HomeMy WebLinkAboutCT 05-03; LINCOLN & OAK MIXED USE; GEOTECHNICAL OBSERVATION & COMPACTION TEST;I
H / f---- V/\ \\-J
I ENGINEERING AND
ENVIRONMENTAL
4373 Viewridge Avenue
Suite B
San Diego, CA 92123
858.292.7575 I Fax 858.292.7570
www.usanova.com
Mr. Russell Bennett January 24, 2012
Lincoln & Oak Mixed Use Project No. 10125-1011071.000
I
Carlsbad, California
Subject: Summary of Geotechnical Observation and Compaction Test Results
I
Lincoln & Oak Mixed Use
3112 Lincoln Street
Carlsbad, California
I Permit No. GR110011, Drawing No. 451-7/7A
Gentlemen:
In accordance with your request, NOVA Engineering and Environmental, LLC's (NOVA) has provided
geotechnical observation and compaction testing services during site grading for the Lincoln & Oak
Mixed Use project located at 3112 Lincoln Street in the City of Carlsbad, California. The scope of our
services reported herein includes the following:
Observation of earthwork operations
Compaction testing of fill during grading
I • Laboratory testing of fill materials to evaluate relative compaction
I
. Preparation of a Field Density Test Location Plan
Preparation of this final report
I PROJECT DESCRIPTION
The Lincoln & Oak Mixed Use project consists of a two- to three-story retail and residential building
development. The project site is bounded by Lincoln Street to the west, Oak Avenue to the north
I
and existing driveways for residential and retail buildings to the east and south, respectively.
GEOLOGIC CONDITIONS
The geologic units encountered during grading at the site included artificial fill and Terrace Deposit
materials. As encountered, the fill materials consisted of brown silty sand and the Terrace Deposits
I consisted of reddish brown, friable silty sandstone. In addition, a vertical pit with an approximate
diameter of five feet and an empty brick-lined tank were encountered during grading at the south-
Offering services nationwide:
Environmental Consulting and Remediation - Geotechnical Engineering - Construction Materials Testing and Inspection Services
Facility Engineering - Building Envelope Consulting - Loss Prevention - Municipal Support/Outsourcing
Code Compliance - Construction Defect Mitigation TM - Private Provider TM
Lincoln & Oak Mixed Use January 24, 2012
Carlsbad, California Project No. 10125-1011071.000
west area of the project. Undocumented fill and debris in this area were completely removed and
replaced with two-sack sand/cement slurry.
SUMMARY OF EARTHWORK OPERATIONS AND SHORING INSTALLATION
Based on our observations, the potentially compressible soils consisting of undocumented fills were
completely removed during grading. Preparation of the soils exposed at the bottom of the remov-
als for fill placement consisted of scarifying to a depth of 6 inches, moisture conditioning, and com-
compacting the soils to 95 percent relative compaction as evaluated by ASTM D 1557. Stockpiled fill
soils derived from on-site excavations were processed, moisture conditioned, and placed in lifts ap-
proximately 6 to 8 inches in loose thickness and compacted. The contractor used dozers to spread
the materials and a loader and vibratory roller to compact the soils placed as fill. Test results indi-
cate the areas tested were compacted to a relative compaction of 95 percent as evaluated by ASTM
D 1557. The approximate locations of the field density tests are shown on the attached Figure 1,
Field Density Test Location Plan. Observation and testing services performed during grading as re-
ported herein were provided by NOVA during the period of November 10 through November 22,
2011.
LABORATORY TESTING
Laboratory determination of maximum dry density and optimum moisture content for
representative samples of on-site soils placed as compacted fill were performed in accordance with
I ASTM Test Method D 1557. Laboratory and field testing results developed during grading are sum-
marized in the text of this report and in Tables I and II of this report. The expansive potential of the
I fill materials was evaluated in general accordance with ASTM D4829 and the results are presented
in Table 1.
TABLE 1
I LABORATORY EXPANSION INDEX TEST RESULTS
I Sample Location
Building 2 - Unit 2
Expansion Index Expansion Potential
3 Very Low
Corrosivity testing was performed on a representative sample of the on-site soils to evaluate pH
I and electrical resistivity, as well as soluble chloride and sulfate contents. The pH and electrical resis-
tivity tests were performed in accordance with California Test Method 643 and the sulfate and
I
chloride tests were performed in accordance with California Test Methods 417 and 422, respective-
ly. These laboratory test results are presented in Table 2.
I S
2
Lincoln & Oak Mixed Use January 24, 2012
Carlsbad, California Project No. 10125-1011071.000
TABLE 2
LABORATORY CORROSIVITY TEST RESULTS
Sample Location pH Resistivity Water-Soluble Water-Soluble
(ohm-cm) Sulfate (ppm) Chloride (ppm)
Building 2 - Unit 2 7.2 3600 18 43
Caltrans Corrosion Guidelines (2003) identify a site as being corrosive if the tested soils have more
than 500 ppm chlorides, more than 2,000 ppm sulfates, or a pH of 5.5 or less. According to the
results of our laboratory testing, the site is not considered to have a corrosive potential based on
Caltrans criteria. A corrosion engineer may be consulted for additional recommendations.
CONCLUSIONS AND RECOMMENDATIONS
Cuts and fills covered by this report have been completed under NOVA's testing and observation.
NOVA certifies that the soil engineering and engineering geologic aspects of the grading are in com-
pliance with the project geotechnical reports (Geosoils, 2004, 2010) and grading plans, Drawing No.
451-7A prepared by Conway & Associates, Inc. (2011).
It is anticipated that building foundations will be underlain by compacted fill, formational materials,
or sand-cement slurry extending to formational materials. Continuous footings should have mini-
mum width and depth of 12 inches and isolated footings should have minimum width and depth of
24 inches. Shallow footings may be designed using an allowable bearing capacity of 1,500 pounds
per square foot (psf) with an increase of 300 psf per additional foot of depth to a maximum value of
2,500 psf. These allowable bearing capacities may be increased by one-third when considering loads
of short duration such as wind or seismic forces. Footings should be reinforced in accordance with
the recommendations of the project structural engineer
LIMITATIONS
This report presents information and data relative to the grading of the subject site. Representa-
tive(s) of this firm conducted periodic tests and made observations during the progress of the
construction in an effort to evaluate whether compliance with the project drawings, specifications
and applicable Building Code was being obtained. The presence of our personnel during the work
progress did not involve any direct supervision of the contractor or his work forces. Professional
and technical advice and suggestions were provided to the owner and/or his designated repre-
sentative based upon our observations. Completed work under the purview of this report is
considered suitable and adequate for the intended use.
3
Lincoln & Oak Mixed Use January 24, 2012
Carlsbad, California Project No. 10125-1011071.000
Conditions of the referenced reports remain applicable unless specifically superseded herein.
Should you have any questions, please do not hesitate to contact the undersigned at (858) 292-
7575, or e-mail at abernal@usanova.com.
Respectfully submitted,
NOVA Engineering and Environmental
2J
No. 2715
Exp.aA49~ 9/30/13
Andres Bernal, E2L15 4*0
Principal Geotechnical
&4f4/44"A
ryan iller- icks, CEG 1323
Engineering Geologist AL
Distribution: (2) Addressee
(2) City of Carlsbad, Attn: Mr. Jay Jordan
Attachments: Figure 1- Field Density Test Plan
Table I -Summary of Density Curves
Table II - Summary of Compaction Test Results
7c U
5/2OtA
fBRYAN Mll.LER-HtCKS\
I NO. 13
I CERIIFIED
ENGINEERING /
401: r, AVN~,O~~
No. 2715
Exp.913Q16
4
IN
Lincoln & Oak Mixed Use January 24, 2012
Carlsbad, California Project No. 10125-1011071.000
REFERENCES
Conway & Associates, Inc., 2011, Grading Plans for Lincoln & Oak Mixed Use, Drawing No. 451-7A.
GeoSoils, 2004, Preliminary Geotechnical Evaluation, 3112 Lincoln Street, Carlsbad, San Diego County,
California, dated: January 14 (their W.O. 4147-Al-SC).
GeoSoils, 2010, Geotechnical Update for Structural Design, 3112 Lincoln Street, San Diego County,
California, dated: September 27 (their W.O. 4147-Al-SC).
GeoSoils, 2011, Geotechnical Review of Grading Plans, Lincoln & Oak Mixed Use, 3112 Lincoln Street,
dated: February 11 (their W.O. 4147-A2-SC).
NOVA Engineering and Environmental, 2011a, Assumption of Geotechnical Engineer of Record, Lincoln
& Oak Mixed Use, Permit No. 110011, dated: October 27.
NOVA Engineering and Environmental, 2011b, Additional Grading and Foundation Recommendations,
Lincoln & Oak Mixed Use, Carlsbad, California, dated: November 4.
5
PH
OAK AVENUE
ENTRANCE
/ ..
-
/ L
:
All
--4 -- - "- .-goo a () 49 51
I47.5I,. • 8 149 I t I 20 2R -T, ,/ 1 5 3 , ..'''G-6 '
" ' " 2 CA GROUND BD 1
50 2C !34° c'iI
k
GAI it
'c 24 4 9.6CA AA'4.i
. 12 2 6 ____ • A 48 5I
, I 49
AR R
39 EjjjA
..) I _____
I
"
49 4G
25 I37I PAAKINÔ GA9AGE . •
Aft 1 47
' LJ 4 40 Afc 61A T 14631 l46.6I 0 iL. , 4Qt)_. RO
I' / Q_3' -/ G-4' '-
I.3l38 IARjZ7 :. AC . 2CAR ''r °f 1481 ...... 1 I 2 • GRON LEVEL LD 2 J J • I! • >A 30 27 .13 14 ,. -29 - I 48 I I
_4 .J465I 0)7.5
--
:
LEGEND 10' 5' 0 10, 20'
Afc Artificial Fill - Compacted SCALE 1" = 20'
Qt Terrace Deposits (bracketed where buried)
41 Approximate Location of Field Density Test REFERENCE: CONWAY & ASSOCIATES, 2011, GRADING PLANS FOR LINCOLN AND OAK MIXED USE.
147.51 Approximate Elevation of Removal Bottom (feet, MSL)
g. . . Approximate Location of Slurry Backfill
- - - Approximate Limits of Grading
NOTE: ALL DIMENSIONS, DIRECTIONS AND LOCATIONS ARE APPROXIMATE.
Lincoln and Oak Mixed Use January 24, 2012
Carlsbad, California Project No. 10125-1011071.000
TABLE I
Summary of Density Curves
Laboratory Maximum Density ASTM:D 1557 (All Soil Types)
Optimum Maximum
Moisture Dry Density
Soil Type & Description (% dry wt.) (lbs./cu.ft.)
A Brown Silty Sand . 8.0 133.5
B Reddish Brown Silty Sand 7.0 137.0
LEGEND
Test Location - Indicated by Building Pad or Driveway area.
Elevation - Indicated by approximate Elevation (feet, msl), or Finish Grade (FG) level.
R,R1... - Indicates retest of previous compaction test failure, following moisture conditioning and/or recompactio
TEST TYPE
N - Indicates test by Nuclear Gauge (per ASTM:D 6398).
NOVA ENGINEERING AND ENVIRONMENTAL
Lincoln and Oak Mixed Use January 24, 2012
Carlsbad, California Project No. 10125-1011071.000
TABLE II
Summary of Compaction Test Results
Test Depth/ Moisture Unit Dry Density Rel. Soil Test Proj.
Date Number Test Location Elevation Opt. Field Max. Field Comp. Type Type Spec. Pass/Fail
11/10/11 1 Building Pad 1 - West 48.0 8.0 7.0 133.5 126.4 95 A N 95 Pass
2 Building Pad 1 - West 48.0 8.0 7.0 133.5 127.1 95 A N 95 Pass
3 Building Pad 1 - Center 48.0 8.0 7.3 133.5 126.3 95 A N 95 Pass
4 Building Pad 1- Center 48.0 8.0 7.4 133.5 126.5 95 A N 95 Pass
11/14/11 5 Building Pad 1 - Center 49.0 8.0 9.0 133.5 127.7 96 A N 95 Pass
6 Building Pad 1 - Center 49.0 8.0 9.7 133.5 126.5 95 A N 95 Pass
7 Building Pad 1 - West 49.5 8.0 9.4 133.5 126.9 95 A N 95 Pass
8 Building Pad 1 - Center 49.5 8.0 8.7 133.5 127.2 95 A N 95 Pass
9 Building Pad 2- G1 47.0 8.0 8.8 133.5 127.0 95 A N 95 Pass
11/15/11 10 Building Pad 1 - East 49.5 8.0 8.1 133.5 126.7 95 A N 95 Pass
11 Building Pad 1 - Center 49.5 8.0 8.0 133,5 130.1 97 A N 95 Pass
12 Building Pad 1 -West 49.5 8.0 9.7 133.5 126.6 95 A N 95 Pass
13 Building Pad 2 - Gi 47.0 8.0 9.0 133.5 126.8 95 A N 95 Pass
14 Building Pad 2 - Stairway G1/G2 47.5 8.0 9.4 133.5 126.7 95 A N 95 Pass
15 Building Pad 2- Gi 48.0 8.0 8.6 133.5 126.5 95 A N 95 Pass
16 Building Pad 2- G2 48.0 8.0 8.1 133.5 126.9 95 A N 95 Pass
17 Building Pad 2 - G2 48.0 8.0 8.6 133.5 127.7 96 A N 95 Pass
18 Building Pad 2 - G4 48.0 7.0 7.8 137.0 131.8 96 B N 95 Pass
19 Building Pad 2 - Storage 48.5 7.0 8.2 137.0 130.4 95 B N 95 Pass
11/16/11 20 Building Pad 2 - G6 50.0 7.0 5.9 137.0 124.0 91 B N 95 Fail
21 Building Pad 2 - G5 49.5 7.0 5.6 137.0 124.6 91 B N 95 Fail
20 R Building Pad 2- G6 50.0 7.0 8.1 137.0 129.9 95 B N 95 Pass
21 R Building Pad 2- G5 49.5 7.0 8.0 137.0 130.4 95 B N 95 Pass
22 Building Pad 2 - Stairway G5/G6 49.5 7.0 7.5 137.0 131.9 96 B N 95 Pass
23 Building Pad 2 - Stairway G6/Storage 49.0 7.0 8.4 137.0 129.9 95 B N 95 Pass
11/16/11 24 FG Building Pad 2 - G6 50.2 7.0 7.3 137.0 131.3 96 B N 95 Pass
25 FIG Building Pad 2- G5 49.5 7.0 7.7 137.0 131.1 96 B N 95 Pass
26 FIG Building Pad 2 -Trash Room 48.9 7.0 7.1 137.0 130.2 95 B N 95 Pass
27 FIG Building Pad 2 - Storage 48.9 8.0 8.6 133.5 127.1 95 A N 95 Pass
28 FIG Building Pad 2- G4 48.7 7.0 8.1 137.0 131.2 96 B N 95 Pass
NOVA ENGINEERING AND ENVIRONMENTAL
Lincoln and Oak Mixed Use S January 24, 2012
Carlsbad, California Project No. 10125-1011071.000
TABLE II -
Summary of Compaction Test Results
Test Depth/ Moisture Unit Dry Density Rel. Soil Test Proj.
Date Number Test Location Elevation Opt. Field Max. Field Comp. Type Type Spec. Pass/Fail
11/16/11 29 FG Building Pad 2 - G3 48.2 8.0 8.8 133.5 127.6 96 A N 95 Pass
(cont.) 30 FG Building Pad 2 - G2 48.4 7.0 7.5 137.0 133.8 98 B N 95 Pass
31 FG Building Pad 2 - G1 48.6 8.0 8.3 133.5 129.5 97 A N 95 Pass
11/18/11 32 FG Building Pad 1 - West 50.2 8.0 6.9 133.5 131.3 98 A N 95 Pass
33 FG Building Pad 1 - Center 50.2 8.0 6.2 133.5 130.8 98 A N 95 Fail
34 FG Building Pad 1 - East 50.2 8.0 7.6 133.5 130.6 98 A N 95 Pass
35 FG Parking Garage - West 48.2 7.0 6.8 137.0 131.7 96 B N 95 Pass
36 FG Parking Garage - West 48.3 7.0 6.4 137.0 132.7 97 B N 95 Pass
37 FG Parking Garage - Center 47.8 7.0 4.4 137.0 118.7 87 B N 95 Fail
38 FG Parking Garage - East 48.2 7.0 4.6 137.0 117.2 86 B N 95 Fail
11/22/11 37 R Parking Garage - Center 47.8 7.0 8.5 137.0 130.0 95 B N 95 Pass
38 R Parking Garage - East 48.2 7.0 8.0 137.0 130.6 95 B N 95 Pass
39 FG Parking Garage - Center 47.0 7.0 8.1 137.0 130.1 95 B N 95 Pass
40 FG Parking Garage - East 48.5 7.0 7.9 137.0 130.7 95 B N 95 Pass
41 FG Driveway - North 50.0 7.0 7.4 137.0 129.8 95 B N 95 Pass
NOVA ENGINEERING AND ENVIRONMENTAL