HomeMy WebLinkAbout2623 GATEWAY RD; 103; CBC2022-0226; PermitBuilding Permit Finaled
C cityof
Carlsbad
Commercial Permit
Print Date: 05/29/2024
Job Address: 2623 GATEWAY RD, # 103, CARLSBAD, CA 92009-1751
Permit No:
Status:
CBC2022-0226
Closed -Finaled
Permit Type: BLDG-Commercial Work Class: Tenant Improvement
Parcel#: 2131910900 Track#:
Valuation: $79,087.84 Lot#:
Occupancy Group: B
#of Dwelling Units:
Project#:
Plan#:
Bedrooms:
Bathrooms:
Construction Type:VB
Orig. Plan Check #:
Occupant Load: 12 Plan Check#:
Code Edition: 2019
Sprin~ed: Yes
Project Title:
Description: COASTAL MEDICAL AESTHETICS: COM-Tl (1,222 SF) NON-STRUCTURAL
Property Owner:
REGENCY BRESSI LLC
100 WILSHIRE BLVD, # STE 700
SANTA MONICA, CA 90401
(949) 398-8750
FEE
BUILDING PLAN CHECK
BUILDING PLAN REVIEW -MINOR PROJECTS (LOE)
BUILDING PLAN REVIEW -MINOR PROJECTS (PLN)
CERTIFICATE OF OCCUPANCY
COMM/IND Tl -NON-STRUCTURAL
SB1473 -GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION -COMMERCIAL (SMIP)
Total Fees: $1,698.82 Total Payments To Date: $1,698.82
Applied: 06/23/2022
Issued: 10/13/2022
Finaled Close Out: 05/29/2024
Final Inspection: 02/07/2023
INSPECTOR: Dreibelbis, Peter
Kersch, Tim
Contractor:
GRACE BUILDERS INC
8139 CENTER ST, # STE 101
LA MESA, CA 91942-2915
(619) 462-2183
Balance Due:
AMOUNT
$515.06
$194.00
$98.00
$16.00
$849.62
$4.00
$22.14
$0.00
Please take NOTICE that approval of your project includes t he "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY t o water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
{ City of
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Plan Check e_ec"2.o-z.~-c::,"2.:
Est. Value j 71 09,,. •1
PC Deposit .i., S-1 :ft O(p
Date t.,,-'2."3 -l,.o ~~
Job Address__,;,_2.irJ=~----=~.;..;;;...;;.~-+---'~::.......----Suite: / 0 "3 APN: .Z \ '3 -I jl -Q'I -00
\@. Ae4:h-et~ot #: ___ Year Built: ~l ~ P.o f 'J-Tenant Name#:
Year Built: __ _ Occupancy: ::f:> Construction Type:~ Fire sprinklers0'ESONO
BRIEF DESCRIPTION OF WORK: fl v>(~tct)(M7 -I dco~
0 Addition/New: ___________ New SF and Use, _________ New SF and Use
______ SF Deck, SF Patio Cover, SF Other (Specify) ___ _
~Tenant Improvement: 12.&!L SF, Existing Use: :JZ,eta.i,t Proposed Use~el. otf\~
____ SF, Existing Use: Proposed Use: _____ _
D Pool/Spa: ____ SF Additional Gas or Electrical Features? __________ _
D Solar: __ KW, ___ Modules, Mounted:0Roof0Ground RECEIVED
D Reroof=----------------------J-ll~-1 .... 2 .... 2 .... 2...,0 ___ 22 __
□ Plumbing/Mechanical/Electrical CITY Q;-C ARLSBAD
Oother: _________________________ B-t1Urttt\L=-ieO,,...l-"'~'r-~,~P_I_J_.s_1_o_N
City: _______ State: ___ Zip: ___ --1
Phone: _______________ --1
Email=---------,,,---.,,.....,,-------1
Architect State License: _-,.~....&.,;;......1. ____ _.:
mail: i"
SLB License#: 4'-f1 utJ~
arlsbad Business License# (Required): ______ _
APPLICANT CERTIFICATION: I certify that I have read the opp c tionandstate that the above information is correct and that the
information on the plans is accurate. I agree to comply with all;[1·t ordinances and State laws relating to building
construction. ~. LJ. a--: .-------/ /
NAME (PRINT): Jt14N b ~>,)®,~K--SIGN:-........,__ .... ~ ....... ----DDATE: fo!l.2-,JJ. ~
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
REV. 07/21
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON
SIGNING THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO
PERMIT ISSUANCE.
OPTION A): LICENSED CONTRACTOR DECLARATION:
lherebyaffirmunderpenaltyofperjurythatlamlicensedunderprovisionsofChapter9(commencingwithSection7000)ofDivision3
of the Business and Professions Code, and my license is in full force and effect. I also affirm under penalty of perjury one of the
following declarations (CHOOSE ONE):
D1 have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
~;~i::~h:11~:::::~:s:oer:~:.:l~:::ensatlon, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
~orkers' compensation lnsuran e carrier an.2,Jlolicy number are: lnsuranceCompany Name: .£J/~T, ,
Policy No. 2£--Expiration Date: --l/-_.,,_.,.Z,&'-'-',,_/..,.2.--,.,.3_..._ ______ _
-OR-
Ocertificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person In any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a ~~ip~ending agency for the performance of the work this permit Is issued (Sec. 3097 (I) Civil Code).
Lender's Name: ____ _,/!,/!,!_._..~~'~IJIC...~~----------Lender's Address: ____________________ _
CONTRACTOR CERTIFICATION: /certify that I have read the application and state that the above information is correct and that
the information on the plans is accurate. /agree to comply with all City ordinances and te laws relating to building
construction.
-OR -
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason: n I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
~44, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through his own employees, provided that such Improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner-builder wlli have the burden of proving that he did not build or Improve for the purpose of sale).
-OR-
D1, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
-OR-□1 am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
AD, D FORM B-61 HOwner Builder Acknowledgement and Verification Form" is required for any permit Issued to a property owner.
By my signature below I acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of the
Improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder if it has not been constructed in its entirety by licensed
contractors./ understand thatacopyof the applicable law, Section 7044 of the Business and Professions Code, is ovailable upon request when this application is
submitted or at the following Web site: http: I lwww.leginfo.ca.gov/ca/aw.html.
OWNER CERT/FICA T/ON: /certify that I have read the application and state that the above information is correct and that the
information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
construction.
NAME (PRINT): SIGN: __________ DATE: ______ _
Note: If the person signing above is an authorized agent for the property owner Include form 8-62 signed by property owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
2 REV. 07/21
Building Permit Inspection History Finaled
(City of
Carlsbad
I
PERMIT INSPECTION HISTORY for {CBC2022-0226)
Permit Type: BLDG-Commercial Application Date: 06/23/2022 Owner: REGENCY BRESSI LLC
Work Class: Tenant Improvement Issue Date: 10/13/2022 Subdivision: CARLSBAD TCT#06-24BRESSI
RANCH COMM
Status: Closed -Finaled Expiration Date: 07/25/2023 Address: 2623 GATEWAY RD, # 103
IVR Number: 41525 CARLSBAD, CA 92009-1751
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date Status
10/24/2022 10/24/2022 BLDG-84 Rough 194813-2022 Partial Pass Tim Kersch Re inspection Incomplete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
11/18/2022 11/18/2022 BLDG-84 Rough 196961-2022 Passed Tim Kersch Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
11 /29/2022 11/29/2022 BLDG-34 Rough 197464-2022 Partial Pass Tim Kersch Relnspection Incomplete
Electrical
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Pass in wall ok to insulate and hang Yes
drywall 2x sides.
12/07/2022 12/07/2022 BLDG-17 Interior 198149-2022 Passed Tim Kersch Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-34 Rough 198148-2022 Passed Tim Kersch Complete
Electrical
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Pass in wall ok to insulate and hang Yes
drywall 2x sides.
01/26/2023 01/26/2023 BLDG-24 Rough/Topout 201569-2023 Passed Peter Dreibelbis Complete
Wednesday, May 29, 2024 Page 1 of 2
PERMIT INSPECTION HISTORY for {CBC2022-0226)
Application Date: 06/23/2022 Owner: REGENCY BRESSI LLC Permit Type: BLDG-Commercial
Work Class: Tenant Improvement Issue Date: 10/13/2022 Subdivision: CARLSBAD TCT#06-24BRESSI
Status: Closed -Finaled Expiration Date: 07/25/2023
IVR Number: 41525
RANCH COMM
Address: 2623 GATEWAY RD, # 103
CARLSBAD, CA 92009-1751
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Relnspection Inspection
Date Start Date
02/06/2023 02/06/2023
02/07/2023 02/07/2023
Wednesday, May 29, 2024
Status
Checklist Item COMMENTS
BLDG-Building Deficiency Water and waste to sink ok
BLDG-Final Inspection 202279-2023 Partial Pass
Checklist Item COMMENTS
BLDG-Building Deficiency
BLDG-Plumbing Final Need to finish scope of work. TCO
granted.
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
BLDG-Final Inspection 202427-2023 Passed
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
NOTES Created By
Angie Teanio
COMMENTS
TEXT
619-917-4106 Craig
Passed
No
Tim Kersch Reinspection Incomplete
Passed
Yes
No
Yes
Yes
Yes
Tim Kersch Complete
Passed
Yes
Yes
Yes
Yes
Yes
Created Date
02/06/2023
Page 2 of 2
August 24, 2022
City of Carlsbad
Community Development Dc.-partment -Building Division
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review: TI Coastal Medical Aesthetics
Address: 2623 Gateway Road, Carlsbad, CA
Applicant Name: Mark Swenson
Applicant Email: mark@studio.cc
OCCUPA.~CY AND BUILDING SUMMARY:
Occupancy Groups: 8
Occupant Load: 12
Type of Construction: V-B
Sprinklers: Yes
Stories: 1
Area of Work (sq. ft.): 1,222 sq. ft.
The plans have been reviewed for coordination with the pcnnit application.
Valuation: Confirmed
Scope of Work: Confinned
Floor Area: Confirmed
Attn: Building & Safety Department,
rlrue No1th
COMPL IANCl-SFRVICES
City of Carlsbad -FINAL REVIEW
City Pennit No: CBC2022-0226
True North No.: 22-018-054
True No1th Compliance Services, Inc. has completed the final review of the following documents for the project
referenced above on behalf of the City of Carlsbad:
l. Drawings: One (I) copy dated August 4, 2022, by Studio C.
The 2019 California Building, Mechanical, Plumbing, and Electrical Codes (i.e .. 2018 JBC, UMC. UPC, and 2017
NEC, as amended by the State of California). 2019 California Green Building Standards Code. 2019 California
Existing Building Code, and 2019 California Energy Code, as applicable, were used as the basis of our review.
Please note that our review has been completed and we have no further comments.
We have enclosed the above noted documents bearing our review stamps for your use. Please call if you have any
questions or ifwe can be of further assistance.
Sincerely,
True North Compliance Services
Review By: Amar Hasenin -Plan Review Engineer
True North Compliance Services, Inc.
3939 Atlantic Avenue Suite 224, Long Beach, CA 90807
T / 562. 733.8030
August 3, 2022
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review: Tenant Improvement
Address: 2623 Gateway Road , Carlsbad CA
Applicant Name: Mark Swenson
Applicant Email: mark@studjoc.cc
Attn: Applicant,
Tn1eNorth
COMPl IANCE SERVICES
SECOND REVlEW
City Pennit No: CBC2022-0226
True North No.: 22-018-054
True North Compliance Services, Inc. has completed the second review of the following documents for the project
referenced above on behalfofthe City of Carlsbad:
1. Drawings: One (I) copy dated June 21 , 2022 with the Della I, by Studio C.
The 2019 California Building, Mechanical. Plumbing, and Electrical Codes (i.e., 2018 IBC, UMC, UPC, and 2017
NEC, as amended by the State of Californ ia), 2019 California Green Building Standards Code, 2019 California
Existing Building Code. and 20 19 California Energy Code, as applicable, were used as the basis of our review. Our
comments and building data information can be found below.
Please call if you have any questions or if we can be of further assistance.
R.ESUBMITT AL INSTRUCT[ONS:
Deliver THREE corrected sets of plans and TWO corrected calculations/reports directly to the City of
Carlsbad Building Division, 1635 Faraday Ave., Carlsbad, CA 92008, (442) 339-2719. The City will route the
plans to True North, Planning and Land Development Engineering Departments (if applicable) for continued
review.
Note: If this project requires FIRE PREVENTION review, ensure that you follow their specific instructions
for rcsubmittal review. The City will not route plans back to Dennis Grubb & Associates for continued Fire
Prevention review.
Sincerely,
True North Compliance Services
Review By: Scot Weisse, PE-Senior Plan Review Engineer
True North Compliance Services, Inc.
3939 Atlantic Avenue Suite 116, Long Beach, CA 90807
T / 562. 733.8030
Tenant Improvement
2623 Gateway Road
August 3, 2022
City of Carlsbad-SECOND REVIEW
City Pennit No.: CBC2022-0226
Tnie North No.: 22-018-054
Page 2
Attn: Permit Technician, the plans have been reviewed for coordination with the pcnnit application. Sec below
for additional information:
Valuation: Confirmed
Scope of Work:
Floor Area:
Confirmed
Confirmed
Notes: NIA
Plan Review Comments
GENERAL INFORMATION:
A. The following comments are referred to the 2019 California Building, Mechanical, Plumbing, Electrical
Codes, Cali fornia Green Building Standards Code. and Energy Code (i.e., 2018 IBC, UMC. UPC. and 2017
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments. then. is only a portion of the plan
review. Contact the City for other items.
C. Respond in writing lo each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
D. Please be sure to include the architect and engineer's stamp and signature on all sheets of the drawings and
on the coversheets of specifications and calculations per CBPC 5536.1 and CBPC 6735. This item will be
verified prior to plan apprornl.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups: B
Occupant Load: 12
Type of Construction: V-B
Sprinklers: Yes
Stories: I
Area of Work (sq. ft.): 1,222 sq. ft.
ARCHITECTURAL COMM.ENTS:
No Comments
ACCESSIBILITY COMMENTS:
D2. Offices of healthcare providers are requirnd to comply with CBC l IB-805. Address the following:
PC2: Per 2019 CBC, Chapter 2 definition for Medical Care -"Care involving medical or surgical
procedures, 11ursi11g or for psychiatric purposes", the Medical Spa, which provides medical proced1tres
will need to comply with 11 B-805 code requirements for Medical Care Facilities. The comments below.
a) Provide a 36" minimum wide clear floor space along the full length of each side of the beds in the
treatment rooms. CBC 11 B-805.2.2 and I lB-805.4. I
Tenant Improvement
2623 Gateway Road
August 3, 2022
City of Carlsbad-SECOND REVLEW
City Pennit No.: CBC2022-0226
True No1th No.: 22-018-054
Page3
PC2: Show the location of the exam tables and the req11ired clear width 011 tlte p/a,rs.
b) Provide turning space in compliance with CBC 11 B-304 in each treatment room. CBC 11 B-805.2.3
PC2: No turning spaces shown on the plans at the treatment rooms.
c) In the waiting rooms, at least 5% of seating shall be wheelchair spaces complying with l lB-802.1.
PC2: The one wheelchair space shown at the reception area appears to meet the minim11m 5%
req11irement, but the wheelchair space is not large enough. The wheelchair spaces clear width
shall be 36-i11ches, not JO-inches JJB-802.1.2.
d) At equipment in exam rooms, provide a clear floor space in compliance with CBC l 1B-305.2. CBC
l lB-805.4.2
PC2: Show the clear floor space at the equipment in the exam rooms, minimum 30"x48" 1 JB-
305.
MECHANICAL COMMENTS:
No Comments.
El,ECTRICAL COMMENTS:
No Comments
PLUMBING COMMEl\'TS:
No Comments
GREEN BUILDING COMMENTS:
No Comments.
ENERGY COMPLIANCE COMMENTS:
Nu Comments
STRUCTURAL COMMENTS:
No Comments
If you have any questions regarding the above comments, please contact Scot Weisse, PE via email
§cotw@tncservices.com or telephone (562) 733-8030.
IE DJ
• TrueNorth
July J 5, 2022
City of Carlsbad
Community Development Department -Building Divi sion
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review: Tenant Improvement
Address: 2623 Gateway Road , Carlsbad CA
Applicant ame: Mark Swenson
Applicant Email: mark@studioc.cc
Attn: Applicant,
·,,1_ COMPLIANCE SERVICES
FJRST REVIEW
City Pennit o: CBC2022-0226
True No11h o.: 22-01 8-054
Resubmit-7/21/22
I I
True No1th Compliance Services, Inc. has completed the first review of the fo llowing documents for the project
referenced above on behalf of the City of Carlsbad:
I. Drawings: One (I) copy dated June 21, 2022, by Studio C.
The 2019 Cali fornia Building, Mechanical, Plumbing, and Electrical Codes (i.e., 2018 IBC, UMC, UPC, and 2017
NEC, as amended by the State of Cali fornia), 2019 California Green Building Standards Code, 2019 California
Existing Building Code, and 2019 California Energy Code, as applicable, were used as the basis of our review. Our
comments and building data information can be found below.
Please call if you have any questi ons or if we can be of fu1t her assistance.
RESUBMITTAL I STRUCTJO S:
Deliver TH REE corrected sets of plans and TWO corrected calculations/reports directly to the City of
Carlsbad Building Division, 1635 Faraday Ave., Carlsbad, CA 92008, ( 442) 339-2719. The City will route the
plans to True orth, Planning and Land Development Engineering Departments (if applicable) for continued
review.
Note: If this project requires FrRE PREVENTION review, ensure that you follow their specific instructions
for resubmittal review. The City will not route plans back to Dennis Grubb & Associates for continued Fire
Prevention review.
Sincerely,
True North Compliance Services
Review By: Amar Hasenin -Plan Review Engineer
True North Compliance Services, Inc.
3939 Atlantic Avenue Suite 116, Long Beach, CA 90807
T / 562.733.8030
Tenant Improvement
2623 Gateway Road
J uly 15, 2022
ATTE T ION PERMIT TECH ICIAN:
City of Carlsbad-FIRST REVIEW
City Permit No.: CBC2022-0226
True 01th No.: 22-018-054
Page2
Please see the list below for additional information and general building data.
I. Occupancy and Building Summary:
Occupancy Groups:
Occupant Load:
Type of Construction:
Sprinklers:
Stories:
Area of Work (sq. ft.):
B
12
V-B
o BUILDING IS SPRINKLERED -REVISED ON PLANS, SHT. Tl
I
1,222 sq. ft.
2. The plans have been reviewed for coordination with the permit application.
Valuation:
Scope of Work:
Floor Area:
otes: /A
Confirmed
Confirmed
Confirmed
Tenant Improvement
2623 Gateway Road
July 15, 2022
City of Carlsbad-FIRST REVIEW
City Pem,it o.: CBC2022-0226
True No11h No.: 22-018-054
Page ]
Plan Review Comments
GE
A. The following comments are referred lo the 2019 California Building, Mechanical, Plumbing, Electrical
Codes, California Green Building Standards Code, and Energy Code (i.e., 2018 I BC, UMC, UPC, and 2017
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Divi sion and/or other City depa11ments that will
also require your attention and response. This attached list of comments, then, is onl y a po11ion of the plan
review. Contact the City for other items.
C. Respond in writing to each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
D. Please be sure to include the architect and engineer's stamp and signature on all sheets of the drawings and
on the coversheets of speci ftcations and calculations per CBPC 5536.1 and CBPC 6735. This item will be
verified prior to plan approval.
ARCHITECTURAL COMMENTS:
A I. On sheet A I, address the following comments:
Sht.Al -
a) The hallway does not have access 10 an exit resulting in a dead end. Revise the design o the dead
end does not exceed 20 '. CBC IO 18.4
b) Revise the occupant load calculation to utilize an occupant load factor of 15 in the break room.
c) The means of egress from the space accessible to the pub I ic cannot travel th rough the Break Room.
This results in access to only one exit being provided. To justify the one exit, dimension the
common path of egress travel. Ensure the limitati ons given in CBC Table 1006.2.1 are not
exceeded.
a) this building is sprinklered (revised on plans) -per CBC I 020.4 exception #2; dead end corridor 50ft length max
b) revised break room occupant load
c) indicated maximum travel distance to exit on plan; no public egress through break room proposed
Tenant Improvement
2623 Gateway Road
July 15, 2022
\
\
\
\
\
\
\
ACCESSIBILITY COMMENTS:
~ QOCCI
City of Carlsbad-FIRST REVIEW
City Pe1111it No.: CBC2022-0226
True North No.: 22-0 18-054
Page4
This is not a health care provider facility. It is a cosmetic skin care facility
therefore CBC 1 lB-805 does not apply
D I. Sheet AO: Provide additional sign age for tow away of unauthorized vehi cles parked in designated accessible
spaces per CBC 11 B-502.8.see detail #3/A0 & site plan for location of sign
D2. Offices of healthcare providers arc required to comply with CBC 11 B-805. Address the following:
a) Provide a 36" minimum wide clear floor space along the full length of each side of the beds in the
treatment rooms. CBC 11 B-805.2.2 and 11 8-805.4.1
b) Provide turning space in compliance with CBC 118-304 in each treatment room. CBC 118-805.2.3
c) In the waitin g rooms, at least 5% of seating shall be wheelchair spaces complying with 11 B-802.1.
i) Provide details showing the bench is compliance with CBC 903.3. #7/A2
d) At equipment in exam rooms, provide a clear floor space in compliance with CBC 11 B-305.2. CBC
I IB-805.4.2
e) Hand washing fixtures, lavatories and sinks shall comply with CBC 11 B-606. CBC 11 B-805.6 #6/A2
D3. Provide a cross section of the counter surface at the break rooms.
Tenant Improvement
2623 Gateway Road
July I 5, 2022
Sht. A I dim. added at counter
City of Carlsbad-FIRST REVIEW
City Pem1it o.: CBC2022-0226
True North No.: 22-01 8-054
Page5
a) Show the depth of the counter surface to be 24-inches maximum per CBC I I B-308.3.2.
b) Show th e height of the counter surface to be 34-inches maximum above the finish fl oor per CBC
11 B-902.3. Sht. A I -general note #4
MECHANICAL COMMENTS: Sht. Ml -ductwork plan provided
MI. Provide mechanical plans for review. Ensure ventilation is provided to all spaces.
ELECTRJCAL COMMENTS:
o Comments
PLUMBI G COMME TS:
No Comments
GREEN BUJLDJNG COMMENTS:
GI . Complete the Waste Management Plan fo rm and incorporate onto the plan set. This form must be
completed before plans can be approved. Please find the fo1111 in the link provided below. Sht. A3
https://www.carlsbadca.gov/home/showpublisheddocument/6709/63 78899677442 J 9 J 64
G2. Climate Action Plan requirements apply to all new structures, residential additions/remodels equal to or
exceeding $60,000 in valuation, and commercial City of Carlsbad requires that all projects that qualify for
CAP compliance will require a completed Climate Action Plan (CAP) Consistency Checklist (city form 8-
50) to be completed by the APPLICA T.
a) For plans submitted to the City the following Climate Action Plan requirements apply, per Carl sbad
ordinance:
b) The applicant is to fil l out the B-50 CAP Consistency Checklist. The scope of work and project
valuation will detem1ine which sections of the CAP are required.
c) Plan examiners review the B-50 CAP Consistency Checkli st for completion. For example: If new
residential construction is the scope of work, CAP sections 2A, 3A, and 4A are required to be tilled
on the B-50 checklist.
E ERGY COMPLIA CE COMME TS:
No Comments
STRUCTURAL COMMENTS:
o Comments
lf you have any questions regarding the above comment , please contact Amar Hasen in via emai l
amar@tncservices.com, or telephone (562) 733-8030.
IE DI
Project Ad %;
SAN DIEGO REGIONAL
HAZARDOUS MATERIALS
QUESTIONNAIRE
OFFICE USE ONLY
RECORD ID# _________________ _
PLAN CHECK# __________________ 1
BP DATE
Mailing Ad State Plan File#
Project Conta Telephone#
The following questions represent the facility's activities, NOT the specific project description.
PART 1: FIRE DEPARTMENT -HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: (not required for protects within the City of San
~: Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled,
applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: Facility's Square Footage (including proposed project):
1. Explosive or Blasting Agents
2. Compressed Gases
3. Flammable/Combustible Liquids
4. Flammable Solids
5. Organic Peroxides 9. Water Reactives
6. Oxidizers 10. Cryogenics
7. Pyrophorics 11. Highly Toxic or Toxic Materials
8. Unstable Reactives 12. Radioactives
13. Corrosives
~ Other Health Hazards
C;) None of These.
PART II: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH -HAZARDOUS MATERIALS DIVISION (HMO): If the answer to any of the
questions is yes, applicant must contact the County of San Diego Hazardous Materials Division. 5500 Overland Avenue, Suite 170, San Diego, CA 92123.
Call (858) 505-6700 prior to the issuance of a building permit.
FEES ARE REQUIRED Project Completion Date: Expected Date of Occupancy: □ CalARP Exempt
1.
2.
3.
4.
5.
6.
7.
8.
YES NO □ ~ B ~
□ □ □ □
□
~ I
(for new construction or remodeling projects)
Is your business listed on the reverse side of this form? (check all that apply).
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
Will your business store or handle carcinogens/reproductive toxins in any quantity?
Will your business use an existing or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal to
or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act).
Date Initials
0 CalARP Required
Date Initials
0 CalARP Complete
I
Date Initials
PART Ill: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT IAPCDl: The following questions are intended to identify the majority of air pollution
issues at the planning stage. Your project may require additional measures not identified by these questions. Some residential projects may be exempt from APCD
requirements. If yes is answered for either questions 1, 2 or 5 or for more comprehensive requirements, please contact APCD at aocdcomo@sdcounty ca,gov:
(858) 586-2650; or 10124 Old Grove Road, San Diego, CA 92131 .
1.
2.
3.
4.
5.
6.
YES NO □ Im Will the project disturb 100 square feet or more of existing building materials?
Will any load supporting structural members be removed? B ~ (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been performed by an individual that has passed an EPA-approved
building inspector course?
□
□
□
D (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Based on the survey results, will the project disturb any asbestos containing material? If yes, a
notification may be required at least 1 O working days prior to commencing asbestos removal. Additionally, a notification may be required prior to
the removal of a load supporting structural member(s) regardless of the presence of asbestos. i1 Will the project or associated construction equipment emit air contaminants? See the reverse side of this form for typical equipment requiring an
APCD permit. If yes, contact APCD prior to the issuance of a building permit.
D (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school
bounda ?
~1 und11,r _pen~ p~rjury that to the best of my knowledge an ~ML ~.U%-?b½:-: bl2.Zt2'b
Date
FOR OFFICAL USE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION: _______________________________ _
BY· DATE· I I
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO• APCD COUNTY-HMO APCD COUNTY-HMO APCD
.. *A stamp in this box 2!lr£ exempts businesses from completing or updating a Hazardous Materials Business Plan. Other perm1tt1ng requirements may still apply
HM-9171 (9/1 8) County of San Diego -DEH -Hazardous Materials Division
LIST OF BUSINESSES WHICH REQUIRE REVIEW AND APPROVAL FROM THE COUNTY OF SAN DIEGO
DEPARTMENT OF ENVIRONMENTAL HEALTH -HAZARDOUS MATERIALS DIVISION
Check all that apply:
AUTOMOTIVE
D Battery Manufacturing/Recycling
0 Boat Yard
D Car Wash
0 Dealership Maintenance/Painting
D Machine Shop
D Painting
D Radiator Shop
0 Rental Yard Equipment
0 Repair/Preventive Maintenance
0 Spray Booth
0 Transportation Services
D Wrecking/Recycling
CHEMICAL HANDLING
0 Agricultural supplier/distributor
0 Chemical Manufacturer
0 Chemical Supplier/Distributor
0 Coatings/Adhesive
D Compressed Gas Supplier/Distributor
0 Dry Cleaning
0 Fiberglass/Resin Application
D Gas Station
0 Industrial laundry
0 Laboratory
0 Laboratory Supplier/Distributor
0 Oil and Fuel Bulk Supply
0 Pesticide Operator/Distributor
CHEMICAL HANDLING
0 Photographic Processing
0 Pool Supplies/Maintenance
0 Printing/Blue Printing
D Road Coatings
D Swimming Pool
0 Toxic Gas Handler
0 Toxic Gas Manufacturer
METAL WORKING
D Anodizing
0 Chemical Milling/Etching
D Finish-Coating/Painting
D Flame Spraying
0 Foundry
D Machine Shop-Drilling/Lathes/Mills
D Metal Plating
0 Metal Prepping/Chemical Coating
D Precious Metal Recovery
D Sand Blasting/Grinding
D Steel Fabricator
0 Wrought Iron Manufacturing
AEROSPACE
0 Aerospace Industry
D Aircraft Maintenance
0 Aircraft Manufacturing
MISCELLANEOUS
0 Asphalt Plant
0 Biotechnology/Research
D Cannabis-related
D Manufacturing D Dispensary D Other
0 Co-Generation Plant
0 Dental ClinidOffice
0 Dialysis Center
0 Emergency Generator
0 Frozen Food Processing Facility
0 Hazardous Waste Hauler
0 Hospital/Convalescent Home
0 Laboratory/Biological lab
0 Medical ClinidOffice
0 Nitrous Oxide (NOx) Control System
0 Pharmaceuticals
0 Public Utility
0 Refrigeration System
D Rock Quarry
0 Ship Repair/Construction
0 Telecommunications Cell Site
0 Veterinary ClinidHospital
0 Wood/Furniture Manufacturing/Refinishing
0 Brewery/Winery/Distillery
ELECTRONICS
0 Electronic Assembly/Sub-Assembly
0 Electronic Components Manufacturing
0 Printed Circuit Board Manufacturing
NOTE: THE ABOVE LIST INCLUDES BUSINESSES, WHICH TYPICALLY USE, STORE, HANDLE, AND DISPOSE OF HAZARDOUS SUBSTANCES.
ANY BUSINESS NOT INCLUDED ON THIS LIST, WHICH HANDLES, USES OR DISPOSES OF HAZARDOUS SUBSTANCES MAY STILL REQUIRE
HAZARDOUS MATERIALS DIVISION (HMD) REVIEW OF BUSINESS PLANS. FOR MORE INFORMATION CALL (858) 505-6880.
LIST OF AIR POLLUTION CONTROL DISTRICT PERMIT CATEGORIES
Businesses, which include any of the following operations or equipment, will require clearance from the Air Pollution Control District.
CHEMICAL
47 -Organic Gas Sterilizers
32 -Acid Chemical Milling
33 -Can & Coil Manufacturing
44 -Evaporators, Dryers & Stills Processing
Organic Materials
24 -Dry Chemical Mixing & Detergent Spray
Towers
35 -Bulk Dry Chemicals Storage
55 -Chrome Electroplating Tanks
COATINGS & ORGANIC SOLVENTS
27 -Coating & Painting
37 -Plasma Arc & Ceramic Deposition Spray
Booths
38 -Paint, Stain & Ink Mfg
27 -Printing
27 -Polyester Resin/Fiberglass Operations
METALS
18 -Metal Melting Devices
19 -Oil Quenching & Salt Baths
32 -Hot Dip Galvanizing
39 -Precious Metals Refining
ORGANIC COMPOUND MARKETING
{GASOLINE, ETCI
25 -Gasoline & Alcohol Bulk Plants & Terminals
25 -Intermediate Refuelers
26 -Gasoline & Alcohol Fuel Dispensing
COMBUSTION
34 -Piston Internal -Combustion Engines
13 -Boilers & Heaters (1 million BTU/hr or larger)
14 -Incinerators & Crematories
15 -Burn Out Ovens
16 -Core Ovens
20 -Gas Turbines, and Turbine Test Cells & Stands
48 -landfill and/or Digester Gas Flares
ELECTRONICS
29 -Automated Soldering
42 -Electronic Component Mfg
FOOD
12 -Fish Canneries
12 -Smoke Houses
50 -Coffee Roasters
35 -Bulk Flour & Powered Sugar Storage
SOLVENT USE
28 -Vapor & Cold Degreasing
30 -Solvent & Extract Driers
31 -Dry Cleaning
ROCK AND MINERAL
04 -Hot Asphalt Batch Plants
05 -Rock Drills
06 -Screening Operations
07 -Sand Rock & Aggregate Plants
08 -Concrete Batch, CTB, Concrete Mixers, Mixers
& Silos
10 -Brick Manufacturing
OTHER
01 -Abrasive Blasting Equipment
03 -Asphalt Roofing Kettles & Tankers
46 -Reverse Osmosis Membrane Mfg
51 -Aqueous Waste Neutralization
11 -Tire Buffers
17 -Brake Debonders
23 -Bulk Grain & Dry Chemical Transfer & Storage
45 -Rubber Mixers
21 -Waste Disposal & Reclamation Units
36 -Grinding Booths & Rooms
40 -Asphalt Pavement Heaters
43 -Ceramic Slip Casting
41 -Perlite Processing
40 -Cooling Towers -Registration Only
91 -Fumigation Operations
56 -WWTP (1 million gal/day or larger) & Pump
Station
NOTE: OTHER EQUIPMENT NOT LISTED HERE THAT IS CAPABLE OF EMITTING AIR CONTAMINANTS MAY REQUIRE AN AIR POLLUTION
CONTROL DISTRICT PERMIT. IF THERE ARE ANY QUESTIONS, CONTACT THE AIR POLLUTION CONTROL DISTRICT AT (858) 586-2600.
HM-9171 (9/18) County of San Diego -DEH -Hazardous Materials Division