HomeMy WebLinkAboutDWG 518-8; 5054; LAKE CALAVERA OUTLET IMPROVEMENTS; 01-32LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
SEPTEMBER 2020
VICINITY MAP
DECLARATION OF ENGINEER OF WORK
I HEREBY DECLARE THAT THE DESIGN OF THE IMPROVEMENTS AS SHOWN ON THESE PLANS
COMPLIES WITH PROFESSIONAL ENGINEERING STANDARDS AND PRACTICES. AS THE
ENGINEER IN RESPONSIBLE CHARGE OF THE DESIGN OF THESE IMPROVEMENTS, I ASSUME
FULL RESPONSIBLE CHARGE FOR SUCH DESIGN. I UNDERSTAND AND ACKNOWLEDGE THAT
THE PLAN CHECK OF THESE PLANS BY THE CITY OF CARLSBAD IS A REVIEW FOR THE
LIMITED PURPOSE OF ENSURING THE PLANS COMPLY WITH CITY PROCEDURES AND OTHER
APPLICABLE POLICIES AND ORDINANCES. THE PLAN CHECK IS NOT A DETERMINATION OF
THE TECHNICAL ADEQUACY OF THE DESIGN OF THE IMPROVEMENTS. SUCH PLAN CHECK
DOES NOT, THEREFORE, RELIEVE ME OF MY RESPONSIBILITY FOR THE DESIGN OF THESE
IMPROVEMENTS.
AS ENGINEER OF WORK, I AGREE TO INDEMNIFY AND SAVE THE CITY OF CARLSBAD, ITS
OFFICERS, AGENTS, AND EMPLOYEES HARMLESS FROM ANY AND ALL LIABILITY, CLAIMS,
DAMAGES, OR INJURIES TO ANY PERSON OR PROPERTY WHICH MIGHT ARISE FROM THE
NEGLIGENT ACTS, ERRORS OR OMISSIONS OF THE ENGINEER OF WORK, MY EMPLOYEES,
AGENTS, OR CONSULTANTS.
PROJECT SITE
CONSTRUCTION PLANS
CONTRACT NO. 5054
FOR THE
CARLSBAD, CALIFORNIA
LAKE CALAVERA OUTLET IMPROVEMENTS
COUNCIL MEMBERS
MATT HALL - MAYOR
CORI SCHUMACHER - COUNCIL MEMBER
KEITH BLACKBURN - COUNCIL MEMBER
VACANT - COUNCIL MEMBER
PRIYA BHAT-PATEL - COUNCIL MEMBER
CITY MANAGER
SCOTT CHADWICK
Carlsbad
1
G-1
TS
RK
AE
TITLE SHEET
LOCATION MAP
SCALE: 1" = 500'
PROJECT
LOCATION
C
I
T
Y
O
F
C
A
R
L
S
B
A
D
TITLE SHEET
LEGEND, GENERAL NOTES AND ABBREVIATIONS
1
2
3
4
5
DRAWING No.DRAWING TITLESHEET No.
SHEET INDEX
G-1
G-2
6
OUTLET PIPE DEMOLITION SECTIOND-2
7
8 M-1
9
10
M-2
OUTLET PIPE MODIFICATION PLAN
OUTLET PIPE MODIFICATION SECTION 1
11
M-3
OUTLET PIPE MODIFICATION SECTION 2
12
M-4
13
M-5
HOSING ROUTING - VALVE 1
OUTLET PIPE DEMOLITION PLAND-1
M-6
FLOW SYMBOLS AND NOTES
M-7
FLOW DIAGRAM - CHANGES TO AIR & HYDRAULIC SYSTEM
GENERAL SITE PLANC-1
PIPE AND HOSE SUPPORT DEMOLITIOND-3
CONTROL CABINET MODIFICATIONS SALVAGE/DEMOLITIOND-4
14
AIR PIPING MODIFICATIONS OUTSIDE OF CONTROL CABINET IN CONTROL BLDG
CONTROL BLDG
CONTROL CABINET SYSTEM MODIFICATION
PULLBOX 'F' MODIFICATIONS
M-815
M-916
M-1017
M-1118
CONTROL HOSING AND PIPING ROUTING SECTIONS - VALVE 1M-1219
HOSING ROUTING - VALVE 2 & 3M-1320
CONTROL HOSING AND PIPING ROUTING SECTIONS - VALVE 2M-1421
CONTROL HOSING AND PIPING ROUTING SECTIONS - VALVE 3M-1522
EXISTING OUTLET BOX MODIFICATIONSM-1623
MECHANICAL DETAILSMD-124
STRUCTURAL GENERAL NOTESS-125
STRUCTURAL PLAN, SECTION AND ELEVATIONS-226
CONTROL CABINET TUBING ROUTING
City of
STANDARD ELECTRICAL SYMBOLS AND ABBREVIATIONSE-127
ELECTRICAL SITE PLANE-228
CONTROL BUILDING ELECTRICAL PLANE-329
CONTROLSE-430
PHOTOSE-531
SCALE: 1" = 5000'
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
TERMINAL BLOCK DIAGRAMSVS-132
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
2
G-2
TS
RK
AE
LEGEND, GENERAL NOTES
AND ABBREVIATIONS
WORK TO BE DONE
THE IMPROVEMENT WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE
FOLLOWING DOCUMENTS, CURRENT AT THE TIME OF CONSTRUCTION, AS DIRECTED
BY THE CITY ENGINEER.
1. CARLSBAD MUNICIPAL CODE
2. CITY OF CARLSBAD ENGINEERING STANDARDS
3. THIS SET OF PLANS
4. THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION (GREEN
BOOK) CURRENT EDITION.
5. THE SAN DIEGO AREA REGIONAL STANDARD DRAWINGS AND AS MAY BE MODIFIED
BY THE CITY OF CARLSBAD STANDARDS.
6. CALIFORNIA STORM WATER QUALITY ASSOCIATION BMP CONSTRUCTION HANDBOOK
AND CALTRANS CONSTRUCTION SITE BMP MANUAL.
LEGEND ABBREVIATIONS
ABANDON
ADDITIONAL
AIR VALVE
ALTERNATE
AMERICAN WIRE GAUGE
ANGLE
APPROXIMATE
ASBESTOS CEMENT PIPE
ASPHALTIC CONCRETE
AT
AVENUE
BEGIN VERTICAL CURVE
BETWEEN
BLOW OFF
BOTTOM
BOTTOM OF PIPE
BUTTERFLY VALVE
BUILDING
CABLE TV
CAST IRON
CATCH BASIN
CITY OF CARLSBAD
CENTER
CENTERED
CENTER LINE
CHECKERED
CHLORINATION
CLASS
CLEAR
CEMENT MORTAR LINED
CARLSBAD MUNICIPAL WATER DISTRICT
COMBINATION
CONCRETE
CONCRETE CYLINDER PIPE
CONCRETE REINFORCING STEEL INSTITUTE
CONNECTION
CONTINUOUS
CORRUGATED METAL PIPE
COUPLING
CARBON STEEL
CUBIC YARD
DIAGONAL
DIAMETER
DRAWING
DUCTILE IRON
DUCTILE IRON MECHANICAL JOINT
DUCTILE IRON PIPE
DRIVE
EACH
EACH FACE
EACH WAY
ELECTRIC
ECCENTRIC
END VERTICAL CURVE
ELECTRICAL
ELEVATION
ENGINEER
EXPANSION
EXISTING
FLOW CONTROL FACILITY
FINISHED GRADE
FIRE HYDRANT
FORCE MAIN
FIBER OPTIC
FINISHED SURFACE
FLANGE
FLEXIBLE
FLOW LINE
FOOT OR FEET
GAS
GAUGE
GALLON
GALLONS PER MINUTE
GALVANIZE
GALVANIZED STEEL
HIGH WATER LEVEL
HORIZONTAL
HYDRANT
HYDRAULIC GRADE LINE
INVERT ELEVATION
INCH OR INCHES
INSIDE DIAMETER
IRON PIPE SIZE
INVERT
INVERT ELEVATION
POUNDS
LINEAL FEET
LONG OR LENGTH
LEFT
LEUCADIA WASTEWATER DISTRICT
LOW WATER LEVEL
MANUAL AIR VALVE
MACHINE BOLT
MANHOLE
MANUFACTURER
ABD
ADDL
AV
ALTN
AWG
ANG
APPROX
ACP
AC
@
AVE
BVC
BTWN
BO
BOT
BOP
BFV
BLDG
CATV
CI
CB
COC
CTR
CTRD
C/L
CHKD
CHL
CL
CLR
CML
CMWD
COMB
CONC
CCP
CRSI
CONN
CONT
CMP
CPLG
CS
CY
DIAG
DIA
DWG
DI
DIMJ
DIP
DR
EA
EF
EW
E
ECC
EVC
ELEC
EL
ENGE
EXP
EXST
FCF
FG
FH
FM
FO
FS
FLG
FLEX
FL
FT
G
GA
GAL
GPM
GALV
GALVS
HWL
HORIZ
HYD
HGL
IE
IN
ID
IPS
INVT
IE
LBS
LF
LG
LT
LWD
LWL
MAV
MB
MH
MFR
MAXIMUM
MECHANICAL
MECHANICAL JOINT
MILE
MILLION GALLON
MINIMUM
NORTH
NORTH AMERICAN VERTICAL DATUM
NORMALLY CLOSED
NATIONAL GEODETIC VERTICAL DATUM
NOT TO SCALE
NUMBER
ON CENTER
OPENING
OUTSIDE DIAMETER
PACKAGE
PLAIN END
PLATE
PUSH ON
POINT
POINT OF VERTICAL INFLECTION
POLYVINYL CHLORIDE
POUNDS PER SQUARE INCH GAUGE
PRESSURE
PRESSURE REDUCING STATION
PRESSURE REDUCING VALVE
PROPERTY LINE
PUMP STATION
RADIUS
RECOMMENDATION
REFERENCE
REINFORCE
REINFORCED CONCRETE PIPE
REQUIRED
RESTRAINED JOINT
RESERVOIR
RIGHT OF WAY
ROAD
ROUGH GRADE
RIGHT
RECYCLED WATER
RESILIENT WEDGE GATE VALVE
SEWER
STORM DRAIN
SAN DIEGO GAS AND ELECTRIC CO.
SAN DIEGO REGIONAL STANDARD DRAWINGS
SCHEDULE
SQUARE FEET
SHEET
SLEEVE
SERVICE POINT
SPECIFICATION
SQUARE
STAINLESS STEEL
STANDARD
STATION
STEEL
SUPPORTS
TELEPHONE
THRUST BLOCK
TEMPORARY BENCH MARK
THREADED
THICK
THICKNESS
TOP OF CONCRETE ELEVATION
TOP OF PIPE
TOP OF WALL ELEVATION
TYPICAL
UNKNOWN
UNLESS NOTED
U.S. COAST AND GEODETIC SURVEY
VERTICAL CURVE
VENDOR SUPPLIED INFORMATION
VENT THROUGH ROOF
VERTICAL
WATER AGENCIES STANDARDS
WATER LEVEL
WATER SURFACE
WATER
WELDED STEEL PIPE
WELDED WIRE FABRIC
WELDED WIRE MESH
WITH
WORK ORDER
MAX
MECH
MJ
MI
MG
MIN
N
NAVD
NC
NGVD
NTS
NO.
OC
OPNG
OD
PKG
PE
PL
PO
PT
PVI
PVC
P.S.I.G.
PRESS
PRS
PRV
P/L
PS
RAD
RECOMM
REF
REINF
RCP
REQD
RJ
RSVR
R.O.W.
RD
RG
RT
RW
RWGV
S
SD
SDG&E
SDRSD
SCHED, SCH
SF
SHT
SLV
SP
SPEC
SQ
SS
STD
STA
STL
SPRTS
TEL, T
TB
TBM
THD
THK
t
T/CONC
TOP
T/WALL
TYP
UNK
U.N.
USC&GS
VC
VS
VTR
VERT
WAS
WL
WS
WTR, W
WSP
WWF
WWM
W/
WO
GENERAL NOTES (CONTINUED)GENERAL NOTES
LEAST TWO FULL WORKING DAYS PRIOR TO STARTING CONSTRUCTION NEAR THEIR
FACILITIES AND SHALL COORDINATE WORK WITH A COMPANY REPRESENTATIVE.
UNDERGROUND SERVICE ALERT
SDG&E
AT&T DISTRIBUTION
TIME WARNER CABLE
NEXTG NETWORKS, INC.
THE CONTRACTOR SHALL NOTIFY AFFECTED UTILITY COMPANIES (SEE BELOW) AT
LEVEL 3 COMMUNICATIONS
(800) 422-4133
(800) 660-7343
(619) 574-3661
(760) 438-7741
(408) 687-0800
(720) 888-2639
15.
CITY OF CARLSBAD(STREETS AND STORM DRAIN)
AT&T TRANSMISSION
(760) 434-2980
(714) 963-7964
CARLSBAD MUNICIPAL WATER DISTRICT (760) 438-2722
UTILITY INFORMATION OBTAINED FROM AVAILABLE RECORD DRAWINGS OR UTILITY
MAPS. VERTICAL ELEVATIONS ARE UNKNOWN. CONTRACTOR SHALL VERIFY
HORIZONTAL AND VERTICAL LOCATIONS AND BEARING AND INCLINATIONS
SUFFICIENTLY AHEAD OF SCHEDULE TO ALLOW TIME FOR DESIGN REVISIONS, IF
NECESSARY. PROVIDE A MINIMUM OF 12 INCHES OF VERTICAL SEPARATION
BETWEEN UTILITY CROSSINGS, UNLESS OTHERWISE APPROVED BY THE ENGINEER.
PRIOR TO FINAL ACCEPTANCE OF WORK BY THE CITY.
THE ORIGINAL DRAWINGS SHALL BE REVISED TO REFLECT AS-BUILT CONDITIONS
CARLSBAD STANDARDS ALL EXISTING IMPROVEMENTS INCLUDING BUT NOT LIMITED
16. THE CONTRACTOR SHALL REPLACE IN KIND AND IN ACCORDANCE WITH ALL CITY OF
TO PAVEMENT, SIDEWALKS, CURBS AND GUTTERS, MEDIAN IMPROVEMENTS, BERMS,
PAVED AND DIRT ROADS, DRAINAGE DITCHES, CULVERTS, DRAIN PIPES, SEWER
LATERALS, WATER SERVICES, LANDSCAPING, HARDSCAPE IRRIGATION FACILITIES,
TRAFFIC CONTROL LOOPS, LIGHTING AND ELECTRICAL, ABOVE AND BELOW GROUND,
DAMAGED DURING CONSTRUCTION OF THE PROJECT, EXCEPT AS SPECIFICALLY
INDICATED ON THE DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRAFFIC CONTROL, INCLUDING
PREPARATION OF APPROVED TRAFFIC CONTROL PLANS.
THE PROJECT SITE AT ALL TIMES DURING CONSTRUCTION.
INCLUDING SHORING, AND SHALL BE SOLELY RESPONSIBLE FOR CONFORMING TO
ALL LOCAL, STATE AND FEDERAL SAFETY AND HEALTH STANDARDS, LAWS AND
REGULATIONS.
A DETAIL PLAN TO THE CITY ENGINEER AND/OR CONCERNED AGENCY SHOWING
THE DESIGN OF SHORING, BRACING SLOPE OR OTHER PROVISIONS TO BE MADE
OF WORKER PROTECTION FROM THE HAZARD OF CAVING GROUND DURING THE
EXCAVATION OF SUCH TRENCH OR TRENCHES OR DURING THE PIPE INSTALLATION
THEREIN. THIS PLAN MUST BE PREPARED FOR ALL TRENCHES FIVE FEET (5') OR
MORE IN DEPTH AND APPROVED BY THE CITY ENGINEER AND/OR CONCERNED
AGENCY PRIOR TO EXCAVATION. IF THE PLAN VARIES FROM THE SHORING SYSTEM
STANDARDS ESTABLISHED BY THE CONSTRUCTION SAFETY ORDERS, TITLE 8
CALIFORNIA ADMINISTRATIVE CODE, THE PLAN SHALL BE PREPARED BY A
ON THE CONSTRUCTION PLANS WERE OBTAINED BY A SEARCH OF THE AVAILABLE
RECORDS. ATTENTION IS CALLED TO THE POSSIBLE EXISTENCE OF OTHER
UTILITY FACILITIES OR STRUCTURES NOT SHOWN OR IN A LOCATION DIFFERENT
FROM THAT SHOWN ON THE PLANS. THE CONTRACTOR IS REQUIRED TO TAKE DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES SHOWN ON THE PLANS AND
ANY OTHER EXISTING FACILITIES OR STRUCTURES NOT SHOWN.
AHEAD OF THE CONSTRUCTION TO PERMIT THE REVISIONS OF THE CONSTRUCTION
PLANS IF IT IS FOUND THAT THE ACTUAL LOCATIONS ARE IN CONFLICT WITH
THE PROPOSED WORK.
ACCESS FOR FIRE AND OTHER EMERGENCY VEHICLES SHALL BE MAINTAINED TO
THE CONTRACTOR SHALL DESIGN, CONSTRUCT AND MAINTAIN ALL SAFETY DEVICES
THE CONTRACTOR SHALL CONFORM TO LABOR CODE SECTION 6705 BY SUBMITTING
ALL OPERATIONS CONDUCTED ON THE SITE OR ADJACENT THERETO, INCLUDING
WARMING UP, REPAIR, ARRIVAL, DEPARTURE OR OPERATION OF TRUCKS,
EARTHMOVING EQUIPMENT, CONSTRUCTION EQUIPMENT AND ANY OTHER ASSOCIATED
GRADING EQUIPMENT SHALL BE LIMITED TO THE PERIOD BETWEEN 7:00 A.M. AND
6:00 P.M. EACH DAY, MONDAY THRU FRIDAY AND NO CONSTRUCTION OPERATIONS
SHALL BE CONDUCTED ON WEEKENDS OR HOLIDAYS. (A LIST OF CITY HOLIDAYS
IS AVAILABLE AT THE ENGINEERING DEPARTMENT COUNTER.)
ALL OFF-SITE HAUL ROUTES SHALL BE SUBMITTED BY THE CONTRACTOR TO THE
CITY ENGINEER FOR APPROVAL TWO FULL WORKING DAYS PRIOR TO BEGINNING OF
WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DEBRIS OR DAMAGE
OCCURRING ALONG THE HAUL ROUTE OR ADJACENT STREETS AS A RESULT OF THE
GRADING OPERATION.
DURING CONSTRUCTION, OPERATIONS WILL CEASE IMMEDIATELY, AND THE
PERMITTEE WILL NOTIFY THE CITY ENGINEER. OPERATIONS WILL NOT RESTART
UNTIL THE PERMITTEE HAS RECEIVED WRITTEN AUTHORITY FROM THE CITY
ENGINEER TO DO SO.
THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EXISTING FACILITIES
THIS PLAN SUPERSEDES ALL OTHER PLANS PREVIOUSLY APPROVED BY THE CITY
OF CARLSBAD REGARDING IMPROVEMENTS SHOWN ON THIS SET OF PLANS.
REGISTERED ENGINEER AT THE CONTRACTORS EXPENSE. A COPY OF THE OSHA
EXCAVATION PERMIT MUST BE SUBMITTED TO THE INSPECTOR PRIOR TO
IF ANY ARCHAEOLOGICAL RESOURCES ARE DISCOVERED WITHIN ANY WORK ZONE
THE EXISTENCE AND LOCATION OF UTILITY STRUCTURES AND FACILITIES SHOWN
(ABOVEGROUND AND UNDERGROUND ) WITHIN THE PROJECT SITE SUFFICIENTLY
EXCAVATION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SECTION AND DETAIL IDENTIFICATION SYSTEM
DRAWING FROM WHICH
SECTION IS CUT
B
SCALE:
SECTION TITLE
SECTION
DRAWING WHERE
SECTION IS SHOWN
SECTION LETTER
-
SECTION CALLOUT
SECTION LETTER
DRAWING ON WHICH
DETAIL APPEARS
DETAIL
A
C-1
SCALE:
DETAIL TITLE
3
-
DETAIL NUMBER
M-3
DETAIL NUMBER
DETAIL CALLOUT 2
EXIST BUILDING / STRUCTURE
EXIST FENCE
EXIST OVERHEAD POWER
DEMO/REMOVE
CONCRETE
FLANGED JOINT
WELDED JOINT
ELBOW DOWN
PLUG VALVE
BUTTERFLY VALVE
BALL VALVE
PNEUMATIC ACTUATOR
HYDRAULIC ACTUATOR
INSPECTION NOTES
1.FIELD INSPECTION BY DSOD: REPRESENTATIVES FROM DSOD WILL PERIODICALLY
INSPECT THE WORK IN PROGRESS DURING CONSTRUCTION, INCLUDING THE MATERIALS
BEING INCORPORATED INTO THE WORKS, AS WELL AS THE TEST RESULTS AND
DOCUMENTATION ASSOCIATED WITH THE PROJECT. THE CONTRACTOR SHALL ALLOW
DSOD REPRESENTATIVES ACCESS TO ALL LOCATIONS WITHIN THE PROJECT BOUNDARIES.
ALL COMMUNICATION WITH DSOD PERTAINING TO THE PROJECT SHALL BE COORDINATED
THROUGH THE OWNER'S ENGINEER OR DESIGNATED REPRESENTATIVE.
A 72-HOUR NOTICE FROM THE OWNER'S REPRESENTATIVE IS REQUIRED TO SCHEDULE A
DSOD INSPECTION. THEREFORE, THE CONTRACTOR SHALL COOPERATE WITH THE
OWNER'S REPRESENTATIVES BY GIVING AT LEAST FIVE (5) BUSINESS DAYS NOTICE
OF ANY INSPECTION REQUIRING DSOD INVOLVEMENT TO ENSURE THE OWNER HAS
SUFFICIENT TIME TO COORDINATE WITH DSOD.
REFERENCE DRAWINGS
LAKE CALAVERA REMEDIAL IMPROVEMENTSCOC DWG NO. 411-6
CALAVERA DAM RESERVOIR SITE COC DWG NO. 806-5
BASIS OF BEARINGS AND COORDINATES BENCHMARK
THE ELEVATION BENCHMARK IS A SET ROD ON TOP OF
EARTHEN DAM 10 FT EAST OF WEST END OF DAM.
NGVD29 ELEVATION = 223.00 FEET
NAVD88 ELEVATION = 225.15 FEET
ELEVATIONS SHOWN HEREON CONFORM WITH NAVD88
DIG ALERT 811
WATER SERVICES, RECYCLED WATER SERVICES AND SEWER LATERALS ARE
SHOWN IN THEIR APPROXIMATE LOCATION. ALL SERVICES SHALL BE KEPT ACTIVE
UNLESS REQUIRED FOR CONSTRUCTION ACTIVITIES. SCHEDULED SERVICE
INTERRUPTIONS SHALL BE COORDINATED WITH THE CITY REPRESENTATIVE PRIOR
TO SERVICE INTERRUPTION. SERVICES DAMAGED DURING CONSTRUCTION SHALL
BE REPLACED TO THEIR ORIGINAL WORKING CONDITION AND TESTED PER CITY
REQUIREMENTS IN ACCORDANCE WITH CITY OF CARLSBAD ENGINEERING
STANDARDS AT THE EXPENSE OF THE CONTRACTOR.
CONTRACTOR SHALL NOT USE ANY PUBLIC RIGHT-OF-WAY FOR STOCKPILING
OR STAGING OF WORK WITHOUT WRITTEN APPROVAL OF THE CITY OF
CARLSBAD.
10.
11.
12.
13.
14.
THE BASIS OF BEARINGS FOR SEGMENT 7 IS THE INVERSE OF THE
CALIFORNIA COORDINATE SYSTEM 1983 ZONE 6, 1991.35 EPOCH
ADJUSTMENT COORDINATES OF THE FOLLOWING SURVEY MONUMENTS
FROM RECORD OF SURVEY NO. 17271, CITY OF CARLSBAD SURVEY
CONTROL.
COORDINATES WERE ESTABLISHED IN SAID SYSTEM ON THE FOLLOWING
DESCRIBED SURVEY MONUMENTS BY GPS SURVEY.
A SET ROD DRIVEN TO REFUSAL IN WELL WITH COVER IN WEST END OF
DAM FOR LAKE CALAVERA.
NORTHING = 2007023.33
EASTING = 6244235.20
A STANDARD STREET SURVEY MONUMENT IN CENTER OF BULB CUL DE
SAC AT THE NORTH END OF MILFORD PLACE, .2 MILES NORTH OF
TAMARACK AVE.
NORTHING = 2009295.68 FEET
EASTING = 6240551.22 FEET
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
3
C-1
TS
RK
AE
GENERAL SITE PLAN
SCALE: 1" = 50'-0"
LAKE CALAVERA
EXST CONTROL BUILDING
EXST PUBLIC TRAIL
EXST DIRT TRAIL
CONTRACTOR STAGING AREA
EXST GATE AND
EXST AC
ACCESS RD
EXST REMOVABLE BOLLARDS
EXST SPILLWAY
EXST OUTLET TOWER & PIPING
EXST AC
ACCESS RD
EXST DIRT/GRAVEL
ACCESS RD
EXST OUTLET BOX
FENCE
SEE DWG M-16 & S-2
FOR MODIFICATIONS
SEE DWGS D-1, D-2, M-8 & M-9
FOR MODIFICATIONS
SEE DWG M-3, M-4, M-5 & M-6
FOR MODIFICATIONS
TA
M
A
R
A
C
K
A
V
E
N
U
E
EXST HIGH VOLTAGE
OVER HEAD POWER LINES
VEGETATION REMOVAL AND MAINTENANCE IN THIS AREA
IS PERMITTED BY STREAMBED ALTERATION AGREEMENT
NOTIFICATION NO. 1600-2013-0241-R5. THE PROJECT IS
EXEMPT FROM ENVIRONMENTAL REVIEW PER CALIFORNIA
ENVIRONMENTAL QUALITY ACT (CEQA) GUIDELINES
SECTIONS 15302 (REPLACEMENT OR RECONSTRUCTION
OF EXISTING FACILITIES); 15303 (NEW CONSTRUCTION);
AND 15304 (MINOR ALTERATION TO LAND AND
VEGETATION). A NOTICE OF EXEMPTION WAS FILED WITH
THE SAN DIEGO COUNTY CLERK IN COMPLIANCE WITH
SECTION 21152(b) OF PUBLIC RESOURCES CODE (CEQA).
ENVIRONMENTAL NOTES:
1.IF VEGETATION DISTURBANCE IS SCHEDULED TO OCCUR DURING THE BIRD BREEDING SEASON
(BETWEEN JANUARY 15 AND SEPTEMBER 15) A BIOLOGIST SHALL PERFORM A NESTING BIRD
SURVEY WITHIN THE PROPOSED CONSTRUCTION AREA AND APPROPRIATELY-SIZED BUFFER NO
MORE THAN 72 HOURS PRIOR TO VEGETATION DISTURBANCE. IF THE PLANNED VEGETATION
DISTURBANCE DOES NOT OCCUR WITHIN 72 HOURS OF THE NESTING BIRD SURVEY, THEN THE
AREA SHALL BE RE-SURVEYED. IF NESTING BIRDS ARE FOUND, THEN THE QUALIFIED BIOLOGIST
SHALL ESTABLISH AN ADEQUATE BUFFER ZONE (ON A SPECIES-BY-SPECIES, CASE-BY-CASE BASIS)
IN WHICH CONSTRUCTION ACTIVITIES WOULD BE PROHIBITED UNTIL THE NEST IS NO LONGER
ACTIVE. THE SIZE OF THE BUFFER ZONE IS DETERMINED BY THE BIOLOGICAL MONITOR BASED ON
THE AMOUNT, INTENSITY, AND DURATION OF CONSTRUCTION, AND CAN BE ALTERED BASED ON
SITE CONDITIONS. IF APPROPRIATE, AS DETERMINED BY THE BIOLOGICAL MONITOR, ADDITIONAL
MONITORING OF THE NESTING BIRDS MAY BE CONDUCTED DURING CONSTRUCTION TO ENSURE
THAT NESTING ACTIVITIES ARE NOT DISRUPTED. CITY WILL PROVIDE BIOLOGICAL SURVEY AND
MONITORING SERVICES AND THE CONTRACTOR WILL MAKE WORK ACTIVITY ADJUSTMENTS AS
DESCRIBED ABOVE IN COMPLIANCE WITH DIRECTION FROM THE CITY.
2.ALL VEHICLES, EQUIPMENT, TOOLS, AND SUPPLIES SHOULD STAY WITHIN THE LIMITS OF THE
APPROVED TEMPORARY IMPACT AREAS. NO VEHICLES, EQUIPMENT, TOOLS, AND SUPPLIES
SHOULD BE PLACED WITHIN THE WATER OR WETLAND VEGETATION OUTSIDE OF APPROVED
TEMPORARY IMPACT AREAS.
3.EQUIPMENT REFUELING SHOULD OCCUR IN AN UPLAND AREA FAR ENOUGH AWAY FROM THE
WATER TO PREVENT CONTAMINATION OF WATERS.
4.CONTRACTOR SHALL INSTALL BMP FEATURES (E.G. SILT FENCING, STRAW WADDLES, AND GRAVEL
BAGS) TO PREVENT OFF-SITE SEDIMENTATION AND STORM WATER & NON-STORM WATER
POLLUTION.
EXST FENCED AREA W/SOME
SPACE FOR STAGING
PUBLIC
TRAIL
PUBLIC
TRAIL
GENERAL NOTES:
1.CONTRACTOR SHALL ALLOW PUBLIC ACCESS AT ALL TIMES EXCEPT
FOR TEMPORARY CLOSURES. TEMPORARY CLOSURE OF THE PUBLIC
TRAILS MAY BE PERMITTED FOR PUBLIC SAFETY REASON FOR 8 HOURS
MAXIMUM DURING CONSTRUCTION. CONTRACTOR SHALL NOTIFY THE
CITY IN 72 HOURS WITH A PUBLISHED SCHEDULE OF CLOSURES.
2.AN 8 FT CHAIN LINK SECURITY FENCE SHALL BE INSTALLED FOR
THE STAGING AREA(S).
3.EXISTING CONTOURS SHOWN ARE FOR INFORMATIONAL PURPOSES
ONLY TO SHOW DIFFERENCE IN ELEVATION FROM CREST OF DAM TO
OUTLET TOWER AND OUTLET BOX.
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
4
D-1
TS
RK
AE
OUTLET PIPE DEMOLITION PLAN
SCALE: 3/16" = 1'-0"
PROTECT-IN-PLACE OUTLET
TOWER AND GRATING COVER
PROTECT-IN-PLACE
CONDUIT BANK (TYP)
PROTECT-IN-PLACE
TERMINAL/PULL BOX
(TYP)
DEMO SECTION OF 8" Ø SCH 10,
TYPE 316 SS AIR VENT PIPE,
PARTLY SUBMERGED, COORDINATE
W/ DWG NO. D-2, M-8 & M-9
EXST 30" (HDPE LINED) RCP OUTLET PIPE
PROTECT-IN-PLACE OUTLET
BOX AND GRATING
INTAKE 1 - PROTECT ENTRANCE
CONE FOR REINSTALLATION AND
REMOVE 18" BFV UNDER PARTLY
SUBMERGED CONDITIONS
INTAKE 2 - REMOVE AND PROTECT
TEE-SCREEN FOR REINSTALLATION
AND REMOVE 18" BFV UNDER
SUBMERGED CONDITION
REMOVE SECTION OF 24" Ø SCH 10, TYPE 316 SS
OUTLET PIPE AS NECESSARY UNDER SUBMERGED
CONDITIONS. FOR REINSTALLATION COORDINATE
W/ DWG NO. D-2, M-8 & M-9
INTAKE 3 - REMOVE 18" BFV UNDER
SUBMERGED CONDITIONS. SEE NOTE 2
PROTECT-IN-PLACE
8"Ø AIR VENT PIPE
AND ASSEMBLY
D-2
UNBOLT FLANGE AND REMOVE SECTION UPSTREAM
UNDER SUBMERGED CONDITIONS. COORDINATE W/ DWG
NO. D-2, M-8, M-9 & M-10. SEE NOTE 1
REMOVE HEADER CLAMP AT
SUPPORT BENT. REINSTALL W/
MODIFIED HEADER. SEE D-2
D-3
2SUPPORT BENT #3. SEE DETAIL
DEMO BFV AND
ACTUATOR NUT
PROTECT-IN-PLACE OUTLET
BOX AND GRATING. REMOVE
ALL DEBRIS WITHIN
DEMO BFV AND ACTUATOR
SEE PHOTO 1
EXST PULL BOX F
NTS
PHOTO 1
A
NOTES:
1.CONTRACTOR TO REMOVE 24" OUTLET PIPE
BETWEEN CONNECTION OF 8" Ø AIR VENT PIPE AND
FLANGE AT OUTLET TOWER IN ORDER TO
TRANSFER TO FABRICATOR FACILITY FOR
MODIFICATION.
2.CITY HAS PREVIOUSLY REMOVED THE BARREL
SCREEN AND IS STORED. CONTRACTOR TO
RETRIEVE FROM THE CITY AND REINSTALL.
PROTECT-IN-PLACE
LEVEL SENSOR
WIRING INSIDE
4" PVC SCH 80
CONDUIT
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
5
D-2
TS
RK
AE
OUTLET PIPE DEMOLITION SECTION
PROTECT-IN-PLACE OUTLET
TOWER AND GRATING COVER
D-1
A
PROTECT-IN-PLACE
TERMINAL/PULL BOX
(TYP)
DEMO SECTION OF 8" Ø AIR VENT
PIPE UNDER SUBMERGED
CONDITIONS, COORDINATE
W/ DWG NO. D-1, M-8 & M-9
PROTECT-IN-PLACE 30" RCP ( HDPE LINED) OUTLET PIPE
PROTECT-IN-PLACE
PIPE SUPPORT BENT
(TYP OF 3)
INTAKE 1 - REMOVE & PROTECT
ENTRANCE CONE FOR REUSE.
REMOVE & DEMO 18" BFV &
ACTUATOR ASSEMBLY.
COORDINATE W/ MECH DWGS
DEMO SECTION OF 24" Ø SCH 10, TYPE 316 SS
OUTLET PIPE AS NECESSARY, COORDINATE W/
DWG NO. D-1, M-8, M-9 & M-10
INTAKE 2 - REMOVE &
PROTECT TEE-SCREEN FOR
REUSE. REMOVE & DEMO 18"
BFV & ACTUATOR ASSEMBLYPROTECT-IN-PLACE
8"Ø AIR VENT PIPE
AND ASSEMBLY
0+00 0+20 0+40 0+60 0+80 1+00 1+20 1+40
160'
170'
180'
190'
200'
210'
220'
230'
PROTECT-IN-PLACE
4" PVC SCH 80 LEVEL
SENSOR WIRING INSIDE
CONDUIT
PROTECT-IN-PLACE
36"x36" CONDUIT BANK
ENCASING HYDRAULIC,
PNEUMATIC AND
ELECTRICAL SUPPLY
LINES
EXST 3'-0"
ROCK BLANKET
INTAKE 3 - REMOVE & DEMO 18" BFV &
ACTUATOR ASSEMBLY, SEE NOTE 2
EL 207.83'
EL 202.15'
16 34"
MIN
16 34"
MIN
PULL BOX F
SEE DWG D-1
UNBOLT FLANGE AND REMOVE SPOOL AS INDICATED.
INSTALL TEMP BLIND FLANGE
SCALE: 3/16" = 1'-0"
SECTION
NOTES:
1.LAKE LEVELS ARE DEPENDENT ON RAINFALL AND
THE CONTRACTOR HAS TO ACCOUNT FOR THE
LEVEL OF LAKE AT THE TIME OF CONSTRUCTION.
THE LAKE LEVELS WILL NOT BE REDUCED BY THE
CITY.
2.CITY HAS PREVIOUSLY REMOVED THE BARREL
SCREEN AND IS STORED. CONTRACTOR TO
RETRIEVE FROM THE CITY AND REINSTALL.
REPLACE LAKE LEVEL
SENSOR AT EL 192.1
CONTRACTOR SHALL NOT
ROTATE VALVE EXTENSION
STEM.
SPILLWAY
EL 218.65'
SEE NOTE 1 24.50'
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
6
D-3
TS
RK
AE
PIPE AND HOSE SUPPORT DEMOLITION
NTS
EXISTING PEDESTAL #1 PIPE AND HOSE SUPPORT
PROTECT EXST HORIZ PIPE SUPPORT
UNI-STRUT P1001 SS 316, TYP
PROTECT EXST 4" x 6" JUNCTION BOX
NEMA 6P, TYP
PROTECT EXST 3/4" TUBING SS 316
PROTECT EXST 3/4" GRAY PVC SCH 40
ELECTRICAL CONDUIT
REMOVE AND REPLACE TO EXST PNEUMATIC ACTUATOR
VALVE 2, MODIFY FOR REINSTALLATION
REMOVE AND REPLACE TO EXST PNEUMATIC ACTUATOR
VALVE 3, MODIFY FOR REINSTALLATION
REMOVE TO HYDRAULIC ACTUATOR END OF
TRAVEL MICRO SWITCHES EXST VALVE 2.
PREPARE TO ADD NEW CONDUIT & CABLE
PROTECT EXST 3/8" x 3" ANCHOR BOLT
SS 316, TYP
TO INTAKE SCREEN AIR
BACKWASH PORT SCREEN 2
REMOVE TO HYDRAULIC ACTUATOR
END OF TRAVEL MICRO SWITCHES
EXST VALVE 3. PREPARE TO ADD NEW
CONDUIT & CABLE
REMOVE AND REPLACE EXST 3" AIR
HOSE. MODIFY FOR REINSTALLATION,
SEE NOTE 3
PROTECT EXST 3" UNI-STRUT
PIPE CLAMP SS 316, TYP
TO EXST PNEUMATIC ACTUATOR
TO HYDRAULIC ACTUATOR END OF
TRAVEL MICRO SWITCHES
PROTECT EXST 3/4" TUBING SS 316
PRE-BENT W/ FEMALE 37° FLARE AND
NUT SS 316, TYP
PROTECT EXST 3/4" GRAY PVC SCH 40
ELECTRICAL CONDUIT
PROTECT EXST 3" SEAMLESS
PIPE SCH 40 SS 316
PROTECT EXST 4" x 6" JUNCTION
BOX PVC NEMA 6P
REMOVE AND REPLACE EXST 3/4" PNEUMATIC
FLEX HOSES TO EXST PNEUMATIC ACTUATOR.
COORDINATE W/ DWG NO. M-11. MODIFY TO FIT
TO INTAKE SCREEN AIR
BACKWASH PORT, SCREEN 1
PROTECT EXST 3" UNI-STRUT
PIPE CLAMP SS 316, TYP
PROTECT EXST UNI-STRUT PIPE
SUPPORT P1001 SS 316, TYP
REMOVE EXST 3" FLEX AIR HOSE W/ FITTING
REMOVE EXST 3/4" HYDRAULIC FLEX HOSES
TO CYLINDER ACTUATOR AND CAP
PROTECT EXST 3/4" UNI-STRUT PIPE
CLAMP SS 316, TYP
BACK FLUSH HYDRAULIC LINES
TO INTAKE SCREEN AIR
BACKWASH PORT SCREEN 3
NOTES:
1. REMOVE HYDRAULIC 34" TUBING AS INDICATED.
2. NOT USED.
3. THE EXIST 3" HOSE REQUIRES REMOVAL AND MODIFICATION
TO RECONNECT TO THE EXIST DUAL DRUM SCREEN
WHICH IS NOW PART OF EXIST INTAKE 2 SCREEN, AND THE
SINGLE BARREL SCREEN ASSOCIATED WITH EXIST INTAKE 3.
CLEAN AND FLUSH AND REMOVE
EXST 3/4" HYDRAULIC FLEX HOSES
TO CYLINDER ACTUATOR AND CAP
REMOVE AND REPLACE EXST 3/4" PNEUMATIC FLEX
HOSES TO PNEUMATIC ACTUATOR
EXST 24"Ø OUTLET PIPE TO BE REMOVED, MODIFIED
AND REINSTALLED
NTS
EXISTING PEDESTAL #3 PIPE AND HOSE SUPPORT
NTS
WATER INTAKE 2 TEE SCREEN
REMOVE CONDUIT AND WIRE. PREPARE TO ADD
NEW CONDUIT & LIMIT SWITCH WIRING & CABLE
PROTECT EXST 3" THREADED FLANGE SS 316
PROTECT IN-PLACE 18"
PIPE SCH 10 SS 316
NTS
WATER INTAKE 3 DRUM SCREEN
DEMO EXST 18" BUTTERLY VALVE &
ACTUATOR
DEMO EXST 18" BUTTERLY VALVE &
ACTUATOR
PROTECT 24"x18" TEE
FLANGED SCH 10 SS 316REMOVE & PROTECT EXST DUAL DRUM
SCREEN FOR REINSTALLATION
REMOVE & PROTECT EXST SINGLE
DRUM SCREEN FOR REINSTALLATION
BACK FLUSH HYDRAULIC LINES
EXST 24"Ø OUTLET PIPE TO BE REMOVED, MODIFIED
AND REINSTALLED
EXST 24"Ø OUTLET PIPE TO BE
REMOVED, MODIFIED AND
REINSTALLED
PROTECT EXST 3" THREADED FLANGE SS 316,
VERIFY EXIST BLIND FLANGE IS IN-PLACE.
ADD NEW IF REQUIRED
SEE NOTE 3
SEE NOTE 3
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
7
D-4
TS
RK
AE
CONTROL CABINET MODIFICATIONS
SALVAGE/ DEMOLITION
REMOVE AND DEMO ALL 14" SS
TUBING (TYP OF 6)
SALVAGE 3/8" TVTP
FITTINGS
(TYP OF 6)
FITTING TO REMAIN IN PLACE (TYP OF 6)
CLEAN AND FLUSH HYDRAULIC LINES
AND CAP
REMOVE AND SALVAGE ALL
SS TUBING AND FITTINGS
(CITY TO STORE)
DEMO SOLENOID VALVES AND ALL
ASSOCIATED WIRING (TYP)
SALVAGE BALL VALVES AND
DELIVER TO THE CITY (TYP)
REMOVE AND DEMO ALL 3/8"
FLEXIBLE TUBING AND FITTINGS
RELOCATE SPEED CONTROL VALVES
(TYP OF 6) COORDINATE W/ DWG NO. M-5
MANUAL BALL VALVE AND
FITTINGS (TYP OF 3) TO REMAIN
NTS
SOLENOID VALVES
(TYP OF 3) TO REMAIN
CONTROL CABINET MODIFICATION DETAIL DEMO KEY
PROTECT IN PLACE
PNEUMATIC
CONTROL WIRING
DEMO ALL WIRING THAT
CONTROLS THE HYDRAULIC
SYSTEM COMPONENTS
REMOVE AND SALVAGE ALL
HYDRAULIC SS TUBING AND
FITTINGS (CITY TO STORE)
DEMO ALL WIRING THAT
CONTROLS THE HYDRAULIC
SYSTEM COMPONENTS
REMOVE AND SALVAGE
ALL HYDRAULIC SS TUBING
AND FITTINGS
(CITY TO STORE)
PROTECT IN PLACE
WIRING TO THE
PNEUMATIC
ACTUATION UNIT
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
8
M-1
TS
RK
AE
FLOW SYMBOLS AND NOTES
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
9
M-2
TS
RK
AE
FLOW DIAGRAM - CHANGES TO AIR
& HYDRAULIC SYSTEM
EXIST RECIPROCATING
COMPRESSOR (2)
AT
M
O
S
P
H
E
R
I
C
A
I
R
HYDRAULIC OIL
RESERVOIR
90 GAL
RECEIVER
AIR TANK
OUTLET BOX
EXISTING
LEGEND
PROPOSED
P
P
P
MODIFY
VALVE NO. 2
VALVE NO. 1
CONTINUATION TO INTAKE
SCREENS NOT SHOWN
ACCUMULATOR
400 GAL
RECEIVER
AIR TANK
NOTES
1
4
VAULT 'F' LOCATED
ON CREST OF DAM
CONTROLS W/ IN
CONTROL BUILDING
CABINET, SEE M-6
NEW IN-LINE 24" ECC PLUG VALVE PNEUMATIC OPERATED
INTAKE NO. 1
1
2
2
5
6
AIR BACKWASH
7
89
9
9
10
11
2 NEW 18" PLUG VALVE PNEUMATIC OPERATED (TYP OF 2)
3 CLEAN AND FLUSH EXIST HYDRAULIC LINES AND CAP
4
5
6
DEMO HYDRAULIC SYSTEM, HYDRAULIC OIL RESERVOIR
7
SALVAGE EXIST HYDRAULIC BLOCK VALVE AT PANEL WALL
8
HYDRAULIC BALL VALVE AND SOLENOID VALVE
9
CONNECT DISCHARGE SIDES OF AIR RECEIVERS
10
ADD 1/2" BRONZE CHECK VALVE
11
USE EXIST IN-LINE FILTER
(TYP OF 3)
NEW STL PIPE
TOGETHER HERE W/ THREADED FITTINGS.
MODIFY OUTLET
BOX, SEE M-16 & S-2
SEE M-8 & M-9
DISABLE EXIST AIR
BACKWASH SYSTEM
DEMO
INSPECT, TEST AND
REPAIR EXIST
REFRIGERATED
AIR DRYER (TYP OF 2)
EXIST SPEED CONTROL VALVE (TYP)
ROTATE 90° EXIST
CHECK VALVE
PIPING & EQUIPMENT INSIDE THE
CONTROL BUILDING BUT OUTSIDE OF
THE CONTROL CABINET, SEE M-3,M-4 & M-5
12
SEE DWG D-4 (TYP OF 6)
12 ADD 3/8" BRONZE BALL VALVE AT PANEL
WALL. SEE DWG M-4 (TYP OF 6)
OVER FLOW
A3B
VALVE NO. 3
H3B
H3A
H2B
H2A
H1B
H1A
A3B
A3A
A2B
A2A
A1B
A1A
A3A
A2B
A2A
A1B
A1A
AND ACCUMULATOR, AND ELECTRICAL
5
14
14
13
COORDINATE WITH MECH DWGS
13 CLEAN AND FLUSH HYDRAULIC LINES. REMOVE
14 INSTALL PRESSURE TRANSMITTERS, ONE PER
RECEIVER AIR TANK, 90 GAL AND 400 GAL. SEE
SECTION B ON M-3 AND DETAIL 3 ON M-4
PIPING TO BACKWASH SCREENS NOT SHOWN.
CLEAN AND FLUSH EXIST HYDRAULIC LINES, REMOVE HOSES
AND CAP, OUTSIDE SUBMERGED PULLBOX 'G'
15 1" BRONZE BALL VALVE
16 1/2" BRONZE BALL VALVE
17 INSTALL NEW 3/4" PNEUMATIC HOSE FROM OUTSIDE
SUBMERGED PULL BOX 'G' TO VALVE NO. 1
18 INSTALL NEW 3/4" PNEUMATIC HOSE FROM OUTSIDE
SUBMERGED PULL BOX 'H' TO VALVES NO. 2 & NO. 3
HOSES AND CAP OUTSIDE SUBMERGED PULL BOX 'H'
REFER TO DWGS D-3 AND M-11.
3
17
18
15
16
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
INSTALL BLIND FLANGE
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
10
M-3
TS
RK
AE
AIR PIPING MODIFICATIONS OUTSIDE OF
CONTROL CABINET IN CONTROL BLDG
SCALE: 1/2" = 1'-0"
EXISTING CONTROL BUILDING FLOOR PLAN MODIFICATION SECTION KEY
A
-
EXST 90 GAL VERT PNEUMATIC RECEIVER
EXST AIR COMPRESSOR
(TYP OF 2)
EXST 400 GAL VERT AIR
RECEIVER TANK
DEMO EXST HYDRAULIC SYSTEM
RESERVOIR AND ACCUMULATOR.
REMOVE HYDRAULIC LINES THAT
LEAD TO THE VALVE CONTROL
CABINET. FOR MODIFICATIONS,
SEE DWG M-5 & M-6
-
A
NTS
SECTION
REPLACE AIR DRYER
(TYP OF 2)
B
-
-
B
NTS
SECTION
EXST 400 GAL VERT
AIR RECEIVER TANK
REMOVE EXST UNION & ADD
1" BRONZE CHECK VALVE
NEW 1" BRONZE BALL VALVE
NEW GALV UNION
NEW 1" GALV PIPING
NEW GALV PIPING
ADD 1" PIPING, TEES, ELBOWS AND UNION
TO EXST DRYER PIPING
NEW 1" BRONZE BALL
VALVE THDxTHD
C
M-4
E
M-4
D
M-4
REUSE EXST GALV ELBOW
REUSE EXST ELBOW NEW 1" BRONZE BALL
VALVE THDxTHD
FROM AIR DRYER
EXST FREE STANDING OUTLET
VALVE CONTROL PANEL
NEW 1" GALV TEE
PIT 400 SEEMD-1
7NEW 1" x 12" BUSHING
TO PIT 400
INSTALL
PIT 90
INSTALL
PIT 400
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
F
-
EXST CONC EQUIPMENT PAD
-
F
NTS
SECTION
REMOVE VALVE #1 AND
INSTALL BLIND FLANGE
REMOVE EXST PIPING THRU
WALL AND PLUG WALL,
SEE PHOTO 1 FOR
CONTINUATION OF PIPING
REMOVAL IN VAULT
REMOVE INLET PIPING AND
INSTALL BLIND FLANGE
NTS
PHOTO 1
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
11
M-4
TS
RK
AE
CONTROL BLDG
M-3
C
NTS
SECTION
FOR
CONTINUATION
SEE
-
D
NEW 1" GALV PIPING TYP
NEW 1" BRONZE
CHECK VALVE
NEW 1" BRONZE BALL VALVE
DEMO PIPING TYP
M-3
E
NTS
SECTION
ROTATE EXST VALVE TO PROPER
ORIENTATION, CAP TOWARD TOP
M-3
D
NTS
SECTION
NEW PIPE CONTINUES TO THE
BACK WALL AND TO THE LEFT-
C
1" GALV CS PIPE
1" THD GALV COUPLING
1" x 1/2" NPT GALV BUSHING
3/8" FLEX TUBING
1/2" BRONZE
CHECK VALVE
1/2" BRONZE BALL VALVE
1/2" NPT x 3/8" FLEX TUBING FITTING
1/2" MNFT x 3/8" TUBING
FITTING
REMOVE EXST FLEX
TUBING & FITTINGS
SEE DETAIL -
1
SEE DETAIL -
2
EXST 90 GAL AIR
RECEIVING TANK
EXST 90 GAL
AIR RECEIVING
TANK
-
1
NTS
DETAIL
-
2
NTS
DETAIL
EXST 2" CPLG
1/2" x 1/2" GALV THD NIPPLE (TYP)
EXST 3/4" x 2"
GALV BUSHING
EXST 3/4" x 3/4"
GALV BUSHING
1/2" GALV THD ELBOW
1/2" BRONZE CHECK VALVE
1/2" BRONZE BALL VALVE
1/2" MNPT x 3/8"
TUBING FITTING
3/8" FLEX TUBING
REUSE EXST
AIR FILTER
REUSE EXST
BALL VALVE
NEW 3/8" BRONZE BALL VALVE
NEW 3/8" BRASS NIPPLE
NEW 3/8" MNPT x 3/8"
TUBING FITTING
NEW 3/8" TUBING
NEW 1" GALV
PIPE TO
FITTING BELOW
NEW 1" GALV PIPE TO
FITTING TO THE RIGHT
3/8" FLEX TUBING
12" GALV NIPPLE
TO EXST AIR FILTER
-
2
FROM EXST 400 GAL
AIR RECEIVER
FROM EXST 90 GAL
AIR RECEIVING TANK
REUSE EXST
FITTING
INTERIOR OF
CONTROL PANEL
1/2" GALV NIPPLE BOTH SIDES
OF CHECK VALVE
NEW 3/8" BRASS NIPPLE
EXST 90 GAL AIR
RECEIVING TANK
DEMO ALL HYDRAULIC
CONNECTIONS, TUBING
AND HOSE
1/2" GALV THD TEE
MD-1
7PIT 90 SEE
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
12
M-5
TS
RK
AE
CONTROL CABINET
SYSTEM MODIFICATION
NTS
MODIFICATIONS TO CONTROL CABINET - CONTROL BUILDING
-
1
DETAIL
NTS
1
-
EXST CONTROL
CABINETDEMO TUBING
NEW 3/8" TUBING,
FOR ROUTING
SEE DETAIL
DEMO FITTING
& REPLACE
W/ BALL VALVE
PROPOSEDEXISTING
ADD NEW VALVE
& FITTING SEE
PROPOSED
SHOWN
(TYP OF 6)
EXST BULKHEAD
FITTING W/ 3/8"
MNPT INTO THE
CABINET
DETAIL
NTS
2
-
RIGHT INTERIOR SIDE
OF EXST CONTROL
CABINET
SALVAGE EXST
BALL VALVE AND
DELIVER TO CITY
EXISTING
CLEAN AND FLUSH HYDRAULIC
LINES AND CAP
NEW EXST
MODIFY EXST PNEUMATIC FITTINGS
AND TUBING BY ADDING NEW VALVES
AT SIX (6) LOCATIONS WHERE LINES
EXIT CONTROL PANEL PER DETAIL
(FOR LOCATION SEE M-3)
DEMO HYDRAULIC
TUBING AND
FITTINGS,
SEE DWG D-4
M-6
1
NOTE: COORDINATE MODIFICATIONS WITH DWG M-2.
NEW 3/8" BRONZE
THDxTHD BALL
VALVE
RIGHT INTERIOR SIDE OF
EXST CONTROL CABINET
PROTECT IN PLACE PNEUMATIC
CONTROLLER AND WIRING
COORDINATE WITH DWG D-4 FOR ALL
OTHER HYDRAULIC SYSTEM
COMPONENTS REMOVAL AND DEMO
SPEED CONTROL
VALVE
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
-
2SEE DWG D-4 AND DETAIL
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
13
M-6
TS
RK
AE
CONTROL CABINET TUBING ROUTING
M-5
1
NTS
NEW 3/8" NYLON TUBING ROUTING W/ IN CONTROL CABINET
A1A
EXST PNEUMATIC 3-POSITION 4-WAY
SOLENOID STACK
EXST CONTROL PANEL
A1B
A2A
A2B
A3A
A3B
MODIFICATIONS PER DWG M-5.
CONNECT TUBING AS INDICATED
ON DWG M-5
CONNECT TUBING TO
CORRESPONDING VALVES PER
DWG M-5, TYP OF 6
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
14
M-7
TS
RK
AE
PULL BOX 'F' MODIFICATIONS
NTS
MODIFICATIONS TO PULL BOX 'F'
-
1 FOR LINE DESIGNATION
LINE DESIGNATION
NTS
1
-
EXST PULL BOX 'F'
NOTE: VERIFY LINE DESIGNATION WITH IN
THE EXISTING CONTROL PANEL PRIOR TO
PERFORMING MODIFICATIONS TO PULL
BOX 'F'
A1A
A1B
A2A
A2B
A3A
A3B
REPLACE LEVEL TRANSMITTER
TERMINATION ENCLOSURE
CAP (TYP OF 6)
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
15
M-8
TS
RK
AE
OUTLET PIPE MODIFICATION PLAN
SCALE: 3/16" = 1'-0"
EXST OUTLET TOWER AND
GRATING COVER
EXST CONDUIT BANK
(TYP)
PROTECT EXST
TERMINAL/PULL
BOX 'F2'
EXST 30" RCP OUTLET PIPE
EXST PIPE SUPPORT BENT
(TYP OF 3)
EXST OUTLET BOX W/GRATING,
FOR MODIFICATIONS SEE
VALVE 3 - INSTALL 24" ECC PLUG VALVE W/PNEUMATIC ACTUATOR
PROTECT EXIST 8"Ø AIR
VENT PIPE AND ASSEMBLY
PROTECT EXST PULL BOX 'F',
SEE M-1
EXST 24"Ø OUTLET PIPE
8"Ø SS TYPE 316 SCH 10 VENT
PIPING
VALVE 2 - INSTALL 18" PLUG VALVE W/PNEUMATIC ACTUATOR.
SEE DWG M-13 & M-14. RETRIEVE BARREL SCREEN FROM CITY
STORAGE AND INSTALL. (REPLACES EXST VALVE 3)
PROTECT EXST
4" CONDUIT
LEVEL SENSOR
PROTECT EXST
TERMINAL/PULL
BOX 'F1'
PROTECT EXST TERMINAL/PULL
BOX 'G'
EXST TERMINAL/PULL BOX 'H'
FABRICATE SCH 10, TYPE 316 SS PIPE W/ CLASS
D 24" TYPE 316 SS FLG. INSTALL UNDER
SUBMERGED CONDITIONS. SEE DWGS M-9 & M-10
VALVE 1 - INSTALL 18" ECC PLUG VALVE
W/ PNEUMATIC ACTUATOR TO REPLACE
18" BFV AND REINSTALL TEE BARREL
SCREENS. INLET SCREEN ROTATED
ONE (1) BOLT HOLE CLOCKWISE. SEE
DWG M-9. (REPLACES EXST VALVE 2)
B
M-1
0
A
M-1
1
A M-9
A
M-1
3
REMOVE OUTLET PIPING HEADER, REUSE EXST 24"x18" TEE SECTION. PROVIDE FULL
PENETRATION WELD EACH END UNDER SHOP CONTROLLED CONDITIONS. REINSTALL
COMPLETE HEADER UNDER SUBMERGED CONDITION. SEE DWG M-10
EXST INTAKE # 1 - INSTALL 18", SCH 10, TYPE 316 SS SPOOL
PIECE W/ 18" CLASS D FLANGES, TYPE 316 SS BOTH ENDS.
VERIFY NEW SPOOL LENGTH PROVIDES ENTRANCE CONE
WEIR ELEVATION TO MATCH EXISTING
M-16
1
NOTES:
1.CONTRACTOR TO REMOVE 24" OUTLET PIPE BETWEEN
THE CONNECTION TO THE 8" Ø AIR VENT PIPE AND THE
24" FLANGE AT OUTLET TOWER TO MODIFY UNDER
SHOP CONDITIONS.
2.VALVE 1, 2 & 3 TO BE INSTALLED WITH 4 - 5 LB MAG
ANODES.
3.INSTALL ISOLATION FLANGE KITS BOTH SIDES OF
VALVES 1, 2 & 3.
4.LEVEL TRANSMITTER SHALL BE WATERPILOT MODEL
FMX21 WITH ORDER NUMBER: FMX21-AA221KGE25A+PS
INCLUDING 120' (CONTRACTOR TO FIELD VERIFY
LENGTH) OF SHORTABLE SUBMERSIBLE CABLE, AND A
TERMINABLE BOX. NO SUBSTITUTIONS.
MD-1
1
MD-1
2
REPLACE LEVEL SENSOR
AND SUBMERSIBLE CORD (SEE NOTE 4)
LEVEL SENSOR
TERMINATION
ENCLOSURE
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
FLANGE (TYP)
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
16
M-9
TS
RK
AE
OUTLET PIPE MODIFICATION SECTION 1
SCALE: 3/16" = 1'-0"
EXST OUTLET TOWER AND
GRATING COVER
M-8
A
EXST TERMINAL/PULL
BOX (TYP)
EXST 30" RCP OUTLET PIPE
PROTECT-IN-PLACE PIPE
SUPPORT BENT #1
PROTECT EXST 8"Ø AIR
VENT PIPE AND ASSEMBLY
SECTION
0+00 0+20 0+40 0+60 0+80 1+00 1+20 1+40
160'
170'
180'
190'
200'
210'
220'
230'
EXST 4" PVC SCH 80 LEVEL SENSOR
WIRING INSIDE CONDUIT
EXST 36"x36" CONDUIT BANK
ENCASING HYDRAULIC, PNEUMATIC
AND ELECTRICAL SUPPLY LINES
EXST 3'-0"
ROCK
BLANKET
VALVE 3 - INSTALL 24" PLUG VALVE W/PNEUMATIC
ACTUATOR TYPE 316 SS HEADER AND 34" FLEXIBLE
HOSE. SEE DWGS M-13 & M-15
NOTES:
1. PERFORMING THE WORK SHOWN ON THIS SHEET REQUIRES ISOLATION
OF OUTLET PIPE WITHIN OUTLET BOX. SEE DWG NO. M-16.
2. REPLACE EXISTING ACTUATOR HOSE CONNECTIONS WITH SS TUBING.
3. FOR TUBING ROUTING SEE DWGS M-11, M-12, M-13, M-14 & M-15.
4. VALVE 1, 2 & 3 TO BE INSTALLED WITH 4 - 5 LB MAG ANODES.
5. INSTALL ISOLATION FLANGE KITS BOTH SIDES OF VALVES 1, 2 & 3.
FABRICATE 24" SCH 10, TYPE 316 SS PIPE W/
CLASS D FLANGE INSTALL UNDER SUBMERGED
CONDITIONS, SEE DWG M-10
PROTECT-IN-PLACE PIPE
SUPPORT BENT #2
PROTECT-IN-PLACE PIPE
SUPPORT BENT #3
VALVE 1 - INSTALL 18" ECC PLUG VALVE W/ PNEUMATIC
ACTUATOR TYPE 316 SS HEADER, AND 34" FLEXIBLE HOSE. SEE
REMOVE OUTLET PIPING & COORDINATE W/ DWG D-2. REUSE
EXST 24"x18" TEE SECTION. PROVIDE FULL PENETRATION WELD.
REINSTALL UNDER SUBMERGED CONDITION. SEE DWG M-10EXST INTAKE #1 - INSTALL 18",
SCH 10, TYPE 316 SS SPOOL
PIECE W/ 18" CLASS D FLANGES,
TYPE 316 SS BOTH ENDS. VERIFY
NEW SPOOL LENGTH PROVIDES AN
ENTRANCE CONE WEIR ELEVATION
TO MATCH EXISTING
VALVE 2 - INSTALL 18" ECC PLUG VALVE W/ PNEUMATIC ACTUATOR
TYPE 316 SS HEADER AND 34" FLEXIBLE HOSE, SEE DWGS M-13
& M-14. RETRIEVE BARREL SCREEN FROM CITY STORAGE AND INSTALL.
REMOVE NUTS AT SUPPORTS
AS NECESSARY TO REMOVE
24" PIPE SECTION. WORK
POTENTIALLY UNDER
SUBMERGED CONDITIONS.
M-11
A
TO OUTLET BOX
M-12
A
MD-1
1
MD-1
2
7' DIA
EL 203.28'
SPILLWAY
EL 218.65'
PROVIDE PIPE
SUPPORTS AT
EACH BENT FOR
NEW 8" VENT
PIPE
EL 207.83'
24.50'
1/2" DIA ROUND BARS x 13' CIRCUMFERENTIAL LENGTH,
WELD TO EVERY OTHER VERTICAL BAR, 5 TOTAL.
GALVANIZE DEBRIS SCREEN AFTER FABRICATION.
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
"S" FITTING
FLANGES
ISOLATION
KIT
160'
170'
180'
190'
200'
220'
230'
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
17
M-10
TS
RK
AE
OUTLET PIPE MODIFICATION SECTION 2
SCALE: 1/2" = 1'-0"M-8
BSECTION
12'-2" ± (FIELD VERIFY)
EXST OUTLET TOWER12"3'-6"
SEE NOTE 1SEE NOTE 1
C/L PIPE SUPPORT
BENT #3
WELD 8"Ø AIR VENT PIPE
CONNECTION, SEE SECTION
THIS SHT
EXSTNEW
PERFORM FULL PENETRATION
WELD UNDER CONTROLLED
FAB SHOP CONDITIONS
EXST 24"Ø PIPE
EXST
[REF]
10
"
±
NEW
FLANGE
24" SCH 10
TYP 316 SS
PIPE
REUSE EXST
TEE SECTION
A-
SCALE: 1/2" = 1'-0"-
ASECTION
24" SCH 10 TYP 316 SS PIPE
10
"
±
38" THK PIPE REINFORCMENT
AND COMPLY W/ AWWA M-11
8" Ø SCH 10 TYP 316 SS
FIELD DETERMINE TO PROVIDE CLEARANCE
AT VALVES, PIPING AND SUPPORT BENTS
VALVE 3
8" CLASS D TYPE 316 SS FLGS
8" Ø SCH 10 TYPE 316 SS PIPE.
SEE M-9 FOR CONTINUATION
INSTALL ISOLATION
FLANGE KIT BOTH
SIDES OF VALVE
MD-1
2
ANODE TYP
INSTALL PER
DETAIL
MD-1
1
12"
NOTE:
1. CONTRACTOR TO INSTALL EXST
TEE AND VALVE 2 TO AVOID
INTERFERENCES W/ VALVE 3.
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
18
M-11
TS
RK
AE
HOSING ROUTING - VALVE 1
SCALE: 1/2" = 1'-0"M-8
ASECTION
B -
SCALE: 1/2" = 1'-0"-
BSECTION
AM-
1
2
B M-
1
2
SEE NOTE 1
34" HOSE IN SAME PLANE
HOSE LENGTH TO ALLOW
FOR DRY CONNECTION
ABOVE WATER SURFACE
TO ACTUATOR HOSE
NOTES:
1.CONNECT NEW 34" HOSE TO THE TWO EXISTING 3 4" PNEUMATIC TUBING LINES,
AND CONTROL WIRING AND CABLE. CLEAN AND FLUSH HYDRAULIC LINES
PRIOR TO REMOVAL AND CAP. COORDINATE WITH DWGS D-3, M-2 AND
ELECTRICAL.
2.FIELD VERIFY AND COORDINATE CONTROL PANEL OPERATION WITH
CORRESPONDING PNEUMATIC TUBING AND CONTROL WIRING PRIOR TO
MAKING CONNECTIONS. VERIFY CONTROL PANEL OPEN COMMAND RESULTS IN
OPENING THE VALVE, AND LIMIT SWITCH RESULTS IN OPEN INDICATIONS.
VERIFY OPEN AND CLOSE ACTION, AND INDICATION FOR EACH VALVE.
3.VALVE / PIPING / TUBING ARRANGEMENT SHOWN SCHEMATICALLY. TUBING MAY
BE FIELD ADJUSTED HORIZONTALLY OR VERTICALLY OR PLACED IN A
DIFFERENT PLANE FROM THAT SHOWN.
NOTES:
1. PNEUMATIC LINE DESIGNATION & LOCATION
WITHIN THE EXST CONDUIT BANK ARE
PROVIDED FOR REFERENCE ONLY. FIELD VERIFY.
2. THE EXIST 3" SS SCH 40 AIR BACKWASH PIPING
REQUIRES MODIFICATION TO RECONNECT TO
THE EXIST DUAL DRUM SCREEN WHICH IS NOW
PART OF EXIST INTAKE 2 SCREEN. MODIFY THE
PIPING AS NECESSARY.
ADD SPOOL TO EXST INTAKE #1,
SEE DWG M-9
NEW
EXST
A1A
CABLE AND CONDUIT FOR OPEN & CLOSE
LIMIT SWITCHES PROVIDE WATER TIGHT
CONNECTION, COORDINATE W/ VALVE
MANUFACTURER.
A1B
-
1
EXIST SUPPORT BENT #1
EXIST SUPPORT BENT #2
EXIST SUPPORT BENT #3
EXIST TERMINAL/PULL BOX 'G'
EXIST TERMINAL/PULL BOX 'H'
NEW
EXST 3/4"
SS TUBING
CONTROL
CONDUIT
A1A
ADD AIR VENT PIPING,
SEE DWG M-8 & M-9
-
1
NTS
WATER INTAKE TEE SCREEN
EXST 18"Ø PIPE
VALVE 1
18" ECC PLUG VALVE
REINSTALL EXST INTAKE TEE
SCREENRECONNECT AIR
BACKWASH PIPING
VALVE 1
INSTALL ISOLATION FLANGE KIT
BOTH SIDES OF VALVE
MD-1
2
ANODE TYP, INSTALL PER DETAILMD-1
1
EXST INTAKE #1
A1B
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
ISOLATION KIT AT CONE
INLET CONNECTION TO
SS FLANGE
UV RESISTANT ELEC CONDUIT. MOUNT
CONDUIT TO THE BOT OF THE 24" HEADER
PIPING. SECURE W/SPECIFIED TIE STRAPS.
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
19
M-12
TS
RK
AE
CONTROL HOSING AND PIPING
ROUTING SECTIONS - VALVE 1
SCALE: 1 1/2" = 1'-0"M-11
AVALVE 1 HOSING SECTION
34" HOSE EXST 3 4" TUBING
SEE M-11 FOR
CONTINUATION
SEAT END
FR
O
M
B
A
R
R
E
L
S
C
R
E
E
N
B -
NOTES:
1.VALVE / PIPING / HOSING ARRANGEMENT SHOWN
SCHEMATICALLY. HOSING MAY BE FIELD ADJUSTED
HORIZONTALLY OR VERTICALLY OR PLACED IN A DIFFERENT
PLANE FROM THAT SHOWN. SUBMIT PROPOSED PIPING &
HOSING ARRANGEMENT FOR ENGINEER'S APPROVAL PRIOR
TO FABRICATION (TYP FOR ALL THREE VALVES).
2.CONNECT NEW 3/4" HOSE TO THE TWO EXISTING 3/4"
PNEUMATIC TUBING LINES, CONNECT CONTROL WIRE AND
CABLE AND FLUSH HYD LINES PRIOR TO REMOVAL AND CAP.
3.VERIFY AT THE CONTROL PANEL THAT PRESSURE ON A1A IS
DESIGNED TO CLOSE THE VALVE.
FR
O
M
B
A
R
R
E
L
S
C
R
E
E
N
SCALE: 1 1/2" = 1'-0"-
BVALVE 1 HOSING SECTION
NOTE:
COORDINATE SUPPLY AND RETURN PNEUMATIC
HOSING FROM CONTROL ROOM. SEE DWG M-11
AND FIELD VERIFY.
WATER SURFACE
VARIES
A1A A1B
WATER SURFACE
VARIES
VALVE 1
TO
O
U
T
L
E
T
B
O
X
A1A
ANODE TYP
INSTALL PER
DETAIL
MD-1
1
INSTALL ISOLATION
FLANGE KIT BOTH SIDES OF
VALVE
MD-1
2
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
A1B
DISCONNECT COUPLING
(TYP)
THREADED
CONNECTION
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
20
M-13
TS
RK
AE
HOSING ROUTING - VALVE 2 & 3
SCALE: 1/2" = 1'-0"M-8
ASECTION
AM-
1
4
SCALE: 3/4" = 1'-0"-
BSECTION
B -
A
M-15
SEE NOTE 1
8 SEPARATE SUPPLY AND
RETURN PNEUMATIC TUBING
LINES FROM CONTROL ROOM.
COORDINATE W/ THIS DWG
SECTION A AND DWG D-3
TOP VIEW
VALVE 3
CONDUIT AND WIRE FOR CONTROL
VALVE 3 OPEN/CLOSED LIMIT SWITCHES
A2A
A2B
A3A
A3B
NOTE: FOR ENLARGED DETAIL OF
TUBING FOR VALVE 3, SEE
M-15
A
NOTE: PNEUMATIC LINE DESIGNATION &
LOCATION WITHIN THE EXST CONDUIT
BANK ARE PROVIDED FOR REFERENCE
ONLY. FIELD VERIFY
FOR CONTINUATION SEE DWG M-14 & M-15.
SEE NOTE 3 THIS SHEET
A2A
A2B
A3A
A3B
VALVE 2 CONTROL CONDUIT AND WIRE
VALVE 3 CONTROL CONDUIT AND WIRE
NOTES:
1.CONNECT NEW 34" HOSE TO THE TWO EXISTING 34" PNEUMATIC TUBING
LINES, CONNECT CONTROL WIRE AND CABLE AND FLUSH HYD LINES PRIOR
TO REMOVAL AND CAP. COORDINATE WITH DWGS D-3, M-2 AND ELECTRICAL.
2.FIELD VERIFY AND COORDINATE CONTROL PANEL OPERATION WITH
CORRESPONDING PNEUMATIC TUBING AND CONTROL WIRING PRIOR TO
MAKING CONNECTIONS. VERIFY CONTROL PANEL OPEN COMMAND RESULTS
IN OPENING THE VALVE, AND LIMIT SWITCH RESULTS IN OPEN INDICATIONS.
VERIFY OPEN AND CLOSE ACTION, AND INDICATION FOR EACH VALVE.
3.VALVE / PIPING / HOSING ARRANGEMENT SHOWN SCHEMATICALLY. HOSING
MAY BE FIELD ADJUSTED HORIZONTALLY OR VERTICALLY OR PLACED IN A
DIFFERENT PLANE FROM THAT SHOWN.
4.SUPPORTS FOR THE HOSING AND CONDUIT ARE NOT SHOWN. CONTRACTOR
TO PROVIDE AS NECESSARY.
EXIST SUPPORT BENT #3
EXIST TERMINAL/PULL BOX 'H'
EXIST OUTLET TOWER
SEE NOTE 1
NEW
EXIST
CONDUIT AND WIRE FOR CONTROL
VALVE 2 OPEN/CLOSED LIMIT SWITCHES
INSTALL ISOLATION FLANGE KIT
BOTH SIDES OF VALVE
MD-1
2
ANODE TYP
INSTALL PER
DETAIL
MD-1
1
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
NOTE: H2A, H2B, H3A AND H3B LINES
HAVE BEEN CAPPED. SEE DWG D-3.
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
21
M-14
TS
RK
AE
CONTROL HOSING AND PIPING
ROUTING SECTIONS - VALVE 2
SCALE: 1 1/2" = 1'-0"M-13
AVALVE 2 - SECTION
DISCONNECT COUPLING
(TYP)
FROM BARREL SCREEN
SIDE VIEW
TOP VIEW
SEAT END
SEAT END
VALVE 2
34" HOSEEXST 34" TUBING
EXST 18"Ø TYPE 316 SS PIPE
EXST 18"Ø TYPE 316 SS PIPE
TO OUTLET HEADER TOWER &
OUTLET BOX
A2B
A2A
-
2
-
2
NTS
WATER INTAKE DRUM SCREEN
EXST 24"Ø PIPE
VALVE #2 ECC PLUG VALVE
EXST 24"x18" TEE
REINSTALL
EXST SCREEN
RECONNECT AIR
BACKWASH PIPING,
SEE NOTE 5
ANODE TYP
INSTALL PER
DETAIL
MD-1
1
INSTALL ISOLATION FLANGE KIT
BOTH SIDES OF VALVE
MD-1
2
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
NOTES:
1.CONNECT NEW 34" HOSE TO THE TWO EXISTING 34" PNEUMATIC TUBING LINES,
CONNECT CONTROL WIRE AND CABLE AND FLUSH HYD LINES PRIOR TO REMOVAL
AND CAP. COORDINATE WITH DWGS D-3, M-2 AND ELECTRICAL.
2.FIELD VERIFY AND COORDINATE CONTROL PANEL OPERATION WITH CORRESPONDING
PNEUMATIC TUBING AND CONTROL WIRING PRIOR TO MAKING CONNECTIONS. VERIFY
CONTROL PANEL OPEN COMMAND RESULTS IN OPENING THE VALVE, AND LIMIT
SWITCH RESULTS IN OPEN INDICATIONS. VERIFY OPEN AND CLOSE ACTION, AND
INDICATION FOR EACH VALVE.
3.VALVE / PIPING / HOSING ARRANGEMENT SHOWN SCHEMATICALLY. HOSING MAY BE
FIELD ADJUSTED HORIZONTALLY OR VERTICALLY OR PLACED IN A DIFFERENT PLANE
FROM THAT SHOWN.
4.SUPPORTS FOR THE HOSING AND CONDUIT ARE NOT SHOWN. CONTRACTOR TO
PROVIDE AS NECESSARY.
5.MODIFY EXIST 3" SS SCH 40 PIPE IN ORDER TO RECONNECT BARREL SCREEN.
THREADED CONNECTION
THREADED CONNECTION
3 4" HOSEEXST 34" TUBING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
22
M-15
TS
RK
AE
CONTROL HOSING AND PIPING
ROUTING SECTIONS - VALVE 3
SCALE: 1 1/2" = 1'-0"
VALVE 3 SECTION
M-11
A
SEAT END
TO TOWER & OUTLET BOX
TO TOWER
TOP VIEW
24"Ø SCH 10 TYPE 316 SS PIPE
24"Ø SCH 10 TYPE 316 SS PIPE
SIDE VIEW
SEE NOTE 1
SEAT END
A3B
A3A
SEE SIDE VIEW
ANODE TYP
INSTALL PER
DETAIL
MD-1
1
INSTALL ISOLATION FLANGE
KITS BOTH SIDES OF VALVE
MD-1
2
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DISCONNECT COUPLING
(TYP)
3 4" HOSEEXST 34" TUBING
NOTES:
1.CONNECT NEW 3 4" HOSE TO THE TWO EXISTING 34" PNEUMATIC TUBING LINES,
CONNECT CONTROL WIRE AND CABLE AND FLUSH HYD LINES PRIOR TO REMOVAL
AND CAP. COORDINATE WITH DWGS D-3, M-2 AND ELECTRICAL.
2.FIELD VERIFY AND COORDINATE CONTROL PANEL OPERATION WITH CORRESPONDING
PNEUMATIC TUBING AND CONTROL WIRING PRIOR TO MAKING CONNECTIONS. VERIFY
CONTROL PANEL OPEN COMMAND RESULTS IN OPENING THE VALVE, AND LIMIT
SWITCH RESULTS IN OPEN INDICATIONS. VERIFY OPEN AND CLOSE ACTION, AND
INDICATION FOR EACH VALVE.
3.VALVE / PIPING / HOSING ARRANGEMENT SHOWN SCHEMATICALLY. HOSING MAY BE
FIELD ADJUSTED HORIZONTALLY OR VERTICALLY OR PLACED IN A DIFFERENT PLANE
FROM THAT SHOWN.
4.SUPPORTS FOR THE HOSING AND CONDUIT ARE NOT SHOWN. CONTRACTOR TO
PROVIDE AS NECESSARY.
5.MODIFY EXIST 3" SS SCH 40 PIPE IN ORDER TO RECONNECT BARREL SCREEN.
THREADED CONNECTION
34" HOSEEXST 3 4" TUBING
THREADED CONNECTION
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
23
M-16
TS
RK
AE
EXISTING OUTLET BOX MODIFICATIONS
M-8
1
SCALE: 3/4" = 1'-0"
EXISTING OUTLET BOX
A -
20" BFV
EXST OUTLET BOX
FLOW
JOINT SEALER,
SIKASWELL A (TYP)
3'-0"
20" SCH 40 TYPE 316
SS PIPE THIMBLE
76" (APPROX)
1'-3"
NEW CONC SEE
STRUCTURAL DWGS
FOR REINFORCEMENT
4" (APPROX)
20" OD SCH 10
TYPE 316 SS
96" (APPROX)
68" (APPROX)
EXST OUTLET BOX
-
A
SCALE: 3/4" = 1'-0"
SECTION
NEW GRATING
B-
-
B
SCALE: 1" = 1'-0"
SECTION
NOTE: CONTRACTOR TO VERIFY
ID OF EXIST OUTLET PIPE LINER
PRIOR TO FABRICATION OF PIPE
THIMBLE AND VALVE
REPLACEMENT.
38" THK x 5" WIDE TYPE 316
THRUST RING. WELDED ALL
AROUND BOTH SIDES
20" BFV
TYPE 316 SS OPERATOR
EXTENSION STEM.
TRUMBULL OR EQUAL
3
MD-1
REMOVE AND DISPOSE OF
EXISTING SOIL TO A DEPTH OF
9 INCHES BELOW AND 4 FT
BEYOND PERIMETER OF VAULT
INSTALL 3/8"x2"x78" GALV FLAT
BAR AND 1/2" DIA x 6" LONG
TYPE 316 SS ALL-THREAD, LOCK
WASHERS AND NUTS SET IN
EPOXY ADHESIVE. TYPICAL OF
4 ASSEMBLIES.
HYDRO-PHILIC WATER
STOP ALL AROUND, SIKA
HYDROTITE CJ (TYP)
EXIST PIPE, ID 20 12"
REPLACE GRATE WITH
NEW, MATCH EXST
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
ISOLATION FLANGE
KIT PER 2
MD-1
EXST GRATING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
24
MD-1
TS
RK
AE
MECHANICAL DETAILS
-
1
NTS
ANODE MOUNTING
-
2
NTS
ISOLATION FLANGE KIT
-
3
NTS
OUTLET BOX "WATER" COVER
1/4" THK PL COVER
(DIAMOND PLATE)
8"
6"
14" FLANGE
WALL BRACKET (TYP OF 2 ON
UPPER STEM EXTENSION)
6" SCH 40 GALVANIZED
PIPE, AFTER FABRICATION
-
7
NTS
PRESSURE INDICATOR / TRANSMITTER
3 12" DIA PRESSURE
GAUGE, LIQUID
FILLED, 14" NPT
CONNECTION,
SPEC 17329
PRESSURE INDICATING
TRANSMITTER AND
SENSOR, SPEC 17329
12" 316 SS DIRECT
MOUNT BLOCK AND
BLEED MANIFOLD
12" 316 SS BALL
VALVE
400 GAL / 90 GAL
RECEIVER
CONNECTOR PER
LOCATION
UNIVERSAL
MOUNTING
BRACKET
12" NPT 316 SS
ADAPTER
A (TO BE FIELD VERIFIED)
B (TO BE FIELD VERIFIED)
3
12"
1"
HOLE Ø TO MATCH
FLANGE HOLE Ø
316" x 2" MILD
STEEL BAR
COATING PER
SECTION 09900
NOTES:
ANODE - FARWEST CORROSION CONTROL COMPANY. PROMAG
SPECIALTY MAGNESIUM ML-5 LAUNCH ANODE 5LBS. MOUNT 4 PER
VALVE. ADJUST TO HANG VERTICALLY. VERIFY ELECTRICAL
CONTINUITY BETWEEN EACH ANODE AND CORRESPONDING CI
VALVE. DO NOT PAINT ANODES.
NO BEND HERE IF USED ON A HORIZONTALLY MOUNTED VALVE.
58" Ø HOLE FOR
MOUNTING ANODE,
UTILIZE 12" Ø BOLTS,
WASHER BOTH SIDES
W/ DOUBLE NUTS
STEEL THREADED STUD
INSULATING SLEEVE (FULL WIDTH)
INSULATING WASHER
(BOTH ENDS OF STUD)
STEEL WAHSER & NUT
(SS FLG END)
INSULATING
GASKET
NOTES:
1.USE HALF WIDTH SLEEVES AT THREADED FLANGE BOLTS (I.E.
AT BFV BONNET).
2.INSULATING MATERIALS:
PHENOLIC GASKE - TYPE "E" NEOPRENE FACED
INSULATING SLEEVE - 132 INCH CE PHENOLIC TUBING
INSULATING WASHER - LAMINATED CE PHENOLIC
1.
2.
SEE NOTE 2
SS BUSHING, SIZE
AS REQUIRED
2" SQ NUT
OMIT THIS PORTION
FOR VALVES
MOUNTED HORIZ
ADD
ADDITIONAL
HOLE AS
NECESSARY
FOR ANY
GIVEN
LOCATION
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
OPERATOR STEM
EXTENSION
1"
M
A
X
NEW GRATING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
REQUIRED VERIFICATION AND INSPECTION OF
CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION CONTINUOUS
INSPECTION
PERIODIC
INSPECTION
CITY OF CARLSBAD
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
518-85054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
KelseyStructural
gkelsey@kelseystructural.com
8320 Lake Ashwood Ave.
San Diego, CA 92119
619.920.1262
25
S-1
STRUCTURAL GENERAL NOTES
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
CITY OF CARLSBAD
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
518-85054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
KelseyStructural
gkelsey@kelseystructural.com
8320 Lake Ashwood Ave.
San Diego, CA 92119
619.920.1262
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
26
S-2
STRUCTURAL PLAN, SECTION,ELEVATION AND DETAILS
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
"RECORD DRAWING"
518-8
27
E-1
CAD
JM
JM
STANDARD ELECTRICAL SYMBOLS
AND ABBREVIATIONS
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
"RECORD DRAWING"
518-8
28
E-2
CAD
JM
JM
ELECTRICAL
SITE PLAN
LAKE CALAVERA
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
"RECORD DRAWING"
518-8
29
E-3
CAD
JM
JM
CONTROL BUILDING
ELECTRICAL PLAN
SCALE: 1/2" = 1'-0"
EXISTING CONTROL BUILDING FLOOR PLAN
PARTIAL SINGLE LINE DIAGRAM
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
"RECORD DRAWING"
518-8
30
E-4
CAD
JM
JM
CONTROLS
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
"RECORD DRAWING"
518-8
31
E-5
CAD
JM
JM
PHOTOS
NTS
HYDRO PNEUMATIC CONTROL
NTS
LCP INTERNAL ELEVATION
NTS
LCP EXTERNAL ELEVATION
NTS
RTU ELEVATION
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024
THIS RECORD DRAWING HAS BEEN PREPARED, IN
PART, BASED UPON INFORMATION FURNISHED BY
OTHERS. THE INFORMATION IS NOT GUARANTEED
AS CORRECT, ACCURATE, OR COMPLETE. USERS OF
THIS RECORD DRAWING ARE ADVISED TO PERFORM
INDEPENDENT VERIFICATION OF ACCURACY BEFORE
APPLYING IT FOR ANY PURPOSE.
RECORD DRAWING
LAKE CALAVERA OUTLET IMPROVEMENTS
IMPROVEMENT PLAN FOR:
32
5054
E N G I N E E R I N G C O R P O R A T I O N
"RECORD DRAWING"
518-8
32
VS-1
TS
RK
AE
TERMINAL BLOCK DIAGRAMS
DocuSign Envelope ID: 01957809-128D-4F7E-BF8A-9807FB0D46A8
6/24/2024