HomeMy WebLinkAboutRP 93-03; Ralph & Eddie's Garden Patio; Redevelopment Permits (RP) (3)March 17,1994
TO: ASSOCIATE PLANNER, TERRI WOODS
FROM: Principal Civil Engineer, Land Use Review
RP 93-03: RALPH & EDDIE'S GARDEN PATIO
The title reports for this project were reviewed by Jim Davis. They confirmed that there is an
existing 20-foot easement along the northerly property line. Therefore, that portion of the
property is encumbered by a legal easement and should not be used for the project's expansion
unless it is vacated. There is also the possibility that the easement may also be a part of the
lease agreement with the Village Faire project. We do not have a copy of the lease agreement,
but have been told that the same 20-foot easement may be a part of the agreement. Therefore,
that lease agreement would also have to be amended before we would recommend the project
going fon^^ard.
The other concern that Engineering has is for the parking shown along Washington Street.
NCTD is in the process of improving Washington Street, thereby changing the 90° parking shown
to parallel parking and not having any available parking on Washington Street on the east side.
Therefore, both Washington Street and the existing NCTD right-of-way that has been used for
Ralph & Eddie's parking will no longer be available to them.
ROBERT J. WOJCIK
Principal Civil Engineer
RJW:jb
March 23, 1994
TO: PLANNING DEPARTMENT, TERRI WOODS
FROM: REDEVELOPMENT DEPARTMENT, DEBBIE FOUNTAIN
RE: CDP 94-3/RP 93-3, RALPH & EDDIE'S GARDEN PATIO
Attached for your review is some recent correspondence forwarded to Ralph Bumette, Jr. and
Bob Burke of Village Faire regarding the easement used for driveway purposes behind Ralph
& Eddie's Cardroom.
According to the Bumette's agreement with Village Faire (TIO-TIL, LTD.), there is a 20'
easement mnning behind Ralph and Eddie's which must be maintained for driveway purposes.
I can't tell from the plans for the garden patio whether or not the patio will block this access.
If the patio does block the driveway, we need to note that in the report to DRB and indicate that
the project would need to be redesigned to maintain the easement.
In addition to maintenance of the easement, Redevelopment Department's only other comment
would be related to the shortage of parking which you have already indicated would be the
reason for denying the project.
If you have any questions regarding the attached correspondence or Redevelopment's position
on the application, please give me a call at X2935.
Thanks,
DEBBIE FOUNTAIN
Senior Management Analyst
CHy of CarlsbUl ^^4081
Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Fire Conditions
Date of Report: Wednesday, March 30,1994 Reviewed by:
Contact Name Terry Woods
Address
City, State JCA .
BIdg. DepL No. Planning No.
Job Name Ralph & Eddies
Job Address 390 Grand Ste. or BIdg. No.
• Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
Kl Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st 2nd 3rd
Other Agency ID
CFDJob# 94081 File#
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121
City of Carlsba# ^
Fire Department • Bureau of Prevention
General Comments:
Date of Report: Wednesday, March 30,1994
Contact Name Terry Woods
Address
City. State CA
BIdg. Dept. No. Planning No.
Job Name Ralph & Eddies
Job Address 390 Grand Ste. or BIdg. No.
Site plan does not provide exiting, door and floor plan (use of area) information that is required for approval.
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121
Requirements Category: lilding Plan Check HAF9408I
Deficiency Item: Pending 01 Project Data
Provide complete address and suite designation. Provide building constmction information
indicating occupancy classification, type of^constmction, number of stories, aggregate square
footage, occupant load, and description of'intended uses.
Deficiency Item: Pending 03 Floor Plan
Provide a complete floor plan of building or suite. Show exiting from all areas. Indicate use or
occupancy of each room including adjacent suite if applicable.
Deficiency Item: Pending 18 Fire Extinguishers Required
Provide one 2A1 OBC fire extinguisher for each 6000 square feet or portion thereof with a travel
distance to the nearest extinguisher not to exceed 75 feet of travel. See item 32 for any additional
fire extinguisher requirements.
20 Number of Exits Deficiency Item: Pending
Every building or usable portion thereof shall have at least one exit, not less than two exits where
required by UBC table 33-A. See item 32 for specific Exit requirement.
Deficiency Item: Pending 21 Ex it Doors
Exit doors shall be of the pivoted type or side hinged swinging type. Exit doors shall swing in the
direction of exit travel when serving an occupant load of 50 or more.
Special Doors- Revolving, sliding and overhead doors shall not be used as required exits.
Power-operated doors complying with UBC Standard No.33-1 may be used for exit purposes.
Addditional Doors- When additional doors are provided for egress purposes, they shall conform to all
the provisions of UBC chapter 33.
See item 32 for specific requirements for your exit doors.
Deficiency Item: 22 Exit Door Hardware Pending
Exit doors shall be openable from the inside without the use of a key or any special knowledge or
effort.
Exception: In group B occupancies, key locking hardware may be used on the Main Exit when the
main exit consists of a single door or pair of doors if there is a readily visible, durable sign on or
adjacent to the door stating, "This door to remain unlocked during business hours."
For State Fire Marshal, sign shall read, "This door to remain unlocked whenever the building is
occupied."
See item 32 for additional exit door hardware requirements.
Deficiency Item: Pending 23 Panic Hardware
In A.E and I occupancies doors serving an area with an occupant load of 50 or more shall not be
provided with a lock or latch unless it is panic hardware. Panic hardware, when installed, shall comply
with the requirements of UBC Std. No.33-4.
Page 2 03/30/94
Rejquirements Category: Binding Plan Check HAF9408I
Deficiency Item: Pending 25 Exit Signs
SEC.3314,(a) Where Required. When two or more exits from a story are required by Section 3303,
exit signs shall be installed at stair enclosure doors, horizontal exits and other required exits from the
story. When two or more exits are required from a room or area, exit signs shall be installed at the
required exits from the room or area and where othenwise necessary to clearly indicate the direction
of egress.
EXCEPTIONS: 1. Main exterior exit doors which obviously and clearly are identifiable as exits
need not be signed when approved by the building official.
2. Group R, Division 3, and individual units of Group R, Division 1 Occupancies.
3. Exits from rooms or areas with an occupant load of less than 50 when located within a Group I,
Division 1.1,1.2 or 2 occupancy or a Group E, Division 3 day-care occupancy.
Illumination: Signs shall be internally or externally illuminated by two electric lamps or shall be of an
approved self-luminous type.
Power Supply: Current supply to one of the lamps for exit signs shall be provided by the premises'
wiring system. Power to the other lamp shall be from storage batteries or an on-site generator set.
26 Exit Illumination Deficiency Item: Pending
Exits shall be illuminated at any time the building is occupied with light having intensity of not less
than 1 footcandle at floor level. The power supply for exit illumination shall normally be provided by
the premises'wiring system. In the event of its failure, illumination shall be automatically provided
from an emergency system of Group I, Division 1 Occupancies and for all other occupancies where
the exiting system serves an occupant load of 100 or more.
Deficiency Item: Pending 27 Occupant Load Signs
Any room having an occupant load of 50 or more where fixed seats are not installed, and which is
used for classroom, assembly or similar purpose, shall have the capacity of the room posted in a
conspicuous place .
Pages 03/30/94
REVIEW AND COMMENT MEM
DATE:
TO:
r . r,yi\
FROM:
MARCH 16, 1994 REVISED PLAN •
ENGINEERING DEPARTMENT
GROWTH MANAGEMENT (MEMO ONLY)
POLICE DEPARTMENT - ATTN: J. SASWAY
FIRE DEPARTMENT
BUILDING DEPARTMENT
PARKS AND RECREATION DEPARTMENT
UTILITIES/MAINTENANCE DEPARTMENT ^
CARLSBAD WATER DISTRICT
LANDSCAPE PLANCHECK CONSULTANT
SCHOOL DISTRICT
NORTH COUNTY TRANSIT DISTRICT - 311 S..Tr^nao;it^l^:^et,
Oceanside, CA 92054-3119 U ^^- ^"^
Always Send Exhibits
Planning Department
REQUEST FOR REVIEW AND COMMENT ON APPLICATION NO. CDP 94-3/RP 93-3
NOTE: PLEASE USE THIS NUMBER ON ALL CORRESPONDENCE CONCERNING THIS
APPUCATION.
PROJECT TITLE:
APPLICANT:
PROPOSAL:
FENCED OFF AREA.
RALPH S EDDIE'S GARDEN PATIO
RALPH F. BURNETTE, JR.
ADDING AN ENCLOSED PATIO, INCLUDING
PROJECT PLANNER: TERRi WOODS
Please review and submit written comments and/or conditions to the Planning Department
by MARCH 30, 1994. If not received by that date, it wiU be assumed that you have
no comment and the proposal has your endorsement as submitted.
THANK YOU
COMMENTS: pUi^ cY(sh^\ 3^ctA/oi
PLANS ATTACHED FRM0020 8/92
DATE:
TO:
FROM:
REVIEW AND COMMENT MEM
MARCH 16, 1994 REVISED PLAN •
ENGINEERING DEPARTMENT
GROWTH MANAGEMENT (MEMO ONLY)
POLICE DEPARTMENT - ATTN: J. SASWAY
FIRE DEPARTMENT
BUILDING DEPARTMENT
PARKS AND RECREATION DEPARTMENT
UTILITIES/MAINTENANCE DEPARTMENT'
CARLSBAD ^ WATER DISTRICT
MAR 'on/?
LANDSCAPE PLANCHECK CONSULTANT (/
SCHOOL DISTRKTT
NORTH COUNTY TRANSIT DISTRICT - 311 S. Tremont Street,
Oceanside, CA 92054-3119 ^ i
Always Send Exhibits
Planning Department
REQUEST FOR REVIEW AND COMMENT ON APPLlCATIQNNO. CDP 94-3/RP 93-3
NOTE: PLEASE USE THIS NUMBER ON ALL CORRESPONDENCE CONCERNING THIS
APPUCATION.
PROJECT TITLE:
APPLICANT:
PROPOSAL:
FENCED OFF AREA.
RALPH S EDDIE'S GARDEN PATIO
RALPH F. BURNETTE, JR.
ADDING AN ENCLOSED PATIO, INCLUDING
PROJECT PLANNER: TERRI WOODS
Please review and submit written comments and/or conditions to the Planning Department
by MARCH 30, 1994. If not received by that date, it will be assumed that you have
no comment and the proposal has your endorsement as submitted.
THANK YOU
COMMENTS: