HomeMy WebLinkAboutDWG 508-7; 3840; KNOTS AND NORTH BATIQUITOS LIFT STATION GENERATOR REPLACEMENTS; 01-09VICINITY MAP PROJECT SITE LOCATION MAPS KNOTS LANE LIFT STATION NORTH BATIQUITOS LIFT STATION LIFT STATION GENERATOR REPLACEMENT PROJECT KNOTS LANE LIFT STATION NORTH BATIQUITOS LIFT STATION C.I.P. 3840-12 CITY OF CARLSBAD CARLSBAD, CALIFORNIA MARCH 2018 DRAWING INDEX SHEET NO.DESCRIPTION 1 TITLE, DRAWING INDEX, VICINITY AND LOCATION MAPS 2 ELECTRICAL ABBREVIATIONS, NOTES AND LEGEND 3 ELECTRICAL DETAILS 4 KNOTS LANE LIFT STATION ELECTRICAL PLANS 5 KNOTS LANE LIFT STATION ELECTRICAL SINGLE LINE DIAGRAMS 6 NORTH BATIQUITOS LIFT STATION ELECTRICAL PLANS 7 NORTH BATIQUITOS LIFT STATION ELECTRICAL SINGLE LINE DIAGRAMS 8 NORTH BATIQUITOS LIFT STATION ELECTRICAL DETAIL PHOTOS 9 BUILDING SECTIONS 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 1 . d w g NI C H O L A S K O K O T A S 12 / 2 1 / 2 0 2 0 3 : 4 1 P M IMPROVEMENT PLAN FOR: LIFT STATION GENERATOR REPLACEMENT THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS 91 MJS MJS SLS TITLE, DRAWING INDEX, VICINITY AND LOCATION MAPS DISTR MANUFACTURER MOTOR CONTROL CENTER MANHOLE MOTOR OPERATED VALVE MISCELLANEOUS NORMALLY CLOSED MOTOR STARTER MOUNTING MOUNTED MANUFACTURER'S ASSOC. NOT IN CONTRACT NOT TO SCALE NATIONAL ELECTRICAL MOTOR CIRCUIT PROTECTOR NORMALLY OPEN, NUMBER MANUAL TRANSFER SWITCH NATIONAL ELECTRICAL CODE THIS IS A GENERALIZED LEGEND SHEET. THIS CONTRACT MAY NOT USE ALL INFORMATION SHOWN. NOTIFY THE ENGINEER IMMEDIATELY IF CONFLICTS IN EQUIPMENT LOCATIONS ARE DISCOVERED OR IF PROBLEMS ARISE DUE TO FIELD CONDITIONS, LACK OF INFORMATION OR ANY OTHER REASON. NO PAYMENT WILL BE MADE FOR CHANGES WHICH HAVE NOT BEEN FAVORABLY REVIEWED BY THE ENGINEER. THESE DRAWINGS ARE DIAGRAMMATIC ONLY; EXACT LOCATIONS OF ELECTRICAL EQUIPMENT SHALL BE DETERMINED IN THE FIELD BY THE ENGINEER. THE INSTALLATION OF ALL EQUIPMENT SHOWN ON THESE DRAWINGS OR DESCRIBED IN THE SPECIFICATIONS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE LATEST EDITIONS OF ALL APPLICABLE CODES AND UTILITY COMPANY STANDARDS. CONTACT THE UTILITY COMPANY REPRESENTATIVES AND VERIFY THEIR REQUIREMENTS. CONDUIT SIZE AND FILL SHALL BE AS INDICATED. WHERE NO SIZE IS SHOWN, THE CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE EDITION OF THE NATIONAL ELECTRICAL CODE ADOPTED BY THE AUTHORITY HAVING CODE ENFORCEMENT JURISDICTION. WHERE NO FILL IS INDICATED, THE FILL SHALL BE 2#12. PROVIDE 3/16 INCH NYLON PULL ROPE IN EACH EMPTY CONDUIT. PLAN NOTES: P1. ELAPSED TIME METERETM FIRE ALARM CONTROL PANEL GENERAL NOTES: G1. FACP FDR FEEDER G3. G2. NTS NIC NO DISTRIBUTION PANEL ELECTRICAL HANDHOLE ELECTRIC, ELECTRICAL EHH EQ EQPT EFFL ENCL EMERG ELEM ELEC EL, ELEV EFFLUENT ENCLOSURE EQUIPMENT EQUAL ELEVATION ELEMENTARY EMERGENCY EA EF DWG (E) DP DN DRAWING EXISTING EXHAUST FAN EACH DISTRIBUTION DOWN NC NEMA NEUT NEC NEUTRAL MTS (N) MTD MTG NEW MH MOV MS MIN MISC MINIMUM MFR MCP MAX MCC MAXIMUM WATERTIGHT TRANSFORMER WATER TREATMENT PLANT INFORMATION SHOWN MAY NOT BE ALL INCLUSIVE. SEE ALSO ANSI C37.2, Y1.1, Y32.2, AND Y32.9. VERIFY ALL COLOR REQUIREMENTS BEFORE ORDERING MATERIALS. G5. G4. XFMR WT WTP TEMPERATURE TELEPHONE UNDERGROUND UNIT HEATER ULTRA VIOLET TYPICAL VOLT-AMPERES VAR-HOUR WIRE, WATTS VERTICAL VOLTS TWISTED SHIELDED PAIR WATTHOUR METER VOLT AMPERES REACTIVE VOLTMETER SWITCH VARIABLE FREQUENCY DRIVE WEATHERPROOF WATTHOUR DEMAND METER VS WHDM WP W WHM VERT VH VAR VFD UG UV VA V UH TEMP TSP TYP TEL FA T FEET, FOOT FREQUENCY GALVANIZED FORWARD GENERATOR HYDROGEN PEROXIDE HAND-OFF-REMOTE HORSEPOWER HORIZONTAL HANDHOLE HAND-OFF-AUTOMATIC HIGH VOLTAGE INPUT/OUTPUT INDICATING LIGHT HIGH PRESSURE SODIUM KILOVOLTS KILOAMPERES KILOVOLT AMPERES LIGHTING PANEL KILOWATT HOURS LOW PRESSURE SODIUM KILOWATTS JUNCTION BOX GALVANIZED RIGID STEEL ABBREVIATIONS KILOVOLT AMPERES REACTIVE THOUSANDS OF CIRCULAR MILS INSTRUMENT, INSTRUMENTATION HERTZ (CYCLES PER SECOND) FULL VOLTAGE, NON REVERSING HUMAN MACHINE INTERFACE GROUND FAULT INTERRUPTER FULL VOLTAGE, REVERSING LIGHTING CONTROL PANEL MILLIAMPERES CONTROL POWER TRANSFORMER CONTINUED, CONTINUATION CURRENT TRANSFORMER CWP DISC DIAG DIA DC CS CT CR CP COLD WATER PIPE DIAGRAM DIRECT CURRENT DISCONNECT DIAMETER CONTROL SWITCH CONTROL RELAY CONTROL PANEL CO CPT CONT COMM COND CKT CL CONDUIT ONLY CONDUCTOR COMMUNICATION CHLORINE CIRCUIT LPS LT(S) (M) mA LTG LIGHT(S) MODIFIED LIGHTING LP LCP KWH KW KV KVAR KVA KCMIL KA I/O JB AUTO/MANUAL CONTROLLER CIRCUIT BREAKER AUX. CONTACT, AMERICAN WIRE GAGE CLOSED WHEN BREAKER IS OPEN AUTOMATIC TRANSFER SWITCH CONDUIT, CONTACTOR CONTROL CABLE, CLOSING COIL BARE COPPER GROUND C CC CB CAB CAP BLDG BCG b CABINET CIRCUIT BREAKER CAPACITOR BUILDING AT AWG AUX AUTO ATS APPROX AS A/M AMMETER TRIP AUTOMATIC AUXILIARY APPROXIMATE INSTITUTE AMMETER SWITCH HV IND LT INSTR HZ HTR HPS HORIZ HP HEATER H O HMI HOR HOA 22 HH GND GRS GEN GFI GROUND CIRCUIT BREAKER AUX. CONTACT, AMMETER, AMPERES ALTERNATING CURRENT ANALOG TO DIGITAL CLOSED WHEN BREAKER IS CLOSED AMPERES INTERRUPTING CAPACITY ABOVE FINISHED FLOOR ADJUSTABLE FREQUENCY DRIVEAFD AIC ALT AL AFF ADJ AF A/D AC ALUMINUM ALTERNATOR ADJUSTABLE AMPERE FRAME a A FVNR FWD GALV GA FVR GAUGE (F) FU FREQ FT FUSE FUTURE PLC PROGRAMMABLE LOGIC CONTROLLER 3/4"C-3#12 SECTION SUPPLY FAN SHEET SOLID NEUTRAL SIGNAL SWITCH SYNCHRONIZING SWITCHGEAR SWITCHBOARD SPECIFICATIONS SECONDS, SECONDARY SINGLE POLE, DOUBLE THROW TERMINAL BOX, TERMINAL BOARD STAINLESS STEEL, SOLID STATE SIGNAL HANDHOLE TELEPHONE CABINET SWBD SWGR SYNC TB TC SPDT SPECS SW SS SF SN SIG SHH SHT SECT SEC PANEL PANELBOARD RELOCATE RELOCATED RECEPTACLE POWER ROOM REQUIRED RESET TIMER PRESSURE SWITCH REVOLUTIONS PER MINUTE POLYVINYL CHLORIDE REPEAT CYCLE TIMER POUNDS PER SQUARE INCH PRIMARY RT SCR RM RPM RCPT (RLD) REQD RCT PS PWR (RL) PVC PSI PNLBD PRI PNL PHOTOELECTRIC PHASE POWER FACTOR PHOTOELECTRIC CELL PULLBOX, PUSHBUTTON MEASURE OF ACIDITY OR ALKALINITY POSITIVE DISPLACEMENT PH PF pH PE PEC PB PD PLAN SYMBOLS OH ELEMENTARY DIAGRAM SYMBOLS TVSS FINISHED FLOORFF FLEX FLEXIBLE OVERHEAD OPERATOR INTERFACE TERMINAL THERMAL OVERLOAD RELAY OH OL OIT DELAYED ELEMENTARY DIAGRAMS NAMEPLATE INSCRIPTIONS. NUMBERS AND LETTERS IDENTIFY DEVICE. DEVICE. ANY ADDITIONAL NAMEPLATES ARE LIGHT, SELECTOR SWITCH, ETC. INDICATE THE "NORMAL" STATUS OF SWITCHES OR CONTACTS IS LEGEND PLATE REQUIREMENT FOR THAT PARTICULAR INDICATED ON ELEVATIONS WITH THE REQUIRED UNDERLINED WORDS SHOWN AT A PUSHBUTTON, E3 E2 THE SHELF POSITION. E1 CLOSED INSTANTANEOUS OPEN TO CLOSE ON REACHING LIMIT CLOSE ON LEAVING LIMIT TIMED CONTACTS CLOSED DELAYED INSTANTANEOUS INSTANTANEOUS LIMIT SWITCHES NORMALSYMBOL CLOSED OPEN OPEN CLOSED TO DELAYED DELAYED INSTANTANEOUS OPEN SENSING SWITCHES RISING CLOSE ON FALLING TEMPERATURE PRESSURE LEVEL SENSED VARIABLE FLOW ON THE OTHER DIAGRAM IF OMITTED, THEN THE SPEC. NORMALLY CLOSED CONTACT SPARE CONTACTS APPLY. REQUIREMENTS REGARDING SPARE CONTACTS ON RELAY. ON THIS DIAGRAM CROSS REFERENCE TO NORMALLY OPEN CONTACT ANOTHER DIAGRAM SINGLE LINE SYMBOLS MOTOR STARTER NUMBER INDICATES NEMA SIZE POWER CIRCUIT BREAKER DRAWOUT ABOVE 1500V RATING AS NOTED CR 1 2-2, 3, 0, 0 FS FS LS LS TS TS ZS ZS TR TR TR TR SMS SAP EMH EHH SHH X " FACP SOLID CIRCLE DENOTES DOWNWARD CONDUIT RISER COMBINATION MOTOR STARTER FIBER OPTICFO PSPS GROUND CONNECTION SWITCH, 3 POLE EXCEPT WHERE NOTED. RATING IN AMPERES AS NOTED AUTOMATIC TRANSFER SWITCH 3 POLE, RATING AS NOTED SHUNT TRIP FUSE FUSE CUTOUT CIRCUIT BREAKER, 3 POLE EXCEPT WHERE NOTED. RATING IN AMPERES AS NOTED. IF TWO RATINGS APPEAR (EG. 100/625) THEN DEVICE IS MCP; NUMERATOR IS CONTINUOUS CURRENT RATING & DENOMINATOR IS INSTANTANEOUS TRIP SETTING. SURGE ARRESTER CURRENT TRANSFORMER VOLTAGE TRANSFORMER POWER OR DISTRIBUTION TRANSFORMER RATING AS NOTED MOTOR. NUMBER INDICATES HORSEPOWER GENERATOR CONTROL PACKAGE PROVIDED WITH THE DRIVEN EQUIPMENT BUS STAB ON MCC OR SWITCHGEAR, CORD & PLUG CONNECTION FOR MOTORS THERMAL OVERLOAD A - AMMETER V - VOLTMETER WH - WATTHOUR METER GS - GROUND FAULT SENSOR AMMETER SWITCH VOLTMETER SWITCH ELEMENTARY DIAGRAM REFERENCE NUMBER KIRK KEY INTERLOCK POWER RECEPTACLE FOR PORTABLE EQUIPMENT RELAY DEVICE FUNCTION, # PER ANSI NUMBER C37.2 TERMINATOR / POTHEAD SPLICE, TERMINATION CAPACITOR - KVAR INDICATED VFD - VARIABLE FREQUENCY DRIVE SINGLE POLE SWITCH NORMALLY OPEN / CLOSED EMERGENCY PUSHBUTTON NORMALLY OPEN / CLOSED PUSHBUTTON NORMALLY OPEN / CLOSED SWITCH 1-POLE / 3-POLE MULTI-POSITION SELECTOR SWITCH HAND-OFF-AUTOMATIC SWITCH X-INDICATES CONTACTS CLOSED HAND-OFF-REMOTE SWITCH X-INDICATES CONTACTS CLOSED TERMINAL CONTROL POWER TRANSFORMER CIRCUIT BREAKER, MCP 1-POLE / 3-POLE GROUND CONNECTION CONTACT NORMALLY OPEN / CLOSED BUS STAB ON MCC; CORD & PLUG CONNECTION FOR MOTORS THERMAL OVERLOAD OVERHEAD POWER LINE UNDERGROUND CONDUIT UNDERGROUND DUCT LINE (CONCRETE ENCASEMENT) NOTE P4 UNDERGROUND DIRECT BURIAL CONDUITS NOTE P4 MULTIPLE CONDUIT RUN CONDUIT CONCEALED IN FLOOR CONDUIT CONCEALED IN WALL OR CEILING CONDUIT EXPOSED CALLOUT INDICATING CONDUIT SIZE, NUMBER OF WIRES AND WIRE SIZE CALLOUT INDICATING CONDUIT PER SCHEDULE CONDUIT RUN, HATCH MARKS INDICATE NO. OF #12 CONDUCTORS NO HATCH MARKS IS 2#12 UNLESS OTHERWISE NOTED HOME RUN TO PANELBOARD OR AS INDICATED FLEXIBLE CONDUIT CONDUIT RUN, BROKEN AND CONTINUED ON SAME SHEET OR AS NOTED CONDUIT WITH SEAL FITTING CAP ON CONDUIT STUB OPEN CIRCLE DENOTES UPWARD CONDUIT RISER INDICATES REMOVAL FIRE ALARM CONDUIT TELEPHONE CONDUIT SURFACE MOUNTED PANELBOARD FLUSH MOUNTED PANELBOARD MOTOR DISCONNECT SAFETY SWITCH MANUAL MOTOR STARTER CONTROL STATION EQUIPMENT MOUNTING STAND GROUND ROD AND BOX INSTRUMENT ELECTRIC MANHOLE / POWER HANDHOLE / SIGNAL HANDHOLE INTRUSION DOOR SWITCH SECURITY ALARM PANEL SINGLE POLE SWITCH 2 = 2 POLE, 3 = 3 WAY, 4 = 4 WAY, K = KEY OPERATED WP = WEATHERPROOF D = DIMMER P = SWITCH WITH PILOT LIGHT SINGLE POLE SWITCH LED FIXTURE LED FIXTURE WITH NIGHT LIGHTING (UNSWITCHED) OR FLUORESCENT FIXTURE WITH SELF-CONTAINED EMERGENCY BALLAST/BATTERY WALL/CEILING MOUNTED FIXTURE WALL/CEILING MOUNTED FIXTURE NIGHT LIGHTING (UNSWITCHED) POLE MOUNTED FIXTURE WALL/CEILING MOUNTED EXIT LIGHT - DIRECTIONAL ARROW WHERE INDICATED, SHADED AREA INDICATES ILLUMINATED FACE EMERGENCY LIGHT WITH SELF CONTAINED BATTERY LIGHT FIXTURE IDENTIFICATION SINGLE RECEPTACLE, 120V SINGLE RECEPTACLE, 208V DUPLEX WALL RECEPTACLE, 120V WP = WEATHERPROOF G = GROUNDED IG = ISOLATED GROUND GF = GROUND FAULT INTERRUPTER DOUBLE DUPLEX WALL RECEPTACLE, 120V DUPLEX FLOOR RECEPTACLE, 120V MULTI-OUTLET ASSEMBLY WITH SINGLE RECEPTACLE, 120V SPACING (X INCHES) AS NOTED, MOUNTING HEIGHT AS NOTED RECEPTACLE, 480V WALL/CEILING MOUNTED JUNCTION BOX FLOOR RECESS MOUNTED JUNCTION BOX THERMOSTAT, WALL MOUNTED WALL TELEPHONE OUTLET (+12") DATA WALL OUTLET TELE-DATA WALL OUTLET FLOOR OUTLETS FIRE ALARM PULL STATION FIRE ALARM FLASHING LIGHT FIRE ALARM HORN BELL BUZZER HEAT DETECTOR SMOKE DETECTOR FIRE ALARM CONTROL PANEL PROXIMITY SENSOR WALL SENSOR S SECURITY SYSTEM CONDUIT INSTRUMENT A D S M J T J J F F B F S H VIDEO CAMERA OUTLET BOXv OFCI OWNER FURNISHED, CONTRACTOR INSTALLEDFLOCFLOCCULATOR, FLOCCULATION SCADA SUPERVISORY CONTROL AND DATA ACQUISTION SILICON CONTROLLED RECTIFIER TRANSIENT VOLTAGE SURGE SUPPRESSOR ANSI AMERICAN NATIONAL STANDARDS SURGE-PROTECTIVE DEVICESPD S* Sab ST MCP 100AT 100AT 100AF 100 GEN OL ** AS VS 2 K # 1 5 OFFON OFFON START STOP START STOP O AH O RH X2X1 H4H3H2H1 ?? OL F FIRE ALARM WITH VISUAL * ** FUSE. RATING IN AMPERES ELAPSED TIME METER CONTROL DEVICE COIL. PREFIX NUMBER, WHEN USED, DISTINGUISHES BETWEEN DEVICES OF THE SAME TYPE. ALT - ALTERNATOR CR - CONTROL RELAY GR - GENERAL RELAY ISR - INTRINSICALLY SAFE RELAY LR - LATCH RELAY SV - SOLENOID VALVE PR - PROBE RELAY TD - TIME DELAY RELAY INDICATING LIGHT PUSH-TO-TEST INDICATING LIGHT COLORS: A - AMBER B - BLUE C - CLEAR G - GREEN R - RED N - NEON W - WHITE Y - YELLOW TR - TIMING RELAY ETM * 1 * ** P123 FLUOR FLUORESCENT OVER TEMPERATUREOT POWER QUALITY METERPQM VFD SS - SOLID STATE STARTERSS IN-LINE REACTOR SOLIDS HANDLING BUILDINGSHB GENERATOR SETGENSET 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 2 . d w g NI C H O L A S K O K O T A S 2/ 2 8 / 2 0 1 9 1 0 : 5 7 A M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS ELECTRICAL ABBREVIATIONS, NOTES AND LEGEND 92 MJS MJS SLS SCALE: NTS 02CONDUIT TRANSITION CONC FLOOR FINISHED GRADE CONC WALL PVC-COATED GRS PVC-COATED GRS COUPLING PVC-COATED GRS COUPLING PVC CONDUIT SCALE: NTS 01 WALL MOUNTED WALL MOUNTED AUTOMATIC TRANSFER SWTICH APPROX 500 LBS MOUNT AT ±4'-0" AFF MASONRY WALL MANUFACTURER SHALL PROVIDE SEISMIC ANCHORAGE CALCULATIONS FOR EXISTING WALL TYPE. CONCRETE ANCHORS MUST CONFORM TO MANUFACTURER'S RECEOMMENDATIONS TRANSFER SWITCH CONCRETE NOTES: 1.BOTTOM CLEAR COVER: 3 IN MIN 2.SIDE AND TOP COVER: 2 IN MIN 3.REINFORCING BARS SHALL BE ASTM A615-GRADE 60 4.MINIMUM 28-DAY CONCRETE STRENGTH: 4000 PSI AS MEASURED IN ACCORDANCE WITH ASTM C39 5.TYPE II CEMENT REQUIRED W/ MAX WATER/CEMENT RATIO OF 0.42 6.MAX 1-INCH AGGREGATE 7.CONCRETE SHALL BE PLACED AND CURED BETWEEN 50 AND 90 DEGREES F 8.PROVIDE SF-2.0 FINISH AT FORMED SURFACES IN ACCORDANCE WITH ACI 301 9.PROVIDE TROWEL FINISH AT HORIZONTAL SURFACES IN ACCORDANCE WITH ACI 301 CONCRETE TESTING: [X] 4 CYLINDERS PER 100 CUBIC YARDS* TEST: 2 @ 7 DAYS, 2 @ 28 DAYS. * EACH MIX PLACED, EACH DAY PLACED 6" 6" 12" 6" CRUSHED ROCK PIPE ENCASEMENT DETAIL NOTES: 1.ENCASEMENT REINFORCEMENT SHALL BE #4@12" UON. PROVIDE 3 INCHES (MIN) CLEAR COVER. 2.SPACE PIPES AND CONDUIT 3xDIAMETER (MIN) ON CENTERS.ROUGH CJ SLAB W/ TYP REINF DEMO DETAIL EDGE OF ENCASEMENT (E) REINF TO REMAIN (E) CONC TO REMAIN DETAIL NOTES: 1.CHIP AWAY CONC AROUND REINFORCING 2.REINFORCING TO REMAIN IN PLACE UNDAMAGED 3.AFTER PLACING PIPE ENCASEMENT REPLACE CONC IN KIND 4.AT CONTRACTOR'S OPTION, REINFORCING MAY BE CUT AND SPLICED WITH A MINIMUM LAP SPLICE ADHERING TO ACI 318-14. SCALE: NTS 03CONCRETE DEMOLITION SCALE: NTS 04PIPE ENCASEMENT SCALE: NTS 05CONCRETE NOTES SCALE: NTS 06TYPICAL TRENCH SECTION 18 " 3" 3" (TYP) 3" 3" (TYP) 3" 6" 3" RED WARNING TAPE COMPACTED FILL INSTRUMENTATION & SIGNAL CONDUIT (TYP) FINISHED GRADE SAND BACKFILL POWER & 120V CONTROL CONDUIT (TYP) ALL DIMENSIONS ARE MINIMUMS. 1. NOTES: ADD 6" FOR RUNS BENEATH ROADS. 2. 12" MIN. SEPARATION TO "WET" UTILITIES WHERE APPLICABLE SCALE: NTS 07TYPICAL CONDUIT STUB-UP FINISHED GRADE 3/4" LIQUID-TIGHT FLEXIBLE CONDUIT AND CONNECTORS TO FIELD INSTRUMENT (TYPICAL) SEE DETAIL 02 GALVANIZED RIGID STEEL/PVC COATED CONNECTOR & REDUCER. SCALE: NTS 08TYPICAL CONDUIT MOUNTING STRAP GRS/PVC CONDUIT, TYPICAL GRS ANCHOR BOLT GRS 1-HOLE CONDUIT STRAP 12" (SEE NOTE 2) SCALE: NTS 09TYPICAL PIPE SLEEVE MOUNTING (E) CONC OR MASONRY WALL PVC SLEEVE I.D. 1/4" LARGER THAN PIPE O.D. SLEEVE 4" LONG RIGID PIPE STRAP PVC PIPE BEING SUPPORTED ON EXISTING CONCRETE SLAB NO T E 4 H 12" NOTES: 1.PLACE ALL EQUIPMENT ON CONCRETE PADS (UON). 2.SEPARATE ALL STEEL SURFACES BEARING ON CONC BY 1/4-INCH (MIN) THICK GROUT LAYER. 3.CONTRACTOR SHALL LOCATE AND AVOID DRILLING THRU EXISTING REINFORCING STEEL. 4.THE MAXIMUM OF 8 TIMES THE BAR DIAMETER OR 3" LESS THAN THE SLAB THICKNESS. #3@12" EW, H <8" #4@12" EW, 8" ≤H ≤ 10" #5@12" EW, H >10" 3/4" CHAMFER VERTICAL EDGES (TYP) ROUGHENED CJ W/ EPOXY BONDING AGENT (E) CONC SLAB ADHESIVE DOWEL ALL AROUND: #3@12" EW, H <8" #4@12" EW, 8" ≤H ≤ 10" #5@12" EW, H >10" SCALE: NTS 10TYPICAL EQUIPMENT PAD 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 3 . d w g NI C H O L A S K O K O T A S 2/ 2 8 / 2 0 1 9 1 0 : 5 8 A M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS ELECTRICAL DETAILS 93 MJS MJS SLS (E) MAIN CONTROL PANEL (E) ATS (E) MCC (E) BUBBLER CONTROL PANEL DEMOLITION SCALE: 1/2" = 1'-0" GENERAL NOTES: 1.REMOVE EVERYTHING ASSOCIATED WITH EXISTING GENERATOR SYSTEM. 2.DISCONNECT AND REMOVE ALL ASSOCIATED CONNECTIONS WITH ATS. 3.PATCH (N) EXHAUST SYSTEM TO MATCH (E) EQUIPMENT. 4.PROVIDE WEATHER-RESISTANT, UV-RESISTANT, LAMINATED PLASTIC SIGNS, CONFORMING TO ANSI Z535.1, AS LISTED BELOW, FOR MOUNTING ON EXTERIOR WALL OF BUILDING: 'DANGER' - 'COMBUSTIBLE LIQUIDS'; 10”H x 14”W SETON M9590BBHTEDPLA, OR EQUAL 'DANGER' - 'FUEL STORAGE - NO SMOKING'; 14”H x 10”W SETON L3764BBVTEDPLA, OR EQUAL 5.PROVIDE WEATHER RESISTANT, UV-RESISTANT, LAMINATED PLASTIC CHEMICAL IDENTIFICATION SIGN FOR DIESEL FUEL, 7½” x 7½”, CONFORMING TO NFPA 704 WITH BLACKE LETTERING AS LISTED BELOW (1 - BLUE PANEL, 2-RED PANEL, 0-YELLOW PANEL, 'BLANK'-WHITE PANEL), FOR MOUTNING ON EXTERIOR WALL OF BUILDING; SETON TB0013, OR EQUAL 6.PROVIDE ADHESIVE LABEL, 9”x2”, GOLD LETTERING ON BLACK BACKGROUND, LABELED 'DIESEL FUEL', FOR MOUTNING ON SUB-BASE FUEL TANK; SETON 91057, OR EQUAL. (N) GENERATOR (N) ATS 3' - 6 " MODIFICATION SCALE: 1/2" = 1'-0" 3' - 8 " 6'-8" 19'-4" 10 ' 2' 1' (E) MCC (N) GENERATOR CONCRETE HOUSEKEEPING PAD 3'-9" x 8'-6" x 8" THICK 1 2 3 4 4 (E) BUBBLER CONTROL PANEL (E) GENERATOR PAD AND GENERATOR (E) EXHAUST (SEE PHOTO ABOVE) (N) EXHAUST. REUSE EXISTING OPENINGS AS PRACTICAL. MODIFY AS NECESSARY FOR NEW EXHAUST SYSTEM (SEE PHOTO ABOVE) 1 1/2"C, 4#2, #8GND 3/4C, - 2#14 + #14 GND (GEN START) (E) SERVICE ENTRANCE METER MAIN (E) SERVICE ENTRANCE METER MAIN 1 1/2"C, 4#2 ,#8GND 3/4C, - 10#14 + #14 GND (GEN FAIL, GEN RUN, FUEL LOW, LOW BATTERY, GEN C.B. TRIP) 3/4C, - 6#14 + #14 GND (UTILITY POWER RUN, STANDBY. POWER RUN, NORMAL POWER FAIL) TYPICAL OF TWO. PATCH AND PAINT TO MATCH. 5 5 (E) GENERATOR CONTROL PANEL AND (E) GENERATOR (E) CONTROL PANEL. NOTE LIMITED SPACE FOR OVERHEAD CONDUIT PENETRATIONS. ASSUME CONDUITS SHALL ENTER FROM THE SIDES NEAR CEILING. (E) CONCRETE HOUSEKEEPING PAD TO BE REPLACED AND SIZED FOR NEW GENERATOR. (E) EXHAUST PIPE. REPLACE THIMBLE AND ROUTE NEW EXHAUST SIMILAR TO EXISTING. WRAP NEW EXHAUST TO MATCH EXISTING, PATCH SOUND MATERIAL TO MATCH EXISTING. (E) EXHAUST PIPE. PATCH AND PAINT TO MATCH AS REQUIRED UPON INSTALL OF NEW EXHAUST SYSTEM. REUSE EXISTING OPENINGS AS PRACTICAL. MODIFY AS NECESSARY FOR NEW EXHAUST SYSTEM (E) GENERATOR BUILDING INTERIOR SCALE: NTS (E) GENERATOR EXHAUST PENETRATION SCALE: NTS 1-1/2"C, 4#2, #8GND 3/4C, - 4#12 + #12 GND (BATTERY CHARGER, JACKET HEATER) 6 6 (E) MAIN CONTROL PANEL 7 7 9 GENERATOR CONTROL PANEL SHEET KEY NOTES: DOOR AND FRAME CAN BE REMOVED IN ORDER TO REMOVE EXISTING GENERATOR, IF NECESSARY. INSTALL NEW FRAME WITH EXISTING DOOR UPON COMPLETION AND INSTALLATION OF NEW GENERATOR. REMOVE CONDUIT AND CONDUCTORS BACK TO SOURCE. DISCONNECT AND REMOVE EXISTING CONTROL & SIGNAL WIRES BACK TO MAIN CONTROL PANEL. REMOVE AND REPLACE CONCRETE HOUSE KEEPING PAD TO ACCOMMODATE MANUFACTURERS GENERATOR SIZE, CENTER GENERATOR SUCH THAT LIVE ELECTRICAL PARTS MEET NEC WORKING CLEARANCE SPACE. REMOVE AND REPLACE EXISTING CEILING MOUNTED LIGHTING FIXTURES AND CONDUIT/CONDUCTORS WITH LITHONIA LED RTLX4 40L LP840 OR EQUAL. INSTALL NEW CONDUIT/CONDUCTORS CONNECT TO EXISTING PANEL PB1, CIRCUIT PB1-10 IN MCC LOCATED IN ELECTRICAL ROOM. PANEL PB1 RECEIVES STANDBY POWER FROM THE GENERATOR. THE PROVIDED ILLUMINATION IS GREATER THAN 1 FOOT-CANDLE AND THEREFORE MEETS THE REQUIREMENTS OF CBC 1008 AND CEC 700.16. CONNECT GENERATOR BATTERY CHARGER AND JACKET HEATER TO SAME CIRCUIT BREAKERS FOR THE EXISTING GENERATOR. REMOVE AND REPLACE EXISTING COOLING AIR DUCTWORK TO ACCOMMODATE MANUFACTURERS REQUIREMENTS. PROVIDE 2-INCH SCH 40 GALVANIZED STEEL PIPE TO EXTEND VENT THROUGH ROOF OF BUILDING. TERMINATE VENT PIPE 12 INCHES ABOVE ROOF PENETRATION. PROVIDE CARB APPROVED ACCESSORY VENT CAP. PROVIDE UL-LISTED 3A : 408 : C FIRE EXTINGUISHER WITH ACCESSORY WALL MOUNTED BRACKET. 8 9 FE 35 (E) LOUVER (2'-8" W x 4'-0" H, TOL @ 5'-4" AFF) (N) 30 KW ENGINE-GENERATOR W/ UL 142 DOUBLE-WALLED SUB-BASE FUEL TANK 168-GALLON CAPACITY (E) LOUVER (2'-8"W x 4'-0" H, TOL @ 5'-4"AFF) (E) LOUVER (4'-0" SQUARE, TOL @ 4'-8" AFF) 2" ENGINE EXHAUST RADIATOR EXHAUST OUTLET GRILLE (E) TURBINE VENTILATOR @ ROOF EDGE OF ROOF GUTTER EDGE OF ROOF GUTTER 8 1 2 2 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 4 . d w g CH E R Y L L O V E 1/ 1 2 / 2 0 2 1 1 1 : 2 2 A M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: KNOTS LANE LIFT STATION ELECTRICAL PLANS 94 MJS MJS SLS A 9 THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS M 2 7.5 "PB1" PANEL 100A 3P GEN 2 7.5 60A 3P 60A 3P 50A 3P (E) SERVICE ENTRANCE METER AND MAIN DISCONNECT 100A, 120/208V, 3Ø, 4W (E) MOTOR CONTROL CENTER "MCC" 125A, 120/208V, 3Ø, 4W, 42KAIC BRACING PACKAGED STANDBY GENERATOR SET 100A, 120/208V, 3Ø, 4W, 3P ATS (E) SDG&E DISTRIBUTION 3P (E) SDG&E 3Ø PADMOUNT TRANSFORMER 120/208V 120/208V, 3Ø, 4W 20KW (25KVA) 35 FRN 35 FRN GND BUS SE W A G E P U M P P- 1 SE W A G E P U M P P- 2 M 2 7.5 "PB1" PANEL 100A 3P GEN 2 7.5 60A 3P 60A 3P 50A 3P (E) SERVICE ENTRANCE METER MAIN 100A, 120/208V, 3Ø, 4W (E) MOTOR CONTROL CENTER "MCC" 125A, 120/208V, 3Ø, 4W, 42KAIC BRACING LEGALLY-REQUIRED STANDBY GENERATOR 100A, 120/208V, 3Ø, 3P, 35 KAIC ATS (E) SDG&E DISTRIBUTION (E) SDG&E 3Ø PADMOUNT TRANSFORMER 120/208V 120/208V, 3Ø, 4W 30KW (37.5KVA) 35 FRN 35 FRN SE W A G E P U M P P- 1 SE W A G E P U M P P- 2 (E) SERVICE ENTRANCE METER MAIN (E) FEEDER TO (E) ATS TO BE REMOVED. AFTER INSTALLING NEW, PATCH AND PAINT WALL TO MATCH EXISTING NEUTRAL GND BUS N N N NG 4#2, 1#8GND GENERAL NOTES: 1.ALL ELECTRICAL EQUIPMENT SHALL BE FULLY-RATED. SERIES-RATED EQUIPMENT SHALL NOT BE USED. SHEET KEY NOTES: CONNECT NEW GENERATOR TO EXISTING BUILDING GROUNDING ELECTRODE SYSTEM. AVAILABLE FAULT CURRENT IS 42 KA. 1 2 2 4#2, 1#8GND 4#2, 1#8GND MIN #8 AWG 1 100A 3P DEMOLITION MODIFICATION (E) SERVICE ENTRANCE METER MAIN N.T.S. KNOTS LANE LIFT STATION ELECTRICAL SINGLE LINE DIAGRAMS 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 5 . d w g NI C H O L A S K O K O T A S 12 / 2 1 / 2 0 2 0 3 : 4 9 P M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS 95 MJS MJS SLS ELECTRICAL ROOM (E) PUMP CONTROL PANEL (PCP) (E ) A T S (E ) M C C (E) MAIN SWITCHBOARD (N ) G E N E R A T O R ELECTRICAL ROOM 26' 19 ' - 4 " 5' 11 ' 2' - 6 " 1'-6" 7'-4" 3' - 4 " (E) PUMP CONTROL PANEL (PCP) (E) MAIN SWITCHBOARD 1 2 1 (N) REMOTE RADIATOR 4 5 6 3 275 GALLON 400 GALLON TANK 10' 8' - 8 " 8" 8" (N ) A T S (E ) M C C 8' - 8 " 4'-6" (E) GENERATOR 7 8 7 LSL AUXILIARY RADIATOR ROOM AUXILIARY RADIATOR ROOM 3/4"C, 10#14, #14GND (GEN FAIL, GEN RUN, FUEL LOW, LOW BATTERY, GEN C.B. TRIP) 3/4"C, - 6#14, #14GND (UTILITY POWER RUN, STANDBY POWER RUN, NORMAL POWER FAIL) 3/4"C, 2#14, #14GND (GEN START) 3/4"C, 4#12, 1#12G (BATTERY CHARGER, JACKET HEATER) (2) 3"C, 3#300MCM, #1GND (2) 3"C, 4#300MCM, #1GND 3/4"C, 2#14 (E) DISCONNECT SWITCH 9 10 SEE PHOTO ON SHEET 8 (2) 3"C, 4#300MCM, #1GND GENERATOR CONTROL PANEL M (E) EXHAUST FANS (N) GENERATOR PAD 1"C, 4#12, #12GND TO LP-A 14 (E) GENERATOR RADIATOR 12 (N) DISCONNECT SWITCH/CONTROLLER 15 M M (N) EXHAUST FANS M 16 18 FUEL TANK SCREENING STRUCTURE (N) 200 KW ENGINE - GENERATOR W/ UL 142 DOUBLE-WALLED SUB-BASE DIESEL FUEL TANK, 240-GALLON CAPACITY 19 UL-142 RECTANGULAR, FREE-STANDING DOUBLE-WALLED DIESEL FUEL TANK 17 FUEL SUMP AIR VENT FU E L SU M P (2) 3/4 UNDERGROUND CONDUIT (1) TSP FROM LEAK DETECTOR CONTROL PANEL TO FUEL TANK LEAK DETECTOR, (2)#14, (1) #14G FROM TANK LSL TO PUMP CONTROL PANEL FLOOR DRAIN REMOTE RADIATOR CONTROL PANEL 1/2 INCH COPPER PIPE FROM RADIATOR TO GENERATOR LEAK DETECTOR CONTROL PANEL (1) 3/4 CONDUIT (2) #14, (1)#14G RADIATOR STARTER TO GEN CONTROL PANEL (1) 3/4 CONDUIT (2)#12, (1) #14G TANK LSL TO GENERATOR FUEL TANK LSL J-BOX (2) 1 INCH FRANKLN XP UNDERGROUND FUEL LINES FROM GENERATOR SUPPLY AND RETURN PUMPS TO EXTERNAL FUEL TANK 3/4 CONDUIT (14)#14, (1) #14G GEN TO VERBATIM 3/4 CONDUIT (4)#14, (1) #14G LEAK SENSOR TO VERBATIM VERBATIM FUEL LINES ABANDON IN PLACE. CUT FRESH, GROUT CAPPED. PER RFI 3/4 CONDUIT (4)#12, (1) #12G FUEL PUMPS TO LP-A RADIATOR LSL J-BOX (1) 3/4 CONDUIT (1) TSP RADIATOR LSL TO GENERATOR J-BOX (1) 3/4 CONDUIT (1) FACTORY CABLE LEAK SENSOR TO LEAK DETECTOR CONTROL PANEL 3/4 CONDUIT (2)#12, (1) #12G LEAK SENSOR TO LP-A FUEL PUMPS AND SUMP PUMP DEMOLITION SCALE: 3/8" = 1'-0" MODIFICATION SCALE: 3/8" = 1'-0" SHEET KEY NOTES: REMOVE EXISTING GENERATOR AND AUTOMATIC TRANSFER SWITCH CONDUIT AND CONDUCTORS BACK TO SOURCE. DISCONNECT AND REMOVE EXISTING GENERERATOR CONTROL & SIGNAL WIRES BACK TO PUMP CONTROL PANEL. EXISTING CONCRETE HOUSEKEEPING PAD REUSED W/ 12-INCH EXTENSION POURED ON THE WEST END. FIELD VERIFY EXACT LOCATION OF EXISTING FUEL TANK FOR DEMOLITION AND REMOVAL. INSTALL NEW TANK AT SAME LOCATION AND CONFIRM SPACE REQUIREMENTS. DEMOLISH AND REPLACE REMOTE RADIATOR, DISCONNECT SWITCH AND ALL ASSOCIATED CONTROLS AND PIPING. DISCONNECT AND SEAL WITH NON-SHRINK GROUT AT GROUND LEVEL, PIPING AND CONDUIT TO PREVENT DIRT AND OTHER HINDRANCES. FUELD LINES ABANDONED IN PLACE. CUT FLUSH AND GROUT CAPPED. CONNECT GENERATOR BATTERY CHARGER AND JACKET HEATER TO SAME CIRCUIT BREAKERS FOR THE EXISTING GENERATOR. CONTRACTOR MAY REPLACE INTERNALS IN THE EXISTING MCC SECTION HOUSING THE AUTOMATIC TRANSFER SWITCH. PROVIDE ALL NECESSARY HARDWARE TO ASSURE MOTOR CONTROL CENTER IS ENCLOSED TO EXISTING NEMA RATING. REMOVE AND REPLACE (E) EXHAUST FANS IN KIND. NOT USED. GENERATOR MANUFACTURER TO INSTALL GENERATOR CONTROLLER AND DISCONNECT FACING DOOR OR ENSURE 36" CLEARANCE TO WALL. NOT USED. NOT USED. CONTRACTOR MAY UTILIZE (E) PIPING PENETRATIONS AT FLOOR LEVEL OR CORE DRILL (2) SEPARATE 3" MAX PENETRATIONS FOR NEW PIPING FROM GENSET TO REMOTE RADIATOR. CONTRACTOR SHALL ADD EQUIPMENT PAD PER DETAIL 10 FOR NEW EXTERIOR FUEL TANK WITH DOUBLE WALL SECONDARY CONTAINMENT. MINIMUM 6" EDGE DISTANCE FOR ANCHORS. PROVIDE 2-INCH, SCH 40, GALVANIZED STEEL PIPE TO EXTEND VENT THROUGH ROOF OF BUILDING. TERMINATE VENT PIPE 12-INCHES ABOVE ROOF PENETRATION. PROVIDE CARB APPROVED ACCESSORY VENT CAP. PROVIDE UL-LISTED 3A:40B:C FIRE EXTINGUISHER WITH ACCESSORY WALL MOUNTING BRACKET. PROVIDE 2-INCH, SCH 40, GALVANIZED STEEL PIPE TO EXTEND VENT TO TERMINATE AT A HEIGHT NOT LESS THAN 12-FEET ABOVE GRADE. PROVIDE CARB APPROVED ACCESSORY VENT CAP. 1 2 3 4 5 6 7 8 9 10 NORTH BATIQUITOS LIFT STATION ELECTRICAL PLANS 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 6 . d w g CH E R Y L L O V E 1/ 1 2 / 2 0 2 1 1 1 : 3 5 A M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: 96 MJS MJS SLS 11 12 13 14 15 16 17 18 19 GENERAL NOTES: 1.REMOVE EVERYTHING ASSOCIATED WITH EXISTING GENERATOR SYSTEM. 2.DISCONNECT AND REMOVE ALL ASSOCIATED CONNECTIONS WITH ATS. 3.PATCH (N) EXHAUST SYSTEM TO MATCH (E) EQUIPMENT. 4.REMOVE AND REPLACE EXISTING CONDUIT AND CEILING MOUNTED LIGHTING FIXTURES WITH LITHONIA MODEL# RTLX4 40L EZ1 LP840 N80 EL7L CONNECTED TO EXISTING PANEL LPA CIRCUIT LPA-1 IN MCC LOCATED IN ELECTRICAL ROOM, GENERATOR ROOM AND RADIATOR ROOM. 5.PROVIDE WEATHER-RESISTANT, UV-RESISTANT, LAMINATED PLASTIC SIGNS, CONFORMING TO ANSI Z535.1, AS LISTED BELOW, FOR MOUNTING ON EXTERIOR WALL OF PUMP STATION BUILDING AND OUTDOOR FUEL TANK ENCLOSURE: 'DANGER' - 'COMBUSTIBLE LIQUIDS'; 10”H x 14”W SETON M9590BBHTEDPLA, OR EQUAL 'DANGER' - 'FUEL STORAGE - NO SMOKING'; 14”H x 10”W SETON L3764BBVTEDPLA, OR EQUAL 6.PROVIDE WEATHER RESISTANT, UV-RESISTANT, LAMINATED PLASTIC CHEMICAL IDENTIFICATION SIGN FOR DIESEL FUEL, 7½” x 7½”, CONFORMING TO NFPA 704 WITH BLACKE LETTERING AS LISTED BELOW (1 - BLUE PANEL, 2-RED PANEL, 0-YELLOW PANEL, 'BLANK'-WHITE PANEL), FOR MOUTNING ON EXTERIOR WALL OF PUMP STATION BUILDING AND OUTDOOR FUEL TANK ENCLOSURE; SETON TB0013, OR EQUAL. 7.PROVIDE ADHESIVE LABEL, 9”x2”, GOLD LETTERING ON BLACK BACKGROUND, LABELED 'DIESEL FUEL', FOR MOUTNING ON SUB-BASE FUEL TANK AND OUTDOOR FUEL TANK; SETON 91057, OR EQUAL. B 9 THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS MODIFICATION M 100 800AF 600AT GEN 150A MCP (E) MOTOR CONTROL CENTER "MCC-1" 480V, 3Ø, 3W, 600A, 50KAIC PACKAGED STANDBY GENERATOR SET 600A, 480V, 3Ø, 3P ATS (E) SDG&E DISTRIBUTION 3P (E) SDG&E 3Ø PADMOUNT TRANSFORMER 480/277V 480V, 3Ø, 4W 200KW RVAT WA S T E W A T E R PU M P P - 1 100 150A MCP RVAT WA S T E W A T E R PU M P P - 2 100 150A MCP RVAT WA S T E W A T E R PU M P P - 3 3/4 3A MCP SU M P P U M P P - 4 1 3/4 3A MCP SU M P P U M P P - 5 1 3/4 3A MCP DR Y W E L L SU P P L Y F A N S F - 1 1 1/2 3A MCP DR Y W E L L EX H A U S T F A N E F - 1 1 1/2 3A MCP WE T W E L L SU P P L Y F A N S F - 2 1 1/2 3A MCP WE T W E L L SU P P L Y F A N E F - 2 1 2 150AF 15AT WE T W E L L GR I N D E R G R - 1 1-1/2 7A MCP SE A L W A T E R PU M P P - 6 5 HY D R A U L I C U N I T GR - 1 1-1/2 7A MCP SE A L W A T E R PU M P P - 7 1 1 1-1/2 150AF 15AT SU R G E T A N K AI R C O M P R E S S O R AC - 1 15 KVA 480-120/208 3Ø A LP 150AF 30AT M 100 800AF 600AT GEN 150A MCP (E) SWITCHBOARD "SE" 800A, 480/277, 3Ø, 4W (E) MOTOR CONTROL CENTER "MCC-1" 480V, 3Ø, 3W, 600A, 50KAIC LEGALLY-REQUIRED STANDBY GENERATOR 600A, 480V, 3Ø, 3P, 50 KAIC ATS (E) SDG&E DISTRIBUTION 300A/3P (E) SDG&E 3Ø PADMOUNT TRANSFORMER 480/277V 480V, 3Ø, 4W 200KW RVAT WA S T E W A T E R PU M P P - 1 100 150A MCP RVAT WA S T E W A T E R PU M P P - 2 100 150A MCP RVAT WA S T E W A T E R PU M P P - 3 3/4 3A MCP SU M P P U M P P - 4 1 3/4 3A MCP SU M P P U M P P - 5 1 3/4 3A MCP DR Y W E L L SU P P L Y F A N S F - 1 1 1/2 3A MCP DR Y W E L L EX H A U S T F A N E F - 1 1 1/2 3A MCP WE T W E L L SU P P L Y F A N S F - 2 1 1/2 3A MCP WE T W E L L SU P P L Y F A N E F - 2 1 2 150AF 15AT WE T W E L L GR I N D E R G R - 1 1-1/2 7A MCP SE A L W A T E R PU M P P - 6 5 HY D R A U L I C U N I T GR - 1 1-1/2 7A MCP SE A L W A T E R PU M P P - 7 1 1 1-1/2 150AF 15AT SU R G E T A N K AI R C O M P R E S S O R AC - 1 15 KVA 480-120/208 3Ø A LP 150AF 30AT DEMOLITION (E) SWITCHBOARD "SE" 800A, 480/277, 3Ø, 4W N N NG GENERAL NOTES: 1.ALL ELECTRICAL EQUIPMENT SHALL BE FULLY-RATED. SERIES-RATED EQUIPMENT SHALL NOT BE USED. SHEET KEY NOTES: CONNECT NEW GENERATOR TO EXISTING BUILDING GROUNDING ELECTRODE SYSTEM. AVAILABLE FAULT CURRENT IS 30 KA. 1 2 2 SETS: 3-300MCM, 1#1GND 2 SETS: 4-300MCM, 1#1GND MIN #1/0 AWG 1 2 SETS: 4-300MCM, 1#1GND2 NORTH BATIQUITOS LIFT STATION ELECTRICAL SINGLE LINE DIAGRAMS 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 7 . d w g NI C H O L A S K O K O T A S 2/ 2 8 / 2 0 1 9 2 : 2 2 P M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: 97 MJS MJS SLS THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS (E) GENERATOR CONTROL PANEL (E) GENERATOR (E) CONCRETE HOUSEKEEPING PAD TO BE REPLACED AND SIZED FOR NEW GENERATOR. (E) EXHAUST PIPE. REPLACE THIMBLE AND ROUTE NEW EXHAUST SIMILAR TO EXISTING. WRAP NEW EXHAUST TO MATCH EXISTING CEILING, ROOF, PATCH SOUND MATERIAL TO MATCH EXISTING. (E) LIGHT FIXTURES ( TYP 8) (E) GENERATOR ROOM N.T.S (E) ELECTRICAL ROOM N.T.S (E) GENERATOR ROOM N.T.S (E) GENERATOR ROOM N.T.S (E) FUEL TANK N.T.S (E) FUEL TANK (E) FUEL TANK LINES TO GENERATOR SAWCUT (E) CONDUIT AND SEAL FOR PROTECTION. (E) RADIATOR (E) DISCONNECT SWITCH (E) AUXILIARY RADIATOR ROOM N.T.S (E) ATS NORTH BATIQUITOS LIFT STATION ELECTRICAL DETAIL PHOTOS 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 8 . d w g NI C H O L A S K O K O T A S 12 / 2 1 / 2 0 2 0 3 : 5 1 P M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: 98 MJS MJS SLS THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS (E) CONCRETE ROOF TILE (E) RAFTER 4 12 5'-0" 2'-0" OVERHANG (E) 14" THICK CONCRETE SLAB (E) GENERATOR PAD(E) AC PAVEMENTFINISH GRADE (E) CONCRETE SLAB SCALE: 3/8" = 1'-0" POSSIBLE ROUTE FOR FUEL VENT, SEE NOTE 1.POSSIBLE ROUTE FOR FUEL VENT, SEE NOTE 1. (E) EXHAUST AND WALL PENETRATION 4 AKNOTS LANE GENERATOR BLDG SECTION SCALE: 3/8" = 1'-0"6 BNORTH BATIQUITOS GENERATOR BLDG SECTION 4 3 2 1 0 0 USE OF DOCUMENTS 25mm SCALES 1" 0 D E F G HABC IF THIS BAR IS NOT DIMENSION SHOWN, ADJUST SCALES ACCORDINGLY. THIS DOCUMENT, INCLUDING THE INCORPORATED DESIGNS, IS AN INSTRUMENT OF SERVICE FOR THIS PROJECT AND SHALL NOT BE USED FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF KENNEDY/JENKS CONSULTANTS. C: \ b m s \ k j c e - p w \ d m s 7 6 8 7 4 \ 1 5 4 4 1 0 6 - 9 . d w g CH E R Y L L O V E 1/ 1 2 / 2 0 2 1 1 1 : 5 1 A M LIFT STATION GENERATOR REPLACEMENT IMPROVEMENT PLAN FOR: BUILDING SECTIONS 99 MJS MJS SLS NOTE: 1.ROUTE FUEL TANK VENT PIPE OUTSIDE OF THE BUILDING AND NOT LESS THAN TWELVE (12) FEET ABOVE THE FINISHED GROUND LEVEL AND NOT LESS THAN FIVE (5) FEET HORIZONTALLY FROM PROPERTY LINES. REPAIR INTERIOR ACOUSTICAL TREATMENT TO MATCH EXISTING. PATCH EXTERIOR AND PAINT AS REQUIRED. SUBMIT PROPOSED PENETRATION LOCATION FOR APPROVAL PRIOR TO PERFORMING WORK. THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND OTHERS. KENNEDY/JENKS CONSULTANTS HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION PROVIDED TO THEM AND DOES NOT WARRANT THE ACCURACY OR COMPLETENESS OF THESE RECORD DRAWINGS. USERS OF THESE RECORD DRAWINGS ASSUME ALL RISK OF LOSS RESULTING FROM THEIR USE. USERS OF THESE DOCUMENTS IN ELECTRONIC FORM ARE CAUTIONED AGAINST USE WITHOUT FIRST DETERMINING WHETHER CHANGES MAY HAVE BEEN MADE TO THESE DOCUMENTS SUBSEQUENT TO THEIR PREPARATION BY KENNEDY/JENKS CONSULTANTS. ORIGINALS OF SIGNED AND SEALED HARD COPIES OF THESE DOCUMENTS ARE THE ONLY TRUE RECORD OF THE CONTRACT DOCUMENTS PREPARED BY KENNEDY/JENKS CONSULTANTS. RECORD DRAWINGS