HomeMy WebLinkAbout2668 GATEWAY RD; 170; CBC2022-0187; PermitBuilding Permit Finaled
(city of
Carlsbad
Commercial Permit
Print Date: 08/20/2024 Permit No:
Job Address: 2668 GATEWAY RD, # 170, CARLSBAD, CA 92009-1783 Status:
CBC2022-0187
Closed -Finaled
Permit Type: BLDG-Commercial Work Class: Tenant Improvement
Parcel#: 2132622100 Track#:
Valuation: $309,934.00 Lot#:
Occupancy Group: A2 Project#:
#of Dwelling Units: Plan#:
Bedrooms:
Bathrooms:
Construction Type:V-B
Orig. Plan Check#:
Occupant Load: 159 Plan Check#:
Code Edition: 2019
Sprinkled: Yes
Project Title:
Description: TORSAP THAI: COM-Tl (2,950 SF) EQUIPM ENT RELOCATION
Applicant:
CHAMPION PERMITS
TIM SEAMAN
1127 11TH ST
IMPERIAL BEACH, CA 91932-2901
(619) 993-8846
FEE
BUILDING PLAN CH ECK
Property Owner:
BRESSI RETAIL LLC
130 VANTIS DR, # 200
ALISO VI EJO, CA 92656-2691
(858) 526-6655
BUILDING PLAN REVIEW -MINOR PROJECTS (LD E)
BUILDING PLAN REVIEW -MINOR PROJECTS (PLN)
CERTIFICATE OF OCCUPANCY
COMM/IND Tl -NON-STRUCTURAL
FIRE A-2 & A-3 Occupancies -Tl
SB1473 -GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION -COMMERCIAL (SMIP)
Total Fees: $3,103.98 Total Payments To Date: $3 ,103.98
Appl ied: 06/02/2022
Issued: 09/19/2022
Finaled Close Out: 08/20/2024
Final Inspection: 08/20/2024
INSPECTOR: Sa lcedo, Felix
Kersch, Tim
Contractor:
SUN COAST CONSTRUCTION INC
PO BOX 1537
VISTA, CA 92085-1537
(760) 630-2079
Balance Due:
AMOUNT
$739.70
$194.00
$98.00
$16.00
$1,212.50
$744.00
$13.00
$86.78
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for process ing in accordance with Carlsbad Municipal Code Section
3.32 .030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
V {_ C1fyof
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Suite: rt<
Pf n Chec:kC0t:Z.t-,'L2 -0 • 87
Es . Vatu II !QCC , 'l3':{. or>
PC Deposit Jt 7 ':¥1 • "7 C>
Date G-, .. z. .. u,&.Z...,
APN: _________ _ Job Address / t ,3 9> l:fa::n .~ ;, 1 \
Tenant Name #: -E; 1 • t \ \ 1 tot#: ____ Year Built: ________ _
Vear Built:. __ _ Oecupancy;.s:..A;i;_;;~ Construction Type: . 1·J NO A/C:
8RUiF D£SCRIPTJON OF WORK~
ESQNO i JI •• i
0 Addltion/New: __________ New SF and Use,. ________ -'New SF and Use
______ SF Deck, SF Patio Cover, SF Other (Specify) ___ _
enant Improvement: /' '\-SF, Existing Use: _1_l.,.......,~---Proposed Use: _____ _
____ SF, Existing Use: Proposed Use:------
□ Pool/Spa: ____ SF Additional Gas or Electrical Features? __________ _
D Sofar: ___ KW, ___ Modules, Mounted70Roof QGround
D Reroof: __________ ..,.... ____________________ _
lSJ Ptumbing/Mech;,mical/Electrical -?s E'
[]Other: ____________ • _______________ .__ ____ _
PRtMA!!_V AP~T ; PROPERTY OWNER
Name: ~. . 5:, ~fl-.'<::.l.,;\ftl\ °'-"" Name:
Addre:S~ ·~b &:.hf ·~""'-5~ .. Addres._s_: -----------------
City:(.);\..,..~ ~~State: U~ Zip: C\\C\\,.. :tty: _________ state:. __ .Zip: ___ _
Phone: . (e\ ~-G... "\ 4, -}$ '6'1 \i Phone: _______________ _
Email! '1\ro (Lc),6,.,,..f,.;" /:1...('IM~~-Emall: _______________ _
DESIGN PROFEssroNAL , Ce,, vv... CONTRACTOR OF R coRo \
Name::-. ,. . ,, ... Business N~e: S--"' C..00-1::>y (µ"'~ < V\L-J-,~""""
Address:_ ____ Address:_P_uu_P>_ ... )(...__S_"b_._• _______ _
City: _______ State:. ___ Zip: ____ City: ~" \V\-"'f (.,,.0 State; CJr Zip: "\. Jtq:z !\
Phone:. _______________ Phone: :J (pH -7 \\p .. Q':\,"-\ g
Email: Email: l::>:::~ (! pC-q" J: \ f--C..,, l,, ~
Architect State License: __________ CSLB Ucense #: 7 C,. ~· ':::\ "; 0 Class: 75
Carlsbad Business License# (Reguired): ______ _
APPUCANT CERT/FICA TION: I certify that I hove read the opplicat/Qnondsta that theab'ove l ormotfon Is correct and that the
lnformatlonon the plans lsaccurate. lagreetocomply with alt ity ordin es and State relating to buildin\ )
construction. . I 'A,. _
NAME(PRINT): _ ~\,>l'i\ .. S:ft_~~Ov-S~N: . 'l'V~ __ DATE: ~ \"J Q d' -= 1635 Faraday Ave Carlsbad, CA 92008 Ph; 442•339-2719 Fall: 700 Emall:.~1 .tl!ll ~~==
-· .REV. 07/21
• --
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECI( NUMBER: -------
A BUIU)ING PERMIT CAN l3E l SUED TO EITHER AS A E UCiNSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON
SIGNING THIS FOf.tM IS AN AGiNT FOR EITHER ENTtTV AN AVTHORJZATION FORM OR tmER IS REQUlRED PRIOR TO
PERMIT ISSUANCE.
(OPTION A :U~~NSED CON A OR DECLARATION~
1/ferebyaffirm under penalty of perjury that I am licensed under provisJonsof Chapter9 ( commencingwith Sec tlonlOOO) of Division 3
of the Busln~ss and Professions Code, and my license is in full force and effect. I alsoaffirm underpenaltyof perjury one of the
following declarations (CHOOSE ONE):
Ot have and will maintain a certificate of con.sent to self-Insure for workers' tompensatlon provklt?d by Section 3700 of the Labor code, ror lhe ~rformanC"e of the
workwhkh this permit ls Issued. PollcVNo. __________________________________ _
~: and will maintain worker's compensation, as required by Section 3700 ol the Labor Code, for the r ance of the work ro wh h !]ll.s ~•!J.11111 ISfUed.
~orkers' p(nfc!tlon In uran~ carri polltYl}l,!rnbe,ere: IMuranqitCo,npany Name: ""'-.:'.) U . \ l
Polley No. v~V-, ).. U ~ ~ • '--d Explratlon Date: -~--~""1-l-A-+Y~~---
•OR-
Ocerllflcate of Exemption: I certlfy that In the performance or the work for which this permit is issued, I shall not emplov any person In any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage ls unlawfuJ and shllll subjec{ art employer to
criminal penalties 11.nd dvll fines up to $100,000.00, In addition the to the cost of compensation, dam11ges as provided for In Section 3706 of the labor Code,
interest and attorney's fees.
CONSTRUCTION DING AGENCY, IF ANY:
I hereby affirm rhat there Is a construction lending agency for the performance of the work this permit Is Issued (Sec. 3097 (iJ Civil Code).
lender's Name: _________________ ___;Lendet's Address: _____ _.,,_.. __________ _
OR -
fOPTION B): OWNER~BUI DER DECLARATtO :
f hereby affirm that f am exempt from Contractor's License Law for the followln9 reason: n 1, as owner of the property or my employees w1th wages as their sole compensation. wlll do the work and the structure Is not Intended or offered for sale {Sec.
t..rrJ44, Business and Professions Code; The Contractot's License law does not apPly to an owner of properly who builds or lmpl'oVCs thereon, and who does such
wor!c himself or througjl his own employees, provided that such Improvements are not Intended or offered ror sale, If, however, the building or lmproYement Is sold
within one yea.r of completion, the owner-bullder wlll n1111e the burden or proving that he did not buJld or Improve for the.purpose of saleJ.
-OR-
0 1, as owner of the property, am exclusively contracting with lrcensed contractors to construct the project (sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or Improves thereon, and contracts for suth projects with contractor(s} 11<:ensed
pursuant to the Contractor's License Law).
-OR-01 am exempt under Business and Professions Code DMslon 3, Chapter 9, Article 3 for this re.ison:
AND, D FORM 8-61 "OWner Bulkier Acknowledgement and Verlflcatlon Form" is required for any permit l»ued to a property owner.
By my signature below I <1cknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion or the
lmprovenients to11ered by this permit, I ClJnnot legally sell a structure th.It I halH! built as an owrier,bullder ff ft has not been constructed ln its entirety by licensed
contractou.luflderstond thotoCtJPYof theoppUcoblelow, Section 70440/ the Business and Prof esslOllS Code, Is available upon request when this app/fcatlon 1s
submitted orat the following Web site: http,/Iwww./eglnfo.ca. 'J()VI calaw. html.
OWNER C£RTIFICA TION; lcertifythat I have read the application and state that theaboveinformationiscorrectand that the
lnformatlonon the plansfsaccurote. lagree tocqmply with all Cfty ordinances and State laws relating to builcnr,g
construction.
NAME (PRINT): ________ _ SIGN~ _________ DATE: _____ _
Note: If the parson si,n1,,_ above Is an autho1lied agent for the propeny C!Wnei Include form ,S.62 511ned by propert'y ow11er.
1635 Faraday Ave cartsbad, CA 92008 Ph: 442-339-2719 Fax: 760-602-85S8 Email~ ,il• 1lJtlillll@@dsb@«~,&Q£
2 REV.07/21
Building Permit Inspection History Finaled
( City of
Carlsbad
PERMIT INSPECTION HISTORY for (CBC2022-0187)
Permit Type; BLDG-Commercial
Work Class: Tenant Improvement
Application Date; 06/02/2022 Owner: BRESSI RETAIL LLC
Issue Date: 09/19/2022 Subdivision: CITY OF CARLSBAD TCT NO
14-09 UPTOWN
Status: Closed -Finaled Expiration Date: 05/01/2023
IVR Number: 41024
Address: 2668 GATEWAY RD, # 170
CARLSBAD, CA 92009-1783
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector
Date Start Date Status
10/25/2022 10/25/2022 BLDG-21 194885-2022 Partial Pass Tim Kersch
Underground/Underflo
orPlumblng
Checklist Item
BLDG-Building Deficiency
COMMENTS
11/02/2022 11/02/2022 BLDG-23 195620-2022 Passed Tim Kersch
GasfTest/Repalrs
Checklist Item COMMENTS
BLDG-Building Deficiency Start 24 hour test.
03/07/2023 03/07/2023 BLDG-Final Inspection 204856-2023 Partial Pass Tim Kersch
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
NOTES Created By
Angie Teanio
COMMENTS
TEXT
760-622-3085 Joh nny// Looking for a
pre-final walk thru // Still needs fire final
03/22/2023 03/22/2023 BLDG-Final Inspection 206074-2023 Failed Tim Kersch
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structura l Final
BLDG-Electrical Final
NOTES Created By
Angie Teanio
Angie Teanio
COMMENTS
Fire pending.
TEXT
760-622-3085 Johnny// Looking for a
pre-final walk thru II Still needs fire final
760-716-0442 Marco JI still shows fire hold
03/24/2023 03/24/2023 BLDG-Final Inspection 206168-2023 Partial Pass Tim Kersch
Tuesday,August20,2024
Reinspectlon Inspection
Reinspection Incomplete
Passed
Yes
Complete
Passed
Yes
Reinspection Incomplete
Passed
No
Yes
Yes
Yes
Yes
Created Date
03/06/2023
Reinspectlon Incomplete
Passed
No
Yes
Yes
Yes
Yes
Created Date
03/06/2023
03/21/2023
Reinspection Incomplete
Page 1 of 2
PERMIT INSPECTION HISTORY for (CBC2022-0187)
Application Date: 06/02/2022 Owner: BRESSI RETAIL LLC Permit Type: BLDG-Commercial
Work Class: Tenant Improvement Issue Date: 09/19/2022 Subdivision: CITY OF CARLSBAD TCT NO
Status: Closed -Finaled Expiration Date: 05/01/2023
IVR Number: 41024
14-09 UPTOWN
Address: 2668 GATEWAY RD, # 170
CARLSBAD, CA 92009-1783
Scheduled
Date
Actual Inspection Type
Start Date
Inspection No. Inspection Primary Inspector Relnspection Inspection
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
NOTES Created By
Angie Teanio
Angie Teanio
Angie Teanio
Status
COMMENTS
Fire pending.
TC O dining room only.
TEXT
760-622-3085 Johnny II Looking for a
pre-final walk thru II Still needs fire final
760-716-0442 Marco II still shows fire hold
760-716-0442 Marco II still shows fire hold
04118/2023 04/18/2023 BLDG-Fire Fina! 206314-2023
COMMENTS
Passed Felix Salcedo
Checklist Item
FIRE-Building Final Operationa l permit required. See
operational permit for details on
requirements
08/20/2024 08/20/2024 BLDG-Final Inspection 258544-2024
COMMENTS
Passed Tim Kersch
Tuesday,August20,2024
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
NOTES Created By
Angie Teanio
Angie Teanio
Angie Teanio
Fire pending.
TC O dining room only.
TEXT
760-622-3085 Johnny II Looking for a
pre-final walk thru II Still needs fire final
760-716-0442 Marco II still shows fire hold
760-716-0442 Marco II still shows fire hold
Passed
No
Yes
Yes
Yes
Yes
Created Date
0310612023
0312112023
0312212023
Passed
No
Passed
Yes
Yes
Yes
Yes
Yes
Created Date
03/06/2023
0312112023
0312212023
Complete
Complete
Page 2 of 2
♦ EMSL Analytical, Inc.
8145 Ronson Road, Suite B San Diego, CA 92111
Tel/Fax: (858) 499-1303 / (858) 499-1304
http://www.EMSL.com / sandiegolab@emsl.com
Attention: Marcelo Braga
Air Check Solutions, LLC
2971 Aber Street
San Diego, CA 92117
Project: A22177 / 2668 GATEWAY RD #170, CARLSBAD, CA 92009
EMSL Order: 432203967
Customer ID: ACHK42
Customer PO:
Project 10:
Phone:
Fax:
Received Date:
Analysis Date:
Collected Date:
(858) 926-9906
05/11/2022 11 :20 AM
05/11/2022
05/11/2002
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample
432203967-0001
2
432203967-0002
3
432203967-0003
4
432203967-0004
5
432203967-0005
Analyst(s)
Alina Hernandez (4)
Joseph Gutierrez (1)
Description
RESTROOM
HALLWAY / OW, JC,
COMP
RESTROOM
HALLWAY / JC
WOMEN'S
RESTROOM / JC
"TAKE OUT AREA"/
CERAMIC FT
"TAKE OUT AREA"/
GROUT
Non-Asbestos
Appearance % Fibrous
White <1% Cellulose
Non-Fibrous
Heterogeneous
White
Non-Fibrous
Homo eneous
White
Non-Fibrous
Homo eneous
Black
Non-Fibrous
Homogeneous
Gray
Non-Fibrous
Homogeneous
% Non-Fibrous
100% Non-fibrous (Other)
100% Non-fibrous (Other)
100% Non-fibrous (Other)
100% Non-fibrous (Other)
100% Non-fibrous (Other)
Riva Alger, Laboratory Manager
or Other Approved Signatory
Asbestos
¾Type
None Detected
None Detected
None Detected
None Detected
None Detected
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above. and may not be
reproduced, except in full. without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as
received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria
and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method') but augmented with procedures outlined In the 1993 ("final") version of the method. This report must not be used by the client to claim product certificalion. approval. or endorsement by
NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis .
Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty Is available on request.
Samples analyzed by EMSL Analytical, Inc. San Diego. CA NVLAP Lab Code 200855-0, CA ELAP 2713. HI L-09-03
( Initial report from: 05/1 2/2022 14:17:48
ASB_PLM_0008_0001 • 1.78 Printed: 5/12/2022 11 :17 AM Page 1 of 1
• lW
INTERW EST
DATE: 08/30/2022
JURISDICTION: CARLSBAD
PLAN CHECK#.: CB-CBC2022-0187.RC1
PROJECT ADDRESS: 2668 Gateway Road
PROJECT NAME: Torsap Thai -COM TI
SET: II
□ APPLICANT
□ JURIS.
[8'.I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The check list transmitted herewith is for the applicant's information. The plans are being held at
lnterwest until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to the jurisdiction at:
Jack Shively
~ lnterwest staff did not advise the applicant that the plan check has been completed .
D lnterwest staff did advise the applicant that the plan check has been completed .
Person contacted : Telephone#: 951 -293-4526
Date contacted:
Mail Telephone
0 REMARKS:
By: Carl Blaisdell
lnterwest
(by: ) Email : jshively@sparcdesigngroup.com
Fax In Person
' \ Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
• lW
IN TERWEST
DATE: 06/21/2022
JURISDICTION: CARLSBAD
PLAN CHECK#.: CB-CBC2022-0187
PROJECT ADDRESS: 2668 Gateway Road
PROJECT NAME: Torsap Thai -COM TI
SET: I
D APPLICANT
D JURIS.
D The plans transmitted he rewith have been corrected where necessary and substantially comply
with the jurisdiction's codes .
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
C8J The check list transmitted herewith is for the applicant's information. The plans are being held at
lnterwest until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
C8J The applicant's copy of the check list has been sent to the jurisdiction at:
Jack Shively
D lnterwest staff did not advise the applicant that the plan check has been completed .
C8J lnterwest staff did advise the applicant that the plan check has been completed.
Person contacted : Telephone#: 951-293-4526
Date contacted:
Mail Telephone
0 REMARKS:
By: Steven Miller
lnterwest
(by: ) Email: jshively@sparcdesigngroup.com
Fax In Person
Enclosures:
06/07/2022
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (85 8) 560-1576
CARLSBAD CB-CBC2022-0187
06/21/2022
PLAN REVIEW CORRECTION LIST
COMMERCIAL
PLAN CHECK#.: CB-CBC2022-O187 JURISDICTION : CARLSBAD
OCCUPANCY: A2 USE: Restaurant
TYPE OF CONSTRUCTION: VB ACTUAL AREA: TI 2,950sq ft Patio 913 sq ft
Existin g 3,863sq ft
ALLOWABLE FLOOR AREA: 24,000 STORIES : 1
HEIGHT:
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED:06/21/2022
FOREWORD (PLEASE READ):
OCCUPANT LOAD: 159
DATE PLANS RECEIVED BY
ESGIL CORPORATION : 06/07/2022
PLAN REVIEWER: Steven Miller
This plan review is limited to the technical requirements contained in the California version of
the International Building Code , Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled . This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Eng ineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2019 CBC , which adopts the 2018 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2018 International Building Code , the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
CARLSBAD CB-CBC2022-0187
06/21/2022
PLAN REVIEWER MAY NOT BE AVAILABLE TO ANSWER QUESTIONS BY
PHONE, BUT MAY BE REACHED BY E-MAIL AT stmiller@esgil.com . (858)
225-7665
GENERAL
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing , corrected sets can be submitted
in one of two ways:
a. Deliver all corrected sets of plans and calculations/reports directly to the
City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA
92008, (760) 602-2700. The City will route the plans to lnterwest and the
Carlsbad Planning, Engineering and Fire Departments.
OR;
b. Bring TWO corrected set of plans and calculations/reports to lnterwest,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-
1468. Deliver all remaining sets of plans and calculations/reports directly to
the City of Carlsbad Building Department for routing to their Planning,
Engineering and Fire Departments.
NOTE: Plans that are submitted directly to lnterwest only will not be
reviewed by the City Planning, Engineering and Fire Departments until
review by lnterwest is complete.
2. Plans may be submitted in electronic format, subject to the jurisdiction's
approval. If so, they must have restrictions removed from the security settings.
Electronic plans with restrictions to markups, printing, or stamping will not be
approved.
Electronic plans must be submitted back to the jurisdiction's building department
and will then be routed to lnterwest. ONLY submit FULL complete and combined
sets of plans, uploading multiple single sheets will not be allowed . Make sure all
plans and calc packages, spec. reports, etc. are labeled clearly and can be read
what they are and WHAT SUBMITTAL they go with. DO NOT SEND documents
directly to lnterwest as they will not be accepted.
3. Provide item-by-item responses on an 8-1/2-inch by 11-inch sheet(s) clearly and
specifically indicating where and how each correction item has been addressed
(vague responses, such as "Done" or "See plans," are unacceptable).
4.
PLANS
Page G0-00 Provide the names, addresses and telephone numbers of the
owner and the responsible design professionals on the Title Sheet. MEP
Designers Sec. 107.2.
CARLSBAD CB-CBC2022-0187
06/21/2022
5. Page G0-00 Sheet Index Pages A3-10, and FS1 -0 -FS7-0 are missing from the
plans and page P9-1 O is misnumbered as P9-00. Please clarify the index.
6. Page G0-00 The City requires that all projects that are required to comply with
the Cities Climate Action Plan to Imprint Form B-55 onto the plans title page and
match the projects information shown on form B-50. Form B-55 is located at the
end of form B-50.
7. All sheets of the plans and the first sheet of the calculations are required to be
signed by the licensed architect or engineer responsible for the plan preparation.
California Business and Professions Code.
8. Page T1 .0 please provide a signed copy of the Title 24 ADA Compliance sheet to
the Title page. Please see a copy of the ADA Compliance Form at the end of the
list. If the Tenant Improvement is not currently 100% compliant, please
provide a list of the ADA improvements to be made, the 3 year adjusted
construction costs. And identify the fee for each ADA element to be upgraded, up
to the max of 20% of the adjust construction costs. See section 118202.4
exception 8.
9. Page G0-00 Provide a note on the plans indicating if any hazardous materials will
be stored and/or used within the building which exceed the quantities listed in
IBC Tables 307 .1(1) and 307.1(2).
10. Page A2-10 Specify on the plans the uses of all rooms or areas. Sec. 107.2.
11. Page G0-00 On the cover sheet of the plans , specify any items that will have a
deferred submittal (trusses, fire sprinklers/alarms, etc.). Additionally, provide
the following note on the plans, per Sec. 107.3.4.1: "Submittal documents for
deferred submittal items shall be submitted to the registered design professional
in responsible charge, who shall review them and forward them to the building
official with a notation indicating that the deferred submittal documents have
been reviewed and that they have been found to be in general conformance with
the design of the building. The deferred submittal items shall NOT be installed
until their design and submittal documents have been approved by the building
official."
EXITS
12 . Page G2-10 Please provide the exiting information that is missing from the
plans. Room occupancy tab, exit count tag, and the exit door tag. The plans
shall designate the number of occupants to be accommodated on every
floor, and in all rooms and spaces . Section 107.2.3.
13. Page G2-10 Please provide the exiting information that is missing from the
plans. Room occupancy tab, exit count tag, and the exit door tag. Please
provide an exit analysis plan (may be 8½" x 11" or any convenient size). Show in
CARLSBAD CB-CBC2022-0187
06/21/2022
this analysis the occupant load of each area, the general exit flow patterns (using
arrows), accumulated occupant loads and required exit widths. Section 107.2.3.
14. Page G2-10 Note on the plans: "All egress doors shall be readily openable from
the egress side without the use of a key or special knowledge or effort." Section
1010.1.9. In lieu of the above, in a Group B, F, M or S occupancies (or places of
religious assembly or Group A occupancies having an occupant load of 300 or
less), you may note on the plans "Provide a sign on or near the exit door, reading
THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED."
This sign age is only allowed at the main exit. Section 1010.1.9.4.
15. Page G2-10 Regardless of occupant load, a floor or landing not more than½
inch below the threshold is required on each side of an egress door. Section
1010.1 .7.
EXIT SIGNS/ILLUMINATION
16. Page E2-00 please show the exit signs above the patio doors. Exit signs are
required whenever two exits are required. Show all required exit sign locations.
Section 1013.1.
17. Page A2-10 Please keynote the tactile sign. A tactile sign stating "EXIT" and
complying with ICC A 117 .1 shall be provided adjacent to each door to an exit
stairway, an exit passageway, and the exit discharge. Section 1013.4.
18. Page E2-00 Show that the means of egress path will be lighted with at least one-
foot candle at floor level. Section 1008.
19. Page E2-00 Show separate sources of power may be required for exit
illumination. Review Section 1008.3.
FIRE EXTINGUISHING
20. Page A2-10 Show the location of the extinguisher or specify on the plans that
portable fire extinguishers will be installed in the building in accordance with
Section 906 .
MISCELLANEOUS LIFE/SAFETY
21 . Page A3-10 If Suspended ceilings are shown. Please provide notes on the
plans to show the suspended ceilings in Seismic Design Categories D, E & F
comply with ASCE 7-16 Section 13.5.6.2.2 as follows :
a. The width of the perimeter supporting closure angle or channel shall be
not less than 2.0 in. unless qualified perimeter supporting clips are used.
b. Closure angles or channels shall be screwed or otherwise positively
attached to wall studs or other supporting structures. Perimeter supporting clips
shall be qualified in accordance with approved test criteria per Section 13.2.5.
CARLSBAD CB-CBC2022-0187
06/21/2022
c. Perimeter supporting clips shall be attached to supporting closure angle or
channel with a minimum of two screws per clip and shall be installed around the
entire ceiling perimeter.
d. In each orthogonal horizontal direction, one end of the ceiling grid shall be
attached to the closure angle, channel, or perimeter supporting clip. The other
end of the ceiling gird in each horizontal direction shall have a minimum 0.75-in
clearance from the wall and shall rest upon and be free to slide on a closure
angle, channel, or perimeter supporting clip.
e. Ceiling areas over 2500 ft.2 must have seismic separation joints or full
height partitions.
f. Ceilings without rigid bracing must have 2" oversize trim rings for
sprinklers and other ceiling penetrations.
INTERIOR WALL AND CEILING FINISHES
22. Page A10-10 Please identify or note where to find the proposed finishes.
Also please provide finishes for Floor, Base Board, Wall, Ceiling Finishes.
Provide a note on the plans or on the finish schedule, stating, "Wall and ceiling
materials shall not exceed the flame spread classifications in IBC Table 803.13."
ACCESSIBILITY
SITE PLAN REQUIREMENTS
23. Page A 1-10 Show that an accessible route of travel is to be provided to all portions
of the building, to accessible building entrances and between the building and
the public way, from the sidewalk, as well as the ADA parking spaces. Show the
access or path of travel to the tenant space. Note or show the different elements
such as , the detectable warning strips, pedestrian ramps, curb ramps , stairways
and handrails etc. per Section 11 B-206.2.1 .
24. Page A1 -10 Show the locations of the detectable warnings, with details and
references on the plans, as per Sections 11B-247 & 11 B-705.
ACCESSIBLE PARKING
25. Page A 1-10 Show on the site plan the required number of accessible parking
spaces for new facilities . Per Table 11 B-208.2, the minimum number of spaces is:
a) 1 for each 25 spaces up to 100 total spaces.
b) 1 additional space for each 50 spaces for between 101 and 200 total
spaces.
26. Page A 1-10 Show that accessible parking spaces comply with Section 11 B-502.2
as follows:
a) Single spaces shall be 14' wide and outlined to provide a 9' parking area
and a 5' loading and unloading area. This loading/unloading area may be
on either side of the vehicle.
CARLSBAD CB-CBC2022-0187
06/21/2022
b) When more than one space is provided, in lieu of providing a 14' space for
each space, two spaces can be provided within a 23' area with a 5' loading
zone between each 9'0" wide space.
c) Each space is to be a minimum of 18' in depth.
27. Page A1-10 The words "NO PARKING" shall be painted on the ground within each
loading and unloading access aisle (in white letters no less than 12" high and
located so that it is visible to traffic enforcement officials). Section 11 B-502.3.3.
28. Page A1 -10 Show or note that the maximum slope of the parking surface at the
accessible space and adjacent access aisle, in any direction, is::; 1 :48, per Section
11 B-502.4.
29. Page A1-10 Show or note on the plans that the accessible parking spaces are to
be identified by a reflectorized sign, permanently posted immediately adjacent to
and visible from each space, consisting of:
a) A profile view of a wheelchair with occupant in white on dark blue
background.
b) The sign shall ;?:70 in .2 in area.
c) Additional language or sign below the symbol of accessibility stating ,
"Minimum Fine $250".
d) When in the path of travel, they shall be posted ;?:80" from the bottom of the
sign to parking space finished grade.
e) Signs may also be centered on the wall of the interior end of the parking
space.
f) Van-accessible spaces shall have an additional sign "Van-Accessible"
mounted below the symbol of accessibility.
g) In addition, the surface of each accessible space is required to be marked
with the international symbol of accessibility.
30. Page A 1-10 Please show the location of the existing sign on the site plan. Also be
sure to use the CA version and not the ICC A 117 version which is missing the
word "special". See 11 B502.8.2 Show, or note, that an additional sign shall also
be posted in a conspicuous place at each entrance to off street parking facilities, or
immediately adjacent to and visible from each stall or space. Section 11 B-502.8.2.
The sign shall be ~17" x 22" with lettering not $1" in height. The required wording
is as follows.
"Unauthorized vehicles parked in designated accessible spaces not displaying
distinguishing placards or special license plates issued for persons with
disabilities may be towed away at owner's expense. Towed vehicles may be
reclaimed at ______ or by telephoning ______ "
Blank spaces shall be filled shall be filled in with appropriate information as a
permanent part of the sign .
CARLSBAD CB-CBC2022-0187
06/21/2022
DOORS
Provide Door Schedule, and Details on page G3-11
31 . Revise plans , or door schedules, to show that every required passage door has
232" clear width, per Section 11 B-404.2.3.
32 . Show, or note, that there is a level floor or landing on each side of all doors. The
floor or landing is to be =s½" lower than the doorway threshold, per Section 11 B-
404.2.5.
33. Show or note that all hand-activated door opening hardware meets the following
requirements, per Section 11 B-404.2.7:
a) Latching, or locking, doors in a path of travel are operated with a single
effort by lever type hardware, by panic bars, push-pull activating bars, or
other hardware designed to provide passage without requiring the ability to
grasp the opening hardware.
b) Is to be centered 234" but =544" above floor.
34. Show or note that the maximum effort to operate doors shall not exceed 5 pounds,
with such pull or push effort being applied at right angles to hinged doors and at
the center plane of sliding or folding doors. When fire doors are utilized, the
maximum effort to operate the door may be increased to not exceed 15 pounds.
Section 11 B-404.2.9.
35 . Show or note that the lower 1 0" of all doors comply with Section 11B-404.2.10, as
follows:
a) To be smooth and uninterrupted, to allow the door to be opened by a
wheelchair footrest, without creating a trap or hazardous condition.
b) Narrow frame doors may use a 1 0" high smooth panel on the push side of
the door.
SANITARY FACILITIES
Provide Details on page G3-11
36. Where toilet rooms are provided, each toilet room shall comply with Section 11 B-
213. Where bathing facilities are provided, each bathing room shall comply with
Section 11 B-603. Section 11 B-213.2.
37 . Where facilities are to be used solely by children, the specific heights may be
adjusted to meet their accessibility needs, per Section 11 B-604.9.
38 . Show that passageways leading to sanitary facilities have required clear access
widths. Show that all doorways have:
a) 232" clear opening .
b) A clear area :
CARLSBAD CB-CBC2022-0187
06/21/2022
i) ~60" in the direction of the door swing.
ii) ~44" away from the direction of door swing .
c) All strike edge clearance dimensions are required to be met (i.e. 18" strike
edge distance).
39. Note that the doorways leading to sanitary facilities shall be identified , per Section
11 B-703.7.2.6, as follows:
a) An equilateral triangle ¼" thick with edges 12" long and a vortex pointing
upward at men's rest rooms .
b) A circle¼" thick, 12" in diameter at women's rest rooms.
c) A 12" diameter circle with a triangle superimposed on the circle and within
the 12" diameter at unisex rest rooms .
d) The required symbols shall be centered on the door at a height of 58" -60".
e) Braille signage shall also be located on the wall adjacent to the latch
outside of the doorways leading to the sanitary facilities.
RESTROOM FIXTURES AND ACCESSORIES
40. Show, or note, on the plans that the accessible water closets meet the following
requirements, per Sections 11 B-604.4 and 11 B-604.6:
a) The seat is to be ~17" but :s;19" in height.
b) The controls for flush valves shall be:
i) Mounted on the side of the toilet area.
ii) Be :s;44" above the floor.
41. Show, or note, on the plans that accessible urinals meet the following
requirements, per Section 11 B-605:
a) The rim of at least one urinal shall:
i) Project at least 13½ " from the wall.
ii) Be :s;17" above the floor.
b) The control mechanism is to be located :s;44" above the floor.
c) ~30" x 48" clear floor space is provided in front of the accessible urinal.
i) 36"x48" clear floor space when the urinal is located in an alcove that
exceeds 24" in depth, per section 11 B-305. 7 .1.
42. Show that accessible lavatories comply with the following, per Section 11 B-606:
a) ~30" x 48" clear space is provided in front for forward approach. The clear
space may include knee and toe space beneath the fixture .
b) When lavatories are adjacent to a side wall or partition, there shall be a
minimum of 18" to the center line of the fixture to the wall.
CARLSBAD CB-CBC2022-0187
06/21/2022
c) The counter top is s;34" maximum above the floor.
d) ~29" high , reducing to 27" at a point located 8" back from the front edge.
e) ~9" high x 30" wide and 17" deep at the bottom.
f) Hot water pipes and drain lines are insulated.
43 . Show that grab bars comply with the following , per Sections 11 B-604.5 and 11 B-
609:
a) Grab bars shall be located on each side or one side and the back of the
water closet stall or compartment.
b) They shall be securely attached 33" -36" above the floor, and parallel.
c) Grab bars at the side shall be located:
i) Be ~42" long with the front end positioned 24" in front of the stool.
ii) Total length of bars at the back shall be ~36".
d) The diameter, or width , of the grab bar gripping surface is ~1 ¼" but s;2", or
the shape shall provide an equivalent gripping surface.
e) If mounted adjacent to a wall, the space between the wall and the grab bar
shall be 1½".
44 . Per Section 11 B-603.5, show on the plans s;40" height for:
a) The operable parts of at least one:
i) Paper towel dispenser.
ii) Sanitary napkin dispenser.
iii) Waste paper disposal.
iv) Other similar dispensing and/or disposal fixtures.
b) The bottom edge of mirrors.
45. Page A2-10 please show the location of the diaper changing stations. A
Baby Diaper Changing Station shall be located per AB 1127 in at least one safe,
sanitary, convenient, and publicly accessible restroom for men and for women or
in a Unisex Restroom accessible to both men and women .
GROUP A OCCUPANCIES
46. Page A2-10 Please show that the ADA seating is in a variety of locations
throughout the tenant space , and patio. Revise plans to clearly show that
accessible seating is provided and noted as follows, per Section 11 B-221 .2:
a) Seating shall be provided in a variety of locations
b) Show a minimum of accessible seats as follows:
CARLSBAD CB-CBC2022-0187
06/21/2022
i) ~4 but ::;26 total seats = ~1.
ii) ~27 but S50 total seats = 2.
iii) ~51 but s150 total seats = 4.
iv) ~151 but S300 total seats = 5.
COUNTERS AND TABLES
47. Page A2-10 BAR ADA seating please identify a portion of the main counter
60" min in length shall be provided with a top surface that is 28" min and 34"
max above finished floor. See 118226.3, and 118902.3
ELECTRICAL
23. Page E2-00 Please identify DW2 on page E100 electrical notes as it is not
identified.
24 . Page E4-00 Please identify Item #11 to the ice machine.
ENERGY CONSERVATION
25. A complete energy plan check will be performed after completed and/or the
corrected energy design has been provided. NRCC Indoor Lighting, NRCC
Water Heater.
PLUMBING
26. P1-00 Provide calculations to show compliance with CPC 422.0 and Table 422.1
"Minimum Plumbing Facilities" using the occupant load CPC Table "A". Please
include the occupancy classification and the number of occupants. Note: If
additional bathroom fixtures are required , the handicap access requirements
must be maintained .
27. Page P2-00, and P3-00 Provide complete plumbing plans, including:
a)
b)
c)
d)
Complete drain, waste and vent plans. Page P2-00.
Provide gas line plans and calculations, showing pipe lengths and
gas demands for each appliance connected to the gas line, and the
gas meter size. Page P3-00.
Provide complete water line sizing calculations, including the water
pressure, pressure losses, water demands, and developed pipe lengths.
Sho1N 'Nater heater size, type and location on plans.
CARLSBAD CB-CBC2022-0187
06/21/2022
28 . Page P3-00 Provide gas line rise isometric and calculations showing gas
demands, pipe lengths, the proper CPC 1215.2 Table and pipe sizing.
29. Page P1 -00 Please make sure the maximum flow rate for each fixture complies
with the following chart:
FIXTURE TYPE MAXIMUM FLOW RA TE
Water closets 1.28 gallons/flush
Urinals (wall mounted) 0.125 gallons/flush
Urinals (floor mounted) 0. 5 gallons/flush
Lavatory faucets-nonresidential 0.5 gpm @60 psi
Kitchen faucets 1.8 gpm@ 60 psi
Metering faucets 0. 2 gallons/cycle
29. P2-00 Please show that Trap primers are required to be used for all
infrequent floor drains (i.e., trap guards are not approved). Please correct
the plans. CPC 1007 .0
30. Page P2-00 Please Provide the following information concerning the water
heater:
• Show that water heater is adequately braced to resist seismic forces. Provide two
straps. One strap at top 1/3 of the tank and one strap at bottom 1/3 of the tank. CPC
507.2
• Show P & T valve on water heater and detail the drain routing to the exterior or
approved location. It may not be installed upwards from the valve. CPC 608.5
• Show the routing of the direct vent combustion air & exhaust vents within the
mechanical plans. Make sure the clearance to forced air inlets are maintained
per CMC 502.2.1.
• Regarding the thermostatic mixing valve, there should be point of use at the
fixture (not at the water heater). Please correct the detail on sheet P-1.2.
31 . Page P2-00 For the hot water recirculating loop system, please detail the
following:
• The installation of an air release valve on the inlet side of the recirculation pump,
within 4' of the pump.
• A check valve is required between the recirculating pump and the water heating
equipment to prevent the hot water from flowing backwards through the recirculation
loop. Energy Code 110.3.(c).5.A
• A check valve is required on the cold-water supply line between the hot water system
and the next closest tee on the cold-water supply line per Energy Code 110.3.(c).5.F
(See CPC 608.3 for expansion tank requirements.)
• Show the required hose bibb installed between the water heater and isolation valve
(after the recirculation pump) per Energy Code 110.3.(c).5.C
• Show the required pump isolation valves (both on the inlet and outlet side) for the
recirculation pump per Energy Code 110.3.(c).5.D
CARLSBAD CB-CBC2022-0187
06/21/2022
ADDITIONAL
30. To speed up the review process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
31. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction
list? Please indicate: □ Yes □ No
32. The jurisdiction has contracted with INTERWEST, located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Steven Miller at
INTERWEST. Thank you.
CARLSBAD CB-CBC2022-0187
06/21/2022
TITLE 24 ADA COMPLIANCE
Permit# ---------------
THE ACCESSIBLE ROUTE(S) OF TRAVEL SHALL BE THE MOST PRACTICAL DIRECT ROUTE. BETWEEN
ACCESSIBLE POINTS.
I AM THE DESIGNER/OWNER IN RESPONSIBLE CHARGE OF THIS PROJECT. I HAVE INSPECTED THE
PREMISES AND DETERMINED THAT THE NEW RESTROOM{S) AND/OR AREA OF ALTERATION WILL
llE FULLY ACCESSmLE ACCORDING TO CURRENT CODE REQUIREMENTS.
SIGNATURE _______________ _
Plint Name ________________ _
DAT£ _______________ _
I AM THC DCSIGN[R/OWNER IN RESPONSl□LE CHARGE OF THIS PROJECT, I HAVE INSPECTED THE
SITE/PREMISES AND DETERMINED THAT EXISTING CONDITIONS SHALL BE MODIFIED IN ~Ult.
COMPLIANCE WITH CURRENT SITE ACCESSIBILITY REQUIREMENTS TO THE EXTENT REOUlfl.ED BY
LAW.
SIGNATURE. _________________ _
P:i1t Nenc:. _________________ _
DATE _______________ _
IF THE BUILDING INSPECTOR DETERMINES NON-COMPLIANCE WI IH ANY CURRE;NT ACCESSIBLITY
PROVIStONS OF THE LAW, HE/SHE SHALL REQUIRE SUBMITTAL OF COMPLET[. AND DCTAILED
PLANS TO BUl~DING AND SAFETY DIVISION o r-THE DEVELOPMENT SERVICES J)FPARMFNT FOR
FURTHER R£VIEW. PLANS MUST CLEARLY SHOW ALL EXISTING NON-COM PL YING CONDITIONS
AFFECTED BY THE REMODEL (INCLUDING SITE PLAN, FLOOR PLANS, DETAILS, l:TC.) AND
PROl-'OSELJ MOUIHCA'l 10N$ Or Pl:f-'ICIENCIES TO MEET CURRENTS /\CCESSIBLITY PROVISIONS.
THE PLANS MUST BE SIGNED AND DAT[D BY rnc f"ll=LD INSPECTOR PRIOR SUBMITTAL FOR PLAN
REVIF-W.
IF THE BUILDING INSPECTOR DETERMINES THAT FULL COMPUANCt:: WITH CURRENT SITE
ACCESSIBILITY REQUIREMENTS IS NOT PROVIDED. HE/SHE 51-W.L fl.CQUIRC SUDl<ollTTAL OF A
DETAILED SITE PLAN FOR ADDITIONAL PLAN Rl"VlFW AND COMMFNTS.
END OF DOCUMENT
Business Name
Torsap Thai
Project Address
SAN DIEGO REGIONAL
HAZARDOUS MATERIALS
QUESTIONNAIRE
Business Contact
Cian Sanchez
OFFICE USE ONLY
RECORD ID # __________________ 1
PLAN CHECK # _________________ 1
Telephone#
415-994-3896
BP DATE
APN#
2668 Gatewa Rd Ste 170
City
Carlsbad
State
CA
Zip Code
92009
Malling Address
2668 Gateway Rd Ste 170
Project Contact
Jack Shively
City
Carlsbad
State
CA
Zip Code
92009
Applicant E-mail Telephone#
jshively@sparc.design 951 .293.4526
Plan File#
The following questions represent the faclllty's activities, NOT the specific project description.
PART I: FIRE DEPARTMENT -HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: (not required for projects within the City of San
Diego): Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled,
applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: A2 Facility's Square Footage (including proposed project): 2950 sf
1. Explosive or Blasting Agents 5. Organic Peroxides 9. Water Reactives 13. Corrosives
2. Compressed Gases 6. Oxid izers 10. Cryogenics
3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials
4. Flammable Solids 8. Unstable Reactives 12. Radioactives
14. Other Health Hazards r 5. None of These. I
PART II: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEAL TH -HAZARDOUS MATERIALS DIVISION (HMDl: If the answer to any of the
questions is yes. applicant must contact the County of San Diego Hazardous Materials Division, 5500 Overland Avenue, Suite 110, San Diego, CA 92123.
Cail (858) 505-6700 prior to the issuance of a building permit.
FEES ARE REQUIRED Project Completion Date: Expected Date of Occupancy: 0 CalARP Exempt
I
1.
2.
3.
4.
5.
6.
7.
8.
YES 0
□
□
□
□ □ D
D
D
(for new construction or remodeling projects)
Is your business listed on the reverse side of this form? (check all that apply).
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
Will your business store or handle carcinogens/reproductive toxins in any quantity?
Will your business use an existing or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal to
or reater than 1,320 allons? California's Above round Petroleum Stora e Act .
Date Initials
□Cal
Date
Date
PART Ill: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT APCD : Any YES' answer requires a stamp from APCD 10124 Old Gro Ro San
Diego. CA 92131 apcdcomp@sdcounty.ca.gov 858) 586-2650). [*No stamp required if Q1 Yes and Q3 Yes and Q4-Q6 No]. The following questions nded
to identify the majority of air pollution issues at the planning stage. Projects may require additional measures not identified by these questions. For comprehensive
requirements contact APCD. Residences are typically exempt, except -those with more than one building' on the property; single buildings with more than four
dwelling units : townhomes; condos; mixed-commercial use; deliberate burns; residences forming part of a larger project. CExcludes garages & small outbuildings.)
1.
2 .
3.
YES NO
-Er D □ ..ei· . er □
Will the project disturb 160 square feet or more of existing building materials?
Will any load supporting structural members be removed? Notification may be required 10 working days prior to commencing demolition.
(ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been performed by a Certified Asbestos Consultant or Site Surveillance
Technician?
4. D ..a (ANSWER ONLY IF QUESTION 3 IS YES) Based on the survey results, will the project disturb any asbestos containing material? Notification
may be required 10 working days prior to commencing asbestos removal.
5. D g Will the project or associated construction equipment emit air contaminants? See the reverse side of this form or APCD factsheet
(www.sdapcd.org/tnfo/facts/perm1ts.pdf) for typical equipment requiring an APCD permit.
6. D D (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school
bounda
Briefly describe business activities:
Dine In Restaurant Briefly describe proposedrroject: Tenant lmprovemen ot re staurant finishes
I declare under penalty of perjury that to the best of my knowledge and belie herein are true and correct. 05 I 18 / 2022
Date
lack Sbively
Name of Owner or Authorized A ent
FOR OFFICAL USE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION: _______________________________ _
BY-DATE· I I
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO' APCD COUNTY-HMO APCD COUNTY-HMO APCD
~ ,oo Lo'>G,.
q~ o,,
.. A.ev,eweo g ~ 05/23/2022-M~ ~
Dllt /lnitaal
.s;,,., !I.
(.O~ o,ego
. . 'A stamp in this box only exempts businesses from completing or updating a Hazardous Materials Business Plan. Other permitting requirements may still apply .
HM-9171 (08/15) County of San Diego -DEH -Hazardous Materials Division
...
C_cicyof
Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
B-50
Development Services
Building Division
1635 Faraday Avenue
442-339-2719
www.carlsbadca.gov
This checklist is intended to help building permit applicants identify which Climate Action Plan (CAP) ordinance requirements
apply to their project. This completed checklist (B-50) and summary (B-55) must be included with the building permit
application. The Carlsbad Municipal Code {CMC) can be referenced during completion of this document by clicking on
the provided links to each municipal code section.
NOTE: The following type of permits are not required to fill out this form
❖ Patio I ❖ Decks I ❖ PME (w/o panel upgrade) I ❖ Pool
Consultation with a certified Energy Consultant is encouraged to assist in filling out this document. Appropriate
certification includes, but is not limited to: Licensed, practicing Architect, Engineer, or Contractor familiar with Energy
compliance, IECC/HERS Compliance Specialist, ICC G8 Energy Code Specialist, RESNET HERS rater certified, certified
ICC Residential Energy Inspector/Plans Examiner, ICC Commercial Energy Inspector and/or Plans Examiner, ICC CALgreen
Inspector/Plans Examiner, or Green Building Residential Plan Examiner.
If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required by ordinance,
check N/A and provide an explanation or code section describing the exception.
Details on CAP ordinance requirements are available at each section by clicking on the municipal code link provided. The
project plans must show all details as stated in the applicable Carlsbad Municipal Code (CMC) and/or Energy Code and
Green Code sections .
r-------------------------------------------
Project Name/Building
Permit No.:
Property Address/APN:
Applicant Name/Co.:
Applicant Address:
Contact Phone:
Application trifonnatlon
CB-CBC2022-0187 BPNo.: ~c,0U:,-Q \qjl,
2668 Gateway Road, Ste 170
Cian Sanchez
1388 Locust Street, Walnut Creek CA, 94596
415 -994 -3896 Contact Email: cian .sanchez@yahoo.com
Contact information of person completing this checklist (if different than above):
Name:
Company
name/address:
Contact Phone: 415 -994 -3896
Contact Email:
Applicant Signature:_C--____ _____.~.__,.__ ________ Date: 8/19/22
B-50 Page 1 of 7 Revised 04/21
Use the table below to determine which sections of the Ordinance checklist are applicable to your project. For
alterations and additions to existing buildings, attach a Permit Valuation breakdown on a separate sheet.
Building Permit Valuation (BPV) $ breakdown $365,000.00
I Construction Type 1 Complete Section(•) I Notes:
A high-rise residential building is 4 or more stories, including a D Residential Low-rise High-rise mixed-use building in which at least 20% of its conditioned floor
area is residential use
□ New construction 2A*, 3A*, 18, 28, *Includes detached, newly constructed ADU 4A*, 38,4A
D Additions and alterations:
□ BPV < $60,000 N/A N/A All residential additions and alterations
□ BPV;:: $60,000 1A, 4A 4A 1-2 family dwellings and townhouses with attached garages
□ Electrical service panel upgrade only only.
*Multi-family dwellings only where interior finishes are removed
□ BPV;:: $200,000 1A, 4A* 18, 4A* and significant site work and upgrades to structural and
mechanical, electrical, and/or plumbing systems are proposed
Ii] Nonresidential
□ New construction 1 B, 28, 38, 48 and 5
!!!!I Alterations:
!!!!I BPV;:: $200,000 or additions;:: 1,000 18,5 square feet
□ BPV;:: $1 ,000,000 1B,2B,5 Building alterations of;:: 75% existing gross floor area
□ ;:: 2,000 sq. ft. new roof addition 28, 5 1 B also applies if BPV;:: $200,000
Checklist Item
Check the appropriate boxes, explain all not applicable and exception Items, and provide supporting calculations and documentation as necessary.
1. Energy Efficiency
Please refer to Carlsbad Municipal Code (CMC) 18.21 .155 and 18.30.190,and the California Green Building Standards Code (CAL Green) for more
information. Appropriate details and notes must be placed on the plans according to selections chosen in the design.
A. D Residentialadditionoralteration~$60,000buildingpennitvaluation. D N/A replace, Existing Patio Light
Details of selection chosen below must be placed on the plans referencing CMC □ Exception: Home energy score~ 7
18.30.190. (attach certification)
Year Built Single-family Requirements Multi-family Requirements
D Before 1978 Select one option:
□ Ductsealing □ Attic insulation □Cool roof □ Attic insulation
□ 1978 andlater Select one option:
□ Lighting package □ Water heating Package
□ Between1978and1991 Select one option:
□ Ductsealing □ Attic insulation □Cool roof
□ 1992 and later Select one option:
□ Lighting package □ Water heating package
Updated 4/16/202 I
I
3
B. ~ Nonresidential* new construction or alterations~ $200,000 building permit valuation,
or additions~ 1,000 square feet. See CMC 18.21.155 and CAL Green Appendix AS D N/A replace, Existing Patio LG
AS.203.1.1 Chooseone: .1 Outdoorlighting □ .2 Restaurant service water heating {CEC 140.5)
D .3Warehousedocksealdoors. □.4DaylightdesignPAFs □.5Exhaustairheatrecovery □ N/A replace, Existing Patio LiiQ
AS.203.1.2.1 Choose one:□ .95 Energy budget {Projects with indoor lighting OR mechanical)
□ .90 Energy budget (Projectswith indoorlightingANDmechanical) l!!!I N/A
AS.211.1 ** □ On-site renewable energy:
D N/A
AS.211.3** D Green power: (If offered by local utility provider, 50% minimum renewable sources)
D N/A
AS.212.1 D Elevators and escalators: (Project with more than one elevator or two escalators)
D N/A
AS.213.1 □ Steel framing: (Provide details on plans for options 1-4 chosen)
D N/A ----------
• Includes hotels/motels and high-rise residential buildings
.... For alterations~ $1,000,000 BPV and affecting> 75% existing gross floor area, OR alterations thatadd2,000square feet of new roof addition: comply
with CMC 18.30.130 (section 28 below) instead.
2. Photovoltaic Systems
A. D Residential new construction (for low-rise residential building permit applications submitted after 1/1/20). Refer to 2019 California
Energy Code section 150.1(c)14 for requirements. If project includes installation of an electric heat pump water heater pursuant to
CAP section 3B below (low-rise residential Water Heating), increase system size by .3kWdc if PVoffset option is selected.
Floor Plan ID (use additional CFA #d.u . Calculated kWdc*
sheets if necessary)
Total System Size:
kWdc = (CFAx.572) / 1,000 + (1.15 x #d.u.)
*Formula calculation where CFA = conditional floor area, #du= number of dwellings per plan type
If proposed system size is less than calculated size, please explain.
kWdc
Exception
D
D
D
D
B. D Nonresidential new construction or alterations ~$1,000,000 BPV AND affecting ~75% existing floor area, OR addition that increases
roof area by ?2,000 square feet Please refer to CMC 18.30.130 when completing this section. •Note: This section also applies to
high-rise residential and hotel/motel buildings.
Choose one of the following methods:
□ Gross Floor Area (GFA)Method
GFA:
D If< 1 O,OOOs.f. Enter: 5 kW de
Min.System Size:
□ If~ 10,000s.f. calculate: 15 kWdc x (GFN10,000) **
kWdc
**Round building size factor to nearest tenth , and round system size to nearest whole number.
Updated 4/16/2021 4
□ Time-Dependent Valuation Method
AnnualTDV Energyuse:* ... ______ x .80= Min. system size:. ______ kWdc
***Attach calculation documentation using modeling software approved by the California Energy Commission.
3. Water Heating
A. D R.esidential and hotel/motel new construction. Refer to CMC 18.30.170 when completing this section.
Provide complete details on the plans.
D For systems serving individual dwelling units choose one system:
D Heat pump water heater AND Compact hot water distribution AND Drain water heat recovery (low-rise
residential only)
D Heat pump water heater AND PV system .3 kWdc larger than required in CMC 18.30.130 (high rise
residential hotel/motel) or CA Energy Code section 150.1(c) 14 (low-rise residential)
□ Heat pump water heater meeting NEEA Advanced Water Heating Specification Tier 3 or higher
D Solar water heating system that is either .60 solar savings fraction or 40 s.f. solar collectors
□ Exception:
D For systems serving multiple dwelling units, install a central water-heating system with ALL of the following:
D Gas or propane water heating system
D Recirculation system per CMC 18.30.150(8) (high-rise residential, hotel/motel) or CMC 18.30.170(8) (low-
rise residential)
D Solar water heating system that is either:
D .20 solar savings fraction
D .15 solar savings fraction , plus drain water heat recovery
D Exception:
B. D Nonresidential new construction. R.efer to CMC 18.30.150 when completing this section. Provide
complete details on the plans.
D Water heating system derives at least 40% of its energy from one of the following (attach documentation):
D Solar-thermal D Photovoltaics D Recovered energy
D Water heating system is (choose one):
D Heat pump water heater
D Electric resistance water heater(s)
□Solar water heating system with .40 solar savings fraction
□ Exception:
It may be necessary to supplement the completed checklist with supporting materials, calculations or certifications, to
demonstrate full compliance with CAP ordinance requirements. For example, projects that propose or require a
performance approach to comply with energy-related measures will need to attach to this checklist separate calculations
and documentation as specified by the ordinances.
Updated 4/16/2 l 5
4. Electric Vehicle Charging
A D Residential New construction and major alterations*
Please refer to CMC 18.21.140 when completing this section.
□ One and two-family residential dwelling or townhouse with attached garage:
□ One EVSE Ready parking space required □Exception : _____________ _
□ Multi-family residential : □Exception : ____________ _
Total Parking Spaces EVSE Spaces
Proposed EVSE (10% of total) Installed (50% of EVSE) Other "Ready" Other "Capable"
Calculations: Total EVSE spaces= .10 x Total pari<ing spaces proposed (rounded up to nearest whole number) EVSE Installed = Total EVSE
Spaces x .50 (rounded up to nearest whole number) EVSE other may be "Ready" or "Capable"
*Major alterations are: ( 1) for one and two-family dwellings and townhouses with attached garages, alterations have a building permit
valuation~$60,000 or include an electrical service panel upgrade; (2) for multifamily dwellings (three units or more without attached
garages), alterations have a building permit valuation~ $200,000, interiorfinishes are removed and significant site work and upgrades to
structural and mechanical, electrical, and/or plumbing systems are proposed.
*ADU exceptions for EV Ready space (no EV ready space required when):
(1) The accessory dwelling unit is located within one-half mile of public transit.
(2) The accessory dwelling unit is located within an architecturally and historically significant historic district.
(3) The accessory dwelling unit is part of the proposed or existing primary residence or an accessory structure.
(4) When on-street parking permits are required but not offered to the occupant of the accessory dwelling unit.
(5) When there is a car share vehicle located within one block of the accessory dwelling unit.
B. D Nonresidential new construction (includes hotels/motels) □ Exception : ____________ _
Please refer to CMC 18.21.150 when completing this section
Total Parking Spaces
Proposed EVSE (10% of total) I Installed (50% of EVSE) I Other "Ready" I Other "Capable"
I I I
Calculation: Refer to the table below:
Total Number of Parking Spaces provided Number of required EV Spaces Number of required EVSE Installed Spaces
D 0-9 1 1
D 10-25 2 1
D 26-50 4 2
D 51-75 6 3
D 76-100 9 5
D 101-150 12 6
D 151-200 17 9
D 201 andover 1 O percent of total 50 percent of Required EV Spaces
Calculations: Total EVSE spaces= .10 x Total pari<ing spaces proposed (rounded up to nearest whole number) EVSE Installed = Total EVSE
Spaces x .50 (rounded up to nearest whole number) EVS E other may be "Ready" or "Capable"
Updated 4/16/2021 6
5. □Transportation Demand Management {TDM): Nonresidential ONLY
An approved Transportation Demand Management (TOM) Plan is required for all nonresidential projects that meet a threshold of employee-generated ADT.
City staff will use the table below based on your submitted plans to detennine whetheror noryour pennit requires a TDM plan. lfTDM is applicable to your
permit, staff will contactthe applicantto develop a site-specific TOM plan based on the permit details.
Acknowledgment:
Employee ADT Estimation for Various Commercial Uses
Use
EmpADTfor
first 1,000 s.f.
EmpADTI
1000 s.f.1
Office (all)2 20
Restaurant 11
Retail3 8
Industrial 4
Manufacturing 4
Warehousing 4
1 Unless otherwise noted, rates estimated from ITE Trip
Generation Manual, 10thEdition
13
11
4.5
3.5
3
1
2 For all office uses, use SAN DAG rate of 20 ADT/1,000 sf to
calculate employee ADT
3 Retail uses include shopping center, variety store, supermarket,
gyms, pharmacy, etc.
Other commercial uses may be subject to special
consideration
sample calcvlatjons:
Office: 20,450 sf
1. 20,450 sf/ 1000 x 20 = 409 Employee ADT
Retail: 9,334 sf
1. First 1,000 sf= 8 ADT
2. 9,334 sf -1,000 sf= 8,334 sf
3. (8 ,334 sf/ 1,000 x 4.5) + 8 = 46 Employee ADT
I acknowledge that the plans submitted may be subject to the City of Carlsbad's Transportation Demand Management Ordinance. I agree to be contacted should
my permit require a TOM plan and understand tha n approved TOM plan is a condition of permit issuance.
Date: 8/19/22
Person other than Applicant to be contacted for TDM compliance (if applicable):
Name(Printed): __________________ _ Phone Number: _____ _
Email Address: __________________ _
Updated 4/16/2021 7