HomeMy WebLinkAbout7205 AVIARA DR; ; AS130162City of Carlsbad
Sprinkler Permit
Permit No: AS130162
Job Address: 7205 AVIARA DR Status: APPROVED
Permit Type: 'SPRINK Applied 9/10/2013
Parcel No: 2156111900 Approved: 9/23/2013
Lot #: 0
Reference No.: Issued: 9/23/2013
PC #: Inspector:
Project Title: BAKER LOPEZ RES.
Applicant:
PREMIER FIRE PROTECTION
12651 RIDGETON DR
LAKESIDE, CA
619-390-5047
Owner:
BAKER/LOPES FAMILY TRUST 12-16-96
607 LYN WOOD DR
ENCINITAS CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
404 0 404 0
March 7, 2013 Sprinkler 147u
\IIKI FREEDOM® RESIDENTIAL
4 CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-81871680 Email: techsvcsvikingcorp.com
1. DESCRIPTION
Viking Freedoms Residential Concealed Pendent Sprinkler VK457 is a small
high-sensitivity solder link and lever residential sprinkler designed for installation
on concealed pipe systems where the appearance of a smooth ceiling is desired.
The orifice design, with a K-Factor of 4.9 (70.6 metric*), allows the sprinklers ef-
ficient use of available water supplies for the hydraulically designed fire-protection
system. The operating element and special deflector characteristics meet the chal-
lenges of residential sprinkler standards.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-
profile small-diameter cover assembly installed flush to the ceiling. The two-piece
design allows installation and testing of the sprinkler prior to Installatlon of the
cover plate The push on thread-off' design of the concealed cover plate as-
sembly allows easy installation of the cover plate after the system has been tested
and the ceiling finish has been applied while also providing up to /2 (11.1 mm) of
vertical adjustment. The cover assembly can be removed and reinstalled, allow-
ing temporary removal of ceiling panels without taking the sprinkler system out of
service or removing the sprinkler.
LISTINGS AND APPROVALS
cULus Listed: Category VKKW
Refer to the Approval Chart on page 147w and Design Criteria on page 147x for cU..us Listing requirements that must be
followed.
TECHNICAL DATA
Specifications:
Available since 2008.
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 4.9 U.S. (70.6 metric')
Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide
the metric K-lactor shown by 10.0.
Material Standards: Viking Technical Data may be found on
Sprinkler Body: Brass UNS-C84400 or QM Brass . The Viking Corporation's Web site at
Deflector: Phosphor Bronze UNS.C51000 http://www.vlklnggroupinc.com. Deflector Pins: Stainless Steel UNSS30200 The Web site may include a more recent Button: Brass UNS-C36000 edition of this Technical Data Page. Seat Assembly; Brass UNS-C31600
Compression Screw: Brass UNS-C36000
Fusible Element Assembly: Beryllium Nickel, coated- with. black acrylic paint
Levers: Stainless Steel UNS-S31600
Lever Bar: Copper Alloy UNS-C72500
Belleville Spring Sealing Assembly Nickel Alloy, coated on both sides with PTFE Tape
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Shipping Cap: Polyethylene
Cover Plate Materials:
Cover Plate Assembly: Copper UNS-C 11000 and Brass UNS-C26800
Spring: Beryllium Nickel
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Freedoms Residential Concealed Pendent Sprinkler VK457 and Cover Plate Assembly must be ordered separately:
Form No. F 072607 Replaces page 147u-z, dated February 3, 2012.
(Revised Approval Chart format.)
4Y, ~ a (&;~,
Sprinkler 147v March 7, 2013
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Sprinkler: Part No. 14694AC (Includes a 165°F (74°C) rated sprinkler with a protective plastic cap covering the unit).
Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part No. 15394
(square cover plate, 3-5/16" diameter)
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A. Brushed Brass = B-/B, Brushed
Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/l, Painted Black = M-/B
Temperature Suffix: 135 °F157 DC =A
For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories' section of the Viking data book.)
Sprinkler Wrenches**:
Heavy Duty Part No. 13623W/B (available since 2006), or
Head Cabinet Wrench Part No. 13619*e (available since 2006)
C Optional Concealed Cover Plate Installer Tool Part No, 1.4.412 (available since 2007)
D. Optional Large Concealed Cover Plate Installer Tool Part No 14867 (available since 2007)
"Requires a W ratchet (not available from Viking). ""Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the fusible element to disengage releasing the sealing
assembly. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of
coverage determined by the water supply pressure at the sprinkler to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
Viking Sprinkler Model VK457 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
1TABLE lwAVAILABLE SPRINKLER Tl?FINISHES
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
Footnotes The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction Refer to specihc inslallaliori standards
3 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
March 7, 2013 Sprinkler 147w
NIKI FREEDOM® RESIDENTIAL
4 CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-9459501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Sprinkler Base SIN NPT Thread Size Nominal K-Factor Maximum Water Working
Part Number 1 Inches mm U.S. metric Pressure
14694A VK457 1/2 15 4.9 70.6 175 psi (12 bar)
Max. Coverage
Area
Ordinary Temp Rating
(165 F174 C)
Listings and Approvals3
_______ _______ _______
Minimum
Width X Length Deflector to Installation Spacing Flow 6 Pressure 6
Ft. X Ft. GPM PSI Ceiling eiing e cULus4 NYC NSF' Ft
(m)
(m X rn) (Llmin) (bar)
12X12 13 7.0
(3.7 X 3.7) (49.2) (0.48)
14X14 13 7.0
(4.3 X 4.3) (49.2) (0.48)
Refer to Figure Concealed with
See
Foot- See
See
Foot- 8 16 X 16 13 7.0
(4.9 X 4.9) (49.2) (0.48) 2 on page 147y Cover Plate note 7 Foot- note 7 (2.4) Assembly and 10 note 5 and 10
18X18 17 12.0
(5.5 X 5.5) (64.4) (0.83)
20X20 20 16.7
(6.1 X6.1) (75.7) (1.15)
Footnotes
'Part number shown is the base part number. For complete part number, refer to current Viking price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured In kPa, divide the metric K-factor shown by
10.0.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for
any additional approvals. Refer also to Design Criteria on page 147x.
Listed by Underwriter's Laboratories, Inc. for use in the U.S. and Canada.
Meets New. York City requirements, effective July 1 2008.
For areas of coverage smaller than shown, use the "Flow" and Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler.
The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum "Flow" and "Pressure" used.
Cover Temperature Rating is 135 "F (57 "C). Cover Part No. 135041. 13642' (large diameter), or 15394' (square cover plate).
UL Classified to. NSF/ANSI Standard 61, Drinking Water System Components (MH48034).
Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufac-
turer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
'° Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black .
Sprinkler 147x March 7, 2013
'JIKI FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
cULus Listing Reaulrements:
When using Viking Residential Concealed Pendent Sprinkler VK457 for systems designed to NFPA 130 or NFPA 13R apply the listed areas of cover-
age and minimum water supply requirements shown in the Approval Chart on page 147w.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following.-
The flow rates given in the Approval Chart on data page 147w for NFPA 130 and NFPA 13R applications for each listed area of coverage.
or
Calculated based on a minimum discharge of 0.1 gpm!sq. It. over the "design area' in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT: Always refer to Bulletin Form No F_091699 - Care and Handling of Sprinklers. Also refer to pages
RESI-17 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained
from the Authorities Having Jurisdiction.
Sprinkler and
Adopter Assembly
(Protective Cap
is removed For
irso.ttation--use
Wrench 13619*)
Step I: Core Futly sl
wrench sideways a
the deFlector oric
2-1/4 (57.2 nn)
diameter opening
is required in
the ceiling. r
Sprinkler
Wrench
(Port No
13623'J/BwIi
is shown)
0
wwA 1/2k ratchet is required
(not avoitable From Viking).
Step 2: CareFully press the wrench
upward and turn slightly to ensure
engagement with sprinkler wrench Flats,
Figure 1: Sprinkler Installation and Correct Use of Wrenches
March 7, 2013 Sprinkler 147y
FREEDOM® RESIDENTIAL
CONCEALED PENDENT IU 'Il SPRINKLER VK457 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone 269-945-9501 Technical Services 977-384-5464 Fax 269-818-1680 Email techsvcsvikingcorp corn
1/2'
(15 mm)
NP I
2-1/8'
(54 mm)
T-
2-9/16'
(65 mm)
Maximum
2-1/16'
(52 mm)
Minimum
2-3/4' (70 rim) or
Note: Upon sprinkler activation, the deflector descends 3-5/16' (84.1 mm) to approximately 13/16' (20.6 mm) below the sprinkler body.
Figure 2: Sprinkler Dimensions and Cover Installation
L1L '0'
Figure 4: Square Cover Assembly 15394
lderrt'icotion Of, Custori P- " . CQr:
AU custom color pokte covet- plates wilt have an ci'yra iio( a F 1:xel to the
inside c he cover that irthca'tes cs-zo color and ond will C prc''en 10 liv'.' ;ampL(.'
<o. point do't) or 'the on the label.
Figure 3: idenfificatlon of Custom Paint Color for Concealed Covers
Form No. F_072607 Replaces page 147u-z, dated February 3, 2012.
(Revised Approval Chart format.)
GRoss
IBE
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
AUTOMATIC. SPRINKLERS
GL SERIES
UPRIGHT' PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a low profile
yet durable design which utilizes a 3mm frangible glass ampule as the
thermosensitive element. This provides sprinkler operation approxi-
mately six times faster than ordinary sprinklers. While the Quick
Response Sprinkler provides an aesthetically pleasing appearance, it
can be installed wherever standard spray sprinklers are specified when
allowed by the applicable standards. It offers the additional feature of
greatly increased safety to life and is available in various styles,
orifices, temperature ratings and finishes to meet many varying design QUICK RESPONSE requirements. Quick Response Sprinklers should be used advisedly UPRIGHT CONVENTIONAL and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
_____ a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At the
prescribed temperature the internal pressure Within the ampule ex-
ceeds the strength of the glass causing the glass to shatter. This results
in water discharge which is distributed in an approved pattern depend-
ing upon the deflector style used.
QUICK RESPONSE
TECHNICAL DATA PENDENT VERTICAL
'See reverse side for Approvals and Specifications. SIDEWALL
'Temperature Ratings - 135°F (57°C), 155°F (680C),
175°F (.79°C), 200°F (93°C), 286°F (141°C)
'Water Working Pressure Rating - 175 psi (12 Bars)
'Factory tested hydrostatically to 500 psi (34 Bars)
le a 'Maximum low temperature glass bulb rating is -67°F (-55°C)
'Frame - bronze ' Deflector - brass • Screw - brass
'Bulb seat - copper • Spring - nickel alloy • Seal - teflon QUICK RESPONSE
'Bulb - glass with alcohol based solution, 3mm size HORIZONTAL SIDEWALL
'SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CLASSIFICATION TEMPERATURES B L COLOR BULB CEILING TEMPERATURE
ORDINARY :355F 574CL68Ca ORANGE/RED 0 °F38°€ INTERMEDIATE T51EL0F 9* 930 YELLOW/GREEN
HIGH 286F 14j0C_____ BLUE 225° 107°C
4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX 989-846-9231
MAY 2011 . A-20 BULLETIN GL5615, REV. #7
989-846-4583
1-800-248-0278
GLbEIE
FIRE SPRINKLER CORPORATION
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
FAX 989-846-9231
www.globesprinkler.com
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT • PENDENT • VERTICAL SIDEWALL
HORIZONTAL SIDEWALL• CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH ' FINISHES
2.8 (39 metric) 1/2 NPT 2 1/4 (5.7 cm) Factory Bronze
4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2
Bright Chrome
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) white Polyester
7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Black Polyester
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Lead Coated 2 _____________
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'HORIZONTAL SIDEWALL IS 2 9/16'.
2 FINISHES AVAILABLE ON SPECIAL ORDER.
3AVAILABLE AS cULus LISTED CORROSION
APPROVALS RESISTANT WHEN SPECIFIED ON ORDER.
STYLE SIN K 135°F 155°F 175°F 200°F 286°F UL F.M.LPC CE NYC - DOB
MODEL FACTOR 57°C 68°C 79°C 93°C 141°C MEA 101-92-E
GL2815 2.8 X X X X X X - - - x
GL4215 4.2 X X X X X X - - - X
UPRIGHT GL5615 5.6 X X X X X X X X X X
GL8115 7.8* X X X X X X X - - X
GL8118 8.1 X X X X X X X X X X
GL2801 2.8 X X X X X X - - - x
GL4201 4.2 X X X X X X -- -- - x
PENDENT GL5601 5.6 X X X X X X X X X X
GL8101 7.8* X X X X X X X - -- X
GL8106 8.1 x X X X X X X X X
VERTICAL GL5632 5.6 X X X X X X x - - -
SIDEWALLt GL8133 8.1 X X X X X X - - --
GL2826 2.8 X X X X X X - - - X
HORIZONTAL GL4226 4.2 X X X X X X - - - x
SIDEWALL § GL5626 5.6 X X X X X X X - - X
GL8127 8.1 X X X X X X - - -
CONVENTIONAL GL5624 5.6 X X X X X - - X X -
(OLD STYLE) GL8125 8.1
1
X
I
X
I
X X
I
X - - X
I
X -
§ HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4' TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6".
t VERTICAL SIDEWALL SPRINKLER cULus LISTED FOR LIGHT HAZARD ONLY.
PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
UPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
ORDERING INFORMATION 112" NPT.
SPECIFY GLOBE® PRODUCT WARRANTY
'Quantity • Model Number • Style
Orifice • Thread Sizes • Temperature
Finishes desired
Quantity - Wrenches - P/N 325390 (1/2");
P/N 312.366 (L.O.)
Globe agrees to repair or replace any of its own
manufactured products found to be defective in mate-
rial or workmanship for a period of one year from date
of shipment.
For specific details of our warranty please refer to
Price List Terms and Conditions of Sale (Our Price List).
DECEMBER 2006 PRINTED U.S.A. BULLETIN GL5615, REV. #6
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
.ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
LICENSE : 939040
DESIGNER : STEVE PETRI
DATE : 08-26-2013
FILE : C:\RESDEN58\BAKER-LOPES.RES
JOB NAME : BAKER-LOPES TWO HEAD CALC 16 X 16
LOCATION : 7205 AVIARA DR.
DESIGN DATA.
DESIGN CRITERION:
MIN SPR FLOW
AREA PER SPRINKLER
TOTAL CALCULATED AREA
TOTAL SPRINKLERS CALCULATED
FLOW DATA.
TOTAL SPRINKLER FLOW
DOMESTIC DEMAND
TOTAL WATER REQUIRED
BASE OF RISER NODE
FLOW
PRESS
13D
13 Gpm
256 Sq Ft
512 Sq Ft
2
2 6. 3 Gpm
5.0 Gpm
31.3 Gpm
B
2 6. 3 Gpm
37.5 Psi
These plans have heeii reviewed for a1paren1 compliance
with the cu clii applicable e dcsiind siaiidards in toree
III the iiip.d Id (ill. The owner 01 colitlaclfll may utilize
it evIc% in support of au application lw a building
11111 oh the epris undersiandi ilu thai this tenets
'ii no %%;I% relics en lhe osvuicu or couutiacior or their
prolessu mat cuueu,leer or architect for stile responsihihii
for full cutitiptu ance trith said codes and suatidauds.
ut luding the building code or for any respoiisihiliy for
tc1 ICICItCICS. errors. 0flhiS5iOt1% or ncgl igeilce in these
plum ss heiher or not noted in this review.
I tue .j11f'(3 Re'. ewer:tj/
gRECOMMENI) APPROVAl.
0 RECOMMEND APPROVAl.. AS NOTED
AUTHORITY HAVING JURISDICTION CARLSBAD FIRE
PHONE
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL. Page 1
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : BAKER-LOPES TWO HEAD CALC 16 X 16
DATE: 08-26-2013 FILE: C:\RESDEN58\BAKER-LOPES.P.ES
I SPRINKLER MANUF : VIKING - VK457, 16 X 16, K=4.9, P-i
I MODEL : VK457
I DENSITY : 0.05 Gpm/Sq Ft FIXED PRESS : 0.0 Psi
I AREA / SPR : 256 Sq Ft DESIGN AREA : 512 Sq Ft
I SPRINKLER Q : 13.0 Gpm
I NODES : 9 PIPES : 8
SOURCE I STATIC : 90 Psi RESIDUAL : 89 Psi FLOW : 31 Gpm
NODE ELEVATION K-FACTOR PRESSURE DISCHARGE
NO. Feet
----------------------------------------------------------- Psi Gpm
1 20.0 4.90 7.0 13.0
2 20.0 4.90 7.3 13.3
3 20.0 7.8
4 10.0 20.5
T 10.0 30.9
B 0.0 37.5
A 0.0 40.3 DOME 5.0
M 0.0 42.6
5 0.0 SOURCE 45.6 31.3
SPRINKLERS FLOWING : 2
AREA PER SPRINKLER : 256 Sq Ft
TOTAL DESIGN AREA : 512 Sq Ft
MIN SPRINKLER FLOW : 13 Gpm
REQUIRED DENSITY : 0.051 Gpm/Sq Ft
COMPUTED DENSITY : 0.051 Gpm/Sq Ft
TOTAL SPRINKLER FLOW : 26.3 Gpm
TOTAL DOMESTIC FLOW : 5.0 Gpm
TOTAL WATER REQUIRED : 31.3 Gpm
TOTAL SPRINKLER PRESS : 45.6 Psi
FIXED PRESS LOSS : 0.0 Psi
Copyright (2012)
SUPPLY PRESS AVAILABLE : 89.0 Psi by
DEMAND PRESS REQUIRED : 45.6 Psi Hydronics Engineering
PRESSURE CUSHION : 43.4 Psi 34119 Fremont Bi, Suite 609
Fremont, CA, 94555
MAXIMUM VELOCITY : 12.1 F/S (800) 845-9819
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL. Page 2
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : BAKER-LOPES TWO HEAD CALC 16 X 16
DATE: 08-26-2013 FILE: C:\RESDEN58\BAKER-LOPES.RES
PIPE BEG FLOW K-FACTOR LENGTH C-FACTOR PRESSURE
NO. Gpm FITTING TYPE FTG FRI-LOSS (Psi)
END DIAMETER TOTAL (Psi/Ft)
1 q= 13.0 K=
-------------------------------------------------------------------------------
4.90 L= 20.0 Pt 7.0 Pt 7.0
1 Q= 13.0 F= RRB F= 7.0 C= 150 Pe 0.0 Pv -0.1
Ve1= 4.4 D= 1.101 TL= 27.0 0.0306 Pf 0.8 Pn 6.9
3 Pt 7.8
2 q= 13.3 K= 4.90
--------------------------------------------------------------------------
L= 11.0 Pt 7.3 Pt 7.3
2 Q= 13.3 F= B F= 5.0 C= 150 Pe 0.0 Pv -0.1
Ve1= 4.5 D= 1.101 TL= 16.0 0.0319 Pf 0.5 Pn 7.2
3 Pt 7.8
3 q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 42.0 Pt 7.8 Pt 7.8
3 Q= 26.3 F= 4BEEL4RF= 33.0 C= 150 Pe 4.3 Pv -0.5
Ve1= 8.8 D= 1.101 TL= 75.0 0.1125 Pf 8.4 Pn 7.3
4 Pt 20.5
4 q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 60.0 Pt 20.5 Pt 20.5
4 Q= 26.3 F= LL3B4R F= 33.0 C= 150 Pe 0.0 Pv -0.5
Ve1= 8.8 D= 1.101 TL= 93.0 0.1125 Pf 10.5 Pn 20.0
T Pt 30.9
T q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 10.0 Pt 30.9 Pt 30.9
5 Q= 26.3 F= SCRR F= 10.0 C= 150 Pe 4.3 Pv -0.5
Ve1= 8.8 D= 1.101 TL= 20.0 0.1125 Pf 2.3 Pn 30.4
B Pt 37.5
B q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 5.0 Pt 37.5 Pt 37.5
6 Q= 26.3 F= LLB F= 13.0 C= 150 Pe 0.0 Pv -0.7
Ve1= 10.2 D= 1.025 TL= 18.0 0.1594 Pf 2.9 Pn 36.8
A Pt 40.3
A q= 5.0 DOME
--------------------------------------------------------------------------
L= 75.0 Pt 40.3 Pt 40.3
7 Q= 31.3 F= LLEECC F= 12.0 C= 150 Pe 0.0 Pv -0.2
Ve1= 5.0 D= 1.590 TL= 87.0 0.0259 Pf 2.3 Pn 40.2
M Pt 42.6
M q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 10.0 Pt 42.6 Pt 42.6 8 Q= 31.3 F= G F= 0.0 C= 125 Pe 0.0 Pv -1.0
Ve1= 12.1 D= 1.025 TL= 10.0 0.3084 Pf 3.1 Pn 41.6
S
-------------------------------------------------------------------------- Pt 45.6
Q= 31.3 <<<
--------------------------------------------------------------------------
--------------------------------------------------------------------------
SOURCE >>> Pt 45.6
E=45-E1b L=90-E1b B=TeeBch R=TeeRun C=CouPlg SSwgChk G=GatVlv
100 150 200 250 300
&--------0 Water Supply
Static : 90 Psi
Resid : 89 Psi
Flow : 31 Gpm
• Water Demand
Avi Press : 89.0 Psi @ 31 Gpm
Req Press : 45.6 Psi @ 31 Gpm
80
70
60
50
40
30
20
10
0
350 400 450 500
FLOW - GPM
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgetori Drive, Lakeside CA 92040.
JOB : BAKER-LOPES TWO HEAD CALC 16 X 16
FILE : C:\RESDEN58\BAKER-LOPES.RES
DATE : 08-26-2013
PSI FIRE SPRINKLER HYDRAULIC GRAPH
100
90
Press Cush: 43.4 Psi
Copyright: Hydronics Engineering, 2012.
34119 Fremont Bi, Suite 609
Fremont, CA 94555.
(800) 845-9819.