HomeMy WebLinkAboutCT 04-11; Poinsettia Commons; Water System Analysis; 2007-03-23RECORD COPY" Initial Bate WATER SYSTEM ANALYSIS FOR POINSETTIA COMMONS March 23, 2007 Prepared By: Dexter Wilson Engineering, Inc. 2234 Faraday Avenue Carlsbad, CA 92008 (760) 438-4422 Job No: 852-001 Oz X Oill X O DEXTER WILSON ENGINEERING, INC. March 23, 2007 DEXTER S. WILSON, P.E. ANDREW M. OVEN, P.E. STEPHEN M. NIELSEN, P.E. DIANE H. SHAUGHNESSY, P.E. 852-001 Tramwell Crow Residential 949 South Coast Drive, Suite 400 Costa Mesa, CA 92626 Attention: Brad Perozzi, Managing Director Subject: Water System Analysis for Poinsettia Commons This letter summarizes our analysis and recommendations for providing potable and recycled water service to the Poinsettia Commons development. The proposed development consists of thirteen buildings comprised of commercial and multifamily residential units. The project is located at the intersection of Avenida Encinas and Embarcadero Lane. The project is located within the Carlsbad Municipal Water District's 318 Water Pressure Zone for potable water service and 385 Zone for recycled water service. Existing potable water service lines within the vicinity of the project include a 12-inch water line in Avenida Encinas and an 8-inch water line in Embarcadero Lane. We recommend that water service connections be made to the existing 318 Zone water pipeline in Embarcadero Lane to serve the project. Based on pad elevations ranging from 56 to 58 feet, maximum static pressures for the project will range from 112 to 113 psi. Water Demands The two demands used to design the system are domestic demands from the buildings and fire flow demands. Table 1 summarizes the projected fixture units for the project based on information provided by the building architect. Using this information and 2234 FARADAY AVENUE • CARLSBAD, CA 92OO8 • (760)438-4422 • FAX (76O) 438-O173 Brad Perozzi March 23, 2007 extrapolating Chart A-2 from the Uniform Plumbing Code, the total project fixture unit count of 2,139 was determined to have an estimated peak water demand of 340 gpm. Appendix A provides a detailed fixture unit count breakdown for the building plan and provides Chart A-2 from the Uniform Plumbing Code. TABLE 1 POINSETTIA COMMONS WATER FIXTURE UNIT COUNT SUMMARY 221.5 343 167.5 134 134 167.5 167.5 167.5 167.5 10 134 11 134 12 100.5 13 100.5 DEXTER WILSON ENGINEERING, INC.PAGE 2 Brad Perozzi March 23, 2007 Table 2 summarizes the maximum number of Water Fixture Units that can be served by a given pipe diameter based on a maximum pipeline velocity of 8.0 feet per second. This table was used to size recommended building service laterals. TABLE 2 SIZE OF PRIVATE DOMESTIC SYSTEM PIPING BASED ON NUMBER OF WATER FIXTURE UNITS SERVED 0- 14 3/4-inch 15-29 1-inch 30-53 P/4 -inch 54 - 105 11/2-inch 106 - 270 2-inch 271 - 500 21/2-inch 501 - 780 3-inch 781 - 1,920 4-inch 1,921 - 3,575 5-inch 3,576-6,175 6-inch A design fire flowrate of 4,000 gpm for commercial developments and 3,000 gpm for multifamily developments were used in the fire system analysis, based on the 2003 Carlsbad Municipal Water District Water Master Plan. Fire sprinkler pipe sizing and design are not considered in this water system analysis and will be provided by others. DEXTER WILSON ENGINEERING, INC.PAGE 3 Brad Perozzi March 23, 2007 Proposed Domestic Water System Based on pad elevations ranging from 56 to 58 feet, the maximum static pressure within the 318 Zone will range from 112 to 113 psi. Domestic water service connections for each of the proposed buildings will be made to the existing 8-inch water line in Embarcadero Lane. Each of the connection points will have a cluster of water master meters and associated reduced pressure principle backflow preventers. The sizing and quantity of water meters in a cluster is not considered in this water analysis and will be determined by others. Table 3 provides the recommended water connection lateral sizes for each building. Figure 1 displays the existing and recommended water system layout for the project. TABLES RECOMMENDED WATER CONNECTION LATERAL SIZES i '••< " {«' ''•-:'?' Wx%sfelflt-;h X'.^' 4/-r--)l- 1 2 3 4 5 6 7 8 9 10 11 12 13 2" 2" (each)1 2" 2" 2" 2" 2" 2" 2" 2" 2" ll/2" 1W !There are two service laterals for this building. DEXTER WILSON ENGINEERING, INC.PAGE 4 Brad Perozzi March 23, 2007 Model Development. Analysis using the KYPIPE computer software developed by the University of Kentucky determined residual pressures throughout the fire protection system. This computer software utilizes the Hazen-Williams equation for determining headless in pipes. The Hazen-Williams "C" value used for all pipe sizes in our analysis is 120. The fire protection system was modeled with an estimated hydraulic grade line of 288 feet at the existing 12-inch water main in Avenida Encinas. The fire protection system has been designed to provide a minimum residual pressure greater than 20 psi under a fire flow scenario at all locations within the proposed project development. For the project, a fire flowrate of 3,000 gpm was modeled at nodes 28 and 40. A fire flowrate of 4,000 gpm was also modeled at nodes 8 and 28. The results of the computer analysis indicate that adequate water pressures are provided to the Poinsettia Commons project. Furthermore, fire flow requirements are being met with greater than 20 psi residual pressure at all locations within the project. Appendix B provides the computer modeling output and Exhibit A provides the corresponding node and pipe diagram. Recycled Water There is some potential for the use of recycled water on the site to irrigate the common landscaped areas within the project. This is proposed to be accomplished by making a single connection to the existing 12-inch recycled water line in Avenida Encinas. Figure 1 provides the approximate location of the existing recycled water line and proposed service connection. The 12-inch recycled water line is part of the City's 385 Zone recycled water system. With service from this zone, maximum static pressures on the project are expected to range from 142 to 143 psi. DEXTER WILSON ENGINEERING, INC. PAGE 5 EX. 12" RECYCLED WATER UNE (385 ZONE) EX. 12" WATER UNE. 318 PRESSURE ZONE EX. 12" WATER UNE, 318 PRESSURE ZONE PROJECT BOUNDARY EX 8" WATER UNE,—i 318 PRESSURE ZONE EMBARCADERO LANE BLOG 10 •PROPOSED RECYCLED WATER METER LEGEND - EXISTING PUBUC WATER UNES EXISTING RECYCLED WATER UNE PROPOSED DOMESTIC SERVICE PROPOSED FIRE PROTECTION SYSTEM txxi PROPOSED FIRE HYDRANT FIGURE 1 POINSETTIA COMMONS WATER SYSTEM LAYOUT \\PACIFIC\DWG\852001\FIGURE-1.DWG 03-23-07 09:49:48 LAYOUT: FIGURE Brad Perozzi March 23, 2007 Conclusions and Recommendations 1. The recommended potable and recycled water facilities for the Poinsettia Commons project are shown on Figure 1. 2. We recommend that building water service lateral sizes of P/2 inches to 21A inches be used to connect to the existing 8-inch water transmission line in Embarcadero Lane. 3. The location and sizing of the water meters and backflow preventers are not considered in this water analysis and will be determined by others. 4. All fire hydrants on the project will be connected to the existing 8-inch water line in Embarcadero Lane. 5. Individual pressure regulators should be installed on all potable water services to maintain maximum water service pressures to the buildings at 80 psi. 6. Recycled water can be provided to the project by connecting to the existing 12- inch recycled water line in Avenida Encinas. Thank you for the opportunity to work on your project. If you have any questions or require additional information, please let us know. Dexter Wilson Engineering, Inc. Stephen M. Nielsen SMN:sbr DEXTER WILSON ENGINEERING. INC. PAGE 7 APPENDIX A WATER FIXTURE UNIT DATA PLUMBING CODE DATA i i it t t i t t i i i i t i i I J II ii ii i * Water FU Project Name Poinsettia Commons Job Number 852-001 Date 8/4/2006 Water Supply Fixture Units The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code DESCRIPTION: Clothes Washer Tub/Shower Shower Urinal Kitchen Sink Dishwasher Laundry Sink Lavatory Water Closet (1.6 GPF) Hose Bibb Each Additional Hose Bibb TOTAL Commercial QUANTITY 0 0 0 1 0 0 0 2 3 1 1 8 FIXTURE UNITS EACH 4 4 2 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 0 0 0 2 0 0 0 2 7.5 2.5 L 1 15 Daycare QUANTITY 0 0 0 0 0 0 0 2 2 0 0 4 FIXTURE UNITS EACH 4 4 2 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 0 0 0 0 0 0 0 2 5 0 0 7 UnItA-1 ;•: QUANTITY 1 1 0 0 1 1 0 1 1 0 0 6 FIXTURE UNITS EACH 4 4 2 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 4 0 0 1.5 1.5 0 1 2.5 0 0 14.5 UnitA-2 QUANTITY 1 1 0 0 1 1 0 1 1 0 0 6 FIXTURE UNITS EACH 4 4 2 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 4 0 0 1.5 1.5 0 1 2.5 0 0 14.5 DESCRIPTION: Clothes Washer Tub/Shower Shower Kitchen Sink Dishwasher Laundry Sink Lavatory Water Closet (1.6 GPF) Hose Bibb Each Additional Hose Bibb Water Fountain Urinal TOTAL UnitA-3 QUANTITY 1 1 0 0 1 1 0 1 1 0 0 0 6 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 4 0 0 1.5 1.5 0 2.5 2.5 0 0 0 16 Unit A-4 QUANTITY 1 1 0 J 01 1 01 1 0 0 0 6 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 4 0 0 1.5 1.5 0 2.5 2.5 0 0 0 16 UnitA-5 QUANTITY 1 1 0 0 1 1 0 1 1 0 0 0 6 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 4 0 0 1.5 1.5 0 2.5 2.5 0 0 0 16 UnitA-6 QUANTITY 1 1 0 0 1 1 0 1 1 0 0 0 6 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 4 0 0 1.5 1.5 0 2.5 2.5 0 0 0 16 Pagel ii i i fc i c i i ii i i I i i i ft J t j i i i t Water FU (2) Project Name Poinsettia Commons Job Number 852-001 Date 8/4/2006 Water Supply Fixture Units The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code DESCRIPTION: Clothes Washer Tub/Shower Shower Kitchen Sink Dishwasher Laundry Sink Lavatory Water Closet (1.6 GPF) Hose Bibb Each Additional Hose Bibb TOTAL ; ;" tfciWf ' QUANTITY 1 2 0 1 1 0 3 2 0 0 10 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 0 1.5 1.5 0 3 5 0 0 23 yniB~2 QUANTITY 1 2 0 1 1 0 3 2 0 0 10 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 0 1.5 1.5 0 3 5 0 0 23 UMtB-3 QUANTITY 1 2 0 1 1 0 3 2 0 0 10 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 0 1.5 1.5 0 3 5 0 0 23 -' * ., ywffr^'' - QUANTITY 1 2 0 1 1 0 3 2 0 0 10 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 0 1.5 1.5 0 3 5 0 0 23 DESCRIPTION: Clothes Washer Tub/Shower Shower Urinal Kitchen Sink Dishwasher Laundry Sink Lavatory Water Closet (1.6 GPF) Hose Bibb Each Additional Hose Bibb Water Fountain TOTAL ewtrpt, ; _ . QUANTITY 1 2 0 0 1 1 0 3 2 0 0 0 10 FIXTURE UNITS EACH 4 4 2 2 1.5 1.5 ' 1.5 1 2.5 2.5 1 0.5 TOTAL FIXTURE UNITS 4 8 0 0 1.5 1.5 0 3 5 0 0 0 23 Unit D-1 QUANTITY 1 2 0 0 1 1 0 3 2 \0 0 0 10 FIXTURE UNITS EACH 4 4 2 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 TOTAL FIXTURE UNITS 4 8 0 0 1.5 1.5 0 3 5 0 0 0 23 Retail QUANTITY 0 0 0 4 1 1 0 .43•r1 0 18 FIXTURE UNITS EACH 4 . 4 2 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 TOTAL FIXTURE UNITS 0 0 0 8 1.5 1.5 0 4 15 2.5 1 0 33.5 Ur*^f QUANTITY 1 2 1 0 1 1 1 4 3 1 1 0 16 FIXTURE UNITS EACH 4 4 2 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 TOTAL FIXTURE UNITS 4 8 2 0 1.5 1.5 1.5 4 7.5 2.5 1 0 33.5 Page 2 Water FU (3) Project Name Job Number Date Poinsettia Commons 852-001 8/4/2006 Water Supply Fixture Units The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code DESCRIPTION: Clothes Washer Tub/Shower Shower Kitchen Sink Dishwasher Laundry Sink Lavatory Water Closet (1.6 GPF) Hose Bibb Each Additional Hose Bibb TOTAL r fhit-E2 ' ,;;;J QUANTITY 1 2 1 1 1 1 4 3 1 1 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 33.5 UnilE-3 QUANTITY 1 2 1 1 1 1 4 3 1 1 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 33.5 UnitF-t Jj QUANTITY 1 2 1 1 1 1 4 3 1 1 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 33.5 ?\ UNfefe^ , : QUANTITY 1 2 1 1 1 1 4 3 1 1 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 33.5 DESCRIPTION: Clothes Washer Tub/Shower Shower Kitchen Sink Dishwasher Laundry Sink Lavatory Water Closet (1.6 GPF) Hose Bibb Each Additional Hose Bibb Water Fountain Urinal TOTAL t "\fc\\b F* O QUANTITY 1 2 1 1 1 1 4 3 1 1 0 0 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 0 0 33.5 • ''. 0nitF-4 QUANTITY 1 2 1 1 1 1 4 3 1 1 0 0 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 0 0 33.5 Unit G-1 QUANTITY 1 2 1 1 1 1 4 3 1 1 0 0 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 0 0 33.5 UnitG-2 QUANTITY 1 2 1 1 1 1 4 3 1 1 0 0 16 FIXTURE UNITS EACH 4 4 2 1.5 1.5 1.5 1 2.5 2.5 1 0.5 2 TOTAL FIXTURE UNITS 4 8 2 1.5 1.5 1.5 4 7.5 2.5 1 0 0 33.5 PageS t i I i I i Water FU (4) Project Name Job Number Date Poinsettia Commons 852-001 8/4/2006 Water Supply Fixture Units The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code DESCRIPTION: Commercial Daycare Unit A-1 UnitA-2 Unit A-3 Unit A-4 UnitA-5 UnitA-6 TOTAL Building 1 QUANTITY 2 1 2 3 1 2 3 1 15 FIXTURE UNITS EACH 15 7 14.5 14.5 16 16 16 16 TOTAL FIXTURE UNITS 30 7 29 43.5 16 32 48 16 221.5 DESCRIPTION: Retail Unit B-1 Unit B-2 Unit B-3 Unit B-4 Unit C-1 Unit D-1 TOTAL Building 2 QUANTITY 2 1 2 3 1 2 3 14 FIXTURE UNITS EACH 33.5 23 23 23 23 23 23 TOTAL FIXTURE UNITS 67 23 46 69 23 46 69 343 DESCRIPTION: Unit E-3 Unit F-1 TOTAL Building 3 QUANTITY 3 2 5 FIXTURE UNITS EACH 33.5 33.5 TOTAL FIXTURE UNITS 100.5 67 167.5 DESCRIPTION: Unit E-2 Unit F-3 Unit G-2 TOTAL Building 4 QUANTITY 2 1 1 4 FIXTURE UNITS EACH 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 134 DESCRIPTION: Unit E-2 Unit F-3 Unit G-2 TOTAL Buildings QUANTITY 2 1 1 4 FIXTURE UNITS EACH 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 134 DESCRIPTION: Unit E-1 Unit F-1 Unit F-2 Unit G-1 TOTAL Buildings QUANTITY 2 1 1 1 5 FIXTURE UNITS EACH 33.5 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 33.5 167.5 Page 1 II li li 1 i li I i I i I i li i i i i I I i Water FU (5) Project Name Poinsettia Commons Job Number 852-001 Date 8/4/2006 Water Supply Fixture Units The basis for the Water Fixture Units is "Private" per the 2001 California Plumbing Code DESCRIPTION: Unit E-1 Unit F-1 Unit F-2 Unit G-1 TOTAL Building? QUANTITY 2 1 1 1 5 FIXTURE UNITS EACH 33.5 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 33.5 167.5 DESCRIPTION: Unit E-2 Unit F-3 Unit F-4 Unit G-1 TOTAL Building 8 QUANTITY 2 1 1 1 5 FIXTURE UNITS EACH 33.5 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 33.5 167.5 DESCRIPTION: Unit E-2 Unit F-3 Unit F-4 Unit G-1 TOTAL Building 9 QUANTITY 2 1 1 1 5 FIXTURE UNITS EACH 33.5 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 33.5 167.5 DESCRIPTION: Unit E-1 Unit F-1 Unit F-2 Unit G-1 TOTAL :.-'. ^Building 10 QUANTITY 2 1 1 1 5 FIXTURE UNITS EACH 33.5 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 134 DESCRIPTION: Unit E-1 Unit F-1 Unit F-2 Unit G-1 TOTAL Building 1.1 QUANTITY 2 1 1 1 5 FIXTURE UNITS EACH 33.5 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 33.5 134 DESCRIPTION: Unit E-2 Unit F-3 Unit F-4 TOTAL Building 12 QUANTITY 2 1 1 4 FIXTURE UNITS EACH 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 100.5 DESCRIPTION: Unit E-2 Unit F-3 Unit F-4 TOTAL . Building 13 QUANTITY 2 1 1 4 FIXTURE UNITS EACH 33.5 33.5 33.5 TOTAL FIXTURE UNITS 67 33.5 100.5 Page 2 SIZING WATER SYSTEMS Appendix A CHART A-3 Enlarged Scale Demand Load &'3i XII I 20 40 60 80 100 120 140 160 180 200 220 240 Fixture Units CHART A-3 (Metric) Enlarged Scale Demand Load 20 40 60 80 100 120 140 160 180 200 220 240 Fixture Units 191 ti t i ii ti li I J i 7oo CHA Estimate Curves 500 [Hill || in 1 1 1 1 1 1 MM 1 1| inn 400 S 300 a. 3 • -»i :::::::::::::::::::::::::;!.: O -ft.... II 1 1 1 1 1 llfjJrfT 1 1 1 1 1 II 1 1 1 1 1 1 II inn -'.'.li'i'.rz-.: ^0- 1 for system pre< , ' . . Mo. 2 for system prw J !::: i "":::":::::::: : 2001 CALIFORNIA PLUMBING RTA-2 for Demand Load .s^ ^s^j*f^ .f^ _ . _ i. _ __ -^^^ : : ::: : : : ::: : : : : : : : ; : : :: : : : j 55! (i. t ---- -^.i.-.. : ;:";?!: : • • : : ;!!""""j * * ..-- -* lominantly for flushometer valves tominantly for flush tanks : : : : CODE \ ^--^ ^ -" 0 500 1000 1500 2000 2500 3000 35*0 •*>«> *sw> s«-. ss*o t-. tsis> 7oot> Fixture Units APPENDIX B WATER SYSTEM ANALYSIS The following conditions were modeled: 1. Average day demands 2. Maximum day demands plus fire flow demand of 4,000 gpm at node 8 and 28 3. Maximum day demands plus fire flow demand of 3,000 gpm at node 28 and 40 4. Peak hour demands Foinsettia Commons Water System Analysis Project No.: 852-001 File Name: point August 17,2006 FLOWRATE IS EXPRESSED IN GPM AND PRESSURE IN PSIG (SCENARIO : PIPE NO AVERAGE DAY DEMANDl . NODE NOS. LENGTH (FEET) 3 7 11 15 19 21 23 27 31 35 39 43 47 51 55 59 63 67 0 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 64 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 4 JUNCTION NUMBER 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 DEMAND .00 2.53 .93 .93 .93 2.53 .93 .93 .93 .93 .93 .93 .93 .93 .93 .00 .00 120 150 120 30 70 50 50 50 60 60 130 50 50 20 30 500 950 250 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 DIAMETER (INCHES) 12.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 12.0 12.0 ELEVATION 56.00 58.00 58.00 58.00 57.00 56.00 57.00 57.00 56.00 56.00 56.00 56.00 56.00 57.00 57.00 57.00 57.00 ROUGHNESS MINOR LOSS K FIXED GRADE 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 120. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 CONNECTING 7 7 11 15 19 21 23 27 31 35 39 43 47 51 55 59 3 67 11 15 19 21 23 27 31 35 39 43 47 51 55 59 63 63 .00 288.00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 PIPES 67 OUTPUT SELECTION: ALL RESULTS ARE OUTPUT EACH PERIOD 3 VALUES ARE OUTPUT FOR MAXIMUM AND MINIMUM PRESSURES THIS SYSTEM HAS 18 PIPES WITH 17 JUNCTIONS, 1 LOOPS AND 1 FGNS THE RESULTS ARE OBTAINED AFTER 9 TRIALS WITH AN ACCURACY = .00114 Dexter Wilson Engineering Page 1 of 9 Poinsettia Commons Water System Analysis Project No.: 852-001 File Name: point August 17,2006 PIPE NO. 3 7 11 15 19 21 23 27 31 35 39 43 47 51 55 59 63 67 JUNCTION 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 4 48 44 16 12 8 NODE 0 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 NOS. 64 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 4 NUMBER FLOWRATE HEAD 16.22 9.90 7.37 6.44 5.51 4.58 2.05 1.12 .19 -.74 -1.67 -2.60 -3.53 -4.46 -5.39 -6.32 -6.32 9.90 DEMAND .00 2.53 .93 .93 .93 2.53 .93 .93 .93 .93 .93 .93 .93 .93 .93 .00 .00 MAXIMUM .00 .93 .93 MINIMUM .93 .93 2.53 GRADE 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 LINE .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 ELEVATION 56.00 58.00 58.00 58.00 57.00 56.00 57.00 57.00 56.00 56.00 56.00 56.00 56.00 57.00 57.00 57.00 57.00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .05 .06 .05 .04 .04 .03 .01 .01 .00 .00 -.01 -.02 -.02 -.03 -.03 -.04 -.02 .03 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 PRESSURE 100. 99. 99. 99. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 53 67 67 67 10 53 10 10 53 53 53 53 53 10 10 10 10 PRESSURES 288 288 288 .00 .00 .00 56.00 56.00 56.00 100. 100. 100. 53 53 53 PRESSURES 288 288 288 .00 .00 .00 58.00 58.00 58.00 99. 99. 99. 67 67 67 THE NET SYSTEM DEMAND =16.22 Dexter Wilson Engineering Page 2 of 9 Poinsettia Commons Project No.: 852-001 Water System Analysis File Name: point August 17,2006 SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 3 16.22 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 16.22 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 Dexter Wilson Engineering Page 3 of 9 Poinsettia Commons Water System Analysis Project No.: 852-001 File Name: point August 17, 2006 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65 THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE: JUNCTION NUMBER DEMAND 8 2002.53 28 2002.53 THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00006 [SCENARIO: FIRE FLOW DEMAND OF 4,000 PIPE NO. NODE 3 7 11 15 19 21 23 27 31 35 39 43 47 51 55 59 63 67 0 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 NOS. 64 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 4 JUNCTION NUMBER 4 8 12 16 20 22 24 28 32 36 40 44 48 52 FLOWRATE 4026.11 2803.94 801.41 799.88 798.35 796.81 792.64 791.10 -1211.43 -1212.96 -1214.50 -1216.03 -1217.57 -1219.10 -1220.64 -1222.17 -1222.17 2803.94 DEMAND .00 2002.53 1.53 1.53 1.53 4.17 1.53 2002.53 1.53 1.53 1.53 1.53 1.53 1.53 HEAD 4. 21. 1. . . _ 1 -1. -3. -1. -1. -. -15. -4. 4. GRADE 278. 256. 255. 254. 253. 253. 252. 251. 253. 255. 259. 260. 262. 263. GPM SPLIT BETWEEN NODES 8 AND 28 LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 66 45 69 42 98 70 69 69 81 82 95 52 53 61 92 36 05 96 LINE 38 93 24 82 85 15 46 78 59 41 35 88 40 01 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 ELEVATION 56. 58. 58. 58. 57. 56. 57. 57. 56. 56. 56. 56. 56. 57. 00 00 00 00 00 00 00 00 00 00 00 00 00 00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 11.42 17.90 5.11 5.11 5.10 5.09 5.06 5.05 -7.73 -7.74 -7.75 -7.76 -7.77 -7.78 -7.79 -7.80 -3.47 7.95 38 143 14 14 13 13 13 13 -30 -30 -30 -30 -30 -30 -30 -30 -4 19 .79 .00 .06 .01 .96 .91 .78 .73 .22 .29 .37 .44 .51 .58 .65 .72 .26 .85 PRESSURE 96 86 85 85 85 85 84 84 85 86 88 88 89 89 .37 .20 .47 .29 .30 .43 .70 .40 .62 .41 .12 .78 .44 .27 Dexter Wilson Engineering Page 4 of 9 Poinsettia Commons Water System Analysis 64 4 60 28 24 16 MAXIMUM PRESSURES .00 283.34 .00 278.38 .00 279.29 MINIMUM PRESSURES 2002.53 251.78 1.53 252.46 1.53 254.82 57.00 56.00 57.00 57.00 57.00 58.00 Project No.: 852-001 File Name: point August 17,2006 56 60 64 1.53 .00 .00 263.93 279.29 283.34 57.00 57.00 57.00 89.67 96.33 98.08 98.08 96.37 96.33 84.40 84.70 85.29 THE NET SYSTEM DEMAND = 4026.11 SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES PIPE NUMBER 3 FLOWRATE 4026.11 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 4026.11 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 Dexter Wilson Engineering Page 5 of 9 Poinsettia Commons Water System Analysis Project No.: 852-001 File Name: point August 17,2006 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 1.65 THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE: JUNCTION NUMBER DEMAND 28 1502.53 40 1500.93 THE RESULTS ARE OBTAINED AFTER 2 TRIALS WITH AN ACCURACY = .00156 SCENARIO : PIPE NO. 3 7 11 15 19 21 23 27 31 35 39 43 47 51 55 59 63 67 JUNCTION 4 8 12 16 20 22 24 28 32 36 40 44 48 52 FIRE FLOW DEMAND OF 3,000 NODE NOS. 0 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 NUMBER 64 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 4 FLOWRATE 3027.15 1653.68 1649.50 1647.97 1646.44 1644.90 1640.73 1639.19 1 136.66 135.13 133.59 -1367.34 -1368.87 -1370.41 -1371.94 -1373.48 -1373.48 1653.68 DEMAND .00 4.17 1.53 1.53 1.53 4.17 1.53 1502.53 1.53 1.53 1500. 93 1.53 1.53 1.53 HEAD 2. 8. 6. 1. 3. 2. 2. 2. . . -1. -1. -. -1. -19. -5. 1. GRADE 283. 275. 268. 267. 263. 260. 258. 255. 255. 255. 255. 257. 259. 260. GPM SPLIT BETWEEN NODES 28 AND 40 LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 75 07 42 60 73 66 65 65 03 03 07 89 89 76 14 07 03 87 LINE 39 32 90 29 56 90 25 60 57 54 47 36 26 02 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 ELEVATION 56. 58. 58. 58. 57. 56. 57. 57. 56. 56. 56. 56. 56. 57. 00 00 00 00 00 00 00 00 00 - 00 00 00 00 00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 8.59 10.55 10.53 10.52 10.51 10.50 10.47 10.46 .87 .86 .85 -8.73 -8.74 -8.75 -8.76 -8.77 -3.90 4.69 22.88 53.78 53.53 53.44 53.35 53.26 53.01 52.91 .53 .52 .51 -37.82 -37.90 -37.98 -38.06 -38.13 -5.29 7.47 PRESSURE 98. 94. 91. 90. 89. 88. 87. 86. 86. 86. 86. 87. 88. 87. 53 17 39 69 51 79 21 06 48 47 44 26 08 97 Dexter Wilson Engineering Page 6 of 9 Poinsettia Commons Water System Analysis Project No.: 852-001 File Name: point August 17,2006 56 60 64 1.53 .00 .00 261.16 280.23 285.25 57.00 57.00 57.00 88.47 96.73 98.91 64 4 60 MAXIMUM PRESSURES .00 285.25 .00 283.39 .00 280.23 57.00 56.00 57.00 98.91 98.53 96.73 28 40 36 MINIMUM PRESSURES 1502.53 255.60 1500.93 255.47 1.53 255.54 57.00 56.00 56.00 86.06 86.44 86.47 THE NET SYSTEM DEMAND =3027.15 SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES PIPE NUMBER 3 FLOWRATE 3027.15 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 3027.15 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 Dexter Wilson Engineering Page 7 of 9 Poinsettia Commons Water System Analysis Project No.: 852-001 File Name: point August 17, 2006 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE DEMANDS ARE CHANGED FROM ORIGINAL VALUES BY A FACTOR = 2.90 THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00013 SCENARIO : PIPE NO. 3 7 11 15 19 21 23 27 31 35 39 43 47 51 55 59 63 67 JUNCTION 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 PEAK HOUR NODE 0 4 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 NOS. 64 8 12 16 20 22 24 28 32 36 40 44 48 52 56 60 64 4 NUMBER DEMAND) FLOWRATE 47.04 28.70 21.36 18.67 15.97 13.27 5.94 3.24 .54 -2.16 -4.85 -7.55 -10.25 -12.94 -15.64 -18.34 -18.34 28.70 DEMAND .00 7.34 2.70 2.70 2.70 7.34 2.70 2.70 2.70 2.70 2.70 2.70 2.70 2.70 2.70 .00 .00 HEAD - GRADE 288 287 287 287 287 287 287 287 287 287 287 287 287 287 287 288 288 LOSS PUMP HEAD MINOR LOSS VELOCITY .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .01 .00 .00 LINE .00 .99 .99 .99 .99 .99 .99 .99 .99 .99 .99 .99 .99 .99 .99 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 ELEVATION 56.00 58.00 58.00 58.00 57.00 56.00 57.00 57.00 56.00 56.00 56.00 56.00 56.00 57.00 57.00 57.00 57.00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .00 .13 .18 .14 .12 .10 .08 .04 .02 .00 -.01 -.03 -.05 -.07 -.08 -.10 -.12 -.05 .08 HL/1000 .01 .03 .02 .01 .01 .01 .00 .00 .00 .00 .00 .00 .00 -.01 -.01 -.01 .00 .00 PRESSURE 100. 99. 99. 99. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 100. 53 66 66 66 10 53 10 10 53 53 53 53 53 10 10 10 10 Dexter Wilson Engineering Page 8 of 9 Poinsettia Commons Water System Analysis Project No.: 852-001 File Name: point August 17,2006 MAXIMUM PRESSURES 4 48 44 .00 2.70 2.70 288.00 287.99 287.99 56.00 56.00 56.00 100.53 100.53 100.53 16 12 8 MINIMUM PRESSURES 2.70 287.99 2.70 287.99 7.34 287.99 58.00 58.00 58.00 99.66 99.66 99.66 THE NET SYSTEM DEMAND = 47.04 SUMMARY OF INFLOWS (+) AND OUTFLOWS (-) FROM FIXED GRADE NODES PIPE NUMBER 3 FLOWRATE 47.04 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = 47.04 .00 Dexter Wilson Engineering Page 9 of 9 i f I EX. 12" WATER UNE, 318 PRESSURE ZONE EX. 8" WATER UNE, 318 PRESSURE ZONE EMBARCADERO LANE /. "• JEX. 12" WATER LINE, 318 PRESSURE ZONE LEGEND EXISTING PUBLIC WATER LINES PROPOSED DOMESTIC SERVICE PROPOSED FIRE HYDRANT COMPUTER MODEL PIPE NUMBER COMPUTER MODEL NODE NUMBER PROJECT BOUNDARY EXHIBIT A POINSETTIA COMMONS NODE AND PIPE DIAGRAM \\PACIFIC\DWG\852001\EXHIBIT-A.DWG 08-17-06 13:36:31 LAYOUT: EXHIBIT