HomeMy WebLinkAboutCT 03-01; LA COSTA RESORT & SPA- PHASE II; COMPACTION REPORTS 2003- 2005; 2005-03-07Sladden Engineering 6782 Stanton Avenue, Suite A, Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369 114 South California Avenue, Beaumont, CA 92223 (951)845-7743 Fax (951) 951-845-8803 39-725 Garand Lane., Suite G, Palm Desert; CA 92211 (760) 772-3893 Fax (760) 772-3895 March 7, 2005 Project No. 422-5019 05-03-079 KSL Development 2100 Costa Del Mar Road Carlsbad, California 92009 Subject: Compaction Report Project: La Costa Resort and Spa Resort Villas-Phase I, Lot 9 2100 Costa Del Mar Road Carlsbad, California This report summarizes the degree of compaction and recommended bearing values for the reworked on-site soils and compacted fills placed on the site and tested by Sladden,Engineering. The project consisted of removing and recompacting artificial fill and native soils and placing primary structural fill soils to support the proposed villas. Sub-surface soil conditions were SIR mmarized in our Geotechnical Investigation Report dated November 11, 2004, Project No. 444- 3161, Report No. 03-10-183. The proposed construction area was first stripped of surface vegetation and debris and. this material was hauled from the site. .. Within the proposed building area and at least 5.0 foot wide perimeter strip beyond the building walls, all artificial fill and some native soils were removed. Removals extended to a depth of at least 2 feet below bottom of footings. The exposed soils Were then scarified to a depth of 6 inches, brought to near optimum moisture content arid compacted to. at least 90% of maximum dry density as determined by test method ASTM D 1557-90. The excavated soils, generally silty sands, were cleaned of deleterious material and then replaced in 6 inch layers,, brought to near optimum moisture content and compacted. Removals and recompaction resulted in a maximum fill depth of approximately 4.5 feet. Compaction was obtained using a Caterpillar 953 track loader. . Field tests and inspections were performed during the work. The test results indicated compliance with the project specifications at the tested locations but are no guarantee or warranty of the contractor's work. Field Tests: In-place density tests were performed at the approximate locations indicated on the attached site plan using a calibrated sand cone in' accordance with test method ASTM D 1556-90. Field moisture tests determinations were made at the time of each test. Testing indicates that the required compaction of 90% has been attained in the areas tested. , ' March 22, 2005 ., '(2) , Project No. 422-5019 05-03-079 Laboratory Tests: The moisture-density relationships for the tested soils were determined in accordance with test method ASTMD 1557-91. Recommendations: Footings should extend at least 18 inches beneath lowest adjacent grade. Isolated square or rectangiilar footings at least 2 feet square may be designed using an allowable bearing pressure of 2500 pounds per square foot. Continuous footings at least 12 inches wide may be designed using an allowable baring value of 2000 pounds per square foot. The allowable bearing pressures may be increased by 200 psf for each additional one foot of width and 250 psf for each additional 6 inches of depth, if desired. The maximum allowable bearing S pressure should be 3000 psf. • S The allowable bearing pressure are for dead' and . frequently applied live loads and may be increased by 1/3 to resist wind, seismic or other transient loading. Drainage form the building ' area should be rapid and complete'. S ' • S All, footing and utility trench' backfill should be compacted to 90% of maximum dry. density. Respectfully submitted, ' S • ' SLADDEN ENGINEERING •. '',' S ' Z' No.C4 389 2010 Brett L. Anders n xp 9-3 010 Principal Engineer tp ;A CIVI OF CAQ~ Copies: 6 —K SL Developme Sladden Engineering Project No. 422-5019 05-03-079 Test Tested Moist Cont Fid Dry Den Max Dry Den Percent No. Date Location Depth Percent Lbs/Cu Ft Lbs/Cu Ft Max 1 2-9-05 Building Area -5.0 13.5 108 118 91 2 2-9-05 ' Building Area -3.0 . 19.5 112 . '. 121 92 3 2-9-05 Building Area -2.0 15.1 : 113 . 121 93 4 2-9-05 . BuildmgArea -1.0 '15.5 . 111. '121 . 92 5 . -1-05 Building Area ..-7.0 16.0 ' ' 110 121 90 6 , 3-1-05 Building Area -5.0' 19.5 107 118 ' 90 7 3-2-05 Building Area -3.0 13.4 108 ' ' 118 . 91 8 3-2-05 Building Area -2.0 120 , 108 , 118 92 9 3-3-05 Building Area 1.0 ' 19.5' , 105 121 , 87* 10 3-7-05 Retest #9 ' -1.0 15.8 110 ' 121 ' 91** '11 .3-7-05. ' Building Area -5.0 15.9 . 111 . . 121 . 92 12 3-8-05 Building Area -3.0 19.0, 103 . ' 118 .87* 13 3-11-05 Retest #13 -3.0 , 15.0 , ' 111 ' 121 ' 91 14 3-11-05 Building Area ' -2.0 ' 19.3 '' 112 121 92 15 ' 3-11-05 BuildingArea '4.0.. . 13.5 112 , , ' 121 , , 93 16 3-12-05 Building Area . S.G. 14.0 , '. 111.. ' ' 121 , 92, 17 . 3-12-05 'Building Area S.G. 12.5. 113 , 121 ' 93 18 , 3-17-05 Keyway -11.0 '14.1 111 ' 118 . '94 19 3-17-05 Keyway. -9.0' 11.9 107 . ' ' ' 118 , 92 20 3-17-05 Keyway . ' -7.0 .13.0 . , 108 , . ' 118 ' 92 21 ' 3-17-05 Keyway ' , -6.0 12.9 .' 112 ' ' 121 93 22. 348-05 Keyway " -5.0. ' 13.5 112 121 ' 93 ' 23 3-18-05' Keyway .. -5.0 14.0 111' ,. 121 ' , 91 24 318-05 Keyway -3.0 " 115 ......114 ' ' . 118 97 Sladden Engineering March 22, 2005 . (4) Project No. 422-501 05-03-079 Test Tested Moist Coñt Fld DryDen Max Dry Den Percent No. Date Location Depth Percent Lbs/Cu Ft • Lbs/Cu Ft Max 25 3-18-05 Keyway . -3.0 146 113 121 93 26 3-18-05 Keyway -10 139 113 121 93 27 3-18-05 Keyway -1.0 12.4 113 . .121 93 *Fàiled Test . . . "Retested . . . . Maximum Dry Densities- 118 Lbs/Cu Ft; Optimum Moistures- 11.7% 121 . 12.4% Silty Sand trace of Clay (SM) . . . . Silty Sand (SM) . . . . . Sladden Engineering c.çO.OI *Sladde'n Engineering 6782 Stanton Ave., Suite A, Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369 39-725 Garand Ln., Suite G, Palm Desert, CA 92211 (760) 772-3893 Fax (760) 772-3895 April 9, 2003 KSL Development 507905 Avenida Bermuda La Quinta, California 92253 Subject: Compaction Report PrOject: New Ballroom Building La Costa Resort and Spa 2100 Costa Del Mar Road Carlsbad, California - PrOject No. 422-2178 03-04-043 Reference:• Compaction Report prepared by Sladden Engineering dated June 28, 2002; Project No.544-2063, Report No. 02-06-361 This report summarizes the degree of compaction and recommended bearing values for the .reworked- on-§ite soils and compacted fills placed on the site and tested by Sladden Engineering. The project consisted of removing and recompacting artificial fill and native soil and placing primary structural fill soils to support the proposed ballroom building. Sub-surface soil conditions were summarized in our Geotechnical Investigation; Project No. 544-2063 dated June 28, 2002, Report No. 02-06-361. . The proposed construction area was first stripped of surface vegetation and debris and this material was removed from the site. Within the proposed building area and at least 10 foot wide perimeter strip beyond the building walls, all artificial fill and at least the upper 2 feet of on-site soil was removed. The exposed native soils comprised of silty sand and clayey sands were inspected and approved prior to placing fill by a representative of Sladden Engineering then scarified to a depth of 6 inches, brought to near optimum moisture content and compacted to 90% Of maximum dry density as determined by test method ASTM D 1557-91. The excavated soils, generally silty and clayey sands, were cleaned of deleterious material and then replaced in 6 inch layers, brought to near optimum moisture content and compacted. Removals and recompaction resulted in a maximum fill depth' of approximately 15 feet. Compaction was obtained using a 824 dozer, 623 F & 513 C Caterpillar scraper, D-6 Dozer, 345 B excavator and a skip loader, 12 G motor grader. There is an isolated area approximately 25' foot in diameter around an. existing water line valve to be backfilled and compacted at a later day. The existing 6" and 12" A.C.P. water lines were left in place in the southern portion of the new building pad and will be abandoned at later date. Field tests and' inspections were performed during the work. The test results indicated compliance with the project specifications at the tested locations but are no guarantee or warranty of the contractor's work. April 9, 2003 (2) Project No. 422-'2178 03-04-043 Field Tests: 1nplace density tests were performed at the approximate locations indicated on the attached site plan using a calibrated sand cone in accordance with test method ASTM D 1556-90. Laboratory Tests: The moisturedensity relationships for the tested soils were determined in accordance with test method ASTM D 1557-91. Recommendations: Footing shOuld extend at least 18 inches beneath lowest adjacent grade. Isolated square or rectangular footing at least 2 feet square may be designed using an allowable bearing value of 2500 pounds per square foot. Continuous footing at least 12 inches wide may be designed using an allowable bearing value of 2000 pounds per square foot. The allowable bearing pressures may be increased by 200 psf for each additional one foot of width and 250 psf for each additional 6 inches of depth. The maximum allowable bearing pressure should be 3500 psf. The allowable bearing' pressures are for dead and frequently applied live loads and may by increased by 1/3 to resist wind, seismic or other transient loading. Care should be taken to see that bearing or subgrade soils are not allowed to become saturated form thepounding of rainwater or irrigation. Drainage from the building area should be rapid and complete. All wall, footing and utility trench backfill should be compacted to 90% of maximum dry density. Respectfully submitted, SLADDEN ENGINEERING roc45389 Ecp 9-30-2010' Brett L. Anderson IV Principal Engineer Copies 6- KSL Development Sladden Engineering Project No. 422-2178 04-03-043 Test . Tested Moist Cont Fid Dry Den Max Dry Den Percent No. Date Location Depth Percent Lbs/Cu Ft Lbs/Cu Ft Max Ballroom . 1 4-2-03 Building Pad , 43.00 12.4 117 130 . .90 2.' 4-2-03 Building Pad. 44.00 , 12.4 117 130 90 3 4-3-03 Building Pad 46.00 13.6 123 130 95 4 4-3-03 Building.Pad 48.00 13.6' 122 130 94 5 4-3-03 Building Pad 47.00 12.4.. 123 , 130 , 95 6 4-3-03 Building Pad 49.00 17.6 111 124 90 7 4-3-03 Building Pad 50.00 ' 19.0 112 , 124 . 90 8 4-3-03 Building Pad 45.00 8.7 • 104 • 112 ' 93 9 4-4-03 Building Pad ' .49.50 • 14.9 115, 124 • 93 10 4-4-03 Building Pad 51.00 '13.6 : 119 . 130 92 11 4-4-03 Building Pad , 52.00 12.4 117 130 90 12 4-403. Building Pad '51.00 ' 13.6 119 . 124 • ' 96- 13 4-4-03 Building Pad 52.00 ' 13.6 ' 116 124 ' 94 14 4-5-03 Building Pad 49.00 • 14.9 122 • ' 130 94 15. 4-5-03 Building Pad 52.00 • 11.1 112 124. ' , 90 16 4-5-03 Building Pad 53.00 • 14.9 117 124 • • 94 17 4-5-03 Building Pad 53.50 14.9 117 • 124 94 18 4-5-03 Building Pad 53.00 17.6 , 117 . 124 94 19 4-5-03 Building Pad 46.00 12.4 125 130 • 96 20 4-5-03 'Building Pad • 52.00 12.4 117 • 127 '92 21' 4-5-03 Building Pad 53.00 12.4: 119 127 94 • • 22 4-5-03 Building Pad 48.00 12.4 124 , ' 130 95 23 4-5-03 Building Pad '47.00. 12.4 ,. 118 ' 127 93 Sladden Engineering (4) ' Project No. 422-2178 03-04-043 Test Tested Moist Cont FId Dry Den Max Dry Den Percent No. Date '• Location , Depth Percent Lbs/Cu Ft Lbs/Cu Ft Max 24 4-7-03 ' 'Building Pad 45.00 11.1 . 109 ' 112 25 4-7-03 Building Pad 49.00 9.9 115 ' 128 26 4-7-03 Building Pad . 54.00 ' 12.4 110 121 27 4-7-03 Building Pad 54.00 14,9 120 . 127 .28 4-7-03 Building Pad 51.00 . 12.4 110. . 121 29 4-7-03 '. Building Pad 52.00 11.1 112' 121 30 4-8-03 Building Pad ' 55.00 9.9 120 129 31 4-8-03 Building Pad 55.00 11.1. , 122 ' 130 32 4-8-03 Building Pad 55.00 11.1 116 127 33 4-8703 Building Pad . 55.0,0 11.1 114 . 127 34,4-8-03 Building Pad '55.00 ' 12.4 114 ' 127 35' 4-8-03 'Building Pad ' 52.00 ' ' 99 , . 107 . , 112' Maximum Dry Densities- 112 Lbs/Cu Ft; Optimum Moistures- . 11.1% 121 127 128 ' " ' ' " ' . 95% 129 ' ".. . : 80% 130 " 11.7% Silty Sand Silty Sand Trace of Clay. '.Silty Sand Trace ofClay Clay Sand . Silty Sand Trace of Gravel , Gravely Sandy Clay Sladden Engineering 97 90 91 94. 91 93 93: 94 91 90 90 96 LOCATION PLAN FA \t) 29 028 oT- - - - • _ Approximate Location Density Test - ---L/Mm QF&Rt File Number: t 22 -2J78 C' L?N • •• NOR '-3 Slodden Engineering Sladden Engineering 6782 Stanton Ave., Suite A, Buena Park, CA 90621 (714) 523-0952 Fax (714) 523-1369 39-725 Garand Ln. Suite G, Palm Desert, CA 92211 (760) 772-3893 Fax (760) 772-3895 January 8, 2003 Project No. 422-2178 03-01002 KSL Development 50-905 Avenida Bermuda La Quinta, California 92253 Subject: Compaction Report Project: La Costa Resort Spa Building S 2100 Costa Del Mar Road Carlsbad, California This report summarizes the degree of compaction and recommended bearing values for the reworked on-site soils and compacted fills placed oil the site and tested by Sladden Engineering. The project consisted of removing and recompacting artificial fill and native soil fill soils to support the proposed industrial building. Sub-surface soil conditions were summarized in our Geotechn ical Investigation; dated June 28, 2002, Project N6.. 544-2063, Report No. 02-06-361. The proposed construction area was first stripped of surface vegetation,ánd pavement and this material was removed from the site. Within the proposed building area and at least 5 foot beyond the building walls, all artificial fill and at least the upper 2 feet of native soil was removed. The exposed native soils comprised of silty sands were inspected and approved by a representative of Sadden Engineering theii scarified to a depth of 6 inches, brought to near optimum moisture content and compacted to a minimum of 90% of maximum dry density as determined by test method ASTM D 1557-91. The excavated soils, generally silty sands, were cleaned of deleterious material and then replaced in 6 inch layers, brought to near optimum moisture content and compacted. Removals and recompaction resulted in a maximum fill depth of approximately 8-9 feet. Compaction was obtained using a track dozer, grader, wheel loader, scraper and roller. Field tests and inspectibns were performed during the work. The test results indicated compliance with the project specifications at the tested locations but are no guarantee or warranty of the contractor's work. . Field Tests: In-place density tests were performed at the approximate locations indicated on the attached site plan using a calibrated sand cone in accordance with test method ASTM D 1556-90. January 8,2003 . (2) . Project No. 422-2178 03-0.1-002 Laboratory Tests: The moisture-density relationships for the tested soils were determined in accordance with test method ASTM D 1557-91. An expansion index test was performed on a sample of the imported soil in accordance with •UBC Standard No. 18-2. The test showed an E.I. of 29 and tested material has.a very low expansion potential. . . Recommendations: Footing should extend at least 18 inches beneath lowest adjacent grade. Isolated square or rectangular footing at least 2 feet square may be designed using an allowable bearing value of 2500 pounds per square foot. Continuous footing at least 12 inches wide may be designed using an allowable bearing value of 2000. pounds per square foot. The allowable bearing pressures may be increased by 200 psf for each additionalone foot of width and 250 psf for each additional 6 inches of depth. The maximum allowable bearing pressure should be 3500 psf. . . The allowable bearing pressures are for dead and frequently applied live loads and may by increased by 1/3 to resist wind, seismic or other transient loading. Care should be taken to see that bearing or subgrade soils are not allowed to become saturated form the pounding of rainwater or irrigation. Drainage from the building area should be rapid and complete. All wall, footing and utility trench backfill should be compacted to 90% of maximum dry density. Respectfully submitted, . SLADDEN ENGINFERING .. . . . 'H .. Brett'L.AndebnL' £( Principal Engineer No.c 4.4 389 Exp. 9-30-201 CIVIL OF C Copies: 6- KSL Development Sladden Engineering January 8, 2.003 (3)' Project No. 422-2178. 03-01-002 Test Tested Moist Cont FId Dry Den Max Dry Den Percent No. Date Location Depth Percent Lbs/Cu Ft Lbs/Cu Ft Max I 12-19-02 Spa Bldg. Pad 49.0 .• 13.4 112 121 93 2 12-19-02 Spa Bldg. Pad 49.5 11.0 117' 121 97 3 12-19-02 Spa Bldg. Pad 51.0 . 8.1 118 121 98 4 12-19-02 Spa Bldg. Pad 51.0 8.3 115 121 95 5 12-26-02 Spa Bldg. Pad 52.5 16.3 119 128 . 93 6 .12-26-02 Spa Bldg. Pad 51.0 14.9 113 121 93 7 12-27-02 Spa Bldg. Pad ' 53.5 ' . 12.4 111 121 92. 8 12-27-02 'Spa Bldg. Pad 50.5 9.9 106 ,• 115 92 9 12-27-02 Spa Bldg. Pad 52.0 '11.1 112 , . 118 ' 95 10 12-30-02 Spa Bldg. Pad 50.0 12.4 112' 118 95 II 12-30-02 Spa Bldg. Pad 53.0 12.4 ' 112 118 , . .95 12 .12-30-02 Spa Bldg. Pad 52.0 13.6. " 110, '' 118 93 .13 12- - 30-0j Spa Bldg. Pad 53.5 12.4 109 . 118 92 14 1-2-03' Spa Bldg. Pad 54.0 12.4 , 117 118 . 99 15 1-2-03 ' Spa Bldg. Pad 54.1 , 11.1" 114 . . ' 118 96 16 1-2-03 Spa Bldg. Pad 54.1 , . 11.1 117 118 99 17 1-2-03, . Spa Bldg. Pad 51.5 9.9 113 118 96 18 1-2-03 Spa Bldg. Pad 50:5 11.1 ' 113 ' . 118 ' , 96 19 1-2-02 Spa Bldg. Pad , 53.0 9.9 ,111 118 ' 94 20 1-2-02 Spa Bldg. Pad 50.5 9.9 . . 106 115 90 21 1-3-03 Spa,Bldg. Pad 52.0 ' 12.4 , 117 121 . 97 22 1-3-03 Spa Bldg. Pad 52.0 8.7 , 123 129 95 23 1-6-03 Spa Bldg Pad PG. ' 8.7 ' 1,12 118' 95 Sladden Engineering / (4) Project No. 422-2178 03-01-002 Test TestedT Moist Cont Fid Dry Den Max Dry Den Percent No. Date Location Depth Percent Lbs/Cu Ft Lbs/Cu Ft Max 24 1-6-03 Spa Bldg. Pad P.G. 7.5 120 129 • 93 Maximum Dry Densities- • 115 Lbs/Cu Ft; Optimum Moisture- 11.0% (1) 1 18 " 11 .5% (2) 121 " 101% (3) 128 " 9.5% (4) 129 . 8.0%. (5) . •• (1) Silty Sand • . . (2) Silty Sand (Import) (3) Silty Sand Trace ofClay (4) Clay Sand • • •. • • • (5) Silty Sand Trace of.Gravel • • • Skidden Engineering