Steel Mounting Box 430299 3.0 Gallon Mechanical Release Shipping Assembly including: 429853 Mechanical Regulated Release Assembly 429862 3.0 Gallon Tank Assembly 430300 1.5 Gallon Mechanical Release Shipping Assembly including 429853 Mechanical Regulated Release Assembly 429864 1.5 Gallon Tank Assembly 430309 3.0 Gallon Regulated Actuator Shipping Assembly including: 429850 Regulated Actuator Assembly 429862 3.0 Gallon Tank Assembly 430316 1.5 Gallon Stainless Steel Enclosure Shipping Assembly including: 429870 Single Tank Mounting Box Assembly 429864 1.5 Gallon Tank Assembly 430317 3.0 Gallon Stainless Steel Enclosure Shipping Assembly including: 429870 Single Tank Mounting Box Assembly 429862 3.0 Gallon Tank Assembly 430324 6.0 Gallon Stainless Steel Enclosure Shipping Assembly including: 429872 Two Tank Mounting Box Assembly 429862 3.0 Gallon Tank Assembly (2) 430332 3.0 Gallon Mounting Bracket Shipping Assembly including: 429878 3.0 Gallon Mounting Bracket Assembly 429862 3.0 Gallon Tank Assembly Part No. Description 418054 OEM Regulated Electric Release Shipping Assembly Includes: Regulated Release Mechanism with Solenoid and Switch 1/4 in. Hose and Mounting Bracket 79493 OEM Regulated Mechanical Release Shipping Assembly Includes: Regulated Release Mechanism 1/4 in. Hose and Mounting Bracket 418691 OEM Regulated Actuator Shipping Assembly Includes: Actuator and Regulator Hose Bracket 429878 3.0 Gallon Bracket Assembly (Bracket Only) 433485 Remote Release Assembly 418522 OEM Regulated Actuator Shipping Assembly Includes: Actuator and Regulator Hose 429862 3.0 Gallon Tank Shipping Assembly 429864 1.5 Gallon Tank Shipping Assembly 56972 Regulator Test Kit Includes: Gauge, Hose and Valve Assembly 79694 1.5 Gallon (5.8 L) Container of ANSULEX Low pH Liquid Fire Suppressant 79372 3.0 Gallon (11.6 L) Container of ANSULEX Low pH Liquid Fire Suppressant 423429 Cartridge Shipping Assembly (LT-20-R) (TC/DOT) 423435 Cartridge Shipping Assembly (LT-30-R) (TC/DOT) 423493 Cartridge Shipping Assembly (R-102 Double-Tank) (IC/DOT) 423491 Cartridge Shipping Assembly (LT-A-101-30) (TC/DOT) 423439 Cartridge Shipping Assembly (101-10) (IC/DOT) 15850 Cartridge Shipping Assembly (101-10) (DOT) 423441 Cartridge Shipping Assembly (101-20) (IC/DOT) 4234.43 Cartridge Shipping Assembly (101-30) (IC/DOT) 428440 Cartridge Shipping Assembly (LT-20-R) (European) 428441 Cartridge Shipping Assembly (LT-30-R) (European) 428446 Cartridge Shipping Assembly (R-102 Double Tank) (European) 428442 Cartridge Shipping Assembly (LT-A-101-30) (European) SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-6 REV. 7 7-1-09 SYSTEM COMPONENT INDEX (Continued) Part No. Description 428443 Cartridge Shipping Assembly (101-10) (European) 428445 Cartridge Shipping Assembly (101-20) (European) 428444 Cartridge Shipping Assembly (101-30) (European) 428948 Cartridge Shipping Assembly (LT-20-R) (Australian) 426553 Cartridge Shipping Assembly (LT-30-R) (Australian) 426563 Cartridge Shipping Assembly (R-102 Double Tank) (Australian) 426555 Cartridge Shipping Assembly (LT-A-1 01-30) (Australian) 419347 Nozzle Shipping Assembly (1W) Includes: 25 1W Nozzles (Part No. 419336) 25 Blow-Off Caps 419345 Nozzle Shipping Assembly (1/2N) Includes: 9 1/2N Nozzles (Part No. 419334) 9 Blow-Off Caps 419346 Nozzle Shipping Assembly (1 N) Includes: 25 1 N Nozzles (Part No. 419335) 25 Blow-Oft Caps 419349 Nozzle Shipping Assembly (3N) Includes: 9 3N Nozzles (Part No. 419338) 9 Blow-Off Caps 419348 Nozzle Shipping Assembly (2W) Includes: 25 2W Nozzles (Part No. 419337) 25 Blow-Oft Caps 419350 Nozzle Shipping Assembly (230) Includes: 25 230 Nozzles (Part No. 419339) 25 Blow-Off Caps 419351 Nozzle Shipping Assembly (245) Includes: 25 245 Nozzles (Part No. 419340) 25 Blow-Off Caps 419352 Nozzle Shipping Assembly (260) Includes: 9 260 Nozzles (Part No. 419341) 9 Blow-Off Caps 418353 Nozzle Shipping Assembly (290) Includes: 9 290 Nozzles (Part No. 419342) 9 Blow-Off Caps 419354 Nozzle Shipping Assembly (2120) Includes: 9 2120 Nozzles (Part No. 419343) 9 Blow-Off Caps 419344 Nozzle Shipping Assembly (1 F) Includes: 9 1 F Nozzles (Part No. 419333) 9 Blow-Off Caps 435672 Stainless Steel Nozzle Shipping Assembly (1 N) Includes: 1 Blow-Oft Cap (Part No. 77676) 432527 Stainless Steel Nozzle Shipping Assembly (1W) Includes: 1 Blow-Oft Cap (Part No. 77676) 419385 Swivel Adaptor Shipping Assembly Includes: 9 Swivel Adaptors (Part No. 418569) Part No. Description 423572 Swivel Adaptor Shipping Assembly Includes: 25 Swivel Adaptors (Part No. 418569) 77695 Blow-Oft Cap Shipping Assembly (Spare) Includes: 50 Blow-Off Caps (Part No. 77676) 77411 Blow-Off Cap Shipping Assembly Includes: 12 Blow-Oft Caps (Part No. 77676) 433208 CB Metal Blow-Oft Cap Shipping Assembly Includes: 10 Blow-Off Caps (Part No. 432153) 434707 CB Stainless Steel Blow-Off Cap Shipping Assembly Includes: 10 Blow-Off Caps (Part No. 435224) 551530 Metal Blow-Off Cap 0-Ring Shipping Assembly Includes: 10 0-Rings (Part No. 550625) 417911 In-Une Burst Disc Shipping Assembly Includes: 10 Burst Discs (Part No. 416970) 25627 1/4 in. Check Valve 551265 Nozzle Aiming Device 1,435547 Series Detector Package ('Scissor") '435548 Series Detector, Pack of 25 ('Scissor") 0,435546 Terminal Detector Package ('Scissor") Includes: Test Link 415671 Pulley Elbows Shipping Assembly (Socket End) - to 700 OF (371 'C) Includes: 50 Elbows (Part No. 415670) 423251 Pulley Elbows Shipping Assembly (Compression End) - to 700 OF (371 'C) Includes: 50 Elbows (Part No. 423250) 427929 Pulley Tee 15821 Wire Rope (50 Feet (15 m)) 79653 Wire Rope (500 Feet (152 m)) 24919 Stop Sleeve Package Includes: 10 Stop Sleeves (Part No. 26317) 1550122 Oval Sleeve Package Includes: 100 Oval Sleeves (Part No. 4596) 436063 Conduit Offset Shipping Assembly Includes: 6 Conduit Offsets (Part No. 435961) 78196 1/4 in. 'Quik-Seal" Adaptor Package Includes: 24 'Quik-Seals" (Part No. 78195) 77285 3/8 in. "Quik-Seal" Adaptor Package Includes: 24 'Quik-Seals" (Part No. 77284) 77287 1/2 in. "Quik-Seal" Adaptor Package Includes: 24 'Quik-Seals" (Part No. 77286) 77289 3/4 in. 'Quik-Seal" Adaptor Package Includes: 24 'Quik-Seals" (Part No. 77288) SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-6.1 7-1-09 REV. 5 SYSTEM COMPONENT INDEX (Continued) Part No. Description 79149 1/4 in. "Compression-Seal" Pipe Adaptor Package Includes: 24 "Compression-Seals" (Part No. 79148) 79151 3/8 in. "Compression-Seal" Pipe Adaptor Package Includes: 24 "compression-Seals' (Part No. 79150) 79147 1/2 in. "Compression-Seal" Pipe Adaptor Package Includes: 24 "Compression-Seals" (Part No. 79146) 79153 1/2 in. "Compression-Seal" EMT Conduit Adaptor Package Includes: 24 "Compression-Seals" (Part No. 79152) 55598 423253 Hood Seal Adaptor Shipping Assembly Includes: 6 Hood Seals 55601 1,436228 Reducing Coupling 435603 Short Handle Cocking Lever 55604 (Mechanical/Electrical ANSUL AUTOMAN) 435790 Short Handle Cocking Lever with Lock Bar 55607 (Mechanical/Electrical ANSUL AUTOMAN) 14995 Long Handle Cocking Lever 55610 (Mechanical/Electrical ANSUL AUTOMAN) 15618 Long Handle Cocking Lever with Lock Bar 25937 (Mechanical/Electrical ANSUL AUTOMAN) 26310 Cocking Lever (ANSUL AUTOMAN II-C) 25938 416018 Cocking Lever (Mechanical Gas Valve) 14985 Lock Bar 15733 13707 Gas Shut-off Equipment (Electrical 110 VAC, 60 Hz) Includes: Solenoid Valve - 3/4 in. 434618 13708 Gas Shut-off Equipment (Electrical 110 VAC, 60 Hz) 435960 Includes: Solenoid Valve - 1 in. 550360 Gas Shut-oft Equipment (Electrical 110 VAC, 60 Hz) 24915 Includes: Solenoid Valve - 1 1/4 in. 13709 Gas Shut-oft Equipment (Electrical 110 VAC, 60 Hz) Includes: Solenoid Valve - 1 1/2 in. 427074 13710 Gas Shut-oft Equipment (Electrical 110 VAC, 60 Hz) 434525 Includes: Fluid Power Gas Valve —2 in. 435959 550363 Gas Shut-off Equipment (Electrical 110 VAC, 60 Hz) 435979 Includes: Fluid Power Gas Valve —2 1/2 in. 17643 Gas Shut-off Equipment (Electrical 110 VAC, 60 Hz) 434347 Includes: Fluid Power Gas Valve —3 in. 426151 Gas Shut-off Equipment (Electrical 110 VAC, 60 Hz) 31809 Includes: Relay - Manual Reset 32335 423878 One Electric Switch (Field Mounted) Kit 32336 Includes: Electric Switch (SPDT), 430815 Mounting Hardware 435982 Gas Shut-off Equipment Mechanical (ANSUL) Includes: Mechanical Gas Valve - 3/4 in. Gas Shut-oft Equipment Mechanical (ANSUL) Includes: Mechanical Gas Valve - 1 in. Gas Shut-off Equipment Mechanical (ANSUL) Includes: Mechanical Gas Valve - 1 1/4 in. Gas Shut-off Equipment Mechanical (ANSUL) Includes: Mechanical Gas Valve - 1 1/2 in. Gas Shut-oft Equipment Mechanical (ANSUL) Includes: Mechanical Gas Valve —2 in. Gas Shut-off Equipment Mechanical (ASCO) Includes: Mechanical Gas Valve —2 1/2 in. Gas Shut-oft Equipment Mechanical (ASCO) Includes: Mechanical Gas Valve —3 in. Gas Shut-oft Equipment Includes: Air Cylinder and Tube Assembly Remote Manual Pull Station Assembly Remote Manual Pull Station Assembly Includes: 50 It (15.2 m) of Wire Rope Break Rod Package Includes: 10 Glass Break Rods (Part No. 4834) (Replacement) Trim Rings (Pack of 10) Flexible Conduit —500 ft (152.4 m) Flexible Conduit —500 It (152.4 m) Includes: 500 ft (152.4 m) of Wire Rope Flexible Conduit Strain Relief Includes: 50 Strain Reliefs Flexible Conduit Inserts Includes: 50 Inserts 16 in. (41 cm) Stainless Steel Actuation Hose 20 in. (51 cm) Stainless Steel Actuation Hose 24 in. (61 cm) Stainless Steel Actuation Hose 42 in. (107 cm) Stainless Steel Actuation Hose Agent Distribution Hose and Restraining Cable Kit Part No. Description 423879 Two Electric Switch (Field Mounted) Kit Includes: 2 Electric Switches (SPOT), Mounting Hardware 423880 Three Electric Switch (Field Mounted) Kit Includes: 3 Electric Switches (SPDT), Mounting Hardware 423881 Four Electric Switch (Field Mounted) Kit Includes: 4 Electric Switches (SPOT), Mounting Hardware 428311 Alarm Initiating Switch Kit SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-6.2 REV. 3 7-1-09 SYSTEM COMPONENT INDEX (Continued) Part No. Description 434455 Henny Penny Fryer Nozzle Kit 423429 Recharge Equipment Includes: LT-20-R Cartridge 423435 Recharge Equipment Includes: LT-30-R Cartridge 423493 Recharge Equipment Includes: Double System Cartridge 423491 Recharge Equipment Includes: LT-A-101-30 Cartridge 423439 Recharge Equipment Includes: 101-10 Cartridge 423441 Recharge Equipment Includes: 101-20 Cartridge 423443 Recharge Equipment Includes: 101-30 Cartridge 79372 Recharge Equipment Includes: 3.0 Gallon (11.4 L) Container of ANSULEX Low pH Liquid Fire Suppressant 79694 Recharge Equipment Includes: 1.5 Gallon (5.7 L) Container of ANSULEX Low pH Liquid Fire Suppressant 417911 Recharge Equipment Includes: Package of 10 Tank Adaptor Bursting Discs 77695 Recharge Equipment Includes: 50 Blow-Off Caps 24916 Recharge Equipment Includes: 10 Test Links (Part No. 15751) 415739 Recharge Equipment Includes: Fusible Link 165 OF (74 °C) 415740 Recharge Equipment Includes: Fusible Link 212 "F (100 "C) 415744 Recharge Equipment Includes: 25 Fusible Links 280 OF (138 °C) (Part No. 415741) 415745 Recharge Equipment Includes: 25 Fusible Links 360 oF (182 "C) (Part No. 415742) 415746 Recharge Equipment Includes: 25 Fusible Links 450 OF (232 °C) (Part No. 415743) Part No. Description 73867 Recharge Equipment Includes: 25 Fusible Links 500 OF (260 "C) (Part No. 56816) 79651 Recharge Equipment Includes: Detector Bracket - "Scissor" 415817 Recharge Equipment Includes: Detector Linkage - "Scissor" 14985 Recharge Equipment Includes: Lock Bar 14995 Recharge Equipment Includes: Cocking Lever 26310 Recharge Equipment Includes: Cocking Lever for ANSULAUTOMAN Il-C 15618 Recharge Equipment Includes: Cocking Lever and Lock Bar Assembly 15240 Recharge Equipment Includes: 500 OF (260 °C) Exhaust Duct Thermometer 197 Recharge Equipment Includes: Lead and Wire Seal 418087 Recharge Equipment Includes: Installation Manual 14 (ORDEI TE 16 18 OOD373 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-7 7-1-09 REV. 4 "ANSUL AUTOMAN" REGULATED RELEASE ASSEMBLY Figure Mechanical Electrical Description Part No. Part No. - Regulated Release Shipping Assembly 429853 429856 1 Mounting Box 419293 419293 2 Basic Release w/Regulator 79140 - Basic Release w/Solenoid, Switch, and Regulator - 79288 3 Self-Tapping Screw 71342 71342 4 Spacer 76555 76555 5 Tension Spring 79094 79094 6 Lever and Bracket Assembly 79300 79300 7 Machine Screw 14973 14973 8 Lockwasher 7310 7310 9 Hex Nut 14732 14732 10 Caution Label 57652 57652 11 Gasket 181 181 12 Expellant Gas Cartridge Assembly LT-30-R/101-20 (Ordered Separately) 423435/423441 423435/423441 Double Tank/101-30 (Ordered Separately) 423493/423443 423443/423443 13 Safety Shipping Cap 77251 77251 14 Tank Assembly 1.5/3.0 Gal. (Ordered Separately) 429864/429862 429864/429862 15 Hose Assembly 79007 79007 16 Enclosure Cover (Includes Label) 423744 423744 17 Solenoid Assembly - 423575 18 Electric Snap-Action Switch - 423878 19 Cover Screw 15362 15362 20 Speed Nut 423479 423479 21 Set Screw 73101 73101 10 (ORDERED EPARATELY1 12 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-8 REV. 3 10-1-02 REGULATED ACTUATOR ASSEMBLY Figure No. Description Regulated Actuator Assembly 1 Mounting Box 2 Pneumatic Actuator Assembly Including Regulator 3 Hex Jam Nut 4 Hole Adaptor (2) 5 Lockwasher 6 Gasket 7 Expellant Gas Cartridge Assembly LT-20-R/101-10 (Ordered Separately) LT-30-R/101-20 (Ordered Separately) Double Tank/101-30 (Ordered Separately) LT-A-101-30/101-30 (Ordered Separately) 8 Safety Shipping Cap 9 Label 10 Tank Assembly 1.5/3.0 Gal. (Ordered Separately) 11 Hose Assembly 12 Enclosure Cover (Without Labels) 13 Cover Screw 14 Speed Nut Part No. 429850 419293 79340 67990 423277 69521 181 423429/423439 423435/423441 423493/423443 423491/423443 77251 426953 429864/429862 79007 419294 15362 423479 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-9 4-1-06 REV. 4 ENCLOSURE ASSEMBLY 4 2j jJ j 0 Figure No. Description - Enclosure Shipping Assembly 1 Enclosure 2 Cover 3 Nameplate 4 Screw 5 Speed Nut Part No. 429870 419295 419296 429871 15362 423479 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-10 REV.3 10-1-02 BRACKET ASSEMBLY Figure 3.0 Gallon NQ. Description Part No. - Bracket Shipping Assembly 429878 1 Bracket Assembly - 2 Grommet 14089 3 Grommet 8688 Wing Nut 12065 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-10.1 7-1-09 REV. 4 TANK ASSEMBLY '-4 Figure NQL - Tank Assembly 1 Tank Adaptor Shipping Assembly 2 Pickup Tube Assembly 3 Vent Plug Assembly 4 0-Ring 5 Union Nut 6 Union Tail Piece 7 Burst Disc 8 Shell 9 Nameplate 375 1.5 Gallon 429864 430103 429883 74247 56909 417705 417706 416974 429861 N/A 3.0 Gallon 429862 79522 417700 74247 56909 417705 417706 416974 429860 N/A 1] 7,8 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-10.2 REV. 2 4-1-06 REMOTE RELEASE Figure N. Description Part No. - Remote Release 433485 1 Mounting Box 419295 2 Cover 419296 3 Maintenance Label 17351 4 Spring 79094 5 Speed Nut 423479 6 Machine Screw 14973 7 Hex Nut 14732 8 Lockwasher 7310 9 101 Release 433702 10 Spacer 76555 11 Screw 71342 12 Cover Screw 15362 13 Tension Lever and Bracket Assembly 79300 14 Gasket 181 15 101 Cartridge (Order Separately) (Not Shown) (TC/DOT) 423439 (DOT) 15850 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-11 10-1-02 REV. 5 ,'Multiple Nozzle Fryer Protection Calculation Examples Example No. 1 - Donut Fryer Without Dripboard. This fryer has a frypot that measures 26 in. in depth x 28 in. in length (66 x 71 cm). Because the frypot exceeds the maximum dimensions for one nozzle, multiple nozzles will be required. Procedure: Find the area of the fryer by multiplying the 26 in. depth x the 28 in. length (66 x 71 cm) which equals 728 sq in. (4697 sq cm). Using the 3N nozzle (approved for fryers with the longest side of 253/8 in. (64 cm) and a maximum of 370.5 sq in. (2390 sq cm) in area), divide the total area of 728 sq. in. (4697 sq. cm) by 370.5 sq in. (2390 sq cm) to find the number of nozzles needed. 728 sq. in. (4697 sq cm) divided by 370.5 sq in. (2390 sq cm) per nozzle = 2 nozzles required. Then verify the maximum longest side dimension of 25 3/8 in. (64 cm). Doing this will require doubling the 3N nozzles to = a total of 4 nozzles, if we are to protect the 26 in. (66 cm) depth and the 28 in. (71 cm) length of the fryer with this 3N nozzle option. See Figure 1. Using the same process, but utilizing the 3N nozzle approved for fryer protection with the longest side of 27 5/8 in. (70 cm) and the maximum of 324 sq in. (2090 sq cm) in area, the calculation will change to 728 sq in. (4697 sq cm) divided by 324 sq. in. (2090 sq. cm) per nozzle = 3 nozzles. Because this 3N nozzle option will protect 27 5/8 in. (70 cm) on the longest side, it will protect the 26 in. (66 cm) side in this example, thus eliminating the need for extra noz- zles. Utilizing this option, in this example, will require a total of 9 flows, but allows less nozzles and less nozzle drops". See Figure 1. *Note: 24low appliance nozzles can also be used. This option requires a total of 4 nozzles (728 sq in. divided by 210 sq in. per nozzle = 4 nozzles, or 8 total flows). Using this option requires that the noz- zles be placed over each quadrant of frypot area pro- tected and aimed to the center of the modules. This option may be desirable if minimizing total system flows is important. 14 IN 19 3/8 l 93181 L N. 91141W. 1 4 .. .1 b(35.6 cm) (23.8 (23. cm)I(23.5 cm)l f I (33 cm) 13 IN. -- I 261N. 26 IN. (66 cm) (66cm) _I I I I • I 28 IN. I (71 cm) "I 28 IN. (71 cm) FIRST 3N NOZZLE OPTION SECOND 3N NOZZLE OPTION FIGURE 1 002466 Example No. 2— Fryer With Dripboard. This fryer has an overall fry vat, including a dripboard, that measures 24 in. (61 cm) in depth x 20 in. (51 cm) in length. The actual frypot measures 20 in. x 20 in. (51 cm x 51 cm). Because both the frypot and the overall fry vat including the dripboard exceed the maximum dimensions for one nozzle, multiple nozzles will be required. Procedure: Divide the fryer cooking area from left to right or from front to back into modules that do not exceed single nozzle area limitations and longest side limitations as described in the table for "Fryer Multiple Nozzle Protection" located in the Design Section. The example fryer can either be divided from left to right into two modules, each measuring 10 in. x 24 in. (25.4 cm x 61 cm), or it can be divided from front to back. See Figure 2. If the fryer is divided from front to back, two 2-flow nozzles may be adequate. To determine this, first protect as much of the rear portion of the vat (the fry- pot area) that is allowed with 2-flow appliance noz- zles using the maximum area of 210 sq in. (1355 sq cm) per nozzle with the maximum longest side of 21 in. (53 cm) for multiple nozzles. See Figure 2. In the example, the frypot is 20 in. (51 cm) from side to side. Use the maximum area of 210 sq in. (1355 sq cm) allowed for one nozzle and divide it by 20 in. (51 cm), a total of 10 1/2 in. (27 cm) of the frypot can be protected with one 2-flow nozzle (210 sq in. divid- ed by 20 in. = 10.5 in.). See Figure 2. This leaves the remainder of 9 1/2 in. (24 cm) of frypot and the entire dripboard yet to protect. One 2-flow appliance nozzle will protect up to 10 1/2 in. (27 cm) of frypot, therefore, there is no need to verify the remain- ing 9 1/2 in. (24 cm). There is only the overall of 9 1/2 in. (24 cm) remaining plus the dripboard to verify. The dripboard measures 4 in. x 20 in. (10 cm x 51 cm), with an overall remainder of frypot + dripboard area size of 131/2 in. x20 in. (34 cm x51 cm) = 270 sq in. (1742 sq cm). Reviewing the "Multiple Nozzle Fryer Table:' a 2-flow appliance nozzle can protect an area, including dripboard, of 294 sq in. (1897 sq cm) with a longest side of 21 in. (53 cm). Because the area is less than the maximum of 294 sq in. (1897 sq cm) and the longest side is less than the maximum of 21 in. (53 cm), a 2-flow nozzle will be sufficient. See Figure 2. Adding the protection required for the back of the fry- pot to the front protection requires two 2-flow appli- ance nozzles as a minimum. See Figure 2. 20 IN. 20 IN. (51 cm) I- (51 cm) 10 1/2 IN. 1 (27 cm) 201W. I (51 cm) 241N. 24 IN. (61 cm) 9 112 IN. (61 cm) _L • I • _j (24 cm) tI 10 IN. 4 IN. (254 cm) I (10 cm) 4 IN. (10 cm) DIVIDED LEFT TO RIGHT DIVIDED FRONT TO BACK FIGURE 2 002467 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-12 REV.4 7-1-09 P WIRING DIAGRAM NFPA standards require simultaneous operation for fire suppres- sion systems when two or more hazards can be simultaneously involved in fire by reason of their proximity. To accomplish simulta- neous operation, the 120 VAC Electric AUTOMAN Regulated Release Assembly can be used. This release can be activated independently by fusible line operation exactly like the mechanical version and can also be triggered electrically using a snap action switch from another. 120 VAC Electric AUTOMAN Regulated Release Assembly or a Mechanical AUTOMAN Regulated Release Assembly. The electrical wiring used to connect from one AUTOMAN Regulated Release Assembly to another will not be supervised. However, NFPA 96 allows an exception for electrically operated systems which "include automatic mechanical detection (fusible link) and actuation as a backup detection system:' In the case of multiple hoods sharing a common exhaust duct, NFPA 17A requires one of two forms of simultaneous operation. The following wiring diagrams (See Figures 3 and 4) identify two principle uses for the 120 VAC Electric AUTOMAN Regulated Release Assembly. Refer to Components Section, Page 3-1, Figure 3. Simultaneous operation of all independent hood, duct, and appliance protection systems. See Figure 3. Simultaneous operation of any hood, duct, and appliance pro- tection system and the system(s) protecting the entire common exhaust duct. See Figure 4. Simultaneous Actuation of Multiple 120 VAC Electric ANSUL AUTOMANs ALL SYSTEMS MUST BE CONNECTED TO THE SAME POWER SOURCE DUAL ELECTRIC SWITCH, PART ACTUATION LINE NO. 423879 115 VAC 60 HZ HOT rNEUTRAL rrT ACTUATION SOLENOID AUTOMAN 1 AUTOMAN 2 TYPICAL FOR ADDITIONAL AUTOMANs - UP TO 4 FIGURE 3 00840 SECTION IX - APPENDIX UL EX3470 ULC EX3470 Page 9-13 7-1-09 REV. 0 WIRING DIAGRAM Simultaneous Actuation of One (1) or More 120 VAC Electric ANSUL AUTOMANs from Multiple Mechanical ANSUL AUTOMANs ALL SYSTEMS MUST BE CONNECTED TO THE SAME POWER SOURCE MECHANIC AUTOMAN, TYP.5 SWITCH, PART NO. 423678 VAC lz FIGURE 4 OWN Note 1: For fusible link detection only. Note 2: Use ANSUL AUTOMANs with solenoid and electric switch. Replace Single Electric Switch, Part No. 423878, with Dual Switch Kit, Part No. 423879. Note 3: See Installation section of this manual for power capacity of solenoid and switches. Note 4: This method does not provide supervision for battery or system wiring. The authority having jurisdiction (AHJ) may waive this requirement. Note 5: When any one of the Mechanical ANSUL AUTOMANs is activated, the microswitch will transfer to the N.O. position, completing the circuit to the N.C. switch in the Electrical ANSUL AUTOMAN. This will activate the ANSUL AUTOMAN. When the ANSUL AUTOMAN fires, the N.C. switch transfers to the N.O. position, opening the circuit to the solenoid. SECTION IX - APPENDIX UL EX. 3470 ULC CEx747 Page 9-14 REV. 0 7-1-09 iellj /4/pp System Model - Serial Number Job Number Type of System: ANSUL R-102 9102 4p LPL)-~ Fire Suppression System Distributor Certificate of Installation To he completed by Fire System Distributor ... /30 CJLSUd tivf Distributor Name. cJ?LpL/c Distributor Address Address R w4 iZL Job Name , Job Address /9'c74ti4 I Gas Valve: MechanicaE} Electrical LI Size fr Electric Equipment Shut-down Tested: BYES [INO Installed. Tested on (MMIDDIYYYY) This Fire Suppression System Is Installed in accordance with the Mariulacturer's instructions and drawings, NFPA 96 and 17 (current Issues) and all applicable state and local codes. All eleb kal work or work perfomied by others to complete the installation of this system has been completed. ExiepliuE.s to the above are noted below. (Use back of sheet if necessary) Installer's Name 24,7-j4 Signature Date\TU 2. .&o/r (MMIDD!YYYY) To be Completed by Owner or Owner's Representative I have received a copy of the Fire Suppression System Owner's Manual and I understand it. I also understand that it is the rarnmmendation of the National Fire Protection Aociation (NFPA) that the system be Inspected every six months to maintain Its reliability. Signifure Date (MM/DD To be Completed by the Authority Having Jurisdiction Functional test have been witnessed and the system performs as designed. Signature Date________ Purchase Ordcr, Change Order, & Distributor Certificate - Fire System CaptiveAire, 0 1-29-09 offlams- Fire Suppression System Distributor Certificate of Installation $\5 1OO 19 To he completed by Fire System Distributor Job Name S"a 44.- 77'ZLf Job Number________________ Job Address 19/c (,&L1ff I&ri.j4 ! )D Tpe of System: ANSUL R-102 29 Distributor Name .-.S014. Distributor Address 3Sfc FFc Ad s System Model 2 C - Serial Number__________ Gas Valve: Mechanica Electrical U Size / Electric Equipment Shut-down Tested: OYES RNO Installed. Tested on (MMIDD!YYYY) This Fire Suppression System Is installed in accordance with the ManuFacturer's instructions and drawings, NFPA 96 and 17 (current Issues) and all applicable state and local codes. All aluch kal work or work performed by others to complete the installation of this system has been completed. Exm..-eptknms to time above are noted below. (Use beck of sheet if necessary) Installer's Name Signature Date (J . (MMiDDIYYYY) To be Completed by Owner or Owner's Representative I have received a copy of recommendation of the N reliability. Signature Fire Suppression System Owner's Manual and I understand it. I also understand that it is the nal Fire Protection Association (NFPA) that the system be Inspected every six months to maintain Its Date______________ (MM/DD/YYYY) To be Cdmpleted by the Authority Having Jurisdiction Function 1- have .-. n witnessed and the system performs as designed. Signat DateSj/))c Purchase Order, Change Order, & Distributor Certificate - Fire System CaptiveAire, v3 1-29-09 Fire Suppression System Distributor Certificate of Installation To he completed by Fire System Distributor OW 9 Job Name 81A L4 1AiLL5' Job Address / 9i,~ CLL. £2A1c)'L-S4-/ Job Number of System: ANS(JL R402 11 Distributor Name....-- Distributor Address SS4 ?J System Model -/O2 /•- Serial Number i%' C0?%1 it Gas Valve: Mechanical, Electrical 1] Size / Electric Equipment Shut-down Tested: IYES 1NO Installed. Tested on - I L( / ç (MMIDD!YYYY) This Fire Suppression System Is Installed in accordance with the ManuiacLurer's instructions and drawings, NFPA 96 and 17 (current Issues) and all applicable state and local codes. All e1ettiha1 work or work performed by others to complete the installation of this system has been completed. ExcepLious to the above are noted below. (Use back of sheet if necessary) Installer's Nam/'J o jig Signature Date (MMIDD!YYYY) To be Completed by Owner or Owner's Representative I have received a copy of the Fire Suppression System Owner's Manual and I understand it. I also understand that it is the recommendation of the National Fire Protection Association (NFPA) that the system be Inspected every six months to maintain Its reliability. I Ify I J--- Signitum___ pate (MM/DU/YYYY) To be Completed by the Authority Having Jurisdiction Functional tests have be nessed.apde system performs as designed. Signatur Date - 7 .)... Purchase Order, Change Order, & Distributor Certificate - Fire System CaptiveAire, v3 1-29-09