HomeMy WebLinkAbout2006 COSTA DEL MAR RD; ; AS05027510/6/2020 AS050275 Permit Data
City of Carlsbad
Sprinkler Permit
2006 COSTA DEL
Job Address:
MAR RD
Permit Type: SPRINK
Parcel No: 2166100201
Lot #: 0
Reference No.:
PC #:
Permit No: AS050275
Status: ISSUED
Applied 12/30/2005
Approved: 1/6/2006
Issued: 1/6/2006
Inspector:
Project Title: LA COSTA RESORT, BLDG. 2 FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant: Owner:
COSCO FIRE PROTECTION
10695 TREENA ST
SAN DIEGO, CA,
-W1 El El I
Fees ($) Add'I Fees ($) Total ($) Balance ($)
2,280 0 2,280 0
1/1
Asoeyo~~S_
c
hydrauhc:calculations Page 1
'2dflbór'4hEàd unit Date 113005
HYDRAULIC DESIGN INFORMATION SHEET
Name - La Costa Resort and Spa Date -
Location - 2006 Costa Del Mar Rd Carlsbad
Building - Building Two 2nd FLOOR LIVING UNIT System No. - 2ND floor UNIT
Contractor - Cosco Fire Protection Inc Contract No. - 10CB-0206
Calculated By - PG Drawing No. - FP3
Construction: (xx) Combustible ( ) Non-Combustible Ceiling Height 9'
OCCUPANCY - Residential
S Type of Calculation: ( x)NFPA 13 Residential (x)NFPA 13R ( )NFPA 13D
Y Number of Sprinklers Flowing: ( )1 ( )2 (x)4
S )Other
T )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 17 Gpm System Type
Listed Pres. at Start Point - 12 Psi (x) Wet C ) Dry
D MAXIMUM LISTED SPACING 18 x 18 Deluge C ) PreAction
E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle
S Additional Flow Added - 100 Gpm Make tyco Model LFII
I Elevation at Highest Outlet - Feet Size K-Factor 4.9
G Note: Temperature Rating 155
N
Calculation Gpm Required 76.25 Psi Required 71.75
Summary C-Factor Used: Overhead 150
W Water Flow Test: Pump Data:
A Date of Test - 10-11-04 Rated Cap.
T Time of Test - @ Psi
E Static (Psi) - 126 Elev.
R Residual (Psi) - 109 Other
Flow (Gpm) - 3000
S Elevation - 40
P Location: ESTRELLA DEL MAR
P
L Source of Information MDS CONSULTING
Y
At Test
Underground 150
Tank or Reservoir:
Cap.
Elev.
Well
Proof Flow Gpm
VVdLI OUI4)Iy %.,Ul VC I.4
hydraulic calculations Page 2
2nd floor 4 head unit Date 113005
City Water Supply: Demand:
Cl - Static Pressure : 126 Dl - Elevation : 10.827
C2 - Residual Pressure: 109 D2 - System Flow : 76.249
stem Pressure : 86.791
HoseAdj City) C2 - Residual Flow : 3000 D2 - S
~Demancf) Hose : 100
D3 - System Demand : 176.249 Safety Margin : 39.120
150
140
130 : !±
p120_
R11°
E10°
S 90
S 80
U 70
R6°
E5°
40
30
20
10 --1-
-.--.
300 600 900 1200 1500 1800 2100 2400 2700
FLOW (NA 1.85)
C2
Comouter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
ILLIIIb USU oUlluhidly
hydraulic calculations Page 3
2nd floor 4 head unit • Date 113005
Fitting Legend
Abbrev. Name ½ ~ 1 1% 1% 2 2% 3 3½ 4 5 6 8 10 12 14 16 18 20 24
E 90 Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F 45' Elbow I I 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
I 90' Flow lhruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Zfa Febco 826YD Fitting generates a Fixed Loss Based on Flow
Computer Proarams by Hvdratec Inc. Route 111 Windham N.H.. USA 03087
Pressure / Flow Summary - STANDARD
hydraulic calculations Page 4
2nd floor 4 head unit Date 113005
Node
No.
Elevation K-Fact Pt
Actual
Pn Flow Density Area Press
Actual Req.
DIOI 25.5 4.9 12.05 na 17.01 0.0525 324 12.0
1 65.0 K= K @ EQOI 12.61 na 17.01
3 65.0 K= K @ EQOI 13.07 na 17.32
5 65.0 K= K @ EQ01 16.37 na 19.38
7 65.0 K = K @ EQOI 22.14 na 22.54
2 65.0 13.91 na
4 65.0 17.34 na
6 65.0 23.12 na
8 65.0 33.39 na
23 65.0 40.71 na
TOR 65.0 60.54 na
BOR 46.0 71.15 na
Dl 42.5 72.77 na
BI 42.0 73.13 na
B2 42.0 73.18 na
B3 42.0 85.87 na
B4 42.0 85.9 na
S 40.0 86.79 na 100.0
The maximum velocity is 18.1 and it occurs in the pipe between nodes 4 and 6
Final Calculations - Hazen-Williams
hydraulic calculations Page 5
2nd floor 4 head unit Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
DIOI 17.01 1.101 IT 6.328 1.000 12.051 K Factor = 4.90
to 120 0.0 6.328 0.0
EQOI 17.01 0.0761 0.0 7.328 0.558 Vel = 5.73
0.0
17.01 12.609 K Factor = 4.79
1 17.01 1.101 2E 7.65 8.600 12.609 K Factor © node EQOI
to 150 IT 9.563 17.213 0.0
2 17.01 0.0504 0.0 25.813 1.302 Vel = 5.73
0.0
17.01 13.911 K Factor = 4.56
3 17.32 1.101 IT 9.563 6.500 13.073 K Factor © node EQOI
to 150 0.0 9.563 0.0
2 17.32 0.0522 0.0 16.063 0.838 Vel = 5.84
0.0
17.32 13.911 K Factor = 4.64
5 19.38 1.101 IT 9.563 5.600 16.369 K Factor © node EQOI
to 150 0.0 9.563 0.0
4 19.38 0.0642 0.0 15.163 0.974 Vel = 6.53
0.0
19.38 17.343 K Factor = 4.65
7 22.54 1.101 IT 9.563 2.080 22.136 K Factor @ node EQOI
to 150 0.0 9.563 0.0
6 22.54 0.0849 0.0 11.643 0.988 Vel = 7.60
0.0
22.54 23.124 KFactor= 4.69
2 34.33 1,101 IT 9.563 9.000 13.911
to 150 0.0 9.563 0.0
4 34.33 0.1849 0.0 18.563 3.432 Vel = 11.57
4 19.38 1.101 IT 9.563 4.100 17.343
to 150 0.0 9.563 0.0
6 53.71 0.4231 0.0 13.663 5.781 Vel = 18.10
6 22.54 1.394 21 19.046 21.000 23.124
to 150 0.0 19.046 0.0
8 76.25 0.2564 0.0 40.046 10.268 Vel = 16.03
8 0.0 1.394 2E 9.523 19.000 33.392
to 150 0.0 9.523 0.0
23 76.25 02564 0.0 28.523 7.314 Vel = 16.03
23 0.0 1.598 3E 17.484 98.000 40.706
to 150 31 34.968 52.452 0.0
TOR 76.25 0.1318 0.0 150.452 19.837 Vel = 12.20
Final Calculations - Standard
hydraulic calculations Page 6
2nd floor 4 head unit Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ***** Notes ******
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
TOR 0.0 2.157 0.0 19.000 60.543
to 120 0.0 0.0 9.729 * Fixed loss = 1.5
BOR 76.25 0.0462 0.0 19.000 0.878 Vet = 6.69
BOR 0.0 4.1 2E 29.067 40.000 71.150
to 140 0.0 29.067 1.516
Dl 76.25 0.0015 0.0 69.067 0.106 Vel = 1.85
Dl 0.0 4.07 IF 6.373 77.000 72.772
to 150 IE 15.932 22.305 0.217
61 76.25 0.0014 0.0 99.305 0.137 Vet = 1.88
BI 0.0 4.1 IT 29.067 5.500 73.126
to 140 0.0 29.067 0.0
B2 76.25 0.0015 0.0 34.567 0.053 Vet = 1.85
B2 0.0 4.1 IE 14.534 5.000 73.179
to 140 lZfa 0.0 14.534 12.661
83 76.25 0.0015 0.0 19.534 0.030 Vel = 1.85
B3 0.0 4.1 IE 14.534 5.500 85.870
to 140 0.0 14.534 0.0
B4 76.25 0.0015 0.0 20.034 0.030 Vet = 1.85
B4 0.0 5.86 IG 3.834 60.000 85.900
to 150 IT 38.342 42.177 0.866
S 76.25 0.0002 0.0 102.177 0.025 Vet = 0.91
100.00 Qa= 100.00
176.25 86.791 KFactor= 18.92
~FA~
Tjt1=.1.M
- - - Fire Protection by Computer Desig
n
COSCO FIRE PROTECTION
10695 TREENA STREET
SUITE 105
CARLSBAD, CA 92131
858 444-2000
Job Name 2nd floor 4
Building : BLD 2 2nd FLOOR. Location : 2006 Costa Del Mai R
d
J
C
a
r
I
s
b
I
System : 2ndfIoorCORR
Contract : IOCB-0206
Data File : LCRV 2wx2
F
; Z 44
Computer Programs by Hydratec Inc.
R
o
u
t
e
111 Windham N.H. USA 03087
El
Most
Protection Design S Ccsung
rith. Comments
Date
tOSCO FIRE PROTECTION
Page 1
2nd floor 4 head CORRIDOR
Date 113005
HYDRAULIC DESIGN INFORMAT
I
O
N
S
H
E
E
T
Name - La Costa Resort and Spa
Date -
Location - 2006 Costa Del Mar Rd Carlsbad Building - BLD 2 2nd FLOOR CORRIDOR
System No. - 2nd floor CORR
Contractor
- Cosco Fire Protection Inc
Contract No.
- IOCB-0206
Calculated By - PG
Drawing No.
- FP3
Construction: (xx) Combustible ( ) Non-Combustible Ceiling Height 9'
OCCUPANCY - Residential
S Type of Calculation: ( x)NFPA 13 Residential (x)NFPA 13R ( )NFPA 13D
Y Number of Sprinklers Flowing
:
C )l ( )2 (x)4 S ( )Other
T ( )Specific Ruling
Made by Date
E
M Listed Flow at Start Point
- 21 Gpm System Type
Listed Pres. at Start Poin
t
- 25 Psi (x) Wet C ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added
- 0 Gpm Sprinkler or Nozzle
S Additional Flow Added
- 100 Gpm Make tyco Model LFII HSW
I Elevation at Highest Outlet
- Feet Size K-Factor 4.2
G Note:
Temperature Rating 155
N
Calculation Gpm Required 86
.
6
5
Psi Required 74.12 At Test
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test:
Pump Data: Tank or Reservoir:
A Date, of Test
- 5-17-05 Rated Cap. Cap. T Time of Test
- @ Psi Elev. E Static (Psi) - 113
, Elev. R Residual (Psi)
- 105 Other
Well Flow (Gpm)
- 1234
Proof Flow Gpm
S Elevation
- 56.33 P Location: ESTRELLA DE
L
MAR & COSTA DEL MAR P
L Source of Information: CO
S
C
O
F
I
R
E
P
R
O
T
E
C
T
I
O
N
/ CWD Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 0
3
0
8
7
COSCO FIRE PROTECTION
Page 2 2nd floor 4 head CORRIDOR
Date 113005
City Water Supply:
Demand: Cl - Static Pressure : 113
Dl - Elevation : 3.755
C2 - Residual Pressure: 105
D2 - System Flow : 88.611 stm Pressure : 83.359
C2 - Residual Flow : 1234
D2 -
SrAd' Hose j City)
________Hose Demand) : 100 D3 - System Demand : 188.611 Safety Margin : 29.394
150
140
130
p120 C1
R11°
E 100
90
IO'odnl
u 70
R6°
E5°
40
30
20
10
200 400 600 800 1000 .1200 1400 1600 1800 FLOW (N"1.85)
Comouter Procirams by Hvdratec Inc. Route 111 Windham N.H. USA
0
3
0
8
7
COSCO FIRE PROTECTION
Page 3 -
2nd floor 4 head CORRIDOR
Date 113005 Fitting Legend
Abbrev. Name % % 1 1% 1V2 2 2'A 3 3V2 4 5 6 8 10 12 14 16 18 20 24 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F 45' Elbow I 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
I 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Zfa Febco 826YD Fitting generates a Fixed Loss Based on Flow
Comouter Proarams by Hvdratec Inc. Route 111
W
i
n
d
h
a
m
N
.
H
.
U
S
A
0
3
0
8
7
I Ii-,Saulu I I Ill VV J UI I SI I Icil y - j I U u.ru LI
OSCO FIRE PROTECTION
Page 4 2nd floor 4 head CORRIDOR
Date 113005 Node Elevation K-Fact Pt Pn Flow Density Area. Press
No.
Actual Actual Rea.
D103 25.5 4.2 25.0 na 21.0 0.082 256 25.0
0105 25.5 4.2 25.0 na 21.0 0.082 256 25.0
EQ21 65.0 4.2 25.0 na 21.0 0.082 256 25.0
EQ20 65.0 4.2 25.22 na 21.09 0.082 256 25.0
20 65.0 26.69 na 21 65.0 31.29 na 8 65.0 31.48 na 22 65.0 K = K @ EQ22 31.53 na 22.18 23 65.0 K = K @ E023 37.05 na 24.34 TOR 65.0 63.24 na BOR 46.0 74.13 na Dl 42.5 75.78 na BI 42.0 76.18 na B2 42.0 76.25 na B3 42.0 89.19 na B4 42.0 89.23 na S 40.0 90.13 na 100.0 J 56.33 83.34 na TEST 56.33 83.36 na
The maximum velocity is 14.18 and it occurs
i
n
t
h
e
p
i
p
e
b
e
t
w
e
e
n
n
o
d
e
s
2
0
a
n
d
2
1
Computer Programs by Hydratec Inc. Route
1
1
1
L Windham N.H. USA 03087
I Ii•IcI .,aI.,UIaLnJI io i I0L.I i vv 111101110
COSCO FIRE PROTECTION
Page 5 2nd floor 4 head CORRIDOR
Date 113005 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv Notes Point Qt Pf/UL Eqv. Ln. Total Pf Pn
D103 21.00 1.101 4E 10.126 12.500 26.000 K Factor = 4.20 to 120 IT 6.328 16.454 0.0 EQ22 21.0 0.1125 0.0 28.954 3.258 Vet = 7.08 0.0
21.00
28.258 K Factor = 3.95 0105 21.00 1.101 4E 10.126 6.500 25.000 K Factor =4.20 to 120 IT 6.328 16.454 0.0 EQ23 21.0 0.1125 0.0 22.954 2.583 Vet = 7.08 0.0
21.00
. 27.583 K Factor = 4.00 EQ2I 21.00 1.101 2E 7.65 5.500 25.000 K Factor = 4.20 to 150 IT 9.563 17.213 0.0 20 21.0 0.0745 0.0 .22.713 1.691 Vet = 7.08 0.0
21.00
26.691 K Factor = 4.06 EQ20 21.09 1.101 2E 7.65 2.400 25.219 K Factor =4.20 to 150 IT 9.563 17.213 0.0 20 21.09 0.0751 0.0 19.613 1.472 Vet = 7.11 20 21.00 1.101 IT 9.563 7.500 26.691 to 150 0.0 9.563 0.0 21 42.09 0.2695 0.0 17.063 4.599 Vet = 14.18 21 0.0 1.394 0.0 2.200 31.290 to 150 0.0 .0.0 0.0 8 42.09 0.0855 0.0 2.200 0.188 Vet = 8.85 8 0.0 1.394 0.0 0.580 31.478 to 150 0.0 0.0 . 0.0 22 42.09 0.0862 0.0 0.580 0.050 Vet = 8.85 22 22.18 1.394 2E 9.523 20.000 31.528 K Factor @ node EQ22
to 150 0.0 9.523 0.0 23 64.27 0.1869 0.0
. 29.523 5.519 Vet = 13.51 23 24.34 1.598 3E 17.484 98.000 37.047 K Factor © node EQ23
to 150 3T 34.968 52.452 0.0 TOR 88.61 0.1741 0.0 150.452 26.194 Vet = 14.17 TOR 0.0 2.157 0.0 19.000 63.241 to 120 0.0 0.0 9.729 * Fixed loss = 1.5
BOR 88.61 0.0610 0.0 19.000 1.159 Vet = 7.78 BOR 0.0 4.1 . 2E 29.067 40.000 74.129 to 140 0.0 29.067 1.516 DI 88.61 0.0020 0.0 69.067 0.139 Vet = 2.15 Dl 0.0 4.07 IF 6.373 77.000 75.784 o 150 IE 15.932 22.305 0.217 BI 88.61 0.0018 0.0 99.305 0.182 Vet = 2.19
Computer Programs by Hydratec Inc. Rout
e
111 Windham N.H. USA 03087
i .i•o, .iait,uiouui ,o
- ivai u
'COSCO FIRE PROTECTION
Page 6 2nd floor 4 head CORRIDOR
Date 113005 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe PV ******* Notes ******
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
Bi
to
B2
0.0
88.61
4.1
140
0.0020
IT 29.067
0.0
0.0
5.500
29.067
34.567
76.183
0.0
0.069 Vel = 2.15 B2 0.0 4.1 1 14.534 5.000 76.252 to 140 lZfa 0.0 14.534 12.898 B3 88.61 0.0020 0.0 19.534 0.040 Vet = 2.15 B3 0.0 4.1 1 14.534 5.500 89.190
V
to 140 0.0 14.534 0.0 V B4 88.61 0.0020 0.0 20.034 0.040 Vet = 2.15 B4 0.0 5.86 to 150 S 88.61 0.0003
S 100.00 5.86 to 150 J 188.61 0.0013
J 0.0' 8.27 to 140 TEST 188.61 0.0003
0.0
188.61
1 3.834 60.000 89.230 IT 38.342 42.177 0.866 0.0 102.177 0.032 VeI= 1.05 2G 7.668 180.000 90.128 Qa = 100 IT 38.342 46.011 -7.073 0.0 226.011 0.285 Vel = 2.24 0.0 '70.000 83.340 0.0 0.0 0.0 V
V 0.0 70.000 0.019 Vel = 1.13
83.359 K Factor = 20.66
Computer Programs by Hydratec Inc.
R
o
u
t
e
1
1
1
W
i
n
d
h
a
m
N
.
H
.
U
S
A
0
3
0
8
7
-. Fire Protection by Computer Design
COSCO FIRE PROTECTION
10695 TREENA STREET
SUITE 105
CARLSBAD, CA 92131
858 444-2000
Job Name : 2nd floor 4 head unit
Building : Building Two 2nd FLOOR LIVING UNIT
Location : 2006 Costa Del Mar Rd Carlsbad
System : 2ND floor UNIT
Contract : I OCB-0206
Data File : LCRV 2.wxl
Computer Programs by Hydratec Inc. Route 111 Wi
n
d
h
a
m
N
.
H
.
U
S
A
0
3
0
8
7
COSCO FIRE PROTECTION
Page 1 .2nd floor head unit
Date 113005
HYDRAULIC DESIGN INFORMATION SHEE
T
Name - La Costa Resort and Spa
Date -
Location - 2006 Costa Del Mar Rd Carlsbad
Building - Building Two 2nd FLOOR LIVING UNIT
System No. - 2ND floor UNIT Contractor Cosco Fire Protection I
n
c
Contract No. - 10CB-0206 Calculated By
- PG
Drawing No. - FP3 Construction: (xx) Combustible ( ) Non-Combustible Ceiling Height 91 OCCUPANCY - Residential
Type of Calculation: ( x)NFPA 13 Residential (x)NFPA 13R )NFPA 13D Number of Srinklers Flowing:
)1 ( )2 (x)4 )Other
)Specific Ruling
Made by Date
Listed Flow at Start Point
- 17 Gpm System Type Listed Pres. at Start Point
- 12 Psi (x) Wet ( ) Dry MAXIMUM LISTED SPACING 18 x 18 ( ) Deluge ( ) PreAction Domestic Flow Added
- 0 Gpm Sprinkler or Nozzle Additional Flow Added
- 100 Gpm Make tyco Model LFII Elevation at Highest Outlet
- Feet Size K-Factor 4.9 Note:
Temperature Rating 155
Calculation Gpm Required 76.25
Psi Required 71.75 At Test Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test
- 5-17-05 Rated. Cap. Cap. T Time of Test
- Psi Elev. E Static (Psi) - 113 Elev. R Residual (Psi) - 105 Other Well Flow (Gpm)
- 1234
ProofFlow Gpm S Elevation
- 40 P Location: ESTRELLA DEL MAR & Costa Del Mar RD P
L Source of Information: COSCO F
I
R
E
P
R
O
T
/ CFD FLOW TEST Y
S
Y
S
T
E
M
D
E
S
I
G
N
Computer Programs by Hydratec Inc. Route
111 Windham N.H. USA 03087
City Water Supply:
Cl - Static Pressure : 101.7 C2 - Residual Pressure: 94.5 C2 - Residual Flow :1234
Demand:
Dl - Elevation : 3.755 D2 - System Flow : 71.81 : 92.177 D2 -
SrAdj
sem Pressure Hose City
_______Hose Demand) : IQO D3 - System Demand : 171.81 Safety Margin : 9.336
COSCO FIRE PROTECTION
Page 2
2nd floor 4 head unit
.
Date 113005.
200 400 600 800 1000 1200 1400 1600 1800 FLOW (N" 1.851)
Comouter Proarams by Hvdratec inc. Route 111 Windham N.H. USA 03087
COSCO FIRE PROTECTION
2nd floor 4 head unit Page 3
Date 113005. Fitting Legend
Abbrev. Name
1% 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24
E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F 45' Elbow I 1 1 1 2 2 3 3 3 4 5 7 9 II 13 17 19 21 24 28
G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
I 90' Flow lhru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Zfa Febco 826YD Fitting generates a Fixed Loss Based on Flow
Computer Proorams by Hvdratec Inc. Route 111 Windham N.H. US
A
0
3
0
8
7
i ou-,jouiv , i njvv ,u, iii. iai y - J i rud(Jru I.J
COSCO FIRE PROTECTION
Page 4 2nd floor 4head unit
Date 113005 Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
D101 64.0 4.9 12.05 na 17.01 1 65.0 K = K @ E001 29.28 na 17.01 3 65.0 K=K©EQ01 29.76 na 17.15 5 65.0 K = K @ EQOI 33.13 na 18.09 7 65.0 K = K c EQO1 38.72 na 19.56 2 65.0 30.59 na 4 65.0 33.99 na 6 65.0 39.48 na 8 65.0 48.67 na 23 65.0 55.21 na TOR 65.0 72.97 na BOR 46.0 83.48 na DI 42.5 85.09 na BI 42.0 85.43 na 82 42.0 85.48 na B3 42.0 98.08 na B4 42.0 98.11 na S 40.0 99.0 na 100.0 J 56.33 92.16 na TEST 56.33 92.18 na
0.0525 324 12.0
The maximum velocity is 17.61 and it occurs in th
e
p
i
p
e
b
e
t
w
e
e
n
n
o
d
e
s
4
a
n
d
6
Computer Programs by Hydratec Inc. Route 111
W
i
n
d
h
a
m
N
.
H
.
U
S
A
0
3
0
8
7
I IlICH 'JQIjUIQUJI I - I IQi..I IV V IIIIQII tO
COSCO FIRE PROTECTION
Page 5 2nd floor 4 head unit
Date 113005 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes Point Qt Pf/UL Eqv. Ln. Total Pf Pn
DIOI 17.01 1.101 IT 6.328 1.000 12.051 K Factor = 4.90 to 120 0.0 6.328 16.674 EQOI 17.01 0.0763 0.0 7.328 0.559 Vel = 5.73 0.0
17.01
29.284 K Factor = 3.14 1 17.01 1.101 2E 7.65 8.600 29.284 K Factor @ node EQol to 150 IT 9.563 17.213 0.0 2 17.01 0.0504 0.0 25.813 1.301 Vel = 5.73 0.0
17.01
30.585 K Factor = 3.08 3 17.15 1.101 IT 9.563 6.500 29.763 K Factor @ node EQOI to 150 0.0 9.563 0.0 2 17.15 0.0512 0.0 16.063 0.822 Vel = 5.78 0.0
17.15
30.585 K Factor = 3.10 5 18.09 1.101 IT 9.563 5.600 33.128 K Factor @ node EQOI to 150 0.0 9.563 0.0 4 18.09 0.0565 0.0 15.163 0.857 Vel = 6.10 0.0
18.09
33.985 K Factor = 3.10 7 19.56 1.101 IT 9.563 2.080 38.719 K Factor @ node EQ01 to 150 0.0 9.563 0.0 6 19.56 0.0653 0.0 11.643 0.760 Vel = 6.59 0.0
19.56
39.479 K Factor = 3.11 2 34.16 1.101 IT 9.563 9.000 30.585 to 150 0.0 9.563 0.0 4 34.16 0.1832 0.0 18.563 3.400 Vel = 11.51 4 18.09 1.101 IT 9.563 4.100 33.985 to 150 0.0 9.563 0.0 6 52.25 0.4021 0.0 13.663 5.494 Vél = 17.61 6 19.56 1.394 2T 19.046 21.000 39.479 to 150 0.0 19.046 0.0 8 71.81 0.2295 0.0 40.046 9.190 Vel = 15.10 8 0.0 1.394 2E 9.523 19.000 48.669 to 150 0.0 9.523 0.0 23 71.81 0.2295 0.0 28.523 6.546 Vel = 15.10 23 0.0 1.598 3E 17.484 98.000 55.215 to 150 3T 34.968 52.452 0.0 TOR 71.81 0.1180 0.0 150.452 17.754 VeI= 11.49
Computer Programs by Hydratec Inc. Route 111
W
i
n
d
h
a
m
N
.
H
.
U
S
A
0
3
0
8
7
I lila. %jai,ulaUJl to - %JLCII lual U
COSCO FIRE PROTECTION
Page 6 2nd flbor4 head unit
Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. •'C11 or Ftng's Pe Pv Notes Point Qt Pf/UL Eqv. Ln. Total Pf Pn
TOR 0.0 2.157 0.0 19.000 72.969 to 120 0.0 0.0 9.729 * Fixed loss = 1.5 BOR 71.81 0.0414 0.0 19.000 0.786 Vel = 6.30 BOR 0.0 4.1 2E 29.067 40.000 83.484 to 140 0.0 29.067 1.516 Dl 71.81 0.0014 0.0 69.067 0.094 Vel = 1.75 DI 0.0 4.07 IF 6.373 77.000 85.094 to 150 IE 15.932 22.305 0.217 B1 71.81 0.0012 0.0 99.305 0.123 Vel = 1.77 BI 0.0 4.1 IT 29.067 5.500 85.434 to 140 0.0 29.067 0.0 B2 71.81 0.0014 0.0 34.567 0.047 Vol = 1.75 B2 0.0 4.1 IE 14.534 5.000 85.481 to 140 lZfa 0.0 14.534 12.576 B3 71.81 0.0014 0.0 19.534 0.027 Vol = 1.75 B3 0.0 4.1 IE 14.534 5.500 98.084 to 140 0.0 14.534 0.0 B4 71.81 0.0013 0.0 20.034 0.027 Vol = 1.75 B4 0.0 5.86 1G 3.834 60.000 98.111 to 150 IT 38.342 42.177 0.866 S 71.81 0.0002 0.0 102.177 0.022 Vel = 0.85 S 100.00 5.89 2G 7.862 180.000 98.999 Qa = 100 to 150 IT 39.308 47.170 -7.073 J 171.81 0.0010 0.0 227.170 0.235 Vel = 2.02 J 0.0 8.27 0.0 70.000 92.161 to 140 0.0 0.0 TEST 171.81 0.0002 0.0 70.000 0.016 Vol = 1.03 0.0
171.81
92.177 K Factor = 17.90
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
- - - Fire Protection by Computer Design
COSCO FIRE PROTECTION
10695 TREENA STREET
SUITE 105
CARLSBAD, CA 92131
858 444-2000
Job Name : 3RD floor 4 head unit
Building : Building Two
Location 2006 Costa Del Mar Rd Carlsbad
System 3RD floor
Contract : IOCB-0206
Data File : LCRV 3.wxl
Computer Programs by Hydratec Inc. Route 111 Windham N.H. U
S
A
0
3
0
8
7
COSCO FIRE PROTECTION
Page 1 3RD floor 4 head unit
Date 113005
HYDRAULIC DESIGN INFORMATION SHEET
Name - La Costa Resort and Spa •
Date - Location - 2006 Costa Del Mar Rd Carlsbad
Building - Building Two System No. - 3RD floor Contractor - Cosco Fire Protection Inc Contract No. - 10CB-0206 Calculated By - PG Drawing No. - FP4 Construction: (xx) Combustible Non-Combustible Ceiling Height 9' OCCUPANCY - Residential
S Type of Calculation: ( x)NFPA 13 Residential (x)NFPA 13R ( )NFPA 13D Y Number of Sprinklers Flowing: ( )1 ( )2 (x)4 S ( )Other
T ( )Specific Ruling Made by Date E
M Listed Flow at Start Point
- 17 Gpm System Type Listed Pres. at Start Point
- 12 Psi (x) Wet ( ) Dry D MAXIMUM LISTED SPACING 18 x 18 ( ) Deluge ( ) PreAction E Domestic Flow Added
- 0 Gpm Sprinkler or Nozzle S Additional Flow Added
- 100 Gpm Make tyco Model LFII I Elevation at Highest Outlet
- Feet Size K-Factor 4.9 G Note: Temperature Rating 155 N
Calculation Gpm Required 76.25 Psi Required 58.8 At Test Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 5-17-05 Rated Cap. Cap. T Time of Test - @ Psi Elev. E Static (Psi) - 113 Elev. R Residual (Psi) - 105 Other Well Flow (Gpm) - 1234 Proof Flow Gpm S Elevation - 56.33 P Location: ESTRELLA DEL MAR @ COSTA DEL MAR RD
- P
L Source of Information: COSCO FIRE PROTECTION
/ CWD FLOW TEST Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03
0
8
7
'-I
COSCO FIRE PROTECTION
Page 2 3RD floor 4 head unit
Date 113005.
City Water Supply: Cl - Static Pressure : 113 C2 - Residual Pressure: 105 C2 - Residual Flow :1234
Demand:
Dl - Elevation : 8.458 D2 - System Flow : 76.249 stem Pressure : 67.699 F-lose
D2 -
Sr'Demand
dj City).
— ) : 100 TOT D3 D3 - System Demand : 176.249 Safety Margin : 45.083
15C
140
130
P 120
R 110
E 100
S90
On
U 70
R601
E5°
40
30
20
10
I
I
I
I ------ ---- -- ----
1____________
I
I
I
I
200 400 400 600 800 1000 1200 1400 1600 1800 FLOW (NA 1.85)
Comouter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
- ---.-..J
COSCO FIRE PROTECTION
Page 3 3RD floor 4 head unit
Date 113005. Fitting Legend
Abbrev. Name 1/2 % 1 11/4 1% 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24
E 90 Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 F 45 Elbow I I I 1 2 2 1 3 3 3 4 5 7 9 11 13 17 19 21 24 28 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T 90'FlowlhruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 SI 91 101 121 Zfa Febco 826YD Fitting generates a Fixed Loss Based on Flow
ComDuter Proarams by Hydratec Inc. Route 111 Windham N.H. USA 03087
I iwoouivi I IJVV JUIIIIIIQI)
COSCO FIRE PROTECTION
Page 4 3RD floor 4 head unit
Date 113005
Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req.
DIOI 25.5 4.9 12.05 na 17.01 1 75.86 K = K @ EQ01 12.61 na 17.01 3 75.86 K= K© EQQ1 13.07 na 17.32 5 75.86 K=K©EQOI 16.37 na 19.38 7 75.86 K = K @ EQOI 22.14 na 22.54 2 75.86 13.91 na 4 75.86 17.34 na 6 75.86 23.12 na 8 75.86 34.16 na TOR 75.86 43.1 na BOR 46.0 58.88 na Dl 42.5 60.5 na BI 42.0 60.85 na 82 42.0 60.9 no B3 42.0 73.6 na B4 42.0 73.63 na S 40.0 74.52 na 100.0 J 56.33 67.68 na TEST 56.33 67.7 na
0.0525 324 12.0
The maximum velocity is 18.1 and it occurs in the pipe between node
s
4
a
n
d
6
Computer Programs by Hydratec Inc. Route 111 Windham N.H
.
U
S
A
0
3
0
8
7
I Ij II %JcH%.,UIQLI%JI I - I IL.I IV V IIIIQI I I
COSCO FIRE PROTECTION
Page 5 3RD floor 4 head unit
Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv Notes Point . Qt Pf/UL Eqv. Ln. Total Pf Pn
DIOI 17.01 1.101 IT 6.328 1.000 12.051 K Factor =4.90 to 120 0.0 6.328 0.0 EQOI 17.01 0.0761 0.0 7.328 0.558 Vel = 5.73 0.0
17.01 12.609 K Factor = 4.79 1 17.01 1.101 2E 7.65 8.600 12.609 K Factor © node EQOI to. 150 IT 9.563 17.213 0.0 2 17.01 0.0504 0.0 25.813 1.302 Vel = 5.73 0.0
17.01 13.911 K Factor = 4.56 3 17.32 1.101 IT 9.563 6.500 13.073 K Factor @ node EQ01 to 150 0.0 9.563 0.0 2 17.32 0O522 0.0 16.063 0.838 Vel = 5.84 0.0
17.32 13.911 K Factor = 4.64 5 19.38 1.101 IT 9.563 5.600 16.369 K Factor © node EQOI to 150 0.0 9.563 0.0 4 19.38 0.0642 0.0 15.163 0.974 Vel = 6.53 0.0
19.38, 17.343 K Factor = 4.65 7 22.54 1.101 IT 9.563 2.080 22.136 K Factor © node EQOI to . 150 0.0 9.563 0.0 6 22.54 0.0849 0.0 11.643 0.988 Vet = 760 0.0
22.54 23.124 K Factor = 4.69 2 34.33 1.101 IT 9.563 9.000 13.911 to 150 0.0 9.563 0.0 4 3433 0.1849 0.0 18.563 3.432 Vel = 11.57 4 19.38 1.101 IT 9.563 4.100 17.343 to 150 0.0 9563 0.0 6 53.71 0.4231 . 0.0 13.663 5.781 Vel = 18.10 6 22.54 1.394 2T 19.046 24.000 23.124 to .150 0.0 19.046 0.0 8 76.25 0.2564 0.0 43.046 11.038 Vel = 16.03 8 0.0 1.598 2E 11.656 44.500 34.162 to 150 IT 11.656 23.312 0.0 TOR 76.25 0.1318 0.0 67.812 8.941 Vel = 12.20 TOR 0.0 2.157 0.0 29.000 43.103 to 120 0.0 0.0 14.432 * Fixed loss = 1.5 BOR 76.25 0.0462 0.0 29.000 1.341 Vel = 6.69
Computer Programs by Hydratec Inc. Route 111
W
i
n
d
h
a
m
N
.
H
.
U
S
A
0
3
0
8
7
I II 101 .,0I,UIQLIIJu 10 - %JLQ1 ivai U
COSCO FIRE PROTECTION
Page 6 3RD floor 4 head unit
Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes Point Qt Pf/UL Eqv. Ln. Total Pf Pn
BOR 0.0 4.1 2E 29.067 40.000 58.876 to 140 0.0 29.067 1.516 DI 76.25 0.0015 0.0 69.067 0.105 Vel = 1.85 Dl 0.0 4.07 IF 6.373 77.000 60.497 to 150 IE 15.932 22.305 0.217 BI 76.25 0.0014 0.0 99.305 0.137 Vel= 1.88 BI 0.0 4.1 IT 29.067 5.500 60.851 to 140 0.0 29.067 0.0 B2 76.25 0.0015 0.0 34.567 0.053 Vel = 1.85 B2 0.0 4.1 1 14.534 5.000 60.904 to 140 lZfa 0.0 14.534 12.661 B3 76.25 0.0015 . 0.0 19.534 0.030 Vel = 1.85 B3 0.0 4.1 IE 14.534 5.500 73.595 to 140 0.0 14.534 0.0 B4 76.25 0.0015 0.0 20.034 0.031 Vel = 1.85 B4 0.0 5.86 IG 3.834 60.000 73.626 to 150 IT 38.342 42.177 0.866 S 76.25 0.0002 0.0 102.177 0.024 Vel = 0.91 S 100.00 5.86 2G 8.148 180.000 74.516 Qa= 100 to 155 iT 40.74 48.888.. -7.073. J 176.25 0.0010 0.0 228.888 0.239 Vel= 2.10 J 0.0 8.27 0.0 70.000 67.682 to 140 0.0 0.0 0.0 TEST 176.25 0.0002 0.0 70.000 . 0.017 Vel = 1.05 0.0
176.25 67.699 K Factor = 21.42
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 030
8
7
--- Fire Protection by Computer Design
COSCO FIRE PROTECTION
10695 TREENA STREET
SUITE 105
CARLSBAD, CA 92131
858 444-2000
Job Name : 3RD floor 4 head CORRIDOR
Building : Building Two 3rd FLOOR CORRIDOR
Location : 2006 Costa Del Mar Rd Carlsbad
System : 3RD floor CORR
Contract : 1 OCB-0206
Data File : LCRV 3.wx2
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
COSCO FIRE PROTECTION• Page 1 3RD floor 4 head CORRIDOR Date 113005
HYDRAULIC DESIGN. INFORMATION SHEET
Name - La Costa Resort and Spa Date - Location - 2006 Costa Del Mar Rd Carlsbad
Building - Building Two 3rd FLOOR CORRIDOR System No. - 3RD floor CORR Contractor - Cosco Fire Protection Inc Contract No. - 10CB-0206 Calculated By - PG Drawing No. - FP4 Construction: (xx) Combustible ( ) Non-Combustible Ceiling Height 9' OCCUPANCY - Residential
S Type of Calculation: ( x)NFPA 13 Residential (x)NFPA 13R ( )NFPA 13D Y Number of Sprinklers Flowing: ( )1 C )2 (x)4 S ( )Other
T ( )Specific Ruling Made by Date E
M Listed Flow at Start Point - 21 Gpm System Type Listed Pres. at Start Point - 25 Psi (x) Wet ( ) Dry D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle S Additional Flow Added - 100 Gpm Make tyco Model LFII HSW I Elevation at Highest Outlet - Feet Size K-Factor 4.2 G Note: Temperature Rating 155 N
Calculation Gpm Required 86.65 Psi Required 50.75 At Test Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 5-17-05 Rated Cap. Cap. T Time of Test - @ Psi Elev. E Static (Psi) - 113 Elev. R Residual (Psi) - 109 Other Well Flow (Gpm) - 1234 Proof Flow Gpm S Elevation - 56.33
P Location: ESTRELLA DEL MAR & COSTA DEL MAR RD P
L Source of Information: COSCO FIRE PROTECTION / CWD FLOW TEST Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
VVdLI øUI4flY UIV IL)
COSCO FIRE PROTECTION Page 2 3RD floor 4 head CORRIDOR Date 113005
City Water Supply: . Demand: Cl - Static Pressure : 113 Dl - Elevation : 8.458 C2 - Residual Pressure: 105 . D2 - System Flow : 86.654 stem Pressure : 59.948 C2 - Residual Flow : 1234 D2 - S
rlDemand Hosedj City) ______ Hose ) : 100 D3 - System Demand : 186.654 Safety Margin : 52.809
150
140
130
In 120
. I-'
:
-
____ ______
--------------
____
-.------.---.-----
_________
C2 —e----_____________
___________ _____________ ______________ E 100
S90 I 09w - ------- -
U70
R6°
E 50
40
30
20
10 l...........•........... ......... ........ .....
200 400 600 800 1000 1200 1400 1600 1800
FLOW (N'1.85) . .
ComDuter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
- III I IA I 7 -
COSCO FIRE PROTECTION.
Page 3 3RD floor 4 head CORRIDOR
Date 113005
Fitting Legend
Abbrev. Name % % 1 11/4 1% 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24
E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 F 45' Elbow I 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28 G Generic Gate Valve 0 0 0 0 0 1 - 1 1 1 2 2 3 4 5 6 7 8 10 11 13 I 90' Flow Thru Tee 3 4 5 6 8 10 - 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zfa Febco 826YD Fitting generates a Fixed Loss Based on Flow
Comnuter Programs by Hvdratec Inc. Route 111 Windham N.H. USA 03087
I I quoQUIV I I fllVV ui III iiaiy - j I rutIJruL.,
COSCO FIRE PROTECTION
Page 4 3RD floor 4 head CORRIDOR
Date 113005
Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Rea.
0101 25.5 4.2 25.0 na 21.0 0.082 256 25.0 D102 25.5 4.2 25.0 na 21.0 0.082 256 25.0 D103 . 25.5 4.2 25.0 na 21.0 0.082 256 25.0 0105 25.5 4.2 25.0 na 21.0 0.082 256 25.0 12 75.86 K = K @ EQI2 28.2 na 21.0 13 75.86 K=K@EQ13 28.44 na 21.17. 8 75.86 . 29.73 na 14 75.86 K = K © E0I4 30.94 na 22.08 15 75.86 K = K @ EQI5 31.25 na 22.4 TOR 75.86 34.92 na BOR 46.0 50.79 na Dl 42.5 52.44 na BI 42.0 52.83 na B2 42.0 52.9 na B3 42.0 65.79 na B4 42.0 65.83 na S 40.0 66.73 na 100.0 J 56.33 59.93 na TEST 56.33 59.95 na
The maximum velocity is 13.86 and it occurs in the pipe between no
d
e
s
1
5
a
n
d
T
O
R
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03
0
8
7
- I IlIQI jQIjUIQLIJI i - I IQ.I IV V 111101110
COSCO FIRE PROTECTION - Page 5 '3RD floor 4 head CORRIDOR Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. licit.or Ftng's Pe Pv ******* Notes Point Qt Pf/UL Eqv. Ln. Total Pf Pn
DIOI 21.00 1.101 4E 10.126 12.000 25.000 K Factor =4.20 to 120 IT 6.328 16.454 0.0 EQ12 21.0 0.1125 0.0 28.454 3.202 Vet = 7.08
0.0
21.00 28.202 K Factor = 3.95 0102 21.00 1.101 4E 10.126 10.000 25.000 K Factor =4.20 to 120 IT 6.328 16.454 0.0 EQ13 21.0 01125 0.0 26.454 2.977 Vet = 7.08
0.0
21.00 27.977 K Factor = 3.97 D103 21.00 1.101 4E 10.126 10.000 25.000 K Factor =4.20 to 120 IT 6.328 16.454 0.0 FQ14 21.0 0.1125 0.0 26.454 2.977 Vel = 7.08
0.0
21.00 27.977 K Factor = 3.97 D105 21.00 1.101 4E 10.126 5.500 25.000 K Factor =4.20 to 120 IT 6.328 16.454 0.0 EQ15 21.0 0.1125 0.0 21.954 2.470 Vel= 7.08
0.0
21.00 27.470 K Factor = 4.01 12 21.00 1.394 0.0 10.000 28.202 K Factor @ node EQ12 to 150 0.0 0.0 0.0 13 21.0 0.0236 0.0 10.000 0.236 Vel = 4.41 13 21.17 1.394 IT 9.523 5.600 28.438 K Factor © node EQ 13 to 150 V 0.0 9.523 0.0 8 42.17 0.0857 0.0 15.123 1.296 Vel = 8.86 8 0.0 1.598 IT 11.656 15.700 29.734 to 150 0.0 11.656 0.0 14 42.17 0.0441 0.0 27.356 1.206 Vel = 6.75 14 22.09 1.598 0.0 3.200 30.940 K Factor @ node EQI4 to 150 0.0 0.0 0.0 15 64.26 0.0962 0.0 3.200 0.308 V Vel = 10.28 15 22.39 1.598 2E 11.656 10.330 31.248 K Factor @ node EQI5 to 150 0.0 11.656 0.0 TOR 86.65 0.1670 0.0 21.986 3.672 Vet = 13.86 TOR 0.0 2.157 0.0 24.500 34.920 to 120 0.0 0.0 14.432 * Fixed loss = 1.5 BOR 86.65 0.0586 0.0 24.500
- 1.436 Vel = 7.61 BOR 0.0 4.1 2E 29.067 40.000 50.788 to 140 0.0 29.067 1.516 Dl 86.65 0.0019 0.0 69.067 0.133 Vol = 2.11
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
1
- I luau jQlIjUI0UUI 10 - .JIQI IUOI U
S
COSCO FIRE PROTECTION Page 6 3RD floor 4 head CORRIDOR Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes Point Qt Pf/UL Eqv. Ln. Total Pf Fin
DI 0.0 4.07 IF 6.373 77.000 52.437 to 150 1 15.932 22.305 0.217 BI 86.65 0.0018 0.0 99.305 0.174 VeI= 2.14
BI 0.0 4.1 IT 29.067 5.500 52.828 to 140 0.0 29.067 0.0 B2 86.65 0.0019 0.0 34.567 0.067 Vel = 2.11 B2 0.0 4.1 IE 14.534 5.000 52.895 to 140 IZfa 0.0 14.534 12.861 B3 86.65 0.0019 0.0 19.534 0.038 Vel = 2.11 B3 0.0 4.1 IE 14.534 5.500 65.794 to 140 0.0 14.534 0.0 B4 86.65 0.0019 0.0 20.034 0.038 Vel = 2.11 84 0.0 5.86 IG 3.834 60.000 65.832 to 150 IT 38.342 42.177 0.866 S 86.65 0.0003 0.0 102.177 0.031 Vel = 1.03 S 100.00 5.89 2G 7.862 180.000 66.729 Qa = 100 to 150 IT 39.308 47.170 -7.073 J 186.65 0.0012 0.0 227.170 0.274 Vel = 2.20 J 0.0 8.27 0.0 70.000 59.930
to 140 0.0 0.0 0.0 TEST 186.65 0.0003 0.0 70.000 0.018 Vel = 1.11 0.0
186.65 59.948 K Factor = 24.11
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
hydraulic calculations Page 1
3RD floor 4 head CORRIDOR Date 113005
HYDRAULIC DESIGN INFORMATION SHEET
Name - La Costa Resort and Spa Date -
Location - 2006 Costa Del Mar Rd Carlsbad
Building - Building Two 3rd FLOOR CORRIDOR System No. - 3RD floor CORR
Contractor - Cosco Fire Protection Inc Contract No. - 10CB-0206
Calculated By - PG Drawing No. - FP4
Construction: (xx) Combustible C ) Non-Combustible Ceiling Height 9'
OCCUPANCY - Residential
Type of Calculation: ( x)NFPA 13 Residential (x)NFPA 13R ( )NFPA 13D
Number of Sprinklers Flowing: C )l C )2 (x)4
)Other
)Specific Ruling Made by Date
Gpm System Type
Psi (x) Wet ( ) Dry
Deluge ( ) PreAction
Gpm Sprinkler or Nozzle
Gpm Make tyco Model LFII HSW
Feet Size K-Factor 4.2
Temperature Rating 155
Calculation Gpm Required 86.65 Psi Required 50.75 At Test
Summary C-Factor Used: Overhead 150 Underground 150
S
Y
S
T
E
M
D
E
S
I
G
N
Listed Flow at Start Point - 21
Listed Pres. at Start Point - 25
MAXIMUM LISTED SPACING 16 x 16
Domestic Flow Added - 0
Additional Flow Added - 100
Elevation at Highest Outlet -
Note:
Water Flow Test:
Date of Test - 10-11-04
Time of Test -
Static (Psi) - 126
Residual (Psi) - 109
Flow (Gpm) - 3000
Elevation - 40
Location: ESTRELLA DEL MAR
W
A
T
E
R
S
P
P
L
Y
Pump Data:
Rated Cap.
8 Psi
Elev.
Other
Tank or Reservoir:
Cap.
Elev.
Well
Proof Flow Gpm
Source of Information: MDS CONSULTING
VVdLI ouppiy -Ul VU I#)
hydraulic calculations Page 2
3RD floor 4 head CORRIDOR Date 113005
City Water Supply: Demand:
Cl - Static Pressure : 126 Dl - Elevation : 15.531
C2 - Residual Pressure: 109 02 - System Flow : 86.654
tem Pressure : 66.729 C2 - Residual Flow : 3000 02- SrA5dj Hose City) ______ Hose Demand) : 100
D3 - System Demand : 186.654
Safety Margin : 59.171
150
140
130
p120 --
R 110
____ _____ ______ - _________ ---------------
E10°
S90
S80
u70 ;02
R60D
E5°
40
30
20 --
DJL 10
300 600 900 1200 1500 1800 2100 2400 2700
FLOW (NA 1.85)
C2
Corn outer Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
rILL1119b UbU OUIIIIIIdI
hydraulic calculations Page 3
3RD floor 4 head CORRIDOR -
Date 113005
Fitting Legend
Abbrev. Name % % 1 1% 1% 2 2% 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F 45' Elbow I I 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Zfa Febco 826YD Fitting generates a Fixed Loss Based on Flow
Corn outer Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
hydraulic calculations Page 4
3RD floor 4 head CORRIDOR Date 113005
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
0101 25.5 4.2 25.0 na
0102 25.5 4.2 25.0 na
D103 25.5 4.2 25.0 na
D105 25.5 4.2 25.0 na
12 75.86 K=K@EQI2 28.2 na
13 75.86 K=K@EQI3 28.44 na
8 75.86 29.73 na
14 75.86 K=K@EQI4 30.94 na
15 75.86 K=K@EQ1S 31.25 na
TOR 75.86 34.92 na
BOR 46.0 50.79 na
Dl 42.5 52.44 na
BI 42.0 52.83 na
B2 42.0 52.9 na
83 42.0 65.79 na
B4 42.0 65.83 na
S 40.0 66.73 na
21.0 0.082 256 25.0
21.0 0.082 256 25.0
21.0 0.082 256 25.0
21.0 0.082 256 25.0
21.0
21.17
22.08
22.4
100.0
The maximum velocity is 13.86 and it occurs in the pipe between nodes 15 and TOR
Final Calculations - Hazen-Williams
hydraulic calculations Page 5
3RD floor 4 head CORRIDOR Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt PfIUL Eqv. Ln. Total Pf Pn
0101 21.00 1.101 4E 10.126 12.000 25.000 K Factor 4.20
to 120 IT 6.328 16.454 0.0
EQ12 21.0 01125 0.0 28.454 3.202 Vel = 7.08
0.0
21.00 28.202 K Factor = 3.95
0102 21.00 1.101 4E 10.126 16.000 25.000 K Factor = 4.20
to 120 IT 6.328 16.454 0.0
EQ13 21.0 0.1125 0.0 26.454 2.977 Vel = 7.08
0.0
21.00 27.977 K Factor= 3.97
D103 21.00 1.101 4E 10.126 10.000 25.000 K Factor = 4.20
to 120 IT 6.328 16.454 0.0
EQ14 21.0 0.1125 0.0 26.454 2.977 Vel = 7.08
0.0
21.00 27.977 K Factor = 3.97
0105 21.00 1.101 4E 10.126 5.500 25.000 K Factor = 4.20
to 120 IT 6.328 16.454 0.0
EQ15 21.0 0.1125 0.0 21.954 2.470 Vel = 7.08
0.0
21.00 27.470 K Factor = 4.01
12 21.00 1.394 0.0 10.000 28.202 K Factor @ node EQ 12
to 150 0.0 0.0 0.0
13 21.0 0.0236 0.0 10.000 0.236 Vel = 4.41
13 21.17 1.394 IT 9.523 5.600 28.438 K Factor © node EQI3
to 150 0.0 9.523 0.0
8 42.17 0.0857 0.0 15.123 1.296 Vel = 8.86
8 0.0 1.598 IT 11.656 15.700 29.734
to 150 0.0 11.656 0.0
14 42.17 0.0441 0.0 27.356 1.206 Vel = 6.75
14 22.09 1.598 0.0 3.200 30.940 K Factor @ node EQi4
to 150 0.0 0.0 0.0
15 64.26 0.0962 0.0 3.200 0.308 Vel = 10.28
15 22.39 1.598 2E 11.656 10.330 31.248 K Factor @ node EQ 15
to 150 0.0 11.656 0.0
TOR 86.65 0.1670 0.0 21.986 3.672 Vel = 13.86
TOR 0.0 2.157 0.0 24.500 34.920
to 120 0.0 0.0 14.432 * Fixed loss = 1.5
BOR 86.65 0.0586 0.0 24.500 1.436 Vel = 7.61
BOR, 0.0 4.1 2E 29.067 40.000 50.788
to 140 0.0 29.067 1.516
Dl 86.65 0.0019 0.0 69.067 0.133 Vel = 2.11
'FinI Calculations - Standard
hydraulic calculations Page 6
3RD floor 4 head CORRIDOR Date 113005
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
DI 0.0 4.07 IF 6.373 77.000 52.437
to 150 1E 15.932 22.305 0.217
BI 86.65 0.0018 0.0 99.305 0.174 Vel = 2.14
81 0.0 4.1 IT 29.067 5.500 52.828
to 140 0.0 29.067 0.0
B2 86.65 0.0019 0.0 34.567 0.067 Vel = 2.11
B2 0.0 4.1 IE 14.534 5.000 52.895
to 140 IZfa 0.0 14.534 12.861
B3 86.65 0.0019 0.0 19.534 0.038 Vet = 2.11
B3 0.0 4.1 1 14.534 5.500 65.794
to 140 0.0 14.534 0.0
B4 86.65 0.0019 0.0 20.034 0.038 Vet = 2.11
B4 0.0 5.86 IG 3.834 60.000 65.832
to 150 IT 38.342 42.177 0.866
S 86.65 0.0003 0.0 102.177 0.031 Vel = 1.03
100.00 Qa= 100.00
186.65 66.729 K Factor= 22.85
San Diego Branch Office
10695 Treena Street., Suite #105
San Diego, CA 92131
(858) 444-2000 fax: 444-2056
State License No: C-16-577621
www.coscofire.com
MATERIAL SUBMITTAL
Date: 12/28/05
TO: CARLSBAD FIRE DEPT
1635 FARADAY AVE.
CARLSBAD, CA.92008
LA COSTA BLDG 2
2006. COSTA DEL MAR RD.
CARLSBAD, CA.92009
CB-050422
All material submitted, may be substituted
by material of equal performance & design, &
shall be deemed acceptable by purchaser.
Submitted By: OFELIA RELLEGUE
NFPA
UR Los Angeles • San Francisco • Orange • Fresno • San Diego • Seattle
San Diego Branch Office
10695 Treena Street., Suite #105
,,lI San Diego, CA 92131
(858) 444-2000 fax: 444-2056
FIRE PROTECTION License No: C-16-577621 I www.coscofire.com
TABLE OF CONTENTS
Fire Sprinkler System Components
Tyco LFIL Residential Pendent Sprinkler
Tyco LFII Residential Sidewall Sprinkler
Tyco TY-FRB Pendent Sprinkler
Tyco TY-FRB Sidewall Sprinkler
Tyco Grooved Butterfly Valve
Wilkens Model 375 ADA RPDA
Potter VSR-F Flow Switch
Potter Electric Bell
Pipe and Fittings
Allied Schedule 10 & 40 pipe
Tyco Grooved Coupling
Tyco Blazemaster CPVC Pipe and Fittings
Pipe Hangers/Miscellaneous Materials
Tolco Fig. 28 Standoff Hanger
Tolco Fig. 22 CPVC Hanger
Tolco Fig. 23 Hanger Double Fastener Strap Type
Tolco Fig. 24 Double Fastener Side Mount
Tolco Fig. 4 Pipe Clamp
tqCU /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series LFII Residential
Concealed Pendent Sprinklers, Flat Plate
49 K-factor
General
Description
The Series LFII (TY3596) Residential
Concealed Pendent Sprinklers are
decorative, fast response, fusible sol-
der sprinklers designed for use in resi-
dential occupancies such as homes,
apartments, dormitories, and hotels.
The cover plate assembly conceals
the sprinkler operating components
above the ceiling. The flat profile of the
cover plate provides the optimum aes-
thetically appealing sprinkler design.
In addition, the concealed design of
the Series LFII (TY3596) provides 1/2
inch (12,7 mm) vertical adjustment.
This adjustment reduces the accuracy
to which the fixed pipe drops to the
sprinklers must be cut to help assure
a perfect fit installation.
The Series LFII are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 131); wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series LFII (TY3596) has a 4.9
(60,5) K-factor that provides the re-
quired residential flow rates at reduced
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
pressures, enabling smaller pipe sizes
and water supply requirements.
The Series LFII (TY3596) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
The Series LFII (TY3596) Residential
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
WARNINGS
The Series LFII (TY3596) Residential
Concealed Pendent Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler/Model
Identification
Number
SIN TY3596
Technical
Data
Approvals:
UL and C-UL Listed.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient:
K = 4.9 GPM/p5i112 (70,6 LPM/barl'2)
Temperature Rating:
160°F/71 °C Sprinkler with
135017/570C Cover Plate
Vertical Adjustment:
1/2 inch (12,7 mm)
Finishes:
Cover Plate:
Flat White, Bright White, Chrome, or
Custom
Physical Characteristics:
Body ..............Brass
Cap ..............Bronze
Saddle .............Brass
Sealing Assembly ..........
Beryllium Nickel w/ Teflont
Soldered Link Halves .....Nickel
Lever .............Bronze
Compression Screw ......Brass
Deflector ......Copper or Brass
Guide Pin Housing .....Bronze
Page 1 of 4 JULY, 2005 TFP442
Page 2 of 4 TFP442
Minimum Flow (b) and Minimum Flow (b) and Minimum Flow (b) and
Maximum Maximum Residual Pressure Residual Pressure Residual Pressure
Coverage Spacing For Horizontal Ceiling For Sloped Ceiling For Sloped Ceiling
Area (a) Ft. (Max. 2 Inch Rise (Greater Than 2 inch (Greater Than 4 inch
Ft. x Ft. (m) for 12 Inch Run) Rise Up To Rise Up To
(mx m) Max. 4 Inch Rise Max. 8 Inch Rise
for 12 Inch Run) for 12 Inch Run)
160°FIT1"C 1600FF71°C 160°FTh"C
Sprinkler Sprinkler Sprinkler
12 x 12 12 13 GPM (49.2 LPM) N/A N/A
(3,7 x 3,7) (3,7) 7.0 psi (0,48 bar)
14x14 14 13 GPM (53,OLPM) N/A N/A
(4,3 x 4,3) (4,3) 7.0 psi (0,48 bar)
16 x 16 16 13 GPM (60,6 LPM) N/A N/A
(4,9x4,9) (4,9) 7.0 psi (0,48 bar)
18x18 18 17 GPM (64,3 LPM) N/A N/A
(5,5 x 5,5) (5,5) 12.0 psi (0,83 bar) I
20 x 20 20 20 GPM (75,7 LPM) N/A N/A
(6,1x6,1) (6,1) 16.7 psi (1,l5bar)
For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the
next highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated
using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A
NFPA 130 AND NFPA 13R HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY3596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
Guide Pins .......Stainless Steel
Support Cup ..........Steel
Cover Plate ..........Copper
Retainer ............Brass
Cover Plate Ejection Spring .....
thinIcc Qtgaal
tDuPont Registered Trademark
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Support Cup at three
points, falls away to expose the Sprin-
kler Assembly. At this point the Deflec-
tor supported by the Arms drops down
to its operated position. The fusible
link of the Sprinkler Assembly is com-
prised of two link halves that are sol-
dered together with a thin layer of sol-
der. When the rated temperature is
reached, the solder melts and the two
link halves separate allowing the sprin-
kler to activate and flow water.
Design
Criteria
The Series LFII (TV3596) Residential
Concealed Pendent Sprinklers are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the Authority Having Jurisdic-
tion.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of "design sprinklers" as
specified in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Table A for
NFPA 13D and 13R as a function of
temperature rating and the maxi-
mum allowable coverage area.
A minimum discharge of 0.1gpmlsq.
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity. The sprin-
klers are to be installed relative to the
ceiling mounting surface as shown in
Figure 3.
Sprinkler Spacing. The minimum
spacing between sprinklers is 9 feet
(2,7 m). The maximum spacing be-
tween sprinklers cannot exceed the
length of the coverage area (Ref. Ta-
ble A) being hydraulically calculated
(e.g., maximum 12 feet for a 12 ft. x
12 ft. coverage area, or 20 feet for a 20
ft. x 20 ft. coverage area).
Installation
The Series LFll (TY3596) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler by the support
cup only (i.e., do not apply pressure to
the fusible link Assembly).
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
I
TFP442
BODY
(1&NPT)
CAP
SADDLE
SUPPORT
CUP WITH -
ROLL FORMED
THREADS
GUIDE
PIN
GUIDE PIN
HOUSING
DEFLECTOR -
THREAD INTO
SUPPORT CUP
UNTIL MOUNTING
SURFACE IS
FLUSH WITH
CEILING
SOLDER
TAB
SEALING
ASSEMBLY
SPRINKLER
WRENCHING
AREA
COMPRESSION
SCREW
LEVER
SOLDER LINK
ELEMENT
DEFLECTOR
-
l (OPERATED
POSITION)
SPRINKLERISUPPORT CUP
ASSEMBLY
RETAINER
F
ITh ThREAD
DIMPLES
0 EJEcT1ON N
SPRING
COVER PLATEIRETAINER
ASSEMBLY COVER
PLATE
FIGURE 1
SERIES LFII(TY3596) RESIDENTIAL
CONCEALED PENDENT SPRINKLER
Page 3 of 4
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Cover
Plate/Retainer Assembly by under- or
over-tightening the Sprinkler. Read-
just the position of the sprinkler fitting
to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, and using
the W-Type 18 Wrench shown in Fig-
ure 2, install and tighten the Sprink-
ler/Support Cup Assembly into the fit-
ting. The W-Type 18 Wrench will
accept a 1/2 inch ratchet drive.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 18
SPRINKLER WRENCH
2-1/2" DIA.
1/2'
991
THREADED SPRINKLER
(635
mm
12,7 mm) FACE OF
yJ
NPT STMENT FITTING
1-7/8"±1/8"
- (47.6 mm /8" GAP *3,2 mm) 3,2mm)
COVER- SPRINKLER- MOUNTING RETAINER SUPPORT CUP
J SURFACE ASSEMBLY ASSEMBLY (4,8 mm)
- 33/16"DIA.
(81,0 MM) i-ip
SPRINKLER-
SUPPORT CUP
ASSEMBLY
OPERATED
SPRINKLER.
COVER
PLATE
RETAINER
7/8" (22,2 mm)
1-1/8"(28,6 mm)
DISPOSABLE
PROTECTIVE CAP DEFLECTOR IN
OPERATED POSITION
FIGURE 3
SERIES LFII (TY3596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
INSTALLATION DIMENSIONS / PROTECTIVE CAP/ACTIVATED DEFLECTOR
Page 4 of 4 TFP442
Step 4. Replace the Protective Cap by
pushing it upwards until it bottoms out
against the Support Cup. The Protec-
tive Cap helps prevent damage to the
Deflector and Guide Pins during ceil-
ing installation and/or during applica-
tion of the finish coating of the ceiling.
It may also be used to locate the center
of the clearance hole by gently push-
ing the ceiling material against the
center point of the Cap.
NOTE
As long as the protective Cap remains
in place, the system is considered to
be "Out Of Service".
Step 5. After the ceiling has been com-
pleted with the 2-1/2 inch (63 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
Deflector moves up and down freely.
If the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 6. Screw on the Cover Plate As-
sembly until its flange comes in con-
tact with the ceiling.
Do not continue to screw on the Cover
Plate Assembly such that it lifts a ceil-
ing panel out of its normal position.
If the Cover Plate Assembly cannot be
engaged with the Mounting Cup or the
Cover Plate Assembly cannot be en-
gaged sufficiently to contact the ceil-
ing, the Sprinkler Fitting must be repo-
sitioned.
Care and
Maintenance
The Series LFII (TY3596) must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Absence of a Cover Plate may delay
the sprinkler operation in a fire situ-
ation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage,
or the like, must be replaced.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
NOTE
The owner must assure that the sprin-
klers are not used for hanging of any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-vertent operation may result.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products are warranted solely
to the original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire & Building Products.
No warranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire & Building Products or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified
or repaired in accordance with applica-
ble Standards of the National Fire Pro-
tection Association, and/or the stand-
ards of any other Authorities Having
Jurisdiction. Materials found by Tyco
Fire & Building Products to be defec-
tive shall be either repaired or re-
placed, at Tyco Fire & Building Prod-
ucts' sole option. Tyco Fire & Building
Products neither assumes, nor author-
izes any person to assume for it, any
other obligation in connection with the
sale of products or parts of products.
Tyco Fire & Building Products shall not
be responsible for sprinkler system de-
sign errors or inaccurate or incomplete
information supplied by Buyer or
Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE &
BUILDING PRODUCTS BE LIABLE,
IN CONTRACT, TORT, STRICT LI-
ABILITY OR UNDER ANY OTHER LE-
GAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE & BUILDING
PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE & BUILDING
PRODUCTS' LIABILITY EXCEED AN
AMOUNT EQUAL TO THE SALES
PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WARR.4N-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PUR-
POSE
Ordering
Procedure
When placing an order, indicate the
full product name. Contact your local
distributor for availability..
Sprinkler Assembly:
Series LFII (TY3596), K=4.9, Residen-
tial Concealed Pendent Sprinkler with-
out Cover Plate Assembly,
P/N 51-112-1-160.
Cover Plate Assembly:
Cover Plate Assembly having a (spec-
ify) finish for the Series LFII (TY3596),
K=4.9, Residential Concealed Pen-
dent Sprinkler, P/N (specify).
Chrome ..................PIN 56-122-9-135 Off White .................PIN 56-122-0.135 Bright White ............... P/N 56-122-4-135 Flat White ................P/N 56-122-5-135 White (RAL9O1O) ........... P/N 56-122.3-135 Custom ..................PIN 56-122-X-135
"Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 18 Sprinkler Wrench,
PIN 56-000-1-265.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqCU Fire & Building
liPro du c ts
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series LFII Residential
Pendent Sprinklers
49 K-factor
General
Description
The Series LFII (TY2234) Residential
Pendent Sprinklers are decorative,
fast response, frangible bulb sprinklers
designed for use in residential occu-
pancies such as homes, apartments,
dormitories, and hotels. When aesthet-
ics and optimized flow characteristics
are the major consideration, the Series
LFII (TY2234) should be the first
choice.
The Series LFII are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 131); wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series LFII (TY2234) has a 4.9
(70,6) K-factor that provides the re-
quired residential flow rates at reduced
pressures, enabling smaller pipe sizes
and water supply requirements.
The recessed version of the Series
LFII (1Y2234) is intended for use in
areas with finished ceilings. It employs
a two-piece Style 20 Recessed Es-
cutcheon. The Recessed Escutcheon
provides 1/4 inch (6,4 mm) of recessed
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
adjustment or up to 1/2 Inch (12,7 mm)
of total adjustment from the flush ceil-
ing position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the pipe nipples
to the sprinklers must be cut.
The Series LFII (TY2234) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
WARNINGS The Series LFII (7Y2234) Residential
Pendent Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The Installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler/Model
Identification
Number
SIN TY2234
Page 1 of 8 MARCH, 2005 TFP400
Page 2 of 8 TFP400
Minimum Flow (b) and Minimum Flow (b) and Minimum Flow ('a) and Maximum Maximum Residual Pressure Residual Pressure Residual Pressure Coverage Spacing For Horizontal Ceiling For Sloped Ceiling For Sloped Ceiling Area (a) R. (Max. 2 inch Rise (Greater Than 2 inch Rise (Greater Than 4 inch Rise Ft. x Ft. (m) for 12 inch Run) Up To Max. 4 inch Rise for 12 inch Run) Up To Max. 8 inch Rise for 12 Inch Run) (m x m) 155°F168°C or 1550F/68"C 175°F179°C 155°F168"C 175°F!79"C 175°F/79"C
12 x 12 12 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) (3,7 x 3,7) (3,7) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 14 x 14 14 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) (4,3 x 4,3) (4,3) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 16 x 16 16 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 17 GPM (64.3 LPM) 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) (4,9 x 4,9) (4,9) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 7.0 psi (0.48 bar) 12.0 psi (0,83 bar) 18x 18 18 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (5,5 x 5,5) (5,5) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 20 x 20 20 20 GPM (75,7 LPM) 20 GPM (75,7 LPM) 20 GPM (75,7 LPM) 21 GPM (79,5 LPM) 22 GPM (83,3 LPM) (6,1 x 6,1) (6,1) 16.7 psi (1,15 bar) 16.7 psi (1,15 bar) 16.7 psi (1,15 bar) 18.4 psi (1,27 bar) 20.2 psi (1,39 bar)
For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures ar
e
c
a
l
c
u
l
a
t
e
d
using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII (TY2234)
RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS
Technical
Data
Approvals:
UL and C-UL Listed. NYC Approved
under MEA 44-03-E.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient:
1< = 4.9 GPM/psi'/2 (70,6 LPM/bari/2)
Temperature Rating:
155°F1680C or 175017/790C
Finishes:
White Polyester Coated,
Chrome Plated, or Natural Brass
Physical Characteristics:
Frame ..............Brass
Button .............Bronze
Sealing Assembly ..........
Beryllium Nickel w/Tefiont Bulb .........3 mm dia. Glass
Compression Screw .....Bronze
Deflector ...........Bronze
Ejection Spring - . . . Stainless Steel
tDuPont Registered Trademark
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series LFll (TY2234) Residential
Pendent Sprinklers are UL and C-UL
Listed for installation in accordance
with the following criteria.
NOTE When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the local Authority havingJuris-
diction.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of "design sprinklers" as speci-
fied in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Table A for
NFPA 13D and 13R as a function of
temperature rating and the maxi-
mum allowable coverage area.
A minimum discharge of 0.1 gpmlsq.
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity.
For "Horizontal Ceilings" (maximum
2 inch rise for 12 inch run), the sprin-
klers are to be installed with a deflec-
tor to ceiling distance of 1-3/8 to 4
inches or in the recessed position
using only the Style 20 Recessed
Escutcheon as shown in Figure 2.
NOTES
The "Beam Ceiling Design Criteria"
section starting on Page 4 permits de-
flector to ceiling distances up to 15-3/4
inches.
So as to help avoid obstructions to
water distnbution, a maximum 12 inch
deflector-to-ceiling distance is permit-ted forNFPA 130 andNFPA 13Rappli-
cations where the sprinklers are located
in closets.
For "Sloped Ceilings" (greater than
2 inch rise up to 8 inch rise for 12
inch run), the sprinklers are to be
installed with a deflector to ceiling
TFP400 Page 3 of 8
7/16" (11,1 mm) 1/2" ESCUTCHEON
________ 2-7/8'DIA.
1 - Frame MAKE-IN SURFACE
2 - Button
(73,0 mm)
Bulb
Compression 2
2-1/4" Screw
Components: NOMINAL NPT PLATE SEATING
H I
3 Sealing Assembly 1
6 - Deflector* ________ (57,2 mm)
L
_____
RENCI
1-5/8' I
STYLE 20 (41,3 mm) I w RECESSED
ESCUTCHEON
* Temperature 5 .___.-..--I FLATS
rating is
indicated on 6* .__C=IJ_JIlZ=
Deflector.
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
SERIES LFII (TY2234) RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS
- 2-7/8" DIA.
7/16±1/8" (73,0 mm) I 1/2"(12,7 mm) r (11,1*3,2 mm) 2-1/4' DIA. I 1/4"(6.4 mm) I
FACE OF I SPRINKLER
(57,2 mm)
['
MOUNTING FITTING PLATE I
II'
I
_ T-7-
MOUNTING
1/8" SURFACE/
(3,2 mm)
CLOSURE / TY2234 1-8" (,9 mm) -
1-1/8"(28,6 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON
FOR USE WITH THE SERIES LFII (TY2234)
RESIDENTIAL PENDENT SPRINKLER
distance of 1-3/8 to 4 inches or in
the recessed position using only the
Style 20 Recessed Escutcheon as
shown in Figure 2
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
length of the coverage area (Ref. Table
A) being hydraulically calculated (e.g.,
maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 feet for a 20 ft. x
20 ft. coverage area).
WRENCH RECESS
(END "A' USED
FOR 1Y2234)
FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 4 of 8 TFP400
Beam Ceiling
Design Criteria
The Series LFII (TY2234) Residential
Pendent Sprinklers are UL and C-UL
Listed for installation in residential oc-
cupancies with horizontal ceilings (i.e.,
slopes up to a 2 inch rise over a 12 inch
run) with beams when installed in ac-
cordance with the following criteria:
General Information. The basic con-
cept of this protection scheme is to
locate the sprinklers on the underside
of the beams, Ref. Figure 5, (not in the
beam pockets); to identify the main
beams that principally run in one direc-
tion as "primary beams"; and, to iden-
tify the beams that run principally per-
pendicular to the main beams, as may
be present (or in some cases may be
necessary for proper sprinkler protec-
tion), as "secondary beams".
Primary and Secondary Beam
Types. Solid surface, solid or hollow
core, combustible or non-combustible.
Primary and Secondary Beam Posi-
tioning. Directly attached to the un-
derside of a combustible or non-com-
bustible smooth ceiling at any
elevation.
Primary Beam Cross-Section: Maxi-
mum depth of 14 inches and the maxi-
mum width is unlimited. The cross-sec-
tional shape of the primary beam may
be rectangular to circular.
Secondary Beam Cross-Section.
Maximum depth to be no greater than
the primary beam and the maximum
width is unlimited. The cross-sectional
shape of the secondary beam may be
rectangular to circular.
Primary Beam Spacing. The primary
beams (Fig. 6A) are to be 3 ft. -4 in. to
6 ft. from the compartment wall to cen-
ter of the nearest beam and from cen-
ter to center between beams.
Secondary Beam Spacing. The sec-
ondary beams principally run perpen-
dicular to the primary beams.
Secondary beams of a depth equal to
the primary beam must be placed so
that the beam pockets created by the
primary beams do not exceed 20 feet
in length (Fig. 6B).
NOTE
When the beam pockets created by
the primal',' beams exceed 20 feet in
length, the installation will require the
use of secondary beams as described
above. Otherwise, secondary beams
need not be present.
Secondary beams of a cross-sectional
depth greater than one-quarter the
depth of the primary beams are to be
a minimum of 3 ft. - 4 in. from the compartment wall to center of the
nearest beam and from center to cen-
ter between beams (Fig. 6C).
Secondary beams of a cross-sectional
depth no greater than one-quarter the
depth of the primary beams may be
placed at any compartment wall to
center of the nearest beam distance
and from any center to center distance
between beams (Fig. 6C).
Lintels. Lintels over doorways exiting
the compartment must be present. The
minimum height for the lintels is 8
inches or no less than the depth of the
Primary Beams, whichever is greater.
Sprinkler Types. Series LFll
(TY2234), 155F and 175F, Pendent
and Recessed Pendent Residential
Sprinklers.
Sprinkler Coverage Area and Hy-
draulic Design. The sprinkler cover-
age areas and hydraulic design criteria
as presented in the Table A for "Hori-
zontal Ceilings" are to be applied.
Sprinkler Position. The deflector to
bottom of primary beams for the Series
LFli (TY2234) Pendent Sprinklers or
Series LFll (TY2234) Recessed Pen-
dent Sprinklers is to be 1-1/4 to 1-314
inches (Fig. 5A). The vertical center-
line of the Series LFll (TY2234) Pen-
dent Sprinklers is to be no greater than
half the primary beam cross-sectional
width plus 2 inches from the centerline
of the primary beam (Fig 513).
NOTES Core drilllng of beams to allow the in-
stallation of sprinkler drops requires
consulting with a structural engineer.
Where core drilling is not permitted,
the previously stated sprinkler position
criteria for the Series LFll (TY2234)
Pendent Sprinklers allows for the
sprinkler drop to be placed adjacent to
the primaiy beam.
Beam and Soffit Arrangements. A
soffit is permitted to be placed around
the perimeter of a compartment with
the beam arrangement within the sof-
fited area (Fig.7).
The cross-section of the soffit may be
any size as long as it does not create
an obstruction to water distribution per
the obstruction rules of NFPA 13 for
residential sprinklers.
When soffits are present, the pre-
viously provided 3 ft. - 4 in. to 6 ft. "compartment wall to adjacent beam"
distance for the primary and secon-
dary beams is to be measured from the
face of the soffit as opposed to the
compartment wall.
A__
1Y2234
B
: LE
Ln
MAXIMUM I ivni ONE-HALF BEAM
WIDTH PLUS
2 (50,8 mm)
FIGURE 5
SPRINKLER POSITIONING
UNDER PRIMARY BEAMS
(Refer to the "Beam Ceiling
Design Criteria" section)
NOTE
Although the distance to the beams is
measured from the face of the soffit,
the sprinkler coverage area is to be
measured from the compartment wall.
I
TFP400
Page 5 of 8
ALL FIGURES: I--A_-i. A_
-'.
A-.—.j DISTANCES ARE I F IF F MEASURED TO
14 (356 mm) COMPARTMENT
MAXIMUM WALL FACES .AND •Y TO CENTERLINES
•. OFBEAMS
A3to6'.O(1,OtO1,8m)
FOR PRIMARY BEAMS HAy-
MAXIMUM DEPTH
PRIMARY
MAXIMUM
COWARTMENT
WALLS
FIGURE 6A
PRIMARY BEAM SPANS UP TO 20'-O (6,1 m)
h—A_.[. A_
--
A— k IF
A=3'-4to6-0(1,0to1,8m)
FOR PRIMARY BEAMS HAV- SECONDARY . B INGA 14'(356 mm) MAXIMUM BEAM DEPTH
B =20'-0 (6,1 m) MAXIMUM
FOR SECONDARY BEAMS
THAT ARE TO BE EQUAL IN PRIMARY DEPTH TO PRIMARY BEAMS BEAM • AND THAT MUST BE IN PLACE
. SO THAT PRIMARY BEAM
POCKETS DO NOT EXCEED
20-0 (6,1 m)
COMPARTMENT :.
WALLS
FIGURE 6B
PRIMARY BEAM SPANS GREATER THAN 20-0' (6,1 m)
h-A__-. A_ A —.-I
I F
,I. . . C A3-4 t06-0 (1,0to1,8m) . \ FOR PRIMARY BEAMS HAy-
'I INGA14'(356 mm) MAXIMUM SECONDARY :. C DEPTH BEAM
•.•..
'
C = Y-4"(1,0 m) MINIMUM FOR
\ SECONDARY BEAMS HAVING
DEPTHS GREATER THAN 25%
OF PRIMARY BEAMS PRIMARY*
—or— BEAM
'•. C =ANY DISTANCE FOR SEC-
ONDARY BEAMS HAVING
DEPTHS UP TO 25% OF * REFER TO :.. . PRIMARY BEAMS FIGURE 6B COMPARTMENT
FOR SPANS WALLS EXCEEDING
2(Y-O"(6,1 m)
FIGURE 6C
COMBINATIONS OF PRIMARY AND SECONDARY BEAMS
FIGURE 6
BEAM ARRANGEMENTS
(Refer to the "Beam Ceiling Design Criteria" section)
Page 6 of 8 TFP400
Installation
The Series LFII (TY2234) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6mm).
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series LFII Pendent Sprinklers
must be installed in accordance with
the following instructions.
Step 1. Pendent sprinklers are to be
installed in the pendent position with
the deflector parallel to the ceiling.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 3).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats.
The Series LFII Recessed Pendent
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step A. Recessed pendent sprinklers
are to be installed in the pendent posi-
tion with the deflector parallel to the
ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 4). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step D. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 20 Closure
over the Series LFII Sprinkler and
push the Closure over the Mounting
Plate until its flange comes in contact
with the ceiling.
Care and
Maintenance
The Series LFII (TY2234) must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Absence of an Escutcheon Plate may
delay the sprinkler operation in a fire
situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
TFP400 Page 7 of 8
age to the sprinklers - before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
NOTE
The owner must assure that the sprin-
klers are not used for hanging of any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-vertent operation may result.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-côrdance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability..
Sprinkler Assembly:
Series LFII (TY2234), K=4.9, Residen-
tial Pendent Sprinkler with (specify)
temperature rating and (specify) finish,
P/N (specify).
155'F/68°C or
Chrome Plated .........P/N 51-201-9-155 155°F/68°C
White Polyester.........PIN 51.201-4-155 155°F/68°C
White
(RAL9O1O) ............. P/N 51-201-3-155 155°F168'C
Natural Brass...........P/N 51-201-1-155 1751F/791C or
Chrome Plated .........P/N 51-201-9-175 175'F179°C
White Polyester.........P/N 51-201-4-175 175°F/79°C
White
(RAL9OIO) ............. P/N 51-201-3-175 175°F/79'C
Natural Brass...........P/N 51-201-1-175
Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style 20 Recessed Escutch-
eon with (specify) finish, P/N (specify).
1/2' (15 mm)
Style 20
Chrome Plated .........P/N 56-705-9-010 1/2' (15 mm)
Style 20
White Color
Coated .................P/N 56-7054-010 1/2' (15 mm)
Style 20
White
(RALSO1O) ............. P/N 56-705-3-010 1/2' (15 mm)
Style 20
Bright Brass
Coated ................ PIN 56-705-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Page 8 of 8
TFP400
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale,
P
e
n
n
s
y
l
v
a
n
i
a
1
9
4
4
6
tqCC Fire & Building
liProducts
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series LFII Residential
Horizontal Sidewall Sprinklers
4,2 K-factor
General
Description
The Series LFII (1Y1334) Residential
Horizontal Sidewall Sprinklers are
decorative, fast response, frangible
bulb sprinklers designed for use in
residential occupancies such as
homes, apartments, dormitories, and
hotels. When aesthetics and optimized
flow characteristics are the major con-
sideration, the Series LFII (TY1334)
should be the first choice.
The Series LFII are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 131); wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy pet NFPA 13.
The Series LFII (TY1334) has a 4.2
(60,5) K-factor that provides the re-
quired residential flow rates at reduced
pressures, enabling smaller pipe sizes
and water supply requirements.
The recessed version of the Series
LFII (1Y1334) is intended for use in
areas with finished walls. It employs a
two-piece Style 20 Recessed Escutch-
eon. The Recessed Escutcheon pro-
vides 1/4 inch (6,4 mm) of recessed
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNINGS that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
adjustment or up to 1/2 inch (12,7 mm)
of total. adjustment from the flush
mounting surface position. The adjust-
ment provided by the Recessed Es-
cutcheon reduces the accuracy to
which the pipe nipples to the sprinklers
must be cut.
The Series LFII (TY1334) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
WARNINGS
The Series LFII (TY1334) Residential
Horizontal Sidewall Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler/Model
Identification
Number
SIN TY1334
Page 1 of 8 APRIL, 2004 TFP4IO
WRENCH RECESS ell
(END 'A" USED
FOR TY1334)
FIGURE 3
W-TYPE 6 SPRINKLER WRENCH
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 2 of 8 TFP4IO
2 - Button Assembly
FLATS
Components: 5 3 2 1
3 - sealing Assembly
1 - Frame
7/16" mm)
WRENCH
Bulb
Compression Screw
Deflector * TOP-OF-
2-7/8" DIA.
(73,0 mm)
NOMINAL DEFLECTOR "1 MAKE-IN
* Temperature rating
is indicated on top
CENTERLINE
OF WATERWAY 7116"
of Deflector.
1/2" NPT RECESSEDIJ
(11,1 mm) STYLE 20
ESCUTCHEON END-OF- (41,3 mm) ESCUTCHEON DEFLECTOR 2-1/4" PLATE SEATING
RECESSED (57,2 mm) SURFACE BOSS
FIGURE 1
SERIES LFII (TY1334) RESIDENTIAL
HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
7/16±1/8"
(11.1±3,2 mm)
MOUNTING FACE OF
SURFACE -.... - SPRINKLER
FITTING
TOP-OF- CLOSURE
DEFLECTOR TY1334
2-7/8"DIA.
(73,0 mm)
1/4"DIA. I
7/16" -
(57,2 mm) I
(11,1mm)
MOUNTING
PLATE
1/8"
END-OF-
DEFLECTOR - -_
BOSS (3,2 mm)
1-3/8" (34,9 mm) 1/2" (12,7 mm)
1-118'(28,6 mm) 1/4" (6,4 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON
FOR USE WITH THE SERIES LFII (TY1334)
RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER
TFP4IO Page 3 of 8
Technical
Data
Approvals:
UL and C-UL Listed. NYC Approved
under MEA 44-03-E.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient:
K = 4.2 GPM/psi'/2 (60,5 LPM/barl/2)
Temperature Rating:
155017/680C or 1750F/790C
Finishes:
White Polyester Coated,
Chrome Plated, or Natural Brass
Physical Characteristics:
Frame ..............Brass Button .............Bronze
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb .........3 mm dia. Glass
Compression Screw .....Bronze
Deflector ...........Copper
tDupont Registered Trademark
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series LFII (TY1334) Residential
Horizontal Sidewall Sprinklers are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
NOTE
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the local Authority Having Ju-
risdiction.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A, B, C, and D as a
function of temperature rating and the
maximum allowable coverage areas.
The sprinkler flow rate is the minimum
required discharge from each of the
total number of "design sprinklers" as
specified in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Tables A, B,
C, and 0 for NFPA 130 and 13R as
a function of temperature rating and
the maximum allowable coverage
area.
A minimum discharge of 0.1 gpmlsq.
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity. The sprin-
klers are to be installed with an end-of-
deflector-boss to wall distance of 1-
3/8 to 6 inches or in the recessed po-
sition using only the Style 20 Re-
cessed Escutcheon as shown in
Figure 2.
In addition the top-of-deflector-to-ceil-
ing distance is to be within the range
(Ref. Table A, B, C, or D) being hydrau-
lically calculated.
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
width of the coverage area (Ref. Table
A) being hydraulically calculated (e.g.,
maximum 12 feet for a 12 ft. x 12 ft.
coverage area, or 16 feet for a 16 ft. x
20 ft. coverage area).
Installation
The Series LFII (TY1334) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch (1,6mm).
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series LFII Horizontal Sidewall
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step 1. Horizontal sidewall sprinklers
are to be installed in the horizontal
position with their centerline of water-
way perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the Deflector is to face towards the
ceiling with the front edge of the De-
flector parallel to the ceiling.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 3).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench fiats.
The Series LFII Recessed Horizontal
Sidewall Sprinklers must be installed
in accordance with the following in-
structions.
Step A. Recessed honzontal sidewall
sprinklers are to be installed in the
horizontal position with their centerline
of waterway perpendicular to the back
wall and parallel to the ceiling. The
word "TOP" on the Deflector is to face
towards the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 4). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step C. After the wall has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 20 Closure
over the Series LFII Sprinkler and
push the Closure over the Mounting
Plate until its flange comes in contact
with the wall.
(Continued on Page 8)
Page 4 of 8
TFP4IO
ELEVATION
Maximum Maximum
Coverage Spacing Minimum Flow (c) and Residual Pressure Area (a)
Width x Length (b)
Ft.
(m) Top-Of-Deflector- To- Ceiling: Top-Of-Deflector- To- Ceiling:
R. x Ft. 4 to 6 Inches (100 to 150 mm) 6 t 12 inches (100 to 150 mm)
(mxm)
155aFI68aC 175°F1790C 155F168°C 175aF/790C
12 x 12 12 12 GPM (45,4 LPM) 12 GPM (45,4 LPM) 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) (3,7 x 3,7) (3,7) 8.2 psi (0,57 bar) 82 psi (0,57 bar) 9.6 psi (0,66 bar) 9.6 psi (0,66 bar) 14 x 14 14 14 GPM (53,0 LPM) 16 GPM (60,6 LPM) 17 GPM (64,3 LPM) 18 GPM (68,1 LPM) (4,3 x 4,3) (4,3) 11.1 psi (0,77 bar) 14.5 psi (1,00 bar) 16.4 psi (1,13 bar) 18.4 psi (1,27 bar) 16 x 16 16 16 GPM (60,6 LPM) 16 GPM (60,6 LPM) 18 GPM (68,1 LPM) 18 GPM (68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi (1,00 bar) 14.5 psi (1,00 bar) 18.4 psi (1.27 bar) 18.4 psi (1.27 bar) 16x18 16 19 GPM (71,9 LPM) 19 GPM (71,9 LPM) 21 GPM (79,5LPM) 21 GPM (79,5LPM) (4,9 x 5,5) (4,9) 20.5 psi (1.41 bar) 20.5 psi (1,41 bar) 25.0 psi (1,72 bar) 25.0 psi (1,72 bar) 16 x 20 16 23 GPM (87,1 LPM) 23 GPM (87,1 LPM) 26 GPM (98,4 LPM) 26 GPM (98,4 LPM) (4,9 x 6,1) (4,9) 30.0 psi (2,07 bar) 1 30.0 psi (2,07 bar) 38.3 psi (2,64 bar) 38.3 psi (2,64 bar)
For coverage area dimensions less than or between those indicated, it is necessary to use the min
i
m
u
m
r
e
q
u
i
r
e
d
f
l
o
w
f
o
r
t
h
e
n
e
x
t
highest coverage area for which hydraulic design criteria are stated.
Width (backwail where sprinkler is located) x Length (horizontal throw of sprinkler).
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressu
r
e
s
a
r
e
c
a
l
c
u
l
a
t
e
d
u
s
i
n
g
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
Sidewall sprinklers, where installed under a ceiling with a slope greater than 0 inch rise for a 12 inch r
u
n
t
o
a
s
l
o
p
e
u
p
t
o
2
i
n
c
h
rise for 12 inch run, must be located per one of the following:
a Locate the sprinklers at the high point of the slope and positioned to discharge down the slope.
Locate the sprinklers along the slope and positioned to discharge across the slope.
TABLE A
NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
FOR HORIZONTAL CEILING (Maximum 2 Inch Rise for 12 Inch Run)
TFP4IO
Page 5 of 8
12"
ELEVATION
Minimum Flow (c) and Residual Pressure (I) Two sprinkler design with the sprinklers at the high point of t
h
e
s
l
o
p
e
and positioned to discharge down the slope. Maximum Maximum
Coverage Spacing
Area (a) R.
Widthx Length (b)
(mx m)
(m)
Top-Of-Deflector- To- Ceiling:
4 to 6 Inches (100 to 150 mm)
Top-Of-Deflector- To- Ceiling:
6 to 12 Inches (150 to 300 mm)
155°F168°C 175°F/790C 155F/68°C 175°F179°C
12 x 12 12 I 12 GPM (45,4 LPM) I 12 GPM (45,4 LPM) F 13 GPM (49,2 LPM) I 13 GPM (49,2 LPM) (3,7 x 3,7) (3,7) 82 psi (0,57 bar)
-
8.2 psi (0,57 bar)
-
9.6 psi (0,66 bar)
-
9.6 psi (0,66 bar) 14 x 14 14 1 14 GPM (53,0 LPM) I 14 GPM (53,0 LPM) 1 17 GPM (64.3 LPM) 1 17 GPM (64.3 LPM) (4,3 x 4,3) (4,3) 11.1 psi (0,77 bar)
-
11.1 psi (0,77 bar) 16.4 psi (1,13 bar)
-
16.4 psi (1,13 bar) 16 x 16 16 1 16 GPM (60,6 LPM) I 16 GPM (60,6 LPM) 1 18 GPM (68,1 LPM) I 18 GPM (68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi (1,00 bar) 14.5 psi (1,00 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar) 16 x 18 16 I 19 GPM (71,9 LPM) 1 19 GPM (71,9 LPM) F 21 GPM (79,5 LPM) I 21 GPM (79,5 LPM) (4,9 x 5,5) (4,9) 20.5 psi (1.41 bar)
-
20.5 psi (1,41 bar). 25.0 psi (1,72 bar) 25.0 psi (1,72 bar) 16 x 20 16 I 24 GPM (90,8 LPM) I 24 GPM (90,8 LPM) 1 26 GPM (98,4 LPM) 1 26 GPM (98,4 LPM) (4,9 x 6,1) (4,9)
- 32.7 psi (2,25 bar)
- 32.7 psi (2,25 bar)
-
38.3 psi (2,64 bar)
-
38.3 psi (2,64 bar)
For coverage area dimensions less than or between those indicated, it
i
s
n
e
c
e
s
s
a
r
y
t
o
u
s
e
t
h
e
m
i
n
i
m
u
m
r
e
q
u
i
r
e
d
f
l
o
w
f
o
r
t
h
e
n
e
x
t
highest coverage area for which hydraulic design criteria are stat
e
d
.
Width (backwali where sprinkler Is located) x Length (horizontal t
h
r
o
w
o
f
s
p
r
i
n
k
l
e
r
)
.
Requirement is based on minimum flow in GPM (LPM) from each
s
p
r
i
n
k
l
e
r
.
T
h
e
a
s
s
o
c
i
a
t
e
d
r
e
s
i
d
u
a
l
p
r
e
s
s
u
r
e
s
a
r
e
c
a
l
c
u
l
a
t
e
d
u
s
i
n
g
the nominal K-factor. Refer to Hydraulic Design Criteria Section for detail
s
.
.
TABLE B NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HO
R
I
Z
O
N
T
A
L
S
I
D
E
W
A
L
L
S
P
R
I
N
K
L
E
R
S
FOR SPRINKLERS AT THE HIGH POINT OF THE SLOPE AND DI
S
C
H
A
R
G
I
N
G
D
O
W
N
T
H
E
S
L
O
P
E
(Greater Than 2 Inch Rise for 12 Inch Run Up To 8 Inch Rise for
1
2
I
n
c
h
R
u
n
)
Page 6 of 8
TFP4IO
12"
ELEVATION
Minimum Flow (c) and Residual Pressure
Two sprinkler design with the sprinklers located along the slope and positione
d
t
o
discharge across the slope. Maximum Maximum Three sprinkler design when there are more than two sprinklers In a compart
m
e
n
t
a
n
d
Coverage Spacing with the sprinklers located along the slopeand positioned to discharge across
t
h
e
s
l
o
p
e
.
Area (a) Ft.
Wldthx Length (b)
m (x in)
(m)
Top-Of-Deflector- To- Ceiling:
4 to 6 Inches (100 to 150 mm)
Top-Of-Deflector- To- Ceiling:
6 to 12 inches (100 to 300 mm)
15FI6C 175°F/790C 155Fi68°C 175°FI79*C
12 x 12 12 II 16 GPM (60,6 LPM) 5 16 GPM (60,6 LPM) U 18 GPM (68,1 LPM) II 18 GPM (68,1 LPM) (3,7 x 3,7) (3,7) 14.5 psi (1,00 bar) 14.5 psi (1,00 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar)
1
14 x 14 14 II 16 GPM (60,6 LPM) II 16 GPM (60,6 LPM) U 18 GPM (68,1 LPM) II 18 GPM (68,1 LPM) (4,3 x 4,3) (4,3)
-
14.5 psi (1,00 bar)
-
14.5 psi (1,00 bar)
-
18.4 psi (1.27 bar) 18.4 psi (1,27 bar) 16 x 16 16 II 16 GPM (60,6 LPM) II 16 GPM (60,6 LPM) II 18 GPM (68,1 LPM) II 18 GPM (68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi (1,00 bar) 14.5 psi (1,00 bar) 18.4 psi (1,27 bar) 1 18.4 psi (1,27 bar) 16 x 18 16 iT 22 GPM (83,3 LPM) II 22 GPM (83,3 LPM) U 22 GPM (83,3 LPM) II 22 GPM (83,3 LPM) (4,9 x 5,5) (4,9) 27.4 psi (1,89 bar) 27.4 psi (1,89 bar) 27.4 psi (1,89 bar) 27.4 psi (1,89 bar) 16 x 20 16 In 23 GPM (87,1 LPM) In 23 GPM (87,1 LPM) Il 26 GPM (98,4 LPM) III 26 GPM (98,4 LPM) (4,9 x 6,1) (4,9) 30.0 psi (2,07 bar)
-
30.0 psi (2,07 bar)
-
38.3 psi (2,64 bar)
-
38.3 psi (2,64 bar)
For coverage area dimensions less than or between those indicated, it is necessary t
o
u
s
e
t
h
e
m
i
n
i
m
u
m
r
e
q
u
i
r
e
d
f
l
o
w
f
o
r
t
h
e
n
e
x
t
highest coverage area for which hydraulic design criteria are stated.
Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkle
r
)
.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. Th
e
a
s
s
o
c
i
a
t
e
d
r
e
s
i
d
u
a
l
p
r
e
s
s
u
r
e
s
a
r
e
c
a
l
c
u
l
a
t
e
d
u
s
i
n
g
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details..
TABLE C NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZ
O
N
T
A
L
S
I
D
E
W
A
L
L
S
P
R
I
N
K
L
E
R
S
FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING AC
R
O
S
S
T
H
E
S
L
O
P
E
(Greater Than 2 Inch Rise for 12 Inch Run Up To 4 Inch Rise for 12 Inch Run)
TFP4IO
Page 7 of 8
12"
ELEVATION
Minimum Flow (c) and Reèiduai Pressure
(LII) Three sprinkler design when there are more than two sprinklers in a c
o
m
p
a
r
t
m
e
n
t
a
n
d
with the sprinklers located along the slope and positioned to discharge across th
e
s
l
o
p
e
.
Maximum Maximum
Coverage Spacing
Area (a) Ft.
Width x Length (b)
R. x Ft.
(mxm)
(m)
Top-Of-Deflector- To- Ceiling:
4to6 Inches (100to150mm)
155°F168°C 175°F/79C
12 x 12 12 111 16 GPM (60,6 LPM) ifi 16 GPM (60,6 LPM) (3,7 x 3,7) (3,7) 14.5 psi (1,00 bar) 14.5 psi (1,00 bar) 14 x 14 14 III 16 GPM (60,6 LPM) III 16 GPM (60,6 LPM) (4,3 x 4,3) (4,3)
- 14.5 psi (1,00 bar)
- 14.5 psi (1,00 bar) 16 x 16 16 III 16 GPM (60,6 LPM) III 16 GPM (60,6 LPM) (4,9 x 4,9) (4,9) 14.5 psi (1,00 bar) 14.5 psi (1,00 bar) 16x18 16 N/A N/A (4,9x5,5) (4,9)
16x20 16 N/A N/A (4,9x6,1) (4,9)
For coverage area dimensions less than or between those indicated, it Is necessary
t
o
u
s
e
t
h
e
m
i
n
i
m
u
m
r
e
q
u
i
r
e
d
f
l
o
w
f
o
r
t
h
e
n
e
x
t
highest coverage area for which hydraulic design criteria are stated.
Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler).
Requirement Is based on minimum flow in GPM (LPM) from each sprinkler. T
h
e
a
s
s
o
c
i
a
t
e
d
r
e
s
i
d
u
a
l
p
r
e
s
s
u
r
e
s
a
r
e
c
a
l
c
u
l
a
t
e
d
u
s
i
n
g
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details..
TABLED NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SI
D
E
W
A
L
L
S
P
R
I
N
K
L
E
R
S
FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING AC
R
O
S
S
T
H
E
S
L
O
P
E
(Greater Than 4 Inch Rise for 12 inch Run Up To 8 Inch Rise for 12 Inch R
u
n
)
Page 8 of 8
TFP4IO
Care and
Maintenance
The Series LFII (1Y1334) must be
maintained and serviced in accord-
ance with the following instructions:
NOTES Absence of an Escutcheon Plate may
delay the sprinkler operation in a fire
situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
NOTE The owner must assure that the sprin-
klers are not used for hanging of any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability..
Sprinkler Assembly:
Series LFIl (TY1334), K=4.2,Residen-
tial Horizontal Sidewall Sprinkler with
(specify) temperature rating and
(specify) finish, P/N (specify).
155'F/68C or
Chrome Plated .........P/N 51.211-9-155 155°F168'C
White Polyester ......... P/N 51-211-4-155 155°F168'C
White (RAL9O1O) ............. P/N 51-211-3-155 155°F/68°C Natural Brass...........P/N 51-211-1-155 175'F179'C or Chrome Plated .........P/N 51-211-9-175 175'F179'C
White Polyester.........P/N 51-211-4-175 175'Ff79'C
White (RAL9O1O) ............. P/N 51-211-3-175 175°F/79°C
Natural Brass...........P/N 51-211-1-175
'Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style 20 Recessed Escutch-
eon with (specify) finish, P/N (specify).
1/2' (15 mm)
Style 20 Chrome Plated .........P/N 56-705-9-010 1/2' (15 mm)
Style 20
White Color Coated ................P/N 56-705-4-010 1/2' (15 mm)
Style 20
White
(RAL9OIO) ............. P/N 56.705-3-010 112 (15 mm)
Style 20
Bright Brass
Coated................P/N 56-705-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqLL' /.fire & Buildflng
/ Th:.:ts
Technical Services: Tel: (800) 381-9312/ Fax: (
8
0
0
)
7
9
1
-
5
5
0
0
Series TY-FRB
- 2.8,4,2 .v 54, and 80 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Cove
r
a
g
e
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
IMPORTANT Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING" that provides cautions
with respect to handling and Instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS The. Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TVII31 - Upright 2.8K, 112"NPT TY1231 - Pendent 2.8K, 112"NPT TY2131 - Upright 4.2K, 1/2"NPT TY2231 - Pendent 4.2K, 1/2"NPT TY3131 - Upright 5.6K, 1/2"NPT
TY3231. Pendent 5.6K, 1/2"NPT
TY4131 - Upright 8.0K, 314"NPT 1Y4231 - Pendent 8.0K, 314"NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.6 GPM/ps1112 (40,3 LPM/barl12) K = 4.2 GPM/ps1112 (60,5 LPM/bar"Z) K = 5.6 GPM/ps11/2 (80,6 LPM/bar112) K = 8.0 GPM/psi112 (115,2 LPM1barl')
Temperature Ratings
Refer to Table A and B
Page 1 of 8
JULY, 2004
ESCUTCHEON 7/16'(11,1 mm) PLATE SEATING • ** NOMINAL SURFACE ,. MAKE-IN
Page 2of8
TFPI7I
STYLE 10or20
RECESSED
ssu ESCUTCHEON DEFLECTOR
(11,1 mm) I NOMINAL
MAKE-IN
AL I
7/16" 1
IIF 'WRENCH 2-3/16"
7 FLATS (55,6 mm)
1/2UNPT** f SSP DEFLECTOR * h"— 2-7/8"(73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression 7- Bushing orifice seat on frame. Screw **pipe thread connections per ISO 7/1 can be provided on special request.
FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (771131) AND PEND
E
N
T
(
T
Y
1
2
3
1
)
S
P
R
I
N
K
L
E
R
S
2,8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16' (11,1 mm) STYLE 10 or 20 PLATE SEAliNG ** NOMINAL RECESSED SURFACE MAKE-IN ESCUTCHEON SSU NPT DEFLECTOR
7/16" 2-3/16' (11,1 mm) 1. J
(55,6 mm)
NOMINAL
MAKE-IN
1-1/2' I I 1]!
3 I
V
2-
3
/
mm) WRENCH (55,6 mm) FLATS
SSP DEFLECTOR* 2-7/8"(73,0 mm) DIA. —"-I 1/2" NPT** I
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw
**Pipe thread connections per ISO 7/1 can be provided on special request.
FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (
T
Y
2
2
3
1
)
S
P
R
I
N
K
L
E
R
S
4.2K-FACTOR, 1/2 INCH NPT
Finishes Bulb ..............Glass Sprinkler: Refer to Table A and B Compression Screw .....Bronze Recessed Escutcheon: White Coated, Deflector.......Copper/Bronze Chrome Plated, or Brass Plated Bushing (K=2.8) .......Bronze
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ............
Beryllium Nickel w/Teflont
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
.4-
SSP DEFLECTOR * h"— 2-7/8" (73,0mm) DIA.
7/16" (11,1 mm)
** NOMINAL
NPT MAKE-IN
STYLE 100r20
RECESSED
ESCUTCHEON
WRENCH
FLATS
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16" (55,6 mm)
1-112
(38,1 mm)
TFPI7I
Page 3 of 8
SSU*
DEFLECTOR
7116"
(11,1 mm)
NOMINAL
MAKE-IN
- 2-3/16"
(55,6 mm)
1/2" NPT** I
6*
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION -Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or a
d
j
a
c
e
n
t
t
o
2- Button Assembly 5- Compression orifice seat on frame. Screw
**Pipe thread connections per ISO 7/1 can be provided on special request.
FIGURE 3 QUICK RESPONSE SERIES TY-FRB U
P
R
I
G
H
T
(
T
Y
3
1
3
1
)
A
N
D
P
E
N
D
E
N
T
(
T
Y
3
2
3
1
)
S
P
R
I
N
K
L
E
R
S
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING ** NOMINAL RECESSED ssu SURFACE MAKE-IN ESCUTCHEON
DEFLECTOR 112"
2-5/16"
_
NPT
(12,7 mm) (58,7 mm)
NOMINAL
MAKE-IN
WRENCH __ 1 (57,2 mm)
3
1-9/16"
FLATS
(39,7 mm)
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 3/4" NPT ** I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
- Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or
a
d
j
a
c
e
n
t
t
o
2- Button Assembly 5-Compression
orifice seat on frame. Screw
**Pipe thread connections per ISO 7/1 can be provi
d
e
d
o
n
special request.
FIGURE 4 QUICK RESPONSE SERIES TY-FRB UP
R
I
G
H
T
(
T
Y
4
1
3
1
)
A
N
D
P
E
N
D
E
N
T
(
T
V
4
2
3
1
)
S
P
R
I
N
K
L
E
R
S
8.0 K-FACTOR, 3/4 INCH NPT
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
TFPI7I
Page 4 of 8
SPRINKLER FINISH (See Nate 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
I PLATED
I WHITE
POLYESTER
2.8
1/2"
PENDENT
(TY1231)
and
UPRIGHT
(TY1131)
135"F/57°C Orange
1,2,3,5
155°F168°C Red
175"F/79°C Yellow
200"F/93"C Green
286°F/141 °C Blue
NPT 135°F/57°C Orange
1,2,5
RECESSED
PENDENT
(TY1231)"
FIgure
155°F/68"C Red
175°F/79°C Yellow
200°F/93"C Green
135"F157"C Orange RECESSED
PENDENT
(TY1231)"
Figure 6
155°F/68"C Red
175°F/79"C Yellow
200°F/930C Green
42
1/2"
NPT
PENDENT
(TY2231)
and
UPRIGHT
TY2131)
1350F/57°C Orange
1,2
155°F/680C Red
175°F/79"C Yellow
200°F/930C Green
286°F/141"C Blue
135"F/57°C Orange RECESSED
PENDENT
(TY2231)*
Figure 7
155"F/68°C Red
1750F/790C Yellow
200°F/93"C Green
135017/571C Orange RECESSED
PENDENT
(rv2231)**
Figure 8
155°F/68°C Red
175"F/79"C Yellow
200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Resp
o
n
s
e
Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response
S
p
r
i
n
-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sp
r
i
n
-
klers are UL and C.UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10(1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20(1/2" NPT) or Style 30(3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Ord
e
r
)
.
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, 0r40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been In-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TV-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch (1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 2860F/1410C temperature ratings.
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
112 NPT connections. A leak tight 314
TFPI7I
Page 5 of 8
SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
I PLATED
I WHITE
IPOLYESTER
LEAD
COATED
5.6
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1,2,3,4,5,6,7 1,2,3,5
1550F/68°C Red
175°F1790C Yellow
200°F193°C Green
286017/1410C Blue 1/2"
NPT 135°F/57°C Orange
1,2,4,5 N/A
RECESSED
PENDENT
(TY3231)"
Figure
155"F/68°C Red
175°F1790C Yellow
200"F/93°C Green
135°F/570C Orange
1, 2, 3. 4,5 ( 1,2,4,5 N/A
RECESSED
PENDENT
(TY3231)""
Figure 10
155°F1680C Red
175"F/79"C Yellow
200"F193°C Green
8.0
PENDENT
(1Y4231)
and
UPRIGHT
(TY4131)
135°F/57°C I Orange
1.2.3, 4,5,6,7 1,2,5
155"F/68*C Red
1750171791C Yellow
200°F193°C Green
286°F/141°C Blue 3/4"
NPT 135017/571C Green
1,2,4,5 N/A
RECESSED
PENDENT
(TY4231)"
FIgure 11
155°F/680C Orange
175"F179°C Red
200"F/93"C Yellow
135°F/570C Orange
1,2, 3, 4,5
Green
N/A
RECESSED
PENDENT
crv4231r
Figure 12
155"F/68°C Red
175°F/79°C Yellow
200°F/930C
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers
.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as
Q
u
i
c
k
R
e
s
p
o
n
s
e
S
p
r
i
n
k
l
e
r
s
.
Approved by Factory Mutual Research Corporation (FM) as Quick Response S
p
r
i
n
k
l
e
r
s
.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 0
0
7
1
4
0
4
)
a
s
Q
u
i
c
k
R
e
s
p
o
n
s
e
S
p
r
i
n
k
l
e
r
s
;
h
o
w
e
v
e
r
,
t
h
e
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, N
e
t
h
e
r
l
a
n
d
s
,
T
e
l
.
3
1
-
5
3
4
2
8
.
4
4
4
4
/
F
a
x
3
1
.
5
3
.
4
2
8
-
3
3
7
7
)
.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06)
a
s
Q
u
i
c
k
R
e
s
p
o
n
s
e
S
p
r
i
n
k
l
e
r
s
.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C
-
U
L
L
i
s
t
e
d
,
t
h
e
s
p
r
i
n
k
l
e
r
s
a
r
e
U
L
a
n
d
C
-
U
L
L
i
s
t
e
d
a
s
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be
F
M
A
p
p
r
o
v
e
d
,
t
h
e
s
p
r
i
n
k
l
e
r
s
a
r
e
F
M
A
p
p
r
o
v
e
d
a
s
a
Corrosion Resistant Sprinklers.
* installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjust
m
e
n
t
R
e
c
e
s
s
e
d
E
s
c
u
t
c
h
e
o
n
,
a
s
a
p
p
l
i
c
a
b
l
e
.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustm
e
n
t
R
e
c
e
s
s
e
d
E
s
c
u
t
c
h
e
o
n
,
a
s
a
p
p
l
i
c
a
b
l
e
.
Frame and Deflector only. Listings and approvals apply to color (Special Or
d
e
r
)
.
N/A: Not Available
TABLE B LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 8
2-7/8' DIA.
518t1/4 (73,0 mm) I 314'(19,1 mm)
FACE OF _57,2
MOUNTING SPRINKLER / PLATE I
(15,9±6,4 mm) 2-1/4' DIA. 1/4' (6.4 mm) I
FITTING
/ I 1/8'
L1
(3,2 mm)
MOUNTING / L11ji
SURFACE
CLOSURE SERIES 1-5/16' (33,3 mm)
TV-FRB 13/16' (20,6 mm)
FIGURE 5 SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
,,_..2-7/8'DIA.
(73,0 mm) I 3/4' (19,1 mm) _____________ (15,9±6.4mm) 2-1/4' DIA. I 1/4'(6,4 mm) I FACE OF MOUNTING
(57,2
SPRINKLER PLATE
FITTING
I
MOUNTING
SURFACE
CLOSURE SERIES 1-114"(31,8 mm)
TV-FRB 3t4"(19.1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
2-7/8' DIA. (73,0 mm) 1/2' (12,7 mm) r (12,7a.2 mm) 2-1/4' DIA. 1/4'(6,4 mm) I
FACE OF mm) MOUNTING SPRINKLER PLATE FITTING
1/8'
I (2mm)
4I/
SURFACE/
1-5116".3(33,3 min)
/
CLOSURE SERIES
TV-FRB 1-1/16'(27,0 mm)
FIGURE 6 SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8' DIA. -
(73,0 mm) 1/2±1/8' 1/2' (12,7 mm) r (12,7±39 mm) 2-1/4' DIA. 1/4'(6,4 mm) I
I SPRINKLER PLATE I
I FACE OF E
(57,2 mm)
-1 MOUNTING I I FITTING
1/8' I (32mm)
MOUNTING/ 4
SURFACE
SERIES 1-1/4"(311,111 mm) CLOSURE TY-FRB 1'(25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Moth-
fled sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the Installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFPI7I
2-7/8' VIA. - 5/8±1/4' (73,0 mm) I 3(4' (19,1 mm) (15,9±6,4 mm)
2-1/4' VIA. 1 1/4' (6,4 mm) I
MOUNTING I FACE OF (572
l SPRINKLER
PLATE FITTING
MOUNTING
SURFACE
SERIES 1-1/4'(31,8 mm) CLOSURE TY.FRS V'(19,1 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8' VIA. ,u
5/8±1/4' (73,0 mm) 314' (19,1 mm)
(15,9±6,4 mm) 2-1/4' VIA. 1/4' (6,4 mm) I
FACE OF (57,2
MOUNTING
PLATE SPRINKLER I
/
/_
RUING
(3,2 mm)
j
MOUNTING I SURFACE
CLOSURE SERIES 1-5/16' (333mm)1 TY-FRB 13/16' (.6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 7 of 8
- 2-718' VIA. -
(73,0 mm) 1/2' (12,7 mm) r (12,7±3,2 mm) - 2-1/4' VIA. 1/4' (6,4 mm) I
FACE OF MOUNTING
(572mm)
PLATE I SPRINKLER
FITTING
1/8'
#JT
MOUNTING
SURFACE
SERIES 1-1/41(31.8 mm) CLOSURE TYFRB 1' (25.4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' VIA.
1/2±1/8' (73,0 mm) 1/2k (12.7 mm) 1 (12,7±3,2mm) - 2-1/4' VIA. 1/4' (6.4 mm)
FACE OF
SPRINKLER
(57,2 mm) MOUNTING
PLATE FITTING
1(8'
SURFACE
(3,2 mm)
\ MOUNTING
CLOSURE SERIES 1-5/16' (33,3 mm)] TYFRB 1-1116'(27.0 mm)
FIGURE 12 SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
WRENCH RECESS
(END A USED FOR
1/2' NPT MODELS)
WRENCH RECESS
(END '8' USED FOR
314' NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
local requirements and/or national
codes.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 8 of 8 TFPI7I
PIN 57-XXX-X--- XXX
L
MODEL/SIN
330 2.8K UPRIGHT (1/2NP1) TV1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2NPT) TY2131
341 42K PENDENT (1/2NPT) TY2231
370 5.6K UPRIGHT (1/2NPT) TY3131
371 5.6K PENDENT (1/2NP1) 1Y3231
390 8.0K UPRIGHT (3/4NPT) TY4131
391 8.0K PENDENT (314NP1) TY4231
I I I
155
175
200
286
RATING
L 135
SPRINKLER
1 NATURAL BRASS 1 55°F/68°C
4 WHITE POLYESTER 175°FI79C
3 WHITE (RAL9010)* 200°F/93°C
9 CHROME PLATED 286°F/141°C
7 LEAD COATED
Eastern Hemisphere sates only.
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
@ontaIabus Local distributor for avail-
abilftY.indicate the fuirproduct name. Refer to
the Price List for
complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
With (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2 (15 mm) Style 10
Chrome Plated ............P/N 56-701-9-010 White Coated .............P/N 56-701-4-010 White RALSO1O. ........... PIN 56-701-3-010 Brass Plated ..............P/N 56-701-2-010
1/2 (15 mm)
Style 20
Chrome Plated ............P/N 56-705-9-010 White Coated .............P/N 56-705-4-010 White RAL9O1O. ........... PIN 56-705-3-010 Brass Plated ..............P/N 56-705-2-010
3/4' (20 mm) Style 30
Chrome Plated ............P/N 56-705-9-011 White Coated .............P/N 56-705-4-011 White RAL9010. ........... PIN 56-705-3-011 Brass Plated ..............P/N 56-705-2-011
314' (20 mm)
Style 40
Chrome Plated ............P/N 56-700.9-010 White Coated .............P/N 56-700-4-010 White RAL9O1O. ........... P/N 56-700-3-010 Brass Plated ..............P/N 56-700.2-010
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
tqco Rt & Build ing g
tc..icts
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series TY-FRB - 56 K-factor Horizontal and Vertical Sidewall Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 5.6 K-Factor, Hori-
zontal and Vertical Sidewall Sprinklers
described in this data sheet are quick
response - standard coverage, deco-rative 3 mm glass bulb type spray
sprinklers designed for use in light and
ordinary hazard, commercial occupan-
cies such as banks, hotels, shopping
malls, etc. They are designed for instal-
lation along a wall or the side of a beam
and just beneath a smooth ceiling.
Sidewall sprinklers are commonly
used instead of pendent or upright
sprinklers due to aesthetics or building
construction considerations, where
piping across the ceiling is not desir-
able.
The recessed version of the Series
TY-FRB Horizontal Sidewall Sprinkler
is intended for use in areas with a
finished wall. It uses a two-piece Style
10 Recessed Escutcheon with 1/2 inch
(12,7 mm) of recessed adjustment or
up to 3/4 inch (19,1 mm) of total adjust-
ment from the flush sidewall position,
or a two-piece Style 20 Recessed Es-
cutcheon with 1/4 inch (6,4 mm) of
recessed adjustment or up to 1/2 inch
(12,7 mm) of total adjustment from the
flush sidewall position. The adjustment
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the 'INSTALLER
WARNING that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and In-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
provided by the Recessed Escutcheon
reduces the accuracy to which the
fixed pipe nipples to the sprinklers
must be cut.
Corrosion resistant coatings, where
Applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
WARNINGS The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any otherauthorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices In proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
1Y3331 - Horizontal TY3431. Vertical
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 5.6 PM/psi1 (80,6 LPM/barl/2)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Page 1 of 6 JULY, 2004 TFPI76
Page 2 of 6
TFPI76
SPRINKLER FINISH (See Note 11) K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
WHITEtm
POLYESTER LEAD
COATED
5.6
1/2"
HORIZ .
SIDEWALL
(TY3331)
135"F/57°C Orange
1,2.3,4,9,10 1,2,3,9
Blue
1,2,3,9
155°F168°C Red
175°F/79°C Yellow
200°F193"C Green
286°F1141°C
NPT RECESSED
HORlZ.
SIDEWALL
(TY3331)"
Figure 3
135°F/570C Orange
_________
1,2.4,9.10 1,2,9 N/A
155°F/68°C Red
175"F179°C Yellow
200°F193"C Green
RECESSED
HORIZ.
SIDEWALL
(TY3331)*
Figure, 4
135"F/57°C Orange
1,2,3,4,9 N/A
155°F/68"C Red
175"F179°C Yellow
200"F/93"C Green
5.6
.
NPT
-
VERTICAL
SIDEWALL ",a,)
Installed
Pendent
or
Upright
135"F/57°C Orange
5, 6, 7, 8,9 5,6,7,9
155°F1680C Red
175°F179"C Yellow
2000F/93°C Green
286°F/141"C Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers for use i
n
L
i
g
h
t
a
n
d
O
r
d
i
n
a
r
y
H
a
z
a
r
d
O
c
c
u
p
a
n
c
i
e
s
a
t
a
4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance.
Listed by Underwriters Laboratories Inc. for use in Canada (C-UI) as Quick Resp
o
n
s
e
S
p
r
i
n
k
l
e
r
s
f
o
r
u
s
e
i
n
L
i
g
h
t
a
n
d
O
r
d
i
n
a
r
y
Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceilin
g
d
i
s
t
a
n
c
e
.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Spri
n
k
l
e
r
s
f
o
r
u
s
e
i
n
L
i
g
h
t
H
a
z
a
r
d
O
c
c
u
p
a
n
c
i
e
s
a
t
a
4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007a/04) at
a
4
t
o
6
i
n
c
h
(
1
0
0
t
o
1
5
0
m
m
)
t
o
p
o
f
deflector to ceiling distance. The LPC does not rate the thermal sensitivity of ho
r
i
z
o
n
t
a
l
s
i
d
e
w
a
l
l
s
p
r
i
n
k
l
e
r
s
.
Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers for use in
L
i
g
h
t
a
n
d
O
r
d
i
n
a
r
y
H
a
z
a
r
d
O
c
c
u
p
a
n
c
i
e
s
.
Listed by Underwriters Laboratories for use In Canada (C-UL) as Quick Response
S
p
r
i
n
k
l
e
r
s
f
o
r
u
s
e
i
n
L
i
g
h
t
a
n
d
O
r
d
i
n
a
r
y
H
a
z
a
r
d
Occupancies.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers
f
o
r
u
s
e
i
n
L
i
g
h
t
H
a
z
a
r
d
O
c
c
u
p
a
n
c
i
e
s
.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06
&
0
0
7
a
1
0
4
)
a
s
Q
u
i
c
k
R
e
s
p
o
n
s
e
S
p
r
i
n
k
l
e
r
s
.
Approved by the City of New York under MEA 354-01 -E.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a106) a
t
a
4
t
o
6
i
n
c
h
(
1
0
0
t
o
1
5
0
m
m
)
t
o
p
o
f
deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horiz
o
n
t
a
l
s
i
d
e
w
a
l
l
s
p
r
i
n
k
l
e
r
s
.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL L
i
s
t
e
d
,
t
h
e
s
p
r
i
n
k
l
e
r
s
a
r
e
U
L
a
n
d
C
-
U
L
L
i
s
t
e
d
as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM
A
p
p
r
o
v
e
d
,
t
h
e
s
p
r
i
n
k
l
e
r
s
a
r
e
F
M
A
p
p
r
o
v
e
d
a
s
Corrosion Resistant Sprinklers.
* Installed with Style 10(1/2" NPT) 3/4" Total Adjustment Recessed Escutcheon.
Installed with Style 20(1/2" NPT) 1/2" Total Adjustment Recessed Escutcheon.
Frame and deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflonf
Bulb ...............Glass
Compression Screw .....Bronze
HSW Deflector ........Bronze
VSW Deflector ........Copper
Patents
U.S.A. 5,810,263
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
TFPI 76
Page 3 of 6
DEFLECTOR '\ HAT
--.
6* 4 2 3 1
9/16" WRENCH 1/2" **
(14,3 mm) FLATS NPT
I 1-13/16'
1 mm
7/16' I r'(46,0 mm)
(11 1 , _____ )
CENTERLINE NOMINAL
OF SPRINKLER MAKE-IN I
WATERWAY I - 1-1/2 (38.1 mm)""l
2-3/16"
(55,6 mm)
STYLE ESCUTCHEON
10 0r20 - PLATE SEATING L
RECESSED SURFACE ESCUTCHEON 1 - Frame
2- Button
3-Sealing
Assembly 4-Bulb 2-7/8" DIA. 5-Compression (73,0 mm) Screw 6- Deflector
* Temperature rating Is indicated on deflector or adjacent to orifice seat on fr
a
m
e
.
**Pipe thread connections per ISO 7/1 can be provided on special request.
FIGURE 1
5.6 K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLER
S
Design
Criteria
The Series TY-FRB Horizontal and
Vertical Sidewall Sprinklers are in-
tended for fire protection systems de-
signed in accordance with the stand-
ard installation rules recognized by the
applicable Listing or Approval agency
(e.g., UL Listing is based on the re-
quirements of NFPA 13, and FM Ap-
proval is based on the requirements of
FM's loss Prevention Data Sheets).
Only the Style 10 or 20 Recessed Es-
cutcheon, as applicable, is to be used
for recessed horizontal installations.
installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES Do not install any bulb type sprinkler if
the bulb is cracked or there is loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/570C to 3/32 inch (2,4 mm) for the 286°F/1410C temperature ratings.
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. Higher levels of
torque may distort the sprinkler and
cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Horizontal and Vertical SIdewall Sprinklers must be
installed in accordance with the follow-
ing instructions.
Step 1. Horizontal sidewall sprinklers
are to be Installed In the horizontal
position with their centerline of water-
way perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the Deflector is to face towards the
ceiling.
Vertical sidewall sprinklers are to be
installed in the pendent or upright po-
sition with the arrow on the Deflector
pointing away from the wall.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 5),
With reference to Figure 1 or 2, the
W-Type 6 Sprinkler Wrench is to be
applied to the wrench flats.
The Series TY-FRB Recessed Hori-
zontal Sidewall Sprinklers must be
installed in accordance with the follow-
ing instructions.
Step A. Recessed horizontal sidewall
sprinklers are to be installed in the
horizontal position with their centerline
of waterway perpendicular to the back
wall and parallel to the ceiling. The
word "TOP" on the Deflector is to face
towards the ceiling.
Step B. After installing the Style 10 or
20 Mounting Plate over the sprinkler
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 6). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step D. After the ceiling has been in-
stalled or the finish coat has been ap-
Page 4 of 6
TFPI76
plied, slide on the Style 10 or 20 Clo-
sure over the Series TY-FRB Sprinkler
and push the Closure over the Mount-
ing Plate until its flange comes in con-
tact with the ceiling
Care and
Maintenance
The Series TY-BFR Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, mustbe re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner Is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or compo-
nents manufactured by companies not
affiliated by ownership with Tyco Fire
Products or for products and compo-
nents which have been subject to mis-
use, improper installation, corrosion,
or which have not been installed, main-
tained, modified or repaired in accord-
ance with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
ARROW MUST
POINT AWAY
7/16' FR BE ESCUTCHEON (11.1 mm) PERPENDICULAR
OM AND
PLATE SEATING 1/2' ** NOMINAL TO THE BACK SURFACE MAKE-IN WALL SURFACE j)
216' \ NPT
IWRE _
1I"11'1\ 2-3/16' jIlt
1-1/2'
(55,6 mm)
NCH
mm):
(38,1mm) FLATS LI
SHOWN SHOWN CROSS PENDENT UPRIGHT SECTION
1 - Frame 3-Sealing 4-Bulb 6- Deflector 2- Button Assembly 5-Compression 7- Election Spring Screw
* Temperature rating is indicated on deflector or adjacent to orifice seat on frame. **Pipe thread connections per ISO 7/1 can be provided on special request.
FIGURE 2
5.6 K-FACTOR QUICK RESPONSE
SERIES TY-FRB VERTICAL SIDEWALL (TY3431) SPRINKLERS
TFPI7G
Page 5 of 6
- 5/8±1/4"
(15,9±6,4 mm)
MOUNTING FACE OF
SURFACE _ SPRINKLER
FITTING
CLOSURE
2-7/8" DIA.
(73,0 mm) SERIES
TY-FRB 2-1/4" DIA.
m (57,2m)
MOUNTING PLATE
(3,2 mm)
I 1-1/4"(31,8mm)
. 314"(19,1 mm)
314'(19,1 mm) 1/4" (6,4 mm)
FIGURE 3 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON
1/2±1/8"
I (12,7±3,2 mm)
MOUNTING I I FACE OF
SURFACE SPRINKLER - 1 FITTING
CLOSURE
2-7/8" DIA.
(73,0 mm) SERIES
TY-FRB 2-1/4"DIA.
(57,2 mm)
MOUNTING
PLATE
(3,2 mm)
1-1/4'(31,8 mm) 1/2"(12,7mm) 1' (25,4 mm) 1/4'(6,4 mm)
FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRI
N
K
L
E
R
WITH 7W0-PIECE 1,2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
WRENCH RECESS
(END 'A" USED FOR
1/2 NPT MODELS)
FIGURE 5
W-TYPE 6 SPRINKLER WRENCH
WRENCH
RECESS
V
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 6
W-TYPE 7 RECESSED
SPRINKLER WRENCH
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR IMPLIED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
RATING
135 1 135017/570C
155 155F/68"C
175 175F/79"C
86 F
uj 200°F193°C
286°F/141°C
Page 6 of 6
TFPI76
P/N 57-XXX-X-XXX
I SPRINKLER MODEL/SIN I. 378 HORIZONTAL SIDEWALL TV3331 1 NATURAL BRASS
375 VERTICAL SIDEWALL TY3431 4 WHITE POLYESTER
3 WHITE RAL9010)
9 CHROME PLATED
7 LEAD COATED
TABLE B * Eastern Hemisphere sales only. PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
Ordering
Procedure
When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TV-FRB
(specify Horizontal Sidewall or Vertical
Sidewall) Sprinkler with (specify type
of finish or coating), P/N (specify from
Table B).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2" (15 mm) Style 10
Chrome Plated.........P/N 56-701-9-010
1/2" (15 mm)
Style 10
White Color
Coated ...............P/N 56-701-4-010
1/2" (15 mm) Style 10
White RAL90I0" .......PIN 56-7013-1 1/2" (15 mm)
Style 10
Brass Plated...........P/N 56-701-2-010 1/2" (15 mm)
Style 20
Chrome Plated .........P/N 56-705-9-010 1/2" (15 mm)
Style 20
White Color
Coated ...............P/N 56-705-4-010
1/2" (15 mm)
Style 20
White RAL90I0" .......P/N 58-705-3-010 1/2" (15 mm)
Style 20
Brass Plated...........P/N 56-705-2-010
Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
'See Fire Protection
Submittal Sheet for
Pressure Rating and
l..istinglApproval Information
ttICU /Fire & Building I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
www:tyco-fire.com
Tyco Fire Products
Model BFV-1
Butterfly Valve
General
Description
The Model BFV-1 Butterfly Valve is
specifically designed to provide for ef-
ficient control of fire protection water
supplies. The Model BFV-1 is designed
to meet the increasing pressure re-
quirements of the Fire Protection In-
dustry with a maximum operating pres-
sure of 300 psi. Flow may be from
either direction, and the valves may be
positioned in any orientation. The valve
is furnished with grooved ends for use
with grooved couplings and can be
easily adapted to flanged components
utilizing Grinnell Figure 71 Class 150
flange adapters. The body and disc
construction provides for increased
strength and durability. The Model
BFV-1 Butterfly Valve is provided with
2 sets of SPDT Supervisory Switches
for use in outdoor and indoor applica-
tions. A high strength stainless steel
upper stem is provided for depend-
ability. The surfaces at the upper stem
and lower trunnion areas incorporate
a reduced dynamic torque and anti-
compression set design to ensure low
operating torque and increased seal
longevity.
This unique Tyco design feature pre-
vents elastomeric failure of the disc
encapsulation that is commonly expe-
rienced with other manufacturers. This
is accomplished by providing uniform
compression throughout the opening
and closing operation of the disc.
The Model BFV-1 Butterfly Valves are
a redesignation for the Central Figure
570, Central Figure 580 and Grinnell
Figure 580.
WARNING
The Model BFV-1 Butterfly Valve de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of this device.
The owner is responsible for maintain-
ing his fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Technical
Data
Model: BFV-1
Sizes: 2-1/2", 3", 4", 5", 6", 8" & 10"
Maximum Working Pressure:
300 psi (2068 kPa)
Factory Hydro Test: 100% at 600 psi
(4137 kPa) in accordance with test
requirements of MSS SP-67, UL, FM
and ULC
Approvals: UL, FM and ULC for both
indoor and outdoor use. Note: 8"
- 10" are FM approved only. See Fire
Protection Submittal Sheet for exact
Listing / Approval information.
Materials of 'Construction: Body: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Body Coating: Epoxy
Disc: Ductile iron conforming to ASTM
A-536, Grade 65-45-12
Disc Seal: Grade EPOM uEencapsu. lated rubber conforming to ASTM
D-2000
Upper Stem: Type 440 Stainless Steel
(2-1/2'-8") Type 17-4 Stainless Steel
(10")
Lower Plug and Stem:
Type 17-4 Stainless Steel
Operator: Gear operator with iron
housing coated with Epoxy
Bracket: Steel - Black Zinc Plated
Ordering
Information
When placing an order, indicate the full product name. Please specify the quantity,
valve model number, size, type of seal;
EPDM "E", and part number from the follow-
ing list.
Valve Valve Size Part Number 2-1/2" 59-300-F-025 59-300-F-030
59-300-F-040 S. 59-300-F-050 6" 59-300-F-060 8" 59-300-F-080 10" 59-300-F-100 Tyco Fire Products, valves, accessories and
other products are available throughout the
U.S., Canada, and internationally, through a
network of distribution centers. You may
write directly or call 215-362-0700 for the
distributor nearest you.
Care and
Maintenance
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in accordance with the applica-
ble standards of the National Fire Pro-
tection Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stalling contractor or product manufac-
turer should be contacted relative to
any questions. Any impairment must
be immediately corrected.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Page 1 of 2 JANUARY, 2005 TFPI530
Supervisory Tamp
Switch Circuits
(Valve Fully Open)
NC
NO
arm Switch Rating:
Panel 1 O 125, 250 VAC
isory I 0.25A 250 VDC
0.50A 125 VOC
End of Line Resistance Or, Next Device
NC 1K! R Voltage
HASSIS 00M NO ( tORN Source
T!ORN Auxiliary WIRINGj
DIAGRAM =1
Utilization and Connection of Auxiliary Switch to be Reviewed and Approved by the Local
Authority Having Jurisdiction
Front view with
valve Open
Side view with
valve open
Nominal Dimensions Approx.
Weight Size A B C D E F G Inches Inches Inches Inches Inches Inches Inches Inches lbs. MR? mm mm mm mm mm mm mm Kg. 21/2" 5.08 10.41 6.97 2.88 3.81 5.72 12.0 73.0 129.0 264.4 177.0 73.0 96.8 145.3 " 5.4 5.41 11.38 7.29 3.50 3.81 5.72 14.0 88.9 1 137.4 289.11 185.2 88.9 1 96.8 145.3
kuIA*
" 6.4 6.37 12.70 825 4.75 1 4.56 5.72 22.0 114.3 161.8 322.6 209.6 120.7 115.8 145.31
"A' 10.0 5 7.33 14.56 10.41 6.25 5.81 6.18 141.3 1862 369.8 264.4 158.8 147,6 157.0 N/A 31.0
14.1 6' 7.62 15.23 10.70 6.75 5.81 6.18 36.0 168.3 193.5 386.8 271.8 171.5 147.6 157.0 '"A' " 16.3 an 9.24 17.50 13.37 10.00 5.25 6.43 1.22 52.0 219.1 234.7 444.5 339.6 254.0 133.4 163.3 31.0 23.6 10' 11.81 21.78 16.93 12.00 625 7.96 1.75 75.0 273.0 299.9 553.2 430.0 304.3 158.8 2022 44.5 34.1
Friction
Resistance
Size
Equiv.
Length
in Feet
2W 6'
3' 7'
6'
10'
13'
8' 14'
10' 16'
Note: Friction Resistance is specified
in equivalent length of Std. weight
(C-120) steel pipe.
Page 2 of 2
TFPI53O
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Model BFV-1. Butterfly Valve
* End of disc does not extend beyond valve body.
General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure that pressure ratings and performance data is not exceeded. Always read and underst
a
n
d
t
h
e
S Installation instructions (IH-1000). Never remove any piping component or correct or modify any piping 001 deficiencies without first depressurizing and draining the system. Material and gasket sel
e
c
t
i
o
n
s
h
o
u
l
d
b
e
verified to be compatible for the specific application.
Ceflifled Company
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
NORYL, NSF Listed
Stainless Steel, 300 Series
EPDM (FDA approved)
Buna Nitrile (FDA approved)
NORYL, NSF Listed
Stainless steel, braided hose
QF
C D
Fasteners & Springs
Elastomers
Polymers
Sensing line
MODEL
375ADA
MODEL
375ADAG
[e]
FEATURES
Sizes: 0 4" 0 6" 0 8"
Maximum working water pressure 175 PSI Maximum working water temperature 140°F
Hydrostatic test pressure 350 PSI End connections (Grooved for steel pipe) AWWA C606
(Flanged) ANSI B16.1
OPTIONS (Suffixes can be combined) Class 125
O - with flanged end OS & Y gate valves (standard)
O L - less shut-off valves (grooved body connections)
0 LM - less water meter
O - with remote reading meter
O - with gpm meter (standard)
O - with cu ft1min meter
O G - with grooved end OS&Ygate valves
O FG - with flanged inlet gate connection and grooved
outlet gate connection
O MS - with Integral Relief Valve Monitor Switch
OBGVIC - with grooved end butterfly valves (See document
#BF-375ADABGVlCfordimensions and approval
status)
ACCESSORIES
O Air gap (Model AG)
O Repair kit (rubber only)
O Thermal expansion tank (Model WXTP)
O OS & Y Gate valve tamper switch (OSY-40)
O QT-SET Quick Test Fitting Set
DlMENSlONS& WEIGHTS (do not include
MODEL wmiour I WITH os&y WITH os&v SIZE I GATES GATES (G)) I GATES (G)G)
in. I mm I lbs. kg lbs. kg lbs. kg 4 100 98 45 252 114 226 103
6 150 151 69 387 176 357 162
MODE. B LESS E E S2E A GATE D OS&Y OS&Y VALVES OPEN CLOSED
UBMI I IAL SHEET
APPLICATION
Designed for installation on potable water lines in fire pro-
tection systems to protect against both backsiphonage and
backpressure of contaminated water into the potable wa-
ter supply. The Model 375A0A shall provide protection where
a potential health hazard exists. Incorporates metered by-
pass to detect leaks and unauthorized water use.
STANDARDS COMPLIANCE
(unless otherwise noted, applies to sizes 4" thru 8")
ASS E® Listed 1047
CSA® Certified
UL® Classified (size 4" & 6")
C-UL® Classified (size 4" & 6")
FM® Approved
Approved by the Foundation for Cross Connection
Control and Hydraulic Research at the University of
Southern California
MATERIALS
Main valve body Ductile Iron ASTM A 536 Grade 4
Access covers Ductile Iron ASTM A 536 Grade 4
Coatings FDA Approved fusion epoxy finish
Internals Stainless steel, 300 Series
i. Inini in. I mm I in. in. Imml in. Inril E. l,yrnl. in. Inmi in. Inmi i. Inmi in.
'' T- - ---- -
400 800 1200 1600
FLOW RATES (GPM)
C, 15 ci) 0.
U) ci)
9 Ui Ce
co Ui 19 -
10
1u'I 0.
C,
a) U)
9 Ui
a)
IL
FLOW CHARACTERISTICS
MODEL 375ADA 4" & 6" (STANDARD & METRIC)
FLOW RATES (Us)
25.2 50.5 75.7 101
20
15
10
5L
0
MODEL 375ADA 8" (STANDARD & METRIC)
FLOW RATES (I/s)
63.1 126.2 189.3 252.4
-
=.—
1000 2000 3000 4000
FLOW RATES (GPM)
*Rated Flow (Established by approval agencies)
TYPICAL INSTALLATION
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturer's instruc-
tions and the latest edition of the Uniform Plumbing Code.
Unless otherwise specified, the assembly shall be mounted
at a minimum of 12" (305mm) and a maximum of 30"
(762mm) above adequate drains with sufficient side clear-
ance for testing and maintenance. The installation shall be
made so that no part of the unit can be submerged.
I PROTECTIVE
OUTDOOR INSTALLATION (MODEL 375ADAVIC)
SPECIFICATIONS
Capacity thru Schedule 40 Pipe (GPM)
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
2 1/2" 75 112 149 224
115 173 230 346
198 298 397 595
6" 1 450 675 1 900 1351
8" 1 780 1169 1 1559 - 2339
10" 1 1229 1843 2458 3687
DIRECTION OF FLOW c)
INDOOR INSTALLATION (MODEL 375ADAG)
The Reduced Pressure Detector Backflow Prevention Assembly shall be ASSE® Listed 1047, and sup
p
l
i
e
d
w
i
t
h
f
u
l
l
p
o
r
t
OS & V gate valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A
5
3
6
G
r
a
d
e
4
)
,
t
h
e
s
e
a
t
ring and check valve shall be NORYL,the stem shall be stainless steel (ASTM A 276) and the seat
d
i
s
c
e
l
a
s
t
o
m
e
r
s
s
h
a
l
l
be EPDM. The checks and the relief valve shall be accessible for maintenance without removing t
h
e
d
e
v
i
c
e
f
r
o
m
t
h
e
l
i
n
e
.
The Reduced Pressure Detector Backflow Prevention Assembly shall be a WILKINS Model 375ADA
.
Page 2 of 2
WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) Website: http://www.zum.com
(E)POTTER
The Symbol of Protection
U.S. Pat. No. 3921989
Canadian Pat. No. 1009680
Other Patents Pending
Potter Electric, Rd., 1990
GENERAL INFORMATION
The Model VSR-F is a vane type waterflow switch for use on
wet sprinkler systems. It is UL Listed and FM Approved for
use on steel pipe; schedules 10 through 40, sizes 2" thru 8"
(50mm thru 200mm).
LPC approved sizes are 2" thru 8" (50mm thru 200mm).
The unit may also be used as a sectional waterfiow detector
on large systems.
The unit contains two single pole, double throw, snap action
switches and an adjustable, instantly recycling pneumatic re-
tard. The switches are actuated when a flow of 10 gallons per
minute (38 LPM) or more occurs downstream of the device.
The flow condition must exist for a period of time necessary to
overcome the selected retard period.
ENCLOSURE: The unit is enclosed in a general purpose, die-
cast housing. The cover is held in place with two tamper resis-
tant screws which require a special key for removal. A field in-
stallable cover tamper switch is available as an option which
may be used to indicate unauthorized removal of the cover. See
bulletin no. 5400775 for installation instructions of this switch.
VSR-F
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
UL,ULCandCSFMUsted,FMandLPCBApproved,NYMEA
Accepted, CE Marked
Service Pressure: Up to 450 PSI (31 BAR)
Minimum Flow Rate forAlarm: IOGPM (38 LPM)
Maximum Surge: 18 FPS (5,5 m/s)
ContactRatings: Two sets of SPDT (Form C)
15.0 Amps at 1251250VAC
2.0 Amps at 30VDC Resistive
Conduit Entrances: Two knockouts provided for 1/2" conduit
Environmental Specifications:
Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
NEMA 4/I P54 Rated Enclosure - use with appropriate
conduit fitting.
Temperature Range: 40°F/1200F, 4,50C1490C Non-corrosive sleeve factory installed in saddle.
Caution: This device is not intended for applications in explosive
environments.
Sizes Available: SteelPipe schedules 10 thru 40, sizes 2"thru 8"
BS 1387 pipe 50mm thru 200mm
Note: For copper or plastic pipe use Model VSR-CF.
Service Use:
Automatic Sprinkler NFPA-1 3 One or two family dwelling NFPA-1 3D Residential occupancy up to four stories NFPA-1 3R
National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, Stock No. 0090018
INSTALLATION: See Fig.2
These devices may be mounted on horizontal or vertical pipe.
On horizontal pipe they should be installed on the top side of the
pipe where they will be accessible. The units should not be in-
stalled within 6" (15cm) of a fitting which changes the direction of
the waterfiow or within 24" (60 cm) of.a valve or drain.
Drain the system and drill a hole in the pipe using a circular saw
in a slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices
require a hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm ±2mm). All other sizes require a hole with a diameter of 2" ±1/8"
(50mm ±2mm).
Clean the inside pipe of all growth or other material for a dis-
tance equal to the pipe diameter on either side of the hole.
Roll the vane so that it may be inserted into the hole; do not bend
or crease it. Insert the vane so that the arrow on the saddle
points in the direction of the watertlow. Install the saddle strap
and tighten nuts alternately to an eventual 50 ft-lbs. (68 n-m) of
torque (see Fig. 2). The vane must not rub the inside of the pipe
or bind in any way.
Specifications subject to change without notice.
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA MKT. #8800001 - REV W PAGE 1 OF 2 MFG. #5400761 - 7/02
FIG. 4
To remove knockouts: Place
screwdriver at edge of knock-
outs, not in the center.
OW!. fi61-4
(E)POTTER
The Symbol of Protection
VSR-F
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
DO NOT LEAVE COVER OFF FOR
EXTENDED PERIOD OF TIME
FIG. I
SWITCH TERMINAL
CONNECTIONS
CLAMPING PLATE
TERMINAL
orG. 1923-5
CAUTION:
An uninsulated section of a
single conductor should not
be looped around the termi-
nal and serve as two sepa-
rate connections. The wire
must be severed, thereby
providing supervision of the
connection in the event that
the wire becomes dislodged
from under the terminal.
FlG.2
OPTIONAL TAMPER SWITCH
RETARD ADJUSTMENT:
TO CHANGE TIME TURN KNOB (EITHER DIRECTION)
FOR DESIRED TIME DELAY. USE THE MINIMUM
AMOUNT OF RETARD NECESSARY TO PREVENT FALSE ALARMS. A B SETTING IS USUALLY ADEQUATE FOR THIS. FACTORY IS SET TO 8.
TO INSTALL, DRILL HOLE AS INDICATED:
PIPE SIZE HOLE SIZE
to 2 1/2" I 1/4" +1/8" -1/16" (50mm to 65mm) (33mm ±2mm)
to 8" 2 ±1/8" (80mm to 200mm) 50mm ±2mm)
Cover Tamper
(with cover in place)
DIRECTION OF
WATERFLOW
C NO WC (*141) (9(0) COlA)
W. fullawl
DWG. 1761-30
TIGHTEN NUTS
ALTERNATELY TO AN EVENTUAL SOFI.-LBS (68 n-m) OF TORQUE
MOUNT ON PIPE 50 ARROW ON SADDLE
POINTS IN DIRECTION OF WATERFLOW
ROLL PADDLE IN
OPPOSITE DIRECTION
OF WATERFLOW
APPROX. RETARD SETTINGS (IN SECS.)
0
0
1 A
10-25
B
20-40
C
1-15-01
DIE
50-70
FIG. 3 TYPICAL ELECTRICAL CONNECTIONS NOTES:
The Model VSR-F has two switches, one can be used to
2 01 operate a central station, pro- IMLV Cfl4Cl9 aos CU MAW ir z€ FROM prietary or remote signaling
unit, while the other contact is
used to operate a local audible
__________ ____________ or visual arinunciator.
J JiJ in A condition of LPC Approval of
this product is that the electri- 1IC IC NC IC WBI*IGS WNW or 114! *11104 FOR OR ' '° cal entry must be sealed to NI MOBIl orOBICIl. nc COW AK CCAnC 0! or *1nBIi. oc exclude moisture. IC.II! . I CXV=C II "C ("-2
For supervised circuits see "Switch Terminal Connec-
tions" drawing and caution
note (Fig. 1).
APPLICATION WARNING I
Due to the possibility of unintended discharges caused by pressure surges, trapped air, or sho
r
t
r
e
t
a
r
d
t
i
m
e
s
,
w
a
t
e
r
f
i
o
w
s
w
i
t
c
h
e
s
that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device
t
o
d
i
s
c
h
a
r
g
e
A
F
F
F
,
d
e
l
u
g
e
,
o
r
chemical suppression systems.
TESTING
The frequency of inspection and testing for the model VSR-F and its associated protective monitori
n
g
s
y
s
t
e
m
s
h
o
u
l
d
b
e
in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector's test valve, that is usually located at the end of the most remote branch l
i
n
e
,
s
h
o
u
l
d
a
l
w
a
y
s
b
e
u
s
e
d
f
o
r
test purposes. If there are no provisions for testing the operation of the flow detection device on the sy
s
t
e
m
,
a
p
p
l
i
c
a
t
i
o
n
o
f
t
h
e
VSR-F is not recommended or advisable.
A minimum flow of 10 gpm (38 Lpm) is required to activate this device.
IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system
t
h
a
t
t
h
i
s
s
y
s
t
e
m
m
u
s
t
b
e
tested in accordance with the testing instructions.
PRINTED IN USA MKr. #8800001 -REV W PAGE 2 OF 2 MFG. #5400761 - 7/02
I
6" BELL SHOWN
Notes:
Minimum dB ratings are calculated from integrated sound pressure measurements m
a
d
e
a
t
U
n
d
e
r
w
r
i
t
e
r
s
L
a
b
o
r
a
t
o
r
i
e
s
a
s
specified in UL Standard 464. UL temperature range is -30° to 150°F (-340 to 660C). Typical dB ratings are calculated from measurements made with a conventional sound
l
e
v
e
l
m
e
t
e
r
a
n
d
a
r
e
i
n
d
i
c
a
t
i
v
e
o
f
output levels in an actual installation.
SUE
INCHES
(mm)
VOLTAGE MODEL NO. STOCK NO. CURRENT
(MAX.)
TYPICAL dB
AT 10 FT.
(3m)(2)
MINIMUM dB
AT 10 FT.
(3m)(1)
8(180) 12VDC P8D126 1708012 .12A 85 76
8(200) 12VOC P00128 1108012 .12A 90 16
10(250) 12VOC PBD1210 1710012 .12A 92 76
6(150) 24V0C P00246 1706024 .06* 87 76
8 (200) 24VDC P8D248 1708024 .06* 91 79
10(250) 24V0C P802410 1710024 .06* 94 79
$ (150) 24VAC P8A246 1808024 - .17* 91 76
8(200) 24VAC PBA248 1808024 .17A 94 76
10(250) 24VAC P8A2410 1810024 .17A 94 76
6(150) 120VAC P0*1206 1806120 .05* 92 82
8(200) 12OVAC P0*1208 1808120 - .05* 99 82
10(250)_- 120VAC P8A12010 1810120 .05* .99 85
BELLS (E)POTTER PBA-AC & PBD-DC
The Symbol of Protection
UL Listed, FM Approved
Sizes Available: 6" (150mm), 8" (200mm) and 10" (250mm)
Voltages Available: 24VAC
120VAC
12VDC (10.2 to 15.6) Polarized
24VDC (20.4 to 31.2) Polarized
Service Use: Fire Alarm
General Signaling
BurgiarAlarm
Environment: Indoor or outdoor use (See Note 1)
-40° to 150°F (-40° to 66°C)
(Outdoor use requires weatherproof
backbox.)
Termination: 4 No. 18 AWG stranded wires
Finish: Red powder coating
Optional: Model BBK-1 weatherproof backbox
These vibrating type bells are designed for use as fire, burglar or general signaling devic
e
s
.
T
h
e
y
h
a
v
e
l
o
w
p
o
w
e
r
c
o
n
-
sumption and high decibel ratings. The unit mounts on a standard 4" (101 mm) square el
e
c
t
r
i
c
a
l
b
o
x
f
o
r
i
n
d
o
o
r
u
s
e
o
r
o
n
a model BBK-1 weatherproof backbox for outdoor applications. Weatherproof backbox mo
d
e
l
B
B
K
-
1
,
S
t
o
c
k
N
o
.
1500001.
ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION:
Potter Electric Signal Company' 2081 Craig Road, St. Louis, MO, 63146-4161
• Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA MKT. #8850001- REV Q - PAGE 1 OF 2 MFG. #5400776 -12101
FIG. I BELLS
2 11/16
(68) ORG. 1776-I
FIG. 2 WEATHERPROOF BACKBOX
BOXHASONEThREADED 1/2"CONDUITENTRANCE
ORG. p776-2
LP3 3/8
(86)
4 1/4
(108)
L r
(250)
BELLS -
®POTTER
The Symbol of Protection
DIMENSIONS
INCHES (mm)
FIG. 3 WIRING (REAR VIEW)
D.C. BELLS (OBSERVE POLARITY) A.C. BELLS
RED (Ia.RM (OUT) WHITE (IN) WHITE (OUT)
FROM CONTROL PANEL TO NEXT BEIj. FROM CONTROL PANEL OR OR END-W-4ME OR PRECEDING ecu.RESISTOR PRECEDING SELL
8LACK jcic (OUT) BLACK ON) BLACK (OUT)
WHEN ELECTRICAL SUPERVISKIN IS REQUIRED USE IN AND OUT EUCS AS SHORN,
NOTES:
OBSERVE POLARITY TO RING D.C. BELLS. RED WIRES POSITIVE (+)
BLACK WIRES NEGATIVE (-)
WHEN ELECTRICAl. SUNERAISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN.
NOTES:
I. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL
2. END-OF-UNE RESISTOR IS NOT REQUIRED ON A.C. BELLS.
DWG. #776-3
INSTALLATION
The bell should be mounted a minimum of 8 ft. (2,4m) from the floor or as close to the ceiling a
s
p
o
s
s
i
b
l
e
.
Removethegong.
Connect wiring (see Fig. 3).
Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing d
o
w
n
)
.
Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in th
e
h
o
l
e
i
n
t
h
e
g
o
n
g
)
.
Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority having jurisdiction).
PRINTED IN USA MKT. #8850001 -REV Q PAGE 2 OF 2 MFG. #5400776-12/01
SchedulemlO"/Schedule
w40" Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-1O/Schedule-40 sprinkler pipe you g
e
t
a
U
L
l
i
s
t
e
d
a
n
d
F
M
a
p
p
r
o
v
e
d
p
r
o
d
u
c
t
.
A
l
t
h
o
u
g
h
t
h
e
s
e
products do not require separate approvals, Schedule-10/Schedule
-
4
0
g
i
v
e
s
y
o
u
t
h
e
e
x
t
r
a
q
u
a
l
i
t
y
a
s
s
u
r
a
n
c
e
y
o
u
d
e
m
a
n
d
.
Our Sch-10 (l"- 8") pipe and Sch40 (1"- 2l4) pipe have passed the same thorough lab testing as our other liste
d
p
i
p
e
products, and receive periodic mill inspections from both UL and
F
M
a
g
e
n
t
s
t
o
e
n
s
u
r
e
c
o
n
s
i
s
t
e
n
t
q
u
a
l
i
t
y
.
E0I.1TEtT1r.ii.
NPS Nominal I.D. WI. WI. (H20 Filled) Pal WVLift (21') WVUft (24') Wt&lft (25' In; mm In; mm Lbs/Ft; Kg/rn Lbs/fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg 1.049 1.680 2.05 70 2,470 2,822 2,940 25 26.6 2.5 3.05 70 1,120 1,280 1,334 1114, 1.380 2.270 2.93 51 2,431 2,778 2,894 32 35.1 4.36 4.36 51 1,103 1,260 1,313 1W 1.610 2.720 3.61 44 2,513 2,872 2,992 40 40.9 4.0 5.37 44 1,140 1,303 1,357 2.067 3.650 5.13 30 2,300 2,628 2,738 50 52.5 5.4 763 30 1,043 1,192 1,242 2W 2.469 5.790 7.86 19 2,310 2,640 2,750 65 62.7 8.6 11.73 19 1,048 1,197 1,247
Sch-10I.1TT
NPS Nominal I.D. WI. M. (1120 Filled) Pcsf Wlllift (21') WtIUft (24') Will: (25' In; mm In; mm LbslFt; Kg/rn LbslFt; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg 11 1.097 1.400 1.81 91 2,675 3,053 3,185 25 27.9 2.1 2.70 91 1,213 1,385 1,445 1W 1.442 1.810 2.52 61 2,319 2,664 2,760 32 36.6 2.7 3.75 61 1,052 1,208 1,252 1W 1.682 2.080 3.04 61 2,664 3,045 3,172 40 42.7 3.1 4.52 61 1,208 1,381 1,439 2.157 2.640 4.22 37 2,051 2,344 2,442 50 54.8 3.9 6.28 37 930 1,063 1,108 2W 2.635 3.530 5.89 30 2,224 2,542 2,648 65 66.9 5.3 8.77 30 1,009 1,153 1,201 3.260 4.330 7.94 19 1,728 1,975 2,057 80 82.8 6.4 11.82 19 784 896 933 4 4.260 5.610 11.78 19 2,238 2,558 2,665 90 108.2 8.3 17.53 19 1,015 1,160 1,209 5.295 7.77 17.33 10 1,632 1,865 1,943 125 134.5 11.56 25.80 10 740 846 881 6.357 9.290 23.03 10 1,951 2,230 2,322 150 161.5 13.8 34.27 10 885 1,012 1,053 8' 8.249 16.490 40.15 7 2,424 2,770 2,885 200 2095. 24.5 59.75 7 1,100 1,256 1,309
Schedule-I0/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications ofASTM A-123.
Superior Coating
Our advanced formula mill coating of-
fers a clean, durable surface. It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF". In scientific laboratory
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
American IMade T[
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
Schedule-10/Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
Welded Outlets
Hydrostatic Pressure
Side Wall Rupture
Vibration Test
tilCo/Flow Control allied
TUBE & CONDUIT
Listed Approved Listed
16100 S. Lathrop. Harvey, IL 60426 Customer Service: 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543 2525 N. 27th Ave. • Phoenix, AZ 85009 Fax 708439.1806
tt,cI3 re & Building.
.1 Products :
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
www.tyco-fire.com
Grinnell Grooved Fire Protection Products
Grooved Fittin
g
s
General
Description
See Fire U' Td] t°O' Pressure Rating and
Listing/Approval YL L Information
The grooved fittings provide an economical
and efficient method of changing direction,
adding an outlet, reducing, or capping
grooved piping systems. Grooved fittings
are available in durable ductile iron or
fabricated steel as indicated.
Note: Figure 510S and 519S fillings are
special short radius fittings with smaller
center to end dimensions than standard
grooved fittings. Depending on the size and
coupling used, there may be interferences at
the bolt pads that require repositioning of the
coupling orientation. The use of flange
adapters is not recommended with Figures
510S and 5193 fittings. Contact Tyco Fire
Products for details.
WARNING
The Fittings described herein must be installed
andniaintainedlncompIiancewithtbisdocumen
as well as with the applicable standards of the
National Fire Protection Association, in addition
to the standards of any other authorities having
jurisdiction. Failure to do so may Impair the
performance of this device.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The instilling contractor or
sprinkler manufacturershould be contacted with any questions.
Technical
Data
Approvals:
UL, FM, ULC, VdS, and LPCB; Note: See Fire Protection Submittal Sheet for
exact Listing I Approval information.
Material:
Cast: FIgures: 201, 210,219,250,260,501,510,
519, 51 ODE. 501S, 510S and 519S - Ductile iron conforming to ASTM A-536, Grade 65-45-12
Fabricated Steel: Figures 391, 392, 393, 312,
313, 321, 327, 341 and 350 - Carbon Steel, (Sizes 11/4' -6' are Schedule 40);
(Sizes 8'- 12' are Schedule 30),
conforming to ASTM A-53 Grade B
Protective Coatings:
Non-lead orange paint
Fire brigade red (optional) non-lead paint
Hot dipped galvanized conforming to ASTM
A-153
Ordering
Procedure
When placing an order, indicate the full product
name. Please specifythe quantity,figure number,
wall thickness, and size.
Grinnell Grooved Piping Products, valves,
accessories and other products are available
throughouttheU.S., Canada, and internationally,
through a network of distribution centers. You may write directly or call 215-362-0700 for the distributor nearest you.
Care and
Maintenance
The owner is responsible for the inspection,
testing, and maintenance of their fire protection
system and devices in accordance with the
applicable standards of the National Are Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractororproductmanulacturer
should be contacted relative to any questions.
Any impairment must be immediately corrected.
It is recommended that automatic sprinkler
systems be inspected, tested, and maintained by
a qualified Inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10)
years against defects in material and workmanship
when paid forand property installed and maintained
under normal use and service. This warranty will
expire ten (10) years from date of shipment byTyco
Fire Products. No warranty is given for products or components manufactured by companies not
affiliated byownershipwtthlyco Fire Products orfor
productsand components which have been subject
tomisuse,improperinstallation,corrosion,orwhich
have not been installed, maintained, modified or
repaired in accordance with applicable Standards of
the National Fire Protection Association (NFPA),
andlorthestandanisofanyotherAuthorities Having
Jurisdiction. Materials found bylyco Are Products
to be defective shall be eitherrepaired or replaced, at
Tyco Fire Products' sole option. Tyco Fire Products
neither assumes, nor authorizes any person to
assumeforit, anyotherobligation in connection with
the sale of products or parts of products. Tyco Fire
Productsshatnotberesponsibleforsprinldersystem
designerTorsorinaccurBteorincompleteinformation
supplied by Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL THEORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR
CONSEQUENTIALDAMAGES,INCUJDINGBUTNOT
LIMITED TO LABOR CHARGESi REGARDLESS OF WHETHER1YCOFIREPRODUC1SWASINFORMED
ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENTSHALL1YCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE.
)7IEFIYIEGOING WARRJNTf IS Mr1DE LV lIEU OF
U1L
Page 1 of 6 September 2004 TFPI8IO
Figure 210
Figure 260
Figure 219
Friction Resistance*
(Expressed as Equivalent Straight Pipe)
Elbow The 900 450 Branch Run Size
Feet Feet Feet Feet Inches
MM Meters Meters Meters Meters 1¼ 1.9 1.0 4.8 1.9 42.4 0.6 0.3 1.5 0.6 1Y2 2.3 1.2 5.8 2.3 48.3 1 0.7 0.4 1 1.8 0.7 2 3.2 1.6 8.0 32 60.3 1.0 0.5 2.5 1.0 2V2 3.9 2.0 9.8 3.9 73.0 1.2 0.6 3.0 1.2
76.1mm 4.1 2.1 10.3 4.1 1.2 0.6 3.1 1.2 3 4.9 2.4 12.2 4.9 88.9 1.5 0.7 3.7 1.5
108.0mm 6.5 3.3 16.3 6.5 2.0 1.0 5.0 2.0 4 6.5 3.3 16.3 6.5 114.3 2.0 1.0 5.0 2.0
133.0mm 8.0 4.0 20.0 8.0 2.4 1.2 6.1 2.4 8.0 4.1 20.0 8.0 139.7..l 2.4 1.3 6.1 2.4 5 8.2 4.1 20.5 8.2- 141.3 2.5 1.3 6.3 2.5
159.OMM 9.5 4.8 23. 9.5 2.9 1.4 7.2 2.9
165.1 mm 9.5 4.8 T --T5- 2.9 1.4 7.2 2.9 6 9.9 5.0 24.8 9.9 168.3 3.0 1.5 1 7.6 3.0
216.3mm 13.1 6.6 32.8 13.1 4.0 2.0 10.0 4.0 8 13.1 6.6 32.8 13.1 219.1 4.0 2.0 10.0 4.0 10 16.5 8.3 41.3 16.5 273.0 5.0 2.5 12.6 5.0 12 19.9
1 9.9 49.7
1 19.9 323.4 6.1 3.0 15.1 6.1
Figure 201 Figure 210 Figure 219 Figure 2601 45° Elbow 90° Elbow Tee End Cap APPX. Wt. 1T Appx. Wt. Appx. Wt. Wt. Nominal Inches Lbs. Inches Lbs. InchesLbs.Size Inches Lbs. rpx.
mm Kg. mm Kg. mm Kg. mmKg. T7 0.9 17 1.0 i7 1.4 W. 0.4 44.5 0.4 69.9 0.5 69.9 0.6 22.4 0.2 V/a" 1.75 1.1 1.2 1.8 1W 0.6 44.5 0.5 69.9 0.5 69.9 0.8 22.4 0.3 2 • T 1.8 r 2.0 2.7 äW 0.9 50.8 0.8 82.6 0.9 82.6 12 22.4 0.4 2'I2" 2.2 äYr 3.0 5.8 -:a - 0.9 57.2 1.0 95.3 1.4 95.3 2.6 22.4 0.4 2.2 3.0 5.8 -u:- 1.1 76.1mm 57.2 1.0 95.3 1.4 95.3 2.6 23.9 0.5 • 3.5 4.5 7.0 ä i.i 63.5 1.6 108.0 2.0 108.0 3.2 22.4 0.5 108.0mm 2.88 5.5 8.5 11.5 - 730 2.5 120.7 3.9 120.7 5.2 - - • 5 5.2 8.5 11.8 T 2.6 76.2 2.4 1 127.0 3.9 127.0 5.4 25.4 1.2 3.25 7.7 5.25 11.3 5.25 10.6 - 1.0mm 82.6 3.5 133.4 5.1 133.4 4.8 - - 7.7 11.3 15.3 4.7 139.7mm
______ 82.6 3.5 139.7 1 5.1 139.7 69 23.4 2.1 • 8.5 5 13.5 17.0 1 - 5.0 82.6 3.9 139.7 6.1 139.7 7.7 25.4 2.3 159.0mm 3.50 12.0 6.00 14.6 6Z 13.9 - 88.9 5.4 152.4 6.6 152.4 6.3 - - 3,50 12.0 6.50 18.5 5 26.0 1.00 7.5 165.1mm 88.9 5.4 165.1 8.4 165.1 11.8 25.4 3.4 -: 12.0 18.5 26.0 1.00 7.5 88.9 5.4 165.1 8.4 165.1 11.8 25.4 3.4 4.25 23.0 r 36.5 45.0 - 216.3mm 108.0 10.4 196.9 16.6 196.9 20.4 - - 8. T 23.0 36.5 45.0 1.19 12.8 108.0 10.4 196.9 16.6 196.9 20.4 30.2 5.8 T 31.0 60.0 W 72.1 1.25 20.0 10 120.7 14.1 228.6 272 228.6 1 32.7 31.8 9.1 [_
5.25 40.0 15 67.0 15 92.5 1.25 36.o 12, 2 1334 18.1 254.0 30.4 254.0 42.0 31.8 16.3 Available with tapped plugs, contact Tyco Fire & Building Products.
'o F2
Figure 201
Page 2 of 6
TFP1810 Figures 201,210, 219, and 260
For reducing tees and branches, use the value that is corresponding
to the branch alse Example: for 8' x 8" x 2" tee, the blanch value 2. Is 8.0 feet Friction resistance for all elbows and tees except Figures 5108 and 5i9S.
No Figure 51IS and 5195f1t jsarsspsclal itaitradlus tngswithsm Ii roenterto end dimensions than standard grooved flwngs. Depending on the size and coupling used, there may
be Intertemnces itO,r bolt pads which requires repositioning of the coupling orientation. The use of
l
h
a
n
g
e
a
d
a
p
t
e
r
s
I
s
not recommended with Figures 510$ and 519$ fittings. Contact Tyco Fire Products for dahlia.
Figure 501S Figure 510S Figure 5198 450 Elbow 900 Elbow Tee Nominal C to E Appx Wt. C to E Appx. Wt. C to E Appx. Wt.
size Inches Lbs. Inches Lbs. Inches Lbs. mm Kg. mm Kg. mm Kg. 2 • 1.8 1.5 2.75 2.1 50.8 0.8 69.9 0.7 69.9 1.0 2'!? 2.25 2.2 50 2.2 7 3.0 57.2 1.0 76.2 1.0 76.2 1.4 76 1 225 "°' 22 -:or 2.3 3.1 572 1.0 76.2 1.0 1.4 • 3.0 4.1 ' 63.5 1.6 85.9 1.3
t4.00
1.9 • 52 :o 5.6 7.7 76.2 2.4 101.6 2.6 3.5 1397 3.25 7.7 r 8.6 . 12.0 82.6 3.5 124.0 3.9 124.0 5.4 325 8.5 -r 8.8 4.88 12.0 82.6 3.9 124.0 3.9 124.0 5.4 165.1mm Tö 12.0 5.50 11.00 5.50 15.0 88.9 5.4 139.7 5.0 139.7 6.8 6 • 12.0 ö 11.2 5.50 152 88.9 5.4 139.7 5.1 139.7 6.9 8 • 23.0 iW 23.4 312 108.0 10.4 1748 10.6 1748 14.2
Page 3 of 6
TFP1S1O Figures 501,510,519 and 51 ODE
.- CtoE
Figure 510
!C to E_.j
AE
Figure 519
1ff'T'TL
'toE
Figure 51 ODE
Figure 501
Figure 501 Figure 510 Figure 519 1 Figure 51ODE 450 Elbow 90° Elbow Tee 90° Drain Elbow Nominal C to Appx. Wt. C to E Appx. Wt. Appx. Wt. C to E A B 1LppL Wt size Inches Lbs. Inches Lbs. Inches Lbs. Inches Inches Inches Lbs. mm Kg. mm Kg. mm Kg. mm mm mm Kg. • 11/44.5 4, 1.75 0.9 2.75 1.0 2.75 1.4 0.4 69.9 0.5 69.9 0.6 - - - 1 h 1.75 1.1 2.75 1.2 2.75 1.8 44.5 0.5 69.9 0.5 69.9 0.8
• 2.00 1.8 3.25 2.0 3.25 2.7 50.8 0.8 82.6 0.9 82.6 1.2 - - • 2,2 2.25 2.2 3.75 3.0 3.75 5.8 3.75 2.00 2.75 2.7 57.2 1.0 95.3 1.4 95.3 2.6 95.3 50.8 69.9 1.2 ,. .s r -r 7.0 4.25 2.34 3.7 63.5 1.6 108.0 2.0 108.0 3.2 108.0 59.4 69.9 1.7 • 3.00 5.2 5.00 8.5 5.00 11.8 5.00 2.85 2.75 7.0 ' 76.2 2.4 127.0 3.9 127.0 5.4 127.0 72.4 69.9 3.2 • 8.5 &r 13.5 17.0 & U T7 13.0 82.6 3.9 139.7 6.1 139.7 7.7 139.7 85.9 69.9 5.9 T5 12.0 55 18.5 T5 26.0 W -: 13.4 88.9 5.4 165.1 8.4 165.1 11.8 165.1 99.6 69.9 6.1 80 23.0 7 36.5 7 45.0 77 2.75 26.3 108.0 10.4 196.9 16.6 196.9 20.4 196.9 125.7 69.9 11.9
Figures 501S9 510S and 519S
CE J!,NDE
Figure 501S Figure 510S° Figure 519S°
Friction Resistance 501S, 5108 & 519S (Expressed as Egulvale,t Straight Pipe)
Elbow The Size .900 45* Brmanch Ru Feet Feet Feet Feet Inches
MITI Meters Meters Meters Meters 2 3.2 1.6 8.0 32 60.3 1.0 0.5 2.5 1.0 2Y2 3.9 2.0 W 3.9 73.0 1.2 0.6 1 3.0 1.2 76.1.. -- -- r 4.1 12 0.6 3.1 1.2 3 4.9 2.4 12.2 4.9 88.9 1.5 0.7 3.7 1.5 4 6.5 3.3 16.3 6.5 114.3 2.0 1.0 5.0 2.0 19 7
°°°
8.0 4.1 20.0 8.0 2.4 1.3 1 6.1 2.4 5 ir i:T- -r --- -8.2 141.3 2.5 1.3 6.3 2.5 9.5 4.8 23.8 9.5 165 1
°°° 2.9 1.4 7.2 2.9 6 9.9 5.0 24.8 9.9 168.3 3.0 1.5 8 6.6
itt
219.1 4.0 2.0
Figure 250
Cast
EffB
Figure 350
Fabricated
Sizes 3" to 6"
1.-E to E-1
BE
Figure 350
Fabricated
Sizes 8" to 12"
Page 4 of 6
TFP181O Figures 250 and 350
Figures 250 and 350 Concentric Reducer
- Groove x Groove
Nominal E to E Appx. Wt. Nominal E to E Appx. Wt. Nominal E to E Appx. Wt. Size Inches Lbs. Size Inches Lbs. Size Inches Lbs. Inches mm Kg. Inches mm Kg. Inches mm Kg. 2.50 1.0 3.50 4.2 4.00 5.8 "2 X 1¼ 63.5 0.5 "139.7mm X 3 88.9 1.9 " 6 X 101.6 2.6 "2 X 1½ 2.50 63.5 1.3
0.6 "139.7mm X 3.50
88.9 4.4
2.0 8 X 2 5.00 127.0 1 12.2 5.5 "2½ x 2 2.50
63.5 1.2
0.5 1 5 X /2 3.50
88.9 4.6 2.1 8 x 2½ 5.00 127.0 12.1
5.5 2.50 1.5 3.50 4.6 5.00 12.0 "76.1mm X 1½ 63.5 0.7 5 x 2 88.9 2.1 8 x 3 127.0 5.5 .76.1,m X 2 2.50
63.5 1.6 0.8 5 x 2½ 3.50 88.9 4.5 2.0 8 x 5.00
127.0 11.9
5.4 3 x 11/4 2.50
63.5 1.3
0.6 5x3 3.50
88.9 4.4 2.0 8x5 5.00 127.0 11.3
5.1 x V/ 2.50
63.5 1.3
0.6 " x 3.50
88.9 4.5 2.0 8 x 6 5.00 127.0 10.8 - 4.9 3 X 2 2.50 63.5 1.3
0.6 "1651 X 4.00
101.6 5.5
2.5 10 X 4 6.00 152.4 21.9
10.0 "3x2½ 3.00 76.2 1.5
0.7 "165.1mmX4 4.00
101.6 6.0
2.7 10x5 6.00 152.4 21.6
9.8 "3 X 76.1mm 3.00 76.2 2.0
0.9 4.00
101.6 5.6
2.5 lOx 6 6.00 152.4 21.1
9.6 4 x 1¼ 3.00 76.2 2.2
1.0 "6 x2 4.00
101.6 6.0 2.7 10 x8 6.00
152.4 19.5
8.9 4 x 1½ 3.00
76.2 2.3
1.0 6 x 2½ 4.00 101.6 6.0 2.7 12 x 7.00 177.8 28.0
11 12.7 3.00 2.3 4.00 6.0 7.00 30.0 *4 X 2 76.2 "6 X 76.1mm 101.6 2.7 12 x 6 177.8 13.6 "4 x 2½ 3.00
762 2.3
1.0 6 x 4.00
101.6 6.0 2.7 12 x 8 7.00
177.8
28.0
12.7 "4X76.lmm 3.00
76.2 3.2 1.5 *6 x 4 4.00 101.6 5.9
2.7 12x10 7.00
177.8 33.0 15.0 X 3.00
76.2 2.6
1.2 "6 X 139.7mm 4.00
101.6 6.3
2.9 Note: Sizes matted with an astetisk ) are only available In Figure 250 Cast Sizes without an asteilaic are only available in FIgure 350 Fabricated.
U 07
Patented
P1 e Nominal Dimensions
Net O.D. Takeout Center to End Size Outlet Wt. A B C 0 Inches NPT Inches Inches Inches Inches Lbs. Inches mm mm mm mm Kg.
1/2 1.25 1.75 1.89 0.77 31.8 44.5 48.0 1 0.3 3/ 1.25 1.75 1.89 0.77 11h 1.900
48.3 31.8 44.5 48.0 0.3 1 1.37 2.00 2.02 0.88 34.8 50.8 51.3 0.4
1/2 125 1.75 1.89 0.92 31.8 44.5 48.0 0.4 3/ 1.25 1.75 1.89 0.92 2 2.375
60.3 31.8 44.5 48.0 0.4 1 1.37 2.00 2.02 1.06 34.8 50.8 51.3 0.5
1/2 1.47 1.97 1.89 1.28 37.3 50.0 48.0 0.6 3/ 1.47 1.97 1.89 1.28 2'/2 2.875
73.0 37.3 50.0 48.0
1
0.6 1 1.37 2.00 2.02 1.50
1 34.8 50.8 51.3 0.7 * ISO-i threaded outlets are available upon request
Figures 391, Figure 312 Figure 313 392 and 393 221/2" Elbow 111/4 Elbow Adapter Nipples
E to E Appx. Wt. C to E Appx. Wt. CtoE Appx. Wt. Nominal Inches Lbs. Inches Lbs. Inches Lbs. Size mm Kg. mm Kg. mm Kg. 11I4" 4.00 0.8 1.75 0.4 1.38 0.4 101.6 0.4 44.5 0.2 35.1 0.2 4.00 0.9 1.75 0.5 1.38 0.5 101.6 0.4 44.5 0.2 35.1 0.2 2• 4.00 1.2 1.88 0.6 1.38 0.6 101.6 0.5 47.8 0.3 35.1 0.3
2'I2" 4.00 1.9 2.00 0.7 1.50 1.1 101.6 1 0.9 50.8 1 0.3 38.1 0.5 • 4.00 2.5 2.25 1.4 1.50 1.2 101.6 1.1 57.2 0.6 38.1 0.5 • 6.00 5.5 2.63 2.4 1.75 2.2 152.4 2.5 66.8 1.1 44.5 1.0 • 6.00 7.4 2.88 4.1 2.00 3.3 152.4 3.4 73.2 1.9 50.8 1.5 6.00 9.5 3.13 5.6 2.00 4.6 61 152.4 4.3 79.5 2.5 50.8 2.1
8 • 6.00 14.2 3.88 11.1 2.00 8.7 152.4 6.4 98.6 5.0 50.8 3.9 8.00 27.0 4.38 14.0 2.13 9.1 203.2 12.2 11.3 6.4 54.1 4.1
12" 8.00 33.0 4.88 22.0 225 16.7 203.2 15.0 1 124.0 10.0 1 57.2 7.6
Figure
391
Figure
392.
Figure
393
Figure
312
ME
Figure
313
CtoE
Figure 327 Figure 341
Cross 150 lbs. flange Adapter
Nominal C to E Appx. Wt. E to E Appx. Wt.
Size riches Lbs. Inches Lbs. mm kg, mm kg.
1'/4• 2.75 2.0 4.00 2.8 69.6 0.9 1 101.6 1.3
1 /2• 2.75 2.2 4.00 3.2 69.9 2.0 101.6 1.5
2• 3.25 2.7 4.0 5.2 82.6 1.2 101.6 2.4 21/? 3.75 5.0 4.00 8.0 95.3 2.3 101.6 3.6 4.25 7.1 4.00 10.2 108.0 3.2 101.6 4.6 • 5.00 11.9 6.00 17.2 127.0 5.4 152.4 7.8 5. 5.50 17.1 6.00 21.4 139.7 7.8 152.4 9.7
6 • 6.50 27.5 6.00 26.0 165.1 12.5 152.4 11.8
8 • 7.75 47.0 6.00 38.4 196.9 21.3 152.4 17.4
10• 9.00 68.0 8.00 65.0 228.6 30.8 203.2 29.5
12• 10.00 107.0 8.00 91.0 254.0 48.5 203.2 41.3
LiiI •ii1
I I
EtoE
i I ; I
Figure 341
E
Figure 327
CthE
LIP
Page 5 of 6
TFPIB1O Figures 391, 392, 393; 312 and 313
Figures 327 and 341
Page 6 of 6 TFP181O
Figure 321
..- CtoE-.1
1CIOE
Figure 321
Figure 321 Reducing Tee Nominal C to E Appx. Wt. Nominal C to E Appx. Wt. Size Inches Lbs. Size Inches Lbs. Inches mm Kg. Inches mm Kg.
1½ x 1½ , 3.25
82.6
2.0
0.9 6 x 6 x 4 6.50
165.1
26.6
12.1
2x2x11h 3.25
82.6
2.7
1.2 6x6x5 6.50 165.1
27.0
12.2
21,4 x 21h x 1/4 3.75
95.3
42
1.9 8 x 8 x 2 196.9
7.75 36.2
16.4
21h x 21h x ½ 3.75
95.3
4.2 8 1.9 x 8 x 3 7.75
196.9
36.5
16.6
2½ x 2½ x 2 3.75
95.3
4.3 8 2.0 x 8 x 4 196.9
7.75 36.6
16.6
3x3x11h 4.25
108.0 5.3
2.4 8x8x5 7.75
196.9 36.8 16.7
3 x 3 x 2 4.25
108.0
5.5
2.5 8x8x6 7.75
196.9 37.0 16.8
3 x 3 x 2½ 425
108.0 5.8
2.6 lOx lOx 2 9.00 228.6
57.1
25.9
4x4x1¼ 5.00
127.0 9.8
4.4 10x10x3 9.00
228.6
57.4 26.0
4x4x1½ 5.00
127.0
9.9
4.5 10x 10x4 9.00
228.6
57.6
26.1
4x4x2 5.00
127.0
10.1
4.6 10x10x5 9.00 228.6
57.8
26.2
4x4x2½ 5.00
127.0 10.3
4.7 - 10x10x6 9.00
228.6
58.0
26.3
4x4x3 5.00
127.0
10.5
4.8 10x10x8 9.00 228.6
58.4
26.5
5x5x2 5.50 14.5 12x12x3 10.00 80.2 139.7 6.6 254.0 36.4
5x5x2½ 5.50 14.8 12x12x4 10.00 80.5 139.7 6.7 254.0 36.5
5x5x3 5.50 15.2 12x12x5 10.00 80.7 139.7 6.9 254.0 36.6
5x5x4 5.50 15.8 12x12x6 10.00 80.9 139.7 7.2 254.0 36.7
6x6x2 6.50 26.5 12x12x8 10.00 91A 165.1 11.9 254.0 41.5
6x6x2½ 6.50 26.5 12x12x10 10.00 91.8 165.1 12.0 254.0 41.6
6x6x3 6.50 26.5
165.1 1 12.0
General Notes: It is the Designers responsibility to select products suitable for the intended service and to ensure ISO that pressure ratings and perfomiance data is not exceeded. Always read and understand the installation instructions 9001 (11-1-1000). Never remove any piping component or correct or modify any piping deficiencies without first
depressurizing and draining the system. Material and gasket selection should be verified to be compatible for the
specific application. Certified Company TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
tqCa Fire & Build/hg
IlProducts
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
www.tyco-fire.com
Grinnell Grooved Fire Protection Products
Figure 707
Flexible Coupling
LY
General
Description
a90
;i See FureProtection
' Submittal Sheet for
Pressure Rating and.
Listing/Approval Information
The Figure 707 Flexible Coupling is capable of
pressures up to 500 psig (3447 kPa) depending
on pipe size and wall thickness when used in fire
protection services. It provides a dependable
method of joining pipe and is suitable for use in
a variety of applications.
Rigid Couplings are recommended for dry pipe and freezer applications.
WARNING
The Figure 70717exible Coupling described herein
must be installed and maintained in compliance
with this document, as well as with the applicable
standards of the National Fire Protection
Association, in addition to the standards of any
otherauthoritieshavingjutisdiction. Failure todo
so may impair the performance of this device.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contractor or sprinklermanufacturer should be contacted with
any questions.
Technical
Data
Figure: 707
Sizes: 1W - 12
Approvals: UL, FM, ULC, VdS, and LPCB;
See Fire Protection Submittal Sheet for exact
Listing / Approval information.
Housing: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Protective Coatings:
Non-lead orange paint
Are brigade red (optional) non-lead paint
Hot dipped galvanized conforming to ASTM
A-153
Ordering
Procedure
When placing an order, indicate the full product
name. Please specifythe quantity, figure number,
type of gasket, Grade "A" EPDMA, Prelubricated
(Grade "A" EPDMA) or Grade "E" EPDM Td-Seal,
and size.
Grinnell Grooved Piping Products, valves,
accessories and other products are available
throughout the U.S., Canada, and internationally,
through a network of distribution centers. You
may write directly or call 215-362-0700 for the
distributor nearest you.
Care and
Maintenance
The owner is responsible for the inspection, testing, and maintenance of their fire protection
system and devices in accordance with the
applicablestandards of theNationaJ Fire Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractoror product manufacturer
should be contacted relative to any questions.
Any impairment must be immediately corrected.
It is recommended that automatic sprinkler
systems be inspected, tested, and maintained by
a qualified Inspection Service.
Limited
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10)
years against defects in material and workmanship
when paid forand properly installed and maintained
under normal use and service. This warranty will
expire ten (10) years from date of shipment byTyco
Fire Products. No warranty is given for products or
components manufactured by companies not
affiliated byownershipwithlyco Are Products orfor
products and components which have been subject
to misuse, improperinstallation,corrosion,orwhich
have not been installed, maintained, modified or
repaired in accordance with applicable Standards of
the National Fire Protection Association (NFPA),
and/orthestandardsof any otherAuthodtiesHaving Jurisdiction. Materials found by Tyco Fire Products
to be defective shall be either repaired or replaced, at
Tyco Fire Products' sole option. Tyco Are Products
neither assumes, nor authorizes any person to
assumeforit,anyotherobligationinconnectionwith
the sale of products or pails of products. Tyco Fire
Productsshalinotberesponsibleforsprinklersystem
designenDrsorinaccurateorincompleteinformation
supplied by Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL THEORY, FOR
INCIDENTAL, INDIRECT, SPECIAL OR
CCNSEQUEN11ALDAMAS,INCLUDINGBLJrNOT
LIMITED TO LABOR CHARGES, REGARDLESS OF
WHEIHERTYCOFIREPRODUCTSWASINFORMED
ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENTSHALLTYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT EQUAL TO THE
SALES PRICE.
IMPLIED, INCLUDING WARRANTIES OF
MERCN4NTABILITY AND FITNESS FOR A
PAR7K1ARP(V,
Boll/Nuts: Track Head Bolts - conforming to
ASTM A-183, Zinc Plated, (Mm. Tensile =Warranty 110,000 psi/758,422 kPa)
Metric - conforming to ASTM F568M
Gasket (specify when ordering)
Grade "A" EPDMA violet color code
ambientto+150°F(+66°C)forfire protection
systems. Not recommended for hot water
systems.
Tri-seal (Grade "E"EPDM), green colorcode.
Prelubricated (Grade "A" EPDMA)
(See Data Sheet 1FP1895 for aid in selecting
proper gasket)
Page 1 of 2 July 2004 TFPI840
Page 2 of 2
TFP1S4O
Figure 707 Grooved Coupling
Pipe Max.
End Gap
Max.t
Pressure
Max.t
End Load
Nominal Dimensions Deflectiont
Bolt
Size *
Net
Wt.
O.D. A B C "Per Inches! Size Inches Inches psi Lbs. Inches Inches Inches Couplin g Foot Dia. x Lg. Lbs. MM mm kPa N mm mm mm mm/rn Kg. 1.900 0.13 500 1,418 2.97 4.63 1.81 0.79 '/2°X3" 2.5 2 48.3 3.3 3,447 6,308 754 117.6 460 -
•
65.8 M12x 76 1.1 2.375 0.13 500 2,215 3.54 5.25 1.88 , 0.63 /2" x 3" 3.0 2 60.3 3.3 3,447 9,853 899 133.4 47.8 3 - 1 52.5 M12x 76 1.4 2.875 0.13 500 3,246 4.06 5.75 1.88 0.52 '/2" x3" 3.5 2" 2 73.0 3.3 3,447 14,439 103.1 146.1 47.8 2° -2g 43.3 M12x76 16 3.000 0.13 300 2,121 4.19 5.75 1.88 0.50 3.7 76.1 76.1 3.3 2,068 9,435 106.4 146.1 47.8 2° -23 417 M12 x 76 1.7 3.500 0.13 500 4,811 4.69 6.38 1.88 0.43 /2" x3' 4.0 30 88.9 3.3 3,447 21,400 119.1 162.1 47.8 20 35.8 M12x 76 1.8 4.500 0.25 500 7,952 5.95 8.25 2.06 , 0.67 /e" x 31/" 7.0
4ff
114.3 6.4 3,447 35,372 151.1 209.6 52.3 55.8 M16x83 3.2 5.563 0.25 500 12,153 7.08 10.00 2.06 0.54 3/4" x 4W 10.5
5.
141.3 6.4 3,447 54,059 1798 254.0 52.3 2 35 45.0 M20x 121 4.8 6.500 0.25 300 9,955 8.19 11.25 2.06 2 - 12• 0.46 12.5 16 5.1 165.1 6.4 2,068 44,282 2080 285.8 523 38.3 M20 x 121 5.7 6.625 0.25 500 17,236 8.30 11.25 2.06 20 -0 1 • 0.45 W x 43/411 12.5 6" 168.3 6.4 3,447 76,670 2108 285.8 52.3 37.5 M20 x 121 57 8.625 025 500 29,213 10.68 14.00 2.47 0.35 /8" x 61/2 23.5 8" 219.1 6.4 3,447 129,946 271.3 355.6 62.7 10 -40 29.2 M22 x 165 10.7 10.750 025 500 45,381 13.06 16.44 2.63 , 028 1" X6V2" 33.0 100 273.0 6.4 3,447 201,864 331.7 417.6 66.8 1 -20 23.3 M24 x 165 150 12.750 025 500 63,838 15.39 18.84 2.63 , 023 1"x61/2" 37.0
12°
1 7 323.9 6.4 3,447 283,966 3909 478.5 66.8 19.2 M24 x 165 16.8 * Maximum available gap between pipe ends. Minimum gap = 0. t Maximum pressure and end load are total from all loads based o
n
s
t
a
n
d
a
r
d
w
e
i
g
h
t
s
t
e
e
l
p
i
p
e
.
P
r
e
s
s
u
r
e
r
a
t
i
n
g
s
a
n
d
e
n
d
l
o
a
d
s
m
a
y
differ on other pipe materials and/or wall thickness. Contact Tyco Ar
e
P
r
o
d
u
c
t
s
f
o
r
d
e
t
a
i
l
s
.
S
e
e
F
i
r
e
P
r
o
t
e
c
t
i
o
n
E
q
u
i
p
m
e
n
t
Submittal Sheet for Listing and Approval pressure ratings.
** Gold color coded metric bolt sizes are available upon request
f Max End Gap and Deflection is for cut grooved standard weight pipe.
V
a
l
u
e
s
f
o
r
r
o
l
l
g
r
o
o
v
e
d
p
i
p
e
w
i
l
l
b
e
½
t
h
a
t
o
f
c
u
t
g
r
o
o
v
e
d
.
General Notes: It is the Designers responsibility to select products s
u
i
t
a
b
l
e
f
o
r
t
h
e
i
n
t
e
n
d
e
d
s
e
r
v
i
c
e
a
n
d
t
o
e
n
s
u
r
e
ISO that pressure ratings and performance data is not exceeded. Alway
s
r
e
a
d
a
n
d
u
n
d
e
r
s
t
a
n
d
t
h
e
i
n
s
t
a
l
l
a
t
i
o
n
9001 instructions (II-1-1000). Never remove any piping component or correct
o
r
m
o
d
i
f
y
a
n
y
p
i
p
i
n
g
d
e
f
i
c
i
e
n
c
i
e
s
w
i
t
h
o
u
t
first depressurizing and draining the system. Material and gasket selecti
o
n
s
h
o
u
l
d
b
e
v
e
r
i
f
i
e
d
t
o
b
e
c
o
m
p
a
t
i
b
l
e
for the specific application.
Certified Company TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylva
n
i
a
1
9
9
4
6
Description
Submittal Sheet for
Pressure Rating and Listing/Approval Information
tqCV Fire & 8u11d1n9
IlProducts
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
www.tyco4ire.com
Grinnell Grooved Fire Protection Products
Figure 772
Rigid Coupling - Patented
t..
General
TheFIguie772 Rigid Coupling providesarigidjointby
firmly gripping along the circumference of the pipe
grooves. Rigid couplings are preferred for dry pipe and freezerappflcalions. Figure 772 Rigid Couplings
are a proven dependable method of joining pipe and are an economical alternative to welding, threading or
using flanges. 1t1s capable 0fpessuresupt0500psig
(3447 kPa) depending on pipe size and wall thickness
when used in fire protection services.
The Figure 772 Rizid Coupling described herein must be installedandmaintainedin compliance with
thiadocumentasllasit4ththeappficebleslendards
oftheNationalFireProtectionAssoc!alion,inaddition
to the standards of any other authorities having jurisdiction. Failure to do so may impair the
pesformance of this device.
The owner is responsible for maintaining their fire
protection stem and det'ices in proper operating
condition. The installing contractor or sprinkler
manufactarershouklbecontaotedvAffianyquesffon&
Technical
Data
Figure: 772
Sizes: 11/4 - 12'
Approvals: UL, FM, ULC, VdS, and LPCB;
See Fire Protection Submittal Sheet for exact listing / Approval Information.
Page 1 of 2
Housing: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Protective Coatings:
Non-lead orange paint
Fire brigade red (optional) non-lead paint
Hot dipped galvanized conforming to ASTM
A-153
ASTM A-183, Zinc Plated, (Mm. Tensile = 110,000 psi/758,422 kPa)
Metric - conforming to ASTM F568M
Gasket (specify when ordering)
Grade "A" EPDMA violet color code
ambientto+1500F(+66°C)forfireprotection
systems. Not recommended for hot water
systems.
Tri-seal (Grade 'E"EPDM), green colorcode
for use in dry pipe or freezer systems.
Prelubricated (Grade "A" EPDMA)
(See Data Sheet TFP1895 for aid in selecting
proper gasket)
Ordering
When placing an order, indicate the full product name. Please specifythe quantity,figure number,
type of gasket, Grade "A" EPUMA, Prelubricated (Grade "A" EPDMA) orGrade"E" EPDMTri-Seal,
and size.
GrinnellGroovedPipingPmducts,valves,accessories
and other products are available throughout the
U.S., Canada, and internationally, through anetwork
of distribution centers. You maywilte directly orcall
215-362-0700 for the distributor nearest you.
Care and
Maintenance
The owner is responsible for the inspection,
testing, and maintenance of their fire protection
system and devices in accordance with the
applicablestandards of theNational Fire Protection Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction.
The installing contractororproduct manufacturer
should be contacted relative to any questions.
Any impairment must be immediately corrected.
It is recommended that automatic sprinkler
systems be inspected, tested, and maintained by
a qualified Inspection Service.
Limited
UU7
Products manufactured by Tyco Am Products am
warranted solelytotheoriginal BWerterten (10) years
againstdefectsinmeterialandworinanshipwhenpaid
forandproperlyinstalledandmakitainedundernormal
useandserv. ThiswananlywIeqireten(10)yeazs
from dale of shipment by Tyco Are Products. No
warranty is given for products or components
bynlesnotaffihiatedbyownership
wthlycoRrePmdudsorforpmductsandcompOneflts
whhvebeensubjecttomisuse,irnpzoperinsfaflation,
cormsion,o beeninsfalled,makitained,
modilled or repaired in accordance with applicable
Standards of the National Am Protection Associon
PRA), and/or the standards of any other Authorities
Having Jurisdiction. Materials found by Tyco Are Products to be defective shall be either repaired or
replaced, at TO Are Products' sole option. Tyco Are
Products neither assumes, nor authorizes any person
umefurit,anytherobligationinconnectionwmth
the sale of products or parts of products. TycoRie
Products shall not be responsible forspfinlder system
design errors or inaccurate or incomplete information
supplied by Buyer or Buyer's representatives.
IN NO BIB'lT SHALL TYCO ARE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIASIUTY OR
UNDElM0MLEG&TffM,FORINCIDENTk INDIREI,SPLORCONSEQUENTIALDNtfIAGES,
INIJJDING BUTNOTUMIIEDTO LABOR cHAFGES,
REGARDLESS 0FWHEIHER1'vtORREPRODUCTS
WAS INFORMEDABOIJrThEPOSSIBIUTYOFSUCH
DAMAGES, AND IN NO RW SHALL TYCO ARE
PRODUCTS' LIABIUWEXCEE)ANAMOIJNtEQUPL
1O THE SALES PRICE
jig
Rigid Couplingsarererommendedfordrypipeand
Procedure freezer applications.
Bolt/Nuts: Track Head Bolts - conforming to M.viiIu
July 2004 i'FPlaSO
I
Page 2 of 2
TFP185O Figure 772 Grooved Coupling
Pipe Max."*
End Gap
Max.f
Pressure
Max.t
End Load
Nominal Dimensions Bolt
Size**
Net
Wt. O.D. A B C Size Inches Inches psi Lbs. Inches Inches Inches Dia x Lg. Lbs. mm mm kPa N mm mm mm 1.660 0.06 300 649 2.75 4.38 1.81 %"X2Y4" 1.0 424 1.5 2,068 2,887 699 111.3 46.0 M10x57 0.5
1½" 1.900 0.08 500 1,417 3.00 4.62 1.81 Wx21/4' 1.0 48.3 2.0 3,447 6,303 76.2 1173 46.0 M10x57 0.5
2" 2.375 0.13 500 2,214 3.41 5.12 1.88 %'X2Y4" 1.5 60.3 3.3 3,447 9,848 86.6 130.0 47.8 M10x57 0.7
21h" 2.875 0.13 500 3,244 3.91 1 5.63 1.88 %"xVAN 2.5 73.0 3.3 3,447 14,430 99.3 1 143.0 47.8 M10x57 1.1
76.1mm 3.000 0.13 300 2,120 4.19 5.72 2.00 M10x57 2.6 76.1 3.3 2,068 9,430 106.4 1453 50.8 1.2 3.500 0.13 500 4,808 4.63 6.25 1.88 %"X2Y4" 2.6 88.9 3.3 3,447 21,387 117.6 158.8 47.8 M10x57 1.2 4.500 0.19 500 7,948 5.81 750 1.97 %" x 21/4" 3.5 114.3 4.8 3,447 35,353 147.6 190.5 50.0 M10x57 1.6
139.7mm 5.500 0.19 300 7,127 7.02 9.72 2.06 M16 x 83 7.5 139.7 4.8 2,068 31,701 178.3 2469 52.3 3.4 50 5.563 0.19 300 7,288 7.09 9.71 2.04 %" x 3W 7.5 141.3 4.8 2,068 32,417 180.1 246.6 51.8 M16x83 3.4
165.1 6.500 0.19 300 9,950 8.09 10.53 2.13 M16 x 83 7.6 165.1 4.8 2,068 44,258 205.5 267.5 54.1 3.4 - 6- 6.625 0.19 400 13,782 8.09 10.53 2.13 %" x 31/40 7.6 168.3 4.8 2,758 61,302 205.5 267.5 54.1 M16x83 3.4
8" 8.625 0.19 450 26,278 10.56 13.56 2.62 3/40 x 43/40 18.0 219.1 4.8 3,103 116,885 268.2 344.4 66.5 M20 x 121 8.2
10" 10. 750 0.13 250 22,679 12.84 16.41 2.62 1" X 61/20 24.6 273.0 3.3 1,724 100,876 326.1 416.8 66.5 M24 x 165 11.2
12" 12.750
1 323-913.3
0.13 250 31,903 1 15.41 18.84 2.62 1"x61h" 42.0 1,724 141,905 391.41478-5. 66.5 M24 x 165 19.1 Maximum available gap between pipe ends. Minimum gap = 0. t Maximum pressure and end load are total from all loads based on standard weig
h
t
s
t
e
e
l
p
i
p
e
.
P
r
e
s
s
u
r
e
r
a
t
i
n
g
s
and end loads may differ on other pipe materials and/or wall thickness. Contact Tyco
F
i
r
e
P
r
o
d
u
c
t
s
f
o
r
d
e
t
a
i
l
s
.
See Fire Protection Equipment Submittal Sheet for Listing and Approval pressu
r
e
r
a
t
i
n
g
s
.
Gold color coded metric bolt sizes are available upon request.
1 Max End Gap is for cut grooved standard weight pipe. Values for roll grooved pipe wi
l
l
b
e
½
t
h
a
t
o
f
c
u
t
g
r
o
o
v
e
d
.
Figure 772 Rigid Couplings have an Anti-Rotation Feature of "gripping teeth" along the c
o
u
p
l
i
n
g
k
e
y
s
i
n
s
i
z
e
s
11/4' -4", which make the Figure 772 perfectly suited for "arm over" installations where the likelihood of rot
a
t
i
o
n
i
s
g
r
e
a
t
e
s
t
.
T
h
i
s
f
e
a
t
u
r
e
m
a
y
e
l
i
m
i
n
a
t
e
t
h
e
n
e
e
d
o
f
extra hangers to support the arm over due to increased rigidity and gripping for
c
e
s
a
v
i
n
g
t
i
m
e
a
n
d
c
o
s
t
.
General Notes: It Is the Designer's responsibility to select products suitable for t
h
e
i
n
t
e
n
d
e
d
s
e
r
v
i
c
e
a
n
d
t
o
e
n
s
u
r
e
ISO that pressure ratings and performance data is not exceeded. Always read and
u
n
d
e
r
s
t
a
n
d
t
h
e
i
n
s
t
a
l
l
a
t
i
o
n
9001 instructions (I1-1-1000). Never remove any piping component or corrector modify a
n
y
p
i
p
i
n
g
d
e
f
i
c
i
e
n
c
i
e
s
w
i
t
h
o
u
t
first depressurizing and draining the system. Material and gasket selection should be v
e
r
i
f
i
e
d
t
o
b
e
c
o
m
p
a
t
i
b
l
e
for the specific application.
Certified Company TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19
9
4
6
Printed U.S.A.
t11CG /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
BlazeMaster ®
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General
Description
Tyco Fire and Building (TFBP) Blaze-
Master CPVC Pipe and Fittings are
designed exclusively for use in wet
pipe automatic fire sprinkler systems.
They are made from a specially devel-
oped thermoplastic compound com-
posed of post chlorinated polyvinyl
chloride (CPVC) resin and state of the
art additives. TFBP BlazeMaster
CPVC products are easier to install
than traditional steel pipe systems,
and at the same time, provide superior
heat resistance and strength as com-
pared to traditional CPVC and PVC
piping materials used in the plumbing
trade. Various adapters are available
to connect CPVC pipe to metallic pip-
ing. All female pipe thread adapters
have brass inserts for durability.
Grooved adapters connect directly to
grooved end valves and metallic pipe,
with flexible grooved end couplings.
WARNING Tyco Fire & Building Products (TFBP)
BlazeMaster CPVC Pipe and Fittings
described herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, In addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Sizes
3/4" to 3"
Maximum Working Pressure
175 psi
Approvals
UL, FM, CUL, NSF, Dade County,
LPCB, MEA, and the City of Los Ange-
les. (Refer to IH-1900, Rev. 0, January
2005 installation instruction & Techni-
cal Handbook" for exact listing/ap-
proval information.)
Manufacture Source
U.S.A.
Material
Pipe: ASTM F442, SDR 13.5
Fittings: ASTM F438 (Sch. 40) and
ASTM F439 (Sch. 80), ASTM F1970
Color
Orange
BlazeMaslert is a registered trademark
of Noveon IP Holding Corp.
Paae I of 6
Page 2 of 6 TFPI9I5
NOMINAL AVERAGE AVERAGE WEIGHT FILLED WEIGHT Ft OF PIPE WEIGHT PER LIFT SIZE O.D. I.D. Ibsflt. IbsJft. PER LIFT lbs.
3/4" 1.050" 0.874" 0.18 0.44 7875 1418 1.315" 1.101' 0.26 0.67 5040 1320 1-1/4" 1.660 1.394" 0.42 1.08 2835 1191 1-1/2" 1.900" 1.598" 0.54 1.41 2205 1186 2.375" 2.003" 0.84 2.20 1260 1063 2-1/2" 2.875" 2.423" 1.26 3.26 1215 1531 3.500 2.952" 1.87 483 720 1344
FIGURE 1—PIPE DIMENSIONS
Installation
Tyco Fire and Building Products
(TFBP) BlazeMaster CPVC Pipe and
Fittings are to be installed in accord-
ance with I1-1-1900, Rev. 0, January
2005 "Installation Instruction & Techni-
cal Handbook'".
Care and
Maintenance
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stalling contractor or product manufac-
turer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
NOTES Before closing a fire protection system
control valve for inspection or mainte-
nance work on the fire. protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
tem must first be obtained from the
proper authorities and all personnel
who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central sta-
tion alarms.
TFPI9I5 Page 3of6
FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT $ CHD WEIGHT TYPE NUMBER (I/O) (lb.)
TEE 80000 3/4• FA. 40 0.11 1/0 80001 1 11/16 40 0.19 I 80002
80003
1-1/4
1-1/2
7/8
1-11W
40
80
0.26
0.51
Th
___ 80004 2 1-3/8 80 0.90 80005 2-1/2 1-9/16'80 1.59 T/O 1/0 80006 3 1-13/16 80 2.41
XxYxZ X Y Z
3141 x 3t4'x V 3/4 3/4 5/8" 80132 40 0.14 80133 1"x3/4"x3/4" 9/16" 9/16" 3/4" 40 0.14 80134 x 3/4" x 3/4" 11I16 3/4" 40 0.17 80260 1"x?x3/4" 5/8" 5/8" 13/16" 40 0.16 80135 1-1/4x1"x3/4" 5/8 5/8" 15116" 40 021 80136 1-1/4"x Vx V 3/4" 3/4" 15/16 40 0.22 80137 1-1/4"x1"x1-1/4" 15/16" 15/16" 7/8" 40 026 REDUCING TEE 80261 1-1/4" x 1-1/4" x 2/4" 5/8" 5/8" 7/8" 40 0.23 80262 1-1/4"x1-1/4xV 314• 3/4" 71W 40 026 80138 1-1/4"xl-1/4x1-112" V 1" 1" 80 0.43 1/0
80140 1.1/2"x1-1/4"x3/4" 9/16" 9/16 1" 80 0.36 80141 1-1/2"x1-1/4"x? 9/16" 9/16" 1.1/16" 80 0.38 80263
80264
1-1/2" x 1-1/2" x 3/4"
1-1/2"xl-1/2"xl"
9/16"
9116"
9/16"
9116"
1"
1-1/16"
80
80
0.36
0.38
X
Ln
VI
80275 1-lIZ" x 1.1/2" x 1-1/4" 7/8" 7/8" 1 80 0.45 T/O 80265 x 2" x 3/4" 3/4" 3/4" 1-318" 80 0.61
Page 4 of 6 TFPI9I5
FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHO. WEIGHT TYPE NUMBER (170) (lb.) 45 ELBOW 80050 3/4 318 40 0.08 80051 1 3/8 40 0.11 80052 1-114 3/4 40 0.20 80053 1.1/2 T/0,
112 80 0.31 80054 2 314 80 0.56 80055 2.1/2 13/16 80 0.89 80056 3 80 1.19
80075 3/4 1/8 40 0.07 COUPUNO & 80076 1. 118 40 0.11 REDUCING COUPLING 80077 1-1/4 3/16 40 0.12 80078 1-112 3/16 80 0.25 80079 2 3/16 80 0.38
IFT/O
80080 2-1I2 1/4 80 0.67 80081 3 3/16 80 0.91
80220 rx3/4 118 40 0.08
80200 ? x 3/4 7116 40 0.04 80201 1-114x314
. Ir2l 40 0.11 80202 1-1/,r x V 5/W 40 0.12 80203 1-1/2x34 5/8 80 0.16 80204 1-112x1 80 0.14 REDUCER BUSHING 80205 1-1/2x1-1/4 3/8 80 0.17 80206 2 x 3/4 13/16 80 0.27 80207 2"x V 11/16 80 026
TFPI9I5
Page 5of6
FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT HD WEIGHT TYPE NUMBER sO) C / (lb.)
SPRINKLER HEAD
ADAPTER
0175E 3/4 x 1PZNPT 7/16 80 0.20 0176E rx 1/2 NPT 7116 80 022
1;T/0
80175WL 3/4 x 112 NPT 7/16 40 0.16 80179 1x3/4NPT 13f16 40 0.43
SPRINKLER HEAD
ADAPTER
80175W 3/4x1I2NPT 1/2 40 0.19
q; T10
80176W 1"x 1/2 NPT 12 40 0.18
SPRINKLER HEAD
ADAPTER (SPIGOT)
80177L 3/4x1/2NPT 1/2 40 0.16 80178 V x 1/2 NPT smill 40 0.20
4-4vo
80180 1 x 3/4' NPT 7/8' 40 0.40
FEMALE ADAPTER
r 80142 3/4'x 3/4' NPT 13/16' 0.4180 40
m
M VxVNPT 7/8' 40 0.63 80146 1-1/4'x1-1/4NPT 1-1/8' 40 1.03
Page 6 of 6
TFPI 915
l 80199 3/4'xl/2'NPT 9/16' V 40 0.20 80189 1' x 1/2' PIPT 3/4' 1.1/4' 40 0.26 _____
X
T/O
80196 1'x314'NPT 1-1/16' 1-7/16' 40 0.28
FIGURE 2— F17TING DIMENSIONS (Part 4 of 4)
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
TYCO FIRE PRODUCTS. 451 North Csannnn A I-a1-fl
tLICO Flo w / Tyco Fire lControl I Products
ARE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET
TYCO ARE PRODUCTS
451 North Cannon Avenue
Lansdale, Pennsylvania 19446
www.tyco-fire.com
TECHNICAL SERVICES
TEL: (800) 381-9312 FAX: (800) 791-5500
E-i,,.. techserv@tycofp.com
..
Introduction
Tyco Fire Products (TFP) BlazeMasters CPVC pipe and
fittings are designed exclusively for use in wet pipe
automatic fire sprinkler systems. They are made from a
specially developed thermoplastic compound composed of
post chlorinated polyvinyl chloride (CPVC) resin and state of
the art additives. TFP BlazeMaster CPVC products are
easier to install than traditional steel pipe systems, and at
Technical Data
the same time, they provide superior heat resistance and
strength as compared to traditional CPVC and PVC piping
materials used in the plumbing trade. Various adapters are
available to connect CPVC pipe to metallic piping. All female
pipe thread adapters have brass inserts for durability.
Grooved adapters connect directly to grooved end valves
and metallic pipe, with flexible grooved end couplings.
Sizes: 3/411_31
Manufacture Source: U.S.A. Maximum Working Pressure: 175 psi Material: Approvals: UL, FM, CUL, NSF, Dade County, LPCBI Pipe: ASTM F442, SDR 13.5 MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and Note: See curmntTFP BlazeMaster Installation Insiniclions and ASTM F439 (Sch. 80) Technical Manual, for exact llsting(appioval infoimation Colon Orange Pipe
Nom.Plpe Size Avg. O.D. Inches Avg. I.D. Inches WI. LbsJFt. Wt. ILO filled Pipe thsjFt. R. of Pipe per Lift WL per Uft Lbs. 3/U 1.050 0.874 0.17 0.43 7875 1413 in 1.315 1.101 0.26 0.67 5040 1320 1114, 1.660 1.394 0.42 1.07 2835 1191 1720 1.900 1.598 0.55 1.40 2205 1136 21 2.375 2.003 0.86 1 2.20 1 1260 1063 21/2- 2.875 2.423 1.26 3.22 1215 1531 3" 3.500 2.952 1.87 1 4.79 720 1344 Fittings
TO 450 Elbow Reducing
900 Elbow
900 Elbow
Part No. Size Sch. T/O I Wt.
80050 3/Il 40 3/1 0.08 lb.
80051 1" 40 /e" 0.11 lb.
80052 11/411 40 3/411 0.20 lb.
80053 1 11/21 80 1 71.' 0.31 lb.
80054 2 80 3/4" 0.56 lb.
80055 2¼" 80 3/4U 0.89 lb.
80056 3" 80 1" 1.19 lb.
IPart
No. Size I lSch. I
I Tb t I.
Ilb.l Ii i I 2
180032 Ii" x/4"l 40 I 1I/U /ie" 10.161
Part No. Size Sch. TO I Wt.
80025 3/I 40 9/is" 0.09 lb.
80026 40 3/0 0.14 lb.
80027 11/4" 40 7411 0.21 lb.
80028 1W' 1 80 iVie" 0.40 lb.
80029 80 11/4" 0.79 lb.
80030 21h" 80 11/2" 1.14 lb.
1 80031 311 80 113/ie" 1.82 1b.
Tee Reducing
Cross Cross
Part No. Size Sch. T/O Wt.
80000 3/41 40 5/i" 0.11 lb.
80001 111 40
80002 1 74" 7/EU
80003
40
1¼" 80 1"
WE26
80004 80 1/e"
80005 21/2" 80 19/is" 1.59 lb.
80006 80 1"/ie" 2.41 lb.
IPart
1No.
i I Size I
I
Sch. I
I 1/0 Wt. I I llb.l 1112
180015 Ii" XI4"I 40]14- I1V1s1 10.281
Part No. Size Sch. T/O Wt.
80009 3/411 40 /Ie" 0.13 lb.
80010 10 40 /" 023 lb.
80011 1'/4" 40 l5/,U 0.34 lb.
80012 1 11/2" 80 1 1'/ie" 0.67 lb.
80013 80 1/e" 1.00 lb.
80014
1
21/2" 80 19/is" 1.91 lb.
80008 80 P3/te" 2.89 lb.
1 Tb0
Reducer - -.
Bushing
Part No. Size ISch. TIO I Wt.
80200 1' X 3/U 40 Vie" 0.04 lb.
80201 11/40 X314" 40 '/ie' 0.11 lb.
80202 11/4' x 1" 40 5/is" 0.12 lb.
80203 1'/2"X 3/4" 80 %" 0.16 lb.
80204 11/2" X 1" 80 Va" 0.14 lb.
80205 11/2" x 11/4M 80 3/s" 0.17 lb.
80206 2" x 3/" 80 3/4k 0.27 lb.
80207 2" x 1' 80 "lie" 0.26 lb.
80208 2" x 11/4" 80 C/ia" 0.24 lb.
80209 x 11/2" 80 'lie" 10.19 lb.
80215 21/2" x 1" 80 1/ie" 0.42 lb.
80214 21/2' X V/c" 80 V/i" 0.45 lb.
80213 21/2" x P/a" 80 1/." 0.46 lb.
80211 21h" x 2" 80 1/,." 0.29 lb.
80210 3"x 2'
I
80 2/ue" 0.72 lb.
80212 x 21/2" 80 1/,e 0.47 lb.
I.
Reducing -i
Tb'
Tee
TaO' TO.
iTIO
Coupling
fEF
Cap
Part No Size Sch. 1/0 WI.
80100 3/" 40she" 0.04 lb.
80101 1" 40 3/s" 0.06 lb.
80102 1114" 40 Va" 0.10 lb.
80103 11/2' 1 80 le" 0.20 lb.
80 5/s" 0.31 lb. 80104±3~'
80105 80 'I." 0.58 lb.
80106 80 Is 0.88 lb.
170
Grooved Coupling - -- Pipjo.D. Adapter
Part No. Size Sch. 1/0 WI. Pipe OD 80160 11/4" x 11/40 Grooved 40 2 /ie" 0.78 lb. 1 i/II (1.660") 80161 11/2" x Via' Grooved 80 2 '/is' 0.95 lb. We (1.900') 80162 2" x 2" Grooved 80 2 /ie" 1.42 lb. 2'(2375') 80163 2'Ia" x 2/2" Grooved 80 2 /e" 2.28 lb. 2¼" (2.875') 80164 3' x 3" Grooved 80 21/41 3.00 lb. 3" (3.500") 80168 3" x 76.1 mm Grooved 80 2¼" 2.72 lb. 76.1 mm (3.000")
Part No Size Sch. 1/0 Wt.
80075 Y-N 40 '/." 0.07 lb.
80076 In 401 Va' 0.11 lb.
80077 1114" 40 /ie' 0.12 lb.
80078 17? 80 3/is" 0.25 lb.
80079 80 /ie" 0.38 lb.
80080 21/21 80 lie" 0.67 lb.
80081 1 80 /,e" 0.91 lb.
170
Female -.-
Adapter
Part No. Size Sch. 1/0 M. 80142 3/40 x 3/" NPTM-/-NOlb.80145 x 1" NPT b.80146 114w x 11141NP lb.80147 1¼" x 1Va' NP lb.80148 x 2" NPT lb.
TO
Male
Adapter
Part No. Size I Sch. 110 I Wt. 80157 3/41 x /" NPT 40 1 1./,e" 0.33 lb. 80158 1" x In NPT 40 1 13/0 1 0.56 lb.
TIO
Reducing
Coupling t:Ld
I PadNo.1 Size ISch.1 TIO Wt.
80220 11" x3/.N 40 1 'Ia" 0.08 lb.
Part
No. Size Sch. 1/0 Wt.
lb. - 1 2 1 - 3 80132 3/4'X 3/4'x 1" 40 3.6" 6" 5/1 0.14 80133 1"X 3/4'X3/4" 40 ¼" "/ie" W 0.14 80134 1" X3 /4" x 1" 40 W W l4" 0.17 80260 1" x 1" x 3/I 40 3/4w 3/" /ie 0.16 80135 1¼" x 1" x 3/" 40 " tie 3 14 lie" 0.21 80136 V/c" xl" x 1" 40 11/1 0 3/4" '5/ie" 0.22 80137 11/41 x 1" x 11/4" 40 Wee" /a" /,e" 0.26 80261 11/4"x 11/4" x /" 40 %" /e" '/a" 0.23 80262 1114" x 11140 x 1" 40 3/" 3/" 7/U 0.26 1 80138 1'/4" x 11/4" X 11/2" 80 IN 1" Is 043 80140 11/2" x 11/4" x /" 80 1/2" shm iN 0.36 80141 11/20 X11/40 X1" 80 Va" 5/s" lYe' 0.38 80263 1¼" x 11/20 X 3/41 80 s/ia" -p ito7 1" 1 0.36 80264 11/28 X 1¼" xl" 80 -/,.a Oheo 1" 0.38 80275 11/2' x 1'/a" X 11/4" 80 7/i" 7/e1 lii 0.45 80265 1 20 x2'x314" _!_ 21 80266 2' x 2" x 1' 80 la" 'I." 1%" 0.66 802741 2" x 2" x 11/4" 80 In 1" 1/." 0.74 802671 2" x 2"x P/a" 80 lYe" V/a" 1/." 10.78 80271 21/2" x 2/2" x 1" 80 1"/te' 1"/,e"' 1°lie" 1.43 80272 21/2'x 21/2" X V/i" 80 1"/ie" 1"/ie" V/ia" 1.46 80273 21/2" X 21l? X V/a" 80 1"/te' 111/ta" 19/16" 1.48 80276 21/a" x 21/2" x 2" 80 1"/a" III/is" V/ia" 1.50 80270 3" x Tx V/a" 80 V/i" 1/4" 11 3/i." 228 80268 3" x 3" x 2" 80 1/4" 1/e" 13/4" 2.25 80269 3" x 3"x 21/2' 80 1/4" P/c" 1'/,e" 2.44
Part No. Size Sch. 110 Wt. I 80175E I4 X 1/21 NPT 80 7b.' 0.20 lb. I 80176E 1" x Va" NPT 80 7/e1 0.22 lb. f80177WL /i x 'k' NPT 40 /.' 0.16 lb. E80179 1 x NPT 40 2/4' 0.43 lb.
Sprinkler Head Adapter
(Spigot)
with Brass Threaded Insert
Part No. Size Sch. 80175W 3/4' x 'Ia" NPT
I I
40 7/1" 1 0.19 lb. 80176W 1" x 'Ia" NPT 40 1/a" 1 0.18 lb.
Back-to-Back Cross
with Brass Threaded Insert
'
TI
Sprinkler Head Adapter
with Brass Threaded Insert Et Sprinkler Head Adapter
with Brass Threaded Insert
Part No. Size Sch. TIO Wt. 80177L
I
Ia" X 1/2" NPT 40 Va" 0.16 lb. 80178 lox /2" NPT 40 1/2" 0.20 lb.
I Part
I No.1
l
Size I
I Sch. i I
I TIO Iwt.
lb.
I 0.471
1 1 1 21 I 80462 1' x 1" x 121 NPT X /2" NPT 40 /" 1 'Ia' 0.46 I_80463 1" x 1" x V2" NPT x 'ía " NPT I 40 I 5/I U 15/,
Sprinkler Head Adapter
900 Elbow
with Brass Threaded Insert Back-to-Back Tee
with Brass Threaded Insert
I Part I No. No.
1 I Size Si I
I
Sch. ch. i
I T/0 Wt.
lb. I I 1 I 2 1 I 80199 I Ia" x 1h" NPT I 40 I i' I Isheo 0.20 I I 80189 i' x 'I? NPT I 40 13/,0 1/u' 0.26 I
Part
No.
Size Sch. T/0 Wt
lb. 1 2 80459 X'Ia'NPT 0.48 80460
_1"X '/2"NPT
_1"X'/2" NPT X'/a'NPT
_40
_40
_1'/ie"
_"/e" _1'/." 0.46
Part
No. Size - Sch. 1/0 Wt.
lb. 2 3 80250 3/41x 1148 x /a NPT 40 "Ia' 5/SI 1" 0.22 80251 x1' x 'Ia' NPT 40 "1,.' /e" '/ie" 029 80249 1"x1"x1'NPT 40 'shs* '/,e' V/i." 0.73 802561 11l." x 1 X '/2"NPT 40 7," '1.' 1'I.' 0.30 80252 1I4_X _V14'X'Ia'NPT 40. 7I e' 1/el VI." 0.31 80257 11/20 x 11140 x Ile NPT 80 /t.' a,,. 1/,.' 0.43 80254 1'/a"x 1'/a"X1/NPT 80 'lie" 'lie" 11/.' 0.46 80258 x1'/a"x'/2'NPT 80 /a 'I.' 1'/,' 0.56 80253 2"X 2_X 1120 NPT 80 'Ia" 'Ia" 15I." 0.62
Sprinkler Head Adapter
Tee
with Brass Threaded Insert
I
gum
MIMI ill
limited Warranty
Products manufactured by Tyco Fire Products are
w
a
r
r
a
n
t
e
d
solely to the original Buyer for ten (10) years against defects In
material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will
expire ten (10) years from date of shipment by Tyco Fire Products. No warranty Is given for products or components manufactured
by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to
misuse. improper installation, corrosion,
or which have not been Installed, maintained, modified or repaired In accordance with
applicable Standards of the National Fire Protection Association (NFPA), and/or the standards of any other Authorities Having
Jurisdiction. Materials found by Tyco Fire Products to be defective skull be either repa
i
r
e
d
o
r
r
e
p
l
a
c
e
d
.
a
t
T
y
c
o
F
i
r
e
P
r
o
d
u
c
t
s
s
o
l
e
option. Tyco Fire Products neither assumes, nor authorizes any person to assume for It, any other obligation In connection with the
sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or
Incomplete Information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONT
R
A
C
T
,
T
O
R
T
,
S
T
R
I
C
T
L
I
A
B
I
L
I
T
Y
OR UNDER ANY OTHER LEGAL
THEORY. FOR INCIDENTAL INDIRECT. SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING B
U
T
N
O
T
LIMITED TO LABOR
CHARGES, REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO FIRE PRODUCTS LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIE
U
O
F
A
N
Y
A
N
D
A
L
L
O
T
H
E
R
W
A
R
R
A
N
T
I
E
S
E
X
P
R
E
S
S
O
R
I
M
P
L
I
E
D
, INCLUDING
WARRANTIES OF MERCHANTABILITY AND FI
T
N
E
S
S
F
O
R
A
P
A
R
T
I
C
U
L
A
R
P
U
R
P
O
S
E
.
tqcu/iow control/ Tyco Fire 7
Dimensions -Weights
Approx. A B C wt.
3/4 3'/a 2 .180 1 3/a 21!. .210 11/4 35/s 2/. .225 112 41/6 2'/2 .310
2 4'/2 2/4 .340
HAMGAFPUCATION KANGI&RESIRAINT
APPLICATION
It ;
Fig. 28
"Stand-Off" Hanger & Restrainer for CPVC Plastic Pipe
Size Range —W through 2"
Material - Carbon Steel, Pre-Galvanized
Function - Designed to be used as a hanger and restrainer for CPVC piping
where the "stand-off' design will ease installation by eliminating the need for
w
o
o
d
blocking.
Features:
Flared edge design protects CPVC pipe from any rough or abrasive surfaces.
Unique twist and lock design holds pipe firmly in place and allows retrofit type
of installation.
The "Stand-Off" design eliminates the need for wood block
extension.
Can be installed on horizontal or vertical piping regardless of mounting sur-
face orientation.
Attached easily to wood structure with two hex head self-threading screws
furnished with product.
Installs easily using rechargeable electrical driver with 5116" extension socke
t
eliminating impact tool damage to pipe.
U.L. Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals - Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to
support automatic fire sprinkler systems. Meets and exceeds the requirements
o
f
NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint requirem
e
n
t
w
h
e
r
e
needed. UL Listed as a hanger and vertical restraint when installed on 3/8"
c
o
m
p
o
s
i
t
e
wood material. Use two Fig. 27B Speed Nuts when used as a hanger and r
e
s
t
r
a
i
n
t
.
Use one Fig. 27B Speed Nut on the upper installed screw when used as a han
g
e
r
o
n
l
y
.
Order by - Figure number and pipe size.
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.
OFFICEIMANUFACTURING FACILITY • 1315 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • SM 7ffi c,
& >1
Fig. 22 - Hanger for CPVC Plastic Pipe
Single Fastener Strap Type
Size Range - 3/4" thru 2" CPVC pipe
Material - Carbon Steel, Pre-Galvanized
Function - Intended to perform as a hanger to support only CPVC piping
used in automatic fire sprinkler systems. The product acts as a hanger when
tab is upward and the fastener screw is in the horizontal position. Figure 22
can be installed on the top of a beam, but in this situation acts as a guide to
the piping which is supported by the beam itself. It is not intended to support
CPVC pipe from under a flat horizontal surface, such as a ceiling. For this
type of installation, use the TOLCOTm Fig. 23, Double Fastener Strap for
CPVC Piping. Fig. 22, when inverted, with the hanger tab downward, can
function as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals - Underwriters' Laboratories Listed in the USA (UL) and Canada
(cUL) to support fire sprinkler piping. Meets and exceeds the requirements of
NFPA 13,1311 and 13D.
Features - Fig. 22 incorporates features which protect the pipe and ease installation. The flared edge design* pro-
tects CPVC pipe from any rough surface. It is easily attached to the building structure using the
s
p
e
c
i
a
l
U
L
L
i
s
t
e
d
h
e
x
head self threading screw furnished with the product, this is the minimum size fastener acceptable. It is rec
o
m
m
e
n
d
e
d
that rechargeable electric drills fitted with a hex socket attachment to be used as installation tools. No im
p
a
c
t
t
o
o
l
s
(such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has bee
n
k
n
o
w
t
o
r
e
s
u
l
t
from installations using impact type tools. No pre-drilling of a pilot hole in wood is required.
Finish - Pre-Galvanized
Note - Fastener into light gauge metal may be ordered separately. Minimum acceptable: #10 x 1" Harde
n
e
d
S
e
l
f
Threading Screw with 5116" hex washer head.
Order By - Figure number and CPVC pipe size.
* Patent Pending
Dimensions 'Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt.I100
3/4 2/ 1/16 1 /16 5/ 5/16 9
I 2"! 17/16 1I1e 6 5/16 9
11I4 The 1°/s 13/I0 61h 5/16 11
1/2 31I 13/4 13/16 7 5/16 12
2 35/4 2V5 13/ 8 5/16 15
OfficelManulaciwlng Facility .1315 Sançsm Ave. • Corona, CA 92819 • Ph. 909.131.5599 • Fax 909.137.0330
_Customer SeMce • 800.1865256
Fig. 23 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type
Size Range - 3/4" thru 2" CPVC pipe
Material - Carbon Steel, Pre-Galvanized
Function - Intended to perform as a hanger/restrainer to support
only CPVC piping used in automatic fire sprinkler systems. Can be
installed on the top or on the bottom of a beam. The Fig. 23 can also
be installed on the side of a beam. The Fig. 23 can also function as
a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals - Underwriters' Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds
the requirements of NFPA 13, 13R and 13D.
Features - Fig. 23 incorporates features which protect the pipe and
ease installation. The flared edge design' protects the CPVC pipe
from any rough surface. It also incorporates snap restrainers allow-
ing easier and faster installation. Easily attaches to the building
structure using the two UL Listed hex head self threading screws'
furnished with the product. It is recommended that rechargeable
electric drills fitted with a hex socket attachment be used as installa-
tion tools. No impact tools (such as a hammer) or impact fasteners
(such as drive screws or nails) are allowed. Damage has been
known to result from installations using impact type tools.
No pre-drilling of a pilot hole in wood is required.
Finish - Pre-Galvanized
Order By - Figure number and pipe size
* Patent Pending
"Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions 'Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size W000
3/4 314 19/I6 1/I6 51/2 5/16 9
I 3I8 I/ie 6 5/16 9
11/4 43/ 1/ 61I 5/16 11
1 /2 4I16 2I 1/1 7 5/16 12
2 4I 8 5/16 15
OfficelManufacturing Facility .1375 Sampson Ave. • Corona. CA 92879 • Ph: 909.731.5599 • Fax: 909.737.0330
Customer Seivice • 800.186.5266
Fig. 24 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type - Side Mount
Size Range - 3/4" thru 2" CPVC pipe
Material - Carbon Steel, Pre-Galvanized
Function - Intended to perform as a hanger/restrainer to support only
CPVC piping used in automatic fire sprinkler systems. Can be installed
on the top or on the bottom of a beam. The Fig. 24 can also function
as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals - Underwriters' Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds the
requirements of NFPA 13,13R and 13D.
Features - Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design* protects the CPVC pipe from any rough surface. Easily attaches to the building structure using the two
UL Listed hex head self threading screws** furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket
attachment be used as installation tools. No impact tools (such as a hammer)
or impact fasteners (such as drive screws or nails) are allowed. Damage has
been known to result from installations using impact type tools. No pre-drilling
of a pilot hole in wood is required.
Finish - Pre-Galvanized
Order By - Figure number and pipe size
* Patent Pending
-- Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions • Weights CPVC Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size W000 3/4 2I 1/ I'l'. 51/2 5/16 9 I 2% 15/16 13/te 6 5/16 9 1 /4 3 11I2 61/ 5/16 11 112 3114 1/. 7 5/16 12 2 31 /
- - 1 V/32 1/1 8 5/16 15
D Main 011lc&Manulacluring Facility .1375 Sampson Ave. • Corona. CA 92879 • Ph: 909.131.5599 • Fax: 909.137.0330 Customer Service • 800.186.5266
Fig. 4 - Standard Pipe Clamp
Fig. 4F - Standard Pipe Clamp Felt Lined
Fig. 4PVC - Standard Pipe Clamp PVC Coated
Size Range — (Fig. 4) Size 1/2" thru 30" pipe.
Size Range — (Fig. 4F) Size 1/2" thru 2112" copper tubing
Material — Carbon Steel
Function — Recommended for the suspension of non-insulated pipe or insulated pipe
with Fig. 220 shields. (Use Fig. 330 Weldless Eye Nut, Fig. 102 Eye Rod or .Fig. 101
Welded Eye Rod.) Also recommended for attachment of sway bracing up to 3'/2" pipe size, for larger pipe sizes use Fig. 4A. Fig. 4F and Fig. 4PVC are designed to reduce
noise and vibration and/or prevent electrolysis.
Approvals — Underwriters' Laboratories Listed in the USA (UL), Canada (cUL)
314" - 8", and approved by Factory Mutual Engineering, 3/4" - 8". Federal Specification WW-H-171 E, Type 4, 11/2" thru 24" and Manufacturers Standardization Society SP-69,
Type 4. Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning
and Development (OSHPD).
Note — When the Fig. 4 is used as a sway brace, to ensure performance, the UL Listing requires that it must be used 7
with other TOLCOThI brace products. Maximum Temperature — 750°F / Finish — Plain
1-1g. 4
Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials.
'N Order By — Figure number, pipe size and finish. Fig. 4F
Fig. 4PVC Order Note — When ordering Fig. 4F allow for 3/16" felt on each half of clamp.
Dimensions -Weights
Pipe Max. Design Load Lbs.
Size A B C D For Service Temp. Approx. Bolt Size 6500 750°F WtJ100 1/2 37/i, 1/4 11!8 11!, 5/16 500 445 29 3/4 311h€ 1/4 1'I4 11/4 5/16 500 445 31 I The 1/4 114 15!16 5/16 500 445 35 114 43/1e 1/2 13/, 11!,, 5/16 500 445 40 1112 49/,, 5/16 1"!, 1/, 5/16 800 715 42 2* 50/,, 1/2 2 21/4 39 1040 930 93 21/2* 6/,6 9/16 2112 2/4 1/2 1040 930 - 126 3* 7 5/8 2/4 The 1/2 1040 930 141 3'/2 711/,, 3/8 31!, 334 1/2 1040 930 154 4 8'/ 5/8 The 311!,, 5/8 1040 930 229 5 93 /4 3/4 3/, 411!. 5/8 1040 930 261 6 11'4 3/4 4'7s 5% 3/4 1615 1440 537 8 131!,. 1 5'!. 6 -- 3/4 1615 1440 625 10 16'/2 1 7'1. 71/4 7/8 2490 2220 1378 12 18'!, 1 8'/4 81/4 7/8 2490 . 2220 1574 14 20 11!. 9 9 7/8 2490 2220 2103 16 23 11!, 10'/4 101/4 7/8 2490 2220 2314 18 25/, 11/4 11'/2 11'/2 1 3060 2730 3276 20 28 j3/, 12'/2 12'I2 11!, 3060 2730 3863 24 331!. 1'!. 15'4 104 11/4 3060 2730 5222 30 41/, 2 19 19 1'/4 . 3500 3360 10511
fl Main OfficelMamifactwlng Facility. 1315 Sampson Ave. • Corona, CA 92879 • Ph: 909.131.5599 • Fax: 909737.0330