HomeMy WebLinkAbout3209 LIONSHEAD AVE; ; FPC2022-0143000C%
PERMIT PERMIT REPORT Carlsbad
Print Date: 07/21/2023 Permit No: FPC2022-0143
Job Address: 3209 LIONSHEAD AVE, CARLSBAD, CA 92010-4710 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2218811500 Track #: Applied: 07/28/2022
Valuation: $1,153,076.00 Lot #: Issued: 08/05/2022
Occupancy Group: Project #: Finaled Close Out: 02/21/2023
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Salcedo, Felix
Plan Check #:
Project Title:
Description: PRANA/COLUMBIA SPORTSWEAR - ADD/RELOCATE SPRINKLERS FOR TI PER NEW RCP LAYOUT (64 HEADS)
Applicant: FPContractor:
WESTERN FIRE PROTECTION INC WESTERN FIRE PROTECTION INC
MARIO MACK 13630 DANIELSON ST
13630 DANIELSON ST POWAY, CA 92064-6830
POWAY, CA 92064-6830 (858) 513-4949
(858) 513-4949
FEE AMOUNT
FIRE NFPA 13 or 13R System 7-100 heads $607.00
Total Fees: $607.00 Total Payments To Date: $607.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
Western Fire Protection Inc.
PrAna HQ Tol
3209 Lionshead Ave.
Carlsbad, CA 92010
Western Job# 22-2287-03
FIRE SPRINKLER SYSTEM
MATERIAL DATA SUBMITTAL
DUE TO AVAILABILITY, MATERIAL MAY BE SUBSTITUTED FOR LIKE EQUIVALENT
13630 Danielson Street • Poway, CA 92064 9 Phone: (858) 513-4949 9 Fax: (858) 513-1322
SPRINKLERS
Standard Coverage, Quick Response
Upright, Pendent and Recessed Pendent Sprinklers 4tauuicr
K2.8 (4.0), K4.2 (6.1), K5.6 (8.1), K8.0 (11.5) 41.01
1.0 PRODUCT DESCRIPTION
QUICK RESPONSE UPRIGHT SPRINKLERS
SIN V2815 V4215 V2704 V3402
ORIENTATION UPRIGHT UPRIGHT UPRIGHT UPRIGHT
K-FACTOR' 2.8 Impj4.0 S.I. 4.2 Imp./6.1 S.I. 5.6 ImpJ8.1 S.I. 8.0 Impi11.5 S.I.
CONNECTION ½" NPT/15mm BSPT ½" NPT/15mm BSPT '/ NPT/15mm BSPT/IGS 3/4 NPT/20mm BSPT/IGS
MAX. WORKING PRESSURE 175 psi/1200 kPa 175 psi/1200 kPa 175 psi/1 200 kPa
cULus 250 psi /1725 kPa 175 psi/1 200 kPa
GLOBE RE-DESIGNATION GL2815 GL4215 - -
GLOBE EQUIVALENT - - GL5615 GL8118
QUICK RESPONSE PENDENT SPRINKLERS
SIN V2801 . . V4201 V2708 V3406
ORIENTATION PENDENT PENDENT PENDENT, PENDENT
K-FACTOR' 2.8 Impi4.0 S.I. 4.2 Impi6.1 S.I. 5.6 Impf8.1 S.I. 8.0 Impi11.5 S.I.
CONNECTION ½ NPT/15mm BSPT ½" NPT/15mm BSPT ½" NPT/15mm BSPT/IGS W NPT/20mm BSPT/IGS
MAX. WORKING PRESSURE 175 p51/1200 kPa 175 psi /1200 kPa 175 psi /1200 kPa
cULus250psi/1725kPa 175 psi/1 200 kPa
GLOBE RE-DESIGNATION GL2801 GL4201 - -
GLOBE EQUIVALENT - - GL5601 GL8101
QUICK RESPONSE RECESSED PENDENT SPRINKLERS
SIN V2801 V4201 V2708 V3406
ORIENTATION PENDENT PENDENT PENDENT PENDENT
K-FACTOR' 2.8 Impi4.0 5.1. 4.2 Impf6.1 S.I. 5.6 ImpJ8.1 S.I. 8.0 Imp./1 1.55.1.
CONNECTION ½ NPT/15mm BSPT ½' NPT/15mm BSPT ½" NPT/15mm BSPT/IGS 3/4" NPT/2Omm BSPT/IGS
MAX. WORKING PRESSURE 175 psi/1200 kPa 175 psi/1200 kPa psi/1 200 cU u
5 27 akPa 175 psi/1 200 kPa
ESCUTCHEON Recessed Recessed Recessed Recessed
GLOBE RE-DESIGNATION GL2801 GL4201 - -
GLOBE EQUIVALENT - - GL5601 GL8101
AVAILABLE GUARDS/SHIELDS
SPRINKLER V28 V42 V27 V34
Upright U
Pendent U U
AVAILABLE WRENCHES
SPRINKLER V56-2 Recessed V56 Open End V27-2 Recessed V27 Open End V34-2 Recessed V34 Open End 3/ Hex-Bit
V2815 and V4215 U
V2707 and V2704 U U
V3402 U U
V2801, and V4201
V2706 and V2708
V3406 I
Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar
Mm. Operating Pressure: UL/FM: 7 psi/48 kPa/.5 bar
VdS: 5 psi/35 kPa/.35 bar (Upright only)
Temperature Rating: See tables in section 2.0
1 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
41.01 16343 Rev C Updated 04/2021 © 2021 Victaulic Company. All rights reserved. /1tauIjcr 1
victaulic corn
2.0 CERTIFICATION/LISTINGS
UPRIGHT APPROVALS/LISTINGS
SIN V2815 V4215 V2704 V3402
Nominal K Factor Imperial 2.8 42 5.6 8.0
Nominal K Factor S.I.2 4.0 6.1 8.1 11.5
Orientation UPRIGHT UPRIGHT UPRIGHT UPRIGHT
Approved Temperature Ratings P/C*
1350F/570C 135°F/57°C 135°F/57°C 135°F157°C
1550F/680C 155°F/680C 15500/680C 155°F/68°C
cULus 175°F/79°C 175°F/790C 1750F/790C 1750F/790C
200°F/93°C 200°F/93°C 200°F/930C 200°F1930C
286°F/141°C 286°F/141°C 286°F1141 0C 286°F/141°C
135°F157°C 135°F157°C
155°F/68°C 155°F/680C
FM - - 175°F/79°C 175°F/79°C
200°F/93°C 2000F/93°C
2860F/1410C 2860F/141 C
135°F/570C 135°F/57°C
155°F168°C 1550F/68°C
LPCB - - 175°F1790C 175°F1790C
2000 F193°C 200F/93°C
2860F/141°C 2860F/141°C
135°F157'C 135°F/570C
1550F/680C 1550F/68°C
CE - - . 175°F/79C 1750F/790C
2000F/930C 2000F/930C
286°F/141°C 2860F/141'C
135°F1570C 135°F/570C
155°F/680C 1550F/680C
VdS - - 175°F/79°C 1750F/790C
2000F/930C 2000F/930C
286°F/141 C 2860F/141°C
CCC 155°F/68°C 1550F/68°C
K-ZSTZ -
-
2860F/1410C
2 For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
PENDENT APPROVALS/LISTINGS
SIN V2801 V4201 V2708 V3406
Nominal K Factor Imperial 2.8 4.2 5.6 8.0
Nominal K Factor 5.1.2 4.0 6.1 8.1 115
Orientation PENDENT PENDENT PENDENT PENDENT
Escutcheon Flush/Extended Flush/Extended Flush/Extended Flush/Extended
Approved Temperature Ratings FO/Co
135°F/57°C 1350F/570C 1350F/570C 135°F/57°C
155°F/68°C 1550F/68eC 155°F/680C 1550F/680C
cULus 175°F/79°C 175°F/79°C 1750F/790C 1750F/790C
200°F/93°C 2000F/930C 200°F/93°C 200°F/93°C
2860F/141 C 286°F/141 C 2860F/141 C 2860F/141 C
135°F/57°C 135eF/57eC
1550F/680C 155°F/680C
FM - - 175°F/79°C 1750F/790C
2000F/930C 2000F/930C
286°F/141 C 2860F/141°C
CCC 1550F/68°C 155°F/680C
v 7c-ry 8C!141°
2860F/1410C
2 For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
NOTES
Listings and approval as of printing.
Where cULus Listed, Polyester and VC-250 Coatings Listed as Corrosion Resistant (V3402 with VC-250 Only)
Where FM Approved, VC-250 Coating Approved as Corrosion Resistant
New York City Acceptance - All UL Listed and/or FM Approved sprinklers acceptable to NYC per section 28-113 of the Administrative Code and the OTCR Rule.
41.01 16343 Rev C Updated 04/2021 © 2021 Victaulic Company. All rights reserved.
viCtaulic.cOm 2 _,4tauiic'
victaulic.com
2.0 CERTIFICATION/LISTINGS (CONTINUED)
RECESSED PENDENT APPROVALS/LISTINGS
SIN V2801 V4201 V2708 V3406
Nominal K Factor Imperial 2.8 4.2 5.6 8.0
Nominal K Factor 5.1.2 4.0 6.1 8.1 115
Orientation PENDENT PENDENT PENDENT PENDENT
Escutcheon Recessed Recessed Recessed Recessed
Approved Temperature Ratings FIC°
135°F/57*C 135F/57C 135°F/57°C 135°F/57C
155°F/68°C 155F/68°C 155 F/68 C 155°F/68°C
cULus 175°F/79°C 175°F/79°C 175 F/79 C 175°F/79°C
200°F/93°C 200°F/93°C 200 F/93 C
200 F/93°C
286F/141°C 286°F/141°C 286°F/141 C
FM 135°F/57°C 135F/57°C
WITH 1h" ADJUSTMENT - -
155F/68C 155F/68°C
ESCUTCHEON ONLY 175F/79C 175F/79C
2000F/930C 200°F/93*C
CCC 155°F/68°C 155F/68C
K-ZSTX -
- 200FI93°C 286°F/141°C 286F/141°C
2 For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
NOTES
Listings and approval as of printing.
Where cULus Listed, Polyester and VC-250 Coatings Listed as Corrosion Resistant (V3402 with VC-250 Only)
Where FM Approved, VC-250 Coating Approved as Corrosion Resistant
New York City Acceptance - All UL Listed and/or FM Approved sprinklers acceptable to NYC per section 28-113 of the Administrative Code and the 01CR Rule.
41.01 16343 Rev C Updated 04/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 3 ,Ltauiicr
victaulic.com
3.0 SPECIFICATIONS - MATERIAL
Deflector: Bronze
Bulb Nominal Diameter: 3.0mm
Load Screw: Bronze
Pip Cap: Bronze
Spring Seal: PTFE coated Beryllium nickel alloy
Frame: Brass
Lodgement Spring: Stainless steel
Installation Wrench: Ductile iron
Sprinkler Frame Finishes:
Plain brass
Chrome plated
White polyester painted34
Flat black polyester painted34
Custom polyester painted34
VC-2505
Not available on the Intermediate Level Style Pendent.
UL Listed for corrosion resistance.
UL Listed and FM Approved for corrosion resistance.
NOTE
For cabinets and other accessories refer to separate sheet.
316"/llmm
rNominal make-in
Lodgement spring
Pip cap and
spring seal 2516?
5 Bulb 58 mm
Load screw
Frame
1 V.?
31 mm
1,l6?
37 mm
Load screw
Bulb
Pip cap and
spring seal 2W!
Lodgement spring 63 jmm
Frame
L W/l3mm
Nominal make-in
%"/13 mm
Nominal make-in
Frame
2½?
Lodgement spring
Pip cap and
spring seal 63 mm
Bulb
Load screw
Deflector -s..
_33 mm
1516?
Deflector 37 mm
Load screw
Bulb
Pip cap and
spring seal
63 mm Lodgement spring 3 T-M, I
Deflector 37 mm
Load screw
Bulb
Pip cap and
spring seal
Lodgement spring 63 mm 3
L ½"/l3mm
Nominal make-in
Deflector
Load screw
Bulb
Pip cap and
spring seal
Lodgement spring
Frame
HW!13 mm
Nominal make-in
0mm
m l
2¼?
57mm
%/42
M"11 1 mm
Nominal make-in
I
41.01 16343 Rev C Updated 04/2021 02021 Victaulic Company. All rights reserved.
victaulic.com 4 \JtaUIicr
victaulic.com
S
4.0 DIMENSIONS
W/22 mm Max. (.Y4" Adj)
W/16 mm Max. (½ Adj.)
W/3 mm Mm.
2W/60 mm
2751 mm -
Hole in ceiling
11
Typical ceiling
16/29 mm Mm. (34" Adj.)
1W/34 mm Mm. (½" Adj.) Finished surface
1W/47 mm Max.
21516775 mm -
2W/60 mm
2751 mm -
Hole in ceiling
34722 mm Max. (N" Adj.)
W/16 mm Max. (½" Adj.)
3473 mm Mm.
Typical ceiling
Finished surface
1W/47 mm Max 2'516/75 mm
1W/29 mm Mm. (34" Adj.)
134734mm Mm. (½" Adj.).
2W/60 mm
2751 mm
Hole in ceiling
1725 mm Max. (VV AdJ.)
3A"/19 mm Max. (½" Adj.)
W/6 mm Mm.
Typical ceiling
1316/30mm Mm. (½" Adj.)
I31"/24 mm Min. (V4" Adfl Finished surface
1'146"/43 mm Max.
21516775 mm
S S
41.01 16343 Rev C Updated 04/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 5 J'tauIicr
victaulic.com
a
5.0 PERFORMANCE
Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards.
6.0 NOTIFICATIONS
_____ • Read and understand all instructions before attempting to install
any Victaulic products.
Always verify that the piping system has been completely depressur-
ized and drained immediately prior to installation, removal, adjust-
ment, or maintenance of any Victaulic products.
Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious
personal injury and property damage.
These products shall be used only in fire protection systems that are designed and installed in accordance with
current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent
standards, and in accordance with applicable building and fire codes. These standards and codes contain
important information regarding protection of systems from freezing temperatures, corrosion, mechanical
damage, etc.
The installer shall understand the use of this product and why it was specified for the particular application.
The installer shall understand common industry safety standards and potential consequences of improper
product installation.
It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media
within the piping system and external environment.
The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature,
chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended
service.
Failure to follow installation requirements and local and national codes and standards could compromise system
integrity or cause system failure, resulting in death or serious personal injury and property damage.
7.0 REFERENCE MATERIALS
Ratings: All glass bulbs are rated for temperatures from -670F/-550C to those shown in the table below.
-40: Victaulic FireLockmi Automatic Sprinklers Installation and Maintenance Instructions
l-V9: Style VO Victaulic FireLockTM IGSTM Installation_ReadyTM Sprinkler Coupling Installation Instructions
User Responsibility for Product Selection and Suitability Note
Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Victaulic products for a particular end-use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions.
standards and project specifications, as well as Victaulic performance, maintenance, Victaulic reserves the right to change product specifications, designs and standard
safety, and warning instructions. Nothing in this or any other document, nor any verbal equipment without notice and without incurring obligations.
recommendation, advice, or opinion from any Victaulic employee, shall be deemed to Installation alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions Reference should always be made to the Victaulic installation handbook or installation of sale, installation guide, or this disclaimer, instructions of the product you are installing. Handbooks are included with each shipment
Intellectual Property Rights of Victaulic products, providing complete installation and assembly data, and are available
No statement contained herein concerning a possible or suggested use of any material, in PDF format on our website at www.victaulic.com.
product, service, or design is intended, or should be constructed, to grant any license Warranty under any patentor other intellectual property right of Victaulic or any of its subsidiaries Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design, or as a recommendation for the use of such
material, product, service, or design in the infringement of any patent or other intellectual Trademarks
property right. The terms "Patented or Patent Pending" refer to design or utility patents Victaulic and all other Victaulic marks are the trademarks or registered trademarks of
or patent applications for articles and/or methods of use in the United States and/or other Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries.
countries.
41.01 16343 Rev C Updated 04/2021 © 2021 Victaulic Company. All rights reserved,
victaulic.com 6
Victaulic® FireLock Model FL-QRIC
Standard Coverage, Quick Response \,Ltaul iii c
Concealed Pendent Sprinklers, K5.6 (8.1) 41.03
n
1.0 PRODUCT DESCRIPTION
QUICK RESPONSE CONCEALED PENDENT SPRINKLERS
SIN 5606 V3802 V3808
ORIENTATION Concealed Pendent Concealed Pendent Concealed Pendent
K-FACTOR' 5.6 Imp./8.1 S.I. 5.6 1mpj8.1 S.I. 5.6 Impi8.1 S.I.
CONNECTION W'NPT/15mm BSPT ½NPT/15mm BSPT ½"NPT/15mm BSPT
MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) 300psi (2068 kPa)
ESCUTCHEON Ccealed Concealed Concealed
GLOBE RE-DESIGNATED GL5606
GLOBE EQUIVALENT GL5604 GL5605
AVAILABLE WRENCHES
SPRINKLER 1" ADJ Concealed V38 Concealed V38 Concealed
PENDENT
CLEAN ROOM GASKET
SPRINKLER 1" ADJ Concealed V38 Concealed V38 Concealed
PENDENT I U
Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar
Mm. Operating Pressure: UL/FM: 7psi/48 kPa/.5 bar
Temperature Rating: See tables in section 2.0
1 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
vktiiilirrnm
41.03 16369 Rev B Updated 04/2021 © 2021 Victaulic Company. All rights reserved.
1 'PJ49taUIic
PIPE
FM Approved and Fully Listed Sprinkler Pipe
Wheatland Tube's Schedule 10 and Schedule
40 steel fire sprinkler pipe is FM Approved
and UL® and C-UL Listed.
Approvals and Specifications
Schedule 10 and Schedule 40 meet or exceed
the following standards:
ASTM A135, Type E, Grade A
(Schedule 10, 1-8 NPS)
ASTM A795, Type E, Grade A
(Schedule 40,1-2 NPS)
ASTM A53, Type E, Grade B
(Schedule 40, 2-8 NPS)
ASTM A53, Type F, Grade A
(Schedule 40,1-4 NPS)
NFPA® 13 and NFPA 14
Manufacturing Protocols
Schedule 10 and Schedule 40 are subjected
to the toughest possible testing protocols to ensure
the highest quality and long-lasting performance.
Finishes and Coatings
All Wheatland black steel fire sprinkler pipe
receives a proprietary mill Coating to ensure a
clean, corrosion-resistant surface that outperforms
and outlasts standard lacquer coatings. This
coating allows the pipe to be easily painted,
without special preparation. Schedule 10 and
Schedule 40 can be ordered in black or hot-dip
galvanized, to meet FM/UL requirements for dry
systems that meet the zinc coating specifications
of ASTM A795 or A53.
Product Marking
Each length of Wheatland fire sprinkler
pipe is continuously stenciled to show
the manufacturer, type of pipe, grade, size
and length. Bar coding is acceptable as a
supplementary identification method.
PROJECT: CONTRACTOR: DATE:
ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE:
LOCATIONS: COMMENTS:
0 BLACK 0 HOT-DIP GALVANIZED
1 Council Avenue, P.O. Box 608
- Wheatland, PA 16161
P 800.257.8182
F 724.346.7260
info@wheatland.com
wheatland.com
Follow us on Twitter:
(cbWheatlanclTube t
Wheatland Tube
A DIVISION OF ZEKEL MAN INDUSTRIES
SCHEDULE 10 WEIGHTS AND DIMENSIONS
WT./FT. WT./LIFT WT./LIFT WT./LIFT
NPS NOMINALOD NOMINAL ID NOMINAL WALL WT./FT. H20 FILLEDPCS./LIFT 21 24 25 UL
in mm In lbs [lbs lbs lbs CRR L -
1 1.315 33.4 1.097 27.9 0.109 2.77 1.405 1.814 70 2065 2360 2459 11.4
1% 1.660 42.2 1.442 36.6 0.109 2.77 1.807 2.514 61 2315 2645 2756 7.3
1% 1.900 48.3 1.682 42.7 0.109 2.77 2.087 3.049 61 2673 3055 3183 5.8
2 2.375 60.3 2.157 54.8 0.109 2.77 2.640 4.222 37 2051 2344 2442 4.7
2¼ 2.875 73.0 2.635 66.9 0.120 3.05 3.354 5.895 30 2226 2544 2651 3.5
3 3.500 88.9 3.260 82.8 0.120 3.05 4.336 7.949 19 1730 1977 2060 2.6
4 4.500 114.3 4.260 108.2 0.120 3.05 5.619 11.789 19 2242 2562 2669 1.6
5 5.563 141.3 5.295 134.5 0.134 3.40 7.780 17.309 13 2124 2427 2529 1.5
6 6.625 168.3 6.357 161.5 0.134 3.40 9.298 23.038 10 1953 2232 2325 1.0
8 8.625 219.1 8.249 209.5 0.188 4.78 16.960 40.086 7 2493 2849 2968 2.1
SCHEDULE 40 WEIGHTS AND DIMENSIONS
WT./FT. WT./LIFT WT./LIFT WT./LIFT NPS NOMINAL OD NOMINAL ID NOMINAL WALL WT./FT. H30 FILLED PCS./LIFT 21 24 25' UL
In.In mm lbs ][I ']IF lbs Llbs 7 CRR
1 1.315 33.4 1.049 26.6 0.133 3.38 1.68 2.055 70 2470 2822 2940 1.000
11/4 1.660 42.2 1.380 35.1 0.140 3.56 2.27 . 2.922 51 2431 2778 2894 1.000
1% 1.900 48.3 1.610 40.9 0.145 3.68 2.72 3.602 44 2513 2872 2992 1.000
2 2.375 60.3 2.067 52.5 0.154 3.91 3.66 5.109 24 1845 2108 2196 1.000
2% 2.875 73.0 2.469 62.7 0.203 5.16 5.80 7.871 20 2436 2784 2900 1.000
3 3.500 88.9 3.068 77.9 0.216 5.49 7.58 10.783 13 2069 2365 2464 1.000
3% 4.000 101.6 3.548 90.1 0.226 5.74 9.12 13.400 10 1915 2189 2280 1.000
4 4.500 114.3 4.026 102.3 0.237 6.02 10.80 16.311 10 2268 2592 2700 1.000
5 5.563 141.3 5.047 158.2 0.258 6.55 14.63 23.262 7 2151 2458 2560 1.000
6 6.625 168.3 6.065 154.1 0.280 7.11 18.99 31.498 5 1994 2279 2374 1.000
Be*8.625 219.1 7.981 202.7 0.322 8.18 28.58 50.240 5 3001 3430 3573 1.000
'Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY The CRR is ratio value used to measure the ability of a pipe to withstand corrosion.
Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0).
8 NPS Schedule 40 is FM Approved but not UL Listed.
C@ <~> APPROVED
WFS-060510
1 Council Avenue, P.O. Box 608 info@wheatland.com
Wheatland, PA 16161 wheatland.com
P 800.257.8182 Follow us on Twitter:
F 724.346.7260 aWheatlandTube ItWheatland Tube
A DIVISION OFZEKELMAN INDUSTRIES
FITTINGS
11 ;iii two I I I
-
--
-
-".
SCI ProPakml System
Ductile Iron Threaded Fittings
Speifiationis
•-
<@> branded fittings are UL Listed and FM Approved at 500 psi
Rated to 300 psi WSP
Ductile iron castings conform to ASTM A536
Fitting dimensions conform to ASME B16.3
Bushings and plugs conform to ASME B16.14
All fittings are 100% air tested
CVZJLUS
-.
LISTED
APPROVED
NPT threads on all fittings conform to ASME B1.20.1
Independent lab verification that fittings meet applicable chemical & mechanical properties
Manufacturing facilities are ISO 9001:2008 and ISO 14001
ProPakTM Packaging
Temperature
Degrees F
Working Pressure, Non-Shock psig
Class 300 Threaded Fittings
-20 to 100 500
150 500
200 480 -
250 - - 460
300 440
350 - - 420
400 400
450
- 380
500 360
550 - 340
600 320
650 300
Fig. 35E 3_900 Elbow
c®US <> APPROVED
LISTED
Size
in Part Number A
in
Packing Weight
lb Inner Master
1/2 35E 3004 1.13 100 200 0.2
3/4 35E 3006 1.31 70 140 0.3
1 35E 3010 1.50 40 80 0.5
1-1/4 35E 3012 1.75 25 0.8 50
1-1/2 35E3014 1.94 18 36 1.1
2 35E 3020 2.25 . 10 20 1.8
2-1/2 35E 3024 2.70 4 8 3.2
Fig. 35R13 - 900 Reducing Elbow
Size
in Part Number A
in
B
in
Packing Weight
lb Inner Master
3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3
1 x 1/2 35RE3010004 1.26 1.36 . .70 140 0.4
1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4
1-1/4x1/2 35RE3012004 1.34 1 35 70 0.5 -
1-1/4x3/4 35RE3012006 1.45 1.63 - 35 70 0.6
1-1/4x1 35RE3012010 1.58 17 30 60 0.7
1-1/2x 1/2 35RE3014004 1.52 1.75 30 60 0.6
1-1/2x3/4 35RE3014006 .1.52 . 1.75 •. 25 50 0.7
1-1/2 x 1 35RE3014010 1.65 1.80 - 20 40 0.8 -
1-1/2x1-1/4 35RE3014012 1.82 1.88 18 36 1.0
2x 1/2 35RE3020004 1.60 1.97 18 36 1.0
2x3/4 . 35RE3020006 1.60 1.97 18 36 1.0
2x1 35RE3020010 1.73 - 2.02 16 32 1.2
2x 1-1/4 35RE3020012 1.90 2.10 . 12 24 1.3
2.16 2x1-1/2 35RE3020014 2.02 10 20 1.5
2-1!2 x 1-1/2 35RE3024014 . 2.16 2.51 6 12 2.2
2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5
Size
in Part Number A
in
Packing Weight
lb Inner Master
1/2 35F 3004 0.88 150 300 0.2
3/4 35F 3006 0.98 . 80 160 - 0.3
1 35F3010 1.13 40 80 0.5
1-1/4 35F3012 1.29 25 50 0.7
1-1/2 35F3014 1.44 20 40 1.0
2 35F 3020 .1.69 10 20 1.6
2-1/2 35F3024 1.95 4 8 2.7
A
Fig. 35F 3-45° Elbow
Fig. 35T 3- Tee
Size
in Part Number a u A
in
Packing Weight
lb Inner Master
1/2 3513004 1.13 80 160 0.3
3/4 - 3513006 1.31 30 60 0.5
1 3513010 1.50 25 50 0.7
1-1/4 3513012 1.75 10 20 1.1
1-1/2 35T 3014 1.94 10 20 1.5
2 3513020 2.25 6 12 2.4
2-1/2 3513024 2.70 4 8 4.3
237 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 • www.smithcooper.com
Size
in Part Number A
in
B
in
C
in
Packing Weight
lb Inner Master
3/4x1/2 35RT3006004 1.29 1.20 1.22 60 120 - 0.4
lx 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6
1xi/2x1 - 35R13010004010 1.50 1.36 1.50 30 60 0.6
1x3/4 35R13010006 1.38 1.38 1.45 25 50 0.6
1x3/4x3/4 35RT3010006006 1.38 1.31 1.45 35 70 0.6
1x3/4x1 35RT3010006010 1.50 1.45 1.50 25 50 0.7
1-1/4 x 1/2 - 35RT3012004 1.34 1.34 1.53 20 40 0.8
1-1/4x1/2x1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9
1 1/4x3/4 35RT3012006 145 145 162 15 30 09
1-1/4x3/4x1-1/4 35R13012006012 1.75 1.62 1.75 20 40 1.0
1-1/4x1 35RT3012010 1.58 1.58 1.67 15 30 1.0
1-1/4xlxl/2 35R13012010004 1.34 1.26 1.53 25 50 0.7
1-1/4x1 x3/4 35R13012010006 1.45 1.38 1.63 20 40 9.8
1-1/4xlx1 35R13012010010 1.58 1.50 1.69 20 40 0.9
1-1/4 x 1 x 1-1/4 35R13012010012 1.75 1.69 1.75 15 30 1.0
1-1/2x1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0
1-1/2x1/2x1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1
.l-1/2x1/2x1-1/2 35RT3014004014 .1.94 1.66 -1.94 12 24 . 1.2
1-1/2x3/4 35R13014006 1.52 1.52 1.75 16 32 1.1
1-1/2x3/4x1-1/4 35R13014006012 1.94 1.66 1.88 20 .40 . 1.1
1-1/2x3/4x1-1/2 35R13014006014 1.94 1.75 1.94 18 36 1.2
1-1/2x1 35RT3014010 1.65 1.65 1.80 7i2 24 1.2
1-1/2x1x1/2 35R13014010004 1.44 1.25 1.69 20 40 0.8
1-1/2x1x3/4 35R13014010006 1.50 1.44 1.75 16 32 0.9
1-1/2xlxl 35R13014010010 1.65 1.50 1.80 16 32 1.0
1-1/2xlx.1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2
1-1/2x1x1-1/2 35R13014010014 1.94 1.80 1.94 12 24 1.3
1-1/2x1-1/4 35RT3014012 1.82 1.82 1.88 12 24, 1.4
1-1/2x1-1/4x1/2 35R13014012004 1.41 1.34 1.66 16 32 0.9
1-1/2x1-1/4x3/4 35R13014012006 1.52 1.45 1.75 16 32 .1.0
1-1/2x1-1/4x1 35R13014012010 1.65 1.58 1.80 16 32 1.1
1-1/2x1-1/4x1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 'T3
1-1/2x1-1/4x1-1/2 35RT3014012014 1.94 1.88 1.94 14 28 1.4
2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5
2x3/4 35RT3020006 1.60 1.60 1.97 10 20 1.6
2x 1 35RT3020010 1.73 1.73 2.02 8 . 16 1.7 -
2x 1 x2 35R13020010020 2.25 2.02 2.25 8 16 1.9
2x1-1/4 35R13020012 1.90 1.90 2.10 8 16 1.9
2x1-1/4x2 35RT3020012020 2.25 2.10 2.25 8 16 2.0
2x1-1/2 35RT3020014 . 2.02 2.02 2.16 8 16 2.1
2x1-1/2x1/2 35R13020014004 1.49 1.41 1.88 10 20 1.3
2x1-1/2x3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4
2x1-1/2x1 35R13020014010 1.73 1.65 2.02 8 16 1.5
2x1-1/2x1-1/4 35 RT3020014012 1.90 1.82 2.10 8 16 1.7
2x1-1/2x1-1/2 35R13020014014 2.02 1.94 2.16 8 16 1.8
C
jb
c®uS
Fig. 35RT3 - Reducing Tee LISTED
Fig. 35BT3 - Bull Head Tee
Size
in Part Number A
in
B
in
C
in
Packing Weight
lb Inner Master
3/4 x 35B13006010 1.45 1.45 1.37 30 - 60 0.6
1 xl 1/4 35B13010012 167 167 158 20 40 09
lx 1-1/2 35B13010014 1.80 1.80 1.65 15 30 1.0
11/4x1x11/2 35B13012010014 188 180 182 15 30 12
1-1/4x1-1/2 35B13012014 1.88 1.88 1.82 15 30 _1.
1-1/4x2 35B13012020 2.10 2.10 1.90 10 20 1.6 -
1-1/2x1-1/4x2 35BT3014012020 2.16 2.10 2.02 10 20 1.8
1-1/2x2 35B13014020. 2.16 2.16 2.02 8 16 1.8
SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 • www.smithcooper.com 238
victaulic.com
p
7.1 REFERENCE MATERIALS
Size Services Pressures per Regulatory Approvals and Listings6
Nominal UL ULC FM VdS LPCB CNBOP
inches psi psi psi psi psi psi
DN kPa kPa kPa kPa kPa kPa
1¼x½ 300 300 300 232 232 232
DN32XDN15 2068 2068 2068 1600 1600 1600
1'.4x% 300 300 300 232 232 232
DN32XDN20 2068 2068 2068 1600 1600
-
1600
1'/4X1 300 300 300 - 232 232 232
DN32XDN25 2068 2068 2068 1600 1600 1600
1 1hxV2 300 300 300 232 232 232
DN40XDN15 2068 2068 2068 1600 1600 1600
1 ½x% 300 300 300 232 232 232
DN40XDN20 2068 2068 2068 1600 1600 1600
1½x1 300 300 300 232 232 232
DN40XDN25 2068 2068 2068 1600 1600 1600
2x½ 300 300 300 232 232 232
DN50XDN15 2068 2068 2068 1600 1600 1600
2x 300 300 300 232 232 232
DN50X20 2068 2068 2068 1600 1600 1600
2x1 300 300 - 300 232 232 232
DN50XDN25 2068 2068 2068 1600 1600 1600
2½x½ 300 300 300 232 232 232
2068 2068 2068 1600 1600 1600
2½x34 . 300......300 390 232 232 232
2068 2068 2068 1600 1600 1600
2 1hx1 300 300 300 232 232 232
2068 2068 2068 1600 1600 1600
300 232 232 232
DN65XDN15 - - 2068 1600 1600 1600
300 232 232 232
DN65XDN20 - 2068 1600 1 1600 1 1600
300 232 232 232
DN65XDN25 - - 2068 1600 1600 1600
6 Pressures listed in this chart are based upon standard wall pipe. Approved and Listed pressures may vary by pipe schedule.
NOTE
Consult regulatory agency websites for details and the most recent regulatory information.
7.2 REFERENCE MATERIALS
05.01: Victaulic Seal Selection Guide
29.01: Victaulic Terms and Conditions of Sale
1-100: Installation Instructions
1-922: Installation Instructions FireLockrM Outlet-T
User Responsibility for Product Selection and Suitability
Each user bears final responsibility for making a determination as to the suitability of
Victaulic products for a particular end-use application, in accordance with industry
standards and project specifications, and the applicable building codes and related
regulations as well as Viclaulic performance, maintenance, safety, and warning
instructions. Nothing in this or any other document, nor any verbal recommendation,
advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede,
or waive any provision of Victaulic Company's standard conditions of sale, installation
guide, or this disclaimer.
Intellectual Property Rights
No statement contained herein concerning a possible or suggested use of any material,
product, service, or design is intended, or should be constructed, to grant any license
under any patent or other intellectual property right of Victaulic or any of its subsidiaries
or affiliates covering such use or design, or as a recommendation for the use of such
material, product: service, or design in the infringement of any patentor other intellectual
property right. The terms "Patented" or "Patent Pending refer to design or utility patents
or patent applications for articles and/or methods of use in the United States and/or other
countries.
Note
This product shall be manufactured by Victaulic or to Victaulic specifications, All products
to be installed in accordance with current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard
equipment without notice and without incurring obligations.
Installation
Reference should always be made to the Victaulic installation handbook or installation
instructions of the product you are installing. Handbooks are included with each shipment
of Victaulic products, providing complete installation and assembly data, and are available
in PDF format on WeChat.
Warranty
Refer to the Warranty section of the current Price List or contact Victaulic for details.
Trademarks
Victaulic and all other Victaulic marks are the trademarks or registered trademarks of i
Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries.
10.52 3355 Rev H Updated 06/2018 © 2018 Victaulic Company. All rights reserved.
victaulic.com JtaUIicr
Lr77
JIM181
A Fig. 3503 - Straight Coupling with Ribs
c®uS <€> APPROVED LISTED
Size A Packing Weight Part Number Inner Master in in lb
1/2 35CP3004 1.38 200 400 0.1
3/ 163 100 - 200 6.2 .5CP3006
1 35CP3010 1.75 60 120 0.4
11/4 35CP3012 200 35 70 05
1-1/2 35CP3014 2.19 25 50 0.7
2 35CP3020 262 15 30 12
2-1/2 35CP3024 3.00 9 18 2.2
Fig. 35RC3 - Hex Reducing Coupling
Size
in Part Number A
in
Packing Weight
lb Inner Master
1 x 1/2 35RC3010004 1.69 - 80 160 0.3
lx 3/4 35RC3010006 1.69 60 120 0.4
1-1/4 x3/4 35R6012006 2.06 40 80 0.6
2x1(nothéx) iC3020010 2.81 20 40 1.0
Fig. 35HB3 - Hex Bushing
Size
in Part Number %
A
in
B
in
Packing Weight
lb Inner Master
lx 1/2 35HB3010004 1.06 1.40 180 360 0.2
1i 3/4 3514B3010006 1.06 1.40 180 360 -. .1 - -
1-1/4x1 35HB3012010 1.19 1.80 90 180 0.2
1-112t 35144015 1.25 - .1.95 75 150 0.4
1-1/2 x 1-1/4 35HB3014012 1.25 1.95 75 150 0.3
_2 _x 1 35HB3020010 1.38 2.55 40 80 0.6
2x 1-1/4 35HB3020012 1.38 2.55 40 80 0.6
2x1-1/2 35HB3020014 1.38 2.55 40 80 - 0.6
Fig. 355P3 - Square Head Plug
Size
in Part Number A
in
Packing Weight
lb Inner Master
1/2 35SP3004 0.94 600 1200 0.07
3/4 . r35SP3006 1.12 350 700 0.1
1 35SP3010 1.25 200 400 0.1
1_1/4_. . 35SP3012 . 1.37 100 200 0.3
1-1/2 35SP3014 1.44 80 160 0.4
2 35SP3020 1.50 45 90 0.6
Fig. 35U 3- Union with Brass Seat
Size
in Part Number
.
A
in
Packing Weight
lb Inner Master
1 35U 3010 - 2.19 20 40 1.0
1-1/4 35U 3012 2.50 15 30 -1-.2--
1-1/2 35U 3014 2.62 10 - - 20 1.7
2 . 35U 3020 j 3.12 6 12 2.4
239 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 9 FAX (323) 890-4456 0 www.smithcooper.com
Fig. 3513- Cross
c®uS <ce> APPROVED
LISTED
Size
in Part Number A
in
Packing Weight
lb Inner Master
1 35X 3010 1.50 - 20 40 0.9
11/4 35301_ 175 12 24 14
1-1/2 35X 3014 1.94 8 16 1.8
235X3020 2.25 6 i2 28
Fig. 35RX3 - Reducing Cross
Size
in Part Number A
in
B
in
Packing Weight
lb Inner Master
1-1/4x1 35RX3012010 - 1.67 1.58 15 30 -
24
1.2
1-1/2x1 35RX3014010 1.80 1.65 12 1.4
2 x 1 35RX3020010 2.02 1.73 8 16 2.0
A
0
U
C
I
L
E
Fig. 35C 3- Cap
Size
in Part Number A
in
Packing Weight
lb Inner Master
1!2 35C 3004 0.87 300 600 0.1
3/4 35C 3006 .T0.97 200 400 0.1
1 35C3010 116 110 220 02
1-1/4 35C 3012 1.28 : 70 140 0.4
1-1/2 35C 3014 1.33 50 100 - 0.5
2 35C 3020 1.45 25 50 0.8
2-1/2 35C 3024 1.70 18 36 1.6
Fig. 35BC3 - Beam Clamp
Size
in Part Number A
in
Packing Weight
lb Inner Master
3/8 35BC3003 0.75 - 100 - 200 0.3 -
1/2 35BC3004 0.75 80 160 0.5
SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 9 www.smithcooper.com 240
Victaulic® FireLockTM Fittings X Ai -0 —ta —U1 ii C r
10.03
1.0 PRODUCT DESCRIPTION
Available Sizes
1 /4 - 8"/DN32 - DN200
Maximum Working Pressure
Pressure ratings for Victaulic FireLockTM Fittings conform to the ratings of Victaulic FireLock EZTM Style 009N
couplings (refer to publication 10.64 for more information).
Application
FireLockTM fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for
Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference.
Connects pipe, provides change in direction and adapts sizes or components
Pipe Materials
Carbon steel
2.0 CERTIFICATION/LISTINGS
4 ILPCBI CE ®
EN 10311
Regulation (EU)
No. 305/2011
3.0 SPECIFICATIONS - MATERIAL
Fitting: Ductile iron conforming to ASTM A536, Grade 65-45-12.
Fitting Coating:
O Orange enamel.
0 Red enamel in Europe, Middle East, Africa, and India.
O Optional: Hot dipped galvanized.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
System No. Location Spec Section Paragraph
Submitted By Date Approved Date
S
victaulic.com
10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. '/ftauIicr 1 _________________
victaulic.com
4.0 DIMENSIONS
.CtoE1 to E1
e Cto'
L_j1j
to E
to -
No. 001 No. 003 No. 002 No. 006
No. 001 No. 003 No. 002 No. 006
90° Elbow 450 Elbow Straight Tee Cap
Approximate Approximate Approximate Approximate Actual
Nominal Outside Weight Weight Weight Weight
Size Diameter C to E Each C to E Each C to E Each T Each
inches inches inches lb inches lb inches lb inches lb
DN mm mm kg mm kg mm kg mm kg
1 Y4 1.660 - - - - - - 0.82 03
DN32 42.4 - - - - - - 21 0.1
11/2 1.900 - - - - - - 0.82 0.4
DN40 48.3 - - - - - - 21 0.2
2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6
DNSO 60.3 70 0.8 51 0.8 70 1.1 22 0.3
2½ 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0
73.0 76 1.4 57 1.0 76 1.6 22 0.5
3.000 3.00 3.30 2.25 2.4 3.00 3.8
DN65 76.1 76 15 57 1.1 76 1.7 - -
3 3.500 3.38 4.0 2.50 3.1 3.38 53 0.88 1.2
DN80 88.9 86 1.8 64 1.4 86 2.4 22 05
4.250 4.00 5.7 3.00 5.1 4.00 73
108.0 102 2.6 76 23 102 3.4 - -
4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4
DN100 1143 102 3.0 76 2.5 102 3.9 25 1.1
5 5.563 4.88 12.6 3.25 83 4.88 15.7 1.00 4.1
141.3 124 5.7 83 3.8 124 7.1 25 1.9
5.500 4.88 12.4 3.25 8.2 4.88 15.4
DN1 25 139.7 124 5.6 82.6 3.7 124 6.9 - -
6.250 530 12.6 3.50 9.2 5.50 17.9
158.8 140 5.7 89 4.2 140 8.0 - -
6 6.625 550 18.3 330 11.7 550 22.7 1.00 5.9
DN150 168.3 140 83 89 53 140 10.3 25 2.7
6.500 5.43 17.6 3.50 11.4 5.50 22.0
165.1 140 7.9 89 5.2 140 9.9 - -
8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7
DN200 219.1 173 11.6 108 93 176 17.6 29 5.8
8.515 6.81 23.1 - - 6.94 33.6 - -
216.3 173 10.5 - - 176 15.2 - -
10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 2 ./(tauIicr
victaulic.com
5.0 PERFORMANCE
Flow Data
Size Frictional Resistance Equivalent of Straight Pipe'
No. 002
Actual Elbows Straight Tee
No. 001 No. 003 Nominal Outside
Size Diameter 90 Elbow 45 Elbow Branch Run
inches inches feet feet feet feet
DN mm meters meters meters meters
1Y4 1.660 - - - -
DN32 42.4 - - - -
1½ 1.900 - - - -
DN40 48.3 - - - -
2 2.375 3.5 1.8 85 33
DN50 60.3 1.1 0.5 2.6 1.1
21/2 2.875 43 2.2 10.8 4.3
73.0 13 0.7 33 1.3
3.000 4.5 23 11.0 4.5
DN65 76.1 1.4 0.7 3.4 1.4
3 3.500 5.0 2.6 13.0 5.0
DN80 88.9 1.5 0.8 4.0 1.5
4.250 6.4 3.2 153 6.4
108.0 2.0 0.9 4.7 2.0
4 4.500 6.8 3.4 16.0 -6.8
DN100 114.3 2.1 1.0 4.9 2.1
5 5.563 83 4.2 21.0 8.5
1413 2.6 13 6.4 2.6
5.500 83 4.1 20.6 83
DN125 139.7 25 1.3 63 25
6.250 9.4 4.9 25.0 9.6
158.8 2.9 13 7.6 2.9
6 6.625 10.0 5.0 25.0 10.0
DN150 168.3 3.0 13 7.6 3.0
• 6.500 9.8 4.9 243 9.8
165.1 3.0 1.5 7.5 3.0
8 8.625 13.0 5.0 33.0 13.0
DN200 219.1 4.0 1.5 10.1 4.0
8.515 13.0 - 33.0 13.0
2163 1 4.0 - 10.1 4.0
1 The flow data listed is based upon the pressure drop of Schedule 40 pipe.
10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 3 _ictaullicr __________
victaulic.com
6.0 NOTIFICATIONS
General Notes
NOTE: When assembling FireLock EZTM couplings onto end caps, take additional care to make certain the end cap
is fully seated against the gasket end stop. For FireLock EZTM Style 009N/009H couplings, use FireLockTM No. 006
end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the
inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H/009N couplings.
7.0 REFERENCE MATERIALS
10.64: Victaulic® FireLockTM Rigid Coupling Style 009N
10.02: Victaulic® FireLock"' Rigid Coupling Style 005H with Vic-Plus Gasket System
29.01: Victaulic® Terms and Conditions of Sale
User Responsibility for Product Selection and Suitability Note
Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Victaulic products for a particular end-use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions.
standards and project specifications, and the applicable building codes and related Victaulic reserves the right to change product specifications, designs and standard
regulations as well as Victaulic performance, maintenance, safety, and warning equipment without notice and without incurring obligations.
Instructions. Nothing in this or any other document, nor any verbal recommendation, Installation advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale, installation
guide, or this disclaimer, instructions of the product you are installing. Handbooks are included with each shipment
of Victaulic products, providing complete installation and assembly data, and are available
Intellectual Property Rights in PDF format on our website at www.victaulic.com.
No statement contained herein concerning a posible or suggested use of any material, Warranty product, service, or design is intended, or should be constructed, to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries
or affiliates covering such use or design, or as a recommendation for the use of such Trademarks
material, product, service, or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of
property right. The terms "Patented" or "Patent Pending" refer to design or utility patents Victaulic Company, and/or its affiliated entities, in the U.S. and/or other Countries.
or patent applications for articles and/or methods of use in the United States and/or other
countries.
10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com jtauIicr 4
Victaulic® FireLockTM Outlet-I A-C—ta—ulicr
Style 922 10.52
1.0 PRODUCT DESCRIPTION
Available Sizes
1 1/4 -2½"/DN32—DN65
Threaded Outlet Sizes: ½"/DN15, 3/4"/DN20, and 17DN25
NOTE
IGS Grooved 17DN25 Outlets available for this product. See publication 10.54.
Maximum Working Pressure
300 psi/2068 kPa/21 Bar
Application
Provides a convenient method of incorporating outlets for directly connecting sprinklers, drop nipples, sprigs,
gauges, drains and other outlet products
Pipe Material
Carbon steel
Contact Victaulic for use on additional pipe types and wall thicknesses
2.0 CERTIFICATION/LISTINGS
®uS 4::. E ILPCB! c USTW
NOTES
See Section 7.2 REFERENCE MATERIALS for additional certification information.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
System No. Location Spec Section Paragraph
Submitted By Date Approved Date
victaulic.com
10.52 3355 Rev H Updated 06/2018 © 2018 Victaulic Company. All rights reserved.
1
victaulic.com
3.0 SPECIFICATIONS - MATERIAL
Housing: Ductile iron conforming to ASTM A536, Grade 65-45-12. Ductile iron conforming to ASTM A395, Grade
65-45-15, is available upon special request.
Housing Coating: (specify choice)
O Orange enamel (North America, Latin America, Asia Pacific).
0 Red enamel (Europe).
O Optional: Contact Victaulic with your requirements for other coatings.
Gasket':
O Grade "E" EPDM (Type A)
EPDM (Violet color code) Applicable for wet and dry (oil-free air) sprinkler services only. Listed/Approved for
continuous use in wet and dry systems. Listed/Approved for dry systems at -40°F/-40°C and above. NOT
COMPATIBLE FOR USE WITH HOT WATER SERVICES OR STEAM SERVICES.
Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should
always be made to the latest Victaulic Seal Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible.
Bolts/Nuts:
O Standard: Carbon steel oval neck track bolts meeting the mechanical property requirements of ASTM A449 (imperial)
and ISO 898-1 Class 9.8 (metric). Carbon steel hex flange nuts meeting the mechanical property requirements of
ASTM A563 Grade B (imperial - hex nuts) and ASTM A563M Class 9 (metric - hex nuts). Track bolts and hex
flange nuts are zinc electroplated per ASTM B633 Fe/Zn 5, finish Type Ill (imperial) or Type II (metric).
10.52 3355 Rev H Updated 06/2018 © 2018 Victaulic company. All rights reserved.
victaulic.com 2 ',9tauIic?
victaulic.com
4.0 DIMENSIONS
Style 922
'-I
Style 922
Size - Bolt/Nut Dimensions Weight
Nominal Actual Approximate
Run x Branch FPT2 Outside Diameter Qty. Size P V W V Z (Each)
inches inches inches inches inches inches inches inches lb
DN mm mm mm mm mm mm mm kg
1¼ ½ 1.660 0.840 X - 2 h 1 1.30 1.83 1.10 3.87 2.56 1
DN32 DN15 42.4 21.3 33 47 28 98 65 0.5
1.28 1.83 1.10 3.87 2.56 1 3/4 1.050
DN20 26.9 2 X 1 47 28 98 65 03
2 X 1 1.52 2.18 1.10 3.87 2.56 1 1 1.315
DN25 55 28 98 65 0.5
1½ 1/2 1.900 0.840 2 1.42 1.95 1.22 4.08 2.56 1
40 DN15 48.3 21.3 36 50 31 104 65 0.5
1.40 1.95 1.22 4.08 2.56 1 3/4 1.050
DN20 26.9 2 X 1 36 50 31 104 65 0.5
2 1xil 1.64 2.30 1.22 4.08 2.56 1 1 1.315
DN25 33.7 42 58 31 104 65 0.6
2 ½ 2.375 0.840 1.66 2.19 1.46 4.60 2.56 1
50 DN15 603 21.3 2 x1 42 56 37 117 65 0.6
1.64 2.19 1.46 4.60 2.56 1 3/4 1.050
DN20 26.9 2 X 1 42 56 37 117 65 0.6
1.88 2.54 1.46 4.60 2.56 2 1 1.315
DN25 2 X 1 48 65 37 117 65 0.7
21/2 ½ 2.875 0.840 1.91 2.44 1.71 5.40 2.56 2
DN15 73.0 X 21.3 2 x1 49 62 43 137 65 0.7
1.89 2.44 1.71 5.40 2.56 2 3/4 1.050
DN20 26.9 2 hi 48 62 43 137 65 0.7
2 hi 2.13 2.79 1.71 5.40 2.56 2 1 1.315
DN25 54 71 43 137 65 0.7
0N65 1/2 3.000 0.840 1.91 2.44 1.71 550 2.56 2
DN15 76.1 213 2 x1 49 62 43 140 65 0.7
1.89 2.44 1.71 5.50 2.56 2 3/4 1.050
DN20 26.9 2 hi 48 62 43 140 65 0.7
2.13 2.79 1.71 5.50 2.56 2 1 1.315
DN25 33.7 2 Jxjj 4 71 43 140 65 0.8
2 Victaulic female threaded products are designed to accommodate standard NPT or BSPT (optional) male pipe threads only. Refer to the specific literature
for these types of special male-threaded products for guidance and possible limitations for use. Failure to verify suitability in advance may result in assembly
problems or leakage.
Center of run to engaged pipe end for NPT threads (dimensions are approximate).
10.52 3355 Rev H Updated 06/2018 © 2018 Victaulic Company. All rights reserved.
victaulic.com 3 "4'tauIic
victaulic.com
5.0 PERFORMANCE
Style 922
Equivalent Length of 1 inch Schedule 40 Steel Pipe (per UL 213, Section 16) (C=120)4
Threaded Grooved5 Run Size x Outlet Size
inches feet feet
DN meters meters
11/4 1 8.5 12.5
DN32 DN25 2.6 3.8
1½ 1 8.5 12.5
DN40 DN25 2.6 3.8
2 1 8.5 12.5
DN50 DN25 2.6 3.8
21/2 1 8.5 125
DN25 2.6 3.8
1 8.5 12.5
DN65 0N25 2.6 3.8
Hazen-Williams coefficient of friction is 120.
1" FireLockTM Innovative Groove System (IGS) outlet
6.0 NOTIFICATIONS
Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic
piping products.
Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic
piping products.
Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.
7.0 REFERENCE MATERIALS
Dimensions
Minimum Hole Diameter! Maximum Hole Diameter!
Hole Saw Size Hole Saw Size
inches inches
mm mm
1316 1¼
F
All Outlet Sizes
30 1 32
10.52 3355 Rev H Updated 06/2018 © 2018 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com
7.1 REFERENCE MATERIALS
Size Services Pressures per Regulatory Approvals and Listings6
Nominal UL ULC FM VdS LPCB CNBOP
inches psi psi psi psi psi psi
ON kPa kPa kPa kPa kPa kPa
1'/4x½ 300 300 300 232 232 232
DN32XDN15 2068 2068 2068 1600 1600 1600
1/4XV4 300 300 300 232 232 232
ON32XDN20 2068 ' 2068 2068 1600 1600 1600
1'/4X1 300 300 300 232 232 232
DN32XDN25 2068 2068 2068 1600 1600 1600
1 ½x½ 300 300 300 232 232 232
DN40XDN15 2068 2068 2068 1600 1600 1600
1½x% 300 300 300 232 232 232
DN40XDN20 2068 2068 2068 1600 1600 1600
1½x1 300 300 300 232 232 232
DN40XDN25 2068 2068 2068 1600 1600 1600
2x½ 300 300 300 232 232 232
DN50XDN15 2068 2068 2068 1600 1600 1600
2x3/4 300 300 300 232 232 232
DN50X20 2068 2068 2068 1600 1600 1600
2x1 300 300 300 232 232 232
DN50XDN25 2068 2068 2068 1600 1600 1600
2½x½ 300 300 300 232 232 232
2068 2068 2068 1600 1600 1600
21hx% 300 300 300 232 232 232
2068 2068 2068 1600 1600 1600
21/2x1 300 300 300 232 232 232
2068 2068 2068 1600 1600 1600
300 232 232 232
DN65XDN15 - - 2068 1600 1600 1600
300 232 232 232
ON65XDN20 - - 2068 1600 1600 1600
300 232 232 232
DN65XDN25 - - 2068 1600 1600 1600
6 Pressures listed in this chart are based upon standard wall pipe. Approved and Listed pressures may vary by pipe schedule.
NOTE
Consult regulatory agency websites for details and the most recent regulatory information.
7.2 REFERENCE MATERIALS
05.01: Victaulic Seal Selection Guide
29.01: Victaulic Terms and Conditions of Sale
1-100: Installation Instructions
1-922: Installation Instructions FireLockTM Outlet-I
User Responsibility for Product Selection and Suitability
Each user bears final responsibility for making a determination as to the suitability of
Victaulic products for a particular end-use application, in accordance with industry
standards and project specifications, and the applicable building codes and related
regulations as well as Viclaulic performance, maintenance, safety, and warning
instructions. Nothing in this or any other document, nor any verbal recommendation,
advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede,
or waive any provision of Victaulic Company's standard conditions of sale, installation
guide, or this disclaimer.
Intellectual Property Rights
No statement contained herein concerning a possible or suggested use of any material,
product, service, or design is intended, or should be constructed, to grant any license
under any patentor other intellectual property right of Victaulic or any of its subsidiaries
or affiliates covering such use or design, or as a recommendation for the use of such
material, product, service, or design in the infringement of any patent or other intellectual
property right. The terms "Patented or "Patent Pending" refer to design or utility patents
or patent applications for articles and/or methods of use in the United States and/or other
countries.
Note
This product shall be manufactured by Victaulic or to Victaulic specifications. All products
to be installed in accordance with current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard
equipment without notice and without incurring obligations.
Installation
Reference should always be made to the Victaulic installation handbook or installation
instructions of the product you are installing. Handbooks are included with each shipment
of Victaulic products, providing complete installation and assembly data, and are available
in POF format on WeChat.
Warranty
Refer to the Warranty section of the current Price List or contact Victaulic for details.
Trademarks
Victaulic and all other Victaulic marks are the trademarks or registered trademarks of
Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries.
10.52 3355 Rev H Updated 06/2018 © 2018 Victaulic Company. All rights reserved.
victaulic.com 5 _
ictaulicr
__________
HANGERS S BRACING
44
Fig. 200-1 to 200-2
Fig. 200F
Fig. 200-i /2. 200-I4
Fig. 200-2'la to 200-8
Fig. 200
Pipe Hangers
Fig. 200 - "Trimline" Adjustable Band Hanger (B-Line Fig. B3110NF) ®T01C0
Fig. 2001 - "Trimline" Adjustable Band Hanger with Felt Lining 10-tine F. B31IONFF) ll
Fig. 200C "Trimline" Adjustable Band Hanger with Plastic Coated (D-Une rig. D317ONFC) USTED
Fig. 2006 - "Trimline" Adjustable Band Hanger with Non -Captured Nut
FM
Size Range:
Fig. 200 - /2" (15mm) thru 8" (200mm) pipe
Material: Steel, Pre-Galvanized to G90 specifications
Function: For fire sprinkler and other general piping purposes. Knurled
swivel nut design permits hanger adjustment after installation.
Features:
(1/2" (15mm) thru 2" (50mm)) Flared edges ease installation for all pipe
types and protect CPVC plastic pipe from abrasion. Captured design
keeps adjusting nut from separating with hanger. Hanger is easily
installed around pipe.
For hanger with non-captured nut order Fig. 200S.
(21/2" (65mm) thru 8" (200mm)) Spring tension on nut holds it securely in
hanger before installation. Adjusting nut is easily removed.
Approvals: Underwriters Laboratories listed (1/2" (15mm) thru 8" (200mm))
in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and
Factory Mutual Engineering Approved (FM) (3/4" (20mm) thru 8" (200mm)).
Conforms to Federal Specifications WW-H-171 E & A-A-1 192A, Type 10
and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58,
Type 10.
Maximum Temperature: 650°F (343°C)
Finish: Pre-Galvanized. Stainless Steel
materials will be supplied with (2) hex nuts
in place of a knurl nut.
Order By: Figure number and pipe size
Designed to meet or exceed requirements of
FM DS 2-0.
Fig. 200C
Pipe Size Rod Size A B Approx. WI1100
Part No. in. (mm) in. (mm) in. (mm) lbs. (kg)
200-'/2 /2" (15) /8"-16 31/8" (79.4) 2/8" (66.7) 11 (5.0)
200-I4 3/4" (20) /811-16 31/8" (79.4) 21/20 (63.5) ii (5.0)
200-1 1° (25) /8"-16 33/8" (85.7) 2/" (66.7) 12 (5.5)
200-11/4 11/4° (32) /"-16 33/4" (94.0) 2/8" (73.0) 13 (5.9)
200-11I2 11/2 (40) /a"-16 31/s" (98.4) 2f8" (73.0) 14 (6.4)
200-2 2" (50) /8"-16 41/20 (114.3) 30 (76.3) 15 (6.9)
200-21/2 21/2" (65) /a"-16 55/8 (142.9) 41/8" (104.1) 21 (12.3)
200-3 3° (75) /8"-16 5/8" (149.1) 4" (101.6) 29 (13.3) Fig 200S
200-31I2 31/2" (90) /8"-16 1/8" (187.3) 51/4" (133.3) 34 (15.6)
200-4 4" (100) /a"-16 7/a" (187.3) 50 (127.0) 35 (16.0)
200-5 5° (125) 1/2.13 91/8" (231.8) 61/4" (158.1) 66 (30.2)
200-6 6" (150) 1/2 -13 101/8" (257.2) 6/4° (111.4) 13 (33.4)
200-8 8" (200) 1/2"13 131/8" (333.4) 8/4" (222.2) 136 (62.3)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line Fire Protection Solutions i by ETsN
Threaded Accessories
B3205 ' Threaded Rod (right-hand threads - both ends) (TOLCO Fig. 103)
B3205L1hreaded Rod (right & left hand threads)
Size Range: 3/8"'tQ,lru 3"-4 rod
Material: Steel
Function: Recommended ?1'.qe as a hanger support in hanger assemblies.
Rod is threaded on both ends wi!l'ght hand threads of the length shown. Also
available with left and right hand thre - specify Fig. B3205L when ordering.
Maximum Temperature: 750°F (399°C)
Finish: Plain or Electro-Galvanized. Contact B-Li for alternative finishes and
materials.
Order By: Figure number, rod size, length and finish
SRd'd Desih4ad
Thread Size Thpd8 Length TL 650°F (343°C) N.50°F (399°C)
Part No. A ./ in. (mm) Us. IN) L NN)
2'/2' (63.5) 130 (3.25) 572 B3205-3/a x
Z'314"-10
B3205-1/2 x 21/2 (63.5) 1350 (6.00)
X 2'/z'
1051
B3205-5/8 (63.5) 2160 (9.61)
3°
1692(1.52)
B3205-3/4 (16.2) 3230 (14.31) 2530 (11.25)
B320 8 x 'L' 1/8u9 31/2 (88.9) 4480 (19.93) 3508 (15.60)
Fafiarger sizes consult full line pipe hanger catalog.
ATR - All Threaded Rod - 120" (3.05m) Lengths (TOLCO Fig. 100)
Fig. 99 - All Threaded Rod Cut To Length
Size Range: /-16 thru 11/2'-6 rod in 120" lengths or cut to length
Material: Steel
Maximum Temperature: 750°F (399°C)
- Finish: Plain or Electra-Galvanized. Contact B-Line for alternative finishes and materials.
Order By: Figure number, rod size, length and finish
Part No. - Size x Length
ATR Fig. 99
Threads
Per Inch
Recommended Load
Lbs. NN)
Approx. Wt./100 Ft.
Lbs. (kg)
ATR 'K x 120 x length 20 240 (1.01) 12 (5.44)
ATR 3/6 x 120 99-/8° x length 16 730 (3.24) 29 (13.15)
ATR 112° x 120 99-1I2° x length 13 1350 (6.00) 53 (24.04)
ATR 5/8° x 120 995/8" x length 11 2160 (9.60) 89 (40.31)
ATR 3/4" x 120 993/4 x length 10 3230 (14.37) 123 (55.19)
AIR hg" x 120 99-/8" x length 9 4480 (19.93) 170 (11.11)
For larger sizes consult full line pipe hanger catalog.
B-Line
by ET'N
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Revised 4/28/2074 94 Fire Protection Solutions
C®US LISTED Fig. 25 - Surge Restrainer
Size Range - One size fits 3/4" thru 2" pipe.
Material - Pre-Galvanized Steel
Function - Designed to be used in conjunction with TOLCO® Band Hangers to
restrict the upward movement of piping as it occurs during sprinkler head
activation or earthquake type activity. The surge restrainer is easily and efficient-
ly installed by snapping into a locking position on the band hanger. This product
is intended to satisfy the requirements as indicated in the National Fire Protection
Association NFPA 13, 2010 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to
restrain either steel pipe or CPVC plastic Pipe.
Approvals - Underwriters' Laboratories Listed oft when used with TOLCO
band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and
Canada (cUL).
Finish - Pre-Galvanized
Order By - Figure number and TOLCO band hanger, size from 3/4"
thru 2".
Patent #5,344,108
.-'. .t.,
1/
OFFICEJMANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266 11
www.tolco.com
®TOLCO
Set Screw and
Locknut Included
I
D E
in. (mm) in. (mm)
B C
in. (mm) in. (mm)
1 1/2" (38.1) 3/4" (19.0) 1" (25.4) /16" (14.3)
11/2" (38.1) 3/4" (19.0) 1" (25.4) /16" (14.3)
Approx. WtI100
Lbs. (kg)
55 (24.9)
55 (24.9)
Part Rod Size
No. A
65-1I2 1/2"-13
65-I8 /811-11
Part F
No. in. (mm)
65-1I2 11/4" (317)
65-5/8 11/4" (31.7)
Beam Clamps
Fig. 65 - Reversible Steel C-Type Beam Clamp 3/4" (19.0mm) Throat Opening
Fig. 65XT - Reversible Steel C-Type Beam Clamp 3/4" (19.0mm) Throat Opening (bottom of page)
Size Range:
Fig. 65 - 1/2°..13 rod sizes, and /8'-11 rod sizes
Fig. 65XT - 3/8L16 rod size (see below)
Material: Steel with hardened cup point set screw and jam nut
Function: Recommended for hanging from steel beam where flange thickness does
not exceed 3/4" (19.0mm).
Features: All steel construction eliminates structural deficiencies associated with
casting type beam clamps. May be used on top or bottom flange of beam. (Beveled lip
allows hanging from top flange where clearance is limited.) May be installed with set
screw in up or down position. Offset design permits unlimited rod adjustment by
allowing the rod to be threaded completely through the clamp. Open design permits
inspection of thread engagement.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
Exceeds requirements of the National Fire Protection Association (NFPA), pamphlet 13,
/8°-16 rod will support 1/2" (15mm) thru 4" (100mm) pipe
1/2"13 rod will support thru 8" (200mm) pipe
Finish: Plain. Contact B-Line for alternative finishes and materials.
Order By: Figure number and finish
Fig. 65 Patent #4,570,885
Fig. 65XT-3/8 - Beam Clamp
Feature: Extruded holes allows for more thread
engagement of threaded rod and set screw.
Weight: Approx. Wt./100 - 28.0 Lbs. (12.7kg)
Finish: Plain or Electro-Galvanized
Order By: Figure number and finish
Approvals: Underwriters Laboratories Listed
(cULus) and FM Approved (FM) for up to 4"
(100mm) pipe.
Designed to meet or exceed requirements of
FM DS 2-0.
Set Screw and
Locknut Included
(3(9)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Fire Protection Solutions 13
B-Line
by ETeN
Beam Clamps
Fig. 69 - Beam Clamp Retaining Strap (B-Line B3361) ®TOLCD
Size Range: /'-16 thru /4'-10 rod
4" (101 .6mm) thru 16" (406.4mm) lengths
Note: longer lengths are available consult factory
Material: Pre-Galvanized Steel
Function: To offer more secure fastening of various types of
beam clamps to beam where danger of movement might be
expected. NFPA 13 requires the use of retaining straps with
all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13.
Important Note: Good installation practice of a retaining
strap requires that the strap be held tightly and securely to all
component parts of the assembly. Therefore a locking
mechanism of some kind, such as a hex nut for the Fig. 69 will
provide a more secure reliable installation.
Approvals: Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL). Approved for use with any listed beam
clamp.
Finish: Pre-Galvanized
Order By: Figure number, length (L), and finish.
Note: Minimum return on strap is 1" (25.4mm)
For Use With: Any B-Line or TOLCO beam clamp.
Hole Dia. 0 Length
Part No. in. (mm)
69-3/s-L /16" (30.1) Specify
69-1/2-L 9/16" (30.1) Specify
69-513-L 11/16" (50.8) Specify
69-/4-L 13/16" (63.5) Specify
B-Line
by ET.N
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
16 Fire Protection Solutions