HomeMy WebLinkAbout1979 PALOMAR OAKS WAY; ; CBC2023-0259; PermitBuilding Permit Finaled
Ccityof
Carlsbad
Commercial Permit
Print Date: 06/04/2024
Job Address: 1979 PALOMAR OAKS WAY, CARLSBAD, CA 92011-1307
Permit No:
Status:
CBC2023-0259
Closed -Finaled
Permit Type: BLDG-Commercial Work Class: Tenant Improvement
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load:
Code Edition:
Sprinkled:
Project Title:
2130922100 Track#:
$15,101.68 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Applied: 08/18/2023
Issued: 01/23/2024
Finaled Close Out: 06/04/2024
Final Inspection: 05/07/2024
INSPECTOR: Kersch, Tim
Description: VERSUM MATERIALS US: 282 SF Tl TO INSTALL 3 VERTICAL STORAGE MODULES IN EXISTING FACILTITY // ADDITONAL
SPRINKLER WORK; NO CHANGE OF USE
Property Owner:
VERSUM MATERIALS US LLC
8555 RIVER PKWY
TEMPE, AZ 85284-2601
FEE
BUILDING PLAN CHECK
BUILDING PLAN REVIEW -MINOR PROJECTS (LOE)
BUILDING PLAN REVIEW -MINOR PROJECTS (PLN)
CERTIFICATE OF OCCUPANCY
COMM/IND Tl -STRUCTURAL
FIRE S Occupancies< 50,000sq. ft. Tl
SB1473 -GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION -COMMERCIAL (SMIP)
Total Fees: $2,120.03 Total Payments To Date: $2,120.03
Contractor:
RAYMOND HANDLING SOLUTIONS INC
9939 NORWALK BLVD
SANTA FE SPRINGS, CA 90670-3321
(562) 944-8067
Balance Due:
AMOUNT
$501.80
$197.00
$104.00
$20.00
$821.00
$471.00
$1.00
$4.23
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
(cityof
Carlsbad
Job Address 1979 Palomar Oaks Way
COMMERCIAL
BUILDING PERMIT
APPLICATION
8-2
Plan Check
Est. Value
PC Deposit
Date
Suite: APN: 2130922100 ·-----
Tenant Name#: EMD Electronic Lot#: Year Built: -------------------------------
Year Built: __ _ Occu pancy:_S_-1 __ Construction Type: I11-B Fire sprinklers@ES0NO A/C:0YES0No
BRIEF DESCRIPTION OF WORK: installation of (3) vertical storage modules In existing facility. Sprinkler work (installation of sprinkler
head(s] in each unit) and electrical work to be deferred.
D Addition/New: ____________ New SF and Use, __________ New SF and Use
_______ SF Deck, _______ SF Patio Cover, SF Other (Specify) ____ _
[{]Tenant Improvement: _2_8_2 ____ SF, Existing Use: _s_-1 ______ Proposed Use: _s_-1 _____ _
_____ SF, Existing Use: Proposed Use: ______ _
D Pool/Spa: _____ SF Additional Gas or Electrical Features? ____________ _
D Solar: ___ KW, ___ Modules, Mounted:0Roof 0Ground
D Re roof: _____________________________________ _
D Plumbing/Mechanical/Electrical
D Other:--------------------------------------
APPLICANT (PRIMARY CONTACT) PROPERTY OWNER
Name: Raymond Handling Solutions Inc Name: Versum Materials US, LLC.
Address· 9939 Norwalk Blvd Address: 1 Technology Place
City· Santa Fe Springs State: CA Zip:_9_06_7_o __ City: Rockland State: MA Zip:_0_27_0_3 __ _
Phone· 503.260.4347 Phone: 760-603-2274
Email· edward.schoch@raymondwest.com Email: Joseph-BenjamlnFerrer@versummaterlals.com
DESIGN PROFESSIONAL
Name: Enhao Zhang
Address: 1815 Wright Ave
City· La Verne State:_C_A __ Zip: 91750
Phone: 909.596.1351
Email: bob@scedinc.com
Architect State License: _9_2_77_8_(_P_E_#_) ______ _
CONTRACTOR OF RECORD
Business Name: Raymond Handling Solutions Inc
Address: 9939 Norwalk Blvd
City: Santa Fe Springs State: CA Zip:_9_0_67_o ____ _
Phone: 503.260.4347
Em a i I: edward.schoch@raymondwest.com
CSLB License#: 842707 Class: B --------
Carlsbad Business License# (Required): BLOS1220365
APPLICANT CERT/A CAT/ON: I certify that I have read the application and state that the above information is correct and that the
information on theplansisaccurate. /agree to comply with all City ordinances and State laws relating to building
construction. () I\ !;;'. /).A_ ~ A
NAME (PRINT): {3,f 1"4-\ S fq> (// ( f"'TPh·.442-339-27S119GFaNx·.:7::: 558 DATE: 0 (. 2 3' 2. T
1635 Faraday Ave Carlsbad, CA 92008 --ov--Email: Bullding@carlsbadca.gov
REV. 07/21
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON
SIGNING THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO
PERMIT ISSUANCE.
(OPTION A): LICENSED CONTRACTOR DECLARATION:
lherebyaffirmunderpenaltyofperjurythatlamlicensedunderprovisionsofChapter9(commencingwithSection7000)ofDivision3
of the Business and Professions Code, and my license is in full f orce and effect. I also affirm under penalty of perjury one of the
following declarations {CHOOSE ONE):
D1 have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued. PolicyNo. ______________________________________ _
-OR-
~I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: _z_url_ch_Am_e_rlca_n_ln_su_ra_n_ce_c_o_m.:...pa_n.:...y __________ _
Policy No. WC4637s1011 Expiration Date: -'04-'1-'01_12_0_24 ____________ _
-OR-
O certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
UCTION LENDING AGENCY IF ANY: NA
onstruction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
CONTRACTOR CERT/FICA T/ON: I certify that/ haverearr?f-..,,nn icationandstate that the above information is correct and that
the information on the plans is accurate. I agree to comply with all ces and State laws relating to building
construction.
NAME (PRINT):
Note: If the person signing above is an authorized agent for the contractor provide a letter of aut rization on contractor letterhead.
PTION B): OWNER-BUILDER DECLARATION: NA -OR -
I he affirm that I am exempt from Contractor's License Law for the following reason: n I, as own f the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
~44, Business an fessions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through • own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completio , e owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
-OR-
D1, as owner of the property, am exclusiv contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an o er of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
-OR-□, am exempt under Business and Professions Code Division 3,
A D, D FORM B-61 "Owner Builder Acknowledgement and Verification Form" is required for an
By my signature below I acknowledge that, except for my personal residence in which I must have resi for at least one year prior to completion of the
improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder i as not been constructed in its entirety by licensed
contractors./ understand that a copy of the applicable law, Section 7044 of the Business and Professions Code, is a
submitted or at the following Web site: http: I !www.leginfo.ca.gov! ca law. html.
OWNER CERT/FICA TION: Jcertifythatl have read the application and state that the above information orrectand that the
information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to
construction.
NAME (PRINT): SIGN: __________ DATE: _____ _;:,,,~
Note: If the person signing above is an authorized agent for the property owner include form B-62 signed by property owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
2 REV. 07/21
Building Permit Inspection History Finaled
{city of
Carlsbad
PERMIT INSPECTION HISTORY for (CBC2023-0259)
Permit Type: BLDG-Commercial
Work Class: Tenant Improvement
Application Date: 08/18/2023 Owner: TRUST VERSUM MATERIALS US LLC
Issue Date: 01/23/2024 Subdivision: PARCEL MAP NO 12354
Status: Closed -Finaled Expiration Date: 11/04/2024
IVR Number: 51428
Scheduled Actual Inspection Type Inspection No.
Date Start Date
05/07/2024 05/07/2024 BLDG-14 247492-2024
Tuesday, June 4, 2024
Frame/Steel/Bolting/We
lding (Decks)
Checklist Item
BLDG-Building Deficiency
COMMENTS
BLDG-Final Inspection 247493-2024
Checklist Item COMMENTS
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
Inspection
Status
Passed
Passed
Address: 1979 PALOMAR OAKS WAY
CARLSBAD, CA 92011-1307
Primary Inspector Reinspection
Tim Kersch
Passed
Yes
Tim Kersch
Passed
Yes
Yes
Yes
Yes
Yes
Inspection
Complete
Complete
Page 1 of 1
C City of
Carlsbad
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special Inspection, structural observation and construction material testing.
ProjecUPermit: ---------Project Address: 1979 Palomar Oaks Way
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder
□. (If you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print) h be.r+ t{-·
(First) (M.I.)
Mailing Address· / <J6, 7 P tl-/~1'1.cr O a.~5 (.J~
Email· Cob• clttpk""-<?.e efl"\J..% <bu f , Con Phone:
Cd cr201r
1roo -~os-2201
I am: ~Property Owner □Property Owner's Agent of Record □Architect of Record □Engineer of Record
State of California Registration Numbe • Expiration Date: _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, constructi t ial estin and off-sit abr' ation of building components, as prescribed in the statement of
special inspections noted t 'a roV/ pl nd r ired by the California Building Code.
Signatur • f ) Date: 0 2 A-'4 ;).o 23
B. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder / owner-builder.
contractor's company Name: Raymond Handling Solutions
Name: (Please print) Edward R S c hoc h
(First) (M.I.)
Mailing Address: 31 48 NE 181st Ave, Portland OR 97217
Please check if you are Owner-Builder D
(Last)
Email: e dward.scho ch@ raymondwest.com Phone: 503.260.4347
State of California Contractor's License Number:_8_4_2_7_0_7 ______ Expiration Date: 713112024
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I will provide a final report/ letter in compliance with CBC Section 1704.1.2 prior to requesting final
inspection.
Date: 7/25/2023
B-45 Page 1 of 1 Rev. 03/20
Structural
Engineering
OC") c,')
ON ■A ~ 0 .. .,
N N ft.I N-,,
O')~ c;, o..-
C") ..-..-
N M
N
0
N
(.)
$ Design, Inc.
al
(.)
1815 Wright Ave
La Verne, CA91750
Phone: 909'.596.1351 Fax: 909.596.7186
Prqject Name : E:MD GROUP
Prqject Number : .23-0628-10
Date : 10/26/23
Street,Address: 1969 PALOMAR OAKS WAY
City/State : CARLSBAD, CA 92011
Scope of Work: VLM
10/26/23
..
Structural
Engin~ering & Design
1816 Wright Aye. la Verne CA 91760 Tel: 909 698 1361 Fax· 909,693.8661
By: Bobs Project: EMO Grp Project#: 23-0628-10
Design Data Configuration: SHUTTLE XP XL0-700 140 in H x 123 L x 109.45 D
1) The analyses of the storage equipment conforms to the requirements of the 2022 CBC & ASCE 7-16
2) Anchor bolts shall be provided by Installer per ICC ref.erence on the calculations herein. The Installer must provide
any special Inspection as called out on plans or calculations, or as required by the !CCC report Indicated herein.
3) All welds shall conform to AWS procedures, utilizing E70xx electrodes or similar. All such welds shall be performed
In shop, with no field welding allowed other than those supervised by a licensed deputy Inspector.
4) The slab on grade Is 5" thick with minimum 4000 psi compressive strength. Soll bearing capacity Is 750 psf.
Configuration: SHUTTLE XP XL0-700 140 in H x 123 L x 109.45 D
D
SHUTTLE
XP XLD-700
Typical Carousel System
Page -,z_ of ~
H
Configuration
D= 109.45 In
H= 140.00 In
L= 123.00 In
Dead Load= 6,063 lb
Live Load= 16,005 lb
Anchors= (8) 5/8" diam x 3-1/8" Embed
HIit! TZ2 #4266 per base
I
t
I -
I
I
I
.. ..
Structural
Engineering & Design Inc.
1816 Wright Ave La Verne CA 91760 Tel· 909 696.1361 Fax· 909 693 8661
By: Bobs Project: EMO Grp Project#: 23-0628-10
Seismic Forces Configuration: SHUTTLE XP XLD-700140 in H x 123 L x 109.45 D
Lateral analysis Is performed with regard to 2018 IBC & ASCE 7-16
_Vaq12.■-2= Sos*I*W/R
Veq13.n= 0.4 * ap * S09 * W * {1 + 2*z/h)/(Rp/Ip)
Veq 13.3·3= 0.3* Sos * Ip * W
Sos= Fa * Ss * (2/3)
C 0,73560
Veq12.8-2= 0.2942
Veq 13-.3-1= 0.1177
Veq 13.3-3= 0.2207
Cs=Selsmlc Coeff= 0.2942
V= 0.2942
W-DL= 6,063 lb
W-LL= 16,005 lb
Weff= 22,068 lb
(Either Direction)
V= 0.2942 * (6063 lb + 16005 lb)
= 6,492 lb
H= 140.0 In
Depth= 109.5 In
Eve 0.147 * 22068 lb
= 3,244 lb
Vrr1,n= 0.015
(RMI Sec 2.5.1.2)
Ss= 1.00
S1= 0.37
Fa= 1.10
Fv= 1.93
R= 2.50
Ip= 1.00
PLRF= 1.00
ap= 1.0
Rp= 2.5
z/h= 0.00
0.9-0.2Sds= 0.753
Evc:0,2Sds= 0.147
I
V H
T H/2
Carousel Side Elevat!on
Anchor
Movt= (V * H/2 + Ev*D/2) * Q
= 1,579,919 In-lb Load Case 1: (DL +LL+ E)
= 434,070 In-lb Load case 2: (DL + E)
T= (Movt-Mst)/D
·= 6,126 lb
c: 1,683 lb
Load Case 1: (0.9*DL +LL+ E)
Load Case 1: (0.9*DL +LL+ E)
Check (8) 5/8" diam x 3-1/8" Embed Hilti TZ2 anchor(s) unit.
Special Inspection Is required per ICC #4266.
Mst= [(0.9-0.2Sds) * WDL + (0.9-0.2Sds)*WLL) * D/2
= (6063 lb*0.753 + 16005 lb*0.753) * 109.45 ln/2
= 909,376 In-lb Load case 1: (0.9*DL +LL+ E)
= 249,844 In-lb Load Case 2: (DL + E)
Tmax= 6,126 lb
Qty anchors per side= 4
Tension per anchor= 1,532 lb
Shear/Anchor*2.5= 2,030 lb
per side
per side
Demand load
Demand load
Page"!> of ·S-
www.hlltl.us
Company: Page:
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: Date:
E-Mail:
,:iis.,
Profis Anchor 2.7 .5
1
EMO Grp
23-0628-10
10/24/2023
Specifier's comments: Machine Anchorage-CAP
1 Input data
Anchor type and diameter:
Effective embedment depth:
Material:
Evaluation Service Report:
Issued I Valid:
Proof:
Stand-off lnstallallon:
Anchor plate:
Profile:
Base material:
Installation:
Reinforcement:
Seismic loads (cat. C, D, E, or F)
Geometry [in.] & Loading [lb, In.lb]
Kwlk Bolt TZ -cs 5/8 (3 1/8)
h01,ac( = 3.125 In., hnom = 3.563 In.
Carbon Steel
ESR-1917
5/1/201715/1/2019
Design method ACI 316-14 / Mech.
eb = 0.000 In. (no stand-off); I = 0.375 In.
I, x ly x t = 12.000 In. x 4.750 In. x 0.375 In.; (Recommended plate thickness: not calculated
Round bars (AISC); (L x W x T) = 0,063 In. x 0.063 In. x 0.000 In.
cracked concrete, 4000, f0' = 4000 psi; h "'5.000 In.
hammer drilled hole, Installation condition: Dry
tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Tension load: yes (17.2.3.4.3 (d))
Shear load: yes (17.2.3.5.3 (c))
'
it
'
Q u.s• :. o _ _::..,---; . .
Input dafa and reoub mu,t be checked for agreement with the exlal!ng conditions and for plauslbllllyl
PROF(S Anchor ( c) 2003-2009 HIIU AG, A.-9494 Schaan HIil is a registered Trademark ol Hlttl AG, Schaan
4./
I , ,
i I www.hlltl.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x 1 1507 2030
2 1826 2030
max. concrete compressive strain: 0.11 [%.]
max. conorete compressive stress: 467 [psi)
resulting tension force in (x/y)=(-0.3821-0.178): 3334 [lb]
resulting compression force In (x/y)=(-4. 728/-2.205): 270 (lb)
3 Tension load
0
0
Shear force y 2030
2030
Page:
Project:
Sub-Project I Pos. No.:
Date:
Compression
,:,is.a,
Profis Anchor 2.7.6
2
EMDGrp
23-0628-10
10124/2023
y
0
Tension
Steel Strength•
Pullout Strength•
Load Nu• [lb]
1826
NIA
3334
Capacity ♦ Nn [lb]
12877
NIA
4949
Utilization µ.. = NuJ♦ Nn
15
NIA
68
Status
OK
cor:icrele Breakout Strength••
• anchor having the highest loading .. anchor group (anchors In tension)
3.1 Steel Strength
N,. = ESR value
f N11 2: Nu1
Varlabl~
A.e~ [ln.2]
0.16
Calculations
N .. (lb)
17170
Results
N01 [lb] 17170
refer to ICC-ES ESR-1917
ACI 318-14 Table 17.3.1.1
fu1. [psi)
106000
~ olool 750 f nonduclllo 1.000
4, N,.[lb]
12877
Input data and results mus! be checked tor agreement with the existing conditions and for plauslbllltyl
PROFIS Anchor ( c) 2003-2009 HIit! AG, Fl-9494 SChaan HIIII Is a registered Trademark of HIIIJ AG, Schaan
"f•.1-
Nua [lb)
1826 .
NIA
OK
www.hlltl.us
.Page:
Project: Company:·
Specifier:
Address: Sub-Project I Pos. No.:
Phone I Fax:
E-Mail:
3.2 Concrete Breakout Strength
Ncbg = (~)' ljl oc.N ljl ed,N 'V c,N ljl cp.N Nb
~ Nc1,g ~ Nu,
~. see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
~.o = 9h~,
'V••.N = (1 +i~):S1.0
ljl ed,N : 0.7 + 0.3 ( ~.•5h:) :S 1.0
= MAX(c•,mh, 1.5ho1) :S 1.0 ljl cp.N Cao C.c
N b = kc A.• ../(. h!;6
Variables
h01[1n.) e01:!Jln.J e.2.N [In.]
3.125 0. 2 0.072
C.c [In.) kc A,.
6.500 17 1.000
Calculations
~.11n.2J ~c0 [ln.2] 6ec1g 164.95 87.89 .92
Results
N,[lb)
1o 51 4' concrete 0.650 ~ oelomlc 0.750
Date:
ACI 318-14 Eq. (17.4.2.1b)
ACI 318-14 Table 17.3.1.1
ACI 318-14 Eq. (17.4.2.1c)
ACI 318-14 Eq. (17.4.2.4)
ACI 318-14 Eq. (17.4.2.Sb)
ACI 318-14 Eq. (17.4.2.7b)
ACI 318-14 Eq. (17.4.2.2a)
Ca,mh [In.]
20.000 'I'&) 1. o
(0 [psi]
4000
"·;s 0.
,nonolucllle 1.000
Input data and n1sults must be chocked lor agreement with tile existing condMlons and for plauslblllyl
PROFIS AnchOr ( c) '2003-2009 HIIII AG, FL-9494 Schaen Hill ls a reglalered Trademark or Hlltl AG, Schaen
4~
Nu, [lb]
3334
,:,is.:•·
Profis Anchor 2.7.6
3
EMO Grp
23-0628-10
10/24/2023
5940
,:11s-•
www.hlltl.us Profis Anchor 2.7.5
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
EMD Grp
23-0628-10
10/24/2023 Phone I Fax:
E-Mail:
4 Shear load
steel strength•
Steel failure {with lever arm)•
Pryout Strength ..
Concrete edge failure In direction y+**
Load Vu. [lb]
2030
NIA
4060
4060
Date:
Capacity ♦ Vn [lb]
4940
NIA
15606
9028
• anchor having the highest load Ing 0 anchor {iroup (relevant anchors)
4.1 Steel Strength
v .. ,oq = ESR value
♦ v.lNI.: Vu•a
refer to ICC-ES ESR-1917
ACI 318-14 Table 17.3.1 .1
Variables
A,,v (lh.2)
0.16
Calculations
V0,~b] 7
Results
V01!~b] 7
4.2 Pryout Strength
'••• (psi] 106000
! nonructlle 1.000
Vor,g = k.,p [(~) 'I' oot-1 'I' ed.N If/ o,N 'I' opt-I Nb]
f Vopg .!: Vua
~. see ACI 318-14, Section 17.4.2.1, Fig. R 1-7.4.2.1(b)
~c0 -= 9 h!r
'l'oot-1 = (1 + ~eN) S 1.0
3 her
If/ ed,N = 0. 7 + 0,3 ( ~5h:) s 1.0
'I' opt-I = MAX(~. 1 ·5h•') S 1.0 . C•o Cao
Nb = k., ;\. a ,ff. h!j6
Variables
~ h., [In.]
3.125
'f' c.N 0,0 [In.]
1.000 6.500
Calculations
~.[ln.2] ANc0 [ln.2]
164.95 87,89
Results
V~[lb]
2 95 ♦ conerele 0.700
e.11-1 (in.]
0.000
17
~ oel,mlo 1.000
t V,. [lb] 4940 Vu, [lb] 2030
ACI 318-14 Eq. (17.5.3.1b)
ACI 318-14 Table ff3.1.1
ACI 318-14 Eq. (17.4.2.1c)
ACI 318-14 Eq. (17.4.2.4)
ACI 318-14 Eq. (17.4.2.5b)
ACI 318-14 Eq . .(17.4.2.7b)
ACI 318-14 Eq. (17.4.2.2a)
Cam'-[in.]
~0.000
(0 [psi]
1.000 4000
♦ non<IJolllo 1.000
Input dab! and 1&aulla must be checked for agreomont with tho exloUng condltJona and for plauolbllltyl
PROFIS Anchor ( c ) 2003-2009 HIit! AG, Fl-9494 Schaan Hlltl la a regls!Dl8d Trademark of HOH AG, Schaan
4-1
Utilization llv = V.,.J♦ Vn Status
42 OK
NIA NIA
27 OK
45 OK
5940
Vua [lb]
4060
www.hlltl.us
Company:
Specifier:
Page:
Project: Address:
Phone I Fax:
Sub-Project I Pos. No,:
E-Mail:
4.3 Concrete edge failure In direction y+
V obg "' (~) ljl oc,V ljl od,V ljl o,V ljl h,V If' paralel,V Vb
~ Vc1,g :!: Vu•
Avo seeACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
Avo0 = 4.5 c!1
'l'oo,v =(1 +\e.)s1.o
3.c.1
If/ od,V =: 0.7 + 0.3( 1.~.J S 1.0
= -lff.•1 .!: 1.0 'l'h,V Y '-i,=
vb =(7(t )°\1a-;);i,1 ./(.c!i6
Variables
c.1 (in.J c.2 (In.]
18.667 20.000
10 (In.] "'. 3.125 1.000
Calculations
Ave [ln.2] Avc0 [In. 2) 240.00 1568.00
Results
v..;sBb) 12 7 pccncr.io 0.700
ecv [In.)
0.000
d, [In.]
0.625
5 Combined tension and shear loads
Date:
ACI 318-14 Eq. (17.5.2.1b)
ACI 318-14 Table 17.3.1.1
ACI 318-14 Eq. (17.5.2.1c)
ACI 318-14 Eq, (17,5.2.5)
ACI 318-14 Eq, (17.5.2.6b)
ACI 318-14 Eq. (17.5.2.8)
ACI 318-14 Eq. (17.5.2.2a)
~ ha [In.)
1. 5,000
(C [psi] If:' parollel,V 4000 1,000
, nonducllle
1.000
Utilization 1-'N,v [%)
79
Status
OK
Input data and results mull be chockad for agr11ementwlth the exlsUng condtlons and for plauslbllltyl
PROFIS Anchor ( c) 2003-2009 Hlltl AO, FL-9494 Schaan Hlltl II a reglslored Trademafk 01 Hlltl AG, Schaan
4:.,-
Vu• [lb]
4060
,:i,s.,
Profis Anchor 2.7.5
5
EMDGrp
23-0628-10
10/24/2023
I ,
' ' i
I
www.hlltl.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
6 Warnings
Page:
Project:
Sub-Project I Pos. No.:
Date:
,:,,s.,
Profis Anchor 2.7.5
6
EMDGrp
23-0628-10
10/24/2023
• The anchor design methods In PROFIS Anchor require rtgld anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This
means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered -the anchor plate Is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the design load Ing. PROFIS Anchor calculates the minimum required anchor plate
thickness with FEM to limit the stre88 of the anchor plate based on the assumptions explained above. The proof If the rigid base plate assumption
Is valld Is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for
plauslbilityl
• Condition A applies when supplementary reinforcement Is used. The ¢> factor Is Increased for non-steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
your local standard.
• Refer to the manufacturer's product literature for cleaning and lnstaliallon instructions.
• Cliecking the transfer of loads Into the base material and the shear resistance are required In accordance with ACI 318 or the relevant standard I
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F Is given in ACI 318-14, Chapter 17, Section
17.2.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the
case, the connection design (tension) shall satisfy the provisions of Section 17.2.3.4.3 (b), Section 17.2.3.4.3 (c), or Section 17.2.3.4.3 (d). The_
connection design (shear) shall satisfy the provisions of Section 17.2.3.5.3 (a), Section 17.2.3.5.3 (b), or Section 17.2.3.5.3 (c).
• Section 17.2.3.4.3 (b) / Section 17.2.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile
yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.2.3.4.3 (c) / Section 17.2.3.5.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension 7 shear that can be transmitted to the
anchors by a non-yielding attachment. Section 17 2.3.4.3 (d) / Section 17.2.3.5.3 (c) waive the ductility requirements and require the defi\lgn
strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E Increased
by O)o,
• Hlltl post-installed anchors shall be Installed In accordance with the HIIII Manufacturer's Printed Installation Instructions (MPII). Reference ACI
318-14, Section 17.8.1.
Fastening meets the design criteria!
Input data and resutts must b<I cheeked for agreement with the exlettng conditlone and for plauslbllltil
PROFIS Anchor ( c ) 2003-2009 Hill AO, FL-949◄ SChaan Hlltl Is a reglslered Trademark of HIIU AG, Schaen
41o
Structural
Engineering & Design Inc.
1a16 Wright Ave La Verne CA 91760 Jel· 000 GBG 1361 fax· 909 693 a&a1
By: BobS Project: EMD Grp Project#: 23-0628-10
Slab on Grade Configuration: SHUTTLE XP XLD-700 140 in H x 123 L x 109.45 D
Base Assembly
Base wldth=B= 3.00 In
Base Length=D= 3.00 In
~
fc= 4,000 psi
tslab=t= 5,0 In
phl=!Zl= 0.60
SQll
fsoll= 750 psf
Movt= 1,579,919 in°Ib
Frame depth= 109.45 In
# corumns=N= 8
Load Case 1: Product + Sel5mlc
Product DL= 758 lb
Product LL= 2,001 lb
Puncture I
Pu= 1.2PDL + 1.0PLL + 1,0*E
= 6,519 lb
Apunct= [(B+t)+(D+t)]*2*t
= 160.0 lnA2
Slab Bending I
Asoll= (P*144)/(fsoll)
= 1,252 ln"2
X= (L-y)/2
= 1_1.2In
Fb= S*(phl)*(fc)"0.5
= 189.74 PSI
Load Case 2: Static Loads
Puncture
POL= 758Ib
Pu= 1.2*PDL + l.6*PLL
= 4,110 lb
Apunct= [(B+t)+(D+t)1*2*t
= 160 ln"2
Slab Bending
Asoll= (Pu*144)/(fsoll)
= 789 fnA2
X= (L-y)/2
= 7.Sln
• Fb= S*(phi)*(fc)A0,5
= 189.74 psi
p
_,
SLAB ELEVATION
P-se!smic=E= Movt/Frame depth
= 3,609 lb
(Strength Design Loads)
L= (Asoll)A0,5
= 35.38 In
M= w*x"2/2
= (fsoll*x"2)/(144*2)
= 326 In-lb
Pll= 2,001 lb
L= (Asoll)A0,5
= 28.09 in
M= w*xA2/2
= (fsoll*xA2)/(144*2)
= 148 In-lb
Page 6" of S-
Fpunct= 2.66*phl*sqrt(fc)
= .100.9 psi
fv/Pv= Pu/(Apunct*Fpunct)
= 0.40 < 1.0OK
y= (B*D)"0.5 + t*2
= 13.0 In
5-slab= 1 *t" 2/6
= 4.17 ln"3
fb/Fb= M/(S·slab*Fb)
= 0.41 < 1.0OK
Fpunct= 2.66*phl*sqrt(fc)
= 100.9 psi
fv/Fv= Pu/(Apunct*Fpunct)
0,25 < 1.0OK
y= (S*D)"0.5 + t*2
= 13.0 In
S-slab= 1 *t" 2/6
= 4.17 ln"3
fb/Fb= M/(S-slab*Fb)
= 0.19 < 1.0, OK
Structural
Engineering & Design Inc.
1816 Wright Ave., La Verne, CA 91760 Tel: 909.698.1361 Fax: 909.693.8581
Appendix
~
,,,
I' l I
,I,
ICC-ES Evaluation Report
ESR-4266 m I
.
www.icc-es.org I (800) 423-6587 I (562)' 699-0543
DIVISION: 03 00 00-CONCRETE
Section: 03 16 00-ConcreteAnchors
DIVISION: 05 00 00-METALS
Section: 05 0519-Post-lnstalled Concrete Anchors
REPORT HOLDER:
HILTI, INC.
EVALUATION SUBJECT:
HILTI KWIK BOLT TZ2 CARBON AND STAINLESS
STEEL ANCHORS IN CRACKED AND UNCRACKED
CONCRETE
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2021, 2018 and 2015 International Building Code® (IBC)
■ 2021, 2018 and 2015 International Residential Code®
(IRC)
For evaluation for compliance with the National Building
Code of Canada® (NBCC), see listing report ELC-4266.
For evaluation tor compllance with codes adopted by the
Los Angeles Department of Building and Safety (LADBS),
see ESR-4266 LABC and LARC Supplement.
Property evaluated:
Structural
2.0 USES
The Hlltl Kwik Bolt TZ2 anchor (KB-TZ2) Is used as
anchorage to resist static, wind, and seismic (Seismic
Design Categories A through F) tension and shear loads In
cracked and uncracked normal-weight concrete .and
lightweight concrete having a specified compressive
strength, f c, of 2,500 psi to 8,500 psi
(17.2 MPa to 58.6 MPa).
The ¼-inch-, 3/e-inch-and ½-Inch diameter (6.4 mm,
9.5 mm and 12.7 mm) carbon steel KB-TZ2 anchors may be
Installed in the topside of cracked and uncracked normal-
weight or sand-lightweight concrete over metal deck having
a minimum member thickness, hm1n,dock, as noted In Table 9
of this evaluation report and a .specified compressive
strength, f c, of 3,000 psi to 8,500 psi (20. 7 MPa to
58.6 MPa)
The ¼-inch-, 3/a-inch-, 1/2-inch-, 5/s-inch-and ¾-inch
diameter (6.4 mm, 9.5 mm, 12.7 mm, 15.9 mm and
19.1 mm) carbon steel KB-TZ2 anchors may be installed in
the soffit of cracked and uncracked normal-weight or
sand-lightweight concrete over metal deck having a
Reissued December 2021
Revised May 2023 .
This report is subject to renewal December 2023.
A Subsidiary of the International Code Council®
minimum specified compressive strength, fc, of 3,000 psi
(20.7 MPa).
The anchoring system compl ies with anchors as
described In Section 1901.3 of the 2021, 2018 and 2015
IBC. The anchors may also be used where an engineered
design Is submitted In accordance with Section R301.1.3 of
the IRC.
3.0 DESCRIPTION
3.1 KB-TZ2:
KB-TZ2 anchors are torque-controlled, mechanical
expansion anchors. KB-TZ2 anchors consist of a stud
(anchor body), wedge (expansion elements), nut, and
washer. The anchor (carbon steel version) Is Illustrated In
Figure 1. The stud is manufactured from carbon steel or AISI
Type 304 or Type 316 stainless steel materials. Carbon
steel KB-TZ2 anchors have a minimum 5 µm (0.0002 Inch)
zinc-nickel plating. The expansion elements for the carbon
steel KB-TZ2 anchors are fabricated from carbon steel or
stainless steel. The expansion elements for the stainless
steel KB-TZ2 anchors are fabricated from stainless steel.
The hex nut for carbon steel conforms to ASTM A563-04,
Grade A, and the hex nut for stainless -steel conforms to
ASTM F594.
The anchor body Is comprised of a high-strength rod
threaded at one end and a tapered mandrel at the other end.
The tapered mandrel is enclosed by a three-section
expansion element. The expansion element movement Is
restrained by the mandrel taper and by a collar. The anchor
is installed in a predrilled hole with a hammer. When torque
Is applied to the nut of the Installed anchor, the mandrel is
drawn into the expansion element, which Is In tum expanded
against the wall of the drilled hole.
3.2 Concrete:
Normal-weight and lightweight concrete must conform to
Sections 1903 and 1905 of the I BC.
3.3 Steel Deck Panels:
Steel deck panels must be in accordance with the
configuration in Figure 5A, Figure 58, Figure 5C and Figure
50 and have a minimum base steel thickness of 0.035 inch
(0.899 mm, 20 gauge). Steel must comply with ASTM
A653/A653M SS Grade 33 and have a minfmurn yield
strength of 33,000 psi (228 MPa).
4.0 DESIGN AND INSTALLATION
4.1 Strength Design:
4.1.1 General: Design strength of anchors ·complying with
the 2021 IBC, as well as Section R301.1 .3 of the 2021 IRC
must be determined in accordance with ACI 318-19 Chapter
17 and this report.
ICC-ES Evalllatlon Reports arc no/ to be co1Js/rucd'" rcprc.rc11ring acsthctlc.r or n11_v o//,,r allribmes not spcc(lioolly tl(/drc.rscd, 1101' arc /Irey to be const111ed ••
ttJ "" t11tlorseme11t of the subject of the rtf)Qrl or a ,.,comm,iufa//011 /01· u, us,. Tlttr·• fs no wal'rt1111r by ICC Eva/11111/011 Se11,fct, uc:, express or Implied, as
lo 1111y finding nr n/1,e,· mailer in th/,, repol'I, nl' as to a11y.111·oduct cnvcred hy the l't/>nrl. --
Copyright@ 2023 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 16
ESR-4266 Most Widely Accepted and Trusted
Design strength of anchors complying with the 2018 and
2015 IBC, as well as Section R301.1 .3 of the 2018 and 2015
IRC must be determined In accordance with ACI 318-14
Chapter 17 and this report.
Design parameters provided in Table 4, Table 5, Table 6
and Table 7 of this report are based on the 2021 IBC (ACI
318-19), and 2018 and 2015 IBC (ACI 318-14) unless noted
otherwise in Sections 4.1.1 through 4.1.12. The strength
design of anchors must comply with ACI 318-19 17.5.1.2 or
ACI 318-14 17.3.1, as applicable, except as required in ACI
318-19 17.10 or ACI 318-14 17.2.3, as applicable.
Strength reduction factors, ¢, as given In ACI 318-19
17.5.3 or ACI 318-14 17.3.3, as applicable, and noted in
Table 4, Table 5, Table 6, and Table 7 of this report, must
be used for load combinations calculated in accordance with
Section 1605.1 of the 2021 IBC or Section 1605.2 of the
2018 and 2015 IBC and Section 5.3 of ACI 318 (-19 and
-14), as applicable. The value of f'c used in the calculations
must be limited to a maximum of 8,000 psi (55.2 MPa), in
accordance with ACI 318-19 17.3.1 or ACI 318-14 17.2.7,
as applicable.
4.1.2 Requirements for Static Steel Strength in
Tension: The nominal static steel strength, Nsa, of a single
anchor In tension must be calculated in accordance with ACI
318--19 17.6.1.2 or ACI 318-1417.4.1.2, as applicable. The
resulting N sa values are provided in Table 4 and Table 5 of
this report. Strength reduction factors ¢ corresponding to
ductile steel elements may be used.
4.1.3 Requirements for Static Concrete Breakout
Strength In Tension: The nominal concrete breakout
strength of a single anchor or group of anchors in tension,
Neb or Nct,g, respectively, must be calculated in accordance
wifh ACI 318-1917.6.2 or ACI 318-14 17.4.2, as applicable,
with mod1ficatlons as described in this section. The basic
concrete breakout strength in tension, Nb, must be
calculated in accordance with ACI 318--19 17.6.2.2 or ACI
318-14 17.4.2.2, as applicable, using the values of her and
kc, as given in Table 4 and Table 5. The nominal concrete
breakout strength in tension in regions where analysis
indicates no cracking In accordance with ACI 318-19
17.6.2.5.1 or ACI 318~14 17.4.2.6, as applicable, must be
calculated with kuncr as given in Table 4 and Table 5 and with
'l'c,N= 1.0.
For carbon steel KB-TZ2 anchors installed in the soffit of
sand-lightweight or normal-weight concrete on steel deck
floor and roof assemblies, as shown in Figure 5A, Figure 5B
and Figure SC, calculation of the concrete breakout strength
Is not required.
4.1.4 Requirements for Static Pullout Strength In
Tension: The nominal pullout strength of a single anchor in
accordance with ACI 318--19 17.6.3.1 and 17.6.3.2.1 or ACI
318-14 17.4.3.1 and 17.4.3.2, respectively, as applicable, in
cracked and uncracked concrete, Np,cr and ncr, Np,uncr and
nuncr, respectively, are given In Table 4 and Table 5. For all
design cases !.Jlc,P = 1.0. In accordance with ACI 318--19
17.6.3 or ACI 318-14 17.4.3, as applicable, the nominal
pullout strength in cracked concrete may be calculated in
accordance with the following equation:
( f/ )Iler N11,tt = Np,cr ,,s•oo (lb, psi) (Eq-1)
(
f,I )lier N -N ' ,,,,; -p,cr ru (N, MPa)
In regions where .analysis Indicates no cracking in
accordance with ACI 318--19 17.6.3.3 or ACI 318-14
17.4.3.6, as applicable, the nominal pullout strength In
tension may be calculated in accordance with the following
equation:
(lb, psi)
(N, MPa)
Page 2 of 16
(Eq-2)
Where values for Np,cr or Np,uncr are not provided in Table
4 or Table 5, the pullout strength In tension need not be
evaluated.
The nominal pullout strength in cracked concrete of
the carbon steel KB-TZ2 installed in the soffit of
sand-lightweight or normal-weight concrete on steel deck
floor and roof assemblies, as shown in Figure 5A, Figure 58
and !=igure SC, Is given in Table 8. In accordance with ACI
318-1917.6.3.2.1 or ACI 318--14 17.4.3.2, as applicable, the
nominal pullout strength in cracked concrete must be
calculated in accordance with Eq-1, whereby the value of
Np,deok,cr must be substituted for Np,crand the value of 3,000
psi (20.7 MPa) must be substituted for the value of 2,500 psi
(17.2 MPa) in the denominator. In regions where analysis
indicates no cracking in accordance with ACI 318-19
17.6.3.3 or ACI 318-14 17.4.3.6, as applicable, the nominal
strength in uncracked concrete must be calculated
according to Eq-2, whereby the value of Np.oocJ<.uncr must be
substituted for Np,11ncrand the value of 3,000 psi (20.7 MPa)
must be substituted for the value of 2,500 psi (17.2 MPa) In
the denor:ninator. The-use of stainless steel KB-TZ2 anchors
Installed in the soffit of concrete on steel deck assemblies is
beyond the scope of this report.
4.1.5 Requirements for Static Steel Strength In Shear:
The nominal steel strength in shear, Vsa, of a single anchor
In accordance with ACI 318--19 17.7.1.2 or ACI 318--14
17.5.1.2, as applicable, is given In Table 6 and Table 7 of
this report and must be used In lieu of the values derived by
calculation from ACI 318-1 9 Eq. 17.7.1.2b or ACI 318-14
Eq. 17.5.1.2b, as applicable. The shear strength Vaa,deck of
the carbon-steel KB-TZ2 as governed by steel failure of the
KB-TZ2 installed in the soffit of sand-lightweight or
normal-weight concrete on steel deck floor and roof
assemblies, as shown In Figure SA, Figure 5B and Figure
6C, is given in Table 8.
4.1.6 Requirements for Static Concrete Breakout
Strength in Shear: The nominal concrete breakout strength
of a single anchor or group of anchors in shear, Vcb or Vcbg,
respectively, must be calculated in accordance with ACI
318-19 17.7.2 or AGI 318-14 17.5.2, as applicable, with
modifications as described in this section. The basic
·concrete breakout strength, Vb, must be calculated in
accordance with ACI 318-19 17.7.2.2.1 or ACI 318-14
17.5.2.2, as applicable, based on the values provided In
Table 6 and Table 7. The value of le used In ACI 318-19 Eq.
17.7.2.2.1a or ACI 318-14 Eq. 17.5.2.2a must be taken as
no greater than the lesser of h.r or 8da. Anchors Installed In
light-weight concrete must use the reduction factors
provided in ACI 318-19 17.2.4 or ACI 318--14 17.2.6, as
applicable.
For carbon steel KB-TZ2 anchors Installed in the soffit of
sand-lightweight or normal-weight concrete on steel deck
floor and roof assemblies, as shown in Figure 5A, Figure 5B
and Figure 5C, calculation of the concrete breakout strength
In shear is not required.
4.1 .7 Requirements for Static Concrete Pryout
Strength In Shear: The nominal concrete pryout strength
of a single anchor or group of anchors, Vcp or Vcpg,
respectively, must be calculated in accordance with ACI
318-1917.7.3 or ACI 318-1417.5.3, as applicable, modified
by using the value of kcp provided in Table 6 and Table 7 of
this report and the value of N eb or N cbQ as calculated in
Section 4.1.3 of this report.
I
I-ESR-4266 I Most Widely Accepted end Trusted
For carbon steel KB-TZ2 anchors installed in the sofflt of
sand-lightweight or normal-weight concrete over profile
steel deck floor and roof assemblies, as shown in Figure SA,
Figure 58, and Figure 5C, calculation of the concrete
pry-out strength in accordance with ACI 318-19 17.7.3 or
ACI 318-14 17.5.3 is not required.
4.1.8 Requirements for Seismic Design;
4.1.8.1 General: For load combinations including seismic,
the design must be performed In accordance with ACI
318-19 17.10 or ACI 318-14 17.2.3, as applicable.
Modifications to ACI 318-14 17.2.3 shall be applied under
Section 1905.1.8 of the 2018 and 2015 IBC.
The anchors comply with ACI 318 (.:19 and -14) 2.3, as
ductile steel elements and must be designed in accordance
with ACI 318-19 17.10.5, 17.10.6, 17.10.7 or 17.10.4 or ACI
318-14 17.2.3.4, 17.2.3.5, 17.2.3.6 and 17.2.3.7, as
applicable. Strength reduction factors, ¢, are given in Table
4, Table 5, Table 6, and Table 7 of this report. The anchors
may be installed in structures assigned to Seismic Design
Categories A through F of the IBC.
4.1.8.2 Seismic Tension: The nominal steel strength and
nominal concrete breakout strength for anchors In tension
must be calculated In accordance with ACI 318-19 17.6.1
and 17.6.2 or ACI 318-14 17.4.1 and 17.4.2, as applicable,
as described in Sections 4.1.2 and 4.1.3 of this report. In
accordance with ACI 318-19 17.6.3.2.1 or ACI 318-14
17.4.3.2, as applicable, Iha appropriate. pullout strength In
tens1on for seismic loads, Np,eq, described in Table 4 and
Table 5 or Np,declc.crdescribed in Table 8 must be used in lieu
of Np, as applicable. The value of N p,eq or Np,dectcr may be
adjusted by calculation for concrete strength In accordance
with Eq-1 and Section 4.1.4 whereby the value of Np.ooclc,cr
must be substituted for Np.er and the value of 3,000 psi
(20. 7 MPa) must be substituted for the value of 2,500 psi
(17.2 MPa) in the denominator. If no values for Np,eq or
Np,dock,eq are given in Table 4, Table 5, or Table 8, the static
design strength values govern.
4.1.8.3 Seismic Shear: The nominal concrete breakout
strength and pryout strength In shear must be calculated in
accordance with ACI 318-19 17.7.2 and 17.7.3 or ACI
318-14 17.5.2 and 17.5.3, respectively, as applicable, as
described in Sections 4.1. 6 and 4.1. 7 of this report. In
accordance with ACI 318-19 17.7.1.2 or AC! 318-14
17. 5.1.2, as applicable, the appropriate value for nominal
steel strength for seismic loads, Vsa,oq described in Table 6
and Table 7 or Vsa,<1ec1<.eq described in Table 8 must be used
In lleu of V86, as applicable.
4.1.9 Requirements for Interaction of Tensile and
Shear Forces: For anchors or groups of anchors that are
subject to the effects of combined tension and shear forces,
the design must be performed in accordance with ACI
318-19 17.8 or ACI 318-14 17.6, as applicable.
4.1.10 Requirements for Minimum Member Thickness,
Minimum Anchor Spacing and Minimum Edge Distance:
In lieu of ACI 318-19 17.9.2 or ACI 318-14 17.7.1 and
17. 7.3, respectively, as applicable, "'.Blues of Smtn and Cm1n as
given In Table 3 of this report must be used. In lieu of ACI
318-1917.9.4 or ACI 318-1417.7.5, as applicable, minimum
member thicknesses hmtn as given In Tables 3 and 4 of this
report must be used. Additional combinations for minimum
edge distance, Cm1n. and spacing, s11~11. may be derived by
linear interpolation between the given boundary values as
described in Figure 4.
For carbon steel KB-TZ2 anchors installed in the topside
of sand-lightweight or normal-weight concrete over profile
steel deck floor and roof assemblies, the anchors must be
installed in accordance with Table 9 and Figure 5D.
Page 3 of 16
For carbon steel KB-TZ2 anchors installed ln the soffrt of
sand-llghtwelght or normal-weight concrete over profile
steel deck floor and roof assemblies, the anchors must be
installed in accordance with Figure 5A, Figure 5B and Figure
5C and shall have an axial spacing along the flute equal to
the greater of 3h.ror 1.5 times the flute width.
4.1.11 Requirements for Critical Edge Distance: In
applications where c < Csc and supplemental reinforcement
to control splitting of the concrete is not present, the
concrete breakout strength in tension for uncracked
concrete, calculated in accordance with AC! 318-19 17.6.2
or ACI 318-14 17.4.2, as applicable, must be further
multiplied by the factor '-l'cp,N as given by Eq-3:
(Eq-3)
whereby the factor 4lcp,N need not be taken as less than
1-5h,, . For all other cases, 4'cp,N = 1.0. In lieu of using ACI c,.
318-19 17.9.5 .or ACI 318-14 17.7.6, as applicable, values
of cac must comply with Table 4 or Table 5.
4.1.12 Lightweight Concrete: For the use of anchors In
lightweight concrete, the modification factor Aaequal to 0.8A
Is applied to all values of .J7:. affecting N,, and Vn.
For ACI 318-19 (2021 IBC) or ACI 318-14 (2018 and 2015
IBC), A shall be determined in accordance with the
corresponding version of ACI 318.
For anchors installed in the soffit of sand-lightweight
concrete-filled steel deck and floor and roof assemblies,
further reduction of the pullout values provided in this report
is not required.
4.2 Allowable Stress Design (ASD):
4.2.1 General: Design values for use with allowable stress
design (working stress design) load combinations
calculated in accordance wifh Section 1605.1 of the 2021
IBC or Section 1605.3 of the 2018 and 2015, must be
established as follows:
Tetlowable,ASD = ¢N n
Va!/owab/o,ASD
where:
Tatlowable,ASD
VaHowuble,ASD
¢Nn
a
= Allowable tension load (lbf or kN).
= Allowable shear load (lbf or kN).
= Lowest design strength of an anchor or
anchor group in tension as determined
in accordance with ACI 318 (-19 and -
14) Chapter 17 and 2021, 2018 and
2015 I BC Section 1905. LB, and
Section 4.1 of this report, as applicable
(lbf or N).
= Lowest design strength of an anchor or
anchor group in shear as determined
in accordance with ACI 318 (-19 and
-14) Chapter 17 and 2021, 2018 ·and
2015 IBC Section 1905.1.8, and
Section 4.1 of this report, as applicable
(lbf or N).
= Conversion factor calculated as a
weighted average of the load factors
for fhe controlling load combination. In
addition, ex must include all applicable
factors to account for nonductile failure
modes and required over-strength.
ESR-4266 I Most Widely Accepted and Trusted
The requirements for member thickness, edge distance
and spacing, described in this report, must apply.
4.2.2 Interaction of Tensile and Shear Forces: The
interaction must be calculated and consistent with ACI
318-19 17.8 or ACI 318-14 17.6, as applicable, as follows:
For shear loads Vappllad $ 0.2V.,11owab1a,Aso, the full allowable
load In tension Is permitted.
For tension loads T(lppl/ad $ 0.2Ta11ownblo,ASD, the full allowable
load In shear Is permitted.
For all other cases:
T applied + V a.pplled $ 1 _2 T allowa.bls,ASD V a.llowable,ASD (Eq-4)
4.3 Installation:
Installation parameters are provided In Table 1 and Figure
2, Figure 5A, Figure 58, Figure 5C and Figure 5D. Anchor
locations must comply with this report and plans and
specifications approved by the code official. The Hilti
KB-TZ2 must be installed In accordance with manufacturer's
published Instructions and this report. In case.of conflict, this
report governs. Anchors must be Installed In holes drilled
Into the concrete using carbide-tipped masonry drill bits
complying with ANSI 8212.15-1994, using the Hilti SafeSet
System"' with Hilti TE-YD or TE-CD Hollow Drill Bits
complying with ANSI B212.15-1994 with a Hilti vacuum in
accordance with Figure 6 and Figure 7, or using Hilti SPX-T
core bits in accordance with Figure 7. The Hollow Drill Bits
ate not permitted for use with the 1/4-lnch and 3/s-lnch
diameter KB-TZ2 anchors. The Hlltl SPX-T core bits are not
permitted for use with the 1/4-inch and 1-inch diameter KB-
TZ2 anchors. The minimum drilled hole depth, ho, is given
in Table 1. If dust and debris is removed from the drilled hole
with the Hilti TE-YD or TE-CD Hollow Drill Bits, the DRS
attachment system, or compressed air or a manual pump,
hnom Is achieved at the •speclfi.ed value of ho noted In Table
1. The anchor must be hammered Into the predrllled hole
untn hnom Is achieved. The nut must be tightened agalnst the
washer until the torque values specified in Table 1 are
achieved, or the anchors may be installed using the
appropriate Hilti Impact Wrench and corresponding Hilt! AT
Module In accordance with Figure 7. The Hilti AT Tool
system is not permitted for use· with the ¼-inch and 1-lnch
diameter KB-TZ2 anchors. For Installation In the soffit of
concrete on steel deck assembltes, the hole diameter in the
steel deck must not exceed the diameter of the hole In the
concrete by more than 1/e Inch (3.2 mm). For member
thickness and edge distance restrictions for Installations into
the soffit of concrete on steel deck assemblies, see Figure
SA, Figure SB, and Figure SC.
4.4 Special Inspection:
Periodic special inspection Is required in accordance with
Section 1705.1.1 and Table 1705. 3 of the 2021, 2018 and
2015 IBC, as applicable. The special inspector must make
periodic Inspections during anchor installation to verify
anchor type, anchor dimensions, concrete type, concrete
compressive strength, anchor spacing, edge distances,
concrete member thickness, tightening torque, hole
dimensions, anchor embedment and adherence to the
manufacturer's printed installation instructions. The special
inspector must be present as often as required In
accordance with the "statement of special inspection."
Under the IBC, additional requirements as set forth in
Sections 1705, 1706 and 1707 must be observed, where
applicable.
5.0 CONDITIONS OF USE
The Hiltl KB-TZ2 anchors described in this report comply
with the codes listed In Section 1.0 of this report, subject to
the following conditions:
Page 4 of 16
5.1 Anchor sizes, dimensions, minimum embedment
depths and other Installation parameters as set forth In
this report.
5.2 The anchors must be installed in accordance with the
manufacturer's published Instructions and this report.
In case of conflict, this report governs.
5.3 Anchors must be limited to use In cracked and
uncracked normal-weight concrete and lightweight
concrete having a specified compressive strength, fc,
of 2,500 psi to 8,500 psi (17.2 MPa to 58.6 MPa), and
cracked and uncracked normal-weight or
sand-lightweight concrete over metal deck having a
specified compressive strength, fc, of 3,000 psi to
8,500 psi (20.7 MPa to 58.6 MPa).
5.4 The values of fc used for calculation purposes must not
exceed 8,000 psi (55.1 MPa).
5.5 The concrete shall have attained its minimum design
strength prior to installation of the anchors.
5.6 Strength design values must be established in
accordance with Section 4.1 of this report.
5.7 Allowable design values are established In accordance
with Section 4.2.
5.8 Anchor spacing and edge distance as well as minimum
member thickness must comply with Tables 3 and 9,
and Figure 5A, Figure 5B, Figure 5C and Figure 5D.
5.9 Prior to installation, calculations and details
demonstrating compliance with this report must be
submitted to the code official. The calculations and
details must be prepared by a registered design
professional where required by the statutes of the
jurisdiction In which the project is to be constructed.
5.10 Since an ICC-ES acceptance criteria for evaluating
data to determine the performance of expansion
anchors subjected to fatigue or shock loading is
unavailable at this time, the use of these anchors under
such conditions is beyond the scope of this report.
5.11 Anchors may be installed in regions of concrete where
cracking has occurred or where analysis indicates
cracking may occur (ft > fr), subject to the conditions of
this report.
5.12 Anchors may be used to resist short-term loading due
to wind or seismic forces in locations designated as
Seismic Design Categories A through F of the IBC,
subject to the conditions of this report.
5.13 Where not otherwise prohibited in the code, KB-TZ2
anchors are permitted for use with fire"resistance-rated
construction provided that at least one of the following
conditions is fulf!lled:
• Anchors are used to resist wind or seismic forces
only.
• Anchors that support a fire-resistance-rated
envelope or a fire-resistance-rated membrane
are protected by approved fire-resistance-rated
rriaterlals, or have been evaluated for resistance to
fire exposure in accordance with recognized
standards.
• Anchors are used to support nonstructural
elements ..
5.14 Use of zinc-coated carbon steel anchors is limited to
dry, Interior locations.
5.15 Use of anchors made of stainless steel as specified In
this report are permitted for exterior exposure and
damp environments.
ESR-4266 I Most Widely Accepted and Trusted
5.16 Use of anchors made of stainless steel as specified in
this report are permitted for contact with preservative-
treated and fire-retardant-treated wood.
5.17 Anchors are manufactured by Hlltl AG under an
.approved quality-control program with inspections by
ICC-ES.
5.18 Special Inspection must be provided in accordance
with Section 4.4.
6.0 EVIDENCE SUBMITTED
6.1 Data in accordance with the ICC-ES Acceptance
Criteria for Mechanical Anchors in Concrete Elements
(AC 193), daled October 2017, (editorially revised
December 2020), which incorporates requirements in
ACI 355.2-19 and ACI 355.2-07 for use in cracked and
uncracked concrete.
6.2 Quality-control documentation.
7.0 IDENTIFICATION
7.1 The ICC-ES mark of conformity, electronic labeling, or
the evaluation report number (ICC-ES ESR-4266)
along with the name, registered trademark, or
registered logo of the report holder must be induded in
the product label.
Page 5 of 16
7.2 In addition, the anchors are Identified by packaging
labeled with the manufacturer's name (Hlltl, Inc.) and
contact Information, anchor name, anchor size, and
evaluation report number (ESR-4266). The anchors
have the letters KB-TZ2 embossed on the anchor stud
and a notch or notches embossed Into the anchor
head. The letters and notches are visible after
installation for verification as depicted in Figure 3 of this
report. The number of notches indicate material type.
The letter system Indicating length embossed on the
head of the anchor is described in Table 2.
7.3 The report holder's contact information Is the following:
HILTI, INC.
7250 DALLAS PARKWAY, SUITE 1000
PLANO, TEXAS 75024
(918) 872..S000
www.hiltl.com •
' ' 1 I \
1-• i j
ESR-4266 I Most Widell. Acceeted and Trusted Page 6 of 16
TABLE 1-SETTING INFORMATION
Nominal bit diameter do In. 1/4 3/8 1/2 5/8 3/4
Effective min. In. 1-1/2 1-1/2 2 2-1/2 1-1/21 2 2-1/2 3-1/4 2-3/4 3-1/4 4 3-1/4 3-3/4 4-3/4 4 5-3/4
hot embedment (mm) (38) (38) (51) (64) (38) (51) (64) (83) (70) (83) (102) (83) {95) (121) (102) (146)
Nominal In. 1-3/4 1-7/8 2c1/2 3 21 2-1/2 3 3-3/4 3-1/4 3-3/4 4-1/2 4 4-1/2 5-1/2 4-5/8 6-3/8
mbedrnenl hnom (mm) (44) (48) (64) (76) (51) (64) (76) (95) (83) (95) (1 14) (102) (114) (140) (117) (162)
In. 2 2 2-3/4 3-1/4 2-1/41 2-3/4 3-1/4 ho 4-1/4 3-3/4 4-1/4 4-3/4 4-1/4 4-3/4 5-3/4 5 6-3/4
(mm) (51 ) (51) (70) (83) (57) (70) (83) (108) (95) (108) (121) (108) (121) (146) (127) (171)
ft-lb 4 30 50 40 110 185
orque Thll
Carbon steel1 (Nm} (5) (41) (68) (54) (149) (251)
Installation ft-lb 6 30 40 60 125 185
torque T1m1
Stainless steel1 (Nm) (8) (41) (54) {81) (169) (251)
In. 5/16 7/16 9/16 11/16 13/16 1-1/8 Fixture hole diameter dn (mm) (7.9) (11. 1) (14.3) (17.5) (20.6) (28.6)
1 Daslgn Information for h.r= 1-1/2 Is only applicable lo carbon stool (CS) KB-TZ2 bolts.
dog point
RGURE 1-HILTI CARBON STEEL KWIK BOLT TZ (KB-TZ2) FIGURE 2-HfLTI KB-TZ2 INSTALLED
TABLE2-LENGTH IDENTIFICATION SYSTEM {CARBON STEEL·AND STAINLESS STEEL ANCHORS)
onch
inches) 2 2½ 3 3½ 4 4½ 5 5½ 6 6½ 7 7½ 8 8½ 9 9½ 10 11 12 13 14 15 16
For SI: 1 Inch = 25.4 mm.
1 ¼ diameter anchOrs with length of 3'/i are ldentlfiacl with an ohm (Q) ID marking oo Iha bolt head.
Ltmglh
ldentlllcat!Qn •
Code
Slalnll$ Steel '304 •
~uble·Notch
Ler'lgt~
• 'ldenUflcatlon
Code
Stalnless.Sleel 316
,:rip1e No_\ch
Length
idf;lntlflcatlon
Code
FIGURE 3-BOLT HEAD WITH LENGTH IDENTIFICATION CODE AND KB-TZ2 HEAD NOTCH EMBOSSMENT
ESR-4266 I Most Widely Accepted and Trusted Page 7 of 16
TABLE 3-MINIMUM EDGE DISTANCE, SPACING AND CONCRETE THICKNESS FOR KB-TZ2
Effective min.
embedment hor
Min. member hm1o hlckness
Cm11,
for s;;:
Smin
for c .!:
Cmin
for s;;:
Smin
for c;;:
For SI: 1 Inch= 25.4 mm
I.
In.
(mm)
In.
(mm)
In.
(mm)
In.
(mm)
in.
(mm)
In.
(mm)
In.
(mm)
In.
(mm)
In.
(mm)
1-1/2 1-1/2 2 2-1/2 1-1/2 2 2-1/2 3-1/4 2-3/4 3-1/4 4 3-1/4 3-3/4 4-3/4 4 5-3/4
(38) (38) (51) (64) (38) (51) (64) (83) (70) (83) (102) (83) (95) (121) (102) (146)
3-1/4 3-1/4 4 5 3-1/2 4 5 5-1/2 5 5-1/2 6 6-1/2 6 8 8 10
(83) (83) (102) (127) (89) (102) (127) (140} (127) (140) (152) (140) (162) (203) (203) (254t
1-1/2 5 2-1/2 2-1/2 8 2-3/4 2-314 2-114 4-1/2 3-1/2 2-314 5 4 3-1/2 8 3
(38) (127) (64) (64) (203) (70) (70) (57) (114) (89) (70) (127) (102) (89) (203) (76)
1-1/2 8 6 5 12 6-1/2 9-3/4 5-1/4 6-1/2 5-1/2 7-1/4 10 5-3/4 5-1/2 8 6-3/4
(38) (203) (152) (127) (305) (140) (248) (133) (165) (140) (184) (254) (146) (140) (203} (171)
1-1-12 5 2-1/4 2 12 3-1/2 3 2 4-1/2 2-3/4 2-1/4 4-1/2 3-3/4 3-3/4 8 4-3/4
(38) (127) (57) (51) (305) (89) (76) (51) (114) (70) (57) (114) (95) (95) (203) (121)
1-1/2 8 3-1/2 4 8 10 8 4-3/4 5-1 /2 7 4-1/4 6 7-1/4 4-3/4 8 3-3/4
(38) (203) (89) (102) (203) (254) (203) (121) (140) (178) (108) (152) (184) (121} (203) (95)
1-1/2 8 5
(38) (203) (127)
1-1/2 5 2-1/4
(38) (127) (57)
1-1/2 8 4
C
5
(127)
2-1/4
(57)
2-3/4 2-1/2 2-1/4 4 3-1/4 2-1/4 6 4 3-3/4 3-3/4 3
(70) (64) (57) (102) (83) (67) (127) (102) (95) (95) (76)
5-1/2 4-1/2 6-1/4 7 5-1/2 7 11 7-1/2 5-3/4 10 6-3/4
(140) (114) (133) (178) (140) (178) (279) (191) (146) (254) (171)
2-3/4 2-1/2 2 5-1/2 2-3/4 3 5 4 4 5 4-3/4
(70) (64) (51) (140) (70) (76) (127) (102) (102) (127) (121)
4-1/8 4-1/2 4-1/2 6~1/2 4 4-1/4 8 6 5-1/4 4-1/4 3-3/4
(105) (114) (114) (140) (102) (108) (203) (152) (133) (108) (95)
h ~ h m1n
0)
C: ·~
C. II)
s
Cm/n at S ?_
Smln at C~
C edge distance (c)
FIGURE 4-INTERPOLATION OF MINIMUM EDGE DISTANCE AND ANCHOR SPACING
l !
I -I !
ESR-4266 I Most Widely Accepted and Trusted Page 8 of16
TABLE 4-HILTI CARBON STEEL KB-TZ2 DESIGN INFORMATION FOR HAMMER AND CORE DRILLED INSTALLATIONS, TENSION7
cp,._N 0.75 0.75 0.75 0.75
lbAn' 100,900 100,900 96,300 ,,
(N/mm') (696) (664) (696)
87,000
,(600)
lbAn' 122,400 126,200 114,000
'"'· (N/mm') (844) (870) (786)
106,700
(736)
In' 0.024 0.051 0.099 0.164 A...H (mm') (15.4) (33.2) (63.6) (106.0)
Steel strength In lb 2,920 6,490 11,240 N,. enslon (kN) (13.0) (28.9) (50.0}
17,535
(78,0)
chor category 3
trength reduction
actor for concrete <l>4N, 0.45 0.65 o.es 0.65 nd pullout fallurll </>p,H
n lenslon:i.
lfectlveness factor
r uncracked k,.,,, 24 24 27 24 24
oncrate
ffectlveness factor
rcraoked I<« 17 21 17 24 21 17 21
011crete
odlflcatlon factor
or anchor
eslstance, tension, '1',N 1.0 1.0 1.0 1.0
noracked
oncrete•
In. 4 5 4-3/8 5-1/2 8 5-1/2 6-3/4 10 10 11-1/2
c .. (mm) (102) (127) (111 (140) (203) (140) (171) (254) (264) (292)
lb 2,100 4,180 5,380
N p..111w,r N/A NIA N/A NIP., NIA NIA NIA
(kN) (9.3) (18.6) (23.9)
lb 625
Ni,.ar NIA NIA N/A NIA NIA NIA NIA NIA NIA
(kN) (2.8)
lb 625
Np,"'I NIA NIA NIA NIA NIA NIA NIA NIA NIA
(kN) (2.8)
n.,,,,,, 0.20 0.22 0.24 0.35 0.50 0.42 0.29 0.35 0.50 0.48
n., 0.39 0.50 0.46 0.28 0.47 0.50 0.48 0.40 0.60 0.47
113,515 167,365
For SI: 1 Inch = 25.4 mm, 1 lbf = 4.45 N, 1 psl = 0,006895 MPa. For pound-Inch units: 1 mm = 0.03937 inches.
' Figure 2 of this report llustrates the Installation parameters.
0,75 0.75
84,700 75,000
(584) (517)
105,900 88,000
(730) (607)
0,239 0.470
(154.4) (303.2)
25,335 41,365
(112.7) {164.1)
0.65 0.65
27 271 24 27 24
17 21 21
1.0 1.0
8-3/4 12 10 9 11 16
(222) (305) (254) (229) (279) (406)
8,995 NIA N/A N/A N/A NIA
(40.0)
NIA NIA NIA 8,835
(39.3) NIA 11,810
(52.6)
NIA NIA NIA
8,700 NIA 11,810
(38.7) (52:6)
0.50 0.35 0.31 0.39 NIA 0.38
0.50 0.36 0.42 0.29 NIA 0.50
62,180
2 TI)e KB-TZ2 Is considered a ducme steel element In accordance with ACI 318 (·19 and-14) 2.3.
3 The strength reduction factor applies when Iha load combinations from the IBC or ACI 318 are used and the-requirements of ACI 318-1917.5.3 or ACI 318-14
17.3.3, as applicable, are mel The strength reductJon factors are applicable with supplementary reinforcement is not present Greater strenglh reduction factors
may be used In areas where supplementary reinforcement can be verified.
• For an design cases, 'l'o,11 = 1.0. The appropriate effectiveness factor for cracked concrete (k.r) or uncrocked concrete (k..,.,) must be used.
• For all design cases, Wo,P c 1.0. Tabular value for pullout strength Is for a concrete compressive strength of 2,500 psi (17.2 MPa). PuUout strength for concrete
compressive strength greater than 2,500 psi (17.2 MPa) may be Increased by multiplying the tabular pullout strength by (tc I2,soor for psi, or (fc / 17.2rfor
MPa, where n Is given as noncr for uncracked concrete and n.,. for cracked concrete and seismic. NA (not applicable) denotes that pullout strenglh does not need
to be oonsldered for design.
8 For core drfll lnstallallons, k..,., = 24 for '/•·Inch diameter anchors Installed at 33/• Inches (95 mm) etrectlve embedment
71i◄•lnch and 1-lnch diameter anchors are not permitted for core drHllng Installations.
I-I
ESR-4266 I Most Widely Accepted and Trusted Page 9 of 16
TABLE 5-HILTI STAINLESS STEEL KB-TZ2 DESIGN INFORMATION FOR HAMMER AND CORE DRILLED
INSTALLATIONS,TENSION•
</)••.N 0.75 0.75 0.75 0.75
lblin2 100,90 96,300 96,300 91,600
fy
(Nlmm2) (696) (664) (664) (632)
lbfln2 122,400 120,100 120,400 114,600
fut,
(Nlmm2) (844) (828) (830) (790}
ln2 0.024 0.051 0.099 0.164 A ... H (mm2} (15.4) (33.2) (63.6) (106.0)
lb 2,920 6,180 11,870 18,835 lee! strength In tension N,. (kN) (13.0) (27.5) (52.8) (83.8)
nchor category 3
trength reduction factor
or concrete and pullout
allure In tension,
Condition B-<P~H. </Jp:11 0.45 0.65 0.65 0.65
upplementary
lnforcement not
resent 0
Effectiveness factor for k.,,.., 24 24 24 24 uncracked concrete
Effectiveness factor for k,,, 17 21 17 17 21 17 21 recked concrete
Modification factor for
nchor resistance, C/'r.,N 1.0 1.0 1.0 tension, uncracked onorete◄
in. 4 4-1/2 5-112 4-1/8 5-112 6-174 7-112 10 ritlcel edge distance c.. (mm) (102) (114) (1-10) (105) (140) (159) (191) . (254)
Pullout strength lb 1,570 4,185 3,380 4,010 5,500 4,085
noracked concrete5 N,,,.,.,, NIA NIA (kN) (7.0) (18.6) (15.0) (17.8) (24.5) (18.2)
Pullout strength cracked lb 670 N,,,,, NIA NIA NIA .NIA NIA NIA' NIA oncrete• (kN) (3.0)
Pullout strength lb 670
eismlc6 N, . .,, NIA NIA NIA .NIA NIA NIA1 NIA (kN) (3.0)
ormall2atlon factor, n"""' 0.39 NIA NIA 0.37 0.46 0.50 0.50 0.50 uncracked concrett,
0.50 NIA NIA NIA NIA NIA 0.50 NIA
For SI: 1 Inch = 25.4 mm, 1 lbf = 4.46 N, 1 psi = 0.006895 MPe For pound-inch unlls: 1 mm = 0.03937 Inches.
1 Figure 2 of this report Ulustrates the ·1nstall11tlon parameters.
1.0
6-112
(165)
6,015
(26.8)
NIA
NIA
0.42
NIA
0.75
84,100
·(500)
100,500
(693)
0.239
(154.4)
24,045
(107.0)
0.65
24 21• 24
17 21 21• 21
1.0
8-314 12 10 10
(222) (305) (254) (254)
8,060 NIA NIA NIA (35.8)
NIA NIA NIA 8,795
(39.1)
NIA NIA
8,795
NIA (39.1)
0.47 NIA NIA 0.30
NIA NIA NIA
75,715
0.75
65,000
(448)
99,900
(689)
0.470
(303.2)
46,955
(208.9)
0.65
27
24 21
1..0
11 15-1/2
(279) (394)
NIA NIA
NIA NIA
NIA NIA
NIA NIA
2 TI1e KB-TZ2 ls considered a ducUle steal element In accordance with ACI 318 (-19 end -14) 2.3.
3 The strengU1 reduction factor applies when the-load comblnaUons from U1e IBC or ACI 318 are used and the requirements of ACI 318-1917.5.3 or ACI 318-14
17.3.3, as applicable, are met. The strength reduction factors are applicable with supplementary reinforooment Is not present Greeter strength reduction factors may
be used In areas where supplementary reinforcement can be verified.
4 For ell design cases, 'l'~H = 1.0. The appropriate effectiveness factor for cracked concrete (kor) or uncraoked concrete (ku11a) must be used.
• For ell design cases, C/'o,p" 1.0. Tabular value for pullout strength Is for a concrete compressive strengtll of 2,500· psi (17.2 MPa). Pullout strength for concrete
compressive strength greater than 2,500 psi (17.2 MPa) may be Increased by multlplylng the tebulerpullout strength by (fc 12,500)" for psi, or (fc 117.2)" for MPe,
where n Is given as nu.., for uncracked concrete and ncr for cracked concrete.NA (not applicable) denotes that pullout strength does not need to be considered for
design.
• For core drill Installations, k,-= 24 and /<., = 17 for •I...-lnch diameter anchors lnstaaed et 3¾ lnches.(95 mm) effective embedment.
7 For core drill Installations, N,,., = 4245 lb (18.9 kN) and N,,, .. = 42451b (18.9 kN) for ½-Inch diameter anchors Installed at 3¼ Inches (83 mm) effective embedment. 811◄-lnch and 1-lnch diameter anchors are not permitted for core drilling Installations.
j I •
I
I i i i l '
•
ESR-4266 I Most Widely Accepted and Trusted Page 10 of 16
TABLE 6--HILTI CARBON STEEL KB-122 DESIGN INFORMATION FOR HAMMER AND CORE DRILLED INSTALLATIONS, SHEAR•
1chorO.D.
teal strength In shear,
seismic
Strength reduction factor
ltor concrete breakout and
pryout failure In shear,
(Condition B -
supplementary
!reinforcement not
1Presentl 3
Load bearing length or
ianchor In shear
Coefficient for pryout
~trength
da
h.r
IP..,v
v ..
v .....
il>o.v. <l>p.v
,.
kq,
In.
(mm)
In.
lb
(kN)
lb
(kN)
In.
(mm}
-
0.250
(6.4)
1-112
0.65
1,345
(6.0)
1,345
(6.0)
0.70
1-112
(38)
1
0.375
3,225
(14.4)
3,225
(14.4)
1-1/2
(38)
1
(9.5)
0.66
3,385
(15.1)
3,385
(15.1)
0.70
2 2-112
(51) (64)
1 2
5;535
(24.6)
5,535
(24.6)
1-112 2
(38) (51)
1 1
0.65
0.70
6,875 •
(30.6)
6,875
(30.6)
2-1/2 3-114
(64) (83)
2 2
2-3/4
(70)
2
For SI: 1 Inch = 25.4 mm, 1 lbf =-4.45 N, 1 psi = 0.006896 MPa For pound-Inch units: 1 mm = 0.03937 Inches.
1 Figure 2 of this r&port lllustrat&S th& lnstallaUon param&ters·.
0.625
(15.9)
0.65
10,255
(45:6)
10,255
(45.6)
0.70
3-1/4
(83)
·2
4
(102)
2
3-1/4
(83)
2
0.750
(19.1)
Q.65
13,805
(61.4)
13,805
(61.4)
0.70
3-3/4
(95)
2
4-314
(121)
2
1.00
(25.4)
0.65
18,795 22,826
(83.6) (101.6)
4
13,805
(6H)
0.70
5-3/4
(102) (146)
2 2
'The KB-T22 Is considel'8d a duct/le stool element In accordance with ACI 318 (-19 and -14) 2.3 or ACI 316-11 0.1.
s The strength reduction factor applies when the load combinations from Iha IBC or ACI 318 are used and the requirements of ACI 316-19 17.5.3, ACI 318-14
17.3,3, as applloabfe, are met. The strength reduction factors are applicable with supplementary reinforcement Is not present Greater strength reduction factors
may be used In areas where supplementary reinforcement can be vertfled.
• ¼•Inch and 1-lnch dlam&ter anchors are not permitted for core drilling lnstalletlons.
TABLE 7-HILTI STAINLESS STEEL KB·T22 DESIGN INFORMATION FOR HAMMER AND CORE DRILLED INSTALLATIONS, SHEAR•
11,. 0.250 0.375
nchorO.o. d,
(mm) (6.4)
In.
Effec0ve min. embedn1ent 1 h,,
lb 1,460 4,615 4;885 v .. (kN) (6.5) (20.5) (21.7)
lb 1,110 4,615 4,885 teal strength In shear, selsmlo v ..... (kN) {4.9) (20.5) (21.7)
0.500
8,345
(37.1)
8,345
(37.1)
0.626
(15.9)
12,355
(55.0).
12,355
(55.0)
0.750
(19.1)
16,560
(73.7)
13,470
(59.9)
1.00
(26.4)
5-314
22,955 31,400
(102.1) (139.7)
13,470
(59.9)
~~,-~~f!:.-c ~·•·t~~ .. ,::~ ··•?_f.l~ .... 1, ,i,.-(1:?':•<. ·• ~~1: ~;~,.-• .,,,-~,..,,~-: r •. :-.;tt$W~~it•x-:,,~~"i-Vffe.+, ~.._.,,..:t;,:;l'(.ii~' av;:::-.-It., il-t'-w• .. ~-.-;: .-:.,'~NII.., ~\1+ir-~•t~t~r~r.,•~~-:-,;~~::-; :'/: ')-,.,:;;~.-.i>,,i;.i,,:~ • :~ ._; \ 1..;l;•~ i ., ~ z.-~ -: :• ~a1}¥~Jltti .!'A)}, slt~tti ~',tl{=l.f:lr ~~·t.t~.;$riAttfrtA~ it..l;tJ~:~t--71.l,tti Ji ':{r ::~~ ~r lJ),.} l~1:J,.1} t g~fil~~t~f%;f?; .. ~41.Jt+,:ii~r-~i~J/ttmu.~~J1t~t/~ ~ ~+: ~. ~+,. •• ~·t·!i ,l~
Strength reducUon factor for
boncrete breakout and pryout
failure In shear, (Condition B-<l>~v. lPp.v -0.7 0.7 0.7 0.7
supplementary reinforcement no
present) 3
~oed bearing length of anchor In In. 1-1/2 1-112 2 2-112 2 2-1/2 3-114 2-3/4 3-1/4 ,. shear (mm) (38) (38) (51) {64) (51) (64) (83) (70) (83)
Coefficient for pryout strength I<., -1 1 1 2 1 2 2 2 2
For SI: 1 Inch = 25.4 mm, 1 lbf = 4.45 N, 1 psi = 0.006095 MPa For pound-Inch units: 1 mm "0.03937 Inches.
' Figure 2 of this report Illustrates the Installation parameters.
0.7 0.7
4 3-1/4 3-3/4 4-3/4 4 5-3/4
(1.02) (83) (95) (121) (102) (146)
2 2 2 2 2 2
2 The KB-T22 ls considered a ductile steel element In accordance with ACI 318 (-19 end-14) 2,3 or ACI 318-11 D.1.
• The strength reduction factor applies when the load combinations from the IBC or ACI 318 are used and U1e requirements of ACI 318-19 17.5.3, ACI 318-14
17.3.3, as eppllcable, are meL The strength reduction factors are applicable with supplementary reinforcement Is not present Greater strength reduction factors
may be used In area& where llupplementary reinforcement can be verified.
• 11.•lnch and 1-lnch diameter anchors are not perml(ted for core drilling Installations.
ESR-4266 I Most Widely Accepted and Trusted Page 11 of 16
TABLE 8-HILTI KB-TZ2 CARBON STEEL ANCHORS TENSION AND SHEAR DESIGN DATA FOR INSTALLATION IN THE SOFFIT OF
3000 PSI, LIGHTWEIGHT CONCRETE-FILLED PROFILE STEEL DECK ASSEMBLIES FOR HAMMER AND CORE DRILLED
INSTALLATIONS t,2.3
ute•
recked concrete ·• NAt»dc.•1nt;1 lb 1,725 1,855 2,625 2,996 1,855 2,750 3,745 4,715 4,415 5,815 3,800 4,795
rout strength,
ked concrete 6·• N,,,-,., lb 515 1,625 2,295 2,405 1,660 2,135 3,275 3,340 3,930 4,395 3,325 3,730
lout strength,
mlc·•.7 Np.11.,Jc..,, lb 515 1,625 2,295 2,405 1,650 2,135 3,275 3,340 3,930 4,395 3,325 3,730
el strength In shear 8 v, .. _ lb 1,630 1,355 2,120 2,120 1,790 2,260 3,555 4,345 3,815 6,150 4,085 7,865
racked concrete u
Np ___ lb 1,725 1,855 2,625 2,995 1,855 2,750 3,745 4,716 4,415 5,815 3,800 4,795
out strength,
ked concrete s.e Np._., lb 515 1,625 '2,295 2,405 1,650 2,135 3,275 3,340 3,930 4;395 3,325 3,730
out strength,
mlc M N"'"""'-"" lb 515 1,625 2,295 2,405 1,650 2,135 3,275 3,340 3,930 4,395 3,326 3,730
I strength In shear• v ... -lb 1,630 1,355 2,120 2,120 1,790 2,260 3,285 4;235 3,815 4,650 4,085 7,885
eked concrete •·• N p.dt#d(.IIIHX lb 1,380 990 2,485 NIA 1,815 1,900 NIA 2,665 2,960 N/A NIA NIA
out strength, Np,IJocA.c, lb 410 670 2,130 N/A 1,480 1,480 NIA 1,890 2,835 NIA NIA NIA ked concrete .,.
out strength,
mic 0•7 N;,,dod<. .. lb 410 870 2,130 NIA 1,480 1,480 NIA 1,890 2,635 NIA NIA NIA
teal strength In shear• v.-lb 1,125 2,370 2,505 NIA 2,680 3,175 NIA 3,465 4,085 NIA NIA NIA
!eel strength in shear, lo( lb 1,125 2,370 2,505 NIA 2,680 3,175 elsmtc 7 ... -... NIA 3,465 4,085 NIA NIA NIA
Installations must oomply with Section 4.1.9 and Section 4.3 end Figure 5A, Figure 5B and Figure 5C o( this report. 2 The values for ¢,,,H In tension can be round In Table 4 of this report. The values for ;..,v In shear can be round In Table 6 of this report. ~ Evaluatioll of concrete breakout capacity In aocordance with ACI 318-19 17.6.2, 17.7.2 and 17.7.3 or ACI 318-14 17.4.2, 17.5.2 end 17.5.3, as applicable, le not
required for anchors Installed In the deck eofflt.
• Minimum concrete thickness refers to concrete thickness above upper flute. See Figures 5A to 5C. 5 Charecterlstlo pullout resistance Jor concrete compressive strengths greater than 3,000 psi (20.7 MPe) may be Increased by multiplying the value in the table by
(( 'c / 3000)" for psi or (( 'c / 20.7)" for MPa. See,Table 4 for normallzatlon (actor. 6 The values listed must be used In aocordance with Section 4.1.4 of this report.
7 The values listed must be used In accordance with Sections 4.1.4 and 4.1.8 of this report. 6 The values listed must be used In acoordarlce with Section 4.1.5 of this report.
• For core drlll lnstallatlons, wlU1 3/;-lnch-0lemeter anchors Installed at 3¾ Inches (95 mm) effective embedrnenl, apply a reduction (actor of 0.89 to the design tension strength o( anchors Installed In uncracked concrete.
' 1'
t
I -1
ESR-4266 I Most Widely Accepted and Trusted Page 12 of 16
h 1111n,deck
Max.3"
Max.3"
TABLE 9--HILTI KB•TZ2 CARBON STEEL ANCHORS SETTING INFORMATION FOR INSTALLATION ON THE TOP OF
CONCRETE-FILLED PROFILE STEEL DECK ASSEMBLIES ACCORDING TO FIGURE 501.2.,
omlnal Embedment Depth hnom
inlmum Hole Depth ho
lnlmum Concrete Thickness•
rttlcal Edge Distance
lnlmum Edge Distance
lnlmum Spacing
Required Installation Torque
2
(51)
2-1/2
64
2-1/2
64)
2-1/2 2-1/2
(64) (64) .
3 16 6
(76) (408) .(204)
In. 3 6 6
mm) (76 (204 (152
ft-lb 4 30
(Nm) (5) 41}
2-3/4
(70
3-1/4
(83)
6
(152)
6
(152)
4
(102)
1 lnstallattons must comply with SecUon 4.1.10 and SecUon 4.3 and Figure 50 of this report.
2 Design capacity shall be based on calculations according to values In Tables 4 and 6 of this report
2
(51)
2-1/2
64
2-1/4 2-3/4
57 70
2~n ~1M S~M
(64) (83) (63)
7-1/2 12 7-1/2
(191) (305) (191)
7-1/2 12 7-1/2
(191) (305) (191)
9 6 9
229) 162) (229
50
68)
8
(204)
6
(152)
3 Applicable for hmkl.<1ec! < hm1n,Tablo a. For hm1t1.a11C1c l!: hrtifl,T-3, use setting lnfonnatlon In Tables 1 and 3 and crlllcal ade distances In Table 4
of this report.
• Minimum concrete thickness refers to concrete thickness above Iha upper flute. Sae Figure 5D.
Lower flute installation
Min.
1"
Mio. 12" typ.
Min. 20-gauge steel deck
FIGURE 5A-KB-TZ2 IN THE SOFFIT OF CONCRETE FILLED PROFILE STEEL DECK ASSEMBLIES -W DECK
Lower flute installation
Min.
l"
Min. 12" typ.
Min. 20-gauge steel deck
FIGURE 5B-KB·TZ2 IN THE SOFFIT OF CONCRETE FILLED PROFILE STEEL DECK ASSEMBLIES -W DECK
..
ESR-4266 I Most Widely Accepted and Trusted Page 13 of 16
hm111,dodr
Max. 1-1/2"
hm1n,u•ck
Min. 1-1/2"
Upper flute installation
Lower flute installation
Min. 20-gauge
steel deck
FIGURE 5C-KB-TZ2 IN THE SOFFIT OF CONCRETE FILLED PROFILE STEEL DECK ASSEMBLIES-B DECK
FIGURE 5D-KB-TZ2 IN THE TOP OF CONCRETE FILLED PROFILE STEEL DECK ASSEMBLIES
hmtn,deck
Min.
20-gauge
steel deck J
1 1 ½ Inches (38 mm) 8-deck 11s a minimum pror,e size. Other deck profiles meeting the 8-deck minimum dlmenskins are also permitted.
t -I ' I I
I I i
ESR-4266 I Most Widely Accepted and Trusted
Hilti TE-CD or TE-YD
Hollow Carbide Drill Bit,
with
Hil.ti Vacuum (per
section 4.3)
Hilti SIW-6AT-A22/SIW-
4AT-22/ SIW-6AT-22
Impact Wrench, with
Hilti SI-AT-A22/SI-AT-22
Adaptive Torque Module
Hiltl Rotary Hammer
Drill with DRS (Dust
Removal System)
Module, or
Hilti TE DRS-D Dust
Removal
System with Hilti
Vacuum
FIGURE 6-HILTI SYSTEM COMPONENTS
FIGURE 7---INSTALLATION INSTRUCTIONS
Page 14 of 16
Handheld Hilti DD 30
Core Drill, with
SPX-T Hilti Core Bits (per
Section 4.3)
ICC-ES Evaluation Report ESR-4266 LABC and LARC Supplement
Reissued December 2021
Revised May 2023
This report is subject to renewal December 2023.
www.lcc-es.org I (800) 423-6587 I (562) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 03 00 00-CONCRETE
Section: 03 16 00-Concrete Anchors
DIVISION: 05 00 00-METALS
Section: 05 051"9-Post-lnstalled Concrete Anchors
REPORT HOLDER:
HILTI, INC.
EVALUATION SUBJECT:
HILTI KWIK BOLT TZ2 CARBON AND STAINLESS STEEL ANCHORS IN CRACKED AND UNCRACKED CONCRETE
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement Is to Indicate that the Kwik Bolt TZ2 (KB-TZ2) carbon and stainless steel
anchors In cracked and uncracked concrete, described in ICC-ES evaluation report ESR-4266, have also baen evaluated for
compliance with the codes noted below as adopted by the Los Angeles Department of Building and Safety (LADBS);
Applicable code editions:
■ 2023 City of Los Angeles Bui/ding Code (LABC)
■ 2023 City of Los Angeles Resident/al Code (LARC)
2.0 CONCLUSIONS
The Kwlk Bolt TZ2 (KB-TZ2) carbon and stainless steel anchors In cracked and uncracked concrete, described In Sections 2.0
through 7.0 of the evaluation report ESR-4266, comply with LABC Chapter 19, and the LARC, and are subject to the conditions
of use described in this supplement.
3.0 CONDITIONS OF USE
The Kwlk Bolt TZ2 (KB-TZ2) carbon and stainless steel anchors in cracked and uncracked concrete described in this evaluation
report supplement must comply with all of the following conditions:
• All applicable sections in the evaluation report ESR-4266.
• The design, Installation, conditions of use and Identification of the Kwlk Bolt TZ2 (KB-TZ2) anchors are In accordance with
the 2021 lnt0mational Building Code~ (IBC) provisions noted in the evaluation report ESR-4266.
• The design, installation and Inspection are In accordance with additional requirements of LABC Chapters 16 and 17, and
City of Los Angeles Information Bulletin P/BC 2020-092, as applicable.
• Under the LARC, an engineered design in accordance with LARC Section R301. 1.3 must be submitted.
• The allowable and strength design values listed in the evaluation report and tables are for the connection of the anchors to
concrete. The connection between the anchors and the connected members shall be checked for capacity (which may
govern).
• For use in wall anchorage assemblies to flexible diaphragm applications, anchors shall be designed per the requirements
of City of Los Angeles Information Bulletin P/BC 2020-071 .
This supplement expires concurrently with the evaluation report, reissued December 2021 and revised May 2023.
ICC-ES l!.va/uat/011 Report, art 110110 bt co,atroetl as 1·ep1vst11tllng aes/lte1/cs or at(Y otl/er allrlbui,s 1101 spt!Ciftcal(v ndtfresstd, nor 11r• they lo be constroell ■ •
ns n,l'c11dorscmcn1 of the subject of 1/,e repo,1 or a ,-ccommc11dalw11 for Its use, There Is 110 warramy by ICC Eva/11alio11 Service, LLC. apr~ss or Implied, as
lo tmy/l11dlng or10ll1er matter /11 this repo,•J, or as lo a11y pro,fuct co1•trtd by //1e report. ~
Copyright @2023 ICC Evaluation Service, LLC. NI rights reserved. Page 15 of 16
..
ICC-ES Evaluation Report
www.lcc-es.org I (800) 423-6587 I (562) 699-0543
DIVISION: 03 00 00-CONCRETE
Section: 03 16 00-Concrete Anchors
DIVISION: 05 00 00---METALS
Section: 05 0519-Post-lnstalled Concrete Anchors
REPORT HOLDER:
HILTI, INC.
EVALUATION SUBJECT:
ESR-4266 FBC Supplement
Reissued December 2021
Revised December 17, 2021
This report is subject to renewal December 2023.
A Subsidiary of the International Code Council®
HILTI KWIK BOLT TZ2 CARBON AND STAINLESS STEEL ANCHORS IN CRACKED AND UNCRACKED CONCRETE
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that the Kwlk Bolt TZ2 (KB-TZ2) carbon and stainless steel
anchors In cracked and uncracked concrete, described in ICC-ES evaluation report ESR-4266, have also been evaluated for
compliance with the codes noted below.
Appllcable code editions:
■ 2020 Florida Bui/ding Code-Building
■ 2020 Florida Building Code-Residential
2.0 CONCLUSIONS
T he Kwlk Bolt TZ2 (KB-TZ2) carbon and stainless steel anchors in cracked and uncracked concrete, described in Sections 2.0
through 7.0 of the evaluation report ESR-4266, comply with the Florida Building Code-Building and the -Florida Building
Code-Residential, provided the design requirements are determined in accordance with the Florida Building Code-Building
or the Florida Building Code-Residential, as applicable. The Installation requirements noted In the ICC-ES evaluation report
ESR-4266 for the 2018 International Bulfdlng Code® meet the requirements of the Florida Bulfdlng Code-Bui/ding or the
Florida Building Code-Resident/a/, as appllcable.
Use of the Kwlk Bolt TZ2 (KB-TZ2) carbon and stainless steel anchors In cracked and uncracked concrete have also been
found to be In compliance with the High-Velocity Hurricane Zone provisions of the Florida Building Code-Building and the
Florida Building Code-Residential, with the following conditions:
a) For anchorage to wood members, the connection subject to uplift, must be designed for no less than 700 pounds
(3114N).
b) For connection to aluminum members, all expansion anchors must be installed no less than 3 Inches from the edge of
concrete slab and/or footings. All expansion anchors shall develop an ultimate withdrawal resisting force equal to
four times the imposed load, with no stress increase for duration of load.
For products falling under Florida Rule 61G20-3, verification that the report holder's quality assurance program is audited
by a quality assurance entity approved by the Florida Buildlng Commission for the type of Inspections being conducted Is
the responsibility of an approved validation entity (or the code official, when the report holder does not possess an
approval by the Commission).
This supplement expires concurrently with the evaluation report, reissued December 2021 and revised May 2023.
ICC-ES Ew,/uallnn Re(1()1'1.t arc nnl In-he cnn,trutd a., l'e/Ji'e.,anllng ae.t1heI/c., nr any ntht1· allrihute., nnl .,pec!fica/ly IIdd1·e.,.,ed, 11nr al'e lhey /h he cnn.t1rued I .. .t..
as <lit cndot\lf!l11enl oftlw subject of/he report or a reco111111andat/011/01· /ts usl!. There i.! 11n worra,uy by ICC Evnlua1io11 Service, LLC. express or implied. as ~
lo a11,v J/11dl11g or of/i,r matter /11 this repo1·4 or as w atl)' produc/ covered by 1h11 report. ~
Copyright C 2023 ICC Evaluation Service, LLC. NI rights reserved. Page 16 of 16