HomeMy WebLinkAbout7180 AVENIDA ENCINAS; ; FA080078City of Carlsbad
Fire Alarm Permit
Permit No: FA080078
7180 AVENIDA
Job Address: Status: ISSUED
ENCINAS
Permit Type: FALARM Applied 11/6/2008
Parcel No: 2144301900 Approved: 11/12/2008
Lot #: 0
Reference No.: Issued: 11/12/2008
PC #: Inspector:
Project Title: POINSETTIA VILLAGE (7180-7188)2 FIRE ALARM INSPECTIONS @
$65/EA
Applicant:
JJJ ENTERPRISES
533 S VINEWOOD ST
ESCONDIDO CA
760-747-3050
Owner:
OBERLIN PARTNERS L L C
P 0 BOX 2062
DEL MAR CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
130 0 130 0
rjc)900:4~
FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS
POINSETTIA VILLAGE
7180-7188 AVENIDA ENCINAS
CARLSBAD, CA 92011
FIRE ALARM SYSTEM
POINSETTIA VILLAGE
7180-7188 AVENIDA ENCINAS, CARLSBAD, CA 92011
Bill of Materials
NOTIFIER NFW-50 FIRE ALARM CONTROL PANEL
CSFM# 7165-0028:239
NOTIFIER NOT- BG12LX ADDRESSABLE MANUAL PULL STATION
CSFM# 7150-0028:199
NOTIFIER NP-100 ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR
CSFM# 7272-0028:231
NOTIFIER NMM-100P ADDRESSABLE MONITOR MODULE
CSFM# 7300-0028:230
WHEELOCK SERIES ZNS-MCW AUDIBLE STROBE APPLIANCES
CSFM# 7125-0785:142
cc
Ce
1 -app",
the
cC
, oc COfl ce'at.\
çoc
aC oc oc
OtC
of Tkot
- jat1 /1 4 OS
tCV
0010 Xpoko .4 PL.
0-1
DN-7102:A • A1-60
FireWarden-50(11E) NOTIFIER ®R Intelligent Addressable FACP
with Built-In Communicator by Honeywell
-- ; .:
.•. -- - :Li - ..
General
The NOTIFIER FireWarden-50 NFW-50 is a Fire Alarm Control
Panel (FACP) and Digital Alarm Communicator/Transmitter
(DACT) combined into one circuit board. This compact, intelli-
gent addressable control panel supports up to 50 addressable
devices in any combination of detectors or modules. With an
extensive list of powerful features, the FireWarden-50 pro-
grams just like FireWarden-100 products, yet fits into applica-
tions previously served only by conventional panels.
The FireWarden-50's integral DACT transmits system status
(alarms, troubles, AC loss, etc.) to a Central Station via the
public switched telephone network.
The power supply and all electronics are contained on a single
circuit board supported on a new quick install chassis and
housed in a metal cabinet. Available accessories include
remote annunciators and reverse polarity/city box transmitter.
(4XTM)
NOTE: Unless otherwise specified, the term FireWarden-50 is
used in this data sheet to refer to both the FireWarden-50 and the
FireWarden-50(E) FACPs.
Features
Listed to UL Standard 864, 9th edition.
Auto-program (learn mode) reduces installation time.
Reports two devices set to the same address.
On-board DACT.
20 software zones.
Two independently programmable Style Z (Class A) or Style
Y (Class B) NAC circuits.
Selectable strobe synchronization for System Sensor,
Wheelock, and Gentex devices.
Remote Acknowledge, Silence, Reset and Drill via address-
able monitor modules.
Two programmable relays and one fixed trouble relay.
Integral 80-character LCD display with backlighting.
Real-time clock/calendar with automatic daylight savings
control.
History file with 500 event capacity.
Detector sensitivity test capability (NFPA 72 compliant).
Maintenance alert warns when smoke detector dust accu-
mulation is excessive.
One person audible or silent walk test with walk-test log and
printout.
Point trouble identification.
Waterflow (nonsilenceable) selection per monitor point.
System alarm verification selection per detector point.
PAS (Positive Alarm Sequence) and Pre-signal per point
(NFPA 72 compliant).
Up to eight ANN-BUS annunciators.
SLC COMMUNICATION LOOP:
Single addressable SLC loop which meets NFPA Style 4, 6
and 7 requirements.
50 addressable device capacity (any combination of
addressable detectors and modules).
Compatible with NOTIFIER FireWarden addressable
devices (refer to the FireWarden SLC Wiring Manual).
NOTIFICATION APPLIANCE CIRCUITS (NACS):
Two independently programmable output circuits. Circuits
can be configured for the following outputs:
- Style Y (Class B)
- Style Z (Class A)
- Door Holder Service
- Aux Power Source
Silence Inhibit and Autosilence timer options.
Continuous, March Time, Temporal or California code for
main circuit board NACs with two-stage capability.
Selectable strobe synchronization per NAC.
2.5 A total power for NACs.
NOTE: Maximum or total 24VDC system power shared between
all NAG circuits and the ANN-BUS is 2.7 A.
PROGRAMMING AND SOFTWARE:
Autoprogram (learn mode) reduces installation time.
Custom English labels (per point) may be manually entered
or selected from an internal library file.
Two programmable Form-C relay outputs.
20 software zones.
Continuous fire protection during online programming at the
front panel.
Program Check automatically catches common errors not
linked to any zone or input point.
DN-71 02:A • 04/09/07 -Page 1 of 4
User interface
LED INDICATORS
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Alarm Silenced signals (yellow)
KEYPAD
16 key alpha-numeric pad.
Acknowledge/Step
Alarm Silenced
Drill (Manual Evacuate)
Reset (tamp test)
Ordering Options
NFW-50(E): Combination DACT/Fire Alarm Control Panel
with one SLC loop. Includes main circuit board with display,
chassis with transformer, backbox with door, plastic bag con-
taining screws, cables, key, etc., manual.
NFW-50R: Same as NFW-50, with red backbox and door.
DP-51050B: Optional dress panel for the FireWarden-50.
TR-CE-B: Trim Ring for semi-flush mounting.
BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
NFS-LBB: Battery box, houses two 55 AH batteries
CHG-75: Battery charger for lead-acid batteries with a rating
of 25 to 75 AH.
BAT Series: Batteries, see data sheet DN-6933.
PRTIPK-CABLE: Cable printer/personal computer interface
cable.
PRN-6: UL listed compatible event printer. Uses tractor-fed
paper.
OPTIONAL MODULES
4XTM Reverse Polarity Transmitter Module: Provides a
supervised output for local energy municipal box transmitter,
alarm and trouble. Includes a disable switch and disable trou-
ble LED.
COMPATIBLE ANNUNCIA TORS
N-ANN-SO: Remote LCD annunciator mimics the FACP dis-
play
N-ANN-I/O: Input/Output Module for driving graphic annunci-
ators or relays
N-ANN-S/PG: Serial/Parallel Printer Interface module for con-
necting printer to FACP
ADDRESSABLE DEVICES
All feature a polling LED and rotary switches for addressing.
NI-100: Addressable low-profile ionization smoke detector.
NP-100: Addressable low-profile photoelectric smoke detec-
tor.
NP-I OOT: Addressable low-profile photoelectric smoke detec-
tor with thermal sensor.
NH-100: Fast-response, low-profile heat detector.
NH-IOOR: Fast-response, low-profile heat detector with rate-
of-rise option.
ND-100: Photoelectric low-flow duct smoke detector.
Page 2 of 4— DN-7102:A04/09/07
ND-100R: Photoelectric low-flow duct smoke detector with
relay option.
NMM-1100: Addressable Monitor Module for one zone of nor-
mally-open dry-contact initiating devices. Mounts in standard
4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-
line resistor. Module may be configured for either .a Style B
(Class B) or Style D (Class A) IDC.
NDM-100: Dual Monitor Module. Same as NMM-100 except it
provides two Style B (Class B) only lDCs.
NMM-IOOP: Miniafure version of NMM-100. Excludes LED
and Style D option. Connects with wire pigtails. May mount in
device backbox.
NZM-100: Similar to NMM-100, but may monitor up to 20 con-
ventional two-wire detectors. Requires resettable 24 VDC
power. Consult factory for compatible smoke detectors.
NC-100: Addressable Control Module for one Style V/Z
(Class B/A) zone of supervised polarized Notification Appli-
ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.
Notification Appliance Circuit option requires external 24 VDC
to power notification appliances.
NC-IOOR: Addressable relay module containing two isolated
sets of Form-C contacts, which operate as a DPDT switch.
Mounts directly to a 4.0" (10.16 cm.) box, surface mount using
the SMB500.
NOT-BGI2LX: Addressable manual pull station with interface
module mounted inside.
N100-ISÔ: Fault Isolator Module.
SMB500: Used to mount all modules except the NMM-100P.
NZM-I00-6: Six-zone interface module. Mount one or two
modules in a BB-XP cabinet (optional). Mount up to six mod-
ules on a CHS-6 chassis in a CAB-3/CAB-4 series cabinet.
NOTE: For more information on Compatible Addressable Devices
for use with the Fire Warden-50, see the following data sheets
(document numbers): NIOO-lSO (DN-6994), NP-100/NP-I00T
(DN-6995), NI-100 (DN-6996), NH-100/NH-IOOR (DN-6997), ND-
100/ND-I0OR (DN-7006), NMM-100/NMM-IOOP/NDM-100/NZM-
100 (DN-6999), NC-100/NC-100R (DN-7000), and NOT-BGI2LX
(DN-7001).
ADDRESSABLE DEVICE ACCESSORIES
End-of-Line Resistor Assembly (R-47K and R-3.9K): 47k
ohm supervises the NMM-100, NDM-100, NMM-100P, and
NC-100 module circuits. 3.9k ohm End-of-Line Resistor
assembly supervises the NZM-100 module circuit. These
resistors are included with each module.
Power Supervision Relay: Supervises the power to 4-wire
smoke detectors and notification appliances.
N-ELR Mounting Plate: Single End-of-Line resistor plate
required for use in Canada.
Wiring Requirements
While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical inter-
ference. Wire size should be no smaller than 18 AWG (0.78 mm2) and no larger than 12 AWG (3.1 mm2). The wire size depends
on the length of the SLC circuit. Use the following table to determine the specific wiring requirements for the SLC. (Refer to the
panel manual for complete details.)
CIRCUIT CONNECTIONS WIRE REQUIREMENTS
Circuit Type Circuit Wire Type and Recommended
Max. Distance Wire Gauge and Compatible Brands Function Limitations Feet (meters)
12 AWG (3.25 mm2): Genesis 4410,
Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm2):Genesis 4408 & 4608
Twisted, shielded pair Signal 98430, Belden 9581, WPW995
40 ohms maximum per 10,000 (3,000 m) 16 AWG (1.30 mm2): Genesis 4406 & 4606
length of Style 6 and 7 8,000 (2,400 m) Signal 98630, Belden 9575, WPW991
loops. 40 ohms per branch 4,875 (1,450 m)
3,225(980 m) Direct Burial Cable Isotec
maximum for Style 4 loops NP713110VNQ-S
18 AWG (0.75 mm2): Genesis 4402 & 4602
Signal 98300, Belden 9574, WPW975
SLC loop Connects to Direct Burial Cable Isotec
(power-limited) Addressable NP714110VNQ-S Devices 12 AWG (3.25 mm2): Belden 5020UL &
6020UL, Genesis WG-4315 & WG-4515
Twisted, unshielded pair 10,000 (3,000 m) 14 AWG (2.00 mm2):Belden 5120UL & 40 ohms maximum per 8,000 (2,400 m) 6120UL, Genesis WG-4313 & WG-4513 length of Style 6 and 7
loops. 40 ohms per branch 4,875 (1,450 m) 16 AWG (1.30 mm2): Belden 5220UL &
maximum for Style 4 loops 3,225 (980 m) 6220UL, Genesis WG-4311 & WG-4511
18 AWG (0.75 mm2): Belden 5320UL &
____ 6320UL,_Genesis WG-4306_&_WG-4506
Untwisted, unshielded 3,000 (900 m) 12-18 AWG (3.25-0.75 mm2) using listed
____ pair1 wire
ANN-BUS Connects to Twisted, shielded pair with
(EIA-485) annunciator mod- a characteristic imped- 6,000 (1,800 m) 18 AWG (0.75 mm2)
(power-limited) ules ance of 120 ohms
ElA-232
(power-limited)
Connects to
remote PC corn- Twisted, shielded pair 50 (15 m) 18 AWG (0.75 mm 2) minimum
puter
Maximum loop wire resis-
monitor module Initiating Device tance is 40 ohms for the 2,500 (760 m) 12-18 AWG (3.25-0.75 mm2) (power-limited) Circuit MMF-300 and 20 ohms for
the MMF-301
No more than a 2.4 volt
monitor module Initiating Device drop allowed at end of cir- 2,500 (760 m) 12-18 AWG (3.25-0.75 mm2) (power-limited) Circuit cuit. Maximum loop wire
resistance is 25 ohms
control module Notification Appli- In alarm, no more than.a
1.2 volt drop allowed at
Distance limitation set by 1.2 volt 12-18 AWG (3.25-0.75 mm2) (power-limited) ance Circuit end of circuit maximum line
drop
1) When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
DN-7102:A • 04/09/07 - Page 3 of 4
SYSTEM SPECIFICATIONS
System Capacity
Intelligent Signalling Line Circuits .1
Addressable device capacity .................................... . ....... 50
Programmable software zones.........................................20
Annunciators ......................................................................8
Electrical Specifications
AC Power: FireWarden-50: 120 VAC, 60 Hz, 0.3 A. FireWar-
den-50E: 240 VAC, 50 Hz, 0.15 A. Wire size: minimum 14
AWG (2.00 mm2) with 600 V insulation. Nonpower-limited,
supervised.
Battery: Two 12 V 18 AK lead-acid batteries. Battery Charger
Capacity: 7-18 AH (FireWarden-50 cabinet holds maximum of
two 18 AH batteries.)
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Terminal Block provides
connections for two NACs, Style Y (Class B) or. Style Z (Class
A). Special Application power. Power-limited, supervised cir-
cuitry. Maximum signaling current per circuit: 2.5 A. End-of-
Line Resistor: 4.7 kohm, % watt (PIN 71252 UL listed) for Style
V (Class B) NAC. Refer to the NOTIFIER Device Compatibility
Document for listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay:
Contact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC
(resistive). Form-C relays, nonpower-limited, nonsupervised.
Cabinet Specifications
Door: 19.26° (48.92 cm.) high x 16.82" (42.73 cm.) wide x
0.72" (1.82 cm.) deep. Backbox: 19.00" (48.28 cm.) high x
16.65' (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring
(TR-CE): 22.00" (55.88 cm.) high x 19.65° (49.91 cm.) wide.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00' (50.80 cm.)
high x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 -
49°C132 - 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 - 27°C/60 - 80°F
NFPA Standards
The FireWarden-50(E) complies with the following NFPA 72
Fire Alarm Systems requirements:
- LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
- AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTM).
- REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTM is required.)
- PROPRIETARY (Automatic, Manual and Waterflow).
- CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
Agency Listings and Approvals
The listings and approvals below apply to the basic.FireWar-
den-50 control panel. In some cases, certain modules may not
be listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
UL: S635
FM approved
CSFM: 7165-0028:239
NOTIFIER®, FireWarden®, and System Sensor® are registered trade-
marks of Honeywell International Inc. Microsoft® and Windows® are regis-
tered trademarks of the Microsoft Corporation.
©2007 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
I SO 9001 We try to keep our product information up-to-date and accurate.
11310=1• , We cannot cover all specific applications or anticipate all requirements.
1111111INE111111111 &MANUMCTUUNG All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S.A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
- -.
Page 4 of 4— DN-7102:A • 04/09/07
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. .7165-0028:239 Page 1 of 1
CATEGORY: Control Unit (Non High-Rise)
LISTEE: Notifier, One Fire-Lite Place, Northford, CT 06472-1653
Contact: Lawrence T. Flood (203) 484-6302 FAX (203) 484-7309
DESIGN: Model FireWarden-50 addressable fire alarm control unit. Unit consists of one communication
loop, two bell circuits, and three relay contact outputs for alarm, trouble and supervisory.
Local, auxiliary, remote station, central station and proprietary (protected premise), automatic,
manual, water flow and sprinkler supervisory service. Refer to listee's data sheet for detailed
product description, operational considerations and required/optional accessories. When
required, accessories shall be CSFM listed.
RATING: 120 VAC, 60 Hz, 3.0 A Primary, 24 VDC Secondary
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and
in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as an addressable fire alarm control panel for use with separately listed compatible
initiating and indicating devices. Refer to listee's Installation Instruction Manual for details.
This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
This control unit meets the requirements of UL-864, 9th Edition Standard.
NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
XLF: 7165-0075:210
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 12, 2008 Listing Expires June 30, 2009
Authorized By: BEN HO, Chief
Fire Engineering Division
©NOTIFIER®
by Honeywell
GENERAL
The NP-100 and NP-100T addressable, low-profile plug-
in photoelectric detectors use a state-of-the-art photoelec-
tric sensing chamber with communications to provide
open area protection and are used exclusively with
NOTIFI ER's FireWarden-100 Addressable Fire Alarm Con-
trol Panel (FACP). The NP-100T adds thermal sensors
that will alarm at a fixed temperature of 135°F (570C).
Since these detectors are addressable, they will help
emergency personnel quickly locate a fire during its early
stages, potentially saving precious rescue time while also
reducing property damage. Two LEDs on each sensor
light to provide a local, visible sensor indication. Remote
LED annunciator capability is available as an optional
accessory (P/N RA400Z).
FEATURES
SLC loop:
Two-wire loop connection.
Unit uses base for wiring.
Addressing:
Addressable by device.
Direct Decade 01 - 99 (FireWarden-100) entry of ad-
dress.
Architecture:
Unique single-source, dual-chamber design to respond
quickly and dependably to a broad range of fires.
Sleek, low-profile design.
Integral communications and built-in type identification.
Built-in tamper-resistant feature.
Removable cover and insect-resistant screen for
simple field cleaning.
Operation:
Withstands air velocities up to 4,000 feet-per-minute
(20 m/sec.) without triggering a false alarm.
Factory preset at 1.5% nominal sensitivity for panel alarm
threshold level.
Visible LED "blinks" when the unit is addressed (com-
municating with the fire panel) and latches on in alarm.
Mechanicals: V
Sealed against back pressure.
Direct surface mounting or electrical box mounting.
Mounts to: single-gang box, 3.5(8.89cm) or 4.0' (10.16
cm) octagonal box, or 4.0 (10.16 cm) square electrical
box (using a plaster ring - included).
Other system features:
Fully coated circuit boards and superior RF/transient
June 15 2005 DN-6995•A1-310
NP-TOO and NP-lOOT
Addressable Photoelectric Detectors
Section: Addressable ® California State Fire
V Marshal
7272-0028:231
LISTED APPROVED
S1115
MARYLAND M EA
State Fire Marshal 243-02-E Vol. II Permit # 2173
NP-100 r V with
1 B71OLP
?base
V
'7/
6934PhOIVlP9
protection.
94-VO plastic flammability rating.
Low standby current.
Options:
Remote LED output connection (P/N RA400Z).
SPECIFICATIONS
Voltage range: 15-32 VDC (peak).
Standby current: 300 pA @ 24 VDC.
LED current: 6.5 mA © 24 VDC (latched "ON").
Air velocity: 4,000 ft./min. (20 m/sec.) maximum.
Diameter: 6.1' (15.5 cm) installed in B71OLP base.
Height: 2.1 (5.33 cm) installed in B71OLP base.
Weight: 3.6 oz. (102 g).
Operating temperature range: for NP-100: 0°C to 49°C
(32°F to 1200F); for NP-100T 0°C to 38°C (32°F to 100°F).
Temperature: 0°C - 49°C (32°F - 1200F).
Relative humidity: 10% - 93%, non-condensing.
This document is not intended 10 be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice. IS09001 For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118 .1
N OTI Fl E R ENGINEEIING & MRNOFAC1UIING
by Honeywell 12 Clintonville Road, Northford, Connecticut 06472 QUALITY SYSTEMS
DN-6995 • 06/15/05 - Page 1 of 2
APPLICATIONS
Use photoelectric detectors in life-safety applications to
provide a broad range of fire-sensing capability, espe-
cially where smoldering fires are anticipated. Ionization
detectors are often better than photoelectric detectors at
sensing fast, flaming fires.
CONSTRUCTION
These detectors are constructed of off-white LEXAN®.
NP-100(T) plug-in, low-profile smoke detectors are de-
signed to commercial standards and offer an attractive
appearance.
LEXAN® is a registered trademark of GE Plastics, a subsidiary
of General Electric Company.
INSTALLATION
NP-100(T) plug-in detectors use a detachable mounting
base to simplify installation, service and maintenance.
Mount base on box which is at least 1.5 inches (3.81 cm)
deep. Suitable boxes include:
4.0' (10.16 cm) square box with plaster ring.
4.0" (10.16 cm) octagonal box.
3.5" (8.89 cm) octagonal box.
Single-gang box.
NOTE: Because of the inherent supervision provided by the
SLC loop, end-of-line resistors are not required. Wiring "T-
taps" or branches are permitted for Style 4 (Class B) wiring.
OPERATION
Each NP-100(T) uses one of 99 possible addresses on
the FireWarden-100 Signaling Line Circuit (SLC). It re-
sponds to regular polls from the system and reports its
type and. status.
The NP-100(T) addressable photoelectric sensor's
unique unipolar chamber responds quickly and uniformly
to a broad range of smoke conditions and can withstand
wind gusts up to 4,000 feet-per-minute (20 rn/sec.) with-
out sending an alarm level signal. Because of its unipo-
lar chamber, the NP-100(T) is approximately two times
more responsive than most photoelectric sensors. This
makes it a more stable detector.
DETECTOR SENSITIVITY TEST
Each detector can have its sensitivity tested (required per
NFPA 72, Chapter 7 on Inspection, Testing and Mainte-
nance) when installed/connected to a FireWarden-100
addressable fire alarm control panel. The results of the
sensitivity test can be printed off the FireWarden-100 for
record keeping.
PRODUCT LINE INFORMATION
NP-100 Addressable photoelectric detector; B71OLP
base included."
NP-100T Same as NP-100 but with thermal element;
B71OLP base included.*
RA400Z Remote LED. Mounts to a single-gang box.
B71OLP Plug-in detector base. Dimensions. 6.1"
(15.5 cm). Mounting:4.0" (10.16 cm) square
box with or without plaster ring, 4.0" (10.16
cm) octagonal box, 3.5" (8.89 cm) octagonal
box, or single-gang box. All mounting boxes
have a minimum depth of 1.5" (3.81 cm).
B224RB Plug-in System Sensor relay detector base.
Diameter: 6.2" (15.75 cm). Mounting: 4.0"
(10.16 cm) square box with or without plas-
ter ring, 4.0" (10.16 cm) octagonal box, or
3.5" (8.89 cm) octagonal box. All mounting
boxes have a minimum depth of 1.5" (3.81
cm).
B224B1 Plug-in System Sensor isolator detector
base. Maximum 25 devices between isola-
tor bases (see DN-6994). Diameter: 6.2"
(15.75 cm). Mounting: 4.0" (10.16 cm)
square box with or without plaster ring, 4.0"
(10.16 cm) octagonal box, or 3.5" (8.89 cm)
octagonal box. All mounting boxes have a
minimum depth of 1.5" (3.81 cm).
B501BH Plug-in System Sensor sounder detector
base. Diameter: 6.0" (15.24 cm). Mounting:
4.0" (10.16 cm) square box with or without
plaster ring. Mounting box has a minimum
depth of 1.5" (3.81 cm).
"Prior to 03/28/05, the B71OLP base was sold separately.
Page 2 of 2 - DN-6995 • 06/15/05
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-0028:231 Page 1 of 1
CATEGORY: Photoelectric Smoke Detector
LISTEE: Notifier, One Fire-Lite Place, Northford, CT 06472-1653
Contact: Lawrence Flood (203) 484-1200 FAX (203) 484-7309
DESIGN: Models NP-100 and NP-100T photoelectric type smoke detectors. Model NP-100T has a
1350F supplement integral heat sensor which only assists in a fire situation. The purpose
of this thermal circuitry is to increase the sensitivity of the detector. This thermal circuitry
is NOT approved for use as a heat detector. Refer to listee's printed data sheet for
additional detailed product description and operational considerations.
RATING: 24VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as photoelectric smoke detector for use with separately listed compatible fire alarm
control units. All units are suitable for installation inside air duct with a maximum air velocity
of 4000 fpm. Refer to listee's Installation Instruction Manual for details.
NOTE: The photoelectric type detectors are generally more effective at detecting slow,
smoldering fires, which smolder for hours before bursting into flames. Sources of these
fires may include cigarettes burning in couches or bedding. The ionization type detectors
are generally more effective at detecting fast, flaming fires, which consume combustible
materials rapidly and spread quickly. Sources of these fires may include paper burning in
a waste container or a grease fire in the kitchen.
XLF: 7272-0075:194
11-03-2004
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
'+ recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 12, 2008 Listing Expires June 30, 2009
Authorized By: BEN HO, Chief
Fire Engineering Division
DN-7001 :A • Al -380
NOT-BGI 2LX
Addressable Manual Pull Station JNOTIFIER®
by Honeywell
-- ,
J *_-_-• - - ---
CAnrlI
The Notifier NOT-BG12LX is a state-of-the-art, dual-action
(i.e., requires two motions to activate the station) pull station
that includes an addressable interface for FireWarden series
intelligent control panels. Because the NOT-BG12LX is
addressable, the control panel can display the exact location of
the activated manual station. This leads fire personnel quickly
to the location of the alarm.
Features
Maintenance personnel can open station for inspection and
address setting without causing an alarm condition.
Built-in bicolor LED, which is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
Handle latches in down position and the word "ACTIVATED"
appears to clearly indicate the station has been operated.
Captive screw terminals wire-ready for easy connection to
SLC loop (accepts up to 12 AWG/3.25 mm2 wire).
Can be surface mounted (with SB-10 or SB-I/O) or semi-
flush mounted. Semi-flush mount to a standard single-
gang, double-gang, or 4' (10.16 cm) square electrical box.
Smooth dual-action design.
Meets ADAAG controls and operating mechanicsms guide-
lines (Section 4.1.3[13]); meets ADA requirement for 5 lb.
maximum activation force.
Highly visible.
Attractive shape and textured finish.
Key reset.
Includes Braille text on station handle.
Optional trim ring (BG12TR).
Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
Construction
Shell, door, and handle are molded of durable LEXAN® (or
polycarbonate equivalent) with a textured finish.
Specifications
Normal operating voltage: 24 VDC.
Maximum SLC loop voltage: 28.0 VDC.
Maximum SLC loop current: pA.
Ambient Temperature: 32°F to 120°F (0°C to 49°C)
Relative Humidity: 93% ± 2% RH (noncondensing) at 32°C
± 2°C (90°F ± 3°F)
For use indoors in a dry location
Installation
The NOT-BG12LX will mount semi-flush into a single-gang,
double-gang, or standard 4(10.16cm) square electrical outlet
box, or will surface mount to the model SB-10 or SB-I/O sur-
face backbox. If the NOT-BG12LX is being semi-flush
mounted, then the optional trim ring (BG12TR) may be used.
The BG12TR is usually needed for semi-flush mounting with 4"
(10.16 cm) or double-gang boxes (not with single-gang boxes).
The NOT-BGI2LX
Addressable Manual Pull Station
Operation
Pushing in, then pulling down on the handle causes it to latch
in the down/activated position. Once latched, the word "ACTI-
VATED" (in bright yellow) appears at the top of the handle,
while a portion of the handle protrudes from the bottom of the
station. To reset the station, simply unlock the station with the
key and pull the door open. This action resets the handle; clos-
ing the door automatically resets the switch.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow address settings
(1 —99 on FireWarden-100-2, 1 —50 for FireWarden-50).
Architectural/Engineering
Specifications
Manual Fire Alarm Stations shall be non-coded, with a key-
operated reset lock in order that they may be tested, and so
designed that after actual Emergency Operation, they cannot
be restored to normal except by use of a key. An operated sta-
tion shall automatically condition itself so as to be visually
detected as activated. Manual stations shall be constructed of
red-colored LEXAN (or polycarbonate equivalent) with clearly
visible operating instructions provided on the cover. The word
FIRE shall appear on the front of the stations in white letters,
1.00 inches (2.54 cm) or larger. Stations shall be suitable for
surface mounting on matching backbox SB-10 or SB-I/O; or
semi-flush mounting on a standard single-gang, double-gang,
or 4" (10.16 cm) square electrical box, and shall be installed
within the limits defined by the Americans with Disabilities Act
(ADA) or per national/local requirements. Manual Stations
shall be Underwriters Laboratories listed.
DN-7001 :A • 02/05/2008— Page 1 of 2
Manual stations shall connect with two wires to one of the con-
trol panel SLC loops. The manual station shall, on command
from the control panel, send data to the panel representing the
state of the manual switch. Manual stations shall provide
address setting by use of rotary decimal switches.
Product Line Information
NOT-BG12LX: Dual-action addressable pull station. Includes
key locking feature.
SB-10: Surface backbox; metal.
SB-1/0: Surface backbox; plastic.
BG12TR: Optional trim ring.
17021: Keys, set of two.
Agency Listings and Approvals
In some cases, certain modules or applications may not be
listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
UL Listed: S692
MEA: 67-02-E Vol. IV
CSFM: 7150-0028:199
FM Approved
0,
Detail ol
BREAKAWAY TAB*
a 15 0 0 14
1302 -J 0)
11 4
Back of station without door
Terminal Connections:
1 SLC (-); 2 SLC (+)
LED
I L_1I
MI Rull
ri r. r11 I
_j li_JLiIIJL =1
Cover open to show easy access to miniature
monitor module, rotary switch, and UL label.
Patented:
U.S. Patent .No. D428,351; 6,380,846; 6,314,772; 6,632,108.
ROTARY DECIMAL SWITCHES J
*Do not remove tab.
NotifierrR is a registered trademark of Honeywell International Inc. LEXAN
is a registered trademark of GE Plastics, a subsidiary of General Electric
Company.
02008 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements. _I U_
MIlftNI &MNO1RC1URINB All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203)484-7118.
www.notifier.com
Page 2 of 2— DN-7001 :A • 02/05/2008
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE Y.
LISTING No. 7150-0028:199 Page 1 of 1
CATEGORY: Boxes/Pull Stations
LISTEE: Notifier, One Fire-Lite Place, Northford CT 06472-1653
Contact: Larry Flood (203) 484*7161 FAX (203) 484-7309
DESIGN: Models NBG-12, NBG-125, NBG-12LR, NBG-12LRA, NBG-12LAO, NBG-12LAOB, NBG-
12-LO, NBG-12LOB, NBG-12W, NBG-12LW, NBG-I2NC, NBG-12WP, NBG-12LWP, NBG-
12L, NBG-12LX, NBG-12LA, NBG-12PS, NBG-I2LSP, NBG-12LPS, NBG-12LPSP, NBG-
I2SP, NOT-BG12LX, and *NBG..12LXSP fire alarm pull boxes. All units except Model NBG-
12S are dual action pull stations. Models NBG-12LR and NBG-12LRA are intended for
agent releasing device. Refer to listee's data sheet for detailed product description and
operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, rating, and UL label.
APPROVAL: Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control units.
Models NBG-12WP, NBG-12LW, NBG-12W, NBG-12LWP, NBG-12LAO, NBG-12L0, NBG-
12LAOB and NBG-12LOB are intended for outdoor use when installed with Models WBB, SB-
I/O, orWP-10 back box. Refer to listee's Installation Instruction Manual for details.
Rev. 1-06-2006 jw
(f5)) This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 12, 2008 Listing Expires June 30, 2009
Authorized By: BEN HO, Chief
Fire Engineering Division
detail of NDM-100 - not
"ones" addresses are I
4, 6, 8 only
dn-6999:a • Al -350
Monitor Modules OTIFIER ®R
NMM.100,NMM-IOOP,NZM-100,and .' 0
NDM-100 for FireWarden Systems by Honeywell
I .w
General n fl
Four different monitor modules are available for Notifier's Fire-
Warden-series intelligent control panels to suit a variety of
applications. Monitor modules are used to supervise a circuit
of dry-contact input devices, such as conventional heat detec-
tors and pull stations, or monitor and power a circuit of two-
wire smoke detectors (NZM-100).
NMM-100 is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Class A (Style
0) or Class B (Style B) circuit of dry-contact input devices.
NMM-100P is a miniature monitor module (a mere 1.3" (3.302
cm) H x 2.75' (6.985 cm) W x 0.5' (1.270 cm) D) used to
supervise a Class B (Style B) circuit of dry-contact input
devices. Its compact design allows the NMM-100P to often be
mounted in a single-gang box behind the device it monitors.
NZM-100 is a standard-sized module used to monitor and
supervise compatible two-wire, 24 volt, smoke detectors on a
Class A (Style D) or Class B (Style B) circuit.
NDM-100 is a standard-sized dual monitor module used to
monitor and supervise two independent two-wire Style B
(Class B) dry-contact initiating device circuits (lOCs) at two
separate, consecutive addresses in intelligent, two-wire systems.
NMM-1 00 Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the control panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFl) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 - 159 on NFW-100, 01 —99
on NFW-50.
LED flashes during normal operation and latches on steady
to indicate alarm.
The NMM-100 Monitor Module is intended for use in intelli-
gent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It pro-
vides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator.
NMM-100 APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
NMM-100 OPERATION
Each NMM-100 uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC); A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limita-
tions on the loop).
NMM-100 SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum operating current: 375 pA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
NMM-IOOP Mini Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the panel.
Powered directly by two-wire FACP. No additional power
required.
High noise (EMF/RFI) immunity.
Tinned, stripped leads for ease of wiring.
dn-6999:a • 04/28/08 - Page 1 of 6
Direct-dial entry of address: 01 —159 on NFW-100, 01 —99
on NFW-50.
o 141 0 1 ADDRESS7 0 1 \2
- LOOP I
10/5
I TENS ONES
LU _J L11J
10 Z
i
The NMM-100P Mini Monitor Module can be installed in a sin-
gle-gang junction directly behind the monitored unit. Its small
size and light weight allow it to be installed without rigid. mount-
ing. The NMM-100P is intended for use in intelligent, two-wire
systems where the individual address of each module is
selected using rotary switches. It provides a two-wire initiating
device circuit for normally-open-contact fire alarm and security
devices. NMM-100P
NMM-100P APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterf low devices, or
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special super-
visory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
A 47K ohm End-of-Line Resistor (provided) terminates the cir-
cuit.
NMM-100P OPERATION
Each NMM-100P uses one of the available module addresses
on an SLC loop, It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC).
NMM-100P SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum operating current: 375 pA.
Maximum IDC wiring resistance: 1,500 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 490C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3' (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65' (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
NZM.1 00 Interface Module
Supports compatible two-wire smoke detectors.
Supervises IDC wiring and connection of external power
source.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 —159 on NFW-100, 01 —99
on NFW-50.
LED flashes during normal operation.
LED latches steady to indicate alarm on command from
control panel.
The NZM-100 Interface Module is intended for use in intelli-
gent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor two-
wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being moni-
tored must be UL compatible with the module.
NZM-100 APPLICATIONS
Use the NZM-100 to monitor a zone of two-wire smoke detec-
tors. The monitored circuit may be wired as an NFPA Style B
(Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K
ohm End-of-Line Resistor (provided) terminates the end of the
Style B or D (class B or A) circuit (maximum IDC loop resis-
tance is 25 ohms). Install ELR across terminals 8 and 9 for
Style D application.
NZM-100 OPERA TION
Each NZM-100 uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limita-
tions on the loop).
NZM-100 SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Maximum operating current: 270 pA (LED flashing).
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 490C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5° (11.43 cm) high x 4" (10.16 cm) wide x
1.25' (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125' (5.398 cm) deep box.
NDM-100 Dual Monitor Module
The NDM-100 Dual Monitor Module is intended for use in intel-
ligent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact
fire alarm and supervisory devices; or either normally open or
normally closed security devices. The module has a single
panel-controlled LED.
NOTE: The NDM-100 provides two Class B (Style B) IDC circuits
ONLY Class A (Style 0) IDC circuits are NOT supported in any
application.
NDM-100 SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Maximum operating current: 750 pA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
EOL resistance: 47K ohms.
Temperature range: 320 to 120°F (00 to 49°C).
Page 2 of 6— dn-6999:a • 04/28/08
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125 (5.398 cm) deep.
NDM-100 AUTOMATIC ADDRESSING
The NDM-100 automatically assigns itself to two addressable
points, starting with the original address. For example, if the
NDM-100 is set to address '26", then it will automatically
assign itself to addresses "26" and "27".
NOTE: "Ones" addresses on the NOM-100 are 0, 2, 4, 6, 0r8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.
CAUTION:
Avoid duplicating addresses on the system.
Installation
NMM-100, NZM-100, and NDM-100 modules mount directly to
a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep,
electrical box. They may also be mounted to the SMB500 sur-
face-mount box. Mounting hardware and installation instruc-
tions are provided with each module. All wiring must conform
to applicable local codes, ordinances, and regulations. These
modules are intended for power-limited wiring only.
The NMM-100P module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL: S635
FM Approved
CSFM: 7300-0028:230 (NMM-100, NMM-100P, NZM-100);
7300-0028:237 (NDM-1 00)
MEA: 72-01-E Vol. II (NMM-100, NMM-100P, NZM-100);
227-03-E Vol. III (NDM-100)
Product Line Information
NMM-100: Monitor module.
NMM-100P: Monitor module, miniature.
NZM-100: Monitor module, two-wire detectors
NDM-100: Monitor module, dual, two independent Class B
circuits.
SM8500: Optional surface-mount backbox.
Architects/Engineers' Specifications
Specifications of these and all FireWarden-compatible prod-
ucts are available from Notifier.
©
L
r,,`7_ 7'1!
(125
CAUTION
DE-ENERGIZE UNIT PRIOR TO SERVICING
/
Face plate for NMM-100, NZM-100,
and NDM-100
Mounting Diagrams for
Standard-sized Modules
dn-6999:a • 04/28/08 - Page 3016
Wiring Diagrams
The following wiring diagrams are included:
NDM-100: Typical dual two-wire Style B initiating device circuit configuration.
NMM-100P: Typical fvo-wire Style B initiating device circuit configuration.
NMM-100: Typical two-wire initiating circuit configuration, NFPA Style B.
NMM-100: Typical four-wire fault-tolerant initiating circuit configuration, NFPA Style D.
NMM-1 00: Typical two-wire initiating circuit configuration for security systems (with alarm versus short capability).
NZM-100: Interface two-wire conventional detectors, NFPA Style B.
NZM-100: Interface two-wire conventional detectors, NFPA Style D.
B. Applications with Conventional Detectors: Resetting Conventional Detectors
Figure 1 NDM-100: Typical dual two-wire Style B initiating device circuit configuration.
Two Initiating Device Circuits
(L&H)
each power-limited TO Next
Device FROM Panel
230 tiA max. @ 12 VDC max. MONITOR
or Previous
Device
omm] 47K EOL MODULE
Resistor ication Line
ELR-47K 2 VDC maximum. Twisted-pair is
TENS
recommended.
47K EOL and power
ELR-47K L T P 58
imited. limited.
Connect modules to listed compatible Not!-
0 fire FireWarden control panels only.
ANY NUMBER of UL Listed contact closure devices may be used.
DO NOT MIX fire alarm initiating, supervisory, or security devices on the same circuit.
Install contact closure devices per manufacturers installation instructions. 6822wu1.wmi
Figure 2 NMM-10013: Typical two-wire Style B initiating device circuit configuration.
r --- TO
10- NEXT (-) F---i ---: DEVICE
UL LISTED BLACK L14 R:iature Monitor Module Compatible I 781 678 Control 56 10 5
Panel )
-
24 1
.13 21 514
()(T)
'4 YELLOW
I [ 47KEOL INCLUDED
I 1 -
9e720wirl.wmt I -
.
-
Page 4 of 6— dn-6999:a • 04/28/08
NOTE: Wiring Diagrams this Page: NMM-100
Connect modules to listed compatible Notifire FireWarden • Any number of UL-listed contact closure devices may be
control panels only. used.
All wiring shown is supervised and power limited. • DO NOT MIX fire alarm initiating, supervisory, and secu-
Install contact closure devices per manufacturers' installa- rity devices on the same circuit.
tion instructions.
Figure 3 NMM-100: Typical two-wire initiating circuit configuration, NFPA Style B.
(—I FROM Panel ext
Device T0N Qcc
,
DcxDcT (+) or Previous
MONITOR Device
Initiating Device Circuit d NFPA style B, power limited: Communication Line
230 IJA max. @12 VDC max.
VDC maximum.
sled-pair is
recommended.
47K EOL
Resistor
I LJ 6 Communication Loss ELR-47K (optional connection for panels
which support this feature)
FUTURE FEATURE 6720w10 wml
Figure 4 NMM-100: Typical four-wire fault-tolerant initiating circuit configuration, NFPA Style D.
TO Next
Device (_) FROM Panel
or Previous
MONITOR Device
MODULE
Communication Line
32 VDC maximum.
Twisted-pair is
EOL Resistor 2 LmET recommended.
is internal at
8 & terminals 9 Communication Loss
uoxerss Loop (optional connection for panels
0 which support this feature)
FUTURE FEATURE
e720wwn,1
Figure 5 NMM-100: Typical two-wire initiating circuit configuration for security systems (with alarm
versus short capability).
Initiating Device Circuit (!DC)Device
TO Next (—) FROM Pane!
or Previous NFPA Style B, power limited: ONITOR (+) Device
230 pA max. @ 12 VDC max. ODULE R Communication Line
Series Resistor 0 32 VDC maximu m.
47K EOL
14K
Twisted-pair is
1 recommended.
Resistor U ELR47K Communication Loss 1. ADDRESS (optional connection for panels00
which support this feature)
FUTURE FEATURE 672r4,wmI
I MIN .11
dn-6999:a • 04/28/08 - Page 5016
NOTE: Wiring Diagrams this Page: NZM-100 and NC-100R
Connect modules to listed compatible control panels only.
Terminal wiring must be power limited.
DO NOT MIX tire alarm initiating, supervisory, and secu-
rity devices on the same circuit.
DO NOT LOOP wire under terminals. Break wire run to
provide supervision of connections.
Detectors must be UL listed compatible with module.
Install detectors per manufacturers' installation instructions.
Power to the interface module must be externally
switched to reset the detectors. An relay control module
can be used to switch power from a standard power sup-
ply; see Figure 8 below.
Figure 6 NZM-100: Interface two-wire conventional detectors, NFPA Style B.
TO Next
Device
INTERFACE
MODULE
3.9K EOL
Resistor
(included)
Li
A2143.10 DD COP A RESS
o 9
rFROM Panel
or Previous
Device
cation Line
ximum.r is ed.
Listed Batten, Backup 4 switched DC I power supply.
- Optional Branch Circuit
TO Next Interface Module
Module supervises supply
voltage and detector loop. 6720ñr5.wmi
Figure 7 NZM-100: Interface two-wire conventional detectors, NFPA Style D.
TO Next FROM Panel
+) Device + or or Previous
Device
INTERFACE I°) (' Communication Line MODULE 32 VDC maximum.
__-) ç Twisted-pair is
7 TENS 2'.
d
recommended.
+ C—> Listed Batley Backup DC 5 4 switched
ONES
I 0 9
'1'
power supply.
Optional Branch Circuit TO Interface Module
'D T•' + Module supervises supply
voltage and detector loop. 6720w1r6.Wmi
Figure 8 Applications with Conventional Detectors; Resetting detectors
NOTE: To reset conventional detectors, externally switch off power to the interface module they are connected to. This example shows NC- 100R
(see separate data sheet).
TO Next FROM Panel
Device or Previous
REL AY Device
CONTROL DC POWER MODULE SUPPLY
Listed for Fire H Communication Line Protection with 32 VOC maximum. Battery Backup Twisted-pair is
recommended
LOOP ADDRESS
00
67r7 wmi
Nolifier® and FireWarclen® are registered trademarks of Honeywell
International Inc.
©2008 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
I so 9001
This document is not intended lobe used for installation purposes.
We try to keep our product information up-to-dale and accurate.
- We cannot cover all specific applications or anticipate all requirements.
I MANIFACIVIINI All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S.A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 6016— dn-6999:a - 04/28/08
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
CATEGORY
LISTEE:
DESIGN:
7300-0028:230 Page 1 of 1
Misc. Devices/Control Unit Accessories
Notifier, 12 Clintonville Rd, Northford CT 06472
Contact: Lawrence Flood (203) 484-1200 Fax (203) 484-7309
Models NMM-100P, NMM-100, and NZM-100 monitor modules; Models NC-100R and
NC-100 control modules. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: 15-32 VDC
INSTALLATION:
MARKING:
APPROVAL:
XLF:
In accordance with listee's printed installation instructions, applicable codes and.
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, model number, electrical rating, and UL label.
Listed as control unit accessories for use with listee's separately listed electrically compatible
fire alarm control units. Refer to listee's Installation Instruction Manual for details.
7300-0075:185
10-20-2004
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 12, 2008 Listing Expires June 30, 2009
Authorized By: BEN HO, Chief
Fire Engineering Division
dn-60304:a
'SNAP' Series Z
Series ZRS Strobes, ZNS Horn Strobes
and Series ZNH Horns
NOTIFIER®
hi W 11 L1y yvvui
T;
General
The The Wheelock Series Z notification appliances feature an easy
snap on base that is designed to simplify the installation and
testing of horns, strobes, and horn/strobes. The separate
Series Z snap-on base can be pre-wired so circuit wiring can
be fully tested before the appliance is installed and before the
walls are covered. Once all surrounding work is complete, the
appliance can be simply installed by snapping it on the base.
Shorting contacts in the base, which provide continuity for cir-
cuit testing, are permanently opened when the appliance is
installed so any subsequent removal of the appliance will indi-
cate a trouble condition on that circuit at the control panel
when circuit supervision is enabled. The same base is used for
all Series Z horns, strobes, and horn/strobes to provide con-
sistent installation and easy replacement of appliances if
required. A locking screw is also included for the appliance to
provide extra secure installation.
The Wheelock Series Z appliances incorporate the same
dependable circuitry and high efficiency optics that are used in
Wheelock RSS strobes, NS Horn/Strobes, and NH Horns that
have the same high performance ratings. The Series Z appli-
ances are compatible with all UL Listed "Regulated" panels
and all panels that are compatibility listed with Wheelock PISS,
NS and NH appliances.
Features
EZ Mount SNAP design, with separate base plate provides
ability to pre-wire the base and test the circuit wiring before
the walls are covered.
The base plate is protected by a disposable cover and the
appliances can quickly snap onto the base after the walls
are painted.
Patented EZ Mount Universal Mounting Plate (ZBASE)
uses single plate for ceiling and wall mount installations.
Wall mount models feature field selectable candela settings
of 15/30175/11 Ocd and 135/185cd.
Ceiling Mount models feature field selectable candela set-
tings of 15/30/75/95cd and 115/177cd.
Strobes can be synchronized using the Wheelock SM• or
DSM Sync Modules or a power supply with built-in Sync
Protocol.
12 and 24 VDC models with UL "Regulated Voltage": using
filtered DC or unfiltered VRMS input voltage.
Strobes produce one (1) flash per second over the "Regu-
lated Voltage" range (ZNS, ZRS models).
Selectable Continuous Horn or Temporal (Code 3) Tones
with selectable 90 or 95 dBA setting (ZNH, ZNS models).
Selectable 12 or 24 VDC In one appliance (ZNH model).
ADA/NFPA/UFC/ANSI and OSHA 29 Part 1910, 165 com-
pliant.
JR
FR
Series ZNS Series ZRS
Series ZNS
o
Series ZRH
WARNING: PLEASE READ THESE
SPECIFICATIONS AND ASSOCIATED
INSTALLATION INSTRUCTIONS CAREFULLY
BEFORE USlN SPECIFYING OR APPLYING
THIS PRODUCT. FAILURE TO COMPLY WITH
ANY OF THE FOLLOWING INSTRUCTIONS,
CAUTIONS AND WARNINGS COULD RESULT
IN IMPROPER APPLICATION, INSTALLATION
AND/OR OPERATION OF THESE PRODUCTS
IN AN EMERGENCY SITUATION, WHICH
COULD RESULT IN PROPERTY DAMAGE AND
SERIOUS INJURY OR DEATH TO YOU AND/OR
OTHERS.
General Notes
Strobes are designed to flash at one (1) flash per second
minimum over their 'Regulated Voltage Range."
All candela ratings represent minimum effective strobe
intensity based on UL Standard 1971.
Series ZNS Strobe products are listed under UL Standards
1971 and 464 for indoor use with temperature range of 32°F
to 120°F (0°C to 49°C) and maximum humidity of 93%
(± 2%).
Series ZNH horns are listed under UL Standard 464 for
audible signal appliances (indoor use only).
'Regulated Voltage Range" is the newest terminology used
by UL to identify the voltage range. Prior to this change UL
used the terminology "Listed Voltage Range."
dn-60304:a • 5/6/08 - Page 1 of 4
Table 1: Series ZNS Rating per UL Standard 1971
Input Regulated Strobe
Model Voltage Voltage
Range Candela
VDC VDCIFWR (CD)
ZNS-MCW 24 16.0-33.0 15/30/75/110
ZNS-MCWH 24 16.0-33.0 135/185
ZNS-MCC 24 16.0-33.0 15/30/75/95
ZNS-MCCH 24 16.0-33.0 115/177
Table 2: Series ZNS!ZNH Horn dBA Ratings
Description Volume
Reverberant
dBA @l Oft per
UL 464
Anechoic dBA
@lOft
I2VDC 24VDC I2VDC 24VDC
Continuous
Horn
High 83 87 89 95
Low 76 81 84 90
Code 3 Horn High 79 82 89 95
Low 72 76 84 90
Table 3: Series ZRS UL Maximum Current*
ZRS 24VDC
Models
ZRS - Wall Mount ZRS - Ceiling Mount
MCW MCWH MCC MCCH
l5cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd ll5cd 177cd
16-33 VDC .060 .092 .0165 .220 .300 .420 .065 .105 .189 .249 .300 .420
* UL maximum current rating is the maximum RMS current within the listed voltage range (16-33V for 24V units). For strobes the UL
maximum current is usually at the minimum listed voltage (16V for 24V units). For audibles the maximum current is usually at the max-
imum listed voltage (16V for 24V units). For unfiltered FWR ratings, see installation instructions.
Table 4: Series ZNS UL Maximum Current*
Series ZNS/ZNH 24VDC
Audible Wall Mount Strobe Models Ceiling Mount Strobe Models
ZNH-12124 ZNS-NCW ZNS.MCWH
_________
ZNS-MCC ZNS-MCCH
______
15cd 30cd 75cd llOcd 135cd 185cd l5cd 30cd 75cd 95cd ll5cd 177cd
High (95) dBA 16-33 VDC .044 .074 .107 .184 .244 .350 .477 .082 .124 .209 .275 .350 .477
Low(90)dBA .018 .066 .101 .177 .232 .306 .429 .071 1 .114 .201 1 .261 .306 1 .429
Series ZNSIZNH I2VDC
Audible
* UL maximum current rating is the maximum RMS current within the listed voltage range
(16-33V for 24V units). For strobes the UL maximum current is usually at the minimum
listed voltage (16V for 24V units). For audibles the maximum current is usually at the
maximum listed voltage (16V for 24V units). For unfiltered FWR ratings, see installation
instructions.
zNH-12!24
High (89) dBA 8-17.5 VDC .021
Low (84) dBA .012
Architectural/Engineering
Specifications
Audible/visual notification appliances shalt be listed for indoor
use and shall meet the requirements of FCC Part 15 Class B.
These appliances shall be listed under UL Standard 1971 (Stan-
dard for Safety Signaling Devices for Hearing Impaired), and UL
Standard 464 (Fire Protective Signaling). The appliances shall
use a Patented Universal EZ Mount backplate that shall allow
mounting to asingle-gang, double-gang, 4-inch square, 4-inch
octal, or a 31/2-inch octal backbox. Two wire appliance wiring
shall be capable of directly connecting to the mounting back-
plate. Continuity checking of the entire NAC circuit prior to
attaching any audible/visual notification appliances shall be
allowed. A dust cover shall fit and protect the mounting plate.
The duct cover shall be easily removed when the appliance is
installed over the backplate. Removal of an appliance shall
result in an alarm condition by the Fire Alarm Control Panel
(FACP).
Strobe appliances shall produce a minimum flash rate of 60
flashes per minute (1 flash per second) over the Regulated Volt-
age Range of 16 to 33 VDC and shalt incorporate a Xenon
flashtube enclosed in a rugged Lexan® lens. The strobes shall
Page 2 of 4- dn-60304:a • 5/6/08
be available with 2 or 4 field selectable settings in one unit and
shall be rated, per UL 1971 for up to 185cd for wall mounting
and 177cd for ceiling mounting. The strobe shall operate over an
extended temperature range of 32°F to 120°F (0°C to 49°C) and
be listed for maximum humidity of 95% RH. Strobe inputs shall
be polarized for compatibility with standard reverse polarity
supervision of circuit wiring by a Fire Alarm Control Panel
(FACP).
Horns and horn/strobes shall be listed for indoor use under UL
Standard 464. The horns shall be able to produce a continuous
output or a temporal Code-3 output that can be synchronized.
The horns shall have at least 2 sound level settings of 90 and 95
dBA.
When synchronization of strobes or temporal Code-3 audibles is
required, the appliances shall be compatible with the Wheelock
Series SM and DSM Sync Modules or a power supply with built-
in Sync Protocol. The strobes shall not drift out of synchroniza-
tion at any time during operation. Audibles and strobes shall be
able to be synchronized on a 2-wire circuit with the capability to
silence the audible if required. If the sync module or power sup-
ply fails to operate (i.e. contacts remain closed), the strobes
shall revert to a non-synchronized flashrate.
Wiring Diagrams
From + PRECEDING { . To NEXT
DEVICE - - I DEVICE
orFACP orEOLR
+ -
SIGNAL
ZNS/ZNH APPLIANCE
SM
STROBE H
Strobe I - STROBE A NAC I
I
P
Circuit
NAC 6e01w1r2a.wml
Circuit
ZNS AND ZNH APPLIANCES
SYNCHRONIZED WITH SM MODULE
SINGLE CLASS "B" NAC CIRCUIT WITH
AUDIBLE SILENCE FEATURE
DSM
-- P I & SYNC -
FACP OUT 1
Q..-IN1
- r—I -- MINUS 1
+ AUDIBLE
SINGAL
CIRCUIT I
OUT
- AUDIBLE
I OUT
p -_i +IN
SIGNAL P MINUS 2 CIRCUIT RETURN
ZNS AND ZNH APPLIANCES SYNCHRONIZED WITH
DSM MODULE DUAL CLASS "A" NAC CIRCUIT WITH
NO AUDIBLE SILENCE FEATURE
NOTE: ZNS/ZNH must be set on Code 3 horn tone to achieve synchronized temporal (Code 3) tone. Refer to
installation instructions (P83983, P83600 respectively).
NOTE: For detail using SM or DSM Sync Module refer to data sheet S3000 or installation instructions P83123
for SM and P83177 for DSM.
dn-60304:a • 5/6/08 - Page 3014
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this. In some cases, certain modules or applications may not
be listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
UL Listed: E5946
Ordering Information
Model Number Strobe
Candela
Vxx
12
VDC
Mounting
Options
Agency Approvals
UL MEA CSFM FM BFP
ZNS-MCW-FR 15/30/75/110 B, D, E, F x x
ZNS-MCW-FW 15/30/75/110 B, D, E, F X X X - -
ZNS-MCWH-FR 135/185 - B, D, E, F X X X - -
ZNS-MCWH-FW 135/185 X X - B, D, E. F X X X - -
ZNH-R - X X X B, D, E, F X X X - -
ZNH-W - X X X B. D. E,F X X X - -
ZNS-MCC-FR 15/30/75/95 X X - B, D. E. F X X X - -
ZNS-MCC-FW 15/30/75/95 X X - B, 0, E, F X X X - -
ZNS-MCCH-FR 115/177 X X - B, D, E, F X X X - -
ZNS-MCCH-FW 115/177 X X - B, 0, E, F X X X - -
ZRS-MCW-FR 15/30/75/110 X X - B, D, E, F X X X. - -
ZRS-MCW-FW 15/30/75/110 X X - B, D, E, F X X X - -
ZRS-MCWH-FR 135/185 X X - B, 0, E, F X X X - -
ZRS-MCWH-FW 135/185 X X - B, D, E, F X X X - -
ZRS-MCC-FR 15/30/75/95 . X X - B, 0, E. F X X X - -
ZRS-MCC-FW 15/30/75/95 X X - B, D, E, F X X X - -
ZRS-MCCH-FR 115/177 X X - B, D, E, F X X X - -
ZRS-MCCH-FW 115/177 X X - B, D. E, F X X X - -
Lexan® is a registered trademark of GE Plastics, a subsidiary of General
Electric Company.
©2008 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
NN I SO 9001 We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
UlCIiERlNE & MAN VFAI11IRINA All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161 FAX: (203) 484-7118.
www.notifier.com
p -
Page 4 of 4— dn-60304:a • 5/6/08
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:142 Page 1 of 1
CATEGORY: Fire Alarm Devices for the Hearing Impaired
LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Deborah Piserchia (732) 433-6001 Fax (732) 222-5607
deborah.piserchia@cooperwheeIock.com
DESIGN: Models NH-12/24, NH-12/24R, and ZNH horns and Models NS-1215W, NS-121575W,
NS-2415W, NS-241575W, NS-2430W, NS-2475W and NS-24110W; NS4-1215W, NS4-
121575W, NS4-241 5W, NS4-241 575W, NS4-2430W, NS4-2475W and NS4-241 lOW,
NS-24MCW, NS4-24MCW, NS-24MCC, NS-24MCCH, ZNS-MCW, ZNS-MCC, ZNS-
MCWH and ZNS-MCCH horn strobes. Model number may be followed by any two-
alpha/numeric characters indicating lens, lettering and color. Units are synchronized or
non-synchronized strobes. Models NH-12/24R, NS-24MCC, NS-24MCCH, ZNS-MCC and
ZNS-MCCH are ceiling mount only. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: Electrical-Strobe Horn: 8-17.5 VDC/FWR and 16-33 VDC/FWR
Horn: 8-17.5 VDC/FWR and 16-33 VDC/FWR
Candela: 15=15cd, 1575=15/75cd on axis, 30=30cd, 75=75cd, 110=110cd (Wall)
NS-24MCW, NS4-24MCW, ZNS-MCW: Selectable 15cd, 30cd, 75cd, 1l0cd
NS-24MCC, ZNS-MCC: Selectable 15cd, 30cd, 75cd, 95cd
NS-24MCCH, ZNS-MCCH: Selectable 115cd, 177cd
ZNS-MCWH: Selectable •135cd, 185cd
Flash rate: 60 Flashes/minute
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction. All units are for wall mount except
for *Models NH-12/24R, NS-24MCC, NS-24MCCH, ZNS-MCC and ZNS-MCCH are for
ceiling mount only.
MARKING: Listee's name, model number, electrical/candela rating and UL label.
APPROVAL: Listed as audible and audible/visual signaling devices for use with separately listed
electrically compatible fire alarm control units. Models with strobe lights are suitable for
the hearing impaired. For indoor use only except for model NH-12124 horn. All
synchronization strobes shall be used with Models SM-12/24, SMX-12/24, DSM-12/24 or
DSMX-12/24 Sync Control Module (CSFM Listing No. 7300-0785:132). Refer to
manufacturer's installation manual for details.
NOTE: These appliances can produce a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
*Corrected 07-25-08 bh
TO
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does -not make an independent verification of any claims. This listing is not an endorsement or
;'• recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JULY 25, 2008 Listing Expires June 30, 2009
Authorized By: BEN HO, Chief
Fire Engineering Division
I