HomeMy WebLinkAbout1817 ASTON AVE; 104; CB071448; Permit07-11-2007
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No: CB071448
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
1817 ASTON AV CBAD
Tl Sub Type:
2121201100 Lot#:
$13,300.00 Construction Type:
RsfGrsncs $'
NRG-380 SF-ADD 2 BATHROOMS &
RECONFIGURE OFFICE WALLS W/ELECTRIC
INDUST
0
NEW
Applicant:
JETT&JONES L L C
T LAWRENCE JETT
P O BOX 455
SANTA YNEZCA 93460
Status:
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
Plan Check*:
Owner: .
JETT&JONES L L C
T LAWRENCE JETT
P O BOX 455
SANTA YNEZCA 93460
ISSUED
05/24/2007
RMA
07/11/2007
07/11/2007
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD#3Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Reel. Water Con. Fee
$130.49 Meter Size
$0.00 Add'l Reel. Water Con. Fee
$84.82 Meter Fee
$0.00 SDCWA Fee
$0.00 CFD Payoff Fee
$2.79 PFF (3105540)
$0.00 PFF (4305540)
$0.00 License Tax (3104193)
$0.00 License Tax (4304193)
$0.00 Traffic Impact Fee (3105541)
$0.00 Traffic Impact Fee (4305541)
$0.00 PLUMBING TOTAL
$0.00 ELECTRICAL TOTAL
$0.00 MECHANICAL TOTAL
$0.00 Master Drainage Fee
Sewer Fee
$0.00 Redev Parking Fee
$0.00 Additional Fees
HMP Fee
TOTAL PERMIT FEES
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$118.00
$20.00
$28.00
$0.00
$0.00
$0.00
$0.00
??
$384.10
Total Fees:$384.10 Total Payments To Date:$384.10 Balance Due:$0.00
BUILDING PLANS
i/'IN STORAGE
ATTACHED
Inspector-
FINAL APPROVAL
Date:Clearance:
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired.
City of Carlsbad
1635 Faraday Ave., Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax: 760-602-8558
Building Permit Application
JOB ADDRESS
CT/PROJECT*#BEDROOI
SUITE#/SPACE#/UNIT#
#BATHROOMS I TENANTBUSILOT*# OF UNITS OCC. GROUP
DESCRIPTION OF WORK: (Please describe present use and proposed use)
_2_-r . /-
BUILDING AREA (SF)ADDITION AREA/fSF)GARAGE (SF)PATIOS (SF)DECKS (SF)FIREPLACE
YESD #
DE ^AtRCONDIlTONlBG J FIRE SPRINKLERS'
! ; NOta^* YES IB^NOQ YES IH^NO-O
CONTACT NAME (If Different Fom Applicant)APPLICANfiNAME
"ADDRESS
\
ADDRESS
ElTY STATE ZIP CITY STATE ZIP
PHONE PHONE FAX
/#/*
EMAIL
— <^ A ^
PROPERTY OWNER-i-CONTRACTOR BUS. NAME
AD ADDRESS
CITY STATE ZIP CITY STATE ZIP
PHONE FAX PHONE
i ?-
FAX
EMAIL EMAIL
ARCH/DESIGNER NAME & ADDRESS STATE LIC. #CLASS CITY BUS. LIC.#
(Sec 7031.5 Business and Professions Code: Any City or County which requires a permit to con,,,,,^ „„, m,f^,,, uc.i.ui»licensed pursuant to the provisions of the Contractor's License Law {Chapter 9, commending with Section 7000 of Division 3Section (031.5 by any applkant for a permit subjects the applicant to a cwil penalty of not m
construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is... _...j with Section 7000 of Division 3 of the Business and Professions Code} or that he is exempt therefrom, and the basis for the alleged exemption. Any violation ofby any applkant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
Workers' Compensation Declaration: / hereby affirm under penalty of perjury one of the following declarations:
n I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
LTI I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. • '. • Policy No. ' : Expiration Date :
This section need not be completed if the permit is for one hundred dollars ($100) or less. .
O Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (4100,000), in
addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
J8*> CONTRACTOR SIGNATURE DATE
I hereby affirm that I am exempt from Contractor's License Law for the following reason: .
d I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
s«te"7lf, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
ty/ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
O I am exempt under Section '• Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and materials for construction of the proposed property improvement. O Yes d No
2.1 (have / have not) signed an application for a building permit for the proposed work.
3.1 have contracted with the following person (firm) to provide the proposed construction (include name address / phone / contractors' license number):
4.1 plan to provide portions of the work, but I hayffihired the following person to coordinate, supervise and provide the major work (include name / address / phone / contractors' license number):
5.1 will provide ^af^eof th^rork, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of work):
_
& PROPERTY OWNER SIGNATURE
Is the applicant or future building occupant required to submit a business plan^juteTyhazardous materials registration form or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? a Yes (JVMo . ^_____
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air qualityjuaftagsment district? OYes UNO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? OYes fa-No
IF ANY OF THE ANSWERS ARE YES, >
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a cons^ruj
Lender's Name
lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Address
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carisbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID CfTY IN CONSEQUENCE OF THE GRANTING OF THISPERMIT.
OSHA: An OSHA perniit is required for excavations over 5'0' deep and demolition or construction of strictures over 3 stories in height
EXPIRATION: Every permit issued by the Buildina^fficial under the provisions ofthisCodeshallexpireby limitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such permit or if the^dingyw^uthorizarfby such permit is suspended or abandoned at any t'me after the work is commenced for a period of 180 jteys (Section 106.4.4 Uniform Building Code).
DATE g/^/0.j-^APPLICANT'S SIGNATURE
City of Carlsbad Bldg Inspection Request
For: 08/13/2007
Permit* CB071448
Title: NRG-380 SF-ADD 2 BATHROOMS &
Description: RECONFIGURE OFFICE WALLS W/ELECTRIC
Inspector Assignment: PD
1817 ASTON AV
Lot:
Type:Tl
Job Address:
Suite:
Location:
OWNER JETT&JONES L L C
Owner:
Remarks: •
Sub Type: INDUST
Phone: 76
Inspe'
Total Time:
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Requested By: NA
Entered By: CHRISTINE
Act Comments
Comments/Notices/Holds
Date
07/30/2007
07/25/2007
07/20/2007
07/20/2007
07/19/2007
07/19/2007
07/19/2007
07/19/2007
Associated PCRs/CVs Original PC#
PCR01107; ISSUED CENTEX HOMES-REVISE TRANSFORME; FROM 45 KVA TO 75 KVA
Inspection History
Description
17 Interior Lath/Drywall
17 Interior Lath/Drywall
14 Frame/Steel/Bolting/Welding
34 Rough Electric
14 Frame/Steel/Bolting/Welding
24 Rough/Topout
31 Underground/Conduit-Wiring
Act Insp Comments
AP PD
PA PD
AP PD WALLS
34 Rough Electric
AP
AP
AP
AP
AP
PD
PD
PD
PD
PD
WALLS
EsGil Corporation
In (Partnership with government jor Quitting Safety
DATE: July 11, 2007 a APPLICANT
a JURIS.
JURISDICTION: Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO.: 07-1448 SET: HI
PROJECT ADDRESS: 1817 Aston Avenue, Suite 104
PROJECT NAME: NRG-Cabrillo Power TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
XI The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
] The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
XI Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
XI REMARKS: Perforated plans are being carried by the applicant. OK to issue with the Building
Official or his Deputy approving the means of egress.
By: Bryan Zuppiger Enclosures:
Esgil Corporation
GA D MB D EJ D PC LOG
trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858)560-1468 +• Fax (858) 560-1576
r EsGil Corporation
In (Partnership with government for (BuiCtfing Safety
DATE: June 27, 2007 a APPLICANT
JURISDICTION: Carlsbad ^-Q-F
a FILE
PLAN CHECK NO.: 07-1448 SET: II
PROJECT ADDRESS: 1817 Aston Avenue, Suite 104
PROJECT NAME: NRG-Cabrillo Power TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Scott Cairns
12220 El Camino Real, Suite 200
San Diego, CA92130
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
XI Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted- Scott Cairns Telephone #: 858 793 4777
Date contacted?^ HO /fby^^) Fax #: 858 793 4787
Mail v^Telephone Fax ^/In Person
REMARKS:
By: Bryan Zuppiger Enclosures:
Esgil Corporation
D GA D MB D EJ D PC 06/21/07
trnsmtl.dot
9320 Chesapeake Drive, Suite 208 * San Diego, California 92123 + (858)560-1468 + Fax (858) 560-1576
Carlsbad O7-1448
Jiine 27, 2007
RECHECK PLAN CORRECTION LIST
JURISDICTION: Carlsbad PLAN CHECK NO.: O7-1448
PROJECT ADDRESS: 1817 Aston Avenue, Suite 104 SET: II
DATE PLAN RECEIVED BY DATE RECHECK COMPLETED:
ESGIL CORPORATION: 06/21/07 June 27, 2007
REVIEWED BY: Bryan Zuppiger
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on laws and
ordinances enforced by the Planning Department, Engineering Department or other departments.
The following items listed need clarification, modification or change. All items must be satisfied before
the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3, 1997 Uniform
Building Code, the approval of the plans does not permit the violation of any state, county or city law.
A. Please make all corrections on the original tracings and submit new sets of prints to:
THE JURISDICTION'S BUILDING DEPARTMENT.
B. To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the revised
plans.
C. The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of the prior
correction list, we have enclosed those pages containing the outstanding corrections. Please
contact me if you have any questions regarding these items.
D. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where they
are located on the plans. Have changes been made not resulting from this list?
QYes QNo
Carlsbad O7-14481 June 27, 2O07
• PLANS
NOTE: The items listed below refer to the item numbers from previous list. These
remaining items have not been adequately addressed. The notes in bold at the end of or
contained within each item are to emphasize the remaining problem.
1. Please make all corrections on the original tracings, as requested in the correction list. Submit
three sets of plans for commercial/industrial projects (two sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
a) Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Avenue, Carlsbad, CA 92008, and (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
b) Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, and (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete.
6. Provide an exit analysis plan (may be 8 1/2" x 11" or any convenient size). Show in this
analysis the occupant load of each area, the general exit flow patterns (by using arrows),
accumulated occupant loads and required exit widths. Two exits are required when the
occupant load exceeds 30. Exits can not go through a lunch room or warehouse.
• A complete description of the activities and processes that will occur in this tenant space
should be provided. A listing of all hazardous materials should be included. The materials
listing should be stated in a form that would make classification in UBC Tables 3-D and 3-E
possible. The building official may require a technical report to identify and develop methods of
protection from hazardous materials. UBC Section 307.1.6.
• Exits shall not pass through kitchens, store rooms, or spaces used for similar purposes. UBC
Section 1004.2.2.
• Exit signs are required whenever two exits are required. Show all required exit sign locations.
UBC Section 1003.2.8.2.
• Exit signs are required, provide the following notes on the plans, per UBC Section 1003.2.8.2.
o Exit signs shall be located as necessary to clearly indicate the direction of egress travel.
No point shall be more than 100 feet from the nearest visible sign.
o Exit signs shall be readily visible from any direction of approach.
• Show that exit path is lighted with at least one foot candle at floor level. UBC Section
1003.2.9.2.
Carlsbad O7-1448
« June 27, 20O7
The person responsible for their preparation must sign all final sheets of plans. (California
Business and Professions Code).
To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review items,
please contact Bryan Zuppiger at Esgil Corporation. Thank you.
EsGil Corporation
In Partnership with government for (RuiUing Safety
DATE: June 5, 2007 a APPLICANT
JURISDICTION: Carlsbad OTCATTREVIEWER
Q FILE
PLAN CHECK NO.: O7-1448 SET: I
PROJECT ADDRESS: 1817 Aston Avenue, Suite 104
PROJECT NAME: NRG-Cabrillo Power TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
1X1 The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Scott Cairns
12220 El Camino Real, Suite 200
San Diego, CA92130
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
IX) Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Scott Cairns Telephone #: 858 793 4777
Date contacted^A/o^by^d ) Fax #: 858 793 4787
Mail Telephone Y ^ax i/l1"1 Person
REMARKS:
By: Bryan Zuppiger Enclosures:
Esgil Corporation
D GA D MB D EJ D PC 05/29/07
trnsmtl.dot
9320 Chesapeake Drive, Suite 208 •* San Diego, California 92123 + (858)560-1468 4 Fax (858) 560-1576
Caftsbad 07-1448
June 5, 20O7
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: O7-1448
OCCUPANCY: B/S2
TYPE OF CONSTRUCTION: VN
SPRINKLERS?: yes
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: June 5, 2O07
JURISDICTION: Carlsbad
USE: office/warehouse
ACTUAL AREA: 380 ft2
OCCUPANT LOAD: 3
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 05/29/O7
PLAN REVIEWER: Bryan Zuppiger
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review is
based on regulations enforced by the Building Department. You may have other corrections based on
laws and ordinances enforced by the Planning Department, Engineering Department, Fire
Department or other departments. Clearance from those departments may be required prior to the
issuance of a building permit.
Code sections cited are based on the 2001 CBC that adopts the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied before
the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3, 1997 Uniform
Building Code, the approval of the plans does not permit the violation of any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each correction
item has been addressed, i.e.. plan sheet number, specification section, etc. Be sure to
enclose the marked up list when you submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC)tiforw.dot
'Carlsbad 07-1448
June 5, 2007
. PLANS
1. Please make all corrections on the original tracings, as requested in the correction list. Submit
three sets of plans for commercial/industrial projects (two sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
a) Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Avenue, Carlsbad, CA 92008, and (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
b) Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, and (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
2. Please imprint the project area into the Cover Sheet of the plans.
3. Where are the details for the new wall at the left on sheet TI2?
4. Please detail the hard ceiling attachment to the existing wall on sheet TI2.
5. The accessible restroom detail sheet as shown on sheet TI2 by detail balloon is referencing an
inappropriate sheet.
6. Provide an exit analysis plan (may be 8.1/2" x 11" or any convenient size). Show in this
analysis the occupant load of each area, the general exit flow patterns (by using arrows),
accumulated occupant loads and required exit widths. Sheet TI3 is blank. Second floor? Exit
lighting? Exit signs?
7. Provide mechanical ventilation capable of providing five air changes per hour in bathrooms
and water closet compartments if required openable windows are not provided. UBC Section
1203.3.
8. WIRING METHODS: AC Cable is not allowed in A, B, E, H, and I occupancies. NM cable is
restricted (without City approval) to one and two family dwellings. Note on plans that an
equipment ground conductor is to be installed in all flexible conduits.
9. The use of flexible metal conduit as a grounding means must comply with City Policy 84-36.
10. Show P & T valve on water heater and detail drain line route from P & T valve to the exterior.
UPC Section 608.4.
Carlsbad 07-1448
June 5, 2007
The person responsible for their preparation must sign all final sheets of plans. (California
Business and Professions Code):
To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review items,
please contact Bryan Zuppiger at Esgil Corporation. Thank you.
Carlsfcad O7-1448
June 5, 20O7
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 07-1448
PREPARED BY: Bryan Zuppiger DATE: June 5, 2007
BUILDING ADDRESS: 1817 Aston Avenue, Suite 104
BUILDING OCCUPANCY: B/S2 TYPE OF CONSTRUCTION: VN
BUILDING
PORTION
ti
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
AREA II Valuation
( Sq. Ft.) Multiplier
380
cb
34.37
By Ordinance
Reg.
Mod.
VALUE ($)
13,061
13,061
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review:
I I Repetitive Fee
^Tj Repeats
Complete Review
D Other
,—I Hourly
D Structural Only
Hour*
Esgil Plan Review Fee
Comments:
$130.49
$84.82
$73.07
macvalue.doc
JUN-06-2007 09:36 ESQIL CORP.8BB 560 1576 P. 002
GmrlsUad O7-1448
June Sf 2OO7
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 07-1448
OCCUPANCY: B/S2
TYPE OF CONSTRUCTION: VN
SPRINKLERS?; yes
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: June 5, 2007
JURISDICTION: Carlsbad
USE: office/warehouse
ACTUAL AREA: 380 fta
OCCUPANT LOAD: 3
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 05/29/^07
PLAN REVIEWER: Bryatt Zuppiger
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review is
based on regulations enforced by the Building Department. You may have other corrections based on
laws and ordinances enforced by the Planning Department, Engineering Department, Fire
Department or other departments. Clearance from those departments may be required prior to the
issuance of a building permit.
Code sections cited are based on the 2001 CBC that adopts the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied before
the plans will be in conformance with the cited codes and regulations. Per Sec, 106.4.3, 1997 Uniform
Building Code, the approval of the plans does not permit the violation of any state, county or city law.
To speed UP the recheck process, please note on this list for a copy) where each correction
item has been addressed. I.e.. plan sheet number, specification section, etc. Be sure .to
enclose the marked UP Hst when you submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC)trforw.dot
JUN-06-2007 09:37 ESGIL CPRP,V, B6B 560 1576 P. 003
€arfsi»&d O7-144S
June 5, 20O7
* PLANS
1. Please make all corrections on the original tracings, as requested in the correction list. Submit
three sets of plans for commercial/industrial projects (two sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
a) Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Avenue, Carlsbad, CA 92008, and (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
b) Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, and (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and l Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete,
2. Please imprint the project area into the Cover Sheet of the plans.^^,
3. Where are the details for the new wall at the left on sheet TI2?<5ee
4. Please detail the hard ceiling attachment to the existing wall on sheet TI2. *&&
5. The accessible restroom detail sheet as shown on sheet TI2 by detail balloon is referencing an
inappropriate sheet, ty^ ^c**M I -teWfatonc&A "fa SWoet
6. Provide an exit analysis plan (may be 8 1/2" x 1 1" or any convenient size). Show in this
analysis the occupant load of each area, the general exit flow patterns (by using arrows),
accumulated occupant loads and required exit widths. Sheet TI3 is blank. Second floor? Exit
lighting? Exit signs?
7. Provide mechanical ventilation capable of providing five air changes per hour in bathrooms
and water closet compartments if required openable windows are not provided. UBC Section
1203.3. *$&& aMe^ «\ot=e. -Sheet"
8. WIRING METHODS: AC Cable is not allowed in A, B, E, H, and I occupancies. NM cable is
restricted (without City approval) to one and two family dwellings. Note on plans that an
equipment ground conductor is to be installed in all flexible conduits.
9. The use of flexible metal conduit as a grounding means must comply with City Policy 84-36.
w MM §cx\€M\ fl0he i cloccf- £*-•/10. Show P & T valve on water heater and detail drain line route from P & T valve to the exterior,
JU¥-06-2007 09:37 ESGIL CORP. B5B 560 1576 P.004
T
Carlsbad 07-1448
June 5, 2O07
The person responsible for their preparation must sign all final sheets of plans. (California
Business and Professions Code).
To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. 11 you have any questions regarding these plan review items,
please contact Bryan Zuppiger at Esgil Corporation. Thank you.
TOTAL P.004
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER Cf\Ol -I DATE
ADDRESS I hoe
MPROVEMENTRESIDENTIAL
RESIDENTIAL ADDITION MINOR PLAZA CAJMINO REAL
(<$10,000.00)
CARLSBAD COMPANY STORES
POOL / SPA
RETAINING WALL
VILLAGE FAIRS
COMPLETE OFFICE BUILDING
OTHER.
PLANNER
ENGINEER
DATE
DATE
Carlsbad Fire Department BLDG. DEPT COPY
Plan Review Requirements Category: TI, INDUST
Date of Report: 06-21-2007
Name:
Address:
Reviewed by
^^T
Permit #: CB071448
Job Name: NRG-3 80 SF-ADD 2 BATHROOMS &
Job Address: 1817 ASTON AV CHAD
for review is incomplete. At this time. this
adequately conduct a review to determing55SiSSBPHPffPiiiiill8BK^3riQds. Please review
the necessary plans and/or
Conditions:
Cond:CON0002117
[MET]
Sheet T13 - Room 1 1 1 cannot exit thru file room 1 14, ref CBC sec 1004.2.2.
Sheets T12 & T13 - Please clarify existing stairway path of travel and oc-load.
Entry: 05/29/2007 By: MS Action: CO Entry: 06/21/2007 By: MS Action: AP APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING
PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT
NOTATIONS,
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
Carlsbad Fire Department BLDG. DEPT COPY
Plan Review Requirements Category: TI, INDUST
Date of Report: 05-29-2007
Name:
Address:
Reviewed by
Permit #: CB071448
Job Name: NRG-380 SF-ADD 2 BATHROOMS &
Job Address: 1817 ASTON AV CBAD
INCOMPLETE The item you have submitted for review is incomplete. At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards. Please review
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval.
Conditions:
Cond:CON0002117
[NOTMET]
Sheet T13-Room 111 cannot-exit thru file room 114,- ref CBC sec 1004.2.2.
iSheets T12,& Tl3 --Please clarify existing stairway path of travel and oc-load.
Entry: 05/29/2007 By: MS Action: CO