HomeMy WebLinkAboutCDP 96-14; Marja Acres PCS Facility; Coastal Development Permit (CDP) (5)HETHERINGTON ENGINEERING, INC. SOIL & FOUNDATION ENGINEERING • ENGINEERING GEOLOGY • HYDROGEOLOGY October 21, 1996 Project No. 1519.1 Log No. 2521 J. M. Consulting Group, Inc. 3530 Camino Del Rio North, Suite 101 San Diego, CA 92108 Attention: Ms. Cheryl M. Hacke Subject: RESPONSE TO PLAN CHECK NO. 96-1376 Proposed Cox California PCS Station SD154 - Marja Acres - 4901 El Camino Real Carlsbad, California References: 1) "Geotechnical Investigation, Proposed Cox California PCS Station, SD154-Marja Acres, Carlsbad, California," by Hetherington Engineering, Inc., dated February 21, 1996. 2) "Supplemental Geotechnical Investigation, Proposed Cox California PCS Station, SD154- Marja Acres, Carlsbad, California," by Hetherington Engineering, Inc. dated May 14, 1996. 3) "Supplemental Retaining Wall Parameters, Proposed Cox California PCS Station, SD154 - Marja Acres, Carlsbad, California," by Hetherington Engineering, Inc., dated July 17, 1996. 4) Plans for Marja Acres, Job #SD154, by KDC Architects, dated July 25, 1996. Dear Ms. Hacke: In accordance with the request of Mr. Barry Lackman of your office, we are providing this response to Plan Check No. 96-1376, dated October 11, 1996 by Esgill Corporation. 1) The intent of UBC Section 1806.4.2. is to protect structures from slope drainage, erosion and shallow failures. The concrete V-ditch provided along the rear of the retaining wall (Reference 1, Sheet C-l, Section A-A) addresses drainage. To protect the structure from erosion and shallow failures, it is recommended that the retaining wall extend a minimum of 3 feet above the slope to act as a slough wall. Periodic removal of soil behind the slough wall should be anticipated. If the 5245 Avenida Encinas, Suite G • Carlsbad, CA 92008-4369 • (619) 931-1917 • Fax (619) 931-0545 32242 Paseo Adelanto, Suite C • San Juan Capistrano, CA 92675-3610 • (714) 487-9060 • Fax (714) 487-9116 RESPONSE TO PLAN CHECK NO. 96-1376 Project NO. 1519.1 Log No. 2521 October 21, 1996 Page 2 slough wall is constructed as recommended it is our opinion that the setback requirement may be eliminated. 2) As the plan checker has indicated, the slab-on-grade should have a minimum thickness of 6-inches and should be reinforced with at least #4 bars spaced at 12-inches, center to center, in accordance with our recommendations. 3) For design of antenna caissons, lateral loads may be resisted by a passive pressure of 200 pounds per square foot per foot of depth in terrace deposits/bedrock, which may be calculated over two pier diameters. This recommendation has alredy incorporated the 2x factor allowed in UBC Table 18-1-A note 3. This opportunity to be of service is appreciated. If you should have any questions, please contact Danny Cohen at the Carlsbad office. Sincerely, HETHER DANNY COHEN Civil Engineer (expires 3/31 MDH cc:KDC Architecture Ken Miller Fax #683-2349 HETHERINGTON ENGINEERING, INC.