LIFT STATION GENERATOR REPLACEMENT PROJECT
KNOTS LANE LIFT STATION
NORTH BATIQUITOS LIFT STATION
C.I.P. 3840-12
CITY OF CARLSBAD
CARLSBAD, CALIFORNIA
MARCH 2018
DRAWING INDEX
SHEET NO.DESCRIPTION
1 TITLE, DRAWING INDEX, VICINITY AND LOCATION MAPS
2 ELECTRICAL ABBREVIATIONS, NOTES AND LEGEND
3 ELECTRICAL DETAILS
4 KNOTS LANE LIFT STATION ELECTRICAL PLANS
5 KNOTS LANE LIFT STATION ELECTRICAL SINGLE LINE DIAGRAMS
6 NORTH BATIQUITOS LIFT STATION ELECTRICAL PLANS
7 NORTH BATIQUITOS LIFT STATION ELECTRICAL SINGLE LINE DIAGRAMS
8 NORTH BATIQUITOS LIFT STATION ELECTRICAL DETAIL PHOTOS
9 BUILDING SECTIONS
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
1
.
d
w
g
NI
C
H
O
L
A
S
K
O
K
O
T
A
S
12
/
2
1
/
2
0
2
0
3
:
4
1
P
M
IMPROVEMENT PLAN FOR:
LIFT STATION GENERATOR REPLACEMENT
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
91
MJS
MJS
SLS
TITLE, DRAWING INDEX, VICINITY
AND LOCATION MAPS
DISTR MANUFACTURER
MOTOR CONTROL CENTER
MANHOLE
MOTOR OPERATED VALVE
MISCELLANEOUS
NORMALLY CLOSED
MOTOR STARTER
MOUNTING
MOUNTED
MANUFACTURER'S ASSOC.
NOT IN CONTRACT
NOT TO SCALE
NATIONAL ELECTRICAL
MOTOR CIRCUIT PROTECTOR
NORMALLY OPEN, NUMBER
MANUAL TRANSFER SWITCH
NATIONAL ELECTRICAL CODE
THIS IS A GENERALIZED LEGEND SHEET.
THIS CONTRACT MAY NOT USE ALL
INFORMATION SHOWN.
NOTIFY THE ENGINEER IMMEDIATELY IF
CONFLICTS IN EQUIPMENT LOCATIONS
ARE DISCOVERED OR IF PROBLEMS ARISE
DUE TO FIELD CONDITIONS, LACK OF
INFORMATION OR ANY OTHER REASON. NO
PAYMENT WILL BE MADE FOR CHANGES
WHICH HAVE NOT BEEN FAVORABLY
REVIEWED BY THE ENGINEER.
THESE DRAWINGS ARE DIAGRAMMATIC ONLY;
EXACT LOCATIONS OF ELECTRICAL
EQUIPMENT SHALL BE DETERMINED IN THE
FIELD BY THE ENGINEER. THE INSTALLATION
OF ALL EQUIPMENT SHOWN ON THESE
DRAWINGS OR DESCRIBED IN THE
SPECIFICATIONS SHALL CONFORM TO THE
REQUIREMENTS SET FORTH IN THE LATEST
EDITIONS OF ALL APPLICABLE CODES AND
UTILITY COMPANY STANDARDS. CONTACT
THE UTILITY COMPANY REPRESENTATIVES
AND VERIFY THEIR REQUIREMENTS.
CONDUIT SIZE AND FILL SHALL BE AS
INDICATED. WHERE NO SIZE IS SHOWN, THE
CONDUIT SHALL BE SIZED IN ACCORDANCE
WITH THE EDITION OF THE NATIONAL
ELECTRICAL CODE ADOPTED BY THE
AUTHORITY HAVING CODE ENFORCEMENT
JURISDICTION. WHERE NO FILL IS INDICATED,
THE FILL SHALL BE 2#12. PROVIDE 3/16 INCH
NYLON PULL ROPE IN EACH EMPTY CONDUIT.
PLAN NOTES:
P1.
ELAPSED TIME METERETM
FIRE ALARM CONTROL PANEL
GENERAL NOTES:
G1.
FACP
FDR FEEDER
G3.
G2.
NTS
NIC
NO
DISTRIBUTION PANEL
ELECTRICAL HANDHOLE
ELECTRIC, ELECTRICAL
EHH
EQ
EQPT
EFFL
ENCL
EMERG
ELEM
ELEC
EL, ELEV
EFFLUENT
ENCLOSURE
EQUIPMENT
EQUAL
ELEVATION
ELEMENTARY
EMERGENCY
EA
EF
DWG
(E)
DP
DN
DRAWING
EXISTING
EXHAUST FAN
EACH
DISTRIBUTION
DOWN
NC
NEMA
NEUT
NEC
NEUTRAL
MTS
(N)
MTD
MTG
NEW
MH
MOV
MS
MIN
MISC
MINIMUM
MFR
MCP
MAX
MCC
MAXIMUM
WATERTIGHT
TRANSFORMER
WATER TREATMENT PLANT
INFORMATION SHOWN MAY NOT BE ALL
INCLUSIVE. SEE ALSO ANSI C37.2, Y1.1,
Y32.2, AND Y32.9.
VERIFY ALL COLOR REQUIREMENTS
BEFORE ORDERING MATERIALS.
G5.
G4.
XFMR
WT
WTP
TEMPERATURE
TELEPHONE
UNDERGROUND
UNIT HEATER
ULTRA VIOLET
TYPICAL
VOLT-AMPERES
VAR-HOUR
WIRE, WATTS
VERTICAL
VOLTS
TWISTED SHIELDED PAIR
WATTHOUR METER
VOLT AMPERES REACTIVE
VOLTMETER SWITCH
VARIABLE FREQUENCY DRIVE
WEATHERPROOF
WATTHOUR DEMAND METER
VS
WHDM
WP
W
WHM
VERT
VH
VAR
VFD
UG
UV
VA
V
UH
TEMP
TSP
TYP
TEL
FA
T
FEET, FOOT
FREQUENCY
GALVANIZED
FORWARD
GENERATOR
HYDROGEN PEROXIDE
HAND-OFF-REMOTE
HORSEPOWER
HORIZONTAL
HANDHOLE
HAND-OFF-AUTOMATIC
HIGH VOLTAGE
INPUT/OUTPUT
INDICATING LIGHT
HIGH PRESSURE SODIUM
KILOVOLTS
KILOAMPERES
KILOVOLT AMPERES
LIGHTING PANEL
KILOWATT HOURS
LOW PRESSURE SODIUM
KILOWATTS
JUNCTION BOX
GALVANIZED RIGID STEEL
ABBREVIATIONS
KILOVOLT AMPERES REACTIVE
THOUSANDS OF CIRCULAR MILS
INSTRUMENT, INSTRUMENTATION
HERTZ (CYCLES PER SECOND)
FULL VOLTAGE, NON REVERSING
HUMAN MACHINE INTERFACE
GROUND FAULT INTERRUPTER
FULL VOLTAGE, REVERSING
LIGHTING CONTROL PANEL
MILLIAMPERES
CONTROL POWER TRANSFORMER
CONTINUED, CONTINUATION
CURRENT TRANSFORMER
CWP
DISC
DIAG
DIA
DC
CS
CT
CR
CP
COLD WATER PIPE
DIAGRAM
DIRECT CURRENT
DISCONNECT
DIAMETER
CONTROL SWITCH
CONTROL RELAY
CONTROL PANEL
CO
CPT
CONT
COMM
COND
CKT
CL
CONDUIT ONLY
CONDUCTOR
COMMUNICATION
CHLORINE
CIRCUIT
LPS
LT(S)
(M)
mA
LTG
LIGHT(S)
MODIFIED
LIGHTING
LP
LCP
KWH
KW
KV
KVAR
KVA
KCMIL
KA
I/O
JB
AUTO/MANUAL CONTROLLER
CIRCUIT BREAKER AUX. CONTACT,
AMERICAN WIRE GAGE
CLOSED WHEN BREAKER IS OPEN
AUTOMATIC TRANSFER SWITCH
CONDUIT, CONTACTOR
CONTROL CABLE, CLOSING COIL
BARE COPPER GROUND
C
CC
CB
CAB
CAP
BLDG
BCG
b
CABINET
CIRCUIT BREAKER
CAPACITOR
BUILDING
AT
AWG
AUX
AUTO
ATS
APPROX
AS
A/M
AMMETER TRIP
AUTOMATIC
AUXILIARY
APPROXIMATE
INSTITUTE
AMMETER SWITCH
HV
IND LT
INSTR
HZ
HTR
HPS
HORIZ
HP
HEATER
H O
HMI
HOR
HOA
22
HH
GND
GRS
GEN
GFI
GROUND
CIRCUIT BREAKER AUX. CONTACT,
AMMETER, AMPERES
ALTERNATING CURRENT
ANALOG TO DIGITAL
CLOSED WHEN BREAKER IS CLOSED
AMPERES INTERRUPTING CAPACITY
ABOVE FINISHED FLOOR
ADJUSTABLE FREQUENCY DRIVEAFD
AIC
ALT
AL
AFF
ADJ
AF
A/D
AC
ALUMINUM
ALTERNATOR
ADJUSTABLE
AMPERE FRAME
a
A
FVNR
FWD
GALV
GA
FVR
GAUGE
(F)
FU
FREQ
FT
FUSE
FUTURE
PLC PROGRAMMABLE LOGIC CONTROLLER
3/4"C-3#12
SECTION
SUPPLY FAN
SHEET
SOLID NEUTRAL
SIGNAL
SWITCH
SYNCHRONIZING
SWITCHGEAR
SWITCHBOARD
SPECIFICATIONS
SECONDS, SECONDARY
SINGLE POLE, DOUBLE THROW
TERMINAL BOX, TERMINAL BOARD
STAINLESS STEEL, SOLID STATE
SIGNAL HANDHOLE
TELEPHONE CABINET
SWBD
SWGR
SYNC
TB
TC
SPDT
SPECS
SW
SS
SF
SN
SIG
SHH
SHT
SECT
SEC
PANEL
PANELBOARD
RELOCATE
RELOCATED
RECEPTACLE
POWER
ROOM
REQUIRED
RESET TIMER
PRESSURE SWITCH
REVOLUTIONS PER MINUTE
POLYVINYL CHLORIDE
REPEAT CYCLE TIMER
POUNDS PER SQUARE INCH
PRIMARY
RT
SCR
RM
RPM
RCPT
(RLD)
REQD
RCT
PS
PWR
(RL)
PVC
PSI
PNLBD
PRI
PNL
PHOTOELECTRIC
PHASE
POWER FACTOR
PHOTOELECTRIC CELL
PULLBOX, PUSHBUTTON
MEASURE OF ACIDITY OR ALKALINITY
POSITIVE DISPLACEMENT
PH
PF
pH
PE
PEC
PB
PD
PLAN SYMBOLS
OH
ELEMENTARY DIAGRAM SYMBOLS
TVSS
FINISHED FLOORFF
FLEX FLEXIBLE
OVERHEAD
OPERATOR INTERFACE TERMINAL
THERMAL OVERLOAD RELAY
OH
OL
OIT
DELAYED
ELEMENTARY DIAGRAMS
NAMEPLATE INSCRIPTIONS.
NUMBERS AND LETTERS IDENTIFY DEVICE.
DEVICE. ANY ADDITIONAL NAMEPLATES ARE
LIGHT, SELECTOR SWITCH, ETC. INDICATE THE
"NORMAL" STATUS OF SWITCHES OR CONTACTS IS
LEGEND PLATE REQUIREMENT FOR THAT PARTICULAR
INDICATED ON ELEVATIONS WITH THE REQUIRED
UNDERLINED WORDS SHOWN AT A PUSHBUTTON,
E3
E2
THE SHELF POSITION.
E1
CLOSED INSTANTANEOUS
OPEN TO
CLOSE ON REACHING LIMIT
CLOSE ON LEAVING LIMIT
TIMED CONTACTS
CLOSED
DELAYED
INSTANTANEOUS
INSTANTANEOUS
LIMIT SWITCHES
NORMALSYMBOL
CLOSED
OPEN
OPEN
CLOSED TO
DELAYED
DELAYED
INSTANTANEOUS
OPEN
SENSING SWITCHES
RISING
CLOSE ON
FALLING
TEMPERATURE
PRESSURE
LEVEL
SENSED VARIABLE
FLOW
ON THE OTHER DIAGRAM
IF OMITTED, THEN THE SPEC.
NORMALLY CLOSED CONTACT
SPARE CONTACTS APPLY.
REQUIREMENTS REGARDING
SPARE CONTACTS ON RELAY.
ON THIS DIAGRAM
CROSS REFERENCE TO
NORMALLY OPEN CONTACT
ANOTHER DIAGRAM
SINGLE LINE SYMBOLS
MOTOR STARTER
NUMBER INDICATES NEMA SIZE
POWER CIRCUIT BREAKER DRAWOUT
ABOVE 1500V RATING AS NOTED
CR
1 2-2, 3, 0, 0
FS FS
LS LS
TS TS
ZS
ZS
TR
TR
TR
TR
SMS
SAP
EMH EHH SHH
X "
FACP
SOLID CIRCLE DENOTES
DOWNWARD CONDUIT RISER
COMBINATION MOTOR STARTER
FIBER OPTICFO
PSPS
GROUND CONNECTION
SWITCH, 3 POLE EXCEPT WHERE
NOTED. RATING IN AMPERES AS
NOTED
AUTOMATIC TRANSFER
SWITCH 3 POLE, RATING AS
NOTED
SHUNT TRIP
FUSE
FUSE CUTOUT
CIRCUIT BREAKER, 3 POLE EXCEPT WHERE
NOTED. RATING IN AMPERES AS NOTED. IF
TWO RATINGS APPEAR (EG. 100/625) THEN
DEVICE IS MCP; NUMERATOR IS
CONTINUOUS CURRENT RATING &
DENOMINATOR IS INSTANTANEOUS TRIP
SETTING.
SURGE ARRESTER
CURRENT TRANSFORMER
VOLTAGE TRANSFORMER
POWER OR DISTRIBUTION
TRANSFORMER RATING AS NOTED
MOTOR. NUMBER INDICATES
HORSEPOWER
GENERATOR
CONTROL PACKAGE PROVIDED
WITH THE DRIVEN EQUIPMENT
BUS STAB ON MCC OR SWITCHGEAR, CORD
& PLUG CONNECTION FOR MOTORS
THERMAL OVERLOAD
A - AMMETER
V - VOLTMETER
WH - WATTHOUR METER
GS - GROUND FAULT SENSOR
AMMETER SWITCH
VOLTMETER SWITCH
ELEMENTARY DIAGRAM
REFERENCE NUMBER
KIRK KEY INTERLOCK
POWER RECEPTACLE FOR
PORTABLE EQUIPMENT
RELAY DEVICE FUNCTION, #
PER ANSI NUMBER C37.2
TERMINATOR / POTHEAD
SPLICE, TERMINATION
CAPACITOR - KVAR INDICATED
VFD - VARIABLE FREQUENCY DRIVE
SINGLE POLE SWITCH
NORMALLY OPEN /
CLOSED
EMERGENCY PUSHBUTTON
NORMALLY OPEN / CLOSED
PUSHBUTTON
NORMALLY OPEN / CLOSED
SWITCH
1-POLE /
3-POLE
MULTI-POSITION
SELECTOR SWITCH
HAND-OFF-AUTOMATIC
SWITCH X-INDICATES
CONTACTS CLOSED
HAND-OFF-REMOTE SWITCH
X-INDICATES CONTACTS
CLOSED
TERMINAL
CONTROL POWER
TRANSFORMER
CIRCUIT BREAKER, MCP
1-POLE / 3-POLE
GROUND CONNECTION
CONTACT
NORMALLY OPEN / CLOSED
BUS STAB ON MCC; CORD & PLUG
CONNECTION FOR MOTORS
THERMAL OVERLOAD
OVERHEAD POWER LINE
UNDERGROUND CONDUIT
UNDERGROUND DUCT
LINE (CONCRETE
ENCASEMENT) NOTE P4
UNDERGROUND DIRECT
BURIAL CONDUITS
NOTE P4
MULTIPLE CONDUIT RUN
CONDUIT CONCEALED
IN FLOOR
CONDUIT CONCEALED
IN WALL OR CEILING
CONDUIT EXPOSED
CALLOUT INDICATING
CONDUIT SIZE, NUMBER OF
WIRES AND WIRE SIZE
CALLOUT INDICATING
CONDUIT PER SCHEDULE
CONDUIT RUN, HATCH MARKS
INDICATE NO. OF #12 CONDUCTORS
NO HATCH MARKS IS 2#12 UNLESS
OTHERWISE NOTED
HOME RUN TO PANELBOARD
OR AS INDICATED
FLEXIBLE CONDUIT
CONDUIT RUN, BROKEN
AND CONTINUED ON SAME
SHEET OR AS NOTED
CONDUIT WITH SEAL FITTING
CAP ON CONDUIT STUB
OPEN CIRCLE DENOTES
UPWARD CONDUIT RISER
INDICATES REMOVAL
FIRE ALARM CONDUIT
TELEPHONE CONDUIT
SURFACE MOUNTED PANELBOARD
FLUSH MOUNTED PANELBOARD
MOTOR
DISCONNECT SAFETY SWITCH
MANUAL MOTOR STARTER
CONTROL STATION
EQUIPMENT MOUNTING STAND
GROUND ROD AND BOX
INSTRUMENT
ELECTRIC MANHOLE / POWER
HANDHOLE / SIGNAL HANDHOLE
INTRUSION DOOR SWITCH
SECURITY ALARM PANEL
SINGLE POLE SWITCH
2 = 2 POLE, 3 = 3 WAY, 4 = 4 WAY,
K = KEY OPERATED
WP = WEATHERPROOF
D = DIMMER
P = SWITCH WITH PILOT
LIGHT
SINGLE POLE SWITCH
LED FIXTURE
LED FIXTURE WITH NIGHT
LIGHTING (UNSWITCHED) OR
FLUORESCENT FIXTURE WITH
SELF-CONTAINED EMERGENCY
BALLAST/BATTERY
WALL/CEILING MOUNTED
FIXTURE
WALL/CEILING MOUNTED
FIXTURE NIGHT LIGHTING
(UNSWITCHED)
POLE MOUNTED FIXTURE
WALL/CEILING MOUNTED EXIT
LIGHT - DIRECTIONAL ARROW
WHERE INDICATED, SHADED
AREA INDICATES ILLUMINATED
FACE
EMERGENCY LIGHT WITH
SELF CONTAINED BATTERY
LIGHT FIXTURE
IDENTIFICATION
SINGLE RECEPTACLE, 120V
SINGLE RECEPTACLE, 208V
DUPLEX WALL RECEPTACLE, 120V
WP = WEATHERPROOF
G = GROUNDED
IG = ISOLATED GROUND
GF = GROUND FAULT
INTERRUPTER
DOUBLE DUPLEX WALL
RECEPTACLE, 120V
DUPLEX FLOOR RECEPTACLE,
120V
MULTI-OUTLET ASSEMBLY WITH
SINGLE RECEPTACLE, 120V
SPACING (X INCHES) AS NOTED,
MOUNTING HEIGHT AS NOTED
RECEPTACLE, 480V
WALL/CEILING MOUNTED
JUNCTION BOX
FLOOR RECESS MOUNTED
JUNCTION BOX
THERMOSTAT, WALL MOUNTED
WALL TELEPHONE OUTLET (+12")
DATA WALL OUTLET
TELE-DATA WALL OUTLET
FLOOR OUTLETS
FIRE ALARM PULL STATION
FIRE ALARM FLASHING LIGHT
FIRE ALARM HORN
BELL
BUZZER
HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM CONTROL PANEL
PROXIMITY SENSOR
WALL SENSOR
S SECURITY SYSTEM CONDUIT
INSTRUMENT
A
D
S
M
J
T
J
J
F
F
B
F
S
H
VIDEO CAMERA OUTLET BOXv
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLEDFLOCFLOCCULATOR, FLOCCULATION
SCADA SUPERVISORY CONTROL AND
DATA ACQUISTION
SILICON CONTROLLED RECTIFIER
TRANSIENT VOLTAGE
SURGE SUPPRESSOR
ANSI AMERICAN NATIONAL STANDARDS
SURGE-PROTECTIVE DEVICESPD
S*
Sab
ST
MCP
100AT
100AT
100AF
100
GEN
OL
**
AS
VS
2
K
#
1
5
OFFON OFFON
START STOP
START STOP
O
AH
O
RH
X2X1
H4H3H2H1
??
OL
F FIRE ALARM WITH
VISUAL
*
**
FUSE. RATING IN AMPERES
ELAPSED TIME METER
CONTROL DEVICE COIL. PREFIX NUMBER,
WHEN USED, DISTINGUISHES BETWEEN
DEVICES OF THE SAME TYPE.
ALT - ALTERNATOR
CR - CONTROL RELAY
GR - GENERAL RELAY
ISR - INTRINSICALLY
SAFE RELAY
LR - LATCH RELAY
SV - SOLENOID VALVE
PR - PROBE RELAY
TD - TIME DELAY RELAY
INDICATING LIGHT
PUSH-TO-TEST INDICATING LIGHT
COLORS:
A - AMBER
B - BLUE
C - CLEAR
G - GREEN
R - RED
N - NEON
W - WHITE
Y - YELLOW
TR - TIMING RELAY
ETM
*
1 *
**
P123
FLUOR FLUORESCENT
OVER TEMPERATUREOT
POWER QUALITY METERPQM
VFD
SS - SOLID STATE STARTERSS
IN-LINE REACTOR
SOLIDS HANDLING BUILDINGSHB
GENERATOR SETGENSET
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
2
.
d
w
g
NI
C
H
O
L
A
S
K
O
K
O
T
A
S
2/
2
8
/
2
0
1
9
1
0
:
5
7
A
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
ELECTRICAL ABBREVIATIONS,
NOTES AND LEGEND
92
MJS
MJS
SLS
SCALE: NTS
02CONDUIT TRANSITION
CONC FLOOR
FINISHED GRADE
CONC WALL
PVC-COATED
GRS
PVC-COATED
GRS COUPLING
PVC-COATED GRS
COUPLING
PVC CONDUIT
SCALE: NTS
01
WALL MOUNTED
WALL MOUNTED
AUTOMATIC
TRANSFER SWTICH
APPROX 500 LBS
MOUNT AT ±4'-0" AFF
MASONRY WALL
MANUFACTURER SHALL
PROVIDE SEISMIC
ANCHORAGE CALCULATIONS
FOR EXISTING WALL TYPE.
CONCRETE ANCHORS MUST
CONFORM TO
MANUFACTURER'S
RECEOMMENDATIONS
TRANSFER SWITCH
CONCRETE NOTES:
1.BOTTOM CLEAR COVER: 3 IN MIN
2.SIDE AND TOP COVER: 2 IN MIN
3.REINFORCING BARS SHALL BE ASTM A615-GRADE 60
4.MINIMUM 28-DAY CONCRETE STRENGTH: 4000 PSI AS MEASURED IN
ACCORDANCE WITH ASTM C39
5.TYPE II CEMENT REQUIRED W/ MAX WATER/CEMENT RATIO OF 0.42
6.MAX 1-INCH AGGREGATE
7.CONCRETE SHALL BE PLACED AND CURED BETWEEN 50 AND 90 DEGREES
F
8.PROVIDE SF-2.0 FINISH AT FORMED SURFACES IN ACCORDANCE WITH ACI
301
9.PROVIDE TROWEL FINISH AT HORIZONTAL SURFACES IN ACCORDANCE
WITH ACI 301
CONCRETE TESTING:
[X] 4 CYLINDERS PER 100 CUBIC YARDS*
TEST: 2 @ 7 DAYS, 2 @ 28 DAYS.
* EACH MIX PLACED, EACH DAY PLACED
6"
6"
12"
6" CRUSHED
ROCK
PIPE ENCASEMENT
DETAIL NOTES:
1.ENCASEMENT REINFORCEMENT SHALL BE #4@12"
UON. PROVIDE 3 INCHES (MIN) CLEAR COVER.
2.SPACE PIPES AND CONDUIT 3xDIAMETER (MIN) ON
CENTERS.ROUGH CJ
SLAB W/
TYP REINF
DEMO DETAIL
EDGE OF ENCASEMENT
(E) REINF TO REMAIN
(E) CONC TO REMAIN
DETAIL NOTES:
1.CHIP AWAY CONC AROUND REINFORCING
2.REINFORCING TO REMAIN IN PLACE UNDAMAGED
3.AFTER PLACING PIPE ENCASEMENT REPLACE
CONC IN KIND
4.AT CONTRACTOR'S OPTION, REINFORCING MAY BE
CUT AND SPLICED WITH A MINIMUM LAP SPLICE
ADHERING TO ACI 318-14.
SCALE: NTS
03CONCRETE DEMOLITION
SCALE: NTS
04PIPE ENCASEMENT
SCALE: NTS
05CONCRETE NOTES
SCALE: NTS
06TYPICAL TRENCH SECTION
18
"
3"
3" (TYP)
3"
3" (TYP)
3"
6"
3"
RED WARNING TAPE
COMPACTED FILL
INSTRUMENTATION &
SIGNAL CONDUIT (TYP)
FINISHED GRADE
SAND BACKFILL
POWER & 120V
CONTROL CONDUIT
(TYP)
ALL DIMENSIONS ARE
MINIMUMS.
1.
NOTES:
ADD 6" FOR RUNS
BENEATH ROADS.
2.
12" MIN.
SEPARATION
TO "WET"
UTILITIES
WHERE
APPLICABLE
SCALE: NTS
07TYPICAL CONDUIT STUB-UP
FINISHED GRADE
3/4" LIQUID-TIGHT
FLEXIBLE CONDUIT
AND CONNECTORS
TO FIELD INSTRUMENT
(TYPICAL)
SEE DETAIL 02
GALVANIZED RIGID
STEEL/PVC COATED
CONNECTOR &
REDUCER.
SCALE: NTS
08TYPICAL CONDUIT MOUNTING STRAP
GRS/PVC CONDUIT, TYPICAL
GRS ANCHOR BOLT
GRS 1-HOLE
CONDUIT STRAP
12"
(SEE
NOTE 2)
SCALE: NTS
09TYPICAL PIPE SLEEVE MOUNTING
(E) CONC OR MASONRY WALL
PVC SLEEVE I.D. 1/4" LARGER
THAN PIPE O.D. SLEEVE 4"
LONG
RIGID PIPE STRAP
PVC PIPE
BEING
SUPPORTED
ON EXISTING CONCRETE SLAB
NO
T
E
4
H
12"
NOTES:
1.PLACE ALL EQUIPMENT ON CONCRETE PADS (UON).
2.SEPARATE ALL STEEL SURFACES BEARING ON CONC BY 1/4-INCH
(MIN) THICK GROUT LAYER.
3.CONTRACTOR SHALL LOCATE AND AVOID DRILLING THRU EXISTING
REINFORCING STEEL.
4.THE MAXIMUM OF 8 TIMES THE BAR DIAMETER OR 3" LESS THAN THE
SLAB THICKNESS.
#3@12" EW, H <8"
#4@12" EW, 8" ≤H ≤ 10"
#5@12" EW, H >10"
3/4" CHAMFER VERTICAL
EDGES (TYP)
ROUGHENED CJ W/
EPOXY BONDING
AGENT
(E) CONC SLAB
ADHESIVE DOWEL ALL
AROUND:
#3@12" EW, H <8"
#4@12" EW, 8" ≤H ≤ 10"
#5@12" EW, H >10"
SCALE: NTS
10TYPICAL EQUIPMENT PAD
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
3
.
d
w
g
NI
C
H
O
L
A
S
K
O
K
O
T
A
S
2/
2
8
/
2
0
1
9
1
0
:
5
8
A
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
ELECTRICAL DETAILS
93
MJS
MJS
SLS
(E) MAIN CONTROL PANEL
(E) ATS
(E) MCC
(E) BUBBLER
CONTROL
PANEL
DEMOLITION
SCALE: 1/2" = 1'-0"
GENERAL NOTES:
1.REMOVE EVERYTHING ASSOCIATED WITH EXISTING
GENERATOR SYSTEM.
2.DISCONNECT AND REMOVE ALL ASSOCIATED
CONNECTIONS WITH ATS.
3.PATCH (N) EXHAUST SYSTEM TO MATCH (E)
EQUIPMENT.
4.PROVIDE WEATHER-RESISTANT, UV-RESISTANT, LAMINATED
PLASTIC SIGNS, CONFORMING TO ANSI Z535.1, AS LISTED
BELOW, FOR MOUNTING ON
EXTERIOR WALL OF BUILDING:
'DANGER' - 'COMBUSTIBLE LIQUIDS'; 10”H x 14”W
SETON M9590BBHTEDPLA, OR EQUAL
'DANGER' - 'FUEL STORAGE - NO SMOKING'; 14”H
x 10”W
SETON L3764BBVTEDPLA, OR EQUAL
5.PROVIDE WEATHER RESISTANT, UV-RESISTANT, LAMINATED
PLASTIC CHEMICAL IDENTIFICATION SIGN FOR DIESEL
FUEL, 7½” x 7½”, CONFORMING TO NFPA 704 WITH BLACKE
LETTERING AS LISTED BELOW (1 - BLUE PANEL, 2-RED
PANEL, 0-YELLOW PANEL, 'BLANK'-WHITE PANEL), FOR
MOUTNING ON EXTERIOR WALL OF BUILDING; SETON
TB0013, OR EQUAL
6.PROVIDE ADHESIVE LABEL, 9”x2”, GOLD LETTERING ON
BLACK BACKGROUND, LABELED 'DIESEL FUEL', FOR
MOUTNING ON SUB-BASE FUEL TANK; SETON 91057, OR
EQUAL.
(N) GENERATOR
(N) ATS
3'
-
6
"
MODIFICATION
SCALE: 1/2" = 1'-0"
3'
-
8
"
6'-8"
19'-4"
10
'
2'
1'
(E) MCC
(N) GENERATOR
CONCRETE
HOUSEKEEPING PAD
3'-9" x 8'-6" x 8" THICK
1
2
3
4
4
(E) BUBBLER
CONTROL
PANEL
(E) GENERATOR
PAD AND
GENERATOR
(E) EXHAUST
(SEE PHOTO
ABOVE)
(N) EXHAUST. REUSE EXISTING
OPENINGS AS PRACTICAL.
MODIFY AS NECESSARY FOR
NEW EXHAUST SYSTEM (SEE
PHOTO ABOVE)
1 1/2"C, 4#2, #8GND
3/4C, - 2#14 + #14
GND (GEN START)
(E) SERVICE
ENTRANCE
METER
MAIN
(E) SERVICE
ENTRANCE
METER
MAIN
1 1/2"C, 4#2 ,#8GND
3/4C, - 10#14 + #14 GND (GEN FAIL, GEN
RUN, FUEL LOW, LOW BATTERY, GEN
C.B. TRIP)
3/4C, - 6#14 + #14 GND (UTILITY
POWER RUN, STANDBY. POWER
RUN, NORMAL POWER FAIL)
TYPICAL OF TWO. PATCH AND PAINT
TO MATCH.
5
5
(E) GENERATOR CONTROL PANEL AND (E)
GENERATOR
(E) CONTROL PANEL. NOTE LIMITED SPACE
FOR OVERHEAD CONDUIT PENETRATIONS.
ASSUME CONDUITS SHALL ENTER FROM
THE SIDES NEAR CEILING.
(E) CONCRETE HOUSEKEEPING PAD TO BE
REPLACED AND SIZED FOR NEW
GENERATOR.
(E) EXHAUST PIPE. REPLACE THIMBLE AND
ROUTE NEW EXHAUST SIMILAR TO
EXISTING. WRAP NEW EXHAUST TO MATCH
EXISTING, PATCH SOUND MATERIAL TO
MATCH EXISTING.
(E) EXHAUST PIPE. PATCH AND PAINT TO
MATCH AS REQUIRED UPON INSTALL OF
NEW EXHAUST SYSTEM. REUSE EXISTING
OPENINGS AS PRACTICAL. MODIFY AS
NECESSARY FOR NEW EXHAUST SYSTEM
(E) GENERATOR BUILDING INTERIOR
SCALE: NTS
(E) GENERATOR EXHAUST PENETRATION
SCALE: NTS
1-1/2"C, 4#2,
#8GND
3/4C, - 4#12 + #12
GND (BATTERY
CHARGER,
JACKET HEATER)
6
6
(E) MAIN CONTROL PANEL
7
7
9
GENERATOR
CONTROL
PANEL
SHEET KEY NOTES:
DOOR AND FRAME CAN BE REMOVED IN ORDER TO
REMOVE EXISTING GENERATOR, IF NECESSARY. INSTALL
NEW FRAME WITH EXISTING DOOR UPON COMPLETION
AND INSTALLATION OF NEW GENERATOR.
REMOVE CONDUIT AND CONDUCTORS BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING CONTROL & SIGNAL
WIRES BACK TO MAIN CONTROL PANEL.
REMOVE AND REPLACE CONCRETE HOUSE KEEPING PAD
TO ACCOMMODATE MANUFACTURERS GENERATOR SIZE,
CENTER GENERATOR SUCH THAT LIVE ELECTRICAL
PARTS MEET NEC WORKING CLEARANCE SPACE.
REMOVE AND REPLACE EXISTING CEILING MOUNTED
LIGHTING FIXTURES AND CONDUIT/CONDUCTORS WITH
LITHONIA LED RTLX4 40L LP840 OR EQUAL. INSTALL NEW
CONDUIT/CONDUCTORS CONNECT TO EXISTING PANEL
PB1, CIRCUIT PB1-10 IN MCC LOCATED IN ELECTRICAL
ROOM. PANEL PB1 RECEIVES STANDBY POWER FROM
THE GENERATOR. THE PROVIDED ILLUMINATION IS
GREATER THAN 1 FOOT-CANDLE AND THEREFORE MEETS
THE REQUIREMENTS OF CBC 1008 AND CEC 700.16.
CONNECT GENERATOR BATTERY CHARGER AND JACKET
HEATER TO SAME CIRCUIT BREAKERS FOR THE EXISTING
GENERATOR.
REMOVE AND REPLACE EXISTING COOLING AIR
DUCTWORK TO ACCOMMODATE MANUFACTURERS
REQUIREMENTS.
PROVIDE 2-INCH SCH 40 GALVANIZED STEEL PIPE TO
EXTEND VENT THROUGH ROOF OF BUILDING. TERMINATE
VENT PIPE 12 INCHES ABOVE ROOF PENETRATION.
PROVIDE CARB APPROVED ACCESSORY VENT CAP.
PROVIDE UL-LISTED 3A : 408 : C FIRE EXTINGUISHER WITH
ACCESSORY WALL MOUNTED BRACKET.
8
9
FE
35
(E) LOUVER (2'-8" W x 4'-0" H,
TOL @ 5'-4" AFF)
(N) 30 KW ENGINE-GENERATOR
W/ UL 142 DOUBLE-WALLED
SUB-BASE FUEL TANK
168-GALLON CAPACITY
(E) LOUVER (2'-8"W x 4'-0" H,
TOL @ 5'-4"AFF)
(E) LOUVER
(4'-0" SQUARE,
TOL @ 4'-8" AFF)
2" ENGINE EXHAUST
RADIATOR EXHAUST OUTLET
GRILLE
(E) TURBINE VENTILATOR @ ROOF
EDGE OF ROOF GUTTER
EDGE OF ROOF GUTTER
8
1
2
2
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
4
.
d
w
g
CH
E
R
Y
L
L
O
V
E
1/
1
2
/
2
0
2
1
1
1
:
2
2
A
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
KNOTS LANE LIFT STATION
ELECTRICAL PLANS
94
MJS
MJS
SLS
A
9
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
M
2
7.5 "PB1"
PANEL
100A
3P
GEN
2
7.5
60A
3P
60A
3P
50A
3P
(E) SERVICE ENTRANCE METER AND MAIN DISCONNECT
100A, 120/208V, 3Ø, 4W
(E) MOTOR CONTROL CENTER "MCC"
125A, 120/208V, 3Ø, 4W, 42KAIC BRACING
PACKAGED STANDBY
GENERATOR SET
100A, 120/208V,
3Ø, 4W, 3P
ATS
(E) SDG&E
DISTRIBUTION
3P
(E) SDG&E
3Ø PADMOUNT
TRANSFORMER
120/208V 120/208V, 3Ø, 4W
20KW (25KVA)
35
FRN
35
FRN
GND BUS
SE
W
A
G
E
P
U
M
P
P-
1
SE
W
A
G
E
P
U
M
P
P-
2
M
2
7.5 "PB1"
PANEL
100A
3P
GEN
2
7.5
60A
3P
60A
3P
50A
3P
(E) SERVICE ENTRANCE METER MAIN
100A, 120/208V, 3Ø, 4W
(E) MOTOR CONTROL CENTER "MCC"
125A, 120/208V, 3Ø, 4W, 42KAIC BRACING
LEGALLY-REQUIRED
STANDBY GENERATOR
100A, 120/208V,
3Ø, 3P, 35 KAIC
ATS
(E) SDG&E
DISTRIBUTION
(E) SDG&E
3Ø PADMOUNT
TRANSFORMER
120/208V 120/208V, 3Ø, 4W
30KW (37.5KVA)
35
FRN
35
FRN
SE
W
A
G
E
P
U
M
P
P-
1
SE
W
A
G
E
P
U
M
P
P-
2
(E) SERVICE
ENTRANCE
METER MAIN
(E) FEEDER TO (E) ATS
TO BE REMOVED.
AFTER INSTALLING
NEW, PATCH AND
PAINT WALL TO MATCH
EXISTING
NEUTRAL
GND BUS
N
N
N
NG
4#2, 1#8GND
GENERAL NOTES:
1.ALL ELECTRICAL EQUIPMENT SHALL BE FULLY-RATED. SERIES-RATED
EQUIPMENT SHALL NOT BE USED.
SHEET KEY NOTES:
CONNECT NEW GENERATOR TO EXISTING BUILDING GROUNDING
ELECTRODE SYSTEM.
AVAILABLE FAULT CURRENT IS 42 KA.
1
2
2
4#2, 1#8GND
4#2, 1#8GND
MIN #8 AWG
1
100A
3P
DEMOLITION MODIFICATION
(E) SERVICE ENTRANCE METER MAIN
N.T.S.
KNOTS LANE LIFT STATION
ELECTRICAL SINGLE LINE
DIAGRAMS
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
5
.
d
w
g
NI
C
H
O
L
A
S
K
O
K
O
T
A
S
12
/
2
1
/
2
0
2
0
3
:
4
9
P
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
95
MJS
MJS
SLS
ELECTRICAL
ROOM
(E) PUMP CONTROL
PANEL (PCP)
(E
)
A
T
S
(E
)
M
C
C
(E) MAIN
SWITCHBOARD
(N
)
G
E
N
E
R
A
T
O
R
ELECTRICAL
ROOM
26'
19
'
-
4
"
5'
11
'
2'
-
6
"
1'-6"
7'-4"
3'
-
4
"
(E) PUMP CONTROL
PANEL (PCP)
(E) MAIN
SWITCHBOARD
1
2
1 (N) REMOTE
RADIATOR
4
5
6
3
275 GALLON
400
GALLON
TANK
10'
8'
-
8
"
8"
8"
(N
)
A
T
S
(E
)
M
C
C
8'
-
8
"
4'-6"
(E) GENERATOR
7
8
7
LSL
AUXILIARY
RADIATOR
ROOM
AUXILIARY
RADIATOR
ROOM
3/4"C, 10#14, #14GND (GEN
FAIL, GEN RUN, FUEL LOW,
LOW BATTERY, GEN C.B. TRIP)
3/4"C, - 6#14, #14GND
(UTILITY POWER
RUN, STANDBY
POWER RUN,
NORMAL POWER
FAIL)
3/4"C, 2#14,
#14GND
(GEN START)
3/4"C, 4#12, 1#12G
(BATTERY CHARGER,
JACKET HEATER)
(2) 3"C, 3#300MCM,
#1GND
(2) 3"C, 4#300MCM,
#1GND
3/4"C, 2#14
(E) DISCONNECT
SWITCH
9
10
SEE PHOTO ON
SHEET 8
(2) 3"C, 4#300MCM,
#1GND
GENERATOR
CONTROL
PANEL
M
(E) EXHAUST FANS
(N) GENERATOR
PAD
1"C, 4#12, #12GND
TO LP-A
14
(E) GENERATOR
RADIATOR
12
(N) DISCONNECT
SWITCH/CONTROLLER
15
M M
(N) EXHAUST FANS
M
16
18
FUEL TANK SCREENING
STRUCTURE
(N) 200 KW ENGINE - GENERATOR W/ UL 142
DOUBLE-WALLED SUB-BASE DIESEL FUEL
TANK, 240-GALLON CAPACITY
19
UL-142 RECTANGULAR,
FREE-STANDING
DOUBLE-WALLED
DIESEL FUEL TANK
17
FUEL
SUMP
AIR
VENT
FU
E
L
SU
M
P
(2) 3/4 UNDERGROUND CONDUIT
(1) TSP FROM LEAK DETECTOR
CONTROL PANEL TO FUEL TANK
LEAK DETECTOR, (2)#14, (1) #14G
FROM TANK LSL TO PUMP CONTROL
PANEL
FLOOR DRAIN
REMOTE
RADIATOR
CONTROL
PANEL
1/2 INCH COPPER PIPE
FROM RADIATOR TO
GENERATOR
LEAK DETECTOR
CONTROL PANEL
(1) 3/4 CONDUIT
(2) #14, (1)#14G
RADIATOR STARTER TO
GEN CONTROL PANEL
(1) 3/4 CONDUIT
(2)#12, (1) #14G TANK
LSL TO GENERATOR
FUEL TANK LSL J-BOX
(2) 1 INCH FRANKLN
XP UNDERGROUND FUEL
LINES FROM GENERATOR
SUPPLY AND RETURN
PUMPS TO EXTERNAL
FUEL TANK
3/4 CONDUIT
(14)#14, (1) #14G
GEN TO VERBATIM
3/4 CONDUIT
(4)#14, (1) #14G LEAK SENSOR
TO VERBATIM
VERBATIM
FUEL LINES
ABANDON IN PLACE.
CUT FRESH, GROUT
CAPPED. PER RFI
3/4 CONDUIT
(4)#12, (1) #12G
FUEL PUMPS
TO LP-A RADIATOR
LSL J-BOX
(1) 3/4 CONDUIT (1) TSP RADIATOR
LSL TO GENERATOR J-BOX
(1) 3/4 CONDUIT
(1) FACTORY CABLE LEAK SENSOR TO
LEAK DETECTOR CONTROL PANEL
3/4 CONDUIT
(2)#12, (1) #12G LEAK
SENSOR TO LP-A
FUEL PUMPS AND SUMP PUMP
DEMOLITION
SCALE: 3/8" = 1'-0"
MODIFICATION
SCALE: 3/8" = 1'-0"
SHEET KEY NOTES:
REMOVE EXISTING GENERATOR AND AUTOMATIC TRANSFER SWITCH
CONDUIT AND CONDUCTORS BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING GENERERATOR CONTROL & SIGNAL
WIRES BACK TO PUMP CONTROL PANEL.
EXISTING CONCRETE HOUSEKEEPING PAD REUSED W/ 12-INCH EXTENSION
POURED ON THE WEST END.
FIELD VERIFY EXACT LOCATION OF EXISTING FUEL TANK FOR DEMOLITION
AND REMOVAL. INSTALL NEW TANK AT SAME LOCATION AND CONFIRM
SPACE REQUIREMENTS.
DEMOLISH AND REPLACE REMOTE RADIATOR, DISCONNECT SWITCH AND
ALL ASSOCIATED CONTROLS AND PIPING.
DISCONNECT AND SEAL WITH NON-SHRINK GROUT AT GROUND LEVEL,
PIPING AND CONDUIT TO PREVENT DIRT AND OTHER HINDRANCES.
FUELD LINES ABANDONED IN PLACE. CUT FLUSH AND GROUT CAPPED.
CONNECT GENERATOR BATTERY CHARGER AND JACKET HEATER TO SAME
CIRCUIT BREAKERS FOR THE EXISTING GENERATOR.
CONTRACTOR MAY REPLACE INTERNALS IN THE EXISTING MCC SECTION
HOUSING THE AUTOMATIC TRANSFER SWITCH. PROVIDE ALL NECESSARY
HARDWARE TO ASSURE MOTOR CONTROL CENTER IS ENCLOSED TO
EXISTING NEMA RATING.
REMOVE AND REPLACE (E) EXHAUST FANS IN KIND.
NOT USED.
GENERATOR MANUFACTURER TO INSTALL GENERATOR CONTROLLER AND
DISCONNECT FACING DOOR OR ENSURE 36" CLEARANCE TO WALL.
NOT USED.
NOT USED.
CONTRACTOR MAY UTILIZE (E) PIPING PENETRATIONS AT FLOOR LEVEL OR
CORE DRILL (2) SEPARATE 3" MAX PENETRATIONS FOR NEW PIPING FROM
GENSET TO REMOTE RADIATOR.
CONTRACTOR SHALL ADD EQUIPMENT PAD PER DETAIL 10 FOR NEW
EXTERIOR FUEL TANK WITH DOUBLE WALL SECONDARY CONTAINMENT.
MINIMUM 6" EDGE DISTANCE FOR ANCHORS.
PROVIDE 2-INCH, SCH 40, GALVANIZED STEEL PIPE TO EXTEND VENT
THROUGH ROOF OF BUILDING. TERMINATE VENT PIPE 12-INCHES ABOVE
ROOF PENETRATION. PROVIDE CARB APPROVED ACCESSORY VENT CAP.
PROVIDE UL-LISTED 3A:40B:C FIRE EXTINGUISHER WITH ACCESSORY WALL
MOUNTING BRACKET.
PROVIDE 2-INCH, SCH 40, GALVANIZED STEEL PIPE TO EXTEND VENT TO
TERMINATE AT A HEIGHT NOT LESS THAN 12-FEET ABOVE GRADE. PROVIDE
CARB APPROVED ACCESSORY VENT CAP.
1
2
3
4
5
6
7
8
9
10
NORTH BATIQUITOS LIFT STATION
ELECTRICAL PLANS
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
6
.
d
w
g
CH
E
R
Y
L
L
O
V
E
1/
1
2
/
2
0
2
1
1
1
:
3
5
A
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
96
MJS
MJS
SLS
11
12
13
14
15
16
17
18
19
GENERAL NOTES:
1.REMOVE EVERYTHING ASSOCIATED WITH EXISTING GENERATOR SYSTEM.
2.DISCONNECT AND REMOVE ALL ASSOCIATED CONNECTIONS WITH ATS.
3.PATCH (N) EXHAUST SYSTEM TO MATCH (E) EQUIPMENT.
4.REMOVE AND REPLACE EXISTING CONDUIT AND CEILING MOUNTED
LIGHTING FIXTURES WITH LITHONIA MODEL# RTLX4 40L EZ1 LP840 N80 EL7L
CONNECTED TO EXISTING PANEL LPA CIRCUIT LPA-1 IN MCC LOCATED IN
ELECTRICAL ROOM, GENERATOR ROOM AND RADIATOR ROOM.
5.PROVIDE WEATHER-RESISTANT, UV-RESISTANT, LAMINATED PLASTIC
SIGNS, CONFORMING TO ANSI Z535.1, AS LISTED BELOW, FOR MOUNTING
ON EXTERIOR WALL OF PUMP STATION BUILDING AND OUTDOOR FUEL
TANK ENCLOSURE:
'DANGER' - 'COMBUSTIBLE LIQUIDS'; 10”H x 14”W
SETON M9590BBHTEDPLA, OR EQUAL
'DANGER' - 'FUEL STORAGE - NO SMOKING'; 14”H x 10”W
SETON L3764BBVTEDPLA, OR EQUAL
6.PROVIDE WEATHER RESISTANT, UV-RESISTANT, LAMINATED PLASTIC
CHEMICAL IDENTIFICATION SIGN FOR DIESEL FUEL, 7½” x 7½”,
CONFORMING TO NFPA 704 WITH BLACKE LETTERING AS LISTED BELOW
(1 - BLUE PANEL, 2-RED PANEL, 0-YELLOW PANEL, 'BLANK'-WHITE PANEL),
FOR MOUTNING ON EXTERIOR WALL OF PUMP STATION BUILDING AND
OUTDOOR FUEL TANK ENCLOSURE; SETON TB0013, OR EQUAL.
7.PROVIDE ADHESIVE LABEL, 9”x2”, GOLD LETTERING ON BLACK
BACKGROUND, LABELED 'DIESEL FUEL', FOR MOUTNING ON SUB-BASE FUEL
TANK AND OUTDOOR FUEL TANK; SETON 91057, OR EQUAL.
B
9
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
MODIFICATION
M
100
800AF
600AT
GEN
150A
MCP
(E) MOTOR CONTROL CENTER "MCC-1"
480V, 3Ø, 3W, 600A, 50KAIC
PACKAGED STANDBY
GENERATOR SET
600A, 480V,
3Ø, 3P
ATS
(E) SDG&E
DISTRIBUTION
3P
(E) SDG&E
3Ø PADMOUNT
TRANSFORMER
480/277V 480V, 3Ø, 4W
200KW
RVAT
WA
S
T
E
W
A
T
E
R
PU
M
P
P
-
1
100
150A
MCP
RVAT
WA
S
T
E
W
A
T
E
R
PU
M
P
P
-
2
100
150A
MCP
RVAT
WA
S
T
E
W
A
T
E
R
PU
M
P
P
-
3
3/4
3A
MCP
SU
M
P
P
U
M
P
P
-
4
1
3/4
3A
MCP
SU
M
P
P
U
M
P
P
-
5
1
3/4
3A
MCP
DR
Y
W
E
L
L
SU
P
P
L
Y
F
A
N
S
F
-
1
1
1/2
3A
MCP
DR
Y
W
E
L
L
EX
H
A
U
S
T
F
A
N
E
F
-
1
1
1/2
3A
MCP
WE
T
W
E
L
L
SU
P
P
L
Y
F
A
N
S
F
-
2
1
1/2
3A
MCP
WE
T
W
E
L
L
SU
P
P
L
Y
F
A
N
E
F
-
2
1
2
150AF
15AT
WE
T
W
E
L
L
GR
I
N
D
E
R
G
R
-
1
1-1/2
7A
MCP
SE
A
L
W
A
T
E
R
PU
M
P
P
-
6
5
HY
D
R
A
U
L
I
C
U
N
I
T
GR
-
1
1-1/2
7A
MCP
SE
A
L
W
A
T
E
R
PU
M
P
P
-
7
1 1
1-1/2
150AF
15AT
SU
R
G
E
T
A
N
K
AI
R
C
O
M
P
R
E
S
S
O
R
AC
-
1
15 KVA
480-120/208
3Ø
A
LP
150AF
30AT
M
100
800AF
600AT
GEN
150A
MCP
(E) SWITCHBOARD "SE"
800A, 480/277, 3Ø, 4W
(E) MOTOR CONTROL CENTER "MCC-1"
480V, 3Ø, 3W, 600A, 50KAIC
LEGALLY-REQUIRED
STANDBY GENERATOR
600A, 480V,
3Ø, 3P, 50 KAIC
ATS
(E) SDG&E
DISTRIBUTION
300A/3P
(E) SDG&E
3Ø PADMOUNT
TRANSFORMER
480/277V 480V, 3Ø, 4W
200KW
RVAT
WA
S
T
E
W
A
T
E
R
PU
M
P
P
-
1
100
150A
MCP
RVAT
WA
S
T
E
W
A
T
E
R
PU
M
P
P
-
2
100
150A
MCP
RVAT
WA
S
T
E
W
A
T
E
R
PU
M
P
P
-
3
3/4
3A
MCP
SU
M
P
P
U
M
P
P
-
4
1
3/4
3A
MCP
SU
M
P
P
U
M
P
P
-
5
1
3/4
3A
MCP
DR
Y
W
E
L
L
SU
P
P
L
Y
F
A
N
S
F
-
1
1
1/2
3A
MCP
DR
Y
W
E
L
L
EX
H
A
U
S
T
F
A
N
E
F
-
1
1
1/2
3A
MCP
WE
T
W
E
L
L
SU
P
P
L
Y
F
A
N
S
F
-
2
1
1/2
3A
MCP
WE
T
W
E
L
L
SU
P
P
L
Y
F
A
N
E
F
-
2
1
2
150AF
15AT
WE
T
W
E
L
L
GR
I
N
D
E
R
G
R
-
1
1-1/2
7A
MCP
SE
A
L
W
A
T
E
R
PU
M
P
P
-
6
5
HY
D
R
A
U
L
I
C
U
N
I
T
GR
-
1
1-1/2
7A
MCP
SE
A
L
W
A
T
E
R
PU
M
P
P
-
7
1 1
1-1/2
150AF
15AT
SU
R
G
E
T
A
N
K
AI
R
C
O
M
P
R
E
S
S
O
R
AC
-
1
15 KVA
480-120/208
3Ø
A
LP
150AF
30AT
DEMOLITION
(E) SWITCHBOARD "SE"
800A, 480/277, 3Ø, 4W
N
N
NG
GENERAL NOTES:
1.ALL ELECTRICAL EQUIPMENT SHALL BE FULLY-RATED. SERIES-RATED
EQUIPMENT SHALL NOT BE USED.
SHEET KEY NOTES:
CONNECT NEW GENERATOR TO EXISTING BUILDING GROUNDING
ELECTRODE SYSTEM.
AVAILABLE FAULT CURRENT IS 30 KA.
1
2
2 SETS:
3-300MCM, 1#1GND
2 SETS:
4-300MCM, 1#1GND
MIN #1/0 AWG
1
2 SETS:
4-300MCM, 1#1GND2
NORTH BATIQUITOS LIFT STATION
ELECTRICAL SINGLE LINE
DIAGRAMS
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
7
.
d
w
g
NI
C
H
O
L
A
S
K
O
K
O
T
A
S
2/
2
8
/
2
0
1
9
2
:
2
2
P
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
97
MJS
MJS
SLS
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
(E) GENERATOR
CONTROL PANEL
(E) GENERATOR
(E) CONCRETE
HOUSEKEEPING PAD TO
BE REPLACED AND SIZED
FOR NEW GENERATOR.
(E) EXHAUST PIPE. REPLACE
THIMBLE AND ROUTE NEW
EXHAUST SIMILAR TO EXISTING.
WRAP NEW EXHAUST TO
MATCH EXISTING CEILING,
ROOF, PATCH SOUND MATERIAL
TO MATCH EXISTING.
(E) LIGHT FIXTURES
( TYP 8)
(E) GENERATOR ROOM
N.T.S
(E) ELECTRICAL ROOM
N.T.S
(E) GENERATOR ROOM
N.T.S
(E) GENERATOR ROOM
N.T.S
(E) FUEL TANK
N.T.S
(E) FUEL TANK
(E) FUEL TANK LINES
TO GENERATOR
SAWCUT (E) CONDUIT
AND SEAL FOR
PROTECTION.
(E) RADIATOR
(E) DISCONNECT
SWITCH
(E) AUXILIARY RADIATOR ROOM
N.T.S
(E) ATS
NORTH BATIQUITOS LIFT STATION
ELECTRICAL DETAIL PHOTOS
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
8
.
d
w
g
NI
C
H
O
L
A
S
K
O
K
O
T
A
S
12
/
2
1
/
2
0
2
0
3
:
5
1
P
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
98
MJS
MJS
SLS
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS
(E) CONCRETE
ROOF TILE
(E) RAFTER
4
12
5'-0"
2'-0"
OVERHANG
(E) 14" THICK
CONCRETE SLAB
(E) GENERATOR
PAD(E) AC
PAVEMENTFINISH GRADE
(E) CONCRETE
SLAB
SCALE: 3/8" = 1'-0"
POSSIBLE ROUTE FOR
FUEL VENT, SEE NOTE 1.POSSIBLE ROUTE FOR
FUEL VENT, SEE NOTE 1.
(E) EXHAUST AND
WALL PENETRATION
4
AKNOTS LANE GENERATOR BLDG SECTION
SCALE: 3/8" = 1'-0"6
BNORTH BATIQUITOS GENERATOR BLDG SECTION
4
3
2
1
0
0
USE OF DOCUMENTS
25mm
SCALES
1"
0
D E F G HABC
IF THIS BAR IS NOT
DIMENSION SHOWN,
ADJUST SCALES
ACCORDINGLY.
THIS DOCUMENT, INCLUDING THE INCORPORATED
DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS
PROJECT AND SHALL NOT BE USED FOR ANY OTHER
PROJECT WITHOUT THE WRITTEN AUTHORIZATION
OF KENNEDY/JENKS CONSULTANTS.
C:
\
b
m
s
\
k
j
c
e
-
p
w
\
d
m
s
7
6
8
7
4
\
1
5
4
4
1
0
6
-
9
.
d
w
g
CH
E
R
Y
L
L
O
V
E
1/
1
2
/
2
0
2
1
1
1
:
5
1
A
M
LIFT STATION GENERATOR REPLACEMENT
IMPROVEMENT PLAN FOR:
BUILDING SECTIONS
99
MJS
MJS
SLS
NOTE:
1.ROUTE FUEL TANK VENT PIPE OUTSIDE OF THE BUILDING AND NOT LESS
THAN TWELVE (12) FEET ABOVE THE FINISHED GROUND LEVEL AND NOT
LESS THAN FIVE (5) FEET HORIZONTALLY FROM PROPERTY LINES. REPAIR
INTERIOR ACOUSTICAL TREATMENT TO MATCH EXISTING. PATCH
EXTERIOR AND PAINT AS REQUIRED. SUBMIT PROPOSED PENETRATION
LOCATION FOR APPROVAL PRIOR TO PERFORMING WORK.
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION
PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS
NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED
TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE
RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF
LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC
FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER
CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR
PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND
SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE
CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS.
RECORD DRAWINGS