HomeMy WebLinkAboutPIP 98-05; Cornerstone Corporate Center; Planned Industrial Permit (PIP) (11)m City of Carlsbd /h rl
981 11
Fire Department e Bureau of Prevention
Plan Review: Requirements Category: Fire Conditions
Date of Report: Tuesday, April 7,1998 Reviewed by: ha Nd
Contact Name Van Lynch
I
Address
City, State CA 92009 ; ..
Bldg. Dept. No. Planning No. PIP98-05
Job Name Cornerstone Lot15
Job Address Wright Ste. or Bldg. No.
5 Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal; bt$. (,ucJiSldL therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
0 Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st 2nd 3rd
CFD Job## 981 11 File# Other Agency ID
2560 Orion Way Carlsbad, California 92008 (619) 931-2121
~~ ~~ ~ ~
v
* Requirements Category: “re Conditions - 981 11
Deficiency Item: P e n d I n g
~~
01 Building Permits
Prior to the issuance of building permits, complete building plans shall be approved by the Fire
Department.
Proposed language:
Prior to issuance of building permits, the Fire Department shall evaluate building plans for
conformance with applicable fire and life safety requirements of the state and local Fire Codes.
Deficiency Item: P e n d i n g 02 Hydrants
Additional on-site public water mains and fire hydrants are required.
Proposed change for Industrial and multi family:
Provide additional public fire hydrants at intervals of 300 feet along public streets and private
driveways. Hydrants should be located at street intersections when possible, but should be
positioned no closer than 100 feet from terminus of a street or driveway.
Proposed change for single family residences:
Provide additional public fire hydrants at intervals of 500 feet along public streets and/or private
driveways. Hydrants should be located at street intersections when possible, but should be
positioned no closer than 100 feet from terminus of a street or driveway.
[ Deficiency Item: P e n d i n g 03 Site Plan/Hydrants
~~ ~ ~~
Applicant shall submit a site plan to the Fire Department for approval, which depicts location of
required, proposed and existing public water mains and fire hydrants. The plan should include
off-site fire hydrants within 200 feet of the project.
Deficiency Item: P e n d i n g 04 Site plan/access
Applicant shall submit a site plan depicting emergency access routes, driveways and traffic
circulation for Fire Department approval.
~~ [ Deficiency Item: P e n d i n g 05 Access during construction
~ ~ ~ ~ ~ ~ ~~~~ ~~~ ~-
An all weather, unobstructed access road suitable for emergency service vehicles shall be provided
and maintained during construction. When in the opinion of the Fire Chief, the access road has
become unserviceable due to inclement weather or other reasons, he may, in the interest of public
safety, require that construction operations cease until the condition is corrected.
1
Deficiency Item: P e n d i n g 06 Combustible construction materials on site
All required water mains, fire hydrants and appurtenances shall be operational before combustible
building materials are located on the construction site. I
Deficiency Item: P e n d i n g 08 Fire lanes
Prior to building occupany, private roads and driveways which serve as required access for
emergency service vehicles shall be posted as fire lanes in accordance with the requirements of
section 17.04.020 of the Carlsbad Municipal Code.
I
Page 2
L t Reguiremenfs Category: "'re Conditions 981 11
Deficiency Item: P e n d I n g 09 Brush clearance
Native vegetation which presents a fire hazard to structures shall be modified or removed in
accordance with the specifications contained in the City of Carlsbad Landscape Guidelines Manual.
Applicant shall submit a Fire Suppression plan to the Fire Department for approval.
Proposed new condition
Prior to issuance of the building permit, the applicant shall obtain fire department approval of a
wildland fuel management plan. The plan shall clearly indicate methods proposed to mitigate and
manage fire risk associated with native vegetation growing within 60 feet of structures. The plan
shall reflect the standards presented in the fire suppression element of the City of Carlsbad
Landscape Guidelines Manual.
mxebebw
Prior to occupancy of buildings, all wildland fuel mitigation activities must be complete, and the
condition of all vegetation within 60 feet of structures found to be in conformance with an approved
wildland fuel management plan.
~ ~~~ ~~
Deficiency Item: P e n d i n g 10 Fire protection systems- sprinklers, alarms, standpipes
Plans and/or specifications for fire alarm systems, fire hydrants, automatic fire sprinkler systems and
other fire protection systems shall be submitted to the Fire Department for approval prior to
construction.
Proposed language
All buildings having an aggregate floor area in excess of 10,000 square feet must be protected by
automatic fire sprinkler systems. Plans and specifications must be approved by the fire department,
and a permit obtained prior to installation.
Proposed multifamily residential buildings must be protected by fire alarm systems. Plans and
specifications must be approved, and a permit obtained prior to installation.
Page 3