HomeMy WebLinkAbout1209 LANAI CT; ; CBR2023-3700; PermitBuilding Permit Finaled
Residential Permit
Print Date: 03/27/2024
Job Address:
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load:
Code Edition:
Sprinkled:
Project Title:
1209 LANAI CT, CARLSBAD, CA 92008-1000
BLDG-Residential
1563513300
$33,087.21
Work Class:
Track#:
Lot 1#:
Project 1#:
Plan 1#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Pool
Permit No:
Status:
{city of
Carlsbad
CBR2023-3700
Closed -Finaled
Applied: 07/31/2023
Issued: 08/28/2023
Finaled Close Out: 03/27/2024
Final Inspection: 03/19/2024
INSPECTOR: de Roggenbuke, Dirk
Description: RAM IREZ: POOL/SPAW/ BAJA SHELF 30 X 17 (510 SF) SPA 7X7 (49 SF); 6' MAX DEPTH; GAS+ ELEC STUB FOR FUTURE BBQ
Applicant:
SUE MONGOVEN
321 SUN BIRD CT
SAN MARCOS, CA 92069-3021
(714) 630-6100
FEE
BUILDING PLAN CHECK
BUILDING PLAN REVIEW -MINOR PROJECTS (LDE)
BUILDING PLAN REVIEW -MINOR PROJECTS (PLN)
SB1473 -GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION -RESIDENTIAL (SMIP)
SWIMMING POOL -RESIDENTIAL
Total Fees: $700.40 Total Payments To Date: $700.40
Contractor:
ZIER POOLS INC
321 SUN BIRD CT
SAN MARCOS, CA 92069-6895
(760) 290-4147
Balance Due:
AMOUNT
$159.90
$194.00
$98.00
$2.00
$0.50
$246.00
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required Information with t he City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Fai lure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DO ES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processi ng or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
,.
(Cityof
Carlsbad
~
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Pian Check C:RQ2C>2..3-3?00
Est.. Value ~~3,o<e17.l.\·
PC Deposit .:J;IS'L °to
Date 7/&\/23. ,
Job Address ( zor lff/AJ Ct>u-&: Unit: ____ APN: l:£'2-¾:f -:,3-0 0
CT/Project#: /(p O £vz lot#: / D Year Built: _.;.~_~__;.::lb:;;.... ____ _
Fire Sprinklers:0,E()No Air C~nditioning:QYEs0No Electrical Panel UpgradeQvEs0No
SRI.ff DESCRIPTION OF WORK: ,, " {:fro i) $£7.l: ?JL7{19t/)
0 New SF: living SF,-..,_~-Deck SF,, ___ Patio SF,, ___ Garage Sf __ _
Is this to create an Accessory Dwelling Unit? QvQN New Fireplace? ovoN, if yes how many? __
□Remodel: :e.n.~a-------1-!s-:tne..aiea a conversion or change of use?Qv QN
}:: Pool/Spa: 59 ___________ s? 'ff(~ wzt--:ru,t'uf2G 6(p,?J
Osolar:. ___ K'W,, ___ Modules, MountedOoofOround, TittO vON, RMA:Qv{)N,
Battery: CJ< OJ, Panel Upgrade: Qv ~
D Reroof:. _______________________________ _
D Plumbing/Mechanical/Electrical
0 Only: Other.
PRIMARY APPLICANT PROPERTY OWNER
Name: S1t;,G kVtQ{Jbz'JV 0/ Name: 1111 ff& felt/vJ«Afk:
Address: ~ 2--1 5~tlt) er-Address: IW'7 IA-,!At q,ufHC
City: W IM&t¼e$State:CA ;,; '6iat;,7 City: ~ _ State: Cit. Zip: f.t,;,z$
Phone: 7wt2--2-71---/b /5? Phone:, _ __:li_~----::2'.......,..~----a...,.'A....,'<-p,.._--------
Email: <;;(dftj;O Z-Z-1>t(:R/H,m-t: Email: _______________ _
DESIGN PROFESSIONAL CONTRACTOR OF RECORD
Name: _ _,o~~~~::......:!:e!::;;;:::;.,_ _____ Business Name:::;2/& ,IL ~ Is ;z;:c_
Address: . Address: ;? 2-/ ,ft(# .;&(Ii# CT
City: zyo 7 City: 'f'1,v A 11#> Sta~e;_q}__ztp: 'o/%241
Phone: 7tf-G OOZJ Phone: 760--672----cl~
Email:. ______ ...,,.........,,.._ _______ Email:, ____ ~---~----~----
Architect State License: C-(MG7 CSLB License#: &:z'1a5(;l Class: ~
Carlsbad Business License# (Required): /J t/0 h~
APPLICANT CERTIRCA TION: I certifytha.t I have read the applicatiqnandsJ;ate tha.t the above information is correct and that the
information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
construction. I
NAME (PRINT): ~/46 f/lUJ.1 6i1]/t?A,I
1635 Faraday Ave carlsbad, CA 92008
1
TH~ PAGE REQUIRED AT PERMIT ISSUANCE PlAN OIECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON
SIGNING THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO
PERMIT ISSUANCE.
(OPTION A): LICENSED CONTRACTOR DECtARATION:
lherebyaflinnunderpenaltyofperjurythatlamlicensedunderprovistonsofChapter9(commendngwithSeetion7(XJ())o/DMsion3
of the Bustnessand Professions Code, and my license #sin full force and effect. I alsoaffinn under penalty of perjury one of the
following declarations(CHOOSE ONE);
Q have and will maintain a certificate of consent t(? self-insure for workers' compensation provided by Section 3700 of the labor Code, for the perfonnance of the rkwhlchthispennitlslssued. PolicyNo.,_ ____________________________________ _
-Oil•
f"11 have and wnt maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is Issued.
~workers' compensation insurance carrier and policy number are: lnsurancaCompany Name: ____________________ _
PollcyNo. ________________________ Expirationl>ate: _____________ _
IQ{'~::;ficate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any mann6 so as to become
~ect to the workers' compensation Laws of California. WARNING: Failure to S4ICU1'e workers compensation coverase Is unlawful and shal subject an employer to
criminal penalties and dvll fines up to $100,000.00, In addition the to the a>st of compensation, damaps as provided for In Section 3706 of the labor Code,
Interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued {Sec. 3097 (i) Civil c.ode).
Lender'sName: ____________________ .Lender'sAddress: ___________________ _
COHTRACTOR CERTIFICATION: I certify that I have read the application and state that the above information is correct and that
the Information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
constructfon.
• OR -
(OPTION B): OWNER-BUILDER DECLARATION:
J.ttereby affirm that I am exempt from Contractor's License Law for the following reason: U I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec
7044, Business and Professions Code: The Contractor's License law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner-builder wilt have the burden of proving that he did not build or improve for the purpose of sale).
-OR-O I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, ·Business and Professions Code: The
Contractor's License Law does not apply to an owner of property wtio builds or improves thereon, and contracts for such projects with contractor{s) licensed
pursuant to the Contractor's License law).
-OR-O I am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
AND.
0 FORM 8-61 "0wner Builder Acknowled1ement and Verification Formn is required for any permit issued to a property owner.
By my signature below l acknowledge that, except for mv personal residence in which I must have resided for c1t least one year prior to completion of the
improvements covered by this permit, I cannot legally sell a structure that I hav.e built as an owner-builder if it has not been constructed in its entirety by licensed
contractors. I understand thatacop'Jof the applicable law, Section 7044of theBusinessOlldProf essioosCode, is available upon request when thisoppllcotion is
submitted orat the following Web site: http://www.leginfo.ca.govlcalaw.html.
OWNER CERTIFJCA TION: I certify that I have read the application and state that the above information is correct and that the
infonnatlonon the plans is accurate. I agree to comply wfth all City ordinances and State laws relating to building
construction.
NAME(PRINT):StiufvJAJ2tJcmm SIGN= ~.-.---.f--1---....... ~ ______ DATE: ?('Pll?P~z
Note: If the person signing ;above Is ;in authorized ;agent fur the property owner lndude form 8-62 d by property owner. (
1635 Faraday Ave Carlsbad, CA 92008 PW-760-602-2719 fax: 760-602-8558 Email: Buildlng@carlsbadca.goy
2 REV. 07/21
Building Permit Inspection History Finaled
(City of
Carlsbad
PERMIT INSPECTION HISTORY for (CBR2023-3700)
Permit Type: BLDG-Residential Application Date: 07/31/2023 Owner: ANONYMOUS COMPLAINTANT
Work Class: Pool Issue Date: 08/28/2023 Subdivision:
Status: Closed -Finaled Expiration Date: 09/03/2024 Address: 1209 LANAI CT
IVR Number: 51006 CARLSBAD, CA 92008-1000
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Re inspection Inspection
Date Start Date Status
10/26/2023 10/26/2023 BLOG-51 228514-2023 Passed Dirk de Roggenbuke Complete
Excav/Steel(Pools)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLOG-52 Pool Plumbing 228513-2023 Passed Dirk de Roggenbuke Complete
BLDG-53 228512-2023 Passed Dirk de Roggenbuke Complete
Elec/Conduit/Wiring(Po
ols)
02/21/2024 02/21/2024 BLDG-54 Equipotential 239903-2024 Passed Dirk de Roggenbuke Complete
Bond(Pools)
BLDG-SW-Inspection 240108-2024 Passed Dirk de Roggenbuke Complete
Wednesday , March 27, 2024 Page 1 of 4
PERMIT INSPECTION HISTORY for {CBR2023-3700)
Permit Type: BLDG-Residential
Work Class: Pool
Application Date: 07/31/2023
Issue Date: 08/28/2023
Status: Closed -Finaled Expiration Date: 09/03/2024
Scheduled
Date
IVR Number:
Actual Inspection Type
Start Date
Inspection No.
Checklist Item
Are inactives slopes properly
stabilized?
Are areas natter than 3:1
covered or protected?
Are sediment controls properly
maintained?
Are erosion control BMPs
functioning properly?
Are natural areas protected
from erosion?
Do basins appear to be
maintained as required?
Are perimeter control BMPs
maintained?
Is the entrance stabilized to
prevent tracking?
Have sediments been tracked
on to the street?
Are storm drain inlets
protected and maintained?
Have materials collected
around the storm drains?
Has sediment accumulated on
impervious surfaces?
Are dumpsters and trash
receptacles covered?
Has trash/debris accumulated
throughout the site?
Are stockpiles and spoils
protected from runoff?
Are all storage areas clean
and maintained?
Are spill kits provided onslte?
Are washout areas maintained
and protected?
Were spills/leaks observed
during the inspection?
Were there any discharges
during the inspection?
Is the SWPPP wall map up to
date and accurate?
Was the SWPPP or Erosion
Control Plan reviewed?
Are portable restrooms
properly positioned?
Do portable restrooms have
secondary containment?
Are BMPs stockpiled for
emergency deployment?
COMMENTS
Wednesday, March 27, 2024
51006
Inspection
Status
Owner: ANONYMOUS COMPLAINTANT
Subdivision:
Address: 1209 LANAI CT
CARLSBAD, CA 92008-1000
Primary Inspector Reinspection Inspection
Passed
No
No
Yes
Yes
No
No
Yes
Yes
Yes
No
No
Yes
No
Yes
No
No
No
No
Yes
Yes
No
No
Yes
Yes
No
Page 2 of 4
PERMIT INSPECTION HISTORY for (CBR2023-3700)
Permit Type: BLDG-Residential
Work Class: Pool
Application Date: 07/31/2023 Owner: AN ONYMO US COMPLAINTANT
Issue Date: 08/28/2023 Subdivision:
Status: Closed -Finaled Expiration Date: 09/03/2024 Address: 1209 LANAI CT
Scheduled
Date
Actual Inspection Type
Start Date
IVR Number:
Inspection No.
03/05/2024 03/05/2024 BLDG-55 241168-2024
03/19/2024
Fence/Prep laster
Checklist Item COMMENTS
BLDG-Building Deficiency
BLDG-SW-Inspection
Checklist Item
241276-2024
COMMENTS
Are erosion control BMPs
functioning properly?
Are perimeter control BMPs
maintained?
Is the entrance stabilized to
prevent tracking?
Have sediments been tracked
on to the street?
Has trash/debris accumulated
throughout the site?
Are portable restrooms
properly positioned?
Do portable restrooms have
secondary containment?
03/19/2024 BLDG-Final Inspection
Checklist Item
242502-2024
COMMENTS
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
BLDG-SW-Inspection
Checklist Item
242750-2024
COMMENTS
Are erosion control BMPs
functioning properly?
Are perimeter control BMPs
maintained?
Is the entrance stabilized to
prevent tracking?
Have sediments been tracked
on to the street?
Has trash/debris accumulated
throughout the site?
Are portable restrooms
properly positioned?
Do portable restrooms have
secondary containment?
Wednesday, March 27, 2024
51006 CARLSBAD, CA 92008-1000
Inspection Primary Inspector Reinspection Inspection
Status
Passed Dirk de Roggenbuke Complete
Passed
Yes
Passed Dirk de Roggenbuke Complete
Passed
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Passed Dirk de Roggenbuke Complete
Passed
Yes
Yes
Yes
Yes
Yes
Passed Dirk de Roggenbuke Complete
Passed
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page 3 of 4
PERMIT INSPECTION HISTORY for (CBR2023-3700)
Permit Type: BLDG-Residential
Work Class: Pool
Status: Closed -Finaled
Scheduled Actual Inspection Type
Date Start Date
Wednesday, March 27, 2024
Application Date: 07/31/2023 Owner: ANONYMOUS COMPLAINTANT
Issue Date: 08/28/2023 Subdivision:
Expiration Date: 09/03/2024 Address: 1209 LANAI CT
IVR Number: 51006 CARLSBAD, CA 92008-1000
Inspection No. Inspection Primary Inspector Reinspection Inspection
Status
Page 4 of 4
Tr11 orth
COMP IANC
August 9, 2023
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
City of Carlsbad -FINAL REVIEW
City Permit No: CBR2023-3700
True North No.: 23-018-718
Carlsbad, CA 92008
Plan Review: Pool and Spa
Address: 1209 Lanai Ct
Applicant Name: Sue Mongoven
Applicant Email: sumo223@cox.net
OCCUPANCY AND BUILDING SUMMARY:
Occupancy Groups: R-3/U
Occupant Load: NI A
Type of Construction: V-B
Sprinklers: NIA
Stories: l
Area of Work (sq. ft.): Pool and Spa: 559 sq. ft.
The plans have been reviewed for coordination with the permit application.
Valuation: Confirmed
Scope of Work: Confirmed
Floor Area: Confinned
Attn: Building & Safety Department,
True North Compliance Services, Inc. has completed the final review of the following documents for the project
referenced above on behalf of the City of Carlsbad:
1. Drawings: Electronic copy dated August 28, 2023, by Zier Pools.
2. Structural Calculations: Electronic copy dated June 28, 2023 , by Chris Biedenbach.
The 2022 California Building, Mechanical Plumbing and Electrical Codes (i .e. 2021 IBC, UMC, UP , and 2020
NEC, as amended by the State of California), 2022 California Green Building Standards Code, 2022 California
Existing Building Code and 2022 California Energy ode as applicable, were used as the basis of our review.
Please note that our review has been comp1eted and we have no further comments.
We have enclosed the above noted documents bearing our review stamps for your use. Please call if you have any
questions or if we can be of further assistance.
Sincerely
True North Compliance Services
Review By: Richard Moreno -Plans Examiner
True North Compliance Services, Inc.
15375 Barranca Pkwy, Suite A202, Irvine, CA 92618
T / 562.733.8030
STORM WATl=R POLLUTION PREVliNTION NO'res
I. ALL NECESSARY E.QUIPMf.NT ANO MA lERIALS SMALL BE
AVAILA!llE ON SITE TD F'ACILITATE RAPID INSTALLATION OF EROSION AND SEDIMENT CONTROL BMPs WHEN RAIN 1$ EMINENT,
2. Tl-IE QVINER/CO\lllRACTOR SMALL R;STORE All EROSION
CONTROL l)t\1CES TO WORKING ORDER TO THE SATISFACTION
OF THE CITY INSPECTOR AFTER EACH RI.JN•OfF PRODUCING RAINF'Al.i:
3. THE OWNEH/CONlRACTOll SHALL INSTALL ADDITIONAL EROSION CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY INSPECTOR DUE TO INCOMPLETE' GRAPING OPERAnONS OR UNl'0RESWI CIRCUMSTANCES WMICH MAY ARISE.
4. Al:L REMOVABLE PRO1ECTIVE OEVICES ~AU. BF. IN PLACE
AT M!: END OF EACH WORKING 0/\Y WHEN THE nvi:; (6}
DAV RAIN PR08ABILITY FORECAST EXCEEDS FORTY PECl!NT ( 40%), Sll T AND OTHER DEBRIS SHALi. Bt R~MOVEO AFTER
EACH RAINFALL.
5. ALL GRAVEL BAGS SHALL OON1'AIN 3/4 INCH MINIMUM AGGREGATE,
6, AO~QUA TE EROSION AND SEOIMEN'f CONmOL /\ND PEfllMETER PROTEC110N BEST MANAGEMENT PRACTICE MEASURES MUST
8E INSTALLED ANO MAINTAINED.
7, 'THE CITY INSPECTOR SHALL HA VE THE AUTHORITY TO ALTER
THIS PLAN OURING OR BEPORE CONSTRUC'llON AS NEEOEO
TO ENSURE COMPLIANCE WITH C1TY STORM WATER QUALITY
REGULATIONS,
QWN§R'S CER1'1FICATE:
I UNOERSTAtil) AND ACKNOWI.EDGE lHAT I MUST: (1) lMPLEMiNT
Bl!ST MANAOEMOIT PRAO'hCES (BMPS) DURING CONSTRUCTION ACJMTIES TO lllE MAXIMUM EXTENT PRACTICASI.E TO AVOID TI-IE MOBIUZA'IIOII OF POLLUTANTS SUCH AS SEDIMENT /\1110 TO AI/OID lHE El<POSURE OF STORM WATER TO COIISTRUCTION REl.,\1£0 POlLUTAlilS; A!IP (2) AO~E 10, AND AT /\t.L 1lMES,
COMPLY V,,11! 'lijS CITY APPROVED TIER 1 CONSTRUCTION S\\PPP lllROUGflOUT 1H£ llURA TION or '!HE CONSTRUCTION ACTIVl11£S
UNTIL THE COKSlRIJOTION WORK IS COMPL£1E AND APPRO\IEO
!:l'f THE CITY Of' CARI.SSAD, , ...-c,, /
.r: fVl orJ Gc; ·V e:;v
f-29
\ . .
STORM WATER COMPLIANCE FORM
·neR 1 CONSTRUCTION SWPPP
E-29
CB ___ _
SW_~ __
BEST MANAGEMENT PRACTICES (BMP) SELECTIOI~ TABLE
t:msto~Conkcl Soillrnon\ Conlco1 BMPs Tr&QIIJOO Non.Slorm WQlor Waslo Managomen1 and M.al~~III~ 8 Ps--Con~ol DfAPs Mllnogemenl aMPa Pollullon Conltol BMPs
] ,§ I I I s ) j 'ti le. j f f i "'II l .i -~ i .QI ,W 6-;; g :s j ~ i li eest Managemanl Pracllce' j J.g;
:.:,
(BMP) D.esortpllon ➔ Ill i rnJl ~ ffJ. i &l ii
!113
55 ,. J r ;;I ~g' u 1 ]~ '51 >,
,., 6 0,
Q .m .2 Q ill iJ f i J M· ·g l elil ii II °";
,. li 11 1 I cl:] 11 ii ii; ,§ 01 0 t'E m~ 111cl! j ~8 if io :icn :,; ill
CASQA Oo"unodon -) "i' If 0, T ~ ·r. Ill I<) ~ ... 0 N ,., 'r "' 1 ; ~ 1 "' J T m ill ~ ~ T rk ~ ~ ~ ti
1-·cUvll•
[rl ftl LlJ ~ Ill lil ~ ~ ~ "' · ,._ i o vrbonco l"L ....... ::,,,,-~ ..,,, :x:
1-Q\'011011 s •
Or*'·-'"··· -
_E!!s11wcutUnn
: u lnalollptlon
,--"""'( -L....
L.... O'"" Area
EnU enl .:.-..i.,.·.1111co c•d Fu•llnn
...,..11/'dauo S!lbslonee • Ua~l~lnrono
D111otsr1M ..
!!Ila A!10ttle Aeroa1 Dirt
"'I~"" 11111\:
lnstruollonor • 1. Chock \ho box lo tho lert of on appllcoblo COI\Bltucttan aollvlty (flrot column) expocled tc occur during conolrucllon.
2, t.ocotod olo0.9 the top of the BMP Tobia Is a list er BMP'e with ll'o oorrpapondlng CQlflornl~ Slormwalor Quality Aoeoclotlon (CASQA) dedlgnollan number. Choooo cnu or rnoro eM?s you Intend lo uso durfno construction from the Unt. Choclt the box whore the cho,on octlvfly row fntereoota with Iha BMP column,
3, Refer lo the, CASOA conolruollon hondbool< lor lnlormutlon ond dotans of the ohosen BMPo • and how lo opply lhOlll lo Iha projoo\,
SHOW Tri/: LOCATIONS OF At.L CHOSEN BMPs ABOVE
ON THE PROJl:CTS SITE PLAN/eROS/ON CONTROL PLAN. SEE THE REVERSE S/Dt; OF THIS SHEET FOR A'SAMPLE
BROS/ON CONTROL Pl.AN,
PROJECT INFORMATION ,
Site Addreom f]-o!f £A,,//tt Ctr
Aosassor'a Porco! Number/.$,-~f-.".,..
.e en i@.,
I
1 1j
~
Emerg:;:e:~'£ k1 e¥k:
24 Hour f'hono:':1./td)--fe IV r&e?J
Co11slr11cl10n lhroat lo $\orm Water Quallly (Choe!< 8011) .
0 MEDIUM LOW
Pago 1 of 1
.e
fl-""5 .Pl$
1 fj.g
d~
;
·=
REV 02/16
Building Permit Finaled
Residential Permit
Print Date: 02/13/2024
Job Address : 1166 LARKSPUR LN, CARLSBAD, CA 92008-3405
Permit Type: BLDG-Residential Work Class:
Parcel#: 2054300600 Track #:
Valuation : $57,735.12 Lot#:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load :
Code Edition:
Sprinkled:
Project Title:
Project#:
Plan #:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Description: MAST: 107 SF ADDITION TO ENTRYWAY// 839 SF REMODEL
Applicant:
BA WORTHING INC
ALENA BLASIO
3864 WESTHAVEN DR
CARLSBAD, CA 92008-2754
(760) 533-8380
FEE
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
Property Owner:
DEAN MAST
2645 A ST
SAN DIEGO, CA 92102-1009
(760) 518-8833
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESI DENTIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
SWPPP INSPECTION FEE TIER 1 -Medium BLDG
SWPPP PLAN REVIEW FEE TIER 1 -MEDIUM
Addition
Total Fees: $1,411.96 Total Payments To Date: $1,411.96
(city of
Carlsbad
Permit No: CBR2020-0868
Status: Closed -Finaled
Applied: 04/24/2020
Issued: 07/30/2020
Finaled Close Out: 01/02/2024
Final Inspection: 12/28/2023
INSPECTOR: Alvarado, Tony
Contractor:
BA WORTHING INC
Renfro, Chris
Dreibelbis, Peter
5145 AVENI DA ENCINAS, # STE I
CARLSBAD, CA 92008-4322
(760) 729-3965
Balance Due:
AMOUNT
$441.44
$309.01
$43 .00
$175.00
$52.00
$80.00
$3.00
$7.51
$246.00
$55.00
$0.00
Ple ase take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processi ng in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
( City of
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
8-1
Plan Check
Est. Value
PC Deposit ---------
Date
Job Address 1166 Larkspur Lane Suite: APN: 205-430-06-00 ----
CT/Project#: _________ Lot#: ____ Fire Sprinklers: yes /Gia Air Conditioning: 8 / no
BRIEF DEscR1PT1ON oF woRK: -1.lb ..... Q~D .... 1_,,::t._.,=IJ=n'---.,To'-=---1.C=-,,Hrrfi.'-+-"-'-~--+~-~.,_--67<...,,8...&..L-9-"Sf==-_.N£y)_-"=-........... i1 ..... .o ... Rl ____ _
)( Addition/New: 107 Living SF, Deck SF, ___ Patio SF, ___ Garage SF
Is t his to create an Accessory Dwelling Unit? Yes /(fi@ New Fireplace? Yes /@a, if yes how many? __
JMt: Remodel: _8_3_9 __ SF of affected area Is the area a conversion or change of use ? Yes/ 6[aJ
0 Pool/Spa: ____ SF Add itional Gas or Electrical Features? ___________ _
□ Solar: ___ KW, __ Modules, Mounted: Roof/ Ground, Tilt: Yes/ No, RMA: Yes/ No, Battery: Yes/ No
Panel Upgrade: Yes/ No
D Reroof: -----------------------------------
□ Plumbing/Mechanical/Electrical Only: ________________________ _
D Other: ------------------------------------
APPLICANT (PRIMARY CONTACT)
Name: Alena Brooks Blasio
Address: 5145 AVENIDA ENCINAS, SUITE I
City: CARLSBAD State: CA Zip: 92008
Phone: 760-729-3965
Email: INFO@THISISBAWINC,COM
DESIGN PROFESSIONAL
Name: BROOKS WORTHING
Address: 5145 AVENIDA ENCINAS, SUITE I
City: CARLSBAD State: CA Zip: 92008
Phone: 760-729-3965
Email: INFO@THISISBAWINC.COM
Architect State license: ---=3'-=9=2=-=8'-=9'-4=---------
PROPERTY OWNER
Name: Dean Mast
Address: 1166 Larkspur Lane
City: Carlsbad State: CA Zip: 92008
Phone: (760) 729-5676
Email: INFO@THISISBAWINC.COM
CONTRACTOR BUSINESS
Name: B.A. WORTHING INC.
Address: 5145 AVENIDA ENCINAS. SUITE I
City: CARLSBAD State: CA Zip: _9=2::.:,0...,.0=8 __ _
Phone: 760-729-3965
Email: INFO@THISISBAWINC.COM
State license: 398764 Bus. License: 549200
(Sec. 7031.S Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
Issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law
(Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she Is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500)).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
8-1 Page 1 of2 Rev. 06/18
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
t have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit ts Issued.
)( i have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is Issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: _ .... IC....._W._.....,G.....,R...,.O.._..U._.p....._ ____________ _
Policy No. WSD 5052565 00 Expiration Date: Q1/Q1/?Q?1
□ Certificate of Exem ption: I certify that in the performance of the work for which this permit is Issued, I shall not employ any person In any manner so as to be come
subject to the workers' compensation Laws of California. WARNING : Failure to secure workers compensation coverage Is unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, In addition the to the cost of compensation, damages as provided for In Section 3706 of the Labor Code,
Interest and attorney's fees.
CONTRACTOR SIGNATURE:
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am eKempt from Contractor's License Low for the following reason:
□ I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not Intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or Improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not Intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
□ t, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
□ i am exempt under Section _______ Business and Professions Code for this reason:
l. I personally plan to provide the major labor and materials for construction of the proposed property Improvement. □ Yes □ No
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (Include name address/ phone / contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (Include name/ address/ phone/ type of work):
OWNER SIGNATURE: -------------------------□AGENT DATE: ______ _
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there Is a construction lending agency for the performance of the work this permit Is Issued (Sec. 3097 (i) Civil Code).
Lender's Name: ____________________ lender's Address: ___________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? □ Yes □ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? □ Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for Inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit Issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void If the building or work authorized
by such permit is not commenced within 180 days from the date of such permit or If the building or work authorized by such permit is suspended or abandoned at any time
aft" ~,wo,k • rnmmeoced lo, a period o/100,.,, (Se~
APPLICANT SIGNATURE: -----~----.-.--~-1-_ ... ~::_:----;------DATE: 04/23/2020
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
B-1 Page 2 of 2 Rev. 06/18
Building Permit Inspection History Finaled
(_ City of
Carlsbad
PERMIT INSPECTION HISTORY for (CBR2020-0868)
Permit Type: BLDG-Residential Application Date: 04/24/2020 Owner: DEAN MAST
Work Class: Addition Issue Date: 07/30/2020 Subdivision: WOODLAND HEIGHTS
Status: Closed -Finaled Expiration Date: 08/04/2021 Address: 1166 LARKSPUR LN
IVR Number: 26099 CARLSBAD, CA 92008-3405
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date Status
08/26/2020 08/26/2020 BLDG-11 136790-2020 Passed Peter Dreibelbis Complete
Foundatlon/Ftg/Piers
(Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
10/14/2020 10/14/2020 BLDG-34 Rough 140839-2020 Partial Pass Peter Dreibelbis Re inspection Incomplete
Electrical
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Elec at interior shear walls Yes
10/16/2020 10/16/2020 BLDG-84 Rough 141131-2020 Passed Peter Dreibelbis Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolling-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
11/05/2020 11/05/2020 BLDG-18 Exterior 142994-2020 Passed Chris Renfro Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
05/27/2021 05/27/2021 BLDG-Final Inspection 158341-2021 Partial Pass Tony Alvarado Reinspection Incomplete
Tuesday, February 13, 2024 Page 1 of 3
PERMIT INSPECTION HISTORY for (CBR2020-0868)
Permit Type: BLDG-Residential
Work Class: Addition
Status:
Scheduled
Date
12/28/2023
Closed -Finaled
Actual Inspection Type
Start Date
Checklist Item
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
12/28/2023 BLDG-Final Inspection
Checklist Item
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
BLDG-SW-Inspection
Tuesday, February 13, 2024
Application Date: 04/24/2020 Owner: DEAN MAST
Issue Date: 07/30/2020 Subdivision: WOODLAND HEIGHTS
Expiration Date: 08/04/2021 Address: 1166 LARKSPUR LN
CARLSBAD, CA 92008-3405 IVR Number: 26099
Inspection No. Inspection Primary Inspector Reinspection Inspection
Status
COMMENTS
May 27, 2021 :
1. No building/re,nodel Deficiencies.
2. Structural, plumbing , electrical, and
mechanical scope of work for single family
residence alteration, per engineer's plans
in detail specifications-approved.
May 27 . 2021 :
1. No building/remodel Deficiencies.
2. Structural. plumbing. electrical. and
mechanical scope of work for single family
residence alteration, per engineer's plans
in detail specifications-approved.
May 27, 2021 :
1. No building/remodel Deficiencies.
2. Structural, plumbing, electrical, and
mechanical scope of work for single family
residence alteration, per engineer's plans
In detail specifications-approved.
May 27, 2021 :
1. No building/remodel Deficiencies.
2. Structural, plumbing, electrical, and
mechanical scope of work for single family
residence alteration, per engineer's plans
in detail specifications-approved.
235148-2023 Passed Tony Alvarado
COMMENTS
235149-2023 Passed Tony Alvarado
Passed
Yes
Yes
Yes
Yes
Complete
Passed
Yes
Yes
Yes
Yes
Complete
Page 2 of 3
PERMIT INSPECTION HISTORY for (CBR2020-0868)
Permit Type:
Work Class:
Status:
Scheduled
Date
BLDG-Res idential Application Date: 04/24/2020
Addition Issue Date:
Closed -Finaled Expiration Date:
IVR Number:
Actual Inspection Type
Start Date
Inspection No.
Checklist Item
Are inactives slopes properly
stabilized?
Are areas flatter than 3:1
covered or protected?
Are natural areas protected
from erosion?
Is the entrance stabilized to
prevent tracking?
Have sediments been tracked
on to the street?
Have materials collected
around the storm drains?
Has sediment accumulated on
impervious surfaces?
Are dumpsters and trash
receptacles covered?
Has trash/debris accumulated
throughout the site?
Are all storage areas clean
and ma intained?
Were spills/leaks observed
during the inspection?
Were there any discharges
during the inspection?
COMMENTS
07/30/2020
08/04/2021
26099
Inspection
Status
Tuesday, February 13, 2024
Owner: DEAN MAST
Subdivision: WOODLAND HEIGHTS
Address: 1166 LARKSPUR LN
CARLSBAD, CA 92008-3405
Primary Inspector Reinspection Inspection
Passed
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page 3 of 3
DATE: 06/03/2020
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2020-0868
PROJECT ADDRESS: 1166 Larkspur
✓. EsG1I
A SAFEbuilt Company
SET: II
~PPLICANT /o JURIS.
PROJECT NAME: Remodel and Addition for the Mast Residence
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil until
corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
Alena Brooks
~ EsGil staff did not advise the applicant that the plan check has been completed .
D EsGil staff did advise the applicant that the plan check has been completed .
Person contacted: Telephone#: 760 729 3965
Date contacted:6 /3{20 (b~ ) Ema il: info@thisisbawinc.com
Mail Telephone
0 REMARKS:
By: Javier Snider
EsGil
Fax In Person
Enclosures:
05/21/2020
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92 I 23 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
PCSD Engrneering Corp
3529 Coastview Court
Carlsbad, CA 92010
Ph: 760-207-1885
Structural Design Calculations
Residential Addition
Client
Brooks Design
Project
Mast Residence
1166 Larkspur Lane
Cartsbad CA 92008
April 17, 2020
PCSD File#: 20-150
,..,c .!-4n°,t¥A-.. 1'~
LH .. ~""'1
Paul Christenson San Diego Engineering
3529 Coastview Ct -Carlsbad, CA 92010
Telephone (760) 207-1 885 -Emall: paul.pcsd@gmall.com
1.0 Design Criteria: Mast Residence
20-150
Code:
Timber:
2019 California Building Code -ASCE 7-16
Douglas Fir-Larch (DF-L), WWPA or WCLIB
2x Wall Framing : DF-L #2 (unless noted otherwise)
2x Rafters & Joists: DF-L #2 " "
Posts & Beams: DF-L #1 "
Glue-Lam Beams: Simple Span: Grade 24F-V4 (DF/DF)
Grade 24F-V8 (DF/DF) Cantilevers:
Sheathing: Min. APA-Rated Sheathing, Exposure 1, Plywood or OSB (U.N.O.)
Engineered Framing Wood I-Joists: TJI 110,210,230,360,560 ICC ESR-1153
1.9E Microllam, 2.0E Parallam ICBO ER-4979
Concrete:
Concrete Block·.
Mortar:
Grout:
LVL, PSL
Compressive Strength @ 28 days per ASTM C39-96:
Footings: f'c = 2500 psi
Grade Beams: f'c = 3000 psi
Grade N-l per A.S"TM C90-95, f'm = '\500 psi per A.S"TM E447-92
Type S Mortar Cement per ASTM C270-95, Min. f'm = 1800 psi@ 28 days.
Coarse Grout w/ 3/8" Max. Aggregate per ASTM C476-91,
Min. f'm = 2000 psi@ 28 days.
Reinforcing Steel: #4 & Lar9er:
#3 & Smaller:
ASTM A615-60 (Fy = 60 ksi)
ASTM A615-40 (Fy = 40 ksi)
Structural Steel: 'W' Shapes: ASTM A992, Fy= 50-65 ksi
Plates, Angles, Channel~ASTM A36, Fy = 36 ksi
Tube Shapes: ASTM A500, Grade B, Fy= 46 ksi
Pipe Shapes: ASTM A53 , Grade B, Fy=35 ksi
Welding Electrodes: Structural Steel: E70-T6
E90 Series
Bolts:
Soils:
References:
A615-60 Rebar:
Sill Plate Anchor Botls & Threaded Rods:
Steel Moment & Braced Frames:
1500 psf Bearing Pressure
A307 Quality Minimum
A325 (Bearing, U.N.O.)
,?',u./r;',tnmh.rt,h ";Jn, ~Jc,
bJUIHFUIJ
JOB 20-150
SHEET NO 2,. OF _ __,,..,.,..,,,.,.,,..,,-
CALCULATEO BY PSC DATE 4/17/20
CHECKBY _____ DATE __ _
3529 Coastview Ct -Carlsbad, CA 92010 SCALE
Telephone (760) 207-1885 -Email: paul.pcsd gmall.com
2.(J LOAD LIST
2.1 Roof {Vaulted)
Roofing
15/32" Sheathing
Roof Framing
5/8" Gyp. Bd.
Insulation and Misc.
IoL =
I,LL =
Total Load=
2.2 Roof (w/ ceiling)
Roofing
15/32" Sheathing
RoofFraming
Insulation and Misc.
2.3 Ceiling
Ceiling Joists
IoL =
ILL=
Total Load=
5/8" Gyp. Bd.
Insulation and Misc.
2.4 Walls
IoL =
.Iu =
Total Load=
Exterior Wall
7/8" Stucco
15/32" Sheathing
2x4 Studs@ 16" o.c.
5/8" Gypsum Bd.
Misc.
6.0 psf
1.5 psf
2.8 psf
2.8 psf
1.9 psf
15.0 psf
20.0 psf
35.0 psf
6.0 psf
1.5 psf
2.8 psf
1.7 psf
12.0 psf
20.0 psf
32.0 psf
1.3 psf
2.8 psf
1.9 psf
6.0 psf
J 0.0 psf
16.0 psf
9.0 psf
1.5 psf
1.1 psf
2.8 psf
0.6 psf
15.0 psf
Interior Wall
1/2"' Gyp. Bd. (2 Sides)
2x4 Studs@ 16" o.c.
Misc.
4.6 psf
I. I psf
2.3 psf
8.0 psf
. ;t
?,n,Jf:',f'TU'&1nJ"On efDt c.V~o
bJ'neerhtf
3529 Coastview Ct -Carlsbad, CA 92010
JOB 2~1~
SHEET NO 3 OF ___ .____ -----
CALCULATED BY PSC DATE 4/17/20
CHECK BY DATE ---SCALE p-...,.L ~rifU"-W"' SA,,c. ~•
?;"'Jinu,i"'J Telephone (760) 207-1885 -Email: paul.pcsd gmall.com
Z.<t LOAD LIS'l'(CON'l'INl
2.5 Floor
Floor Cover
Sheathing
2x F.J.
5/8" Gyp. Bd.
rnsulation and Misc.
IoL =
ILL =
Total Load=
5.5 psf
2.3 psf
3.5 psf
2.8 psf
0.9 psf
15.0 psf
40.0 psf (60.0 psf -Decks)
55.0 psf
WIND PARAMETERS
2.6 Wind Basic Wind Speed = 110 mph Exposure Cat = B
Ps = ),.Kzt•t•Ps30 (ASCE 7-16 • Equation 28.5-1)
P = 26.6 psf
P = 16.0 psf (•0.6 -ASD)
2.7 Seismic
SMs = 1.136
S05 = (2/3) SMs
S0s = 0.757
Sos
Cs = (R/I)
Cs = 0.117
USE:
V= 0.117 WoL
ASD BASE SHEAR
VASD
(I 1.4.5)
>.= 1.00 (fig.28 . .5.1-Ps30= 26.6 psf
Kzt= 1.00 (fig.26.8-1 ) I= 1.0
USGS APPLICATJON
Ss = l.054 S1 = 0.382
Fa = 1.08
R = 6.5
h0 = 25.00
Occupancy Category:
Site Class:
f v= 0.00
I = 1.00
2
D
SEISMIC DESIGN CATEGORY
s, <0.7~
s, >0.04
Ss >o.u
(11.6 ASCE 7-16)
(11.4.2 ASCE 7-16)
(fig. 28.5-1)
(table 1.5-2)
1'. = C1 • ('n,;)°-75 = 0.224
Ts = So,ISos. 0
k= 1.0
:'.qn. 12.8-l Not 01
Ta<0.5
Seismic Design Category: D
4116/2020 U.S. Seismic Design Maps
Mast
1166 Larkspur Ln, Carlsbad, CA 92008, USA
Latitude, Longitude: 33.154725, -117.3335287
~ Econo Lodge Inn T & Suites Carlsbad Near ..
D,:.iys nn by
Wyndh~m Carlsb<,1d
'' \\ ' ~ o,., Ft <;
., o'enault's Ace Hardware f
' .... -· .. ·,.·, St Patrickft
\\ ,.\./\.Catholic Church y ·
•,.::
OSHPD
)/('
Valley Middle ft
School Track T
'l>c'+-
~'o\ i. 'o
\>-"~
<\-\i,:-;· Map data ~2020
Date
Dulgn Code Reference Document
Risk Category
'Site Class
Type Value
Ss 1.054
S1 0,382
SMs 1.137
SM1 null-See Section 11.4.8
• Sos 0.758
'. So1 null -See Section 11 .4.8
Type Value
'soc null-See Section 11.4.8
Fa 1.078
Fv null -See Section 11.4.8
PGA 0.464
FpGA 1,136
PG~ 0.527
• TL 8
, SsRT 1.054
SsUH 1.177
, SsD 1.5
S1RT 0.382
S1UH 0.421
S10 0.6
PGAd 0.547
CRs 0.895
https:/fseismicmaps.org
Description
4/16/2020, 2:24:53 PM
ASCE7-16
II
D -Stiff Soil
MCER ground motion. (for 0.2 second period)
Description
MCER ground motion. (for 1.0s period)
Site-modified spectral acceleration value
Site-modified spectral acceleration value
Numeric selsmic design value at 0.2 oecood SA
Numeric seismic design value at 1.0 second SA
Seismic design category
Site ampllflcatlon factor at 0.2 second
Site amplification factor at 1.0 second
MCE0 peal< ground acceferatlon
Site amplification factor at PGA
Site modified peak ground acceleration
Long-period transition period in seconds
Probabilistic risk-targeted ground motion. (0.2 second)
Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration
Factored deterministic acceleration value. (0.2 second)
Probabilistic risk-targeted ground motion. {1.0 second)
Factored uniform-hazard (2% probability of exceedance In SO years) spectral accelerstion.
Factored deterministic acceleration value. (1 .0 second)
Factored deterministic acceleration value. (Peak Ground Acceleration)
Mapped value of the risk coefficient at short periods
1/3
+ 0
MEMBER REPORT
Floor Framing, (FB·l) Fir Bm
1 piece(s) 7" x 9 1/2" 2.0E Parallam® PSL
Overall Length: 18' 3"
All locations are measured from the outside face of left support ( or left cantilever end). All dimensions are horizontal.
;I· " • ~'!Altiit;:;1~1; ;l~~'Q'\-:• ~(I'-_, • ~ .. f.1u,1 ~t!~ ,.__i,,.~~~-V ";f/ ,, <· ~t~0L~~~~iti! 11,·~,~ ~i ,,,co ,'" '."'t : ,, "•N:•wt;~~~t,~;~f' ' ,.,_H,~1~rq;:
Member Reaction (lbs) 3290 @ l' 7 3/4" 15313 (3,50") Passed (21%) .. 1.0 D + 1.0 L (All Spans)
Shear (lbs) 2802@ 17' 2" 12857 Passed (22%) 1.00 1.0 D + l.0 L (Alt Spans)
Moment (Ft-lbs) 12496@ 9' 11 5/8" 26114 Passed (48%) 1.00 1,0 D + 1.0 L (Aft Spans)
Live Load Defl. (In) 0.420 ~ 9' 11 1/16" 0.548 Passed (L/470) -1.0 D + 1.0 L (Alt Spans)
Total Load Defl. (In) 0,630 @ 9' 10 11/16" 0.822 Passed (L/313) .. 1.0 D + 1.0 L (Aft Spans)
• Deftectlcn criteria: U. (lJ360) and TL (l/240),
• Overhang deflection criteria: LL (2L/360) and TI. (2L/240).
• Top Edge Bracing (Lu): Top compression edge must be braced at 18' 3" olc based on loads applied, unless detailed otherwise.
• Bottom Edge Bracing (lu): Bottom compression edge must be braced at 18' 3" olc baied on loads applied, unless detailed otherwise.
• Member should be side-loaded from both sides of the member or braced to prevent rotation.
0 • Self Weight (PLF) 0 to 18' 3" NIA 20.8
l • Uniform (PV) 0 to l' 6" (Front) NIA 55.0 60.0 20.0 Default Load
2 • Uniform (Plf) l' 6" to 13' 7" (Front) NIA 110.0 233.0 20.0 Default Load
3 • Uniform (PLF) 13' 7" to 18' 3' (Front) NIA 79.0 315.0 Default LOild
PASSED
..
0
System : Floor
Member Type : Drop Beem
Building Use : Residential
Building Code : IOC 2018
Design Methodology : ASO
Weyerhaeuser wam,nts that tt,e sizing of its products will be in accordance with Weyerhaeuser product de.sign crib!r1a and pubfished design values. Weyerhaeuser expressly disclaims any other warTant1es
related to the software. Use of this software Is not Intended to circumvent the need for a design professional as dete,mlned by the aultlorlty having jurisdiction. The designer of record, bullder or framer 1s
responsible to assure that this calculation Is compatJbl!! with the 011erall Pfoject. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at
Weyerhaeuser fadPties are third-party cert1fled to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by JCC·ES under evaluatron reports ESR-1153 and ESR-1387
ar..d/or tested In accordance with applicable ASTM standards. For current code evaluatfon reperts, Weyerhaeuser product Hterature and Installation details refe( to
www.~ .ccm,lwoodp'oouct,,'documer>t-1'bra,y.
The product appllcatron, Input design loads, dimensions and support Information have been provided by ForteWEB Soltware o~ator
PorteWH Software Operator Job Notes
Paul Christenson
PCSO Engineering
(760) 207-1885 A
paul.pcscl@gmail.com
4/17/2020 6:12:41 PM UTC
ForteWEB v2.4, Engine: V8.0.1.S, Data: V?.3.2.0
File Name: Mast
Page 1 / 1
+
0
MEMBER REPORT
Floor Framing, (FB·2) Hdr Bm
1plece(s)31/2" x 91/2K 2.0E Parallam® PSL
PASSED
rJ
All locatlons are measured from the outside face of fen: support {or left cantilever end). All dimensions are horizontal.
Member Reaction (lbs)
Shear (lbs) 6235 C 1' 3"
Moment (Ft-lbs) 7825 @ l' 7"
Passed (97%)
13057 Passed (60%)
System : Floor
Member Twe : Crop Beam
Bulldlng lJ5e : Residential
Bulldtng Code : IBC 2018
Design Methodology : ASD
Live Load Oefl. (in) 0.031 ~ 2' 5/8" 0.117 Passed (l./999+) 1.0 D + 1.0 L All Spans
Total Load Defl. (in) 0.056@ 1' 7" 0.175 Passed {l,/755) 1.0 D + 1.0 L (All Spans)
• Deflection a1~a: Ll (L/360) and TL (L/240).
• Top Edoe &acing (Lu): Top compression edge must be braced at ◄' 2' o/c based on loads applied, unless detailed o!herwise.
• BottDm f.d9e Bracing (Lu): Bollom compression edge must be braced at◄' 2' o/c based on loads applied, unless detalled otherwise.
0 • Sett Weight (PI.F) 0 ID ◄' 2" N/A 10.◄
1 • Unlfonn (Plr) o to 1 • r (Front) N/A 15.0 60.0 Default Load
.2 -Unlfom> (PIF) J' 7" lo 4' .:i· (Front) NIA J60.0 80.0 20.0 Oefaultload
3 • Point (lb) l' 7" ( Front) N/A 368? ◄151 1S63 Default Load
4 • Point (lb) 2' g• (Front) N/A 965 2286 86 Default 1.Qod
Weyert,aeuser warrants that the si?lng d Its products wm be In accordance with Weyerhaeuser product design crlter1a and poblshed design values. Weyemaeuser expressly disclaims any other waminlles
related to the sottware. Use of this sottware 15 not Intended to cirrumvent the need for a design professional as determined by the authority having Jur1sdlctlon. The designer r:J record, builder o, frame-Is
responsible to assure ltlat this catculetlon Is compaUble With the overall project Accessor1es (Rim Board, BlockJng Panels and Squash Blocks) are not designed by this software. Products manUfadUred at
Weyerhaeuser radltles are thlrd1)artv czrtlfled to sustaloable roresnv standards. Weyerhaeuser Engineered Lumber Product5 have been evaluatlld by ICC-es unde-evafUatlon reports ESR-1153 and ESR-1387
and/or tested In accordance with applicable ASTM standards, For current code evauatlon reports, Weyerhaeuser product literature and lnstalletlon detalls mer to
www ,weyerhaeuser ,comjwoodproductS/document-llbrary.
The product application, Input design lollds, dlmenskw and support lrtormatkln have been prD'Jkled by ForteWE8 Sortware Operator
PorteWH .loftwaNI 0peratot loll Notes
Paul Chmtvnron
PCSO Engineering
(760) 207-1885 A
paul.pad@gmi,n.com Weytrhaewtt
4/17/2020 6:19:35 PM UTC
ForteWEB v2.4, Engine: VS.0.1.5, Data: V7.3.2.0
File Name: Mast
Page 1 / l
•:s· •,l.1i .. t ':.,..
Description:
PCSD Engineering
3529 Coastview Court
, Carlsbad, CA 92010
(760) 207-1885
-paul.pcsd@gmall.com
('FB-3) Flr Bm
Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
f1!1«terfafPro .e.rtlea. • ,-~
Analysls Method : Allowable Strength Design
Beam Bracing : Beam Is Fully Braced against lateral-torsional buckllng
Bending Axis : Major Axis Bending
' \'
Project Title:
Engineer:
Project ID:
Pro1ect Descr:
Fy : Steel Yield :
E: Modulus :
Span= 17.750 1't
7/
Pnrited: 21 APR 2020, 10:59AM
50.0 ksl
29,000.0 ksi
. App]tH'll-<> (ls , , . ,, __ .. , _ ~ ~ __ __ Service toads entered. Load Factors will be applied for calculations.
Beam self welAht calculated and added to loadinA
Uniform Load ; D = 0.2850, Lr= 0.020, L = 0.560 klfl, Tributary Width = 1.0 ft
... ·aES.IGN..SUMMARYi .• .. ~:~~ • ~. Maitinum~e·endirig·stress Ratio ;d -. ,
Section used for this span
Ma : Applied
Mn I Omega : Allowable
Load Combination Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total Deflect.Ion ..
. ·OveraifMa·xt.muni Det1,ct1ons
Load Comblnation Span
·tO-+L-+H
:'V~r:tlcal:R~i~ttons _,,; ~: : .. .-·, '
Load Combination Support 1
OveraH MAXimum 7.7
Overall MINimum 0.178
+0-+H 2.778
+0-+L-+H 7.748
+{}flr+H 2.955
+O+S-+H 2.778
+{}t().750Lr-+0.750L +H 6.639
-+0..0.750L-+0.750S-+H 6.505
-Ot-0.60W+H 2.778
+0-+0.750lr-+0.450W-+H 2.911
+0-+-0.750S-+0.450W+H 2.778
-+0.60O-+-0.60W-+0.60H 1.667
+0-+0.70E-+0.60H 2.778
+0-+0.750L ~-750S-+0.5250E+H 6,505
-+0.600~. 70E-+H 1.667
D Only 2.778
Lr Onty 0.178
LOnly 4.970
S Only
Max.•.• Def!
0.6892
Support 2
,7 8
0.178
2.778
7.748
2.955
2.778
6.639
6.505
2.778
2.911
2.778
1.667
2.778
6.505
1.667
2.778
0.178
4.970
-6:so1 : 1
W8x28
34.381 k-ft
67.864k-ft
+D-tl+H
Maximu·m Shear Stress Ratio = •••
Section used for this span
8.875ft
Span# 1
0,442 in Ratio=
0.000 in Ratio""
0.689 in Ratio =
0.000 In Ratio =
Location In Span
8.926
Va : Applied
Vn/Omega : Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
481 >=360
0 <360
309 >=180
0 <180
Load Combination
Support notation : Far left is #1
Desi n OK
·o.1s9 :· f
W8x28
7.748 k
45.942 k
+D-tl+H
0.000 ft
Span# 1
Max, '+' Defl Location in Span
0.0000 0.000
Values In KIPS
~,ru/f;,tTZJ'len.ron ';tnt ,D/~o
bJ'neerlnJ
3529 Coastvlew Ct -Carlsbad, CA 92010
Telephone (760) 207-1885-Email : paul.pcsd@gmail.com
5.0 Lateral Design & Analysis (Two-Story)
Wind: P = A Kzt I psJo
J,..= 1.00
Kzt = 1.0
PSJO = 26.6 psf
I= 1.0
P = 16.0 psf
(A.S 'E 7• I 6 -llqu•tion 28 S-1)
/fls 28 S.1-1)
<fls 26.SJ
tfig. z~ -1,
(tablo I ~-2)
Criteria
JOB 20-1 50
SHEET NO 'f; OF ___ _
CALCULATED BY PSC DATE 4/17/20
CHECK BY DATE
SCALE
s = s 1.054
F= 8 I.I
R = 6.50
----
(ASCE 7-16 • Eqn 12.8-2)
S1 = 0.382
Fv= 0.0
I = 1.00
Y = 0.083 •Wt• p (p -Redwidancy)
1st Story 2nd Story
Each Story Resists > 35% Base Shear: satisfied satisfied
W.ind Loads Any Shear Wall w/ (h/1)>1 .0 Is< 33% Story Force:
P = 16.0 psfx Trib Area
Roof Level
Direction:
Direction:
2nd Floor Level
Direction:
Direction:
Roof Weight
Roof Wt. =
Exterior Wall Wt =
Interior Wall Wt =
Ceiling Wt =
Floor Wei&ht
Diaphragm =
Exterior Wall Wt =
Interior Wall Wt =
1st Flr. Roof Wt. =
N /S = 16.0 psf X 281 sq. ft.=
E /W = 16.0 psf X 181 sq. ft.=
N /S = 16.0 psf X 475 sq. ft.=
E/W = 16.0 psf X 415 sq. ft.=
12.0 psf x 755 sq. ft.= 9060 lbs.
15.0 psf x 353 sq. ft .= 5295 lbs.
8.0 psf x 318 sq. ft.== 2544 lbs.
6.0 psf x 629 sq. ft.= 3774 lbs. ------Total Trib. WR = 20673 lbs.
15.0 psf X 967 sq. ft. = 14505 lbs.
15.0 psf X 1099 sq. ft. = 16485 lbs.
8.0 psf X 994 sq. ft. = 7952 lbs.
15.Q psf X 1447 sq. ft. = 21705 lbs.
Total Trib. WR = 60647 lbs.
Total Seismic Dead Load: Wt = 81320 lbs.
ASD Base Shear: V = 0.083 • Wt = 6769 lbs.
4485 lbs.
2889 lbs .
7581 lbs.
6623 lbs.
satisfied not satisfied
p = 1 1
tp',nJf;°,f"'rl.dm,,ron ~mt rD"!fc,
bJfntJerUtJ
JOB 20-150
SHEET NO ~ OF ___ _
CALCULATED BY PSC DATE 4/1 7/20
CHECK BY ____ DATE __ _
3529 Coastview Ct -Carlsbad, CA 92010 SCALE
Telephone (760) 207-1885 -Email: paul.pcsd gmall.com
Roof Dianhra~:
N / S Direction
V= 4485 lbs.
A= 755 sq. ft
f = V/A = p 5.94 psf
Floor Diaphragm:
N I s Direction
V = 7581 lbs.
A= 2414 sq. ft ,,.,..,...----,,-,-,---f P = V / A = 3 .14 psf ------Seismic Lateral Distribution
V = 6769 lbs. • p
Level h~ W71. hx
(lbs) (ft) (lbs-ft)
Roof 20673 18 372114
2nd Floor 60647 9 545823
917937
E/W Direction
V = 2889 lbs.
A= 755 sq. ft
f =VIA= p 3.83 psf
E/W
V=
Direction
6623 lbs. --------A= 2414 sq. ft ,,.,..,...---........ ---f P = V / A = 2. 7 4 psf ------
F V
k
Wx (hx )
lw-k (lbs) (lbs)
0.405 2744 2744
0.595 4025 6769
1.000 6769
,?5 ,u/"{;,tn'.d,m,1r,h ';n, t.ZH,.o
bfaeerurJ
3529 Coastview Ct-Carlsbad, CA 92010
JOB 20-150
SHEET NO fC, OF
CALCULATED BY PSC DAT-E--4-/-17_/_2_0_
CHECK BY ____ DATE __ _
SCALE
Telephone (760) 207-1885 -Email: paul.pcsd@gmail.com
5.2 Lateral Design & Analysis -1st Story Shear Walls
N IS E /W
Gridliae Length of Sheaxwalls Total Wall Ht. Type Gridline Length of Shearwalls Total Wall Ht. Type
2 10 10 8 B B 1 1 8 tJSW l
3 19 19.33 8 s C 5 5 8 A
0 ,f D 14 14 8 B
0 ( ,0 0 "J
0 i J 0 ~~
0 #D V/0! 0 #DI /01
0 #D ~/0! 0 #DI /0!
0 #D ~/0! 0 #D /0!
0 #~ V/0! 0 #DI /0!
0 #0 /0! 0 #D /0!
?,u/f;,tn'.deh.n,H ';In, 4., JOB 20-150
SHEET NO L\ OF
bfatltlrUff CALCULATED BY PSC DATE 4/17/20
CHECK BY DATE
p-,ut 6/u-ilUtt,W,.. ~ ~• 3529 Coastview Ct -Carlsbad, CA 92010 SCALE
z..,...,.,...., Telephone (760) 207-1885 -Email: paul.pcsd@gmail.com
5.2 Lateral Design & Analysis ( cont.)
Gridline CJ) 37 % 7581 X 0.37 2805 #)
2805 lbs. + 2242 ~ V = 10 ft. 421 plf
OTF "" 3365 lbs. HDU4
Gridline Q 30 % ( 7581 X 0.30 = 2274 #)
2274 lbs . + 987 & V = 19.33 ft. 169 plf ~)
OTF 1350 lbs.
? ,u_/f;,i"'r/.,t:,J.NJ'OH -;,.,, ~~O JOB 20-150
SHEET NO l1.. OF
bpee.rbtJ CALCULATED BY PSC DATE 4/17/20
CHECK BY DATE • ,,, 3529 Coastview Ct -Carlsbad, CA 92010 SCALE 'F'lfMf ~KJl'N .5An Pu,, Telephone (760) 207-1885 -Email: paul.pcsd@gmail.com z-, ..... ....,
5.2 Lateral Design & Analysis (cont.)
Oridline Cl) 8 % ( 6623 X 0,0 8 530 #)
530 lbs. + 433 ffi. V = ft. 963 plf
u,Jc.,I~ .. ~
Gridline G 8 % ( 6623 X 0.08 = 530 #)
530 lbs. + 422 ~ V = 5 ft. 190 plf
OTF 1523 lbs. -/ HDU2
Gridlinc ~ 50 % 6623 X 0.50 = 33 ]2 #)
3312 lbs.+ 1647 ~ V = 14 ft. 354 plf
OTF 2834 lbs. HDU2
SIMPSON STRONG-TIE COMPANY INC.
(800) 999-5099
5956 W. Las Positas Blvd,, Pleasanton, CA 94588.
www.strongtle.com
Job Name: Mast
Wall Name: Wall Line B
Application: 1st Story Wood Floor Systems
Design Criteria:
• 201B International Bldg Code
•Wind
* 2500 psi concrete
* ASO Design Shear = 963 lbs
* Floor Joist Depth = 1 O"
Selected Strong-Wall® Panel Solution:
Actual Shear & Drift Distribution:
Model
Actual Aiiowable •• ·r Actual / I Actual I Drift
Shear Shear : Allow Drift Limit
1 (lbs) (lbs) j Shear : (In) 1 (In)
--· .. ---·------------· ---.J .. •--·-""•-1-·----·----·-------------4•--·--~J.---------~--.. ---·
WSW18x8 ,! 963 S 1330 OK ; 0.72 1 0.33 ,. 0.53
··---------.. ____ ---·---------·-....... -----~ -·----·------... ,_ ._ .... _,., ___ _L_ ---·-----~---
Notes:
1. Strong-Wall Wood Shearwalls have been evaluated to the 2018 IBC/IRC.
See www.strongtle.com for additional design and installation infom,ation.
2. Allowable shear, drift and anchor tension values may be interpolated for intermediate height or vertical loads.
3. Drifts at lower design shear may be linearly reduced.
SIMPSON
Stro1igl,.Tie
4. Allowable vertical load denotes the total maximum vertical load permitted on the panel acting in combination with the allowable shear
loads.
5. Panels may be trimmed to a minimum height of 7 4 1 /2".
6. For panels 74½" -78" tall, use the values for a 78" tall panel.
7. Anchor templates are recommended for proper anchor bolt placement. and are required in some Jurisdictions.
8. Minimum standard strength anchor bolts are required unless a lower strength grade Is Justified by the registered design professional.
Disclaimer:
It Is the ~s ,esponslbllity to wtrify product 5Ultabilily Uff<NJI' appbbttt bu/ld/ng codtr.;. In ord«" to verify code //$ted 11ppllcstion5 ph,ffe refer to !he
appropriate product code reports at www.strongUe.com or contact Simpson Strong• Tie Company Inc. at 1-800-999-5099.
Page 1 of 3
SIMPSON STRONG-TIE COMPANY INC.
(800) 999-5099 SIMPSON
5956 W. Las Posltss Blvd., Pleasanton, CA 94588.
www.strongtle.com Strong-Tie
GD -------------------------------·-·---------------------
Job Name: Mast
WaU Name: Wall Line B
Application: 1st Story Wood Floor Systems
Design Criteria:
• Stemwall • Perimeter
"2018 International Bldg Code
*Wind
• 2500 psi concrete
Anchor Solution Details:
Stemwall Installation Stemwall Extension Installation
WSW·A8
+. r,/ ' . . ' • n,ii,, for : :
_ a· Mlloirnom curo/otemwol I
WSW•AB'~i4--· IIW ..-. \IW• .;;::.::I ~ ... ··• ·W· ·-•••
St9111wall Secllon View
' ' r-----____ J________ . .. --I -"I
: ----1 T
: • \frW
l --·-•·•---i \~
l i.;w 1
: I I • , _______ -------------'... .. _, .....
~-IIW '4•\\W .,
Foottnp Plan
211· ♦-
s,..,.,,,..
H<Ngr4 •
r,1/SW·AS \, •
W..W-11SR \, ~
2\l'·do)
T .
s· min to,
WiN/' /IS '4 • I &· rm1or -
WSW,ABI
Sactton at Stemwall
WSW-AB and WSW-fiSR
Extanllon Awllcallon
-A8
Anchor Solution Assuming Cracked Concrete Design: Anchor Solution Assuming Uncracked Concrete Design:
Notes:
1. Anchorage designs conform to ACI 318--14 and 318-11 Appendix D with no supplementary reinforcement for
cracked and uncracked concrete as noted.
2. Anchorage strength Indicates required grade of anchor bolt. Standard (ASTM F1554 grade 36)
or High Strength (HS)(ASTM A449).
3. Wind Includes Seismic Design Category A and B and detached 1 and 2 family dwellings In SOC C.
4. Foundation dimensions are for anchorage only. Foundation design (size and.reinforcement) by others.
The registered design professional may specify alternate embedment, footing size or anchor bolt.
Page 2 of 3
~ ,ru/f;°,tn,de.11.ro.11 ~llll 2fz,'!f"
£JV1een.11J
JOB 20-150 ,< OF \L
PSC DATE 4/17/20
DATE
SHEET NO
CALCULATED BY
CHECK BY
SCALE -------3529 Coastview Ct -Carlsbad, CA 92010
Telephone (760) 207-1885 -Email: paul.pcsd@gmail.com
6.0 FOUNDATION DESIGN
6.1 CONTINUOUS FOOTING
w = 1125 plf
width = ....!,g1_ plf
1500 psf
0. 75 ft (MIN.) => 9 INCHES (MIN.)
( E) 12 11 WIDE CONTIN. FTG W/
1 -# 4 TOP AND BOTTOM & EMBED.
12 11 INTO UNDISTURBED SOIL (MIN.)
6.2 MAX POINT LOAD ON FOOTING
p alJ = 1500 ill E_ * ~
12 12
P Bil = 4500 lbs
I I
6.3 PAD DESIGN
SIZE LOAD
ASBP = 1500 psf
Pl 42 " SQUARE x 12 "THK
WI 5 -# 4 EACH WAY
Pmax = 1500 • 4 2
Pmax = 18375 lbs
.
STORM WATER COMPLIANCE FORM
I TIER 1 CONSTRUCTION SWPPP CB ri;i Z a5 -e50lP B
E-29 SW -
STORM WATER POLLUTION PREVENTION NOTES BEST MANAGEMENT PRACTICES (BMP) SELECTION TABLE
Erosion Control Sediment Control BMPs Tracking Non-Storm Water Waste Management and Materials
1. ALL NECESSARY EQUIPMENT AND MATERIALS SHALL BE BMPs Control BMPs Management BMPs Pollution Control BMPs
AVAILABLE ON SITE TO FACILITATE RAPID INSTALLATION C:
OF EROSION AND SEDIMENT CONTROL BMPs WHEN RAIN C: C: 0 ...... ..... 0 0 :;::; C: C: -0 :;:; :;::; Ol C (I) -0 (I) -0 IS EMINENT. {f) C: u u C: C: O'> E C: E C: -C :::, 2 0 '5 ·c .Q-C C C .... .... (I) (I) E Cl> :;:; .... >, THE OWNER/CONTRACTOR SHALL RESTORE ALL EROSION ::!: "O (I) en .... .... ...., C: '-:::, Ol ..... Q) 2. C: Q) .... .5 (I) £ !/) {f) {f) 0 ·c er .... 0 C: Cl) -en C 0 C. Q) ·c C: {f) C: > .... w -~ C: 0 0 Cl) Best Management Practice"' ~ .5 0 ID C. 0 .... c:., Q) :;::; 3=_, CONTROL DEVICES TO WORKING ORDER TO THE SATISFACTION a, ,_ 0 Q) (I) Q) C ..., 0-+-' .c Cl) :e: .... Q) 0 C u .... c..> ...,
-0 Q) C: (I) C: C 3= C: C: I-E Q) O'> ·e C:
(J) -0 (J) ~ (J) :::E
OF THE CITY INSPECTOR AFTER EACH RUN-OFF PRODUCING (BMP) Description ➔ Cl) u (I) en ·a (I) (/l O'> (D o> C C a ::::> ~ ..... Cl) !/) (I) (I) .!!! ~ Q) ...... C 0 :e: C: -g~ -0 >, 0 Cl) C: C: 0 [fl E :::, E Q) E :;:; :::, .... u C: Cl 0 ID en ·-Ol o.2 u Q) Co Ol .!!! (I)
RAINFALL. :::E Cl o> Cl C: Q) c::: ..., E 0 ..... N Ul ~ 0 u en:;:; (I) _!!!.5 :§ ~ 0 ·o.. i...-3= Cl) 0 (I) ..., Cl)
X 0 Q) Q) .J:J Eg = (J) =:e: :u~ J5 ·;:: Cl. e en -0 o> (I) O> Cl) Q) LL E ..:,c (I) :::, C: 0 UC: .... C ..:,c so t;c .... -0 .c C: u ,_ "O ·-(I) ·--0 C Q) .... (I) u i=C: "O 0 > (I) :::, ......... ..0 .... .J:J C .... u ·s; t ·-0 0 0 -·-C. :;s Cl) Q) C: ...., ..., 0 ..... 0 ·;; § NC cc 3. THE OWNER/CONTRACTOR SHALL INSTALL ADDITIONAL EROSION .... 0 0 ..... 0 .... u 00 Co> .s 0 co .c Q) Cl) ~ 0 .... Q) .c ..0 .... ..... 0 0 ......... _. C ;s::ct C C. 0 Cl>-o..., 0 -a. 0 co oo c:., WO u; vi en <.> i.i: c:., tn> en en a.. (/)_ tn c::: Cl.0 a.. >u :.!: tn :.!: en (/)(.) (/) :::E :c :::E U:.!:
CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY
INSPECTOR DUE TO INCOMPLETE GRADING OPERATIONS OR CASQA Designation ➔ r--00 (7) ....-I'") -.I-IO r--co 0 N ~ n r--co ...... N l") '<r LO co 00 'T ....-co ....-'T I I I I I I I I I I I I I I I I I I I I I I I UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE. (.) c..> c..> (.) w w w w w w w w g; ~ tn Cl) (/) Cl) i i i i i i i Construction Activity w w w w (/) (/) en en (/) (/) (/) en z z z z
4. ALL REMOVABLE PROTECTIVE DEVICES SHALL BE IN PLACE Grading/Soil Disturbance
AT THE END OF EACH WORKING DAY WHEN THE FIVE (5) • Trenching/Excavation >< X'
DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PECENT • Stockoilina x x
( 40%). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER Drillina/Borina
EACH RAINFALL. Concrete/ Asphalt Sawcutting
5. ALL GRAVEL BAGS SHALL CONTAIN 3/4 INCH MINIMUM Concrete Flatwork
Paving AGGREGATE. Conduit/Pipe Installation
6. ADEQUATE EROSION AND SEDIMENT CONTROL AND PERIMETER • Stucco/Mortar Work ><
PROTECTION BEST MANAGEMENT PRACTICE MEASURES MUST • Waste Disposal ')<,_
BE INSTALLED AND MAINTAINED. Staging/Lay Down Area
Eauipment Maintenance and Fuelina
7. THE CITY INSPECTOR SHALL HA VE THE AUTHORITY TO ALTER Hazardous Substance Use/Storaae
THIS PLAN DURING OR BEFORE CONSTRUCTION AS NEEDED Dewatering
TO ENSURE COMPLIANCE WITH CITY STORM WATER QUALITY Site Access Across Dirt
REGULATIONS. Other (list):
Instructions: 1. Check the box to the left of all applicable construction activity (first column) expected to occur during construction.
2. Located along the to~ of the BMP Table is a list of BMP's with it's corresfionding California Stormwater Quality Association (CASQA) designation number. Choose one or more BMPs you in end to use during construction from the list. Check he box where the chosen activity row intersects with the BMP column.
3. Refer to the CASQA construction handbook for information and details of the chosen BMPs and how to apply them to th e project.
OWNER'S CERTIFICATE:
I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT
BEST MANAGEMENT PRACTICES {BMPS) DURING CONSTRUCTION PROJECT INFORMATION ACTIVITIES TO lHE MAXIMUM EXTENT PRACTICABLE TO AVOID
lHE MOBIUZA TION OF POLLUTANTS SUCH AS SEDIMENT AND TO SHOW THE LOCATIONS OF ALL CHOSEN BMPs ABOVE Site Address:\\ l p(Z) L-A ~\<.~ ~ Ll-,...J.
AVOID lHE EXPOSURE Of STORM WATER TO CONSTRUCTION
RELATED POLLUTANTS; AND (2) ADHERE TO, AND AT ALL TIMES, ON THE PROJECTS SITE PLAN/EROSION CONTROL PLAN. Assessor's Parcel Number: 2 d>5 -45("1-c;t?L o
COMPLY Willi lHIS CITY APPROVED TIER 1 CONSTRUCTION SWPPP SEE THE REVERSE SIDE OF THIS SHEET FOR A SAMPLE lHROUGHOUT lHE DURA llON OF lHE CONSTRUCTION ACTIVITIES EROSION CONTROL PLAN. Emergency Contact:
UNTIL lHE CONSTRUCTION WORK IS COMPLETE AND APPROVED Name:-ALE:.1'...IA 0-::P-$\O BY lHE CITY OF CARLSBAD.
-ALE.r--.....JA. BL..AScO 24 Hour Phone: ~ D. -==l-2 q . ~ v 5
OWNER(S)~.:_, ~7:::-, ~
o-::i-/3c> Construction Threat to Storm Water Quality
r_, { ~-====---. (Check Box)
OWNER{:>J~ ;> -~ NI nnn11 ... , _;~NA TlJRE) DATE 0 MEDIUM ~ow
✓
E-29 Page 1 of 1 REV 02/16
C cityof
Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
B-50
Development Services
Building Division
1635 Faraday Avenue
(760) 602-2719
www.carlsbadca.gov
This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance
requirements apply to their projects. Unless none of the requirements apply, the completed checklist must be
included in the building permit application. It may be necessary to supplement the completed checklist with
supporting materials, calculations or certifications, to demonstrate full compliance with CAP ordinance
requirements. For example, projects that propose or require a performance approach to comply with energy-
related measures will need to attach to this checklist separate calculations and documentation as specified by
the ordinances.
A If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required
by ordinance, an explanation must be provided to the satisfaction of the Building Official.
A Details on CAP ordinance requirements are available on the city's website.
Appllcatlon Information
Project Name/Building
Permit No.: MAST ADDITION / REMODEL BP No.: CJB\Q.o4?);lt,,.. 6 Z(g8' ------------------Property Address/APN: 1166 LARKSPUR LANE, CARLSBAD, CA 92008 / 205-430-06-00
Applicant Name/Co.: ALENA BROOKS BLASIO / B.A. WORTHING, INC.
Applicant Address: 5145 AVENIDA ENCINAS, SUITE I, CARLSBAD, CA 92008
Contact Phone: 760-729-3965 Contact Email: ADMIN@THISISBAWINC.COM
Contact information of person completing this checklist (if different than above):
Name:
Company
name/address:
B-50
Contact Phone:
Contact Email:
Page 1 of 3 Revised 04/19
City of Carlsbad Climate Action Plan Consistency Checklist
Use the table below to determine which sections of the Ordinance Compliance checklist are applicable to your project.
For residential alterations and additions to existing buildings, contact the building counter for the building permit valuation.
Building Permit Valuation (BPV) $ ___________ _
Construction Type I Complete Sectlon(s) I Notes:
D Residential
D New construction 1A
i2'.I Alterations: □ exempt
&1 BPV 2: $60,000
□ Electrical service panel upgrade
1A
1A
1-2 family dwellings and townhouses with attached garages
only
□ BPV 2: $200,000 1A
Multi-family dwellings only where interior finishes are removed
and significant site work and upgrades to structural and
mechanical, electrical, and/or plumbing systems are proposed
D Nonresidential
D New construction 1B and 2
D Alterations 2
1. Electric Vehicle Charging
A D Residential New construction and major alterations (or electric panel upgrade)*
Please refer to Carlsbad Ordinance CS-349 when completing this section.
□ One and two-family residential dwelling or townhouse with attached garage:
D One EVSE ready parking space required □ Exception :
D Multi-family residential· □ Exception •
Total Parking Spaces EVSE Spaces
Proposed Capable I Ready I
I I
Calculations: Total EVSE spaces= .10 x Total parking (rounded up to nearest whole number)
EVSE Installed = Total EVSE Spaces x .50 (rounded up to nearest whole number)
EVSE other= Total EVSE spaces-EVSE Installed
(EVSE other may be "Capable," "Ready" or "Installed.")
Installed I Total
I
*Major alterations are: (1) for one and two-family dwellings and townhouses with attached garages, alterations have a building permit valuation ~ $60,000 or
include an electrical service panel upgrade; (2) for multifamily dwellings (three units or more without attached garages), alterations have a building permit valuation
~ $200,000, interior finishes are removed and significant site work and upgrades to structural and mechanical, electrical, and/or plumbing systems are proposed.
B D Nonresldentlal new construction (Includes hotels/motels) □ Exception •
Total Parking Spaces EVSE Spaces
Proposed Capable I Ready I Installed I Total
I I I
Calculation: Refer to the table below:
Total Number of Parking Spaces provided Number of required EV Spaces Number of required EVSE Installed Spaces
□ 0-9 1 1
□ 10-25 2 1
□ 26-50 4 2
□ 51-75 6 3
□ 76-100 9 5
□ 101-150 12 6
□ 151-200 17 9
□ 201 and over 1 0 percent of total 50 percent of ReQuired EV Spaces
Updated 4/12/2019 2
City of Carlsbad Climate Action Plan Consistency Checklist
2. D Transportation Demand Management (TDM)
A. List each proposed nonresidential use and gross floor area (GFA) allocated to each use.
B. Employee ADT/1,000 square feet is selected from the table below.
Use GFA Employee ADT for first Employee ADT for each
1,000 S.F. subsequent 1,000 S.F.
Total
If total employee ADT is greater than or equal to 110 employee ADT, a TOM plan is required.
TOM plan required: Yes D No D
Updated 4/12/2019
Employee ADT Estimation for Various Commercial Uses
Office (all)2 20
Restaurant 11
Retail3 8
Industrial 4
Manufacturing 4
Warehousin 4
1 Unless otherwise noted, rates estimated from /TE Trip
Generation Manual, 1CJlhEdition
20
11
4.5
3.5
3
1
2 For all office uses, use SANDAG rate of 20 ADT/1,000 sf to
calculate employee ADT
a Retail uses include shopping center, variety store, supermarket,
gyms, pharmacy, etc.
Other commercial uses may be subject to special
consideration
Sample calculations:
Office: 20,450 sf
1. 20,450 sf/ 1000 x 20 = 409 Employee ADT
Retail: 9,334 sf
1. First 1,000 sf= 8 ADT
2. 9,334 sf -1,000 sf= 8,334 sf
3. 8 334 sf/ 1,000 x 4.5 + 8 = 46 Em lo ee ADT
Total Employee ADT
3