MMK Management Group, LLC July 19, 2024
c/o John Allen NOVA Project No. 1024024
PO Box 1555
La Jolla, CA 92038
Subject: Responses to Plan Review Comments - First Review
Romeria Pointe Apartments
One Legoland Drive, Carlsbad, California
References: GeoSoils, Inc., 2022, Geotechnical Update Evaluation and Response to Third-Party
Geotechnical Review Comments, Romeria Pointe Apartments, 7527 Romeria Street,
Carlsbad, San Diego County, California 92009, Assessor’s Parcel Numbers (APNs)
216-300-12-00 and -13-00, City of Carlsbad Grading Permit No: GR2021-, 28, W.O.
7297-A5-SC, May 18.
NOVA Services, Inc. (NOVA), 2024, Assumption of Geotechnical Consultant of
Record, Romeria Pointe Apartments, Romeria and Gibraltar, Carlsbad, California,
NOVA Project No. 1024024, Revised June 24.
True North Compliance Services (TNCS), 2024, Geopiers Only, 7527 Romeria
Street, Carlsbad CA, City Permit No. GR2021-0039, TNCS No. 24-018-600, July 16.
Western Ground Improvement, Inc. (WGI), 2024, Design Submittal for a Geopier®
Foundation System – Delta 1, Romeria Pointe Apartments, Carlsbad, California, GFC
Project No.: GDC-835, July 18.
Dear Mr. Allen:
NOVA Services, Inc. (NOVA) prepared this letter to respond to the referenced third-party review
comments from True North Compliance Services (TNCS, 2024) for the Romeria Pointe Apartments
project in Carlsbad California. NOVA is retained by MMK Management Group, LLC as the
geotechnical consultant of record for the project. The review comments and our responses are
provided below.
Comment S1: Nova Soils Report dated March 7, 2024, states “The geopier can safely support
foundation bearing a 4,000 psf to 5,000 psf, as appropriate.”, but the geopier design notes only
allowable bearing of 4,000 psf. Soils engineer and geopier engineer to coordinate and justify the
geopier design and assumed capacity for supporting the loads from the proposed structures being
built above the geopier system.
Response: WGI specializes in design and installation of aggregate piers (Geopiers®). The aggregate
pier system has been designed to achieve an allowable bearing capacity of 6,000 psf as indicated on
THESE PLANS/DOCUMENTS HAVE BEENREVIEWED FOR COMPLIANCE WITH THEAPPLICABLE CALIFORNIA BUILDING STANDARDSCODES AS ADOPTED BY THE STATE OFCALIFORNIA AND AMENDED BY THEJURISDICTION. PLAN REVIEW ACCEPTANCE OFDOCUMENTS DOES NOT AUTHORIZECONSTRUCTION TO PROCEED IN VIOLATION OFANY FEDERAL, STATE, NOR LOCAL REGULATION.
BY: _________________ DATE: ________________
True North Compliance Services, Inc.
THIS SET OF THE PLANS AND SPECIFICATIONSMUST BE KEPT ON THE JOB SITE AT ALL TIMESAND IT IS UNLAWFUL TO MAKE ANY CHANGESOR ALTERATIONS WITHOUT PERMISSION FROMTHE CITY. OCCUPANCY OF STRUCTURE(S) ISNOT PERMITTED UNTIL FINAL APPROVAL ISGRANTED BY ALL APPLICABLE DEPARTMENTS.
Scott Weisse 07/23/24
Responses to Plan Review Comments - First Review
Romeria Pointe Apartments, Carlsbad, California
NOVA Project No. 1024024
July 19, 2024
2
Geopier Design Note #4 in Drawing No. 534-1A. The design indicates that an allowable bearing
capacity of 6,000 psf can be achieved within settlement tolerances of the proposed structures.
Accordingly, an allowable bearing capacity of 6,000 psf is acceptable to NOVA.
Comment S2: Per the most recent soils report letter by NOVA dated June 24, 2024, it recommends
two options for mitigating the effects of expansive soils beneath interior slab-on-grade which are okay,
but please clarify if these recommendations are to be installed at the building foundation systems
where the geopiers are installed. If yes, please update the geopier design accordingly and clearly
define the mitigation option that will be used.
Response: To mitigate expansive soils beneath interior slabs-on-grade, the owner has elected to
utilize cement stabilization as detailed in the geotechnical addendum (NOVA, 2024). The existing soils
within the upper 18 inches of the proposed building pads will be cement stabilized. Subsequently, the
shallow foundations will be excavated through the treated soils to bear on Geopiers®.
Comment S4: Provide the geotechnical engineer’s stamp and signature on the geopier plan and all
sheets geopier details confirming the geopier plans, details and specifications have been reviewed
and that it has been determined that the recommendations the geotechnical report are properly
incorporated into the plans.
Response: NOVA reviewed the referenced Geopier® design submittal, which contains plans, details,
and specifications for the Geopier® foundation system (WGI, 2024). NOVA’s review was limited to the
geotechnical aspects of the design submittal. In NOVA’s opinion, the recommendations contained in
the project geotechnical report have been properly incorporated into the Geopier® design submittal.
NOVA’s review stamp has been added to the submittal.
NOVA appreciates the opportunity to be of service to MMK Management Group, LLC on this project.
If you have any questions regarding this letter, please call us at 858.292.7575 x 417.