Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series TV-B - 2.8, 5.6, and 8,0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General
Description
The Series TV-B, 2.8, 5.6, and 8.0
K-factor, Upright and Pendent Sprin-
klers described in this data sheet are
standard response - standard cover-
age, decorative 5 mm glass bulb type
spray sprinklers designed for use in
light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories, refin-
eries, chemical plants, etc.
The recessed version of the Series
TV-B Pendent Sprinkler, where appli-
cable, is intended for use in areas with
a finished ceiling. It uses a two-piece
Style 10(1/2 inch NPT) or Style 40(3/4
inch NPT) Recessed Escutcheon. The
Recessed Escutcheon provides 1/2
inch (12,7 mm) of recessed adjust-
ment or up to 3/4 inch (19,1 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level version of the
Series TV-B Pendent Sprinkler can be
obtained by utilizing the Series TV-B
Pendent Sprinkler in combination with
the Model S2 Shield.
WARNINGS
The Series TV-B Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TYII5I - Upright 2.8K, 112"NPT
TY1251 - Pendent 2.81K, 112"NPT
TY3151 - Upright 5.61K, 1!2"NPT
TY3251 - Pendent 5.61K, 1!2"NPT
TY4151 - Upright 8.0K, 314"NPT
TY4251 - Pendent 8.0K, 314"NPT
1Y4851 - Upright 8.0K, 112"NPT
TY4951 - Pendent 8.0K, 112"NPT
Pagel W8 APRIL, 2006 TFPI 51
SSU*
DEFLECTOR
7/16(11,1 mm)
NOMINAL
MAKE-IN
ESCUTCHEON
PLATE SEATING 1/2" **
SURFACE NPT
T_
2-1/4"
(57,2 mm) (U. ••.JJ
WRENCH
FLATS
SSU*
DEFLECTOR
6*
7/16"
1 (11,1mm)
NOMINAL I
;
: MAKE-IN
2-3/16" "
55,6 mm) 3
1/2" NPT f
UPRIGHT CROSS SECTION
ESCUTCHEON 7/16"(11,1 mm)
PLATE SEATING 1/2' ** NOMINAL
SURFACE M01 MAKE-IN
STYLE 10
RECESSED
ESCUTCHEON
T_
2-3/16"
(55,6 mm) -
L FRENCH
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
SSP DEFLECTOR*
PENDENT
Page 2 of 8 TFPISI
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
STANDARD RESPONSE SERIES TY-B UPRIGHT (TYII5I) AND PENDENT (TY1251) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
- Frame 3 - Sealing 4 Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2-Button Assembly 5- Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS
5.6K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4"
6mm)
(57,2 mm)
1-
(39,
7/16"(11,1 mm)
1/2" ** NOMINAL
MAKE-IN NPT
SSU*
DEFLECTOR
.-..-.. SSP*
DEFLECTOR CROSS
UPRIGHT SECTION
WRENCH
FLATS
PENDENT
TFPISI Page 3 of 8
ESCUTCHEON 1/2"(12,7 mm) STYLE 40
PLATE SEATING 3/4fl ** NOMINAL RECESSED SSU SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
2-5116" __________
1/2"
__________ (12,7 mm)
NOMINAL (58,7 mm)
2-1/4"
MAKE-IN w _ H
1-9/16"
_______
7,2 mm) I (39,7 mm)
__________ WRENCH
FLATS
I SSP DEFLECTOR* 2-7/8"(73,0 mm) DIA. -'4 3/4 NPT
PENDENT RECESSEDPENDENT UPRIGHT CROSS SECTION
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4151) AND PENDENT (TY4251) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Page 4 of 8 TFPISI
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE""
IPOLYESTER
LEAD
COATED
I WAX
COATED
I WAX OVER
LEAD COATED
2.8
1/2"
NPT
PENDENT
(TY1251)
and
UPRIGHT
(TYII5I)
135"F/57°C Orange
1,2,3 N/A
155°F/68°C Red
175°F/79°C Yellow
200°17/93"C Green
286°F1141°C Blue
360"F/182"C Mauve 1,2
5.6
1/2"
NPT
PENDENT
(TY3251)
and
UPRIGHT
(TY3151)
135"F/57"C Orange
1,2,3,4,5,6,7 1,2,3,5 1,2,3.5 1.2.3,5
155"F/68"C Red
175"F179"C Yellow
200°F193°C Green
286"F/141°C Blue 1,2**, 3** 5** 1, 2",3",5"
360"F/182°C Mauve N/A
135°F/57°C Orange
1.2. 3,4,5
I
I I
I I 1,2,4,5 N/A
RECESSED
PENDENT
(TY3251)"
Figure 4
155"F/68°C Red
175°F179°C Yellow
200°F/93"C Green
286°F/141"C Blue 1.2
8.0 3/4*
NPT
PENDENT
(TY4251)
and
UPRIGHT
(TY4151)
135°F/57"C Orange
1,2, 3.4, 5, 6. 7
1,2,5 1.2,3,5 1.2,5
155"F/68°C Red
175°F/79°C Yellow
200"F193°C Green
286"F/141°C Blue 1**,2**, 3'-,5** 1, 2k", 5**
360"F/182°C Mauve N/A
135"F/57°C Orange
1, 2, 3, 4,5 N/A
RECESSED
PENDENT
frY4251)"
Figure 5
155"F/68°C Red
175"F179°C Yellow
200"F/93"C Green
286"F/141"C Blue 1.2
8.0
1/2"
NPT
PENDENT
(TY4951)
and
UPRIGHT
(TY4851)
135"F/57°C Orange
1, 2, 3, 5 N/A
155"F/68°C Red
175"F/79"C Yellow
200°F/93"C Green
286"F/141°C Blue
360°F/182"C Mauve
NOTES:
Listed by Underwriters Laboratories, Inc. (UL).
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Approved by Factory Mutual Research Corporation (FM).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k103).
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05).
Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the
sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated
Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** 150"F/66°C Maximum Ceiling Temperature.
TABLE A, LABORATORY LISTINGS AND APPROVALS
TFPI5I Page 5 of 8
SPRINKLER FINISH
K TYPE NATURAL I CHROME I WHITE LEAD WAX WAX OVER
BRASS I PLATED POLYESTER COATED COATED LEAD COATED
2.8 PENDENT(TY1251)
1/2" and 175 PSI (12,1 BAR) N/A
NPT UPRIGHT (TYII5I)
PENDENT (TY3251)
5.6 and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
1/2" UPRIGHT (TY3151) OR
NPT 175 PSI (12,1 BAR) RECESSED PENDENT
(TY3251) (SEE NOTE 1) N/A
8.0 PENDENT (TY4251)
3/4" and 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4151)
RECESSED PENDENT
(TY4251) 175 PSI (12,1 BAR) N/A
8.0 PENDENT (TY4951)
1/2" and 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4851)
NOTE:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York.
TABLE B, MAXIMUM WORKING PRESSURE
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, VdS, and NYC Approved.
(Refer to Table A for complete ap-
proval information including corrosion
resistant status.)
Maximum Working Pressure
Refer to Table B.
Discharge Coefficient
K = 2.8 GPM/psi1'2 (40,3 LPM/barl/2)
K = 5.6 GPM/ps11/2 (80,6 LPM/bar112)
K = 8.0 GPM/psi112 (115,2 LPM/bar112)
Temperature Ratings
Refer to Table A.
Finishes
Sprinkler: Refer to Table A.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel wlTeflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector ...........Copper
Bushing (K=2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TV-B Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 10 or 40
Recessed Escutcheon, as applicable,
is to be used for recessed pendent
installations.
Page 6 of 8 TFPISI
2-7/8" DIA.
5/8±1/4"
(73,0 mm) I 3/4"(19,1 mm)
- (15,9±6,4 mm) 2-1/4" DIA. I 1/4" (6,4 mm)
FACE OF
SPRINKLER
2 mm) MOUNTING
PLATE
FITTING
1/8"
(3,2 mm)
__ __ ___
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm) 1
TV-B 3/4"(19,lmm)
FIGURE 5
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm)
- (15,9±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm)
(572 FACE OF mm) MOUNTING
SPRINKLER PLATE
FITTING
________ 1/8" I - (3,2 mm)
/
MOUNTING /
CLOSURE SERIES 1-5/16" (33,3 mm)
SURFACE
,
//
TV-B 13/16" (20,6 mm)
FIGURE 6
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 7
W-TYPE 6 SPRINKLER
WRENCH
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 8
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The Series TV-B Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/570C to 3/32
inch (2,4 mm) for the 360°F/1820C temperature ratings.
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.Ibs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
Page 8 of 8 TFPI5I
TV1251 P/N 57-XXX-X-XXX
I I
MODELJSIN
SPRINKLER
RATING
530 1 2.8K UPRIGHT (1/2'NPT) TY1I51 I 1 NATURAL BRASS 135 I l35FI57°C
590 2.8K UPRIGHT (1/2"NPT) 4 WHITE POLYESTER 155 155°F/6&C
570 5.6K UPRIGHT (1/?NPT) 3 WHITE (RAL90I0) 175 175FI79°C
571 5.6K PENDENT (1/2'NPT) 9 CHROME PLATED 200 200F/93C
590 8.0K UPRIGHT (3/4"NPT) 7 LEAD COATED 286 286°F/141 C
591 8.0K PENDENT (3/4'NPT) 6 WAX COATED 360 1 360°F1182*C
286°F/141C MAX. 560 8.0K UPRIGHT (1/2"NPT)
8 WAX OVER LEAD
561 8.0K PENDENT (1/2"NPT) 286°F/141*C MAX.
TABLE C
PART NUMBER SELECTION
SERIES TV-B PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Stand-
ard Response, (specify K-factor),
(specify temperature rating), Series
TV-B (specify Pendent or Upright)
Sprinkler with (specify type of finish or
coating), P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify 10 or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
TFPI5I Page 7 of 8
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-B Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 7),
except that an 8 or 10 inch adjustable
Crescent wrench is to be used for wax
coated sprinklers. With reference to
Figures 1, 2, 3, and 4 the W-Type 7
Sprinkler Wrench or the adjustable
Crescent wrench, as applicable is to
be applied to the wrench flats.
When installing wax coated sprinklers
with the adjustable Crescent wrench,
additional care needs to be exercised
to prevent damage to the wax coating
on the sprinkler wrench flats or frame
arms and, consequently, exposure of
bare metal to the corrosive environ-
ment The jaws of the wrench should
be opened sufficiently wide to pass
over the wrench flats without damag-
ing the wax coating. Before wrench
tightening the sprinkler, the jaws of the
wrench are to be adjusted to just con-
tact the sprinkler wrench flats. After
wrench tightening the sprinkler, loosen
the wrench jaws before removing the
wrench.
After installation, the sprinkler wrench
flats and frame arms must be in-
spected and the wax coating re-
touched (repaired) whenever the coat-
ing has been damaged and bare metal
is exposed. The wax coating on the
wrench flats can be retouched by gen-
tly applying a heated 1/8 inch diameter
steel rod to the areas of wax that have
been damaged, to smooth it back over
areas where bare metal is exposed.
NOTES
Only retouching of the wax coating ap-
plied to the wrench flats and frame
arms is permitted, and the retouching
is to be performed only at the time of
the initial sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken, when handling the
heated rod, in order to prevent the
installer from being burned.
The Series TY-B Recessed Pendent
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step A. After installing the Style 10 or
40 Mounting Plate, as applicable, over
the sprinkler threads and with pipe
thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 8). With reference to Figure 3
or 4, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10 or 40 Clo-
sure over the Series TV-B Sprinkler
and push the Closure over the Mount-
ing Plate until its flange comes in con-
tact with the ceiling.
Care and
Maintenance
The Series TV-B Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
XL51i&&i
SPECIFICATION SUBMITTAL IAL SHEET
(with OS&Y gates) (with BGVIC valves)
FEATURES Sizes: U 2 1/2" U 3" 0 4" 0 6" U 8" U 10"
Maximum working water pressure 175 PSI
Maximum working water temperature 140°F
Hydrostatic test pressure 350 PSI
End connections (Grooved for steel pipe) AWWA C606
(Flanged) ANSI B16.1
OPTIONS Class 125
(Suffixes can be combined)
U - with flanged end OS & V gate valves (standard)
U L - less shut-off valves (grooved body connections)
U LM - less water meter
U - with remote reading meter
U - with gpm meter (standard)
U - with cu fl/min meter
U G - with grooved end OS&Ygate valves
U FG - with flanged inlet gate connection and grooved
outlet gate connection
U P1 - with Post Indicator Gate Valves (4"-1 0")
U BGVIC - with grooved end butterfly valves
ACCESSORIES
0 Repair kit (rubber only)
U Thermal expansion tank (Model WXTP)
U OS & V Gate valve tamper switch (OSY-40)
U Test Cock Lock (Model TCL24)
DIMENSIONS & WEIGHTS (do not include
WEIGHT
MODEL WITH
350ADA WITHOUT WITH OS&Y WITH OS&Y BUTTERFLY
SIZE GATES GATES (G)F) GATES (G3) VALVES
(G)E3)
II ••T•ITI
APPLICATION
Designed for installation on potable water connections in
fire sprinkler systems to protect against both backsipho-
nage and backpressure of polluted water into the potable
'water supply. Model 350ADA shall provide protection where
a potential health hazard does not exist. Incorporates me-
tered by-pass to detect leaks and unauthorized water use.
STANDARDS COMPLIANCE (4"-8" Horz. & Vertical)
ASSE® Listed 1048
AWWA Compliant C510 (with gates only)
a CSA® Certified
UL® Classified (21/2"-10")
C-UL® Classified (2 1/2"-l0")
FM® Approved
Approved by the Foundation for Cross Connection
Control and Hydraulic Research at the University of
Southern California (2 1/2"-10" except 10" BGVIC)
MATERIALS
Main valve body
Access covers
Coatings
Internals
Fasteners & springs
Elastomers
Polymers
Ductile Iron ASTM A 536 Grade 4
Ductile Iron ASTM A 536 Grade 4
FDA Approved electrostatic epoxy finish
Stainless steel, 300 Series
NORYLTM, NSF Listed
Stainless Steel, 300 Series
EPDM (FDA approved)
Buna Nitrile (FDA approved)
NORYLTM, NSF Listed
MODEL 350ADA
with OS&Y optIOn
MODEL 350ADA with
BGVIC option
Attention: Model 350ADA
(grooved body) and Model 350DA
(flange body) have different lay
lengths.
C,
9,) a.
'a U,
S
'U
12 Ui
a.
FLOW CHARACTERISTICS
MODEL 350ADA 21/2", 3" & 4" (STANDARD & METRIC)
FLOW RATES (118)
12.6 25.2 37.9
11H 1111
I - .
--- —•—' i- _ii:- -
600
FLOW RATES (GPM)
MODEL 350ADA 6", 8" & 10"(STANDARD & METRIC)
FLOW RATES (us)
63.1 126.2 189.3 15
10
3000
C, 15
10
5
0
0 200 400
1000 2000
FLOW RATES (GPM)
ORated Row (Established by approval agencies)
50.5
104
69
35 cc
800
252.4
104
69 SQ
35
12
4000 a.
— .--;---- -
11
TYPICAL INSTALLATION
Local codes shall govern installation requirements. Unless
otherwise specified, the assembly shall be mounted at a
minimum of 12" (305mm) and a maximum of 30" (762mm)
above adequate drains with sufficient side clearance for
testing and maintenance. The installation shall be made so
that no part of the unit can be submerged.
MODEL 350ADABGVIC (VERTICAL INSTALLATION)
Capacity thru Schedule 40 Pipe (GPM)
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
21/2" 75 112 149 224
115 173 230 346
198 298 397 595
6" 450 675 900 1351
8" 780 1169 1559 2339
10" 1229 1843 2458 3687
12" 1763 2644 3525 5288
PROTECTIVE
MODEL 350ADA (OUTDOOR INSTALLATION)
SPECIFICATIONS
The Double Check Detector Backflow Prevention Assembly shall be ASSE® Listed 1048, and supplied with full port gate
valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and check
valve shall be NorylTM (NSF Listed), the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall
be EPDM. The first and second check valves shall be accessible for maintenance without removing the device from the
line. The Double Check Detector Backf low Prevention Assembly shall be a WILKINS Model 350ADA.
Page 2of2
WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 112 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zum.com