Loading...
HomeMy WebLinkAboutCT 03-02; CARLSBAD RANCH PA 5; SOILS COMPACTION REPORT; 2010-05-20OFES. No.5721? - Exp. 1v31/I)) Geotechnica! Engineering Construction Inspection Materials Testing Environmental May 20,2010 Grand Pacific Carlsbad, LP. . . Project No. 1916-A07 5900 Pasteur Court, Suite 200 Log No. 10-455 Carlsbad, CA 92008 . Attention: Mr. Bruce Zelenka . Subject: ' Soils Compaction Report Project: Villa 51 - Building Pad - Carlsbad Grand Pacific Resort . Carlsbad, CA . . CT 03-02, Drawing No. 428-9A Dear Mr. Zelenka: In accordance with your request and authorizatior, we have completed our observation and testing during the grading of the building pad for Villa 51. The results of our findings, with our test results and recommendations are to be found in the accompanying report. Based oi the results of our observation and testing between May 13 and 19, 2010, we certify that the described earthwork has been completed in general accordance with the intentions and recommendations 1of the -geotechnical reports by Leighton & Associates, Inc. (see references) and the approved grading plans. Should you have any 4uestions regarding this report, please do not hesitate to contact our office. Respectfully submitted, . . MTGL Inc. , Edyuard,o Dizon, RCE Senior Engineer Office Locations Orange County Corporate Branch: 2992 E. La Palma Avenue Suite A Anaheim, CA 92806 Tel: 714.632.2999. Fax: 714.632.2974 San Diego Imperial County 6295 Ferris Square Suite C San Diego, CA 92121 Tel: 858.537.3999 Fax: 858.537.3990 Inland Empire 14467 Meridian Parkway Building 2A Riverside, CA 92518 Tel: 951.653.4999 Fax: 951.653.4666 Indio 44917 Golf Center Parkway Suite 1 India, CA 92201 Tel: 760.342.4677 Fax: 760.342.4525 OClLAllnland Empire Dispatch 800.491.2990 San Diego Dispatch 888.844.5060 www.mtglinc.com TABLE OF CONTENTS INTRODUCTION ........... ......... ........................................................................................................ .1 GEOTECHNICAL REPORT .........................................................................................................1 SITEDESCRIPTION ........................................................................... ............................................. 1 GRADING AND EARTHWORK ......................... ........................... .1 GEOTECHNICAL TESTING ................................. . .......................................................................... 2 CONCLUSIONS .............................. ........................ ........................................................................ 2 RECOMMENDATIONS................................................................................................................. 2 LIMITATIONS................................................................................................................................3 References • • . • Figures 1 - Field Density Test Loëation Plan • • • . • Table 1 - Laboratory Compaction Test Results . . • • - Table 2 - Field Density Test Results • Carlsbad Grand Pacific Resort Villa 51 Project No 1916-A07 Carlsbad CA Log No 10-455 INTRODUCTION This report presents the results of our observation and testing during the grading of the building pad for Villa 51 at Carlsbad Grand Pacific Resort in Carlsbad, California.This report covers testing services performed between May 13 and 19, 2010 GEOTECHNICAL REPORT Geotechnical information pertaining to the site was presented in the geotechnical and grading reports by Leighton and Associates, Inc. dated April 11, 2005, August 2, 2006 and September 11, 2007. Our function during grading was limited to observation and testing of earthwork for the building pad of Villa 51 between May 13 and 19,2010.* SITE DESCRIPTION Prior to this grading work, the project site consists of a sheet graded lot, which is relatively level The site is bounded by ascending graded slope to the north, by existing villa to the east and by descending slope to the south and west Generally, the project site was essentially in the same condition as reported in the reference as-graded geotechnical report, dated August 2,2006 and September 11, 2007. GRADING AND EARTHWORK Grading of the building pad consisted of the removal and recompaction of the existing soil The existing soil over the entire building pad was removed and recompacted such that there is at least 5 feet of compacted fill below finish pad elevation Exposed subgrade to receive fill was scarified, moisture conditioned and compacted The horizontal hunts of the earthwork grading for the building pad extended laterally to at least 5 feet beyond the building footprint Engineered fill soils used consisted of the existing on-site soils suitable for recompaction per the recommendations of the reference geotechnical reports Fill soils were moisture conditioned to within optimum moisture content Fill soils were placed in lifts and compacted with heavy compaction equipment 4 - - - .4. . . - . - Carlsbad Grand Pacific Resort Villa 51 Project No. 1916-AO7 Carlsbad, CA . . . Log No. 10-455 W . GEOTECHNICAL TESTING • .• -• . : - - . * Field Tests . . Test procedures based upon ASTM D6938 was used 'for fiela density testing of the soil density and moisture content.- Field density testing was at rañdom loctións and elevations. The approximate extent of the, compacted fill and locatiobklevatibn of the performed density tests described in this report are indicated on Figure 1. Fill soils were compacted to a minimum relative compaction of 90 'perceni based on Test Method ASTM D1557, withcthe upper 12 inches finish subgrade compacted to at least 95 pedent relative compaction. ' • • •. Laboratory Tests The maximum density and optimum ,moisture 'content of representative samples Of the' fill soils were determined in the laboratory inccordance with ASTM D1557 test procedures. The results of the -' laboratory maximum density tests are presented in Table 1. . . 4 ..-• ''••. . CONCLUSIONS Based upon the information presented in the referenôe geotechnical reports and on the observation and testing conducted by MTGL, Inc. as described herein, we certify that the grading of the building pad for Villa 51 has been completed in gederal accordance with the intentions and recommendations of the reference geotechnical reports and approved grading plahs: It is our opinion that the site is suitable for the intended use provided the recommendations presented in this report ànd'the reference geotechnical reports are considered for final planning and structural design, and implemented dunng construction RECOMMENDATIONS '- • ' -' . - -- • -- 4. .• . . - . * The recommendations presented in the reference geotechnical reports are considered to remain in ., effect; except where superseded by addendum 'recommendations or as specifically recommended . - • herein. The reference geotechnical reports should be considered a part of the project plans and' specifications. ,. :. ' - • I • - • -' • Carlsbad Grand Pacific Resort Villa 51 Project No. 1916-A07 Carlsbad, CA Log No. 10-455 Continuous and spread footings are suitable for support of the proposed. structure. It is our opinion that the recommendations and,.soil criteria for soil .bearing values for foundations and slab-on-grade contained in the reference geotechnical reports are applicable 'arid shall be implemented in the design of the proposed structure LIMITATIONS This report has been prepared in accordance with generally accepted geotechnical practices. Our work is considered to be in accordance with the usual standards of the profession and with local practice. No other warranty is expressed or implied as to the professional advice or data included in this report. It should be recognized that that our work does not constitute a guarantee that the grading contractor has performed his work in accordance with the project specifications. In addition, no representations are made as td the quality or extentofmaterials not observed, for any subsequent change to the site, or failure of others to properly repair damages by the uncontrolled actions 4of water. . 'S • • . . 5 S. . ,. . .5 • S.- S • • . p REFERENCES .1. Leighton and Associates, Inc., 2005, Geotechnical Investigation, Proposed 53-Acre Resort. Development - Phase 1, Carlsbad Ranch, Planning Area No 5, iCarlsbad, CA, Project No 040575-003, dated April 11, 2005 2 Leighton and Associates, Inc,', 2006, As-Graded Geotechrncal Report of Rough and Fine Grading, Hotel One, Resort and Conference Facilities, Sales Building, and Villas 53 Through 56 Lots 10, 11 and A Portion of Lot 1, Grand Pacific Carlsbad, Carlsbad, California Project No 040575-005, dated August 2, 2006 3 Leighton and Associates, Inc , 2007, Grading Plan Review and Supplemental Letter, Carlsbad Planning Area 5, Villas 50 through 52, Carlsbad, California, Project No 040575-005, dated September 11, 2007 3 Excel Engineering, Grading and Erosion Control Plans for Carlsbad Ranch, Planning Area No 5, Resort Site - Villas 50 - 52, Project No CT 03-02, Drawing No 428-9D, Sheets 1 tO 8. .4;. MTGL, Inc, 2010, Change of Geotechnical Consultant, Carlsbad Ranch, Villas 50 thru 52, Project No 1916-A07, Log No 10-441, dated April 23, 2010 I.. I /. 030 1! III Li 20, / tgàO'2 033 .6 "a14 ii9a'o J•• •.f..jjJ 47j4 51 •16 1r8 I ' •29 -r°5---_._ •4 .32 • L. -- . •1•-• -- -10 r -- - .23QSZi c - --.- r -. .-r------ - - .. . . DM 428r.-- L EGEND .33 Approximate Location of Field Density Test -'—'A pproximate Limits of Grading FIELD DENSITY TEST PLAN CARLSBAD GRAND PACIFIC RESORT Project No. . 1916-A07 Date: - MAY 2010 FIGURE 1 * Table 2 Field Density Test Results r Test No. Date Location Depth! Elev. (Feet) Moisture Content (%) Dry Density (pcf) Curve No. Relative Comp. % . Test Type Remarks 1 5/13/10 Villa 51 191 15.4 100.5 146 91 NU 2 5/13/10 Villa 51 191 16.6 100.4 146 91 NU 3 5/13/10 Villa 51 191 15.1 100.9 146 92 NU '4 5/13/10 Villa 51 192 14.6 108.9 147 92 MU 5/13/10 Villa 51. 192 16.7 1020 .146 93 NU 6 5/13/10 Villa 51 193 17.3 102.4 146 93 NU 7 5/13/10 Villa 51 193 13.4 99.3 146 90 NU 8 5/13/10 Villa 51 193 16.6 103.3 146 94 NU 9 5/13/10 Villa 51 194 14.2 100.7 146 92 NU 10 5/13/10 Villa51 194 13.9 104.5 146 95 NU 11 5/13/10 Villa 51 191 16.5 103.8 146 94 MU 12 5/13/10 Villa 51 . 191 16.7 . 99.2 146 90 MU 13 5/13/10 Villa 51 192 1 13.0 102.8 146 93 NU 14 5/14/10 1 Villa 51 195 1 174 1034 146 94 NT! 15 5/14/10 Villa 51 195 14.6 105.4 146 96 MU .16 5/14/10 Villa 51 193 16.7 99.6 146 91 MU 11 /14/1(J Vi1a.51 193 13.3 113.2 147 95. NU 18 5/14/10 Villa 51 194 15.9 99.2 146 90 MU 19 5/14/10 Villa 51 191 14.6 99.2 146 90 MU 20 5/14/10 Villa 51 192 14.0 106.5 146 97 NU 21 5/14/10 Villa 51 195 1 10.9 108.8 147 91 NU 22 5/14/10 Villa 51 195 13.5 99.8 146 91 NU 23 5/14/10 Villa 51 191 17.3 101.3 146 92 NU 24 5/14/10 Villa 51 192 12.4 109.1 147 92 MU 25 5/14/10 Villa 51 • 193 12.9 113.7 147 96 MU. 26 5/17/10 Villa 51 194 14.8 111.4 147 94 MU 27 5/17/10 Villa 51 195 10.8. 109.5 147 92 MU 28 5/17/10 Villa 51 195 14.8 105.8 146 96 MU 29 5/18/10 Villa 51 FSG 13.3 113.6 147 . 96 NU 30 5/18/10 Villa 51 FSG 14.4 115.6 . 147 97 NU 31 5/18/10 Villa 51 FSG 11.6 114.5 147 96 NU • 32 5/18/10 Villa 51 FSG 11.6 116.8 147 98 • MU 33 5/18/10 Villa 51 FSG - 10.4 113.9 1 147 • 96 • MU