Model BV-20 QR
8.0 K-factor
Quick Response
Extended Coverage Light Hazard
Pendent & Rec. Pendent Glass Bulb Automatic Sprinkler
Tyco Fire Products - www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446— USA
Customer Service/Sales: Tel: (215) 362-0700/ Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
CENTRAL
111141111111w,
U.! Description
The Central Model BV-20 OR,
8.0 K-factor Quick Response, Extended
Coverage Light Hazard (ECLH)
Pendent and Recessed Pendent
Sprinklers are decorative glass bulb
sprinklers designed for use in light
hazard occupancies such as churches,
hospitals, offices, and restaurants.
They are intended for use in automatic
sprinkler systems designed in accor-
dance with standard installation rules
(e.g., NFPA 13) for the protection of
light hazards up to a maximum cover-
age area of 400 ft2 (37,2 in2), as
compared to the maximum coverage
area of 225 112 (20,9 nf) for standard
coverage sprinklers.
The recessed version of the Central
Model BV-20 OR ECLH, intended for
use in areas with a finished ceiling, uses
a two-piece Model ELO Recessed
Escutcheon. The Model ELO Recessed
Escutcheon provides up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position. The adjustment
provided by these Recessed Escutch-
eons reduces the accuracy to which the
fixed pipe drops to the sprinklers must
be cut
Operation: The glass bulb contains a
fluid which expands when exposed to
heat When the rated temperature is
reached, the fluid expands sufficiently to
shatter the glass bulb, which then
allows the sprinkler to activate & flow
water.
WARNING
The Model BV-20 OR ECLH Pendent Rec. Pendent Sprinkleis descnbed
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association,
in addition to the standards of any other
authorities having jurisdiction. Failure to
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Technical
Data
Sprinkler Identification Number
SIN C4232
Approvals
UL & ULC Listed.
(The approvals apply only to the service
conditions indicated in the Design Criteria
Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
4 inch NPT
Discharge Coefficient
K = 8.0 GPM4si112 (115,2 LPM/bar)
Temperature Ratings
135°F1570C or 155°F/68°C
Finishes
Sprinkler White Polyester, Chrome
Plated, or Natural Brass
Rec Escutcheon White Coated, Chrome
Plated, or Brass Plated
Physical Characteristics
The Model BV-20 OR ECLH Pendent &
Rec. Pendent Sprinklers utilize a dedndfI-
cation resistant (DZR) bronze frame and a
3mm bulb. The two.piece button
assembly is brass and copper. The
sprinkler frame orifice is sealed with a
gasketed spring plate (Belleville Sea!)
consisting of a beryllium nickel disc spring
that is seated on both its inside and
outside edges with a Teflon' gasket The
compression screw is bronze, & the
deflector is brass.
*1
Extended
Coverage Light
Hazard Pendent
& Rec. Pendent
Me s
Figure 1- Cross Section
Model BV-20 QR ECLH,
Pendent Sprinkler
GASKETED SPRING
BU1TON PLATE
ASSEMBLY (BELLEVILLE
SEAL)
F SPRINKLER
GLASS BULB (lt-JJ FRAME
OPERATING
ELEMENT
/
DEFLECTOR COMPRESSION
SCREW
General do so may impair the integrity of these
devices.
No. 2-10.0
Figure 2- Model BV-20 OR ECLH, Pendent & Recessed Pendent Sprinklers
ELEVATION VIEW
I /
I FACE OF I I
REDUCING I
_________ / COUPLING
I
rL
1VH1N3
3/4" NPT 3/8" (9,5 mm) _________
1 Mm.
-1/8"(28,43 mm)
\CEILING LINE
Max. I FINISHED 21/8 OUTER '
(54:O
LT
FLAT RING/
._.-; L1-3116"J SUPPORT CUP
RENCH ESCUTCHEON
WRENCH
FLAT MODEL ELO RECESSED ___________ RECESSED 2-114"(57,2 mm) Mm. ESCUTCHEON
(30,2 mm)
.114" (82,6 mm)
Figure 3- W-Type 3 Sprinkler Wrench (Part #1073) Figure 4- ELO Offset Wrench (Part #1093)
Table 1- UL and ULC Listing Criteria for the Installation of Model BV-20 OR
Extended Coverage Light Hazard Pendent Sprinklers
Minimum
Spacing Flow/Pressure Style Temperature Rating
LH (0.1 gpm/sq. ft.)
16' x 16' 26.0 gpm /10.6 psi Pendent 135°F/570C 155°F1680C
(4,9 m 4,9 m) 98,4 Lpm / 0,73 bar Recessed Pendent 1350FI570C 155°F/680C
18' x 18' 33.0 gpm 117.0 psi Pendent 135°F1570C 155°F/680C
(5,5mx5,5m) 124,9 Lpm /1,l7bar Recessed Pendent 135°F/570C -
20' x 20 40.0 gpm /25.0 psi Pendent 135°F/570C -
Al m 6,1 m) 151,4 Lpm /1,72 bar Recessed Pendent 1350F/570C -
3Design
Criteria
The Model BV-20 OR, Extended Coverage Ught Hazard
(ECLH) Pendent and Recessed Pendent Sprinklers are UL
and ULC listed for use in light hazard occupancies, using the
design criteria in Table I as well as any additional
requirements specified in current NFPA 13 Standards for
Extended Coverage Pendent Sprinklers.
The minimum lateral spacing between the BV-20 OR ECLH
Pendent and Recessed Pendent Sprinkers to prevent cold
soldering, is 8 feet (2,4 m).
The Model BV-20 OR Sprinklers can be used with any metalic
flush or extended escutcheon, provided the maximum calling
to top of sprinkler deflector dimension specified in NFPA 13 is
maintained. For recessed applications, only the Model ELO
Recessed Escutcheon Assemblies may be used.
13 Installation
The Model BV-20 OR ELCH Sprinklers must be installed in
accordance with the following instructions:
NOTES
Do not install any bulb type sprinkler if the bulb is cracked
or there is a loss of liquid from the bulb. With the sprinkler
held horizontally, a small air bubble with an approximate
diameter of 1/16 inch should be present.
A leak tight 3/4 inch NPTspnnklerjoint should be obtained
with a torque of 10 to 20 ft ft. (13,4 to 26,8 Nm). A maximum
of 30 ft.lbs. (40,7 Nm) of torque is to be used to install 3/4 Inch
NPT sprinklers. Higherlevels of torque may distort the
sprinkler inlet with consequent leakage or impairment of the
sprinkler.
Do not attempt to compensate for insufficient adjustment in an
Escutcheon Plate by under- or over-tightening the Sprinkler.
Readjust the position of the sprinkler fitting to suit
Step 1. Pendent sprinklers must be installed only in the
pendent position. The deflector is to be parallel to the ceiling,
roof, or mounting surface, as applicable.
Step 2. After installing the ELO support cup (or other escutch-
eon, as applicable) over the sprinkler pipe threads & with pipe
thread sealant applied to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Wrench tighten the sprinkler using only the following
wrenches:
BV-20 OR Pend - W-Type 3 (Ref. Fig. 3)
BV-20 OR Rec. Pend - ELO Offset (Ref. Fig. 4)
Wrenches are to be applied to the sprinkler wrench flats (Ref.
Fig. 2) only.
a Care &
Maintenance
The Model BV-20 OR ECLH Sprinklers must be main-
tained and serviced in accordance with the following
instructions.
NOTES
Absence of an escutcheon which is used to cover a
clearance hole, may delay the time to operation in a fire
situation.
Before closing a fire protection system main control valve
for maintenance work on the fire protection system it
controls, permission to shut down the affected fire protec-
tion systems must be obtained from the proper authorities.
All personnel who may be affected by this action must be
notified.
Sprinklers which are found to be leaking or exhibiting
visible signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperatures will exceed 1000171380C and they
must never be painted, plated, coated or otherwise altered
after leaving the factory. Modified sprinklers must be
replaced. Sprinklers that have been exposed to corrosive
products of combustion, but have not operated, should be
replaced if they cannot be completely cleaned by wiping the
sprinkler with a cloth or by brushing it with a soft bristle
brush.
Care must be exercised to avoid damage - before, during,
and after installation. Sprinklers damaged by dropping,
striking, wrench twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that has a cracked bulb
or that has lost liquid from its bulb (Ref. Installation Sec-
tion).
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Association
(e.g., NFPA 25), in addition to the standards of any other
authorities having jurisdiction. The installing contractor or
sprinkler manufacturer should be contacted relative to any
questions.
It is recommended that automatic sprinkler systems be
inspected, tested, and maintained by a qualified Inspection
Service.
Limited V-i Ordering
Warranty I±l Information
Products manufactured by Tyco Fire Ordering Information: When placing an Products are warranted solely to the order, indicate the full product name. original Buyer for ten (10) years Please S ecify the quantity, model, style, against defects in material and orifice size, temperature rating, type of
workmanship when paid for and finish or coating, and sprinkler wiench.
properly installed and maintained Refer to price list for complete listhgof
under normal use and service. This Part Numbers.
warranty will expire ten (10) years Teflon isatrademark of the DuPont Cop from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufac-
tured by companies not affiliated by
ownership with Tyco Fire Products or
for products and components which
have been subject to misuse, im-
proper installation, corrosion, or which
have not been installed, maintained,
modified or repaired in accordance
with applicable Standards of the
National Are Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction.
Materials found by Tyco Are Products
to be defective shall be either repaired
or replaced, at Tyco Fire Products'
sole option. Tyco Fire Products
neither assumes, nor authorizes any
person to assume for it, any other
obligation in connection with the sale
of products or parts of products. Tyco
Fire Products shall not be responsible
for sprinkler system design errors or
inaccurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE
POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY
EXCEED AN AMOUNT EQUAL TO
THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OFANYAND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED. INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
tqco/Flowcontroi/Tyco Fir.
, Products Printed in U.S.A. 2-01
Model KI I ECOH Amih Model K14 ECOW,
Extended Coverage EENTRAL
Ordinary Hazard Sprinklers
Tyco Fire Products - www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Customer Services/Sales: Tel: (215) 362-0700/ Fax: (215) 362-5385
Technical Services: Tel. (800) 381-9312/ Fax: (800) 791-5500
General
Description
The Central Models K1 1 & K14
ECOH, 11.2 and 14.0 K-Factor,
Standard Response, Extended Cov-
erage Ordinary Hazard (ECOH) Pen-
dent, Recessed Pendent, and Up-
right Sprinklers are decorative glass
bulb sprinklers designed for use in
ordinary hazard occupancies such
as showrooms, retail stores, and
light manufacturing.
They are intended for use in automat-
ic sprinkler systems designed in ac-
cordance with standard installation
rules (e.g., NFPA 13) for the protec-
tion of ordinary hazards up to a maxi-
mum coverage area of 256 ft2 (23,8 M2) for the Ki 1 and 400 ft2 (37,2
m2) for the K14, as compared to the
maximum coverage area of 130 ft2
(12,1 m2) for standard coverage
sprinklers.
The Models Ku 1 & K14 ECOH Sprin-
klers feature a UL and C-UL Listing
that permits their use with unob-
structed or non-combustible ob-
structed ceiling construction as de-
fined and permitted by NFPA 13.
The Models Ku 1 & K14 ECOH Sprin-
klers have been fire tested to com-
pare their performance to that of
standard spray sprinklers installed at
standard spacings (i.e. 15 feet maxi-
mum on center spacing and 130 sq.
ft. maximum coverage area for ordi-
nary hazard). These tests have
shown that the protection provided
by these ECOH Sprinklers is equal
to or more effective than standard
spray sprinklers.
The recessed version of the Models
Ki 1 & K14 ECOH Sprinklers using a
two-piece Series 4211 Recessed Es-
cutcheon provides up to 3/4 inch
(19,1 mm) of total adjustment from
the flush pendent position. The ad-
justment provided by the Recessed
Escutcheon reduces the accuracy to
which the fixed pipe drops to the
sprinklers must be cut.
Operation. The glass bulb contains
a fluid which expands when exposed
to heat. When the rated temperature
is reached, the fluid expands suffi-
ciently to shatter the glass bulb,
which then allows the sprinkler to ac-
tivate and flow water.
WARNINGS
The Models Ku I & K14 ECOH Sprin-
klers described herein must be in-
stalled and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the integ-
rity of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. The installing contractor or
sprinkler manufacturer should be
contacted relative to any questions.
Technical
Data
Sprinkler Identification Numbers
SIN C5137 K=11.2 Upright
SIN C5237 K=1 1.2 Pendent
SIN C6137 K=14.0 Upright
SIN C6237 K=14.0 Pendent
Approvals
UL and C-UL Listed. FM Approved.
(Refer to Table A. The approvals ap-
ply only to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
K11 & K14
ECOH
Pendent,
Recessed &
Upright
Sprinklers
No. 2-1.1
K=11.2
ORDINARY HAZARD
GROUP 1 ORDINARY HAZARD GROUP2
0.15 gpm1ft2 Density 0.20 gpmlft2 Density Coverage Area Maximum Distance
From
wall Ft
Minimum Flow, GPM
Minimum
Pressure, PSI
Minimum Flow, GPM
Minimum Pressure, PSI
Ft. x Ft. Sq. Ft
14x14 196 7 29.6 7.0 39.2 12.3
16x16 256 8 38.4 11.8 51.2 120.9
K=14.0
ORDINARY HAZARD GROUP 1 ORDINARY HAZARD GROUP 2
0.15 gpm/ft2 Density 0.20 gpm/112 Density Coverage Area Maximum Distance From Wall Ft.
Minimum Flow, GPM
Minimum Pressure, PSI
Minimum Flow, GPM
Minimum Pressure, PSI
Ft. x Ft. Sq. R.
16x16 256 8 38.4 7.5 51.2 13.4
18x18 324 9 48.6 12.1 64.8 21.4
20x20 400 10 1 60.0 1 18.4 1 80.0 32.7
Table B
UL and C-UL Listing Criteria For The Installation Of
Model Ku 1 & K14 ECOH Sprinklers
Nominal Discharge Coefficients
K= 11.2 GPM/psi 2
(161,3 LPMIbari'2)
K = 14.0 GPM/psi112
(201,6 LPM/bar"2)
Temperature Ratings
Pendent and Upright: 135°F/57°C to
2860F/1 82°C
Recessed Pendent:
135°F/570C to 200°F/930C
Finishes
Sprinkler: White Polyester, Chrome
Plated, Natural Brass, Lead Coated
Recessed Escutcheon: White
Coated or Chrome Plated
(Other finishes are available on re-
quest.)
Physical Characteristics
The Ku I & K14 ECOH utilize a 3 m
diameter glass bulb and a dezincifi-
cation resistant bronze alloy frame.
The frame orifice is sealed with gas-
keted spring plate (Belleville Seal)
consisting of a beryllium nickel disc
spring that is sealed on both its in-
side and outside edges with a Tef-
lon? gasket.
Design
Criteria
The Models Ku 1 & K14 ECOH Sprin-
klers must only be installed in ac-
cordance with the applicable UL and
C-UL Listing or FM Approval require-
ments as indicated below. Only the
Series 4211 Recessed Escutcheon
is to be used for recessed installa-
tion.
UI and C-UL Listing
Requirements
The Models Ku I & K14 ECOH
Sprinklers may be used for the
coverage areas shown in Table B,
based on maintaining the mini-
mum specified flow rate as a func-
tion of coverage area and hazard
group for all of the sprinklers in the
design area.
With respect to heat sensitivity,
the Models Ku 1 & 1(14 ECOH
Sprinklers are permitted to be
used with unobstructed or non-
combustible obstructed ceiling con-
struction as defined and permitted
by NFPA 13. For example:
Unobstructed, combustible or non-
combustible, ceiling construction
with a deflector to ceiling/roof deck
distance of 1 t 12 inches (25 to
300 mm).
Obstructed, noncombustible, ceil-
ing construction with a deflector lo-
cation below structural members
of 1 to 6 inches (25 to 150 mm)
and a maximum deflector to ceil-
ing/roof deck distance of 22 inches
(550 mm).
The minimum allowable spacing
between the Models Ku 1 & K14
ECOH Sprinklers, to prevent
cold soldering, is 8 feet (2,4 m) for
upright sprinklers and 9 feet (2,7
m) for pendent sprinklers.
The Models Ki 1 & K14 ECOH
Sprinklers are to be installed in ac-
cordance with all other require-
ments of NFPA 13 for extended
coverage upright and pendent
sprinklers.
FM Approval
Requirements
The Models Ku 1 & K14 ECOH Sprin-
klers are to be installed in accord-
ance with the applicable Factory Mu-
tual Loss Prevention Data Sheet for
limited use in buildings of specific
roof construction and for the protec-
tion of certain specific ordinary haz-
ard (non-storage and/or non-flamma-
ble or combustible liquid)
occupancies. Information provided in
the FM Loss Prevention Data Sheets
relate to, but are not limited to, hy-
draulic design, ceiling slope and ob-
structions, minimum and maximum
allowable spacing, and deflector-to
ceiling distance.
r3 Installation
The Models Ku I & K14 ECOH Sprin-
klers must be installed in accord-
ance with the following instructions:
NOTES
Do not install any bulb type sprinkler
if the bulb is cracked or there is a
loss of liquid from the bulb. With the
sprinkler held horizontally, a small
air bubble should be present. The di-
ameter of the air bubble is approxi-
mately 1/16 inch (1,6 mm) for the
135°F/57°C to 3/32 inch (2,4 mm) for
the 286°F/141 °C temperature ratings.
A leak tight 3/4 inch NPT sprinkler
joint should be obtained with a
torque of 10 to 20 ft.lbs. (13,4 to
26,8 Nm). A maximum of 30 ftlbs.
(40.7 Nm) of torque is to be used to
install sprinklers. Higher levels of
torque may distort the sprinkler inlet
with consequent leakage or impair-
ment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutch-
eon Plate by under- or over-tighten-
ing the Sprinkler. Readjust the
position of the sprinkler fitting to suit.
Step 1. The sprinkler must be in-
1/2" (12.7 mm)
NOMINAL MAKE-IN
2-7/16"
(61.9 mm)
1-11/16"
(42.7 mm)
ESCUTCHEON PLATE
SEATING SURFACE
WRENCH FLAT
(BOTH SIDES)
2-7/8" DIA.
(73.0 mm) FLUSH
- (19.1*9.5 mm) - 2-1/4" DIA. 3/4"(19.1 mm)
FACE OF (57.2 mm)
SPRINKLER 1/8"
FITTING (3.2 mm)
MOUNTING /MOUNTING
SURFACE/ SjJ( PLATE
CLOSURE
5/8"(15.9 mm)
1-3(8" (34.9 mm)
Figure 2
Figure 1 Models Ku I ECOH or K14 ECOH
Models Ku 1 ECOH or K14 ECOH Pendent Sprinklers Pendent and Upright Sprinklers With Series 4211 Recessed Escutcheon
SPRINKLER FINISH
Pendent (C5237 or C6237)
Upright (C5137 or C6137)
Recessed (C5237 or C6237)
wlSenes 4211 Escutcheon
Temperature
Rating
Bulb
Color Code
Natural
Brass
Chrome
Plated
Polyester
Coated
(All Colors)
Lead
Coated
Natural
Brass
I Chrome
Plated
Polyester
Coated
I (All Colors)
135°F/570C Orange 1,2,3 1,2
155°F1680C Red 1,2,3 1,2
1750F/790C Yellow 1,2,3 1,2
200°F/93°C Green 1,2,3 1.2
286°F/930C Blue 1,2, 3 N/A
Notes:
Listed by Underwriters Laboratories, Inc.
Listed by Underwriters Laboratories for use in Canada (i.e., C-UL Listed)
Approved by Factory Mutual Research Corporation.
N/A: Not Available.
Table A
Laboratory Listings and Approvals
(The laboratory listings and approvals only apply to the service conditions
indicated in the Design Criteria section.)
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
Figure 3
W-Type 3
Upright and Pendent
Sprinkler Wrench
Figure 4
W-Type 4
Recessed Pendent
Sprinkler Wrench
stalled with the deflector parallel to
the mounting surface. Pendent sprin-
klers must be installed in the pen-
dent position, and upright sprinklers
must be installed in the upright posi-
tion.
Step 2. After installing the Series
4211 mounting plate (or other es-
cutcheon, as applicable) over the
sprinkler pipe threads and with pipe
thread sealant applied to the pipe
threads, hand tighten the sprinkler
into the sprinkler fitting.
Step 3. Wrench tighten upright or
pendent sprinklers using only the W-
Type 3 (End A) Sprinkler Wrench.
Wrench tighten the recessed pen-
dent sprinklers using only the W-
Type 4 Sprinkler Wrench. The
wrench recess of the applicable
sprinkler wrench (Ref. Figure 3 and
4) is to be applied to the sprinkler
wrench flats (Ref. Figure 1).
]Maintenance
Care&
The Model Ki 1 & K14 ECOH Sprin-
klers must be maintained and serv-
iced in accordance with the following
instructions:
NOTES
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to operation in a fire
situation.
Before closing a fire protection sys-
tem main control valve for mainte-
nance work on the fire protection sys-
tem which it controls, permission to
shut down the affected fire protec-
tion systems must be obtained from
the proper authorities and all person-
nel who may be affected by this ac-
tion must be notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where their tem-
perature will exceed 100°F/38°C and
they must never be painted, plated,
coated, or otherwise altered after
leaving the factory. Modified sprin-
klers must be replaced. Sprinklers
that have been exposed to corrosive
products of combustion, but have not
operated, should be completely
cleaned by wiping the sprinkler with
a cloth or by brushing it with a soft
bristle brush.
Care must be exercised to avoid
damage before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slip-
page, or the like, must be replaced.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb (Ref. Installation Sec-
tion).
The owner is responsible for the in-
spection, testing, and maintenance
of their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer. for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under nor-
mal use and service. This warranty
will expire ten (10) years from date
of shipment by Tyco Fire Products.
No warranty is given for products or
components manufactured by com-
panies not affiliated by ownership
with Tyco Fire Products or for prod-
ucts and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with
applicable Standards of the National
Fire Protection Association, and/or
the standards of any other Authori-
ties Having Jurisdiction. Materials
found by Tyco Fire Products to be de-
fective shall be either repaired or re-
placed, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products
or parts of products. Tyco Fire Prod-
ucts shall not be responsible for
sprinkler system design errors or in-
accurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDI-
RECT, SPECIAL OR CONSEQUEN-
TIAL DAMAGES, INCLUDING BUT
NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POS-
SIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY EX-
CEED AN AMOUNT EQUAL TO THE
SALES PRICE.
flOrdering
infonnation
Ordering Information: When placing
an order, indicate the full product
name. Please specify the quantity,
model, style, and size, as applicable.
Refer to Price List for complete list-
ing of Part Numbers.
Please Specify:
Model Ku 1 ECOH Upright Sprinkler.
Model Ki 1 ECOH Pendent Sprinkler.
Model K14 ECOH Upright Sprinkler.
Model 1(14 ECOH Pendent Sprinkler.
W-Type 3 Sprinkler Wrench.
W-Type 4 Sprinkler Wrench.
Series 4211 Recessed Escutcheon.
Patents:
U.S.A. Patent Numbers 5,366,022;
5,579,846; 5,584,344; 5,609,211;
5,862,994; and 5,865,256 are ap-
plicable to the Models K1 & K1
ECOH Sprinklers. Other patents are
pending with regard to other design
features.
Conversion Factors:
lft.= 0.3048m 1 sq. ft.= 0.093 m2
1 gpm = 3.785 1pm 1 psi = 0.06895 bar
1 gpm/ft2 = 40.74 mm/mm
tqca/Rowcontrol/ Tyco Fire Products Printed in U.S.A. 2-01