HomeMy WebLinkAbout2052 CORTE DEL NOGAL; ; AS080172; Permit5/9/24, 2:44 PM AS080172 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address:
2052 CORTE DEL
NOGAL
Permit Type: SPRINK
Parcel No: 2130610600
Lot#: 0
Reference No.:
Permit No: AS080172
Status: ISSUED
Applied 10/29/2008
Approved: 11/5/2008
Issued: 11/5/2008
PC#: Inspector:
Project Title: TRANSWORLD MEDIA (MEZZANINE) Tl FIRE SPRINKLER PLAN
CHECK & INSPECTIONS
Applicant: Owner:
AAA FIRE SPRINKLERS
20942 JAPATUL RD
ALPINE CA
619-445-9898
about:blank
Fees($)
130
Add'I Fees ($)
0
2052 CD NL LC
C/O CRUZAN MONROE INVESTMENTS
LLC
12275 EL CAMINO REAL #100
SAN DIEGO CA
Total($)
130
Balance($)
0
1 /1
Hydraulic Design Information Sheet
Name: TRANSWORLD MEDIA MEZZANINE Date: 10-27-08
Location: 2052 CORTE DEL NOGAL, CARLSBAD
Building: EXISTING System No. .:..l ______ _
Contractor: AAA FIRE SPRINKLERS Contract No.
Calculated By: EFP Drawing No. 1 Construction: '0..,...-C.,..o_mb_ustJ.-:-:-.b,,.-le--... □---N,-on--C-,-om_b_ustJ.---,,-.b-le _____ Ceiling Height _8 _____ F_t_.
SYSTEM DESIGN
l2S.] NFPA 13: l2S.] Light Huard Ordinary Hazard Group U 1U2U 3 U Extra Hazard 0 NFPA231 0 NFPA231C: Figure: Curve: D Other (Specify)
□Specific Ruling Made By Date
Area of Sprinkler Operation 900SQFT SYEm)TEe
Density .10 IZI Wet 0 Dry D Deluge D Pre-Action
Area Per Sprinkler 225 SQ FT MAX Sprinkler or Nozzle
Hose Allowance GPM: Inside 0 Make TYCO Model TY-FRB
Hose Allowance GPM: Outside 100 Size ½" K-Factor: 5.6
Rack Sorinkler Allowance NA Temnerature Ratinit ~OR
CALCULATION SUMMARY
GPM Required _2_0_1.__,~'-'------PSI Required 47.o+ At Base of Riser
"C" Factor Used: Overhead 120 Unde d 150
WATER SUPPLY
W1ter Flow Test Pump Data Tanlc or Reservoir
Date& Time 10-14-08 Rated Capacity Capacity
Static PSI 120 AtPSI Elevation
Residual PSI 115 Elevation
GPMF!owing 1400 Well
Elevation 0 ProofFlow GPM
Location SITE
Source of Information CARLSBAD WATER AND AAA FIRE FLOW TEST
COMMODITY STORAGE
Commodity OFFICE Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized %Rack
Rack D SingleRow 0 Conventional Pallet 0 Automatic Storage D Encapsulated D DoubleRow 0 Slave Pallet 0 Solid Shelving D Non-Encapsulated D Multiple Row D 0pen
Flue Spacing In Inches Clearance From TQI! Qf Storag@to Ceiling
Longitudinal Transverse Ft. In.
Horizontal Barriers Provided
TRANSWORLD MEZZANINE ADDITION .10/900
260
240
230
220
2
200
190
1
170
1
I
I
I
I
80
1
ii 1
I!:. 1 !
&O
40
90
io I ! 10.
1 00
90
ao
10
80
~
=i ;m
•
-t,
J
O 200 400 ~ ---800
System Demand ..
Sprlnlcl•r D••and 50.27 PSI
flddl'tlon•l F'lowl
HOH •"t Sourc•
To"t•l D••and 50. 27 PSI
·---1000 ----1200
I 201.31 8PN o.oo 8PN
100.00 8PN
I 301.31 GPN
•
----1400 war Flow (GPM)
Sigma Dynemloa Corporedon
7700 Supply / Demand Greph
' Margin L-
Pr•H,...• 57.47 PSI L-now 5252.17 GPN
s
N 1.1111 ----1600 ----1800 2000
Water Supply ..
S"t•"tlc 108.00 PSI
R•sldu•l 103.50 PSI
El•Y•"tlon O.OO PSI
I 1400.00 GPN
SUBMITTAL SERIAL NO:2932HY7
TRANSWORLD MEZZANINE ADDITION .10/900
FLOW TEST RESULTS
Water Supply
STATIC 108.00 PSI
RESIDUAL 103.50 PSI @ 1400.00 GPM
CITY PRESSURE AVAILABLE AT 301.3
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR --------
100 22.76 18.20 5.60
101 21.28 18.20 5.60
102 20.38 18.20 5.60
103 19.95 18.20 5.60
104 19.84 18.20 5.60
105 22 .17 18.20 5.60
106 19.95 18.20 5.60
107 18.58 18.20 5.60
108 18.20 18.20 5.60
109 18.20 18.20 5.60
TOTAL WATER REQUIRED FOR SYSTEM
OUTSIDE HOSE STREAMS AT 0
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 10 TO 12
GPM 107.74 PSI
PRESSURE --------
16.52
14.43
13.24
12.69
12.55
15.68
12.69
11.01
10.57
10.56
201.31 GPM
100.00 GPM
301.31 GPM
50.27 PSI
0.00 PSI
18.04 FPS
10-27-2008 PAGE 1
SUBMITTAL SERIAL N0:2932HY7 10-27-2008 PAGE 2
TRANSWORLD MEZZANINE ADDITION .10/900
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
21 109 1.080 L a.so C=120 PT 10.56 (109)
Q 18.20 F=T,E F 11. 00 PE 0.00
AO T 11.50 0.0948 PF 1.09
20 21 1.536 L 3.00 C=120 PT 11.65 21)
Q 18.20 F=O F 0.00 PE 0.00
BN T 3.00 0.0171 PF 0.05
PT 11.70 20) ------------------20 108 1.080 L 1.00 C=120 PT 10.57 (108)
Q 18.20 F=T,E F 11.00 PE o.oo
AO T 12.00 0.0949 PF 1.14
19 20DQ 18.20 1.536 L 8.00 C=120 PT 11.71 ( 20)
Q 36.40 F=O F 0.00 PE 0.00
BN T 8.00 0.0615 PF 0.49
PT 12.20 ( 19) ------------------19 107 1.080 L 1.00 C=120 PT 11.01 (107)
Q 18.58 F=T,E F 11.00 PE 0.00
AO T 12.00 0.0986 PF 1.18
18 19DQ 36.40 1.536 L 14.00 C=120 PT 12.19 ( 19)
Q 54.99 F=O F 0.00 PE 0.00
BN T 14.00 0.1320 PF 1.85
PT 14.04 18) ------------------18 106 1.080 L 1.00 C=120 PT 12.69 (106)
Q 19.95 F=T,E F 11.00 PE o.oo
AO T 12.00 0.1124 PF 1.35
17 18DQ 54.99 1.536 L 14.00 C=120 PT 14.04 18)
Q 74.94 F=O F 0.00 PE o.oo
BN T 14.00 0.2340 PF 3.28
PT 17.32 ( 17) ------------------17 105 1.080 L 1.00 C=120 PT 15.68 (105)
Q 22.17 F=T,E F 11.00 PE 0.00
AO T 12.00 0.1367 PF 1.64
11 17DQ 74.94 1.536 L 17.00 C=120 PT 17.32 ( 17)
Q 97.11 F=T F 8.90 PE o.oo
BN T 25.90 0.3779 PF 9.79
PT 27.11 11) ------------------16 104 1.080 L 2.50 C=120 PT 12.55 (104)
Q 19.84 F=T,E F 11.00 PE 0.00
AO T 13.50 0.1112 PF 1.50
SUBMITTAL SERIAL NO:2932HY7 10-27-2008 PAGE 3
TRANSWORLD MEZZANINE ADDITION .10/900
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
15 16 1.536 L 7.50 C=120 PT 14.05 ( 16)
Q 19.84 F=0 F 0.00 PE 0.00
BN T 7.50 0.0200 PF 0.15
PT 14.20 15)
------------------15 103 1.080 L 2.50 C=120 PT 12.69 (103)
Q 19.95 F=T,E F 11.00 PE 0.00
AO T 13.50 0.1124 PF 1.52
14 15DQ 19.84 1.536 L 8.50 C=120 PT 14 .21 15)
Q 39.78 F=0 F 0.00 PE 0.00
BN T 8.50 0.0725 PF 0.62
PT 14.83 14)
------------------14 102 1.080 L 2.50 C=120 PT 13.24 (102)
Q 20.38 F=T,E F 11.00 PE 0.00
AO T 13.50 0.1169 PF 1.58
13 14DQ 39.78 1.536 L 8.50 C=120 PT 14.82 14)
Q 60.16 F=0 F 0.00 PE 0.00
BN T 8.50 0.1558 PF 1.32
PT 16.14 ( 13)
------------------13 101 1.080 L 2.50 C=120 PT 14.43 (101)
Q 21.28 F=T,E F 11.00 PE 0.00
AO T 13.50 0.1266 PF 1.71
12 13DQ 60.16 1.536 L 8.50 C=120 PT 16.14 ( 13)
Q 81.44 F=0 F 0.00 PE 0.00
BN T 8.50 0.2729 PF 2.32
PT 18.46 12)
------------------12 100 1.080 L 2.50 C=120 PT 16.52 (100)
Q 22.76 F=T,E F 11.00 PE 0.00
AO T 13.50 0.1435 PF 1.94
10 12DQ 81.44 1.536 L 13.00 C=120 PT 18.46 12)
Q 104.20 F=T F 8.90 PE o.oo
BN T 21.90 0.4305 PF 9.43
PT 27.89 10)
------------------10 11 2.203 L 12.00 C=120 PT 27.11 ( 11)
Q 97.11 F=0 F 0.00 PE 0.00
FM2 T 12.00 0.0653 PF 0.78
9 l0DQ 104.20 2.203 L 25.00 C=120 PT 27.89 ( 10)
Q 201.31 F=0 F 0.00 PE 0.00
FM2 T 25.00 0.2514 PF 6.28
SUBMITTAL SERIAL N0:2932HY7 10-27-2008 PAGE 4
TRANSWORLD MEZZANINE ADDITION .10/900
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
8 9 2.203 L 15.00 C=l20 PT 34.17 9)
Q 201.31 F=2E F 9.60 PE -5.20
FM2 T 24.60 0.2514 PF 6.18
7 8 3.314 L 8.00 C=l20 PT 35.15 8)
Q 201.31 F=T F 18.90 PE 0.00
FM T 26.90 0.0344 PF 0.93
6 7 6.357 L 32.00 C=l20 PT 36.08 7)
Q 201.31 F=T F 24.80 PE 0.00
FM T 56.80 0.0014 PF 0.08
1 6 6.357 L 25.00 C=l20 PT 36.16 6)
Q 201.31 F=E F 9.90 PE 10.83
FR T 34.90 0.0014 PF 0.05
0 1 6.210 L 110.00 C=l50 PT 47.04 1)
Q 201.31 F=T,GV/2EE,E F 60.34 PE 3.03
UN T 170.34 0.0011 PF 0.19
COMMENT: 3 PSI LOSS FOR HERSEY DET. CHECK SHOWN AS ELEVATION
PT 50.26 ( 0)
Oct 09 08 09:37a AAA Fire Sprinklers 16194454052
Flow Test Record
Test Hydrant
Hydrant ID No. _____ Size Main ____ _
Static ............. l 'LO
Residual......... \ \?
Pressure Drop.. "::> (PDI 1) ..... K factor for PDI 1 __ _
Flow Hydrant(s)
Hydrant I location ____________________ _
Hydrant 2 location ____________________ _
Hydrant 3 location ____________________ _
Hydrant I Pitot. __ .l.uOue·----·PSI GPM: \L\CO
Hydrant 2 Pitel PSI GPM: ___ _
Hydrant 3 Pitot PSI GPM: ___ _
Total: ----
(Ql)
Calculated test and flow data• 0 xPD2 k =Q2
PDl*k
Static: .................... ___ _
Desired Residual.. ..... _20
Size of Orifice ___ _
Size of Orifice ----Size of Orifice '-----
Pressure Drop (PD 2) .. ____ ................................ .K factor PD 2: _____ _
____ x ____ divided by _____ equals. ____ GPM at 20 psi residual
Ql PD2 k PD 1 k Q2
p.2
Aoo3ol1-.2-
Comments:. ____________________________ _
Test conducted for: T1.,;rl'S \,\JC:{\d Med,a
7-c,v:J-Z. C.c·t\ e. De.\ N~cs\
Conducted by: Ab.A, £ire, '.:::r:,v:: .rvL\e{S '
Date: 1.Dj B{ 1,ctf3 Time:_9.!..:-:.J.l.,.U:___ __ AAA FIRE SPRINKLERS
20942 JAPATUL RD.
ALPINE CA 91801
Oct 09 08 09:37a AAA Fire Sprinklers 16194454052
Carlsbad Municil)al Water District
Potable Water Discharge
Event Report
Date:
Location: 2D
Type of Event:
Dewatering Water Mains
Note: Includes flow testing and flushing
Dewatering Reservoins
Unscheduled Water Discharge
Clear flow path of debris, surface
contaminants and/or hazardous
materials. Do not remove native
vegetation.
Erosion control, i.e.
sandbags, silt fencing, hay bales,
gravel bags, decreasing the velocity
of discharge water.
Upon completlon of dewatering, ensure
that the flow path ls free of all
temporary erosion prevention materials.
Upon completion of dewatering, ensure
that any sediment or silted areas are
cleared.
Initial
Estimated Discharge Flow:
Start Time
End Time
Pre-Dechlorination Residual:
.Ust-Dechlorinatlon Residual:
./(less than 0.1 mg/L) ·
pH within limits of 6.0 and 9.0
p.3
Water Sampling Performed by: ------------~-----
Comments: ~----------------------------
Submitted by: -----------Revl
(Name & Date)
{/