HomeMy WebLinkAbout234 DATE AVE; ; AS080023City of Carlsbad
Sprinkler Permit
Permit No: AS080023
Job Address: 234 DATE AV Status: ISSUED
Permit Type: SPRINK Applied 2/19/2008
Parcel No: 2060802500 Approved: .2/21/2008
Lot #: 0
Reference No.: Issued: 2/21/2008
PC #: Inspector:
Project Title: CRESCENT DEL SOL ESTATES 24 (8bIdgs x 3) FIRE SPRINKLER
INSP. @ $65/EA .
Applicant:
VANGUARD FIRE PROTECTION
1604 LA MIRADA DR #105
SAN MARCOS CA
760-727-8540
Owner: .
LAGOON BREEZE DEVELOPMENT CORP.
7237 SANDERLING CT
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
1,560 0 1,560 . 0
APPROV5P P SUBMITTED
CARLS 7PARTMENT
CRSCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:28
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: CRESCENT DEL SOL ESTATES
Location: 234/236 DATE AVENUE
CARLSBAD, CA
Drawing Date: 11-16-07
Contractor: VANGUARD FIRE PROTECTION
925 POINSETTIA
SUITE 11
VISTA, CA 92081
Designer: S.B.
Calculated By:SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-NR
Reviewing Authorities:CARLSBAD FD
Remote Area Number: 1
Telephone:760-727-8540
Occupancy: RES
SYSTEM DESIGN
Code:NFPA 13 D Hazard:RES System Type:WET
Area of Sprinkler Oper. 648 sq ftj Sprinkler or Nozzle
Density (gpm/sq ft) 0.053 I Make: TYCO
Area per Sprinkler 324.0 sq ftl Model: LFII
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 0 gpm I Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 34.8 psi Required: 68.9 @ Source
WATER SUPPLY
Water Flow Test I Pump Data I
Date of Test 11-29-07 I Rated Capacity 0 gpm I
Static Pressure 100.0 psi I Rated Pressure 0.0 psi I
Residual Pres 95.0 psi I Elevation 0 I
At a Flow of 1405 gpm I Make:
Elevation 0" I Model: I
Location: SITE
Source of Information: VNGRD FLOW TEST
SYSTEM VOLUME 174 Gallons
Notes:
These plans have been reviewed for apparent coiiipivance
with the current applicable codes and standarth in force
in the jurid144in. The owiier or contractor juar uuIu,
this review in support of an application for a building
permit with the express understanding ihai this review
in no way relieves the owner or contractor or their
professional engineer or architect for sole responsibility
for full compliance with said codes and standards.
including the building code or for any responsihilty for
deficiencies. errors, omissions or negligence in these
plans whether or not noted in this review.
Date:'2( 11 Revicwer4)
ECOMMENI) APPROVAL
0 RECOMMEND APPROVAL. AS NOTED
CR.SCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:28
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gpm psi TOTALS
Hydr Ref W Required at Hyd Area 1 35 47.6 psi
2 1" CPVC 90 Eli 120 1.049 35 4.6
1 Pipe 1" PVx15 12' 150 1.101 35 2.2
1 1" Thrd Check Valve Generic NFPA Va 5' 120 1.049 35 1.8
Elevation Change 111 6" 5.0
Hydr Ref BOR Required at BASE OF RISER 35 61.2 psi
1 Pipe 2" Kx21 Copper 4' 150 1.962 35 0.0
2 2" Sweatd 90 Eli 120 2.067 35 0.2
1 2" Thrd Ball Valve "F19" 0' 0 2.067 35 0.0
4 2" CPVC 90 Eli 36' 120 2.067 35 0.6
1 Pipe 2" PVx15 120' 150 2.003 35 1.2
3 4" Flngd 90 Eli 30' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
1 4" Flngd Back Flow Valve FEBCO 11876 CHART LOSS 35 5.7
1 Pipe 4" DIx18 Cl 350 - 25' 140 4.238 35 0.0
1 4" Flngd Gate Valve "722U" 2' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
Hydr Ref SC Required at Source 35 68.9 psi
Water Source100..0 psi static, 95.0 psi residual @ 1405 gpm 35 gpm 100.0 psi
SAFETY PRESSURE 31.1 psi
Available Pressure of 100.0 psi Exceeds Required Pressure of 68.9 psi
This is a safety margin of 31.1 psi or 31 % of Supply
Maximum Water Velocity is 11.8 fps
CRSCEIiT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:28
Page 3
FITTING NAME TABLE
ABBREV. NAME
C -Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
LEGEND
HYD REF Hydraulic reference. Refer to accompanying flow diagram.
- K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)Al.85 / ID"4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x QA2/IDA4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are hated to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
CRESEIT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:28
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI")) (PSI) (GPM) (GPM) (GPM/SQ.FT)
1 23.50 12.3
is 23.00 4.90 12.3 17.2 17.2 0.05
2 23.50 13.0
2S 23.00 4.90 12.9 17.6 17.2 0.05
30 23.50 13.3
Fl 11.50 44.4
W 11.50 47.6
Max velocity of 11.84 occurs in the pipe from Fl TO 30
Nodes with "5" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "S" is on the branch.
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:28
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF HCHTYPES FTNG'S Pe Pv NOTES
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 1 TO W (PRIMARY PATH)
17.17 1.101 1E 0.50 12.3 12.3 K = 4.90
is C=150 5.00 -0.2 0.0
17.17 0.051 5.50 0.3 12.3 Vel = 5.84
1.101 1E 13.50 12.3 12.3 EqK = 4.89
1 C=150 IS 6.00 0.0 0.0
17.17 0.051 19.50 1.0 12.3 Vel = 5.84
17.63 1.101 6E 93.12 13.3 13.3
30 C=150 IT 43.00 5.2 0.0 See PATH 2
34.80 0.190 8S 136.12 25.8 13.3 Vel = 11.84
1.101 2E 7.29 44.4 44.4
Fl C=150 10.00 0.0 0.0
34.80 0.190 17.29 3.3 44.4 Vel = 11.84
W 34.80 47.6 K = 5.04
PATH 2 FROM HYDRAULIC REFERENCE 2 TO 30
17.63 1.101 1E 0.50 12.9 12.9 K = 4.90
2S C=150 5.00 -0.2 0.0
17.63 0.054 5.50 0.3 12.9 Vel = 6.00
1.101 IT 1.00 13.0 13.0 EqK = 4.89
2 C=150 5.00 0.0 0.0
17.63 0.054 6.00 0.3 13.0 Vel = 6.00
30 17.63 13.3 K = 4.83
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 4
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: CRESCENT DEL SOL ESTATES
Location: 234/236 DATE AVENUE
CARLSBAD, CA
Drawing Date: 11-16-07
Contractor: VANGUARD FIRE PROTECTION
925 POINSETTIA
SUITE 11
VISTA, CA 92081
Designer: S.B.
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-NR
Reviewing Authorities:CARLSBAD FD
SYSTEM DESIGN
Code: Hazard:
Remote Area Number: 2
Telephone:760-727-8540
Occupancy: RES
System Type:WET
Area of Sprinkler Oper. 648 sq ftl Sprinkler or Nozzle
Density (gpm/sq ft) 0.053 I Make: TYCO
Area per Sprinkler 324.0 sq ftl Model: LFII
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 0 gpm I Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 34.7 psi Required: 63.4 @ Source
WATER SUPPLY
Water Flow Test Pump Data I Date of Test 11-29-07 I Rated Capacity 0 gpm I
Static Pressure 100.0 psi I Rated Pressure 0.0 psi I
Residual Pres 95.0 psi I Elevation 0 I
At a Flow of 1405 gpm I Make: I
Elevation 0" I Model:
Location: SITE
Source of Information: VNGRD FLOW TEST
SYSTEM VOLUME 174 Gallons
Notes:
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 4
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gpm psi TOTALS
Hydr Ref W Required at Hyd Area 2 35 33.3 psi
2 1" CPVC 90 Eli 10' 120 1.049 35 4.6
1 Pipe 1" PVx15 25' 150 1.101 35 4.6
1 1" Thrd Check Valve Generic NFPA Va 5' 120 1.049 35 1.8
Elevation Change 24'6" 10.6
Hydr Ref BOR Required at BASE OF RISER 35 54.9 psi
1 Pipe 2" Kx21 Copper 4' 150 1.962 35 0.0
2 2" Sweatd 90 Eli 11' 120 2.067 35 0.2
1 2" Thrd Bali Valve "F19" 0' 0 2.067 35 0.0
4 2" CPVC 90 Ell 36' 120 2.067 35 0.6
1 Pipe 2" PVx15 200' 150 2.003 35 2.0
3 4" Flngd 90 Eli 30' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
1 4" Flngd Back Flow Valve FEBCO 11876 CHART LOSS 35 5.7
1 Pipe 4" DIx18 Cl 350 25' 140 4.238 35 0.0
1 4" Flngd Gate Valve "722U" 2' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
Hydr Ref SC Required at Source 35 63.4 psi
Water Source100.0 psi static, 95.0 psi residual @ 1405 gpm 35 gpm
-
100.0 psi
SAFETY PRESSURE 36.6 psi
Available Pressure of 100.0 psi Exceeds Required Pressure of 63.4 psi
This is a safety margin of 36.6 psi or 37 % of Supply
Maximum Water Velocity is 11.8 fps
CRESCENT DEL SQL ESTATES Drawing Date:11-16--07 1/25/08 10: 4
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
HYD REF Hydraulic reference. Refer to accompanying flow diagram. -
K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\IP
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Fe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)^1.85 / ID"4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q"2/ID"4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 4
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI')) (PSI) (GPM) (GPM) (GPM/SQ.FT)
3 23.50 12.3
35 23.00 4.90 12.3 17.2 17.2 0.05
4 23.50 12.9
4S 23.00 4.90 12.8 17.5 17.2 0.05
El 24.50 32.6
W 24.50 33.3
Max velocity of 11.81 occurs in the pipe from El TO W
Nodes with "5" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "5" is on the branch.
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 4
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv ******* NOTES
POINT Qt Pf/ft TOTAL Pf Pn
PATE 1 FROM HYDRAULIC REFERENCE 3 TO W (PRIMARY PATH)
17.17 1.101 1E 0.50 12.3 12.3 K = 4.90
3S C=150 5.00 -0.2 0.0
17.17 0.051 5.50 0.3 12.3 Vel = 5.84
1.101 is 9.00 12.3 12.3 EqK = 4.89
3 C=150 1.00 0.0 0.0
17.17 0.051 10.00 0.5 12.3 Vel = 5.84
17.52 1.101 4E 72.17 12.9 12.9 EqK = 4.89
4 C=150 2T 35.00 -0.4 0.0
34.69 0.188 5S 107.17 20.2 12.9 Vel = 11.81
1.101 3.47 32.6 32.6
El C=150 0.00 0.0 0.0
34.69 0.188 3.47 0.7 32.6 Vel = 11.81
W 34.69 33.3 K = 6.01
17.52 1.101 iT 0.50. 12.8 12.8 K = 4.90
4S C=150 5.00 -0.2 0.0
17.52 0.053 5.50 0.3 12.8 Vel = 5.96
4 17.52 12.9 K = 4.89
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 1
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: CRESCENT DEL SOL ESTATES
Location: 234/236 DATE AVENUE
CARLSBAD, CA
Drawing Date: 11-16-07
Contractor: VANGUARD FIRE PROTECTION
925 POINSETTIA
SUITE 11
VISTA, CA 92081
Designer: S.B.
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-NR
Reviewing Authorities:CARLSBAD FD
SYSTEM DESIGN
Code: Hazard:
Remote Area Number: 3
Telephone:760-727-8 540
Occupancy: RES
System Type:WET
Area of Sprinkler Oper. 648 sq ftl Sprinkler or Nozzle
Density (gpm/sq ft) 0.053 I Make: TYCO
Area per Sprinkler 324.0 sq ftl Model: LFII
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 0 gpm I Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 34.8 psi Required: 67.2 @ Source
WATER SUPPLY
Water Flow Test I Pump Data I
Date of Test 11-29-07 Rated Capacity 0 gpm I
Static Pressure 100.0 psi I Rated Pressure 0.0 psi
Residual Pres 95.0 psi I Elevation 0 I
At a Flow of 1405 gpm I Make: I
Elevation 0" I Model: I
Location: SITE
Source of Information: VNGRD FLOW TEST
SYSTEM VOLUME 174 Gallons
Notes:
FLOW LOSS
gpm psi TOTALS
35 36.2 psi
35 4.6
35 4.6
35 1.8
10.6
35
35 0.0
35 0.2
35 0.0
35 0.6
35 2.9
35 0.0
35 0.0
35 5.7
35 0.0
35 0.0
35 0.0
57.8 psi
1/25/08 10: 1 CRESCENT DEL SQL ESTATES Drawing Date:11-16-07
HYDRAULIC CALCULATION DETAILS
HYDRAULIC
QTY DESCRIPTION LENGTH C ID
Hydr Ref W Required at Hyd Area 3
2 1" CPVC 90 Eli 10' 120 1.049
1 Pipe 1" PVx15 25' 150 1.101
1 1" Thrd Check Valve Generic NFPA Va 5' 120 1.049
Elevation Change 24'6"
Hydr Ref BOR Required at BASE OF RISER
1 Pipe 2" Kx21 Copper 4' 150 1.962
2 2" Sweatd 90 Eli 11' 120 2.067
1 2" Thrd Ball Valve "F19" 0' 0 2.067
4 2" CPVC 90 Eli 36' 120 2.067
1 Pipe 2" PVx15 280' 150 2.003
3 4" Flngd 90 Eli 30' 120 4.026
1 4" Flngd Tee 20' 120 4.026
1 4" Flngd Back Flow Valve FEBCO 11876 CHART LOSS
1 Pipe 4" DIx18 Cl 350 25' 140 4.238
1 4" Flngd Gate Valve 11722U" 2' 120 4.026
1 4" Flngd Tee 20' 120 4.026
Hydr Ref SC Required at Source 35 67.2 psi
Water Source100.0 psi static, 95.0 psi residual @ 1405 gpm 35 gpm 100.0 psi
SAFETY PRESSURE 32.8 psi
Available Pressure of 100.0 psi Exceeds Required Pressure of 67.2 psi
This is a safety margin of 32.8 psi or 33 % of Supply
Maximum Water Velocity is 11.8 fps
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 1
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T .90' Flow Thru Tee
V Valve
HYD REF Hydraulic reference. Refer to accompanying flow diagram. -
K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)"1.85 / IDA4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x QA2/ID/4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 1
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW. DENSITY
(FT) (GPM/(PSI')) (PSI) (GPM) (GPM) (GPM/SQ.FT)
5 23.50 12.3
5S 23.00 4.90 12.3 17.2 17.2 0.05
6 24.50 12.7
6S 23.00 4.90 13.0 17.6 17.2 0.05
20 24.50 12.9
Dl 24.50 34.5
W 24.50 36.2
Max velocity of 11.85 occurs in the pipe from 20 TO Dl
Nodes with "S" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "Sn is on the branch.
CRESCEI1T DEL SOL ESTATES Drawing Date:11-16-07 1/25/08 10: 1
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C't TYPES FTNG'S Pe Pv ******* NOTES
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 5 TO W (PRIMARY PATH)
17.17 1.101 1E 0.50 12.3 12.3 K = 4.90
5S C=150 5.00 -0.2 0.0
17.17 0.051 5.50 0.3 12.3 Vel = 5.84
1.101 1E 9.00 12.3 12.3 EqK = 4.89
5 C=150 IT 11.00 -0.4 0.0
17.17 0.051 IS 20.00 1.0 12.3 Vel = 5.84
17.64 1.101 2E 65 80.77 12.9 12.9
20 C=150 3T 33.00 0.0 0.0 See PATH 2
34.82 0.190 2F 113.77 21.6 12.9 Vel = 11.85
1.101 8.59 34.5 34.5
Dl C=150 0.00 0.0 0.0
34.82 0.190 8.59 1.6 34.5 Vel = 11.85
W 34.82 36.2 K = 5.79
PATH 2 FROM HYDRAULIC REFERENCE 6 TO 20
17.64 1.101 1E 1.50 13.0 13.0 K = 4.90
6S C=150 5.00 -0.6 0.0
17.64 0.054 6.50 0.3 13.0 Vel = 6.00
1.101 is 4.09 12.7 12.7 EqK = 4.96
6 C=150 1.00 0.0 0.0
17.64 0.054 5.09 0.3 12.7 Vel = 6.00
20 17.64 12.9 K = 4.90
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 0
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: CRESCENT DEL SOL ESTATES
Location: 234/236 DATE AVENUE
CARLSBAD, CA
Drawing Date: 11-16-07
Contractor: VANGUARD FIRE PROTECTION
925 POINSETTIA
SUITE 11
VISTA, CA 92081
Designer: S.B.
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-NR
Reviewing Authorities:CARLSBAD FD
SYSTEM DESIGN
Code: Hazard:
Remote Area Number: 4
Telephone: 760-727-8540
Occupancy: RES
System Type:WET
Area of Sprinkler Oper. 648 sq ftl Sprinkler or Nozzle
Density (gpm/sq ft) 0.053 I Make: TYCO
Area per Sprinkler 324.0 sq ftl Model: LFII
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 0 gpm I Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 35.1 psi Required: 64.1 @ Source
WATER SUPPLY
Water Flow Test Pump Data I
Date of Test 11-29-07 I Rated Capacity 0 gpm I
Static Pressure 100.0 psi I Rated Pressure 0.0 psi I
Residual Pres 95.0 psi I Elevation 0 I
At a Flow of 1405 gpm I Make: I
Elevation 0" I Model:
Location: SITE
Source of Information: VNGRD FLOW TEST
SYSTEM VOLUME 174 Gallons
Notes:
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 0
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gym psi TOTALS
Hydr Ref W Required at Hyd Area 4 35 32.5 psi
2 1" CPVC 90 Eli 10' 120 1.049 35 4.6
1 Pipe 1" PVx15 25' 150 1.101 35 4.7
1 1" Thrd Check Valve Generic NFPA Va 5' 120 1.049 35 1.8
Elevation Change 24'6" 10.6
Hydr Ref BOR Required at BASE OF RISER 35 54.3 psi
1 Pipe 2" Kx21 Copper 4' 150 1.962 35 0.0.
2 2" Sweatd 90 Eli 11' 120 2.067 35 0.2
1 2" Thrd Ball Valve "F19" 0' 0 2.067 35 0.0
4 2" CPVC 90 Eli 36' 120 2.067 35 0.6
1 Pipe 2" PV x15 310' 150 2.003 35 3.2
3 4" Flngd 90 Eli 30' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
1 4" Flngd Back Flow Valve FEBCO 11876 CHART LOSS 35 5.7
1 Pipe 4" DIx18 Cl 350 25' 140 4.238 35 0.0
1 4" Flngd Gate Valve "722U" 2' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
Hydr Ref SC Required at Source 35 64.1 psi
Water Source100.0 psi static, 95.0 psi residual @ 1405 gpm 35 gpm 100.0 psi
SAFETY PRESSURE 35.9 psi
Available Pressure of 100.0 psi Exceeds Required Pressure of 64.1 psi
This is a safety margin of 35.9 psi or 36 % of Supply
Maximum Water Velocity is 11.9 fps
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 0
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
LEGEND
HYD REF Hydraulic reference. Refer to accompanying flow diagram. -
K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction -loss (psi) to fitting
where Pf = 1 x 4.52 z (Q/C)"l.85 / ID'4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q'2/ID"4
Pn Normal pressure (psi), where Pn = Pt - Pv
IM*c
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 0
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI')) (PSI) (GPM) (GPM) (GPM/SQ.FT)
7 23.50 12.3
7S 23.00 4.90 12.3 17.2 17.2 0.05
8 24.50 13.1
8S 23.00 4.90 13.4 17.9 17.2 0.06
Cl 24.50 31.5
W 24.50 32.5
Max velocity of 11.94 occurs in the pipe from 8 TO Cl
Nodes with "Sn indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "S" is on the branch.
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10: 0
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv ******* NOTES
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 7 TO W (PRIMARY PATH)
17.17 1.101 1E 0.50 12.3 12.3 K = 4.90
7S C=150 5.00 -0.2 0.0
17.17 0.051 5.50 0.3 12.3 Vel = 5.84
1.101 2E 11.79 12.3 12.3 EqK = 4.89
7 C=150 iS 11.00 -0.4 0.0
17.17 0.051 22.79 1.2 12.3 Vel = 5.84
17.92 1.101 1E 6S 77.66 13.1 13.1 EqK = 4.95
8 C=150 iT 18.00 0.0 0.0
35.09 0.193 2F 95.66 18.4 13.1 Vel = 11.94
1.101 5.09 31.5 31.5
Cl C=150 0.00 0.0 0.0
35.09 0.193 5.09 1.0 31.5 Vel = 11.94
W 35.09 32.5 K = 6.16
17.92 1.101 iT 1.50 13.4 13.4 K = 4.90
85 C=150 5.00 -0.6 0.0
17.92 0.056 6.50 0.4 13.4 Vel = 6.10
8 17.92 13.1 K = 4.95
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
CR$SCEIJT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 9:53
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: CRESCENT DEL SOL ESTATES
Location: 234/236 DATE AVENUE
CARLSBAD, CA
Drawing Date: 11-16-07
Contractor: VANGUARD FIRE PROTECTION
925 POINSETTIA
SUITE 11
VISTA, CA 92081
Designer: S.B.
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-NR
Reviewing Authorities:CARLSBAD FD
SYSTEM DESIGN
Remote Area Number: 5
Telephone:760-727-8540
Occupancy: RES
Code: Hazard: System Type:WET
Area of Sprinkler Oper. 648 sq ftl Sprinkler or Nozzle
Density (gpm/sq ft) 0.053 I Make: TYCO
Area per Sprinkler 324.0 sq ftl Model: LFII
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 0 gpm I Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 34.7 psi Required: 61.6 @ Source
WATER SUPPLY
Water Flow Test I
Date of Test 11-29-07 I
Static Pressure 100.0 psi I
Residual Pres 95.0 psi I
At a Flow of 1405 gpm I
Elevation 0" I
Pump Data
Rated Capacity 0 gpm
Rated Pressure 0.0 psi
Elevation 0
Make:
Model:
Location: SITE
Source of Information: VNGRD FLOW TEST
SYSTEM VOLUME 174 Gallons
Notes:
CRESCENT DEL SOL ESTATES Drawing Date:11-16-07 1/25/08 9:53
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gpm psi TOTALS
Hydr Ref W Required at Hyd Area 5 35 29.6 psi
2 1" CPVC 90 Eli 10' 120 1.049 35 4.6
1 Pipe 1" PVx15 25' 150 1.101 35 4.6
1 1" Thrd Check Valve Generic NFPA Va 5' 120 1.049 35 1.8
Elevation Change 241 6" 10.6
Hydr Ref BOR Required at BASE OF RISER 35 51.2 psi
1. Pipe 2" Kx2l Copper 4' 150 1.962 35 0.0
2 2" Sweatd 90 Eli 11' 120 2.067 35 0.2
1 2" Thrd Ball Valve "F19" Of 0 2.067 35 0.0
4 2" CPVC 90 Eli 36' 120 2.067 35 0.6
1 Pipe 2" PVx15 380' 150 2.003 35 3.9
3 4" Flngd 90 Eli 30' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
1 4" Flngd Back Flow Valve FEBCO 11876 CHART LOSS 35 5.7
1 Pipe 4" DIx18 Cl 350 25' 140 4.238 35 0.0
1 4" Flngd Gate Valve "722U" 2' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
Hydr Ref SC Required at Source 35 61.6 psi
Water Source100.0 psi static, 95.0 psi residual @ 1405 gpm 35 gpm 100.0 psi
SAFETY PRESSURE 38.4 psi
Available Pressure of 100.0 psi Exceeds Required Pressure of 61.6 psi
This is a safety margin of 38.4 psi or 38 % of Supply
Maximum Water Velocity is 11.8 fps
CRESCENT DEL SOL ESTATES Drawing Date:11-16-07 1/25/08 9:53 I
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
HYD REF Hydraulic reference. Refer to accompanying flow diagram.
- K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)"1.85 / IDA4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x QA2/ID4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 9:53
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI-;I)) (PSI) (GPM) (GPM) (GPM/SQ.FT)
9 23.50 12.3
9S 23.00 4.90 12.3 17.2 17.2 0.05
10 23.50 12.9
lOS 23.00 4.90 12.8 17.6 17.2 0.05
Bi 24.50 28.5
W 24.50 29.6
Max :velocity of 11.82 occurs in the pipe from W TO B].
Nodes with'IS" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "5" is on the branch.
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 9:53
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv NOTES
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 9 TO W (PRIMARY PATH)
17.17 1.101 1E 0.50 12.3 12.3 K = 4.90
9S C=150 5.00 -0.2 0.0
17.17 0.051 5.50 0.3 12.3 Vel = 5.84
1.101 is 10.00 12.3 12.3 EqK = 4.89
9 C=150 1.00 0.0 0.0
17.17 0.051 11.00 0.6 12.3 Vel = 5.84
17.55 1.101 3E 54.91 12.9 12.9 EqK = 4.89
10 C=150 iT 30.00 -0.4 0.0
34.73 0.189 6S 84.91 16.0 12.9 Vel = 11.82
1.101 5.87 28.5 28.5
B1 C=150 0.00 0.0 0.0
34.73 0.189 5.87 1.1 28.5 Vel = 11.82
W 34.73 29.6 K = 6.38
17.55 1.101 iT 0.50 12.8 12.8 K = 4.90
lOS C=150 5.00 -0.2 0.0
17.55 0.053 5.50 0.3 12.8 Vel = 5.97
10 17.55 12.9 K = 4.89
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:50
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: CRESCENT DEL SOL ESTATES
Location: 234/236 DATE AVENUE
CARLSBAD, CA
Drawing Date: 11-16-07
Contractor: VANGUARD FIRE PROTECTION
925 POINSETTIA
SUITE 11
VISTA, CA 92081
Designer: S.B.
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-NR
Reviewing Authorities:CARLSBAD FD
SYSTEM DESIGN
Remote Area Number: 6
Telephone: 760-727-8540
Occupancy: RES
Code: Hazard: System Type:WET
Area of Sprinkler Oper. 648 sq ftP Sprinkler or Nozzle
Density (gpm/sq ft) 0.053 I Make: TYCO
Area per Sprinkler 324.0 sq ftl Model: LFII
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 0 gpm I Temperature Rating: 155
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 34.8 psi Required: 63.6 @ Source
WATER SUPPLY
Water Flow Test
Date of Test 11-29-07
Static Pressure 100.0 psi
Residual Pres 95.0 psi
At a Flow of 1405 gpm
Elevation 0"
Pump Data
Rated Capacity 0 gpm
Rated Pressure 0.0 psi
Elevation 0
Make:
Model:
Location: SITE
Source of Information: VNGRD FLOW TEST
SYSTEM VOLUME 174 Gallons
Notes:
CRESCENT DEL SOL ESTATES Drawing Date:11-16-07 1/25/08 10:50
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gpin psi TOTALS
Hydr Ref W Required at Hyd Area 6 35 31.6 psi
2 1" CPVC 90 Eli 10' 120 1.049 35 4.6
1 Pipe 1" PVx15 24' 150 1.101 35 4.4
1 1" Thrd Check Valve Generic NFPA Va. 5' 120 1.049' 35 1.8
Elevation Change 23'6" 10.2
Hydr Ref BOR Required at BASE OF RISER 35 52.6 psi
1 Pipe 2" Kx21 Copper 4' 150 1.962 35 0.0
2 2" Sweatd 90 Eli 11' 120 2.067 35 0.2
1 2" Thrd Bail Valve "F19" 0' 0 2.067 35 0.0
4 2" CPVC 90 Eli 36' 120 2.067 35 0.6
1 Pipe 2" PVx15 440' 150 2.003 35 4.5
3 4" Flngd 90 Eli 30' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
1 4" Flngd Back Flow Valve FEBCO 11876 CHART LOSS 35 5.7
1 Pipe 4" DIx18 Cl 350 25" 140 4.238 35 0.0
1 4" Flngd Gate Valve "7220" 2' 120 4.026 35 0.0
1 4" Flngd Tee 20' 120 4.026 35 0.0
Hydr Ref SC Required at Source 35 63.6 psi
Water Source100.0 psi static, 95.0 psi residual @ 1405 gpm 35 gpm 100.0 psi
SAFETY PRESSURE 36.4 psi
Available Pressure of 100.0 psi Exceeds Required Pressure of 63.6 psi
This is a safety margin of 36.4 psi or 36 % of Supply
Maximum Water Velocity is 11.8 fps
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:50
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
HYD REF Hydraulic reference. Refer to accompanying flow diagram. -
K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)'l.85 / ID"4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q"2/ID'4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:50
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL
NUMBER K-FACTOR FLOW FLOW DENSITY
(FT) (GPM/(PSI'4)). (PSI) (GPM) (GPM) (GPM/SQ.FT)
11 23.50 12.3
115 23.00 4.90 12.3. 17.2 17.2 0.05
12 23.50 13.0
12S 23.00 4.90 12.9 17.6 17.2 0.05
Al 24.50 29.9
W 24.50 31.6
Max velocity of 11.83 occurs in the pipe from 12 TO Al
Nodes with "5" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "S" is on the branch.
CR.ESCEIS)T DEL SQL ESTATES Drawing Date:11-16-07 1/25/08 10:50
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv ******* NOTES
POINT Qt Pf/ft TOTAL Pf Pn
PATH 2. FROM HYDRAULIC REFERENCE 11 TO W (PRIMARY PATH)
17.17 1.101 1E 0.50 12.3 12.3 K = 4.90
uS C=150 5.00 -0.2 0.0
17.17 0.051 5.50 0.3 12.3 Vel = 5.84
1.101 is 11.31 12.3 12.3 EqK = 4.89
11 C=150 1.00 0.0 0.0
17.17 0.051 12.31 0.6 12.3 Vel = 5.84
17.60 1.101 7E 51.45 13.0 13.0 EqK = 4.89
12 C=150 5S 40.00 -0.4 0.0
34.77 0.189 91.45 17.3 13.0 Vel = 11.83
1.101 9.16 29.9 29.9
Al C=150 0.00 0.0 0.0
34.77 0.189 9.16 1.7 29.9 Vel = 11.83
W 34.77 31.6 K = 6.19
17.60 1.101 iT 0.50 12.9 12.9 K = 4.90
125 C=150 5.00 -0.2 0.0
17.60 0.054 5.50 0.3 12.9 Vel = 5.99
12 17.60 13.0 K = 4.89
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
tqco Ffre & Building
IlProducts
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
if
rapid response
HOME FIRE SPRINKLER SYSTEM
Series LFil Residential
Concealed Pendent Sprinklers, Flat Plate
49 K-factor
General
Description
The Series LFlI (1Y3596) Residential
Concealed Pendent Sprinklers are
decorative, fast response, fusible sol-
der sprinklers designed for use in resi-
dential occupancies such as homes,
apartments, dormitories, and hotels.
The cover plate assembly conceals
the sprinkler operating components
above the ceiling. The flat profile of the
cover plate provides the optimum aes-
thetically appealing sprinkler design.
In addition, the concealed design of
the Series LFl! (TY3596) provides 1/2
Inch (12,7 mm) vertical adjustment.
This adjustment reduces the accuracy
to which the fixed pipe drops to the
sprinklers must be cut to help assure
a perfect fit installation.
The Series LFll are to be used In wet
pipe residential sprinkler systems for one- and two-family dwellings and mo-
bile homes per NFPA 13D; wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
1311; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series LFIl (TY3596) has a 4.9
(60,5) K-factor that provides the re-
quired residential flow rates at reduced
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the 'INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate In a fire situation or cause
it to operate prematurely.
Page 1 Of 4
pressures, enabling smaller pipe sizes
and water supply requirements.
The Series LFll (1Y3596) has been designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
The Series LFll (TY3596) Residential
Concealed Pendant Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate Assembly installed.
WARNINGS
The Series LFII (1Y3596) Residential
Concealed Pendent Sprinklers de-
scribed herein must be installed and
maintained In compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
SprinkleriModel
Identification
Number
SIN TY3596
JANUARY, 2006
Technical
Data
Approvals:
UL and C-UL Listed.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient: K = 4.9 GPM/pslll2 (70,6 LPM/barl/2)
Temperature Rating:
160°F/710C Sprinkler with
135°F/57°C Cover Plate
Vertical Adjustment:
1/2 inch (12,7 mm)
Finishes:
Cover Plate:
Flat White, Bright White, Chrome, or Custom
Physical Characteristics:
Body ..............Brass
Cap ..............Bronze
Saddle .............Brass
Sealing Assembly ..........
Beryllium Nickel w/ Teflonf
Soldered Link Halves .....Nickel
Lever .............Bronze
Compression Screw ......Brass
Deflector ......Copper or Brass
Guide Pin Housing .....Bronze
TFP442
P
Page 2 of 4 TFP442
Minimum Flow IN and
Maximum Maximum Residual Pressure
Coverage
Area (a)
Spacing
Ft.
For Horizontal Ceiling
(Max. 2 Inch Rise
Ft. x Ft. (m) for 12 Inch Run)
(mx m)
160"F171"C
Sprinkler
12x12 12 I3 GPM (49,2LPM)
(3,7 x 3,7) (3,7) 7.0 psi (0.48 bar)
14x14 14 I3 GPM (53,OLPM)
(4,3 x 4,3) (4,3) 7.0 psi (0.48 bar)
16x16 16 I3 GPM (60,6LPM)
(4,9 x 4,9) (4,9) 7.0 psi (0,48 bar)
18x18 18 17 GPM (64,3 LPM)
(5.5 x 5.5) (515) 12.0 psi (0.83 bar)
20 x 20 20 20 GPM (75,7 1PM)
(6,1x6,1) (6,1) 16.7 psi (1,l5bar)
For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the
next highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (1PM) from each sprinkler. The associated residual pressures are calculated
using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY3596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
Guide Pins ......Stainless Steel
Support Cup ..........Steel
Cover Plate ..........Copper
Retainer ............Brass
Cover Plate Ejection Spring .....
............Stainless Steel
tDuPont Registered Trademark
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Support Cup at three
points, falls away to expose the Sprin-
kler Assembly. At this point the Deflec-
tor supported by the Arms drops down
to its operated position. The fusible
link of the Sprinkler Assembly is com-
prised of two link halves that are sol-
dered together with a thin layer of sol-
der. When the rated temperature is
reached, the solder melts and the two
link halves separate allowing the sprin-
kler to activate and flow water.
Design
Criteria
The Series LFll (1Y3596) Residential
Concealed Pendent Sprinklers are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
NOTE
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the Authority Having Jurisdic-
tion.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of "design sprinklers" as
specified in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Table A for
NFPA 13D and 13R as a function of
temperature rating and the maxi-
mum allowable coverage area.
A minimum discharge of 0.1 gpm/sq.
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity. The sprin-
klers are to be installed relative to the
ceiling mounting surface as shown in
Figure 3.
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
length of the coverage area (Ref. Ta-
ble A) being hydraulically calculated
(e.g., maximum 12 feet for a 12 ft. x
12 ft. coverage area, or 20 feet for a 20
ft. x 20 ft. coverage area).
Installation
The Series IFlI (TY3596) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Damage to the fusible Link Assembly
during Installation can be avoided by
handling the sprinkler by the support
cup only (i.e., do not apply pressure to
the fusible link Assembly).
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
TFP442
BODY SEALING
(112" NPT) ASSEMBLY
SUPPORT COMPRESSION
CUP WITH SCREW
ROLL FORMED
THREADS
LEVER
GUIDE I
PIN ..I
/
SOLDER LINK
ELEMENT
GUIDE PIN /1
HOUSING I I
I --" - DEFLECTOR
DEFLECTOR'
________________
POSITION)
SPRINKLER/SUPPORT CUP
ASSEMBLY I
THREAD INTO RETAINER
SUPPORT CUP WITH THREAD
UNTIL MOUNTING II - DIMPLES
SURFACE IS 0
FLUSH WITH U EJECTION
CEILING II Ii SPRING
SOLDER COVER PLATE/RETAINER "— COVER TAB ASSEMBLY PLATE
FIGURE 1
SERIES LFII (TY3596) RESIDENTML
CONCEALED PENDENT SPRINKLER
Page 3 of 4
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be Used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or Impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Cover
Plate/Retainer Assembly by under- or
over-tightening the Sprinkler. Read-
just the position of the sprinkler fitting
to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, and using
the W-Type 18 Wrench shown in Fig-
ure 2, install and tighten the Sprink-
ler/Support Cup Assembly into the fit-
ting. The W-Type 18 Wrench will
accept a 1/2 inch ratchet drive.
WRENCH RECESS
0
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 18
SPRINKLER WRENCH
2-1/2" DIA. r-T (63.5 mm)
1/2" NPT.. -
1/2"(12,7 mm) FACE OF
THREADED SPRINKLER ADJUSTMENT FITTING
SPRINKLER-
SUPPORT CUP
ASSEMBLY
1/8" GAP
1-1/8"*1/8"
(47.6 mm
*3,2 mm)
- S I COVER- SPRINKLER- I MOUNTING RETAINER SUPPORT CUP 3/16" 1 SURFACE ASSEMBLY ASSEMBLY (4,8 mm)
3-3/16" DIA. (81,0 mm) TIP
DISPOSABLE
PROTECTIVE CAP DEFLECTOR IN
OPERATED POSITION
FIGURE 3
SERIES LFII (TY3596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
INSTALLATION DIMENSIONS / PROTECTIVE CAP IACTIVA TED DEFLECTOR
MasterSeries® 876V
Double Check Detector Assemblies
Size:21h" - 10' (65mm - 250mm)
The FEBCO MasterSeriese 876V Double Check Detector Assemblies are
designed for use in non-health hazard fire sprinkler systems.
Standard orientation is inlet flow vertical up, outlet flow vertical down.
Vertical orientation is inlet and outlet flow vertical up.
Shutoff Valves:
Trim:
Elastomer Discs:
Spring:
Ductile iron Grade 6$45.12
Fusion epoxy coated internal and external
AWWA C550-90
OS&Y resilient wedge gate
valves AWWA C509
Bronze
EPDM
Stainless steel
MODEL 816V DOUBLE CHECK DETECTOR ASSEMBLY
(Shown in vertical orientation)
U.S. Potent No. 4,989,635 • U.S. Patent No. 5,107,888
U.S. Patent No. 5,385,166 • U.S. Patent No. 5,226,441
U.S. Patent No. 5,392,803 • U.S. Patent No. 5,503,176
Models
Valve Setter with MJ x MJ, MJ x FL or FL x FL ends
End Connections —Flanged ANSI B16.1 Class 125
Pressure - Temperature
Maximum Working Pressure: 175ps1 (12.1 bar)
Hydrostatic Test Press: 350ps1 (24.1 bar)
Temperature Range: 32°F to 140°F (0°C to 60°C)
Approvals - Standards
a ANSVAWNA (C510)
Approved by the Foundation for Cross-Connection Control and Hydraulic
Research at the University of Southern California.
ec® eFM >.
Approved c®us
1048 064.5
'Less gate not FM approved. Less gate not UL Classified unless installed
with UL Listed gate valves
MODEL 876V DOUBLE CHECK DETECTOR ASSEMBLY
(Shown in standard orientation)
Job Name Contractor
Job Location Approval
Engineer Contractor's PO. No.
Approval Representative
FEBCO product specifications . customary units and metric are approximate and are provided for reference only. For precise me-
kPa pal
11 6" (200mm)
---..
-
1000 3893 5580 7560 9460
________
119
1v 91 14
83 12
69 to
558
41 6
284
14 2
00
pm
11350 1pm
Installation
Standard orientation (Series 876V)
18" mm
(450mm)
PAW
verticar orientation (Series 876V)
18"min + (450mm) 4- I
L Flow ri_ 18"min
8"min U '1(450mm)
Flow
10
mm
0mm)
Colin
000mm) Support
(QjlUI1)
'bfl
(~~shipeed by customer)
for valve weight only.
Optional Valve
. . Recommended
minimum clearances
S er
from permanent
structures for ease
of testing and
maintenance are shown
on above drawings. Capacity
liPa pal 2Yz"(65mm) kPa pal 6" (150mm) lie is
110 16 97 14 97 14 to 12 83 12
28 4
14 2
0 50 100 150 200 250 300 am 0 190 380 570 760 950 1140 Ipm 0 700 1520 2200 3040 3800 4540 5300 1pm
kP. psi
kPa psi
124 18
ItO 16
69 to
41
21 4
14 2
0 300
A-Vertical orientation
8-Standard orientation
4" (100mm)
B
760 1140 1520 1900 2280 2660
110 10
97 14
13 12
69 10
00558
41 8
284
14 2
00
10" (250mm)
gpm 0 38400 7500 11350 15140 18530 1pm
The 6' and 10" flow curves (B-standard orientation) include the
Setter Sofas 611. FEBCO Valve
I CERTIFIED1
J9Oo1
A Division of Wafts Water Technologies, Inc. USA; 4381 N. Brawiey • Ste. 102 • Fresno, CA • 93722 • Tel. (559) 441-5300 • Fax (559) 441-5301 • www.FEBCOonllne.cOm Canada: 5435 North Service Rd. • eufllngton, ONE • IlL 5H7 9 Tel. (905) 3324090 • Fax: (905) 332-7068 • Www.FEBCOonhine.ca