HomeMy WebLinkAbout1905 ASTON AVE; 101; CB152245; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
08-31-2015 Commercial/Industrial Permit Permit No: CB152245
Building Inspection Request Line (760) 602-2725
Job Address: 1905 ASTON AV CBADSt: 101
Permit Type: Tl Sub Type: IN DUST Status: ISSUED
Applied: 07/17/2015
Entered By: LSM
Parcel No: 2121201300 Lot#: 0
Valuation: $138,711.00 Construction Type: 58
Occupancy Group: Reference# Plan Approved: 08/31/2015
Issued: 08/31/2015
Inspect Area
Plan Check #:
Project Title: ADVANCED BIOLOGICS= CONSTRUCT
CLEAN ROOM IN EXIST WAREHOUSE 2,576 SF// RESTROOM/SHOWER
AREA RENOVATION OF 626 SF// BREAKROOM SINK//PLUMB/MECH/
ELECT
Applicant:
MICHELE ARNOLD KUSH
925 FORT STOCKTON
SAN DIEGO CA 92103
619-297-6153
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Building Permit Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Reel. Water Con. Fee
Green Bldg Stands (SB1473) Fee
Fire Expedidted Plan Review
$764.51
$0.00
$535.16
$0.00
$0.00
$38.84
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$6.00
$430.00
Total Fees: $2,202.57 T tal Payments To Date:
Inspector: Date:
Owner:
H&M EAGLE L P
P 0 BOX 3802
RCHO SANTA FE CA 92067
Meter Size
Add'l Reel. Water Con. Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (31 04193)
License Tax (4304193)
Traffic Impact Fee (31 05541)
Traffic Impact Fee (4305541)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
HMP Fee
Green Bldg Standards Plan Chk
TOTAL PERMIT FEES
$2,202.57 Balance Due:
Clearance:
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$243.00
$143.00
$42.06
$0.00
$0.00
$0.00
$0.00
??
??
$2,202.57
$0.00
NOTICE: Please take NOT t approval of your project includes the "Imp sition" fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." Y u have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which au have reviousl been iven a NOTICE similar to this or as to which the statute of limitations has reviousl otherwise ex ired.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNING 0ENGINEERING OBUILDING OFIRE OHEALTH []HAZMATIAPCD
( Cicyof Building Permit Application Plan Check No. C-/.3 I :;;-.!). ;).-L/ $
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value J3g1 71 I
Carlsbad Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Deposit 5:3GP ·I~ email: building@carlsbadca.gov
www.carlsbadca.gov Date 7}17}1~ I
JOB ADDRESS SUITE#/SPACE#/UNIT# SUITE<8IAP~ l.;t -lXJ 1905 ASTON AVENUE 101 -;3 -cz:;
CT/PROJECT # I LOT# I PHASE# I# OF UNITS I# BEDROOMS #BATHROOMS ITENA~~~~~2~~ BIOLOGICS I CONS~NTYPE I occ ;OUP 63
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
TENANT IMPROVEMENT INCLUDES CONSTRUCTION OF CLEAN ROOM IN EXISTING WARE HOUSE WITH INDEPENDENT LIGHTING AND MECHANICAL SYSTEM. INTERIOR SUITE WORK INCLUDES
RENOVATION OF (4) RESTROOMS AND SHOWER TO INCLUDE REPLACEMENT OF (5) TOILETS, (1) URINAL, (1) NEW TOILET, AND (1) NEW SINK. BREAKROOM SCOPE INCLUDES REPLACEMENT OF
NON-COMPLIANT BASE CABINET WITH SINK. TENANT IMPROVEMENT WILL INCLUDE STRUCTURAL WORK FOR CLEAN ROOM. TENANT IMPROVEMENT WILL INCLUDE NON-LOAD BEARING PARTITIONS
ONLY. EXISTING CEILING, AND NEW LIGHTING AT RESTROOMS. HVAC I MECHANICAL SYSTEMS ARE EXISTING AT TENANT SPACE, NEW AT CLEAN ROOM. RESTROOM I SHOWER AREA OF IMPROVEMENT:
626 SQ FT APPRO X. CLEAN ROOM AREA OF IMPROVEMENT: 2,576 SQ FT APPROX.
EXISTING USE lPROPOSED USE I GARAGE (SF) PATIOS (SF) I DECKS (SF) FIREPLACE I AIR CONDITIONING I FIRE SPRINKLERS
VACANT B, S-1 YES[)! Noi2J YES[Z]No0 YES(Z]No0
APPLICANT NAME• MICHELE ARNOLD KUSH PROPERTY OWNER NAME E.G.L.L. LLC ............... _
ADDRESS ADDRESS 925 FORT STOCKTON 5414 OBERLIN DRIVE STE. 140
CITY STATE ZIP CITY STATE ZIP
SAN DIEGO CA 92103 SAN DIEGO CA 92121
PHONE rAX PHONE .I FAX 619 297 6153 619 299 6072
EMAIL EMAIL
MICHELE(OlSAFDIERABINES.COM
DESIGN PROFESSIONAL MICHELE ARNOLD-KUSH CONTRACTOR BUS. NAME WHITE CONSTRUCTION
ADDRESS ADDRESS
925 FORT STOCKTON 2524 GATEWAY ROAD
CITY STATE ZIP CITY STATE ZIP
SAN DIEGO CA 92103 SAN DIEGO CA 92009
PHONE I FAX PHONE I FAX 619 297 6153 619 299 6072 760.931.1130 760.931.1171
EMAIL EMAIL
MICHELE@SAFDIERABINES.COM SEAN@WHITECONSTRUCTIONINC.COM I STATE LIC. # STATE LIC.# 'CLASS B I CITY BUS8I19950 11681 452513
(Sec. 7031.5 Bus1ness and Professions Code: Any C1ty or County wh1ch requ1res a permit to construct, alter, Improve, demoliSh or repa1r any structure, prror to 1ts ISsuance, also requ1res the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a c1vil penalty of not more than five hundred dollars [$500}).
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one ofthe following declarations:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. 0 I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carr'1er and policy
number are: Insurance Co ____ ____!=IIEREST NATIONAL INSURANCE CO Policy No. 7600014158151 Expiration Date 01·01·2016
This section need not be completed if the permit is for one hundred dollars ($100) or less. 0 Certificate of Exemption: I certify that in the of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure 1 coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000}, in
addition to the cost of compensation, damages as 3706 of the Labor code, interest and attorney's fees.
,g CONTRACTOR SIGNATURE
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D
D
D
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s} licensed pursuant to the Contractor's License Law).
I am exempt under Section _____ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. DYes 0No
2. I (have I have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work):
,g PROPERTY OWNER SIGNATURE 0AGENT DATE
I
I
'
I certify that I have read the application and state that the above infonnation is conectand that the infonnation on the plans is accurate. I agree to comply with all City ordinances and State law.; relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes.! ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CI1Y OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CI1Y IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA pennrt is required for excavations over 5'0' deep and demolition or oonstruction of structures over 3 stories in height
EXPIRATION: Every penn it issued by the Building Official e rovisions of this Code shall expire by limitation and beoome null and void if the building or v.ork authorized by such pennit is not oommenoed within
180 days from the date of such penn it or if 1ng orv.ork authonz such_~nnit is suspended or abandoned at any time after the v.ork is oommenoed for a period of 180 days (Section 106.4.4 Unifonn Building Code).
~APPLICANT'S SIGNATURE DATE
----.-· ----------.... ----------------------
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
CERTIFICATE OF OCCUPANCY (Commercial Projects 0 n ly)
Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
1
CO#: (Offii ~o&c 3
CONTACT NAME OCCUPANT NAME
MICHELE ARNOLD-KUSH ADVANCED BIOLOGICS
ADDRESS BUILDING ADDRESS 925 FORT STOCKTON 1905 ASTON AVENUE, SUITE 200
CITY STATE ZIP CITY STATE ZIP
SAN DIEGO CA Carlsbad CA 92008
--PHONE I FAX 619-297-6153 619-299-6072
EMAIL -OCCUPANT'S BUS. LIC. No.
MICHELE@SAFDIERABINES.COM
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1) /5"221~ ASSOCIATED CB# MAIL TO: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1) NO CHANGE IN USE I NO CONSTRUCTION
MAIL I FAX TO OTHER:
CHANGE OF USE I NO CONSTRUCTION
A$ APPLICANT'S SIG~IJ ~--DATE /-tlo-ts-
Inspection List
Permit#: CB152245 Type: Tl
Date Inspection Item
01/19/2016 89 Final Combo
01/19/2016 89 Final Combo
01/19/2016 89 Final Combo
01/07/2016 21 Underground/Under Floor
01/07/2016 21 Underground/Under Floor
01/07/2016 39 Final Electrical
01/06/2016 21 Underground/Under Floor
12/22/2015 92 Compliance Investigation
1 0/20/2015 39 Final Electrical
10/07/2015 85 T-Bar
1 0/05/2015 44 Rough/Ducts/Dampers
10/02/2015 44 Rough/Ducts/Dampers
09/17/2015 34 Rough Electric
09/14/2015 15 Roof/Reroof
09/10/2015 14 Frame/Steei/Bolting!Weldin
09/02/2015 21 Underground/Under Floor
09/01/2015 14 F rame/Steei!Bolting!Weldin
Wednesday, January 20, 2016
IN DUST
Inspector Act
PY AP
PY AP
Rl
Rl
PY AP
Rl
PY AP
PY PI
PY NR
PY AP
PY AP
PY AP
PY NR
PY AP
PY AP
PY AP
PY PA
ADVANCED BIOLOGICS= CONSTRUCT
CLEAN ROOM IN EXIST WAREHOUSE 2,5
Comments
COF
Page 1 of 1
s~~~~s~tis~n INSPECTION RECORD
til INSPECnON RECORD CARD WITH APPROVED
PLANS MUST BE KEPT ON THE JOB
til CALl. BEFORE .1:30am FOR NUT WORK DAY INSPEcnON
til FOR BUILDING INSPEcnON CALL: 760-602·2725
_oR GO TO: www.CNfsbadq.aoytlulldlng AND CUCK ON
Request Inspection-
DATE: -
CB152245 1905 ASTON AV 101
ADVANCED BIOLOGICS= CONSTRUCT
CLEAN ROOM IN EXIST WAREHOUSE 2.516 SF/I
RESTROOM/SHOWER AREA RENOVATION OF 626 SF II
BREAKROOM SINKIIPLUMBIMECHI ELECT
Tl. INDUST
Lot# MICHELE. __ ARNOLD KUSHCOPV REGORD
Type of Inspection
COOE" ELECTRICAL
OUFIR
coo£ " MECHANICAL
,(
1qoo AsToN Av.'
) 5 2 a uS' Eagl~ Special Inspections, LLC
" ICC-ACI
1934 Calle Sinaloa Vista, Calif 92084 ~"'""""~ .
Cell760-716-0244 Fax 760-758-0089
Email-Eagle46@cox.net
DAILY OBSERVATION REPORT
Sam les " X " Quantity
DESCRIPTION OF WORK OBSERVED DATE (DAY)
013 s L -1. \{A-\' :;-,{..) ~ ,_( \Jt.:,. !)L~ A/..; c.:.~ \ ~~?( .;\ l-t..... (Y
L)AL.~ -, (lA'-'\'" ) { c. ;:;; t...-v/~.-1 ;V ~.>{~c;C-I -,Is wo~'> vl2-> u_~~: ~ .
Lf I c.n:-A~ .,-_:70 ~ I J "2--,, 'IJ~?fU vtrn .. -1 It ~(.t:,,S 1-
,_ -lz ., . t-1~ s--, _Q~, 1-\.. ~r? -;-....;.> L"""'_l ,A.) f)£7fL+ 'V-'rt-
~L..~') ~UA~.t·v. f'ltt--r' ~ I i "~-.., j '-~~ yy-lz...
AJ->C--t~? f ,Ve, ,. A-L-l_ '"'-77 A.vr;; -, ~rz._ D JLC '7 ,-...;;;
"'L ~ f "( (., 17 j t./.::;, f-r 1.-~ ?~.1._. .. c. .c:......-E'51L-Ji!J 17 .
~_;/~ J ctz--47
_til c, f1... }. 7
ATI'ORNEY-8 FEES-If action at law Ol' in "is to Ol'
TlMEIN tiME our MIN. FEE DAILY FEE O.T. D.T. HRS.
t.l \t(ti .
All ot.avatioas bad 1111 allliuimum tile tbr up to 4 bllum or a daily fee tbr 4 to 8 homs.
Au! obllcrYaliaas edaiiJiqgpast 1lOOil win be based 011 a daily fcc. ~ Sllotn 8lld 8llunb.Y
is time IIIII a half. OW:r llllom$ aod Suodlly is doubJc time.
.l\pflt'oved By
OJa..Sim Rtlpi-utive
·"'
_\)~
dle11:rms of 1his the shall be IIDtiled to laSOIIIble atfmlle1 s
I llereby ~. tJaal: at die time of11ais 1ep01t, I haw Clilsem:cl all offllcabcwe R(IOded work,
!Usa otherwise DOled. To lbe best of my bowfedae aud belief; I bawl fiiiDd 1ilis wodt to
aaply willa die IIJl1lRMICl p1aas,. • • • -aioa(s) of the 1JuiidiDB code
as applies ro dlejmiscliclioa wllllft: die 11liJ l'l!plllt c:alllllll be GOIIS&nJOd to
be a JW!OII!IIM'"'•rion oflllldr. of 'Ihe Owacr. or a IAICCeSSDrin
ildLnst, .. hold flanulall Jiuaaayaacltllclpt ~ af
myllllure wbalsoever, that are services plU'Iided.
'"
, I
I
1
!
i
j
I
,]
EsGil Corporation
In Partnersliip witli government for CJJuifaing Safety
DATE: 7/30/15
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 15-2245 SET: I
PROJECT ADDRESS: 1905 Aston Ave Suite 101
PROJECT NAME: Advanced Biologics-TI
D .b-PPLICANT
if JURIS.
D PLAN REVIEWER
D FILE
[gj The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: ) Email:
Mail Telephone Fax In Person
D REMARKS:
By: Doug Moody Enclosures:
EsGil Corporation
0 GA 0 EJ 0 MB 0 PC 7/20/15
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
City of Carlsbad 15-2245
7/30/15
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: 15-2245
PREPARED BY: Doug Moody DATE: 7/30/15
BUILDING ADDRESS: 1905 Aston Ave Suite 101
BUILDING OCCUPANCY: B
BUILDING AREA Valuation
PORTION (Sq. Ft.) Multiplier
Tl 3202 43.32
----~-
Air Conditioning
Fire Sprinklers
TOTAL VALUE ------------------
Jurisdk:tion Code cb By Ordina nee
Bldg. Permit Fee by Ordinanoe
Plan Oleck Fee by Ordinance
Type of Review: [] Complete Review
0Repetitive Fee Repeats .....
Comments:
D Other
D Hourly
EsGil Fee
Reg. VALUE
Mod.
·---------~-~--------
t--------------
[] Structural Only
f--------11 Hr @ •
($)
138,711
138,711
$764.511
$496.931
$428.131
Sheet 1 of 1
macvalue.doc +
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: PROJECT NAME:
PLAN CHECK NO: 1
VALUATION: S 138711
SET#: 1. ADDRESS: 1.905 ASTON STE 101
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
PROJECT ID:
APN:
This plan check review is complete and has been APPROVED by the ENGINEERING
Division.
A Final Inspection by the ENGINEERING Division is required Yes No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to:
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760-602-4610
Chris Sexton
760-602-4624
. Chris.Sexton@carl@adca.go\'
Gina Ruiz
760-602-4675
Gina.Ruiz@carlsb<)Qca,gm;
Remarks:
ENGINEERING
760-602-2750
Kathleen Lawrence
760-602-27 41
Kathleen.Lawrence@carlsba.ili;.a.gov,
Linda Ontiveros
760-602-2773
Linda.Qt]jjl!.flros@carlsbadJ;g,.gQ_y
VaiRay Marshall
760-602-2741
FIRE PREVENTION
760-602-4665
Greg Ryan
760-602-4663
<:aregory.RY9J:!@glJ:l.?badc(l,.g0y
Cindy Wong
760-602-4662
Qynthia"WoDg@c(lrlst:>.gdca.,gQ'-'
Dominic Fieri
760-602-4664
Pomirtlc.EierJ@c<.l.rJs!'?C1<:lca.gol/
BUILDING PLANCHECK
CHECKLIST
QUICK-CHECK/APPROVAL
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www .carlsbadca .gov
ENGINEERING Plan Check for Date
Project Address:
Project Description: SF BATHROOM Tl
ENGINEERING Contact :
Phone:
RESIDENTIAL INTERIOR
RESIDENTIAL ADDITION MINOR
(<$20,000.00)
APN
Valuation
Email
Fax:
TENANT IMPROVEMENT
PLAZA CAMINO REAL
CARLSBAD PREMIER OUTLETS COMPLETE OFFICE BUILDING
OTHER: GYM
r··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··, OFFICIAL USE ONLY
ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT
BY: DATE: 5
REMARKS:
Notification of Engineering APPROVAL has been sent to
via on -··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-·
E-36 Page 1 of 1 REV 4/30/11
Fee Calculation Worksheet
ENGINEERING DIVISION
Prepared by: Date: GEO DATA: LFMZ: I B&T:
Address: Bldg. Permit#:
Fees Update by: Date: Fees Update by: Date:
EDU CALCULATIONS: List types and square footages for all uses.
Types of Use: Sq.Ft./Units EDU's:
Types of Use:
Types of Use:
Types of Use:
Sq.Ft./Units
Sq.Ft./Units
Sq.Ft./Units
ADT CALCULATIONS: List types and square footages for all uses.
EDU's:
EDU's:
EDU's:
Types of Use: Sq.Ft./Units ADT's:
Types of Use:
Types of Use:
Types of Use:
FEES REQUIRED:
Sq.Ft./Units
Sq .Ft./Units
Sq.Ft./Units
ADT's:
ADT's:
ADT's:
Within CFD: YES (no bridge & thoroughfare fee in District #1, reduces Traffic Impact Fee) NO
1. PARK-IN-LIEU FEE: NW QUADRANT NE QUADRANT SE QUADARANT SW QUADRANT
ADT'S/UNITS: I X FEE/ADT: I =$ D
2.TRAFFIC IMPACT FEE:
ADT'S/UNITS: IX FEE/ADT: I=$ D
3. BRIDGE & THOROUGHFARE FEE: DIST. #1 DIST.#2 DIST.#3
ADT'S/UNITS: ~ FEE/ADT: 1=$ D
4. FACILITIES MANAGEMENT FEE ZONE:
ADT'S/UNITS: IX FEE/SQ. FT./UNIT: I=$ D
5. SEWER FEE
EDU's IX FEE/EDU: I=$ D
BENEFIT AREA:
EDU's IX FEE/EDU: I=$ D
6. DRAINAGE FEES: PLDA: HIGH MEDIUM LOW
ACRES: IX FEE/AC: I=$ D
7. POTABLE WATER FEES:
UNITS CODE CONN. FEE METER FEE SDCWA FEE TOTAL
PLANNING DIVISION
BUILDING PLAN CHECK
I y 0 F REVIEW CHECKLIST
CARLSBAD P-28
DATE: 8-11-15 PROJECT NAME: PROJECT ID:
Planning Division
1635 Faraday Avenue
(760} 602-4610
www.carlsbadca.eov
PLAN CHECK NO: CB 15-2245 SET#: 2 ADDRESS: 1905 Aston APN: 212-120-13-00
[g) This plan check review is complete and has been APPROVED by the Planning
Division.
By: Chris Sexton
A Final Inspection by the Planning Division is required DYes [SJ No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: michele@safdierabines.com
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760-602-4610
~ Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
D Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
D
Remarks:
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
REVIEW#:
1 2 3
~DO
~DO
~DO
~DO
~DO
~DO
P-28
Plan Check No. CB 15-2245 Address 1905 Aston Date 8-11-15 Review#~
Planner Chris Sexton Phone (760) 602-4624
APN: 212-120-13-00
Type of Project & Use: Tl, warehouse to clean room Net Project Density: DUlAC
Zoning: C-M General Plan: PI Facilities Management Zone:§
CFD (in/out) #_Date of participation: __ Remaining net dev acres: __
(For non-residential development: Type of land use created by this permit: __ )
Legend: ~ Item Complete D Item Incomplete -Needs your action
Environmental Review Required: YES 0 NO 0 TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES 0 NO 0 TYPE __
APPROVALIRESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval: __
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES 0 NO 0
CA Coastal Commission Authority? YES 0 NO 0
If California Coastal Commission Authority: Contact them at -7575 Metropolitan Drive,
Suite 103, San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
Habitat Management Plan
Data Entry Completed? YES D NO D
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application
and assess fees in Permits Plus
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of
Habitat Type impacted/taken, UPDATE!)
lnclusionary Housing Fee required: YES D NO D
(Effective date of lnclusionary Housing Ordinance-May 21, 1993.)
Data Entry Completed? YES D NO D
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct
Housing Y/N, Enter Fee, UPDATE!)
Housing Tracking Form (form P-20) completed: YES D NO D N/A D
Page 2 of 3 07111
Site Plan:
~DO
~DO
~DO
~DO
~DO
~DO
~DO
D~D
D~D
Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines,
easements, existing and proposed structures, streets, existing street improvements, right-of-
way width, dimensional setbacks and existing topographical lines (including all side and rear
yard slopes). Provide legal description of property and assessor's parcel number.
City Council Policy 44-Neighborhood Architectural Design Guidelines
1. Applicability: YES D NO D
2. Project complies: YES D NOD
Zoning:
1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown __
2. Accessory structure setbacks:
Front:
Interior Side:
Street Side:
Rear:
Structure separation:
3. Lot Coverage:
4. Height:
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown
Required __ Shown __
5. Parking: Spaces Required bio-industrial 1 ,305 Shown 1/300 sq ft ~
Office -27, 127 sq ft 1/250 = 1 09
Warehouse-17,900 sq ft 1/1,000 = 18
Total = 132 needed 145 provided
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required __ Shown __
Additional Comments 1) Please show parking breakdown for the entire building. An example
has been attached. 2) Please show how new roof mounted equipment will be screened -
will be screened by existing parapet and equipment will be painted to match the roof surface.
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER Chris Sexton DATE 8-11-15
P-28 Page 3 of 3 07111
PLANNING DIVISION
BUILDING PLAN CHECK
1 v or REVIEW CHECKLIST
CARLSBAD P-28
DATE: 7-20-15 PROJECT NAME: PROJECT ID:
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.eov
PLAN CHECK NO: CB 15-2245 SET#: 1 ADDRESS: 1905 Aston APN: 212-120-13-00
D This plan check review is complete and has been APPROVED by the Planning
Division.
By: Chris Sexton
A Final Inspection by the Planning Division is required DYes ~No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
C2J This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: michele@safdierabines.com
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760-602-4610
~ Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
D Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
D
Remarks:
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
REVIEW#:
1 2 3
~DO
~DO
~DO
~DO
rgJOD
rgJOD
P-28
Plan Check No. CB 15-2245 Address 1905 Aston Date 7-20-15 Review# 1
Planner Chris Sexton Phone (760) 602-4624
APN: 212-120-13-00
Type of Project & Use: Tl, warehouse to clean room Net Project Density: DU/AC
Zoning: C-M General Plan: PI Facilities Management Zone: §
CFD (in/out) #_Date of participation: __ Remaining net dev acres: __
(For non-residential development: Type of land use created by this permit: __ )
Legend: cgj Item Complete D Item Incomplete -Needs your action
Environmental Review Required: YES 0 NO 0 TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES 0 NO 0 TYPE __
APPROVALIRESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval: __
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES 0 NO 0
CA Coastal Commission Authority? YES 0 NO 0
If California Coastal Commission Authority: Contact them at -7575 Metropolitan Drive,
Suite 103, San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
Habitat Management Plan
Data Entry Completed? YES 0 NO 0
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application
and assess fees in Permits Plus
(NP/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of
Habitat Type impacted/taken, UPDATE!)
lnclusionary Housing Fee required: YES D NO D
(Effective date of lnclusionary Housing Ordinance-May 21, 1993.)
Data Entry Completed? YES 0 NO 0
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct
Housing YIN, Enter Fee, UPDATE!)
Housing Tracking Form (form P-20) completed: YES D NO D N/A D
Page 2 of 3 07/11
Site Plan:
!?SJDD
!?SJDD
!?SJDD
!?SJDD
!?SJDD
[300
DOD
DOD
Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines,
easements, existing and proposed structures, streets, existing street improvements, right-of-
way width, dimensional setbacks and existing topographical lines (including all side and rear
yard slopes). Provide legal description of property and assessor's parcel number.
City Council Policy 44-Neighborhood Architectural Design Guidelines
1. Applicability: YES D NO D
2. Project complies: YES 0 NOD
Zoning:
1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown
2. Accessory structure setbacks:
Front: Required __ Shown __
Interior Side: Required __ Shown __
Street Side: Required __ Shown __
Rear: Required __ Shown __
Structure separation: Required __ Shown __
3. Lot Coverage: Required __ Shown __
4. Height: Required __ Shown __
5. Parking: Spaces Required __ Shown __
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required __ Shown __
Additional Comments 1) Please show parking breakdown for the entire building. An example
has been attached. 2) Please show how new roof mounted equipment will be screened.
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER DATE
P-28 Page 3 of 3 07/11
/~. r;' ~1 ,
,l_ -· ...... ·' r--~ ~-. , H:· ''T CC ~·'l
<'~' ?c.··· .. ,~,. ... '~ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: 8·27-15 PROJECT NAME: Advanced Biologics
PLAN CHECK NO: CS152245 SET#: I ADDRESS:
Communtty & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.earlsbadca.gov
PROJECT ID:
APN:
~.5] This plan check review Is complete and has been APPROVED by the Fire Division.
By: D. Fieri
A Final Inspection by the Fire Division is required 0 Yes 0 No
O This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to:
You may a/so have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
D Chris Sexton
760~602-4624
Chrls.Sexto~rlsbS~dca.ggy
Remarks:
D Kathleen Lawrence
760·602-27 41
Kathleen.Lawrence~badca.gQy
D Greg Ryan
760-602~4663
Gregory.Ryan@carlsbadca.gov
Carlsbad Fire Department
Plan Review Requirements Category: Tl, INDUST
Date ofReport:08~27~2015
Name: MICHELE ARNOLD KUSH
Address:
Permit #: CB 152245
925 FORT STOCKTON
SAN DIEGO CA
92103
Job Name: ADVANCED BIOLOGICS:::: CONSTRUCT
Reviewed by:
Job Address: 1905 ASTON AV CBAD St: 101 \
('
INCOi'PlETE The i~m yau ~a:re submitte~,for''re.\'~ew is inco~l~te.'·-4t.this time, ~s of~,cannot ad.q~ate\ .. ~onduct tll'eview to deterririRe ~ompli~ce with the ~pplical7\t codes' as(,i~or stant\trds. Pl~e revie;w
carefu'M~~lr·~pmments attpched, Please re~mbxnit t~e necessary ~s an~or specifications, \Vijh changes'"''~louped",
to this offi'be ~r review and appr<yal. ,J J , .) J
Ctll!&ij~fo IJSJ
Cond: CON0008523
[MET]
"'\PPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF
BUILDING PERMlT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON,
CONDITIONS IN
CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW.
Entry: 08/27/2015 By: d.fieri Action: AP
Page 1 or .5
·<<·~ l ·:\ :, : '1:<Ji·';' i '()P 'i
Conditional Recommendation for Approval
E2.0
UPDATE CODE REFERENCES TO 2013 CBC IN EGRESS LIGHTING NOTE 2 & GENERAL RCP
NOTE 6 UPON FIRE OFFICIAL REQUEST
Daryl K. James & Associates, Inc<
205 Colina Terrace
Vista, CA 92084
T. (760) 724-7001 Email: kitfire@sbcglobal.net
Checked by: Daryl Kit James
Date: 8/20/2015
APPLICANT: Michele Arnold-Kush
PROJECT NAME: Advanced Biologics
JURISDICTION: Carlsbad Fire Department
PROJECT ADDRESS: 1905 Aston Avenue, Ste. 101
PROJECT DESCRIPTION: CB152245 3,202[fl Tl includes construction of clean room in existing
warehouse with independent lighting and mechanical system. Interior suite work includes renovation of
4 RR and shower to include replacement of 5 toilets, 1 urinal, 1 new toilet and 1 new sink. Breakroom
scope includes replacement of non-compliant base cabinet with sink, Tl will include structural work for
clean room, and Tl will include non-load bearing partitions only. Existing ceiling and new lighting at RR,
HVAC/Mech systems are existing at tenant space, new at clean room. RR/Shower area of
improvement: 626[fl approx., clean room area of improvement: 2,578[fl approx ...
COMMENTS
ADDITIONAL COMMENTS MAY BE GENERATED BASED ON RESUBITTAL RESPONSES
vTS1
vProvide the Following List of Applicable Codes
2013 California Building Code ......... based on the 2012 International Building Code
2013 California Fire Code ............. based on the 2012 International Fire Code
2013 California Electrical Code . . . . .. based on the 2011 National Electrical Code
2013 California Mechanical Code . . . based on the 2012 Uniform Mechanical Code
2013 California Plumbing Code .. .. . based on the 2012 Uniform Plumbing Code
2013 California Energy Code
II' NOTES
UPDATE CODE REFERENCES TO 2013 CALIFORNIA CODES, WHERE APPLICABLE.
REPLACE REFERENCES TO CITY OF SAN DIEGO OR CITY ADDRESSES WITH THE CITY OF
CARLSBAD, WHERE APPLICABLE.
REVISE FIRE SAFETY AND PREVENTION NOTES 1, 2 & 22 & STORM WATER QUALITY NOTE
vBuilding Information
Site Address: Building Permit Application Suite# is 101. Clarify Suite #200 shown on drawings.
II' Occupancy Type
Verify that the clean room is a Group F occupancy.
v Provide a detailed description of clean room purpose and possible use of hazardous materials within
the room, in the form of a letter or Fire Protection Technical Opinion & Report. Detail clean room
operations, quantity and use of hazardous materials, hazardous operations and occupancy
classification, in accordance with California Building and Fire Codes.
t'age ~or .5
V'ltem C. Provide a list of the Materials, Class , Amount in Storage, Amount in Use-Closed Systems,
and Amount in Use-Open Systems CFC Table 2703.1.1 (1) & 2703.1.1 (2). Address CFC requirements,
Contact the Carlsbad Fire Department for a list of qualified California Fire Code consultants, acceptable
to the Carlsbad Fire Department. The California Fire Code Consultant is to analyze the acceptability of
technologies, processes, products, facilities, materials and uses attending the design, operation or use
of a building or premises, subject to inspection by the fire code official, and to recommend necessary
changes.
VWAREHOUSE STORAGE CONDITIONS
CLARIFY WHETHER THE CLASSIFICATION OF THE S-1 WAREHOUSE WILL NOT BE USED AS
AN S-1 OCCUPANCY, WHICH INDICATES STORAGE, MARK EACH SHEET THAT SHOWS AN S-1,
AS "NO STORAGE" AND DESCRIBE ACTIVIES THAT WILL OCCUR IN THE SPACE.
IF THE EXISTING S-1 WAREHOUSE WILL CONTINUE TO USED AS AN S-1 AND STORAGE
ARRAY WILL BE ALTERED DUE TO THE CONSTRUCTION OF THE CLEAN ROOM AND
ACCESSORY ROOMS, A HIGH-PILED STORAGE PLAN TECHNICAL REPORT WILL BE
REQUIRED.
V'Construction Type: Revise construction type in accordance with California Building Code Chapter 6.
vDeferred Submittals
List all Deferred Submittals
Fire Sprinkler System 2013 CFC 903 and 2013 NFPA 13.
Fire Alarm System 2013 CFC 907 including CFC 907.2 sections applicable to occupancy groups, and
2013 NFPA 72.
VSP.2
REVISE OFFICE OCCUPANCY CLASSIFICATION. B-11S NOT A 2013 CBC OCCUPANCY GROUP.
CBC CHAPTER 3.
VEX.3
Exit Plan First Floor
Identify Clean Rooms and refer to applicable CR sheets.
vSquare Foot Summary by Occupancy
Provide data in Summary that matches the Exit Plan
Revise office occupancy classification. See 2013 California Building Code Section 304. B-1 IS NOT
LISTED AS AN OCCUPANCY GROUP.
VT1-4
Demolition Plan Keynotes
Note 1. Revise sheet reference
VT1-5
First Floor Partition Plan
Identify Clean Rooms
Refer to CR sheets for applicable Clean Room sheets.
VTI-7
General Notes
First note: Add deferred submittal for fire official approval.
t'age 5 or 5
Provide specifications and California State Fire Marshal listings or other acceptance criteria for flame
spread and smoke developed index for new carpet, padding and carpet base. CFC 804
Specifications and California State Fire Marshal listings or other acceptance criteria for flame spread
and smoke developed index for Acoustical Ceilings CBC 808.
vTI.12.1 (#2)
Revise sheet number to Tl.12.2
E2.0
EGRESS LIGHTING NOTE 2 & GENERAL RCP NOTE 6. UPDATE CODE REFERENCES TO 2013
CALIFORNIA BUILDING CODE.
vCR-A5
Provide Door Hardware Specifications and Hardware Groups in order to verify that all doors are
openable from the egress side without the use of a key or special knowledge or effort.
Identify on plan, all doors that are equipped with "CARD READERS," or that are electromagnetically
locked or that have access-control functions and address CBC, Sections 1 008.1.9.8 and 1 008.1.9.9
requirements.
vCR-M4
Mechanical Roof Plan
Carlsbad Roof Policy
Imprint Carlsbad Policy 80-6 to roof plan. Indicate provisions taken to comply with Carlsbad Policy 80-6
Intent 8 (Fireman Safety) where roof mounted unit will be added.
City of Carlsbad Policies and Procedures document number 80-6: Roof Mounted Equipment is intended
to prevent the installation of hazardous items such as; utility piping and conduit 1.4-inches or higher
above roof surface and electrical or other utility wiring or cabling not securely placed in conduit,
raceways or properly affixed to the structure or that which may be a trip or strangulation hazard.
Additionally, it was intended to address building openings and roof coverings or features that posed a
fall hazard to those unfamiliar or subject to impaired senses as might be encountered during smoky and
fire conditions or at night.
Denote the location of roof access.
t'age 1 or .5
PLAN CHECK COMMENTS 2
Daryl K. James & Associates, Inc.
205 Colina Terrace
Checked by: Daryl Kit James
Date: 8/17/2015
Vista, CA 92084
T. (760) 724-7001 Email: kitfire@sbcglobal.net
APPLICANT: Michele Arnold-Kush
PROJECT NAME: Advanced Biologics
JURISDICTION: Carlsbad Fire Department
PROJECT ADDRESS: 1905 Aston Avenue, Ste. 101
PROJECT DESCRIPTION: CB152245 3,202UJ Tl includes construction of clean room in existing
warehouse with independent lighting and mechanical system. Interior suite work includes renovation of
4 RR and shower to include replacement of 5 toilets, 1 urinal, 1 new toilet and 1 new sink. Breakroom
scope includes replacement of non-compliant base cabinet with sink, Tl will include structural work for
clean room, and Tl will include non-load bearing partitions only. Existing ceiling and new lighting at RR,
HVAC/Mech systems are existing at tenant space, new at clean room. RR/Shower area of
improvement: 626UJ approx., clean room area of improvement: 2,578UJ approx ...
COMMENTS
ADDITIONAL COMMENTS MAY BE GENERATED BASED ON RESUBITTAL RESPONSES
TS1
v Provide the Following List of Applicable Codes
2013 California Building Code ......... based on the 2012 International Building Code
2013 California Fire Code . . . . . . . . . . . . . based on the 2012 International Fire Code
2013 California Electrical Code . . . . . . based on the 2011 National Electrical Code
2013 California Mechanical Code . . . based on the 2012 Uniform Mechanical Code
2013 California Plumbing Code . . . . . based on the 2012 Uniform Plumbing Code
2013 California Energy Code
NOTES
UPDATE CODE REFERENCES TO 2013 CALIFORNIA CODES, WHERE APPLICABLE.
REPLACE REFERENCES TO CITY OF SAN DIEGO OR CITY ADDRESSES WITH THE CITY OF
CARLSBAD, WHERE APPLICABLE.
REVISE FIRE SAFETY AND PREVENTION NOTES 1, 2 & 22 & STORM WATER QUALITY NOTE
vBuilding Information
Site Address: Building Permit Application Suite # is 101. Clarify Suite #200 shown on drawings.
vOccupancy Type
Verify that the cleanroom is a Group F occupancy.
v Provide a detailed description of clean room purpose and possible use of hazardous materials within
the room, in the form of a letter or Fire Protection Technical Opinion & Report. Detail clean room
operations, quantity and use of hazardous materials, hazardous operations and occupancy
classification, in accordance with California Building and Fire Codes.
vltem C. Provide a list of the Materials, Class , Amount in Storage, Amount in Use-Closed Systems,
and Amount in Use-Open Systems CFC Table 2703.1.1 (1) & 2703.1.1 (2). Address CFC requirements,
Contact the Carlsbad Fire Department for a list of qualified California Fire Code consultants, acceptable
to the Carlsbad Fire Department. The California Fire Code Consultant is to analyze the acceptability of
Yage .l. or .5
technologies, processes, products, facilities, materials and uses attending the design, operation or use
of a building or premises, subject to inspection by the fire code official, and to recommend necessary
changes.
WAREHOUSE STORAGE CONDITIONS
CLARIFY WHETHER THE CLASSIFICATION OF THE S-1 WAREHOUSE WILL NOT BE USED AS
AN S-1 OCCUPANCY, WHICH INDICATES STORAGE, MARK EACH SHEET THAT SHOWS AN S-
1, AS "NO STORAGE" AND DESCRIBE ACTIVIES THAT WILL OCCUR IN THE SPACE.
IF THE EXISTING S-1 WAREHOUSE WILL CONTINUE TO USED AS AN S-1 AND STORAGE
ARRAY WILL BE ALTERED DUE TO THE CONSTRUCTION OF THE CLEAN ROOM AND
ACCESSORY ROOMS, A HIGH-PILED STORAGE PLAN TECHNICAL REPORT WILL BE
REQUIRED.
vConstruction Type: Revise construction type in accordance with California Building Code Chapter 6.
vDeferred Submittals
List all Deferred Submittals
Fire Sprinkler System 2013 CFC 903 and 2013 NFPA 13.
Fire Alarm System 2013 CFC 907 including CFC 907.2 sections applicable to occupancy groups, and
2013 NFPA 72.
SP.2
REVISE OFFICE OCCUPANCY CLASSIFICATION. 8-1 IS NOT A 2013 CBC OCCUPANCY GROUP.
CBC CHAPTER 3.
vEX.3
Exit Plan First Floor
Identify Clean Rooms and refer to applicable CR sheets.
Square Foot Summary by Occupancy
Provide data in Summary that matches the Exit Plan
Revise office occupancy classification. See 2013 California Building Code Section 304. 8-1 IS NOT
LISTED AS AN OCCUPANCY GROUP.
VT1-4
Demolition Plan Keynotes
Note 1 . Revise sheet reference
V'T1-5
First Floor Partition Plan
Identify Clean Rooms
Refer to CR sheets for applicable Clean Room sheets.
vTl-7
General Notes
First note: Add deferred submittal for fire official approval.
¥VTI-9
Provide specifications and California State Fire Marshal listings or other acceptance criteria for flame
spread and smoke developed index for new carpet, padding and carpet base. CFC 804
Specifications and California State Fire Marshal listings or other acceptance criteria for flame spread
and smoke developed index for Acoustical Ceilings CBC 808.
Page 5 or 5
vTI.12.1 (#2)
Revise sheet number to Tl.12.2
E1.0 & E2.0
EGRESS LIGHTING NOTES AND GENERAL RCP NOTES
UPDATE CODE REFERENCES TO 2013 CALIFORNIA BUILDING CODE.
vCR-A5
Provide Door Hardware Specifications and Hardware Groups in order to verify that all doors are
openable from the egress side without the use of a key or special knowledge or effort.
Identify on plan, all doors that are equipped with "CARD READERS," or that are electromagnetically
locked or that have access-control functions and address CBC, Sections 1 008.1.9.8 and 1 008.1.9.9
requirements.
vCR-M4
Mechanical Roof Plan
Carlsbad Roof Policy
Imprint Carlsbad Policy 80-6 to roof plan. Indicate provisions taken to comply with Carlsbad Policy 80-6
Intent B (Fireman Safety) where roof mounted unit will be added.
City of Carlsbad Policies and Procedures document number 80-6: Roof Mounted Equipment is intended
to prevent the installation of hazardous items such as; utility piping and conduit 1.4-inches or higher
above roof surface and electrical or other utility wiring or cabling not securely placed in conduit,
raceways or properly affixed to the structure or that which may be a trip or strangulation hazard.
Additionally, it was intended to address building openings and roof coverings or features that posed a
fall hazard to those unfamiliar or subject to impaired senses as might be encountered during smoky and
fire conditions or at night.
Denote the location of roof access.
Yage 1 or J
CORRECTION LIST
Daryl K. James & Associates, Inc.
205 Colina Terrace
Checked by: Daryl Kit James
Date: 7/25/2015
Vista, CA 92084
T. (760) 724-7001 Email: kitfire@sbcglobal.net
APPLICANT: Michele Arnold-Kush
PROJECT NAME: Advanced Biologics
JURISDICTION: Carlsbad Fire Department
PROJECT ADDRESS: 1905 Aston Avenue, Ste. 101
PROJECT DESCRIPTION: CB152245 3,202tt~ Tl includes construction of clean room in existing
warehouse with independent lighting and mechanical system. Interior suite work includes renovation of
4 RR and shower to include replacement of 5 toilets, 1 urinal, 1 new toilet and 1 new sink. Breakroom
scope includes replacement of non-compliant base cabinet with sink, Tl will include structural work for
clean room, and Tl will include non-load bearing partitions only. Existing ceiling and new lighting at RR,
HVAC/Mech systems are existing at tenant space, new at clean room. RR/Shower area of
improvement: 626tt~ approx., clean room area of improvement: 2,578tt~ approx ...
RESUBMITTAL INSTRUCTIONS TO AVOID DELAY IN EXPEDITED RECHECK SERVICES
• Corrections or modifications to the plans must be clouded and provided with numbered deltas and
revision dates.
• Provide a written response following each comment, On This Correction List, explaining how and
where each plan review comment has been addressed.
• Provide a copy of Building Department (EsGil) comments
• Please direct any questions regarding this review to: Daryl K. James 760-724-7001 or
kitfire@sbcglobal. net
• COMMENTS MUST BE SUBMITTED DIRECTLY TO THE FOLLOWING ADDRESS
DARYL K. JAMES & ASSOCIATES, INC.
205 COLINA TERRACE
VISTA, CA 92084
PLEASE DO NOT REQUIRE MY SIGNATURE TO ACCEPT DELIVERY OF REVISED PLANS
COMMENTS
ADDITIONAL COMMENTS MAY BE GENERATED BASED ON RESUBITTAL RESPONSES
TS1
Provide the Following List of Applicable Codes
2013 California Building Code ......... based on the 2012 International Building Code
2013 California Fire Code . . . . . . . . . . . . . based on the 2012 International Fire Code
2013 California Electrical Code .. .. .. based on the 2011 National Electrical Code
2013 California Mechanical Code . . . based on the 2012 Uniform Mechanical Code
2013 California Plumbing Code .. .. . based on the 2012 Uniform Plumbing Code
2013 California Energy Code
Page~ or 5
Notes
Update code references to 2013 California Codes, where applicable.
Replace references to City of San Diego with City of Carlsbad, where applicable.
Building Information
Site Address: Building Permit Application Suite# is 101. Clarify Suite #200 shown on drawings.
Occupancy Type
Verify that the cleanroom is a Group F occupancy. Provide a detailed description of clean room
purpose and possible use of hazardous materials within the room, in the form of a letter or Fire
Protection Technical Opinion & Report. Detail clean room operations, quantity and use of hazardous
materials, hazardous operations and occupancy classification, in accordance with California Building
and Fire Codes.
Warehouse Storage Conditions
Indicate whether a storage permit exists for the warehouse and whether any changes to storage
conditions in the warehouse will occur. If previously approved storage conditions exist, a high-piled
storage permit number and a copy of the most recent technical report may be necessary.
If not previously permitted, provide High-Piled Storage (HPS) drawings along with a Fire Protection
Technical Opinion & Report to address storage conditions for compliance with California Fire Code
Chapter 32 and NFPA 13.
The construction documents, should at minimum, reflect the information listed in CFC 3201.3;
specifically items 1 through 14.
Additionally, the storage analysis must determine the commodity classification of a mixed commodity in
a package, carton, or on a pallet where plastics are involved. Refer to 2013 CFC, Figure 3203.7.4
(percent by volume/percent by weight). The information contained in the report is used to identify
additional fire protection requirements, including but limited to an increase in the hazard
classification/sprinkler density and the alterations to building conditions. It will also clarify and provide a
solid justification of which fire protection provisions may not apply.
Qualified engineer or fire code consultant with extensive CFC Chapter 32 and NFPA 13 knowledge and
experience shall prepare the HPS report.
Contact Fire Prevention at 760-602-4665 for a complete list of fire & life safety consultants.
Construction Type: Revise construction type in accordance with California Building Code Chapter 6.
Deferred Submittals
List all Deferred Submittals
Fire Sprinkler System 2013 CFC 903 and 2013 NFPA 13.
Fire Alarm System 2013 CFC 907 including CFC 907.2 sections applicable to occupancy groups, and
2013 NFPA 72.
Site Plan
Revise Clean Room Occupancy Classification. See Occupancy Type on Sheet TS.1
EX.3
Exit Plan First Floor
Identify Clean Rooms and refer to applicable CR sheets.
Revise Clean Room Occupancy Classification. See Occupancy Type on Sheet TS.1
Square Foot Summary by Occupancy
Provide data in Summary that matches the Exit Plan
Revise office occupancy classification. See 2013 California Building Code Section 304.
· EX3.f
Provide data in Summary that matches the Exit Plan
T1-4
Demolition Plan Keynotes
Note 1 . Revise sheet reference
T1-5
First Floor Partition Plan
Identify Clean Rooms
Refer to CR sheets for applicable Clean Room sheets.
Tl-7
General Notes
1st note. Add deferred submittal for fire official approval.
Tl-9
Yage .5 or .5
Provide specifications and California State Fire Marshal listings or other acceptance criteria for flame
spread and smoke developed index for new carpet, padding and carpet base. CFC 804
Specifications and California State Fire Marshal listings or other acceptance criteria for flame spread
and smoke developed index for Acoustical Ceilings CBC 808.
Tl.12.1 (#2)
Revise sheet number to Tl.12.2
E1.0
Egress Lighting Notes
Update code references to 2013 California Building Code.
CR-A5
Provide Door Hardware Specifications and Hardware Groups in order to verify that all doors are
openable from the egress side without the use of a key or special knowledge or effort.
Identify on plan, all doors that are equipped with "CARD READERS," or that are electromagnetically
locked or that have access-control functions and address CBC, Sections 1 008.1.9.8 and 1 008.1.9.9
requirements.
CR-M4
Mechanical Roof Plan
Carlsbad Roof Policy
Imprint Carlsbad Policy 80-6 to roof plan. Indicate provisions taken to comply with Carlsbad Policy 80-6
Intent B (Fireman Safety) where roof mounted unit will be added.
City of Carlsbad Policies and Procedures document number 80-6: Roof Mounted Equipment is intended
to prevent the installation of hazardous items such as; utility piping and conduit 1.4-inches or higher
above roof surface and electrical or other utility wiring or cabling not securely placed in conduit,
raceways or properly affixed to the structure or that which may be a trip or strangulation hazard.
Additionally, it was intended to address building openings and roof coverings or features that posed a
fall hazard to those unfamiliar or subject to impaired senses as might be encountered during smoky and
fire conditions or at night.
Denote the location of roof access.
END OF COMMENTS
5762 bolso avenue. suite 215
huntington beach. co 92649
714 891-5582
STRUCTURAL CALCULATIONS
CLEAN ROOM
ADVANCE BIOLOGICS
1905 ASTON AVENUE
CARLSBAD, CA 92008
CLEAN ROOMS WEST, INC.
CONTRACTOR
,lOB NO. 15106
sv we
DATE 6/15
SH. OF
5762 bolso avsnue S-J''e ~~ 5
~~unT;ngto:--1 t·e!Jch. ca .:\26L:;·
Lt>M:?:
Oc=:c.~ LoM~ '•
(7L_ C/f-:c.\Ll uJ.\
)t.J~ \) L-.A-11 D,.)
(?~ t-ll-oJ t1
J/Jt,~
CE:~tt...tNt1
? rR..tiJ 'l..t.f-....t. !>
Me;,~"''-
H1 t ~(....
L6P~(
{.5
~!
It~
(.p tf)
t.,...
t,S""
\,0
l1.~P7F
'LO
t cttt? P;,-F
~'t 1~·r1tJ4 r?~~f-l.t'J4,t.?7: .
-... -·----................ -~-·-............--.... -,....... . .... -----·· ~--~-~·~-· .. ''---.... '~
V'L ff~~,J?i. 4-~f?r-
ft.'-1 wJJ ~ '· ~ Pv f3? Pva ,,~..J. \1'
PtJ 4-1 tJ.b t ,t:> t?P~oJJI.des \,~ Mt~'-L~
\--r .o P~r-~AM? t..-.tt>
\ 4.,!) fl7t:-
LL-
JOB No.ll3 t C)~
BY W£-
DATE &/rt[i
SH. J OF
5762 nois:J avenue s·~:·te 2:::-,
hunrln;:Jtcn beach. co 926~;
714 891-5582
fMTWU~~ LI'M~:
lAT/~JJ'It ::-3$. ,~0'\ ?../-1'1: ~611t.,P
'S?p/~ ~ L~1o/.+tv ~~tlfflf; 7t'ft;_ [~~ p ~()~)7t?l ::=-I 1G6qj. "1 !'11 r: .:::/,0
JOB No.l ~I f) CO
BY v/t,.....
DATE t.!/1 '5
SH. Z-oF
1/{.f :::-L 0 ~.:: {,, ~ ~;t..p &: 1 4 Po ~.c,
::... t ,r:; ~ ~ ,!) ,.. f/f!, r-I 'f (1 Gcp 'J, ~
Fp~ (,4-lfr 1(b~){,~o) ( l t-z,) ~-, ;?M-/f,~
~ t t/J JJ-r (A?(?).
{, tf 1;) .=: 1 ~1 u) I / /Jr!-; p)
r-: · .f ~If-f-e :-. F1t~J:r LA?&~ l. ::v ~ 1 tl u.JT 'MCI
• q -E=v ~ ... 1q w-r
U) uJ!,? b?tt1/z ;
7f~P-\ ION1PH
I=;~P -· ~
:C: -I tO
\~A -t,P ~~. -,16 HT~Pe>1
t\.c.t -• e~
'· -I 9z? ~4 -1,1 ~ ~/)(Jf-wP ~il(JtP L5" t v ...,..
F;:;. (~LP ~ t t..?)[,tlt6)(.e>$)(t,'J) -~ .. ~tjf:_7f _::,
. (t,~~ ~?P~f'l'
5762 bols:J ·ovsnus. sL:"s 2; 2
l·,unti~gton beoch. co <;26-"<;
714 891-5.582
A c.; t,A~ t...
LO-r ... z:.ct tf;" l ll c;, 1 t-F-""· ~z_tf ~ ~8; I )C +D ·T.4LL
.JOB No/f;l t)~
BY v.)e,__
DATE t.P./t ~
SH. ~OF
5762 bois:J o·1enue ''~: .. e 2-5
huntin·;JtOil beach, co ~'26~;.·
714 89l-55F32
M:-ctLttJ4
Lt 4 1
~Jrt... :;t. ~ f!'J f *
r )!;.rt;. M aJ , .-z,-t M JEJZ_ 42 H-9 5
c?fi;?14tJk{ ·-
w~-~· -,7'bf?f
( D "" TO t,.LTr t t3; 0 tP tJ~ rJ F-!;t lj) 0
u> tor;_ 12~ tJ ... :, -J~~ 9t1 PSr0
Jo !?TZ':..
f \ t J I L.:::.. q , t ~ t t u , t 1 r -co ·
JOB No.( ;?J CJ /.,J
BY WL--
DATE C/?/1 '!}'
SH.4 OF
consult1ng & des1gn • str:.:ct:..ra! engtnee'S
5762 balsa avenue. suite 215
huntington beach. co 92649
714 891-5582
l.u't1~5
L-=:-U 1
p ::.. ( ~l1) J 4:'){6 I~~ \I ;?p tt· M c:. t:..t ~~ ... ~·
~· {~A,e;ei) ~,J et)OT Z5D~·11)~ U/~4'1 .
.::;.. ~.4~4f21;ff-4?~
JOB NO! 5! 0~,;;
BY WI-
DATE V/tS
st!.{-A OF
/.f.d;J~ JZ:4~ ~~~ {)~tf.f&J.~ w t n+ .tt.), t::L:. . 'i}' iVI /) r: E::AtJra.t..z ...
~ ~ ?66.r t/57.1'~ 11;4 ~
cMt-n+ (~) 4~'tf ~Jt'?!
~/ 7?t.etJ~~"t:fdtl i
\ J .\1'[1 ,, . l;: 'IA·fA., ~ t7bO)l . Y~;s wf;
t' I r),;Se_ {~ 14-H,J ~IL2
i'O ~) p..~ 27V f)~
1-0
TABLE 1: STRUCfURAL PROPERTIES OF SfUDS, JOIST, AND TRACK (CONTINUED)
11:? l 0~
1 B. 16, & 14 "HDJ"
. 6" & B" Web Depth
Floor Joist
16 & 14 "HOJ"
10" & 1211 ·web Depth
Floor Joist
Web De \II 0.0. Web 0. lh 0.0.
16, 14, & 12 "FJ"
Floor Joist
.219" inside roclius
.4l3" for 18 It 16 CIJJGE I .481" fo< 14 G.ll.JGE
16, 14, 12, & iD "XFJ"
6" end B" Web Depth
Floor Joist
,4.3311 typ. 15 GA. I .461" eyp. 1• GA.
.16, 14, 12, & 10 "XFJ"
1 O" end 12" Web Oepth
Floor Joist
9
Web De \II 0.0. Web De th O.D. Web 0. lh D.O.
_[ .7!50" typlcol
MEMBER MINIMUM WEIGHT
DESIGNATION DESIGN (1belfl). GROSS SECTION PROJ'£R11ES
TIUCXNESS
(inches) Area bx Rx Iyy Ry
(inA2) (inA4) (inA3) (in A 4) (in A3)
18HDJ600 0.0451 1.415 0.417 2.061 2.225 O.Q92 0.469
1SHDJIOO 0.0451 1.721 0.507 4.173 2.870 O.Q98 0.440
16HDJ600 0.0566 1.765 0.520 2.554 2.217 0.112 0.464
16HDJIOO 0.0566 2.149 0.633 5.181 2.861 OJ19 0.435
16HDIIOOO 0.0566 2.629 0.774 9.773 3.553 0.191 0.496
.9G2" typ. 1G, 14, 12 GA.
_[ 1.000" lyp. 10 GA.
EFFECI'IVl!SECTION
PROJ'£R11ES
bx Sx Area
(mA4) (in A3) (in All
2.061 0.687 0.417
4.173 1.043 0.501
2.554 0.851 0.520
5.181 1.295 0.633
9.773 1.955 0.774
MOM!NI'
CAPACITY
Ma
(in-lbo)
14536
20705
25492
38781
493%7
.9&2" typ. 15, 14, 12 GA. I 1.000" eyp. 10 GA.
TORSIONAL SECTION
PROPERTIES
Xo J cw Ro
(in) (inA4) (_inA6}_ _(ml
-0.849 1.S24E-04 0.679 2.427
-0.731 3.436E-04 1.299 2.994
-0.838 5.54l!E-04 0.826 2.415
-0.721 6.1S1E-04 1.585 2.983
-0.794 8.26SE-04 3.920 3.674
s
0.878
0.940
0.880
0.942
0.953
TABLE I: STRUCfURAL PROPERTIES OF STUDS JOIST. AND TRACK(CONTINUED) t 01[0!.
TORSIONAL SECilON L!
MEMBER MINIMUM WEIGHT E1'FECilVE SECTION
PROPERTIES MOMENt" PROPERTIES
DESIGNATION DESIGN (lbslft) GROSS SECilON PROPERTIES
14HDJ600
14HDJ&IO
14HDJ1000
14HDJ1200
16FJ600
16FJ&IO
16FJ1000
14FJ600
14FJ&IO
14FJ1000
14FJ1200
12FJ600
12FJ&IO
12FJIOOO
12FJ1200
16XFJ600
16XFJ&IO
16XFJ1000
14XFJISOO
14XFJ&IO
14XFJ1000
14XFJ1200
12XFJ600
12XFJ&IO
12XFJ1000
12XFJ1200
10XFJ600
10XFJ&IO
10XFJ1000
10XFJ1200
CAPACITY
TinCKNESS
(lnchel) Area lxx Rx I I" I Ry lliX Sx I Area Ma Xo J I Cw
Rol
(ln All lin A4) linA3) linA4) (inA3) (iDA4) (UIA3) (inAl) (in-lbo) (in) (in A 4) (ill A6) tinl I
0.0713 2.219 0.653 3.191 2.210 0.139 0.462 3.191 1.D64 0.653 31550 -0.541 1.107E-03 1.035 2.409
0.0713 2.703 0.796 6.457 2.855 0.149 0.433 6.457 1.622 0.796 48556 -0.723 1.349E-03 1.990 2.976
0.0713 3.309 0.974 12.253 3..546 0.239 0.495 12.253 2.451 0.974 73005 -0.796 1.6S!E-03 4.931 3.668
0.0713 3.793 1.117 19.4a! 4.169 0.247 0.471 19.4a! 3.235 1.117 8700! -0.715 1.893E-03 7.481 4.256
0.0566 2.278 0.671 3.775 2.373 0..579 0.929 3.775 1.258 0.671 32974 -2.006 7.162E-04 4.650 3.243
·0.0566 2.662 0.754 7.409 3.074 0.634 0.900 7.409 1.852 0.754 48831 -1.788 8.37CE-04 8..566 3.669
0.0566 3.Q46 0.897 12.611 3.749 0.676 0.868 12.611 2..522 0.897 60210 -1.617 9..579E-04 14.00S 4.175
0.0713 2.852 0.840 4.697 2.365 0.714 0.922 4.697 1..566 0.840 42985 -1.991 1.423E-03 5.112 3.226
0.0713 3.336 0.982 9.234 3.066 0.782 0.892 9.234 2.309 0.982 637(1;1 -1.774 1.66SE-03 10..547 3.653
0.0713 3.820 1.125 15.737 3.740 0.833 0.861 15.737 3.147 1.125 87779 -1.604 1.906E-03 17.270 4.159
0.0713 4.305 1.268 24.489 4.395 0.873 0.830 24.489 4.081 1.268 1041Sl -1.466 2.148E-03 26.Dl4 4.707
0.1017 4.017 1.183 6..527 2.349 0.973 0.907 6..527 2.176 1.183 64807 -1.961 4.078E-03 7.731 3.191 -0.1017 4.707 1.386 12.882 3.049 1.067 0.877 12.882 3.221 1.386 . 9,5928. -1.744 4.779E-03 14.34:2 3.620
'· ·'·"" . , "'.
0.1017 5.398 1..590 22.010 3.721 1.137 0.846 22.010 4.402 1..590 13~14! -1..575 5.48CE-03 23..554 4.128
-·
0.1017 6.089 1.793 34.316 4.315 1.191 0.815 34.316 5.719 1.793 170430 -1.438 6J81E-03 35..564 4.677
0.0566 2..541 0.748 4.357 2.413 0.981 1.145 4.295 1.a19 0.741 37819 -2.622 7.99CE-04 8.632 3.743
0.0566 2.925 0.861 8.489 3.139. 1.083 1.121 8.374 2.076 0.854 55822 -2.363 9.199£-04 15.362 4.056
0.0566 3..502 1.031 15.744 3.907 1.681 1.277 15.340 3.020 1.015 70231 -2.577 1.101E-03 35.197 4.852
0.0713 3.184 0.937 5.427 2.406 1.215 1.138 .. 5.427 1.809 0.937 48210 -2.607 1..589E-03 10.635 3.726
0.0713 3.668 1.080 10..591 3.131 1.341 1.114 10..591 2.648 1.080 71086 -2.348 1.830E-03 18.968 4.D70
0.0713 4.394 1.294 19.673 3.899 2.086 1.270 19.i77 3.803 1.274 98863 -2..562 2.193E-03 43..594 4.835
0.0713 4.879 1.437 30,222 4..587 2.202 1.238 30.092 5.000 1.432 117686 -2.372 2.434E-03 64.985 5.310.
0.1017 4.490 1.322 7..560 2.391 1.670 1.124 7..560 2..520 1.322 79397 -2..576 4..558E-03 14.486 3.690
0.1017 5.181 1..526 14.806 3.115 1.845 1.100 14.806 3.701 1..526 11~225 -2.318 5.28CE-03 25.950 4.036
1
0.1017 6.217 1.831 27..594 3.882 2.882 1.255 27..594 5..519 1.831 158709 -2..532 6.311E-03 60.028 4.802
0.1017 6.908 2.034 42.458 4..569. 3.043 1.223 42.458 7.076 2.034 198211 -2.343 7.013E-03 89.655 5.278
0.1285 5.650 1.664 9.393 2.376 2.077 1.117 9.393 3.131 1.664 93747 -2..576 9.157E-03 18.196 3.679
0.1285 6..522 1.921 18.465 3.101 2.297 1.093 18.465 4.616 1.921 138211 -2.317 1.057E-Ol 32..517 4.D22
0.1285 7.832 2.306 34..Sa! 3.868 3..598 1.249 34..Sa! 6.902 2.306 199831 -2..531 1.269E-02 75.3Cll 4.789 --
0.1285 8.704 2.563 S3.173 4.5SS 3.800 1.218 53.173 8.862 2..563 256860 -2.341 1.411E-02 112.4:21 5.264
1. Effective properties are based on all18-gauge and lighter steel studs, track, and joists having a yield strength
(Fy) of 33 ksi. All16-gauge and heavier steel studs, track, and joists are based on a yield strength of 50 ksi.
2. The Effective section properties are determined from the total effective widths of each element in accordance
with the 1991 U.B.C. Standard No. 27-9.
3. Effective Ixx is based on Procedure I for deflection determination at the allowable moment (Ma).
B
0.875
0.941
0.953
0.972
0.617
0.762
0.850
0.619
0.764
0.851
0.903
0.623
0.768
0.854
0.905
0..509
0.666
0.718
0..510
0.667
0.719
0.800
0..513
0.670
0.722
0.803
0..509
0.668
0.721
0.802
11
5762 Oo:s:J 'JV-?nue. S:_;·+e :·~ 5
1-iunlington beech, -:::::1 ~26.:1;
71£~ 891-5582
I L-=-Wf
w~~ (~)o1)~~tp7~
A A _.# e ~r 4" ~.t 1. h. 1.-·~) , .. ,, ;:. 7 ~7,' ( Jl!':-. t7ll :::-'t"c:.v .
.:J:;L ::.. 0 4,0r
t$e£ M 1J WI t.>t zz.._
J lP ~ ~ j\ I-+ V tJ t ~ c ~ N'Te~ctJ ov t= fl C.-&P 1-;
JOB NO/ t; I Otp
BY WL-
DATE at f5
SH. 7 OF
~A-: ~Off"~---?()llt-.C' ~t:Rvt~ t...L. "I'D l8 f~ ( /1 c.-U> eo tJ. )
C:ot.JMaJ$:
H-... :;:_ l1',1 ~ . ! lJF·4-f t"L ~ Cl LIS'O · fl\ ~{~tt) / t.-~ tz ).r: ~ 0
~-t ~.~It-+ ~\I:: tc:i~A~
u) t -t-14 ~+s c; 4'PJ ~ ~(... ~
PA-u....:;. ~&~,e~ .C~ ~ tp,o ~?' f..ltA.~ +~~{A_::,-;~ f;; .-_;,. q.,., ~\ /t1,~~, ';~ .
UtJ l '"Ill.( L_ L 0
57 62 boise avenue S.J'"e 2 · 5
r-,untington beach, c~ 92b4;
714 891-55.32
b BM·~ f)~IE:~i&vtJeAnotJ? :
r)qe We: ~~AA~fJ /Atrrn~oC'
A~ 71) rA r;_ 0_.,a,p 11-+·f.-. ,:.. !}11 (h)
h "L, .. I /.1> j ·~·· "'!" "t ~t~ ~ ~ u4-.,Q(J~ h ~-L eD4P
A$>v t"flt=.. ~. :: .. C?a fC\ A-~., )'t, ~ e., ~ "~
~ tte f~ \
~~ '-{, q)L ri)( ~t:Pi)"' I lA 0 ~ 11~ P?'
JOB NO. f 51()~
BY \A.Jt__
DATE U/1§
SH.0 OF
5762 CO·SC '.J\/2n'J8, 5L'~B :·::
huntir,gton beocr·. co 92649
714 891-5582
& r2-PA .. tJ'bt-I A~ft:;; ;?e.r-C?H!J7 ll-~ 7, ,
r'~-nJ,,t.,.g. $(;4N Bt:.:rw, L.Vutt ?rtJV'?~ 4--'tit--
H-r=-t"Z..'
JOB NO.{ q~/)~~
BY WL,.,.-
DATE tl/f~
SH. \t> OF
9~tt ?~ UP~~ t~l ~41'1'!.-WlrZt::. 7n)p P~ff:.~JJf.:.G
WH-tllt-1 ~ :;c { ~) 14) :;;-Z&> ~ vJ c.; Ut:> ~ M 'C: t.f1, 'U> !!~
f/ . :Ctz. C 'il~t.?)~J~&ttuJ+ ~L 1 Z..tJ-~1~ ~ ~ Jfltta I f?l
\pI Jc·;:;. ,·t>~y,p'1 ~I~ 1--r-;;;~ 11,., 'Jt-? I
P,t :; ( (1-t -u;){ tt) {tl, t1?) ~ ·~L)JJ MAX;
+t-L ~ l~t~1 P$ t
(LPjY' ~ I'Z. )tt-y'l. u4.r I W
F-A ,. '?"I Jtlo /1 't.t' t. r:::-? 51 ?rPJ I
, '. VJ't n ~· ~ ~ z/;, ~, '; :;.. ... ~ o lt.--
i' ' I 4-lf u) I a IE:-'71V ft?-e tf~ tt ~ t!> ~
p 8 J 7 LA--1$ -==~ ~,{ {j£) tt·t-11 A~">1 I J. I~ u 'L.£;;: + ~~ f?f) /11.) c CJ t;/.J ~
("'' ..-:7" n, c {p ?tpr7~ ~I vi P r~ F·
/, (~)7'-A-~ 0\t.-
Prepared by:
J< 7 . /If{ l · {,r4-v"-w v
Bharath Gomatam
Consultant
RADCO TEST REPORT ·
Test Report No. RAD-2858
Project No. C-8129
Lab No. TL-2046
Transverse Load Tests on Steel Faced Aluminum D-lite Panels
Prepared for
CLEAN ROOMS WEST, INC.
1392 Industrial Drive
Tustin, CA 92780
by
RADCO
Resources, Applications, Designs and Controls, Inc.
Listing and Testing Division
3220 E. 59th Street
Long Beach, CA 90805
Telephone: 562-272-7231
Facsimile: 562-529-7513
www.radcoinc.com
Issued: July 2001
. Tucker, P.E.
enior Vice President
1?/tJ~
r f
RADCO reports are for the exclusive use of the client to whom they ere addressed. Permission Ia granted to reproduce this report provided It Ia
reproduced In Its entirety. The use of the name RADCO (Resources Applications, Designs and Controls, Inc.,) In any advertising or related materials
must receive prior written approval from RADCO. Reports apply only to samples tested at the time of testing and are not necessarily Indicative of the
quality of apparently Identical or similar producta. Thla report contains confidential information Intended for the sole use of the addressee. Transmittal
by facsimile Ia prohibited without the express approval and concurrence of the addressee.
RAD-2858
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 TEST SPECIMENS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.0 TEST SETUP & PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4.0 TEST RESULTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5.0 CONCLUSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
APPENDIX
Table: Load Vs. Deflection Data (A 1)
Chart: Load Vs. Deflection Curves (81)
Figure: Typical Test Setup (C1)
Photographs: (D1)
ii
RAD-2858
1.0 INTRODUCTION
At the request of Clean Rooms West, Inc. RADCO conducted a transverse load test on one (1)
nominal 4 ft. x 1 0 ft. panel. The test was conducted in accordance with ASTM E 72-98, "Standard
Methods of Conducting Strength Tests of Panels for Building Construction•.-· ··-
2.0 TEST SPECIMENS
One panel was submitted by Clean Rooms West for testing and received at RADCO's testing facility
in Long Beach, California on June 7, 2001. The panel was described to RADCO as follows:
"Panel is 3 mm Aluminum 0-/ite panel on each side of 3-9116• EL foam with Staybond U283
adhesive"
3.0 TEST SETUP & PROCEDURE
3.1 EQUIPMENT
1. Digital Manometer, 0.1 inch of water column increment readings.
2. Digital dial indicators, 4" travel with 0.0001" resolution.
3. Computerized data acquisition system.
4. Vacuum pump.
3.2 TEST SETUP
The panel was placed horizontally in a reinforced frame such that the ends rested on W' diameter
steel rods placed between %" metal skins, on the 3%'' wide support surface. The test chamber was
completed through the use of a 6 mil thick polyethylene sheet draped over the test panel, folded over
the edges of the test fixture, assuring that bridging of the poly sheet would not occur, and sealed to
the floor. The load was applied by evacuating the air below the test specimen. The applied load was
measured with the digital manometer. Deflection measurements were taken at three locations across
the mid-point of the panel and at the center of each end to record any vertical movement at those
locations. ·
3.3 TEST PROCEDURE
Load was applied in pre-set increments, held for 5 minutes, and returned to zero after each load
increment. Deflection readings were taken at each load increment and after the load was released.
The panels were allowed a five minute recovery period before taking the zero load deflections and
proceeding to the next increment. The panel was then continuously loaded to failure after taking the
last deflection and set readings.
Pon"' 1 nf?
RAD-2858
The average panel deflections and sets were calculated as follows:
Average Panel Deflection (&set)= Average Midpoint Deflection-Average Endpoint Deflection
The digital manometer reading in inches of water column was converted to pounds per square foot
using the relation; 1• w.c. = 5.20 psf
4.0 TEST RESULTS
The table in the appendix contains the raw load vs. deflection data collected during the test, and the
chart shows the load vs. deflection curve. The test was conducted at RADCO's Long Beach,
California facility on July 20, 2001.
ULTIMATE LOAD AT FAILURE (psf)
PANEL SIZE ULTIMATE LOAD AT FAILURE (psf)
4' X 1 0' Aluminum 0-lite 42.12
Mode of Failure
Failure in the panel occurred when the top metal skin buckled approximately 48" from one
end.
5.0 CONCLUSION
The panel design load is 14.04 psf utilizing a safety factor of 3.0.
****END OF REPORT****
Paae 2 of 2
APPENDIX
Table: Load Vs. Deflection Data (A1)
Chart: Load Vs. Deflection Curves (B1)
Figure: Typical Test Setup (C1)
Photographs: (01)
RAD-2858
TRANSVERSE LOAD TEST on 4ft. x 10ft. WALL PANEL
LOAD
Inches of w.c. osf lbs. -Defln.
0.0 0.0 0.0 0.0000
0.4 2.1 83.2 0.0206
0.8 4.2 166.4 0.0708
1.2 6.2 249.6 0.1219
1.6 8.3 332.8 0.1772
2.0 10.4 416.0 0.2304
2.4 12.5 499.2 0.2802
3.2 16.6 665.6 0.4046
4.0 20.8 832.0 0.5228
Ultimate Load (psf) 42.12
A1
-Set
0.0000
0.0028
0.0044
0.0081
0.0109
0.0141
O.o126
0.0151
0.0300
L ;-1o b
ttl
RAD-2858
i c. -"D "' 0 ....
2 5
9
2 0 : . . . . . . . . . . . . cp . . . .
15 . . . . . . . . . . CD . . . : .
I
6
10 . . . . . .
(!) . . . . . . cp . .
5 . .
~ . . . . .
~
0
0.00
/
0.10
Transverse Load Test on 4' X 1 o• Panel
J-e--Deflection - -o · ·Set J
I
I
I
v
I I
.
0.20
I
/
I
I I
0.30
Deflection (in.)
B-1
I
/I
I
I .
0.40
RAD-2858
L-J>
I
I
0.50 0.60
Fig 1: Transverse Load Test Setup
%• roller support
resting between
'""'"'~r-7' metal plates
Test Panel
Vacuum
Fig 2: Dial Indicator Locations
Digital Dial Indicators
Average Deflection= (2+3+4)/3-(1+5)/2
Iestl..ab-P:\Cinrooml .tcw
Not to Scale C1
RAD-2858
\_ 6 mil Plastic
sheet
RAD-2858
Transverse Load Test per ASTM E 72-98
Close-up view of end support
Close-up view of failure
n-1
SGS•SGS•SGS•SGS•!:3S•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGSeSGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGSeSGSeSGS•SGS• Cll • 0 m ~ ~ US-0-0PS-04-01-T ~ i @ BGB ® SGS U.S. Testing Company Inc. ~
(/) (/) ~ 5555 Telegraph Road • los Angeles, CA 90040 • Tel: 323-838-1600 • Fax: 323-722-8251 ~
(/) (/) 0 0 ~ ~ ~ CLIENT: CLEAN ROOMS WEST, INC. ~ ~ ~ m 1392 ln~ustrial Way ~
(/) (/) ~ Tustin, CA 92780 &> 0 0 ~ Dieter Graf ~ 0 0 ~ ~ (/) (/) 0 0 ~ ~ ~ ~ ~ ~ ~ T.est Report No: 151195 Date: January 30, 2001 ~
(/) (/) 0 0 ~ f ~ SAMPLE ID: The Client submitted and identified the following test materials as 3mm ~
~ Aluminum D-lite panel on each side of 3 9/16" of El foam w/ Staybond U283 g
~ adhesive. JJ ~ ~ ~ ~ ~ g fg DATE OF RECEIPT: Entered into SGS USTC sample tracking system on January 19, 2001 as STN 0
~ g ~ 32782. J,
<Q g 13 ~
<Q TESTING PERIOD: January 29, 2001. g tg ~
<Q g
~ AUTHORIZATION: Client's Purchase Order No. 10158. ~
~ ~
<Q ~ m TEST REQUESTED: Perform standard flame spread and smoke density developed classificatio~ tests on :g
~ the sample supplied by the Client in accordance with ASTM Designation E84-99, ~ ~ "Standard Method of Test for Surface Burning Characteristics of Building Materials". ~
~ The foregoing test procedure is comparable to UL 723, ANSI/NFPA No. 255, and ~
<Q UBC No. 8-1. g ~ ~ <Q g
~ TEST RESULTS: Flame Spread Smoke Density ~ ~ ~ ~ (/) ~ g m 5 90 &> <Q g
fg For detailed results see page 3. 0 ~ ~ m m <Q g m ~ <Q g m ~ <Q 0
(/) ~ ~ Prepared by ~~ for and on behalf of ~
~ Greg Banasky ~omash ~
~ Supervisor Fire Technology .,'Branch D1rector ~ m ~ <Q ) ~ fg :g <Q (/) ~ ~
<Q 1 f g ~ Page o 4 0 ~ This report is issued by SGS U.S. Testing Company Inc. under its General Conditions for Testing Services (copy available upon request}. SGS ~
~ U.S. Testing's responsibility under this report is limited to proven n&gligence and will in no case be more than the amount of the testing fees. ~
:g Except by special arrangement, samflles are not retained by SGS U.S. Testing for more than 30 days. The results shown on this test report refer ~
~ only to the sample(s) tested unless otherwise stated, under the conditions agreed upon. Anyone relying on this report should understand all of ~ m the details of the engagement. Neither the name, seals, marks nor insignia of SGS U.S. Testing may be used in any advertising or promotional ~ ~ materials without the prior written approval of SGS U.S. Testing. The test report cannot be reproduced, except in full, without prior written ~ ~ permission of SGS U.S. Tasting Company Inc. g
~ lA.a ....... l...a. ,.,. .~.. .... ~~e ~--"-~~--:.t..,~. ,...~.._,~.. __ ._ ~-,... ______ !11----' -~
[fi?lt'/P
Z·l
SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS• 0 ~ * ~ .US·D·OPS-04-03-T ~ I t~·L\s~s® i ~ S l.iil SGS U.S. Testing Comp~ny Inc. Report No.: 151195 ~
en en g. g en Date: January 30, 2001· ~
~ CLIENT: CLEAN.ROOMS WEST, INC. Page: 3 of 4· ~ en en
f f ~ ! ~ g
en E 84 TEST DATA SHEET: ~ ~ ~ .. ~ ~ ~ •. CLIENT: Clean Rooms West, Inc. DATE: 1/29/01 ~ ~ ~ en ~
(!> " ~ SAMPLE: 3mm Aluminum D-lite panel on each side of 3 9/16" of El foam w/ Staybond U283 adhesive <e en -en
(!> " ~ ~ en en ~ ~ ~ THICKNESS: 3 3/4" nominal i ~ m ! ·~
(!> " ~ FLAME SPREAD: ~
~ 'e en en
(!> " ~ IGNITION: 3 minutes, 46 seconds ~ ! ~ f FLAME FRONT: 2 feet maximum ~
(!> ~ ~ 'e ~ TIME TO MAXIMUM SPREAD: 6 minutes, 27 seconds ~
en en
(!> " ~ TEST DURATION: 10 minutes ~
~ ~
(!> " ~ CALCULATION: 10.67 X 0.515 5.50 ~
(!> ~ ~ ~
(!> " ~ ~ en en ~ SUMMARY: FLAME SPREAD: 5 SMOKE DENSITY: 90 ~
~ ~
(!> " ~ 'e
(!> OBSERVATIONS: Sample surface ignition occurred at 3 minutes, 46 seconds. A maximum flame front ~ ~ ~ o advance of 2 feet was observed at 6 minutes, 27 seconds. ~ ~ ~ en en ~ ~
0 ~ ~ ~ o m ; ~
0 ~ ~ ~ ~ " en ~ 0 (!> ~ ~ en en ~ ~ ~ m ~ ~
0 ~ ~ ~ ~ In 0 (!> ~ ~ ~ (!>
m ~ ~ " en ~
(!> m ~ ~ ~ In ~ ~ ~ g ~ MAmhar of the SGS Grouo (5oci8t8 G8n8rale de Surveillance) ~ .•
\:PIP{}
t,.~
SGS•SGS•SGS•SGS•SGS•SGSoSGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS• Ill ~ ~
Ill US-0-0PS-04-03-T Ill ~ g I @SGS® SGS U.S. Tes~ng Company Inc. Report No.: 151195 ~
~ ~ ~ ~ ~ Date: January 30, 2001 ~ ~ 0 ~ CLIENT: CLEAN ROOMS WEST, INC. Page: 2 of 4 ~
g ~ . . Ill Ill ~ ~ ~ Q,
Cl 0 ~ re ~ PREPARATION AND CONDITIONING: The sample material was submitted in three pieces, 24" wide by g
~ 8' long. The pieces were placed end to end to form a specimen 24" wide by 24' long. ~ ~ ~ Ill Ill Cl ~ ~ Prior to testing, the specimen was placed in the conditioning room (maintained at 73.4 ±5° F and a ~ ! relative humidity of 50 ±5%.) and allowed to reach moisture equilibrium. ~
~ ~ . . Ill Ill ~ SUMMARY OF ASTM E84 RESULTS: .Because of the possible variations in reproducibility, the results ~
Ill Ill ~ are adjusted to the nearest figure divisible by 5. ~
0 0 w ~ ; SAMPLE FLAME SMOKE g
~ IDENTIFICATION SPREAD DENSITY ~ ~ ~ ~ ~
:+: D-lite pa·nels 5 90 If 0 Ill ~ Adhered to each side of ~
~ Elfoam ~ m ~ ~ ~
; In order to obtain the Flam.e Spread Classification, the above results should be compared to the ~ ~ following table: ~
~ ~ ~ ~ m NFPA CLASS UBC CLASS FLAME SPREAD ~ ~ A I ~ ~ 0 through 25 ~ ~ g ~ B II 26 through 75 ~
~ ~ ~ C Ill 76 through 200 ~
~ :E ~ fn ~ ~ m BUILDING CODES CITED: ~ ~ 1. National Fire Protection Association, ANSI/NFPA No. 101, "Life Safety Code", 1994 Edition.· ~
~ ~ ~ ~ ~ 2. Uniform Building Code, 1994 Edition, Chapter 8, Interior Finishes, Sections 801-807. ~ ~ ~ ~ ~ m ~ ~ If 0 Ill ~ 0
0 If 0 Ill ~ g ~ ~ ~ ~
Ill ~ 0 Ill ~ 0
Ill ~ ~ m ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ 0
Ill ~ ~ m ~ ~ Cl 0 ~ ~ ~ ~ ~ Ill m ~ ~ ~ m ~ ~ ~
:g · Member of the SGS Group (Societe Generale de Surveillance) ~
---------U)
. (~IP?'
8, S03S•SGS•SGS•SGS•SIJS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGSoSGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGS•SGSt~~
f US-0-0PS-04-03-T ~
(/)(/)~. ~s~s® ! ~ _. 1.:1 SGS U.S. Testing Company Inc. Report No.: 151195· ;
(/) (/) f ~. Ul Date: January 30, 2001 (/) ~ CLIENT: CLEAN ROOMS WEST, INC. P 4 f 4 ~ ~ age: o (/)
m ~ 8, (/) ~ ~ ~. ~
(1.) & ~ Cl
tn & ~. Cl
en ~ ~ FLAME SPREAD AREA ~ ~ (/) ~ Cl ~ ALUM. D-LITE PANELS ADHERED TO FOAM ~
~ 20 1------~··~-~-··--·· ---__ . -··-;;,;;;;;;.--...;.._ -·-----~
i.i: ' / Cl • I r. ~ Ul / (/) Ul~ 15 ...j ,..... . g
I 8, ~ 1-' / Cl ~ ·~10l /,..... ~
Cl J ~ ~ 5 ! I ~ ~ • _, . ::rv• 1 I I I I I I I I I I I I re
i.i: 0 ~-~...._.~o~l<'l:;.~..,_l ...._'-, •' ...... .~-.~.1-'1.:-1 .~oo..~ool .JII"""' ·'·-~ JS .L I.J..Ll..J...LJ_J..l~U..J.. ~ ~ ~ Cl 0 2 3 4 5 6 7 8 9 10 (/) ~ Cl
Ul ~ ~ TIME (MINUTES) ~
Cl ~ ~ ~ ~ --SAMPLE - -RED OAK F .S. AREA ~
0 ~ Cl Cl ~ ~ Ul (/) Cl Cl ~ ~
Cl ~ ~ ~ ~ (/) ~ Cl ~ SMOKE DENSITY .~
Ul ~ ~ ALUM. 0-LITE PANELS ADHERED TO FOAM ~
Cl Cl ~ 100 ~ _...;__ ·------'--.. ·-----· __ .. ~ ~ I. l ~ ~ I ~ Cl c 80 .. (/)
rq 0 .. ~
Ul = I 0
i.i: ~ 60 j Cl ~ ~ : . ~ ~ !::1 -./----'"-~L i
! / ~ ~ 0 i. .. l. .J. -~.l.LLLLL.LU_J..l..LLJ.. Cl ~ 0 2 3 4 5 6 7 8 9 10 ~
Ul ~ ~ TIME (MINUTES) ~
Cl ~ ~ ~
Cl ~ ! SAMPLE - -RED OAK ~
Cl ~ ~ ~ ~ Cl
0 ~ ~ Cl
Ul ~
Cl ~ ~ ~
l,g ******** (/) ~ ~ ~ End of Report ~
~ Member of the SGS Group (Societe Gemlrale de Surveillance) · ~ ----------------------------------~------,roo-(I)
a.· -· :: OF INDtANAPOLJS ."NO. 0
•
~nuhc:terer/Fabric.ttor ()/ ELFOAM" ttolyiso Produt:U
ELFOAM P200 Polyisoc anurate Foam
Product Description
sroamc81 1'200 Ia a 2.0 lblft,, rigid, unfaced, closad ceH,
HCFC fret polylsocyanurate foam s1.1pplied as aJt Shetl$,
CU$10m shapes and in lutstock form for • variety of
insulation and oore material applications. PolyiGOCy11nurate
foam I$ chemically slmDar to polyurelhene fofm but offers
better dlmenslonlll stabiHty over 11 Wider service temperature range.
Elfoam P200 Ia manufactured In burlliltock fonn 24• (61cm)
thick by 48" (122cm) width by 72" (183cm), 98" (244cm),
108" (274cm), 120• {30$:m) and 144• (39Elom) tongths.
Cut thtete are offered in thlckneU from 118" (.32an) to
12" (30cm) In 1/32" (.OScm) Increments. Custom fabrioated
parts are avaDable for r;uetomers wlshlng to eliminate in-
houee cutting, handling and scrap disposal. Contact the
Indianapolis omoe for additional information.
Application••
Eltoam P200 Is designed ror use In environiYlllntl; where
temperaturctlll'ltlgt from -so•F to +300"F (~•c to
+14ga0). However. In non-lamlflated appliclltkms whare
P200 It exposed to tampGritU11t exceeding 140"F (SO•C)
and/or rel1t1ve humidif;y Is In excess of 70%. aHowances
fol' foam expansion must be tnc:orporatad Into the
engineering dellgn. Regardless of oper4ting conditions, a
qualified design engineer &tlOUid revieW d foam
applicatiOnS.
etoam, like aH cellufar plfttics. \\'il degrtldt upon
prolongod tlCpoturt to sunDghL Cover foam material In
Older to bloCk ultravJotet radiation ""d prevent
degradation. Other coveringalo protoct ~ foam
surlJcta from the elemsnts and to meet appUcable flra
regulations may also be required.
Typically Used In
• Refrigerated (cod service equipment
• Laminated buDding waD panete
• Commerelal and lndusbtal door&
• FRP tanke and $heltenl
• Proofing ovens and dough rttarde11
• CNC taolln; and proofing E~ppltcatiOI'ts
Environmental Data
Ell'bam P200 le spdc:ally formulated to provide excenent
phy$1cal propertias Without the use of chloroftuorocarbon
(CFC) or hydi""Cldllorofluoi'OCI81bon (HCFC) blowinfl agents.
In compUance With the Montreal Protocol and the Clean Nr
Act, Elfoam P200 Ia manufaclurad wllh hydrocarbon blowing
agents whioh heve no ozone de~on and no global
WBlTiling potenUal.
Safety
All peraona wtlo work with Elfoam products should follow
proper handling prooedtWS. The cu!Ttnt Material s..rety
Oata Sheet (MSOS) containS information on the proper
hand6ng, storage liNld use of this malarial. A copy Of the
MSOS may be obtained by calfing the lndianapoli$ Sales
Offl06.
9Z00 Zionsville Road •Indianapolis, lndiaM 46268 • elllott@cUiottfoam.com
Toll Frtetl-R00-$46-1213 • Phone: (317) 291·1213 • FalL: (317) 291-1219
December 2004
Product Desc:riptfon Etroam P200 Is a rigid unfaced closed ceft potylsoeyanurate foam material. This HCFC free product provides exceRent thermal
lnsulalion perfonnance 1n servlee tamperature environments betWeen .SO"F to +300"F (-45"C to 149•C) when property laminated on
tiOih sides wltl1 rigid vapor barrier ty(M materials. etoam is r.uppr~ed In &tandard and custoM fabrlcatad sizes and shapes.
ASTM Typieal ValueS(")
Phy!ic:al Proer!fet!1l!21!3' Method l!nglllh Metric
Density, Average.. .. .. .. .. .. .. .. . .. .. .. . .. .. . • . 01622 2.0 lblfr 31.91<g/m5
k..fadOf(D) ...... ' I ••• ' ••••• I • ' ' ••• ' •• I •••••••• ' I .~18
lnltiiJiat 75'F (24•C) ................... 0 ••••• o •• :. o •• 0.165 BTU • inlhr • rt2-•f
Aged 10 dsya lit 15B•F (70'C) ......................... 0.185 STU •lnlhr • ~· •f
R-valuelinch
Aged 10 d8Y$ at t58•F {70°C) • • • • • • • • • • • • • • . . • • . • . • . . . . . • . 5.4 Hr • tr• "F/BTU
Comprasslvt Strength ........................... 01821
Parallel ..... ., ~ ....... , .......................................... 261blin2
Perpendioular ••..•••....•..•.••..•••••••..•••••.......••.•• 171blin2
Compressive ModUlUS •••••••• , ••••••••••••••..•• 01621 Patt~llel ..•.•.••...........•................•.•.•......••.• 445 lbtm2
Perpendicular ..••..•••..•••••••••••........•.••••••••••..•. 3881blln2
Shear Strength •.••.....••••.•••.••••••.......•• C273
Parallel. I ••• Ill •••• ' ' r ••• I I •• I : •• a , ' ' ' I I I I ' I •• • .••• ' •• I ••••• I 221blin2
Perpendicular •......•••.••••••....•.••..•••..•..•..•••••••. 161blin2
Tensile Strength •••••.•••••.••.....•••..•••....• 011323
P.-rallel ............................................... , .... 51 tblin2
Perpendlculllr • • • I I I II I I I I I a • • • • • o I I I I 'II' I I I I I I I • • • I I I I I I I I I I I I 47lblin2
Tensile Modulus .••.••••.•..••..••...••.•••••••• 01623
PefiJ//e/ •. I I I I I I I I I I I I I I • I • • • If I I I I I I I If I o oo • • • • • o o I I I I I I I I 1.3951blin2
Pefpendloular t t f I I I I. I I I I I I I t f I • 't f I 1 1 I I I I I I • • 1 f t I f 1 I I I I oo oo • 1, 1341b/in2
Closed 0811 Conten~) ............................ 02856
F~bllity {wel;ht toss) ..•••••••••••••• I • , ••••••••• 0421
Water Absorption {by volume} ••• 1 •••••••••••••••••• C272
92%
8%
1.27%
Dlmenslonrd Stability (volume change) ••••••••.•.••.• 02126
15B'F ('10°0) + 97" R.Hn dsys •••................•......•.....••.•.... ~.0%
212"F (100'0) ~Ambient R.Hn days •.••.....•....••••••............••.• +0.9%
-40"F (-40'C) +Ambient R.Hfl days ••••• , ..••.•....•..••..••....•.•..•..• -0.6%
Surface Bumlng ChareotaristiC$(1) .•..••.•...•.•..... E84-Q1a
Flamt Spread up to 6• (15.23 em)........ . . . . . • . • . . • . . . . . . .. . .. .. . .. • • . . . 25
Smokt Dfvttloped up to 6• (1~.23 em) •••.•.••...• , ••.•••••••.•••..••.••.•• 185
.024WJm•c
.027W/m'C
172kPa
117 k?a
3~066kPa
2~535kPa
151 kPa
110kPa
351 kPa
323kP•
9,611 kPa
7,813 kPa
(t) O.ta•hown •re ·~ Vlllu• e~'b!Ainal tmm fiPIWCIIIIIIVC productlollllplils. wd= lllhmwi" indiQtlld. ~ The tulraltilil)l ot!hil prodDet tor ltlrf panil>lllar applitilillll illha n:lflllllllbllity 11flhe uHf, 'rM poccotill wocr l•1q10ruible ftlr performiq any pmtillc!!l WI requhw to
dallnnlne tha produoi'IIUitabillty f~~r tha ialendod appiii!Aiiollo
(31 All pi'Ojll!rties IIIIUunllial 74"f (ll"C:) u•d•J otllorwitc indicoled.
(4) Te~ bt ,_,only II I ;uidt fot etiSinteftcla.
151 k·!Wwl wtn Y"ob)' Willi apand use aondiliooL
1&1 ~w eydiqliiiWI en\lironmalll may cause ~11011 of Ullpt'Qt~~~:r.d r ...... 'a domi cell JttUeture, resultina m the d<blrion~tim of ph)l•l=-1 prvpartiev.
(1J Numerical MPiame Spread" llld M$11111t• 0.-.loped" liltillll' m nat intended 10 Nftect hJJ:IIthl pl"!!<lnted by thit or any olhet II\Jiteri.t umlar DO!Iull fire conditi0111. Thi• m;ucrial
Is L'lllllbuldib~ •nd wiU lnlm whca exposed 10 luge li~W ~~~~""
fiOTl!: 1M lnt'onMtian F-led heNift il 0)!1'....., io pMl with as ~Ia, but witho\U WOITIIIII)"1 Cll~ loll' lmp!lal, rq,'BI\Iin& ~~Jlii:Y or c:omcllltliS. C~rkuuo uCIW! and
.abUity of the pnxluct for partlnabr 111a .,. beyond 1hoc011trol ~rEiliou Cumpmy Dflndlanllpolil 1~. ch;ntorc aU rl:dcs oflhc-= ur 1111• prod~Kt liR auumcd II¥ die user.
16912 balsa chlca road, suite 101
huntington beach, ca 92649
714 840-5582
o''·
@-rvP
CD CD
@ ~ ....
. ~, .lluo1 l +:P
1 1 1
( 3,q~)(.o1)(z,)::. • ~
(l 13~1 )f,O't6){t)::. I I '57!
{,t;t,l )(,d'l6)U,)::. t ~ ~
() 0411
;z == z,~\,3te# ''""s-
..:I.~ ::. I I ~. 'Z.k I ,J 4-'
l~'l'tei
3,'l.4c ~
,D4-t3
l,qcy.~
~ )C :::-l, q uj t. 'l ct G"".::: , ~ ~4--"J:;
(l?C; ~ 11 z.o4,...J
0
\.~41
L.4~1
0
JOB NO.I f? ' p !;
BY 1/J t,.-·
DATE Cl/t5
SH.~/,pOF
-
,5t:{ I
,5tfl --
16912 bolso chico road, suite 101
huntington beach, co 92649
714 840-5582
et-ESMw-r A-tE:A-(irJ ~)
I ,55&f
t I ( S"(tJ
3 ""~ ~-,4~
,, "3'2~
r 1 -c.-t. 6t-6"1J tr
y (,,j)
z,ott6
.. 14-JJ
~. "l(Gf
~, oq!i
? !.j ;::;. I , ~ z...'o/1,o<t 5"" "" • €>"1 " .J '
rt.j c::. L l1 '3 t,J
A-Y dJ~,J) A-J..?,
(,t~1· ,~5!5
L4-1tf .~41
L41t1 • ~4'1
0 -
I,S"41
JOB NO. ~ ~ I tJ I/
BY Wt:-
DATE (IJ/15
SHt1 OF
:I:o
-, o' r
,D \ \
,t,(t;Z,
,2PJ4
consulting&. des1gn • structure! e"'glreers
5762 bolsa avenue, suite 215
huntington beach, co 92649
714 891-5582
C!Pw0 TO 2:~
Wt+~ ( GP~~fl{LP) ~-~o!f< -t.. ~ '=-rt"' ~
Wt rn '?f> 1 ~ t? L4 t "'T1 7"; ~~"( ·
.{1~ =. 17..-f/ {,1;/15)(111) ~ 4511 ~~~l·,e>1'-"
I~, /).?€; 7f:/11J t+t L.-1/ Tk,
. f2o L..-'JS e ~fJ'b .... -
rt1tL t)u_r-:?vlftHZ.~ rtf/. C~lLt~ ~~
?
v A"f f3 1 t t ~ 1.: &~1} I !P P~r) It 1-) (~.:-l S7t? ~
T \ t0 I -z., ti A ... w r (2 ~ ~ { L4: 14-)/lS/)~ t,W~
-f. Jr-· ...... =--~t:P ~;. t ~ -ro; '-~ ?G ~ .s.-'
''I t)}E;, (a-) WA '-1 7ft-A>' V?I;Jg
17-t1 A-w !12.(~>5' M ~ I¥~ f -z. J
C. l J U>H1 p 5~1J'T:.. [~ t.l
· L 61F '9f1!.t);·:. z/ -:?4-tl ')C l {p 44, U?Lt?
~tJ t,.(,f:t' c::~ A,tJ iU. ~ t-
JOB NO, (7101,1
BY '\I. I '~"-( /.,·
DATE Cljf 7
SH~bF
consulting & des1gn • str:..:cturol eng1reer.s
5762 bolsa avenue, suite 215
huntington beach, co 92649
714 891-5582
7vPf(/)fL-r ~f' fY\Uri 1l-; f§qtJ1f~
'I lU:!Ifll't :MM .. ftltiWI:oM'(floe'~~ ..........
6~
~.:.-~()~ ~ w Lr6d-l 11\f. ~~;. ret ~ WI j ~""'s;t/~ 'f{~~\ ~)~-~\ tJl { ~t !?) c;,, •
W ~v~ r?l+ t...~ ~I){!)., {w){4 Jt;IJ.)-::=. o
/,-r:;~ )t'l~~ 0~-
JOB Nol91£>f"
BY w~
DATE 4?/15
SH.t-tf OF
consulting & design • stn.;ctura} er.g1nee.'s
5762 bolsa avenue. suite 215
huntington beach. co 92649
7 l 4 891 -558 2
C ~+F~ v,... J !?~ ;
L..'(;.~~) ' I w (Mit?)~ (ct~>~?r)ltt)~·a bt-1 !!1)f ~ )~-4~et~.;
f; m~ -;...4'; f:J + ( -z.-~ :.-l tJ <t tJ ~-
~t>HtJ ~ ~ 7,. +-f'!,-~ •l;pp ~
M ~6~t'-v.-
"!:t . .;;.. t i t (p r J 17
'-J!~t I~)~ 7ZPS~ . .
1'1\{?f:.;. t!;) -~ ( 'fit> t5 ) { Z-t 1 J .::: \ ~ I ~ I ~tt . . .
{ $1 G)~ l4. 1 ~ ~,lj Pr'H ti)(l..~
I 1?1 Pl-a.rtt ~( ltl '74}/ 1d3~) ~+15b',.r4/.·
~ f ~ 1-J'o ,Jr~-T' Jfy~r
vI ~r~tJE;f2. :::::-t.t,) ~---zf3::~-PLA:tJ$
JOBNo.p; [t)Lf
BY Vi(, .
DATE t.l/1 s
SH' tJ OF
consulting & des1gn • str:...-cfliral e."gh"ee·s
5762 balsa avenue. suite 215
huntington beach, co 92649
714 891-5582
A0 l1 A? -t-1 aJ l-!.t;u t,;
wr~ ?qoJ:f:-
y(~,;,)~ I~?~
'1 I w , tJ !?. ) " {"J r;J i'r,4 t l t 1,1 ;f).,. r-?74-'~
rt\f W lf.Jf7)~ {P P ~ 1
I lPrlt..JZrl\• (Z$f)/tt ?7)~ $11 1~Jt:
'ivP ~ (t-J; Ppf') /z~t~VL4';t:i t)e-~()1-ti
,' ,17 ~ L CJ~"'" '11--1 /t.&1 ./-~Dz/j-
.. ; -e1~ ~ t~eert $ Jt
,-I u> f<tJ~.:: e.., 1;: '1/ "? f r? (!:;. ~· Z}7 1--
JOB NO.I ~ t~ II
BY ""f.-
DATE (p/ t5"
SH~ 1 ·o~
'. ,C}f?t [_ 7 ~; ~~ ~~~ "!.:(!) ' ... :./110
~: J~~n~~JrltA1lc?
-rtJ rf2. A
LV \ m t5 1 ')(:_ 4-1 f'<..Arr-r:HZM :
.'
u) --7Wj ~ z.~ t--t, t P~r
uJ oF--(l c,lr:rroll..M. -... -r {J .>-r
/ ~~~~).:: tq (/~r L. l.Jf~F
: I cJ; ~ ~I ,c Cp I f1-A1rf-p£M'b ~/
~'ti'~t, ic-tfp VN?f#., e f"'(J}Jt~ SE:E-
p~.> fpf-.:.J2.~
consulti11g & des1gn • strvctural enQJr"eers
5762 balsa avenue, suite 215
huntington beach. co 92649
714 891-5582
' ( t
JOB No{f.? lD4c>
BY WC-
DATE (C;/1 f;
s~z_. OF
5762 bo:so ovel'\ue. s:.!'•e 2' 5
hunt•ng1on beech. co 026<1~
714 891-5582
®
jJ & J'4.1lf--~ V-rt1 Q,_ ~~~f"ltS1 ,j
~C(vtf w~ ~ !-\(){f)~(~ )l_;,pp)-;. 4$00~
(~l u) (~~t? )d, t1)(/l'l 'r~)-r (?r?f'){tp){~))=-w~% :=-~.t1)[~)/tt:-:1 -=: tjf
::: t,t1)( L \q){lvt5l r-(~ l{~}) ~ cto
JOB No.\ ~It>~
BY W~
DATE lP/1"'5' ,
S~~ OF
5762 bOISO OV9'1U9, SU'IG 211\
nuntington oeach, :::: 9264;
714 891-5582
w{7f:-\~) \-~---~"lz.,~ WJtt~ t: :t;~.1· ~
WI~->, e ~~?tPJJ)~ t:JO ~ w*-t$1'~ . '!,, ~ 1/P, t' ~.
t ~, "': ::;.. ,'?;f) tR I·~~ ~I 1 q ~·f? ·~ M?C-df4-'--~
I)~"~ ~ t t; ~~
~ -r -c:-.c., ~ tci ' e
JOB No\5lD&
BY we:,
DATE l.P/t5
S~OF
'/~+-u-C~\0 ~ tJwf CA-P)::-Cf.7G){~t;ee)-I'BO~
tJo (2, f:;{( f/~ l 01 1
~ r-i1 C::7 M 7PL-itJ:;:..Z _Jj_ &-tO T"e=~~ t:e.
5762 bolso ovenue. suite 215
huntington beoch, co 92649
714 891-5582
~ ,-o ~f ~ t,..t. ' .. lt..'.__ tDl
L oF-f?~.h'-:;. ~4/
u\ 11+ ( ·z.-) ;,v -z, t? '"!? 1-~ .$> CV
JOB NO., s l tJ (,1)
BY w(,;
DATE ~'IS s~dF
1/-~ /"' )f:; lA--'It l Z/L 'tp::; J Z.Z, -F ~::. q I "L tL.b I U-1/~ u!tT14 ~lrJIAt...t. ~1:-~ 3;4~F'&I.. =-I?M~D
?~:::. 4-?4: 1, 'fL -0 ~
··t (),£;, ~~)$ltZ.~t>?--"32
;;;-nJt92 A:r B~$
5762 bol$0 avenue. suite 215
huntington beach. co 92649
714 891-5582
'I A-u... ( 11 1 + ?c.t1.6N) e-f eA)l' vr}'(t{p 11) "'
.= t~l )(./tl.l~ 't-tt).
tJ D. f) r.;, tt 14 7U6tJ -ro f-riMt-t ~ 1/fufl)t-Jo
G-(;,1~' ./
1 ·~ tJ>~ 1) ~P? ~~ J lz-~U&at7
JOB N~·f.? tO~
BY WL
DATE C!(J5' S?/P OF
A ~fA ~4> 1? To r:=ut111JA~ u ft.,J PJ~ t~ s-7/r~ .. ,:;sr:
. ' . ,. ===-~~~~r 1-. L. ~ r? .;. 6lf tJ :;; l ~. €> -ArrA·C·8 T72 fj) 12 t, I ,Jz
Wl'rH u' L./)~a 7P~Ul. Btt\ ~
G);;; tJG-Pvrt.L-tJ c:-ro~}/tt·.:: Z?~ if;.
M ~ , ~, -z.-'1-¥+ {tfJ)/~){fJ) tft,~~· t,5" ~ -r, 1''*
Sr, (1. ~ tr)::: (R, ~)(, "~){ \tl 61/!,?J(J,v)
-;...-.'$.lr,J?
c ~ e.'JiJ?f'-~ 4 ~tJB ... (V/f:~ltJb o ~
--
5762 boise avenue. suite 215
huntington beach. co 92649
714 891-5582
w(fJ.t;r 7).;;. (r7.1 ){ {1'1)(4i)~ l'>f£-f)lt1)(3)) ::=. '[,~~
-:co(,t1l{+~t>2/4'1 ~ t~~ z..B'I J
::: (, t1)/LI'1) (c,?,'5) + { 3PJf'~/u)[?)) ~ \4-5}1
'J(~e\'f):: (w\)(41) ~ t~,t3~~ l'lt~-~1-'t.-
:::-( 14?) (l ~~"'::;-vroo ~ :=. .. ? ,~-
.,-:;; ~ -r;,. 1101 #-
~q,~~
t ~. ft.,k1C:-~pL. ~'-e. ~ '1/-
~
L,rJe.s ~.~ ~;
'{ --(/'r IJ() +-1 ~otP +-r, t-7 l t ~P$ ?)fuft 4-1)
~ f? ~ z.,i} It:. .
k)s@t::. (4).-'~~ or-~Mc!E:-s/
i;.11J~ 5rNlc ,.zl 7H1-_s ~~~ >~
'-)I ('!; f-A-(/f~, ::.--I 0 tf I JJ,:
k1\ I'L J { ell~ ,,_,__ ,, .. L
17t ,,j '?th;/"'·P'V/ZL.t ::. 1:/ t--'Z-? :::'l.-'7
Svt-: l-~ 7uJ? Me -t..; 6 ro {r:;)
2Vr2--rveutJ I
coN<Jiing a daSlgn • slryeturO! eng.nen
5762 bolsa avenue. suite 215
huntington beach. co 92649
714 891-5582
JOB NO.," f ti(l
BY Wt.--
DATE 1/tS'
s~g OF
Project Name: Advanced Biologics NRCC-PRF-01-E Page 1 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 revl.cibd
A. PROJECT GENERAL INFORMATION
1. Project Location (city) Carlsbad 7. #of dwelling units 0
2. CA Zip Code 92008 8. Compliance Software (version) CBECC-Com 2013-3b (717)
3. Climate Zone 7 9. Building Orientation (deg) (N) 0 deg
4. Total Conditioned Floor Area 2,145 ft2 10. Permitted Scope of Work ExistingAiteration
5. Total Unconditioned Floor Area 0 ft2 11. Building Type(s) Nonresidential
6. #of Stories (Habitable Above Grade) 1
--------
B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS 1§ 140.1
BUILDING COMPLIES
1. Energy Component 2. Standard Design (TDV) 3. Proposed Design (TDV) 4. Compliance Margin (TDV) 5. Percent Better than Standard
Space Heating 0.5 --0.5 --
Space Cooling 110.3 137.3 -27.0 -24.5%
Indoor Fans 167.6 136.3 31.3 18.7% ~
Heat Rejection --------
Pumps & Misc. --------~
Domestic Hot Water --------
Indoor Lighting 103.8 103.8 --0.0%
COMPLIANCE TOTAL 382.2 377.4 4.8 1.3%
Receptacle 90.3 90.3 0.0%
Process 344.3 344.3 0.0%
Process Ltg ------
TOTAL 816.8 812.0 0.6%
L__ -----
:""'--...
.......
~
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance RoportVoe>iooNRCCPRF~7rs .. ~6
~ ~ ~
Project Name: Advanced Biologics NRCC-PRF-01-E Page 2 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 revl.cibd
C. PRIORITY PLAN CHECK/INSPECTION ITEMS (in order of highest to lowest TDV energy savings)
1st Indoor Fans: Check envelope and mechanical Compliance Margin By Energy Component (from Table 8 column 4}
2nd Space Heating: Check envelope and mechanical
3rd Heat Rejection: Check envelope and mechanical
4th Pumps & Misc.: Check mechanical
5th Domestic Hot Water: Check mechanical
6th Indoor Lighting: Check lighting
7th I Space Cooling: Check envelope and mechanical
D. EXCEPTIONAL CONDITIONS
E. HERS VERIFICATION
This Section Does Not Apply
F. ADDITIONAL REMARKS
Indoor Fans
Space Heating
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Indoor Lighting
Space Cooling
This is a 100% Process Clean Room. Cooling load is process driven not comfort driven. Temperature and room press-
urization are precisely controlled. Trim heaters are typically used to control room temperature precisely. Economizer
cycles not applicable as room pressurization goes out of spec.
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: N RCC-PRF-01-E-06012015-717 ...
Project Name: Advanced Biologics NRCC-PRF-01-E Page 3 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 201S
~pliance Scope: ExistingAiteration Input File Name: Project 06091S rev1.cibd
-------
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
Identify which building components use the performance ar prescriptive path for compliance. "NA"= not in project
For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans.
Building Component Compliance Path Compliance Forms (required for submittal) Location of Mandatory Notes on
Plans
D Performance NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E)
Envelope D Prescriptive NRCC-ENV-01 I 02 I 03 I 04 I OS I 06-E
~ NA
~ Performance NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E) I
Mechanical D Prescriptive NRCC-MCH-01 I 02 I 03 I 04 I OS I 06 I 07-E
D NA
~ Performance NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E)
Domestic Hot Water D Prescriptive NRCC-PLB-01-E
D NA
D Performance NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E)
Lighting (Indoor Conditioned) D Prescriptive NRCC-LTI-01 I 02 I 03 I 04 I OS-E
~ NA
D Performace 52 (section of the NRCC-PRF-01-E)
Covered Process: D Prescriptive NRCC-PRC-01/ 03-E Commercial Kitchens
~ NA
D Performance 53 (section of the NRCC-PRF-01-E)
Covered Process: D Prescriptive NRCC-PRC-01/ 04-E Computer Rooms
~ NA
D Perform ace 54 (section of the NRCC-PRF-01-E)
Covered Process: D Prescriptive NRCC-PRC-01/ 09-E Laboratory Exhaust
~ NA _I
-
\.>0 -.....:_ .,......
~ CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06012015-717
~ ~
~
Project Name: Advanced Biologics
Project Address: 2800 Roosevelt Street Carlsbad 92008
Compliance Scope: ExistingAiteration
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
The following building components are only eligible for prescriptive compliance. Indicate which are
relevant to the project.
Yes NA Prescriptive Requirement Compliance Forms
Lighting (Indoor D 181 NRCC-LTI-01 I 02 I 03 I 04 I 05-E Unconditioned) §140.6
D 181 Lighting (Outdoor) §140.7 NRCC-LT0-01 I 02 I 03-E
D 181 Lighting (Sign) §140.8 NRCC-LTS-01-E
D 181 Solar Thermal Water NRCC-STH-01-E Heating: §140.5
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance
NRCC-PRF-01-E Page 4 of 16
Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Input File Name: Project 060915 rev1.cibd
The fallowing building components may have mandatory requirements per Part 6. Indicate
which are relevant to the project.
Yes NA Mandatory Requirement Compliance Forms
Commissioning: §120.8
181 D Simple Systems NRCC-CXR-01 I 02 I 03 I 05-E
D 181 Complex Systems NRCC-CXR-01 I 02 I 04 I 05-E
D 181 Electrical: §130.5 NRCC-ELC-01-E
D 181 Solar Ready: §110.10 NRCC-SRA-01 / 02-E
Covered Process: §120.6 NRCC-PRC-01-E
D 181 Parking Garage NRCC-PRC-02-E
D 181 Commercial Refrigeration NRCC-PRC-05-E
D 181 Warehouse Refrigeration NRCC-PRC-06/07 /08-E
D 181 Compressed Air NRCC-PRC-10-E
D 181 Process Boilers NRCC-PRC-11-E
Report Version: NRCC-PRF-01-E-06012015-717
Project Name: Advanced Biologics NRCC-PRF-01-E Page 5 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 rev1.cibd
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)-
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance Confirmed (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Building Component Compliance Forms (required for submittal) Pass Fail
181 NRCI-ENV-01-E-For all buildings D D
Envelope D NRCA-ENV-02-F-NFRC label verification for fenestration D D
181 NRCI-MCH-01-E-For all buildings with Mechanical Systems D D
181 NRCA-MCH-02-A-Outdoor Air D D
181 NRCA-MCH-03-A-Constant Volume Single Zone HVAC D D
D NRCA-MCH-04-H-Air Distribution Duct Leakage D D
D NRCA-MCH-05-A-Air Economizer Controls D D
D NRCA-MCH-06-A-Demand Control Ventilation D D
D NRCA-MCH-07-A-Supply Fan Variable Flow Controls D D
D NRCA-MCH-08-A-Valve Leakage Test D D
D NRCA-MCH-09-A-Supply Water Temp Reset Controls D D
Mechanical D NRCA-MCH-10-A-Hydronic System Variable Flow Controls D D
D NRCA-MCH-11-A-Auto Demand Shed Controls D D
D NRCA-MCH-12-A-Packaged Direct Expansion Units D D
181 NRCA-MCH-13-A-Air Handling Units and Zone Terminal Units D D
D NRCA-MCH-14-A-Distributed Energy Storage D D
D NRCA-MCH-15-A-Thermal Energy Storage D D
0 NRCA-MCH-16-A-Supply Air Temp Reset Controls D D
D NRCA-MCH-17-A-Condensate Water Temp Reset Controls D D
D NRCA-MCH-18-A-Energy Management Controls Systems D D
D NRCV-MCH-04-H-Duct Leakage Test D D
~ -~ CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: N RCC-PRF-01-E-06012015-717
~;
~
~
Project Name: Advanced Biologics NRCC-PRF-01-E Page 6 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 revl.cibd
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)-
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Building Component Compliance Forms (required for submittal} Pass
D NRCI-PLB-01-E-For all buildings with Plumbing Systems D
D NRCI-PLB-02-E-required on central systems in high-rise residential, hotel/motel application. D
D NRCI-PLB-03-E-Single dwelling unit systems in high-rise residential, hotel/motel application. D
D NRCI-PLB-21-E-HERS verified central systems in high-rise residential, hotel/motel application. D Plumbing D NRCI-PLB-22-E-HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. D
D NRCV-PLB-21-H-HERS verified central systems in high-rise residential, hotel/motel application. D
D NRCV-PLB-22-H-HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. D
D NRCI-STH-01-E-Any solar water heating D
D NRCI-LTI-01-E-For all buildings D
D NRCI-LTI-02-E-Lighting control system, or for an Energy Management Control System (EMCS) D
D NRCI-LTI-03-E-Line-voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to D energize only line-voltage track lighting
D NRCI-LTI-04-E-Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater D
Indoor Lighting D NRCI-LTI-05-E-Lighting Control Credit Power Adjustment Factor (PAF) D
D NRCI-LTI-06-E-Additional wattage installed in a video conferencing studio D
D NRCA-LTI-02-A-Occupancy sensors and automatic time switch controls. D
D NRCA-LTI-03-A-Automatic daylighting controls D
D NRCA-LTI-04-A-Demand responsive lighting controls D
D NRCI-LT0-01-E-Outdoor Lighting D
Outdoor Lighting 0 NRCI-LT0-01-E-EMCS Lighting Control System D
D NRCA-LT0-02-A-Outdoor Lighting Control D
Sign Lighting D NRCI-LTS-01-E-Sign Lighting D
Electrical D NRCI-ELC-01-E-Electrical Power Distribution D
Photovoltaic D NRCI-SPV-01-E Photovoltaic Systems D
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06012015-717
Confirmed
Fail
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
Project Name: Advanced Biologics NRCC-PRF-01-E Page 7 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 rev1.cibd
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)-
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance Confirmed (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Building Component Compliance Forms (required for submittal) Pass Fail
D NRCI-PRC-01-E Refrigerated Warehouse D D
D NRCA-PRC-01-F-Compressed Air Systems D D
D NRCA-PRC-02-F-Kitchen Exhaust D D
D NRCA-PRC-03-F-Garage Exhaust D D
Covered Process D NRCA-PRC-04-F-Refrigerated Warehouse-Evaporator Fan Motor Controls D D
D NRCA-PRC-05-F-Refrigerated Warehouse-Evaporative Condenser Controls D D
D NRCA-PRC-06-F-Refrigerated Warehouse-Air Cooled Condenser Controls D D
D NRCA-PRC-07F-Refrigerated Warehouse-Variable Speed Compressor D D
D NRCA-PRC-08-F-Electrical Resistance Underslab Heating System D D
I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information)
1. Total Conditioned Floor Area 2,145 ft2 5. Number of Floors Above Grade 1 Confirmed
2. Total Unconditioned Floor Area 0 ft2 6. Number of Floors Below Grade 0
3. Addition Conditioned Floor Area 0 ft2
"C ..,
Ql Ql 4. Addition Unconditioned Floor Area 0 ft2 "' -"'
7. Opaque Surfaces & Orientation 8. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio
North Wall 2 ft2 0 ft2 00.0% D D
East Wall 0 ft2 0 ft2 00.0% D D
South Wall 0 ft2 0 ft2 00.0% D D
West Wall 0 ft2 0 ft2 00.0% D D
Total 2 ft2 0 ft2 00.0% D D
Roof 0 ft2 0 ft2 00.0% D D '----·---·-· ·--
~
~
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06012015-717
~ ........ ~
~
Project Name: Advanced Biologics NRCC-PRF-01-E Page 8 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 rev1.cibd
J. FENESTRATION SUMMARY 1§ 110.6
This Section Does Not Apply
1 Newly installed fenestration shalf have a certified NFRC Label Certificate or use the CEC default tables found in Table 110.6-A and Table 110.6-B. Site-built fenestration less than 1,000 ft2, or more than or equal to 1,000 ~see Reference Nonresidential
Appendix NA6.
Taking compliance credit for fenestration shading devices? (if "Yes", see NRCC-PRF-ENV-DETAILS for more information) No
K. OPAQUE SURFACE ASSEMBLY SUMMARY § 120.1 I § 140.3 Confirme
d
1. 2. 3. 4. 5. 6. 7. 8.
" "T1
Framing Cavity Continuous U-Factor I F-Factor I Ill ~ Surface Name Surface Type Area (ft2) Condition Status "' "' Type R-Value R-Value C-Factor
ConstructAssembly 1 lnteriorFioor NA 0 NA U-Factor: 0.508 D D
ConstructAssembly 2 Ceiling NA 0 13 U-Factor: 0.069 D D
ConstructAssembly 3 ExteriorWall NA 0 NA U-Factor: 0.027 D D _L___ --·------
l. ROOFING PRODUCT SUMMARY I § 140.3
This Section Does Not Apply
M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information) § 110.1 I§ 110.2
Dry System Equipment 1 (Fan & Economizer info included below in Table N) Confirmed
1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
System Type Efficiency Acceptance " "T1
Total Heating Supp Heat Supp Heat Total Cooling Ill ~ (Simple 3 or "' Equip Name Equip Type Qty Testing Required? "'
Complex 4)
Output (kBtulhl Source (YIN) Output (kBtuh) Output (kBtulhl (YIN) 5
Cooling Heating
ZoneSystem 1 PTAC Simple 1 0 No 0 120 EER-12.1 NA Yes D D
ZoneSystem 2 PTAC Simple 1 0 No 0 48 EER-12.0 NA Yes D D
-·---
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: N RCC-PRF-01-E-06012015-717
Project Name: Advanced Biologics NRCC-PRF-01-E Page 9 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 201S
Compliance S~~pe: --~xistingAiteration ___ Input File Name: Project 060915 rev1.cibd
Wet System Equipment 2 Pumps
11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22.
Rated Capacity Tank Ext. R VSD Equip Name Equip Type Qty Vol (gal) Efficiency Standby Loss GPM Qty HP (kBtu/h) Value (Y/N)
FluidSystem 1 Heating Hot Water, NA NA FluidSegment 1 Primary Only
Boiler 1 HotWater NA NA
---1 Dry System Equipment includes furnaces, air handling units, heat pumps, etc.
2 Wet System Equipment includes boilers, chillers, cooling towers, water heaters, etc.
3 Simple Systems must complete NRCC-CXR-03-E commissioning design review form
4 Complex Systems must complete NRCC-CXR-04-E commissioning design review form
NA
100
-
5 A summary of which acceptance tests are applicable is provided in NRCC-PRF-MCH-OETAILS
NA NA NA
AFUE: 0.82 NA NA ----~ -----
Discrepancy between modeled and designed equipment sizing? (if "Yes", see Table F. "Additional Remarks" for an explanation)
N. ECONOMIZER & FAN SYSTEMS SUMMARY1
1. 2. 3. 4.
Outside Supply Fan Return Fan Air
1 5.0 0.125 No
NA NA NA No
No
§ 140.4
5.
Confirmed
'tl ., "' ~ "' "'
0 0
0 0
Confirmed
'tl .,
Economizer Type "' ~ "' Equip Name "' TSP TSP (if present)
CFM CFM HP BHP (inch Control CFM HP BHP (inch Control
WC) WC)
ZoneSystem 1 429 6000 3.000 1.576 1.40 ConstantVolume NA NA NA NA NA NA 0 0
ZoneSystem 2 86 1500 0.500 0.394 0.76 ConstantVolume NA NA NA NA NA NA 0 0
-1 Mechanical ventilation calculations and exhaust fans are included in the NRCC-PRF-MCH-OETA/LS section
0. EQUIPMENT CONTROLS 1 § 120.2 Confirmed
1. 2. 3. 'tl ., "' ~ Equip Name Controls "' Equip Type "'
FluidSystem 1 Heating Hot Water, Primary Only Fixed Temperature Control, No DDC 0 0
FluidSystem 2 Service Hot Water, Primary Only Fixed Temperature Control, No DDC 0 0
---------------------L__ -
P. SYSTEM DISTRIBUTION SUMMARY r § 120.4/ § 140.4(i)
~ 1 This Section Does Not Apply -.. '•
~-
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: N RCC-PRF-01-E-06012015-717
Project Name: Advanced Biologics NRCC-PRF-01-E Page 10 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
~p!ia~ce Scope: ExistingAiteration Input File Name: Project 060915 revl.cibd
--------
Does the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) Yes
Does the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No
Multifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information) No
Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info) § 140.6
Confirmed
1. 2. 3. 4. 5.
"C .,
Conditioned Floor Area 2 Installed lighting Power lighting Control Credits Ill ~ Occupancy Type 1 Additional (Custom) Allowance "' "' (ft2) (Watts) (Watts)
Area Category Footnotes Tailored Method (Watts) 0 0 (Watts)
Building Totals: NaN 0
1 See Table 140.6-C
2 See NRCC-LTI-01-E for unconditioned spaces
R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E)l 1 § 13o.o
This Section Does Not Apply
11f lighting power densities were used in the compliance model Building Departments wilf need to check prescriptive forms for Luminaire Schedule details.
51. COVERED PROCESS SUMMARY-ENCLOSED PARKING GARAGES j§ 140.9
This Section Does Not Apply
52. COVERED PROCESS SUMMARY-COMMERCIAL KITCHENS 1§ 140.9
This Section Does Not Apply
53. COVERED PROCESS SUMMARY-COMPUTER ROOMS l§ 140.9
This Section Does Not Apply
54. COVERED PROCESS SUMMARY-LABORATORY EXHAUSTS 1§ 140.9
This Section Does Not Apply
-~ --........
~-
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06012015-717
.......... -. ----..
Project Name: Advanced Biologics NRCC-PRF-01-E Page 11 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 revl.cibd
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1§ 1o-103 I
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: SB
Company: Clean Rooms West Inc
Signature:
Address: 1392 Industrial Drive Signature Date:
City/State/Zip: Tustin I CA I 92780 CEA Identification {If applicable): nowayj
Phone:7142587700
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1 I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am
licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
2 I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its
preparation; and that I am a licensed contractor performing this work.
3 I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to
Business and Professions Code Sections 5537, 5538 and 6737.1.
Responsible Envelope Designer Name: SR
Signature:
Company: Usual Suspects
Address: 1031 E Grand Ave Date Signed:
City/State/Zip: Corona I CA I 92880 Declaration Statement Type:
Phone:714 677 4104 Title: I License #:Yes
Responsible Lighting Designer Name: Luis
Company: Quinteros Electric
Signature:
Address: PO Box 460360 Date Signed:
City/State/Zip: Transformer I CA I 98765 Declaration Statement Type:
Phone:951 232 7606 Title: I License #:Yes
Responsible Mechanical Designer Name: SB
Company: CRW
Signature:
Address: 1392 Industrial Drive Date Signed:
City/State/Zip: Tustin I CA I 92780 Declaration Statement Type:
Phone:714 258 7700 Title: I License #:yes
L__ ---·-----·--
-('• CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06012015-717
--~ ~ ~
Project Name: Advanced Biologics N RCC-PRF-01-E Page 12 of 16 I
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 revl.cibd I
NRCC-PRF-ENV-DETAILS -SECTION START-
A. OPAQUE SURFACE ASSEMBLY DETAILS Confirmed I
1. 2. 3. 4. "C 'T1 Ill ~ Surface Name Surface Type Description of Assembly Layers Ill
I Notes Ill
ConstructAssembly 1 I nteriorFioor Concrete-140 lb/ft3-6 in. D D
ConstructAssembly 2 Ceiling Glass fiber batt-3 1/2 in. R13 (CEC Default) D D I
ConstructAssembly 3 ExteriorWall Metal Insulated Panels-6 in. D D
B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E)
This Section Does Not Apply
NRCC-PRF-MCH-DETAILS -SECTION START-
A. MECHANICAL VENTILATION AND REHEAT {Adapted from 2013-NRCC-MCH-03-E) Confirmed
1. DESIGN AIR FLOWS 2. VENTILATION(§ 120.1)
:X: c c ::a -i m m m s: s: s: n c m ~ "' "' 0 m s: 0 c ::a I Cl Cl z )> )> c z s: "' z 0 m )> z X ,x Cl "' z z )>Z 'T1-c < c z < Cl "' In :ij-c r-s: ... 3: 53: n m =t z -n< m 'T1 "C Oc z z m -::a ... ~ r-c ::ec n 0 ~< ,m z c ::Es: ~s: 0 -i Om z s:z -i ~< ::a "C 'T1 n n3: r-s: ,S: ,z c n Ill CONDITIONED _Q z "' z --i nm )> < ~ I 0)> 'T1"C < S:-i s: )> Ill co ,)> ~:!! ~:x: ::a:x: -i m , "C ;a ,z ;a < Ill ZONE NAME S:::a ::E::a l>m ::a "' c -"C 111 m S:-i .... nm -i 'T1 z -< ~< !:IS: 3:~ g~ 0 m )> :=rm 0 ii1 ::a 'T1 -)> .... ~ Qs: .... s: ~::a 'T1 0 "C .... ;a 0 In )> -)> < ::a 0 ::e = ;a s:-O;:a -z oz m )> "C ::I m ::e "' _z Z< In Zln ~ a )> ::a m -::a 'T1 I < 0 "' .... -n "' 'T1 3: ~ ~ ;e: ~ m 0 -n 0 -i .... -= )> "C ::e 'T1
m 0 c ::a ::a ::a "' .... z 'T1 s: s: ::e s: -m !
I
ThermaiZone 1 ZoneSystem 1 NA NA NA NA NA N ZoneSystem 1 2,145 0.15 21 15 322 429 NA N D D
ThermaiZone 2 ZoneSystem 2 NA NA NA NA NA N ZoneSystem 2 431 0.15 4 15 65 86 NA N D D
TOTAL 2,576 25 387 515 NA D D
. --L__----L__ --
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: N RCC-PRF-01-E-06012015-717
-~ ~ ~-
Project Name: Advanced Biologics
Project Address: 2800 Roosevelt Street Carlsbad 92008
Compliance Scope: ExistingAiteration
B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY
1. 2. 3. 4. 5.
Rated Capacity
(kBtuh)
System ID System Type Qty Economizer
Heating Cooling
ZoneSystem 1 PTAC 1 NA 120.00 No
ZoneSystem 2 PTAC 1 NA 48.00 No
--------L__ -L__-L___ ~-----------
C. EXHAUST FAN SUMMARY
This Section Does Not Apply
D. DHW EQUIPMENT SUMMARY-(Adapted from NRCC-PLB-01}
This Section Does Not Apply
E. MULTI-FAMILY CENTRAL DHW SYSTEM DETAILS
This Section Does Not Apply
F. SOLAR HOT WATER HEATING SUMMARY {Adapted from NRCC-STH-01}
This Section Does Not Apply
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance
NRCC-PRF-01-E Page 13 of 16
Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Input File Name: Project 060915 rev1.cibd
§ 140.4
6. 7. 8. Confirmed
Airflow (cfm) Fan
"C , Zone Name Ql ~ "' Min. ECM "' Design Min. Ratio BHP Cycles Motor
ThermaiZone 1 6000 NA NA 1.6 D D D D
ThermaiZone 2 1500 NA NA 0.4 D D D D
--------------
Report Version: NRCC-PRF-01-E-06012015-717
Project Name: Advanced Biologics NRCC-PRF-01-E Page 14 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 rev1.cibd
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adapted from 2013-NRCC-MCH-01-E) § RA4
Declaration of Required Acceptance Certificates (NRCA)-Acceptance Certificates that may be submitted. (Retain copies and verify forms are completed and signed to post in field for Field
Inspector to verify).
s: s: s: s: s: s: s: s: s: s: s: s: s: s: s: s: s:
Test Description n n n n n n n n n n n n n n n n n Confirmed ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: ::r:: 6 6 6 6 6 6 6 6 ,!. ,!. ,!. ,!. ,!. ,!. ,!. ,!. ,!. N .... .1> U1 a'l ...... 00 "' 0 ,_. N .... .1> U1 a'l ...... 00 )> )> )> )> )> )> )> )> )> )> )> )> )> )> )> )> )>
Vl
Vl m Vl )> 0 c :;· n c I c ,., )> v;· -o n 0 Vl -o -< c -o ;:oO CJQ !:': ::J c ~ -o a_ 8 0 8 "" < Equipment 0 m-~ 0 -o 0 m -I Ill ::J c 3 < < n~ nO m )> "' D.. .-+ N 0 -o 0 ,., 0 ::J Vl Ill Ill m #of < Ill ~~ 0 Ill NO .-+ ::J Requiring a_ 0 v;· ;::;· 0 0 ~ ~ X~ Vl ~ n -g -n 0 ::J "" Ill n ,., m ::J -· ::J 3 0 0 )>~ -< ~ n"' s: Ill Ill Testing or units 0 Ill ~ < QJ QJ "' .-+ .-+ QJ .-+ Q) 0 ::J ...., ~ 0 Ill II> ~ 0 ~ ~ ~ <:J Q_~ X Ill ~ 3 ::J ~ "' -n ::J "' 0 -nVl Ill Vl c c -Ill "i ::2: Verification )> ::J 0 ~ Q) ~ c .-+ 3 -o
~ ~ a ::J CJQ ,., Vl ::J !:': 0 "' 0 Q) .-+ Ill 3 0 ::r ;::;: ~ OJ :::0 ~~ ~ 0 :E Ill "' !20 CJQ Ill ;;;--o D.. Ill "' ~
Fluid System 1 -- ---------------- -------- --------0 0 1
Fluid System 1 ------------------ -- --------------0 0 2
ZoneSystem 1 X ------------ --0 0 1 -- -------- --------
ZoneSystem 1 X ---------- ----------------0 0 2 ------
-----------
NRCC-PRF-LTI-DETAILS -SECTION START-
A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E) 1§ 140.6
This Section Does Not Apply
B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E) 1 § 130.1
This Section Does Not Apply
§130.l{a) =Manual area controls; §130.0{b} =Multi Level; §130.l{c) =Auto Shut-Off; §130.l{d) =Mandatory Daylight; §130.l(e) =Demand Responstve
C. TAILORED METHOD LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E) § 140.6
"'-... I General lighting power (see Table D)
~· -.. ~-CA Building Energy Efficiency Standards-2013 Nonresidential Compliance
0
Report Version: NRCC-PRF-01-E-06012015-717
Project Name: Advanced Biologics NRCC-PRF-01-E Page 15 of 16 I
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 rev1.cibd I
-----------
C. TAILORED METHOD LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E) § 140.6
General lighting power from special function areas (see Table E) NA
Additional "use it or lose it" (See Table G) 0
Total watts 0
D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E) T§ 140.6-D
This Section Does Not Apply
E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E) § 140.6(c) 3H
Illuminance Value Room Cavity Ratio Confirmed
Room Number Primary Function Area (LUX) (Table G) Allowed LPD Floor Area (ft2) Allowed Watts Pass Fail
NA NA NA NA NA NA NA D D
Note: Tailored Method for Special Function Areas is not currently implemented
F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E)
Rectangular Spaces
Confirmed
Room Number Task/Activity Description Room Length (ft) Room Width (ft) Room Cavity Height (ft) RCR
Pass Fail
NA NA NA NA NA NA D D
Non-Rectangular Spaces
This Section Does Not Apply
Note: All applicable spaces are listed under the Non-Rectangular Spaces table
G. ADDITIONAL "USE IT OR LOSE IT" (Adapted from NRCC-LTI-04-E)
1. 2. 3. 4. Confirmed
Combined Floor Display and Task Combined Ornamental and Special Allowed Watts -o .., Wall Display Very Valuable Merchandise Cll ~ Lighting Effects Lighting "' "'
0 0 0 0 0 D D
s. Wall Display
........ This Section Does Not Apply
~ -. ~ CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06012015-717
Project Name: Advanced Biologics NRCC-PRF-01-E Page 16 of 16
Project Address: 2800 Roosevelt Street Carlsbad 92008 Calculation Date/Time: 11:10, Tue, Jun 09, 2015
Compliance Scope: ExistingAiteration Input File Name: Project 060915 rev1.cibd
6. Floor Display and Task Lighting
This Section Does Not Apply
7. Combined Ornamental and Special Effects Lighting
This Section Does Not Apply
8. Very Valuable Merchandise
This Section Does Not Apply
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS {Adapted from NRCC-LTI-01-E and NRCC-LT0-01-E) § 130.4
Declaration of Required Acceptance Certificates {NRCA) -Acceptance Certificates that must be verified in the field. {Retain copies and verify forms are completed and signed to post in field for
Field Inspector to verify).
Indoor Outdoor Confirmed Test Description
NRCA-LTI-02-A NRCA-LTI-03-A NRCA-LTI-04-A NRCA-LT0-02-A
-c .,
Equipment Requiring Occ Sensors I Auto Time Qj ~ #of units Auto Daylight Demand Responsive Outdoor Controls "' "' Testing or Verification Switch
Occupant Sensors D D D D D D
Automatic Time Switch D D D D D D
Automatic Daylighting D D D D D D
Demand Responsive D D D D D D
Outdoor Controls D D D D D D
--
-.....
~. ,..,._
~ CA Building Energy Efficiency Standards-2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06012015-717
Di:,tf UJt ~-t/1-/-IVI l~f-CJ03 til OFFICE USE ONLY
RECORDID# __________________ ~
SAN DIEGO REGIONAL HHMBP# ______ --1
HAZARDOUS MATERIALS QUESTIONNAIRE
Zip Code q Joo g APN#
Mailing Address _..... SAm~ City State Zip Code Plan File#
The following questions represent the facility's activities, NOT the specific project description.
PART I; FIRE DEPARTMENT-HAZARDOUS MATERIALS DIVISION; OCCUPANCY CLASSIFICATION: (not required for proiects within the City of San
Diego); Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled.
applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: Facility's Square Footage (including proposed project):
1. Explosive or Blasting Agents 5. Organic Peroxides 9. 13. Corrosives
2. Compressed Gases 6. Oxidizers 10.
Water Reactives
Cryogenics 14. Other Health Hazards
3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials
Radioactives
15. None of These.
4. Flammable Solids 8. Unstable Reactives 12.
PART II: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH-HAZARDOUS MATERIALS DIVISION IHMDl: If the answer to any of the
questions is yes, applicant must contact the County of San Diego Hazardous Materials Division, 5500 Overland Avenue, Suite 170, San Diego, CA 92123.
Call (858) 505-6700 prior to the issuance of a building permit.
FEES ARE REQUIRED. Project Completion Date: Expected Date of Occupancy:
1.
2.
3.
4.
5.
6.
7.
8.
YES NO (for new construction or remodeling projects)
Is your business listed on the reverse side of this form? (check all that apply). m o
lll D D 0 Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
D D D
D D
~ Will your business store or handle carcinogens/reproductive toxins in any quantity?
181 Will your business use an existing or install an underground storage tank?
[8 Will your business store or handle Regulated Substances (CaiARP)?
f!5;l Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)? ~ Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal to
or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act).
D CaiARP Exempt
I
Date Initials
D CaiARP Required
I
Date Initials
D CaiARP Complete
I
Date Initials
PART Ill: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCDl: If the answer to Question #1 below is no or the answer to any of the
Questions #2-5 is yes, applicant must contact the APCD at 10124 Old Grove Road, San Diego, CA 92131-1649 or telephone (858) 586-2600 prior to the issuance
of a building or demolition permit. If the answer to questions #4 or #5 is yes, applicant must also submit an asbestos notification form to the APCD at least 10
working days prior to commencing demolition or renovation. (Some residential projects may be exempt from the notification requirements. Contact the APCD for
more information.)
1.
2.
3.
YES
D
D
D
t)IQ lll· Has a survey been performed to determine the presence of Asbestos Containing Materials?
$ Will the subject facility or construction activities include operations or equipment that emit or are capable of emitting an air contaminant? (See the
APCD factsheet at http://\iWIW.sdapcd.org/info/facts/pennits.pdf, and the list of typical equipment requiring an APCD permit on the~~r~e
of this from. Contact APCD if you have any questions). ~ D (ANSWER ONLY IF QUESTION 1 IS YES) Will the subject facility be located within 1,000 feet of the outer boundary of a school (K rough 1 ?
(Search the California School Directory at http://www.cde.ca.gov/re/sd/ for public and private schools or contact the appropriate school disj!ict).,
4. D fB. Will there be renovation that involves handling of any friable asbestos materials, or disturbing any material that contains non-friable as~'
5. D ffi Will there be demolition involvin the removal of a load su ortin structural member?
!~clare u~def penal~f perjury that to the best of my knowledge and b · e re~p9'JJ~e~e herein are true and correct. Ldg VI Q. /..) V"'! c ;J.., I ~ 1-> ,_,____--]J 15 I 20lS
Name of Owner or Authorized Agent Signature of Owner or Authorized Agent Date
FOR OFFICAL USE ONLY:
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION: ________________________________________________________ _
BY: DATE: I I
RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
APCO COUNTY-HMO APCO COUNTY-HMO APCO
xempts businesses frorn completing or updating a Hazardous Materials Business Plan. Other permitting requirements may still apply.
HM-tJI71 (05/14) County of San Diego-DEH-Hazardous Materials Division
INDUSTRIAL WASTEWATER DISCHARGE PERMIT
I ! . SCREENING SURVEY
Date 7 17 i!5
Business Name AJ..1~ _£:,,_,, o""'---'(C:,la.-r~_,_,\l...""-'S::::___--,---:---------
StreetAddress (1Q5 ~ ~. ~~iv(<;btlc{ OA-q 2CX8 ,
Email Address. _________________________ _
PLEASE CHECK HERE IF YOUR BUSINESS IS EXEMPT: (ON REVERSE SIDE CHECK TYPE OF BUSINESS) D
Check all below that are present at your facility:
Acid Cleaning Ink Manufacturing Nutritional Supplement I
Assembly Laboratory Vitamin Manufacturing
Automotive Repair Machining I Milling Painting I Finishing
Battery Manufacturing Manufacturing Paint Manufacturing
Biofuel Manufacturing Membrane Manufacturing Personal Care Products
Biotech Laboratory (i.e. water filter membranes) Manufacturing
Bulk Chemical Storage Metal Casting I Forming Pesticide Manufacturing I
Car Wash Metal Fabrication Packaging
Chemical Manufacturing Metal Finishing Pharmaceutical Manufacturing
Chemical Purification Electroplating (including precursors)
Dry Cleaning Electroless plating Porcelain Enameling
Electrical Component Anodizing Power Generation
Manufacturing Coating (i.e. phosphating) Print Shop
Fertilizer Manufacturing Chemical Etching I Milling Research and Development
Film I X-ray Processing Printed Circuit Board Rubber Manufacturing
Food Processing Manufacturing Semiconductor Manufacturing
Glass Manufacturing Metal Powders Forming Soap I Detergent Manufacturing
Industrial Laundry Waste Treatment I Storage
SIC Code(s) (if known): ---"l2"'--""8":___::__3__.ce:::....__ _______________ _
Brie description of busine~~ activities (Production I Manufacturing Operatio9s ): ......... __ ___,~
nec.c{;.S'3.n-r-,;,.1 or-'?1S.SuE Mbr,tc/ S/tJJtc t-U1~7;l,JSvt7;t}AJ
r •
Descriptio,n of operations generating wa~tew9ter (d[sc~arged to---rewer,. hauled or evaporated):
t.... ;61c) flr1·z..rPz.-t<-fi-S.7i:::_ .-Ut~/-'oSH-L ric~-"';~ 8 '/
Estimated volume of industrial wastewater to be discharged (gal/ day): _______ _
List hazardous wastes ~enerated (type I volume): tsr'C't!fr? rtJt. iJ IJ.rtts,l'£ @ r;; G lfz .. LcJ tl s· re:>-~ D '!7
Date operation began/or will begin at this location:----------------
Have you ap~ for a Wastewater Discharge Permit from the Encina Wastewater Authority?
Yes ~) lfyes,when: __________________________ __
Site Contact / brt o/; 1~ U '1 PIC th.J Title ~e:N cvt i"f-C I!/ I {i r1 .
Signature~ dJ:).__..____-Phone No. (J;_5--Lf / Cf-:?? q Cf 3
ENCINA WASTEWATER AUTHORITY, 6200 Avenida Encinas Carlsbad, CA 92011 (760) 438-3941
FAX: (760) 476-9852
Project Address:
PLUMBING,
ELECTRICAL,
MECHANICAL
WORKSHEET
B-18
Permit No.:
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Building@carlsbadca.gov
Information provided below refers to worR being done on the above mentioned permit only.
This form must be completed and returned to the Building Division before the permit can be issued.
B-18
Building Dept. Fax: (760) 602-8558
Number of new or relocated fixtures, traps, or floor drains ....................................................... _2.2_
New building sewer line? ......................................................................................... Yes-X_ No __
Number of new roof drains? ............................................................................................................... ..bl.M
Install/alter water line? ......................................................................................................................... 'i.:tS_
Number of new water heaters? ......................................................................................................... _J_
Number of new, relocated or replaced gas outlets? .................................................................... __
Number of new hose bibs? .................................................................................................................. __Q_
Residential Permits:
New/expanded service: Number of new amps: --------
Minor Remodel only: Yes__ No
Commercial/Industrial:
Tenant Improvement: Number of existing amps involved in this projed:
Number of new amps involved in this projed:
New Construdion: Amps per Panel:
000
400
Single Phase ............................................................... Number of new amperes _______ _
Three Phase ................................................................. Number of new amperes _______ _
Three Phase 480 ........................................................ Number of new amperes _______ _
Number of new furnaces, A/C, or heat pumps? ............................................................................ _Q_
New or relocated duct worl:?? .......................................................................... Yes No ~
Number of new fireplaces?................................................................................................................. "6
Number of new exhaust fans?............................................................................................................ \
Relocate/install vent?............................................................................................................................ 't {J
Number of new exhaust hoods? ........................................................................................................ _Q__
Number of new boilers or compressors? ........................................................... Number of HP Q
Page 1 of 1 Rev. 03/09
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
10-19-2015 Plan Check Revision Permit No:PCR15100
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Reference #:
PC#:
Project Title:
Applicant:
1905 ASTON AV CBAD
PCR
2121201300 Lot#: 0
$0.00
CB152245
Construction Type: 58
ADVANCED BIOLOGICS: REVISIONS
TO BATHROOM CONSTRUCTION
Owner:
MICHELE ARNOLD-KUSH H&M EAGLE L P
P 0 BOX 3802
Status:
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
RCHO SANTA FE CA 92067
619-297-6153
Plan Check Revision Fee
Fire Expedited Plan Review
Additional Fees
Total Fees: $161.25
Inspector:
$161.25
$0.00
$0.00
Total Payments To Date: $161.25 Balance Due:
FINAL APPROVAL
Date: Clearance:
ISSUED
10/07/2015
JMA
10/19/2015
10/19/2015
$0.00
N0T1CE Rease take NOTlCE that approval of your rx-oject indudes the "lrrposition" ci fees, dedications, reservations, or other exactions hereafter oolectively
referred to as "fees/exactions." You have 00 days from the date this pemit vvas issued to protest irrposition of these fees/exactions. If you protest them, you rrust
fallON the rx-otest rrocecJures set forth in G:Jvemrrent O:Jde Section 66020(a), and file the protest and any other required information wth the Oty flklnager for
processing in acrordance wth Carlsbad 11/unidpal O:Jde Section 3.32.030. Failure to tirrely fallON that fYocedure wll bar any subsequent legal action to attack,
review, set aside, void, or annul their irrposition.
You are hereby FURTl-IER NOTlFIED that your right to protest the spedfied fees/exactions DOES NOT IlPPI... Y to water and Sf'Nier oonnection fees and capacity
changes, nor planning, zoning, grading or other sinilar application processing or servioe fees in oonnection wth this rx-oject. 1\XJR DOES IT M'PL Y to any
fees/exactions of 'Ahich vou have oreviousv been aiven a NOTlCE sinilar to this or as to 'Ahich the statute of linitations has oreviouslv otherWse exoired.
f} (_City of
Carlsbad
PLAN CHECK REVISION
APPLICATION
B-15
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Plan Check Revision No. fC~l~-lOO Original Plan Check No. CB 15-2245
Project Address 1905 ASTON AVENUE CARLSBAD, CA 92008 Date 10/07/15
Contact MICHELE ARNOLD-KUSH Ph 619-297-6153 Fax 619-299-6072
Email MICHELE@SAFDIERABINES.COM
Contact Address 925 FORT STOCKON DRIVE City SAN DIEGO Zip CA
General Scope of Work TENANT IMPROVEMENT
Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person.
1 . Elements revised:
I v I Plans D Calculations D Soils D Energy 0 Other
2.
Describe revisions in detail
ORIGINAL PLANS CALLED FOR DEMOLITION OF EXISTING
RESTROOMS AND CONSTRUCTION OF NEW SHOWER ROOM,
(2) NEW MEN'S RESTROOMS AND (2) NEW WOMEN'S
RESTROOMS. PLAN REVISION CALLS FOR EXISTING
RESTROOM AND SHOWER ROOM FOOT PRINT TO REMAIN.
NEW PARTITIONS, NEW PLUMBING FIXTURES, NEW ADA
COMPLIANT ROLL IN SHOWER UNIT IN SHOWER ROOM, NEW
LIGHT FIXTURES. E-SHEETS AND P-SHEETS ARE REVISED TO
REFLECT PLAN CHANGES.
5.
6.
Does this revision, in any way, alter the exterior of the project?
Does this revision add ANY new floor area(s)?
7. Does this revision affect any fire related issues?
8. Is this a complete set? 0 Yes 0 No
DYes
[2fYes
3.
List page{s) where
each revision is
shown
T1.4, Tl.5, Tl.6,
T1.7, Tl.8, Tl.9,
Tl.12.1, E1.0,
E2.0, E3.0,
E4.0, E5.0,
PO.O, P1.0, P2.0
DYes
0No
0No
4.
List revised sheets
that replace
existing sheets
Tl.4, Tl.5, Tl.6,
Tl.7, T1.8, Tl.9,
Tl.12.1, E1.0,
E2.0, E3.0,
E4.0, E5.0,
PO.O, P1.0,
P2.0
[Z]No
~Signatu~ __ · ___ -_·~===--------------------------------------------
1635 Faraday Avenue, Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: building@carlsbadca.gov
www.carlsbadca.gov
EsGil Corporation
In (]?artnersfiip witfi C}overnment for (]JuiMing Safety
DATE: 10/15/15
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 15-2245 PCR15-100 SET: I
PROJECT ADDRESS: 1905 Aston Ave Suite 101
PROJECT NAME: Advanced Biologics-TI
0 A~ICANT
_j:¥":fURIS. ~
D PLAN REVI ER
0 FILE
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: ) Email:
Mail Telephone Fax In Person
D REMARKS:
By: Doug Moody Enclosures:
EsGil Corporation
0 GA 0 EJ 0 MB 0 PC 10/8/15
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
City of Carlsbad 15-2245 PCR15-100
10/15/15
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
100
PLAN CHECK NO.: 15-2245 PCR15-
PREPARED BY: Doug Moody DATE: 10/15/15
BUILDING ADDRESS: 1905 Aston Ave Suite 101
BUILDING OCCUPANCY: B
BUILDING AREA Valuation
PORTION (Sq. Ft.) Multiplier
revision
-~~~~--~---~----~-~--
Air Conditioning
Fire Sprinklers
TOTAL VALUE ---~--------~
Jurisdetion Code cb By Ordina nee
Bldg. Permt Fee by Ordnance .,...
Plan Gieck Fee by Ordinance
Type of Review: D Complete Review
0Repetitive Fee Repeats .....
* Based on hourly rate
Comments:
D Other
[IJ Hourly
EsGil Fee
Reg. VALUE
Mod.
----~~
-~--~----
D Structural Only
1-----1_.---lsl Hrs. @ •
$86.00.
($)
----
$161.251
$129.001
Sheet 1 of 1
macvalue.doc +
PLANNING DIVISION
BUILDING PLAN CHECK
I l y APPROVAL
CARLSBAD P-29
DATE: 10-7-15 PROJECT NAME: PROJECT ID:
Planning Division
1635 Faraday Avenue
(760} 602-4610
www.carlsbadca.1mv
PLAN CHECK NO: PCR 15-100 SET#: 1 ADDRESS: 1905 Aston Av APN:
~ This plan check review is complete and has been APPROVED by the Planning
Division.
By: Chris Sexton
A Final Inspection by the Planning Division is required 0 Yes [8] No
You may a/so have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to: michele@safdierabines.com
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760-602-4610
~ Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
D Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
Remarks:
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
q~ (( ~
'\"*' ~ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: 10/15/2015 PROJECT NAME: ADVANCED BIOLOGICS
PLAN CK NO: SET#: 1/1 ADDRESS: 1905 ASTON AV
BUILDING DEPT.
c&;.Qiff.~ & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
PROJECTID:PCR15100
~ This plan check review is complete and has been APPROVED by the FIRE Division.
By: GR
A Final Inspection by the FIRE Division is required ~Yes D No
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan check comments have been sent to: Michele@safdierbines.com
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
,,,,
.IIIII· .. ENQINI;@~II~" FIRE·,Pt1QEAIION ···PJ.A
~'%''<' -24&~0 . 76CH:i02.750 .. ··7~···
D Chris Sexton D ~ Greg Ryan
760-602-4624 760-602-4663
Chris.Sexton@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
D Gina Ruiz D Linda Ontiveros D Cindy Wong
760-602-4675 760-602-2773 760-602-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov C}'nthia.Wong@carlsbadca.gov
D D D Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Carlsbad Fire Department
Plan Review Requirements Category: PCR ,
Date of Report: 10-15-2015
Name: MICHELE ARNOLD-KUSH
Address: 925 FORT STOCKTON DR
SAN DIEGO, CA
Permit#: PCR15100
Job Name: ADVANCED BIOLOGICS: REVISIONS
Job Address: 1905 ASTON AV CBAD
Please review carefully all comments attached.
Conditions:
CITY OF CARLSBAD FIRE DEPARTMENT-APPROVED:
BUiLDU~G DEPT.
COPY
Reviewed by: q Jfal(
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON,
CONDITIONS IN CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW.
Entry: 10/15/2015 By: GR Action: AP