HomeMy WebLinkAbout234 DATE AVE; ; AS070303City of Carlsbad
Sprinkler Permit
Permit No: A8070303
Job Address: 234 DATE AV Status: ISSUED
Permit Type: SPRINK Applied 12/27/2007
Parcel No: 2060802500 Approved: 12/27/2007
Lot #: 0
Reference No.: Issued: 12/27/2007
PC #: Inspector:
Project Title: CRESCENT DEL SQL ESTATES 3 FIRE SPRINKLER INSPECTIONS
@$65/EA
Applicant:
VANGUARD FIRE PROTECTION
1604 LA MIRADA DR #105
SAN MARCOS CA
760-727-8540
Owner: .•
LAGOON BREEZE DEVELOPMENT CORP
7237 SANDERLING CT
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($).
195 0 195 0
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 12/ 7/07 14:13
HYDRAULIC DESIGN INFORMATION SHEET
Job Name: CRESCENT DEL SOL ESTATES
Location: 234/236 DATE AVENUE
CARLSBAD, CA
Drawing Date: 11-16-07
Contractor: VANGUARD FIRE PROTECTION
925 POINSETTIA
SUITE 11
VISTA, CA 92081
Designer: S.B.
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: S-3
Reviewing Authorities : CFD
Remote Area Number: 1
Telephone :760-727-8540
APPROVED A1
BMITTED
CARLOAD ENT
Occupancy:
SYSTEM DESIGN
Code:NFPA 13 Hazard:ORD 1 System Type:WET
Area of Sprinkler Oper. 911 sq ftl Sprinkler or Nozzle
Density (gpm/sq ft) 0.150 I Make: TYCO Area per Sprinkler 113.0 sq ftl Model: TY-FRB Hose Allowance Inside 0 gpm I K-Factor: 5.60
Hose Allowance Outside 250 gpm I Temperature Rating: 200
CALCULATION SUMMARY 10 Flowing Outlets
gpm Required: 437.5 psi Required: 79.2 @ Source
WATER SUPPLY
Water Flow Test I Pump Data I Date of Test 11-29-07 I Rated Capacity 0 gpm I Static Pressure 100.0 p5i I Rated Pressure 0.0 psi I Residual Pres 95.0 si I Elevation 0
At a Flow of 1405 gpm I Make: I
Elevation 0" I Mol: I
Location: SITE
Source of Information: VANGUARD FLOW TEST
SYSTEM VOLUME 236 Gallons
Notes:
These plaits have been reviewed for apparent cotiipllance
with the current applicable codes and siandard in lbrce in the jurisdiction The owner or contractor iiia uiilii this ievless in uppot t of an application for a hit ildiii&i
perunti with the express understanding that this res iew Ili no way relies en the owner or contractor or their
proiensional enguteer or aivhiiect for sole responsihilits
for full compliance with said codes and standards;
including the building code or 11w any responsihilty for
deficiencies. errom omissions or negligence in these plans whether or not noted in this review.
Date: A00,7 Rcviewer)
RECOMMEND APPROVAL
0 RECOMMEND APPROVAL. AS NOTED
A60
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 12/ 7/07 14:13
HYDRAULIC CALCULATION DETAILS
HYDRAULIC FLOW LOSS
QTY DESCRIPTION LENGTH C ID gpni psi TOTALS
Hydr Ref W Required at Hyd Area 1 188 68.5 psi 1 Pipe 2" DFx21 18' 120 2.703 188 1.5 4 2-1/2" Grvd 90 Eli 120 2.469 188 2.9
Hydr Ref BOR Required at BASE OF RISER 188 72.8 psi 1 Pipe 4" DIx18 Cl 350 20' 140 4.238 188 0.1 4 4" Flngd 90 Eli 40' 120 4.026 188 0.5 1 4" Flngd Back Flow Valve FEBCO "876 CHART LOSS 188 5.3 1 Pipe 4" DIx18 Cl 350 140 4.238 188 0.2 1 4" Flngd Gate Valve 11722tJ" 2' 120 4.026 188 0.0 1 4" •Flngd Tee 20' 120 4.026 188 0.2
Fixed Flow Flow Loss 250 gpm
Hydr Ref SC Required at Source 438 79.2 psi
Water Source100.0 psi static, 95.0 psi residual @ 1405 gpm 438 gpm 99.4 psi
SAFETY PRESSURE 20.2 psi
Available Pressure of 99.4 psi Exceeds Required Pressure of 79.2 psi
This is a safety margin of 20.2 psi or 20 % of Supply
Maximum Water Velocity is 16.5 fps
CRESCENT DEL SOL ESTATES Drawing Date:11-16-07 12/ 7/07 14:13
Page 3
FITTING NAME TABLE
ABBREV. NAME
C
-
Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
HYD REF Hydraulic reference. Refer to accompanying flow diagram.
K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)'l.85 / ID"4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q"2/ID"4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 12/ 7/07 14:13
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K-FACTOR FLOW FLOW DENSITY (FT) (GPM/(PSI-&i)) (PSI)
_____________
(GPM) (GPM) (GPM/SQ.FT)
1 10.17 5.60 10.0
p
17.7
u.rriup -• cr.rr.-
17.0
- in-
0.16 2 10.17 5.60 9.2 16.9 17.0 0.15 3 10.17 5.60 10.4 18.0 17.0 0.16 4 10.17 5.60 11.7 19.2 17.0 0.17 5 10.17 5.60 14.1 21.1 17.0 0.19 6 10.17 5.60 9.9 17.6 17.0 0.16 7 10.17 5.60 10.1 17.8 17.0 0.16 8 10.17 5.60 10.7 18.3 17.0 0.16 9 10.17 5.60 12.1 19.5 17.0 0.17 10 10.17 5.60 14.6 21.4 17.0 0.19 20 10.17 10.1
Al 10.17 18.0
A2 10.17 18.6
Bi 10.17 63.1
W 10.17 68.5
Max velocity of 16.54 occurs in the pipe from A2 TO 10
L
CRESCENT DEL SOL ESTATES Drawing Date:11-16-07 12/ 7/07 14:13
Tyco Fire Products Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv NOTES *******
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 2 TO W (PRIMARY PATH)
16.95 1.080 iT 6.09 9.2 9.2 K = 5.60
2 C=120 5.76 0.0 0.0
16.95 0.083 11.85 1.0 9.2 Vel = 5.99
17.73 1.536 3.71 10.1 10.1
20 C=120 0.00 0.0 0.0 See PATH 3
34.68 0.056 3.71 0.2 10.1 Vel = 6.06
18.02 1.536 11.20 10.4 10.4 K = 5.60
3 C=120 0.00 0.0 0.0
52.70 0.122 11.20 1.4 10.4 Vel = 9.21
19.17 1.536 11.20 11.7 11.7 K = 5.60
4 C=120 0.00 0.0 0.0
71.87 0.217 11.20 2.4 11.7 Vel = 12.57
21.06 1.536 iT 1.00 14.1 14.1 K = 5.60
5 C=120 10.11 0.0 0.0
92.94 0.348 11.11 3.9 14.1 Vel = 16.25
2.203 10.12 18.0 18.0
Al C=120 0.00 0.0 0.0
92.94 0.060 10.12 0.6 18.0 Vel = 7.90
94.59 2.203 5E 137.53 18.6 18.6
A2 C=120 2T 64.10 0.0 0.0 See PATH 2
187.53 0.220 iF 201.63 44.5 18.6 Vel = 15.94
2.703 1E 57.43 63.1 63.1
Bi C=120 9.33 0.0 0.0
187.53 0.081 66.76 5.4 63.1 Vel = 10.59
W 187.53 68.5 K = 22.66
PATH 2 FROM HYDRAULIC REFERENCE 6 TO A2
17.60 1.536 11.20 9.9 9.9 K = 5.60
6 C=120 0.00 0.0 0.0
17.60 0.016 11.20 0.2 9.9 Vel = 3.08
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
CRESCENT DEL SQL ESTATES Drawing Date:11-16-07 12/ 7/07 14:13
Tyco Fire Products Page 6
1-IYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv NOTES *******
POINT Qt Pf/ft TOTAL Pf Pn
PATH 2 FROM HYDRAULIC REFERENCE 6 TO A2 CONTINUED
17.76 1.536 11.20 10.1 10.1 K = 5.60 7 C=120 0.00 0.0 0.0
35.35 0.058 11.20 0.7 10.1 Vel = 6.18
18.32 1.536 11.20 10.7 10.7 K = 5.60 8 C=120 0.00 0.0 0.0
53.68 0.126 11.20 1.4 10.7 Vel = 9.39
19.50 1.536 11.20 12.1 12.1 K = 5.60
9 C=120 0.00 0.0 0.0
73.17 0.224 11.20 2.5 12.1 Vel = 12.79
21.42 1.536 iT 1.00 14.6 14.6 K = 5.60
10 C=120 10.11 0.0 0.0
94.59 0.360 11.11 4.0 14.6 Vel = 16.54
A2 94.59 18.6 K = 21.92
PATH 3 FROM HYDRAULIC REFERENCE 1 TO 20
17.73 1.536 7.49 .10.0 10.0 K = 5.60
1 C=120 0.00 0.0 0.0
17.73 0.016 7.49 0.1 10.0 Vel = 3.10
20 17.73 10.1 K = 5.57
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
Job Water Required Hose Allowance CRESCENT DEL SOL ESTATES Static Pressure: 100.0 psi Pressure: 79.2 psi Inside: 0 gpm 234/236 DATE AVENUE Residual Pressure: 95.0 psi System Flow: 188 gpm Outside: 250 gpm CARLSBAD, CA Flow: 1405 gpm System+Hose: 438 gpm Remote Area: I Date: 11-29-07 Safety Pres: 20.2 psi
Loc: SITE Head Elev Pres: 68.5 psi
140-- I I I I I I I I
120 -
1001 Su
P 80 hose
S
I 68.5
60 -
40 -
20
100 150 200 250 300 350 400 450 500
Flow (anm
tqCC /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series TY-FRB -
Upright, Pendent,
Quick Response,
General
Description
The Tyco® Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TV-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in afire situation or cause
if to operate prematurely.
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The-owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TYII3I - Upright 2.8K, 1l2"NPT
TV1231 - Pendent 2.8K, 1I2"NPT
TY2131 - Upright 4.2K, 112"NPT
TY2231 - Pendent 4.2K, 1I2"NPT
TY3131 - Upright 5.6K, 1!2"NPT
TY3231 - Pendent 5.6K, 1l2"NPT
TY4131 - Upright 8.0K, 3I4"NPT
TY4231 - Pendent 8.0K, 314"NPT
TY4831- Upright 8.0K, 112"NPT
TY4931- Pendent-8.0K, 1I2"NPT
28,4.2,5.6, and 8.0 K-factor
and Recessed Pendent Sprinklers
Standard Coverage
Page 20f 10 TFPI7I
ESCUTCHEON
PLATE SEATING
SURFACE
I \2-1/4"
(57,2 mm)
1-9/16"
(39,7 mm)
SSP DEFLECTOR * 2-7/8"(73,0 mm) DIA.
SSU*
DEFLECTOR
iL
7/16" 1
(11,1 mm) I
NOMINAL I
MAKE-IN
I 2-3/16" WRENCH t (55,6 mm) FLATS
1/2"NPT
7/16"(11,1 mm) STYLE 10or20
NOMINAL RECESSED
NPT MAKE-IN ESCUTCHEON
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5-Compression 7-Bushing orifice seat on frame. Screw
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYII3I) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 112 INCH NPT
ESCUTCHEON 7/116"(1111,11 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE 1/2" MAKE-IN ESCUTCHEON SSU
NPT DEFLECTOR
2-3116"
(N(
mm) (55,6 mm) -* NAL
_______
"
6*
1-1/2" III ii il/ -IN 2 3/
WRENCH
____
FLATS
(55,6mm)(38,1mm) I
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. -""I 1/2" NPT t
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5-Compression orifice seat on frame. Screw
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
TFPI7I Page 3of 10
ESCUTCHEON 7/16"(11.1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED * SURFACE NPT MAKE-IN ESCUTCHEON SSU
DEFLECTOR
(55,6 mm) J NOMINAL
FLATS 3
*
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
- Frame 3-Sealing 4-Bulb 6-Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw
FIGURE 3 -
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
STYLE 30 or 40
RECESSED ssu ESCUTCHEON DEFLECTOR
6*
ESCUTCHEON 1/2"(12,7 mm)
PLATE SEATING NOMINAL
SURFACE MAKE-IN NPT
*-T 2_J16"
(58,7 mm)
1-9/16"
(39,7 mm) WRENCH
FLATS
SSP DEFLECTOR * l 2-7/8"(73,0 mm) D. 3/4" NPT
PENDENT RECESSED PENDENT UPRIGHT
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
I 2-1/4"
(57,2 mm)
5
il
r
CROSS SECTION
I - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5-Compression orifice seat on frame. Screw
FIGURE 4
QUICK RESPONSE SERIES 7Y-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3M INCH NPT
7/16"(11,1 mm)
NOMINAL SSU
MAKE-IN DEFLECTOR 1/2"
NPT
2
(57,
sSP*
DEFLECTOR
PENDENT UPRIGHT
CROSS
SECTION
Page 40110 TFPI7I
- Frame 3-Sealing 4- Bulb 6- Deflector * Temperature rating is Indicated on deflector or adjacent to 2- Button Assembly 5-Compression orifice seat on frame. Screw
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
LO K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approve( information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psill2 (40,3 LPM/barl'2)
K = 4.2 GPM/psi112 (60,5 LPM/bar1'2)
K = 5.6 GPM/psi112 (80,6 LPM/bar112)
K = 8.0 GPM/psi112 (115,2 LPMIbarl12)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
4.-
TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
CHROME
PLATED
I WHITE'""
JPOLYESTER
2.8
1/2"
PENDENT
(TY1231)
and
UPRIGHT
(TYII3I)
135°F157°C Orange
1,2,3,5
155°F/680C Red
175°F179°C Yellow
200°F/93°C Green
286°F/141°C Blue
NPT 135°F/57°C Orange
1,2,5
RECESSED
PENDENT
(rv1231)'
Figure 6
155°17/680C Red
175°F/79°C Yellow
200°F/93°C Green
135°F157°C Orange
RECESSED
(rY1231)""
Figure 7
PENDENT
155'F168"C Red
175°F179°C Yellow
200°F193"C Green
4.2
1/2'
NPT
PENDENT
(M231)
and
UPRIGHT
(TY2131)
135°F/57°C Orange
1,2
155°F/680C Red
1756F1790C Yellow
200°F/93"C Green
286"F/141°C Blue
135°F157°C Orange
RECESSED
PENDENT
(TY2231)*
Figure 8
155"F/68°C Red
1750F/790C Yellow
200°F/93°C Green
135°F157°C Orange
RECESSED
PENDENT
(Y2231
Figure 9
1556F/680C Red
175"F/79'C Yellow
200°F193°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use In Canada (C-UL) as Quick Re-
sponse Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers. * Installed with Style 10(112" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Page 5 of 10
Page 6 of 10 TFPI7I
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. I BULB
LIQUID
NATURAL
BRASS
VCHROME
PLATED
WHffE
POLYESTER
I LEAD
COATED
-
5.6
1/2"
PENDENT
and
UPRIGHT
M131)
135°F/57°C Orange
"M31)1,2,3"M31)1,2,3,4,5,6,7
1550F/680C Red
175°F179°C Yellow
200°F/93°C Green
286°F/141°C Blue
NPT 1350F157°C Orange
1,2,4,5 N/A
RECESSED
PENDENT
(Y3231)*
Figure 10
1550171680C Red
175°F/79°C Yellow
193°C
E
Green
/57"C Orange
1, 2, 3,4,5 N/A
RECESSED
PENDENT
(TY3231)
Figure 11
155°F/68°C Red
175°F/79"C Yellow
200"F/93°C Green
-
8.0
3,4"
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135°F/57°C Orange
1,2, 3,4,5, 6,7
1,2,5 155°F/68°C Red
175017/790C Yellow
200017/93"C Green
286°F/141°C Blue
NPT 135°F/57°C Green
1,2,4,5 N/A
RECESSED
PENDENT
(TY4231)*
Figure 12
155"F/68'C Orange
175°F179°C Red
2000171930C Yellow
135017/570C Orange
1,2,3,4,5 N/A
RECESSED
PENDENT
(rv4231)-
Figure 13
155617/680C Red
175°17/796C Yellow
200°F/93°C Green
-
8.0
1/2"
NPT
PENDENT
(T'V'4931)
and
UPRIGHT
(TY4831)
ff
1350F/570C Orange
1, 2,4,5, 6
1, 2, 5 155°F/68°C Red
1750F1790C Yellow
200"F/93°C Green
286'F/141-Cl Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k104) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA354-01-E.
VdS Approved (For details contact Tyco Mre & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* installed with Style 10(1/2" NPT) or Style 40(314" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** installed with Style 20 (1/2" NP or Style 30 (314" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12.1 BAR) N/A 1/2" RECESSED PENDENT NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (1Y4131) 175 PSI (12.1 BAR) N/A
RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12.1 BAR)
5.6 UPRIGHT (TY3131) OR
10 175 PSI (12,1 BAR) RECESSED PENDENT NPT (TY3231) (SEE NOTE NIA
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12.1 BAR)
8.0 UPRIGHT (TY4131)
RECESSED PENDENT NPT (1Y4231) N/A
8.0 PENDENT (TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (1Y4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/570C to 3/32
inch (2,4 mm) for the 286°F/14 1°C
temperature ratings.
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tamed with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series 1Y-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be Installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler Into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Page 8 of 10
- 2-7/8" DIA.
5/8±1/4" (73.0 mm) I 3/4"(19,11 mm)
- (15,90,4 mm) - 2-1/4" DIA. 1/4" (6,4 mm) I
FACE OF (57 2 mm)
-;::;i I MOUNTING I SPRINKLER / PLATE I FITTING
1/8"
MOUNTING
CLOSURE SERIES 11-5/116"(33.1 mm)1
SURFACE//'
TY-FRB 13116"(20,6 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
5/8±1/4" (73,0 mm) 34"(194 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (572 MOUNTING SPRINKLER 7J1 PLATE FITTING
iLiJ
4
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(119,11 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
2-7/8" DIA.
(73,0mm) 1/2±1/8" I 1/2"(12,7 mm) r (12,70.2 mm) 2-1/4" DIA. I 114" (6.4 mm) I I FACE OF
PLATE I SPRINKLER
(57.2 mm) MOUNTING I
FITTING
/
____
(3,2mm)
j/;-
1/8" I
MOUNTING f t SURFACE
CLOSURE SERIES 1-5/16" (33.3 mm)f
TY-FRB 1-1/16" (27,0 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-718* DIA. -
1/2±1/8" (73,0 mm) I 1/2" (12,7 mm)
1 (12,7±3.2 mm) 2-1/4" DIA. 1/4" (6,4 mm) I
I FACE OF (57,2 mm) I MOUNTING I I SPRINKLER I I PLATE I FITTING
01/ 4
T \
MOUNTING
SURFACE
CLOSURE SERIES I- 1/4" (31 8mm)
TYFRB 1" (25,4 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Care and
Maintenance
The Series TY-FRB Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from The proper authorities
and all personnel who maybe affected
by this action must be notified.
The owner must assure that The sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been corn-
TFPI7I
2-7/8" DIA. •
5/8±1/4" (73,0 mm) I 3/4'(19,1 mm)
(15,9±6,4 mm) - 2-1/4" DIA. I 1/4" (6,4 mm) I
I FACE OF 57,2 MOUNTING SPRINKLER PLATE FITTING
1/8"
Au
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
TV-FRB 3/4" (19,1 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA. -
5/8±1/4" (73,0 mm) 3/4.(19.1 mm)
- (15,9±8,4 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF I (57,2 mm) TJ MOUNTING
SPRINKLER 'c - PLATE
FITTING
(3,2 mm)
_____ _____
MOUNTING
SURFACE
I . 4 CLOSURE SERIES 1-5/16"f33 mm)
TYFRB 13/16"(20.6 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT
Page 9 011''10
- 2-7/8" DIA
(73.0 mm) I 1/2±1/8" j 1/2" (12,7 mm) r (12,70.2 mm) 2-1/4" DIA. I 1/4"(6,4 mm) I
I SPRINKLER I PLATE
I FACE OF
157.2
mm) MOUNTING
I FITTING
1/8"
t \
MOUNTING
SURFACE 7W1
SERIES 1-1/4' (31,8 mm) CLOSURE 1YFRB 1"(25,4 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7I8 DIA.
(73,0 mm) I 1/2"(12,7mm)
(12.7±3,2 mm) f 24/4" DIA. I 1/4" (6,4 mm)
I FACE OF MOUNTING
SPRINKLER
FITTING
(57,2mm)
PLATE
13 2 I 'I
t \ —
MOUNTING
SURFACE
CLOSURE SERIES 1-&16"(33,3 mm)
TY-FRB 1-1/16"(27.0 mm)
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHINGAREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes.
Page 10 of 10 TFPI7I
PIN 57-XXX-X--XXX
I MODELJSIN I
1
I
4
3
9
7
TY4131
SPRINKLER
NATURAL BRASS
WHITE POLYESTER
WHITE (RAL95IO)*
CHROME PLATED
LEAD COATED
I RATING ..L...
135 1356171570C
155 155F/68°C
175 175Ffl9eC
200 2000F193°C
286 286°F11418C
* Eastern Hemisphere sales only.
330 2.8K UPRIGHT (1/2"NPT) TY1131
331 2.8K PENDENT (112"NPT) TY1231
340 4.2K UPRIGHT (112"NPT) 1Y2131
341 4.2K PENDENT (112"NPT) TY2231
370 5.6K UPRIGHT (112"NPT) TY3131
371 5.6K PENDENT (112"NPT) TY3231
390 8.0K UPRIGHT (314"NPT)
391 8.0K PENDENT (3/4 N PT) TY4231
360 8.0K UPRIGHT (1/2*NPT) TY4831*
361 8.01< PENDENT (10NPT) 1Y4931*
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
Installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN) Quick
Response, (specify K-factor), (specify
temperature rating), Series TV-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-ish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
MODEL 876V DOUBLE CHECK DETECTOR ASSEMBLY
(Shown in vertical orientation)
U.S. Patent No. 4,989,635 • U.S. Patent No. 5,107,888
U.S. Patent No. 5,385,166 • U.S. Patent No. 5,226,441
U.S. Patent No. 5,392,803 • U.S. Patent No. 5,503,176
MODEL 876V DOUBLE CHECK DETECTOR ASSEMBLY
(Shown in standard orientation)
ES-F-876V
MasterSeries® 876V
Double Check Detector Assemblies
Size: 2½" - 10" (65mm - 250mm)
The FEBCO MasterSeriesO 876V Double Check Detector Assemblies are
designed for use in non-health hazard fire sprinkler systems.
Standard orientation is inlet flow vertical up, outlet flow vertical down.
Vertical orientation is inlet and outlet flow vertical up.
Materials
Main Valve Body: Ductile iron Grade 65-45-12
Coating: Fusion epoxy coated internal and external
AWtAJA C550-90
Shutoff Valves: OS&Y resilient wedge gate
valves AWWA C509
Trim: Bronze
Elastomer Discs: EPDM
Spring: Stainless steel
Models
Valve Setter with MJ x MJ, MJ x FL or FL x FL ends
End Connections - Flanged ANSI B16.1 Class 125
Pressure - Temperature
Maximum Working Pressure: 175psi (12.1 bar)
Hydrostatic Test Press: 350psi (24.1 bar)
Temperature Range: 32°F to 140°F (0°C to 60°C)
Approvals - Standards
ANSI/A\MNA (C510)
Approved by the Foundation for Cross-Connection Control and Hydraulic
Research at the University of Southern California.
®
*
Approved C®US
1048 864.5
* Less gate not FM approved. Less gate not UL Classified unless installed
with UL Listed gate valves
Job Name Contractor
Job Location Approval
Engineer Contractor's RO. No.
Approval Representative
FEBCO product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise mea-
Model 876V / Materials of Construction
U DESCRIPTION MATERIAL U DESCRIPTION MATERIAL # DESCRIPTION MATERIAL
1 Body A536 GR 65.4502 8 Lower Sprg. Retainer B584 Alloy C836O0 350-ring EPDM ASTM D1999
2 Cover A536 GR 6545-12 Spring Stem 304SS 35.1 Back UpRing Acetal Resin
2.1 0-ring EPDMASTMD2000 9.1 Elastic Stop Jam Nut 188SS 36 Cover B584AllC83600
2.2 Cap Screw Plated Steel 10 Spnng A31131ype 631 SS 40 BailVake 8584 Alloy C83600
23 Hex Nut Plated Steel 102 Spring Shim Acetal Resin 41 Nipple Brass
2.5 Cover (wibholes) A536 GR 6545-12 103 Spring Shim Acetal Resin 42 GateVave(0S&) AWrNAC509
3 Seat Ring 8524Alloy C83600 11 Spring Guide B130AflrC22000 43 Bulkhead Frtting B584Aff,C83600
31 Gasket EPDMASTMD2000 12 Upper Sprg. Retainer B584AlloyC83600 43.1 Bulkhead Fitting B584 Alloy C83600
4 Arm B584Albt, C83600 12.1 Bushing Sprg. Stem Acetal Resin 44 Bulkhead Fitting B584ftJ1oy C83600
4.1 Bushing-Swing Pin Metal Resin 13 Pivot Bearing B5B5 Alloy C83600 45 Gasket EPDMASTM D2000
4.2 Swing Pin 304S5 14 Flange Gasket Rubber/Fabric 45.1 Gasket EPDMASTMD2001
5 Retaining Clip 3025S 15 Bearing Socket AcetaiResin 46 Washer B36 Alloy 260
5.1 Retaining Clip 30255 16 Hex Jam Nut 188SS 46.1 Washer B36 Alloy 260
6 Check Disk (2W-81 EPDM Coated GR, 45 Capscrew(1(1) 188SS 47 Nut 8584AlloyC83601
Ductile Iron w/type 17 Washer 302S5 471 Nut B584 Alloy C63602
3045S 18 Flange Nut PlatedSteel 60 Identification Plate B36 Alloy C26000
Seat Disc MY) Silicone ASTMD2000 18.1 Range Nut Plated Steel 61 Identification Plate B36ftJkC26000
6.1* Disc Holder (101 ASIM A743 304 ss 19 Cover 436 Stt Epoxy Coated 62 Drive Screw Stainless Steel
6.2* Disc Retainer (10) ASTM A43 304 SS 24 Bolt Plated Steel 70 Clamp 8?BV Only AWNAC6O6
6.3 Capsorew iioi ss 24.1 Washer Plated Steel
7 1 .I 25 Nut Plated Steel
Model 876V Model 876V
Standard Orientation Vertical Orientation
Note: The Series 876V is shipped in the standard
(N-Shape) orientation as shown above.
OS&Y Side V
Dimensions - Weights
Size: 21/a" - 10" (65 - 250mm)
SIZE(DN) DIMENSIONS WEIGHT
EL -
A
in. I mm
B
in. I mm
C
in. I mm
El OS&Y
in. I mm
F
in. mm
G
in. I mm
H
I in. I mm
J
in. I mm
K
in. I mm
M
in. I mm
OS&Y
tbs. kgs.
2½ 65 12% 318 25/4 654 241A 616 16% 416 16% 422 61/4 159 111h 292 3½ 89 13% 346 271/4 692 230 104
3 80 12½ 318 253/4 654 24/4 629 22¼ 565 16% 422 6¼ 159 11½ 292 3~ 95 141A 359 281/4 718 300 136
4 100 14 356 27% 708 26~ 680 23'/4 591 13 330 4½ 114 15½ 394 31 787 330 150
6 150 16 406 32¼ 819 32¼ 819 30', 765 21,4 203 13 330 5½ 140 18% 473 37¼ 946 520 236
8 200 18½ 470 37½ 953 36% 924 37% 959
17/4C4517178
24% 235 14½ 368 6% 172 20% 527 41½ 1054 860 390
10 250 21 533 42½ 1080 40~ 1035 48 1219 27½254 1 15 381 8 203 24 610 48 1219 1460 662
'OS&Y OPEN
Weights do not include risers or optional valve seller.
Note: Dimensions shown are nominal. Allowances must be made for normal manufacturing tolerances.
Flow 9 C min ?
Flow
ir mm r mm
mm
0mm)
_____________
i
-
All 11 "1 -.1
97 14
83 12
69 10
41 6
284
14 2
00
IcPa psi
110 16
97 14
83 12
69 10
D550
41 6
204
14 2
00
0
msi 1mm imm 4553 1355 $J gpm
1960 3880 5600 7560 3480 11350Ipm
r(200mm)
TvDical Installation
Standard orientation (Series 816V) Verticaf orientation (Series 876V)
18°min
(450mm) ir mm
IIh.n.% I
(100mm) _______ - "- Pipe Support
-01~ IF
(100mm
°r valve weight only.
NAM *Aft 4fl min (furnished by customer)
Optional Valve Recommended Seter minimum clearances
from permanent
structures for ease
of testing and
maintenance are shown
on above drawings. Capacity
kPa pi 2t1f(65mm) kPa pd 61150mm)
110
97
0093
69
55
41
28
14
W lixi iu zmi ax axgpm
190 380 570 760 950 1140 km
kPa psi 4 (100mm)
124 It - - - - - - -
110 it —
97 I -
41
'
-
83 it —A
69 W --
= 56 8 — — — —
28 4
142_— I 4 -
0 380 160 1140 1520 1902 2200 2660
A-Vertical orientation
B-Standard orientation
110 16
97 14
83 12
69 10
55
= 41 8
284
14 2
00
ir (250mm)
B
0 1060 2800 2450 4080 6000gpm
0 3860 7560 11350 15140 18000 1pm
The 6 and 10 flow curves (B-standard orientation) include the
FEBCO Valve Setter Series 611.
A Division of Watts Water Technologies, Inc. USA: 4381 N. Brawley • Ste. 102 • Fresno, CA • 93722 • Tel. (559) 441-5300 • Fax: (559) 441-5301 • www.FE8C0online.com
Canada: 5435 North ServIce Rd. • Burlington, ONT. • 1-71- 51-17 9 Tel. (905) 332-4090 • Fax: (905) 332-7068 9 www.FEBC0online.ca
Tol-Brace Seismic Calculations
Project CRESCENT DEL SOL
it
VANGUARD FIRE PROTECrlON Address.
. 925 POINSETTIA AVE SUITE'?I
. .•
234/236 DATE
....
VISTA, .1 •';..'I.'.;.. V , I
487475
CARLSBAD, CA 760-727-8540
Job # Calculations based on 2002 NFPA Pamphlet #13 with TIA 02-1
Brace Information Tolco Brace Components
Tolco Component Fig. Number Adjusted Load Maximum Spacing 10'-0" (3.08m)
Fig. 1000 Clamp 567 lbs. (257 Kg.) Length of Brace 7 '- 0 "(2.2m) Fig. 980 Universal Swivel 2395 lbs. (1086 Kg.)
Bracing Material 1" Sch.40 *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for Tolco components only.
A Angle from Vertical W Ifl. Use of any other components voids these calculations and the
listing of the assembly.
Least Rad. of Gyration 0.42" (11mm) Assembly Detail
LIR Value 200
Maximum Horizontal Load 3061 lbs. (1388Kg.) VNI'VERS'AL $'-WAY
BRACE FITflNG
TC•LC: FIG. 1000
FAST CLAMP- -..
Fastener Information
STEEL PIPE
_. . Fastener Orientation NFPA Type C LATERAL
4? BR-ACE
Type Wedge Anchor
Diameter 3/8in. (10mm) 600 Mm. From vertical
Length 3m. (76mm) Brace Identification on Plans A
Maximum Load 615 lbs. (279Kg.) Orientation of Brace Lateral
Load Information
Size and Type of Pipe Total Length Total Calculated Load
2W(63mm) Schedule 7 Pipe 10 ft. (3m) 26 lbs. (12Kg.)
Percentage added for Fittings and Sprinklers 15% 4 lbs. (1.74Kg.)
Total Adjusted Load of all pipe within Zone of Influence 29 lbs.(14Kg.)
(Tol-Brace Version 5.1.67)
Tol-Brace Seismic Calculations
For
CRESCENT DEL SQL
234/236 DATE Job #
Brace Identification
Brace Type (Per NFPA#13)
Spacing of Brace
Orientation of Brace
Bracing Material
Length of Brace
Slenderness Ratio used for Load Calculation
True Angle of Brace for Calculation
Type of Fastener
Length of Fastener
A
NFPA Type C
10 Ft.(3m)
Lateral
1" Sch.40
7Ft. (2m)
200
60°
318in. (10mm) In. Wedge Anchor
3m. (76mm) In.
Summary of Pipe within Zone of Influence
2% inch Sch. 7 10 Feet (3m)
Allowance for Heads and Fittings 0.15%
Conclusions
Total Adjusted Load of Pipe in Zone of Influence 29 Ibs.(13Kg.)
Material Capacity 3060.5991574859 lbs.(1388Kg.)
Fastener Capacity 615 lbs.(279Kg.)
Fig. 1000 Clamp 567 Ibs.(257K9.)
Fig.980 Universal Swivel 2395 Ibs.(1086Kg.)
Structural Member: CONC DECK*
Calculations prepared by SB
*The description of the Structural Member is for informational purposes only.
Toi.Brace software calculates the brace assembly only, not the structure it is attached to.
Calculated with 101-Brace 5.1 vtsft us atvus.tolco.com
Tol-Brace Seismic Calculations
Project CRESCENT DEL SOL Address. VANGUARD FIRE PROTECTION
925 POINSETTIA AVE SUITE ti •. ...
234/236 DATE VISTA, CA 92081 ?.I
487475
CARLSBAD, CA 760-727-8540
Job # Calculations based on 2002 NFPA Pamphlet #13 with TIA 02-1
Brace Information Tolco Brace Components
Tolco Component Fig. Number Adjusted Load Maximum Spacing 1O'-O" (3.O 8m)
Fig.4 Clamp 342 lbs. (155 Kg.) Length of Brace 7 - 0 "(2.2m) Fig. 980 Universal Swivel 2395 lbs. (1086 Kg.)
Bracing Material 1" Sch.40 *Calculation Based on CONCENTRIC Loading
*Please Note: These calculations are for Tolco components only.
ng.e from Angle I Vertical
.
60° Mm Use of any other components voids these calculations and the
listing of the assembly.
Least Rad. of Gyration 0.42" (11mm) Assembly Detail
LiR Value 200 TOLCO FIG. 'sc'
Maximum Horizontal Load 3061 lbs. (1388Kg.)
UNIVERSAL SWAY ..
BRACE FITTING TYP.
STEEL FIFE
LATERAL -- • /' BRACE -
Fastener Information TOLCO FIG. 4.4
FIFE CLAMP FOR
SWAY BRACING
Fastener Orientation NFPA Type C
Type Wedge Anchor
Diameter 3/81n. (10mm) 600 Mm. From Vertical Detail 01241
Length 3m. (76mm) Brace Identification on Plans B
Maximum Load 615 lbs. (279Kg.) Orientation of Brace Longitudinal
Load Information
Size and Type of Pipe Total Length Total Calculated Load
2Y2"(63mm) Schedule 7 Pipe 10 ft. (3m) 26 lbs. (12Kg.)
Percentage added for Fittings and Sprinklers 15% 4 lbs. (1.74Kg.)
Total Adjusted Load of all pipe within Zone of Influence 29 lbs.(14Kg.)
(Tol-Brace Version 5. 1.67)
Tol-Brace Seismic Calculations
For
CRESCENT DEL SQL
234/236 DATE Job #
Brace Identification
Brace Type (Per NFPA#13)
Spacing of Brace
Orientation of Brace
Bracing Material
Length of Brace
Slenderness Ratio used for Load Calculation
True Angle of Brace for Calculation
Type of Fastener
Length of Fastener
B
NFPA Type C
10 Ft.(3m)
Longitudinal
Sch.40
7Ft. (2m)
200
60°
3181n. (10mm) In. Wedge Anchor
3m. (76mm) In.
Summary of Pipe within Zone of Influence
2% inch Sch. 7 10 Feet (3m)
Allowance for Heads and Fittings 0.15%
Conclusions
Total Adjusted Load of Pipe in Zone of Influence 29 lbs.(13Kg.)
Material Capacity 3060.5991574859 Ibs.(1388Kg.)
Fastener Capacity . 615 Ibs.(279Kg.)
Fig.4 Clamp 342 lbs.(155Kg.)
Fig.980 Universal Swivel 2395 lbs.(1086Kg.)
Structural Member: CONC DECK*
Calculations prepared by SB
The description of the Structural Member Is for informational purposes only.
Tol-Brace software calculates the brace assembly only, not the structure it is attached to.
Calculated with Tot-Brace 5.1
vtslt us at wvm.tot.cOm
Tol-Brace Seismic Calculations
Project CRESCENT DEL SOL Address.
.......................
VANGUARD FIRE PROTECTION
925 POINSETTIA AVE SUITEII •..,.......,.......'
234/236 DATE VISTA, CA 92081 ..........•.
487475
CARLSBAD, CA 760-727-8540
Job # Calculations based on 2002 NFPA Pamphlet #13 with hA 02-1
Brace Information Tolco Brace Components
Tolco Component Fig. Number Adjusted Load Maximum Spacing 80'-0" (24.64m)
Fig.4 Clamp 342 lbs. (155 Kg.) Length of Brace 7'- 0 "(2.2m) Fig. 980 Universal Swivel 2395 lbs. (1086 Kg.)
Bracing Material 1" Sch.40 *Calculation Based on CONCENTRIC Loading
*please Note: These calculations are for Tolco components only.
A Angle from Vertical RO O Use of any other components voids these calculations and the
listing of the assembly.
Least Rad. of Gyration 0.42" (11mm) Assembly Detail
LIR Value 200 TOLCO FIG. 80
Maximum Horizontal Load 3061 lbs. (1388Kg.)
UNIVERSAL SWAY -
BRACE FITTING TYP.
STEEL PIPE
LATERAL - BRACE
Fastener Information TOLCO FIG. 4A
PIPE CLAMP FOR
Fastener Orientation NFPA Type C
SWAY BRACING
Type Wedge Anchor . )
Diameter 3/81n. (10mm) 60 Mm. From Vertical
Length 3m. (76mm) Brace Identification on Plans D
Maximum Load 615 lbs. (279K0.) Orientation of Brace Longitudinal
Load Information
Size and Type of Pipe Total Length Total Calculated Load
2W(63mm) Schedule 7 Pipe 80 ft. (24.4m) . 204 lbs. (93Kg.)
Percentage added for Fittings and Sprinklers 15% 31 lbs.(13.88Kg.)
Total Adjusted Load of all pipe within Zone of Influence 235 Ibs.(107Kg.)
(ToI.Brace Version 5.1.671
Tol-Brace Seismic Calculations
For
CRESCENT DEL SOL
234/236 DATE Job #
£. UI e-
Brace Identification
Brace Type (Per NFPA#13)
Spacing of Brace
Orientation of Brace
Bracing Material
Length of Brace
Slenderness Ratio used for Load Calculation
True Angle of Brace for Calculation
Type of Fastener
Length of Fastener
0
NFPA Type C
80 Ft.(24m)
Longitudinal
1" Sch.40
7Ft. (2m)
200
600
3/8in. (10mm) In. Wedge Anchor
3m. (76mm) In.
Summary of Pipe within Zone of Influence
21,4 inch Sch. 7 80 Feet (24m)
Allowance for Heads and Fittings 0.15%
Conclusions
Total Adjusted Load of Pipe in Zone of Influence 235 Ibs.(107Kg.)
Material Capacity 3060.5991574859 lbs.(1388Kg.)
Fastener Capacity 615 lbs.(279Kg.)
Fig.4 Clamp 342 Ibs.(155Kg.)
Fig.980 Universal Swivel 2395 lbs. (1 086Kg.)
Structural Member: CONG DECK*
Calculations prepared by SB
*The description of the Structural Member is for informational purposes only.
Tot-Brace softare calculates the brace assembly only, not the structure it is attached to. Calculated with Tot-Brace 5.1 visit us at .tolco.com