HomeMy WebLinkAbout2131 PALOMAR AIRPORT RD; ; CBC2017-0022; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Print DaW 08/11/2017 Commercial Permit Permit No: CBC2017-0022
www.carlsbadca.gov
Job Address: 2131 Palomar Airport Rd -
Permit Type: BLDG-Commercial Work Class: Tenant Improvement Status: Closed - Finaled
Parcel No: 2130702700 Lot #: . Applied: 01/11/2017
Valuation: $48,277.38 Reference #: . Issued: 02/23/2017
Occupancy Group: Construction Type: Finaled:
# Dwelling Units: Bathrooms: Inspector: AKrog
Bedrooms: Orig. Plan Check N:
Plan Check U:
Project Title:
Description: BROOKWOOD: RENOVATION OF ELEVATOR LOBBIES 1/ 146 SF AT 1ST, 149 AT 2ND, AND 148 SF AT 3RD FLOOR // RENO
1ST FLOOR BATHROOM AT 295 SF // 2ND FLOOR AT 300 SF
Applicant: Owner: Contractor:
HURKES HARRIS DESIGN ASSOCIATES BROOKWOOD CARLSBAD EXECUTIVE PLAZA S P WHITE CONSTRUCTION INC
JEFFERYHURKES tIC
2524 Gateway Rd
72 Cherry Hill Dr Carlsbad, CA 92009-1742
619-702-0380 BERVERLY, MA 01915 760-931-1130
BUILDING PERMIT FEE $2000+ . $399.60
BUILDING PLAN CHECK FEE (SLOG) S $279.72
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL S $43.00
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL . $45.00
5B1473 BUILDING STANDARDS FEE $2.00
STRONG MOTION-COMMERCIAL $13.52
Total Fees: $782.84 Total Payments To Date: $782.84 Balance Due: $0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: EPLANNING IENGINEERING DBUILDING FIRE EHEALTH DHAZMAT!APCD I
Building Permit Application Plan Check No. C2'7 14
Est. Value, c('-, 277 L City of 1635 Faraday Ave.,Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558 Cd1sbad
Plan Ck. Deposit email: buildingcarlsbadca.gov
Date I I ('. 1 17 Iswppp - www.carlsbadca.gov
JOB ADDRESS 2131 Palomar Airport Rd, Carlsbad, CA 92011
SUITE#/SPACE#/UNII# APN
)by/ Restrj 213 - 070 16 -
CT/PROJECT it LOT it PHASE it it OF UNITS it BEDROOMS it BATHROOMS TENANT BUSINESS NAME CONSTR. TYPE 0CC. GROUP
Ill-A B
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
Renovation of 1st, 2nd, 3rd floor elevator lobbies. New ceiling, lighting, and finishes.
Renovation of 1st & 3rd floor restrooms. New partitions, partial new ceiling, lighting, fixtures and finishes.
- EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE AIR CONDITIONING
Office Office I I I YESD#. NOE YES ENO
I FIRESPRINKLERS
YESN0E
APPLICANT NAME White Construction, Inc. PROPERTY OWNER NAME Brookwood Management Partners, LLC
ADDRESS . ADDRESS
2524 Gateway Rd 2131 Palomar Airport Rd, Suite 203
CITY STATE ZIP CITY STATE ZIP Carlsbad CA 92009 Carlsbad CA 92011
PHONE FAX PHONE
760-931-1130 760-804-0340
EMAIL EMAIL
shelly@whiteconstructioninc.com svalentino@brookwoodfinancial.com
DESIGN PROFESSIONAL Hurkes Harris Design Associates CONTRACTOR BUS. NAME
White Construction
ADDRESS ADDRESS
1620 Fifth Ave. Suite 100 2524 Gateway Rd
CITY STATE ZIP CITY STATE ZIP
San Dieao CA 92101 Carlsbad CA 92009
PHONE FAX PHONE . FAX
619-702-0380 (760) 93101130x118
EMAIL EMAIL
lwise@hhdainc.com shelly@whiteconstructioninc.com
STATE LiC. it STATE LiC.# CLASS CITY BUS. LiC.#
JeffervHurkes 1 0807 452513 1 B 1 12023880
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any Structure, prior to its issuance, also requires the applicant for such permit to file a Signed statement that he is licensed pursuant to the provisions of the Contractor's License Law fChapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)).
J®OI2UOO OL&OOD -.
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
El I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. Everest National insurance corn Policy No. 7650014158171 Expiration Date 01101018
This section need not be completed if the permit is for one hundred dollars ($100) or less. [J Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
CONTRACTOR SIGNATURE [—]AGENT DATE 1/11/1 7
GJOOoWO(MXJr3 000 -
thereby affirm that lam exempt from Contractor's License Law for the following reason:
EJ I, as owner'of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
LII I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractors License Law).
I am exempt under Section ______________Business and Professions Code for this reason:
I personally plan to provide the major labor and materials for construction of the proposed property improvement. Dyes ElNo
I (have / have not) signed an application for a building permit for the proposed work. -
-
I have contracted with the following person (firm) to provide the proposed construction (include name address I phone! contractors' license number):
I plan to provide portions of the work, butt have hired the following person to coordinate, supervise and provide the major work (include name/address/ phone contractors' license number):
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address / phone / type of work):,
.
,.PROPERTY OWNER SIGNATURE . . . DAGENT DATE
-
._ • •1
,1
I
a-
G00I011 11D00 OOC3?00 (Ø0 000-0000MG)vDiza OOOO Gumove GIs?
Is'sie applicanror future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes 1vNo
f_` ts the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? I Yes ;,No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? - ,Yes 1 No -
IF ANY OF THEANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
G®OOi1OWC9O®&) womme awwv
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name N/A Lender's Address
Liàc&Jf? @OOOG9eaI
I certifythatl have read the application and statethatthe above information isconectand that the information on the plans is accurate. I agree to complywith all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA An OSHA permit is required for excavations over 50' deep and demolition or construction of structures over 3 stories in height
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such permit orifth building orwork authorized by such permitis suspended or abandoned at any time after the work is commenced bra period of 180 days (Section 106.4.4 Uniform Building Code).
..APPLICANT'S SIGNATURE , DATE .1/11/2017 . .
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
gCERTIFIC ATE .i OCCUPANCY (Comm erci a l uaPr oj ects .irj
- Fax (760) 602-8560, Email buiIdingCarIsbadCa.gov or Mail thecompleted form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
CO#: (Office Use Only), -
21
CONTACT NAME - . . -: OCCUPANT NAME -.
-. ADDRESS - . BUILDING ADDRESS
CITY - , -. - STATE ZIP - CITY , STATE - ZIP
Carlsbad CA.
PHONE . . . . FAX
EMAIL . . OCCUPANTS BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above) CONTRACTOR (On Pg. 1)'
,-
- •- ' . - - . ASSOCIATED CB#__- MAIL TO: CONTACT (Listed above) OCCUPANT (Listed above)' - - ,
: •- - . CONTRACTOR (On Pg. 1) NO CHANGE IN USE/ NO CONSTRUCTION
Mill. /FAX TOOTHER: -
-.• -,
'
. . . CHANGE OF USE/ NO CONSTRUCTION - -
-
-
APPLICANT S SIGNATURE DATE
PERMIT INSPECTION HISTORY REPORT (CBC20I7-0022)
Permit Type: BLDG-Commercial Application Date: 01/11/2017 Owner: BROOKWOOD CARLSBAD
• EXECUTIVE PLAZA LLC
Work Class: -
Tenant Improvement Issue Date: 02/23/2017 Subdivision:
Status: Closed - Finaled - Expiration Date: 12/05/2017 Address: 2131 Palomar Airport Rd
Carlsbad, CA 92011
IVR Number: 1410
Scheduled 1 Actual Inspection Type Inspection No. inspection Status Primary Inspector Reinspection Complete
Date Start Date
-
08/11/2017 08/11/2017 BLDG-Final 031473-2017 Passed Andy Krogh Complete
- Inspection -
Checklist Item COMMENTS Passed - • -
-
• BLDG-Plumbing Final Yes
BLDG-Mechanical Final • •
- - - Yes
- • BLDG-Structural Final Yes
• BLDG-Electrical Final I
• Yes
- 1--
-
I -
-
-- -
- I
- .1 -
* -
1*. - • S .
I -
.
'•
'-
- I
- l .-_,:,. I
•,
. .- -
.-
-
-- - .
August 112o17 -. - • -Page 3 of 3
Permit Type: BLDG-Commercial Application Date: 01/11/2017 Owner: BROOKWOOD GARLSAL)
EXECUTIVE PLAZA LLC
Work Class:. Tenant Improvement Issue Date: 02/23/2017 Subdivision:
Status.. Closed - Finaled -. Expiration Date: - 12/05/2017 Address:. 2131 Palomar Airport Rd
Carlsbad, CA 92011:
IVR Number:
--
1410
Scheduled Actual
Date ' Start Date Inspection Type Inspection No. . Inspection Status Primary Inspector Reinspection Complete
ChecklistItem _.COMMENTS Passed
. BLDG-Building Deficiency 2cd floor, restroom'ok to occupy . . . - Yes
-
BLDG-Plumbing Final . - No
BLDG-Mechanical Final r ' . . No
BLDG-Structural Final - . .. No
BLDG-Electrical Final .-, No
05/31/2017 05/31/2017 BLDG-24 024838-2017 Passed Andy Krogh - Complete
• Rough/Topout
• Checklist Item COMMENTS ..Passed
BLDG-Building Deficiency - First floor restrooms Yes
-
BLDG-85 T-Bar, 024839-2017 -
Passed Andy Krogh .
Complete
Ceiling Grids, - - . . . V
. - Overhead - .- - • ,. . V
1
-
V ,
ChecklistItem COMMENTS •.Passed
BLDG-Building Deficiency - 2cd floor lobby - . t - Yes •
BLDG-14 ' .- Yes
Frame-Steel-Bolting-Welding
(Decks) - • . • -
. BLDG-24 Rough-Topout . - .. . Yes
- BLDG-34 Rcugh Electrical - -. Yes
- . BLDG-44 . - ( . Yes
Rough-Ducts-Dampers
06108/2017 06/08/2017 BLDG-14 025659-2017 . - Passed •, Andy Krogh" V Complete'
Frame/Steel/Bolting!
Welding (Decks) V
V V
Checklist Item COMMENTS _'Passed
BLDG-Building Deficiency 1st floor restroom V, Yes
- BLDG-34 Rough 025658-2017 V Passed Andy Krogh V - Complete -
Electrical
1 Ch$èklistItem - ___COMMENTS __.V Passed '
BLDG Building Deficiency 1st floor restroom Yes
V - •
V
,,- - V •
V
,• -
BLDG-85 T-Bar, 025660.2017 - Passed Andy Krogh V
V Complete
V Ceiling Grids, , . . . • ' V • • V
- - Overhead , •. . . . .
V '
V
- •.V
V V . ,
V
-
. Checklist Item .COMMENTS
VV _
,••-.
_Pissed V
• V BLDG-Building Deficiency First floor lobby .
V Yes -
V BLDG-14' -
V
-. Yes
V Frame-Steel-Bolting-Welding • V . • - - ,
(Decks) .
V
- V
- BLDG-24 Rough-Topout V - Yes V
• . • BLDG-34 Rough Electrical V
V • Yes -
V V BLDG-44 •. - . - . Yes -
V - Rough-Ducts-Dampers V
- -, "- • ,- V
ALi9LI5t11,2017 . . . V - . ,, -
V Pagé2of3
Permit Type: BLDG-Commercial Application Date: 01/11/2017 Owner: BROOKWOOD CARLSBAD
EXECUTIVE PLAZA LLC
Work Class: Tenant Improvement - , Issue Date: 02/23/2017 Subdivision:
Status: Closed - Finaled Expiration Date: 12/05/2017 Address: 2131Palomar Airport Rd'
Carlsbad, CA 92011
IVR Number: 1410
Scheduled Actual
Start te Inspection Type Inspection No Inspection Status Primary Inspector Reinspection Complete
Date
• 03/15/2017 ' 03/15/2017 BLDG-86 T-Bar, 016575-2017 Failed Andy Krogh Reinspection Complete
'Ceiling Grids, '
• . Overhead - - -
Checklist Item ., COMMENTS Passed
BLDG-Building Deficiency Cannot locate contractor, called # and no '. No
• answer, left message -
BLDG-14 ' - - ' - ,. No
Frame-Steel-Bolting-Welding
(Decks)
- ' BLDG-24 Rough-Topout - -
•• No
- BLDG-34 Rough Electrical I
, ' ,
' No
• -
-
' BLDG-44 ' ' ' , , No
. . Rough-Ducts-Dampers
03/16/2017, 03/16/2017 BLDG-85 T-Bar, . 016784.2017 , Passed - Andy Krogh Complete
Ceiling Grids, * •• -
- Overhead - '• -'
Checklist Item ' COMMENTS . , -- ' - Passed - -
- .- BLDG-Building Deficiency 3rd floor lobby Yes
BLDG-14 I - I Yes
• , Frame-Steel-Bolting-Welding -
-
-
(Decks) s
I ' BLDG-24 Rough-Topout - Yes
- BLDG-34 Rough Electrical .
.
'Yes
-
BLDG-44 - '• Yes
-
Rough-Ducts-Dampers
03/24/2017 03/24/2017 BLDG-84 Rough 017585-2017 Passed Peter Dreibelbis • * Complete
....' Combo(14,24,34,44) "
• Checklist Item COMMENTS - Passed
BLDG-Building Deficiency • ' - -
Yes
• ' BLDG-14 '
- •
, Yes - -
Frame-Steel-Bolting-Welding
(Decks) -
• , - ' BLDG-24 Rough-Topout , • Yes
-
BLD6-34 Rough Electrical ' Yes,'
- BLDG-44 ' - - Yes -
- Rough-Ducts-Dampers
03/29/2017 03/29/2017 BLDG-17 Interior 018036.2017 1Cancelled Andy Krogh Reinspection Complete
Lath/Drywall -
-
-. , i• -
- Checklist Item - COMMENTS. - 'Passed -
BLDG-Building Deficiency - - - -
' No, •
'
,-
•
05/11/2017 • 05/11/2017 BLDG-Final 023200-2017 Partial Pass Andy Krogh - Reinspection Incomplete
Inspection -'
August 11, 2017
.
- - - Page 1 of 3
EsGil Corporation
In Partnership with government for Building Safety
DATE: 2/21/17 . 1 APPLICANT
...J URIS.
JURISDICTION: City ofClibid Ll PLAN REVIEWER
FILE
PLAN CHECK NO.: C2017-0022 SET: II
PROJECT ADDRESS: 2131 Palomar Airport Rd
PROJECT NAME: Carlsbad Executive Plaza Lobby and Restroom Renovation - TI
Z The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
LI The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
El The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
El The applicant's copy of the check list has been sent to:
EsGil Corporation staff did not advise the applicant that the plan check has been completed.
EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by ,.-W ) Email:
Mail Telephone Fax In Person
REMARKS:
By: Doug Moody Enclosures:
EsGil Corporation
E GA El EJ i:i MB El PC 2/14/17
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
/
EsGil Corporation
In cPartnersñip witfi government for cBui&fzng Safety
DATE: 1/26/17
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: C2017-0022 SET:!
PROJECT ADDRESS: 2131 Palomar Airport Rd
APPLICANT
,ea JURIS.
0 PLAN REVIEWER
0 FILE
PROJECT NAME: Carlsbad Executive Plaza Lobby and Restroom Renovation - TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
LII The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
El The applicant's copy of the check list has been sent to:
III EsGil Corporation staff did not advise the applicant that the plan check has been completed.
El EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: White Construction. Telephone #: 760-931-1130 ext. 118
ate contacted: I f £..çí (by'Yj. Email: shellywhiteconstructioninc.com
i1flaiI ?Ins Fax In Person
REMARKS:
By: Doug Moody Enclosures:
EsGil Corporation
Li GA LI EJ i:i MB f PC 1/17/17
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
City of Carlsbad C2017-0022
1/26/17
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: C2017-0022 JURISDICTION: City of Carlsbad
OCCUPANCY: B USE: Elevator Lobby Restrooms
TYPE OF CONSTRUCTION: lilA ACTUAL AREA: 1038sf
ALLOWABLE FLOOR AREA: STORIES: 3
HEIGHT:
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 1/10/17
DATE INITIAL PLAN REVIEW
COMPLETED: - 1/26/17
FOREWORD (PLEASE READ):
OCCUPANT LOAD: N/A
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 1/17/17
PLAN REVIEWER: Doug Moody
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2013 CBC, which adopts the 2012 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad C2017-0022
1/26/17
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
Bring two corrected sets of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
Please clarify the plans to show the hard lid ceiling that is to be removed to not
be a 1 hour rated ceiling assembly as part of the elevator lobby. Section 107.2.
Please correct the plumbing fixture schedule to show the urinals to use .125 GPF
and not the .5GPFshown.
Please clarify the plumbing plans to show floor drains in the following locations,
as per UPC. Section 411.2:
a) Toilet rooms containing two or more water closet or a combination of 1
water closet and 1 urinal.
Advisory Note : When alterations, structural repairs or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the following requirements, per Section 11 B-202.4:
A primary entrance to the building and the primary path of travel to the
altered area, must be shown to comply with all accessibility features.
The path of travel shall include the existing parking.
Please address the following comments that are the result of the alterations.
4. Show on the site plan the complying disabled accessible path of travel from the
disabled accessible parking spaces to the primary entrance of the tenant space.
Please provide detailed plans of the path of travel, indicate slope and width, any
pedestrian ramps, curb ramps, walks, handrails, provide dimensioned parking
stall details etc.
City of Carlsbad C2017-0022
1/26/17
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of correction's from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes L3 No U
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation. Thank you.
City of Carlsbad C2017-0022
1/26/17
[DO NOT PAY— THIS IS NOTAN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: C2017-0022
PREPARED BY: Doug Moody DATE: 1/26/17
BUILDING ADDRESS: 2131 Palomar Airport Rd
BUILDING OCCUPANCY: B
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
TI 1038 46.51 48,277
Air Conditioning
Fire Sprinklers
TOTAL VALUE 48,277
Jurisdiction Code Icb IBY Ordinance I
V Bldg. Permit Fee by Ordinance
V Plan Check Fee by Ordinance
Type of Review: Eli Complete Review
I $400.091
I $260.061
Structural Only
Repetitive Fee
Repeats
El Other
El Hourly Hr. @ *
EsGil Fee I $224.051
Comments: .
Sheet of I
macvalue.doc +
STORM WATER Development Services
CITY OF COMPLIANCE Building Division
CARLSBAD ASSESSMENT 1635 Faraday Avenue
760-602-2719
B-24 www.carlsbadca.gov
I am applying to the City of Carlsbad for the following type(s) of construction permit:
ZI Building Permit U Right-of-Way Permit
U My project is categorically EXEMPT from Electrical Patio/Deck
the requirement to prepare a storm water . Fire Additional
i
Photo Voltaic
pollution prevention plan (SWPPP) because it Fire Alarm Re-Roofing
only requires issuance of one or more of the Fixed Systems
Mechanical
Sign
Spa-Factory
following permit types: Mobile Home Sprinkler
Plumbing Water Discharge
Project Storm Water Threat Assessment Criteria*
No Threat Assessment Criteria
My project qualifies as NO THREAT and is exempt from the requirement to prepare a storm water pollution prevention plan (SWPPP) because
it meets the "no threat" assessment criteria on the City's Project Threat Assessment Worksheet for Determination of Construction SWPPP Tier
Level. My project does not meet any of the High, Moderate or Low Threat criteria described below.
Tier I Low Threat Assessment Criteria
U My project does not meet any of the Significant or Moderate Threat criteria, is not an exempt permit type (See list above) and the project
meets one or more of the following criteria:
Results in some soil disturbance; and/or
Includes outdoor construction activities (such as saw cutting, equipment washing, material stockpiling, vehicle fueling, waste stockpiling).
Tier 2 • Moderate Threat Assessment Criteria
U My project does not meet any of the Significant Threat assessment Criteria described below and meets one or more of the following criteria:
Project requires a grading plan pursuant to the Carlsbad Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code); or,
Project will result in 2,500 square feet or more of soils disturbance including any associated construction staging, stockpiling, pavement
removal, equipment storage, refueling and maintenance areas and project meets one or more of the additional following criteria:
Located within 200 feet of an environmentally sensitive area or the Pacific Ocean, and/or
Disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical, and/or
Disturbed area is located along or within 30 feet of a storm drain inlet, an open drainage channel or watercourse, and/or
Construction will be initiated during the rainy season or will extend into the rainy season (Oct. 1 through April 30).
Tier 3 Significant Threat Assessment Criteria
U My project includes clearing, grading or other disturbances to the ground resulting in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, stockpiling, pavement removal, refueling and maintenance areas: and/or
U My project is part of a phased development plan that will cumulatively result in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, refueling and maintenance areas: or,
0 My project is located inside or within 200 feet of an environmentally sensitive area (see City ESA Proximity map) and has a significant
potential for contributing pollutants to nearby receiving waters by way of storm water runoff or non-storm water discharge(s).
I certify to the best of my knowledge that the above
checked statements are true and correct. I understand
and acknowledge that even though this project does
not require preparation of a construction SWPP, I must
still adhere to, and at all times during construction
activities for the permit type(s) check above comply
with the storm water best management practices
pursuant to Title 15 of the Carlsbad Municipal Code
and to City Standards.
"The City Engineer may authorize minor variances from the Storm
Water Threat Assessment Criteria in special circumstances where it
can be shown that a lesser or higher Construction SWPPP Tier Level is
warranted.
Project Address: Assessor Parcel No.
2131 Palomar Airport Rd, Carlsbad, CA 92011 213-070-16
Owner/Owner's Authorized Agent Name: Title:
Steve White, CEO C.E.O.
Owner/Owner's Authorized Agent Signature: Date:
1/11/2017
City Concurrence: By: Date: Project ID:
DYES ONO
B-24 Page 1 of 1 ' Rev.03/09
ENaNA
INDUSTRIAL WASTEWATER DISCHARGE PERMIT WASrRVAM
SCREENING SURVEY
Date01/11/2017
Business Name Brookwood Management Partners, LLC
Street Address2131 Palomar Airport Rd, Carlsbad, CA 92011
Email Address svalentino@brookwoodfinanciaI.com
PLEASE CHECK HERE IF YOUR BUSINESS IS EXEMPT: (ON REVERSE SIDE CHECK TYPE OF BUSINESS)
Check all below that are present at your facility: None
Acid Cleaning Ink Manufacturing Nutritional Supplement/
Assembly Laboratory Vitamin Manufacturing,
Automotive Repair Machining / Milling Painting / Finishing
Battery Manufacturing Manufacturing Paint Manufacturing
Biofuel Manufacturing Membrane Manufacturing Personal Care Products
Biotech Laboratory (i.e. water filter membranes) Manufacturing
Bulk Chemical Storage Metal Casting'/ Forming Pesticide Manufacturing I
Car Wash Metal Fabrication Packaging
Chemical Manufacturing Metal Finishing Pharmaceutical Manufacturing
Chemical Purification Electroplating (including precursors)
Dry Cleaning Electroless plating Porcelain Enameling
Electrical Component Anodizing Power Generation
Manufacturing Coating (i.e. phosphating) Print Shop .
Fertilizer Manufacturing Chemical Etching / Milling Research and Development
Film /X-ray Processing Printed Circuit Board Rubber Manufacturing
Food Processing Manufacturing Semiconductor Manufacturing
Glass Manufacturing Metal Powders Forming, Soap I Detergent Manufacturing
Industrial Laundry i Waste Treatment/ Storage
SIC Code(s) (if known):
Brief description of business activities (Production I Manufacturing Operations):_______________
Business Office
Description of operations generating wastewater (discharged to sewer, hauled or evaporated):
None other than sanitary waste from restrooms.
Estimated volume of industrial wastewater to be discharged (gal I day): N/A
List hazardous wastes generated (type/ volume): N/A
Date operation began/or will begin at this location:
Have you applied for a Wastewater Discharge Permit from the Encina Wastewater Authority?
Yes No If yes, when: No
Site Contact Sunny Valentino Title Property Manager
Signature Phone No. 760-804-0340
ENCINA WASTEWATER AUTHORITY, 6200 Avenida Encinas Carlsbad, CA 92011 (760) 438-3941
FAX: (760) 476-9852
SAN DIEGO REGIONAL . OFFICE USE ONLY
to 1'k1 I
MATERIALS RECORD ID #_____________________________________ 7Y HAZARDOUS PLAN CHECK #__________________
QUESTIONNAIRE BP DATE
Business Na'me Business Contact Telephone #
Brookwood Management Partners, LLC Sunny Valentino 760-804-0340
Project Address City State Zip Code APN# 2131 Palomar Airport Rd Carlsbad CA 92011 213-070-16
Mailing Address City State Zip Code Plan File#
2131 Palomar Airport Rd Carlsbad CA 92011
Project Contact Applicant E-mail Edwards Telephone # Shelly shelly@whiteconstructioninc.com 760-931-1130
rhe following questions represent the facility's activities, NOT the specific project description.
inaicate oy circiing me item, wnetner your business will use, process, or store any
nt must contact the Fire Protection Agency with jurisdiction prior to plan submittal. any ot tne items are
Occupancy Rating: Facility's Square Footage (including proposed project):
1. Explosive or Blasting Agents 5. Organic Peroxides 9. Water Reactives 13. Corrosives
2. Compressed Gases 6. Oxidizers 10. Cryogenics 14. Other Health Hazards
3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials 15. None of These.
4. Flammable Solids 8. Unstable Reactives 12. Radioactives
questions is yes, applicant must contact the County of San Diego Hazardous Materials Division, 5500 Overland Avenue, Suite 110, S Call (858) 505-6700 prior to the issuance of a building permit.
FEES ARE REQUIRED Project Completion Date: Expected Date of Occupancy:
YES NO (for new construction or remodeling projects)
0 lJ Is your business listed on the reverse side of this form? (check all that apply).
0 Will your business dispose of Hazardous Substances or Medical Waste in any amount?
0 I Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
E3 21 Will your business store or handle carcinogens/reproductive toxins in any quantity?
0 El Will your business use an existing or install an underground storage tank?
0 Q Will your business store or handle Regulated Substances (CalARP)?
0 L Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
0 EJ Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal to
or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act).
If the answer to any of the
Diego, CA 92123.
0 CalARP Exempt
Date Initials
El CalARP Required
Date Initials
El CalARP Complete
Date Initials
PART III: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCD): Any YES* answer requires a stamp from APCD 10124 Old Grove Road, San
Diego, CA 92131 apcdcomp(sdcounty.ca.gov (858) 586-2650). [*No stamp required if 01 Yes and 03 Yes and Q4-06 No]. The following questions are intended
to identify the majority of air pollution issues at the planning stage. Projects may require additional measures not identified by these questions. For comprehensive
requirements contact APCD. Residences are typically exempt, except - those with more than one buiIding on the property; single buildings with more than four
dwelling units; townhomes; condos; mixed-commercial use; deliberate bums; residences forming part of a larger project. [Excludes garages & small outbuildings.]
YES NO
El Will the project disturb 160 square feet or more of existing building materials?
0 M Will any load supporting structural members be removed? Notification may be required 10 working days prior to commencing demolition.
l El (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been performed by a Certified Asbestos Consultant or Site Surveillance
Technician?
0 l (ANSWER ONLY IF QUESTION 3 IS YES) Based on the survey results, will the project disturb any asbestos containing material? Notification
may be required 10 working days prior to commencing asbestos removal.
0 EJ Will the project or associated construction equipment emit air contaminants? See the reverse side of this form or APCD factsheet
(www.sdapcd.org/info/facts/permits.pdf) for typical equipment requiring an APCD permit.
0 0 (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school
boundary
Briefly describe business activities: Briefly describe proposed project: Lobby & Restrooms of Commercial Office Replace ceiling tile, lighting, finishes
I declare under penalty of perjury that to the best of my knowledge and belief the responses made herein are true and correct. Steve WhlteC.E.O. 1. 01/ 11 /2017
Name of Owner or Authorized Agent Signature of Owner or Authorized Agent v Date
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION: FOR OFFICAL USE ONLY:
BY: DATE:
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR occupcy
COUNTY-HMD APCD COUNTY-HMD APCD COUNTY-HMO APCD
A stamp in this box oniv exempts businesses trom completing or updating a Hazardous Materials Business Plan. Other permitting requirements may still apply.
HM-9171 (08/15) County of San Dieao - DEH - Hazardous Materials Division
(. City of
Carlsbad
WASTE MANAGEMENT
PLAN
B-59
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Owner:
Brookwood Management Partners, LLC
Contractor: White Construction, Inc.
2131 Palomar Airport Rd, Carlsbad, CA 92011
Job Address: Phone Number: 760-931-1130
Permit #: Estimated Cost of Project: $
85,000
Type of Project: o New Construction Remodel or TI. []Residential Commercial 0 Demolition
(check all that apply) 0 Other
Non-hazardous construction waste generated during the course of this project shall be recycled and/or salvaged for re-use at a
minimum of 50% per CALGreen Sec. 5.408.1. Failure to comply may result in a penalty fee up to $1,000. For projects which
consist of mainly equipment and/or racking, that have a combined weight of new construction disposal that does not exceed 2
lbs per square foot of building area affected by this permit, may be deemed to meet the 50% minimum requirement upon
approval of Building Department.
ALTERNATIVE FORMS OF COMPLIANCE: (If selected, do not complete Tables 1 & 2 below)
0 Construction waste shall not exceed 2 lbs. per sf. of area. All receipts shall be provided to the Building Official prior to
final. (This option not applicable for most construction projects.)
Square feet of construction area X 2 lbs. = lbs. of allowable waste.
I plan on using a WASTE MANAGEMENT roll-off bin. All receipts shall be provided to the Building Official prior to final.
Table 1 - Estimated Waste (To be filled out prior to permit issuance - refer to example on Page 2.)
MATERIALS lbs. of waste to betaken to
LANDFILL
lbs. of waste to be
RE-USED or RECYCLED Waste Hauling Company or Re-Use Method
Asphalt/ Concrete N/A Brick / Masonry N/A
Cardboard 10 lbs EDCO Drywall 50 lbs
Landscape Debris N/A
Lumber/Wood N/A Millwork sub will recycle at shop
Metals 20 EDCO
Mixed Waste 225 lbs EDCO
Trash / Garbage 25 lbs
Other:
TOTAL lbs: 75 2551bs
Estimated Percentage to be Re-Used or Recycled 60
I certify that the information provided herein, to the best of my knowledge, is true and correct. Steve White
Contractor or Owner (Print name 01/11/2017
Contractor or Owner (signature) Date
Official Use Only
0 Plan Approved 0 Plan Denied 0 Project Valuation Approved
Reviewed / Approved by:_____________________________________________
Page 1 of 2