Job Address: 1815 ASTON AVE, CARLSBAD, CA 92008-7340
Permit Type: FIRE-Construction Commercial Work Class:
Parcel It: 2121201100 Track It:
Valuation: $0.00 Lot It:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Permit No: FPC2019-0272
Status: Closed - Finaled
Fire Alarm
Applied: 12/09/2019
Issued: 01/08/2020
Finaled Close Out: 05/13/2020
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check It: INSPECTOR: Maldonado, Adalmira
Plan Check#:
Project Title:
Description: JEU AND JONES LLC - REPLACE FACU TO CELLULAR COMMUNICATOR INSTEAD OF CURRENT POTS LINE
Applicant: FPContractor:
BAY ALARM COMPANY BAY ALARM COMPANY
TIM GIOUTLOS 8205 RONSON RD, U STE F
8205 RONSON RD, U STE F SAN DIEGO, CA 92111-2014
SAN DIEGO, CA 92111-2014 (858) 586-3803
(858) 231-6895
FEE AMOUNT
FIRE Sprinkler Monitoring $383.00
Total Fees: $383.00 Total Payments To Date: $383.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
8205 Ronson Rd. Ste F
San Diego, CA 92111
0119— (800) 470-1000
Contractor License # 880138
PROTECTED PREMISE
JETT & JONES LLC
FACP ROOM
1819 ASTON AVE
CARLSBAD, CA 92008
MONITORING COMPANY
Bay Alarm Company
5130 Commercial Circle
Concord, CA 94520
800-470-1000
California Alarm Operating License
Number: ACO28
EQUIPMENT SUPPLIER & INSTALLER
8205 Ronson Road, Suite F
San Diego, CA 92111 1(800)470-1000
Contractor License # 880138
DMP.COM 0 0 0 0 0 0 @DMPALARMS
XR150F(/XR55OF( FAR
FEATURES
Up to 562 two-wire smoke Eight communication paths
detector or fire initiating between the panel and
zones on XR550FC central station
Up to 142 two-wire smoke Built-in remote or
detector or fire initiating on-site firmware
zones on XR150FC upgrade capability
Up to .5 Amps 12 VDC 12,000 event buffer
smoke and auxiliary output
with OW protection French, Spanish and English
menus available
Up to .1 Amps 12 VD(
supervised bell output Multiple onboard status LEDs
Up to 506 fully Up to 100 output schedules
programmable Form C relays to control relays and panel
outputs
Serial Digital Dialer or (ID
reporting to multiple receivers 32 individual reporting
areas with common areas
Built-in 32-character LED
annunciator on panel door
Output groups deliver
maximum functionality
with easy programming
Onboard Network
Onboard 10/100
autosensing Ethernet or
Wi-Fi connection
Customizable check-in time
and retry time
Suitable for multi-site
applications
____ DMP.COM 0 0 0 0 0 0 @DMPALARMS
S
XR150FC AND XR550FC FIRE PANELS
The XR150DFC and XR550DFC provide
basic fire monitoring for any single
site application. The XR150DNFC and
XR550DNFC panels provide all the same
basic fire monitoring as the XR150DFC
and XR550DFC, enhanced by the
onboard Ethernet connection that allows
the use of Network Monitoring. Both
panels come fully assembled from the
factory with the following components:
Control Panel
The XR150FC and XR550FC Series
addressable fire panels provide
complete system control for local
NAC operation. Additionally, DACT,
NET, or Cell communication to the
central station are provided. The
microprocessor-based panel also
provides input for Class A zone
expansion, conventional and addressable
smoke detectors, pull stations, and heat
detectors.
Keypad Annunciator
The Fire Command Center mounted in
the door offers a 32-character full text
LCD readout that displays system events
and menu prompts, making it efficient
and easy to use.
Transformer and Enclosure
The 16 VAC, 56 VA wire-in transformer is
factory installed and features a built-in
PTC for power circuit protection.
FLEXIBLE COMMUNICATION
The XR150/XR550 Series of
commercial fire panels has transitioned
from dialer-focused communications
to a true network and cellular
communications approach by
providing stronger, multi-layered
panel communications that ensure a
constant link between the panel and
central station.
The unique DMP Serial 3 format
supports 16 or 32-character users,
zone and area names to decrease the
central station response time and limit
dependence on automation literal tables
for message conversion.
REMOTE ANNUNCIATOR
Install up to eight 630F remote
annunciators to meet the requirements
of virtually any installation.
NETWORK OR CELLULAR COMMUNICATION
Built-in 10/100 auto-sensing Ethernet
connection enhances both standard
and encrypted line security options.
Both UDP and TCP are supported. The
network option can be used as the
primary or backup path to the digital
dialer or cellular option.
The XR150FC and XR550FC Series
panels may be used with the 263
Series Cellular Communicators as the
primary path (no backup required) for
commercial fire installations.
The check-in and fail time settings
are programmed for five minutes.
As the backup path, the 263
communicator provides the security of
a communication link that continues to
function, even when landlines are cut or
compromised. The communicators can
be used as a stand-alone communicator
without the need for a backup. This
interface works over a variety of
carriers in the USA and Canada.
EIGHT COMMUNICATION PATHS
Configure up to eight communication
paths between the panel and central
station. Each path has its own
panel communication programming
parameters, and can be identified as
either primary or backup. This enables
installers to configure a reliable
communication link, offering greater
confidence that the panel will always
be connected to the central station.
COMMUNICATION FUNCTION DIAGNOSTICS
The enhanced diagnostic menu enables
technicians to check network and cellular
communication status, cell signal strength,
and e-mail status from the keypad.
12,000 EVENT MEMORY
Allows the user to view the last 10,000
door accesses or 2,000 system events
that occurred over the past 45 days.
FIRE ZONE PROGRAMMING
Program zones for fire, fire verify,
fire retard, presignal, cross zoning, or
fire supervisory. This flexibility allows
the ability to match individual zone
characteristics to the needs of any area
in the fire installation.
ZONE EXPANSION
The XR150FC and XR550FC provide
up to 574 zones, programmable for a
variety of fire applications. The system
provides Class B 12 VDC powered
zones, two on board and four on the 715
Module, plus eight panel burglary zones.
Up to 64 zones are available on 16
keypad addresses, and up to 100 zones
are available on each built-in LX-Bus
using expansion modules.
FIRE VERIFY
This is used primarily for smoke detector
circuits to verify the existence of an actual
fire condition. When a Fire Verify zone
initiates an alarm, the panel performs
a Sensor Reset. If any Fire Verify zone
initiates an alarm within 120 seconds after
the reset, an alarm is indicated. If an alarm
is initiated after another 120 seconds, the
cycle is repeated.
NOTIFICATION CIRCUIT EXPANSION
Easily add NAC outputs to the XR150FC/
XR550FC system. Up to three Class B
modules can be mounted within the
FACP. Model 865 or 866 Class B NAC
Modules may be combined with a power
supply to provide additional 4 Amp NAC
outputs. Use an 867 on the SLC Loop to
further expand NAC circuits.
FIRE DRILL AND ONE-MAN WALK TEST
Users can test fire notification bells
using the Fire Drill feature. A special
code is also available for installers to
test the system. The One-Man Walk test
allows a single technician to check the
panel response to fire, burglary, panic,
and supervisory zones.
BUILT-IN PROGRAMMER AND DIAGNOSTICS
No programming device is required,
enabling installers and service technicians
to fully program the system and run
diagnostics from any DMP LCD keypad.
Check the electrical state of zones, find
individual zone numbers, check the LX-
Bus for missing, overlapping and/or extra
zones, and much more, all from any DMP
LCD keypad.
FLASH UPDATABLE
The XR150FC and XR550FC panels
accept software updates using Remote
LinkTM software. This makes it easy to
perform the flash update remotely any
time new panel feature updates release.
1183-135R 1103-W
Wireless Rate of Rise Universal Transmitter
Heat Detector
s
Universal Transmitter
1184-W
Wireless Carbon
Monoxide Detector
FIRE PANELS
OUTPUTS
The XRI50FC and XR550FC allow the
use of two SPDT relay outputs and four
open collector outputs, which may be
activated by zone or system events,
by schedule, through the User Menu,
or when a card is presented. Output
Groups allow multiple outputs to
activate with a single event and/or can
be assigned to a particular user profile.
OUTPUT SCHEDULES
Achieve maximum system flexibility
with 100 programmable schedules that
simplify planning and operations. Control
any contact-activated device with
schedules that automatically regulate
relays and switched-ground outputs.
STATUS LIST
To provide maximum system flexibility,
fire zones may be programmed to
display at a specific keypad. In this
manner, all fire zones can be monitored
in one location, and other zones can
be programmed to display and be
monitored at different keypad locations.
REMOTE LINK
The Remote Link programming software
takes advantage of the easy-to-use
simplicity of Microsoft Windows. The
XR150FC and XR550FC panels include
an interface connection for installers to
use to connect a laptop computer.
COMMERCIAL WIRELESS FIRE DEVICES
The list of DMP wireless devices that
have earned the UL Commercial Fire
Listing include:
1103 Universal Transmitter: Two-input
transmitter typically used in commercial
burglary door or window applications.
1100R Wireless Repeater: Extends the
communication range of DMP receivers,
enabling physically larger, more reliable
wireless security systems.
1100X Wireless Receiver: The
1100X Receiver supports up to 500
transmitters and satisfies all wireless
applications.
1100XH High Power Wireless Receiver
Provides additional transmit and receive
amplification for improved performance
at greater distance or in harsh building
environments.
Commercial Smoke Detectors: The
1164 includes synchronized sounders,
and a tamper switch. The 1164NS is
for applications with existing sounder/
notification devices.
1183 Wireless Heat Detector: The 1183
Series is a reliable, ceiling-mount heat
sensor available in two versions. The
1183-135F responds if the temperature
exceeds 1350. The 1183-135R adds a
rate-of-rise feature that responds if
the temperature increases by 15°F per
minute or more.
1184 Carbon Monoxide Detector:
The 1184 Carbon Monoxide Detector
is the ideal choice for difficult-to-
wire locations, applications where
room aesthetics are critical, or where
hazardous materials are present.
The sensor provides an early alert of
potentially harmful levels of carbon
monoxide in residential or commercial
installations. In addition, it also transmits
trouble, tamper, and low-battery
messages to the panel.
Mini-Horn
Strobe
I
Sync Module
.
Motor Bell
Horn Strobe
I
Sync Module
1164-W
Commercial listed Smoke Detector
with Svchronized Sounder
850S
Manual Fire Alarm
Pull Station
1100XH-W
711 715-8 or 715-16
Zone Expansion Module Zone Expansion Module
FIRE PANELS
Keypads
630F LCD Remote Fire Command
Expansion Modules
710 Bus Splitter/Repeater
711 Single Zone Expansion
714 4-zone Class Expansion
714-8 8-zone Class-B Expansion
114-16 16-zone Class-B Expansion
715 4-zone 2-wire Smoke Expansion
715-8 8-zone 2-wire Smoke Expansion
715-16 16-zone 2-wire Smoke Expansion
716 Output Expansion, 4 Form C
relays 4 Open Collector Outputs
717 Graphic Annunciator: 20 Open
Collector Outputs
Cellular Communicators
263C COMA Cellular Communicator
263H HSPA+ Cellular Communicator
263HCAN HSPA+ Cellular Communicator
Canada
263L1E-V LIE Communicator for Verizon
263L1E-A LIE AT&T oming Soon)
Auxiliary Modules
860 Relay Output Module
865 Style WIX Notification Circuit
Module
866 Style W Notification Circuit
Module
867 IX-Bus Notification Circuit Module
869 Style D Class A Initiating Circuit
Module
893A Dual Phone line Module
Power Supplies
505-12/LX 5 Amps @12 VDC
505-121 5 Amps @12 VDC
505-12A 5 Amps @12 VDC
Pull Stations
850 Series Pull Stations
Smoke/Heat Detectors
2W-BIX Conventional Smoke
2W1-BLX Conventional Smoke/Heat
Accessories
210 Network Transient Suppressor
277 Commercial Fire Buzzer Module
300 Four-wire Harness
303 Silence/Reset Push Button
305 Plug-in Output Relay
306 Tamper Harness
307-S Screw-On Tamper Switch
3012 Clip-On Tamper Switch
335 Intrusion Siren
370 Lightning Suppressor
374 Surge Voltage Suppressor
381-2 18 Coax Extension
431 Output Harness
861 Power Distribution Module
Central Station Receivers
S(S-111 Network Enabled Receiver
compatible with central station
receivers that accept Standard
CID, DD, or DMP Serial 3
messaging
SCS-VR Virtual Receiver
Software only solution that runs
on a server for network IP and
cellular communications
DMP Wireless
1100X Receiver
1100XH High-Power Receiver
flOOR Repeater
1103 Universal Transmitter, External
Contact
1164 Wireless Smoke Detector with
Synchronized Sounder
1164NS-W Wireless Smoke Detector with
No Sounder
1183-135F Heat Detector
1183-135R Heat Detector
1184 Carbon Monoxide Detector
Computer Software
Remote Link Programming Software
Dealer Admin
System Specifications
Primary Power Onduded):
16 VAC 56 VA transformer
Secondary Power:
12 VDC Battery
Models: 365,366,368 or 369
Output Rating:
Bell Up to .1 Amps at 12 VDC
Smoke and Auxiliary Upto .5 Amps at 12 VDC
For installaff0ns total bell, smoke, and
auxiliary cannot weed L2 Amps using a56
VA transforrnec
Current Draw:
180mA
Enclosure.,
Material Cold-rolled steel (Red)
Ordering Information
XR1500FC-R XR15O Fire Control Panel
XR15ODNFC-R XR150 Fire Control Panel with
Network
XR55ODFC-R XR550 Fire Control Panel
XR55ODNFC-R XR550 Fire Control Panel with
Network
Listings and Approvals
California State Fire Marshal (CSFM)
New York FDNY
Refer to the XR15OFCIXR55OFC Compliance
Guide (LT-1330) and specific compliance
listings for installation and programming
requirements necessary to meet a particular
approval.
FCC Part 68
FCC Part 15
Underwriters laboratories (UI) Listed
ANSLIUL 864 Fire Protective Signaling
For additional information,
go to DMP.corrilCompliance.
800.641.4282 I DNP.com
2500 N. Partnership Blvd, Springfield, NO 65803
Designed, Engineered & Manufactured in
Springfield, NO using U.S. & global components
@2018 Digital Monitoring Products, Inc. I LT-13111 18143
-- SIJ% iJuiII -- - -
6.8 Power Requirements
During AC power failure, the X111 50FC/XR550FC Series panel and all connected auxiliary devices draw their power
from the battery. All devices must be taken into consideration when calculating the battery standby capacity. The
following table Lists the panel power requirements. You must add the additional current draw of keypads, zone
expansion modules, smoke detector output, and any other auxiliary devices used in the system for the total current
required. The total is then multiplied by the number of standby hours required to calculate the total ampere-hours
required.
Standby Battery Power Calculations Standby Current Alarm Current
XR150FC/XR550FC Series control Panel Qty 1 x 174mA 174 mA Qty 1 x 217mA 217 mA
Relay Outputs 1-2 (ON) Qty _______ 30mA ______ Qty _______ 30mA
Switch Grounds 3-6 (ON) Qty _______ 5mA Qty _______ 5mA
Active Zones 1-8 Qty _______ 1.6mA Qty _______ 2mA*
Active Zones 9-10 Qty _______ 4mA Qty _______ 30mA
2-Wire Smoke Detectors Qty ______ 0.1mA Qty ______ 0.1mA
Panel Bell Output 1500mA ______mA
893A Dual Phone Line Module Qty x 12mA Qty x 50mA
263C CDMA Cellular Communicator Qty x 13mA Qty _______ x 13mA
263H HSPA+ Cellular Communicator Qty x 24mA Qty x 28mA
277 Buzzer Module Qty x 5mA Qty x 5mA
1100X Wireless Receiver Qty x 46mA Qty x 46mA
1100XH Wireless High Power Receiver Qty x 160mA Qty x 160mA
860 Relay Output Module (one relay active) Qty x 34mA Qty x 34mA
All four relays active 138mA 138mA
865 Style Y or Z Notification Module Qty x 26mA Qty x 85mA
866 Style W Notification Module Qty x 45mA Qty x 76mA
867 LX-Bus Style W Notification Module Qty x 30mA Qty x 86mA
869 Dual Style D Initiating Module Qty x 25mA Qty x 75mA
630F Remote Fire Command Center Qty x 63mA Qty x 92mA
7060/7160 Thinline/7060A Aquafite Keypad Qty x 72mA Qty x 80mA
7063/7163 lhinLine/7063AAqualite Keypad Qty x 85mA Qty x lOOmA
7070/7170 Thinline/7070A Aqualite Keypad Qty x 72mA Qty _______ x 87mA
Active Zones (EOL Installed) 1.6mA Qty x 2mA*
7073/7173 Thinline/7073AAqualite Keypad Qty x 85mA Qty x lOOmA
Active Zones (EOL Installed) 1.6mA Qty _______ x 2mA*
7872 Graphic Touchscreen Keypad Qty x 145mA Qty x 215mA
Active Zones (EOL Installed) 1.6mA Qty x 2mA*
7873 Graphic Touchscreen Keypad Qty x 143mA Qty x 243mA
Active Zones (EOL Installed) 1.6mA Qty x 2mA*
734 Wiegand Interface Module Qty x 15mA Qty x 15mA
Active Zones (EOL Installed) Qty x 1.6mA Qty x 2mA*
Annunciator (ON) Qty x 20mA
734N Wiegand Interface Module Qty x 146mA Qty x 148mA
Active Zones (EOL Installed) Qty x 1.6mA Qty x 2mA*
Annunciator (ON) Qty x 20mA Wiegand Reader Qty x 200mA Qty x 200mA
Copy Sub-Totals to next page Sub-Total Standby ______mA Sub-Total Alarm ______mA
*Based on 10% of active zones in alarm.
Digital Monitoring Products XRI50FC/XR550FC Series Installation Guide
10
Standby Battery Power Calculations Standby Current Alarm Current
736P POPIT Interface Module Qty x 25mA Qty x 25mA
Radionics Popex, POPITs, OctoPOPITs Qty x _mA Qty x _mA
738A Ademco Wireless Interface Module Qty x 75mA Qty x 75mA
710 Bus Splitter/Repeater Module Qty x 32mA Qty x 32mA
711 Zone Expansion Module Qty x 11 mA Qty x 11 mA
Active Zone (EOL Installed) Qty x 1.6mA Qty x 2mA
714 Zone Expansion Module Qty x 7mA Qty x 7mA
Active Zones (EOL Installed) Qty x 1.6mA Qty x 2mA*
712-8 Zone Expansion Module Qty x 17mA Qty x 17mA
Active Zones (EOL Installed) Qty x 1.6mA Qty x 2mA*
714-8, 714-16 Zone Expansion Module Qty x 20mA Qty x 20mA
Active Zones (EOL Installed) Qty x 1.6mA Qty x 2mA*
715 Zone Expansion Module Qty x 7mA Qty x 7mA
Active Zones (EOL Installed) Qty x 4mA Qty x 30mA*
2-Wire Smokes Qty x .1mA Qty ______ x .1mA
715-8, 715-16 Zone Expansion Modules Qty x 20mA Qty x 20mA
Active Zones (EOL Installed) Qty x 4mA Qty x 30mA*
2-Wire Smokes Qty x .1mA Qty x .imA
716 Output Expansion Module Qty x 13mA Qty x 13mA
Active Form C Relays Qty x 12mA
717 Graphic Annunciator Module Qty x lOmA Qty x lOmA
Annunciator Outputs Qty _______ x 1 mA
521 LX, 521LXT Smoke Detectors Qty x 8.8mA Qty x 28mA*
2W-BLX, 2WT-BLX Smoke Detectors Qty x ilmA Qty x 31mA*
COSMOD2W Module Qty x 45mA Qty x 174mA*#
COSMO-2W Smoke and CO Detectors Qty x 1 mA Qty x 50mA*#
Aux. Powered Devices on Terminals 7 and 11 mA ______mA
Other than Keypads and LX-Bus Modules
Sub-Totals this page Sub-Total Standby ______mA Sub-Total Alarm mA
Sub-Totals from previous page Sub-Total Standby ______mA Sub-Total Alarm ______mA
*Based on 10% of active zones in alarm Total Standby mA Total Alarm ______mA
# For systems that are not central station monitored, multiply alarm current by 12.
Total Standby mA x number of Standby Hours needed ______ = _______mA-hours
Total Alarm mA + mA-hours
Total _______mA-hours
X ooi
= Amp-hrs Required
Refer to section 6.9 for standby battery selection.
I
XRI50FC/XR550FC Series Installation Guide Digital Monitoring Products
DMP.COM 0 0 0 0 0 0 @DMPALARM$
Digital Cellular Communicators
263EXT
XR Series
FEATURES
Plug-and-play installation
and activation of add-on
communication modules
Direct reporting to any
DMP monitoring center
receiver with no relaying or
intermediary retransmission
of alarm signals
Power from panel with low
current draw for long standby
battery life
Fully supervised to ensure
communication
Can be equipped with local or
remote antenna
Check signal strength
indication at the keypad
Supports the DMP Virtual
Keypad" app
XR550E provides privacy
for your data with DMP
encryption technology
XRI5DFC/XR550FC with 263
Series communicators have
FDNY approval for network or
cell primary communication
DMP Adaptive Technologytm
switches communication
paths while maintaining
supervision if the current
path becomes unavailable on
the XR Seriestm panels
263EX1 Cellular Extension
Modules extend cellular reach
up to 300 feet using a single
wired connection without
losing dB strength
CELLULAR COMMUNICATORS
PRIMARY OR BACKUP PATH
Configure your DMP digital cellular
communicator as the primary path, providing
installation flexibility and cost savings. For
commercial fire applications, the 263LTE
can be used as a stand-alone communicator
without the need for a backup.
Cellular is the right choice for locations
not easily reached by phone or land lines,
or where there are concerns that physical
communication links might be tampered
with. Your cellular communicator can also
be a backup communication path, providing
the security of a communication link that
continues to function, even when land lines
are cut or compromised.
FULLY SUPERVISED
You're kept fully informed of system status.
The unit sends full reporting messages
including Zones, Areas, and Users, with all
names and details included. Full supervision
ensures that the cellular communication path
is intact and functional.
ADAPTIVE TECHNOLOGYN
If the primary communication path is
compromised or becomes unavailable,
Adaptive Technology almost instantly switches
to a designated backup path. Where multiple
backups are available, communications can
be programmed to switch to another path
as necessary. The check-in frequency and
programming for a backup path adapt to the
check-in programming of the primary path.
When the primary path becomes available,
normal communications are restored. Adaptive
Technology provides additional confidence in
the integrity of your system, while protecting
you from unexpected cellular service charges.
DIRECT DATA TRANSMISSION
The digital cellular communicators transmit
IP data packets directly from the panel's
processor over the LTE wireless data
network. All of the messages that are
capable of being sent by the control panel
are received directly by the DMP monitoring
center receiver. There are no intermediary
servers or network operation centers, and
no retransmission or reinterpretation of the
information. Direct reporting means faster
response, with no concerns about signals
not being properly relayed or intermediate
communication links failing.
CELLULAR SERVICE FLEXIBILITY
With SecureCom WirelessT from DMP, you
have a one-stop resource for both hardware
and cellular service. DMP digital cellular
communicators, whether selected as original
equipment in a new panel or added to an
existing panel via an expansion card, are
ready to use the SecureCom service.
VIRTUAL KEYPAD` APP
The DMP app provides users with the ability
to access a number of system functions
remotely via a cellular or Internet connection.
As a dealer, you can brand the app using
your company logo.
VIRTUALKEYPAD.COMT°
Users can access their security system via
Internet connection on a tablet or computer.
Customers log into VirtualKeypad.com with
their login and system user code.
263LTE CELLULAR COMMUNICATORS
For existing XT/XR Series panels not
originally configured with cellular
communications, the 263 Series expansion
cards let you add cellular capabilities.
The 263LTE allows alarm messages to be
communicated to an SCS-1R or SCS-VR
Receiver over their respective HSPA+ or LTE
networks. It provides a fully supervised alarm
communication path over the network.
The 263LTE is installed in the panel enclosure
and powered by the panel so no additional
enclosure, power supply, or battery backup
is needed. Plug-and-play installation makes
upgrading your panel quick and easy. The
263LTE includes an embedded SIM card for
easy activation. All modules are ready for
activation with SecureCom Wireless.
263EXT CELLULAR EXTENSION MODULES
The 263EXT comes with a module that
installs directly on the control panel inside
the enclosure. Also included is a second
remote module to install with a cell modem
in the attic or wherever signal strength is
best. Between the two, you can have up to
300 feet of continuous reach with a CATS
cable or 22 AWG shielded wire. The modules
communicate with each other through a single
wired connection, maintaining dB signal.
With DMP's 263EXT Cellular Extension
Modules, you can extend cellular reach
without losing a single dB. The modules are
compatible with all 263 type modems and
with all XT and XR Series panels.
265LTE CELLULAR COMMUNICATORS
XTLpIus Series panel users can plug in the
265LTE cellular communicators to quickly and
easily incorporate cellular communications.
In the panel plastic, it requires no additional
enclosures, power supplies, batteries, cabling,
or conduit connections. The 265LTE contains
LTE technology. It includes an embedded SIM
card for easy activation. All modules are ready
for activation with SecureCom Wireless.
Specifications
Primary Power 12 VD( from panel
Current Draw (26311E)
Standby 14 mA
Alarm 14 mA
Current Draw (2651T
Standby 13 mA
Alarm 13 mA
Ordering Information
26311E-W381-2 A1&TLTelkilarCommu,Xm(RSers
26311E-A AT&T Cellular Communicator, XT Series
265LTE-A AT&T Cellular Communicator, XTI.plus
263LTE-V Wrizon LTE Cellular mmuracatoXtfl(RSeries
263EXT Cellular Extension Modules, XTIXR Series
265LTE-V Verizon LIE Cellular Communicator, XlLplus
Accessories
381-2 18' Coax Extension
381-12 17 Coax Extension
381-25 25' Coax Extension
383 Dual Band Antenna
386 Wall Mount Antenna Bracket
387-2 2 dB Attack Enclosure Antenna
387-4 4' SMA to N Extension Cable
387-8 1SMA to N Extension Cable
387-25 SMATO N CABLE, 25F1, LMR195
387-50 SMATO N (ABLE, 50F1 LMR195
388-1 3dB Fiberglass Antenna w/bracket
388-2 2 d Attack Enclosure Antenna
388-3 3 d MEG Antenna
Certifications
California State Fire Marshal ((SFM)
New York City (FDNY COA #6167)
Underwriters Laboratodes(UL)
Underwriters Laboratories Canada (ULC)
For additional information, visit DMP.com
and select Compliance.
800-641-4282 I DMP.com
2500 N. Partnership Blvd, Springfield, 110 65803
Designed, engineered & manufactured In
Springfield, NO using U.S. & global components
LIMITED WARRANTY: DMP warrants that the
products manufactured by DMP and described
herein shall be free from defects of manufacture,
labeling, and packaging for a period of three
(3) years from the Invoice date to the original
Buyer, provided that representative samples
of the defective products are returned to DMP
for Inspection ... To read the full DMP Limited
Warranty, go to DMP.com/Warranty or check the
DMP Price List or Catalog.
© 2019 Digital Monitoring Products, Inc. I LT-1017 119094
Simple Expansion
lutions
" = I A *!-*"X9
SECURITY
SIGNAUNG
LISTED
Expand your DMP panel options with a wide array of
expansion modules.
Add supervised Class B burglary zones.
Connect non-powered burglary or fire type
devices for intrusion, glassbreak, and motion
detection.
Add 12 VDC zones for addressable 2-wire smoke
detectors with 715 modules.
ZONE EXPANSION MODULES:
SINGLE AND MULTIPLE POINT
ZONE EXPANSION MODULE FEATURES
Provides Class B zones for burglary and fire
Compatible with DMP Panels that allow zone expansion
Suitable for mounting near protection devices
Connect devices using 4-wire bus
Proven design ensures stability and performance
Data LED on zone expander indicates good panel
communication
Durable and attractive plastic or metal housing
t.'J E §=_3CIF:WAa&"S1CPW4
USE ON THE DMP LX-BUSTM 708 BUS EXTENDER MODULES 710
The modules can be used on the LX-Buslm The 708 Bus Extender Modules allow you As a spLitter, the 710 provides superior
of DMP Panels. The modules connect to to increase the Length of wire used to run mechanical wire connecting capability
the 4-wire bus and use only one zone an LX-Bus or keypad bus by a maximum of for up to three additional 12 VDC LX-
address. To assign an additional zone 4,000 feet, while providing immunity to Bus or keypad bus circuits. This makes
expander use the next available zone noise on the wires. The 708 Bus Extenders the 710 module an excellent junction
address. are received from the factory as a pair of box when terminating multiple LX-Bus/
mrvli iIc thit rnnnrt htwn thin nnI kunrI hi Ic ri inc nt nnio InrHnn r' •S7
and LX-Bus or keypad bus devices. CONNECT TO KEYPAD BUS
You can also use the modules as an
addressed device on the keypad data
bus of DMP Command Processor panels.
Simply set the module to an available
keypad address and connect the wiring
to the appropriate screw terminals.
SIMPLE ADDRESSING
Address the 711, 714, 714-8, 714-16, 715,
715-8, and 715-16 modules by setting
two on-board rotary switches with a
small screwdriver. The 712-8 uses slide
dip switches.
EASY INSTALLATION
Zone Expansion Modules are mounted in
a decorative plastic housing suitable for
installing outside the panel enclosure,
such as on walls or single gang boxes.
After ail wiring connections are made,
the covers go on to form tight-fitting
protection against incidental contact or
tampering.
714-8, 714-16, 715-8, and 715-16 Zone
Expanders are housed in a rugged,
20-gauge, cold-rotted steel enclosure.
You may also mount the 708 and 710
modules inside a DMP enclosure using
the 3-hole configuration and the provided
standoffs. The 712-8 only mounts using
the 3-hole configuration and provided
standoffs.
ZONE PROGRAMMING
Program the zone on the modules with
any of the panel's available zone types
for use in burglary applications including
Arming type zones when used with
keyswitches.
The expansion zones are programmable
for annunciation on DMP keypads
connected to the panel. Each zone
can also be individually programmed to
report alarms, troubles, and restoraLs to
remote DMP SCS-1 R Receivers.
Use the 708 Modules for applications
that include running wire over Long
distances, through noisy environments,
or where the bus is bundled with other
wires, such as telephone company wire.
The 708 Extender can be used on all DMP
panels.
708 FEATURES
Extends Keypad Bus or LX-Bus by
4000 feet with one pair of modules
Connects to an auxiliary power
supply for added power
Uses existing wire: No need to run
additional wire
Allows twisted pair and/or shielded
wire between the 708 modules
710 BUS SPLITTER!
REPEATER MODULE
The 710 Bus SpLitter/Repeater Module
allows you to expand the typical LX-Bus
or Keypad bus installation both in the
number of devices and the Length of the
wire used. Each 710 Module provides
three bus connections each up to 2,500
feet. When using multiple modules, the
total distance of ail circuits can be an
incredible 15,000 feet!
As a repeater, the 710 module can be
installed at the end of an LX-Bus or
keypad bus circuit to allow an additional
circuit to be added, thus increasing the
total wire Length.
712-8 ZONE EXPANSION
MODULE
Expand your system at an affordable
price! You can connect non-powered
burglary devices to DMP Command
Processor panels using the 712-8 Module.
The 712-8 Module is compatible with
many intrusion contacts, gLassbreak
detectors, motion detectors, and
intrusion detectors.
712-8 FEATURES
Eight grounded, addressable burglary
zones
Set jumper for LX-Bus or Keypad bus
operation
Compatible with all DMP panels
Expand systems by daisy chaining a
second 712-8
Easily address using dip switches
Snaps into panel enclosure using
3-hole pattern
Separate zone 1K End-of-Line
resistors included
SI-F
-
7141715 ZONE EXPANDERS 714-8, 714-16, 715-8,AND 714-8,714-16,71 S-8, AND
The 714 contains four Class B burglary 715-16 DESCRIPTION 715-16 FEATURES
zones and is suitable for use with burglary The expanders are housed in a Model 8 or 16 protection zones per
and fire devices that are normally opened 340 Locking metal enclosure suitable expander
or normally closed. Individual zones are for mounting in a remote location. Durable metal enclosure housing
supervised with 1k Ohm EOL resistors and Each expander provides screw terminal with lock and key
can be programmed with any burglary or strips for zone inputs and data bus Individual screw terminals
fire zone type. connections, a two position jumper to accommodate 14 to 22 gauge wire
The 715 contains four Class B powered designate connection to the keypad bus for easy connection
zones and is suitable for use with 12 VDC, or the LX-Bus, and an LED to indicate Suitable for mounting in a remote
2-wire smoke detectors and non-powered communication with the panel. Separate location
fire or burglary devices. Individual zones zone End-of-Line resistors are included 711 DESCRIPTION
on the 715 are cunervict1 with a 3 3k with each expander.
Ohm EOL resistor and can be programmed
with any burglary or fire zone type.
OPTIONAL ACCESSORIES
The standard wiring harness can be
replaced with the optional 718T Plug-in
Screw Terminal.
The enclosure can also accommodate the
719T Terminal Boards for the 714 or the
720T Terminal Boards for the 715, which
pass through the wiring of the panel's
LX-Bus. 1K EOL resistors are included
with the 719T and 3.3K resistors are
included with the 720T.
7141715 FEATURES
Four protection zones on each
module
Comes with 12-conductor wire
harness
Optional 12-position screw terminal
714-81714-16 EXPANDERS
The 714-8 Expander contains 8 Class B
zones. The 714-16 Expander contains 16
Class B zones. Both are suitable for use
with normally open or normally closed
burglary and fire devices. Individual
zones are supervised with a 1k Ohm EOL
resistor and can be programmed as any
zone type.
71 S-8/7 1 5-16 EXPANDERS
The 715-8 Expander contains 8 Class B
powered zones. The 715-16 Expander
contains 16 Class B powered zones.
Both are suitable for use with 12 VDC
2-wire devices, such as smoke detectors
or with non-powered fire or burglary
devices. Individual zones are supervised
with a 13k Ohm EOL resistor and can be
programmed as any zone type.
I ne I II Lone Expansion avioaute connects
to the panel's 4-wire Keypad bus or
LX-Bus and are set to an address that
determines the reporting zone number.
The 711 provides one Class B zone for the
connection of detection devices.
711 FEATURES
Single-zone expander
Rugged screw terminals
accommodate 14 to 22 AWG
Board fits in Radionics POPIT housing
Easy rotary switch addressing
Nil
Digital Mon1tau4ng Praducta
I
.• E ___
ZONE EXPANSION MODULE COMPARISON CHART
Refer to the chart below for a comparison of the features for each DMP Zone Expansion Module.
Module Address Number of
Zones 3-Hole Plastic Case Operating
Voltage Compatible Panels
708 N/A N/A Yes Yes 12 VDC ALL DMP 12 VDC 710 N/A N/A Yes Yes
712-8 Dip Switch 8 Yes No 12 VDC
XT Series and XR100/XR500 Series
12 VDC
711 Rotary 1 No Yes 12 VDC
714 Rotary 4 Class B No Yes 12 VDC
714.8 Rotary 8 Class B No Metal Enclosure 12 VDC
714-16 Rotary 16 Class B No Metal Enclosure 12 VDC
715 Rotary 4 Class B No Yes 12 VDC
715-8 Rotary 8 class B No Metal Enclosure 12 VDC
715-16 Rotary 16 Class B No Metal Enclosure
MODULE SPECIFICATIONS 7141715 SPECIFICATIONS
708 SPECIFICATIONS (NON-UL) Operating Voltage 8.8 to 15.0 VDC
Operating Voltage 8.8 to 15.0 VDC Operating Current
Operating Current 20mA Per Pair 714 Average 7mA + 1.6mA per zone
Dimensions 4.5" X 2.75" X 1.75" Alarm 7mA + 2mA per zone
Maximum Distance 4,000 feet between the two 715 Average 7mA + 4mA per zone + 0.1 per 2-wire smoke
708 Modules Alarm 7mA + 58mA per shorted zone + 0.1 per
710 SPECIFICATIONS 2-wire smoke + 30mA per smoke in alarm
Operating Voltage 8.8 to 15.0 VDC Dimensions 4.5" X 2.75" X 1.75"
Operating Current 7148, 714-16, 71 58, AND 71 516 SPECIFICATIONS
710 30mA Operating Voltage 8.8 to 15.0 VDC
Dimensions 45" X 2.75" X 1.75" Operating Current
Distance 2,500 feet (one module), 714-8/16
15,000 feet maximum Average 20mA + 1.6mA per zone
711 SPECIFICATIONS Alarm 20mA + 2mA per zone
Operating Voltage 8.8 to 15.0 VDC 715-8/16
Operating Current Average 20mA + 4mA per zone + 0.1 per 2-wire smoke
Average 11 mA + 1.6mA per active zone Alarm 20mA + 58mA per shorted zone + 0.1 per
Alarm 11 mA + 2mA per zone in alarm 2-wire smoke + 30mA per smoke in alarm
Zone Voltage 5 VDC (1.6mA across EOL) Enclosure 20-Gauge cold-rolled steel
Dimensions 4.5" X 2.75" X 1.75" Dimensions 12.5" W x 11.5" H x 35" D
7 14-8/-16 Color Gray
712-8 SPECIFICATIONS 715-8/-16 Color Red
Operating Voltage 8.8 to 15.0 VDC LISTINGS AND APPROVALS Current Draw 17mA + 1.6mA per active zone Refer to the appropriate panel programming and installation guide 17mA + 2mA per zone in alarm for specific compliance listings for installation and programming
Dimensions 4.5" H x 2.5" W requirements necessary to meet a particular approval.
California State Fire Marshall (CSFM)
New York City (FDNY COA#6055) (711, 714, 715 only)
Underwriters Laboratories (UL) Listed
For additional information, access www.dmp.com and select
Compliance.
p e1VAIflSLlWCSY fl.ppwpfl fl ap r .
2500 North Partnership Boulevard
Nil
Waftel Munftorft Pr=Wcft M a d e tIiI t he USA Springfield, Missouri 65803-8877
mm
Contents
ZONE EXPANSION MODULE FEATURES 1
USE ON THE DMP LX-BUSTm 2
CONNECT TO KEYPAD BUS 2
SIMPLE ADDRESSING 2
EASY INSTALLATION 2
ZONE PROGRAMMING 2
708 BUS EXTENDER MODULES 2
710/710F BUS SPLITTER/REPEATER MODULES 2
712-8 ZONE EXPANSION MODULE 2
712-8 FEATURES 2
714/715 ZONE EXPANDERS 3
714-8, 714-16, 715-8, AND715-16 DESCRIPTION 3
725 24 VDC EXPANSIONMODULE 3
711 DESCRIPTION 3
711 FEATURES 3
ZONE EXPANSION MODULE COMPARISON CHART 4
MODULE SPECIFICATIONS 4
LISTINGS AND APPROVALS 4
SYSTEM ~ OF I& ~4, SENSOR®
Photoelectric
Smoke Detectors
System Sensor's j3" series smoke detectors repres
significant advancement in conventional detecti
The j3 family is founded on three principles: insta
ease, intelligence, and instant inspection.
Features
Plug-in detector line, mounting base included
Large wire entry port
In-line terminals with SEMS screws
Mounts to octagonal and single-gang backboxes, 4-square
backboxes, or direct to ceiling
Stop-Drop 'N Lock attachment to base
Removable detector cover and chamber
Built-in remote maintenance signaling
Drift compensation and smoothing algorithms
Simplified sensitivity measurement
Wide angle, dual color LED indication
Loop testing via EZ Walk feature
Built-in test switch
Agency Listings
Installation ease. The i3 line redefines installation ease with its
plug-in design.This allows an installer to pre-wire the bases included
with the heads. The large wire entry port and in-line terminals
provide ample room for neatly routing the wiring inside the base.
The base accommodates a variety of back box mounting methods,
as well as direct mounting with drywall anchors.To complete the
installation, P heads plug in to the base with a simple Stop-Drop 'N
Lock' action.
Intelligence. i3 detectors offer a number of intelligent features
to simplify testing and maintenance. Drift compensation and
smoothing algorithms are standard with the i3 line to minimize
nuisance alarms.Two-wire i3 detectors needing cleaning can
generate a remote maintenance signal, when connected to the
2W-MOD2 loop test/maintenance module, or to a panel equipped
with the i3 protocol.This signal is indicated by LEDs located at the
module and the panel. The SENS-RDR, a wireless device, displays the
sensitivityof P detectors in terms of percent per-foot-obscuration.
Instant inspection. The i3 series provides wide-angle red and
green LED indicators for instant inspection of the detector's
condition: normal standby, out-of-sensitivity, alarm, or freeze trouble.
When connected to the 2W-MOD2 loop test/maintenance module
or a panel with the P protocol, the EZ Walk loop test feature is
available on two-wire i3 detectors. This feature verifies the initiating
loop wiring by providing LED status indication at each detector.
@
LISTED <~> A
APPAWM
S911 3011446 7272-1209:210
MEAMSFM
approved approved
290-01-E 2093
(j, Smoke Detector Specifications
Smoke detector shall be a System Sensor il Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The
detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F
(57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal, single gang, and 4-inch square back boxes with a plaster
ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of
the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.
The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide
dual color LED indication which blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When
used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control
panel, and shall provide a loop testing capability to verify the circuit without testing each detector individually.
Operating Voltage Nominal: 12/24V non-polarized
Minimum: 8.5V
Maximum: 35V
Maximum Ripple Voltage 30% peak to peak of applied voltage
Standby Current 2-wire: 50 pA maximum average; 4-wire: 50 pA maximum average
Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12V, 23mA @ 24V
Peak Standby Current 2-wire: 100 pA; 4-wire: n/a
Alarm Contact Ratings 2-wire: n/a; 4-wire: 05 A @ 30V AC/DC
Physical Specifications
Dimensions (including base) 53 inches (127 mm) diameter; 2.0 inches (51 mm) height
Weight 6.301(178 grams)
Operating Temperature Range 2W-B and 4W-B: 32°F-1 20°F (0°C-49°C); 2WT-B and 4WT-B: 32°17-1 00°F (0°C-37.8°C)
Operating Humidity Range 0 to 95% RH non-condensing
Thermal Sensor 135°F (57.2°C) fixed
FreezeTrouble 2WT-B and 4WT-B only: 41°F (5°C)
Sensitivity 2.5%/ft. nominal
Input Terminals 14-22 AWG
Mounting
lT LED IModes
LED Mode Green LED
31/2-inch octagonal back box
4-inch octagonal back box
Single gang back box
4-inch square back box with a plaster ring
Direct mount to ceiling
Power Up Sequence for LED Indication
Red LED Condition Duration
Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds
Normal (standby) Blink every 5 seconds off
Out of sensitivity off Blink every 5 seconds
Freeze trouble off Blink every 10 seconds
Alarm off Solid
Ordering Information
Model Thermal
2W-B No
Wi ring Alarm Current
2-wire 130 mA max. limited by control panel
2WT-B Yes 2-wire 130 mA max. limited by control panel
4W-B No 4-wire 20 mA @i2V, 23mA © 24V
4WT-B Yes 4-wire 20 mA © IN 23mA © 24V
Accessories
2W-MOD2 2-wire loop test / maintenance module RT Removal / replacement tool
SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 in. (16.76cm) diameter
s$
&S"Y'aS7E1I1
SENSOR
3825 Ohio Avenue St. Charles, IL 60174 02006
Sys ern Sensoi.
Phone: 800-SENSOR2. Fax: 630-377-6495 current product info nnation, including the latest version ofthts data sheet.
I
CUSTOM DOCUMENT ENCLOSURE
Modified Mier BW-106R for Bay Alarm
12W x 12"H x 4"D
Durable Red Texture Powder-Coat
SYSTEM RECORD DOCUMENTS" graphic printed in
white, on two lines, on the door
Rugged construction & 10.5-inch, one-piece, piano hinge
for added strength
Key holes for quick and easy mounting
1/4-Turn Thumb-Latch installed, as well as holes in place
for bolting the door shut. Will also work with Mier's cam
locks
Two electrical knockouts on left side, right side, and back
as well as one electrical knockout on top and on bottom
Additional customization of this enclosure, or assistance in
designing a new model, including color and/or graphics, is
available by calling or emailing Mier Productslnc.
(
-J --.
1 L1fl
-
800-473-0213 1 info@mierproducts.com I www.mierproducts.com
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL _____
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-1157:0135 Page 1 of 2
CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Digital Monitoring Products2500 N. Partnership Blvd, Springfield, MO 65803
Contact: Brad Tucker (417) 831-9362 Fax (417) 831-1325
Email: btucker@dmp.com
DESIGN: Models XRI50, XR350 and XR550 combination fire and burglary alarm control units. Local,
remote station, proprietary and central station services. Models may have a combination of
the following suffixes: D (dialer), N (network), E (encryption) or FC (fire control). Refer to
listee's data sheet for additional detailed product description and operational considerations.
System components:
XRI50, XR350, XR550: Main Board
341, 349, 350, 350A, 352P 352X: Enclosures
352S: Battery Enclosure
630F: Supervised LCD Keypad
7070, 7070A, 7073, 7073A, 7170, 7170A, 7173, 7173A, 7570, 7570A, 7573, 7573A: LCD
Keypads
325: Transformer Bracket
322, 323, 324, 324P, 327: Transformers
711, 714, 714-8, 714-16, 715, 715-8, 715-16: Zone Expanders
*711 S: Zone Expander (NOT for use with XR350)
Output Expander
Annunciator Module
860 Relay Module
893A: Dual Phone Line Module
734, 734N: Wegand Interface
710: Bus Splitter
270: Network Transient Suppression Module
277: Trouble Sounder
9060, 9063: Wreless Keypads
263C, 263H: Cellular Communicator (May be used as the standalone primary communicator)
263L1E: Cellular Communicator (NOT for use with XR350) (May be used as the standalone
primary communicator)
865, 866, 867: Indicating Module
869: Initiating Module
303: Reset/Silence Switch
IlOOX, IIOOXH: RF Wreless Receiver
IlOOR: Wreless Repeater
1103: Wreless Transmitter
*Rev 04-05-19 gt
* This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing No. 7165-1157:0135
Page 2 of 2
1135: Wireless Siren
RATING: 120 VAC, 0.5 A, 60 Hz
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, rating and UL label.
APPROVAL: Listed as combination fire and burglary alarm control units for use with separately listed
electrically compatible initiating and indicating devices. Refer to listee's Installation
Instructions Manual for details.
NOTE: 1. The Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed-30 seconds.
2. Burglary and other non-fire functions were not examined.
*Rev 04-05-19 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator U
Fire Engineering Division
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL _____
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-1653:0152 Page 1 of 1
CATEGORY: 7272 - SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: System Sensor, Unincorporated Div of Honeywell Intl Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309
Email: megan.sisson©honeywell.com
DESIGN: Models 2W-B, 2WT-B, 4W-B and 4W1-B photoelectric type smoke detectors. Models 2W-B
and 2WT-B are 2-wire and model 4W-B and 4WT-B are 4-wire detectors. Models 2WT-B and
4WT-B employ a thermistor type heat sensor (1350F). The heat sensor is are supplemental
to the detector and is not intended for use as a required heat detector. Refer to listee's
printed data sheet for additional detailed product description and operational considerations.
RATING: 8.5-35 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. For vertical wall or ceiling
mount
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm
control units. Suitable for installation in open areas with air velocity range from 0-1000 ft/mm.
NOTE: Formerly 7272-1209:210
06-20-05
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division