HomeMy WebLinkAboutPIP 91-02; H. A. Lavezzi Distributing Corporate Headquarters; Planned Industrial Permit (PIP) (2)hare & Malcomb Architects, II >L. 6125 Cornerstone Court, Suite 200, San Diego, CA 92121 (619) 546-1121 FAX (619) 546-1062 July 24, 1992 Mr. Michael Smith, Fire Marshal CITY OF CARLSBAD FIRE DEPARTMENT 2560 Orion Way Carlsbad, CA 92008 RE: PLANNED INDUSTRIAL PER"' PIP #91-2 HA. LAVEZZI DISTRIBUTING Dear Mike, Below are responses to your attached deficiency items and conditions of approval. They are as follows: Pending 01: a) b) Pending 02 a) Pending 07 a) Pending 10 a) See note no# 11, sheet 2 Permits for the underground fuel tanks will be issued at time of building permit issuance. The above grade propane tank has been relocated 25 feet away from property line. The proposed tank will not exceed 1,0oO gal., thus complying with UFC, Article 82. A rack layout and list of commodities of high piled stock will be submitted during building plan check. On-site fire hydrants and water mains are shown on the civil plan, sheet #3. The proposed hydrants are not obstructed by parking. See note #14, sheet 2. See note #13, sheet 3. IRVINE - SAN DlEGO * WOODLAND HILLS * ONTARIO c I appreciate your immediate attention to these responses. The planned Industrial Permit application is due to expire September 6, 1992. Should you have any questions or comments do not hesitate to call me at 546-1121. Regards, WARE & MALCOMB ARCHrrEm, INC. "w . /[remenis Category: rr, Conditions ? " Jefidency Item: Pen d I n g, 01 Building Permits 4) Prior to the Issuance bl building permits, complete building plans shall be approved by the Fire Department. A) Permits are required for t,he fuel tanks. proposed locatiQn of propane t?nk is unameptable per UFC art 82. I High piled storage i!s indicated. Applicant must submit a plan for storage which includes a description of commodities and the intended storage array. Deficiency Item: P e n d 1 n g 02 Hydrants Ir) Additional on-site public water mains and fire hydrants are required. L) Proposed hydrant locations are unacceptable due to obstruction by parking. 4 Deficiency Item: P e n d I n g 07 Security gate systems . All security gate systems controlling vehicular access shall be equipped with a 'Knox", keysperated emergency entry device. Applicant shall contcqcl the, Fire Prevention Bureau for specifications and approvals prior to Installation. - .. I Deficiency Item: P e n d In g 10' Fire protection systems- sprinklers, alarms, standpipes I Plans andlor specifications for fire alarm systems, fire hydrants, automatic fire sprinkler systems and other .: .I fire protectioo sys!ems shall bqwbmitted to the Fire Depattment for approval prior to construction. I ." . * Page 2 "~ 1 2/20/91 .