R-102 RESTAURANT
FIRE SUPPRESSION SYSTEM
Design, Installation, Recharge and Maintenance Manua
[tiANSUL.
SECTION IV - SYSTEM DESIGN• UL EX. 3470 ULC CEx747 Page 4-1
4-1-06 REV.6
SYSTEM DESIGN
The ANSUL R-102 Restaurant Fire Suppression System may be
used on a number of different types of restaurant cooking appli-
ances and hood and duct configurations. The design information
listed in this section deals with the limitations and parameters of
this pre-engineered system. Those individuals responsible for the
design of the R-102 system must be trained and hold a. current
ANSUL certificate in an R-102 training. program.
The R-102 and the PIRANHA systems use compatible agents and
components, therefore, they may be used together for cooking
appliance, hood, and duct protection. The primary ANSUL
AUTOMAN Release can be either. an R-102 or a PIRANHA ANSUL AUTOMAN Release and can actuate up to two additional
R-102 or. PIRANHA Regulated Actuators. In systems utilizing a
101 remote release, any combination of the maximum number of
regulated actuators can be used.
Both systems must actuate simultaneously.
Each system must be designed and installed per its apprOpri-
ate manual.
Adjacent appliances requiring protection must be protected
With the same type of system, either R-102 or PIRANHA,
unless the center-to-center spacing between the adjacent
R-102 and PIRANHA flozzles is no less than 36 inches.
When appliances are protected with R-102 nozzles, the hood
and connecting duct above those appliances cannot be pro-
tected with PIRANHA nozzles.
Mixing systems in a common plenum IS not allowed.
One of the key elements for restaurant fire protection is a correct
system design. This section is divided into ten sub-sections: Noz-
zle Placement Requirements, Tank Quantity Requirements, Actu-
ation and Expellant Gas Line Requirements, Distribution Piping
Requirements, Detection System Requirements, Manual Pull Sta-
tion Requirements, Mechanical Gas Valve Requirements, Electri-
cal Gas Valve Requirements, Electrical Switch Requirements, and
Pressure Switch Requirementè. Each of these sections must be
completed before attempting any installation. System design
sketches should be made of all aspects of design for reference
during installation.
NOZZLE PLACEMENT REQUIREMENTS
This section gives guidelines for nozzle type, positioning, and
quantity for duct, plenum, and individual appliance protection. This
section must be completed before determining tank quantity and
piping requirements.
Duct Protection - Single Nozzle
All duct protection is UL listed without limitation of maximum duct
length (unlimited length). This includes all varieties of ductworks
both horizontal and vertical including ducts that run at angles. to
the horizontal and ducts with directional. bends.
The R-102 system uses different duct nozzles depending On the
size of duct being protected.
GENERAL INFORMATION
1. Nozzles must be located 2-8 in. (5-20 cm) into the center of the
duct opening, discharging up. See Figure 1.
2-8 IN. (5-20 cm)
FIGURE 1
00cm In installatiOns where a UL. listed damper assembly is
employed, the duct nozzle can be installed beyond the 8 in.
(20 cm) maximum, to a point just beyond the damper assem-
bly that will not interfere with the damper. Exceeding the maxi-
mum of 8 in. (20 cm) in this way will not void the UL listing of
the system.
.Previously listed 3 flow number and 5 flow number duct pro-
tection detailed in earlier published manual, Part No. 418087-
06, can also still by utilized.
F
T SIZES UP 1050 IN. (127 cm)
IMETER! 16 IN. (41cm) DIAMETER
One1W nozzle (Part No. 41W36) = One flow number
50 in. (127 cm) perimeter maximum
16 in. (41 cm) diametei maximum
. DUCT SIZES UP 10100 IN. .(254 cm)
PERIMETER! 32 IN. (81.3 cm) DIAMETER
One 2W Nozzle (Part No. 419337) = two flow numbers
100 in. (254 cm) perimeter maximum
32 in. (81.3 cm). diameter maximum
A 2WH nozzle (Part No. 78078) must be substituted for a 2W
nozzle for any installation using Option 2 of the 1.5 gallon sys-
tem coverage (duct and plenum protection only). A 2WH nozzle
is limited to a maximum of 75 in. (190 cm) perimeter or a maxi-
mum diameter of 24 in(61 cm) of coverage.
The chart below shows-the maximum protection available from
each duct nozzle.
Part,• 3.0 Gallon 1.5 Gallon Desôription . No... : :. System System
2W Nozzle 419337 Maximum Maximum 100 in. (254 cm) 100 in. (254 cm)
Perimeter Perimeter ' 1W Nozzle 419336 Maximum 'Maximum 50 in. (127 cm) 50 in. (127 cm)
Perimetef Perimeter
FIGURE 11
FIGURE 14
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-6
REV. 5 4-1-06
Plenum Protection (Continued)
HORIZONTAL PROTECTION - OPTION 2 For a plenum, either single or "Vp bank, with a linear extension
1W NOZZLE - PART NO. 419336— ASP BANK PROTECTION longer than 10 feet (3.1 m), each bank maybe protected using one
IN nozzle every 10 ft. (3.1,'m) or less depending on the overall One 1W nozzle will protect 6 linear feet (1.8 m) of U5/A bank plenum. length of the plenum. See Figure 12. The nozzles may point in the The nozzle must be mounted horizontally, positioned 1/3 the filter opposite directions as long as the entire plenum area is protected, height down from the top of the filter. Nozzles can be located at 6 fL and the 10 ft. (3.1 m) limitation is not exceeded. See Figure 13. The 1 (1.8 m) spacings on longef plenums. The nozzle must be positioned nozzle positioning shown in Figure 14 is not an acceptable method 0-6 in. (0-15 cm) from the end of the hood to the tip of the nozzle. of protection because the plenum area directly under the tee Is not See Figure 10. within the discharge pattern of either nozzle.
IWNOW.E
10Ft(3.1m)
MAXIMUM '1
IOFT.(3.1 in)
MAXIMUM
10 FT. (3.1 m)
MAXIMUM
FT. (9.1 m)
FIGURE 12
10FT.(3.1 m)
MAXIMUM
FIGURE 10
MAXIMUM
W FT. (31
MAXIMUM
m) 42
1 NOZZLE - PART NO. 419335 - "Va BANK PROTECTION
Two IN nozzles will protect 10 linear feet' (3.1 m) by 4 ft. (1.2 m)
wide of 115f bank plenum. The nozzles must be mounted in the
plenum, 2 to 4 in. (5 to 10 cm) from the face of the filter, centered
between the filter height dimension, and aimed down the length.
The nozzle must be positioned 0-6 in. (0-15 cm) from the end of the
'hood to the tip of the nozzle. See Figure 11.
FIGURE 13
I
FIGURE 8
HORIZONTAL PROTECTION - OPTION 1
1 NOZZLE - PART NO. 419335 - SINGLE BANK PROTECTION
One IN nozzle will protect 10 linear feet (3.1 m) of single filter bank
Plenum. The nozzle(s) must be mounted in the plenum, 2 to 4 in.
(5 to 10cm) from the face of the filter, centered between the filter
height dimension, and aimed down the length. The nozzle must be
positioned 0-6in. (0-15 cm) from the end of the hood to the tip of the
I
nozzle. See Figure 9.
FIGURE 6
cm197 When protecting plenums with the 1W nozzle, two options of cov-
I- erage are available:
Option 1: The 1W nozzle must be On the center line of the single
or 'V bank filter and positioned within 1-20 in.
(2.5-51 cm) above the top edge of the filter. See
Figure 7.
FIGURE 9
SECTION IV - SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-5
4-1-06 REV.4
Plenum Protection.
The R-102 system uses the 1W Nozzle (Part No. 419336) or the
IN Nozzle (Part No. 419335) for plenum protection. The 1W noz-
zle tip is stamped with 1W and the I nozzle tip is stamped with
iN, indicating they are one-flow nozzles and must be counted as
one flow number each. When protecting a plenum chamber, the
entire chamber must be protected regardless of filter length.
VERTICAL PROTECTION - GENERAL
One 1W nozzle will protect 4 linear feet (1.2 m) of plenum. The
maximum distance from the end of the hood to the first and last
nozzle must be no more than 2 ft. (.6 m). After the first nozzle, any
additional nozzles must be positioned at a:maximum of 4 ft. (1.2 m)
apart down the entire length of the plenum. The plenum width must
not exceed 4 ft. (1.2 m). (The 1W nozzle can be used on single or
V-bank filter arrangements.) See Figure 6.
Option 2: The 1W nozzle must be placed perpendicular, 8-12 in.
(20-30 cm) from the face of the filter and angled to the
center of the filter. The nozzle tip must be within 2 in.
(5 cm) from the perpendicular center line of the filter.
See Figure 8.
8 IN. (20 cm)
MINIMUM
NOZZLET1P
MUST BE WITHIN
THIS AREA
20 IN. (51 cm)
MAXIMUM
1 IN. (2.6 cm)
MINIMUM
FIGURE 7
m0199
SECTION IV - SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4-9
4-1-06 REV.8
Fryer -Single Nozzle Protection (Continued)
Maximum Area Dimensions - Single Nozzle Fryer Protection (Continued)
Max. Size Max. Size Overall Type of Nozzle Height Frypot Only With Dripboard Nozzle Above Top of Fryer
19.5 in. x19 in. 19.5 in. x253/8 in. 290 13 in. to 16 in. (50 cm 48 cm) (50 cm x 65 cm) (33 to 41 cm)
19.5 in.x 19 in. 19.5 in. x 25 318 in. 3N See Figure (50 cm x 48 cm) (50 cm x 65 cm) 18
18 in. x 18 in. 18 in.x 273/4 in. 3N 25 in. to 35 in (46 cm x 46 cm) (46 cm x 70.5 cm) (64 cm to 89 cm)
Nozzle
Location
See Figure 17
See Figure 18
See Figure 19
11
,1 FRYER WITHOUT DRIPBARD FRYER WITH DRIPBOARD
290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE HAZARD AREA ± 3 IN. (7.6 cm) FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE HAZARD AND ±1 IN. (2.5 a FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE HAZARD AND 00M10 CENTERUNE AIMED AT THE MIDPOINT OF THE COOKING AREA.
FRYER WIThOUT DRIPBOARD FRYER WITH DRIPBOARD FIGURE 17 NOTE: SN NOZZLE TIP MUST BE LOCATED WITHIN THE PERIMETER OF THE SURFACE AREA WITHIN THE FRONT HALF OF THE FRY POT AND AIMED AT THE CENTER.
FIGURE 19
34 IN. (86 cm) MAXIMUM DIAGONAL
DISTANCE BETWEEN NOZZLE AND CENTER OF HAZARD AREA
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
SN NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOK- ING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA.
FIGURE 18
Range Protection 2-FloW Nozzle
High Proximity Application (2-Flow Nozzle): 40 in. to 50 in. (102 cm to 127 cm) above the cooking surface.
This high proximity application uses the 245 nozzle, Part No.
419340.
The nozzle tip is stamped with 245 indicating this is a two-flow
nozzle and must be counted as two flow numbers.
One 245 nozzle will protect a maximum cooking area of 672 sq. In. LOCA TI COOKING SURFACE
o ) (4335 sq. cm) with a maximum longest dimension of 28 in. (71 cm).
When using this nozzle for range protection, the nozzle must OR
ii 3/8 IN. (29 cm) be pointed vertically down and positioned as shown In Figures
CENTERLINE OF NOZZLE 29 and 30. TO CENTER OF ANY 101 BURNER GRATE
ING
245 NOZZLETIP
LOCATION CENTER OF)
COOKING SURFACE
OR 1138 IN. (29 cm)
MAXIMUM FROM
CENTERLINE OF NOZZLE TO CENTER OF ANY BURNER GRATE
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-14 REV.5 10-1-02.
245 NOZZLE TIP LOCATION CENTERLINE OF COOKING SURFACE
501. I lIr
02. —.1
MAXIMUM I HEIGHT I OF 245
- NOZZLE -lip
40 IN. 1 (102 an)
MINIMUM
HEIGHT I 0F245 I NOZZLE
TIP
I I— 00236 0 00 0 0
I
FIGURE 29
NOTICE
Four burner grates shown in Figure 30. For sin-
gle or double burner grates, locate nozzle at
center of cooking surface or 113/8 in. (29 cm)
maximum from nozzle centerline to center of
any burner grate.
FIGURE 30
- AIM POINT
(DIAGONAL
CENTER OF CENTER OF MODULE I Ij I MODULE COOKING AREA) COOKING
i
IMIO
IN
T
(DIAGONAL
N
AREA)
I J RIGHT-TO-I.EFT RIGH1TO-
CENTERUNE LEFT
- CENTER-
LINE
SECTION IV - SYSTEM DESIGN UL EX. 3470 ULCCEx747 Page 4-11
4-1-06 REV.8
Fryer - Multiple Nozzle Protection (Continued)
Maximum Area Dimension - Multiple Nozzle Fryer Protection
Max. Size Module Max. Size Module Overall Type of Frypot Only With Drlpboard Nozzle
Full or Split Vat Full or Split Vat 21 In. x 210 in.2 21 in. x 294 in.2 230 (53cmx.14m2) (53cmx.19m2)
Full or Split Vat Full or Split Vat 21 in. x 210 in.2 21 in. x 294 in.2 245 (53 cmx .14 m2) (53 cm .19 m2)
Full or Split Vat Full or Split Vat 21 in. x 210 in.2 21 in. x 294 in.2 290 ..(53cmx.14m (53cmx.19m2)
25 3/8 x 370.5 in2 253/8 x 495 in2 290 (65 cm x .24 m2) (65 cm x .32 m2)
' Full or Split Vat Full or Split Vat 26 1/2 in. x 203 in.2 26 1/2 in.x 384 1/4 in.2 290 (67cmx.13m2) (67 cmx .25 m2)
253/8 x 370.5 in2 253/8 x 495 In2 3N (65cmx.24m2) (65cmx0.32m2)
273/4 x 324 In.2 273/4 x 497 in2 3N (70.5 cm x .21 m2) (70.5 cm x .32 m2)
Nozzle Height Nozzle Above Top of Fryer Location
27 in. to 47 in. See Figure 21 (69 cm to 119 cm)
20 in. to 27 In. See Figure 21 (51 to 69 cm)
13 in. to 16 in. See Figure 22 (33 to 41 cm)
13 in. to 16 in. See Figure 22 (33 to 41 cm)
16 In. to 27 in. See Figure 22 (41 to 69 cm)
See Figure 23 See FIgure 23
25 in. to 35 In. See Figure 24 (64 cm to 89 cm)
84 IN. (86 cm) MAXIMUM DIAGONAL
DISTANCE BETWEEN NOZZLE
9 AND CENTER I
HAZARD AREA
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
POSITION NOZZLE TIP ANYWHERE ALONG OR WITHIN THE PERIMETER OF THE MODULE IT IS PROTECTING AND AIM AT THE MIDPOINT OF THAT MODULAR AREA.
FIGURE 21
FRYER WITHOUT DRIPBOARD FRYER WITh DRIPBOARD
3M NOZZLE TIP MUST BE POSITIONED ANYWHERE ALONG OR WITHIN THE
PERIMETER OF THE MODULAR if IS PROTECTING AND AIMED AT THE MIDPOINT OF THAT RESPECTIVE MODULE AREA.
FIGURE 23
21 In. (53
MINIMUM
VERTICAL
NOZZLE
HEIGHT
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE RESPECTIVE MODULAR AREA ± S IN. (1.6 cm) FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE MODULE AND ± I IN. (2.5 an) FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE MODULE AND AIMED AT THE MIDPOINT OF THE MODULE.
FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD
THE SN NOZZLE TIP MUST BE POSITIONED ANYWHERE ALONG OR WITHIN THE PERIMETER AND FORWARD OF THE RIGHT-TO-LEFT CENTERLINE OF THE COOKING AREA. THE AIMING POINT OF THE NOZZLE MUST BE AT THE DIAGONAL CENTER OF
THE MODULAR COOKING AREA. FIGURE 22. FIGURE 24
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-24
REV.6 4-1-06
Gas-Radiant/Electric Char-Broiler Protection
The R-102 system uses the 1 N nozzle, (Part No. 419335) for gas-
' radiant/electric char-broiler protection.
The nozzle tip on the 1 nozzle is stamped with a IN, indicating
that this is a one-flow nozzle and must be counted as one flow
number.
One IN nozzle will proteât a hazard with a maximum length of
36 in. (91 cm) and a total cooking area which does not exceed
864 sq. in. (5574 sq. cm). The nozzle tip must be located 15 to
40 in. (38 to 102 cm) above the hazard surface. When using this
o. nozzle for gas-radiant/electric char-broiler protection, the nozzle
must be positioned anywhere along or within the perimeter of the
maximum cooking area and shall be aimed at the center of the
cooking surface. See Figure 51.
COOKING
AREA
40 IN.
(102 cm)
MAXIMUM
15 IN. (38cm)
MINIMUM
FIGURE 51
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-28
REV.5 4-1-06
Nozzle Application Chart
The following chart has been developed to assist in calculating the
quantity and type of nozzle required to protect each duct, plenum,
or appliance.
NOTICE
This chart Is for general reference only. See
complete details for each type of hazard.
Minimum : Nozzle Tip
Hazard
Maximum Hazard
Dimensions
Nozzle
Quantity
Nozzle
Height
Nozzle
Part No.
Stamping -
Flow No.
'Duct or Transition Length - Unlimited 1 - 430912 1W (Single Nozzle) Perimeter —50 in. (127 cm)
Diameter —16 in. (40.6 cm)
Duct or Transition Length - Unlimited 1 - 419337 2W (Single Nozzle) Perimeter-100 in. (254 cm)
Diameter —31 7/8 in. (81 cm)
Duct or Transition Length —Unlimited 2 - 419337 2W (Dual Nozzle) Perimeter —150 in. (381 cm)
Diameter —48 In. (122 cm)
Electrostatic Precipitator Individual Cell 1 - 419334 1/2N (At Base of Duct)
Plenum Length —10 ft. (3.1 m) 1 - 419335 iN (Horizontal Protection)
'Plenum Length —6 ft. (1.8 m) 1 - 430192 1W (Horizontal Protection) Width —4 ft. (1.2 m) 1 - 419336 1W
Plenum Length —4ft. (1.2 m) 1 - 419336 1W (Vertical Protection) Width— 4 ft. (1.2 m)
'Fryer (Split or Maximum Size
Non-Split Vat) (without drip board)
14 In. (36 cm) x
15 in. (38 cm) .1 13-16 in. 419342 290 Low Proximity (33 —41 cm)
Fryer (Split or Maximum Size
Non-Split Vat) (without drip board)
14 1/2 in. (37 cm) x
141n. (36 cm) I 16-27 in. 419342 290 Medium Proximity (41 —69 cm)
Fryer (Split or Maximum Size Non-Split Vat)* (without drip board)
15 in. 38 cm) x
14in.(36cm)
High Proximity 1 27-47 in. 419339 230 Medium Proximity 1 20-27 in. 419340 245 Fryer (Non-Split Vat Only) Maximum Size
(without drip board)
191/2 in. (49.5 cm)x
19 in. (48.2 cm)
High Proximity 1 21 —34 in. 419338 3N Low Proximity I 13-16 in. 419342 290 Maximum Size
(without drip board)
18 in. (45.7 cm)
x 18 In. (45.7 cm)
High Proximity 1 25-35 in. 419338 3N (64-89 cm)
For multiple nozzle protection of single fryOrs, see detailed Information on Pages 4-12 through 4-14.
27-47 in.
20-27 in.
21 —34 in.
13-16 in.
25-35 in.
(64-89 cm)
13-16 in.
(33 —41 cm)
16 —27 in.
(41 —69cm)
30-40 in.
(76-102 cm)
40-48 in.
'(102-122 cm)
(With Backshelt)
40-50 in.
(102-127 cm)
30-40 In.
(76-102 cm)
15-20 in.
(38-51cm)
419339 230
419340 245
419338 3N 419342 290
419338 3N
419342 290
419342 290
419335 IN
419333 IF
419340 245
419341 260
419342 290
SECTION IV - SYSTEM DESIGN UL EX. 3470 ULC CEx747 Page 4.29
4-1-06 REV.5
Nozzle Application Chart (Continued)
Minimum Nozzle lip Maximum Hazard Nozzle Nozzle Nozzle Stamping - Hazard Dimensions Quantity Heights Part No. Flow No, Fryer (Non-Split Maximum Size Vat Only)* (with drip board)
21 in. (53 cm) x
14 in. (36 cm)
(Fry Pot must not exceed
15 in.x 14 in.
(38 cm x 36 cm))
High Proximity
Medium Proximity
Maximum Size
(with drip board)
253/8 in. (64.4 cm)
x 19 1/2 in. (49.5 cm)
(Fry pot side must not
exceed 19 1/2 in.
(49.5 cm) x 19 in.
(48.2cm)
High Proximity
Low Proximity
Maximum' Size
,(with drip board)
. : 18 in. (45.7 cm)
x 273/4 in. (70.5 cm)
High Proximity
Fryer (Split or Maximum Size Non-Split Vat) '(with drip board)
l4 in. (36 cm) x
21 in. (53 cm)
Low Proximity
Fryer (Split or Maximum Size Non-Split Vat) (with drip board)
14 1/2 in. (37 cm) x
26 1/2 in. (67 cm)
Medium Proximity
Range Longest Side
:32 in. (81 cm)
Area —384 sq. in.
(2477 sq. cm)
Longest Side
28 in. (71 cm)
Area —336 sq. in.
(2168 sq. cm)
Longest Side (High Proximity)
28 in. (71 cm)
Area —672 sq. In.
(4335 sq. cm)
Longest Side
(Medium Proximity)
32 in. (81 cm)
Area —768 sq. in.
(4955 sq. cm)
Longest Side (Low Proximity) 2 36 in. (91 cm)
Area —1008 sq. in.
(6503 sq. cm)
For multiple nozzle pmtectlon of single fryem see detailed information on Pages 4-
7
t
h
m
u
g
h
4
-
1
1
.
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-30
REV.3 10-1-02
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Hazard
Maximum Hazard
Dimensions Nozzle
Quantity
Nozzle
Heights
Nozzle •
Part No
Stamping -
Flow No.
Griddle Longest Side (High Proximity) 1 30-50 in. 419341 260 48 in. (122 cm) (76-127 cm) Area —1440 sq. in. (perimeter (9290 Sq. cm) located)
Longest Side (High Proximity) 1 30-50 in. . 419342 290 30 in. (76 cm) (76-127 cm) Area —720 sq. in. (center located) (4845 sq. cm)
Longest Side (High ProximIty) 1 35 - 40 in. 419335/417332 1N/1NSS 361n.(91 cm) (89-102 cm) . Area - 1080 sq. in. (perimeter located) (6968 sq. cm)
Longest Side 1 20-30 in. 419342 .290 (Medium Proximity) (51 —76 cm) 48 in.. (122 cm) (perimeter Area— 1440 sq. in. located) (9290 sq. cm)
Longest Side (Low Proximity) 1 10-20 in. 419343 2120 48 in. (122 cm) (25 —51 cm) Area —1440 sq. in. (perimeter (9290 sq. cm) . located) . .
Chain Broiler Longest Side —34 in. (86 cm) 2 10-26 in. 419336/417333 . IW/1WSS (Overhead Protection) Area - 1088 sq. In. (25 —66 cm) (7019 sq. cm)
Chain Broiler Length —43 in. (109 cm) 2 1•— 3 in 4193351417332 . iN/i NSS (Horizontal Protection) Width —31 in. (79 cm) (3-8 cm)
Gas-Radiant Char-Broiler Longest Side —36 in. (91 cm) 1 15-40 in. 419335/417332 iN/i NSS Area — 864 sq. in. (38-102cm) (5574 sq. cm)
Electric Char-Broiler Longest Side —34 in. (86 cm) 1 20-50 in. 419335/417332 iN/i NSS Area —680 sq. in. (51 - 127 cm) (4388 sq. cm)
Lava-Rock Broiler Longest Side —24 in. (61 cm) 1 18-35 In. 419335/417332 1 N/l NSS Area — 312 sq. in. (46-89cm) (2013 sq. cm)
Natural Charcoal Broiler Longest Side - 24 in. (61 cm) 1 18-40 in. 419335/417332 IN/i NSS Area-288 sq. in. (46 —102 cm) (1858 sq. cm)
Lava-Rock or Natural Longest Side —30 in. (76 cm) 1 14-40 in. . 419338 3N Charcoal Char-Broiler Area —720 sq. in. (36-102 cm) (4645 sq. cm)
Minimurn chain broflerexhaust opening -.121n.xl2 In. (31 cmx3l m), and not Ins than o%of Internal broiler size.
I-
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-48 REV.4 4-1-06
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements —1.5 Gallon System
DUCT, PLENUM, AND APPLIANCE PROTECTION
This option allows for duct protection, plenum protection,
appliance protection, or any combination.
When using a combination of plenum and duct protection only, only one duct nozzle, either a 1W, or a 2W, may be used.
The previous Option 2 (using 2WH nozzle for plenum and duct
protection) still can be utilized. For detailed design information,
see previous version of this manual, Part No. 418087-06.
Note: When using this option, all design parameters must:be
followed as listed in manual version -06.
All distribution piping, supply and branch, must be 3/8 in.
Schedule 40 black iron, chrome-plated, or stainless steel.
Each 1.5 gallon tank allows a maximum of five flow numbers.* a.
The pipe length between the start of the first branch line and the start of the last branch line must not exceed 8 ft. (2.4 m).
When the supply line is split, the combined length of both
legs of the supply line (start of first branch line to start of last branch line) must not exceed 8 ft. (2.4 m). See Figure 91.
The combined length of all branch lines must not exceed 22 ft..
(6.7 m). See Figure 92.
The requirements of the'following table must not be exceeded:
Duct Requirements . Supply Branch Line
Pipe Size 3/8 in. 3/8 in.
Maximum Length 40 ft. 6 ft.
(12.2 m) (1.8 m)
Maximum Rise 61% -4 ft.
(1.8m) (1.2m)
Maximum 900 Elbow 9 . 4
Maximum Tees 1 1
Maximum Flow Numbers 5* 2
START OF LAST
BRANCH LINE
START OF FIRST
BRANCH LINE
SUPPLY
.
•.j;ç-
•miJ LINE TEE L LENGTH
MUST NOT
EXCEED a Fr.
iSTART OF LAST
.J BRANCH LINESTART OF FIRST
BRANCH LINE
FIGURE 91
1W NOZZLE
(BRANCH LINES IN BOLD) . COMBINED LENGTH MUST
NOT EXCEED 22 Ft (6.7 m)
FIGURE 92
000715
Plenum Appliance
3/8 in. 3/8 in.
4 f 10 f
(12m) (3m)
2 f 21t
(.6 m) (.6 m
4 6
2. 3.
2 . .3
ExceptIons:
. . Six (6)110w numbers are allowed when a duct branch One Is the last branch line on the pipIng network and no IN nozzles are used to protect wOks orgrldctes.
SIx (6) flow numbers are allowed when sIx (6) IN nozzles are used and none of the nozzles axe used to protect woks and griddles. NOTE: Only five (5) flow
numbers are allowed If a IN nozzle Is used for wok or griddle protection.
Six (6) flow numbers are allowed when only two (2) 3N nozzles are used
LINE MUST NOT
EXCEED 24 FT. (7.3 m)
2W NOZZLE
3 BRANCH LINES
IN NOZZLE
:J~
_'*- IN NOZZLE
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-49
4-1-06 REV.4
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements -3.0 Gallon System
The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft. (7.3 m). When the supply line is. split, the combined total of
both legs of the supply fine (from the start of the first branch line to the start of the last branch line) must not exceed 24 ft. (7.3 m). See Figure 93.
The total length of all branch lines must not exceed 36 ft.
10. (10.9 m). See Figure 93.
Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. supply line.
A maximum of two nozzles are allowed per duct branch line.
The requirements of the following table must not be exceeded:
230 NOZZLE /
245 NOZZLE 112N NOZZLE
(BRANCH LINE IN BOLD)
COMBINED LENGTH MUST 000502 NOT EXCEED 36 Ft (10.9 m)
FIGURE 93
Duct Plenum Appliance Requirements Supply Line Branch Una Branch Urie Branch Line
Pipe Size . 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft. 8 ft. 4 ft . 12 ft. (12.2 m) (2.4 m) (1.2 m) (3.7 m)
Maximum Rise 6 ft 4 ft 2 ft. 2 ft. (1.8 m) (1.2 m) (.6 m) (.6m).
Maximum 90° .9 4 . 4 6 Elbows
Maximum Tees 1 2 2 4
Maximum Flow 11* .4 2 4 Numbers
Exceptlons:
I. Twelve (12)110w numbers are allowed In anyone tank for duct and plenum protection only.
flvelve (12) flow numbers are allowed With any one tank using only two-How appllancenozzles. Twelve (12)110w numbers are allowed With anyone tank using only three-flow appliance nozzles.
SpecIal Instructions:
Twelve (12)110w numbers are.aflowed when four (4) Dean Ifldusti1es Gil Gas Fryars are protected at low proximity as shown In Figure 58 on Page 4-32. The discharge piping must be as shown In FIgure 59 on Page 4-32.
For certain McDonald applications, 11.5110w numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 112N electrostatic precipitator nozzle, one (1) 1N plenum nozzle, and four (4) two4tow appliance nozzles. Contact Maul Applications Englneedng Department for additional information.
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-52
REV.3 4-1-06
DISTRIBUTION PIPINGREQUIREMENTS (Continued)
Distribution Piping Requirements -9.0 Gallon System
This optional configuration consists only of three 3-gallon tanks, all pressurized from a single double-tank nitrogen cartridge with expellant gas hoses connected as shown in Figure 97. Tanks No. 1 and No.2 must be connected directly to the regulator with sepa-rate expellant gas hoses and Tank No. 3 must be connected to 'Tank No.2 with a third expellant gas hose as shown in Figure 97. Each tank must be connected to an independent distribution pip-
sing network as shown in Figure 97. Distribution piping require-
ments for each network must be as follows:
The maximum length between the start of the first branch line and the start of the last branch line must not exceed 24 ft. (7.3 m). When the supply line is split the combined total of
both legs of the supply line (from the start of the first branch line to the start of the last branch tine) must not exceed 24 ft.
' (7.3 m). See Figure 93.
The total length of all branch lines must not exceed 36 ft.
' (10.9 m). See-Figure 93.
Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. supply line.
A maximum of two nozzles are allowed per duct branch line.
When using this 9.0 gallon system configuration, no nianl-
folding of distribution piping is allowed.
When an ANSUL AUTOMAN RégulatedRelease is utilized in
this configuration, additional regulator actuators cannot be
used.
Only 3 gallon tanks can be utilized In- this configuration.
The requirements of the following table must not be exceeded.
for each 3 gallon tank:
&0 &0 &0, GALLON GALLON GALLON TANK TANK lANK NO.3 NO.2 NO.1
TWO TANK ENCLOSURE 3 GALLON REGULATED DOUBLE TAM( NITROGEN
ASSEMBLY PART NO. RELEASE ASSEMBLY, CARTRIDGE OR 430324 (INCLUDES (2) OR 3 GALLON LT4001.30 CARTRIDGE HOSES AND (2) REGULATED ACTUATOR (REGULATED ACTUATOR GROMMETS) ASSEMBLY ONLY)
NOTE: IFiWOTANK ENCLOSURE ASSEMBLY..PART NO. 43ON4.1$ CONNECTED TO THE 3 GALLON REGULATED RELEASE ASSEMBLY. NO ADDrrIoNA1. REGULATED ACTUATOR(S) ASSEMBUES CAN BE USED.
FIGURE 97
new?
Duct Requirements Supply Line Branch Line
Plenum
Branch Una
Appliance
Branch Una. Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft. 8 ft. .4 It. 12 it. (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 ft. 4 ft. 2 ft. (1.8 m) (1.2 rn) (.6 m) (.6 m)
Maximum 900 9 4 4 6 Elbows
Maxlmum.Tees 1 2 2 4
Maximum Flow 11* 4 2 4 Numbers
EXcapttons:
Twa We (12) flow numbers are allowed In anyone tank for duct and plenum protection ONLY. Twelve (12) flow numbers are allowed with any one tank using only heo-lbe appliance nozzles. Twelve (12) flow numbers are allowed with any one tank using only threeftow appliance nozzles.
special Instruatloow
When four (4) Dean lndustiles OTT Gas Fvyers are protected at low prrsdmfty as shown In Figure 58 on Page 442. the discharge piping must be asshownIn Figure 59 on Page 4-32.
For certain McDonald applications. 11.5 flow numbers are allowed when using a combinatIon of one (I) 2W duct nozzle. one (I) II2N electrostatic precipitator nozzle. one (1) 1N plenum node. and four (4) 1w0410w appliance nozzles. Contact Maul Applications Englnaedng Department 1* additional Information.