HomeMy WebLinkAbout1933 DOVE LN; ; AS03022510/8/2020 AS030225 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS030225
Job Address: 1933 DOVE LN Status: ISSUED
Permit Type: SPRINK Applied 10/29/2003
Parcel No:. 2150521500 Approved: . 1/14/2004
Lot #: 0
Reference No.: Issued: 1/14/2004
PC #: Inspector:
Project Title: LA COSTA GREENS BLDG.6 OH AS PLAN CHECK & INSPECTIONS
Applicant: Owner:
REAL ESTATE COLLATERAL MANAGEMENT
CO
C/O LIZ LAYMAN/ MORROW DEV
1903 WRIGHT PL #180
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
472.25 0 472.25 0
at
1/1
LIFEGUARD FIRE PROTECTION,N .C.
2605 TEMPLE HEIGHTS DR. STE: F, OCEANSIDE, 4P 92056
(760)806-9997 .FAX(760)806-4813
Hydraulic Design Information Sheet çØ
Name: La Costa Greens Date: 03/24/04
Location: -1933 Dove Lane"
Building: 46 System No. Carport
Contractor: Lifeguard Fire Protection, Inc. Contract No.
Calculated By: Lifeguard Fire Protection, Inc Drawing No. FP7
Construction: Z Combustible 0 Non-Combustible Ceiling Height 8'-0" Ft.
DQ NFPAJ3:
El NFPA 231
o Other (Specify)
OSpecific Ruling
SYSTEM L)IS1UN
0 Light Hazard Ordinary Hazard Group
0 NFPA 231C: Figure:
Area reduced ocr NFPA 13 Section 7-2.3.2.4
Made By
1 LI 2 II 3 II Extra Hazard
Curve:
Date
Area of Sprinlder Operation 900 sq ft System Tvoe
Density .15 . . Wet 0 Dry 0 Deluge 0 Pre-Action
Area Per Sprinkler 125 sq ft . Sprinider or Nozzle
Hose Allowance GPM: Inside. 0 Make Tyco Model LFII
Hose Allowance GPM: Outside 250 . Sze 1/2" K-Factor: 4.9
Rack Sprinkler Allowance n/a Temperature Rating 155
CALCULATION SUMMARY
GPM Required 158.10 PSI Required 65.69 At City Connection
"C" Factor Used:. . Overhead 120 Underground 150
Water Flow Test Pump Data Tank or Reservoir
'Date & Time 10/17/03 10:45am Rated Capacity n/a Capacity n/a
Static PSI 72 At PSI n/a Elevation n/a
Residual PSI 64 Elevation n/a
GPM Flowing 1480 Well
Elevation 190' Proof Flow n/a GPM Location Point of connection at existing main in Dove Lane
Source of Information Carlsbad Fire Department
COMMODITY STORAGE
Commodity Class. Location
- Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized % Rack
El Single Row 0 Conventional Pallet 0 Automatic Storage 0 Encapsulated O Double Row []Slave Pallet 0 Solid Shelving 0 Non-Encapsulated O Multiple Row [J Open
Flue Spacing In Inches Clearance From Top of Storage to Ceiling Longitudinal ' Transverse , . ' Ft. In Horizontal Barriers Provided
I.
La Costa Greens Bldg 06 Carport .151900 Sigma Dynamlo. Corporation TTOO Supply I Demand Graph
iuiu• • : iiiu uuu•
Ii--- iuus ; iiiu• - -€--- - iiii• iui••• iiii••
I
iiu•• ii• iuu••____________
iii••
Watar Flow (GPM)
System Demand...
Sprinkler Deland 61.95 PSI 1 158.10 GPM
Additional Flows 250.00 GPM
Hose at Source 0.00 GPM
Total Demand 62.28 PSI 0 408.10 GPM
Water Supply..
Static 64.80 PSI
Residual 57.60 PSI
Elevation 0.00 PSI
S 1480.00 GPM
)0
SUBMITTAL SERIAL NO:2932HY4
La Costa Greens
Building #6 Carport .15/900
FLOW TEST RESULTS
Water Supply
STATIC 64.80 PSI
RESIDUAL 57.60 PSI @ 1480.00 GPM
CITY PRESSURE AVAILABLE AT 408.1 GPM
0-08-2002 PAGE 1
64.14 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR PRESSURE
101 22.13 18.25 5.60 15.62
102 20.24 18.25 5.60 13.06
103 19.31 18.25 5.60 11.89
104 19.05 18.25 5.60 11.57
105 21.22 18.25 5.60 14.36
106 19.39 18.25 5.60 11.99
107 18.50 18.25 5.60 10.92
108 18.25 18.25 5.60 10.62
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 4
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 15 TO 16
158.10 GPM
250.00 GPM
408.10 GPM
62.28 PSI
0.00 PSI
21.63 FPS
SUBMITTAL SERIAL NO:2932HY4 03-08-2002 PAGE 2
La Costa Greens
Building #6 Carport .15/900
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
104 108 1.080 L 10.00 C=120 PT 10.62 (108)
Q 18.25 F=0 F 0.00 PE 0.00
BN T 10.00 0.0953 PF 0.95
23 104DQ 19.05 1.080 L 5.25 C=120 PT 11.57 (104)
Q 37.30 F=T,E F 8.10 PE 0.32
BN T 13.35 0.3577 PF 4.78
PT 16.67 ( 23)
103
------------------
107 1.080 L 10.00 C=120 PT 10.92 (107)
Q 18.50 F=0 F 0.00 PE 0.00
BN T 10.00 0.0978 PF 0.98
22 103DQ 19.31 1.080 L 5.25 C=120 PT 11.90 (103)
Q 37.81 F=T,E F 8.10 PE 0.32
BN T 13.35 0.3669 PF 4.90
------------------ PT 17.12 ( 22)
102106 1.080 L 10.00 C=120 PT 11.99 (106)
Q 19.39 F=0 F 0.00 PE 0.00
BN T 10.00 0.1067 PF 1.07
21 102DQ 20.24 1.080 L 5.25 C=120 PT 13.06 (102)
Q 39.63 F=T,E F 8.10 PE 0.32
BN T 13.35 0.4002 .PF 5.34
PT 18.72 ( 21) -----------------
101 105 1.080 L 10.00 C=120 PT 14.36 (105)
Q 21.22 F=0 F 0.00 PE 0.00
BN T 10.00 0.1260 PF 1.26
20 101DQ 22.13 1.080 L 5.25 C=120 PT 15.62 (101)
Q 43.36 F=T,E F 8.10 PE 0.32
BN T 13.35 0.4725 PF 6.31
PT 22.25 ( 20)
5 4 7.758 L 174.00 C=150 PT 61.88 ( 4)
Q 156.14 F=0 F 0.00 PE 0.00 LU T 174.00 0.0002 PF 0.03
6 7.758 L 415.00 C=150 PT 61.91 ( 5)
Q 156.14 F=GV,2EE/2BB F 60.40 PE 0.00
LU T 475.40 0.0002 PF 0.10
7 6 7.758 L 623.00 C=150 PT 62.01 ( 6)
Q 156.14 F=EE,GV/EB,GV,2BE F 66.44 PE 0.00
LU T 689.44 0.0002 PF 0.14
SUBMITTAL SERIAL NO:2932HY4 03-08-2002 PAGE 3
La Costa Greens
Building #6 Carport .15/900
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
8 7 . 7.758 L 220.00 C=150 PT 62.15 ( 7)
Q 156.14 F=GV F 6.04 PE 0.00.
LU T 226.04 0.0002 PF 0.05
3 8 7.758 L 158.00 C=150 •PT 62.20 ( 8)
Q 156.14 F=GV,EE/GV,T F 78.57 PE 0.00
LU T 236.57 0.0002 PF 0,05
1 3 7.758 L 1.00 C=150 PT 62.25 ( 3)
Q 156.14 F=0 F 0.00 PE 0.00
• LU T 1.00 0.0002 PF 0.00
PT. 62.25 (. 1)
2
------------------
4 7.758 L 596.00 C=150 PT 61.88 ( 4)
Q 251.96 F=T,GV,4EE/GV.,2EE F 146.52 PE 0.00
• LU T 742.52 0.0005 PF 0.37
1 2 7.758 L 1.00 C=150 PT 62.25 ( 2)
Q 251.96 F=0 F 0.00 PE 0.00
LU • T 1.00 0.0005 PF 0.00
PT 62.25 ( 1)
22
------------------
23 1.728 L 12.17 C=120 PT 16.67 ( 23)
Q 37.30 F=0 F 0.00 PE 0.00
FM T 12.17 0.0363 PF 0.44
21 22DQ 37.81 1.728 L 12.17 C=120 PT 17.11 ( 22)
Q 75.12 F=0 F 0.00 PE 0.00
FM T 12.17 0.1324 PF 1.61
20 21DQ 39.63 1.728 • L 12.17 C=120 PT 18.72 ( 21)
Q 114.75 F=0 F 0.00 PE .0.00
FM T 12.17 0.2900 PF 3.53
16 20DQ 43.36 1.728 L 41.50 C=120 PT 22.25 ( 20)
Q 158.10 F=T F 9.00 PE 0.00 FM T 50.50 0.5246 PF 26.49
15 16 1.728 L 11.50 C=120 PT 48.74 ( 16)
Q 158.1.0 F=2E F 7.40 PE 0.00
FM T 18.90 0.5246 PF 9.91
11 15 .2.203 L 7.58 C=120 PT 58.65 ( 15)
• Q 158.10 F=CV,E F 15.80 PE 3.28
FR T 23.38 0.1608 PF 3.76
SUBMITTAL SERIAL NO: 2932HY4 03-08-2002-PAGE 4
La Costa Greens
Building #6 Carport .15/900
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
10 11 4.280 L 7.00 C=140 PT 65.69 ( 11)
Q 158.10 F=E F 17.92 PE 0.00
UN T 24.92 0.0048 PF 0.12
9 10 4.266 L 118.00 C=150 PT 65.81 ( 10)
Q 158.10 F=T/3E F 96.05 PE 0.00
UN T 214.05 0.0043 PF 0.92
___ 4266 - - -L---7900- C=150 PT -6673-( 9.)-
Q 158.10 F=T,cV,DDC/3E F. 99.89 PE -20.37
UN T 178.89 0.0043 PF 0.77
4" Watts 909 RPDA 14.74
PT 47.13 ( 4)
0. 1
------------------
7.758 . L 1.00 C=150 PT 62.28 ( 1)
Q 408.10 F=0 F 0.00 PE 0.00
UN T 1.00 0.0013 PF 0.00
PT 62.28 ( 0)
LIFEGUARD FIRE PROTECTION, INC.
2605 TEMPLE HEIGHTS DR. STE: F, OCEANSIDE, CA 92056
(760) 806-9997 • FAX (760) 806-4813
Hydraulic Design Information Sheet
Name: La Costa Greens Date: 03/24/04
Location: 1933 Dove Lane
Building: #6 System No. 2-head
Contractor: Lifeguard Fire Protection, Inc. Contract No.
Calculated By: Lifeguard Fire Protection, Inc Drawing No. FP7
Construction: Z Combustible El Non-Combustible Ceiling Height 8'-0" Ft.
SYSTEM DESIGN
IZI NFPA 13: El Light Hazard Ordinary Hazard Group 0 1 0 2 D 3 0 Extra Hazard
O NFPA 231 0 NFPA 231C: Figure: Curve:
O Other (Specify)
Specific Ruling Residential Made By Date
Area of Sprinkler Operation 2-head . System Type
Density .10 Z Wet 0 Dry 0. Deluge 0 Pre-Action
Area Per Sprinlder 20' x 20' Sprinider or Nozzle
Hose Allowance GPM: Inside 0 Make Tyco Model LFII
Hose Allowance GPM: Outside Size 1/2" K-Factor: 4.9
Rack Sprinkler Allowance n/a Temperature R1ing 155.
- CALCULATION SUMMARY
GPM Required 40.21 PSI Requited 55.49 At City Connection
"C" Factor Used: Overhead 120 Underground 150
I
Water Flow Test Pump Data Tank or Reservoir
Date & Time 10/17/03 10:45am. Rated Capacity n/a Capacity n/a
Static PSI 72 At PSI n/a . Elevation n/a
Residual PSI 64 Elevation n/a
GPM Flowing 1480 jj
Elevation 190' . Proof Flow n/a GPM
Location Point of connection at existing main in Dove Lane
Source of Information Carlsbad Fire Department
uivnvivuii x i viutur
Commodity Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized % Rack
Rack
0 Single Row 0 Conventional Pallet
O Double Row 0 Slave Pallet
O multiple, Row 0 Open
Flue Spacing In Inches
Longitudinal - Transverse
Horizontal Bathers Provided
0 Automatic Storage. 0 Encapsulated
O Solid Shelving 0 Non-Encapsulated
Clearance From Top of Storage to Ceiling
Ft. In.
La Costa Greens Bldg 06 2-head cab Sigma Dyn•mlua Corporation
7100 8uDDlv I Demand Grah
I II....
Margin_________
Pressure 15.50 PSI Flo 2199.63 GP;r=
: i....
• 'iuiu ___________ ___________ ;•
I iu•u
------
- -€--- -
iui• iuuu•
1111•
Water Flow (GPM)
System Demand..
Sprinkler Demand
Additional Flows
Hose at Source
Total Demand
49.29 PSI
49.29 PSI
40.21 GPM
0.00 GPM
0.00 GPM
0 40.21 GPM
Water Supply..
Static 64.80 PSI
Residual 57.60 PSI
Elevation 0.00-PSI
1 1480.00 GPM
SUBMITTAL SERIAL NO:2932HY4 03-08-2002 PAGE 1
La Costa Greens
Building #6 second floor 2-head calculation
20' x 20' spacing
FLOW TEST RESULTS
Water Supply
STATIC 64.80 PSI
RESIDUAL 57.60 PSI @ 1480.00 GPM
CITY PRESSURE AVAILABLE AT 40.2 GPM 64.79 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR PRESSURE
162 20.21 20.00 4.90 17.02
163 20.00 20.00 .4.90 16.66
TOTAL WATER REQUIRED FOR SYSTEM 40.21 GPM
TOTAL WATER REQUIREMENT 40.21 GPM
PRESSURE REQUIRED AT 0 49.29 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 150 TO 151 13.55 FPS
SUBMITTAL SERIAL NO:2932HY4 03-08-2002. PAGE 2
La Costa Greens
Building #6 second floor 2-head calculation
20' x 20' spacing
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
161 163 1.101 L 13.00 C=150 PT 16.66'(163)
Q 20.00 F=DPV,E F 6.00 PE 0.00
AO T 19.00 0.0680 PF 1.29
PT 17.95
161 162
------------------
1.101 L 7.50 C=150 PT . 17.02
Q 20.21 F=DPV,E F 6.00 PE 0.00
AO T 13.50 0.0694 PF 0.94
160 161DQ 20.00 1.101 L 2.50 C=150 PT 17.96 (161)
Q 40.21 F=T/E F 10.00 PE. 0.22
BN1 T 12.50 0.2477 PF 3.10
152 160 1.101 L 33.00 C=150 PT 21.28 (160)
Q 40.21 F=E,DPV,4E/2DPV,E F 33.00 PE 0.00 BN1 T 66.00 0.2477 PF 16.35
PT 37.63 (152)
150 151
-------------------
-1.101 L 1.75 C=150 PT 44.67 (151)
Q 40.21 F=T/E F 10.00 PE 0.32
BN T 11.75 0.2477 PF 2.91
PT 47.90 (150)
5 4 - - 7.758 L 174.00 C=150 PT 49.29 ( 4)
Q 15.23 F=0 F 0.00 PE 0.00 LU T 174.00 0.0000 PF 0.00
6 5 7.758 L 415.00 C=150 PT 49.29 ( 5) Q 15.23 F=GV,2EE/2EE .F 60.40 . PE 0.00 LU T 475.40 0.0000 PF 0.00
7 6 7.758 L 623.00 C=150 PT 49.29 C 6) Q 15.23 F=EE,GV/EE,GV,2EE F 66.44 PE 0.00 LU T 689.44 0.0000 PF 0.00
8 7 7.758 L 220.00 C=150 PT 49.29 ( 7) Q .15.23 F=GV F 6.04 PE 0.00 LU T 226.04 0.0000 PF 0.00
3 8 7.758 L 158.00 C=150 PT 49.29 ( 8) Q 15.23 F=GV,EE/GV,T F 78.57 PE 0.00 LU T 236.57 0.0000 PF 0.00
1 3 7.758 . L 1.00 C=150 PT 49.29 ( 3) Q 15.23 F=0 F 0.00 PE 0.00 LU T 1.00 0.000.0 PF 0.00
PT 49.29 ( 1)
SUBMITTAL SERIAL NO:2932HY4 . 03-08-2002 PAGE 3
La Costa Greens
Building #6 second floor 2-head calculation
20' x 20' spacing
Location Flow Pipe. Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
-------------------
2 4 7.758 L 596.00 C=150 PT 49.29 ( 4)
Q 24.98 F=T,GV,4EE/GV,2EE F 146.52 PE 0.00
LU T 742.52 0.0000 PF 0.00
1 2 7.758 L 1.00 C=150 PT 49.29 ( 2)
Q 24.98 F=0 F 0.00 .PE 0.00
LU T 1.00 0.0000 PF 0.00
PT 49.29 ( 1)
151 152 -- - . 1.101 . L 10.00 C=150 PT 37.61 (152)
Q 40.21 F=DPV F 1.00 PE .433
FR]. T 11.00 0.2477 PF 2.72
------------------ PT 44.66 (151)
16 150 1.728 L 68.00 C=120 PT 47.91 (150)
Q 40.21 . F=T F 9.00 PE 0.00
FM T 77.00 0.0417 PF 3.21
15 16 1.728 L 11.50 C=120 PT 51.12 ( 16)
Q 40.21 F=2E F 7.40 . PE 0.00
FM T 18.90 0.0417 PF 0.79
11 15 . 2.203 . L 7.58 C=120 PT 51.91 ( 15)
Q 40.21 . F=CV,E F 15.80 PE 3.28
FR T 23.38 0.0128 PF 0.30
10 11 4.280 L 7.00 C=140 PT 55.49 ( 11)
Q 40.21 F=E F 17.92 PE 0.00
UN T 24..92 0.0004 PF 0.01
9 10 4.266 L 118.00 C=150 PT 55.50 ( 10)
Q 40.21 F=T/3E F 96.05 PE 0.00
UN T 214.05 0.0003 PF 0.06
4 9 4.266 L 79.00 C=150 PT 55..56 ( 9) Q 40.21 F=T,GV,DDC/3E F 9.9.89 PE -20.37 UN T 178.89 0.0003 PF. 0.05
4" Watts 909 RPDA 14.02
PT 35.24 ( 4)
0 1 .7.758 L 1.00 C=150 PT 49.29 ( 1) .. Q 40.21 F=0 F 0.00 PE 0.00 UN . T 1.00 0.0000 PF 0.00
PT 49.29 ( 0)
LIFEGUARD FIRE PROTECTION, INC.
2605 TEMPLE HEIGHTS DR. STE: F, OCEANSIDE, CA 920:56
(760) 806-9997 • FAX (760) 806-4813
Hydraulic Design Information Sheet
Name: La Costa Greens Date: 03/24/04
Location: 1933 Dove Lane
Building: #6 System No. 1-head
Contractor: Lifeguard Fire Protection, Inc. Contract No.
Calculated By: Lifeguard Fire Protection, Inc Drawing No. FP7
Construction: . Combustible El Non-Combustible Ceiling Height 8'-0" Ft.
IJ NFPA 13:
NFPA 231
Other (Specify)
ZSpecific Ruling
SYSTEM DESIGN
0 Light Hazard Ordinary Hazard Group
0 NFPA 231C: Figure:
Residential . . Made By
1 LI 2 U 3 U Extra Hazard
Curve:
Date
Area of Sprinlder Operation 1-head . System Type
Density .10 . Wet 0 Dry 0 Deluge 0 Pre-Action
Area Per Sprinlder 18'x 18' . . SprinlderorNozzle
Hose Allowance GPM: Inside 0 Make Tyco Model LFII
Hose Allowance GPM: Outside Size 1/2" K-Factor: 4.9
Rack Sprinider Allowance n/a. Temperature Rating 155
LOP i S]L1SJM!'
GPM Required 1768 PSI Required 28.22 At City Connection
"C" Factor Used:
.
Overhead 120 Underground 150
WAT1R SI TPPI V
Water Flow Test Pump Data Tank or Reservoir
Date & Time 10/17/03 10:45am Rated Capacity n/a Capacity n/a
Static PSI 72 At PSI n/a Elevation n/a
Residual PSI 64 Elevation n/a
GPM Flowing 1480 Well
Elevation 190' Proof Flow n/a GPM
Location Point of connection at existing main in Dove Lane
Source of Information Carlsbad Fire Department
Commodity Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized % Rack
Rack
O Single Row 0 Conventional Pallet El Double Row 0 Slave Pallet
O Multiple Row 0 Open
Flue Spacing In Inches
Longltodinal Transverse
Horizontal Bathers Provided
El Automatic Storage 0 Encapsulated
O Solid Shelving . 0 Non-Encapsulated
Clearance From TOD of Storage to Ceiling
Ft. In.
La Costa Greens Bldg 06 1-head cab
Sigma Dynamic. Corporation
7700 Supply I Demand Graph —.
____________________________
iLIr)L.Ll,:i PSI i. w 3970. 5L!tK- I_..____ 'iuiu• I.
.1 iuiu• • uuiu•
1uu• II.... - -
-
--
'iii uiva• 'ii•u• i• ;
'I'I'~Iim I' [K' 14J
Water Flaw (CPU)
System Demand..
Sprinkler Demand 19.66 PSI 117.69 GPM
Additional Flows 0.00 GPM
Hose at Source 0.00 GPM
Total Demand 19.66 PSI S 17.68 GPM
Water Supply..
Static 64.80 PSI
Residual 57.60 PSI 1 1480.00 GPM
Elevation 0.00 PSI
SUBMITTAL SERIAL NO:2932HY4 03-08-2002 PAGE 1
La Costa Greens
Building #6 second floor 1-head calculation
FLOW TEST RESULTS
Water Supply
STATIC 64.80 PSI
RESIDUAL 57.60 PSI @ 1480.00 GPM
CITY PRESSURE AVAILABLE AT 17.7 GPM 64.80 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR PRESSURE
164 17.68 17.00 4.90 13.02
TOTAL WATER REQUIRED FOR SYSTEM
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 150 TO 151
17.68 GPM
17.68 GPM
19.66 PSI
0.00 PSI
5.96 FPS
'I
SUBMITTAL SERIAL NO:2932HY4 03-08-2002 PAGE 2
La Costa Greens
Building #6 second floor 1-head calculation
Location Flow Pipe Fittings Equiv Friction Pressure
in Size Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
160 164 1.101 L 13.00 C=150 PT 13.02 (164)
Q 17.68 F=DPV,2E F 11.00 PE 0.22
AO T 24.00 0.0542 PF 1.30
152 160 1.101 L 33.00 C=150 PT 14.54 (160)
Q 17.68 F=E,DPV,4E/2DPV,E F 33.00 PE 0.00
BN1 T. 66.00 0.0542 PF 3.58
PT 18.12 (152)
150 151
------------------
1.101 L 1.75 C=150 PT 23.04 (151)
Q 17.68 F=T/E F 10.00 PE 0.32
BN T 11.75 0.0542 PF 0.64
PT 24.00 (150)
5 4
------------------
7.758 L 174.00 C=150 PT 19.66 ( 4)
Q 6.06 F=0 F 0.00 PE 0.00
LU T 174.00 0.0000 PF 0.00
6 5 7.758 L 415.00 C150 PT 19.66 ( 5)
Q 6.06 F=GV,2EE/2EE F 60.40 PE 0.00
LU T 475.40 0.0000 PF 0.00
7 6 7.758 L 623.00 C=150 PT 19.66 ( 6)
Q 6.06 F=EE,GV/EE,GV2EE F 66.44 PE 0.00
LU T 689.44 0.0000 PF 0.00
8 7 7.758 L 220.00 C=150 PT 19.66 ( 7)
Q 6.06 FGV F 6.04 PE ' 0.00
LU T 226.04 0.0000 PF 0.00
3 8 7.758 L 158.00 ' C=150 PT 19.66 ( 8)
Q 6.06 F=GV,EE/GV,T F 78.57 PE 0.00
LU T 236.57 0.0000 PF 0.00
1 3 7.758 L 1.00 C=150 PT 19.66 ( 3) 6.06 F=0 F 0.00 PE 0.00 LU T 1.00 '0.0000 PF 0.00
------------------ PT , 19.66 ( 1)
2 4 7.758 L 596.00 C=150 PT 19.66 ( 4)
Q 11.62 .F=T,GV,4EE/Gv,2BE F 146.52 PE 0.00
LU T 742.52 0.0000 PF 0.00
1 2 7.758 L 1.00 C=150 PT 19.66 ( 2) Q 11.62 F=0 F 0.00 PE 0.00 LU T 1.00 0.0000 PF 0.00
PT 19.66 ( 1)
SUBMITTAL SERIAL NO:2932HY4 03-08-2002. PAGE 3
La Costa Greens
Building #6 second floor 1-head calculation
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & . Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
--------------
151 152 .. 1.101 L 10.00 C=150 PT 18.11 (152)
Q 17.68 F=DPV F 1.00 PE 4.33
FRi T 11.00 0.0542 PF 0.60
PT 23.04 (151)
16 150
------------------
1.728 L 68.00 C=120 PT 24.00 (150)
Q 17.68 F=T . F 9.00 PE 0.00
FM T 77.00 0.0091 PF 0.70
15 16 1.728 L 11.50 C=120 PT 24.70 ( 16)
Q 17.68 . F=2E F 7.40 PE 0.00
FM T 18.90 0.0091 PF 0.17
11 15 2.203 L 7.58 C=120 PT 2.4.87 ( 15)
Q 17.68 F=CV,E F 15.80 PE 3.28
FR T 23.38 0.0028 PF 0.07
10 11 4.280 L 7.00 C=140 PT 28.22 ( 11)
Q 17.68 F=E F 17.92 PE 0.00
UN . T 24.92 0.0001 PF 0.00
9 10 4.266 L 118.00 C=150 PT 28.22 ( 10) o 17.68 F=T/3E F 96.05 PE 0.00
UN T 214.05 0.0001 PF 0.02
4 9 4.266 L 79.00 C=150 PT 28.24 ( 9)
Q 17.68 F=T,GV,DDC/3E F 99.89 PE -20.37
UN T 178.89 0.0001 PF 0.02
4" Watts 909 RPDA 11.77
PT . 7.89 ( 4)
0 1 . 7.758 L 1.00 C=150 PT 19.66 ( 1)
Q 17.68 F=0 F 0.00 PE 0.00
UN . T 1.00 0.0000 PF 0.00
PT 19.66 ( 0)
B
LIFEGUARD FIRE PROTECTION, INC.
20505 TEMPLE HEIGHTS DRIVE, STE. F
OCEANSIDE,_CA9205S
700-80-9997 • 7080g-4813 FIAX
Protection Design & Consulting
- Db
ith.. Comment.
Dae
'ga . %~ A6o3o7.!~5~
/1 tCop,.
M,ATERAL DATA SUBMITTAL
La Cosfo Greens
Building i*3 1933 cove Lane
Carlsbad, CA.
DOUBLE CHECK DETECTOR ASSEMBLY
BACKFL.OW PREVENTION
Physical Properties U.S. Patent No. 4.M.635 • U.S. Patent No. 5.107888
U.S. Patent No. 5.385,166 • U.S. Patent No. 5.22M41
Size of Mainline 2-1/2", 3 4" 80, 8", & 10" U.S. Patent No. 5.392.803 • U.S. Patent No, 5.5W,176
Max. Working Pressure 175 PSI (1200 KPa)
Hydrostatic Test Press. 350 PSI (2400 KPa)
Temperature Range 320 F to 1400 F
(00 C to 600 C)
End Connections Flanged ANSI B16.1
Class 125
0
Materials
Main Valve Body
Coating
Shut Off Valves
Trim
Elastomer Discs
Spring
Installation Views -
18" min
Ductile iron Grade 65-45-12
Fusion epoxy coated
internal and external
AWWA C550-90
OS & Y resilient wedge
gate valves AWWA C509
Bronze
EPDM
Stainless steel
MODEL 876V DOUBLE CHECK DETECTOR
(Shown In vertical posItion)
MODEL 8760876V DOUBLE CHECK DETECTOR
(Shown In standard orientation)
Suppod iilied by customer) sJv. weIght 01*/.
FLOW
Standard orientation (Model 876'I876V)
* Note-Model 876 does not include grooved end coupling.
Recommended minimum clearances from permanent structures for
ease of testing and maintenance.
Vertical orientation (Model 876V)
, A ~~ ,q !I
876/876V Materials of Construction
ITEM DESCRIPTION MATERIALS ITEM DESCRIPTION MATERIALS ITEM DESCRIPTION MATERIALS
I Body A536 GR 6545-12 8 Lower Spring RetaIner 8584 Alloy C83600 26 Gasket EPDM ASTM 02000
2 Cover A536 GR 6545-12 9 Spring Stem 30488 35 0-ring EPDM ASTM 01999
2.1 0-ring EPDM ASTM 02000 9.1 mastic Stop Jam Nut 18-8 $$ 35.1 Back Up Ring Metal Resin
2.2 Cap Screw Plated Steel 10 Spring A313 Type 631 SS 36 Cover 8584 Alloy C83600
2.3 Hex Nut Plated Steel 10.2 Spring Shim Acetal Resin 40 Ball Val* 8584 Alloy C83600
2.5 Cover (w/o holes) A536 GR 65-45-12 10.3 Spring Shim Acetal Resin 41 Nipple Brass
3 Seat Ring 8524 Alloy C83600 ii Spring Guide B130 Alloy C22000 42 Gate Valve (OS&Y) AWWA C509
3.1 Gasket EPDM ASTM D2000 12 Upper Spring Retainer 8584 Alloy C83600 43 Bulkhead Filling 8584 Alloy C83600
4 Arm B584 Alloy C83600 12.1 Bushing Spring Stem Acetal Resin 43.1 Bulkhead Filling 0584 Alloy C83600
4.1
4.2
Bushing-Swing Pin Metal Resin 13 Pivot Bearing - 8585 Alloy C83600 44 Bulkhead rifling B584 Alloy C83600 Swing Pin 30488 14 Flange Gasket RubberlFabrlc 45 Gasket EPDM ASTM 02000 5
5.1
Retaining Clip 302 SS 15 Bearing Socket Metal Resin 45.1 Gasket EPDM ASTM 02001
6
Retaining Clip
Check Disk (2-112 - 8)
302 SS
EPDM Coated GR. 45
16 Hex Jam Nut 18-8 SS 46 Washer 836 Alloy 260
Ductile Iron
Capsaaw, (l(r Only) 18-8 SS 46.1 Washer 836 Alloy 280 WI type
304 SS
17
18
Washer 302 SS 47 Nut 8584 Alloy C83601
Seat Disc (10Only) Silicone ASTM 02000 18.1
Flange Nut Plated Steel 47.1 Nut 8584 Alloy C83602
6. Disc Holder (10 Only) ASTM A743 304 SS
Flange Nut Plated Steel 60 Identification Plate B36 Alloy C26000
6.2 Disc Retainer (10k Only) ASTM A743 304 SS
19
24
Cover
Bolt
A36 511. Epoxy Coated 61 Identification Plate B36 Alloy C26000
6.3
Plated Steel 62 Drive Screw Stainless Steel
7
Capscrew(l(Only)
Load Pin
118-8 SS
30458
24.1
25
Washer
Bolt
Plated Steel
Plated Steel
10 Clamp 876VOnly AWWAC6O6
08 &Y
Side View
arooved end
CE
Model 876V Model 876V
Standard Orientation Vertl Oritaticn
Note: The Model 876V is shipped in the
standard (N-Shape) orientation as shown
Dimensions Approximate
El Net
oS&Y Osay
Size A B C OPEN F G. H J K M (Lbs.)
2112" 12' 2914 24'1 1634 1661. 61k 11 112 3'I2 1361. 271!. 230
65 317.50 654.05 615.95 415.93 42228 158.75 292.10 88.90 348.08 692.15 104.33
3" 1211 2534 24314 2214 1611h 61!4 111h 3314 141I6 2811, 300
80 317.50 654.05 628.65 565.15 422.28 158.75 292.10 95.25 35818 717.55 136.08
4 14 27!6 2914 231/4 1l'14 7 13 4' 15'12 31 330
100 355.80 708.03 679.45 590.55 450.85 177.80 330.20 114.30 393.70 787.40 149.69
on 16 32'1 3211 3011e 214!? 8 13 5112 1851e 37114 520
150 406.40 819.15 819.15 765.18 547.9 203.20 330.20 139.70 473.08 946.15 235.87
8" 18112 37112 363/8 37314 24116 911. 1411 6 3 14 20!4 4111a 860
200 469.90 952.50 923.93 958.85 631.80 234.95 368.30 171.45 527.05 1054.10 390.09
10" 21 421!2 4031 48 27'!. 10 15 8 24 48 1480
250 533.40 1079.50 1035.05 1219.20 698.50 254.00 381.00 203.20 609.60 1219.20 682.24
Weights do not include risers or optional valve setter.
Note: Dimensions shown are nominal. Allowances must be made for normal manufacturing tolerances. Refer to Specification Sheet SS VS for details on valve setter.
Application
Non-Health Hazard Fire Sprinkler Systems
Flow Orientation
Standard orientation Is inlet flow vertical up, outlet flow
vertical down. Vertical orientation is inlet and outlet flow
vertical up.
Options
0 Valve Setter with MJ x FL, MJ x MJ
or FLxFL ends
Agency Compliance
Approved by the Foundation for Cross
Connection Control and Hydraulic Research
at the University of Southern California.
ASSE (Ste. 1048)
ANSI/AWWA (C510-89)
CAN/CSA (B64.5)
FM*
UL*
cUL
Less gate not FM approved.
Less gate not UL Hated unless Installed with UL lIsted
gated valves.
Model 8761876V Flow Curves
I-
,,-
- — -- --- - - - -
I I It I II I II I II II .11 II III It II
- _
I II III II III 'It III
10" 18 16
.14
12
10
2
BI
16
14
,12
10
38
2
B
0 100 200 30) 40)
GPM
A-Vertical orientation (model 876V)
B-Standard orientation (model 876)
500 600 70) 0 1000 2000 3000 4000 5000
GPM
The W and 10" flow curves in the standard orientation
include the FEBCO valve setter model 611.
FEBCO Bacictiow Prevention
P.O. Box 8070• Fresno, CA 93747-8070
559 252-0791 Far 559453-9030- www.cmb-Ind.com
NOW OliOl vIW901 cus kIthEUee. Inc.
7-]CM InmstrIs, Inc.
A ON-6 a COWAN/
ISO 9001 Certified
Scheduleml0q/Schedulem406
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product Although these
products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (l"- 8") pipe and Sch-40 (1"- 2'4") pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Schedule-10/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A-123.
Our advanced formula mill coating of-
fers a clean, durable surface. It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF". In scientific laboratory
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
[iISpecifications
NPS Nominal I.D. WI. Wt. (1120 Filled) Pcs/ WI/Lift (21) WI/Lift (24) WI/Un (25)
In; mm In; mm Lbs/Fl; Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1' 1.049 1.680 2.05 70 21470 2.822 2,940
25 26.6 2.5 3.05 70 1,120 1,280 1,334
1W 1.380 2.270 2.93 51 2,431 2,778 2,894
32 35.1 4.36 4.36 51 1,103 1,260 1,313
1'/2 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
2 2.067 3.650 5.13 30 2,300 2,628 2,738
50 52.5 5.4 7.63 30 1,043 1,192 1,242
2W 2.469 5.790 7.86 19 2,310 2,640 2,750
65 62.7 8.6 11.73 19 1,048 1,197 1,247
UTT1i'iii.
NPS Nominal I.D. M. WI. (1120 Filled) PCs/ WI/LIft (21) WI/LIft (24) WI/LIft (25')
In; mm In; mm Lbs/Fl; Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1' 1.097 1.400 1.81 91 2,675 3,053 3,185
25 27.9 2.1 2.70 91 1,213 1,385 1,445
1W 1.442 1.810 2.52 61 2,319 2,664 2,760
32 36.6 2.7 3.75 61 1,052 1,208 1,252
1W 1.682 2.080 3.04 61 2,664 3,045 3,172
40 42.7 3.1 4.52 61 1,208 1,381 1,439
20 2.157 2.640 4.22 37 2,051 2,344 2,442
50 54.8 3.9 6.28 37 930 1,063 1,108
21/2" 2.635 3.530 5.89 30 2,224 2,542 2,648
65 66.9 5.3 8.77 30 1,009 1,153 1,201
3.260 4.330 7.94 19 1,728 1,975 2,057
80 82.8 6.4 11.82 19 784 896 933
4.260 5.610 11.78 19 2,238 2,558 2,665
90 108.2 8.3 17.53 19 1,015 1,160 1,209
5° 5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
6' 6.357 9.290 23.03 10 1,951 2,230 2,322
150 161.5 13.8 34.27 10 885 1,012 1,053
80 8.249 16.490 40.15 7 2,424 2,770 2,885
200 209.5 24.5 59.75 7 1,100 1,256 11309
Schedule-10/Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
Welded Outlets
Hydrostatic Pressure
Side Wall Rupture
Vibration Test
tqcu/Fiow Control allied
TUBE & CONDUIT
@ <S> 0 1
Listed Approved Listed
16100 S. Lathrop Harvey, IL 60426 Customer Service:
11350 Norcom Rd.. Philadelphia, PA 19154 (800) 882-5543
2525 N. 27th Ave. 'Phoenix, AZ 85009 Fax 708-339-1806
S5-3
$1 per Flog/DynawFlowe
Aigh Strength Steel Pipe—
The original high-strength IightwaIl sprinkler pipe with hydraulics superior to Schedule-10,
Super Flo/Dyna-Flow pipe is the "original1'
high-strength lightwall sprinkler pipe.
Super Flo/Dyna-Flow has outstanding
hydraulic capabilities and is recognized
as the most popular alternative to
Schedule-10 pipe. Lightweight, easy to
cut and easy to handle for installation.
Super Flo/Dyna-Flow is a valuable
addition to any fire protection system.
4 Superior Hydraulics _
With an inside diameter of up to 11%
larger than Schedule-40 and up to 7%
larger than Schedule-10, SuperFlo/
Dyna-Flow pipe hydraulics are exceptional.
er I.D.s enable Super Flo/Dyna-Flow,
.uid related components, to be down-
sized within the system, thus increasing
the potential for job cost savings. For
complete Hazen-Williams charts, refer to
"Super Flo/Dyna-Flow Hydraulic Data
Tables."
Coatings & Fabrication
Super Flo/Dyna-Flow products are coated
with an environmentally approved and
specially formulated modified-acrylic or
water-based coating. This durable coating
is painrable. The black coating acts as
an excellent primer and is resistant to
weathering and U.V. degradation from
outdoor storage.
Metallurgical properties provide excellent
fabrication characteristics for end prep
finishes, welding and roll grooving. No
.'-"cial process or equipment are needed
fabrication and installation.
-n allied
TUBE & CONDUIT
Ill,
Product Nominal Wt/Ft Wt/Ft PCs/ Wt/Lift Wt/ Lift Wt/Llft
NPS 1. D. H20 Filled Lift 21' 24' 25'
X 1" 1.191 0.830 1.31 91 1586 1.81.2 1888
*25 30.3 1.2 1.95 91 719 822 856
x 1 1/4" 1.536 1.059 1,87 61 1356 1550 1615
*32 39.0 1.6 2.78 61 615 703 733
xl 1/2" 1.728 1.667 2.71 61 2135 2440 2542
*40 43.9 2.5 4.03 61 968 1107 1153
2.203 2.104 3.79 37 1634 1868 1946
*50 56.0 - 3.1 5.64 37 741 847 883
x21/2" 2.703 264 5.10 30 1615 1846 1923
*65 68.7 3.8 7.59 30 733 837 872
3.314 3.387 7.18 19 1351 1544 1608
*80 84.2 5.0 10.69 1.9 613 700 729
x 4" 4.310 4.473 10.86 19 1784 2039 2124
*90 109.5 6.7 16.16 19 809 925 963
x6" 6.403 7.714 21.70 10 1620 1.851. 1928
*150 162.6 11.5 32.29 10 735 840 875
Specifications & Approvals
Super Flo/Dyna-Flow pipe is
manufactured to meet ASTM A-
795 pe E, Grade A and is in
compliance with NFPA-13 and
NFPA-14. All sizes of Dyna
Flow/SuperFlo are UL Listed,
FM Approved and ULC Listed.
(@ 0 t0c
Listed Approved Listed
Super Flo/Dyna-Flow is UL/ULC
Listed for use with roil grooved,
plain-end couplings, and welded
joints for wet, dry, preaction and
deluge systems. It is FM Approved
for roll grooved, plain-end, and
welded joints for wet systems.
Refer to appropriate documentation
for up-to-date listing and approval
information, Super Flo/Dyna-Flow
is now available "hot-dip"galvanjzed
and has been specifically approved
by FM for dry systems uses,
Lightweight and easy to install,
resulting in more efficient use of
your freight and labor dollars.
Provides stability needed to
comply with standard hanger
spacing (15 ft O.C.) per NFPA.
Available in Standard lengths
for your convenience, or can be
ordered in custom lengths
upon approval. -
Fast cutting and welding, as well
as easy roll grooving and end
preparation.
Available in Factory roll grooved
form for quicker shop turnaround.
Clean, durable mill coating
provides longer "shelf life" and
acts as an excellent primer for
custom paint applications.
1.6100 S. Lathrop 11350 Norcom Rd. 2525 N. 271h Ave. Customer Service:
Harvey, IL 60426 Philadelphia, PA 19154 Phoenix, AZ 85009 1•800-797-6210
Fax 70,9-339-1806
ubmttaI Data Sheet
Super 40®/Dyna-Thread" Slamp Here
Full Line Sch-40 Replacement
Super -lWDvna.Thread sprinkler pipe represents an engineering advancement for the. sprinkler
pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with quality and
superior hydraulic advantes.
Comparison to Schedule 40 Super 40/Dyna-Threads inside diameter is up to 3.6%
larger than Sch-40 giving it superior hydraulics. Also, when used in combination with Dyna-Flow
pipe. down sizing often occurs. Super 40/Dyna-Thread is Fully listed and approved UL. ULC, and
FM for lire sprinkler applications. The life expectancy of Super 40/Dyna-Thread and Sch-40 are
equal based on the calculated wall thicknesses per UL (see CRR), The consistent qualify of steel
u-ed to make Super 40/Dna-Thread facilitates smooth threading and lower maintenance costs.
The exterior of Super 40/Dyna-Thread is protected by a clean, durable mill coating for extended
Ii life and easy paint application. With its increased strength and lighter weight. Super40/
0.. tin-Thread reduces installation ln igue and is ideal for retro-fit applications. Corrosion
lciiance Ratio ICRRt is a UL. (Underwriters Laboratory) term for the estimated life expecuiney
ot a pipe joint. This is based on the calculated wall thickness at the base of the First exposed thread,
n.timed to be the weakest point of the pipe length. Super 40/Dyna-Thread and Sch-40 have the
.ttne calculated wall thicknesses at this point and are both assigned the same CRR of 1.00.
Comparison to L.K.T. Pipe More wall thickness at the thread (CRR1.00) gives
Super 40/Dma-Thread better life expectancy than hightwall threadable pipe joints. Unlike
lighiwall threaduble pipe. Super 40/Dyna-Thread has no thread gauge warning. Super 40/
Dyna-Thread is approved for standard hanger spacing( 15 ft. O.C.. can be used as earthquake
sway lracing. and is safe to use as drops. Super 401 Dyna-Thread is safer to weld on than many
zinc-coated light wall threadable pipe products. Super 40/Dyna-Thread is more widely accepted
than lighiwall threadable where Sch-40 is specified.
Product Nominal Wt/Ft Wt/Ft PCs/ Wt/Lilt Wt/Litt Wt/Lift
NPS 1. D. H20 Filled Lift 21 24' 25'
X 1 1.080 1.330 1.75 70 1955 2234 2327
*25 27.4 2.0 2.60 70 887 - 1013 1056
1 1/4 1.408 1.870 2.54 51 2002 2288 2384
*32 35.8 2.8 3.78 51 908 1038 1081
1 1/2 1.639 2.290 3.22 44 2115 2418 2519
*40 416 3.4 4.79 44 959 1097 1143
x2 2.104 3.050 4.57 30 1921 2196 2287
*50 53.4 4.5 6.80 30 871 996 1037
American Tube and Pipe was acquired by Allied Thbe and Conduit on February 1, 1997. The engineered lighiwall and standard wall family or products although they
have different names are the same in all respects with regard to strength weight, bundle count listings and approvals. For example, Dyna.Flow and Super Plo are the
same product as are Dyna Thread and Super 40. XL is manufactured with Exterior galvanized coating. BLT is manufactured ivith Black lacquer catlng.
Project: Sprinkler Contractor: Date:
Engineer: Specification Reterence: System Type:
Locations: Comments:
Spèifications & Approvals
Siiper4O/Dyna-Thread pipe is mnnttliucrttred to
meet: ASTM A 135. Grade A and is in compliance
u ith NFPA- 13. All sizes of Super 40/Dyna-Thread
are rated at 300 psi working pressure. Super 40/
Dma-Thread is UL and ULC Listed for wet, dry
atid pre-action sprinkler systems and FM Approved
fur use in wet systems. Super 40/Dyna-Thread can
be hot-dip' galvanized to meet FM requirement
ku dry NY.Uems. Super 40/Elyria-Thread is approved
fur all threaded couplings and celded outlets and is
suttable for all roll-grooved, and plain-end fittings.
(See listing information).
(9-L 0 @
Listed Approved LtIed
Flow Data
Friction Resistance
The chart expresses the frictional
resistance of various Victaulic
fittings as equivalent feet of
straight pipe. Fittings not listed
cnn be estimated from the data
given, for example, a 221/20 elbow
is appluidmately one-halt the
resistance of a 450 elbow. Values of
rind-sizes can be interpolated.
IFIS CARBON' ISTE
Grooved IPS Fittings
Victaulic fittings are designed specifically for use
in grooved piping systems.
Victaulic offers a broad line of
fittings in sizes through 24'
(600 mm) in a variety of straight
and reducing styles. Most standard
fittings are cast of durable ductile
iron to precise tolerances. Victaulic
standard fittings pressure ratings
conform to the ratings of Victaulic
Style 77 couplings.
All fittings are 'supplied with
grooves or shoulders to permit last
installation without field
preparation. The grooved design
permits flexibility for easy
alignment. These fittings are not
intended for use with Victaulic
couplings for plain end pipe (refer
to page 55 for fittings available for
plain end applications).
Fittings are provided in various
materials including malleable iron,
ductile iron, steel or segmentally
welded steel depending on styles
and size. Fittings pre painted
orange enamel with galvanized
optionally available, contact
Victaulic for details.
Victaulic fittings are designed
specifically for use in grooved
piping systems. Fittings are
provided grooved or with
shoulders conforming to standard
steel pipe outside diameters. When
connecting wafer or lug-type
butterfly valves directly to
Victaulic fittings with 741 or 743
Vic-Flange adapters, check disc
clearance dimensions with I.D.
dimension of fitting.
Request 07.01.
Alternate Materials
Stainless Steel - Grooved end
fittings are available in Schedule 10
Type 316 stainless steel (Schedule
5, 40 and Type 304 optionally
available) in various sizes. Fitting
center-to-end dimensions will vary
depending upon type and
schedule.
Request 17.04 for details.
Aluminum - Grooved end fittings
are available in aluminum alloy 356
T6, in sizes from 1 - 8' (25 - 200
mm). Request 21.03 or contact
Victaulic for details,
Alternate Styles
EndSeal "ES" Fittings -
EndSeal fittings are available in 2 -
12' (50 300 mm) for use with "ES"
grooved pipe and HP-70ES
EndSeal or FiroRT1 couplings.
"ES" fittings are painted green for
easy identification. EndSeal (and
standard) fittings may be easily
internally coated (by others) for
severe service requirements.
Always specify "ES EudSeal
fittings" when ordering.
Request 07.04 for information on
EndSeal fittings,
Fittings Machined for Rubber
or Urethane Lining (MRL) -' For
severe abrasive services, Victaulic
fittings may be rubber or urethane
lined (by others). Lining may be
inside diameter/end (abrasion
resistance) or wrap-around
(corrosion and/or abrasion)
machined.
Request 25.03 or contact Victaulic
for specific details:
Pipe Pipe Inches/mm Equivalent Feel/meters ofStraight Pipe Inches/mm Equivalent Feel/meters of Straight Pipe
- - 900 Elbows 450 Elbows Tees 900 Elbows . 451 Elbows Tees
No. 100 No. 110 No. No. 110 No.10 1½0 No. 1 1 1½D No.10 1½0 No. 11 1½0 Nom. Actual SId, Long Std. Long Nom. Actual SId. Long Sid. Long Size Size Radius Radius Radius Radius Branch Run Size Size Radius Radius Radius Radius Branch Run
1 1.315 1.7 - 0.8 - 4.2 1.7 6 6.625 10.0 7.5 5.0 3.0 20 10.0 25 311 (L5 0.2 . 13 0.5 150 1683 30 2.3 1.5 0.9 76 10
2 2.375 3.5 2.5 1.8 1.1 8.5 3.5 6.500 9.6 -. 5.0 - 25.0 10.0 50 60.3 1.1 08 05 03 26 ii 64 1851 2.9 - 15 7.6 30
3.000 4.3 -. 2.1 -. 10.8 4.3 8 8.625 13.0 9.8 6.5 4.0 33.0 iao 76.1 1.3 ... 07 .. 33 1.3 200 2191 4.0 3.0 2.0 1.2 101 40
3 3.500 5.0 3.8 2.6 1.6 13.0 5.0 10 10.750 17.0 12.0 8.3 5.0 41.0 17.0 80 88.9 15 12 08 0.5 40 1.5 250 273.0 52 3.7 2.5 1.5 1 12.5 5.2
4 4.500 6.8 5.0 3.4 2.1 16.0 6.8 12 12.750 20.0 14.5 10.0 6.0 50.0 200 100 1143 21 15 10 06 49 2.1 300 3239 6.1 4.4 30 1.8 15.2 61
04t 4.250 6.4 3.2 15.3 6.4 14 14.000 41 23.0 If 18.0 60.0 17.0 ioao 1 1.8 09 . 47 20 350 3556 4 7.0 it 5.5 1113 5.2
5 5.563 8.5 - 4.2 - 21.0 8.5 16 16.000 41 26.0 Il 20.0 70.0 20.0 125141.32.6 1.3 -. 6.4 26 111)0 40134 it 79 II ill 213 (31
5.250 8.1 - 4.1 - 20.0 8.1 18 18.000 41 29.0 41 23,0 80.0 2,0 25 1.6 6.7.2.5 450 457.0 41 5.6 if O 24470
5.500 8.5 - 4.2 - 21.0 8.5 20 20.000 If 33,0 II 26.0 90.0 25.0 2.6 - 1.3 6.4 2.8 1 500 508.0 5 10.1 Ii 7.9 27.4 7.6
6.250 9.6 - 5.0 -. 25.0 10.0 24 24.000 If 40.0 41 30.0 30.5 34.0 159.0 2.9 .- 15 . 76 30 600 '100 U 12.2 U 91 93 10.4
It '...UIIidLI Viciauliu IOF details.
O.D. Dimension.
14
The unique angle-pad design of
ZeroFlex® Style 07 adjusts to
standard pipe and roll or cut
groove tolerances, positively
clamping the pipe to resist flexural
and torsional loads. Wider key
section fills more of the groove
area.
Request 06.02.
Style 77
Standard
Flexible Coupling
Style 77 couplings are designed
with cross-ribbed construction to
provide a strong component for
pressure piping systems. Sizes
3/4 -12(20-300 mm) are two-piece
housings. Sizes 14 - 22
(350 - 550 mm) are cast in four
identical segments, With larger
sizes cast in six segmelflS.
Request 06.04.
I P :AM OU 114
GROOVED' COUPUNGS'
....... ......
Style 07
ZeroFlex® Rigid Coupling
0
x
2- 12" Sizes
c J O
14-16 Sizes 18- 24" Sizes
ICV' WO
:V.- 12° Sizes 14-22 Sizes
1zr. iZr.
10
24" Size
Nom,
Size
Max.
Work Press. Dimensions - Inches/mm WgIEach
X Y Z Inches/mm PSI'/kPa LbsAg
750 2.45 4.13 1.88 1.6
132 105 -Ill it
11/4 750 2.60 4.00 1.88 1.6
:3.' :,I'5 06 10? -.43 07
11/2 750 2.94 4.81 1.88 1.6
:i 22 119 07
2 750 3.19 - 5.44 1.88 2.3
10
2½ 750 3.68 6.13 1.88 2.8
750 4.25 5.75 1.86 3.6 31: )17 'mill 146 113
3 750 4.56 6.81 1.88 3.1 130 17!1 lid 173 4111 1.1
4 750 5.81 8.25 2.06 4.8
103) :,1 1.111 2113 52 22
750 5.56 7.44 2.06 5.2 41/4 1 :',i7, 1.11 11,9 1;:'
5 750 7.06 9.75 2.06 7.1 '15 170 248 5.1 .3
700 6.36 9.18 2.06 7.4
:11121. 74 33
700 6.94 9.42 2.06 7.6 5½t i6 .'33 .4-I
6 700 8.00 10.75 2.06 8.7
I. '11325 203 : 52 3
700 7.85 10.18 2.06 9.2 6¼ .I 331:•'lm 99 259 5? -i
700 6.00 10.75 2.06 7.2
4625 "03 .52 3 2
600 10.25 13.50 2.50 14.9
71(1) .1 130 No 3.13 94 (41;
10§ 500 12.88 16.75 2.56 25.0
J 'U 3453) .37 32,3 61, 1 '.3
12§ 400 14.88 18.50 2.56 28.2
:400 .'7,t) .4713 I'ii 95 '23'
14 300 16.19 19.75 2.94 32.8 411 '('2 75 1'10
16 300 18.38 21.75 2.94 411.2 .1(13) 1((155 467 ,:33 71, ii3
18 300 20.69 23.88 3.06 54.2 iso :'o, 571, 9044 75 24 0
20 300 23.00 27.38 3.06 67.2 7,361, 34 319:, 78 .13) 5
24 250 27.13 31.50 3.13 76.2 31,13) i7':, '1339 3043 70 3.10
O.D. Dimension. Refer to notes on page 7. § Available to J.I.S. dimension
'? Woi 'ess. Dimensions - Inches/mm Wgi. Each
X V Z Inches/min PSI/lPa Lbs./kg
3/4 1,000 2.13 3.63 1.75 - 1.1
03)3)9 ;14 04' .1_I it I'
1 1,000 2.38 3.88 1.75 - 1.3
'A 6900 140 0143 .1.1 01;
1'/, 1,000 2.63 4.63 1.75 2.0
13900 i' 1144 4.1 9))
11/2 1.000 3.00 5.00 1.75 2.1 £9 049933 16 i? 1.1 It)
2 1,000 3.63 5.63 1.75 2.6
ml 9)1330 9? 143 II
2½ 1,000 4.25 6.25 1.75 3.1
'35 3000 Wlt iso .1.1 1.1
31: 1,000 4.31 6.31 1.75 3.6
119 1339 1.1 113
3 1,000 5.00 7.00 1.75 3.5
130 11900 12.' 1 .i .34 1,1
3½ 1,000 5.63 8.00 1.75 5.6 90 0900 143 21).; 1.1 ' 1'
it 1.000 6.38 8.50 2.00 - 6.6 3111)33 111' .110 1,1 iii
4/1: 1,000 5.88 8.06 2.06 - 7.0
i'lL)
5 1,000 7.63 10.25 2.00 - 10.6
(19130 19.3 .'00 SI .l t)
1:
1.000 7.34 9.20 2.06 10.0
(3900 190 234 112 .1
5%.f 1,000 7.60 9.44 2.06 11.0 61)X01 1043 'Ii) :,? 1.1)
6 1,000 9.00 11.50 2.00 11.8
439(13) 229 ji.' 51 :' -I
6/4 1: 1000 8.50 10.38 2.06 13.2
330430 21(1 '6.1 :':' 130
6 * 1,000 9.19 11.50 2.06 - 13.2
ooc .'a :'2 ill'
8 § 800 11.38 14.50 2.38 - 20.1 203) :,(100 9th) .4043 90 111
10 § 800 13.50 16.75 2.50 - 28.3 '500 :143 .l75 0.1
12 § 800 16.50 19.00 2.50 34.2 3110 SSJO .39.1 193 9.1 15:.
14 300 16.63 20.00 2.88 - 35.6 3065 413 s3) ill I
15 300 17.88 21.25 2.88 - 48.8
16 300 19.00 22.36 2.68 - 51.1 :.13.11 .1133 11613 :3 ;'
18 300 21.25 24.38 3.13 - 64.4 -'lit) 2961' tlO 3310 70 20 J 300 23.50 27.50 3.13 - 91.2 21131:, sO' 1)03) ..9 4 1
22 300 25.83 30.00 3.13 - 92.0 510 2'S ilDi '02 79 41 7
24 250 27.63 31.38 3.13 - 94.0
1)00 172:4 'Oi' 9'
1: O.D. Dimension. . Refer 10 notes on page 7. § Available to J.I.S. dimension.
Size Range - 1/4 thru 1-1/2 inch rod in 10'-0"
lengths.
Material - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain, Electro-Galvanized, and Stainless
Steel.
Order By - Figure number, rod diameter, and
finish.
MAX. REC. LOAD LBS, APPROX.
ROD FOR SERVICE TEMPS WEIGHT
SIZE 650'F 750'F PER 100 FT.
1/4 240 215 12
1/2 1130 1010 .53
3/4 2710 2420 123
J79 ki
4960 4420 222
1-1/2 11630 10370 510
I PAM To C.- . U
INCORPORATED
CORONA. CA • (909) 737-5599 53
FIG. 99
ALL THREAD ROD CUT TO LENGTH
Size Range 3/8 thru 7/8 inch rod in 1 inch
increments.
Material - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain, Electro-Galvanized, and Stainless
Steel.
Order By - Figure number, rod diameter, rod
length, and finish.
MAX. REC. LOAD LBS.
ROD FOR SERVICE TEMPS.
SIZE 650F 750F
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
FIG. 100
ALL THREAD ROD FULL. LENGTHS
TOL o
INCOPO1ATD
CORONA. CA • (909) 737.5599 15
FIG. 2 ADJUSTABLE RING HANGER
FIG, 2 NFPA ADJUSTABLE RING HANGER WITH REDUCED ROD SIZE
Size Range - 1/2 thru 6 inch pipe.
Material - Carbon Steel, Mu. Galvanized to G-90
specification.
Function - For general piping purposes. Knurled
swivel nut design permits hanger adjustment after
installation. Spring tension on swivel nut holds it
securely in hanger before installation. Swivel nut
easily removed.
Approvals - Underwriters' Laboratories listed and
Factory Mutual Engineering approved. Conforms
to Federal Specification WW-H-171E, type 10, and
Manufacturers Standardization Society SP-69,
type 10.
Maximum Temperature .650'F
Finish - Mil. Galvanized and Stainless Steel.
Order By - Figure number and pipe size.
PIPE ROD STOCK
MAX.
REC. APPROX. WEIGHT PER 100
FIG. 2
SIZE SIZE A B C SIZE LOAD LBS. FLG.2 NFPA
1/2 3/8 3.1/8 2-5/8 1.3/8 16gax1 400 17 17 ..i;:.•. ......... •.. . ....
- /4
1 3/8 3-3/8 2-5/8 1-1/8 169ax1 400 18 18
j
1-1/2 3/8 3-7/8 2.7/8 1 169ax1 400 21 21
t. 4 a6a1 400
1/2 2-1/2 * 5-3/4 4-1/4 1.5/8 149ax1-3/16 600 41 40
3 /2' 4 1/8 jt-14 ,. J4j1 23,'6 600
3-1/2 112* 7.3/8 5-1/4 2.1/8 14a>1-3/16 600 52 50
';•.1 ., .. .... .......
u .. . 'Lt 1/4 . . .. . . ....... ... . .,; . 1000
5 5/8 9 6-1/8 2.1/4 l2gaxl.1/4 1250 L! -
97 95
3/8 nut is used when NFPA rod sizing is requested.
1I2" nut is used when NFPA rod sizing is requested.
/\
1I I
I 1'
_.
TOLCO
- INCORPORATED
1.20 CORONA, CA • (909) 737-5599
FIG. 1000
"FAST CLAMP" SWAY BRACE ATTACHMENT
Size Range - Pipe size to be braced: 1" through 8"
Sch. 10 and 40. Pipe size used for bracing: 1" and
1-1/4" Sch. 40 IPS.
Material - Carbon Steel
Function - For bracing pipe against sway and
seismic disturbance. The pipe attachment com-
ponent of a sway brace system: Fig. 1000 is used
in conjunction with a Tolco 900 Series Fitting and
joined together with bracing pipe per NFPA H3*,
forming a complete sway brace assembly.
Features - Can be used to brace Schedules 10 and
40 IPS.
Field adjustable, making critical pre-engineering of
bracing pipe unnecessary.
Unique design requires no threading of bracing
pipe.
Can be used as 4-way riser brace.
Can be used as longitudinal brace.
All steel construction eliminates structural
deficiencies associated with casting type sway
brace fittings.
Comes individually packaged with illustrated
installation instructions - sizes are clearly marked.
Steel leaf spring insert provided to assure installer
and inspector that necessary minimum torque
(5 lb/It) has been achieved.
Application Note - Fast Clamp need not be field
assembled. Position Fast Clamp and tighten two
hex nuts until leaf spring flattens.
*Length of bracing pipe per National Fire
Protection Association, Pamphlet #13, paragraph
A-3-10.3.5: 1" Schedule 40 bracing pipe maximum
7'-2". 1-114" Schedule 40 bracing pipe maximum
9'-2".
Approvals - Underwriters' Laboratories listed.
Note - Must be used with Tolco U.L. Listed 900
Series attachment.
Finish - Plain, Electro-Galvanized, HDG, and
Stainless Steel.
Order By - Order first by pipe size to be braced
followed by pipe size used for bracing, figure
number, and finish.
/ D
TOLCO
INCORPORATED
118 CORONA. CA • (909) 737.5599
FIG. 910
SWIVEL SWAY BRACE FITTING
Size Range - 1 & 1.1/4 inch bracing pipe.
Material - Carbon Steel
Function - For bracing pipe against sway and
seismic disturbances. The building attachment
component of a sway brace system; The Fig. 910 is
used in conjunction with the Fig. 1000 "Fast
Clamp" (or with a Fig. 4A Pipe Clamp), and joined
together with a brace pipe per NFPA #13*.
Features - Universal swivel design allows Fig. 910
to be attached at any surface angle. All steel
construction eliminates deficiencies associated
with casting type attachments.
Application Note - *Length of bracing pipe per
National Fire Protection Association Pamphlet
#13, paragraph A-3-10.3.5: 1" Schedule 40 bracing
pipe maximum 7-2". 1-1/4" Schedule 40 bracing
pipe maximum 9'.2"
Approvals - Underwriters' Laboratories listed.
Note -The Fig. 910 Swivel Attachment and the Fig.
1000 "Fast Clamp" (or Fig. 4A Pipe Clamp), make
up a sway brace system of U.L. Listed attachments
and bracing materials which satisfies the
requirements of- Underwriters' Laboratories and
the National Fire Protection Association (NFPA).
Finish - Plain, EleotrQ-3alvanized, and Stainless
Steel.
Order By - Figure number, pipe size, and finish.
Note - Specific weight load conditions may require
more than one fastener to the building structure.
Swau brace attachments may be ordered with
D A? ME r10L WI SIZE A B C SIZE E F PER 100
2 1-1/2 3 9/16 2-5/16 2 88
. ..9/:16 2-5/16 ..2..5/16 1.
BRECCO Brecco Corporation
- - >GAUGES(
GAUGES
FOR USE WITH WET OR DRY
SYSTEMS. GAUGES HAVE A
BRONZE BURBON TUBE
MOVEMENT IN A STAINLESS
STEEL PLATED CASE
(UNLESS OTHERWISE
NOTED). 3-1/2" DIAMETER.
U.L. AND F.M. APPROVED
(UNLESS OTHERWISE
NOTED).
Pan No. Description Bo*cajj
aly
- GAAWSS350 AIR / WATER 0.300 PSI 60 - Wi STAINLESS STEEL CASE
GMSS250 AIR W/ RETARD 250 PSI
3-Wo DIA, W/ STAINLESS STEEL 60 CASE
GAWP200 2" RESIDENTIAL GAUGE 300 PSI
1 00 (NOT UI. OR F.M. APPROVED)
GMWP350 AIR I WATER WI PLASTIC CASE 60
1-800543-4194 Paz: 1-877474-9248 AR AS REQUIRED
bwccocorp@earthiink.net
02000
FIG. 51
FIG. 51 for NFPA Rod and Fastener Sizing
Q:9 Mh
INCORPORATED
CORONA. CA • (909) 737-5599 41
FIG. 51 AND FIG. 52
SIDE BEAM BRACKETS (CONT.)
APPROX.
PIPE ROD HOLE SIZE STOCK WEIGHT
SIZE - SIZE A B C H-i H-2 SIZE PER 100
1/2 -2 3/8 2 3/4 2 7/16 7/16 3/16x2 35
T4r, , - 3/4 9/6 7/16 /16x2
5-6 1/2 2.1/2 3/4 2.1/2 9/16 L 9/16 3/8x2.1/2x2.1/2
,
71
3/8.x2 1/2x2 1/2 7Q I
FIG. 52 - 6 Hole Bracket
APPROX.
ROD HOLE SIZE STOCK WEIGHT
SIZE A B C H-i H-2 H.3 SIZE PER 100
3/8x1/2 2 1-1/16 29/16 7/16 9/32 3/16x2 35
FIG. 56
TAPPED SIDE BEAM CONNECTOR
Size Range - 1/2 thru 4 inch pipe (3/8 inch rod).
Material - Carbon Steel
Function - Practical and economical bracket used
to support hangers from steel or wood beams. Can G be used with concrete shot-type inserts. Tapped
hole allows easy adjustment of hanger rod.
Approvals - Underwriters' Laboratories listed and E
Factory Mutual Engineering approved for 1/2 . 4" A H
pipe. 4( Finish - Plain, Electro-Galvanized, HDG, and F Stainless Steel.
Order By - Figure number and finish. I '0 Note -Per NFPA #13: 1/2 thru 2 inch pipe use 3/8
inch fastener; 2.1/2 thru 4 inch pipe use 1/2 inch
lastener.
ROD APPROX, PIPE SIZE HOLE SIZE STOCK WEIGHT SIZE A B C D E F G H J SIZE PER 100
1/2 -4 2-5/83/8 1 3/8 1.1/16 1-1/8 7/16 9/16 1-1/4 1/4x1 20
Schedule-1O/Schedule-40
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-10/Schedule4() sprinkler pipe you get a UL listed and FM approved product. Although these
products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (l"- 8") pipe and Sch-40.(l"-- 214") pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Schedule- 10/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A-123.
Our advanced formula mill coating of-
fers a clean, durable surface It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF'. In scientific laboratory
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
American Made
Meets "Buy American" requirement
and is available through distributors in
the USA Canada and Mexico.
Sch-40 Specifications
NPS Nominal I.D. WI. WI. (1120 Fitted) Pcs/ WtlLlft (21') WIILIft (24') WVUft (25')
In; mm In; mm Lbsfft; Kg/rn Lbs/Pt; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
ill 1.049 1.680 2.05 70 21470 2,822 2,940
25 26.6 2.5 3.05 70 1,120 1,280 1,334
1W 1.380 2.270 2.93 51 2,431 2,778 2,894
32 35.1 4.36 4.36 51 1,103 1,260 1,313
1W 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
2' 2.067 3.650 5.13 30 2,300 2,628 2,738
50 52.5 5.4 7.63 30 1,043 1,192 1,242
2W 2.469 5.790 7.86 19 2,310 2,640 2,750
65 62.7 8.6 11.73 19 1,048 1,197 1,247
3[sI Specifications
NPS Nomlnall.D. WI. Wt. (H20Riled) No/ WVLift(21') WIND (24') WI/Uft(25')
In; mm In; mm LbslFt; Kg/rn Lbs/Pt; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.097 1.400 1.81 91 2,675 3,053 3,185
25 27.9 2.1 2.70 91 1,213 1,385 1,445
1¼' 1.442 1.810 2.52 61 2,319 2,664 2,760
32 36.6 2.7 3.75 61 1,052 1,208 1,252
1i12" 1.682 2.080 3.04 61 2,664 3,045 3,172
40 42.7 3.1 4.52 61 1,208 1,381 1,439
2.157 2.640 4.22 37 2,051 2,344 2,442
50 54.8 3.9 6.28 37 930 1,063 1,108
2W 2.635 3.530 5.89 30 2,224 2,542 2,648
65 66.9 5.3 8.77 30 1,009 1,153 1,201
3" 3.260 4.330 7.94 19 1,728 1,975 2,057
80 82.8 6.4 11.82 19 784 896 933
4' 4.260 5.610 11.78 19 2,238 2,558 2,665
90 108.2 8.3 17.53 19 1,015 1,160 1,209
5" 5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
6' 6.357 9.290 23.03 10 1,951 2,230 2:322
150 161.5 13.8 34.27 10 885 1,012 1,053
8' 8.249 16.490 40.15 7 2,424 2,770 2,885
200 209.5 24.5 59.75 7 1,100 1,256 1,309
Schedule-10/Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
Welded Outlets
Hydrostatic Pressure
Side Wall Rupture
Vibration Test
tqctl/F/ow Control Qr allied
TUBE & coiourr
@ <~> 9
Listed Approved Listed
16100 S. Lathrop • Harvey, IL 60426 Customer Service:
11350 Norcom Rd. - Philadelphia, PA 19154 (800) 882-5543
2525 N. 27th Ave. • Phoenix, AZ 85009 FaX 708-339-1806
S5-3
tqcci /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series LFII Residential
Pendent Sprinklers
49 K-factor
Customer Service/Sales:
Tel: (414) 570-5000 / (800) 558-5236
Fax: (414) 570-50101(800) 877-1295
General
Description
The Series LFII (1Y2234) Residential
Pendent Sprinklers are decorative,
fast response, frangible bulb sprinklers
designed for use in residential occu-
pancies such as homes, apartments,
dormitories, and hotels. When aesthet-
ics and optimized flow characteristics
are the major consideration, the Series
LFII (TY2234) should be the first
choice.
The Series LFII are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 13D; wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series LFII (1Y2234) has a 4.9
(70,6) K-factor that provides the re-
quired residential flow rates at reduced
pressures, enabling smaller pipe sizes
and water supply requirements.
The recessed version of the Series
LFII (TY2234) is intended for use in
areas with finished ceilings. It employs
a two-piece Style 20 Recessed Es-
cutcheon. The Recessed Escutcheon
provides 1/4 inch (6,4 mm) of recessed
adjustment or up to 1/2 inch (12,7 mm)
of total adjustment from the flush ceil-
ing position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the pipe nipples
to the sprinklers must be cut.
The Series LFII (1Y2234) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
WARNINGS
The Series LFII (TY2234) Residential
Pendent Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with The applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities haying jurisdic-
tion. Failure to do so may impair the
integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Sprinkler/Model
Identification
Number
SIN TY2234
Technical
Data
Approvals:
UL and C-UL Listed.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient:
K = 4.9 GPM/ps11'2 (70,6 LPMIbarl/2)
Temperature Rating:
155°F/68°C or 175°F/79°C
Finishes:
White Polyester Coated,
Chrome Plated, or Natural Brass
Physical Characteristics:
Frame .............Brass
Button .............Bronze
Sealing Assembly . ..........
Beryllium Nickel w/Teflont
Bulb .........3 mm dia. Glass
Compression Screw .....Bronze
Deflector ...........Bronze
Ejection Spring . . . Stainless Steel
tDuPont Registered Trademark
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb allowing the sprinkler to
activate and flow water.
Page 1 of 8 JANUARY, 2003 TFP400
Page 2 of 8 TFP400
Minimum Flow (b) and Minimum Flow (b) and Minimum Flow (b) and
Maximum Maximum Residual Pressure Residual Pressure Residual Pressure
Coverage Spacing For Horizontal Ceiling For Sloped Ceiling For Sloped Ceiling
Area (a) Ft. (Max. 2 inch Rise (Greater Than 2 Inch Rise (Greater Than 4 inch Rise
Ft. x Ft. (m) for 12 Inch Run) Up To Max. 4 Inch Rise for 12 Inch Run) Up To Max. 8 Inch Rise for 12 inch Run)
(m x m) 155"F168°C or 155°F/68°C 175"F179°C 155°FI68C 175°F179"C 175°F179°C
12 x 12 12 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 17 GPM (643 LPM) 13 GPM (49,2 LPM) 18 GPM (68,1 LPM) (3,7 x 3,7) (3,7) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 7.0 psi (0,48 bar) 13.5 psi (0,93 bar)
14 x 14 14 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 13 GPM (49,2 LPM) 18 GPM (68,1 LPM) (4,3 x 43) (4,3) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 7.0 psi (0,48 bar) 13.5 psi (0,93 bar)
16 x 16 16 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 13 GPM (49,2 LPM) 18 GPM (68,1 LPM) (4,9 x 4,9) (4,9) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 7.0 psi (0,48 bar) 13.5 psi (0,93 bar)
18 x 18 18 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) 23 GPM (87,1 LPM) (5,5 x 5,5) (5,5) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 22.0 psi (1,52 bar)
20 x 20 20 20 GPM (75,7 LPM) 20 GPM (75,7 LPM) 20 GPM (75,7 LPM) 21 GPM (79,5 LPM) N/A (6,1 x 6,1) (6,1) 16.7 psi (1,15 bar) 16.7 psi (1,15 bar) 16.7 psi (1,15 bar) 18.4 psi (1,27 bar)
For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated
using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A
NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII (TY2234)
RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS
Design
Criteria
The Series LFII (TY2234) Residential
Pendent Sprinklers are UL and C-UL
Listed for installation in accordance
with the following criteria.
NOTE
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the localAuthority having Juris-
diction.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of "design sprinklers" as speci-
fied in NFPA 130 or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Table A for
NFPA 130 and 13R as a function of
temperature rating and the maxi-
mum allowable coverage area.
A minimum dischargeofo.1 gpm/sq.
ft over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity. The sprin-
klers are to be installed with a deflector
to ceiling distance of 1-3/8 to 4 inches
or in the recessed position using only
the Style 20 Recessed Escutcheon as
shown in Figure 2.
NOTE
So as to help avoid obstructions to
water distribution, a maximum 12 inch
deflector-to-ceiling distance is permit-
ted for NFPA 13D and NFPA 13Rap-
plications where the sprinklers are lo-
cated in closets.
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
length of the coverage area (Ref. Table
A) being hydraulically calculated (e.g.,
maximum 12 feet for a 12 ft. x 12 ft.
coverage area, or 20 feet for a 20 ft. x
20 ft. coverage area).
Beam Ceiling
Design Criteria
The Series LFll (TY2234) Residential
Pendent Sprinklers are UL and C-UL
Listed for installation in residential oc-
cupancies with horizontal ceilings (i.e.,
slopes up to a 2 inch rise over a 12 inch
run) with beams when installed in ac-
cordance with the following criteria:
General Information. The basic con-
cept of this protection scheme is to
locate the sprinklers on the underside
of the beams, Ref. Figure 5, (not in the
beam pockets); to identify the main
beams that principally run in one direc-
tion as "primary beams"; and, to iden-
tify the beams that run principally per-
pendicular to the main beams, as may
be present (or in some cases may be
necessary for proper sprinkler protec-
tion), as "secondary beams".
Primary and Secondary Beam
Types. Solid surface, solid or hollow
core, combustible or non-combustible.
Primary and Secondary Beam Posi-
tioning. Directly attached to the un-
derside of a combustible or non-com-
bustible smooth ceiling at any
elevation.
Primary Beam Cross-Section: Maxi-
mum depth of 14 inches and the maxi-
mum width is unlimited. The cross-sec-
tional shape of the primary beam may
be rectangular to circular.
- 2-7/8" DIA. -
7/16±1/8' (73,0 mm) I 1/2"(12,7mm)
(11,1±3,2 mm) 2-1/4" DIA. I 1/4(64mm) I
I FACE OF mm)
I SPRINKLER 1572 MOUNTING I FITTING PLATE
j •3
MOUNTING
SURFACE
////#//\7j
(3.2 mm)
1-3/8(34,9 mm) ! CLOSURE TY2234 1-1/8" (28,6 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON
FOR USE WITH THE SERIES LFII (TY2234)
RESIDENTIAL PENDENT SPRINKLER
TFP400 Page 3 of 8
7/16(11,1 mm) 1/2 ESCUTCHEON
_________ 2-7/8' DIA.
I- Frame MAKE-IN SURFACE
2 - Button
(73.0 mm)
4-Bulb
-1/4"
6 - Compression 2
2 Screw
Components: NOMINAL NPT PLATE SEATING
_T
3 - Sealing Assembly
Deflector * '
' _________
(57,2 mm) \J
Ejection Spring
(41,3 mm) WRENCH STYLE 20
RECESSED I
Temperature FLATS ESCUTCHEON
*
rating is indicated on
Deflector.
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
SERIES LFII (TY2234) RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS
Secondary Beam Cross-Section.
Maximum depth to be no greater than
the primary beam and the maximum
width is unlimited. The cross-sectional
shape of the secondary beam may be
rectangular to circular.
Primary Beam Spacing. The primary
beams (Fig. 6A) are to be 3 ft. - 4 in. to
6 ft. from the compartment wall to cen-
ter of the nearest beam and from cen-
ter to center between beams.
Secondary Beam Spacing. The sec-
ondary beams principally run perpen-
dicular to the primary beams.
Secondary beams of a depth equal to
the primary beam must be placed so
that the beam pockets created by the
primary beams do not exceed 20 feet
in length (Fig. 613).
NOTE
When the beam pockets created by
the primary beams exceed 20 feet in
length, the installation will require the
use of secondary beams as described
above. Otherwise, secondary beams
need not be present.
Secondary beams of a cross-sectional
depth greater than one-quarter the
depth of the primary beams are to be
a minimum of 3 ft. - 4 in. from the
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W- TYPE 7 RECESSED
SPRINKLER WRENCH
compartment wall to center of the
nearest beam and from center to cen-
ter between beams (Fig. 6C).
Secondary beams of a cross-sectional
depth no greater than one-quarter the
depth of the primary beams may be
placed at any compartment wall to
center of the nearest beam distance
/
> NCH RECESS
(END A" USED
FOR TY2234)
FIGURE 3
W- TYPE 6
SPRINKLER WRENCH
Page 4 of 8 TFP400
and from any center to center distance
between beams (Fig. 6C).
Lintels. Lintels over doorways exiting
the compartment must be present. The
minimum height for the lintels is B
inches or no less than the depth of the
Primary Beams, whichever is greater.
Sprinkler Types. Series LFll
(1Y2234), 155F and 175F, Pendent
and Recessed Pendent Residential
Sprinklers.
Sprinkler Coverage Area and Hy-
draulic Design. The sprinkler cover-
age areas and hydraulic design criteria
as presented in the Table A for Hori-
zontal Ceilings" are to be applied.
Sprinkler Position. The deflector to
bottom of primary beams for the Series
LFII (TY2234) Pendent Sprinklers or
Series LFll (TY2234) Recessed Pen-
dent Sprinklers is to be 1-1/4 to 1-3/4
inches (Fig. 5A). The vertical center-
line of the Series LFII (TY2234) Pen-
dent Sprinklers is to be no greater than
half the primary beam cross-sectional
width plus 2 inches from the centerline
of the primary beam (Fig 5B).
NOTES
Core drilllng of beams to allow the in-
stallation of sprinkler drops requires
consulting with a structural engineer.
Where core drilling is not permitted,
the previously stated sprinkler position
criteria for the Series LFII (TY2234)
Pendent Sprinklers allows for the
sprinkler drop to be placed adjacent to
the primary beam.
Beam and Soffit Arrangements. A
soffit is permitted to be placed around
the perimeter of a compartment with
the beam arrangement within the sof-
fited area (Fig.7).
The cross-section of the soffit may be
any size as long as it does not create
an obstruction to water distribution per
the obstruction rules of NFPA 13 for
residential sprinklers.
When soffits are present, the pre-
viously provided 3 ft. - 4 in. to 6 ft.
"compartment wall to adjacent beam"
distance for the primary and secon-
dary beams is to be measured from the
face of the soffit as opposed to the
compartment wall.
NOTE
Although the distance to the beams is
measured from the face of the soffit,
the sprinkler coverage area is to be
measured from the compartment wall.
Installation
The Series LFll (1Y2234) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6mm).
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series LFII Pendent Sprinklers
must be installed in accordance with
the following instructions.
Step 1. Pendent sprinklers are to be
installed in the pendent position with
the deflector parallel to the ceiling.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 3).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats.
The Series LFII Recessed Pendent
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step A. Recessed pendent sprinklers
are to be installed in the pendent posi-
tion with the deflector parallel to the
ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 4). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step D. After the ceiling has been in-
stalled or the finish coat has been ap-
aqR
1Y2234
LO
MAXIMUM TY2234 ONE-HALF BEAM
WIDTH PLUS
2' (50.8 mm)
FIGURES
SPRINKLER POSITIONING
UNDER PRIMARY BEAMS
(Refer to the "Beam Ceiling
Design Criteria" section)
plied, slide on the Style 20 Closure
over the Series LFll Sprinkler, and
push the Closure over the Mounting
Plate until its flange comes in contact
with the ceiling.
TFP400 . Page 5 of 8
ALL FIGURES: -.--A A_-.
A—.-
DISTANCES ARE
MEASURED TO
COMPARTMENT 14(356mm)
MAXIMUM
WALL FACES AND
TO CENTERLINES
FOR PRIMARY BEAMS HAV-
ING A 14" (356 mm) MAXIMUM
DEPTH
PRIMARY
MAXIMUM
COMPARTMENT
WALLS
FIGURE 6A
PRIMARY BEAM SPANS UP TO 20-0 (6.1 m)
A_JA -IA k
A=3-4to6'-O"(1.Oto1.8m)
FOR PRIMARY BEAMS HAV-
SECONDARY B INC A 14(356mm) MAXIMUM
BEAM DEPTH
B = 204 (6.1 m) MAXIMUM
FOR SECONDARY BEAMS
THAT ARE TO BE EQUAL IN
PRIMARY DEPTH TO PRIMARY BEAMS
BEAM AND THAT MUST BE IN PLACE
. SO THAT PRIMARY BEAM
POCKETS DO NOT EXCEED
20'-0"(6.1 m)
COMPARTMENT
WALLS .
FIGURE 68
PRIMARY BEAM SPANS GREATER THAN 29-0"(6.1 m)
H—A - AI A—
C A = 3-4 to 6-0 (1.0101.8 m)
FOR PRIMARY BEAMS HAV-
ING A 14" (356 mm) MAXIMUM
SECONDARY . C DEPTH
BEAM C = 3-4(1.0 m) MINIMUM FOR \ SECONDARY BEAMS HAVING
DEPTHS GREATER THAN 25116
OF PRIMARY BEAMS
PRIMARY*
. —or—
BEAM C = ANY DISTANCE FOR SEC-
ONDARY BEAMS HAVING
DEPTHS UP TO 25% OF * REFER TO PRIMARY BEAMS
FIGURE 6B COMPARTMENT
FOR SPANS WALLS
EXCEEDING ..... , -•.•.-• -.: -...
20'-0"(6,1 m)
FIGURE 6C
COMBINATIONS OF PRIMARY AND SECONDARY BEAMS
FIGURE 6
BEAM ARRANGEMENTS
(Refer to the 'Beam Ceiling Design Criteria" section)
Page 6of8 TFP400
Care and
Maintenance
The Series LFII (TY2234) must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Absence of an Escutcheon Plate may
delay the sprinkler operation in a fire
situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing It with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
NOTE
The owner must assure that the sprin-
klers are not used for hanging of any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
It is recommended that automatic
sprinkler systems be,inspected,
tested, and maintained by a qualified
Inspection Service.
TFP400 Page 7 of 8
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability..
Sprinkler Assembly:
Series LFII (TY2234), K=4.9, Residen-
tial Pendent Sprinkler with (specify)
temperature rating and (specify) finish,
P/N (specify).
155F/68'C or
Chrome Plated .........P/N 51-201-9-155 155°F/68'C
White Polyester ........P/N 51-201-4.155
155'F/68C
Natural Brass ..........P/N 51-201.1-155
175Ff79'C or
Chrome Plated .........P/N 51-201-9-175
175°F/79C
White Polyester ........P/N 51-201-4-175 175'F/79'C
Natural Brass ..........P/N 51-201-1-175
Recessed Escutcheon:
Specify: Style 20 Recessed Escutch-
eon with (specify) finish, P/N (specify).
1/2 (15 mm)
Style 20
Chrome Plated .........P/N 56-705-9-010
1/2' (15 mm)
Style 20
White Color
Coated ...............P/N 56-705-4-010
1/2' (15 mm)
Style 20
Bright Brass
Coated ...............PIN 56-705-2-010
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Page 8 of 8 TFP400
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqCO /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
A®
Oem
Customer Service/Sales:
Tel: (414) 570-5000/(800) 558-5236
Fax: (414) 570-5010/(800) 877-1295
Series TYFRB - 2,8,4.2,5.6, and 80 K-factor
Upright, Pendent, and Recessed Pend ent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping mails, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TV-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TV-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any otherauthorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Model/Sprinkler
Identification
Numbers
TY1131 - Upright 2.81K, 1/2NPT
TY1231 - Pendent 2.81K, 1/2'NPT
TY2131 - Upright 4.21K, 1/2'NPT
TY2231 - Pendent 4.2K, 1/2 'NPT
TY3131 - Upright 5.61K, 1/2NPT
TY3231 - Pendent 5.61K, 112"NPT
TY4131 - Upright 8.01K, 3/4'NPT TY4231 - Pendent 8.01K, 3/4'NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
-,
. ....-, r •r
;.....:-'
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/p5i1/2 (40,3 LPM/bari12)
K = 4.2 GPM/psi1/2 (60,5 LPM/bar1/2)
K = 5.6 GPM/psi112 (80,6 LPM/barl'2)
K = 8.0 GPM/psi1'2 (115,2 LPM/bar112)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ............Bronze
Button ........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflonf
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .........Bronze
to E
E 0 a.
Page 1 of 8 APRIL, 2003 TFPI7I
ESCUTCHEON 7/16"(11,1 mm) STYLE 10or20
PLATE SEATING NOMINAL RECESSED
SURFACE kiflY MAKE-IN ESCUTCHEON
1..—
W
FLATS
RENCH
2-7/8 (73,0 mm) DIA.
RECESSED PENDENT
SSP DEFLECTOR *
PENDENT
SSU*
DEFLECTOR
6* I
7/16° I
NOMINAL I : MAKE-IN
11,1mm
1 2-3/16°
$ (55,6 mm)
1/2° NPT** I
UPRIGHT CROSS SECTION
ESCUTCHEON
PLATE SEATING
SURFACE
T_
2-3/16° \-
(55,6 mm)
1-1/2°
(38,1 mm)
7/16"(11,1 mm) STYLE 10or20
NOMINAL RECESSED
MAKE-IN ESCUTCHEON 1/2° **
NPT
SSP DEFLECTOR*
PENDENT
\[WRENCH
--
FLATS
27/80 (73,0 mm) DIA. -I
RECESSED PENDENT
Page 2 of 8 TFPI 71
SSU* I
DEFLECTOR I
61
7/160 1
5I
(11,1 mm) I
NOMINAL I
MAKE-IN
I 2-3/16
(55,6 mm)
1
1/2° NPT** t 7
UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5- Compression 7 - Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TV-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
- Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TV2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
7/160 (11,1 mm)
1/2 ** NOMINAL
NPT MAKE-IN
6*
1
2-7/8 (73,0 mm) DIA
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16° \T
(55,6 mm)
1-1/2°
(38,1 mm)
SSP DEFLECTOR *
STYLE 100r20
RECESSED
ESCUTCHEON Ut-LUIUH
mm) I
NAL ;rN(
°
IN 2-3/16°
WRENCH (55,6 mm)
FLATS
1/2' NPT
STYLE 30 or 40
RECESSED SSU* ESCUTCHEON DEFLECTOR
..*
1/2° I
(12,7 mm) I
NOMINAL I
MAKE-IN
_4
: 2-1/4°
(57,2 mm) / 3
3/4k NPT I
UPRIGHT CROSS SECTION
1E I
WRENCH
FLATS
-7/8"(73,0 mm) DIA.
ESSED PENDENT
TFPI7I Page 3 of 8
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
- Frame 3 - Sealing 4 - Bulb 6 - Deflector - Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT(TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2° (12,7 mm)
PLATE SEATING 3/4fl ** NOMINAL
SURFACE MAKE-IN
2-5/16°
NPT
(58,7mm)
1-9/16°
I (39,7 mm)
SSP DEFLECTOR * L 2
e
PENDENT REC
1 - Frame 3- Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TV-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Page 4 of 8 TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE
IPOLYESTER
2.8
1/2
PENDENT
(TY1231)
and
UPRIGHT
(TY1131)
135°F/57°C Orange
12,3,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
NPT RECESSED
PENDENT
(TY2231)°
Figure 5
135°F/57°C Orange
1, 2, 5
155°F/681C Red
175°F/79°C Yellow
200°F/93°C Green
RECESSED
PENDENT
(TY2231)"
Figure 6
135°F/57°C Orange
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
4.2
1/2°
NPT
PENDENT
(TY2231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1,2
155°F/681C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
RECESSED
PEN DENT
(TY2231)°
Figure 7
135°F/57°C Orange
155°F/68° C Red
175°F/79°C Yellow
200°F/93°C Green
RECESSED
PENDENT
(TY2231)°°
Figure 8
135°F/57°C Orange
155°F168°C Red
175°F/79°C Yellow
200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2U NPT) or Style 40 (3/4 NPT) 3/4° Total Adjustment Re-
cessed Escutcheon, as applicable.
** Installed with Style 20(1/2° NPT) or Style 30 (3/4° NPT) 1/2° Total Adjustment Re-
cessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to all colors (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/570C to 3/32
inch (2,4 mm) for the 286°F/141 °C
temperature ratings.
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ftibs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft. lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft lbs. (40, 7Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
TFPI7I Page 5 of 8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE
1POLYESTER
LEAD
COATED
5.6
1/2°
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1. 2.3,4,5.6 12,3,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286F/141°C Blue
NPT RECESSED
PENDENT
(TY3231)°
Figure 9
135°F/571C Orange
1,2,4,5 N/A
155°F/68°C Red
175°F/791C Yellow
200°F193°C Green
RECESSED
PENDENT
(TY3231)**
Figure 10
135°F/57°C Orange
1,2,3,4,5
I I
I 1,2,4,5 I
Green
N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C
8.0
3/4',
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135°F/57°C Orange
/
1,2, 3,4,5, 6
1,2,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
NPT RECESSED
PENDENT
(TY4231)°
Figure 11
135°F/57°C Green
1,2,4,5 N/A
155°F/68°C Orange
1751F/79°C Red
200°F/93°C Yellow
RECESSED
PENDENT
(1Y4231)"
Figure 12
135°F/57°C Orange
1,2,3,4,5 N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB) as Quick Response Sprinklers; however, the LPC does not rate the thermal
sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2 NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to all colors (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Page 6 of 8
- 2-7/8" DIA.
5/8±1/4" (73.0 mm) I 314"(19,1 mm)
(15.9±6.4 mm) 2-1/4" DIA. I 1/4" (6.4 mm) I
FACE OF MOUNTING I PLATE I
FITTING
1/8"
SPRINKLER
I
fm)
MOUNTING
SURFACE/
CLOSURE SERIES 1-5/16" (33.3 mm)
TY-FRB 13/16"(20.6 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8 DIA. -
5/8±1/4"
(73.0 mm) 3/4(19.1 mm)
(15.9±6.4 mm) 2-1/4 DIA. I 1/4(6.4mm) I
FACE OF MOUNTING I
SPRINKLER PLATE I
FITTING
_
MOUNTING
SURFACE
CLOSURE /
.i.
SERIES 1-1/4" (31.8 mm)
TY-FRB 3/4" (19.1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
- 2-7/8 DIA.
1/2±1/8" I (73,0 mm) 1/2"(12,7 mm) r (12,7±3.2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
SPRINKLER PLATE I
FACE OF
157.2 mm) -1
MOUNTING I
FITTING
(3.2mm) I
______ I
CLOSURE SERIES 1-5/16'.
_______
1/8" I
ftMOUNTING
SURFACE
(33,3 mm)l
TY-FRB 1-1/16"(27.0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA. - (73.0 mm) 1/2±1/8" I 1/2(12,7mm) r (12.7±3.2 mm) 2-1/4" DIA. 1/4'(6.4 mm) I I FACE OF MOUNTING _ I SPRINKLER PLATE I FITTING
1/8"
(3.2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4(31,8 mm) 1
TYFRB 1"(25.4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFPI7I
- 2-7/8" DIA. -
5/8±1/4" (73.0 mm) 3/4(19.1 mm)
(15.9±6.4mm) - 2-1/4" DIA. 1/4(6,4 mm) ]
FACE OF MOUNTING SPRINKLER PLATE FITTING
(3.21
MOUNTING
SURFACE/
SERIES 1-1/4(31.8mm) CLOSURE TY-FRB iv (19.1 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
5/8±1/4" (73.0 mm) I 314"(19.1 mm)
- (15.9±6.4 mm) 2-1/4 DIA. 1/4"(6.4 mm) I
I I (57.2 MOUNTING FACE OF
SPRINKLER PLATE
FITTING
1(8"
_ __________ (3.2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"(333 mm)
TYFRB 13116"(20.6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 7 of 8
2-7/8 DIA.
(73.0 mm) I
1/2±1/8" I 1/2"(12,7 mm) r (12.7±32 mm) 2-1/4" DIA. I 1/4'(6.4 mm) I
I SPRINKLEqR PLATE I
FACE OF mm) MOUNTING
FITTING
1/8
__________
I \
MOUNTIN
SURFACESERIES
1-1/4(31.8mm) CLOSURE TYFRB 1'(25.4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
1/2±1/8" (73.0 mm) I 1/2(12.7mm) I r (12.7±3.2 mm) 2-1/4" DIA. I 1/4" (6.4 mm) I I I (57.2 I FACE OF MOUNTING I SPRINKLER I PLATE I I FITTING
(3.2
"
__
1/8
mm)
//#_
4
I \
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm
TY-FRB 1-1/16"(27.0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4' NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
- - WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
P/N 57- XXX
MODEL/SIN
IPERATU
RATING
I l
Page 8 of 8 TFPI7I
330 2.8K UPRIGHT (1/2NPT) TY1131
331 2.8K PENDENT (1/2NPT) 1Y1231
340 4.2K UPRIGHT (1/2'NPT) 1Y2131
341 4.2K PENDENT (1/2NPT) 1Y2231
370 5.61K UPRIGHT (1/2"NPT) 1Y3131
371 5.6K PENDENT (1/2°NPT) TY3231
390 8.0K UPRIGHT (3/4'NPT) TY4131
391 8.0K PENDENT (3/4'NPT) TY4231
SPRINKLER
1 NATURAL BRASS
4 WHITE POLYESTER
9 CHROME PLATED
7 LEAD COATED
135 1 135"F/57°C
155 155°F/68°C
175 175°F/79"C
200 200°F/93"C
286 286°F/141"C
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
Ordering
Procedure
When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2' (15 mm)
Style 10
Chrome Plated .........P/N 56-701-9-010
1/2' (15 mm)
Style 10
White Color
Coated ................PIN 56-701-4.010
1/2' (15 mm)
Style 10
Brass Plated ...........P/N 56-701-2-010 1/2' (15 mm)
Style 20
Chrome Plated .........P/N 56-705-9-010
1/2' (15 mm)
Style 20
White Color
Coated ................P/N 56-705-4-010
1/2' (15 mm)
Style 20
Brass Plated ...........P/N 56-705-2-010 3/4'P(20 mm)
Style 30
Chrome Plated .........P/N 56-705-9-011
3/4' (20 mm)
Style 30
White Color
Coated ................P/N 56-705-4-011 3/4 (20 mm)
Style 30
Brass Plated ...........P/N 56-705-2-011
3/4" (20 mm)
Style 40
Chrome Plated .........P/N 56-700.9-010 3/4 (20 mm)
Style 40
White Color
Coated ................P/N 56-700-4-010 3/4' (20 mm)
Style 40
Brass Plated ...........PIN 56-700-2-010
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqcol
Flow I Tyco Fire
Control I Products
BlazeMaster',?
FIRE SPRINKLER PIPE & F:rnNGs SUBMITTAL SHEET
Tyco ARE PRODUCTS
451 North Cannon Avenue
Lansdale Pennsylvania 19446
wwwtyco-flr.com
TECHNICAL SEH&%S5
Tn.. (800) 381-9312' FAX (800) 7914500
E-MAIL: techseWtycofp.Cam
NO. 19-1.5
TD9IS
4-1.1.20
9/2001
Tee
Part No. Size Sch. 1/0 I Wt.
80000 3/0 40 /° 1 0.11 lb.
80001 1° 40 3/40 0.19 lb.
80002 11/4' 40 'I" 0.26 lb.
80003 11/20 80 1° 0.51 lb.
80004 20 80 1/." 0.90 lb.
80005 21!2" 80 V/,6" 1.59 lb.
80006 3° 80 1"/ie1. 2.41 lb.
'Part'
I -No. I Size I Sch.
I
I 1/0 iWtl
lb. I 1112 F 80015 I 1 " X/4° I 40 I "/ie" 1 "/,.' 10.28
Cross
Part No.1 Size Sch. 1/0 I Wt.
80009 3/lI 40 6/0 0.13 lb.
80010 1" 40 0.23 lb.
80011 1V4° 40 16/,iU 0.34 lb.
80012 VI? 1 801 V/Is" 0.67 lb.
80013 2° 80 1/.° 1.00 lb.
80014 22 80 1ne" 1.91 lb.
80008 3°1 80 - 11 'Sh-a 2.89 lb. _
Reducing
Cross
1.
--if
r91
41 Qfl $ £0c4yco ie Pructs (TFP) BlazeMastet CPVC pipe and 90
fittings are designed exclusively for use in wet pipe
automatic fire sprinkler systems. They are made from a
specially developed thermoplastic compound composed of
post chlorinated polyvinyl chloride (CPVC) resin and state of
the art additives. TFP BlazeMaster CPVC products are
easier to install than traditional steel pipe systems, and at
Technical Data
SIZeR: 3/40 - 3
Maximum Working Pressure: 175 psi
Approvaim UL, FM, CUL, NSF, Dade County, LPCB,
MM, and the City of Los Angeles
Note., See aanw,tTFP BzeMeeter histallalion Indftaons and
Tethnl Manual, for exact ltinglappiova1 infoimalion
Pine
arr1I1ey prb heat resistance and
strength as compared to traditional CPVC and PVC piping
materials used in the plumbing trade. Various adapters are
available to connect CPVC pipe to metallic piping. All female
pipe thread adapters have brass Inserts for durability.
Grooved adapters connect directly to grooved end valves
and metallic pipe, with flexible grooved end couplings.
Mare Sourcei U.S.A.
Material:
Pipe: ASTM F442, SDR 13.5
Fittings: ASTM F438 (Sch. 40) and
ASTM F439 (Sch. 80)
Golan Orange
Nom.Pipe Size Avg. 0.D. inches Avg. LD. Inches Wt. Llis,/Ft. Wt. No filled Pipe Lbs fft. Ft. of Pipe per Lift Wt. per LIft Lbs. 3/40 1.050 0.874 0.17 0.43 7875 1413
1" 1.315 1.101 0.26 0.67 5040 1320
V/4° 1.660 1.394 0.42 1.07 2835 1191
10/20 1.900 1.598 0.55 1.40 2205 1136
2' 2.375 2.003 _0.86 2.20 1260 1063
2 1/20 2.875 -2.421-_1.26 3.22 1215 1531
3" 3.500 2.952 - .87 4.79 72b 1 1344
Fittings
450 Elbow
- 1L!TO
5 i~ 90- Elbow i:4
lBl' __7
Part Part No. Size Sch. T/O Wt.
80050 /4 3/4" 40 /" 0.08 lb.
80051 10 40 3/11 0.11 lb.
80052 1114° 40 3/0 0.20 lb.
80053 1 Will 80 1 'lie" 0.31 lb.
80054 80 5/
4
1 0.56 lb.
80055 21!2" 80 3/40 0.89 lb.
80056 80 1" 1.19 lb.
'Part I No. l Siz I e I
I' h. I
I 1/0 lwt.I u I I lb.l 1112
180032 1° x 3/401 40 1 '%.' 1 0.16
Part No. Size Sch. T/O Wt.
80025 3/41 40 /is" 0.09 lb.
80026 1' 40 3/41' 0.14 lb.
80027 11/4' 40 7/60 0.21 lb.
80028 1'/2" 1 80 1V,e' 0.40 lb.
80029 2° 80 11!4" lb.
80030 2Vs° 80 11/20
!*79
3°
.14 lb.
80031 80 1/,?.82 lb.
: : . ...• . ... .... .. . .. .
.. .
Coupling
-EEF--
Cap LII
Part No Size Sch. TIC Wt.
80100 3/4" 40 'I." 0.04 lb.
80101 40 3/s" 0.06 lb.
80102 11/4° 40 I/al 0.10 lb.
80103 11/2" 80 6/ 0.20 lb.
80104 80 5/i" 0.31 lb.
80105 2'I2" 80 7/6" 0.58 lb.
80106 3° 80 1'TO 8-8 lb.
Tb
Grooved _____
Coupling -..-.. PIpO.D.
Adapter
Part No. Size Sch. T/O Wt. Pipe CD
80160 11I4" x 11/4" Grooved 40 0.78 lb. 11/4" (1.660')
80161 1'/a" x 11Ia" Grooved 80 2/i." 0.95 lb. 11/2" (1.900")
80162 2° x 2" Grooved 80 2/,e" 1.42 lb. 2" (2.375")
80163 21/2" x 2'/a" Grooved 80 2'I,e" 2.28 lb. 2'/2" (2.875")
80164 3" x 3° Grooved 80 2'/4" 3.00 lb. 3'(3.500')
80168 3" x 76.1 mm Grooved 80 21/4" 2.72 lb. 76.1mm (3.000")
Part No. Size Sch. 1/0 Wt.
80200 1" x '/'." 40 Vise 0.04 lb.
80201 116" x /" 40 0.11 lb.
80202 11I4° x 1" 40 5/,11 0.12 lb.
80203 11/2" x 3/4"80 °k" 0.16 lb.
80204 11/2" X 1" 80 the 0.14 lb.
80205 11/2" X 11/4" 80 3/11 0.17 lb.
80206 2" x 3/4" 80 3/4" 0.27 lb.
80207 2' x 1° 80 "/." 0.26 lb.
80208 2° x V/4" 80 /t." 0.24 lb.
80209 2" x 11/2" 80 7/," 0.19 lb.
80215 The x 1" 80 Vohs" 0.42 lb.
80214 21/2" x 1',." 80 1/4" 0.45 lb.
80213 21l2" X 11/2" 80 1/." 046 lb
80211 2'/z° x 2° 80 1°!,." 0.29 lb.
80210 3" X 2° 80 2 0.72 lb.
80212 3" X 21/2° 80 116/i," 0.47 lb.
,-J
Reducing Td
Tee
Tb'
Part No Size Sch. T/O Wt.
80075 3/4° 40 V." 0.07 lb.
80076 1" 40 'I." 0.11 lb.
80077 1'/4" 40 3/,11 0.12 lb.
80078 V/2" 80 3he° 0.25 lb.
80079 2° 80 3/," 0.38 lb.
80080 2'I2° 80 3/,11 0.67 1b.
80081 3" 80 3/" 0.91 lb.
Reducer
Bushing
T/O
Female
Adapter
Part No. Size Sch. 1/0 I Wt.
80142 3/411 X 3/4' NPT 40 0.41 lb.
80145 x 1" NPT 40 W' 0.63 lb.
80146 11/4" X 11/4" NPT 40 7/i" 1.03 lb.
80147 1'/a" x V/a" NPT 80 1" 1.42 lb.
80148 x 2" NPT 80 1/.' 2.68 lb.
ldo
Male
Adapter
Part No. Size I Sch. 1/0 wJ
80157 /" X 3/40 NPT 40 1/'e" 0.33 lb.
80158 1" x 1° NPT 40 1/." 1 0.56 Ibi
Reducing . ..-
Coupling
I PartNo.1 Size lSch.IT/01 Wt.
80220 1" x 3/4" 40 I 'I." 1 0.08 lb.
Part
No. Size - Sch. T/O Wt.
lb. 1 2 3
80132 1 3/4" X 3/I' x 1" 40 3/4" 3/411 6/i" 0.14
80133 1" x 3/4 X 3/4" 40 ¼" "lie" 3/ 0.14
80134 1"x 3/4"x 1" /U xl" 40 6/," 3/
4
11 3/4' 0.17
80260 x 1" x 3/4"40 3/4w I/4 "I,." 0.16
80135 11/4" X 1" x 3/4" 40 'I,." 3/4" '/." 0.21
80136 11/4"x 1" x 1" 40 "I,." 3/4" "/." 0.22
80137 11/4" x 1" x 11/4° 40 i3/,° I I5/," 3/ieuu 0.26
80261 11/4"x 11/4" X 3/4 40 6/," /," ?/" 0.23
80262 11/4" X 11/411 x 1" 40 l4" 3/4 'I." 0.26
80138 11/4" X 11/4" X 11/2" 80 1" 1" 1" 0.43
80140 11/2" X 11/4" X 3/4" 80 /a 6/' 1" 0.36
80141 1 '/2" X 11/4" X 1" 80 'Ia" '/." 1 the 0.38
80263 11/2" X 11/2" x l4" 80 1i." 'I,." 1" 0.36
80264 11/a" X 11/2" x 1" 80 5/,, °/,." 1" 0.38
80275 11/2" X V/a" X 11/4" 80 'I." 'I," 1" 0.45
802661 x 2" x she 80 3/4fl '14' /4 1/e" 0.61
80266 2" x 2" X 1" 80 'I." 'I," 1 she 0.66
80274 2" x 2" X 11/4" 80 - 1° - 1" - 1/." - 0.74 - 80267 2° x 2" X 1'la" 80 1'/e" VI." 1/." 0.78
80271 21/2" x 21/2" x 1" 80 1 '!,.'1 1"iie"" 1'!,." 1.43
80272 21/2"x 21/2" X 1114' 80 1"!16" 1"/,e" 1/i." 1 1.46
80273 21/2" x 21/" X 11/2" 80 1 "1,0° 1 "Ii." 1 'li." 1.48
80276 21l2" X 2¼" x 2" 80 1"!,.' 111!,." 1/,e" 1.50
80270 3" X 3" X V/a" 80 1/4" 1/4" 1'/,." 2.28
80268 3" x 3"x 2" 80 1/" 1/4" 1/4" 2.25
80269 3" x 3" x 21I2" 80 1/4" 1/4" r 1 'eli." 2.44
T/O
Sprinkler Head Adapter -
with Brass Threaded Insert _______
Fart No. I Size i75 wt.
80175E 1 is" X 1/2" NPT 80 7/,," 0.20 lb.
80176E 1"x ½" NPT 80 0:22 lb.
80177L 3/4" X /2'• NPT 40 'I'." 0.16 lb.
80179 1 x 3/4" NPT 1 40 3/' 0.43 lb.
roe!I
Part No. Size I Sch. I T/O Wt.
80177L 3/4" x '/2" NPT 40 1/2 0.16 lb.
80178 1" x 1/2" NPT 40 ½" 0.20 lb.
Sprinkler Head Adapter _....
with Brass Threaded Insert
I Part No. Size Sch. T/O I Wt.
I 80175W 3/4"X /2" NPT 40 T/,,n 1 0.19 lb.
[80176W 1" x '/" NPT 40 1/,,' 1 0.18 lb.
Part
No. Size Sch. I/O Wt.
lb. 1 2
80462 1" x 1" x 1/2" NPT x 'Ia" NPT 40 6/," 1'!." 0.46
80463 1" X 1° X 'Ia" NPT x t/fl NPT 40 'I." 1'/,." 0.47
Sprinkler Head Adapter
(Spigot)
with Brass Threaded Insert
Back-to-Back Cross
with Brass Threaded Insert
Sprinkler Head Adapter
90° Elbow
with Brass Threaded Insert Back-to-Back Tee
with Brass Threaded Insert
Part •
No. Size Sch. T/O Wt. I
lbj 1 1 2
80199 3/4 x /2" NPT .40 '/," "I,." 1 0.20
80189 1"x /2" NPT 40 I3/,, 0.26
Sprinkler Head Adapter T!ct
Tee -..--.
with Brass Threaded Insert I
- I..
LImited Warranty
Part
No.
Size Sch. I/O I Wt.
lb. 1 T-2-1
80459 1" x 1/2" NPT x 'Ia" NPT 40 "/." 15/is° 0.48
80460 1" x 'Ia" NPT x 1/2° NPT 40 ii/,,n 1'/." i 0.46
Part
No. Size Sch. I/O . Wt.
lb. T 1 2 3
80250 3/4fl x 3/4" x 'Ia" NPT 40 '/." '/.' 0.22
80251 1"x 1" x 'Ia" NPT 40 "/." "I,," I3/,,n 0.29
80249 1"x 1" x 1" NPT - 40 "It." "/,." 17I,." 0.73
80256 1'/4" X 1" X ½" NPT . 40 7/,," '/." 1'!." 0.30
80252 11/" X 11/4' X Va" NPT 40 1/,, 7/,,' 1'!." 0.31
80257 1'/a"xi'/"x'/"NPT T
80254 11/2 X 11/2" X 1/2 NPT 80 'I,." 'I,." . VI,." 0.46
80258 Ia 2" x i'Ia" x '" NPT 80 'Ia" 'I." 1'!." 0.56
80253 2" x 2" x '/" NPT 80 '/2" 'Ia" 1'/." Q6
Products manufactured by Tyco Fir. Products are warranted solely to the original Buyer for ten (10) years against defects In
material and workmanship when paid for and properly Installed and maintained under normal use and service. This warranty will
expire top (10) years from date of ih1pnont by Tyco Fire Products. No warranty is given for products or components manufactured by compact., not affiliated by ownership with Tyco Fire Product, or for products and components which have been subject to misuse. Improper installation, corrosion, or which have not been Installed, maintained, modified or repaired In accordance with applicable Standards of the National Fire Protection Association (NFPA). and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products mole option. Tyco Fire Products neither asiumes. nor authorizes any person to assume for It any other obligation In connection with the sal, of products or parts of product.. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or Incomplete Information supplied by Buyer or Buyer's representatives.
UI NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONTRACT. TORT. STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY. FOR INCIDENTAL. iNDIRECT. SPECIAL OR CONSEQUENTIAL DAMAGES. INCLUDING BUT NOT LIMITED TO LABOR CHARGES. REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES. AND UI NO EVENT SNAIL TYCO FIRE PRODUCVS LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED. INCLUDING WARRANTIES OF MERCHANTABilITY AND FITNESS FOR A PARTICULAR PURPOSE.
tqco/Rowconzro//
?y0o8Mo#4 1mi.3 VVE xd I"MtMO
od M0M0? c5