Bulletin 136 Rev.L
neli ble Model Fl FR
Model F1FR Recessed
Quick Response
Sprinklers
CD
CD
-S
0) 0)
CD
I-
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model Fl FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters' Laboratories of Canada (ULC)
Certified by FM Approvals
Loss Prevention Council (LPC, UK)
NYC BS&A No. 587-75-SA
Meets MIL-S-901C and MIL-STD 167-1
Verband der Schadenversicherer (VdS, Germany)
NYC MEA 258-93-E
I UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV
Product Description
Reliable Models F1FR and F1FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models Fl FR and Fl FR Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are five
to ten times faster than standard response sprinklers. This
quick response enables the Model Fl FR and Fl FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manufac-
tured glass capsule. This glass bulb is specially constructed to
provide fast thermal response. The balance of parts are made
of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
Upright Pendent
Vertical Sidewall Conventional
Horizontal Sidewall
HSW 1 Deflector Recessed Pendent
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
NZ
Mode! Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Sprinkler Type
Standard-Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
K Factor Sprinkler
Height
Approval
Organization
Sprinkler Identification
Number(SIN) US Metric SSU SSP
)' (15mm) Standard Orifice with )" NPT (R)) Thread 5.6 80 2.2' (56mm) 1,2,3,456,7 R3625 R3615
%" (20mm) Large Orifice with X11 NPT (R'A)Thread 8.0 115 2.3" (58mm) 12,3,4,7,8 R3622 R3612
Y,," (17mm) Small Orifice with Y2" NPT (R)) Thread 4.2 60 2.54" (65mm) 1,2,8 R3623 R3613
%" (10mm) Small Orifice with )" NPT (R)) Thread 2.8 40 2.54- (65mm) 1,2,8 R3621 R3611
l0mm Orifice XLH with R%"Thread 4.2 60 56.1mm 4.6,7 R3624 R3614
Conventional-Install in Upright or Pendent Position
4.2
5.6
8.0 1
60
80 115
56.1mm
56.1mm 58.4mm 1
-
4,6,7
4,7
R3674
R3675
R3672
l0mm Orifice XLH with R%Thread 15mm Standard Orifice with )" NPT (R)) Thread 20mmLarge Orifice with 3A"NPT(R34)mread
Upright Pendent
Upright Conventional
Model Fl FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Nominal
Orifice Thread
Size
K Factor Sprinkler
Height
Approval0
Organizations Sprinkler Identification
Number (SIN) us Metric
X" (15mm) ,Y;NPT(R½) 5.6 80 2.2' (56mm) 1,2,3,4.5,7,8 R3615
%7(20mm) %"NPT(R'A) 8.0 115 2.3"(58mm) 1,2,3 R3612
" (11mm) "NPT(R1/2) 4.2 60 2.54 (65mm) 1,2,8 R3613
% (10mm) ,3" NPT (R1/2) 2.8 1 40 2.54 (65mm) 1,2,8 R3611
10mm R% 4.2 60 1 56.1mm 4,7 R3614
"Refer to escutcheon data table for approvals and dimensions.
2 l/41a.EC&(
15/f6 CM (49.2m'n) I I riz I
'• x 'a RLCIR nm cOLLAR ima ir
L 13.2mm)
;;7m.k _-J (72.A-1 IWW1O
(I) RR 10 fU1D*D*4 DATA TARE FOR AFRROWLS APØ
2.
Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Orifice Thread Size K Factor
US Metric Sprinkler Height Approval
Organizations
Sprinkler Identification
Number (SIN)
Y2" NPT (RY2)__f 5.6 80 2.2 (56mm) 1,2,3,6,8
R3685 15mm ½" NPT (R'/2) 5.6 80 2.2" (56mm) 4(1)
(1) LPC Approval is for Pendent position only.
I Orientation I Deflector to Ceiling I Dimension (Mm. - Max.) I
Upright 411- 12" (102mm - 305mm)
I Pendent I 6 - 12" (152mm - 305mm)
Vertical Sidewall
Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
K Factor Approval Organizations
and Type of Approval Sprinkler
Identification
US I Metric Light
Hazard
I Ordinary I Hazard
Nominal
Orifice Thread
Size Sprinkler
Length Number
(SIN)
X"(l5mm) " NPT(R½) 5.6 80 2.63(67mm) 1,2,3,5,8 1,2,5,8 R3635
NOTE: UL and ULC Listing permits use with Fl or F2 recessed escutcheon.
I-lorlzontal siaewall
Installation
Quick response sprinklers are intended for installation
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed.
The Model F1FR Recessed Quick Response Sprinklers
are to be installed as shown. The Model Fl or F2 Escutch-
eons illustrated are the only recessed escutcheons to be
used with the Model Fl FR Sprinklers. The use of any other
recessed escutcheon will void all approvals and negate all
warranties.
When installing Model Fl FR Sprinklers, use the Model D
Sprinkler Wrench. When installing Model Fl FR Recessed
Sidewall Sprinklers, use the Model GFR1 Sprinkler
Wrench. Use the Model RC1 Wrench for installing F1FR
Recessed Pendent Sprinklers. Any other type of wrench
may damage these sprinklers.
Temperature Ratings
Classification
Sprinkler
—Tempe'ature
Max. Ambient
Temp. OF
Bulb
Color C
Ordinary 57 135 10o°F(38°c) Orange Ordinary 68 iss 100°F(381c) Red Intermediate 79 175 150°F(661c) Yellow Intermediate 93 200 150°F(66°c) Green
High (1) 141 286 225OF(1070c) Blue
(1) Not available for recessed sprinklers.
Escutcheon Data
Escutcheon Faceof Fitting
Model A to ceiling or
EDkToWm Wail imenslon
12,4 X6 _15/Fl 19mm) (5mm - 24mm)
F2 1,2,3,4,5,7,8 1" X6" -X"
(13mm) (25mm) (5mm- 17mm)
F1' 1,2 Fully Recessed t11 mm
12 Fully Retracted
Push-on/
Thread-off
(24mm)
Maintenance
The Models F1FR and F1FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
Finishes ("4
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated (3)
White Polyester Coated White Painted (3)
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
Other finishes and colors are available on special order.
Consult the factory for details.
FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
FP Push-on/Thread-off escutcheon
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the united States, Canada and foreign countries.
Manufactured by
Reliabld
The Reliable Automatic Sprinkler Co., Inc.
(800)431-1588 Sales Offices
(800)848-6051 Sales Fax
(914)668-3470 Corporate Offices
www.rellablesprinkler.com Internet Address
®Recycled
Paper
Revision lines indicate updated or new data