FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
To be completed by the system installation contractor at the time ofsystem acceptance and approval.
It shall be permitted to mod(fy this form as needed to provide a more complete and/or clear record
Insert N/A in all waned lines.
Attach additional sheets, data, or calculations as necesiar, to provide a complete record
I. PROPERTY INFORMATION
Name of property: SKLZ Pro Performance
Address: 2081 Faraday Ave
Description of prcpc!ty. WarehouseIshipping.
Occupancy type: B, SI
Name of property representative: Nick Fousslanes
Address: 2081 Faraday Ave
Phone: 1-858-231-1691 Fax: E-mail:
Authority having jurisdiction over this property- City of Carlsbad
Phone: 760-802-4660 Fax: E-mail:
INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION
Installation contractor for this SDA Security
Address: 2054 State St, San Diego Ca 92101
License or certification number: C-7/C-10 245668
Phone: 1-600-896-1144 Fax: 619-338-1208 E-mail:
Service organization for this equipment: Same
Address:
License or certification number
Phone: Fax: Email:
A contract for test and inspection in accordance with NFPA standards is in effect as of:
Contracted testing company: Same
Address:
Phone: Fax E-mail
Contract expires: Contract number: Frequency of routine inspections:
DESCRIPTION OF SYSTEM OR SERVICE
Fire alarm system (nonvoice)
Fire alarm with in-building fire emergency voice alarm communication system (EVACS)
D Mass notification system WS)
D Combination system, with the following components:
D Fire alarm 0 EVACS 0 MNS 0 Two-way, in-building, cmeigcncy communication system
0 Other (specify);
NFPA 72, Fig. 10.18.2.1.1 (p. 1 of 12)
Ccp)rght 02009 NaSanal Fe PrcUctlanAaacIicn. ThiaCnn nay be aWWforhalMduai tue otherthaUor resale. It may not be copied far canunuiclal sais uid1b1bu5an.
It
p
3. DESCRIPTION OF SYSTEM OR SERVICE (continued)
NFPA 72 edition: 2010
3.1 Control Unit
Manulhcturer. DMP
3.2 Mass Notification System
3.2.1 System Type:
O In-building MNS—combination
E3 In-building MNS—stand-alone
Other (specify):
3.2.2 System Features:
Additional description of system(s):
Model number XR-2400F
This system does not incorporate an MNS
0 Wide-area MNS 0 Distributed recipient MNS
O Combination fire alarm/MNS 0 MNS autonomous control unit 0 Wide-area MNS to regional national
alerting interface
Local operating console (LOC) 0 Direct recipient MNS (DRMNS) 0 Wide-area MNS to DRMNS interface
D Wide-area MNS to high-power speaker array (HPSA) interface [3 In-building; MNS to wide-area MNS interface
0 Other (specify):
3.3 System Documentation
An owner's manual, a copy of the manufacturer's instructions a written sequence of operation, and a copy of
the numbered record drawings are stored on site. Location: FACP Room
3A System Software This system does not have alterable site-specific software.
Operating system (executive) software revision level:
Site-specific software revision date: Revision completed by:
A copy of the site-specific software is stored on site. Location:
3.5 Off-Premises Signal Transmission 0 This system does not have off-premises transmission.
Name of organization receiving alarm signals with phone numbers:
Mann: SDA Security Phone: 1800.896.1144
Supervisory: SDA Security Phone: 1400-896-1144
Trouble: SDA Security Phone: 1-800496-1144
Entity to which alarms are retransmitted: SDA Security Phone: 1-800-896-1144
Method of retransmission: Cell Communicator
If Chapter 26, specify the means of transmission from the protected premises to the supervising station:
If Chapter 27, specify the type of auxiliary alarm system: 0 Local energy 0 Shunt 0 Wired 0 Wireless
NFPA 72, Fig. 10.18.2.1.1 (p 2 o 12)
Capyright 02009 Netenal Fe PmtedonAwdetim This torn maybe copWfbr1rdftW use otlseirnn for rse. kmayndbecapiadfor....e.U1ads arot.tilbeUor.
4. CIRCUITS AND PATHWAYS
4.1 Signaling Line Pathways
4.1.1 Pathways Class Designations and Survivability
Pathways class: B Survivability level: I Quantity: 3
(See NFPA 72, Sections 12.3 and 12.4)
4.1.2 Pathways Utilizing Two or More Media
Quantity: 0 Description:
4.1.3 Device Power Pathways
0 No separate power pathways from the signaling line pathway
IN Power pathways are separate but of the same pathway classification as the signaling line pathway
fl Power pathways are separate and different classification from the signaling line pathway
4.1.4 Isolation Modules
Quantity: 0
4.2 Alarm Initiating Device Pathways
4.2.1 Pathways Class Designations and Survivability
Pathways class: B Survivability level:
(See NFPA 72, Sections 12.3 and 12.4)
4.2.2 Pathways Utilizing Two or More Media
Quantity: 0 Description:
Quantity. 3
4.2.3 Device Power Pathways
0 No separate power pathways from the Initiating device pathway
IM Power pathways are separate but of the same pathway classification as the Initiating device pathway
D Power pathways are separate and different classification from the initiating device pathway
4.3 Non-Voice Audible System Pathways
4.3.1 Pathways Class Designations and Survivability
Pathways class: B Survivability level: I Quantity: 17
(See NFPA 72, Sections 12.3 and 12.4)
4.3.2 Pathways Utilizing Two or More Media
Quantity: 0 Description:
4.3.3 Appliance Power Pathways
No separate power pathways from the notification appliance pathway
Power pathways are separate but of the same pathway classification as the notification appliance pathway
Power pathways arc separate and different classification from the notification appliance pathway
NFPA 72, Fig. 10.18.2.1.1 (p.3of12)
CopyrghtO2OO9 NaSonel Fire Poteon Amd0m. Tha form maybe copsd for brd]v!ieluse ottn for rueela. ftnuy not b.c edcronmms eele or th.fr ii.
S. ALARM INITIATING DEVICES
5.1 Manual Initiating Devices
5.1.1 Manual Fire Alarm Boxes
Type and number of devices: Addressable:
Other (specify):
5.1.2 Other Alarm Boxes
Description:
Type and number of devices: Addressable:
Other (specify):
5.2 Automatic Initiating Devices
0 This system does not have manual fire alarm boxes.
Conventional: I Coded: Transmitter:
This system does not have other alarm boxes.
Conventionaj: Coded: Transmitter:
5.2.1 Smoke Detectors 0 This system does not have smoke detectors.
Type and number of devices: Addressable: Conventional: 5
Other (specify):
Type of coverage: 0 Complete area Partial area 0 Nonrequired partial area
Other (specify):
Type of smoke detector sensing techoologr. 0 Ionization Z Photoelectric 0 Multicriteria 0 Aspirating 0 Beam
Other (specify):
5.2.2 Duct Smoke Detectors 0 This system does not have alarm-causing duct smoke detectors.
Type and number of devices: Addressable: Conventional: 17
Other (specify):
Type of coverage:
Type of smoke detector sensing technology: 0 Ionization Photoelectric D Aspirating 0 Beam
5.23 Radiant Energy (Flame) Detectors 3 This system does nothave radiant energy detectors.
Type and number of devices: Addressable: Conventional:
Other (specify):
Type of coverage:
5.2.4 Gas Detectors 0 This system does not have gas detectors.
Type of detector(s):
Number of devices: Addressable: Conventional:
Type of coverage:
5.2.5 Heat Detectors This system does not have heat detectors.
Type and number of devices: Addressable: Conventional:
Type of coverage: 0 Complete area 0 Partial area 0 Nonrequired partial area D Linear. 0 Spot
Type of heat detector sensing technology: 0 Fixed temperature 0 Rate-of-rise 0 Rate compensated
NFPA 72, Fig. 10.182.1.1 (p.4of 12)
Ccpyttght 02009 NotIonal Fue Pioteotion Meociatlan. Thlsfcnn may be capiedror bldMaI uee other thi forr.ul.. It may not be copIed for coimerced eel. ordaliibid
5. ALARM INITIATING DEVICES (continued)
5.2.6 Addressable Monitoring Modules
Number of devices: 8
5.2.7 Waterfiow Alarm Devices
Type and number of devices: Addressable:
5.28 Alarm Verification
Number of devices subject to alarm verification:
5.2.9 Preslgnal
Number of devices subject to presignal:
Describe presignailbuctions:
5.2.10 Positive Alarm Sequence (PAS)
Describe PM:
52.11 Other Initiating Devices
Describe:
D This system does not have monitoring modules.
0 This system does not have waterfiow alarm devices.
Conventional: 3 Coded: Transmitter
Z This system does not incorporate alarm verification.
Alarm verification set for seconds
This system does not incorporate pre.signat
This system does not incorporate PAS.
IM This system does not have other Initiating devices.
S
6. SUPERVISORY SIGNAL-INITIATING DEVICES
6.1 Sprinkler System Supervisory Devices 0 This system does not have sprinkler supervisory devices.
Type and number of devices: Addressable: Conventional: 3 Coded: Transmitter:
Other (specify):
6.2 Fire Pump Description and Supervisory Devices IN This system does not have a fire pump.
Type fire pump: 13 Electric pump 0 Engine
Type and number of devices: Addressable: Conventional: Coded: Transmitter:
Other (specify):
6.2.1 Fire Pump Functions Supervised
13 Power 11 Running O Phase reversal D Selector switch not inSato jJEngine or control panel trouble Cl Low fuel
Other (specify):
6.3 Duet Smoke Detectors (DSDs) 10 This system does not have DSDs causing supervisory signals.
Type and number of devices: Addressable: Conventional:
Other (specify):
Type of coverage:
Type of smoke detector sensing technology: 0 Ionization 0 Photoelectric 0 Aspirating 0 Beam
6A Other Supervisory Devices This system does not have other supervisory devices.
Describe:
NFPA 72, Fig. 10.182.1.1 (p. 5 of 12)
capydgttO2OO9 Netemi Fe P teIonAuodaIii. Thistem maybe copied for irvIOuI use otIurthen?ocreaa It may not be 00pledcommnot.1 Is mdbetiIan.
MONITORED SYSTEMS
7.1 Engine-Driven Generator
7.1.1 Generator Functions Supervised
0 Engine or control panel trouble 0 Generator running
0 Other (specify):
7.2 Special Hazard Suppression Systems
Description of special hazard system(s):
7.3 Other Monitoring Systems
Description of special hazard system(s):
ANNUNCIATORS
8.1 Location and Description of Annunciators
Location 1: Lobby
Location 2:
Location 3:
I
IN This system does not have a generator.
0 Selector switch not in auto 0 Low fuel
This system does not monitor special hazard systems.
10 This system does not monitor other systems.
0 This system does not have annunciators.
9. ALARM NOTIFICATION APPLIANCES
9.1 In-Building Fire Emergency Voice Alarm Communication System 0 This system does not have an EVACS.
Number of single voice alarm channels: Number of multiple voice alarm channels:
Number of speakers: Number of speaker circuits:
Location of amplification and sound-processing equipment:
Location of paging microphone stations:
Location 1:
Location 2:
Location 3:
9.2 Nonvoice Notification Appliances D This system does not have nonvoice notification appliances.
Horns: 48 With visible: 48 Bells: 0 With visible: 0
Chimes: 0 With visible: 0
Visible only 60 Other (describe):
9.3 Notification Appliance Power Extender Panels D This system does not have power extender panels.
Quantity: 4
Locations: 1 at Panel. I Upetaim Data Room, 2 Back WIne Data Room
NFPA 72, Fig. 10.18.2.1.1 (p.6 of 12)
OcpiigMCNatxI Fire Pratedian Amociatoa llisform mwb*ooPWfbrhdvftW= o5Ditan for ressle. Cc ynotbecaped1ccnunvcat sele ardatitMoit
MASS NOTIFICATION CONTROLS, APPLIANCES, AND CIRCUITS 0 This system does not have an MNS.
10.1 MNS Local Operating Consoles
Location I:
Location 2:
Location 3:
10.2 High-Power Speaker Arrays
Number of I1PSA speaker initiation rcnes
Location I:
Location 2:
Location 3:
10.3 Mass Notification Devices
Combination fire alarm/MNS visible appliances: MNS-only visible appliances:
Textual signs: Other (describe):
Supervision class:
10.3.1 Special Hazard Notification
El This system does not have special suppression predischarge notification-
13 MNS systems DO NOT override notification appliances required to provide special suppression predischarge notification.
TWO-WAY EMERGENCY COMMUNICATION SYSTEMS
111 Telephone System IN This system does not have a two-way telephone system.
Number of telephone jacks installed; Number of warden stations installed:
Number of telephone handsets stored on site:
Type of telephone system installed. D Electrically powered 0 Sound powered
11.2 Two-Way Radio Communications Enhancement System
I] This system does not have a two-way radio communications enhancement system.
Percentage of area covered by two-way radio service: Critical areas: % General building areas:
Amplification component locations:
Inbound signal strength. dBm Outbound signal strength: dBm
Donor antenna isolation is: dB above the signal booster gain
Radio frequencies covered:
Radio system monitor panel location:
NFPA 72, Fig. 10.18.2.1.1 (p. 7of12)
RLI
copydght 02009 NatIonal Fire F, Auooiafia,LThIoftrm Maybe aWled nI use aft thntfarma lifflayrotbecoplaciftowmeidaI aalembdioa
TWO-WAY EMERGENCY COMMUNICATION SYSTEMS (continued)
11.3 Area of Refuge (Area of Rescue Assistance) Emergency Communications Systems
0 This system does not have an area of refuge (area of rescue assistance) emergency communications system.
Number of stations: Location of central control point
Days and hours when central control point is attended
Location of alternate control point:
Days and hours when alternate control point is attended:
11.4 Elevator Emergency Communications Systems
0 This system does not have an elevator emergency communications system.
Number of elevators with stations: Location of central control point
Days and hours when central control point is attended:
Location of alternate control point
Days and hours when alternate control point is attended:
115 Other Two-Way Communication Systems
Describe:
CONTROL FUNCTIONS
This system activates the following control fuctions:
Hold-open door releasing devices 0 Smoke management IM HYAC shutdown IN F/S dampers
D Door unlocking D Elevator recall 0 Fuel source shutdown 0 Extinguishing agent release
Elevator shunt trip C] Mass notification system ovenide of fire slam notification appliances
Other (specify):
12.1 Addressable Control Modules
Number of devices:
Other (specify):
13. SYSTEM POWER
13.1 Control Unit
13.1.1 Primary Power
Input voltage of control panel: 120 VAC
Overcunent protection: Type: Ckt Bkr
Location (of primary supply panel board): In Panel Room
Disconnecting means location:
13.1.2 Engine-Driven Generator
Location of generator:
Location of fuel storage:
0 This system doss not have control modules.
Control panel amps: 1.85A
Amps: 20
IM This system does not have a generator.
Type of fuel:
NFPA 72, Fig. 10.18.2.1.1 (p. 8.0? 12)
CcpyTI9M6 2009 HaVaid FffePm*danAvsaWkn This m ITy bs CX eCIittLot um a0w1ftr resote. It toy not be cxd for caena eornbuItott
13. SYSTEM POWER (conflnued)
13.1.3 Umnterruptlble Power System 0 This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system
Calculated capacity of UPS batteries to drive the system components connected to it-
In standby mode (hours): In alarm mode (minutes):
13.1.4 Batteries
Location: In Panel Type: Sealed Nominal voltage: I2VDC Amp/hour rating: 14Ah
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24 In alarm mode (minutes): 5
Batteries are marked with date of manufacture 0 Battery calculations are attached
13.2 In-BuildIng Fire Emergency Voice Alarm Communication System or Mass Notification System
This system does not have an EVACS or MNS system.
13.2.1 Primary Power
Input voltage of EVACS or MNS panel:
Overcurrent protection: Type:
Location (of primary supply panel board):
Disconnecting means location:
132.2 Engine-DrIven Generator
Location of generator.
Location of fuel storage:
EVACS or MNS panel anipar
Amps:
0 This system does not have a generator.
Type of fad:
13.2.3 Uninterruptlble Power System D This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it
In standby mode (hours): In alarm mode (minutes):
13.2.4 Batteries
Location: Type: Nominal voltage: Amp/hour rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
0 Batteries are marked with date of manufacture 0 Battery calculations are attached
NFPA 72, Fig. 10.18.2.1.1 (p.90112)
copyrIhte2009 NutIcsJ FftPAAecftnAs9odvftL This ftm ny be pisd ICr bIdMI ian if,ieie. ftnuy mt be xpied ?wnmeivI ss dsbtu5at
13. SYSTEM POWER (continued)
13.3 NotIfication Appliance Power Extender Panels 0 This system does not have power extender panels.
13.3.1 Primary Power
Input voltage of power rtender panel(s): 120 VAC Power extender panel amps: 2A
Overcwreat protection: Type: Ckt Breaker Amps: 20
Location (of primary supply panel board): In S3iflO rOOn as NAC Power Supply
Disconnecting means location:
13.3.2 Engine-Driven Generator R This system does not have a generator.
Location of generator.
Location of fire! storage: . Type of fuel:
13.3.3 Unlnterruptible Power System 0 This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to in
In standby mode (hours): In alarm mode (minutes):
13.3.4 Batteries
Location: in Panels Type: Sealed
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24
IN Batteries are marked with date of manutucture
Nominal voltage: 12 (24) Amp/hour rating 7
In alarm mode (minutes): 5
0 Battery calculations are attached
14. RECORD OF SYSTEM INSTALLATION
Fill out after all Installation Is complete and wiring has been checkedfor opens, shora groundfaults, and improper branching but before conducting operational acceptance tests.
This is n: D New system IM Modification to an existing system Permit number: FA120055
The system has been installed in accordance with the following requirements: (Note any or all that apply.)
IN NFPA 72, Edition: 2010
IN NFPA 70, National Fiectrical Code, Article 760, Edition:. 2008
Manufacturer's published instructions
Other (specify):
System deviations from referenced NFPA standards:
Signed: Printed name: Date:
Organization: Title: Phone:
NFPA 72, Fig. 10.182.1.1 (p. 10 of 12)
Copyright O2O9 Natlanal Ffre P tmXjiAaaoctatlan. Thl.rTn maybe ccpAdfbrbxjftWuwadwftmfbrraW@L it may trot be cplSd for cammeraI sabortwMAim
RECORD OF SYSTEM OPERATIONAL ACCEPTANCE TEST
13 New system
All operational features andfrndiong ofthLs system were tested by, or In the presence of; the signer shown below, on the date shown below. and were fow4 to be operatlngproperly in accordance with the requirements
for the following;
Modifications to an adstin system
All newly mothfted operationalfeatures andfunetlone ofthe system were tested by, Orin the presence of; the signer shown below, on the date shown below. and were found to be operating properly In accordance with the requirements ofthefollowing:
NFPA 72, Edition: 2010
NFPA 70, National Electrical Code, Article 160, Edition: 2008
IM Manufacturer's published instructions
Other (specify):
II Individual device testing docmeentation (Inspection and Testing Form (Figure 14.61.4) is attached]
Signed: Printed name: Date:
Orgntion Title: Phone:
CERTIFICATIONS AND APPROVALS
16.1 System Installation Contractor.
This system, as specified herein, has been installed and tested according to all NFPA standards cited herein.
Printed name: LEE HOPPER Date: 2-28-13
Organization: SDA SECURITY Title: FIELD SUPERVISOR Phone: 619.414-2844
16.2 System Service Contractor:
The undersigned has a service contract for this system In effect as of the date shown below.
4
Signed:
__
Printed name: LEE HOPPER
Organization: SDA SECURITY Title: FIELD SUPERVISOR
16.3 Supervising Station:
This system, as specified herein, will be monitored according to all NFPA standards cited herein.
Signed: name: LEE HOPPER
Organization: SDA SECURITY Title: FIELD SUPERVISOR
Date: 2-28-13
Phone: 619-4142644
Date: 2-28-13
Phone: 619414-2644
NFPA 72, Fig. 10.18.2.1.1 (p. 11 of 12)
Copight 02009 K.ticn.I Fhe ProtecXnAu.odian, ThTrcnn imybe xpedtuhidMduaI te athere ifarreselo. ft.my flat be oatsd for commethI udiibu5on.
It CERTIFICATIONS AND APPROVALS (continued)
16.4 Property or Owner Representative:
I accept this system as having been installed and tested to its specifications and all NFPA standards cited herein.
Signed: Printed name: Date:
Organization: Title: Phone:
163 Atitborlty Having Jurisdiction:
I have witnessed a satisfhctozy acceptance test of this system and find it to be installed and operating properly
in accordance with its approved plans and speciflcafion with its approved sequence of operatlons and with all NFPA stan cited herein.
Signed Printed name: eeP/ L 7(4#iJ Date Z. Z. Z8 15
Organization: Te:tjrfljjtg (I4jjE5#*tL Phone: 7 (.ô q9eds
NFPA 72, Fig. 10.182.1.1 (p. 12 of 12)