VIASAT -(IN RACK SPRINKLERS) Tl RACK AREA FIRE
SPRINKLER PLAN CHK & INSP.
Owner:
AAA FIRE SPRINKLERS WAL TON CWCA NORTHPOINTE 76 LLC
WALTON STREET CAPITAL
20942 JAPATUL RD
ALPINE CA
619-445-9898
about:blank
Fees($)
130
Add'I Fees ($)
0
PO BOX4900
SCOTTSDALE AZ
Total($)
130
Balance($)
0
1/1
Tyco Fire & Building Products
tqca I Fire & Building f Products
Technlc:al Senrlcea: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-8 -5.6 and 8.0 K-factor
Page 2 of3
ASogo1s1
Upright and Pendent Intermediate Level Sprinkle,
Standard Response
General
Description
The Serles TY·B, 5.6 and 8.0 K-lactor
Upright and Pendent lntermedlale
Level Sprinklers described in thls dala
sheet are automatic sprinklers of the
"slandard resp011$e" 5 mm frangible
bulb type. They are 'slancfard spray"
sprinklers intended la< use in fire sprln•
kier systems designed in accordance
with the standard installation rol,es rec-
ognized by the applicable Ualing or
Approval agency (e.g., UL Listing is
based on NFPA requirements). Solh
the Pendent and Upright Sprinklers
produce a hemispherical water dlstr1•
bulion patlern below the de1lec1or.
Intermediate Level Sprinklers are pri-
marily designed lor use In rack storage
sprinkler systems where their ther-
mally sensitive elemenls must be
shielded lrom the water spray ol h,gher
elll\llltion sprtnlders lhal could operale
earlier during a lire. Intermediate Level
Sprinklers are also used in olher appli·
cations such as beneath open gridded
cetwalks,
Corrosion resistant coatings, wh&re
applicable. are utWlzed to extend the
lile of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at•
mospheras. Although corrosion resis•
tanl ccated sprinklefll have passed lhe
IMPORTANT
Always re/er lo Technical Data
ShHI TFP700 for Ille 'INSTALLER
WARNING" /tlat provides cautions
with re,;pect to handling and Ins/al•
lat/on ol sprlr,k/er systems and com•
pof/8111S. Improper handling and In·
sta/lallon can permanently dsmsga
a sprlnkJer system or /Is compo-
nent,; and cause the sprinkler to fall
lo operate In a lire sllua/lon orc8USIJ
it lo operate prematurely.
standard corrosion tests of the appll•
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the eod user be
consulted wllh respect to the sultability
of these coatings lor any given corro-
sive environment. The effects of ambi-
ent lemperature, concentration of
chemlcels, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to wt,ch the spflnklel'S will be
exposed.
WARNINGS
The Serles TY-B Sprlnk/6rs described
herein must i,,, Install~ and main•
ta/ned in compliance with this docu-
ment, as well as with Iha applicJible
standards of the Nations/ Fire Profec..
tfon Assoc/al/on, In addition to the
slandards of any olhltf authorities hav•
Ing /urlsdlctJon. Fllltur. to do .., m•y
Impair tM pi,rformance of,,.. .. t»-
v/cee,
The owner iS rl1SpOIISible tor maintain•
Ing their r,,o protection system and de·
vices In proper oper116ng condlrlon.
The Installing con/faC1or or sprinkler
manufacturer should be contacllld
with ""Y questions.
ModeVSprinlcler
Identification
Numbers
TY3153 •
TY3251 •
TY4153 • TY4251 •
Upright 5.IIK, 1/2'NPT
Pendent SAK, 1/2'NPT
Upright 8.0K, 3/4"NPT
Pendent I.OK, 3/4"NPT
Technical
Data
Approvata
UL and C·UL Usled. FM and NYC Approved,
(Reier to Table A lor complete a ppr
inl0<ma1ion Including corrosion n
tant Slalll$,)
Maximum Working Prenure
175 psi (12, 1 bar)
011<:ha,ge Coelffcienl
K • 5.6 GPM!ptM'l2 (80,6 LPM/ba,
K• 8.0GPM/psi"2 (115,2 LPM/ba
TempeNOIUNI R•tlr\09
Reier to Table A
FlnlshN
Sprinkler: Aeir,r to Table A
http://www.tyco-fire.com/index.php?P=show&E=&B=&id=TFP351 _ 01 _ 2005&BK =tdse... 10/02/2008
11:1:10 JI t'l' IJ ! I ! I ! 9 ! R >--i
i,"1
111 1 ,1 ; ; ; ii ; i ; Ii • I. Jj~: lljf I I 11 11 I I •
i :!! ,,!~I--a I h·1 ) J J J ) ) i ) z i "' !h~r ! 'J1, .... • I I -.JJ l ii: I I ~~ i i i I i i i ~ I D GI 11'n~r"'r1'11ij11ij111ijr,~ -itl( ~ I
1 _ ~-1r11 i"'~•r,.iri i.1,1 _ i! !i1
-><
I ~ ~ I ~-~J r . . : . . • : . nl r . .. •• . --111~~! !!!! ~ "",1 11· p h i i I ! I f t ' ' ' ' ' ' ' ' I f f • I I I I I I I I i~ ;ii u J I I I -u I i I
I arJr; 'i rf 11 tiff nr ;;=i 11 !1 !;!;! ~ r-JH I ~f Ii! I! : 1r: ~ ff'! r I I § ii i i -
i ' ff~ u◄◄, 111 • : • ijl1 ! I I I i i i I ◄ I lH ---j I
if ii! i I Hi ltU I 5 a i J • ~
Hydraulic Design Information Sheet
Name: VIASAT IN-RACK ADDITION
Location: 6197 EL CAMINO REAL, CARLSBAD
Building: EXISTING
Contractor: AAA FIRE SPRINKLERS
Calculated By: E~F=P-------~~-----------
Construction: tg/ Combustible D Non-Combustible
SYSTEM DESIGN
Date: 9-24-08
System No. 1 OF2
Contract No.
Drawing No. 1 OF 1
Ceiling Height 30 Ft.
IXl NFPA 13· LJ Light Hazard Ordinary Hazard Group LJ 1 u2 □ 3 ~ Extra Hazard
0 NFPA231 0 NFPA 231C: Figure: Curve:
D Other (Specify)
□Specific Ruling Made By Date
Area of Sprinkler Operation 2000SQ FT. S~emT:)!Re
Density .32 ~Wet 0 Dry D Deluge D Pre-Action
Area Per Sprinkler 96 S11rinkler or Nozzle
Hose Allowance GPM: Inside 0 Make TYCO Model ELOITYB
Hose Allowance GPM: Outside 500 Size ¾", ½" K-Factor: 11.2/5.6
Rack Sorinkler Allowance SEECALCS Temoerature Rating 286/155
CALCULATION SUMMARY
GPM Required 1564.41 PSI Required 61.65 At Base of Riser --"''--'-'-'-'--"-------'-'-'-'--------" C" Factor Used: Overhead 120 Under und 150
WATER SUPPLY
Water Flow Test Pump Data Tank or Reservoir
Date & Time 9-18-08 Rated Capacity Capacity
Static PSI 110 At PSI Elevation
Residual PSI 104 Elevation
GPMFlowing 1400 Well
Elevation 0 Proof Flow GPM
Location SITE
Source of Information CARLSBAD WATER & AAA FIRE FLOW TEST
COMMODITY STORAGE
Commodity SEE TECHNICAL REPORT Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized %Rack
Rack D SingleRow D Conventional Pallet 0 Automatic Storage D Encapsulated
D DoubleRow D Slave Pallet 0 Solid Shelving D Non-Encapsulated
D Multiple Row D Open
Flue Spacing In Inches Clearance From TQP of Storage to Ceiling
Longitudinal Transverse Ft. In.
Horizontal Barriers Provided
f
I
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING Sigma Dynamlo1 Corporation
7700 Supply / Demand Graph 125
120
115
110
105
100.
96
90
86
80
75
70
65
60
56
50
45
40
3S
30
25
20
15
10
5
•
/
/
/
~•r
A~o/
/
~
ro'f
/
0250 600 750
I.ti,
• ~ ~ ~ 1000
System Demand ..
Sprlnkl•r D•■..,d 84.74 PSI
Additional f'lows
Hos• at Sourc•
Total o ..... d 84. 74 PSI
•
/.
~
/ ,
/
/
/
. . . 1250 .. 1600
I 1S84.41 GPM
0.00 GPM
S00.00 GPM
I 2084.41 8PM
._. ____
1750
Waler Flow (GPU)
Margin f---
p,. ........ 3.18 PSI f'low 300.8S GPM f---
I •' 1S' '3/ ~
... 2000 . . . 2250
Water Supply ..
Static 99.00 PSI
R•sldual 93.60 PSI I 1400.00 8PM
El•vatlon 0.00 PSI
N1.86
2500
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 1
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
FLOW TEST RESULTS
Water Supply
STATIC 99.00 PSI
RESIDUAL 93.60 PSI @ 1400.00 GPM
CITY PRESSURE AVAILABLE AT 2064.4 GPM 87.92 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR PRESSURE ----------------
200 23.96 21.69 5.60 18.30
201 23.21 21.69 5.60 17.18
202 22.64 21. 69 5.60 16.34
203 22.23 21. 69 5.60 15.75
204 21. 95 21.69 5.60 15.36
205 21. 79 21. 69 5.60 15.14
206 21.71 21.69 5.60 15.03
207 21.69 21.69 5.60 15.00
100 50.89 30.72 11.20 20.64
101 50.33 30.72 11.20 20.20
102 50.06 30.72 11.20 19.97
103 49.95 30.72 11. 20 19.89
104 49.92 30.72 11.20 19.86
105 49.96 30.72 11.20 19.90
106 50.19 30.72 11. 20 20.08
107 50.18 30.72 11.20 20.08
108 49.60 30.72 11.20 19.61
109 49.30 30.72 11.20 19.37
110 49.18 30.72 11.20 19.28
111 49.14 30.72 11.20 19.25
112 49.17 30.72 11.20 19.27
113 49.37 30.72 11.20 19.43
114 49.95 30.72 11.20 19.89
115 49.36 30.72 11.20 19.42
116 49.05 30.72 11.20 19.18
117 48.93 30.72 11.20 19.08
118 48.89 30.72 11.20 19.05
119 48.91 30.72 11. 20 19.07
120 49.10 30.72 11.20 19.22
SUBMITTAL SERIAL NO:2932HY7
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR --------
121 49.91 30.72 11.20
122 49.31 30.72 11.20
123 49.00 30.72 11.20
124 48.88 30.72 11.20
125 48.84 30.72 11.20
126 48.86 30.72 11.20
127 49.05 30.72 11.20
TOTAL WATER REQUIRED FOR SYSTEM
OUTSIDE HOSE STREAMS AT 0
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 24 TO 25
PRESSURE --------
19.86
19.38
19.14
19.04
19.01
19.03
19.18
1564.41 GPM
500.00 GPM
2064.41 GPM
84.74 PSI
0.00 PSI
16.75 FPS
09-24-2008 PAGE 2
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 3
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
206 207 2.203 L 7.25 C=120 PT 15.00 (207)
Q 21.69 F=0 F 0.00 PE 0.00
BN T 7.25 0.0041 PF 0.03
205 206DQ 21. 71 2.203 L 7.25 C=120 PT 15.03 (206)
Q 43.40 F=0 F 0.00 PE 0.00
BN T 7.25 0.0147 PF 0.11
204 205DQ 21. 79 2.203 L 7.25 C=120 PT 15.14 (205)
Q 65.19 F=0 F 0.00 PE 0.00
BN T 7.25 0.0312 PF 0.23
203 204DQ 21.95 2.203 L 7.25 C=120 PT 15.37 (204)
Q 87.14 F=0 F 0.00 PE 0.00
BN T 7.25 0.0534 PF 0.39
202 203DQ 22.23 2.203 L 7.25 C=120 PT 15.76 (203)
Q 109.37 F=0 F 0.00 PE 0.00
BN T 7.25 0.0813 PF 0.59
201 202DQ 22.64 2.203 L 7.25 C=120 PT 16.35 (202)
Q 132.00 F=0 F 0.00 PE 0.00
BN T 7.25 0.1151 PF 0.83
200 201DQ 23.21 2.203 L 7.25 C=120 PT 17.18 (201)
Q 155.21 F=0 F 0.00 PE 0.00
BN T 7.25 0.1554 PF 1.13
PT 18.31 (200) ------------------
126 125 2.703 L 8.00 C=120 PT 19.01 (125)
Q 43.99 F=0 F 0.00 PE -0.03
BL T 8.00 0.0056 PF 0.04
127 126DQ 48.86 2.703 L 8.00 C=120 PT 19.02 (126)
Q 92.85 F=0 F 0.00 PE -0.03
BL T 8.00 0.0222 PF 0.18
48 127DQ 49.05 2.703 L 12.00 C=120 PT 19.17 ( 127)
Q 141. 89 F=0/T F 8.00 PE -0.05
BL T 20.00 0.0486 PF 0.97
28 48 2.703 L 2.00 C=120 PT 20.09 ( 48)
Q 141.89 F=T F 8.00 PE 0.87
RN T 10.00 0.0486 PF 0 .49
27 28 4.310 L 10.00 C=120 PT 21.45 ( 28)
Q 141.89 F=0 F 0.00 PE 0.00
CM2 T 10.00 0.0050 PF 0.05
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 4
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
90 27DQ 142.37 4.310 L 7.00 C=120 PT 21.50 27)
Q 284.26 F=0 F 0.00 PE 0.00
CM2 T 7.00 0.0181 PF 0.13
PT 21. 63 90) ------------------
124 125 2.703 L 8.00 C=120 PT 19.01 (125)
Q 4.85 F=0 F 0.00 PE 0.03
BL T 8.00 0.0001 PF 0.00
123 124DQ 48.88 2.703 L 8.00 C=120 PT 19.04 (124)
Q 53.72 F=0 F 0.00 PE 0.03
BL T 8.00 0.0081 PF 0.06
122 123DQ 49.00 2.703 L 8.00 C=120 PT 19.13 (123)
Q 102.72 F=0 F 0.00 PE 0.03
BL T 8.00 0.0267 PF 0.21
121 122DQ 49. 31 2.703 L 8.00 C=120 PT 19.37 (122)
Q 152.03 F=0 F 0.00 PE 0.03
BL T 8.00 0.0552 PF 0.44
38 121DQ 49.91 2.703 L 170.00 C=120 PT 19.84 (121)
Q 201. 94 F=T F 8.00 PE 0.64
BL T 178.00 0.0934 PF 16.63
18 38 2.703 L 2.00 C=120 PT 37.11 ( 38)
Q 201. 94 F=T F 8.00 PE 0.87
RN T 10.00 0.0934 PF 0.93
17 18 6.357 L 10.00 C=120 PT 38.91 18)
Q 201.94 F=0 F 0.00 PE 0.00
CMl T 10.00 0.0015 PF 0.02
PT 38.93 17)
------------------
119 118 2.703 L 8.00 C=120 PT 19.05 ( 118)
Q 44.36 F=0 F 0.00 PE -0.03
BL T 8.00 0.0057 PF 0.05
120 119DQ 48.91 2.703 L 8.00 C=120 PT 19.07 (119)
Q 93.27 F=0 F 0.00 PE -0.03
BL T 8.00 0.0224 PF 0.18
47 120DQ 49.10 2.703 L 12.00 C=120 PT 19.22 (120)
Q 142.37 F=0/T F 8.00 PE -0.05
BL T 20.00 0.0489 PF 0.98
27 47 2.703 L 2.00 C=120 PT 20.15 47)
Q 142.37 F=T F 8.00 PE 0.87
RN T 10.00 0.0489 PF 0.49
PT 21.51 27)
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 5
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
------------------117 118 2.703 L 8.00 C=l20 PT 19.05 (118)
Q 4.52 F=0 F 0.00 PE 0.03
BL T 8.00 0.0001 PF 0.00
116 117DQ 48.93 2.703 L 8.00 C=l20 PT 19.08 (117)
Q 53.45 F=0 F 0.00 PE 0.03
BL T 8.00 0.0080 PF 0.06
115 116DQ 49.05 2.703 L 8.00 C=l20 PT 19.17 (116)
Q 102.50 F=0 F 0.00 PE 0.03
BL T 8.00 0.0266 PF 0.21
114 115DQ 49.36 2.703 L 8.00 C=l20 PT 19.41 (115)
Q 151. 86 F=0 F 0.00 PE 0.03
BL T 8.00 0.0551 PF 0.44
37 114DQ 49.95 2.703 L 170.00 C=l20 PT 19.88 (114)
Q 201.81 F=T F 8.00 PE 0.64
BL T 178.00 0.0933 PF 16.61
17 37 2.703 L 2.00 C=l20 PT 37.13 ( 3 7)
Q 201. 81 F=T F 8.00 PE 0.87
RN T 10.00 0.0933 PF 0.93
16 17DQ 201. 94 6.357 L 10.00 C=l20 PT 38.93 17)
Q 403.75 F=0 F 0.00 PE 0.00
CMl T 10.00 0.0052 PF 0.05
PT 38.98 16)
------------------
112 111 2.703 L 8.00 C=l20 PT 19.25 (111)
Q 46 .42 F=0 F 0.00 PE -0.03
BL T 8.00 0.0062 PF 0.05
113 112DQ 49.17 2.703 L 8.00 C=l20 PT 19.27 (112)
Q 95.59 F=0 F 0.00 PE -0.03
BL T 8.00 0.0234 PF 0.19
46 113DQ 49.37 2.703 L 12.00 C=l20 PT 19.43 (113)
Q 144.95 F=0/T F 8.00 PE -0.05
BL T 20.00 0.0506 PF 1.01
26 46 2.703 L 2.00 C=l20 PT 20.39 46)
Q 144.95 F=T F 8.00 PE 0.87
RN T 10.00 0.0506 PF 0.51
PT 21. 77 26)
------------------
110 111 2.703 L 8.00 C=l20 PT 19.25 ( 111)
Q 2.72 F=0 F 0.00 PE 0.03
BL T 8.00 0.0000 PF 0.00
SUBMITTAL SERIAL N0:2932HY7 09-24-2008 PAGE 6
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length LOBB Summary
From To GPM IN Devices Ft PSI/Ft PSI
109 llODQ 49.18 2.703 L 8.00 C=120 PT 19.28 (110)
Q 51. 90 F=O F 0.00 PE 0.03
BL T 8.00 0.0076 PF 0.06
108 109DQ 49.30 2.703 L 8.00 C=120 PT 19.37 (109)
Q 101.20 F=O F 0.00 PE 0.03
BL T 8.00 0.0260 PF 0.21
107 108DQ 49.60 2.703 L 8.00 C=120 PT 19.61 (108)
Q 150.80 F=O F 0.00 PE 0.03
BL T 8.00 0.0544 PF 0.44
36 107DQ 50.18 2.703 L 170.00 C=120 PT 20.08 (107)
Q 200.98 F=T F 8.00 PE 0.64
BL T 178.00 0.0926 PF 16.48
16 36 2.703 L 2.00 Ccl20 PT 37.20 ( 36)
Q 200.98 F=T F 8.00 PE 0.87
RN T 10.00 0.0926 PF 0.93
15 16DQ 403.75 6.357 L 11. 00 C=120 PT 39.00 16)
Q 604.73 F=O F 0.00 PE 0.00
CMl T 11.00 0.0110 PF 0.12
PT 39.12 15)
------------------
104 103 2.703 L 8.00 C=120 PT 19.89 (103)
Q 3.05 F=O F 0.00 PE -0.03
BL T 8.00 0.0000 PF 0.00
105 104DQ 49.92 2.703 L 8.00 C=120 PT 19.86 (104)
Q 52.96 F=O F 0.00 PE -0.03
BL T 8.00 0.0079 PF 0.06
106 105DQ 49.96 2.703 L 8.00 C=120 PT 19.89 (105)
Q 102.92 F=O F 0.00 PE -0.03
BL T 8.00 0.0268 PF 0.21
45 106DQ 50.19 2.703 L 12.00 C=120 PT 20.07 (106)
Q 153.11 F=O/T F 8.00 PE -0.05
BL T 20.00 0.0560 PF 1.12
25 45 2.703 L 2.00 C=120 PT 21.14 45)
Q 153.11 F=T F 8.00 PE 0.87
RN T 10.00 0.0560 PF 0.56
PT 22.57 25)
------------------
102 103 2.703 L 8.00 C=120 PT 19.89 (103)
Q 46.91 F=O F 0.00 PE 0.03
BL T 8.00 0.0063 PF 0.05
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 7
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
101 102DQ 50.06 2.703 L 8.00 C=120 PT 19.97 (102)
Q 96.96 F=0 F 0.00 PE 0.03
BL T 8.00 0.0240 PF 0.19
100 101DQ 50.33 2.703 L 8.00 C=120 PT 20.19 ( 101)
Q 147.30 F=0 F 0.00 PE 0.03
BL T 8.00 0.0521 PF 0.42
35 l00DQ 50.89 2.703 L 170.00 C=120 PT 20.64 (100)
Q 198.18 F=T F 8.00 PE 0.64
BL T 178.00 0.0902 PF 16.06
15 35 2.703 L 2.00 C=120 PT 37.34 ( 35)
Q 198.18 F=T F 8.00 PE 0.87
RN T 10.00 0.0902 PF 0.90
14 15DQ 604.73 6.357 L 12.00 C=120 PT 39.11 15)
Q 802.91 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0186 PF 0.22
PT 39.33 14)
------------------
26 90 4. 310 L 3.00 C=120 PT 21.63 90)
Q 463.43 F=0 F 0.00 PE 0.00
CM2 T 3.00 0.0448 PF 0.13
25 26DQ 144.95 4. 310 L 11. 00 C=120 PT 21.76 ( 26)
Q 608.38 F=0 F 0.00 PE 0.00
CM2 T 11. 00 0.0740 PF 0.81
24 25DQ 153.11 4.310 L 12.00 C=120 PT 22.57 ( 25)
Q 761.49 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.1122 PF 1. 35
44 24DQ -610.33 2.703 L 2.00 C=120 PT 23.92 ( 24)
Q 151.17 F=T F 8.00 PE -0.87
RN T 10.00 0.0546 PF 0.55
34 44 2.703 L 230.00 C=120 PT 23.60 ( 44)
Q 151.1 7 F=T/T F 16.00 PE 0.87
BL T 246.00 0.0546 PF 13.43
14 34 2.703 L 2.00 C=120 PT 37.90 ( 34)
Q 151.17 F=T F 8.00 PE 0.87
RN T 10.00 0.0546 PF 0.55
13 14DQ 802.91 6.357 L 18.00 C=120 PT 39.32 14)
Q 954.08 F=2E F 19.80 PE 0.00
CMl T 37.80 0.0256 PF 0.97
PT 40.29 13)
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 8
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
------------------
23 24 4.310 L 12.00 C=120 PT 23.92 ( 24)
Q 610.33 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0745 PF 0.89
43 23DQ -458.73 2.703 L 2.00 C=120 PT 24.81 ( 23)
Q 151.59 F=T F 8.00 PE -0.87
RN T 10.00 0.0549 PF 0.55
33 43 2.703 L 230.00 C=120 PT 24.49 ( 43)
Q 151.59 F=T/T F 16.00 PE 0.87
BL T 246.00 0.0549 PF 13.51
13 33 2.703 L 2.00 C=120 PT 38.87 ( 33)
Q 151. 59 F=T F 8.00 PE 0.87
RN T 10.00 0.0549 PF 0.55
12 13DQ 954.08 6.357 L 12.00 C=120 PT 40.29 13)
Q 1105.67 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0337 PF 0.40
PT 40.69 12)
------------------
22 23 4.310 L 12.00 C=120 PT 24.82 23)
Q 458.73 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0439 PF 0.53
42 22DQ -307.83 2.703 L 2.00 C=120 PT 25.35 ( 22)
Q 150.90 F=T F 8.00 PE -0.87
RN T 10.00 0.0545 PF 0.54
32 42 2.703 L 230.00 C=120 PT 25.02 ( 42)
Q 150.90 F=T/T F 16.00 PE 0.87
BL T 246.00 0.0545 PF 13.41
12 32 2.703 L 2.00 C=120 PT 39.30 ( 32)
Q 150.90 F=T F 8.00 PE 0.87
RN T 10.00 0.0545 PF 0.54
11 12DQ 1105.67 6.357 L 12.00 C=120 PT 40.71 12)
Q 1256.57 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0427 PF 0.51
PT 41.22 11)
------------------
21 22 4.310 L 12.00 C=l20 PT 25.35 22)
Q 307.83 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0210 PF 0.25
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 9
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
41 21DQ -155.47 2.703 L 2.00 C=120 PT 25.60 ( 21)
Q 152.36 F=T F 8.00 PE -0.87
RN T 10.00 0.0554 PF 0.55
31 41 2.703 L 230.00 C=120 PT 25.28 ( 41)
Q 152.36 F=T/T F 16.00 PE 0.87
BL T 246.00 0.0554 PF 13.63
11 31 2.703 L 2.00 C=120 PT 39.78 ( 31)
Q 152.36 F=T F 8.00 PE 0.87
RN T 10.00 0.0554 PF 0.55
10 llDQ 1256.57 6.357 L 12.00 C=120 PT 41.20 11)
Q 1408.94 F=0 F 0.00 PE 0.00
CMl T 12.00 0.0528 PF 0.63
PT 41. 83 10)
------------------
20 21 4.310 L 12.00 C=120 PT 25.60 21)
Q 155.47 F=0 F 0.00 PE 0.00
CM2 T 12.00 0.0059 PF 0.07
40 20 2.703 L 2.00 C=120 PT 25.67 ( 20)
Q 155.47 F=T F 8.00 PE -0.87
RN T 10.00 0.0576 PF 0.58
30 40 2.703 L 230.00 C=120 PT 25.38 ( 40)
Q 155.47 F=T/T F 16.00 PE 0.87
BL T 246.00 0.0576 PF 14.17
10 30 2.703 L 2.00 C=120 PT 40.42 30)
Q 155.47 F=T F 8.00 PE 0.87
RN T 10.00 0.0576 PF 0.58
PT 41.87 10)
------------------
92 200 2.203 L 4.00 C=120 PT 18.30 (200)
Q 179.17 F=T F 11.60 PE 0.00
FM T 15.60 0.2026 PF 3.16
91 92 2.703 L 16.00 C=120 PT 21.46 ( 92)
Q 179.17 F=BV F 6.00 PE -6.93
FM T 22.00 0.0748 PF 1. 65
90 91 2.703 L 61. 00 C=120 PT 16.18 91)
Q 179.17 F=T/E F 11. 90 PE 0.00
FM T 72.90 0.0748 PF 5.45
PT 21. 63 90)
------------------
8 10 6.357 L 25.00 C=120 PT 41.85 10)
Q 1564.41 F=E F 9.90 PE 0.00
FM T 34.90 0.0640 PF 2.23
SUBMITTAL SERIAL NO:2932HY7 09-24-2008 PAGE 10
VIASAT IN-RACK CALC .32/2000 WITH 8 IN-RACKS FLOWING
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
3 8 6.357 L 26.00 C=120 PT 44.08 ( 8)
Q 1564.41 F=T,BV,E F 45.80 PE 11.27
FR T 71. 80 0.0640 PF 4.60
2 3 8.249 L 5.00 C=120 PT 59.95 3)
Q 1564.41 F=T F 41.11 PE 0.87
MA T 46.11 0.0180 PF 0.83
1 2 8.280 L 200.00 C=150 PT 61. 65 2)
Q 1564.41 F=T,DDC/2E F 83.39 PE 0.00
UN T 283.39 0.0117 PF 3.32
8" RPDA 11.93
0 1 8.280 L 615.00 C=150 PT 76.89 1)
Q 1564.41 F=T,GV,EE F 56.38 PE 0.00
UN T 671.38 0.0117 PF 7.86
PT 84.75 0)
Sep 23•08 12:38p AAA Fire Sprinklers !6194454052
Sep-22-2008 01: 12 PM C1 tyorcarisoaa r ire rn:::•vt:."u'-"',._.,u. ...,...,"""""""" ..
1'"tow Test Record
Test Hydrant
Location ... 1c\9J u Camion Qe!l\
Hydrant ID No. __ ............. Size Mnin ____ _
. I ·'\ Sta\lc ........ , .... -U.\,.;_
ltesidunl. ........ ..\..Dl::L--
Prcssurc Drop.. Io (PDI J) ..... K fnctor for !'DI 1 __ _
Flow 1-lydrnnl(s)
Hydrant I location. ____ _
Hydrant 2 location __ ...... .
Hydrant 3 location, ____________________ _
Hydrant I Pi101, ___ 1..!.,i, ___ PSI (iPM:. 14£!,9_._
Hydrant 2 l'itot ____ . PSI GPM:. ___ _
~lydmnt 3 Pitot PSI GPM.: ___ _
Total: ___ _
(Ql)
Calculated test and !low datli • OxPD2 k =Q2
PDJ*k
Static: .................... ___ _
Desired Residual ....... __ .. 20 __
Size of Orifice. ___ _
Size of Orifice. ___ _
Sil:e of Orifice. ___ _
l'ressure Drop (PD 2) ... ____ ................................. K fudor .l'D 2:, _____ _
--·· __ x ___ __;dividcd by _____ equ~ls, ____ Gl'M nt 20 psi residual
Ql PD2k PD lk Q2
Comments: ____________________________ _
-------
Te,;t conducted for :
Conducted by: _______________________ _
Date:. _____ _ Time: _____ _
Sep 23 08 12:38p AAA Fire Sprinklers 16194454052
Cansnao ,tiurW~-a/.. W:iter District
Potable Water Discharge
Event Report
Date:
Reason for Discharge Event ~~ ~~
Dewatering Water Mains
Note: Includes flow testing and flushing
.Dewaterlng Reservoins
Unscheduled Water Discharge
Clear flow path of debris, surface
contaminants and/or hazardous
materials. Do not remove native
vegetation.
Erosion control, I.e.
sandbags, silt fencing, hay bales,
gravel bags, decreasing the velocity
of discharge water.
Upon completion of dewatering, ensure
that the flow path is free of all
temporary erosion prevention materials.
Upon completion cf dewatering, ensure
that any sediment or silted areas are
cleared.
Initial
Estimated Discharge Flow:
Start Time
End Time
Pre-Dechlorlnatlon Residual:
/ Post-Dechlorination Residual:
/ (less than 0.1 mg/L) •
pH within limits of 6.0 and 9.0
p.3
Water Sampling Performed by: ____________________ _
Comments: '-"-----------------------------
Submitted by: __________ _
(Name & Date)
Sep ~4 08 03:l0p AAA Fire Sprinklers 16194454052
AAA Fire Sprinklers
Commercial Tenant Improvement Specialists
Fax Cover Sheet
To: Marie Master
Company: City of Carlsbad
Fax Number: 760.602.8561
Phone Number:
,RE, 6197 El Cam;~ Real Flow Te•
From: Katie Watson
Date: Wednesday, September 24, 2008
Pages: 3
Job#:
[Urgent] [For Review) [Please Comment] [Please Reply] [As Requested)
Comments:
Good Afternoon Marie,
Here's the other information you needed for the flow test.
Pitot:70
PSI: 110
GPM: 1400
Please let met know if there's anything else I can provide for you.
Thanks,
Katie
p. 1
C-16# 908752
20942JapatuIRoad
Alpine, CA 91901
Office 619.445.9898
Fax: 619.445.4052