Loading...
HomeMy WebLinkAbout2774 GATEWAY RD; ; AS1001449/12/23, 2:40 PM AS100144 Permit Data City of Carlsbad Sprinkler Permit Job Address: 2774 GATEWAY RD Permit Type: SPRINK Parcel No: 2133000600 Lot #: 0 Reference No.: Permit No: AS100144 Status: ISSUED Applied 11/17/2010 Approved: 11/17/2010 Issued: 11/17/2010 PC #: Inspector: Project Title: AXIS FINANCIAL T.I. FIRE SPRINKLER PLAN CHECK & INSPECTIONS Applicant: ACTION FIRE SYSTEMS CO., INC. 9185 HARNESS ST SPRING VALLEY, CA 91977-3948 619-462-9210 Owner: OAS SPECTRUM L L C C/O STEVE OAS 2231 RUTHERFORD RD CARLSBAD CA Fees ($) Add'l Fees ($) Total ($) Balance ($) 130 0 130 0 about:blank 1/1 October 8, 2010 Sprinkler 41a MICROFAST® AND MicrofastHP® QUICK 4J I FJ F1G RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com DESCRIPTION Viking Microfaste and MicrofastHPO Quick Response Pendent Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several different finishes and temperature ratings and K-Factors to meet design requirements. The special Polyester and TeflonO coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive at- mospheres and are cULus listed as corrosion resistant as indicated in the Approval Chart. (Note: FM Global has no approval classification for TeflonO and Polyester coat- ings as corrosion resistant.) LISTINGS AND APPROVALS cULus Listed: Category VNIV Ow FM Approved: Class 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984C-PDA VdS Approved: Certificates G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021 LPC Approved: Ref. Nos. 096e/03 and 096e/04 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40130, and 0786-CPD-40170 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1 008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart I and Design Criteria on page 41 d for cULus Listing requirements and refer to Approval Chart 2 and Design Criteria on page 41e for FM Approval requirements that must be followed. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- http:IIwww.vikinggroupinc.com. sure (HP) sprinklers can be identified by locating "250" stamped on The Web site may Include a more recent the deflector. All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to -65 OF (-55 °C) Overall Length: Refer to the Approval Charts CULUS Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06662B and 12282. Brass UNS-C84400 for all other sprinklers. Deflector: Phosphor Bronze UNS-05 1000 or Copper UNS-C 19500 for Sprinklers 06662B, 06666B, and 06765B. Copper UNS- C19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-06000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-ClI000 and Stainless Steel UNS-530400 Form No. F_081296 Replaces page 41a-f, dated May 7, 2010. (Clarified FM Approval.) Sprinkler 41b October 8, 2010 MICROFAST® AND I MicrofastHP® QUICK sJII(IF41G RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com For TeflorwO Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-TefionO Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list) Order Microfast' and MicrofastHPe Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin- ish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, ChromeEnloye = F, White Polyester = M-M, Black Polyester = M-/B, and Black TefionO = N Temperature Suffix (°FrC): 135°I57° = A, 155°/680 = B, 1757790 = D, 200°/93" = E, and 286°/141° = G For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 155 °F/68 "C temperature rating = Part No. 06662BAB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: Standard Wrench: Part No. 10896W/B (available since 2000). Wench for Coated and/or Recessed Sprinklers: Part No. 12144W1B* (available since 2003) Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool** Part No. 15915 (available since 2010.) NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W1B. A W ratchet is required (not available from Viking). "Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Sprinkler Cabinets: Six-head capacity: Part No. 01724A (available since 1971) Twelve-head capacity: Part No. 01725A (available since 1971) INSTALLATION Refer to appropriate NFPA Installation Standards. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. AVAILABILITY The Viking Microfast' and Microfastl-1100 Quick Response Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Wrench FLats Protective Sprinkler Cap 10896 =0 Figure 1: Standard Sprinkler Wrench 10896W/B October 8, 2010 Sprinkler 41c MICROFAST® AND :RESPONSE icrofastHP® QUICK SjjI(JrJ PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Ordinary 135 'F (57 'C) 100 'F (38 DC) Orange Ordinary 155 'F (68 'C) 100 'F (38 'C) Red Intermediate 175 'F (79 'C) 150 'F (65 °C) Yellow Intermediate 200 'F (93 'C) 150 'F (65 DC) Green High 286 'F (141 'C) 225 'F (107 'C) Blue Sprinkler Finishes: Brass, Chrome-Enloy", White Polyester, Black Polyester, and Black Teflon' Corrosion-Resistant Coating83: White Polyester, Black Polyester, and Black Teflon' Footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon' coatings. I I I V V I Mo Sprinkler Wrench ,. J 12144W/Baa For installing coated and/or recessed pendent sprinklers Carefully slide the A with protective caps. :t:L------- wrench sideways i I :'-- around the protective cap, ensuring engage— ment with the sprinkler awA 1/2' ratchet is required wrench flats. (not available from Viking). Figure 2: Wrench 12144W!B for Coated and/or Recessed Pendent Sprinklers Sprinkler 41d October 8, 2010 MICROFAST® AND MicrofastHP® QUICK SJ I FJ Il6i :RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com - M1thi51rSI ( 21JNP - -- Sprinkler Th ad Size re Nominal Overall Listings and Approvals3 Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No.' NPT j BSP U.S. metric2 Inches I mm cULus4 NYC' VdS LPCB CE I Standard Orifice 06662B I VK302 1/2" 1 15 mm 5.6 80.6 2-1/4" 58 J AIX, BIY AIX, BIY A3 A3X, 133Y C3X, E3Y1' C3X. E3Y'3 Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 AIX, B1Y AIX, B1Y A3 A3X C31' - 06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 1 60 1 AIX, BIY AIX, B1Y A3 - - -- Small Orifice' 06718B' VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 AIX, BIY AIX, BIY - - -- - -- 0672013' VK331 1/2" 15 mm 42 57 2-1/4" 58 AIX, B1Y AIX, BIY -- - - -- 06932B VK331 -- 10 mm 4.2 57 2-3/8" 60 - - A3 - G212 - Maximum 250 PSI (17 bar) WWP Standard Orifice Sprinkler Thread Size Nominal Overall Listings and Approvals3 Base SIN - K-Factor Length (Refer also to Design Criteria on page 41e.) Part No' NPT BSP U.S. metiic2 Inches mm cULus' NYC10 VdS LPCB 12282 VK317 1/2" 15mm 5.6 1 80.6 2-1/4" 58 AIX, B1Y AIX - - - Maximum 250 PSI (17 bar) WWP Small Orifice' 1229010 VK342 1 1/2" 115 mm 1 2.8 1 40.3 1 2-3/16" 1 56 AIX, BIY I AIX -- Approved Temperature Ratings A -135 "F (57 "C), 155 "F (68 "C), 175 "F (79 "C), 200°F (93 "C), Approved Escutcheons and 286 "F (141 "C) Approved Finishes X - Standard surface-mounted escutcheon or B - 135 -F (57 "C), 155 "F (68 "C), 175 "F (79 "C), and 200 "F 1 - Brass, Chrome-Enloy, White the Viking Microfast" Model F-i Adjustable C - 155 "F (68 "C), 175 "F (79 "C), 200 "F (93 "C), and 286 "F Polyester '7, Black Polyester 6.7, Escutcheon (141 "C) and Black Teflodw V - Standard surface-mounted escutcheon or D - 135 "F (57 "C), 155 "F (68 "C), 175 "F (79 "C), and 286 "F 2 - Brass and Chrome-Enloy" the Viking Microfast" Model F-1 Adjustable (141 "C) 3 - Brass, Chrome-Enloy", White Escutcheon or recessed with the Viking E - 155 "F (68 "C), 175 "F (79 "C), and 200 "F (93 "C) Polyester7, and Black Polyester7 Micromatic" Model E-1 or E-2 Recessed F - 155 "F (68 "C), 175 "F (79 "C), and 286 "F (141 "C) Escutcheon G -155 "F (68 "C) I Footnotes 1 Base part number is shown. For complete part number, refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, dMde the metric K-factor shown by 10.0. This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA. 6 cULus Listed as corrosion resistant. Other colors are available on request with the same Listings and Approvals as the standard colors. 'Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 'The sprinkler orifice is bushed. 10A.ccepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 16. ç Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. 12 t Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40130 0786-CPD-40170. and 13 ® MED Certified, Standard EN 12259-I, EC-certiflcate of conformity 0832-MED-I003 and 0832-MED-I008. October 8, 2010 Sprinkler 41e The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com cULus Usthia Reaulmments: Microfast° and MicrofastHPO Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. Designed for use in Light and Ordinary Hazard occupancies (exception: smell orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Ceiling Opening Size: 2-5/16' (58,7 mm) minimum I 2-1/8' 2-1/2' (63.5 mm) maximum (54 mm) 1/2' (15 mm) NPT I- 2-1/4' 1-5/8' (58 mm) (41 mm) W Pendent Sprinkler 06662B (VK302) 1-3/4' (44.5 mm) Installed with a standard 1/8' surface- mounted escutcheon. r- J (i) 2' tll II Ill 1-1/2' (38.1 mm) (50.8 mm) UK (JII Minimum Maximum Installed with a Mlcrofast Model F-i Adjustable Escutcheon Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-I Adjustable Escutcheon I 2-1/8' I Ceiling Opening Size: 2-1/8' I I. (54 mm) 2-5/16' (58.7 mm) minimum I (54 mm) 2-1/2' (63.5 mm) maximum 1-3/4' Minimum I \ 1-1/8' (28.6 mm) (44.5 rim) Maximum -- Installed with a Micromatic Model E-1 Recessed Escutcheon 2' Uk J( )J1-1/8' (28.6 mm) (50.8 mm) çJ Minimum Maximum Installed with a thread on Model E-2 Recessed Escutcheon Figure 4: Sprinkler VK302 Dimensions with the Model E-I and E-2 Recessed Escutcheons Sprinkler 41f October 8, 2010 MICROFAST° AND MicrofastHP® QUICK N1KJ:N::G*1 1 JJJ11 RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Sprinkler Thread Size Nominal K Factor Overall Length FM Approval83 i I I SIN __ Base Part No.' NPT BSP U.S. metric- Inches (Refer also to Design Criteria below.) Standard Orifice 0666213 VK302 1/2" 15 mm 5.6 80.6 1 2-1/4" 58 A2X, B2Y Large Orifice 06666B VK352 20 mm 8.0 1152 1 2-3/8" 60 AiX, B1Y Small Orifice' 06718B6 VK329 1/2" 115 mm 2.8 40.3 2-3/16" 56 AiX Approved Escutcheons Approved Temperature Ratings Approved Finishes X-Standard surface-mounted escutcheon or the Viking A - 135 "F (57 "C), 155 "F (68 "C), 175 "F (79 "C), 1 - Brass and Chrome-EnloyO Microfast Model F-I Adjustable Escutcheon 200 "F (93 "C), and 286 °F (141 "C) 2 -Brass, Chrome-Enloy', White Polyester5, Y - Standard surface-mounted escutcheon or the "F °C), 'F 'C), 'F 'C), B - 135 (57 155 (68 175 (79 and Black Polyester5 Viking MicrofasP Model F-I Adjustable Escutcheon 'F 'C) and 200 (93 or recessed with the Viking Micromatic Model E-1 or E-2 Recessed Escutcheon Footnotes 1 Base part number is shown. For complete part number, refer to Viking's current price schedule. 2Methc K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, dMde the metric K-factor shown by 10.0. 3This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. FM Approved as standard response control mode standard spray Non-storage sprinklers. For specific application and installation requirements, refer- ence the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). Other colors are available on request with the same Listings and Approvals as the standard colors. 0 The sprinkler orifice is bushed. FM Aooroval Reaulrements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-storage standard spray pendent sprinklers as indicated in the FM Approval Guidet. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheets 2-0 and 8-9). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. tSprinklers VK302 and VK352 are also FM Approved as quick response Rack Storage standard spray pendent sprinklers. Refer to technical data page 131a-e for Intermediate Level In-Rack Sprinklers. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_081296 Replaces page 41a-f, dated May 7, 2010. (Clarified FM Approval.)