August 11, 1986
Project No. 4851485-02
TO:
ATTENTION:
SUBJECT:
Reference:
Caliber Development, Inc.
4521 Campus Drive, Suite 308
Irvine, California 92715
Mr. Jim Bosler
Observation and Testing of Storm Drain Trench Backfill, Avenida
Encinas, South of Palomar Airport Road, Carlsbad, California
"As-Graded Report, Carlsbad Pacific Center, Palomar Airport Road and
Avenida Encinas, Carlsbad, California," dated April 18, 1986, Project
No. 4851485-02, by Leighton and Associates, Inc.
Introduction
In accordance with a request from Grant General Contractors, Inc. and your
authorization, we have performed the required geotechnical services during the
backfilling of the subject storm drain. This report summarizes our observations
and field and laboratory test results encountered during the backfilling opera-
tions between May and June 1986.
Accompanying Maps, Illustration, and Appendices
Figure 1 - Site Location Map - Page 2
Plate 1 - Density Test Location Map - In Pocket
Appendix A - Summary of Field Density Tests
Appendix B - Laboratory Test Results
Appendix C - Compaction Zones for Trench Backfill
5421 AVENIDA ENCINAS. SUITE C. CARLSBAD. CALIFORNIA 9xX)8 (619) 931-93s
- lR”lNE . WESTLAKE/“ENTURA . DlAMOND BARiWALNUT . SAN BERNARDlNO,R,“ERSlDE . SAN DIEG:
PALM DESERT l S.4NTA CLARITANALENCIA . CAFILSBAD . TEMECllLn,RANCHO CALIFORNIA
-
.-
-
-
-
-
-
-
-
_-
-
-
-
-
-
-
0 2000 4000
.- rcalo
BABE MAP: Aerial Foto-Map Book,
-
-
-
-
-
-
-
-
4851485-02
Project Description and Location
The subject storm drain is associated with the surface drainage of the Carlsbad
Pacific Center One commercial development located south of the southeast corner
of Palomar Airport Road and Avenida Encinas (Figure 1). The storm drain consists
of a 24-inch diameter, reinforced, concrete pipe which drains to the south. The
northern end of the subject storm drain is located approximately 550 feet south
of the intersection of Palomar Airport Road and Avenida Encinas, and extends
southerly for approximately 751 feet. The northern end of the storm drain
connects to the drainage system associated with the Carlsbad Pacific Center One
commercial development, and the southern end of the storm drain terminates at the
intersection with an existing storm drain (see Plate 1).
Storm Drain Trench Excavation and Backfill
Prior to backfilling of the storm drain trench, the trench excavation was
observed by a representative from our firm. The excavation was observed to be
free of loose soils or debris.
The backfilling of the storm drain trench was performed in accordance with
the City of Carlsbad's specifications for trench backfill. These specifications
are provided in Appendix D for your review. The trench was backfilled to within
3 feet of street subgrade elevations with on-site soils which were moisture
conditioned, as needed, to attain near-optimum moisture content, and compacted to
a minimum relative compaction of 90 percent in accordance with ASTM D1557-78.
Within 3 feet of street subgrade elevation, the storm drain trench was backfilled
by compacting on-site soils to a minimum of 95 percent relative compaction (ASTM
D1557-78). Compaction of the fill materials was accomplished with heavy con-
struction equipment and hand-operated tampers.
Gas Line Trench
Due to the relatively close proximity of a 3-inch diameter San Diego Gas and
Electric high pressure line to the subject storm drain trench excavation,
portions of the gas line were relocated. Backfill of the relocated gas line
trench was accomplished by compacting on-site soils to a minimum relative
compaction of 95 percent in accordance with ASTM 01557-78, and in compliance with
the specifications of the City of Carlsbad for trench backfill (Appendix 0).
-3-
LEIGHTON and ASSOCIATES
4851485-02
Field and Laboratory Testing
-.
-
Field density tests and observations were performed during the backfilling of the
trenches. Density tests were performed using the sand-cone method (ASTM
D1556-64), drive-cylinder method (ASTM D2937-71), and nuclear gauge method (ASTM
02922-78). The approximate density test locations are shown on the accompanying
Density Test Location Map, Plate 1. The results of the field density tests are
summarized in Appendix B.
- Representative soil samples were tested for maximum density as determined by ASTM
test method 01557-78. The maximum density test results are presented in
Appendix C.
Conclusions
- Based on our field observations and the results of our field and laboratory test
results, the backfilling of the trenches mentioned in this report were performed
in general compliance with our recommendations and the City of Carlsbad's
requirements. -
-
-
If you have any questions regarding our report, please do not hesitate to contact
this office. We appreciate this opportunity to be of service.
Respectfully submitted,
LEIGHTON AND ASSOCIATES, INC.
Stan Helenschmidt, RCE 36570
Chief Geotechnical Engineer
-
-
-
RLW/SRH/RW/lj
Distribution: (3) Addressee
(3) Grant General Contractors, Inc.
Attention: Mr. Rick Lloyd
-4-
LElGHTON and ASSOCIATES ._._^^^ ^I_--_
SUMMARY OF FIELD CENSIlY TESTS PAGE 1
- PROJECT NW&R : 4841485-02
PRQJECT NM? : CUBER - PACIFIC CENTER
TEST TEST TEST TEST LOCATION SOIL
No DATE OF TYPE
-
-
-
-
-
-
-
-.
-
-
-
-
-
-
-
s1- 05/19/86 so
52’ 05/20/86 SD
53” 05/20/86 SD
S4- 05/20/86 SD
S5- 05/20/86 SO
SC 05121186 SD
S7- 05/21/& SD
SB- 05/22/86 YJ
S9’ 05/22/86 SO
SlO- 05/22&6 SD
Sll- 05/22/86 SD
s12- 05123185 SD
X3- 05/23/86 SD
SW 05/29&j SD
s15- 05/30/86 xl
S16- 05/30/86 So
s17- 05/3o/B6 SD
SW 05/30/86 SD
s19- 05/3o/B6 so
s2u- 06/16&s SD
S21- 06/17/B6 SO
sr 06/18/86 SD
Gl- 06/1B/B6 GM
G2- 06/18/B6 GM
AVENIOA ENCINAS STA 27+0 5
SEE F.D. TEST LOCATION MAP
AVENIDA ENCINAS STA 27+2 5
SEE F.D. TEST LOCATION MAP
AVENIDA ENCINAS STA 28+0 2
SEE F.D. TEST LOCATION MAP
AMNIDA ENCINAS STA 27+9 2
SEE F.D. TEST LOCATION Mb'
AVENIOA ENCINAS STA 28+7 3
SZE F.D. TEST LOCATION MAP
AVENIDA ENCINAS STA 29+3 5 SE F.D. TEST LOCATICN MAP
AMNIDA ENCINAS STA 29+7 5 SE F.D. TEST L0CATIC.N NW'
AVENIDA ENCINAS STA 33+2 5
SEE F.D. TEST LOCATION W
AVENIDA ENCINAS STA 32+3 3
SEE F.D. TEST LOCATION MP
AMNIDA ENCINAS STA 33+5 5
SEE F.D. TEST LOCATION itAP
AVENIDA ENCINAS STA 33+0 3 SEE F.D. TEST LOCATICU K4P
AMNIDA ENCINAS STA 33+0 5 SEE F.D. TEST LOCATION MAP AMNIDA ENCINAS STA 32+7 5 SEE F.D. TEST LOCATION MAP A’iENIDA ENCINAS STA 33+7 7
SEE F.D. TEST LOCATION Mb’
AMNIDA ENCINAS STA 33+5 7 = F.D. TEST LOCATION MAP AMNIDA ENCINAS STA 33+3 7 SEE F.D. TEST LOCATION MAP
AMNIDA ENCINAS STA 33+4 7 SEE F.D. TEST LOCATICN MAP
AMNIDA ENCINAS STA 33+3 5
SEE F.D. TEST LOCATION NW
AMNIDA ENCINAS STA 33+5 5
SEE F.D. TEST LOCATION MAP AMNIDA ENCINAS STA 30+5 3 SEE F.D. TEST LOCATION MbP AMNIDA ENCINAS STA 29+8 2
SEE F.D. TEST LOCATION MAP AKNIDA ENCINAS STA 31+2 3 SEE F.D. EST LOCATION MAP
AVENIDA ENCINAS STA 31+8 3
SEE F.D. TEST LOCATION MAP AVENIDA ENCINAS STA 31+4 3 = F.D. TEST LOCATIcEl MAP
ELEV OR DEPlH
(RET)
-4.5
-1.5
-3.0
-3.0
-1.5
-3.5
-2.0
-5.5
-5.5
-3.5
-1.5
-3.5
-1.5
-5.0
-4.0
-3.0
-3.0
-2.0
-1.5
-4.0
-1.0
-1.0
-2.0
-2.0
DRY CENS(PCF) M3ISllJRf(%) WATIVE IEMNKS
FIELD MAX FIELD OPT COMPACTION
117.9 120.0 13.5 13.0
117.7 120.0 14.2 13.0
105.2 121.5 13.4 11.5
110.7 121.5 16.3 11.5
117.8 123.0 10.4 Il.5
107.9 120.0 16.4 13.0
114.8 120.0 13.5 13.0
110.5 120.0 14.9 13.0
116.4 123.0 12.9 11.5
111.1 120.0 14.9 13.0
116.4 123.0 12.0 11.5
108.7 120.0 19.0 13.0
113.7 120.0 12.3 13.0
127.3 133.5 8.4 9.0
122.3 133.5 9.9 9.0
120.3 133.5 11.0 9.0
122.0 133.5 11.8 9.0
114.0 120.0 15.3 13.0
114.8 120.0 15.0 13.0
118.8 123.0 13.2 11.5
118.3 121.5 14.1 11.5
118.0 123.0 11.4 11.5
120.8 123.0 16.3 11.5
117.8 123.0 15.9 11.5
(%)
98.
98.
87. RETESTED ON TESTNO s4
91. RETEST OF TESTNO s3
96.
90.
96.
92.
95.
93.
95.
91.
95.
95.
92.
90.
91.
95.
96.
97.
97.
96.
98.
96.
-
-
-.
-
-
-
.-
-
-
-
-
-
-
-
-
-
-
SUtWRY OF FIELD CENSITY lESTS PAGE 2
PROJECT NUMBER : 484148502
PROJECT NAM : CALIBER - PACIFIC (ENTER
TEST TEST TEST TEST LOCATION SOIL ELEV OR
No DATE OF
G3- 06/19/& GM
G4- 06119186 GM
65” 06/19/86 GM
G6- 06/19/86 GM
G7- 06/19/86 GM
S23- 06123186 SO
S24- 06/23/86 SO
S25” 06/23/86 SD
l-m DYTH
(W
AMNIDA ENCINAS STA 31+1 1 -2.0 SEE F.D. TEST LOCATION MAP
AMNIDA ENCINAS STA 29+3 1 .O
SEE F.D. TEST LOCATION MAP
AVENIDA ENCINAS STA 29+1 3 .O
SEE F.D. TEST LOCATION MAP
AVENIDA ENUNAS STA 28+8 3 .O SEE F.D. TEST LOCATION MAP
AMNIOA ENCINAS STA 28+3 3 .O
SEE F.D. TEST LOCATION MAP
AMNIDA ENCINAS STA 33+9 2 -1.0
SEE F.D. TEST LOCATION MAP
AMNIDA ENCINAS STA 28+6 2 -1.0 SEE F.D. TEST LOCATION MAP
AKNIDA ENCINAS STA 31+4 2 -1.0 SEE F.D. TEST LOCATION YAP
DRY oENS(pCF) MoISTUkf(%) BLATIM IWARKS
FIELD MAX FIELD OPT COMPACTION
M
120.3 126.5 16.8 10.0 95.
122.3 126.5 13.6 10.0 97.
120.8 123.0 17.1 11.5 93.
121.8 123.0 12.1 11.5 59.
122.5 123.0 10.6 11.5 100.
120.5 121.5 12.4 11.5 99.
118.8 121.5 14.5 11.5 98.
117.3 121.5 14.2 11.5 97.
4851485-02 -
APPENDIX B
LABORATORY TEST RESULTS -
Maximum Density Tests: -
The maximum dry density and optimum moisture content of typical materials were
determined in accordance with ASTM 01557-78 (five layers). The results of these
- tests are presented in Figure B-l.
-
B-i
-
-
-
-
-
-
-
-
-
-
-
-
-
-
SAMPLE SOIL DESCRIPTION
No. 1
No. 2
No. 3
No. 4
No. 5
ri0. 6
No. 7
MAXIMUM DENSITY TEST RESULTS
Brown, silty fine sand (topsoil).
Brown, silty, clayey sand mixed wit
brown clay
Brown, silty sand
Tan, fine to coarse sand (Class II)
Reddish brown, clayey, silty sand
Imported, gray, silty sand (Sand
Equivalent)
Gray, silty, fine- to coarse-graine
sand (Class III)
MAXIMUM OPTIMUM DRY DENSITY MOISTURE (PC?) CONTENT (%I
126.5
121.5
10.0
11.5
123.0
136.0
120.0
-__
133.5
11.5
7.0
13.0
---
9.0
p Proloct N;;41485-02
I CALIBER/CARLSBAO PACIFIC CENTER
L CITY OF CJRLSBAD
1
ENGINEERING DEPARTMENT POLICY
NUMBER:
I
25 SUBJECT: COMPACTION ZONES FOR TRENCH BACKFILL
-
EFFECTZVE: 6/a/65 APPROVED BY:
1 SUPERSEDES: NONE
:I PURPOSE: To establish compaction zones for trench backfill.
1. TRENCH ZONES
a. Bedding, pipe and middle zones shall be 90% relative compaction (see attached drawing).
-I
b. UPPer toni?, (3"'0"), shall be 95% relatffve,compactfon (see atcached drawing).
2. TRENCH TYPE
a. Shall be all types.
3. TRENCH AREAS
a. Shall be al.1 areas.
4. TRENCH TESTING
a. Shall be ASTM D-1556 and O-1557.
-
-
-
-
-
-
NOTE :
/-FINISH SURFACE
l 1. Minimum Relative Compaction
DATE APPROVED CITV OF CARLSBAD OFFICE OF THE CITY ENGINEER
TRENCH BACKFILL
(Compaction Zones) Not to Scale