HomeMy WebLinkAbout2091 Rutherford Rd; ; CBC2018-0085; Permit(city of
Carlsbad
Commercial Permit
Print Date: 06/21/2018
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2091 Rutherford Rd
BLOG-Commercial
2121202500
$30,000.00
Work Class:
Lot#:
Reference#:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Description: RUTHERFORD LLC: CREATE NEW TRASH ENCLOSURE
Applicant:
TIM SEAMAN
619-993-8846
BUILDING PERMIT FEE ($2000+)
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG}
BUILDING PLAN CHECK FEE (BLDG)
Owner:
DC T RUTHERFORD LLC
Po Box 173382
DENVER, CO 80217
303-597-2400
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
561473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
STRONG MOTION-COMMERCIAL
Total Fees: $1,142.00 Total Payments To Date:
Tenant Improvement
$1,142.00
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Permit No: CBC2018-0085
Closed -Finaled
02/14/2018
04/26/2018
TFraz
6/21/2018 3:14:36PM
$0.00
$278.00
$278.00
$194.60
$194.60
$43.00
$43.00
$45.00
$45.00
$2.00
$2.00
$8.40
$8.40
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
THE FOLLO'MNG APPROVALS REQUIRED PRIOR TO PERIIIT ISSUANCE: QPLANNING (JENGINEERINO 0BU1LDING OFIRE OHEALTH C]HAZMATIAPCD
Cacy of Bulldlng Permit Appllcatlon Plan Check No. Ct!(_A_(l I~ 1/JRCj
1635 Faraday Ave., C.r11bed, CA 92008 Est. Value 11. 1..P,OOO
Carlsoad Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. DapoalJ emall: bullding@carlabadca.gov
www.carl11N1C1C11.gov Date :J 114 II <;( ISWPPP
JOIIADDREA 2091 Rutherford Road, Cartsbad, CA 92008 r'N 212 -120 -25 -00
1w,,rn~=••
'LOT# r-~· r vr ~, .. ~ row--#IIA,......,_ 1·-·----· r-•~ TYPE r-unuur Lot 51
Of'-IIK! ........... Fut rl NrNCdArM(II)
New trash enclosure, new roof over trash enclosure and new concrete level loading area.
/JIVL Jo,c&o
EUITINIIUII
I ·-r"RAGE (SF) l'ATIOB(SF) 1~(5F) FIREPLACE IA1RumD111UP1ING rRE ....... NKLERS YES0, Nt(1] m ONO [Z] YES0Nc(2]
APPUCWff NAMI-Manuel Montalvo PIIOPUTY OMID NAME OCT Rutherford LLC ... ·-···"· ..... ADDRESS ADDRESS 1717 Fifth Avenue 12 Corporate Plaza, Suite 150
CITY STATE ZIP cnv STAlE ZIP
San Dl&AO CA 92101 NeWDOrt Beach CA 92660
PHONE lfAX PHONE rAX 619.232.0261 949.219.1241
EMAIL EMAIL Manuelftoclodasigngroup.com Roley@dctlnduslrial.com D-PllOFE8MMW. Rodoffo Ocio CCllffltMmlR BUI, NAME White Construction
ADDRESS ADDRESS
1717 Fifth Avenue 2524 Gateway Road
CITY STATE ZIP CITY STATE ZIP
San Dleao CA 92101 Carts bad CA 92009
PHONE rAJ( PHONE I FAX 619.232.0261 780 931.1130
EMAIL EMAIL Rodolfo@ociodesigngroup.com Randy@whleconstructJonlnc.com l STi\TE LIC. ft STi\lELJC.t la>as l QTY Ill& UC..
W O R I< r: fl 5 C O M P E N S A T I O N ~Dldnlon:l,.., ....... ,....",,.,.,_dfha ..... ....._
._ ..... _. ,_...otW ID ....... tor....-.a.,....-ianu lJO'Aded i,,Slclml 3700dlht L..-Cudii, ilrll9 pri,rmanatol .. waikbwllldllllsPl'fflllllllllld . ...................... ~c ~~bvSlc!!fn~ ....... CodJ,ba.--~~;1111111111..i.Mylllllfln"Cllll1*• ... w,--lildpalcy
nl.lll'QHII: lneurllllQII Cu. .... ~ :5 I J>... ")t CC' Poley No. I ++:/ &plratlull l'.llllll I I '
11111..aar. 1111d net Ill ~lflhl Plfllll far cae luldlllll daln (tllllJ ar laa l.J Certlllcllla ol lDmpllan.: I ...,.1111 ln the pdlnnlnm 11,-WOJI. IOr wt.k:11 thll Plllilll II ilMld, 1 nl nol M1pi{¥ an, PG1W1111 • "'1-., a ID bllarilM Nljld: IDb WINn' CDn!pa,laiDn "-Of
C1111ma. WM1111G: Fllu .. 1o-.......... 11111 .......... ....,.. .............. o1v11 ....... 1o_...._._...._Cl'llll,IIII).-. .......... GOltlrl-..,....... fflld .. i,..,eo111, nllllll .. ....,.. .....
.I$ COtffltACTORIIIIMTIIRI
, MIWifdlllllllrn-.mn Conn:tll"IU..'-b'O.~ l9Mft D l • ..._dh~cr ny lffllllcl)w•W11811 • lhllr .. 11111+-a w1 c1ot11e• • a. IWCin II not.._ t111111ndbalt(SIC. 71144, ..._ltid~ Coclt: The~
UC.. LlwdDNIIClllll!ll>'lo111-!Jlpnlpllty1illo blllldl • ._ .._, •• dollu:h m~or.._ 19M'l emiqw.jlllllild8d llslUCh ~"' nallnllndld or .... b
-. I, i-,llleldilll er~ 11-*l•hcae ,-dcampllllon. ,._......, .. .,.,. bu!den olpmq,. !-.ell na1 IIUldarlrnpMfllrh iu,-!JI'*~ D l, •-dl1'pqierty, .. -.....,m-.i ........ ~ IDCOIIDIClh pllj9i::l(Sec.1tN4, a--nlPml'mlon&l:ode: TheContnlctn ~ t..dllll l'llltlipl)l)'IDlll-d
ll"lPIIIY llhD buldl or11111DM.._,ml i:rilmb lUCII prlljeal win CIIIIJll:b(•J b1lld pnm 11111'11 ein..:wt IJclllN LAW). D , ... _.... .... fldon &.,.111111 Pn:lflDllnCodJrarllil-:
1.1 ...... 19 ID i:mr,ilelhl!lllp llbcwMd llllllflill b aonn:tall !Jllht pn,pmad POl*I¥ mplMfflll'II. C]va Oto
2. I tt-/hllw nal) ... Ill 8Pliblm111"1 llulcrrVpmmll b .. p..,..i Md.
3.1,-Glllft:fld wll U.Mawq pnr. (11,,)IDPftl','ldllhl p.lJpCINd cannucllan ~ ,......._,..,., ...... .._ IU'lbll1;
,t. I plm 1111 pnMltpailllnl ~llleWlllk,bul I~ ~kid lhtt7aMlg !*m'l 1111_..., ...-n PltJ*-h lllljorwCllll(WAHll rmm lllkbN/ phune/lXlllhclm' lane llll!al):
5.1 WI pnwtdt-dbwin, Id 1 '-contr.:lld (hnd) ~ i--ID plwdtlha Mn lndblllCI jn,:illl -..1 ldlt.-/ plllm /Ip rlWDik):
DATE
COMPLETE THIS sFCJ/ON FOR NON RESIDENTIAL BUILDING PERMITS ONLY
1..W,MIIIM-lllllapplillllllntlllMlllllth.__,... ............... ~ ........ 11-.I ... ID ...... IIGW._ ... _._IIIWflWIID..._ ___
,......,...._ ... __...d' .. CIIJ'cfClltllmlD .... .-i .. llDl_...~b.,_...,...._,IUIONR:ElOMIE, N&NfYNCIICEEPIWN.El!S1tEOOY<FCM.811,t,D
IDIHir M.l. l.WIIUl'ES..am.tENJS. aJSlllNG EXPENSESNICHMAY 1'4NflWAY ICCRIEN.WNBTSAIDCRYINCCWSBIBl:E OF'lliEGIMTIGCJI-THS ~.
O&HA:.-.iOSHApimtllapadilr.....__.lD'dllplllddlndblllrllnlluclillfl....__.311a1111t1118Ut
EXF1RATD1:e.ypmtilludbt" .. Ui'uatirlfll'lllr .. 11117MnrlNIQldanl-llylnillblllldlmml'dlllllldlJ .. IIIB,gmwadl....._brlldlpnlllnolaamnnedllihrl
18Ddl,allum .. drlllaflldlpintal .. lllB,galllllli:......_.byllldlpntll....-im......_•..,.,.* .. mkll---lnplllodol1811diiiJB(Slclon 108A.41Aibm~Qmi
AS"APPLICMT'l._-n. DATE Ol,. 0 £ I f,
• STOP: THIS SECTION NOT REQUIRED FOR BUILDIN.G PERMIT ISSUANCE.
Complete the following ONLY I a Certificate of Occupancy wlll ba raqlllltad at flnal inspection.
Fa (780) 802-8580, 1:111111 building@cadsbadca.gov ar MIi iiie COl'l""'8d bm ID Cltyof Cartabad, Ulq Diwml 1835 Fllllday A-, Carlebad, Cllbnll ll2008.
Al>IJR
$TATE
FAX
DBMIWOPl'IONI
PICK UP: CONTM:I (Llad lbcM) OCCUPANT (Ulllla •-.J
CONnACl'CIRi(III .... :IJ
MAIL 10: CONTACI' (1.1111111 alNMI) OCCUPANT (UIDd mDllt)
CONTRACl'OR ton .... l)
MAIL/FAXfOO'nlER: _____________ _
COl:(llfllMU.Oni,t
CA
BUS. UC.
NO CHMIE IN UIE/ NO CONl'IRIICIIDN
CHANIIE 01' UIE/ IIO CONIIRUCmON
DATI
+c,rv o,
PLUMBING,
ELECTRICAL,
MECHANICAL
WORKSHEET
De11elopment Services
Bulldlns Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Building@ca rlsbad ca.gov CARLSBAD B-18
Project Address: Permit No.:
lnbmatlon provldad below reren to wort. balll; dona on the abaw menl:lonad pemt on"-
Tllis form m•st be com11tted and nt11ntd to ... lulhfl•g Dlyl11N before tlle Nnnlt can be ltned.
Budding Dept. Fmc (160) 60H5S8
Number of new or relocated fixtures, traps, or floor drah ·----·--------· Q
Number of new roof drains?,,---·-------------------~
lratall/alter water line?___ --------------· _a Number of newwat.r haabm?-.. _ .. _____ ,. _________ .. ________ A
Number of new, relocated or replaced gas outleb?-----.. ------------A Numb« of l'IBIN hose bb? _______________________ ..:Q.__
llelldenl:lal Pennltsl \. \ (I+ New/expanded service: Number of uw amps: __ \"' ______ _
Minor Remoc:W an&,t Yes_ No -:fL
Commerdal/lnduslrlah '\ ~\-'\ t:"tvc.A ~ v(l..~
Tenant lmprowment: Number of mdstllll amps /nwJNtJd In this p,r,Jed: v{A
Number of new amps /nwlwJd In this proJsd:
New CGIIIINdlonl AmPI per Panel: ~ Sb,gla R,asa, _ ............ ___ .. ____ "........ 4¥ Nufflber of w amperes ___ =----
Three Phase.--------------· Number of w amperes.. ___ :@:. ____ _
Three Phase 480---"""'" -·------Number of new C111peres ___ @,..... __
Number of new furnaces. AJC. or heat pumps?---------.. , .............. -....... 8
r.u, or relocated d&.lct \AIOl'tt?..---·······••••••t ···--------Yes No )<
Nunlberof nawflreplace5?----"------------· ~
NIM"l'll>ar of r1aA1 e,cl,mJst fclrls? .. __ .....,....._....... • , .... "_ ... ______ _
Relocate/lnsta'II Ulllt7 Mff4....._ __ ,_.,........,._ ... _....._NM ...... ________ ... _____ _
NulTlber of l'NMU flXl1at.lst lioodl?-.. -....... ...__ ........ -. ................... __ _......,. .......... _ ... _ .. , __
Number of new bolers or a,mpressors?,.,....... ... --------Number of HP .--.
B-18 Page 1 of 1 Rev. OMl9
PERMIT INSPECTION HISTORY REPORT (CBC2018-0085)
Permit Type: BLDG-Commercial Application Date: 02/14/2018 Owner: D C T RUTHERFORD LLC
Work Class: Tenant Improvement Issue Date: 04/26/2018 Subdivision: CARLSBAD TCT#85-24 UNIT#04
Status: Closed -Finaled Expiration Date: 11/13/2018 Address: 2091 Rutherford Rd
Carlsbad, CA 92008-7320
IVR Number: 9529
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Re inspection Complete
06/21/2018 BLDG-Final 061936-2018 Passed Tim Frazee Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Structural Final Yes
05/1112018 06/10/2018 BLDG-11 067647-2D18 Passed Tim Frazee Complete
Foundation/Ftg/Pler
s (Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
0611412018 05/14/2018 BLDG-66 Grout D67877•2018 Passed Tim Frazee Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
06/2112018 06/2Dl2D18 BLDG-Flnal 061621-2018 Passed Tim FrazlliJ Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Structural Final Yes
June 21, 2018 Page 1 of 1
i'
Es Gil
DATE: February 23, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0085 SETI
PROJECT ADDRESS: 2091 Rutherford Rd.
PROJECT NAME: Trash Enclosure
D APPLICANT ;zt' JURIS.
[g] Th~lans transmitted herewith have been corrected where necessary and substantially comply
wifh the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
[g] EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted:
Mail Telephone
D REMARKS:
By: Kurt Culver
EsGil
Telephone#:
(by~) Email:
Fax In Person
Enclosures:
2/20/18
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
I'
Carlsbad CBC2018-0085
F,ebruary 23, 2018
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK#.: CBC2018-0085
PREPARED BY: Kurt Culver DATE: February 23, 2018
BUILDING ADDRESS: 2091 Rutherford Rd.
BUILDING OCCUPANCY:
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Trash Encl.
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Building Permit Fee
1997 UBC Plan Check Fee
Type of Review: 0 Complete Review
0 Repetitive Fee -----;;i Repeats
Comments:
D Other
D Hourly
EsGII Fee
Reg. VALUE ($)
Mod.
30 000
30,000
$278.49!
$181.021
D Structural Only
1-------1,Hr. @ • $158.741
Sheet 1 of 1
PCSD Engineering Corp
3529 Coastview Court
carlsbad, CA 92010
Ph: 760-207·1885
Structural Design CalculathMt-CEJ
Trash Enclosure I"{ C: VE D
Client
Oclo Design Group
1717 Fifth Avenue
San Diego. CA 92101
Project
2091 Rutherdford Road
Carlsbad.CA 92008
January 31, 2018
PCSD FIie #: 18-040
JAN 1 B 2018
CITY OF CAR LSBAO
BUILDING DIVISION
Paul Christenson San Diego Engineering
3529 Coastview Ct -Carlsbad, CA 92010
Telephone (760) 207-1885 -Email: paul.pcsd@gmail.com
1.0 Design Criteria: · 2091 Rutherdford Road
Code:
Timber:
18-040
2016 California Building Code -ASCE 7-10
Douglas Fir-Larch (DF-L), WWPA or WCLIB
2x Wall Framing: DF-L #2 (unless noted otherwise)
2x Rafters & Joists: OF-L #2 " "
Posts & Beams: DF-L #1 " "
Glue-Lam Beams: Simple Span: Grade 24F-V4 (DF/DF)
Grade 24F-V8 {DF/DF) Cantilevers:
Sheathing: Min. APA-Rated Sheathing, Exposure 1, Plywood or OSB (U.N.0.)
Engineered Framtng Wood I-Joists: TJf 110,210,230,360,560 ICC ESR-1153
1.9E Microllam, 2.0E Parallam ICBC ER-4979
Concrete:
Concrete Block:
Mortar:
Grout:
LVL,PSL
Compressive Strength @ 28 days per ASTM C39-96:
Footings: f'c = 2500 psi
Grade Beams: f'c = 3000 psi
Grade N-1 per ASTM C90-95, fm = 1500 psi per ASTM E447-92
Type S Mortar Cement per ASTM C270-95, Min. fm = 1800 psi@ 28 days.
Coarse Grout w/ 3/8" Max. Aggregate per ASTM C476-91,
Min. f'm = 2000 psi @ 28 days.
Reinforcing Steel: #4 & Larger:
#3 & Smaller:
ASTM A615-60 (Fy = 60 ksi).
ASTM A615-40 (Fy = 40 ksi)
Structural Steel: ·w· Shapes: ASTM A992, Fy= 50-65 ksi
Plates, Angles, Channel! ASTM A36, Fy = 36 ksi
Tube Shapes: ASTM ASOO, Grade B, Fy= 46 ksi
Pipe Shapes: ASTM A53, Grade B, Fy=35 ksi
Welding Electrodes: Structural Steel: E70-T6
E90 Series
Bolts:
Soils:
References:
AS 15-60 Rebar:
Sill Plate Anchor Botls & Threaded Rods:
Steel Moment & Braced Frames:
1500 psf Bearing Pressure
A307 Quality Minimum
A325 (Bearing, U.N.O.)
'
, ;rs>... PCSD Engineering i.; ,. · 3521 Coastvlew Court
.. , . Carlsbad, CA 11201 D · "'t<i•hci c1so> 2111.1as
-~ ... '""' paul.pc:sdOgmall.com
Title 6' CM!J Wall
Job#:
Description ....
6' CMU Block Wall
This Wall in File: C:\Ueers\PaulC\Desktop\PCSD\2018\18-000-0cioTrash\calc\poway.RPX
Dagnr: pc
Page: 1
Date: 20 JAN 2018
R-..lnPro (C) 1917-2017, Butkl 11.17.11.03 ucenae: KW.-0112S2 Cantilevered Retaining Wall Uc:enn To : PCSD Engineering Code: CBC 2016,ACI 318-14,ACI 530-13
,· c.rtte_,,_._-----·· __ _.I / iouoaia ___ . • Retained Height
Wall height above soil =
Slope Behind Wall ,.
Height of Soil over Toa •
Waler height over heel =
0.50 ft
6.00 ft
0.00
6.00in
0.0 ft
Allow Soil Bearing • 1,500.0 psf
Equivalent Fluid Pressure Method
Active Heel Pressure = 30.0 psflft
Passive Pres$Ure
Soll Density, Heel
sou Density, Toe
Footingl\So\l friction
Soil height to Ignore
=
150.0 psf/ft
:: 110.00 pcf
• 0.00 pc-f
• 0.400
i '
I
i I '
··~-~ '
.·· 1
··. l
. I .,
>i
for passive pressure " 12.00 in I ----·-·· j Surcharge Loads
Surcharge over Heal = 0.0 psf
Used To Resist Sliding & Overturning
Surcharge Over Toe = 0.0
Used tor Sliding & Overturning
1 Axlal Load Apr,fled to Stem • Axial Dead load = 50.0 lbs
Axial li\18 Load = 50.0 lbs
Axial Load Eccentricity = 0.0 in
[laieral Load Applied to Stem -)
Lateral Load
... Height to To~
... Height to Bottom
Load Type
=
=
0.0 #lft
0.00 ft
0.00 ft
"' Wlndc,N)
(Service Level)
Wind on Expcsed Stem _
(Service Level)
0.0 psf
! Adjacent Footing Load ·
A acent oot ng Loa s
Footing Width "' 0.00ft
Eccentricity "' o.oo;n
wan to Ftg CL Diet • 0.00 ft
FootJng Type Line La11d
Base Above/Below Soil = o.o ft at Bad< of Wall
Poisson's Riltlo ::, 0.300
I S•te-m•.•W•e•ig•h•t•S•e•l•s•m•lc-L.o.ad __ _.1 Fp f Wp Weight Multiplier 0.330 g Added seismic base force 126.1 lbs
I Design Summary · ----:J
Wall Stability Ratios
Overturning "' 1.73 OK
Slat, Resists All Sliding !
Total Bearing Load
... resultant ecc. .. 983 Iba
6.45 in
Soll Pressure @ Toe 1,417 psf OK
Soil Pressure@ Heel = 0 pst OK
Allowable = 1,500 psf
Soll Pressure Less Than Allowable
ACI Factored@ roe "" 1,983 psf
AC! Factored ® Heel = 0 psf
Footing Shear G Toe = 6.9 psi OK
Footing Shear O Heel = 1.3 psi OK
Allowable = 75.0 psi
Slldlng calcs
Lateral Sliding Force 159.9 lb.S
Vertical com?Qnent of active lateral soil pressure IS
NOT considered in the catc:ulation of soil bearing
Lo.ad F.tc:tofa ---~--
Building Code CBC 2018,ACI
Dead Load 1.200
Live Load 1 .600
Earth, H 1.600
Wind, W 1.000
Seismic, E 1.000
/ Stem Construction ) _Bottom_·----~-. -~m~
Da1lgn Height Above Fts; ft• 0.00
Wall Material Above RHr -= Masonry
Design Method "' ASD
Thicknagg = 8.00
Rebar Size # 4
Rebar Spacing 24.00
Rebar Placed at Center Design Data ~---------· ·----~---·-·
fb/FB + fa!f=a = 0.745
Totll Force 41 soeuon
Serv1ce Level lbs = 129.9
Strength Level Iba=
Moment ••.• Actual
Service Level ft-#• 410.5
Strength Leval ft-# ..
Moment. .... AHowable • 569.8
Shear ..... Actual
Servlce Level pai s 1.4
Strength Level psi =
Shear ..... Allcwable psi• 45.8
Anet (Masonry) in2 = 91.50
Rebar Depth 'd' In= 3.75
M•onry Data -··--· -·-----·
rm psi "" 1 ,500
Fs psi"" 20,000
Solid Grouting = Yes
Modular Ratio 'n' = 21.46
Well Weight psf= 84.0
Short Term Fedor ~ 1.000
Equiv. Solid Thick. In• 7 .60
Masonry Block Type = Normsl Weight
Masonry Design Method "" ASD
Concrete Data
f'c
Fy
psi=
psi"'
-----···---
..
.......... .,.... _____ .................... ...-... ~.----·
,;;, · ·· · 3&29 Coastvlew Court • t:1),::,.,. PCSD Engineering Title I' CM!,J Wall
Job#: Dsgnr: pc
Page: 2
Date: 20 JAN 201 B
. . , .. ~ Cartsbad, CA 92010
· ~Q,~& (780) 207-1885 ... ,~,..,..,. paul.pcsdGafflall.com
Description ....
I' CMU Block Wall
This Wall In FIie: C:\Usars\PaulC\Desktcp\PCSD\2018\18-000-0cioTrash\Calc\poway.RPX
RnlnPro (cl 1981•2U1T, Build 11.17. 11.03 LJcenN : KW.QIOl1232
Llctm• To : PCSD Enplnearlng
Cantilevered Retaining Wall Code: CBC 2016,ACI 318-14,ACI 530-13
/ FooUng Onnenslons & strengths I
Toe Width = 0.67 ft
Heel Width • 1.33
Total Footing Width = -2.00
Footing Thickness = 12.00 In
KeyWidlh = 0.00 in
Key Depth = 0.00 In
Key Distance from Toe = 0.00 tl
fc • 2,500 pir.l Fy • 60,000 pal
Footing Ccncrete Density • 150.00 pd
Min. M %. = 0.0018
Cover G Top 3.00 @ Btrn.• 3.00 in
Footfng Design Resufts
Ia
Factored Press1Jre = 1,983
Mu' : Upward • 370
Mu' : Downward = 82
Mu: Outgn = 288
Actuat 1.JNay Shear = 6.88
ANaw 1-Way Shear "' 40.00
Toe Reinforcing = None Spec'd
Heel Reil\'forclng = None Spec'd
Kay Reinforcing = None Spec'd
Olher Acceptable Sizes & Spacings
•• Hl!I 0 psf
0 fl-:#
82 ft-#
82 ft-#
1.35 pei
40.00 psl
Toa: Not req'd: Mu < phi*5"1ambda"aqrt(f'c)*Sm
Heel: Not req'd: Mu< phi*S"lambda"sqrt(f'crsm
Key: No key defined
Min footing T&S reinf Area
Min footing T&S relnf Area per foot
If one layer of horizontal bars:
#4@ 9.26in
t5@14.35in
#6@20.371n
0-52 ln2
0.26 ln2 Ill
If two layers of horizontal bars:
#4@ 18.52 in
#5@2S.70 in
#6@40.74 In
: Summary of Overturnlnp & Resisting Forces & Moments
. . .... OVERTURNING ..... • .... RESISTING .....
Heel ACIIVe Pressure =
Surcharge over Heel •
Surcharge Over Toe =
Acljacent Footing Load =
Added Lateral Loaa =
Load CD Stem Above Soil •
Seismic Stem Self Wt
Total
=
Resisting/Overturning Ratio
Force Diatanc:e Moment
lbs ft ft-# ---·--·----
33.8 0.50 16.9
126.1 4.25 536.0 -----159.9 O.T.M. 552.9
=
= 1.73
vertical Loads used for Soll Pressure = 982.6 Iba
Force Dlnance _ ... ___ _
Soil OVer Heel =
Sloped Soil 0....-Heel "'
Surcharge Over Hael •
Adjacent Footing Load =
Axial Dead Load on Stem•
• Axial Live Load on Stem =
Soil Over Toe •
Surcharge OVer Toe
Stem Weight(&) =
Earth @ Smm Transitions=
Footing Weight =
Key Weight =
Vert. Component _• __
lbs ft
38.6 ,.87
50.0 1.00
50.0 1.00
0.33
548.0 1.00
300.0 1.00
·-----,
Moment
it-#
61.1
50.0
50.0
546.2
300.0
Total• 932.6 lbs R.M.• 957.3
If &eisrnic Is Included the OTM and sliding ratios bl!l 1.1 per section 1807.2.3 of IBC 2009 or IBC 201
Vertical component of active lateral soil pressure IS NOT considered in
the calculation of Sliding Resistance.
Vertical component of active lateral son pressure IS NOT considered in
the calculation of Overturning Resistance.
TIit I
• Axial live load NOT Included In total displayec:11 _or uaed for overturning resistance, but is included for soil pressure caiculation.
Horizontal Deflection at Top of Wall due to settlement of soil
(Deflection due to wall bending not conaide18d)
Soll Spring Reaction Modulus
Horizontal Defl O Top of Wall (a,ppn»dmate only)
250.0 pei
0.128 In
The above calculation is not valid if the heel soil bearing pressure excttt!S'§ that of lhe toe.
because the wan would then tend to rotate into the retained soil.
..
PCSO Engineering
-3529 Coastview Court
· Ca~sbad, CA 92010
Project Title:
Engineer: Project ID:
Project Descr:
; (760) 207-1885
paul.pcsd@gmail.com
Descllptfon : sreer Coklmn a Trasfl E'nclosure
};.,~-~.i)·-~:;-<_;<,:',\+:Si-/· .. ::~:/:(i~,:. __ .,·-'YJr: __________________ _ ---------·---" -----·--···--Calculations per AISC 36~10, IBC 2015, CBC 2016, ASCE 7-10
Load Combinations Used : ASCE 7-10
_;':~J~~-!f:'":·:;\)::.;,i_t,:\:>-·/t<···:>::"\C"c;_·;\: _____ ,, ___ _ ---------·--· .. ---
Steel Section Name : HSS6x8x1/8
Analysis Method : Allowable Strength
Overall Column Height 6 ft
Top & Bottom Fixity Top Free, Bottom Fixed
Steel Stress Grade Brace condition for deflection (buckling) along columns :
Fy : Steel Yield 36.0 ksl X-X (width) axis :·
!: : Elaalic Bending Modulus 29,000.0 ksl Unbraced Lenglh for X-X Axis buckling "6 ft. K = 2.1
Y-Y (depth) axis:
Unbrac:ed'Lenglh forY-V Axis buckling= 6ft K; 2.1
, i~e,Hect.~~:>I)• :;-~ \: /:f)< :,;;>::_'>\)/<,,;;·•:.~<~,,::,;•,,:i:.:__ _
Column self weight Included : 59.160 lbs• Dead Load Factor
AXIAL LOADS .•.
_ Service loads ent~red. Load Fa~ors will be applied for calculations.
Axial Load st 6.0 ft. Xecc = 26.0 in, D = 0.20 k
BENDING LOADS .•.
lat Uniform Load creating Mx-x, W = 0.050 k.llt J-····----!(: ~<>;··>~t/~\;;(:),:."\{·\J?'-':,:<t __ .. ____ _
Bending & Shear Check R88ult.s
PASS Max. Axial-+Bending Stress Ratio =
Load Cormlnation
Location of max.above baas
At maximum lacalion values are ...
Pa :Axiel
Pn I Omega : Allo#able
Ma-x : Applied
Mn-x I Omega : AIIOWable
Ma-)' ; Applled
Mn-y I Omega : Allowable
PASS Maximum Shear Stress Rsllo =
L~~
Location of max.above base
At maKimum location values are ...
0.1189 : 1
+D+0.60W+H
0.0 fl
0.2592 k
41.807 k
-0.540 k-ft
8.408 k-fl
-0.4333 k-ft
8.408 k..ft
0.01061 : 1
+D~.60W+H
0.0 ft
Va : Applied 0. 180 k
Vn I Omega : Allowable 16.960 k
·----···----
Maximum Load Reactions ••
Top along X-X
Bottom along X-X
Top along Y-Y
Bottom along Y .y
Mulmum load Deftlcllona ...
Along Y-Y 0.0310 In at
for load combination :W Only
Along X-X 0.02978 In at
for load combination : +D+H
O.Ok
O.Ok
O.Ok
0.30k
6.0ft above bese
6.0ft above base
~,:;it~.,.,~_tnria.tt•••,;:::).\tdt<.'~:.ry: .;~:,:;,:.·/ ·------·--··---
_J._oad Combln@tlon_....-______ _
+O+H
+O+l.+H
+O+Lr+H
-tO+S+H
+0-+0.750Lr-t0.750L+H
-+0+0.750L-t-0.750S+H
-+0...0.60W+H
-+0+0.70E'*l
-+0..0.750lr-t0.750L-1-0.450W+H
+Q-+0.750L+0.750S+0.450W+H
~.750L-+0.750S-+0.5250E-+H
-t0.60D-t0.60W..0.60li
-t0.60D-t0.70E..0.60H
Maximum Axial + Bending Stress Ratios
Stress Ratio Status location
Maxlmum Shear Ratios
Stress Ratio · Status Location -· --··----·-----0.055 PASS 0.00ft 0.000 PASS 0.00 ft
0.055 PASS 0.00 ft 0.000 PASS 0.00 fl
0.055 PASS 0.00 ft 0.000 PASS 0.00 ft
0.055 PASS 0.00 ft 0.000 PASS 0.00 ff
0.055 PASS 0.00 fl 0.000 PASS 0.00 ft
0.055 PASS 0.00 ft 0.000 PASS 0.00 ft
0.119 PASS 0.00 ft 0.011 PASS 0.00 ft
0.055 PASS 0.00 ft 0.000 PASS 0.00 ft
0.103 PASS 0.00 ft 0.008 PASS 0.00 ft
0.103 PASS 0.00ft 0.008 PASS 0.00 ft
0.055 PASS 0.00 ft 0.000 PASS 0.00 fl
0.097 PASS 0.00 ft 0.011 PASS 0.00 ft
0.033 PASS 5.68 ft 0.000 PASS 0.00 ft
Description :
··•-CQOE,REFERelteE$
PCSD Engineering
3529 Coaatvlew Coun
Carlsbad, CA 92010
(760} 207 • 1885
paul.pcsd@gmall.com
Calculations per AISC 360-10, IBC 2015, ASCE 7-10
Load Combination Set : ASCE 7 -1 O
-t.t••l'P~ofl!~ee -· ·
Analysis Method : Allowable Strength Design
Beam Bracing : Completely Unbraced
Bending Axis : Major Axis Bending
•
Project TIiie:
Engineer:
Project Oescr:
D(0.015~Lr(0.1)
HSS10X3Jc1/4
Spen ~ 29 .330 ft
Fy : Steel Yleld :
E: Modulus:
•
Proiect ID:
36.0 ksi
29,000.0 ksl
Service loads entered. Load Factors will be applied for calculatlons.
Beam self weiQht calculated and added to loadlllQ
Uniform Load : D = 0.050, Lr= 0.10 k/ft, Tributary Width = 1.0 fl
.· D9Gt,f SUMMARY' ... _ .. __ . · ·_ · · · Maifrnum· senciing"'Streas Ratio·-·; ·
Section used for this span
Ma :Applied
Mn I Omega : Allowable
Load Combination
LocaUon of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total Deflection
·~. ·--
· Over•ilMixrmunt&efltJctlons ·
Load Combloatlon
..0-+lr+H
Vertlcal "R.-cJtons: · · .
load Combination
CMraH MAxknum
Oterall MINlmum
+O+H
..0-+l+H
..O-+lr-1-H
..0-+S'*i
..0..0.750Lr-t0.750L +H
..0..0.750l-+O. 750S-+H
..0-+0.60W+H
-0+0.TOf-+H
-+0-+0. 7501.r-tO. 750L-+0.450W-+H
+O-t0.750L-t0.750~.450W-+H
+0-+0.750L-t0.750S-t0.5250E+H
-t0.60D-+0.60W-t0.60H
-t0.600-t0.70E..0.60H
D0nly
Lr Only
LOnly
S0nly
Span
Support 1
2.504
0.622
1.037
1.037
2.504
1.037
2.137
1.037
1.037
1.0:rr
2.137
1.037
1.037
0.622
0.622
1.037
1.467
· · ·1ts12: 1 . . Ma1<lmum Shear Stress Ratio =
Section used tor this span
Va :Applied
Vn/Omega : Allowable
Load Combination
HSS1 Dx3x1/4
18.358k-fl
30.000k-ft
-+CM.r+H
Max. '-· Dell
1.5482
14.665ft
Span# 1
0. 905 ln Ratio •
0.905 in Ratio•
1.548 In Ratio •
0.000 in Ratio •
Location In Span
1,4.749
l.ocatlon of maximum on span
Span # where maximum occurs
388>=360
388 >:360
227 >=200
0 <200
Load Combination
Support notation: Far left Is #1
Support2
2.504
0.622
1.037
1.037
2.504
1.037
2.137
1.037
1.037
1.(137
2.137
1.037
1.037
0.622
0.622
1.037
1.467
Design OK ·o:ii45·:T
HSS10x3x1/4
2.504 k
56.060 k
+O+Lr+H
0.000 ft
Span#1
Max.··· 0en
0.0000
Values In KIPS
Location In Span
0.000
. 00 U)
SECTION A-A
-DRAIN TO BMP
(TYP.)
----• REFUSE TRUCK
LOADING APPROACH
~· ... ···~-·....----·, ... ···-----
TYPE B -DRIVE AND LOAD SIDE APPRO
SECTION B-B
SHEET 1 OF 2
~R_E_v~--A_PP_R_O~V-ED ....... D_A_TE .... _____ C_I_T_Y __ O_F __ C_A_R_L_S_B_A_D ____ __./5£_ ~ 0~~
REFUSE BIN ENCLOSURE
FOR 3 CUBIC YARDS BINS
-C\1Y ENGINEER
SUPPLEMENTAL
STANDARD NO_
DAlE
GS-16
..
,._.
....... ~ ...... __....,...,... ______ _
NOTES:
1. LOCATION OF REFUSE BIN ENCLOSURES SHALL BE APPROVED BY THE PLANNING
DIRECTOR AND THE CJTY ENGINEER_ ENCLOSURE SHALL BE OF SIMILAR COLORS
AND/OR MATERIALS AS THE PROJECT TO THE SATISFACTION OF 1HE PLANNING
DIRECTOR-
2. THE ENCLOSURE SLAB AND LOADING AREA SHALL BE LEVEL IN ORDER TO
FACILITATE THE ROLLING OF BINS FOR LOADING POSITIONING.
3. GATES SHALL BE MOUNTED SO THAT THEY SWING FULLY OPEN WITH NO
PROTRUSION INTO THE PATH OF THE BIN. THE GATES SHALL HAVE CHAINS,
HOOKS OR PIN STOPS AT THEIR FULL OPEN POSITION TO HOLD THEM OPEN.
4. ALL GATE CONNECTION LATCHES, SECURING BOLTS, FRAMING, ANO HINGES
SHALL BE HEAVY DUTY TYPE AND PAINTED OR TREATED AGAINST CORROSION_
5. GATE MATERIALS TO BE APPROVED BY PLANNING DIRECTOR
6. POSJTIVE DRAJNAGE AWAY FROM THE ENCLOSURE AND LOADING AREAS SHALL
BE PROVIDED ANO MAINTAINED.
7. ALTERNATIVE CONFIGURATION AND LOCATION OF THE ACCESS WAY MAY BE
ACCEPTABLE ON A CASE BY CASE BASIS PROVIDED NO PORTION OF THE TRASH
BINS ARE DIRECTLY VISIBLE TO THE PUBLIC.
8. LOADING AND ENCLOSURE AREA DRAINAGE SHALL BE INDEPENDENT
AND DRAINED TOWARDS AN APPROVED SITE BMP.
9. DEVELOPMENT PROJECTS SHALL JNCORPORATE THE REQUIREMENTS OF THE
"MODEL ORDINANCE OF THE CALIFORNIA JNTEGRA TED WASTE MANAGEMENT
BOARD RELATING TO AREAS FOR COLLECTING AND LOADING RECYCLABLE
MATIERIALS".
10. AREAS FOR RECYCLING SHALL BE ADEQUATE IN CAPACITY, NUMBER AND
DISTRIBUTION TO SERVE THE DEVELOPMENT WHERE THE PROJECT OCCURS.
11. RECYCLJNG AREAS SHALL BE SECURED TO PREVENT THE TIHEFT OF RECYCLABLE
MA TIERIALS BY UNAUTHORIZED PERSONS WHILE ALLOWlNG AUTHORIZED PERSONS
ACCESS FOR DISPOSAL OF MATERIALS.
12. RECYCLING AREAS OR THE BINS AND CONTAINERS PLACED THEREIN MUST PROVIDE
PROTECTION AGAINST SEVERE ENVIRONMENTAL CONDITIONS WHICH MIGHT RENDER
THE COLLECTED MATERIALS UNMARKETABLE.
13. A SIGN CLEARLY IDENTIFYING All RECYCLING AND SOLID WASTE COLLECTION
AND LOADING AREAS AND THE MAlERIALS ACCEPTED THEREIN SHALL BE POSlED
ADJACENT TO ALL POINTS OF ACCESS TO THE RECYCLING AREAS.
14. EACH RECYCLING AREA WITHIN A MUL 11-FAMILY RESIDENTIAL DEVELOPMENT SHALL
BE NO GREATER THAN 250 FEET FROM EACH LIVING UNIT.
• SHEET 2 OF 2
--...... v...i. i,,;.;A .... PP...,R ... O .... VE=D..,..D_A .... TE.....,. ___ c_IT_Y_O_F_C_A_R_L_S_B_A_D ___ .... .,,,,!;1~ ~ 6-04
REFUSE BIN ENCLOSURE
FOR 3 CUBIC YARDS BINS
CITY ENGINEER DA TE
SUPPLEMENTAL GS 16 STANDARD NO. -
SAMPLE PARKING CALCULATION
CHART:
PARKING REQUIRED:
BIO-INDUSTRIAL: 4,519 sq/ft @ 1/300 = 15
OFFICE: 15,373 sq/ft @ 1/250 = 62
*MANUFACTURJNG: 7,750sq/ft@ 1/400= 19
RESEARCH & DEVELOPMENT: 7,514 sq/ft@ 1/250 = 30
*WAREHOUSE: 21,250 sg/ft @ 1/1 1000 = 22
TOT~ REQUIRED: 148.
PARKING PROVIDED·:
REGULAR SPACES:
**COMPACT SPA~ES: · ·
ACCESSIBLE SPACES:
TOTAL PROVIDED:
148
37
8
193
RE.QUIRED PA.RKING STALL SIZE:
Standard Stall Size - 8 ~ minimum width 170 square feet of area.
Compact Stall Size -8'. x 15', no overhang permitted.
See Carlsbad Municipal Code 21.44 for details.
* Please note that in addition to one/space per gross floor area as stated above, one staU for each
vehicle used in conjunction with the us~ must be provided.
**Up to 25% of the total required parking may be compact spaces.
CARLSBAD RESEARCH CENTER SPECIFIC PLAN -CHAPTER 4 Development
Regulations
or other satisfactory evidence that adequate parking will be provided and the modification
will not adversely affect the neighborhood, as allowed pursuant to Chapter 21 .44.040 of
the Carlsbad Municipal Code,
Parking structures may be developed in conjunction with an approved building subject to
the requirement that such structure be generally and adequately screened from the street
and be architecturally compatible with the occupied buildings on the site.
4.3.2.4 Storage and Loading Areas
The following criteria shall apply to all storage, service, maintenance and loading areas:
1. Any equipment storage not contained within the main structure shall be fully
visually screened from adjacent streets and property. Said screening shall consist
of a wall constructed in an architectural style similar to adjacent structures and of
compatible materials as approved by the City Planner and the CRC ARC, not less
than a height sufficient to fully conceal the stored materials.
2. No storage shall be pennitted between streetside and the building line OJ," be
visible from the street. ·
3. No storage areas may extend into a required setback area.
4. No storage areas may eliminate any required parking space(s) or access aisles.
5. Streetside loading shall be allowed provided the loading dock is set back a
minimum of 70 feet from the street right-of-way line. Said loading area must be
screened from adjacent streets and property.
4.3.2.5 Refuse Collection Areas
Outdoor refuse collection areas shall comply with the following criteria:
1. All outdoor refuse collection areas shall be completely enclosed and screened
from access streets and adjacent property by a wall constructed an architectural
style similar to adjacent structures and of compatible materials, as approve_d by
the City Planner, not less than six feet in height. All such areas shall have
concrete floors, and shall be of sufficient size to contain all refuse generated by
the business. These areas shall be no less than six by eight feet in size.
2. No refuse collection areas shall be permitted between the streetside and the
building line.
3. Refuse collection areas should be effectively designed to contain all refuse
generated on-site and deposited between collections. Deposited refuse should
not be visible from outside the refuse enclosure.
CARLSBAD RESEARCH CENTER SPECIFIC PLAN
FEBRUARY 3, 2016 Page IV-14
CARLSBAD RESEARCH CENTER SPECIFIC PLAN -CHAPTER 4
' .... .,_ .. ~.------------
Development
Regulations
4. Refuse collection areas should be properly situated upon the lot in order to
provide clear and convenient access to refuse collection vehicles and thereby
minimize wear and tear to on-site and off-site improvements.
5. If provided, recycling bins shall be installed in conjunction with the refuse
collection bins.
4.3.2.6 Screening of Equipment
Exterior mechanical, electrical and related equipment shall comply with the following
criteria. Consistency with these requirements shall be determined by the City of Carlsbad
and separately by the CRC ARC.
1. Exterior components of roof-mounted equipment, including plumbing,
processing, heating, cooling, and ventilating systems (including but not limited to
piping, tanks, stacks, collectors, heating, cooling, and ventilating equipment fans,
blowers, ductwork, vents, louvers, meters, compressors, motors, incinerators,
· ovens, etc.) shall not be directly visible from a height of five feet above any
ground or ground-floor elevation at a distance closer than 500 feet from the
closest building wall on any lot. '
2. All onsite electrical lines (excluding transmission lines) and telephone lines shall
be placed underground. On-ground electrical transformer or terminal equipment
shall be visually screened from view from streets and adjacent properties. Visual
screening may be provided through construction of an enclosure. If an enclosure
is necessary, transformer enclosures should be aesigned of durable materials,
finishes, and colors which are compatible, unified and harmonious with the
overall architectural theme.
3. It is recommended, in the case of roof-mounted mechanical equipment, that
building parapets be of such a height that separate roof-mounted screening
devices will not be required. If building parapets do not provide the required
screening, mechanical equipment shall be screened by an unobtrusive screening
device that will appear as an integrated and compatible part of the overall
architectural design.
4. Any devices employed to screen exterior components of plumbing, processing,
heating, cooling, and ventilating systems from dfrect view shall appear to be an
integrated part of the architechlral design and, as such, shall be constmcted of
complementary and durable materials and finished in a texture and color
scheme complementary to the overall architectural design. Equipment
enclosures should be designed of durable materials, finishes, and colors which
are unified and harmonious with the overall design theme of the project,
constructed in an architectural style similar to adjacent structures and of
compatible materials. No fabric or metal mesh materials may be used for any
screening within the park.
CARLSBAD RESEARCH CENTER SPECIFIC PLAN
FEBRUARY 3, 2016
Page IV-!5