HomeMy WebLinkAbout1818 ASTON AVE; ; CB130608; Permit04-15-2013
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No
Building Inspection Request Line (760) 602-2725
CB130608
Job Address
Permit Type
Parcel No
Valuation
Occupancy Group
Project Title
1818 ASTON AVCBAD
Tl Sub Type INDUST
2121200500 Lot# 0
$8,000 00 Construction Type NEW
Reference #
COBRA GOLF= INSTALL SHELVING
CATWALK SYSTEM
Status
Applied
Entered By
Plan Approved
Issued
Inspect Area
Plan Check #
ISSUED
03/12/2013
LSM
04/15/2013
04/15/2013
Applicant
DAVID MALLORY
Owner
BLACKMORE PARKVIEW ASSOCIATES
8575 CHERRY
FONTANA CA 92335
951-551-5678
P 0 BOX 424
RANCHO SANTA FE CA 92067
Building Permit $107 27 Meter Size
Add'l Building Permit Fee $0 00 Add'l Red Water Con Fee $0 00
Plan Check $75 09 Meter Fee $0 00
Add'l Building Permit Fee $0 00 SDCWA Fee $0 00
Plan Check Discount $0 00 CFD Payoff Fee $0 00
Strong Motion Fee $1 68 PFF (3105540) SO 00
Park Fee $0 00 PFF (4305540) $0 00
LFM Fee $0 00 License Tax (3104193) $0 00
Bndge Fee $0 00 License Tax (4304193) $0 00
BTD #2 Fee $0 00 Traffic Impact Fee (3105541) $0 00
BTD #3 Fee $0 00 Traffic Impad Fee (4305541) $0 00
Renewal Fee $0 00 PLUMBING TOTAL $0 00
Add'l Renewal Fee $0 00 ELECTRICAL TOTAL $0 00
Other Building Fee $0 00 MECHANICAL TOTAL $0 00
Pot Water Con Fee $0 00 Master Drainage Fee $0 00
Meter Size Sewer Fee $0 00
Add'l Pot Water Con Fee $0 00 Redev Parking Fee $0 00
Red Water Con Fee $0 00 Additional Fees $0 00
Green BIdg Stands (SB1473) Fee $1 00 HMP Fee 9?
Fire Expedidted Plan Review $0 00 Green BIdg Standards Plan Chk 99 Fire Expedidted Plan Review
TOTAL PERMIT FEES $185 04
Total Fees $185 04 Total Payments To Date $185 04 Balance Due $0 00
Inspector
INALAPPROVAL
Date S ^Zo-f ? Clearance
NOTICE Please take NOTICE that approval of your project indudes the Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions" You have 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Cartsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which vou have oreviouslv been given a NOTICE similar to this, or as to which the statute of limitations has previously othenAfise expired
THEF0L10WIN6 APPROVALS REQUIRED PRIOR 10 PERMIT ISSUANCE PLANNING SfENGINEERING Sl^UILDING D^IRT" RE • HEAITH • HAZMAT/APCD
^ CITY OF
Building Permit Application
1635 Faraday Ave , Carlsbad, CA 92008
Ph 760-602-2719 Fax 760-602-8558
email buidllng@carlsbadca gov
www carlsbadca gov
Plan Check No. <2-^ \ '^i£>0%
Est. Value S, OOb
Plan Ck. Deposit
Date 13 SWPP
JOB ADDRESS SUITE#/SPACE«/UN1TW
CT/PROJECT # # BATHROOMS TENANT BUSINESS NAME CONSTR T^'PE OCC GROUP
DESCRIPTION OF WORK Include Square Feet of Affected Area(s)
/^^•TALJ^ ^htft-Vi^/ci C^i^A^K Si^ri^
EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE
YESD # NO n
AIR CONDITIONING
YES • NOD
FIRE SPRINKLERS
YES • NO •
APPLICANT NAME (Primary Contact) APPLICANT NAME (Secondary Contact)
ADDRESS ADDRESS
CITY STATE
CA
ZIP CITY STATE ZIP
PHONE FAX PHONE FAX
EMAIL EMAIL
ADDRES
>ERTY OWNER NAME
ss
CONTRACTOR BUS NAME
ADDRESS
CITY STATE CITY STATE
CA
ZIP
PHONE PHONE FAX
EMAIL EMAIL
ARCH/DESIGNER NAME & ADDRESS CLASS CITY BUS LICfl
TO /VPPCV
(Sec 7031 5 Business and Professions Code Any City or County whicfi requires a permit to construct, alter improve demolish or repair any structure prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor s License Law fCnaoter 9, commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom, and the basis for the alleged exemption Any violation of Section tosi 5 by any applicant for a permit subjects the applicant to s civil penalty of not more than five hundred dollars {$500)) . — •
Workers' Compensation Declaration / hereby affirm under penalty of perjury one of (he following declarations
• I have and will maintain a certificate of consent to self insure for workers compensation as provided by Section 3700 of the Labor Code for the perfomiance of Ihe work for which this perm A is issued
"^1 have and will maintain workej^s' compensation as required by Section 3700 of the Labor Code for the performance of the viwk for which ttiis permil is issued My workers' compensation insurance earner and policy
number are InsuranceCo 7^V/gc-ffltJ fj^jC^A^fJlT-f Policy No fa.f7A^ ^J-SIB Expiration Dale i/ j /
This section need not be completed if the permit is for one hundred dollars (S100) or less
n Certtficate of Exemption I certify that in the performance of the work for which this pemiit is issued I shall nol employ any person in any manner so as to become subject to the Workers Compensation Laws of
Calibrma WARNING Failure to secure workers'compensation coverage is iir)l3u'fuJ, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,OOD), in
addition lo the cost of compensation, daniMes as provided foyo^ction 3706 of the Labor code, interest and attorney's fees
,€5'CONTRACTOR SIGNATURE _ DAGENT DATE 3/^ / Z./
/ dereby affirm that I am exempt from Contractor s bcense Law for Ihe fallowing reason
O I, asowneroftheproperly or my employees with wages as Iheir sole compensation, will do ttie work and the structure is not intended or offered for sale (Sec 7044, Business and Professions Code The Contractors
License Law does not apply lo an owner of property v^o builds or improves thereon and who does such work himself or through his own employees provided that such improvements are not mlendecf or oifered for
sale If, however, the building or improvement is sold wilhin one year of completion the owner builder will have the burden of proving that he did not build or improve for the purpose of sale)
• .1, asownerof the property, am exclusively contractng wilhlicensed contractors loconstnjct the project (Sec 7044 Business and Professions Code The Contractors License Law does nol apply loan owner of
property who builds or improves thereon and conlracts for such projects with contractor(s) licensed pursuant lo the ConVacior s License Law)
• I am exempt under Seclion Business and Professions Code for this reason
1 I personally plan to provide the major labor and matenals for construction of the proposed property improvement d Yes • No
2 I (have / have nol) signed an application for a building permit for the proposed work
3 I have contracted with the following person (firm) to provide the proposed construction (include name address / phone /contractors license number)
4 1 plan to provide portions of Ihe wori< but I have hired Ihe fdlowing person to coordinate, supen/ise and provide the maior work [include name / address / phone / contractors license number)
5 I will provide some of the work, but I have contracled (hired) the following persons lo provide the work indicated [include name / address / phone / type of work)
,€lS*PROPERTY OWNER SIGNATURE •AGENT DATE
Is the applicant or future building occupant required to submit a business plan acutely hazardous matenals registration form or nsk management and prevemion program under Sections 25505 25533 or 25534 of the
Presley Tanner Hazardous Substance Account Act' Q Yes JSQJo
is the applicant or future building occupant required to obtain a pennil from the air pollution control disIncl or air quality management distncf • Yes O No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site'' • Yes a No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS USEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUHON CONTHOL DISTRfCT
I hereby affirm thai there is a constnjctton iending agency for the performance of the work this permit is issued (Sec 3097 (i) Civil Code}
Lender s Name Lender s Address
I ceitfy that] have iBadtheapplication and stalsthatthe above infomiation Is correaandthat&einfbm^ la^tecomplywith all City oidinances and Stale laws reiating&buiidingcoitstnicbon
I hereby aulhonze representatve of the City of Carisbad to enter upon the above mentioned property for inspecCon ixirposes I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CrTY OF CARLSBAD
AGAINST ALL LIABILITIES JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMFT
OSHA An OSHA peimit is required for excavations over 5'0' deep and demolition orconstitidion of stnictures over 3 stones in he^ht
EXPIFIATION Every permit issued by the Building Ofibal underihe provisions of this Coie shall expire t)y limitation and become null and void if the ixiilding ix Vtork authonzed by sucJi permit is not commenced within
180 days from tfie date of such permit or if thejjiilding or vrork authonzed by such pemiit is suspended or abandoned at any time aiter the mtk is commenced for a penod of 180 days (SecJon 106 4 4 Uniform Building Code)
^APPLICANT'S SIGNATURE DATE
STOP- THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection
TIPICATE OF OCCUPANCY fCommerciaf Projects Only)
Fax (760) 602-6560, Email wvw buildinq@carlsbadca Qov or Mail the completed fomn to Citv of Cartsbad. Building Division 1635 Faraday Avenue, Carlsbad, California 92008
C0# (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE ZIP
Carlsbad CA
PHONE FAX
EMAIL OCCUPANTS BUS LIC No
DELIVERY OPTIONS
D PICK UP • CONTACT (Listed above) • OCCUPANT (Listed above)
n CONTRACTOR (On Pg 1)
• MAIL TO n CONTACT (Listed above) • OCCUPANT (Listed above)
• CONTRACTOR (On Pg 1)
n MAIL / FAX TO OTHER __.___„_
• ASSOCIATED CB#-
• NO CHANGE IN USE/NO CONSTRUCTION
• CHANGE OF USE/NO CONSTRUCTION
.eS'APPUCANrS SIGNATURE DATE
Inspection List
Permits CB130608
Date _ Inspection Item
05/17/2013 89 Final Combo
05/17/2013 89 Final Combo
05/10/2013 89 Final Combo
05/10/2013 89 Final Combo
Type Tl INDUST
lnspectqr_^ct
Rl
PB AP
Ri
PB CO
COBRA GOLF= INSTALL SHELVING
CATWALK SYSTEM
Comments
COF
COF
Monday, May 20, 2013 Page 1 of 1
BS^^H INSPECTION RECORD
0 INSPECTION RECORD CARD WITH APPROVED
PLANS MUST BE KEPT ON THE JOB
0 CALL BEFORE 3:30 pm FOR NEXT WORK DAY INSPECTION
EI FOR BUILDING INSPECTION CALL: 760-602-2725
OR GO TO; www CarUbadca-oov/Buildino AND CLICK ON
"Request Inspection"
DATE: ^ rC [ ^
IF "YES" IS CHECKED BELOW THAT DIVISION'S APPROVAL IS REQUIRED PRIOR TO IREQUESTING A FlNAL BUILDINS INSPECTION.
IF YOU HAVE ANY QUESTIONS PLEASE CALL THE APPLICABLE DIVISIONS AT THE; PHONE NUMBERS PROVIDED BELOW. AFTER
ALL REQUIRED APPROVALS ARE SIGNED OFF- FAX TO 760-GO2-8560. EMAIL TO BLDGINSPECTION5@CARLSBADCA.GOV
OR BRING IN A COPY OF THIS CARD TO: 1635 FARADAY AVE.. CARLSBAD. CA 92008. BUILDING INSPECTORS CAN BE
REACHED AT 760-602-2700 BETWEEN 7:30 AM - 8:00 AM THE DAY OF YOUR INSPECTION.
CB130608 1818 ASTON AV
COBRA GOLF= INSTALL SHELVING
CATWALK SYSTEM
Tl INDUST
Lot# DAVID MALLORY
ktv^ORD COPY
NO YES Required Pnbrfo Requesting Building Final If Checked YES Date Inspector Notes
Landscape 760-944-6463 Allow 48 hours
CM&l (Engineering Inspettlons) 760-438-389^^ Call before 2 pm
v/ Frre Prevention 760-60^^660 Allow 48 hours
- ^ 0
Type of Inspection Type of Inspection
coDK tt BUILDING Date Inspector ^^^^QH^^^^^^^^^H[[|HH Date Inspector
#11 FOUNDATION #31 • ELECTKIC UNDERGROUND • UFER
#12 REINFORCED STEEL #34 ROUGH ELECTRIC
#66 MASONRY PRE GROUT #33 • ELECTRIC SERVICE • TEMPORARY
• GROUT O WALL DRAINS #35 PHOTOVOLTAIC
#10 TILT PANELS #39 FINAL
#11 POUR STRIPS CODE H MECHANICAL
#11 COLUMN FOOTINGS #41 UNDERGROUND DUCTS & PIPING
#14 SUBFRAME O FLOOR • CEILING #44 DDUCTA PLENUM • REF PIPING
#15 R00FSKEATT1ING #43 HEAT-AIR COND SYSTEMS
#13 EXT SHEAR PANELS #49 RNAL
#16 INSULATION CODE « COMBO INSPECTION
#18 EXTHRIORUTH #81 UNDERGROUND (11,12,21,31)
#17 INTERIOR UTH&DRYWALL #82 DRYWALL,EXTUTH,GASTES(17,18,23)
#51 POOIEXCA/STEEL/BOND/FENCE #83 ROOFSHEATING,EXTSHEAR (13,15)
#55 PREPLASTER -"J VritC- S #84 FRAME ROUGH COMBO (14,24,34,44)
#19 FINALn€eA<^V5^ '^dll > #89 nNAL0CCUPANCY(19,29,39,49)
coD> n PLUMBING Date Inspector
#22 • SEWER&BL/CO DPI/CO FIRE Date Inspector
#21 UNDERGROUND nWASTE • WTR
#24 TOP OUT • WASTE DWTR A/SUNDERGROUNDVISUAL
#27 TUB & SHOWER PAN A/S UNDERGROUND HYDRO
#23 • GAS TEST • GAS PIPING A/SUNDERGROUND FLUSH
#25 WATER HEATER A/S OVERHEAD VISUAL
#28 SOWR WATER A/S OVERHEAD HYDROSTAnC
#29 FINAL A/S RNAL
Comn H STORM WATER F/A ROUGH-IN
#600 PRE-CONSTRUCTION MEETING F/A HNAL
#603 FOLLOW UP INSPECTION FDCED EXTINGUISHING SYSTEM ROUGH-IN
#605 NOTICETO CLEAN FIXED EKTING SYSTEM HYDROSTATIC TEST
#607 WRITTEN WARNING FDCED EXnNGUISHINO SYSTEM HNAL
#609 NOTICEOFVIOLATION MEDICAL GAS PRESSURE TEST
#610 VERBALWARNING MEDICAL GAS FINAL
REV 10/2012 SEE BACK FOR SPECIAL NOTES
Vi/ww mtglinc com
Corporate
2992 E LaPalmaAve Ste A
Anaheim, CA 92806
Tel 714 632 2999
Fax 714 632 2974
Dispatch 800 491 2990
San Dlego/impenal County
6295 Ferris Square, Suits C
San Diego, CA 92121
Tel 858 537 3999
Fax 858 537 3990
Dispatch 888 844 5060
MTGL Proiect # jfs / 'Zfi3.X_
Permits.
Inland Empire
14467 Meridian Pkw, BIdg 2-A
Riverside, CA 92518
Tel 951 653 4999
Fax 951 653 4666
Dispatch 800 ^91 2990
DbA/CllY
IndiQ
44917 Golf Center Pkwy, #1
Indio.CA 92201
Tel 760 342 4877
fax 760 342 4525
Dispatch 800 491 2990
Report #. PG. A_ OF \ DSA/LEA#
Special Inspection Reports must be distributed to Ihe parties listed below within 14 days of the inspection Reports of non-compliant conditions must be distributed immediately
Separate reports shall be prepared for each type ot special inspeclinn, on a daily basis Each report shall be completed and signed by the special inspector conducting the inspection
PBOJECT NAM. Dm
ARCHITECT TIME ARIIIVEO TIME DEPARrED
EWGINEER
mn O
TRAVEL TtWE. LUNCH TIME
compncmR SUSCOflTRACTOR
INSPECllON ADDRESS ADORES -0'^ PROJECT
TYPE OF INSPECTION
• ENGINEERED FILL
• FOUNDATION
• BACK FILL
• BATCH PLANT
• PT CONCRETE
• SHOrCRETE
• CONCRETE
• MASONRY
• HIGH STRENGTH BOLTING
• WELDING
Q SHOP WELD
• FIREPROQFIMG
^ ANCHOR/DOWEL
n NDE FIELD
• NDESHOP
n CEILING WIRE
•
•
•
DSA/OSHPD/PROJECT
APPROVED DOCUIVIENTS
AVAILABLE
APPROVED FLANS YQ NO
SOIL REPORT YD ND SPECS Yn ND
APPROVED SHOP DRAWING VG ND
MATERIALS USED BY GONTRACTCB {IHCLUDC RESEARCH REPORT NO OR MATERIAL TEST REPORTS)
CONTRACTORS EOUlPMtNT / MANPOWER USED
AREA GRID LINES PIECES IfJSPECTED City of Carlsbad
MAY 1 3 2013
BUILDING DIVISION-
STRUCTURAL MOTES DETAIL OR RRS USED
REMARKS INCLUDING amiNGS
REWORK AS PERCEMT OF ALL WORK TODAY PERCENT PROJECT COMPLETE
THE WORK WASSJiLWASNOrn
Inspected in accordance with tb^ requirements ot the DSA/OSHPD/PROJECT
approved documents
MATERIAL SAMPLING WASQ WASNOTD N/A-Q
Performed in accordance with DSA/OSHPD/PROJECTapproved documents
CC Proiect Architect Contractor
Structural Engineer Building Department
OSA Regional Office Owner
School District
THE WORK INSPECTED METS DID NOT MEET •
The requirements of the DSA/OSHPD/PROJECT approved documents
Samples taken
Weather ii^Si t\ K, Temp,
nature of Special Inspector
Prml Name
Certification i
Verified by
EsGil Corporation
In (partnership with government for (Buifding S^ifety
DATE 3/22/2013 • APPLICANT
^JURIS
JURISDICTION City of Carlsbad • PLAN REVIEWER
• FILE
PLAN CHECK NO 13-0608 SET I
PROJECT ADDRESS 1818 Aston
PROJECT NAME Shelving/Catwalk Installation for Cobra Puma Golf
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes
XI The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check hst
and should be corrected and resubmitted for a complete recheck
I I The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
I I The applicant's copy of the check list is enclosed for the junsdiction to forward to the applicant
contact person
I I The applicant's copy of the check list has been sent to'
^ EsGil Corporation staff did not advise the applicant that the plan check has been completed
I I EsGil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Telephone #
Date contacted (by ) Email Fax #
Wlail Telephone Fax In Person
^ REMARKS 1 Fire Department approval is required 2 City to field verify that the path of travel
from the handicapped parking space to the rack area and the bathrooms serving the rack area
comply with all the current disabled access requirements
By David Yao Enclosures
EsGil Corporation
• GA • EJ n PC 3/14
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
City of Carlsbad 13-0608
3/22/2013
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION City of Carlsbad PLAN CHECK NO 13-0608
PREPARED BY David Yao DATE 3/22/2013
BUILDING ADDRESS 1818 Aston
BUILDING OCCUPANCY TYPE OF CONSTRUCTION
BUILDING
PORTION
AREA
(Sq Ft)
Valuation
Multiplier
Reg
Mod
VALUE ($)
1
shelvingSt catwalk per city 8,000
Air Conditioning
Fire Sprinklers
TOTAL VALUE 8,000
Junsdiction Code cb By Ordinance
BIdg Permit Fee by Ordinance • $107 27
Plan Cfieck Fee by Ordinance
Type of Review
[ I Repetitive Fee
Repeats
0 Complete Review
• Other
Hourly
EsGil Fee
$69.73
• Structural Only
Hr @
$60 07
Comments
Sheet 1 of 1
macvalue doc
^ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 Faraciay Avenue
Carlsbad CA 92008
www carlsbadca gov
DATE: 03/14/13 PROJECT NAME: COBRA PUMA GOLF
PLAN CHECK NO: 1 SET#: 1 ADDRESS: 181SAST0N
VALUATION: $8,000
PROJECT ID: CB13-0608
APN:
/ This plan check review is complete and has been APPROVED by the ENGINEERING
JLJ Division.
By: KATHLEEN LAWRENCE 03/14/13
A Final Inspection by the Division is required Cves [ZINO
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: DAVID IVIALLORY@HAWTHORNELIFT.COM
Vou may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked
PLANNING
760-602-4610
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
Chns Sexton
760-602-4624
Chris Sexton@carlsbadca gov
Kathleen Lawrence
760-602-2741
Kathleen Lawrence@carlsbadca ^ov
1 Greg Ryan
-i 760-602-4663
Gregory Rvan@carlsbadca gov
j Gina RUIZ
760-602-4675
Gina Ruiz@carlsbadca gov
1 Linda Ontiveros
J 760-602-2773
Linda Ontiveros@carlsbadca gov
1 Cindy Wong
760-602-4662
Cynthia Wong@carlsbadGa gov
Dominic Fieri
760-602-4664
Dommic Fien@carlsbadca gov
Remarks:
Development Services
Land Development Engineering
1635 Faraday Avenue
BUILDING PLANCHECK Development Services
Land Development Engineering
1635 Faraday Avenue ^ CITY OF CHECKLIST
Development Services
Land Development Engineering
1635 Faraday Avenue
CARLSBAD QUICK-CHECK/APPROVAL 760-602-2750
www carlsbadca gov
ENGINEERING Plan Check for CB13-0608 Date 03/14/13
Project Address 1818 ASTON APN
Project Description INSTALL SHELVING CATWALKK SYSTEM Valuation $8,000
ENGINEERING Contact Kathleen Lawrence
Phone 760-602-2741
Email kathleen.tawrence@carlsbadca.gov
Fax 760-602-1052
• RESIDENTIAL INTERIOR
• RESIDENTIAL ADDITION MINOR
INTERIOR ONLY (<$20,000.00)
• CARLSBAD PREMIER OUTLETS
• OTHER: CELL ANTENNAS
H TENANT IMPROVEMENT
• PLAZA CAMINO REAL
• COMPLETE OFFICE BUILDING
OFFICIAL USE ONLY
ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT
BY KATHLEEN LAWRENCE
REMARKS NO ADDITIONAL ENG. FEES
DATE 03/14/13
" 1
Notification of Engineering APPROVAL has been sent to
via EMAIL on 03/14/13
E-36 Page 1 d 1 REV 4/30/11
^ CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www carlsbadca eov
DATE: 3/14/13 PROJECT NAME: INTERIOR SHELVING ONLY PROJECT ID:
PLAN CHECK NO: CB130608 SET#: ADDRESS: 1818 ASTON AV APN:
^ This plan check review is complete and has been APPROVED by the PLANNING
Division.
By: GINA RUIZ
A Final Inspection by the PLANNING Division is required • Yes g] No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit
Resubmitted plans should include corrections from all divisions.
• This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required
Plan Check APPROVAL has been sent to:
DAVID.MALLORY@HAWTHORNELIFT.COIVI
For questions or clarifications on the attached checklist please contact the following reviewer as marked
PLANNING
760-602-4610
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
1 1 Chris Sexton
760-602-4624
Chris Sexton@carlsbadca gov
1 1 Kathleen Lawrence
760-602-2741
Kathleen Lawrence@carlsbadca eov
Q Greg Ryan
760-602-4663
Gre^orv Rvan@carlsbadca gov
Q Gina Ruiz
760-602-4675
Gina Ruiz@carlsbadca aov
1 1 Linda Ontiveros
760-602-2773
Linda Ontiveros@carlsbadca eov
1 Cindy Wong
760-602-4662
Cvnthia Wone@carl5badca gov
• • 1 1 Dommic Fieri
760-602-4664
Dommic Fieri@carlsbadca gov
Remarks.
f
^ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
iV
Communif^^'^tonomic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
wvi/w carlsbadca gov
DATE: 04/02/2013 PROJECT NAME: COBRA GOLF - SHELVING & CATWALK PROJECTID: CB130608
PLAN CHECK NO: 1 SET#: 1 ADDRESS: 1818 ASTON AV APN:
•
This plan check review is complete and has been APPROVED by the FIRE Division.
By:GR
A Final Inspection by the FIRE Division is required ^ Yes • No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: NHMH
Vou may a/so have correct/o/is from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked
"PMNNING^^; ENGINEERING ;
760-602-2750:1 };
FIRE RREVENT|6N : ^
" 760-602-4665 tf^^'yi^^;
1 1 Chris Sexton
760-602-4624
Ohns Sf?xton@carlsbadca ^ov
Kathleen Lawrence
760-602-2741
Kathleen Lawfrence@carlsbadca gov
X Greg Ryan
760-602-4663
Gre^orv Rvan@carlsbadca gov
1 Gina Ruiz
760-602-4675
Gina RMiz@carlsbadca fiov
Linda Ontiveros
760-602-2773
Linda Ontiveros@carlsbadca gov
Q Cindy Wong
760-602-4662
Cynthia Wong@carlsbadca gov
• • 1 1 Dominic Fieri
760-602-4664
Dominic Fieri@carlsbadca eov
Remarks: SEE ATTACHED
Carlsbad Fire Department COPY
plan Review Requirements Category Tl, INDUST
Date of Report- 04-02-2013 Reviewed by.
Name. DAVID MALLORY
Address. 8575 CHERRY
FONTANA CA
92335
Permit # CB130608
Job Name- COBRA GOLF= INSTALL SHELVING
Job Address 1818 ASTON AV CBAD
Please review carefully all comments attached
CITY OF CARLSBAD FIRE DEPARTMENT - APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF BUILDING PERMIT
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON, CONDITIONS IN
CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW
Conditions:
Requirement:
The High-pile Combustible Storage permit for this address is expired and 2-years past-due
Prior to Final inspection, Cobra Golf shall be held to obtain and maintain an Operational Use permit for this and al
storage systems at this property
Information regarding this permit may be obtained by contacting our office at 760.602 4665
Entry: 04/02/2013 By: GR Action. AP
EST 198^
SPECIAL PRODUCTS
TANK SUPPORTS
MACHINERY
RACK BLDGS
SHKDS
MEZZANINES
FOOTINGS
CONVbYORS
TALL SUPPORTS
HEADER STEEL
SORT PLATFORM
PICK MODULES
ROOF VERIFICATION
STORAGE RACKS
SELECTIVE
DRIVE IN
PUSH BACK
FLOW RAC K
CANTILEVER
OTHER SERVICES
SEISMIC ANALYSIS
PERMIT ACQUISITION
EGRESS PLANS
ST AT E APPROVALS
PRODUCT TESTING
SHELVING
MFTAL
METAL/WOOD
MOVABLE
GONDOLAS
LOCKERS
CATWALKS
SPECIALS PRODUCTS
SEJUTTLES
VLM
CAKOUSELS
VRC
MODULAR OFFICES
hENCES
LICENSED IN ALL 50 STATES
161 ATLANTIC STREET POMONA CA 91768 TEL 909-869-09S9 FAX 909-869-0981
C6 iVo^i
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET POMONA, CA 91758
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS(SD)
2
TC
2/19/2013
TABLE OF CONTENTS
DESCRIPTION
Title Page
Table of Contents
Shelving w/catwalk
Rack Support
Stairway
PAGE
1
2
3 to 29
30 to 42
43 to 47
tt
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
2
TC
2/19/2013
Shelving w/catwalk
Proiect Scope
The purpose of this analysis is to show that the following light duty storage fixtures complies with the specifications
set forth in the 2010 California Building Code
The light duty storage fixtures are prefabricated and are to be field installed only without any field welding
Proiect Parameters
The fixtures will be analyzed as a steel storage rack w/catwalk system
The fixtures will be located in the stock room area
The system will be analyzed for seismic loading utilizing the following equation
V = Cs X Ws
Cs = X I / R
= 2/3 X Fa X Ss
1= 1
R= 4
Seismic Factors
Proiect Specifications
Fa = 1 03
Ss = 118
SEISMIC DESIGN CATEGORY D
Steel • Shaped steel & Rods, ASTM A570 Grade 36, Fy = 36,000 psi
Rivet - 50,000 PSI
Bolts - A307 UNLESS OTHERWISE NOTED
Anchors-3/8"0x 2-1/2" mm embed Hilti KB-TZ (ICC ESR-1917)
Slab - 5 IN X 2500 PSI
Soil - 1,000 PSF
Configurations
Standard Storage
Standard Storage
Club Storage
48"Wx24"Dxl80"H
36"Wx24"Dxl80"H
48"Wx24"Dxl80"H
calcs pages
3 to 12
13 to 19
Critical configuration to be analyzed only, the rest can be verfied by simple review
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
3
TC
2/19/2013
Loads & Distribution Standard Storage
Fa = 103
Ss = 1 18
SDS = 2/3*Fa*Ss
= 0 81
R = 4
1 = 1
Cs = SDS X 1 / R
= 0 203
<=== IN AREA NOT OPEN TO THE PUBLIC
Product Load/Level, wPL
Dead Load/Level, wDL
Ws
Uof Shelf Levels
Depth
300 LB
20 LB
S{0 67*wPL-HwDL)+Catwalk DL+Catwalk LL/4
1,447 LB
6
24 0 IN
shelf bay width = 48.0 IN
catwalk width = 48 5 IN
TRIBAREA= 8 1 FT'^2
Catwalk LL = 40 PSF
Catwalk DL = 5 PSF
Tributary Catwalk LL = 323 LB
Tributary Catwalk DL = 40 LB
Vtotal= Cs*Ws
-0 203 X 1447 LB
294 LB
Level wx hx wx hx Fi Movt
1 221 LB 3 0 IN 663 IN-LB 154 LB 5 IN-LB
2 221 LB 33 3 IN 7,359 IN-LB 17 13 LB 570 IN-LB
3 221 LB 63 6 IN 14,056 IN-LB 32 71 LB 2,080 IN-LB
4 (Catwalk) 342 LB 99 0 IN 33,883 IN-LB 78 85 LB 7,807 IN-LB
5 221 LB 138 0 IN 30,498 IN-LB 70 98 LB 9,795 IN-LB
6 221 LB 180 0 IN 39,780 IN-LB 92 58 LB 16,664 IN-LB
1,447 LB TOTAL = 126,239 IN'LB 294 LB 36,921 IN-LB
I
This IS the tributary area being analyzed
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
151 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
4
TC
2/19/2013
Longitudinal & Transverse Analysis. Standard Storage
The "double rivet beams" engage the moment resisting thru the rivet connections to columns
Lonfiitudinal Loads
Mbase= 0 IN-LB <== Based Assumed to be pinned
Level Pcol-static Pcol-seismic Mcol Mconn-seismic
1 1,324 LB OLE 441 IN-LB 1,327 IN-LB
2 1,164 LB 0 LB 2,214 IN-LB 2,149 IN-LB
3 1,004 LB OLB 2,084 IN-LB 2,115 (N-LB
4 (Catwalk) 844 LB OLB 2,145 IN-LB 1,870 IN-LB
5 320 LB 0 LB 1,595 IN-LB 1,283 IN-LB
6 160 LB OLB 972 IN-LB 486 IN-LB
Transverse Loads'
<== critical
Level Pcol-static Pcol-seismic Mcol Mconn-seismic
1 1,324 LB 1,538 LB 441 IN-LB 1,327 IN-LB
2 1,164 LB 1,538 LB 2,214 IN-LB 2,149 IN-LB
3 1,004 LB 1,514 LB 2,084 IN-LB 2,115 IN-LB
4 (Catwalk) 844 LB 1,428 LB 2,145 IN-LB 1,870 IN-LB
5 320 LB 1,102 LB 1,595 IN-LB 1,283 IN-LB
6 160 LB 694 LB 972 IN-LB 486 IN-LB
<=== critical
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
5
TC
2/19/2013
ASD analysis per AISI Section properties are based on net effective sections
. P=(l+0 11SDS)DL+0 75(1+0 14SDS)PL+0 75LL= 1,093 LB
M=0 75*0 7*Mcol= 1,162 IN-LB
KxLx/rx= 12x30 IN/0 637 IN
= 56 5 <=== (Kl/r)max
KyLy/ry = 1 2 x 30 IN/0 813 IN
= 44 3
ro= (rx'^2 + ry'*2 + yo''2)'^0 5
= 1 131 IN
(?= l-(yo/ro)'^2
= 0 834
Per Section C4 1, Fe is taken as the smaller of Fel and Fe2
Fel= n'^2E/(KL/r)max'^2
= 9116 KSI
0ex= 7t'^2E/(KxLx/rx)'^2
= 91 16 KSI
at= l/Aro/^2[GJ-H(n'^2ECw)/(KtLt)'^2]
= 15 51 KSI
Fe2= l/(2fi)*{(CT,,-fCTt)-[(ae,+crt)'^2-(4*B*a,/at)I'^0 5}
= 15 02 KSI
Fe= 15 02 KSI
Post Analysis: Longitudinal Direction
|-*- 1-7/8"
T
7/8-
L
SECTION PROPERTIES
Xc = (Fy/Fe)'^0 5 t = 0 075 IN
= 155 A= 0 570 iN'^2
Fn = (0 877/(lc'\2))Fy Aeff= 0 410IN'^2
= 13 1? KSI lx= 0 161iN'^4
Pn= Aeff * Fn Sx= 0 117IN'^3
= 5,400 LB rx = 0 637 IN
Pa= Pn/Oc !y = 0 262 INM
= 3,000 LB Sy= 0 140IN'^3
P/Pa= 0 36 > 0 15 ry = 0 813 IN
Thus, Check P/Pa + {Cmx*Mx)/(Max*ax) < 1 0 J = 0001 INM
P/PaD-HMx/Max<10 Cw = 0 000 IN'^e
Pno= Aeff * Fy yo = -0 460 IN
= 14,760 LB Kx = 1 2
Pao= Pno/Oc Lx = 30 00 IN
= 8,200 LB Ky = 12
Fe = Cb *ro*A*(CTex*at)'\0 5/Sf Ly = 30 00 IN
= 124 KSI Kt = 1 0
Since Fe > 2 78 * Fy, Fc = Fy Lt = 30 00 IN
Fc = 36 KSl Fy= 36 KSI
Pcr= TT'^2E!/(k[)max'^2 G= 11,300 KSI
= 36,170 LB E= 29,500 KSI
oix= {l/[l-(Oc*P/Pcr)ir-l Cmx= 0 85
= 0 95 Cb= 10
My= Sy * Fe Qb = 1 67
= 5,040 IN-LB nc = 18
IVlax=Maxo= Mc/Ob
= 3,018 IN-LB
(1093 LB/3000 LB) -i- (0 85 x 1162 IN-LB)/{3018 IN-LB x 0 95) =
(1093 LB/8200 LB) -t- (1162 IN-LB/3018 IN-LB) =
0 71
0 52
< 1 0, OK
< 1 0, OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
6
TC
2/19/2013
Post Analysis Transverse Direction
ASD analysis per AISi Section properties are based on net effective sections
P=:(l+0 11SDS}DL+0 75(1+0 14SDS)P1-+0 75LL+0.75*0 7*Pseism(C= 1,901 LB
M=0 75*0 7*Mcol= 1,162 IN-LB
KxLx/rx= 12x30 IN/0 637 IN
= 56 5 < = = = (Kl/r)max
KyLy/ry = 1 2 x 30 IN/0 813 IN
= 44 3
ro= (rx'^2 + ry"! + xo'^2)'^0 5
= 1 033 IN
R= l-(xo/ro)'^2
= 1 000
Per Section C4 1, Fe is taken as the smaller of Fel and Fe2
Fel= rt'^2E/(KL/r)max'^2
= 9116 KSI
aex= n'^2E/(KxLx/rx)'^2
= 91 16 KSI
CTt= l/Aro'^2IGJ-(-(n'\2ECw)/(KtLt)'^2]
= 18 58 KSI
Fe2= l/{2f5)*{{a,,+ot)-[(a,,+cTt)'^2-(4*R*a,/at)]-0 5}
= 18 58 KSI
Fe= 18 58 KSI
1^ 1-7/8"
T
•7/8"
i
SECTION PROPERTIES
Xc = (Fy/Fe)'^0 5 t = 0 075 IN
= 1 39 A= 0 570 IN'^2
Fn= (0 658'^(lc'^2))Fy Aeff = 0 410 IN'^2
= 16 00 KSI lx = 0 161 INM
Pn= Aeff * Fn Sx = 0 117 IN'^3
= 6,561 LB rx = 0 637 IN
Pa= Pn/Qc ly = 0 262 INM
= 3,645 LB Sy = 0 140 IN'^3
P/Pa= 0 52 > 0 15 ry = 0 813 IN
Thus, Check P/Pa + (Cmx*Mx)/(M3x*ax) < 1 0 J = 0 001 INM
P/Pao + Mx/Max < 1 0 Cw = 0 000 IN'^6
Pno= Aeff * Fy xo = 0 000 IN
= 14,760 LB Kx = 1 2
Pao= Pno/Oc Lx = 30 00 IN
= 8,200 LB Ky = 1 2
Fe = Cb *ro*A*(CTex*at)'^0 5/Sf Lv = 30 00 IN
= 149 KSI Kt = 1 0
Since Fe> 2 78 *Fy, Fc = Fy Lt = 30 00 IN
Fc = 36 KSI Fy= 36 KSI
Pcr= n'^2ei/{kl)max'^2 .G= 11,300 KSI
- ' ~ ="36,170 lb •: .E= 29,500 KSI
ax= {l/[l-(Qc*P/Pcr)]r-l Cmx= 0 85
= 0 91 Cb= 10
My= Sx * Fe Ob = 1 67
= 4,212 IN-LB ac = 1 8
IVlax=Maxo= Mc/Qb
= 2,522 IN-LB
(1901 LB/3645 LB) -i- (0 85 x 1162 IN-LB)/(2522 IN-LB x 0 91) =
(1901 LB/8200 LB) -t- (1162 tN-LB/2522 IN-LB) =
0 95
0 69
< 1 0, OK
< 1 0, OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
7
TC
2/19/2013
Double Rivet Beam Connection
Since the frame is assumed to resist the seismic loads as a moment resisting frame, the capacity of the rivet beam
connection shall be determined and justified
Mconn = 0,75*0 7*Mconn-seismic
= 1,128 IN-LB
CAPACITY OF STUD IN SHEAR
Vallow= 04 * Fy * AREA
= 982 LB
BEARING CAPACITY OF STUDS
Vallow= stud 0 * tmin * Fu
= 1,088 LB
Vallow,min= 9S2 LB
Mallow= Vallow,mm * d
= 1,473 IN-LB
where d=l 5 IN
> Mconn OK
0= 0 250 IN
AREA= 0 049 IN'^2
Fy= 50,000 PSI
tmin= 0 075 IN
Fu-IV1ETAL= 58,000 PSI
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
8
TC
2/19/2013
Shelf Beam Analysis:
Analyze beam as having pinned connections
LOAD/BEAM = {300 LB-H20 LB)/(2*60 IN)
= 2 67 LB/IN
Mbeam =: wl'^2/8
= 1,200 IN-LB
fb/Fb = IV1/(S X Fb)
=: 1200 IN-LB/(0 11 ms*0 6*36000 PSI)
= 0 51 < 1 0 OK
i5,n6"
5/8"
r
LENGTH =
Fy =
lx =
Sx=
60 IN
36,000 PSI
0 180 INM
0 IIQIN'^S
DEFLECTION
D=: 5WL'*4/(384EI)
= 5*2 67 LB/IN*{60 IN)M/(384*29 5X10'^6 PSI*0 18 INM)
= 0 080 IN
Dallow=L/240 = 0 250 IN OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
9
TC
2/19/2013
Catwalk Beam Analysis: Deck Support Angle
Analyze beam as having pinned connections
W= LOAD*TRIB WIDTH
= 45 PSF * 4 FT
= 180 00 LB/FT
V= W*L/2
= 180 LB/FT * 4 FT/2
= 360 LB
M = WL'^2/8
= 180 LB/FT* (4 FT)'^2*12/S
= 4,320 IN-LB
Fb= {0 6)'(Fy}
= 06 * 33000 PSI
= 19,800 PSI
f b = M/Sx
= 4320 lN-LB/0 24 IN'^3
= 18,000 PSI
fb/Fb= 18000 PSI/19800 PSI
0.91 < 1 0 OK
12 GA
USED FOR CATWALK DECK SUPPORT
LOAD= 45 PSF
TRIBWIDTH= 4 OFT
L = 4 0 FT
Fy = 33,000 PSI
lx= 0 480 INM
Sx = 0 240 IN'^3
DEFLECTION
D= 5WLM/(384E1)
= 5*180 LB/FT*(4 FT)M*1728/(384*29 5X10'^6 PSI*0 48 INM)
= 0 070 IN
Dallow=L/240 = 0 200 IN OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
10
TC
2/19/2013
Overturning Analysis- Standard Storage
Fully Loaded
Movt= 36,921 IN-LB
MDL = 20 LB X 6 Levels x 24 IN / 2
1,440 IN-LB
MpLapp = 0 67*300 LB X 6 Levels x 24 IN / 2
= 14,472 IN-LB
Vcol = 0 7*Vtotal
= 206 LB
Depth, d= 24 0 IN
Puphft = [0 75 X 0 7 X Movt - (0 6-0 llS^s) x MQL - 0 75 x (0 6-0 14SDS) X MpLapo] / d
= [0 75*0 7*36921 - (0 6-0 11*0 81)*1440 - 0 75*(0 6-0 14*0 81)*14472] IN-LB / 24 IN
= 557 LB <=== UPLIFT Allowable Tension = 790 LB
Allowable Shear = 900 LB
Interaction Equation # of Anchors per Double Foot Plate = 2
[557 LB/ 1580 LB] + [103 LB/ 1800 LB] = 0 41 < 1 2 Therefore OK
USE (2) 3/8"0 x 2" MIN EMBED HILTI KB-TZ (ICC ESR-1917) PER DOUBLE FOOT PLATE
USE (1) 3/8"0 X 2" MIN EMBED HILTI KB-TZ (ICC ESR-1917) PER SINGLE FOOT PLATE
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
11
TC
2/19/2013
LRFD Load Combination - Slab System
Load combination per RMI 2 2 Resultant Load combination
1
2
3
4
5
6
DL-total/col
PL-total/col
LL-total/col
14DL+12PL 14DL-H2PL
1 2DL + 1 6PL + 1 6LL -1- 0 5(Lr or SL or RL) 1 2DL -H 6PL + 1 6LL
1 2DL + 0 S5PL + (0 5LL or 0 8WL) + 1 6(Lr or SL or RL) 1 2DL + 0 85PL + 0 5LL
1 2DL + 0 85PL + 0 5LL + 1 6WL + 0 5(Lr or 51 or RL) 1 2DL -f- 0 85PL + 0 5LL
{1 2+0 2SDS)DL + (0 85-HO 2SDS)PL -i- 0 5LL + EL + 0 2SL (1 2+0 2SDS)DL + (0 85+0 2SDS)PL + 0 5LL + EL
(0 9-0 2S[,s)DL + (0 9-0 2SDs)PLapp - EL (0 9-0 2SDS)DL + (0 9-0 2SDs)PLapp - EL
100 LB
900 LB
323 LB
EL = 1,538 LB
Load combination 1
Pmax= 14DL+ 1 2PL
= 1 4 X 100 LB + 1 2 X 900 LB
= 1,221 LB
Load combination 2
Pmax = 1 2DL + 1 6PL + 1 6LL
= 1 2 X 100 LB + 1 6 X 900 LB +1 6 X 323 LB
= 2,078 LB
Load combination 3 & 4
Pmax = 1 2DL + 0 85PL + 0 5LL
= 1 2 X 100 LB + 0 85 X 900 LB + 0 5 X 323 LB
= 1,04? LB
Load combination 5
Pmax = (1 2+0 2Sps)DL + (0 85+0 2SDS)PL + 0 5LL + EL
= (1 2+0 2*0 81) X 100 LB + (0 85+0 2*0 81) x 900 LB + 0 5 x 323 LB + 1 0 x 1538 LB
= 2,747 LB
Load combination 6
Pmax = (0 9-0 2Sos)DL + (0 9-0 2SDs)PLapp - EL
= (0 9-0 2*0 81) x 100 LB + (0 9-0 2*0 81) x 603 LB - 1538 LB
= -703 LB
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
12
TC
2/19/2013
Slab and Soil Check
The slab will be checked for puncture and bearing stress If no puncture occurs, the slab is assumed to distribute
the load over a larger area of the slab
Pmax = 2,747 LB
a) Puncture
Fpunct= 2 66x(F'c'^0 5)
= 2 66 x (2500 PSO'^OS
= 133 PSI
Apunct = [{Weff +t/2)+(Deff +t/2)l x 2 x t
= [(5 25 IN + 5 IN/2) + (2 5 IN + 5 IN/2)] x 2 x 5 IN
= 128 m"!
fv/Fv= P/[(Apunct)(Fpunct)]
= 2747 LB/[128 IN'^2 x 133 PSI x 0 55]
= 0.29 < 1 0 OK
b) Bearing
0Bn= O85x0xf'cxAl
= 15,340 LB
Pu / 0Bn = 2747 LB / 15340 LB
= 0 18 < 1 0 OK
c) Slab Tension
Asoil= P/[10xfsoilI
= 2747 LB/[1 0 X 1000 PSF/(144IN'^2/FT'^2)]
= 396 IN'^2
L= Asoi^O 5
= (396 IN^2)'*0 5
= 19 9 IN
B= [(Weff )(Deff )l'^0 5 + t
= [5 25INx25INl'^05 + 5
= 8 6 IN
b = (L-B)/2
= (19 9IN-8 6IN)/2
= 5 6 IN
Mconc = (w)(b'^2)/2 = [(1 0)(fsoil)(b'^2)]/[144 (IN'^2/FT'^2) x 2]
= [1 0 x 1000 PSI X (5 64 IN)'^2]/[144 (IN''2/FT'^2) x 2]
= 110IN-LB
Scone = llNx(t'^2)/6
= llNx(5IN)'^2/6
= 4 17 IN'^3
Fconc = 5 X 0 X f'c'^O 5
= 5 X 0 55 X (2500 PS\)''0 5
= 137 5 PSi
fb/Fb = Mconc/[(Sconc)(Fconc)]
= 110 39 IN-LB/[(4 17 IN'^3)(137 5 PSI)]
= 0 19 < 1 0 OK
Base Plate
Weff = 5 25 IN
Deff = 2 50 IN
Al= 13 13IN'^2
Concrete
t = 5 00 IN
f c = 2,500 PSI
sqii
fsoil = 1,000'PSF
0= 0 55
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
13
TC
2/19/2013
•oads & Distribution- Club Storage
Fa -1 03
Ss 1 18
Sos = 2/3*Fa*Ss
= 0 81
R = 4
1 = 1
Cs SDSXI/R
= 0 203
<=== IN AREA NOT OPEN TO THE PUBLIC
Product Load/Level, wPL
Product Load/Level, wPL
Dead Load/Level, wDL
Ws
# of Typical Shelf Levels
U of Narrow Shelf Levels
300 LB Levels 1-5
100 LB Levels 6-16
20 LB
1(0 67*wPL+wDL)+Catwalk DL+Catwalk LL/4
1,226 LB
5
11
shelf bay width = 48 0 IN
catwalk width = 48 5 IN
TRIBAREA= 8 1 FT'^2
Catwalk LL= 40 PSF
Catwalk DL= 5 PSF
Tributary Catwalk LL = 323 LB
Tributary Catwalk DL = 40 LB
Depth = 24 0 IN
Vtotal = Cs*Ws
= 0 203 X 1226 LB
-249 LB
Level wx hx wx hx Fl Movt
1 221 LB 3 0 IN 663 IN-LB 0 74 LB 2IN-LB
2 221 LB 33 3 IN 7,359 IN-LB 8 18 LB 272 IN-LB
3 221 LB 63 6 IN 14,056 IN-LB 15 62 LB 994 IN-LB
4 (Catwalk) 342 LB 99 0 IN 33,883 IN-LB 37 66 LB 3,728 IN-LB
5 221 LB 112 5 IN 24,863 IN-LB 27 63 LB 3,109 IN-LB
6 87 LB 118 5 IN 10,310 IN-LB 11 46 LB 1,358 IN-LB
7 87 LB 124 5 IN 10,832 IN-LB 12 04 LB 1,499 IN-LB
8 87 LB 130 5 IN 11,354 IN-LB 12 62 LB 1,647 IN-LB
9 87 LB 138 0 IN 12,006 IN-LB 13 34 LB 1,841 IN-LB
10 87 LB 144 0 IN 12,528 IN-LB 13 92 LB 2,005 IN-LB
11 87 LB 150 0 IN 13,050 IN-LB 14 50 LB 2,176 IN-LB
12 87 LB 156 0 IN 13,572 IN-LB 15 08 LB 2,353 IN-LB
13 87 LB 162 0 IN 14,094 IN-LB 15 66 LB 2,538 IN-LB
14 87 LB 168 0 IN 14,616 IN-LB 16 24 LB 2,729 IN-LB
15 87 LB 174 0 IN 15,138 IN-LB 16 82 LB 2,927 IN-LB
16 87 LB 180 0 IN 15,660 IN-LB 17 40 LB 3,133 IN-LB
2,183 LB TOTAL = 223,982 IN-LB 249 LB 32,309 IN-LB
This IS the tributary area being analyzed
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
14
TC
2/19/2013
Longitudinal & Transverse Analysis. Club Storage
The "double rivet beams" engage the moment resisting thru the rivet connections to columns
Longitudinal Loads
Mbase = 0IN-LB <=- Based Assumed to be pinned
Level Pcol-static Pcol-seismic Mcol Mconn-seismic
1 1,824 LB OLB 373IN-LB 1,127 IN-LB
2 1,664 LB 0 LB 1,880 IN-LB 1,849 IN-LB <== critical
3 1,504 LB 0 LB 1,818 IN-LB 1,902 IN-LB
4 (Catwalk) 1,344 LB OLB 1,986 IN-LB 1,308 IN-LB
5 660 LB 0 LB 630 IN-LB 942 IN-LB
6 360 LB OLB 1,253 IN-LB 931 IN-LB
7 60 LB OLB 609 IN-LB 305 IN-LB
Transverse Loads
Level Pcol-static Pcol-seismic Mcol Mconn-seismic
1 1,824 LB 1,346 LB 373 IN-LB 1,127 IN-LB
2 1,664 LB 1,346 LB 1,880 IN-LB 1,849 IN-LB <=== critical
3 1,504 LB 1,335 LB 1,818 IN-LB 1,902 IN-LB
4 (Catwalk) 1,344 LB 1,293 LB 1,986 IN-LB 1,308 IN-LB
5 660 LB 1,138 LB 630 IN-LB 942 IN-LB
6 360 LB 744 LB 1,253 IN-LB 931 IN-LB
7 60 LB 472 LB 609IN-LB 305 IN-LB
i
•
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
15
TC
2/19/2013
ASD analysis per AISI Section properties are based on net effective sections
P=(l+0 11SDS)DL+0 75(1+0 14SDS)PI-+0 75LL= 1,536 LB
M=0 75*0 7*Mcol= 987 IN-LB
KxLx/rx= 12x30 IN/0 637 IN
= 56 5 <=^= (Kl/r)max
KyLy/ry = 12X30|N/0 813 IN
= 44 3
ro= (rx'^2 + ry/'2 + yo'^Zj'^O 5
= 1131 IN
R- l-(yo/ro)'\2
= 0 834
Per Section C4 1, Fe is taken as the smaller of Fel and Fe2
Fel= Ti'^2E/(KL/r)max'^2
= 91 16 KSI
aex= Ti'^2E/(KxLx/rx)'\2
= 91 16 KSI
cjt= l/Aro'^2[GJ+(TT'^2ECw)/(KtLt)'^2]
= 15 51 KSI
Fe2= l/(2ft)*{(a^,+at)-[(a„+c7t)'^2-(4*(i*cT^,*at)]'^0 5}
= 15 02 KSI
Fe= 15 02 KSI
Post Analysis: Longitudinal Direction
1^ 1-7/8" -*-|
T
7/8"
i
SECTION PROPERTIES
Xc = (Fy/Fej'^O 5 t = 0 075 IN
= 1 55 A= 0 570IN'^2
Fn = (0 877/{lc'^2))Fy Aeff = 0 410 m^2
= 13 17 KSI lx = 0 161 INM
Pn= Aeff * Fn 5x = 0 117 IN'^3
= 5,400 LB rx = 0 637 IN
Pa= Pn/Qc ly = Q 262 INM
= 3,000 LB Sy = 0 140 IN''3
P/Pa= 0 51 > 0 15 rY = 0 813 IN
Thus, Check P/Pa + (Cmx*Mx)/(Max*ax) < 1 0 J = 0 001 IN'^4
P/Pao + Mx/Max<10 Cw = 0 000 IN'^6
Pno= Aeff * Fy yo = -0 460 IN
= 14,760 LB Kx = 1 2
Pao= Pno/Qc Lx = 30 00 IN
= 8,200 LB Ky = 1 2
Fe = Cb *ro*A*(aex*at)'^0 5/Sf Ly = 30 00 IN
= 124 KSI Kt = 1 0
Since Fe > 2 78 * Fy, Fc = Fy Lt = 30 00 IN
Fc = 36 KSI Fy= 36 KSI
Pcr^ TT'^2FI/{kl)max'^2 G= 11,300 KS!
= 36,170 LB E= 29,500 KSI
ax= {l/[l-(Dc*P/Pcr)]}^-l Cmx= 0 85
= 0 92 Cb= 1 0
My= Sy * Fe Qb = 167
= 5,040 IN-LB Qc = 1 8
Max=Maxo= Mc/Qb
= 3,018 IN-LB
(1536 LB/3000 LB) + (0 85 x 987 IN-LB)/(3018 IN-LB x 0 92) =
(1536 LB/8200 LB) + (987 [N-LB/3018 IN-LB) =
0 81
0 51
< 1 0, OK
< 1 0, OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
16
TC
2/19/2013
ASD analysis per AISI Section properties are based on net effective sections
P=(l+0 11SDS)DL+0 75(1+0 14SDS)PL+0.75LL+0 75*0.7*Pseismic= 2,243 LB
M=0 75*0 7*Mcol= 987 IN-LB
KxLx/rx= 12x30IN/0 637 IN
= 56 5 < === (Kl/r)max ^
KyLy/ry = 1 2 x 30 IN/0 813 IN
= 44 3
ro= (rx'^2 + ry/^2 + xo''2)'^0 5
= 1 033 IN
R= l-ixo/ro)"!
= 1 000
Per Section C4 1, Fe is taken as the smaller of Fel and Fe2
Fel= K'^2E/(KL/r)max^2
= 9116 KSI
aex= n'^2E/(KxU/rx)'*2
= 91 16 KSI
at= l/Aro'^2[GJ+(n^2ECw)/(KtLt)^2]
= 18 58 KSI
Fe2= l/(2B)*{(o„+CFt)-[(ae,+at)'^2-(4*li*Oe.*crt)]'^0 5}
= 18 58 KSI
Fe= 18 58 KSI
Post Analysis: Transverse Direction
|-*- 1-7/8"
T
1-7/8"
SECTION PROPERTIES
Xc = (FY/Fe)'*0 5 t = 0 075 IN
= 139 A= 0 570 )N'^2
Fn= (0 658'^(lc'^2))Fy Aeff= 0 410IN/^2
= 16 00 KSI lx= 0 161 INM
Pn= Aeff * Fn Sx= 0 117 IN'^3
= 6,561 LB rx= 0 637 IN
Pa= Pn/Qc ly= 0 262 INM
= 3,645 LB Sy= 0140IN'^3
P/Pa= 0 62 > 0 15 ry = 0 813 IN
< P/Pa + (Cmx*Mx)/(Max*ax) < 1 0 J = 0001 INM
P/Pao + Mx/Max<10 Cw = 0 000 iN'^e
Pno- Aeff * Fy xo = 0 000 IN
= 14,760 LB Kx = 1 2
Pao= Pno/Qc Lx = 30 00 IN
= 8,200 LB Ky = 1 2
Fe = Cb *ro*A*(aex*cit)''0 5/Sf Ly= 30 00 IN
= 149 KSI Kt = 1 0
I 78 * Fy, Fc = Fy Lt = 30 00 IN
Fc= 36 KSI Fy= 36 KSI
Pcr= n'^2EI/(kl)max'^2 ^ • 5= 11,300 KSI
' ='36,170 ib "- :.E=-29,500KSI
ax= {l/[l-(Qc*P/Pcr)]K-l Cmx= 0 85
= 0 89 Cb= 10
My= Sx * Fe Qb = 1 67
= 4,212 IN-LB Oc = 1 8
Max=Maxo= Mc/Qb
= 2,522 IN-LB
(2243 LB/3645 LB) + (0 85 x 987 IN-LB)/{2522 IN-LB x 0 89) =
(2243 LB/8200 LB) + (987 IN-LB/2522 IN-LB) =
0 99
0 66
< 1 0, OK
< 1 0, OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX {909) 869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
17
TC
2/19/2013
Overturning Analysis: Club Storage
Fully Loaded-
Movt= 32,309 IN-LB
= 20 LB X 16 Levels x 24 IN / 2
= 3,840 IN-LB
MpLapp = (0 67*300 LB X 5 Levels + 0 67*100 LB x 11 Levels) x 24 IN / 2
= 20,904 IN-LB
Vcol = 0 7*Vtotal
= 174 LB
Depth, d = 24 0 IN
Puplift = [0 75 x 0 7 X Movt - (0 6-0 llSos) x M^L - 0 75 x (0 6-0 145^) x MpL^pp] / d
= [0 75*0 7*32309 - (0 6-0 11*0 81)*3840 - 0 75*(0 6-0 14*0 81)*20904] IN-LB / 24 IN
= 307 LB <=== UPLIFT Allowable Tension = 790 LB
Allowable Shear = 900 LB
Interaction Equation # of Anchors per Double Foot Plate = 2
[307 LB/ 1580 LB] + [87 LB/ 1800 LB] = 0.24 < 1 2 Therefore OK
USE (2) 3/8"0 x 2" MIN EMBED HILTI KB-T7 (ICC ESR-1917) PER DOUBLE FOOT PLATE
USE (1) 3/8"0 X 2" MIN EMBED HILTI KB-TZ (ICC ESR-1917) PER SINGLE FOOT PLATE
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
18
TC
2/19/2013
LRFD Load Combination - Slab System
Load combination per RM) 2 2 Resultant Load combination
1
2
3
4
5
6
DL-total/col
PL-total/col
LL-total/col
14DL+12PL 14DL+12PL
1 2DL + 1 6PL + 1 6LL + 0 5{Lr or SL or RL) 1 2DL + 1 6PL + 1 6LL
1 2DL + 0 85PL + (0 5LL or 0 8WL) + 1 6(Lr or SL or RL) 1 2DL + 0 85PL + 0 5LL
1 2DL + 0 85PL + 0 5LL + 1 6WL + 0 5(Lr or SI or RL) 1 2DL + 0 85PL + 0 5LL
(1 2+0 2SDS)DL + (0 85+0 2SDS)PL + 0 5LL + EL + 0 2SL {1 2+0 2SDS)DL + (0 85+0 2SDS)PL + 0 5LL + EL
(0 9-0 2SD5)DL + (0 9-0 2SDs)PI-app - EL (0 9-0 2SDS)DL + (0 9-0 2SDs)PLapp - EL
200 LB
1,300 LB
323 LB
EL = 1,346 LB
Load combination 1
Pmax= 14DL+12PL
= 14x200 LB + 1 2 x 1300 LB
= 1,841 LB
Load combination 2
Pmax= 1 2DL+1 6PL+1 6LL
= 1 2 x 200 LB + 1 6 X 1300 LB +1 6 x 323 LB
= 2,838 LB
Load combination 3 & 4
Pmax= 12DL + 0 85PL + 0 5LL
= 1 2 X 200 LB + 0 85 X 1300 LB + 0 5 x 323 LB
= 1,507 LB
Load combination 5
Pmax =^ (1 2+0 2Sos}DL + (0 85+0 2SD5)PL + 0 5LL + EL
= (1 2+0 2*0 81) X 200 LB + (0 85+0 2*0 81) x 1300 LB + 0 5 x 323 LB + 1 0 x 1346 LB
= 3,096 LB
Load combination 6
Pmax = (0 9-0 2Sos)DL + (0 9-0 2SDs)PLapp - EL
= (0 9-0 2*0 81) X 200 LB + (0 9-0 2*0 81) x 871 LB -1346 LB
= -533 LB
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMANN HOBBS (SD)
19
TC
2/19/2013
Slab and Soil Check
The slab will be checked for puncture and bearing stress If no puncture occurs, the slab is assumed to distribute
the load over a larger area of the slab
Pmax = 3,096 LB
a) Puncture
Fpunct= 2 66x(F'c'^0 5)
= 2 66 X (2500 PSl)'^0 5
= 133 PSI
Apunct = [{Weff +t/2)+(Deff +t/2)] x 2 x t
= 1(5 25 IN + 5 IN/2) + (2 5 IN + 5 IN/2)] x 2 x 5 IN
= 128 IN'^2
fv/Fv= P/[(Apunct)(Fpunct)]
= 3096 LB/[128 lN'^2 x 133 PSI x 0 55]
= 0 33 < 1 0 OK
b) Bearing-
0Bn= O85x0xf'CxAl
= 15,340 LB
Pu / 0Bn = 3096 LB / 15340 LB
= 0 20 < 1 0 OK
c) Slab Tension
Asoil= P/[10xfsoil]
= 3096 LB/[1 0 X 1000 PSF/(144IN'^2/FT'*2)]
= 446 IN'^2
L = Asoil'^0 5
= (446 IN'^2)'^0 5
= 21 1 IN
B= [(Weff )(Deff )]'*0 5 + t
= [5 25INx2 5IN]'^0 5 + 5
= 8 6 IN
b = (L-B)/2
= (21 1 IN-8 6IN)/2
= 62 IN
Mconc = (w)(b'^2)/2 = [(1 0)(fsoil)(b'^2)]/[144 (IN'^2/FT'^2) x 2]
^ LI 0 X 1000 PSI X (6 25 IN)/^2]/[144 (IN'^2/FT'^2) x 2]
= 136 IN-LB
Scone = llNx(t'^2)/6
= llNx(5IN)/^2/6
= 4 17 IN'^3
Fconc =5x0 xf'c'^0 5
= 5x0 55x(2500 PSO'^O 5
= 137 5 PSI
fb/Fb = Mconc/[(Sconc)(Fconc)]
= 135 54 IN-LB/[(4 17 IN'^3)(137 5 PSI)]
= 0.24 < 1 0 OK
Base Plate.
Weff = 5 25 IN
Deff = 2 50 IN
Al= 13 13IN'^2
Concrete
t = 5 00 IN
fc= 2,500 PSI
Soil
fsoil= 1,000 PSF
0= 0 55
MATERIAL HANDUNG ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
30
TC
2/19/2013
Rack Support
Proiect Scope
The purpose of this analysis is to show that the following Interlake Storage Racks complies with Sectton 2208 of the
2010 California Building Code
The racks are prefabncated and are to be field installed only, without any type of field welding
Parameters
The Rack will be analyzed as Steel Storage Rack as specified in Section 2208 of the 2010 California Building Code
which references the RMI utilizing the formula
Where
Specifications
E = (2/3) X Fa X Ss X I X Wseismic / R
Fa = 1 03
Ss = 1 18
1=10
R = 4 0
Wseismic = 0 67*wPL + wLL/4 + wDL
Steel - Shaped steel, Astm A570 Grade 55, Fy = 55,000 psi
All others, Astm A36, Grade 36, Fy = 36,000 psi
Bolts - A307 unless otherwise noted
Welds - E70XX minimum required
Anchors- 1/2"0x 2-1/2" Mm Embed HILTI KB-TZ (ICC ESR--)917)
Slab - 5 in X 2500 psi
Soil - 1,000 psf
Load Combination as specified in Section 2 1 of the 2006 RMI
1 DL
2 DL LL + PL
3 (0 6-0 11SDg)DL -F 0 75*{0 6-0 14SDs)Plapp -0 75*0 7EL
4 ' (1+0 11SDS)DL + 0 75*(H-0 14SDS)PL 0 75*LL -t-0 75*0 7EL
Dead Load Cntical
Gravity Load Critical
Seismic Uplift Cntical
^Gravity Plus Seismic Critical
MATERIAL HANDUNG ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
31
TC
2/19/2013
Loads & Distribution
Rack Analysis will be based on Section 2208 of the 2010 CBC
E = (2/3) X Fa X Ss X 1 X Wseismic / R
Fa = 1 03
Ss = 1 18
Sps -0 81
1 = 1 0
R = 40
Wseismic = 0 67*wPL + wLL/4 -f wDL
# of Shelf #1 = 1
wPL = Olb < = = no pallet loads
wLL, deck = 100 psf Width / Bay = 80 00 in
wDL, rack = 100 lb Depth per Frame = 42 00 in
wDL, deck = 5 psf Tnbutary Depth = 90 00 in
Total PL-seismic = Oib
Total LL-seismic = 1,250 lb
Total LL = 5,000 lb
Total DL = 350 tb
Seismic Shear
0 7E = 0 7 X (2/3) X 1 03 X 1 18 X 1 X 1600 lb / 4
= 227 lb
Level wDL wLL/4 hx WX hx Fl Movt
1 350 lb 1,250 lb 96 0 in 153,600 in-ib 227 lb 21,780 in-lb
350 lb
Lonaitudinal Loads
1,250 lb
< = = Based Assumed to be pinned
153,600 in-lb 227 lb 21,780 in-lb 350 lb
Lonaitudinal Loads
1,250 lb
< = = Based Assumed to be pinned Mbase = 0 in-lb
1,250 lb
< = = Based Assumed to be pinned
Level Pcol-wDL Pcol-wLL Pcol-seismic Mcol Mconn-seismic
1 88 lb 1,250 lb 136 lb 5,445 in-lb 5,445 in-lb
Transverse Loads
Level Pcol-wDL Pcol-wLL Pcol-seismic
1 88 lb 1,2501b 259 lb
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
32
TC
2/19/2013
Static Column Analysis:
DL -f- LL -f PL
Analyzed per AISI Section properties are based on net effective sections
P= 1,338 1b
KxLx/rx = 1 7 X 96 in/1 273 in
= 128 2 < = = = (Kl/r)max
KyLy/ry = 1 x42in/1 17 in
35 9
ro= (rx'^2-F ry''2-F xo'^2)''0 5
= 3 343 in
8= 1-(xo/ro)"2 (EQ C4 2-3)
= 0 268
Fe IS taken as the smaller of Fel and Fe2
Fe1= Tr'^2E/(KL/r)max'^2 (EQ C4 1-1)
= 17 7ksi
aex= TT2e/(KxLx/rx}" 2 (EQ C3 1 2-7)
= 17 7ksi
at= 1/Aro'"2[GJ+(7r'' 2ECw)/(KtLt)'^2] (EQ C3 1 2-9)
= 58 8 ksi
Fe2= 1/{2B)*{(aex-Fat)-[(oex-Fat)'^2-(4*B*aex*ot)]'^0 5} (EQ C4 1-1) Section Properties
= 14 3 ksi A= 3 000 in
Fe= 14 3 ksi B= 3 000 in
Fy/2= 27 5 ksi C= 0 750 in
Since, Fe < Fy/2 t = 0 070 in
Then, Fn= Fe (EQ C4^) Aeff = 0 600 in 2
- 14 3 ksi lx = 0 974 in ^ 4
Pn= Aeff X Fn (EQ C4-2) Sx = 0 649 in 3
= 8,599 lb rx = 1 273 in
Qc= 1 92 ly = 0 822 in 4
Sy = 0 491 in "3
Pa= Pn/Qc (EQ C4-1) ry = 1 170 in
= 4,479 lb J -0 001 in ^4
Cw = 2 307 in 6
P/Pa= 0 30 xo = -2 861 in
Kx = 1 7
Lx = 96 0 in
Ky = 1 00
Ly = 42 00 in
Kt = 1 00
Lt = 42 00 in
Fy= 55 ksi
G = 11,300
• E= 29,500 ksi
• * - t"*" '
Cmx= 0 85
Cb= 1 0
Qf= 1 67
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
33
TC
2/19/2013
Lonqltudinal Column Analysis:
(1-1-0 11 SDO)DL -1- 0 75*LL -i-0 75*0 7EL
Analyzed per AISI Section properties are based on net effective sections
P= 1,135 lb
M= 4,084 in-lb
KxLx/rx = 1 7 X 96 in/1 273 in
= 1282 < = = = (Kl/r)max
KyLy/ry = 1 x42in/1 17 in
35 9
ro= (rx 2 + ry " 2 -F xo 2) ^ 0 5
= 3 343 m
8= 1-(xo/ro)"2 (EQ 04 2-3)
= 0 268
Fe IS taken as the smaller of Fel and Fe2
Fe1= Tr'^2E/(KL7r)max^2 (EQ C4 1-1)
= 17 7 ksi
aex= 7r'^2E/{KxLx/rx)^ 2 (EQ C3 1 2-7)
= 17 7 ksi
C5t= 1/Aro^2[GJ-F(Tr'' 2ECw)/(KtLt)^2] (EQ C3 1 2-9)
= 58 8 ksi
Fe2= 1/(2B)*{(aex-Fat)-[(aex+CTt}-^2-(4*6*aex*at)I^0 5} (EQ C4 Section Properties
= 14 3 ksi A= 3 000 m
Fe= 14 3 ksi B= 3 000 in
Fy/2= 27 5 ksi C= 0 750 in
Since, Fe < Fy/2 t = 0 070 in
Then, Fn= Fe (EQ C4^) Aeff = 0 600 in 2
- 14 3 ksi lx = 0 974 in 4
Pn= Aetf X Fn (EQ C4-2) Sx = 0 649 in ^ 3
= 8,599 lb rx = 1 273 in
Oc= 1 92 ly =
Sy =
0 822 in''4
0 491 in ^3
Pa= Pn/Oc (EG C4-1) ry = 1 170 in
- 4,479 lb J ^
Cw =
0 001 in'^4
2 307 in ^6
P/Pa= 0 25 > 015 xo = -2 861 in
Thus, Check P/Pa -F (Cmx*Mx)/(Max*)Ux) < 1 0 (EQ C5-1) Kx = 1 7
P/Pao + Mx/Max < 1 0 (EQ C5-2) U = 96 0 in
Pno= Ae X Fy Ky = 1 00
= 33,000 lb Ly = 42 00 in
Pao= Pno/flc Kt = 1 00
= 17,188 lb Lt = 42 00 in
Me= Cb*ro*Aeff*(aey*CTt)'"0 5 Fy= 55 ksi
= 231 in-kip G= 11,300
My= Sx*Fy E= 29,500 ksi
= 35,695 lb
Mc= My[1-My/(4Me)]
= 34,3171b Cmx= 0 85
Max=Maxo= Mc/Of Cb= 1 0
= 20,549 lb nf= 1 67
fix^ {1/[1-(Qc*P/Pcr)]}'^-1
= 0 80
(1135 lb/4479 lb) -F (0 85 x 4084 in-lb)/(20549 in-lb xO 8) = 0 47 < 1.0, OK (EQ C5-1)
(1135 lb/17188 lb) -F (4084 in-lb/20549 in-lb) = 0 26 < 1.0, OK (EQ C5-2)
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989/FAX (909)869-0981
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
34
TC
2/19/2013
Transverse Column Analysis:
(1 -FO 11 SDS)DL + 0 75*LL -FO 75*0 7EL
Analyzed per AISI Section properties are based on net effective sections
PCQl= 1,227 lb
KxLx/rx = 1 7 X 100 in/1 273 in
= 133 5 < = = = (Kl/r)max
KyLy/ry = 1 x50in/1 17 in
= 42 7
(KL/r)max = 133 5
ro=- (rx-"2 -f- ry'^2 + xo ^"2) ''0 5
= 3 343 in
13= 1-(xo/ro)''2 (EQ C4 2-3)
= 0 268
Fe IS taken as the smaller of Fel and Fe2
Fel= Tt'^2E/(KL/r)max''2 (EQ C4 1-1)
= 16 3 ksi
Section Properties
aex= Tr'"2E/(KxLx/rx)'"2 (EQ C3 1 2-7) A= 3 000 in
= 16 3 ksi B= 3 000 in
at= 1/Aro"2[GJ-F(7i'^2ECw)/(KtLt)''2] (EQ C3 1 2-9) C= 0 750 in
= 39 1 ksf t = 0 070 in
Fe2= 1/{20)*{(aex-f-ot)-[(<Tex-l-CTt) ''2-(4*0*CTex*cTt)] "0 5> (EQ C4 M) Aeff = 0 600 in 2
= 12 2 ksi lx = 0 974 in "4
Sx = 0 649 in ^3
Fe= 12 2 ksi rx = 1 273 in
Fy/2- 27 5 ksi ly = 0 822 in'•4
Since, Fe < Fy/2 Sy = 0 491 in'^3
Then, Fn= Fe (EQ 04-4) ry = 1 170 in
= 12 2 ksi J = 0001 in^4
Cw = 2 307 in ^ 6
Pn = Aeff X Fn (EQ C4-2) xo = -2 861 in
= 7,342 lb Kx = 1 7
Lx = 100 0 in
nc= 1 92 Ky = 1 00
Ly = 50 00 in
Kt = 1 00
Pa= Pn/Qc (EQ C4-1) Lt = 52 00 in
= 3.824 lb Fy= 55 ks)
G = 11,300
: P>col/Pa=~ 0 32 < 1 0, OK E=:29,500 ksi
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
PROJECT
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
35
TC
2/19/2013
Beam Analvsig
Beam to column connections provide adequate moment capacity to stabalize the system, although it does not provide
full fixity Thus, the beams shall be analyzed assuming partial end fixity In justifying the beam to column moment
connection, the partial end fixity moment will be added to the Longitudinal frame moment for the analysis of the
connection
% End Fixity = 25 %
Effective Moment for Partiallv Fixed Beam
For simply supported beams, the max imum moment at the center is given by wL'^ 2/8 An assumption partial
fixity will decrease the maximum moment by the following method
0 = 025
Thus,
Mcenter = Mcenter(simple ends) - 0*Mcenter(fixed ends)
= wL''2/8-{0 25'wL'^ 2/12)
= wL"2/8 - wL^2/48
= 0 104 * wL2
Reduction
Coeff8= 0 104/0 125
= 0 832
Mcenter = e*(wL^2/8)
= 0 832 X (wL ^ /8)
Mends = 0*Mmax(fixed ends)
= (WL'"2/12)*0 25
= 0 0208 X wL " 2
Mcenter(simple)
TOPICAL BEAM FRONT VIEW
Efective Deflection tor Partially Fixed Beam
For simply supported beam conditions, the maximum deflection at the center is given by 5wL ^ 4/384EI An
assumption of partial fixity will decrease this maximum deflection by the following method
Amax= S * [5w(L) ^4/(384*E*lx)]
r SEIZMIC ^
i_ IISic ^ PROJEa
MATERIAL HANDLING ENGINEERING SHEET NO
TEL (909) 869-0989 / FAX (909) 869-0981 CALCUUTED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
36
TC
2/19/2013
Beam Analysis cont.
Live Load = 5,000 lb
Dead Load = 350 lb
End fixity = 25 %
Mcenter = 0 104*wL'"2
= 22,256 in-lb
Mends = 0 0208xwL'"2
= 3,338 in-lb
Lmax= [1950-F1200(M1/M2)]b/Fy
M1/M2 =0 15 < = = = Since Mcenter > Mends
Lmax = (1950 + 180) x 2/55
= 77 5 tn < L
Thus, Fb = 0 6 X Fy
= 33,000 psi
Maximum Static Load per Level depends on
1) Moment Caoacitv
if, fb = M/Sx
Then, 0 6 * Fy = (B*wL ^ 2/8)/Sx
Thus,
Max Wt /Level = [9 6*Fy*Sx/(l3 * L)]*a
= (9 6* 55 KSI * 0 746 IN ^ 3)/(0 832*80 IN)*1
= 5,918 lb/Level < = = = Governs
QR,
2) Allowable Deflection
Beam Properties
lx = 1 589 in'^4
Sx = 0 746 in "3
Fy = 55,000 psi
Length=L = 80 0 in
a = 4 000 in
If, Dallow = L/180
= 0 444 IN
And, D= [5w(L)"4/(384*E*ix}l*R
Then,
Max Wt /Level = 2* [(384*E*lx*Aallow)/(5*L 3 * 8)]
= 7,385 lb/Level
b = 2 000 in
Thus, Maximum Allowable Ljve Load / Level = 5,568 lb/Level |
MATERIAL HANDUNG ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
37
TC
2/19/2013
Beam to Column Connection Analysis
Mconn max= Mconn seismic -F Mend
5,445 in-lb
Connection capacity depends on the following parameters
1) Shear capacitv of the studs
Stud 0 = 7/16 in
Fy= 55,000 psi
Pmax-shear= 0 4 x Fy x Area
= 0 4 X 55000 psi x (0 4375 in)2 x 7T/4
= 3,3071b
2) Beannq capacitv on column
tcol= 0 074 in
Fu= 65,000 psi
Pmax-brg= Bearing Area * Fbeanng
= (tmin * thickness) "(10' Fu)
= (0 4375 IN * 0 074 IN) * (1 0 *65000 PSI)
= 2,104 4 LB < 3307 lb
3) Moment capacitv of bracket
Mcap= Sbracket * Fbending
= 0 11 in 3 X 0 66 x Fy
= 3,993 in-lb
C- Mcap/0 75 = 1 11 x P1
Thus, PI = 1 2 X Mcap
= 4,792 in-lb > 3307 3 lb
Thus, the Governing value is the minimum value of PI,
P1-eff= 2,104 lb
Mconn-allow= PI x 4 5 in -F P2 x 0 5 in
= 4 55 X Pl-eff
= 9,575 in-lb > Mconn max, OK
C = P^ +P2
= P1-FP1*(0 5/4 5)
= 1 11*P1
Sbracket = 0 110 in^3
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
38
TC
2/19/2013
3 75 * Vtransv/2= 85 lb
Diagonal Member
Transverse Brace Analysis
It IS assumed that the transverse braces resist the seismic shear in tension and compression, with compression
being critical in the design
Ldiag= f(D-3")"2 + (H-6")^21^'^
= 53 1 in
Pmax= V*(Ldiag/D)
= 1081b
(kl/r)max= (k x Ldiag)/r mm
= 1 X 53 1 in /O 52 in)
= 102 1 in
Fe= Tr^E/(kl/r)'
= 27,474 pSi
Since Fe>Fy/2,
Fn= Fy*{1-fy/4fe)
= 27,251 psi
Pn= Area x Fn
= 0 259 in2x27251 psi
= 7.058 lb
Pallow= Pn/Qc
= 7058 LB /I 92
= 3,676 lb
fa/Fa=
Honzontal Member
0 03 < 1 0 OK
(kl/r)max= (k * Lhoriz)/r mm
= (0 8 X 42 IN /O 52 IN )
= 64 6 IN
Fe= 7i^E/(kl/r)^
= 68,553 PSI
Fy/2= 25,000 PSI
SINCE Fe>Fy/2, Fn=Fy*(1-fy/4fe)
= 40 883 PSI
Pn= AREA*Fn '
= 0 259IN^2*40883 PSI
= 10,589 LB
Pallow= Pn/Oc
= 10589 LB/I 92
= 5,515 LB
LOWER BRACE PANEL ELEVATION
H= 42 00 in
D= 42 00 in
Diagonal Member
C1.5 X 1 5 X 16ga
A = 1 500 in
B = 1 500 in
t = 0 060 in
AREA= 0 259 in ^2
r min= 0 520 in
Fy= 50,000 psi
Honzontal Member
01.5x1 5x16ga
A = 1 500 in
B = 1 500 in
t = 0 060 in
AREA= 0 259 in'^2
r min= 0 520 m
Fy= 50 000 psi
Oc= 1 92
fa/Fa= 0 02 < 1 0 OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
39
TC
2/19/2013
Overturning Analysis
Full Loaded Condition
0 7E = 227 lb
Movt= 0 75*5;(Fixhi)
= 16,335 in-lb
Mst = [(0 6-0 11SDS)DL -F 0 75*(0 6-0 USoslPLapp] x Depth / 2
= 13.334 in-!b
Puplift = (Movt - Mst) / Depth
= (16335 in-lb - 13334 in-lb) / 42 in
= 71 lb
Allowable Tension = 830 lb
Allowable Shear = 900 lb
# of Anchors / Plate = 2
Depth = 42 00 in
Vcol = 57 lb
Interaction Eqn. [71 lb/1660 lb] + [57 lb/1800 lb] = 0 06 < 1 2 Therefore, Ok
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
40
TC
2/19/2013
Base Plate Analysis
Pool,max = 1,338 lb
Mb = in-lb
Effective Base Width (B) = 8 00 m
Effective Base Depth (D) = 5 00 in
b = 3 00 in
b1 = 2 50 in
Thickness (t) = 0 375 in
Fy = 36,000 pSi
fa =P/A = Pcol/(D x B) = 33 4 psi
fb = Mb/(DxB ^ 2/6) = 0 0 psi
fb2 = 2xb1xfb/B = OOpsi
fbl = fb-fb2 = 0 0 psi
Mbase = wbl ^^2/2 = b1 ^2/2[fa -F fbl -F 67fb2]
Mbase =104 in-lb
Sbase=(1)(t'^2)/6 = 0 02 m'^3
Fbase = 0 75 x Fy = 27,000 psi
fb/Fb = Mbase/(Sbase x Fbase)
0 17 < 1.0, OK
J5I
b1
Pcol
b1
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
41
TC
2/19/2013
Load Combination for Slab Analysis
Load combination per 2006 RMI
1) 1 4DL + 1 2PL
2) 1 2DL -F 1 4PL -F 1 6LL + 0 5(SL or RL)
3) 1 2DL -F 0 85PL -F 0 5LL -F 1 6(SL or RL)
4) 1 2DL -F 0 85PL + 0 5LL -F 1 3WL + 0 5(SL or RL)
5) (1 2-FO 2SDS)DL + (0 85-FO 2SDS)PL + EL -F 0 5LL -F 0 2SL
DL-total/col = 88 lb
LL-total/col = 1,250 lb
EL = 370 lb
Load combination 1
Resultant Load combination
1 4DL
1 2DL -F 1 6LL
1 2DL -F 0 5LL
1 2DL -F 0 5LL
(1 2-FO 2SDS)DL -F 0 5LL -F EL
Pmax = 1 4DL
= 1 4 X 88 lb
= 123 lb
Load combination 2
Pmax = 1 2DL -F 1 6LL
= 1 2x88 lb + 1 6 X 1250 lb
= 2,105 lb
Load combination 3 St 4
Pmax = 1 2DL + 0 5LL
= 12x88lb-F05x 1250 lb
= 730 lb
Load combination 5
Pmax = (1 2+0 2SDS)DL -F 0 5LL -F EL
= 1 36 X 88 lb -i- 0 5 X 1250 lb -F 370 lb
= 1,1151b
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS 9SD)
42
TC
2/19/2013
Slab & Soil Analysis
The slab will be checkecj for puncture and beanng stress If no puncture occurs, the slab is assumed to distribute
the load over a larger area of the slab
a) Puncture
Pmax = 2,105 lb
Fpunct= 2 66>c(Fc''0 5)
= 2 66 X (2500 psi) "0 5
= 133 psi
Apunct = [(Weff -i-t/2) + (Deff -Ft/2)] x 2 x t
= [(8 in -F 5 m/2) -F (5 in + 5 in/2)] x 2 x 5 in
= 180 in "2
fv/Fv = P/[Apunct X Fpunct]
= 2105 lb/[180 in " 2 X 133 psi X 0 55] 0 16 < 1 0 OK
b) Bearing
0Bn = 0 85x0 xfcxAl
= 46,750 lb
Pu/0Bn = 2105 lb/48750 lb
c^ Slab Tension
0 05 < 1 0 OK
Asoil = P/[1 0 X fs]
= 2105 lb/[1 0x1000 psf/(l44 in"2/ft'^2)l
= 303 in 2
L = Asoil '^0 5
= (303l2in'^2)"05
= 17 4 in
B ^ [Weff xDeff]'"0 5 -F t
= [8 m X 5 in] '^0 5 -F 5 in
= 11 4 in
b = (L-B)/2
= (17 41 in-11 4in)/2
= 3 0 in
Mconc = (w)(b'^2)/2 = [(1 0)(fs)(b'^2)]/[144 (m "2/ft2) x 2]
= [1 0x1000psix(3in)'^2]/[144(in'^2/ft'^2)x2]
= 31 in-lb
Scone = 1 in X (t'^2)/6
= 1 mx (5 in)'^2/6
= 4 17in "^3
Fconc = 5x0xfc'^O5
= 5x055 X (2500 psi)''0 5
= 137 5 psi
fb/Fb = Mconc/[Sconc x Fconc]
= 31 33 in-lb/[{4 17 in ^ 3) (137 5 psi)]
Base Plate
Weff
Deff
8 00 in
5 00 in
Al = 40 0 in 2
Concrete"
Thickness = 5 00 in
fc = 2,500 psi
Soil
fs = 1,000 psf
0= 0 55
0 05 < 1 0 OK
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909) 869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS (SD)
43
TC
2/19/2013
SCOPE
VERIFY ADEQUACY OF THE STAIRWAY SYSTEM TO MEET THE REQUIREMENTS OF THE 2010 CBC
THE ANALYSIS IS BASED ON A STAIRWAY SERVING AREAS THAT ARE NOT ACCESSIBLE TO THE GENERAL PUBLIC
AND THAT HAVE AN OCCUPANT LOAD OF LESS THAN 50
PARAMETERS:
STEEL - Fy= 46000 PSI
BOLTS - Fv= 10000 PSI (A307)
DESIGN LOAD 100 PSF DISTRIBUTED
300# CONCENTRATED (TREAD)
200 # (POST/HANDRAIL)
CONFIGURATION:
Lvert= 96 0 IN
Lhoriz= 144 0 IN
Hl= 38 00 IN
Lrail= 42 00 IN
WIDTH= 36 00 IN
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989/FAX (909)869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS (SD)
44
TC
2/19/2013
TREAD ANALYSIS
BENDING
THE TREADS SHALL BE ANALYZED FOR A WORST CASE
LOAD SITUATION FROM THE FOLLOWING LOAD CASES
fa) CONCENTRATED LOAD AT CENTER
Mpoint= PL/4
= 300 LB* 36 IN/4
= 2,700 IN-LB
fb) DISTRIBUTED LOAD
w = (100 PSF) * (12 IN/12 IN/FT)
= 100 0 LB/FT
= 83 LB/IN
= 2700 IN-LB/2 9773 IN'^3
= 907 PSI
Fb= 0 6*Fy
= 27,600 PSI
fb/Fb=
DEFLECTION
0 03 <1.0 OK
TREAD WIDTH
w
A" 7^
d= 12 0 IN
Mdist= w*L'^2/8 b= 2 0 IN
= 8 3 LB/FT * (36 IN)'>2/8 t= 0 105
1,350 IN-LB WIDTH=L= 36 0 IN
1= 14 89 INM
THUS, Mmax= 2,700 IN-LB S= 2 98 IN'^3
Fy= 46,000 PSI
fb= Mmax/S E= 29,000 KSI
TREAD OK FOR BENDING
D= 5WL'^4/384EI
= 000 IN
Dallow= L/240
= 36 IN/240
0 15 > ACTUAL DEFLECTION, OK
TREAD OK FOR DEFLEaiON
MATERIAL HANDUNG ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS (SD)
45
TC
2/19/2013
STRINGER ANALYSIS
DEAD LOADS
STRINGER= 7 LB/FT
TREADS= 10 LB/FT
HANDRAILS= 2 LB/FT
WDL= 19 LB/FT
LIVE LOAD
BENDING
WLL= LIVE LOAD ' TRIB WIDTH
= 100 PSF* (36 IN/12 IN/FT)/2
= 150 LB/FT
W= WDL+WLL
= 169 LB/FT
= 14 1 LB/IN
Mdist= w*L'^2/8
= 14 1 LB/FT * (144 IN)'^2/8
= 36,504 IN-LB
THUS, Mm3X= LIVE LOAD * TRIB WIDTH
fb= Mmax/S
= 36504 IN-LB/4 0688 IN'^3
= 8,972 PSI
Fb= 0 6*FY
= 27,600 PSI
HI
Lnoriz
Lvert
I ^
fb/Fb= 0.33 <10 OK STRINGER
Lvert= 96 0 IN
DEFLECTION Lhoriz= 144 0 IN
Hl= 38 0 IN
D= 5WL'^4/384EI Lrail= 42 0 IN
= 134 IN STAIR WIDTH= 36 0 IN
lx= 20 34 INM
Dallow= L/240 Sx= 4 07 IN'^3
= 173 1 IN/240 A= 10 IN
-0 72 > ACTUAL DEFLECTION, OK 8= 2-3/8 IN
! t= 0 1046 IN
STRINGER OK FOR DEFLECTION Fy= 46,000 PSI
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)859-0981
161 ATLANTIC STREET POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS (SD)
46
TC
2/19/2013
TREAD ATTACHMENT
ATTACH TREAD TO STRINGER WITH (2) 0 375 IN DIAMETER BOLTS PER SIDE
Vbolt= 100 PSF * 3 FT/2
= 150 LB <=== SHEAR PER ATTACHMENT
Vallow= Fv * AREA * # OF BOLTS
= 10000 PSI * (0 375 )'^2*(3 14159/4) * 2
= 2,209 LB > Vbolt OK
STRINGER ATTACHMENT
ATTACH STRINGER TO PLATFORM WITH (2) 0 375 IN DIAMETER BOLTS
Vbolt= 169 LB/FT * 12 FT/2
= 1,014 LB <=== SHEAR PER ATTACHMENT
Vallow= Fv * AREA
= 10000 PSI * (0 375 )'^2*(3 14159/4)* 2
= 2,209 LB > Pbolt OK
CONCRETE BEARING
LOWER BRACKET IS 4 5 IN x 2 75 IN
AREA= 12 38 IN'^2
Pend= 1,014 LB
fp= Pend/AREA
= 82 PSI
Fp= 0 7 *f'c
1,750 PSI
fp/Fp=
ANCHORAGE
0.05 < 10 OK
USE (1) 0 5 IN DtA X 2 5 IN MIN EMBED HILTI KB-TZ (ICC ESR-1917) ANCHORS PER BASE
MATERIAL HANDLING ENGINEERING
TEL (909) 869-0989 / FAX (909)869-0981
161 ATLANTIC STREET, POMONA, CA 91768
PROJEa
FOR
SHEET NO
CALCULATED BY
DATE
COBRA-PUMA GOLF
NAUMAN HOBBS (SD)
47
TC
2/19/2013
POST AND HANDRAIL
PER THE REQUIREMENTS, THE POST AND HANDRAIL MUST RESIST A POINT LOAD OF 200 LB
POST
Mmax= P* Hl/2
= 200 * 38lN/2
= 3,800 IN-LB
fb= M/S
= 24,051 PSI
Fb= 0 66*Fy
= 30,360 PSi
fb/Fb= 0 79
HANDRAIL
Mmax= P* Lrail/4
= 200 * 42 IN/4
= 2,100 IN-LB
fb= M/S
= 21,000 PSI
Fb= 0 6*Fy
= 27,600 PSI
fb/Fb= 0 76
LOAD IS SHARED BETWEEN 2 POSTS
HAND RAT
HI
< 1 0 OK
i.hori:
Lvert
l-5/8"0 D X 13 GA
POST
Sx= 158IN'^3
Fy= 46,000 PSI
< 1 0 OK
t-l/2"0D xl6GA
Sx= IOOIN'^3
Fy= 46,000 PSI
SAN DIEGO REGIONAL
HAZARDOUS MATERIALS QUESTIONNAIRE
OFFICE USE ONLY
UPFP#
HV«
BP DATE I L
Business Name
CoSfi^ TUAV\ 6vou/^
Business Contact Telephone #
Project Address City State Zip Code
f l-ooS
APN#
Mailing Address City state Zip Code Plan File#
Project Contact Telephone #
The following questions represent the facility's activities, NOT the specific project descnption
PART I FIRE DEPARTMENT - HAZARDOUS MATERIALS DIVISION OCCUPANCY CLASSIFICATION Indicate by circling the item, whether your business
will use, process, or store any of the following hazardous materials If any of the items are circled, applicant must contact the Fire Protection Agency with
junsdiction pnor to plan submittal
5 Organic Peroxides 9
6 Oxidizers 10
7 Pyrophoncs 11
8 Unstable Reactives 12
1 Explosive or Blasting Agents
2 Compressed Gases
3 Flammable/Combustible Liquids
4 Flammable Solids
Water Reactives
Cryogenics
Highly Toxic or Toxic Materials
Radioactives
13 Corrosives
14 Other Health Hazards
<^5^one of These
PART II SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH - HAZARDOUS MATERIALS DIVtSIONS fHMDl If the answer to any of the
questions is yes, applicant must contact the County of San Diego Hazardous Matenals Division, 1255 impenal Avenue, 3'" floor, San Diego, CA 92101
Call (619) 338-2222 pnor to the issuance of a building permit
/ / FEES ARE REQUIRED Expected Date of Occupancy
YES
•
•
•
•
•
•
NO
Si
(SL
Is your business listed on the reverse side of this fomi? (check all that apply)
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities equal to or greater than
55 gallons, 500 pounds, 200 cubic feet, or caranc^ens/reproduclive (oxins in any quantity'?
Will your business use an existing or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article ^0p
• CalARP Exempt
/ Date Initials
• CalARP Required
/ Dale Initials
• CalARP Complete
I
Date Iniliats
PART III SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT If the answer to any of the questions below is yes. applicant must contact the Air
Pollution Control Distnct (APCD), 10124 Old Grove Road, San Diego, CA 92131-1649, telephone (858) 586-2600 prior to the issuance of a building or demolition
permit Note if the answer to questions 3 or 4 is yes, applicant must also submit an asbestos notification form to the APCD at least 10 working days prior to
commenang demolition or renovation, except demolition or renovalion of residential structures of four units or less Contact the APCD for more information
1
YES
•
•
D
•
B
Will the subject facility or construction activities include operations or equipment that emit or are capable of emitting an air contaminant? (See the
APCD factsheet at http y/www sdapcd org/info/facts/permits pdf, and the list of typical equipment requmng an APCD permit on the reverse side
of this fnDm Contact APCD if you have any questions)
(ANSWER ONLY IF QUESTION 1 IS YES) Will the subject facility be located within 1,000 feet of the outer boundary of a school (K through la)?
(Public and pnvate schools may be found after search of the California School Directory at http //www cde ca gov/re/sd/. or contact the
appropnate school distnct)
Will there be renovation that involves handling of any fnable asbestos matenals, or disturbing any matenal that contains non-friable asbestos?
Will there be demolition involving the removal of a load supporting structural member?
Bnefly descnbe business activities Bnefly descnbe proposed project
^U^cVifJGt fz>IL ^OL^ £^€M£tyr 57^Mcs.i^
I d^lare under penalty of perjury that to the t>est of my knowledge and belief,
Name of owner or Authonzed Agent
tiiefibe responses madeJie lerein are true and correct
Signature of Owner or AuthonzefMiSSnt Date
FOR OFFICIAL USE ONLY
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION
BY DATE
EXEMPT OR NO FURTHER INFORMATION HEQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMD APCD COUNTY-HMD APCD COUNTY-HMD APCD
HM-9171 (04/07) County of San Diego- DEH - Hazardous Matenals Division
CB130608 1818 ASTON AV
COBRA GOLF= INSTALL SHELVING
CATWALK SYSTEM
• cv
4 ,s(l5 -^'-'^
niwi infp. Approved Date By
BUILDING cu
PLANNING tna
ENGINEERING ^
FIRE Expedite? Y f N^
AFS Checked tjy
HazMat
h?CO
Health
Forms/Fees Sent Reed Due? By
ErKina Y N j
Fire ^ 1 __ V N
HazHealthAPCD V N
PE&M 1 ' V N
School r N
Sewer V N
Stormwater Y N
Special Inspection Y N
CFD- Y N
LandUse Density- ImpArea FY Annex: Factor
PFF Y N
Continents Date Date Date Date
Building
Planning
Engineering
Fire
Need?
• Done
• Done
• Done
• Done
S W a Issued